T14_Troubleshooting the 3500 Monitoring System

download T14_Troubleshooting the 3500 Monitoring System

of 12

Transcript of T14_Troubleshooting the 3500 Monitoring System

  • 8/10/2019 T14_Troubleshooting the 3500 Monitoring System

    1/12

    3500 Operation and Maintenance - Section 14: Page 1

    Rev K 139317

    Troubleshooting the

    3500 Monitoring System

    Topic Objectives:

    You will be able to explain the various kinds of problems that can potentially occur

    with a 3500 monitoring system installation.

  • 8/10/2019 T14_Troubleshooting the 3500 Monitoring System

    2/12

    Page 2: 3500 Operation and Maintenance - Section 14

    Rev K 139317

    Potential Connection Problems

    There are several wiring issues that can affect the 3500 monitoring system, including the

    following:

    open or shorted field wiring from the transducer system to the monitor rack

    improper connections at the monitor rack, and/or at the transducer interface

    monitoring rack or I/O jumpers incorrectly installed for the given configuration

    corrosion on the field wiring connections

    grounds loops

    When the wiring is complete and uninterrupted, there may still be wiring issues.Grounding of the transducer wiring anywhere but at the rack, or at the selected single

    point ground can create voltage potential differences, and noise. In addition, placing thelow voltage transducer signal wiring near high voltage wiring or fields may also

    introduce noise, or unexpected effects.

  • 8/10/2019 T14_Troubleshooting the 3500 Monitoring System

    3/12

    3500 Operation and Maintenance - Section 14: Page 3

    Rev K 139317

    Configuration of the Monitor

    In most cases, the 3500 configuration software will not allow the improper use of a

    monitor or I/O module. However, the following conditions can still cause problems:

    incorrect or unusable setpoint adjustments

    incorrect configuration of the transducer devices

    incorrect scales and/or limits for the direct measurement, or for any of the related

    variables

    As mentioned in an earlier section, the best practice for configuring a set of monitors and

    channels is to set the first of each kind of monitoring channel very carefully, and reviewthe configuration. Then, use the Copy process available at three levels (i.e., channel,

    channel pair, and monitor) to configure the remainder of that group of monitors. This is amuch easier, and much safer practice.

  • 8/10/2019 T14_Troubleshooting the 3500 Monitoring System

    4/12

    Page 4: 3500 Operation and Maintenance - Section 14

    Rev K 139317

    Configuration Issues

    Some dynamically configured devices, such as the rotary potentiometer Valve Position

    transducer or the LVDT Case Expansion measurement, must be partially configuredwhile the software is connected to the monitoring system. This is a significant

    convenience, since it allows the ability to calibrate the monitor using the actual

    transducer signal. The process is implemented by allowing the lowest and highest

    voltage or measurement inputs to be set in the software, and then downloaded to the

    monitor. Without the software process, a voltage measurement and manual entry wouldbe required to set the lower and higher limits. However, it is critical that the stepsspecified in the Rack Hardware Installation, Operations, and Maintenance manual are

    implemented properly and in the correct order for these devices to be properly

    configured.

  • 8/10/2019 T14_Troubleshooting the 3500 Monitoring System

    5/12

    3500 Operation and Maintenance - Section 14: Page 5

    Rev K 139317

    Use of I/O Modules

    As with monitors, the software will not allow an improper I/O module to be downloadedto the rack. The configuration software displays the proper module when the monitor

    data has been uploaded from the rack.

    It is recommended to use the 3500 Configuration software and perform an upload fromthe rack before the initial software configuration is done. When uploading the

    configuration, this will include all inserted monitors and I/O modules causing lesslikelihood for a mis-match.

  • 8/10/2019 T14_Troubleshooting the 3500 Monitoring System

    6/12

    Page 6: 3500 Operation and Maintenance - Section 14

    Rev K 139317

    Compatibility Issues

    Older monitors and modules may cause problems when applied to newer devices and/or

    installations. In most cases, an older monitor can be updated by way of eitherdownloading the firmware through the configuration software, or replacing an EPROM

    (erasable read only memory) chip on the board.

