Tbdp a e Ds 0104 Rev 0

download Tbdp a e Ds 0104 Rev 0

of 11

Transcript of Tbdp a e Ds 0104 Rev 0

  • 8/11/2019 Tbdp a e Ds 0104 Rev 0

    1/11

    PROJECT NAME : PROVISION OF DETAILED DESIGN SERVICESFOR THAI BINH DEVELOPMENT PROJECT,

    BLOCKS 102 & 106, OFFSHORE VIETNAM

    DOCUMENT TITLE : DATASHEET FOR AIR-CONDITIONER

    DOCUMENT NO.

    CONTRACT NO.

    CTR NO.

    :

    :

    :

    TBDP-A-E-DS-0104

    PCV/TBDP- A/2011/702

    D-EL-400

    REV CODEISSUE

    DATE

    DOC

    STATUS

    CONTRACTOR COMPANYACCEPTANCEAUTHOR CHECKER APPROVER

    NAME NAME NAME NAME DATE

    A 21-01-14 IFR HNT Quang NM Thao Andrew Hoang

    0 17-03-14 AFC HNT Quang NM Thao Andrew Hoang

    Document Class: B - Confidential (Should only be shared with staff or contractors who have a need-to-know)

  • 8/11/2019 Tbdp a e Ds 0104 Rev 0

    2/11

    Cl ient Nam e: PETRONAS Car ig al i Over seas Sd n B hd (PCOSB )

    Datasheet No. : TB DP-A-E-DS-0104

    Revision No. : 0

    Specification No:

    Project: Page No. : 1 of 10

    Equipment Name: Fan co il Unit

    Equipment Tag No.: FCU-01A/01B

    Location: Thai Binh Dri l ling Wel lhead Plat form, i .e. TBDP-A, Of fshore Vietnam

    1 Quantity 2 (1 duty, 1standby)

    2 Description Fan coil unit+ Built-in thermostat

    3 Service Instrument room

    4 Manufacturer / Model No. *

    5 Unit Type Wall mounted type

    6 Cabinet Material Manufacturer's Standard

    7 Overall Dimensions (L x W x H mm) 940 x 275 x 199/*

    8 Weight (Kg) 10/*

    9 Total Supply Air (L/S) , minimum 223

    10 Cooling Capacity :

    11 Sensible heat (kWR), minimum *

    12 Total heat (kWR), minimum

    13 Area Classification Safe area

    14 Base Frame Material Manufacturer's Standard

    15 Noise Level (dBA) @ 1 m (low/high) 44/47

    16 Capacity (L/s), minimum *

    17 External Discharge Pressure (Pa) *

    18 Volume Control Device *19 RPM (Max. 1450) 1300/*

    20 Mounting *

    21 Electrical Characteristic 230V/1Pha/50Hz

    22 Fan Motor Absorbed Power (W) 30/*

    23 Fan Motor Rating (W) *

    24 Material Manufacturer's Standard

    PROVISION OF DETAILED DESIGN SERVICES FOR

    THAI BINH DEVELOPMENT PROJECT, BLOCKS 102 & 106,

    OFFSHORE VIETNAM

    5.3

    25 EVAPORATOR COIL

    26 Air On-Coil C DB/WB *

    27 Air Off-Coil C DB/WB *

    28 Coil Face Velocity (m/s) 2.5 MAX.

    29 No. of Rows 3/*

    30 No. Fins per inch (FPI) *

    31 FILTER

    32 Manufacturer / Model No. *

    33 Type / Material Washable / *34 Filter Size *

    35 Filter Efficiency 85% min

    36 Filter Face Velocity (m/s) 2.5 MAX.

    37

    38

    39

    40

    41

    42

    43

    44

    45

    46

    47

    48

    4950

    51

    52

    53 * VENDOR TO COMPLETE

    54

    55

    56

    57

    58

    0 17-03-14 AFC HNT Quang NM Thao Andrew Hoang

    A 21-01-14 IFR HNT Quang NM Thao Andrew Hoang

    0

    COMPANY ACCEPTANCE ACCEPTANCE DATECONTRACTOR

    REV ISSUE DATE DOC. STATUSAUTHOR CHECKER APPROVER

  • 8/11/2019 Tbdp a e Ds 0104 Rev 0

    3/11

    Cl ient Nam e: PETRONAS Car ig al i Over seas Sd n B hd (PCOSB )

