Technical and economic assessment of the integrated solar combined cycle power plants in Iran

15
Technical and economic assessment of the integrated solar combined cycle power plants in Iran R. Hosseini a, * , M. Soltani b,1 , G. Valizadeh b,1 a Mechanical Engineering Department, Amirkabir University of Technology, 424 Hafez Ave., P.O. Box 15875-4413, Tehran, Iran b Mechanical Systems Department, Niroo Research Institute (NRI), End of Pounak Bakhtari Blvd., P.O. Box 14665-517, Shahrak Gharb, Tehran, Iran Received 13 June 2004; accepted 7 November 2004 Available online 24 December 2004 Abstract Thermal efficiency, capacity factor, environmental considerations, investment, fuel and O&M 2 costs are the main parameters for technical and economic assessment of solar power plants. This analysis has shown that the Integrated Solar Combined Cycle System with 67 MW e solar field (ISCCS-67) is the most suitable plan for the first solar power plant in Iran. The Levelized Energy Costs (LEC) of combined cycle and ISCCS-67 power plants would be equal if 49 million $ of ISCCS-67 capital cost supplied by the international environmental organizations such as Global Environmental Facilities (GEF) and World Bank. This study shows that an ISCCS-67 saves 59 million $ in fuel consumption and reduces about 2.4 million ton in CO 2 emission during 30 years operating period. Increasing of steam turbine capacity by 50%, and 4% improvement in overall efficiency are other advantages of ISCCS-67 power plant. The LEC of ISCCS-67 is 10 and 33% lower than the combined cycle and gas turbine, respectively, at the same capacity factor with consideration of environmental costs. q 2004 Elsevier Ltd. All rights reserved. Keywords: Solar thermal; Parabolic trough; Power plant; Assessment 0960-1481/$ - see front matter q 2004 Elsevier Ltd. All rights reserved. doi:10.1016/j.renene.2004.11.005 Renewable Energy 30 (2005) 1541–1555 www.elsevier.com/locate/renene * Corresponding author. Tel.: C98 21 6405844; fax: C98 21 6419736. E-mail addresses: [email protected] (R. Hosseini), [email protected] (M. Soltani), [email protected] (G. Valizadeh). 1 Tel.: C98 21 8079393; fax: C98 21 8590171. 2 Operation and maintenance.

Transcript of Technical and economic assessment of the integrated solar combined cycle power plants in Iran

Page 1: Technical and economic assessment of the integrated solar combined cycle power plants in Iran

Technical and economic assessment of the integrated

solar combined cycle power plants in Iran

R. Hosseinia,*, M. Soltanib,1, G. Valizadehb,1

aMechanical Engineering Department, Amirkabir University of Technology, 424 Hafez Ave.,

P.O. Box 15875-4413, Tehran, IranbMechanical Systems Department, Niroo Research Institute (NRI), End of Pounak Bakhtari Blvd.,

P.O. Box 14665-517, Shahrak Gharb, Tehran, Iran

Received 13 June 2004; accepted 7 November 2004

Available online 24 December 2004

Abstract

Thermal efficiency, capacity factor, environmental considerations, investment, fuel and O&M2

costs are the main parameters for technical and economic assessment of solar power plants. This

analysis has shown that the Integrated Solar Combined Cycle System with 67 MW e solar field

(ISCCS-67) is the most suitable plan for the first solar power plant in Iran. The Levelized Energy

Costs (LEC) of combined cycle and ISCCS-67 power plants would be equal if 49 million $ of

ISCCS-67 capital cost supplied by the international environmental organizations such as Global

Environmental Facilities (GEF) and World Bank. This study shows that an ISCCS-67 saves 59

million $ in fuel consumption and reduces about 2.4 million ton in CO2 emission during 30 years

operating period. Increasing of steam turbine capacity by 50%, and 4% improvement in overall

efficiency are other advantages of ISCCS-67 power plant. The LEC of ISCCS-67 is 10 and 33%

lower than the combined cycle and gas turbine, respectively, at the same capacity factor with

consideration of environmental costs.

q 2004 Elsevier Ltd. All rights reserved.

