T Service Manual
-
Upload
anderson103 -
Category
Documents
-
view
236 -
download
0
Transcript of T Service Manual
-
8/10/2019 T Service Manual
1/65
-
8/10/2019 T Service Manual
2/65
-
8/10/2019 T Service Manual
3/65
-
8/10/2019 T Service Manual
4/65
1.2 Operation Instructions
1.2.1 System Start-up Procedure
Please check the following noticed items before UPS start-up:
1. All circuit breakers and isolators are in OFF position and battery fuse is out.
2. Ensure that neutral line and grounding are the same voltage level.
3. Apply power to the AC input cables and check that input voltage, frequency and
phase order are with in the machine specifications.
When UPS comply with the above mentioned conditions, start-up UPS according to the
following procedures:
1. Close MANUAL BYPASS breaker, at the same time LCD display LOAD ON
BYPASS .
2. Close AC INPUT and RECTIFIER INPUT breakerwait 1520 seconds until
BATT LOW LED behind the door is off.
3. Close RESERVED INPUT breaker, at the same time LCD display LOAD ON
RESERVE .
4. Close UPS OUTPUT breaker.
5. Open MANUAL BYPASS breaker.
6. Close BATTERY FUSE ISOLATOR in battery cabinet.
7. Press the inverter ON & button simultaneously, the load will be transferred
from reserve to inverter automatically, at the same time LCD display LOAD ON
INVERTER .
Note: It must never turn on manual bypass circuit breaker when the
inverter is turned on. It will damage the UPS owing to utility power
parallel with inverter output.
1.2.2 Maintenance Manual Bypass Procedure
This procedures leave the critical load undisturbed and the UPS batteries will still be
charged. The operating procedures are as follows:
1-2
-
8/10/2019 T Service Manual
5/65
1. Check MAIN FREQ ABNORMAL RES MAINS FAIL LEDS behind the door are
all off.
2. Press inverter OFF & button simultaneously. Check that INV ON LED
behind the door is off.
3. Close MANUAL BYPASS breaker.
4. Open UPS OUTPUT breaker.
5. Open RESERVE INPUT breaker.
1.2.3 Return from Bypass to Normal Mode
This operating procedures will transfer load from bypass to normal mode as follows:
1. Check that INV ON LED behind the door is off.
2. Close RESERVE INPUT breaker.
3. Close UPS OUTPUT breaker.4. Open MANUAL BYPASS breaker.
5. Press the inverter ON & button simultaneously.
6. The load will be transferred from reserve to inverter automatically.
1.2.4 System Shutdown Procedure
This operating procedure can turn off power supply to UPS, please first confirm the load
has been shutdown, the procedures as follows
1. Press inverter OFF & button simultaneouslyCheck that INV ON LED
behind the door is off.
2. Close MANUAL BYPASS breaker.
3. Open BATTERY FUSE ISOLATOR in battery cabinet.
4. Open RECTIFIER INPUT breaker.
5. Open RESERVE INPUT breaker.
6. Open UPS OUTPUT breaker.
7. Wait 5 mins for DC CAP to discharge.
8. Open AC INPUT & MANUAL BYPASS breaker.
1-3
-
8/10/2019 T Service Manual
6/65
1.3 Technical Specifications
1.3.1 Rectif ier Input Characterist ics
(a) 380/220 Input
3 input3 output 3 input1 output
Power rating KVA (P.F.0.8) 10 15 20 30 40 50 60 80 100 120 150 10 15 20 30 40 50
(1) Nominal voltage V 220/380() 220/380()
(2) Voltage range % 20 20
(3) Nominal frequency Hz 50 / 60 50 / 60
(4) Frequency range % 5 5
(5) Nominal input power
(with charged battery)KVA Power rating120% Power rating120%
(6) Input power factor cosq 0.7 0.7
(7) Maximum input power
(with battery under charge)KVA Power rating 135% Power rating 135%
(8) Range input current A 18 28 37 55 73 90 108 144 180 215 270 18 28 37 55 73 90
(9) Maximum input current A 26 39 52 78 103 127 152 203 253 304 376 26 39 52 78 103 127
(10) Start-up time sec 20 20
(11) Efficiency % 96 96
1-4
Item Spec.
