    TABLE OF STANDARDS

    ASTM: DESIGN AND CONSTRUCTION OF SANITARY AND STORM SEWERS

    STANDARDS FOR THE DESIGN OF MANHOLES

    DESCRIPTION STANDARD

    GENERAL SHAPE & DIMENSION Inside diameter must be least 4ft

    Maintain the 4ft diameter up to a conical

    section

    Frames under diameter at least 24inches P to

    30 inches, within 2ft of the surface.

    Walking space of manhole 3ft x 4ft vault

    STEPS Manhole steps should be wide enough for a

    man to place both feet on one step, and should

    be designed to prevent lateral slippage off the

    step.

    General spacing of steps, 12 to 16in intervals(30-50cm)

    CHANNEL AND BENCH For sizes of 15 inches and larger, the required

    channel height rarely is less than three- fourths

    of the diameter.

    The bench should provide good footing for a

    workman and a place where minor tools and

    equipment can be laid.

  • 8/10/2019 Table of Standards (ASTM MANHOLES)

    2/8

    STANDARDS FOR HE DESIGN OF MANHOLES

    0.5in /ft is specified in some areas to provide

    safer footing.

    MAN HOLES ON LARGE SEWERS Where a sewer is larger than 2ft and the small

    sewer type of man hole is used, the diameter of

    the manhole should be increased sufficiently to

    maintain an adequate width of bench,

    preferably a foot or more on each side.

    For sewers up to 3ft in diameter, covers

    sometimes are used having a clear opening of

    3ft to accommodate cleaning equipment

    equalling the sewer diameter.

    Many authorities do not use openings larger

    than 2ft, openings larger than 3ft are used onlyin special cases.

    SHALLOW MAN HOLES If the depth of the invert is only 2 or 3ft, all

    maintenance operations can be conducted

    from the surface. A manhole 2 or 3ft in

    diameter at the bottom generally suffices in

    these cases; narrow slots also have been used.

    If man hole is usual type, height from the bench

    to surface is in the range 2 to 4ft or 5ft( 0.6 to

    1.2 or 1.5m), with the shaft tapering to a 22inchclear opening , the structure is one in which a

    man cannot work effectively.

    Brick or concrete block walls normally are built

    8 inches (20.3cm ) thick at the shallower

    depths, and may increase to 12 inches (0.3m)

    below 8 to 12ft (2.4 to 3.6m) from the surface

  • 8/10/2019 Table of Standards (ASTM MANHOLES)

    3/8

    STANDARDS FOR THE DESIGN OF MANHOLES

    The outside walls of brick or block manholes

    should be filled completely with cement

    mortar. The outside walls of brick or block man

    holes should be parged with cement mortar not

    less than 1/2in (1.3cm) thick. In wet areas it is

    advisable to apply a coating of bituminous

    damp-proofing compound.

    BENDS A curve of very short radius causes energy

    wasting turbulence. Some authorities

    recommend for optimum performance that the

    radius of the centre line be three times the pipe

    diameter or channel width. Reasonably

    satisfactory conditions usually can be obtained

    if the radius is not less than 1.5 times the

    diameter.

    Bands of less than 90 degrees can of course be

    accommodated more easily. For angles

    substantially less than 90 degrees on sewers

    larger than 12 inches in diameter, the manhole

    maybe centre d over the pipe

    DROP MANHOLES Drop manholes should be used sparingly and

    generally, only when it is not economically

    feasible to steepen the incoming sewer. Some

    engineers eliminate drops by using verticalcurves.

    BUILDING SEWERS Building sewers also called house connections,

    service connection, or source laterals, are the

    branches between the street sewer and the

    property or curb, serving individual properties,

    and usually are required to be 4, 5 or 6 inches

    in diameter (10 to 15inches) preferably with a

    slope of 1/4 in/ft (2cm/m) or 2 percent.

  • 8/10/2019 Table of Standards (ASTM MANHOLES)

    4/8

    STANDARDS FOR THE DESIGN OF MANHOLES

    GUTTER INLETS A horizontal opening in the gutter covered by

    one or more grates through which the gutter

    flow passes is called a gutter inlet. Tests

    indicate that grates with slots parallel to the

    curb are the least subject to plugging and

    provide the best inflow conditions.

    Width of the opening must not be greater than

    1inch (2.5cm) so that bicycle tyres will not pass

    through.

  • 8/10/2019 Table of Standards (ASTM MANHOLES)

    5/8

    WATER AND SEWERAGE AUTHORITY (WASA) OF TRINIDAD AND TOBAGO

    WATER AND WASTE WATER DESIGN GUIDE MANUAL

    DESIGN STANDARDS

    DESCRIPTION STANDARD

    Co efficient of roughness For all pipe materials, the coefficient of roughness should be set as 0.013

    Minimum Pipe Size For residential areas, the minimum pipe shall be 200 mm diameter

    For commercial and industrial areas, the minimum pipe size shall be 250

    mm diameter.