Keywords: Solar thermal; Parabolic trough; Power plant; Assessment

Renewable Energy 30 (2005) 1541–1555

www.elsevier.com/locate/renene

0960-1481/$ - see front matter q 2004 Elsevier Ltd. All rights reserved.

doi:10.1016/j.renene.2004.11.005

* Corresponding author. Tel.: C98 21 6405844; fax: C98 21 6419736.

E-mail addresses: [email protected] (R. Hosseini), [email protected] (M. Soltani), [email protected]

(G. Valizadeh).1 Tel.: C98 21 8079393; fax: C98 21 8590171.2 Operation and maintenance.

Page 2: Technical and economic assessment of the integrated solar combined cycle power plants in Iran

Nomenclature

AC Annual investment cost, $

C Total investment cost, $

Cg Initial investment cost in gas unit, $

Cs Initial investment cost in steam unit, $

Csol Initial investment cost in solar unit, $

Cf Basic fuel price, ¢/m3

CRF Cost Recovery Factor

Eout Total amount of gross generated energy, kW h

Fb Annual fuel cost without consideration of discount rate, $

gf Annual fuel cost discount rate, %

Ha1 Annual working hours of power plant (peak mode)

Ha2 Annual working hours of gas units (peak mode)

Hsol Annual working hours of solar unit

kg O&M factor for gas unit

ks O&M factor for steam unit

ksol O&M factor for solar unit

LEC Levelized energy cost, ¢/kW h

LHV Fuel lower heating value, kJ/m3

N Power plant life expectancy, year

Ng Number of gas units

Ns Number of steam units

O&M Operation and maintenance cost, $

PVF Annual fuel cost, $

r Dollar discount rate, %

Wg Net power of gas unit, MW

Wgn Nominal power of gas units, MW

Wsn Nominal power of steam units, MW

Wsr Net power of steam unit, MW

h Thermal efficiency, %

hg Annual net efficiency of gas unit, %

hs Net efficiency of SEGS power plant in fossil mode, %

R. Hosseini et al. / Renewable Energy 30 (2005) 1541–15551542

1. Introduction

Iran is situated in 378N and has large areas that receive solar energy. It has a

considerable potential for solar power plants. About 25% of Iran is consisted of deserts

which receive daily solar irradiation about 5 kW h/m2. If 1% of these areas can be covered

Page 3: Technical and economic assessment of the integrated solar combined cycle power plants in Iran

R. Hosseini et al. / Renewable Energy 30 (2005) 1541–1555 1543

by solar collectors,3 energy obtained will be five times more than annual gross electricity

production in Iran4 [1].

Suitable areas for constructing solar thermal power plant in Iran are in center and south

of Iran. Studies show that the most suitable place is in Yazd5 [2].

Nowadays, the highest capacity of solar power plants belongs to solar troughs. This

kind of solar power plant is more economical than the others. Pressure drop in solar field

limits the capacity of solar trough to 100 MW. Pressure drop is a direct function of solar

field dimensions. The solar field is comprised of parallel rows of Solar Collector

Assemblies (SCA). SCAs supply thermal energy to produce steam to drive a steam

turbine/generator in Rankine cycle or ordinary combined cycle. The collectors are single-

axis tracking and aligned on a north–south line, thus tracking the sun from east to west.

Low-iron glass parabolic mirrors reflect the solar radiation to the absorber, which is

situated in focus axis of mirrors. The concentration factor of solar radiation on absorber is

about 20–100%. This value is about 80% in LS-3 collectors [3]. The maximum

temperature in absorber is about 400 8C. Thermal storage system is rarely used because of

high prices, however, it can be used in small solar power plants6.

This technology can be used for nations in regions with high direct normal solar

radiation (such as Africa, China, Middle East, the Mediterranean and Central and South

America) to develop a rational approach the deployment of solar thermal electric systems

within their country. Egypt, Jordan and Brazil are considered for building Integrated Solar

Combined Cycle System (ISCCS). Financial analysis in Jordan has shown that solar

thermal electricity generation is possible at 4.5 ¢/kW h [4]. The cost of electricity from

line—concentrator solar parabolic trough plants decreased by 83% in less than a decade,

due both to technological improvements and economies of scale in production [4].