    Datasheet No. : TB DP-A-E-DS-0104

    Revision No. : 0

    Specification No:

    Project: Page No. : 2 of 10

    Equipment Name: Fan co il Unit

    Equipment Tag No.: FCU-02A/02B

    Location: Thai Binh Dri l ling Wel lhead Plat form, i .e. TBDP-A, Of fshore Vietnam

    1 Quantity 2 (1 duty, 1standby)

    2 Description Fan coil unit+ Built-in thermostat

    3 Service Electrical room

    4 Manufacturer / Model No. *

    5 Unit Type Wall mounted type

    6 Cabinet Material Manufacturer's Standard

    7 Overall Dimensions (L x W x H mm) 940 x 275 x 199/*

    8 Weight (Kg) 10/*

    9 Total Supply Air (L/S) , minimum 223

    10 Cooling Capacity :

    11 Sensible heat (kWR), minimum *

    12 Total heat (kWR), minimum

    13 Area Classification Safe area

    14 Base Frame Material Manufacturer's Standard

    15 Noise Level (dBA) @ 1 m (low/high) 44/47

    16 Capacity (L/s), minimum *

    17 External Discharge Pressure (Pa) *

    18 Volume Control Device *19 RPM (Max. 1450) 1300/*

    20 Mounting *

    21 Electrical Characteristic 230V/1Pha/50Hz

    22 Fan Motor Absorbed Power (W) 30/*

    23 Fan Motor Rating (W) *

    24 Material Manufacturer's Standard

    5.3

    PROVISION OF DETAILED DESIGN SERVICES FOR

    THAI BINH DEVELOPMENT PROJECT, BLOCKS 102 & 106,

    OFFSHORE VIETNAM

    0

    0

    25 EVAPORATOR COIL

    26 Air On-Coil C DB/WB *

    27 Air Off-Coil C DB/WB *

    28 Coil Face Velocity (m/s) 2.5 MAX.

    29 No. of Rows 3/*

    30 No. Fins per inch (FPI) *

    31 FILTER

    32 Manufacturer / Model No. *

    33 Type / Material Washable / *34 Filter Size *

    35 Filter Efficiency 85% min

    36 Filter Face Velocity (m/s) 2.5 MAX.

    37

    38

    39

    40

    41

    42

    43

    44

    45

    46

    47

    48

    4950

    51

    52

    53 * VENDOR TO COMPLETE

    54

    55

    56

    57

    58

    A 21-01-14 IFR HNT Quang NM Thao Andrew Hoang

    0 17-03-14 AFC HNT Quang NM Thao Andrew Hoang

    APPROVERCOMPANY ACCEPTANCE ACCEPTANCE DATE

    CONTRACTORREV ISSUE DATE DOC. STATUS

    AUTHOR CHECKER

  • 8/11/2019 Tbdp a e Ds 0104 Rev 0

    4/11

    Cl ient Nam e: PETRONAS Car ig al i Over seas Sd n B hd (PCOSB )

    Datasheet No. : TB DP-A-E-DS-0104

    Revision No. : 0

    Specification No:

    Project: Page No. : 3 of 10

    Equip ment Name: Fan Coi l Unit

    Equipment Tag No.: FCU-03A/03B

    Location: Thai Binh Dri l ling Wel lhead Plat form, i .e. TBDP-A, Of fshore Vietnam

