technical data - Recair Oy · • Air Handling Unit Connection • Heat pump 3 • Air Handling...

31
air conditioning systems technical data Air handling unit connection ERQ-AV1

Transcript of technical data - Recair Oy · • Air Handling Unit Connection • Heat pump 3 • Air Handling...

air conditioning systems

technical data

Air handling unit connection

ERQ-AV1

air conditioning systems

technical data

Air handling unit connection

ERQ-AV1

• Air Handling Unit Connection • Heat pump 1

• Air Handling Unit Connection • ERQ-AV1

TABLE OF CONTENTSERQ-AV1

1 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

2 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3Nominal Capacity and Nominal Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

3 Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

4 Integrated heating capacity coefficient . . . . . . . . . . . . . . . . . . . . . . . . . . 6

5 Capacity tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7Combination table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7Cooling capacity tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8Heating capacity tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14Capacity correction factor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

6 Dimensional drawing & centre of gravity . . . . . . . . . . . . . . . . . . . . . . . 20

Dimensional drawing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20Centre of gravity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

7 Piping diagram. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

8 Wiring diagram. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22External connection diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

9 Sound data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23Sound pressure spectrum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23Sound power spectrum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

10 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26Service space . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26

11 Operation range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28

• Air Handling Unit Connection • ERQ-AV1

• Air Handling Unit Connection • Heat pump2

1 Features

Air Handlin ERQ-AV1 Heat pump Heat pump • Wide range of Daikin units offers maximum application potential plus flexible control options.

• The system provides optimized air conditions such as fresh air and humidity control, both in heating and in cooling, and can be used in small warehouses, showrooms and offices.

• Control box and expansion valve kit are required for each combination plus an air handling unit.

• Air Handling Unit Connection • Heat pump 3

• Air Handling Unit Connection • ERQ-AV1

2 Specifications

2-1 Nominal Capacity and Nominal Input ERQ100A7V1B ERQ125A7V1B ERQ140A7V1B

Nominal Capacity Cooling capacity Standard kW 11.2 14.0 15.5Heating capacity Standard kW 12.5 16.0 18.0

For combination indoor units + outdoor units

EER Nominal 3.99 3.42COP Nominal 4.56 4.15 3.94

2-2 Technical Specifications ERQ100A7V1B ERQ125A7V1B ERQ140A7V1B

Capacity range HP 4 5 6PED category Category 1Casing Colour Daikin White

Material Painted galvanized steel plateDimensions Unit Height mm 1,345

Width mm 900Depth mm 320

Packing Height mm 1,524Width mm 980Depth mm 420

Weight Unit kg 120Packed Unit kg 130

Packing Material Carton + Wood + EPSWeight kg 8

Heat Exchanger Dimensions Length mm 857Nr of Rows 2Fin Pitch mm 2Nr of Passes 10Face Area m² 1.131Nr of Stages 60

Tube type Hi-XSS(8)Fin Type Non-symmetric waffle louvre

Treatment Corrosion resistantFan Type Propeller

Discharge direction HorizontalQuantity 2Air Flow Rate (nominal at 230V)

Cooling m³/min 106Heating m³/min 102 105

Motor Quantity 2Model Brushless DC motor

Motor Speed (nominal) Cooling rpm 850/815Heating rpm 820/785 840/805

Fan Motor Output W 70Drive Direct Drive

Compressor Quantity 1Motor Model JT100G-VDL

Type Hermetically sealed scroll compressorSpeed rpm 6,480Motor Output W 2.5 3.0 3.5Starting Method Direct on lineCrankcase Heater

W 33

Operation Range Cooling Min °CDB -5Max °CDB 46

Heating Min °CWB -20Max °CWB 15.5

Sound Level (nominal) Cooling Sound Power dBA 66 67 69Sound Pressure dBA 50 51 53

Heating Sound Pressure dBA 52 53 55

• Air Handling Unit Connection • ERQ-AV1

• Air Handling Unit Connection • Heat pump4

2 Specifications

Refrigerant Type R-410ACharge kg 4.0Control Expansion valve (electronic type)Nr of Circuits 1

Refrigerant Oil Type Daphne FVC68DCharged Volume l 1.5

Piping connections Liquid (OD) Type Flare connectionDiameter (OD) mm 9.52

Gas Type Flare connection Braze connectionDiameter (OD) mm 15.9 19.1

Drain Quantity 3Diameter (OD) mm 26x3

Piping Length Maximum m 55Heat Insulation Both liquid and gas pipes

Defrost Method Reversed cycleDefrost Control Sensor for outdoor heat exchanger temperatureCapacity Control Method Inverter controlledCapacity control Cooling Minimum 24%

Maximum 100%Safety Devices High pressure switch

Fan motor thermal protectorInverter overload protector

PC board fuseStandard Accessories Item Installation manual

Quantity 1Item Operation manualQuantity 1Item Connection pipesQuantity 3

Notes Nominal cooling capacities are based on: indoor temperature: 27°CDB/19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 7.5m, level difference: 0m

Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB/6°CWB, equivalent refrigerant piping: 7.5m, level difference: 0m

Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings

Sound values are measured in a semi-anechoic room.