The World Bank has made 200 million USD in financial assistance available for

new combined-cycle gas and solar thermal power plants in developing countries. In

Spain, a law increasing compensation for electricity produced from solar thermal

energy with a premium of 12 ¢/kW h above the market price of 4 ¢/kW h is expected

shortly [5].

A feasibility study was carried out for the World Bank/GEF and the Commission

Federal de Electricidad on a net 285.1 MW e power plant consisting of a solar steam

system integrated with a natural gas fired combined cycle system located at Cerro

Prieto near Mexicali, Baja California Norte. The Levelized Electricity Cost is about

9 ¢/kW h [6].

Solar trough is among the most cost effective renewable power technologies with near-

term power generation costs in the range of 12–20 ¢/kW h and of 5–10 ¢/kW h for long

term considerations. And it is the lowest cost solar electricity in the world, promising cost

competitiveness with fossil-fuel plants in future. The Intergovernmental Panel for Climate

Change (IPCC) demands drastic reductions of the greenhouse gas emissions in order to

avoid a collapse of the world climate by committed itself to a 6%, US to 7% and

3 Assume the efficiency of solar energy conversion to electricity 10%.4 Total gross electricity production in 2001 is 127,138 MW h.5 It is situated in center of Iran.6 Lower than 15 MW.

Page 4: Technical and economic assessment of the integrated solar combined cycle power plants in Iran

R. Hosseini et al. / Renewable Energy 30 (2005) 1541–15551544

the European Union to 8% CO2 reduction of the 1990 levels until 2012 [7]. Also some of

the main sponsors of energy investments in the developing world, i.e. the Worldbank

Group, the Kreditanstals fur Wiederaufbau (KfW) and the European Investment Bank

(EIB) have recently been convinced of the environmental promises and the economic

prospectives of Solar Thermal Power technologies: only in spring 2000, the broad of the

GEF approved grants for first solar thermal projects in Egypt, India, Mexico, and Morocco

of app. US$ 200 million in total [7].

In 1998, Pilkington predicted 877 $/kW capital cost and lower than 8 ¢/kW h Energy

price for an ISCCS plant in Morocco [8].

The main parameters, which considered and compared in these plants, are power plant

net efficiency, capacity factor, fuel consumption and solar field capacity. The Levelized

Energy Cost method (LEC) is a suitable way for economical assessment of different cases.

LEC is the summation of investment, operation and maintenance cost as well as fuel cost,

and it is expressed as ¢/kW h.

In this study, six cases are considered for Yazd power plant

(1)

Gas Turbine power plant (GT): 2!123.4 MW gas turbine;

(2)

Combined Cycle power plant (CC): 2!123.4 MW gas turbine C123.4 MW steam

turbine;

(3)

Integrated Solar Combined Cycle System with 33 MW e solar field (ISCC-33): 2!123.4 MW gas turbine C156 MW steam turbine C33 MW solar field;

(4)

Integrated Solar Combined Cycle System with 67 MW e solar field (ISCC-67): 2!123.4 MW gas turbine C198 MW steam turbine C67 MW solar field;

(5)

Integrated Solar Combined Cycle System with 67 MW e solar field and Auxiliary

Firing system (ISCC67-AF): 2!123.4 MW gas turbine C198 MW steam turbine C67 MW solar field C67 MW Auxiliary Firing;

(6)

Solar Electric Generating System (SEGS): 67 MW steam turbine C67 MW solar

field.

2. Integrated solar combined cycle system

In an ISCC, gas turbine is the same as conventional combined cycle, and the

required energy for producing steam can be supplied by both gas turbine exhaust and

solar field (Fig. 1). Preheating the feed water and superheating the steam will be

performed by gas turbine exhaust. In ISCC power plant, higher pressure and

temperature steam can be produced because of extra solar energy compared with

combined cycle.