    1 Quantity 2 (1 duty, 1standby)

    2 Description Fan coil unit+ Built-in thermostat

    3 Service Battery room

    4 Manufacturer / Model No. *

    5 Unit Type Wall mounted type

    6 Cabinet Material Manufacturer's Standard

    7 Overall Dimensions (L x W x H mm) 790 x 275 x 195/*

    8 Weight (Kg) 8.4/*

    9 Total Supply Air (L/S) , minimum 162

    10 Cooling Capacity :

    11 Sensible heat (kWR), minimum *

    12 Total heat (kWR), minimum

    13 Area Classification Zone 1, Group IIC, T3

    14 Base Frame Material Manufacturer's Standard

    15 Noise Level (dBA) @ 1 m (low/high) 44/47

    16 Capacity (L/s), minimum *

    17 External Discharge Pressure (Pa) *

    18 Volume Control Device *19 RPM (Max. 1450) 1300/*

    20 Mounting *

    21 Electrical Characteristic 230V/1Pha/50Hz

    22 Fan Motor Absorbed Power (W) 30/*

    23 Fan Motor Rating (W) *

    24 Material Manufacturer's Standard

    PROVISION OF DETAILED DESIGN SERVICES FOR

    THAI BINH DEVELOPMENT PROJECT, BLOCKS 102 & 106,

    OFFSHORE VIETNAM

    3.70

    0

    25 EVAPORATOR COIL

    26 Air On-Coil C DB/WB *

    27 Air Off-Coil C DB/WB *

    28 Coil Face Velocity (m/s) 2.5 MAX.

    29 No. of Rows 3/*

    30 No. Fins per inch (FPI) *

    31 FILTER

    32 Manufacturer / Model No. *

    33 Type / Material Washable / *34 Filter Size *

    35 Filter Efficiency 85% min

    36 Filter Face Velocity (m/s) 2.5 MAX.

    37

    38

    39

    40

    41

    42

    43

    44

    45

    46

    47

    48

    4950

    51

    52

    53 * VENDOR TO COMPLETE

    54

    55

    56

    57

    58

    A 21-01-14 IFR HNT Quang NM Thao Andrew Hoang

    0 Andrew Hoang17-03-14 AFC HNT Quang NM Thao

    REV ISSUE DATE DOC. STATUSAUTHOR CHECKER APPROVER

    COMPANY ACCEPTANCE ACCEPTANCE DATECONTRACTOR

  • 8/11/2019 Tbdp a e Ds 0104 Rev 0

    5/11

    Cl ient Nam e: PETRONAS Car ig al i Over seas Sd n B hd (PCOSB )

    Datasheet No. : TB DP-A-E-DS-0104

    Revision No. : 0

    Specification No:

    Project: Page No. : 4 of 10

    Equip ment Name: Fan Coi l Unit

    Equipment Tag No.: FCU-04

    Location: Thai Binh Dri l ling Wel lhead Plat form, i .e. TBDP-A, Of fshore Vietnam

    1 Quantity 1

    2 Description Fan coil unit+ Built-in thermostat

    3 Service Shelter room

    4 Manufacturer / Model No. *

    5 Unit Type Wall mounted type

    6 Cabinet Material Manufacturer's Standard

    7 Overall Dimensions (L x W x H mm) 790 x 275 x 195/*

    8 Weight (Kg) 8.4/*

    9 Total Supply Air (L/S) , minimum 162

    10 Cooling Capacity :

    11 Sensible heat (kWR), minimum *

    12 Total heat (kWR), minimum

    13 Area Classification Safe zone

    14 Base Frame Material Manufacturer's Standard

    15 Noise Level (dBA) @ 1 m (low/high) 44/47

    16 Capacity (L/s), minimum *

    17 External Discharge Pressure (Pa) *

    18 Volume Control Device *19 RPM (Max. 1450) 1300/*

    20 Mounting *

    21 Electrical Characteristic 230V/1Pha/50Hz

    22 Fan Motor Absorbed Power (W) 30/*

    23 Fan Motor Rating (W) *

    24 Material Manufacturer's Standard

    3.70

    PROVISION OF DETAILED DESIGN SERVICES FOR

    THAI BINH DEVELOPMENT PROJECT, BLOCKS 102 & 106,

    OFFSHORE VIETNAM

    25 EVAPORATOR COIL

    26 Air On-Coil C DB/WB *

    27 Air Off-Coil C DB/WB *

    28 Coil Face Velocity (m/s) 2.5 MAX.

    29 No. of Rows 3/*

    30 No. Fins per inch (FPI) *

    31 FILTER

    32 Manufacturer / Model No. *

    33 Type / Material Washable / *34 Filter Size *

    35 Filter Efficiency 85% min

    36 Filter Face Velocity (m/s) 2.5 MAX.

    37

    38

    39

    40

    41

    42

    43

    44

    45

    46

    47

    48

    4950

    51

    52

    53 * VENDOR TO COMPLETE

    54

    55

    56

    57

    58

    A 21-01-14 IFR HNT Quang NM Thao Andrew Hoang

    0 17-03-14 AFC HNT Quang NM Thao Andrew Hoang

    0

    APPROVERCOMPANY ACCEPTANCE ACCEPTANCE DATE

    CONTRACTORREV ISSUE DATE DOC. STATUS

    AUTHOR CHECKER

  • 8/11/2019 Tbdp a e Ds 0104 Rev 0

    6/11

    Cl ient Nam e: PETRONAS Car ig al i Over seas Sd n B hd (PCOSB )