2-3 Electrical Specifications ERQ100A7V1B ERQ125A7V1B ERQ140A7V1B

Power Supply Name V1Phase 1~Frequency Hz 50Voltage V 220V-240VVoltage range Minimum V -10%

Maximum V +10%Current Nominal running

current (RLA)Cooling A 15.9 20.2 22.2

Starting current (cooling/heating) A 15.9 20.2 22.2Minimum Ssc value kVa Equipment complying with EN/IEC 61000-3-12Max. running current (RLA) A 27.0Minimum circuit amps (MCA) A 27.0Maximum fuse amps (MFA) A 32.0Full load amps (FLA) A 0.3+0.3 (fan motor)

Wiring connections For Power Supply Quantity 3Remark Earth wire included

For connection with indoor

Quantity 2Remark F1+F2

Field earth leakage breaker mA 300Power Supply Intake Both indoor and outdoor unit

2-2 Technical Specifications ERQ100A7V1B ERQ125A7V1B ERQ140A7V1B

• Air Handling Unit Connection • Heat pump 5

• Air Handling Unit Connection • ERQ-AV1

2 Specifications

3 Options

Notes RLA is based on following conditions: indoor temperature: 27°CDB/19°CWB, outdoor temperature: 35°CDB

Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits

Maximum allowable voltage range variation between phases is 2%.Select wire size based on the value of MCA

Instead of fuse, use circuit breaker. MFA is used to select circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker).

MSC means the maximum current during start up of the compressorEN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and <= 75A per

phaseSSC means short-circuit power

2-3 Electrical Specifications ERQ100A7V1B ERQ125A7V1B ERQ140A7V1B

ERQ-AV1

N° Item ERQ100 ERQ125 ERQ140

1 Cool/heat selector KRC19-26A6

2 Fixing box KJB111A

3 Central drain plug KKPJ5F180

Note: all options are kits 4TW32001-4

• Air Handling Unit Connection • ERQ-AV1

• Air Handling Unit Connection • Heat pump6

4 Integrated heating capacity coefficient

3TW30402-1

Integrated heating capacity coefficientThe heating capacity tables do not take account of the reduction in capacity, when frost has accumulated or while the defrosting operation is in progress.The capacity values, which take these factors into account, in other words, the integrated heating capacity values, can be calculated as follows

Formula:Integrated heating capacity = AValue given in table of capacity characteristics = BIntegrating correction factor for frost accumulation (kW) = CA = B x C

Correction factor for finding integrated heating capacity

ERQ-AV1

Inlet port temperature of heat exchanger (°C/RH 85%) -7 -5 -3 0 3 5 7Integrating correction factor for frost accumulation 0,88 0,86 0,8 0,75 0,76 0,82 1,0

Please note that, when there is an accumulation of snow against the outside surface of the outdoor unit heatexchanger, there will always be a temporary redusion in capacity, although this will of course vary in degree inaccordance with a number of other factors, such as the outdoor temperature (°CDB), relative humidity (RH) andthe amount of frosting which occurs.

Note:1. The figure shows that the integrated heating capacity

expresses the integrated capacity for a single cycle (fromdefrost operation to defrost operation) in terms of time.

Defrosting operation Defrosting operation

Time

One cycle

Hea

ting

capa

city

• Air Handling Unit Connection • Heat pump 7

• Air Handling Unit Connection • ERQ-AV1

5 Capacity tables5 - 1 Combination tableERQ-AV1Combination table

Control box Expansion valve kitOutdoor unit EKEQDCBV3 EKEQFCBV3 EKEXV63 EKEXV80 EKEXV100 EKEXV125 EKEXV140 EKEXV200 EKEXV250

1 phERQ100 P P P P P P - - -ERQ125 P P P P P P P - -ERQ140 P P - P P P P - -

3 phERQ125 P P P P P P P - -ERQ200 P P - - P P P P PERQ250 P P - - - P P P P

Heat pump

P: Pair: Combination depending on AHU heat exchanger volume and capacity

Allowed heat exchanger volume (dm ) Allowed heat exchanger capacity (kW)EKEXVClass Minimum Maximum Minimum Maximum

63 1.66 2.08 6.3 7.880 2.09 2.64 7.9 9.9100 2.65 3.3 10 12.3125 3.31 4.12 12.4 15.4140 4.13 4.62 15.5 17.6200 4.63 6.6 17.7 24.6250 6.61 8.25 24.7 30.8

Saturated suction temperature (SST) = 6°C, Superheat (SH = 5KAir temperature =27°CDB/19°CWB

If conflicting result occurs, capacity selection has priority over volume.3TW32009-1

)

3

• Air Handling Unit Connection • ERQ-AV1

• Air Handling Unit Connection • Heat pump8

5 Capacity tables5 - 2 Cooling capacity tables

ERQ100AV1

Cooling TC: Total capacity; kW; PI: Power Input; kW (Comp. + Outdoor fan motor)

Combination %

kW

(Capacity index)

Outdoor

air temp.

(°CDB)

Indoor air temp. °CWB

14.0 °CWB 16.0 °CWB 18.0 °CWB 19.0 °CWB 20.0 °CWB 22.0 °CWB 24.0 °CWB

20.0 °CDB 23.0 °CDB 26.0 °CDB 27.0 °CDB 28.0 °CDB 30.0 °CDB 32.0 °CDB

TC PI TC PI TC PI TC PI TC PI TC PI TC PI

4TW32002-2

NOTES - ANMERKUNGEN - - NOTAS - REMARQUES - NOTE - OPMERKINGEN - - NOTLAR

1 The above table shows the average value of conditions which may occur.

Die obige Tabelle zeigt den Durchschnittswert der Bedingungen. die auftreten können.