Steam produced in ISCC power plant is 500 8C with 100 bar pressure. These values are

higher than steam properties in SEGS and conventional combined cycle, thus the

efficiency in ISCC is more than SEGS and CC.

Steam turbine capacity in conventional combined cycle, is 50% of gas turbine capacity,

but in ISCC, the solar field increases steam turbine capacity about 50% compared with CC.

Electricity production drop in summer does not occur in ISCC because as ambient

Page 5: Technical and economic assessment of the integrated solar combined cycle power plants in Iran

Fig. 1. Schematic of an integrated solar combined cycle system.

R. Hosseini et al. / Renewable Energy 30 (2005) 1541–1555 1545

temperature increases, solar field absorbs more energy. Thus, it has a stable energy

production through the year. The ISCC can work in following modes

(1)

7 A

Integrated solar combined cycle mode at solar hours;

(2)

Conventional combined cycle mode at non-solar hours;

(3)

Gas turbine mode when the steam turbine is not functioning.

This study considers three ISCC power plant. ISCC-33 is a combination of two gas

turbine (each one has 123 MW e), a steam turbine (161 MW e) and solar field (33 MW e),

ISCC-67 is the same, but the steam turbine capacity is 198 MW e and solar field

(67 MW e), ISCC67-AF is the same as ISCC-67, but it has auxiliary firing system for non-

solar hours. The capacity of auxiliary firing system is 67 MW e.

At non-solar hours, steam turbine of ISCC-67 will work in 63% of its capacity.

Therefore, an auxiliary firing system can be performed to use the idle capacity of steam

turbine. Auxiliary firing devices, can be installed at the inlet of flue gas passage. When flue

gas passes through this system, its temperature will raise and more steam in heat recovery

steam generator can be produced. The efficiency of fuel energy conversion to electricity in

auxiliary burners is about 36.9%.7 This amount is lower than the gas turbine efficiency in

ISO conditions [9]. Therefore, it is recommended to use auxiliary firing system just at peak

hours. For example, if we use it 4 h a day (1200 h a year), the annual electricity production

will be 85.8 GW h and fuel consumption through this period will be 22!106 m3 [9,10].

mbient temperature is assumed 20 8C.

Page 6: Technical and economic assessment of the integrated solar combined cycle power plants in Iran

Fig. 2. Net efficiency of different cases in maximum capacity factor.

R. Hosseini et al. / Renewable Energy 30 (2005) 1541–15551546

For ISCC-33, steam turbine will work in 78% of its full capacity at non-solar hours. So it is

not essential to use the auxiliary firing system. Other advantages of ISCC power plants are

Tab

Ene

Tot

pro

(M

CC

ISC

Sol

ISC

ISC

Sol

ISC

Increasing the steam turbine capacity of conventional combined cycle;

Better performance of combined cycle power plants in warm days.

3. Technical assessment of the cases

One of the main factors in technical evaluation of different power plants, is the net

efficiency. Annual net efficiency of six cases are shown in Fig. 2. These values are related

to maximum capacity factor. Low quality of generated steam in SEGS decreases its

efficiency to the lowest level. Extra solar energy in ISCC-33, ISCC-67 and ISCC67-AF,

raises the quality of generated steam and thus their efficiencies are higher than the

conventional combined cycle

hISCC�67 OhISCC67�AF OhISCC�33 OhCC OhSEGS OhGT

Energy production is influenced by local conditions of power plant. Table 1 shows the

produced energy of the cases in different seasons.

Produced energy in different seasons by ISCC-67 are shown in Fig. 3.

It can be seen that the energy production by solar part is maximum in summer. As

mentioned before, power generation in summer decreases in ordinary power plants, but in

le 1

rgy production in different seasons

al energy

duction

W h)

Spring Summer Autumn Winter Annual

749,868 708,059 737,931 780,890 2,976,748

C-33 767,298 732,090 756,494 794,084 3,049,966

ar field of

C-33

17,430 24,031 18,563 13,194 73,218

C-67 785,257 756,850 775,619 807,678 3,125,403

ar field of

C-67

35,389 48,791 37,688 26,788 148,655

Page 7: Technical and economic assessment of the integrated solar combined cycle power plants in Iran

Fig. 3. Variation of energy production of ISCC-67 through seasons.