-
8/10/2019 T Service Manual
7/65
(b) 208/120 Input
3 input3 output 3 input1 output
Power rating KVA (P.F.0.8) 10 15 20 30 40 50 60 80 100 120 150 10 15 20 30 40 50
1) Nominal voltage V 208/120() 208/120()
2) Voltage range % 15 15
3) Nominal frequency Hz 50 / 60 50 / 60
4) Frequency range % 5 5
5) Nominal input power
(with charged battery)KVA Power rating120% Power rating120%
6) Input power factor cosq 0.7 0.7
7) Maximum input power
(with battery undercharge)
KVA Power rating 135% Power rating 135%
8) Range input current A 33 51 68 101 134 165 198 264 330 394 495 33 51 68 101 134 165
9) Maximum input current A 48 72 95 143 189 233 279 372 464 557 689 48 72 95 143 189 233
10) Start-up time sec 20 20
11) Efficiency % 96 96
() The different voltage specification is available.
1-5
Item Spec.
-
8/10/2019 T Service Manual
8/65
1.3.2 Rectif ier Output Characteristics
3 input3 output 3 input1 output
Power rating KVA (P.F.0.8) 10 15 20 30 40 50 60 80 100 120 150 10 15 20 30 40 50
(1) DC voltage range V 300420 300420
(2) Output voltage
(with Ni-Cd battery)
---float charge V 393 393
---boost charge V 415 415
(3) output voltage (with
sealed lead acid battery)
---float charge V 393 393
---boost charge V 405 405
(4) Voltage stability
(for input voltage and
output current change
simultaneously)
% 1 1
(5) DC voltage ripple
(Vrms/Vb100)% 2 2
(6) Nominal current Adc 22 34 45 67 89 110 131 175 219 263 324 22 34 45 67 89 110
(7) Maximum output current Adc 32 47 63 95 126 155 185 247 309 371 459 32 47 63 95 126 155
(8) Maximum charge current Adc 7 10 13 19 25 31 37 49 62 74 92 7 10 13 19 25 31
(9) Adjustable charging
current
Yes Yes
(10) Battery charging system DIN 41773 DIN 41773
1-6
ItemSpec.
-
8/10/2019 T Service Manual
9/65
-
8/10/2019 T Service Manual
10/65
1.3.5 Inverter Output Characteristics
(a) 380/220 Output
3 input3 output 3 input1 output
Power rating KVA (P.F.0.8) 10 15 20 30 40 50 60 80 100 120 150 10 15 20 30 40 50
(1) Nominal voltage V 220/380() 220()
(2) Nominal current A 15 23 30 45 61 76 91 121 152 182 227 45 68 91 136 182 227
(3) Nominal voltage
adjustment range
% 10 10
(4) Waveform Sinusoid Sinusoid
(5) T.H.D.(with linear load) % 3 3
(6) Output voltage
regulation (for input
voltage and output loadchange simultaneously)
% 1 1
(7) Output voltage dynamic
regulation for 0100%
load variations% 5 5
(8) Voltage symmetry with
balanced load
% 1 1
(9) Voltage symmetry with
100% unbalanced load % 1 1
(10) Displacement angle
between three phases1203 NA
(11) Output frequency Hz 50 / 60 50 / 60
(12) Phase lock range Hz 3 3
(13) Frequency stability
with internal oscillator
with mains synchronize
%
%
0.01
1
0.01
1
(14) Overload
110%15 minutes
125%10minutes
150%1minutes200%
110%15 minutes
125%10minutes
150%1minutes200%
(15) Inverter efficiency % 88 90 91 92 93 94 94 94 94 94 94 88 90 91 92 93 94
() The different voltage specification is available.
1-8
ItemSpec.