    Datasheet No. : TB DP-A-E-DS-0104

    Revision No. : 0

    Specification No:

    Project: Page No. : 5 of 10

    Equipment Name: A ir Cooled Condenser Un it

    Equipment Tag No.: ACCU-01A/01B

    Location: Thai Binh Dri l ling Wel lhead Plat form, i .e. TBDP-A, Of fshore Vietnam

    1 Quantity 2 (1 duty, 1 standby)

    2 Description Air Cooled Condenser Unit

    3 Service Instrument room

    4 Manufacturer/Model No. *

    5 Type Direct Expansion Air Cooled

    6 Casing Material SS 316L

    7 Overall Dimensions (L x W x H mm) 780 x 540 x 250/*

    8 Dry Weight (Kg) 35/*

    9 Operating Weight (Kg) *

    10 Total Cooling Capacity (KwR) 5.3

    11 Unit Classification Safe zone

    12 Casing Thickness ( mm ) 1.5

    13 Noise Level ( dBA ) @ 1 M 58

    14 Refrigerant Receiver NOTE ( 2 )

    15 COMPRESSOR

    16 Type *

    17 Manufacturer/Model No. *

    18 No. off Compressor 119 Refrigerant Type (CFC free type) R407C or equivalent

    20 Operating Charge Refrigerant (Kg) *

    21 Lubricating Oil (L) *

    22 Saturated Suction Temp (C) *

    23 Saturated Discharge Temp (C) *

    24 No. of Cycle *

    PROVISION OF DETAILED DESIGN SERVICES FOR

    THAI BINH DEVELOPMENT PROJECT, BLOCKS 102 & 106,

    OFFSHORE VIETNAM

    25 Capacity Reduction Method *

    26 Capacity Reduction (%) *

    27 Net Refrigeration Capacity (Kw) *

    28 Total Absorbed Power (Kw) 1.5/*

    29 Total Rated Power (Kw) *

    30 Electrical Characteristic (V/Phase/H) 230V/ 1Phase/50Hz

    31 Mounting ( NOTE 3) / *

    32 COIL

    33 Manufacturer/Model No. *34 Coil / Fin Material Copper / Cooper (Treated with anti-corrosion coating)

    35 No. of Rows 2

    36 No. of Fins per inch (FPI) *

    37 Condensing Temp (C) *

    38 Air Inlet Temp (C) 36/*

    39 Total Heat Rejection (Kw) *

    40 Coil Design Pressure ( Pa ) *

    41 CONDENSING FANS

    42 Type of Fan Permanent split capacitor

    43 No. & Size of Fans 2/*

    44 Air Volume (L/S) *

    45 Fan Motor Absorbed Power (w) *

    46 Fan Motor Rating (w) *

    47 Impeller Material Polyamide Glass Reinforced (PAGAS)

    48 Cowl Material *

    49 Mounting 95% Anti vib mounts50

    51

    52

    53 * VENDOR TO COMPLETE

    54 NOTE ( 1 ) : VENDOR SHALL FURNISH EQUIPMENT NOISE DATA & COMPLY TO REQUIREMENTS AS PER SPECS

    55 NOTE ( 2 ) : VENDOR SHALL BE RESPONSIBLE TO SIZE & PROVIDE RECIEVER TO STORE ALL REFRIGERANT IN THE SYSTEM DURING

    56 PIPING PUMP DOWN CYCLE.

    57 NOTE ( 3 ) : VIBRATION ISOLATORS SHALL PROVIDE 95% ANTI VIBRATION ISOLATION AT COMPRESSOR RUNNING SPEED.

    58

    A 21-01-14 IFR HNT Quang NM Thao Andrew Hoang

    0 17-03-14 AFC HNT Quang NM Thao Andrew Hoang

    0

    APPROVERCOMPANY ACCEPTANCE ACCEPTANCE DATE

    CONTRACTORREV ISSUE DATE DOC. STATUS

    AUTHOR CHECKER

  • 8/11/2019 Tbdp a e Ds 0104 Rev 0

    7/11

    Cl ient Nam e: PETRONAS Car ig al i Over seas Sd n B hd (PCOSB )