R. Hosseini et al. / Renewable Energy 30 (2005) 1541–1555 1547

solar power plants the power generation drop in summer is compensated by the solar

energy. So solar power plants have more stable power generation.

Fig. 4 is a comparison of power generation between CC, ISCC-33 and ISCC-67 in a

summer day. It expresses that when power generation in combined cycle is minimum, the

others have maximum power generation.

To specify the capacity of solar field, some points should be considered. At non-solar

hours, the steam turbine must work at least in its 50% capacity. So the maximum capacity

of solar field will be 100 MW. On the other hand, for SEGS and ISCCS, the solar field

capacity cannot be more than 100 MW, because the pressure drop through the solar field

rises considerably and the main part of absorbed energy should be used to overcome the

pressure drop. Therefore, in this study two capacity, that is 33 and 67 MW e are considered

for solar field. These are 22 and 37% of steam turbine capacity, respectively. So at non-

solar hours the steam turbine will work in a capacity factor which is higher than 0.7.

The proposed thermal capacity in conceptual design is 185 MWth (equal to 67 MW e)

[9]. Although, the lower field capacity like 33 MW e makes the power plant performance

better, but decreases solar energy share in power generation about 50%. This reduces

Fig. 4. Net power variation of ISCC plans and CC in a summer day.

Page 8: Technical and economic assessment of the integrated solar combined cycle power plants in Iran

Table 2

Gross energy production in different cases

Type of power plant Annual energy pro-

duction (GW h)

Capacity factor (%) Annual work hours

(full load)

GT 1732 80.1 7017

CC 2730 82.8 7343

ISCC-33 2799 79.3 6950

ISCC-67 2870 73.7 6453

ISCC67-AF 2958 76 6658

SEGS 140 23.9 2092

R. Hosseini et al. / Renewable Energy 30 (2005) 1541–15551548

the chance to gain loans from World Bank and Global Environmental Facilities (GEF) [11,

12]. Also economical aspects are main characters in specifying the solar field capacity.

One of the main variables for technical evaluation of a power plant is the capacity

factor, which is defined as the ratio of annual produced energy to maximum annual energy

that can be produced. To determine capacity factor, we should know the annual

energy production. By considering 1 month for power plant overhauls, total annual energy

production and the capacity factor of GT, CC, ISCC-33, ISCC-67, ISCC67-AF and SEGS

are calculated and shown in Table 2. The capacity factor of combined cycle is about

5–10% more than ISCC plans. The reason is that the solar hours are eliminated through

the year.

4. Economical assessment of the cases

Levelized Energy Cost method (LEC), is used to compare different cases. The lowest

LEC determines the best choice. So, the investor should calculate the LEC of power plant

at first. The lowest LEC does not mean the best efficiency. LEC is a relationship between

the efficiency and cost and LEC calculation can lead us to the economical choice. LEC can

be expressed as:

LEC ZðACÞC ðO&MÞC ðPVFÞ

Eout

(1)

This part describes the method of calculating the LEC. Cost Recovery Factor (CRF)

cross to total investment cost (C) gives annual investment cost

AC Z ðCRFÞ!C (2)

Eq. (3) determines the cost recovery factor:

ðCRFÞ Zr

1 K ð1 CrÞKN(3)

Gas turbine life expectancy is about 20 years and the steam power plant and ISCC plans

life are 30 years. Eq. (4) calculates the total investment cost (C)

C Z Cg CCs CCsol (4)

Page 9: Technical and economic assessment of the integrated solar combined cycle power plants in Iran

R. Hosseini et al. / Renewable Energy 30 (2005) 1541–1555 1549

The operation and maintenance cost is a percentage of total investment cost. It is 5, 2

and 1.5% of investment cost in gas unit, steam unit and solar unit, respectively

ðO&MÞ Z kgCg CksCs CksolCsol (5)