-
8/10/2019 T Service Manual
11/65
(b) 208/120 Output
3 input3 output 3 input1 output
Power rating KVA (P.F.0.8) 10 15 20 30 40 50 60 80 100 120 150 10 15 20 30 40 50
1) Nominal voltage V208/120(
) 110(
)
2) Nominal current A 28 42 55 83 112 139 167 222 279 334 417 91 136 182 273 364 455
3) Nominal voltage
adjustment range
% 10 10
4) Waveform Sinusoid Sinusoid
5) T.H.D.(with linear load) % 3 3
6) Output voltage regulation
(for input voltage and
output load change
simultaneously)
% 1 1
7) Output voltage dynamic
regulation for 0100%
load variations% 5 5
8) Voltage symmetry with
balanced load
% 1 1
9) Voltage symmetry with
100% unbalanced load % 1 1
10) Displacement angle
between three phases1203 NA
11) Output frequency Hz 50 / 60 50 / 60
12) Phase lock range Hz 3 3
13) Frequency stability
- with internal oscillator
- with mains
synchronize
%
%
0.01
1
0.01
1
14) Overload
110%15 minutes
125%10minutes
150%1minutes200%
110%15 minutes
125%10minutes
150%1minutes200%
15) Inverter efficiency % 86 87 88 89 90 90 90 91 91 91 91 87 88 89 90 91 91
() The different voltage specification is available.
1-9
ItemSpec.
-
8/10/2019 T Service Manual
12/65
1.3.6 Static Switch Input / Output Characteristics
(a) 380/220 Input / Output
3 input3 output 3 input1 output
Power rating KVA (P.F.0.8) 10 15 20 30 40 50 60 80 100 120 150 10 15 20 30 40 50
(1) Input / Output voltage V 380 220
(2) Input / Output frequency Hz 4565 4565
(3) Overload current
--- 30 minutes
--- 10 seconds
--- 30 milliseconds
%
%
%
120
500
1000
120
500
1000
(4) Maximum transfer time
- From inverter to reserve
(a) inverter failure
(b) inverter overload or
manual operation
- From reserve to inverter
manual operation or
automatic return
msec
msec
msec
1
0
0
1
0
0
(5) Efficiency (at nominal
load)
% 99.5 99.5
(6) High / Low AC voltage
transfer rate
% 20 20
(7) Slew rate Hz / sec 1 1
1-10
ItemSpec.
-
8/10/2019 T Service Manual
13/65
(b) 208/120 Input / Output
3 input3 output 3 input1 output
Power rating KVA (P.F.0.8) 10 15 20 30 40 50 60 80 100 120 150 10 15 20 30 40 50
1) Input / Output voltage V 208 120
2) Input / Output frequency Hz 4565 4565
3) Overload current
--- 30 minutes
--- 10 seconds
--- 30 milliseconds
%
%
%
120
500
1000
120
500
1000
4) Maximum transfer time
- From inverter to reserve
a) inverter failure
b) inverter overload or
manual operation
- From reserve to inverter
manual operation or
automatic return
msec
msec
msec
1
0
0
1
0
0
5) Efficiency (at nominal
load)
% 99.5 99.5
6) High / Low AC voltage
transfer rate
% 20 20
7) slew rate Hz / sec 1 1
1-11
ItemSpec.