    Flow Velocities The maximum velocity shall not be greater than 3.0 m/sec with the pipe

    flowing full and the

    minimum velocity shall not be less than 0.60 m/sec with actual flow on a

    daily basis. The depth of flow should never exceed 75% of the internal

    diameter of the sewer.

    System Layout Location of Wastewater

    Main

    All new wastewater mains shall be located within the road allowance

    Location of replacement wastewater mains shall be determined

    specifically based on the location of existing utilities and other site

    conditions and will be dealt with as situation arises. Preferably, sewers areto be 1.5 m offset from roadway centreline. System arrangement shall

    include redundancy and overflows to propose alternate routes in case of

    blockage. Overflow shall be

    rerouted in the sewer system. Sewer easements are required if sewer

    located out of roadway

    Gas pipelines need a minimum separation of 0.9 m at crossings. See

    section 5.5.3 for distances

  • 8/10/2019 Table of Standards (ASTM MANHOLES)

    6/8

    from drinking water lines & pipes

    Forcemains Pipe Size Forcemains shall be sized to have a flow velocity in the range of 0.7 to 3.0

    m/s, with the lower limit being preferred for the initial phase. The

    minimum size of the forcemain shall be 100 mm in diameter

    Pipe Depth Consultants shall allow a minimum of 1.2 m of cover for forcemains

    Maintenance Chamber (Manhole)1.

    At maintenance chambers where pipe sizes change from smaller pipe size to a larger downstream pipe size, match the pipes obvert

    elevations. It is not permissible to design downstream pipe size smaller than the upstream pipe size.

    2.

    Drop maintenance chambers shall be provided where the difference in elevation is greater than 0.60 metres. The drop pipe shall be

    one size smaller than the wastewater main. The economic feasibility of providing deeper wastewater mains versus excessive invertdrops drop maintenance chambers, or excessively steep benching shall be ascertained prior to finalizing the design. Prefabricated

    drops internal to the maintenance chamber are not permitted on 1200 mm diameter maintenance chambers. Where the

    maintenance chamber depth exceeds 10 m, provide safety grating.

    3.

    Watertight and locking covers shall be provided on maintenance chambers located on all easements and in areas where

    maintenance chambers are susceptible to flooding. Where significant sections of wastewater mains are provided with watertight

    covers, extended vents may be required which shall be determined by the Consultants on a case-by-case basis. Frames and covers

    to be a floating style (NF80 or 90) capable of withstanding H-20 loading.

    4.

    Tee maintenance chambers may be used for wastewater mains 1200 mm or larger in diameter

    5.

    Sanitary sewer service connection to a maintenance chamber should be avoided. However, it may be permissible should the

    proposed sanitary sewer service falls within the same obvert elevation of the sanitary sewer entering the maintenance chamber.

    6.

    For commercial and industrial establishments, an inspection maintenance chamber must be placed at a location immediately

    behind the property line to service the lateral connection.

    7.

    All enclosures and rails should be corrosion resistant.

  • 8/10/2019 Table of Standards (ASTM MANHOLES)

    7/8

    MANHOLE HYDRAULICS

    Alignment Change Required Drop

    15o45o min. 0.030 m

    45o90o min. 0.050 m

    *Pipe Slopes & Manhole distances

    The minimum slopes shown are those required for self-cleansing velocity set as 0.7 meter per second, The maximum length between manholes and

    the absolute minimum slopes for different sewer sizes shall conform the following:

    SEWER SIZE (mm) MAXIMUM LENGTH (m) BETWEEN

    MANHOLES

    MINIMUM SLOPE (m/100m)

    200 90 0.40

    250 110 0.28

    300 110 0.20

    350 110 0.17

    375 110 0.15

    400 120 0.14

    450 120 0.12

    525 120 0.10

    600 150 0.08

    900 150 0.046

    1200 Assess 0.031

    1800 Assess 0.020

  • 8/10/2019 Table of Standards (ASTM MANHOLES)

    8/8

    *Street Line Connection

    Single family and semi-detached dwellings in residential areas shall have a minimum of 150 mm diameter street line connection.

    Dual connections or two separate lines in a common trench are acceptable in residential areas where the difference in basement elevation does not

    exceed 0.60 m. Two or more units serviced on a common line with wye branches are acceptable. Where the diameter of the lateral connection isgreater than or equal to half the diameter of the wastewater main, the connection shall be made with a tee-wye or wye connection. The minimum and

    maximum cover at property line shall be 1.2 m and 1.8 m, respectively. A 2% minimum grade for lateral connections shall be maintained. Pipe size

    change must be made through similar quality eccentric pipe reducers. In multiple family blocks in residential areas, the lateral connections shall meet

    the following requirements:

    Connection Size and Grade

    Diameter of Drain (mm) Slope Of Drain

    2% 4%

    Maximum Number of Fixture Units per Connection

    150 840 1000

    200 1920 2300

    250 3500 4200

    300 5600 6700

    375 10000 12000