To find fuel cost, it is required to determine the net power and net efficiency of gas

unit.8 For SEGS power plant, the net power of steam unit, its efficiency and working hours

should be specified

PVF Z Fb

1 Cgf

r Kgf

� �1 K

1 Cgf

1 Kr

� �N� �(6)

Fb can be caculated as follows:

Fb1 ZCf !Wsr !ðHa1 KHsolÞ

hs !LHVðfor SEGSÞ (7)

Fb2 ZCf !Wgr !Ha2

hg !LHVðfor other casesÞ (8)

Ha1 Z Cf !8760 (9)

Total amount of gross generated power is:

Eout Z ðNg !Wgn CNs !WsnÞ!Cf !8760 (10)

Substituting these values in Eq. (1), will give us the LEC. Because of complicated

calculations and many parameters involved, a computer program was prepared.

5. Results

Fig. 5 shows the fuel consumption in six cases. In order to compare the fuel

consumption of each power plant, it is expressed as m3/MW h. The fuel consumption in

conventional combined cycle is more than the others. The ISCC-67 has lower fuel

consumption about 16% than combined cycle. The decrease in fuel consumption in ISCC-

33 and SEGS are 8 and 13% respect to combined cycle. The ISCC-67 and SEGS have the

same solar field capacity, but the better efficiency of ISCC-67 makes its fuel consumption

lower. Studies show that by using solar field, fuel cost of conventional combined cycle

decreases considerably. If we assume the fuel price (natural gas) 4.5 ¢/m3, ISCC-67 and

SEGS save about 1.3!109 m3 (58.8 million $) through 30 years. This amount for ISCC-33

is about 29 million $.

Greenhouse effects lead us to consider the environmental effects of different cases. CO2

is the main part of pollution in atmosphere, which increases greenhouse effects. Fig. 6

shows the CO2 production by different cases in capacity factor of 0.74. CO2 production in

gas unit is maximum and it decreases in SEGS, conventional combined cycle, ISCC-33,

ISCC-67, respectively. ISCC-33 and ISCC-67 produce 16 and 8% lower CO2 than

8 Only gas unit consumes fuel.

Page 10: Technical and economic assessment of the integrated solar combined cycle power plants in Iran

Fig. 5. Natural gas consumption per unit of produced energy for different cases in capacity factor 0.74.

R. Hosseini et al. / Renewable Energy 30 (2005) 1541–15551550

combined cycle. Pollutant emission not only has the environmental effects, but also results

to economical problem. This economical problem returns to extra cost for equipments that

can remove the CO2 from flue gas. If we consider the CO2 removal cost about 25 $/ton

[13], the difference in specific cost between combined cycle, ISCC-33 and ISCC-67 will

be decreased about 74–168 $/kW.

LEC is the main economical parameter for evaluating the proposed cases. The

economical assumptions for calculating LEC are presented in Table 3. Fig. 7 shows the

LEC amount based on Table 3 values and the maximum capacity factor. It has broken

the LEC to three parts as investment cost, O&M cost and fuel cost. Fig. 8 shows the

amount of LEC at conditions like Fig. 7, but it considers the environmental costs. The

interesting point of Fig. 7 is the effect of environmental cost. As mentioned before,

the pollutant emission damages the environment and increases the cost. If we ignore

the environmental cost, the combined cycle has the lowest LEC (Fig. 7).

In this case, the LEC of ISCC-33, 14%, ISCC-67, 24% and gas unit 21% are higher than

combined cycle.

In Fig. 8, where the environmental effects are considered, LEC of ISCC-67 will be

lower than combined cycle. In this case the LEC of ISCC-33, 8%, combined cycle 11%

Fig. 6. CO2 emission per unit of produced energy for different cases in capacity factor 0.74.