    Datasheet No. : TB DP-A-E-DS-0104

    Revision No. : 0

    Specification No:

    Project: Page No. : 6 of 10

    Equipment Name: A ir Cooled Condenser Un it

    Equipment Tag No.: ACCU-02A/02B

    Location: Thai Binh Dri l ling Wel lhead Plat form, i .e. TBDP-A, Of fshore Vietnam

    1 Quantity 2 (1 duty, 1 standby)

    2 Description Air Cooled Condenser Unit

    3 Service Electrical room

    4 Manufacturer/Model No. *

    5 Type Direct Expansion Air Cooled

    6 Casing Material SS 316L

    7 Overall Dimensions (L x W x H mm) 780 x 540 x 250/*

    8 Dry Weight (Kg) 35/*

    9 Operating Weight (Kg) *

    10 Total Cooling Capacity (KwR) 5.3

    11 Unit Classification Safe zone

    12 Casing Thickness ( mm ) 1.5

    13 Noise Level ( dBA ) @ 1 M 58

    14 Refrigerant Receiver NOTE ( 2 )

    15 COMPRESSOR

    16 Type *

    17 Manufacturer/Model No. *

    18 No. off Compressor 119 Refrigerant Type (CFC free type) R407C or equivalent

    20 Operating Charge Refrigerant (Kg) *

    21 Lubricating Oil (L) *

    22 Saturated Suction Temp (C) *

    23 Saturated Discharge Temp (C) *

    24 No. of Cycle *

    PROVISION OF DETAILED DESIGN SERVICES FOR

    THAI BINH DEVELOPMENT PROJECT, BLOCKS 102 & 106,

    OFFSHORE VIETNAM

    25 Capacity Reduction Method *

    26 Capacity Reduction (%) *

    27 Net Refrigeration Capacity (Kw) *

    28 Total Absorbed Power (Kw) 1.5/*

    29 Total Rated Power (Kw) *

    30 Electrical Characteristic (V/Phase/H) 230V/ 1Phase/50Hz

    31 Mounting ( NOTE 3) / *

    32 COIL

    33 Manufacturer/Model No. *34 Coil / Fin Material Copper / Cooper (Treated with anti-corrosion coating)

    35 No. of Rows 2

    36 No. of Fins per inch (FPI) *

    37 Condensing Temp (C) *

    38 Air Inlet Temp (C) 36/*

    39 Total Heat Rejection (Kw) *

    40 Coil Design Pressure ( Pa ) *

    41 CONDENSING FANS

    42 Type of Fan Permanent split capacitor

    43 No. & Size of Fans 2/*

    44 Air Volume (L/S) *

    45 Fan Motor Absorbed Power (w) *

    46 Fan Motor Rating (w) *

    47 Impeller Material Polyamide Glass Reinforced (PAGAS)

    48 Cowl Material *

    49 Mounting 95% Anti vib mounts50

    51

    52

    53 * VENDOR TO COMPLETE

    54 NOTE ( 1 ) : VENDOR SHALL FURNISH EQUIPMENT NOISE DATA & COMPLY TO REQUIREMENTS AS PER SPECS

    55 NOTE ( 2 ) : VENDOR SHALL BE RESPONSIBLE TO SIZE & PROVIDE RECIEVER TO STORE ALL REFRIGERANT IN THE SYSTEM DURING

    56 PIPING PUMP DOWN CYCLE.

    57 NOTE ( 3 ) : VIBRATION ISOLATORS SHALL PROVIDE 95% ANTI VIBRATION ISOLATION AT COMPRESSOR RUNNING SPEED.

    58

    NM Thao

    NM Thao

    AFC

    HNT Quang

    HNT Quang

    Andrew Hoang

    Andrew Hoang17-03-14

    21-01-14 IFRA

    0

    0

    0

    CONTRACTOR

    AUTHOR CHECKER APPROVERCOMPANY ACCEPTANCE ACCEPTANCE DATEREV DOC. STATUSISSUE DATE

  • 8/11/2019 Tbdp a e Ds 0104 Rev 0

    8/11

    Cl ient Nam e: PETRONAS Car ig al i Over seas Sd n B hd (PCOSB )