.

La tabla de arriba muestra el valor medio de condiciones que pueden ocurrir.

Le tableau ci-dessus donne la valeur moyenne pour des conditions qui peuvent survenir.

La tabella in alto mostra il valore delle condizioni medie che si possono riscontrare.

De tabel hierboven geeft de gemiddelde waarde aan van situaties die kunnen voorvallen.

. .

erini göstermektedir.

• Air Handling Unit Connection • Heat pump 9

• Air Handling Unit Connection • ERQ-AV1

5 Capacity tables5 - 2 Cooling capacity tables

ERQ100AV1

Cooling TC: Total capacity; kW; PI: Power Input; kW (Comp. + Outdoor fan motor)

Combination %

kW

(Capacity index)

Outdoor

air temp.

(°CDB)

Indoor air temp. °CWB

14.0 °CWB 16.0 °CWB 18.0 °CWB 19.0 °CWB 20.0 °CWB 22.0 °CWB 24.0 °CWB

20.0 °CDB 23.0 °CDB 26.0 °CDB 27.0 °CDB 28.0 °CDB 30.0 °CDB 32.0 °CDB

TC PI TC PI TC PI TC PI TC PI TC PI TC PI

4TW32002-2

• Air Handling Unit Connection • ERQ-AV1

• Air Handling Unit Connection • Heat pump10

5 Capacity tables5 - 2 Cooling capacity tables

ERQ125AV1

Cooling TC: Total capacity; kW; PI: Power Input; kW (Comp. + Outdoor fan motor)

Combination %

kW

(Capacity index)

Outdoor

air temp.

(°CDB)

Indoor air temp. °CWB

14.0 °CWB 16.0 °CWB 18.0 °CWB 19.0 °CWB 20.0 °CWB 22.0 °CWB 24.0 °CWB

20.0 °CDB 23.0 °CDB 26.0 °CDB 27.0 °CDB 28.0 °CDB 30.0 °CDB 32.0 °CDB

TC PI TC PI TC PI TC PI TC PI TC PI TC PI

4TW32002-2

NOTES - ANMERKUNGEN - - NOTAS - REMARQUES - NOTE - OPMERKINGEN - - NOTLAR

1 The above table shows the average value of conditions which may occur.

Die obige Tabelle zeigt den Durchschnittswert der Bedingungen. die auftreten können.

.

La tabla de arriba muestra el valor medio de condiciones que pueden ocurrir.

Le tableau ci-dessus donne la valeur moyenne pour des conditions qui peuvent survenir.

La tabella in alto mostra il valore delle condizioni medie che si possono riscontrare.

De tabel hierboven geeft de gemiddelde waarde aan van situaties die kunnen voorvallen.

. .

erini göstermektedir.

• Air Handling Unit Connection • Heat pump 11

• Air Handling Unit Connection • ERQ-AV1

5 Capacity tables5 - 2 Cooling capacity tables

ERQ125AV1

Cooling TC: Total capacity; kW; PI: Power Input; kW (Comp. + Outdoor fan motor)

Combination %

kW

(Capacity index)

Outdoor

air temp.

(°CDB)

Indoor air temp. °CWB

14.0 °CWB 16.0 °CWB 18.0 °CWB 19.0 °CWB 20.0 °CWB 22.0 °CWB 24.0 °CWB

20.0 °CDB 23.0 °CDB 26.0 °CDB 27.0 °CDB 28.0 °CDB 30.0 °CDB 32.0 °CDB

TC PI TC PI TC PI TC PI TC PI TC PI TC PI

4TW32002-2

• Air Handling Unit Connection • ERQ-AV1

• Air Handling Unit Connection • Heat pump12

5 Capacity tables5 - 2 Cooling capacity tables

ERQ140AV1

Cooling TC: Total capacity; kW; PI: Power Input; kW (Comp. + Outdoor fan motor)

Combination %

kW

(Capacity index)

Outdoor

air temp.

(°CDB)

Indoor air temp. °CWB

14.0 °CWB 16.0 °CWB 18.0 °CWB 19.0 °CWB 20.0 °CWB 22.0 °CWB 24.0 °CWB

20.0 °CDB 23.0 °CDB 26.0 °CDB 27.0 °CDB 28.0 °CDB 30.0 °CDB 32.0 °CDB

TC PI TC PI TC PI TC PI TC PI TC PI TC PI

4TW32002-2

NOTES - ANMERKUNGEN - - NOTAS - REMARQUES - NOTE - OPMERKINGEN - - NOTLAR

1 The above table shows the average value of conditions which may occur.

Die obige Tabelle zeigt den Durchschnittswert der Bedingungen. die auftreten können.

.

La tabla de arriba muestra el valor medio de condiciones que pueden ocurrir.

Le tableau ci-dessus donne la valeur moyenne pour des conditions qui peuvent survenir.

La tabella in alto mostra il valore delle condizioni medie che si possono riscontrare.