Page 11: Technical and economic assessment of the integrated solar combined cycle power plants in Iran

Table 3

Economic assumptions for calculating the LEC in different cases

Parameter Symbol Unit Value

Life expectancy of steam unit Ns year 30

Life expectancy of gas unit Ng year 15

Life expectancy of solar field Nsol year 30

Annual discount rate R year 10

Specific cost of steam unit of CC Cs $/kW 635

Specific cost of gas unit Cg $/kW 235

Specific cost of solar field 33 MW Csol33 $/kW 1400

Specific cost of solar field 67 MW Csol67 $/kW 1000

O&M cost factor of steam unit of CC ks % 2

O&M cost factor of gas unit kg % 5

O&M cost factor of solar field ksol % 1.5

LHV of natural gas LHV kcal/m3 8590

Natural gas price Cf ¢/m3 4.5

Solar hours (full load) Hsol h 2092

Net efficiency of SEGS hSEGS % 33.4

Efficiency of supplementary heater of SEGS hH % 83

Annual net efficiency of gas turbine hg % 32.2

Efficiency of auxiliary firing unit hAF % 36.9

Internal consumption of SEGS ASEGS % 8

Internal consumption of gas unit AG % 1.5

Internal consumption of CC ACC % 3

Internal consumption of ISCC-33 AISCC-33 % 3.5

Internal consumption of ISCC-67 AISCC-67 % 3.9

R. Hosseini et al. / Renewable Energy 30 (2005) 1541–1555 1551

and gas turbine 33% are higher than ISCC-67. The environmental cost in combined cycle

and gas turbine increases their LEC about 38 and 36%, respectively.

Figs. 9 and 10 show the LEC of cases as a function of capacity factor. As it can be seen,

the LEC decreases by increasing the capacity factor. Fig. 11 explains the variation of

ISCC-67 LEC, when solar field specific cost, changes.

Fig. 7. LEC of different cases in maximum capacity factor without considering environmental cost (natural gas

price, 4.5 ¢/m3).

Page 12: Technical and economic assessment of the integrated solar combined cycle power plants in Iran

Fig. 8. LEC of different cases in maximum capacity factor with considering environmental cost (natural gas price,

4.5 ¢/m3).

R. Hosseini et al. / Renewable Energy 30 (2005) 1541–15551552

If the solar field specific cost decreases to 300 $/kW, the LEC without considering

environmental effects, is equal to conventional combined cycle. So it is required to invest

49 million $ extra to economize the ISCC-67 case.

The other main parameter in economical assessment is the specific cost. The specific

cost of each part of power plant is in certain range (Table 4), but for power plant it should

be calculated.

Fig. 9. LEC variation of different cases without considering the environmental costs (natural gas price, 4.5 ¢/m3).

Fig. 10. LEC variation of different cases with considering the environmental costs (natural gas price, 4.5 ¢/m3).

Page 13: Technical and economic assessment of the integrated solar combined cycle power plants in Iran

Fig. 11. LEC variation of ISCC-67 in different solar field specific cost.

R. Hosseini et al. / Renewable Energy 30 (2005) 1541–1555 1553

The computer program, calculates this parameter. The results are presented in Fig. 12.

It expresses that the specific costs of ISCC plans are about 37–52% more than

conventional combined cycle. Thus, these projects need to be supported by international

organizations like GEF. GEF statistics shows that four projects in India, Morraco, Egypt

and Mexico have used this loan [14].

Table 4

Overall technical and economic specifications of different cases for Yazd solar power plant

Parameter Unit GT CC ISCC-33 ISCC-67 ISCC67-

AF

SEGS

Nominal

capacity of

power plant

MW e 246 371 407 444 444 67

Annual net

efficiency

% 32.2 49.3 50.9 51.6 50.9 35.4

Maximum

capacity factor

% 80.1 83.8 79.3 73.7 76 74

Investment cost Million $ 58 137 206 251 255 110

Specific cost $/kW 235 370 506 564 573 1635

Saving fuel

in 30 yearsa

Million $ – – 29 59 59 59

CO2 emission

reduction

in 30 yearsa

Million

ton

– – 1.2 2.4 2.4 2.4

LECb ¢/kW h 1.986 1.639 1.878 2.035 2.087 4.116

LECc ¢/kW h 2.716 2.263 2.195 2.035 2.29 4.116

a Fuel saving and reduction in CO2 emission return to solar energy usage.b Without considering of environmental costs (pollutant removal cost), natural gas price 4.5 ¢/m3 and in

maximum capacity factor.c With considering of environmental costs (pollutant removal cost), natural gas price 4.5 ¢/m3 and in maximum

capacity factor.