    Datasheet No. : TB DP-A-E-DS-0104

    Revision No. : 0

    Specification No:

    Project: Page No. : 7 of 10

    Equipment Name: A ir Cooled Condenser Un it

    Equipment Tag No.: ACCU-03A/03B

    Location: Thai Binh Dri l ling Wel lhead Plat form, i .e. TBDP-A, Of fshore Vietnam

    1 Quantity 2 (1 duty, 1 standby)

    2 Description Air Cooled Condenser Unit

    3 Service Battery room

    4 Manufacturer/Model No. *

    5 Type Direct Expansion Air Cooled

    6 Casing Material SS 316L

    7 Overall Dimensions (L x W x H mm) 700 x 540 x 250/*

    8 Dry Weight (Kg) 28/*

    9 Operating Weight (Kg) *

    10 Total Cooling Capacity (KwR) 3.7

    11 Unit Classification Safe zone

    12 Casing Thickness ( mm ) 1.5

    13 Noise Level ( dBA ) @ 1 M 58

    14 Refrigerant Receiver NOTE ( 2 )

    15 COMPRESSOR

    16 Type *

    17 Manufacturer/Model No. *

    18 No. off Compressor 119 Refrigerant Type (CFC free type) R407C or equivalent

    20 Operating Charge Refrigerant (Kg) *

    21 Lubricating Oil (L) *

    22 Saturated Suction Temp (C) *

    23 Saturated Discharge Temp (C) *

    24 No. of Cycle *

    PROVISION OF DETAILED DESIGN SERVICES FOR

    THAI BINH DEVELOPMENT PROJECT, BLOCKS 102 & 106,

    OFFSHORE VIETNAM

    25 Capacity Reduction Method *

    26 Capacity Reduction (%) *

    27 Net Refrigeration Capacity (Kw) *

    28 Total Absorbed Power (Kw) 1.5/*

    29 Total Rated Power (Kw) *

    30 Electrical Characteristic (V/Phase/H) 230V/ 1Phase/50Hz

    31 Mounting ( NOTE 3) / *

    32 COIL

    33 Manufacturer/Model No. *34 Coil / Fin Material Copper / Cooper (Treated with anti-corrosion coating)

    35 No. of Rows 2

    36 No. of Fins per inch (FPI) *

    37 Condensing Temp (C) *

    38 Air Inlet Temp (C) 36/*

    39 Total Heat Rejection (Kw) *

    40 Coil Design Pressure ( Pa ) *

    41 CONDENSING FANS

    42 Type of Fan Permanent split capacitor

    43 No. & Size of Fans 2/*

    44 Air Volume (L/S) *

    45 Fan Motor Absorbed Power (w) *

    46 Fan Motor Rating (w) *

    47 Impeller Material Polyamide Glass Reinforced (PAGAS)

    48 Cowl Material *

    49 Mounting 95% Anti vib mounts50

    51

    52

    53 * VENDOR TO COMPLETE

    54 NOTE ( 1 ) : VENDOR SHALL FURNISH EQUIPMENT NOISE DATA & COMPLY TO REQUIREMENTS AS PER SPECS

    55 NOTE ( 2 ) : VENDOR SHALL BE RESPONSIBLE TO SIZE & PROVIDE RECIEVER TO STORE ALL REFRIGERANT IN THE SYSTEM DURING

    56 PIPING PUMP DOWN CYCLE.

    57 NOTE ( 3 ) : VIBRATION ISOLATORS SHALL PROVIDE 95% ANTI VIBRATION ISOLATION AT COMPRESSOR RUNNING SPEED.

    58

    A 21-01-14 IFR HNT Quang NM Thao Andrew Hoang

    0 Andrew Hoang17-03-14 AFC HNT Quang NM Thao

    0

    0

    REV ISSUE DATE DOC. STATUSAUTHOR CHECKER APPROVER

    COMPANY ACCEPTANCE ACCEPTANCE DATECONTRACTOR

  • 8/11/2019 Tbdp a e Ds 0104 Rev 0

    9/11

    Cl ient Nam e: PETRONAS Car ig al i Over seas Sd n B hd (PCOSB )

