TABLE OF STANDARDS
ASTM: DESIGN AND CONSTRUCTION OF SANITARY AND STORM SEWERS
STANDARDS FOR THE DESIGN OF MANHOLES
DESCRIPTION STANDARD
GENERAL SHAPE & DIMENSION Inside diameter must be least 4ft
Maintain the 4ft diameter up to a conical
section
Frames under diameter at least 24inches P to
30 inches, within 2ft of the surface.
Walking space of manhole 3ft x 4ft vault
STEPS Manhole steps should be wide enough for a
man to place both feet on one step, and should
be designed to prevent lateral slippage off the
step.
General spacing of steps, 12 to 16in intervals(30-50cm)
CHANNEL AND BENCH For sizes of 15 inches and larger, the required
channel height rarely is less than three- fourths
of the diameter.
The bench should provide good footing for a
workman and a place where minor tools and
equipment can be laid.
-
8/10/2019 Table of Standards (ASTM MANHOLES)
2/8
STANDARDS FOR HE DESIGN OF MANHOLES
0.5in /ft is specified in some areas to provide
safer footing.
MAN HOLES ON LARGE SEWERS Where a sewer is larger than 2ft and the small
sewer type of man hole is used, the diameter of
the manhole should be increased sufficiently to
maintain an adequate width of bench,
preferably a foot or more on each side.
For sewers up to 3ft in diameter, covers
sometimes are used having a clear opening of
3ft to accommodate cleaning equipment
equalling the sewer diameter.
Many authorities do not use openings larger
than 2ft, openings larger than 3ft are used onlyin special cases.
SHALLOW MAN HOLES If the depth of the invert is only 2 or 3ft, all
maintenance operations can be conducted
from the surface. A manhole 2 or 3ft in
diameter at the bottom generally suffices in
these cases; narrow slots also have been used.
If man hole is usual type, height from the bench
to surface is in the range 2 to 4ft or 5ft( 0.6 to
1.2 or 1.5m), with the shaft tapering to a 22inchclear opening , the structure is one in which a
man cannot work effectively.
Brick or concrete block walls normally are built
8 inches (20.3cm ) thick at the shallower
depths, and may increase to 12 inches (0.3m)
below 8 to 12ft (2.4 to 3.6m) from the surface
-
8/10/2019 Table of Standards (ASTM MANHOLES)
3/8
STANDARDS FOR THE DESIGN OF MANHOLES
The outside walls of brick or block manholes
should be filled completely with cement
mortar. The outside walls of brick or block man
holes should be parged with cement mortar not
less than 1/2in (1.3cm) thick. In wet areas it is
advisable to apply a coating of bituminous
damp-proofing compound.
BENDS A curve of very short radius causes energy
wasting turbulence. Some authorities
recommend for optimum performance that the
radius of the centre line be three times the pipe
diameter or channel width. Reasonably
satisfactory conditions usually can be obtained
if the radius is not less than 1.5 times the
diameter.
Bands of less than 90 degrees can of course be
accommodated more easily. For angles
substantially less than 90 degrees on sewers
larger than 12 inches in diameter, the manhole
maybe centre d over the pipe
DROP MANHOLES Drop manholes should be used sparingly and
generally, only when it is not economically
feasible to steepen the incoming sewer. Some
engineers eliminate drops by using verticalcurves.
BUILDING SEWERS Building sewers also called house connections,
service connection, or source laterals, are the
branches between the street sewer and the
property or curb, serving individual properties,
and usually are required to be 4, 5 or 6 inches
in diameter (10 to 15inches) preferably with a
slope of 1/4 in/ft (2cm/m) or 2 percent.
-
8/10/2019 Table of Standards (ASTM MANHOLES)
4/8
STANDARDS FOR THE DESIGN OF MANHOLES
GUTTER INLETS A horizontal opening in the gutter covered by
one or more grates through which the gutter
flow passes is called a gutter inlet. Tests
indicate that grates with slots parallel to the
curb are the least subject to plugging and
provide the best inflow conditions.
Width of the opening must not be greater than
1inch (2.5cm) so that bicycle tyres will not pass
through.
-
8/10/2019 Table of Standards (ASTM MANHOLES)
5/8
WATER AND SEWERAGE AUTHORITY (WASA) OF TRINIDAD AND TOBAGO
WATER AND WASTE WATER DESIGN GUIDE MANUAL
DESIGN STANDARDS
DESCRIPTION STANDARD
Co efficient of roughness For all pipe materials, the coefficient of roughness should be set as 0.013
Minimum Pipe Size For residential areas, the minimum pipe shall be 200 mm diameter
For commercial and industrial areas, the minimum pipe size shall be 250
mm diameter.