De tabel hierboven geeft de gemiddelde waarde aan van situaties die kunnen voorvallen.

. .

erini göstermektedir.

• Air Handling Unit Connection • Heat pump 13

• Air Handling Unit Connection • ERQ-AV1

5 Capacity tables5 - 2 Cooling capacity tables

ERQ140AV1

Cooling TC: Total capacity; kW; PI: Power Input; kW (Comp. + Outdoor fan motor)

Combination %

kW

(Capacity index)

Outdoor

air temp.

(°CDB)

Indoor air temp. °CWB

14.0 °CWB 16.0 °CWB 18.0 °CWB 19.0 °CWB 20.0 °CWB 22.0 °CWB 24.0 °CWB

20.0 °CDB 23.0 °CDB 26.0 °CDB 27.0 °CDB 28.0 °CDB 30.0 °CDB 32.0 °CDB

TC PI TC PI TC PI TC PI TC PI TC PI TC PI

4TW32002-2

• Air Handling Unit Connection • ERQ-AV1

• Air Handling Unit Connection • Heat pump14

5 Capacity tables5 - 3 Heating capacity tables

ERQ100AV1

Heating TC: Total capacity; kW; PI: Power Input; kW (Comp. + Outdoor fan motor)

Combination %

kW

(Capacity index)

Outdoor

air temp.

Indoor air temp. °CWB

16.0 18.0 20.0 21.0 22.0 24.0

TC PI TC PI TC PI TC PI TC PI TC PI

°CDB °CWB kW kW kW kW kW kW kW kW kW kW kW kW

4TW32002-3

NOTES - ANMERKUNGEN - - NOTAS - REMARQUES - NOTE - OPMERKINGEN - - NOTLAR

1 The above table shows the average value of conditions which may occur.

Die obige Tabelle zeigt den Durchschnittswert der Bedingungen. die auftreten können.

.

La tabla de arriba muestra el valor medio de condiciones que pueden ocurrir.

Le tableau ci-dessus donne la valeur moyenne pour des conditions qui peuvent survenir.

La tabella in alto mostra il valore delle condizioni medie che si possono riscontrare.

De tabel hierboven geeft de gemiddelde waarde aan van situaties die kunnen voorvallen.

. .

erini göstermektedir.

• Air Handling Unit Connection • Heat pump 15

• Air Handling Unit Connection • ERQ-AV1

5 Capacity tables5 - 3 Heating capacity tables

ERQ100AV1

Heating TC: Total capacity; kW; PI: Power Input; kW (Comp. + Outdoor fan motor)

Combination %

kW

(Capacity index)

Outdoor

air temp.

Indoor air temp. °CWB

16.0 18.0 20.0 21.0 22.0 24.0

TC PI TC PI TC PI TC PI TC PI TC PI

°CDB °CWB kW kW kW kW kW kW kW kW kW kW kW kW

4TW32002-3

• Air Handling Unit Connection • ERQ-AV1

• Air Handling Unit Connection • Heat pump16

5 Capacity tables5 - 3 Heating capacity tables

ERQ125AV1

Heating TC: Total capacity; kW; PI: Power Input; kW (Comp. + Outdoor fan motor)

Combination %

kW

(Capacity index)

Outdoor

air temp.

Indoor air temp. °CWB

16.0 18.0 20.0 21.0 22.0 24.0

TC PI TC PI TC PI TC PI TC PI TC PI

°CDB °CWB kW kW kW kW kW kW kW kW kW kW kW kW

4TW32002-3

NOTES - ANMERKUNGEN - - NOTAS - REMARQUES - NOTE - OPMERKINGEN - - NOTLAR

1 The above table shows the average value of conditions which may occur.

Die obige Tabelle zeigt den Durchschnittswert der Bedingungen. die auftreten können.

.

La tabla de arriba muestra el valor medio de condiciones que pueden ocurrir.

Le tableau ci-dessus donne la valeur moyenne pour des conditions qui peuvent survenir.

La tabella in alto mostra il valore delle condizioni medie che si possono riscontrare.

De tabel hierboven geeft de gemiddelde waarde aan van situaties die kunnen voorvallen.

. .

erini göstermektedir.

• Air Handling Unit Connection • Heat pump 17

• Air Handling Unit Connection • ERQ-AV1

5 Capacity tables5 - 3 Heating capacity tables

ERQ125AV1

Heating TC: Total capacity; kW; PI: Power Input; kW (Comp. + Outdoor fan motor)

Combination %

kW

(Capacity index)

Outdoor

air temp.

Indoor air temp. °CWB

16.0 18.0 20.0 21.0 22.0 24.0

TC PI TC PI TC PI TC PI TC PI TC PI

°CDB °CWB kW kW kW kW kW kW kW kW kW kW kW kW

4TW32002-3

• Air Handling Unit Connection • ERQ-AV1

• Air Handling Unit Connection • Heat pump18

5 Capacity tables5 - 3 Heating capacity tables

ERQ140AV1

Heating TC: Total capacity; kW; PI: Power Input; kW (Comp. + Outdoor fan motor)

Combination %

kW

(Capacity index)

Outdoor

air temp.