    Datasheet No. : TB DP-A-E-DS-0104

    Revision No. : 0

    Specification No:

    Project: Page No. : 8 of 10

    Equipment Name: A ir Cooled Condenser Un it

    Equipment Tag No.: ACCU-04

    Location: Thai Binh Dri l ling Wel lhead Plat form, i .e. TBDP-A, Of fshore Vietnam

    1 Quantity 1

    2 Description Air Cooled Condenser Unit

    3 Service Shelter room

    4 Manufacturer/Model No. *

    5 Type Direct Expansion Air Cooled

    6 Casing Material SS 316L

    7 Overall Dimensions (L x W x H mm) 700 x 540 x 250/*

    8 Dry Weight (Kg) 28/*

    9 Operating Weight (Kg) *

    10 Total Cooling Capacity (KwR) 3.7

    11 Unit Classification Safe zone

    12 Casing Thickness ( mm ) 1.5

    13 Noise Level ( dBA ) @ 1 M 58

    14 Refrigerant Receiver NOTE ( 2 )

    15 COMPRESSOR

    16 Type *

    17 Manufacturer/Model No. *

    18 No. off Compressor 119 Refrigerant Type (CFC free type) R407C or equivalent

    20 Operating Charge Refrigerant (Kg) *

    21 Lubricating Oil (L) *

    22 Saturated Suction Temp (C) *

    23 Saturated Discharge Temp (C) *

    24 No. of Cycle *

    PROVISION OF DETAILED DESIGN SERVICES FOR

    THAI BINH DEVELOPMENT PROJECT, BLOCKS 102 & 106,

    OFFSHORE VIETNAM

    25 Capacity Reduction Method *

    26 Capacity Reduction (%) *

    27 Net Refrigeration Capacity (Kw) *

    28 Total Absorbed Power (Kw) 1.5/*

    29 Total Rated Power (Kw) *

    30 Electrical Characteristic (V/Phase/H) 230V/ 1Phase/50Hz

    31 Mounting ( NOTE 3) / *

    32 COIL

    33 Manufacturer/Model No. *34 Coil / Fin Material Copper / Cooper (Treated with anti-corrosion coating)

    35 No. of Rows 2

    36 No. of Fins per inch (FPI) *

    37 Condensing Temp (C) *

    38 Air Inlet Temp (C) 36/*

    39 Total Heat Rejection (Kw) *

    40 Coil Design Pressure ( Pa ) *

    41 CONDENSING FANS

    42 Type of Fan Permanent split capacitor

    43 No. & Size of Fans 2/*

    44 Air Volume (L/S) *

    45 Fan Motor Absorbed Power (w) *

    46 Fan Motor Rating (w) *

    47 Impeller Material Polyamide Glass Reinforced (PAGAS)

    48 Cowl Material *

    49 Mounting 95% Anti vib mounts50

    51

    52

    53 * VENDOR TO COMPLETE

    54 NOTE ( 1 ) : VENDOR SHALL FURNISH EQUIPMENT NOISE DATA & COMPLY TO REQUIREMENTS AS PER SPECS

    55 NOTE ( 2 ) : VENDOR SHALL BE RESPONSIBLE TO SIZE & PROVIDE RECIEVER TO STORE ALL REFRIGERANT IN THE SYSTEM DURING

    56 PIPING PUMP DOWN CYCLE.

    57 NOTE ( 3 ) : VIBRATION ISOLATORS SHALL PROVIDE 95% ANTI VIBRATION ISOLATION AT COMPRESSOR RUNNING SPEED.

    58

    A 21-01-14 IFR HNT Quang NM Thao Andrew Hoang

    0 17-03-14 AFC HNT Quang NM Thao Andrew Hoang

    0

    APPROVERCOMPANY ACCEPTANCE ACCEPTANCE DATE

    CONTRACTORREV ISSUE DATE DOC. STATUS

    AUTHOR CHECKER

  • 8/11/2019 Tbdp a e Ds 0104 Rev 0

    10/11

    Cl ient Nam e: PETRONAS Car ig al i Over seas Sd n B hd (PCOSB )