Flow Velocities The maximum velocity shall not be greater than 3.0 m/sec with the pipe
flowing full and the
minimum velocity shall not be less than 0.60 m/sec with actual flow on a
daily basis. The depth of flow should never exceed 75% of the internal
diameter of the sewer.
System Layout Location of Wastewater
Main
All new wastewater mains shall be located within the road allowance
Location of replacement wastewater mains shall be determined
specifically based on the location of existing utilities and other site
conditions and will be dealt with as situation arises. Preferably, sewers areto be 1.5 m offset from roadway centreline. System arrangement shall
include redundancy and overflows to propose alternate routes in case of
blockage. Overflow shall be
rerouted in the sewer system. Sewer easements are required if sewer
located out of roadway
Gas pipelines need a minimum separation of 0.9 m at crossings. See
section 5.5.3 for distances
-
8/10/2019 Table of Standards (ASTM MANHOLES)
6/8
from drinking water lines & pipes
Forcemains Pipe Size Forcemains shall be sized to have a flow velocity in the range of 0.7 to 3.0
m/s, with the lower limit being preferred for the initial phase. The
minimum size of the forcemain shall be 100 mm in diameter
Pipe Depth Consultants shall allow a minimum of 1.2 m of cover for forcemains
Maintenance Chamber (Manhole)1.
At maintenance chambers where pipe sizes change from smaller pipe size to a larger downstream pipe size, match the pipes obvert
elevations. It is not permissible to design downstream pipe size smaller than the upstream pipe size.
2.
Drop maintenance chambers shall be provided where the difference in elevation is greater than 0.60 metres. The drop pipe shall be
one size smaller than the wastewater main. The economic feasibility of providing deeper wastewater mains versus excessive invertdrops drop maintenance chambers, or excessively steep benching shall be ascertained prior to finalizing the design. Prefabricated
drops internal to the maintenance chamber are not permitted on 1200 mm diameter maintenance chambers. Where the
maintenance chamber depth exceeds 10 m, provide safety grating.
3.
Watertight and locking covers shall be provided on maintenance chambers located on all easements and in areas where
maintenance chambers are susceptible to flooding. Where significant sections of wastewater mains are provided with watertight
covers, extended vents may be required which shall be determined by the Consultants on a case-by-case basis. Frames and covers
to be a floating style (NF80 or 90) capable of withstanding H-20 loading.
4.
Tee maintenance chambers may be used for wastewater mains 1200 mm or larger in diameter
5.
Sanitary sewer service connection to a maintenance chamber should be avoided. However, it may be permissible should the
proposed sanitary sewer service falls within the same obvert elevation of the sanitary sewer entering the maintenance chamber.
6.
For commercial and industrial establishments, an inspection maintenance chamber must be placed at a location immediately
behind the property line to service the lateral connection.
7.
All enclosures and rails should be corrosion resistant.
-
8/10/2019 Table of Standards (ASTM MANHOLES)
7/8
MANHOLE HYDRAULICS
Alignment Change Required Drop
15o45o min. 0.030 m
45o90o min. 0.050 m
*Pipe Slopes & Manhole distances
The minimum slopes shown are those required for self-cleansing velocity set as 0.7 meter per second, The maximum length between manholes and
the absolute minimum slopes for different sewer sizes shall conform the following:
SEWER SIZE (mm) MAXIMUM LENGTH (m) BETWEEN
MANHOLES
MINIMUM SLOPE (m/100m)
200 90 0.40
250 110 0.28
300 110 0.20
350 110 0.17
375 110 0.15
400 120 0.14
450 120 0.12
525 120 0.10
600 150 0.08
900 150 0.046
1200 Assess 0.031
1800 Assess 0.020
-
8/10/2019 Table of Standards (ASTM MANHOLES)
8/8
*Street Line Connection
Single family and semi-detached dwellings in residential areas shall have a minimum of 150 mm diameter street line connection.
Dual connections or two separate lines in a common trench are acceptable in residential areas where the difference in basement elevation does not
exceed 0.60 m. Two or more units serviced on a common line with wye branches are acceptable. Where the diameter of the lateral connection isgreater than or equal to half the diameter of the wastewater main, the connection shall be made with a tee-wye or wye connection. The minimum and
maximum cover at property line shall be 1.2 m and 1.8 m, respectively. A 2% minimum grade for lateral connections shall be maintained. Pipe size
change must be made through similar quality eccentric pipe reducers. In multiple family blocks in residential areas, the lateral connections shall meet
the following requirements:
Connection Size and Grade
Diameter of Drain (mm) Slope Of Drain
2% 4%
Maximum Number of Fixture Units per Connection
150 840 1000
200 1920 2300
250 3500 4200
300 5600 6700
375 10000 12000