    The configuration software allows the user to view the firmware revisions in most of the

    newer monitors, and as mentioned earlier, it is possible to download the new firmware tosome of the newer monitors via the configuration software.

    An older monitor that does not seem to respond to the proper configuration process, or is

    not acting properly after a configuration process may need to have a firmware upgrade.

    When updating firmware on the 3500/22M Transient Data Interface (TDI), the TDI DSP

    update will need to be applied also. Contact your local Bently Nevada representative toassist in this process.

  • 8/10/2019 T14_Troubleshooting the 3500 Monitoring System

    7/12

    3500 Operation and Maintenance - Section 14: Page 7

    Rev K 139317

    Disabling (Bypassing) Monitors

    Monitors may be bypassed at any time from the configuration or display software by

    selecting the appropriate channel or monitor switches and changing their state(s).Bypassed or Not OK channels are not allowed to drive alarms, so this will not change the

    state of any relays.

    As an added note here, and as mentioned previously in this course, it is actually possible

    to change a relay state by placing a monitor into bypass. An example might be if twomonitors are Normally ANDed. If one is already at the appropriate level (i.e., Alert orDanger), and the other is REMOVED from the logical equation, the relay will change

    state on the information provided by the monitor already in alarm. In other words, the

    relay will change state, potentially (and unexpectedly) taking a machine off line. Once

    again, it is always a good idea to identify the voting monitors, and place them into theappropriately bypassed or inhibited state when making configuration changes to any of

    the monitors.

  • 8/10/2019 T14_Troubleshooting the 3500 Monitoring System

    8/12

    Page 8: 3500 Operation and Maintenance - Section 14

    Rev K 139317

    Disabling (Bypassing) Monitors

    Monitors and power supplies are designed to be removed from the monitor rack while the

    monitoring system is powered up; this is called Hot Swapping. The monitor will placeitself in bypass when it is reinstalled, and during the time period required for it to go

    through its self-test process.

  • 8/10/2019 T14_Troubleshooting the 3500 Monitoring System

    9/12

    3500 Operation and Maintenance - Section 14: Page 9

    Rev K 139317

    Hot Swapping Components

    As mentioned earlier, monitors and power supplies (one at a time) can be removed with

    the power applied to the rack. However, it is recommended that the following not beHot Swapped:

    the Rack Interface Module (RIM) and Transient Data Interface (TDI);

    communications to outside devices and monitor management will be lost causing

    unreliable or unexpected results I/O modules are not designed for removal during power on conditions. For safety

    reasons, as well as for potential voltage arcing, power interface modules (PIMs)

    should not be removed or installed with power applied to the device

    finally, considering that there are usually several wires and cables in the back of a

    monitoring rack, any of which could be bumped, and possibly cause problems, it isgenerally a good practice, when possible, to only work behind the monitoring

    system when the power to the rack is off, and the machine is not running

  • 8/10/2019 T14_Troubleshooting the 3500 Monitoring System

    10/12

    Page 10: 3500 Operation and Maintenance - Section 14

    Rev K 139317

    Review

    Wiring, miswiring, system jumpers

    Monitor configuration

    Use of proper I/O modules

    Firmware and hardware compatibility

    Bypassing or disabling monitors

    Hot swapping monitoring system

    components

    Name some wiring conditions that could stop the data transfer from the transducer system

    to the monitoring rack.

    Identify some monitor configuration issues that could cause problems with the

    monitoring system.

    Explain what could happen if older monitors are used with newer monitoring systems,and identify the way this can be resolved.

    Explain how monitors can be bypassed using the display or configuration software.

    Explain some rules or guidelines for Hot Swapping monitors and I/O modules.

  • 8/10/2019 T14_Troubleshooting the 3500 Monitoring System

    11/12

    3500 Operation and Maintenance - Section 14: Page 11

    Rev K 139317

    Troubleshooting the

    3500 Monitoring System

    Topic Objectives Revisited:

    You will be able to explain the various kinds of problems that can potentially occurwith a 3500 monitoring system installation.

  • 8/10/2019 T14_Troubleshooting the 3500 Monitoring System

    12/12

    Page 12: 3500 Operation and Maintenance - Section 14

    Rev K 139317

    < This page intentionally left blank >