-
8/10/2019 T Service Manual
14/65
1.3.7 General Specif icat ion
(a) 380/220 Input / Output
Item Spec. 3 input3 output 3 input1 o
Power rating KVA (P.F.0.8) 10 15 20 30 40 50 60 80 100 120 150 10 15 20 30
(1) ACAC efficiency
---nominal load % 86 88 89 90 91 92 92 92 92 92 92 86 88 89 90
---75 % 84 86 87 88 89 90 90 90 90 90 90 84 86 87 88
---50 % 81 82 83 84 85 86 86 86 86 86 86 81 82 83 84
---25 % 73 74 75 77 79 81 82 82 82 82 82 73 74 75 77
(2) Maximum dissipated
power at nominal load kw 1.30 1.63 1.98 2.67 3.16 3.48 4.17 5.57 6.95 8.35 10.4 1.30 1.63 1.98 2.67
(3) Audible noise(at a
distance of 1.5 m)
dB 60 65 60
(4) Ambient temperature 040 040
(5) Relative humidity % 90 90
(6) Dimensions:
--- Depth mm 800 800
--- Width mm600 600 600 600 600 800 800 1200 1200 1200 1200 600
--- Height mm 1700 1700
(7) Weight kg 480 380 420 490 550 670 750 900 1050 1200 1400 460 350 390 450
(8) Grade of protection IP20 IP20
(9) Control cabinet color DELTA COOL GREY DELTA COOL
1-12
-
8/10/2019 T Service Manual
15/65
(b) 208/120 Input / Output
Item Spec. 3 input3 output 3 input1 o
Power rating KVA (P.F.0.8)
10 15 20 30 40 50 60 80 100 120
150
10 15 20 30
(1) ACAC efficiency
---nominal load % 85 86 87 88 89 90 90 90 90 90 90 85 86 87 88
---75 % 83 84 85 86 87 88 88 88 88 88 88 83 84 85 86
---50 % 80 81 81 82 83 84 84 84 84 84 84 80 81 81 82
---25 % 71 72 73 75 77 79 80 80 80 80 80 71 72 73 75
(2) Maximum dissipated
power at nominal load kw 1.41 1.95 2.39 3.27 3.96 4.44 5.33 7.11 8.89 10.7 13.4 1.41 1.95 2.39 3.27
(3) Audible noise(at a
distance of 1.5 m)
dB 60 65 60
(4) Ambient temperature 040 040
(5) Relative humidity % 90 90
(6) Dimensions:
--- Depth mm 800 800
--- Width mm 540 450 490 590 650 780 870 1050 1200 1400 1600 600
--- Height mm 1700 1700
(7) Weight kg 480 380 420 490 550 670 750 900 1050 1200 1400 540 420 460 540
(8) Grade of protection IP20 IP20
(9) Control cabinet color DELTA COOL GREY DELTA COOL
1-13
-
8/10/2019 T Service Manual
16/65
2. Introduction to PCB Function
2.1 A Board (Inverter Control Board)
A. Function:
a. Generate three-phase sine-wave reference signal and triangle-wave which are transmitte
to T board.
b. Detect reserve AC voltage and frequency whether they are normal or not.
c. Produce high frequency square-wave signals, P1 and P2 signals are transmitted to B
board, SW+ and SW- signals to T board, and HF signals to P board.
d. When the inverter short circuit, heatsink over temperature or fuse fail, the LED will show
malfunction.
e. Dip switch (SWA1) function setting are as follows:
1 2 3 4 5 6 7 8
OTFS OTFP OTFGT OTFGS SEL1 SEL2 D/Y
(1) OTFS (Rectifier heatsink over temperature): When switch on, disable ove
temperature function.
(2) OTFP (Static switch heatsink over temperature): When switch on, disable ovetemperature function.
(3) OTGT (Inverter heatsink over temperature, T phase): When switch on, disable ove
temperature function.
(4) OTGS (Inverter heatsink over temperature, S phase): When switch on, disable ove
temperature function.
(5) SEL1 and SEL2 are used to set Boost charge time, as following table:
SEL1 SEL2 HRS
OFF OFF 4
OFF ON 8
ON OFF 16
ON ON 32
(6) D/Y : If AC input is Y connection, setting the dip switch to ON, and if Dconnectio
setting to OFF.
2-1
-
8/10/2019 T Service Manual
17/65
f. If the UPS loading is greater than 70%, the CPU will send control signal to B board focooling fan speed control.
g. Press SWA2 push button switch that will reset BOOST CHARGE function, if the rectifier i
in boost charge mode.
B. Test and adjustment
a. VRA1-----Amplitude adjustment of the triangle wave(6V).
b. VRA2-----Amplitude adjustment of the reserve AC source(2.5V).
c. VRA3----- phase-lock adjustment of the reserve AC source frequency.
d. TPA2,3---The 30 kHz constant frequency square waves are transmitted to B and T board
for switching signals.
e. TPA4,5---Reserve AC source frequency (square wave) and amplitude test points.
f. TPA6,7---Triangle wave signals test points, TPA6 and TPA7 are 180 phase shift.