Indoor air temp. °CWB

16.0 18.0 20.0 21.0 22.0 24.0

TC PI TC PI TC PI TC PI TC PI TC PI

°CDB °CWB kW kW kW kW kW kW kW kW kW kW kW kW

4TW32002-3

NOTES - ANMERKUNGEN - - NOTAS - REMARQUES - NOTE - OPMERKINGEN - - NOTLAR

1 The above table shows the average value of conditions which may occur.

Die obige Tabelle zeigt den Durchschnittswert der Bedingungen. die auftreten können.

.

La tabla de arriba muestra el valor medio de condiciones que pueden ocurrir.

Le tableau ci-dessus donne la valeur moyenne pour des conditions qui peuvent survenir.

La tabella in alto mostra il valore delle condizioni medie che si possono riscontrare.

De tabel hierboven geeft de gemiddelde waarde aan van situaties die kunnen voorvallen.

. .

erini göstermektedir.

• Air Handling Unit Connection • Heat pump 19

• Air Handling Unit Connection • ERQ-AV1

5 Capacity tables5 - 3 Heating capacity tables

ERQ140AV1

Heating TC: Total capacity; kW; PI: Power Input; kW (Comp. + Outdoor fan motor)

Combination %

kW

(Capacity index)

Outdoor

air temp.

Indoor air temp. °CWB

16.0 18.0 20.0 21.0 22.0 24.0

TC PI TC PI TC PI TC PI TC PI TC PI

°CDB °CWB kW kW kW kW kW kW kW kW kW kW kW kW

4TW32002-3

• Air Handling Unit Connection • ERQ-AV1

• Air Handling Unit Connection • Heat pump20

5 Capacity tables5 - 4 Capacity correction factor

4 Dimensional drawing & centre of gravity6 - 1 Dimensional drawing

3TW32002-1

ERQ-AV1Rate of change in cooling capacity

of ERQ140Rate of change in cooling capacity

of ERQ100, ERQ125

Notes:1 These figures illustrate the rate of change in capacity of the system at

maximum load under standard conditions.Under partial load conditions there is only a minor deviation from therate of change in capacity shown in the figures above.

2 Method of calculating cooling capacity (max. capacity)Cooling capacity = Cooling capacity obtained from the coolingcapacity characteristics table X Capacity correction factor

3 Method of calculating heating capacity (max. capacity)Heating capacity = Heating capacity obtained from the heatingcapacity characteristics table X Capacity correction factor

Explanation of symbols:Hp: Level difference (m) between indoor and outdoor unit whenindoor unit is installed below the outdoor unit.Hm: Level difference (m) between indoor and outdoor unit whenindoor unit is installed above the outdoor unit.L: Equivalent piping length (m)d: Capacity correction factor

Diameter of pipes:

Model Gas LiquidERQ100ERQ125 J15.9 J9.5

ERQ140 J19.1 J9.5

Rate of change in heating capacity

3TW32004-1

1 Gas pipe connection A2 Liquid pipe connection - J9.5 flare3 Service port (in the unit) (2x)4 Electronic connection and grounding terminal M5 (in switch box)5 Refrigerant piping intake6 Power supply wiring intake (knock out hole J34)7 Control wiring intake (Knock out hole J27)8 Drain outlet

Hole for anchor bolt 4-M12

ERQ-AV1

Model AERQ100 J15.9 flareERQ125 J15.9 flareERQ140 J19.1 Brazing

• Air Handling Unit Connection • Heat pump 21

• Air Handling Unit Connection • ERQ-AV1

6 Dimensional drawing & centre of gravity6 - 2 Centre of gravity

5 Piping diagram

4D052604

ERQ-AV1

The position of foundationbolt

3D052712

ERQ-AV1

Heat exchanger

Compressor

High pressuresensor

Filter

Filter

Filter

Pressure regulating valve

4-way valve

Solenoid valve

Electronic expansionvalve

Electronic expansionvalve

Low pressuresensor

Capillary tube

Service port

Double pipe heatexchanger

Oil

sepa

rato

r

Stop valve (with service port on field piping side J 7.9mm flare connection)

Solenoid valve

Filter

Service port

Capillary tube

Capillary tube

Accumulator

• Air Handling Unit Connection • ERQ-AV1

• Air Handling Unit Connection • Heat pump22

8 Wiring diagram

8 - 2 External connection diagram

2TW32006-1

ERQ-AV1A1P : Printed circuit board (Main)A2P : Printed circuit board (INV.)A3P : Printed circuit board (Noise filter)A4P : Printed circuit board (C/H selector)BS1∼BS5 : Push button switch

(Mode, set, return, test, reset)C1∼C4 : CapacitorDS1 : Dip switchE1HC : Crankcase heaterF1U,F4U : Fuse (T 6,3A/250V)F6U : Fuse (T 5,0A/250V)FINTH : Thermistor (fin)H1P∼H8P : Light emitting diode (service monitor orange)