Page 14: Technical and economic assessment of the integrated solar combined cycle power plants in Iran

Fig. 12. Specific cost of different cases.

R. Hosseini et al. / Renewable Energy 30 (2005) 1541–15551554

6. Conclusions

The technical and economic assessment of different cases for Yazd solar power plant

shows that the INTEGRATED SOLAR COMBINED CYCLE SYSTEM (ISCC-67) is the

most suitable project for construction of first solar power plant in Iran. Its construction

can be performed modular, which is consisted of solar field and combined cycle. The

results of technical and economical assessment are summarized in Table 4. It shows that,

LEC of combined cycle without considering the environmental effects is the lowest.

If we consider the environmental effects, the ISCC-67 will have the lowest LEC, which

is about 10 and 33% lower than combined cycle and gas turbine, respectively. Also if 49

million $ of investment cost is supplied by international organizations, the LEC of ISCC-

67 will be equal to combined cycle. If we assume the natural gas price 4.5 ¢/m3, we will

save 59 million $.9 This amount will change to 118 million $ if we consider the natural gas

price 8.5 ¢/m3. On the other hand, using solar field decreases the CO2 emission about 2.4

million ton. Using auxiliary burners in ISCC67-AF will increase LEC about 2.5% more

than ISCC-67 case, but will enable us to use the idle steam turbine capacity in non-solar

hours especially at peak hours. Auxiliary firing system increases 3% the power plant

capacity factor.

References

[1] Tavanir Organization. Detail statistics of Iran power industry. Tehran, Iran: Statistics Department; 2002.

[2] Mechanical Engineering Department. Assignment of suitable areas for installation of first solar power plant

in Iran. Tehran, Iran: Electric Power Reasearch Center; 1997.

[3] Benemann J. Status report on solar thermal power plants. Munich: Pilkington Solar International GmbH;

1996.

[4] Terrado E. Economics and financing of solar thermal power. The WorldBank. www.SolarPACES.org/

solutions/economics.html

[5] Quaschning V, Muriel MB. Photovoltaics or solar thermal power plants. Brussels: VGB Congress Power

Plants; 2001.

9 If we use 67 MW e solar field.

Page 15: Technical and economic assessment of the integrated solar combined cycle power plants in Iran

R. Hosseini et al. / Renewable Energy 30 (2005) 1541–1555 1555

[6] Spencer Management Associates. Mexico feasibility study for an integrated solar combined cycle system

(ISCCS). WorldBank; 2000.

[7] Geyer M, Quaschning V. Solar thermal power. Renewable Energy World, July–Aug 2000 p. 184–91.

[8] Morse HF. The commercial path forward for concentrating solar power technologies. Washington, DC:

Morse Associates, Inc.; 2000.

[9] Mechanical Engineering Department. Technical and economic assessment of Yazd solar power plant.

PMESB01/T1. Tehran, Iran: Niroo Reasearch Institute; 2000.

[10] Renewable Energies Department. Feasibility study of the first solar power plant in Iran. Tehran, Iran: Niroo

Reasearch Institute; 2000.

[11] Enermodal Engineering Ltd, Marbek Resource Consultants Ltd. Cost reduction study for solar thermal

power plants. Washington, DC: WorldBank; 1999.

[12] Brakmann G. Integrated technical, economic and ecological consideration of large scale solar thermal

power plants for developing countries. World Clean Energy Conference UNCED, Geneva; 1991.

[13] Tavanir Organization. Plan power generation. Economic comparison of solar thermal power plants. Tehran,

Iran; 2000.

[14] Sunlab. Quarterly news and information about parabolic trough technology. www.eren.gov/troughnet/

documents/jan_2000.html