C. Troubleshooting:
a. Confirm that CPU board and EPROM are inserted in right direction.
b. Confirm that three-phase sine reference signals are normal.
c. Confirm that amplitude and frequency of triangle wave are normal.d. Confirm that dip switch setting is correct.
e. Confirm that +16VA, +12VA, +5VA and all wire connections are correct.
2-2
-
8/10/2019 T Service Manual
18/65
-
8/10/2019 T Service Manual
19/65
2.2 B Board (Power Supply Board)
A. Function:
a. Transfer AC main power from 200 VA transformer or DC bus voltage into 16VA, 16VB
and +8VR, for the usage of other PCB.
b. Battery ground fault detection.
c. Control relay to drive cooling fan in high or low speed operation.d. Battery charge current limitation.
e. High DC bus voltage detection.
f. Battery current sensing.
B. Test and adjustment:
a. VRB1-----Adjustment of the battery charge current limitation. The following are the prese
values.
KVA 10 15 20 30 40 50 60 80 100 120 150
A 3 5 7 10 14 17 20 22 25 30 36
b. VRB2----- Adjustment of the High DC shutdown voltage level.
c. TPB2,3---PWM drive signals for DC/DC converter, TPB2 and TPB3 are 180 phase shift.
C. Troubleshooting:
a. Confirm that TPB2, TPB3 are 30 kHz square waves, and indicators LEDB2~LEDB5 are
emitted.
b. When UPS loading over 70% rated power, confirm that FAN signal from A board is set highand relay is close correctly.
c. After battery supplies power for a period of time and utility power is recovered, confirm tha
battery charge current within tolerance(< 0.2C).
d. Confirm that HIGH DC SHUTDOWN is set on correct level and function normally.
2-4
-
8/10/2019 T Service Manual
20/65
2.3 C Board (Rectifier Control Board)
A. Function:
a. Utility power low voltage level (-20%) detection.
b. Rectifier over current.
c. Shutdown protection of high DC bus voltage.d. Float charge and boost charge status setting.
e. Three-phase input power phase sequence detection.
f. Rectifier soft-start function.
g. 12-pulse rectifier configuration with rectifier output current sharing .
h. Battery temperature compensation and battery test function.
B. Test and adjustment
a. VRC1-----Adjustment of the utility power low voltage level.
b. VRC2-----Float charge voltage adjustment, when battery in floating(393Vdc), LEDC3 will b
lit.
c. VRC3-----Boost charge voltage adjustment, when battery in boost(405Vdc), LEDC4 will b
lit.
d. VRC4-----Level adjustment of rectifier over current protection.
e. VRC5-----Battery test rectifier output voltage adjustment, when battery in test mode, the
rectifier will output constant voltage (335Vdc), LED5 will be lit.
f. VRC6-----Battery temperature compensation voltage adjustment, If the battery temperatur
is grater than 35, the rectifier output voltage will be reduced 5V(i.e. 388V in floatin
charge).
g. TPC17(RECT INH)---When utility power and rectifier operation are normal, this detectio
point is low voltage level, the contrast is high and blocks rectifier.
h. TPC8~TPC13---SCR trigger signals, transmitted to rectifier drive board (S board).
i. TPC1~TPC3--- R, S, T phase sequence of the utility power.
j. TPC16 (DC E/A OUT)---DC error voltage output, control SCR fire angle.
C. Troubleshooting:
a. RECT MAINS FAIL:
(1) Confirm whether the utility power is normal or not. (Test point TPC17)
(2) Confirm whether the utility phase sequence is normal or not. (Test point TPC1~TPC3)
b. HIGH DC SHUTDOWN:
(1) Confirm whether the DC capacitors are correct or not.
(2) Confirm whether the HIGH DC SHUTDOWN adjustment (B board VRB22) is se
correctly or not.
(3) Confirm that rectifier over current protection is correct.