: Prepare test ----------- Flickering[H2P] : Malfunction detection--- Light upHAP : Light emitting diode (service monitor green)(A1P)K1M : Magnetic contactor (M1C)K1R : Magnetic relay (Y1S)K2R : Magnetic relay (Y2S)K3R : Magnetic relay (Y3S)K4R : Magnetic relay (E1HC)K5R : Magnetic relayL1R : ReactorM1C : Motor (compressor)M1F : Motor (fan) (upper)M2F : Motor (fan) (lower)PS : Switching power supplyQ1DI : Field earth leak detector (300mA)R1 : ResistorR2 : ResistorR1T : Thermistor (air)R2T : Thermistor (discharge pipe)R3T : Thermistor (suction 1)R4T : Thermistor (heat exchanger)R5T : Thermistor (suction 2)R6T : Thermistor (subcooling H.EX)R7T : Thermistor (liquid pipe) 1R8T : Thermistor (liquid pipe) 2S1NPH : Pressure sensor(High)S1NPL : Pressure sensor(Low)S1PH : Pressure switch (High)V1R : Power moduleV2R,V3R : Diode moduleV1T : IGBTX1M : Terminal strip (Power supply)X2M : Terminal strip (Control)X1M : Terminal strip (C/H selector) (A4P)Y1E : Electronic expansion valve (Main)Y3E : Electronic expansion valve (Subcool)Y1S : Solenoid valve (4 way valve)Y2S : Solenoid valve (Hot gas)Y3S : Solenoid valve (U/L circuit)Z1C∼Z7C : Noise filter (ferrite core)Z1F∼Z4F : Noise filter

Cool/heat selectorS1S : Selector switch (Fan/Cool - Heat)S2S : Selector switch (Cool - Heat)

Notes:1. This wiring diagram only applies to the outdoor unit2. L: Live, N: Neutral, : Field wiring3. : Terminal strip : Connector : Connection

: Protective earth (screw) : Relay connector: Noiseless earth : Terminal

4. Refer to the manual on how to use BS1 ∼ BS5 and DS1, DS2 switch.5. Do not operate the unit by short-circuiting protection device S1PH6. Colours: WHT: White / RED: Red / BLU: Blue /

BRN: Brown / GRN: Green / YLW: Yellow / ORG: Orange7. Refer to the installation manual for connection wiring to control box.

Position ofcompressorterminal

Wire entrance

Outdoor

Componentlocation

(Back) (Front)

(Note 7)

C/H selector

Cool/heat selector

Cool

HeatS2S Air control

S1SFan

3TW27176-2

ERQ-AV1

Notes:1 All wiring, components and materials to be procured on the site must comply

with the applicable local and national codes.2 Use copper conductors only.3 For more details, see wiring diagram.4 Install a circuit breaker for safety.5 All field wiring and components must be provided by a licensed electrician.6 The unit shall be grounded in compliance with the applicable local and national

codes.7 Wiring shown are general points-of-connection guides only and are not intended

for or to include all details for a specific installation.8 Be sure to install the switch and the fuse to the power line of each equipment.9 Install the main switch that can interrupt all power sources in an integrated

manner because this system consists of the equipment utilizing the multiplepower sources.

10 For detailed control box side connection, see control box manual and wiringdiagram.

Power supply

Outdoor unit

Main switch

Switch

Fuse

Switch

Fuse

Transmission line

Control box

Power line

• Air Handling Unit Connection • Heat pump 23

• Air Handling Unit Connection • ERQ-AV1

9 Sound data

4D052713A

Oct

ave

band

soun

dpr

essu

rele

veld

B(0d

B=0.

0002

μba

r)

Octave band center frequency (Hz)

ERQ100AV1

Overall (dB)

Scale A 50.0Scale C 62.0

(B,G,N is already rectified)

Measure in anechoic room

Note: The operating sound is measured in anechoicchamber, if it is measured under the actualinstallation conditions, it is normally over the setvalue due to enviromental noise and soundreflection.

Location of microphone

approximatethreshold hearingfor continuousnoise

Operating conditions

Power source 220-240V 50Hz, 220V 60Hz

Return air temperature: 27°C DB, 19°CWBOutdoor temperature: 35°C DB, 24°CWB

Cooling:

4D052719AO

ctav

eba

ndso

und

pres

sure

leve

ldB

:(0dB

=0.

0002

μba

r)

Octave band center frequency (Hz)

ERQ100AV1

approximatethreshold hearingfor continuousnoise

Power source 220-240V 50Hz, 220V 60Hz

Heating: Return air temperature: 20°C DBOutdoor temperature: 7°C DB, 6°C WB

Location of microphone

Overall (dB)

Scale A 52.0Scale C 63.5

(B,G,N is already rectified)

Measure in anechoic room

Note: The operating sound is measured in anechoicchamber, if it is measured under the actual installationconditions, it is normally over the set value due toenviromental noise and sound reflection.

Operating conditions

Oct

ave

band

soun

dpr

essu

rele

veld

B(0d

B=0.

0002

μba

r)

ERQ125AV1

Location ofmicrophone

4D052714COverall (dB)

Scale A 51.0Scale C 63.5

(B,G,N is already rectified)

Measure in anechoic room

Note: The operating sound is measured in anechoicchamber, if it is measured under the actualinstallation conditions, it is normally over the setvalue due to enviromental noise and soundreflection.