    Datasheet No. : TB DP-A-E-DS-0104

    Revision No. : 0

    Specification No:

    Project: Page No. : 9 of 10

    Equipment Name: Exhaust Fan

    Equipment Tag No.: EF-01A/01B

    Location: Thai Binh Dri l ling Wel lhead Plat form, i .e. TBDP-A, Of fshore Vietnam

    1 Quantity 2 (1 duty, 1 standby)

    2 Description Exhaust Air Fan

    3 Service Battery room

    4 Manufacturer/Model No. *

    5 Type/Drive Wall mounted type

    6 Material Manufacturer's Standard

    7 Capacity (L/S) 90

    8 Ext. Static Pressure (Pa) 50/*

    9 Volume Control Device *

    10 RPM (max 1450) 900/*

    11 Mounting *

    12 Anti Spark Design *

    13 Electrical Characteristic 230V/ 1Phase/50Hz

    14 Fan Motor Rating (Kw) *

    15 Fan Motor Absorbed Power (Kw)

    16 Area Classification Zone 1, Group IIC, T3

    17 Insulation class F

    18 Operating Temp class B19

    20

    21

    22

    23

    24

    PROVISION OF DETAILED DESIGN SERVICES FOR

    THAI BINH DEVELOPMENT PROJECT, BLOCKS 102 & 106,

    OFFSHORE VIETNAM

    0.15/* 0

    25

    26

    27

    28

    29

    30

    31

    32

    3334

    35

    36

    37

    38

    39

    40

    41

    42

    43

    44

    45

    46

    47

    48

    4950

    51

    52

    53 * VENDOR TO COMPLETE

    54

    55

    56

    57

    58

    A 21-01-14 IFR HNT Quang NM Thao Andrew Hoang

    0 Andrew Hoang17-03-14 AFC HNT Quang NM Thao

    REV ISSUE DATE DOC. STATUSAUTHOR CHECKER APPROVER

    COMPANY ACCEPTANCE ACCEPTANCE DATECONTRACTOR

  • 8/11/2019 Tbdp a e Ds 0104 Rev 0

    11/11

    Cl ient Nam e: PETRONAS Car ig al i Over seas Sd n B hd (PCOSB )

    Datasheet No. : TB DP-A-E-DS-0104

    Revision No. : 0

    Specification No:

    Project: Page No. : 10 of 10

    Equipment Name: Exhaust Fan

    Eq ui pm en t Tag No .: EF-02

    Location: Thai Binh Dri l ling Wel lhead Plat form, i .e. TBDP-A, Of fshore Vietnam

    1 Quantity 1

    2 Description Exhaust Air Fan

    3 Service Shelter room

    4 Manufacturer/Model No. *

    5 Type/Drive Wall mounted type

    6 Material Manufacturer's Standard

    7 Capacity (L/S) 90

    8 Ext. Static Pressure (Pa) 50/*

    9 Volume Control Device *

    10 RPM (max 1450) 900/*

    11 Mounting *

    12 Anti Spark Design *

    13 Electrical Characteristic 230V/ 1Phase/50Hz

    14 Fan Motor Rating (Kw) *

    15 Fan Motor Absorbed Power (Kw)

    16 Area Classification Safe zone

    17 Insulation class F

    18 Operating Temp class B19

    20

    21

    22

    23

    24

    0.15/*

    PROVISION OF DETAILED DESIGN SERVICES FOR

    THAI BINH DEVELOPMENT PROJECT, BLOCKS 102 & 106,

    OFFSHORE VIETNAM

    0

    25

    26

    27

    28

    29

    30

    31

    32

    3334

    35

    36

    37

    38

    39

    40

    41

    42

    43

    44

    45

    46

    47

    48

    4950

    51

    52

    53 * VENDOR TO COMPLETE

    54

    55

    56

    57

    58

    A 21-01-14 IFR HNT Quang NM Thao Andrew Hoang

    0 17-03-14 AFC HNT Quang NM Thao Andrew Hoang

    APPROVERCOMPANY ACCEPTANCE ACCEPTANCE DATE

    CONTRACTORREV ISSUE DATE DOC. STATUS

    AUTHOR CHECKER