2-5
-
8/10/2019 T Service Manual
21/65
2-6
TPC3
R-SQ
TPC1
S-SQ
TPC2
T-SQ
TPC5
R-RAMP
TPC6
S-RAMP
TPC7
T-RAMP
-
8/10/2019 T Service Manual
22/65
2-7
TPC9
S-
TPC12
T+
TPC11
T-
TPC8
R+
TPC13
R-
TPC10
S+
-
8/10/2019 T Service Manual
23/65
2.4 E Board and AA Board (IGBT Snubber Board)
A. Function:
a. Suppress and absorb the transient voltage and current produced by IGBT switching.
b. Connected to E board when using single IGBT module, and AA board when using paralleIGBT.
B. Troubleshooting:
a. Confirm whether the capacitors are fluid leakage or destructive.
b. Confirm whether the diodes, resistors, and capacitors are normal or not.
2.5 G Board (Inverter Drive Board)
A. Function:
a. System automatic shutdown protection when IGBT is over temperature( heatsin
temperature greater than 70).
b. Isolate and amplify the PWM signals generated by T board to drive IGBT.
c. DC bus voltage level detection to determine the IGBT fuse fail.
B. Test and adjustment:
a. TPG1~4-----Inverter drive signal connected to terminals of IGBT module.
b. SW+, SW- -----Generated from A board, as the power source control signals for IGBT
driving.
C. Troubleshooting:
a. IGBT drive abnormal:
(1) Confirm that IGBTs and fuses are normal.
(2) Confirm that PWM waveforms are normal(TPG1 and TPG2 are 180phase shift, TPG
and TPG4 are 180phase shift.)
b. PWM waveform abnormal:(1) Confirm that PWM waveforms generated from T board are correct.
(2) Confirm power supply (SW+, SW-) generated from A board is correct.
2-8
-
8/10/2019 T Service Manual
24/65
2-9
TPG1PWM
TPG2
PWM
TPG1
PWM
TPG2
PWM
-
8/10/2019 T Service Manual
25/65
2.6 H Board (Alarm Switch Board)
A. Function:
a. LED displays 4 status of alarm signals for users reference.
b. Press SELECT key for LCD item inquiring.
c. Press ENTER key for confirmation.
B. Troubleshooting:
a. Confirm that LEDs are not destroyed and buttons are in good contact.
b. Confirm that connector are in good contact with lead.
2.7 J Board and M Board (MOV Board)
A. Function:
a. Absorb high voltage surge from input terminal of the UPS.b. When input power is Dconnection using J board, and when Y connection using M Board.
B. Troubleshooting:
a. Confirm that the wiring is in good contact and tighten adequately.
b. Confirm that MOV is not destroyed and choosing the correct MOV type.
2.8 L Board (System LED Board)
A. Function:
a. Transfer twelveUPS status into system diagram and four LEDs driving signals.
b. Transfer R board series in signals into parallel out signals by IC 74HC164 to drive LEDs.
c. When pressing ON & CTRL key simultaneously, there is +5V voltage between them (INV
ON).
d. When pressing OFF & CTRL key simultaneously, there is +5V voltage between them
(INV OFF).
B. Troubleshooting:a.Confirm that LEDs are not destroyed and buttons are in good contact.
b.Confirm that +5V power supply and IC 74H164 whether they are correct or no
destroyed.
c.If the LEDS are all lit, confirm that R board or EPROM on CPU board are correct.
2-10
-
8/10/2019 T Service Manual
26/65
2.9 N Board (Remote Panel Board) and Y Board (Switch Board)
A. Function:
a. Communicated with UPS for remote monitoring.
b. Monitoring three sets of UPS at same time via RS485 interface.c. With 120V or 220V receptacles depends on UPS output.
d. By communication, user can set inverter ON/OFF and alarm ON/OFF.
e. Power supply:
(1) +12V: Supplied to buzzer and LCD CCF.
(2) -5V: Supplied to CPU board and RS485 Interface.
(3) -12V: Supplied to LCD bias (contrast adjustment).
f. The dip switch SWN1 setting is the same as SWR1 on R board, according to the input
output voltage and KVA rating.