Octave band center frequency (Hz)

approximatethreshold hearingfor continuousnoise

Operating conditions

Power source 220-240V 50Hz, 220V 60Hz

Return air temperature: 27°C DB, 19°CWBOutdoor temperature: 35°C DB, 24°CWB

Cooling:

4D052718C

Oct

ave

band

soun

dpr

essu

rele

vel

dB:(0

dB=

0.00

02μ

bar)

Octave band center frequency (Hz)

ERQ125AV1

approximatethreshold hearingfor continuousnoise

Power source 220-240V 50Hz, 220V 60Hz

Heating: Return air temperature: 20°C DBOutdoor temperature: 7°C DB, 6°C WB

Location of microphone

Overall (dB)

Scale A 53.0Scale C 65.0

(B,G,N is already rectified)

Measure in anechoic room

Note: The operating sound is measured in anechoicchamber, if it is measured under the actual installationconditions, it is normally over the set value due toenviromental noise and sound reflection.

Operating conditions

• Air Handling Unit Connection • ERQ-AV1

• Air Handling Unit Connection • Heat pump24

9 Sound data9 - 1 Sound pressure spectrum

4D052716B

Oct

ave

band

soun

dpr

essu

rele

veld

B(0d

B=0.

0002

μba

r)

Octave band center frequency (Hz)

ERQ140AV1

Overall (dB)

Scale A 53.0Scale C 64.5

(B,G,N is already rectified)

Measure in anechoic room

Note: The operating sound is measured in anechoicchamber, if it is measured under the actualinstallation conditions, it is normally over the setvalue due to enviromental noise and soundreflection.

Location of microphone

approximatethreshold hearing forcontinuous noise

Operating conditions

Power source 220-240V 50Hz, 220V 60Hz

Return air temperature: 27°C DB, 19°CWBOutdoor temperature: 35°C DB, 24°CWB

Cooling:

4D052717BO

ctav

eba

ndso

und

pres

sure

leve

ldB

:(0dB

=0.

0002

μba

r)Octave band center frequency (Hz)

ERQ140AV1

approximatethreshold hearingfor continuousnoise

Power source 220-240V 50Hz, 220V 60Hz

Heating: Return air temperature: 20°C DBOutdoor temperature: 7°C DB, 6°C WB

Location of microphone

Overall (dB)

Scale A 55.0Scale C 67.0

(B,G,N is already rectified)

Measure in anechoic room

Note: The operating sound is measured in anechoicchamber, if it is measured under the actualinstallation conditions, it is normally over the setvalue due to enviromental noise and soundreflection.

Operating conditions

• Air Handling Unit Connection • Heat pump 25

• Air Handling Unit Connection • ERQ-AV1

9 Sound data9 - 2 Sound power spectrum

3TW27637-3

Soun

dpo

wer

leve

l(dB)

Octave band center frequency (Hz)

ERQ100AV1

NOTES1 dBA = A-weighted sound power level (A-scale according to IEC)2 Refernece acoustic intensity 0dB = 10E-6μW/m_3 Measured according to ISO 3744

3TW27647-3

Soun

dpo

wer

leve

l(dB)

Octave band center frequency (Hz)

ERQ125AV1

NOTES1 dBA = A-weighted sound power level (A-scale according to IEC)2 Refernece acoustic intensity 0dB = 10E-6μW/m_3 Measured according to ISO 3744

3TW27657-3

Soun

dpo

wer

leve

l(dB)

Octave band center frequency (Hz)

ERQ140AV1

NOTES1 dBA = A-weighted sound power level (A-scale according to IEC)2 Refernece acoustic intensity 0dB = 10E-6μW/m_3 Measured according to ISO 3744

• Air Handling Unit Connection • ERQ-AV1

• Air Handling Unit Connection • Heat pump26

10 Installation

(2) Series installation (2 or more)

(b) Obstacle above, too.

1 Stand-alone installation

2 Series installation (2 or more).

3. Where there are obstacles on both suction and discharge sides:

(a) No obstacle above.

ERQ-AV1Required installation spaceThe unit of the values is mm.

1. Where there is an obstacle on the suction side

+ Obstacle on the suction side andboth sides.

+ Obstacle on the suction sideand both sides.

1 Stand-alone installation.

2 Series installation (2 or more).

(a) No obstacle above

Where the obstacles on the discharge side is higher than theunit.There is no height limit for obstructions on the intake side.

2 Series installation (2 or more).

Pattern 1

2 Series installation (2 or more).+ Obstacle on both sides

(b) Obstacle above, too.

1 Stand-alone installation+ Obstacle on the suction side,.

1 Stand-alone installation+ Obstacle on the suction side only.

(2) Where there is an obstacleon the discharge side

100 or more

100 or more

100 or more

100 or more

300 or more

1000 or more

100 or more

500 or less

150 or more

500 or less

150 or more

150 or more

300 or more

500 or less

200 or more

1000 or more

500 or more

500 or more

1000 or more

1000

orm

ore

500 or less

1000 or more

500 or less

100 or more

500 or more

300 or more

1000

orm

ore

1000

orm

ore

1000

orm

ore

1000

orm

ore

200 or more

+ Obstacle on both sides.

(a) No obstacle above(1) Stand-alone installation

3D045696C (1)

1000 or more

• Air Handling Unit Connection • Heat pump 27

• Air Handling Unit Connection • ERQ-AV1

10 Installation10 - 1 Service space

(a) One row of stand-alone installation.

(b) Rows of series installation(2 or more).

1 Series installation.

The relations between H, A and L areas follows.

L A

L ≤ H0 < L ≤ 1/2 H 2501/2 H < L ≤ H 300

H < L Set the stand as : L <= H

4. Double-decker installation(a) Obstacle on the discharge side.

Close the gap A (the gap between the upperand lower outdoor units) to prevent thedischarged air from being bypassed.

Do not stack more than two unit..

The relations between H, A and L are as follows.L A

L ≤ H0 < L ≤ 1/2 H 2501/2 H < L ≤ H 300

H < L Cannot be installed

(b) Obstacle on the suction side only.Close the gap A (the gap between the upperand lower outdoor units) to prevent thedischarged air from being bypassed.

Do not stack more than one unit..

5. Multiple rows of series installation(on the rooftop, etc.).

ERQ-AV1(b) Obstacle above, too

Close the bottom of the installation frame to preventthe discharged air from being bypassed.

Only two units can be installed for this series.

1 Stand-alone installation.

2 Series installation (2 or more).

The relations between H, A and L are as follows.L A

L ≤ H0 < L ≤ 1/2 H 7501/2 H < L ≤ H 1000

H < L Set the stand as : L <= H

The relations between H, A and L are as follows.L A

L ≤ H0 < L ≤ 1/2 H 10001/2 H < L ≤ H 1250

H < L Set the stand as : L <= H

Pattern 2Where the obstacle on the discharge side islower than the unit.There is no height limit for obstructions on theintake side.

(a) No obstacle above.1 Stand-alone installation.

2 Series installation (2 or more).

The relations between H, A and L are as follows.L A

0 < L ≤ 1/2 H 2501/2 H < L ≤ H 300

(b) Obstacle above, too.

1 Stand-alone installation.

The relations between H, A and L are as follows.L A

L ≤ H0 < L ≤ 1/2 H 1001/2 H < L ≤ H 200

H < L Set the stand as : L <= H

Close the bottom of the installation frame toprevent the discharged air from beingbypassed.

Close the bottom of the installation frame toprevent the discharged air from being bypassed.

Close the bottom of the installation frame to preventthe discharged air from being bypassed.

Only two units can be installed for this series.

500 or less

250 or more

500 or less

300 or more

100 or more

500 or more

1500 or more

1000 or more

500 or less

500 or less

1500 or more

Dra

inpi

ping

cons

truct

ion

dim

ensio

n

1000 or more

300 or more

1000 or more

200 or more

2000 or more

100 or more

3000 or more

600 or more

1500 or more

1000

orm

ore

100

orm

ore

1000

orm

ore

1000

orm

ore

3D045696C (2)

L ≤ H

Dra

inpi

ping

cons

truct

ion

dim

ensio

n

• Air Handling Unit Connection • ERQ-AV1

• Air Handling Unit Connection • Heat pump28

11 Operation range

3D045713C

ERQ-AV1

Out

door

tem

p.(°

CDB)

Indoor temperature (°CWB)

Note:

These figures assume the followingoperating conditions.Indoor and outdoor units+ Equivalent piping length 7.5m+ Level difference 0m

Ope

ratio

nra

nge

Rang

efor

pulld

own

oper

ation

Cooling Heating

Ope

ratio

nra

nge

Rang

efor

pulld

own

oper

ation

Indoor temperature (°CDB)

outd

oort

empe

ratu

re(°

CWB)

Copy

right

Daiki

nPr

epar

ed in

Belg

ium by

Lann

oo (

www.

lanno

oprin

t.be)

, a co

mpan

y who

se co

ncer

n for

the en

viron

mont

is se

t in th

e EMA

S an

d ISO

1400

1 sys

tems.

Resp

onsib

le Ed

itor:

Daiki

n Eur

ope N

.V., Z

andv

oord

estra

at 30

0, B-

8400

Oos

tende

Daikin Europe N.V. is approved by LRQA for its QualityManagement System in accordance with the ISO9001standard. ISO9001 pertains to quality assurance regardingdesign, development, manufacturing as well as to servicesrelated to the product.

Daikin units comply with the European regulations thatguarantee the safety of the product.

The present publication is drawn up by way of information only and does notconstitute an offer binding upon Daikin Europe N.V.. Daikin Europe N.V. hascompiled the content of this publication to the best of its knowledge. Noexpress or implied warranty is given for the completeness, accuracy,reliability or fitness for particular purpose of its content and the products andservices presented therein. Specifications are subject to change withoutprior notice. Daikin Europe N.V. explicitly rejects any liability for any direct orindirect damage, in the broadest sense, arising from or related to the useand/or interpretation of this publication. All content is copyrighted by DaikinEurope N.V..

VRV® products are not within the scope of the Euroventcertification programme.

Naamloze VennootschapZandvoordestraat 300B-8400 Oostende, Belgiumwww.daikin.euBE 0412 120 336RPR Oostende

Daikin’s unique position as a manufacturer of airconditioning equipment, compressors andrefrigerants has led to its close involvement inenvironmental issues. For several years Daikin hashad the intension to become a leader in the provisionof products that have limited impact on theenvironment. This challenge demands the eco designand development of a wide range of products and anenergy management system, resulting in energyconservation and a reduction of waste.

ISO14001 assures an effective environmentalmanagement system in order to help protect human healthand the environment from the potential impact of ouractivities, products and services and to assist inmaintaining and improving the quality of the environment.