B. Troubleshooting:
a. Confirm whether the power supply and signals are normal or not.
b. Confirm whether the LCD and push button are normal or not.
2.10 P Board (Static Switch Board)
A. Function:
a. Generate SCR trigger signals for static switch transferring between Reserve and Inverte
mode.
b. Inverter output voltage abnormal detection. If the UPS output voltage is over or under 20%
of nominal voltage, the SSOP fault signal will be generated and sent to A board.
B. Test and adjustment:
a. VRP1, TPP3-----High voltage level adjustment of inverter output.
b. VRP2, TPP2-----Low voltage level adjustment of inverter output. The following are th
different nominal output voltage and VRP1, VRP2 preset values.Nominal voltage 380/220 400/230 415/240
TPP3 5.1V 5.3V 5.6V
TPP2 2.7V 2.9V 3.0V
c. TPP4---------------When transfer signal (transmitted from A board) is from low going to
high level, it means UPS is transferred from Reserve mode to Inverter
mode, at the same time.
2-11
-
8/10/2019 T Service Manual
27/65
C. Troubleshooting:
a. Confirm that all wire terminals and static switches are connected correctly.
b. Confirm whether VRP1 and VRP2 are adjusted correctly(When Inverter output voltage i
abnormal, SSOP signal is low level).
c. Confirm that reserve and inverter SCR, only one set is triggered at any time.
2-12
ZDP5
(+)
ZDP3
(+)
-
8/10/2019 T Service Manual
28/65
2.11 Q Board (Dry Contact Board)
A. Function:
Generate four sets of dry contact signals output as follows:
a. Load on inverter (P1,P2 are closed at that time).
b. Load on reserve(P3,P4 are closed at that time).c. Warning Message ( RES MAINS FAIL, RES FREQ ABNORMAL, RECT MAINS
FAIL, BATT LOW,INV OVERLOAD, BATT LOW STOP, Load on bypass) (P5,P6 ar
closed at that time).
d. Fault Messages ( RECT HI DC STOP, OVERTEMP/FUSE FAULT, BATT GND
FAULT, INV FAULT) (P7,P8 are closed at that time).
B. Troubleshooting:
a. Confirm that +12V power supply and relay are normal.
b. Confirm that signals transmitted from R board are all normal.
2.12 R Board (Display Board)
A. Function:
a. Transfer the signals from A board into twelve UPS status for LED display, and to fron
panel for users reference.
b. Display the Input / Output voltage, current, and frequency, battery voltage and curren
and loading percentage, by feedback voltage and current signals to CPU.
c. Provide RS485 interface.
d. The power supply of LCD lamp is provided from R board INVR1 (DC/AC
12V30KHz/250V), and the character contrast is controlled by -12.6V supply.
e. According to Input / Output voltage and KVA rating, the dip switch SWR1 must be set a
follows:
SWR1-1 SWR1-2 I / P Voltage O / P Voltage
ON ON 3f4W 3f4W
OFF ON 1f3W 1f3W
ON OFF 3f4W 1f2W
OFF OFF
2-13
-
8/10/2019 T Service Manual
29/65
SWR1-3 SWR1-4 KVA-1 KVA-2 KVA-3 KVA-4
ON ON 5 30 70 120
OFF ON 10 40 80 150
ON OFF 15 50 90
OFF OFF 20 60 100
f. The 12 LEDs on R board (from left to right), status explanations are as follows:
(1) RECT MAINS FAIL: When utility power is under voltage (less than 20% rating), th
LED will be lit.
(2) RECT HI DC STOP: When DC bus voltage is too high, the LED will be lit.
(3) OVERTEMP/FUSE FAIL: When the heatsink is over temperature or fuse fail, the LED
will be lit.
(4) BATT LOW/STOP: When UPS in back-up mode and DC bus voltage below 330V, th
LED will flash, and when DC bus voltage below 300V, the LED will be lit.
(5) LOAD LEVEL: When UPS in normal mode, the LED will flash, and the flashing ratdepends on loading percentage.
(6) BATT GND FAULT: When the battery is shorted with ground, the LED will be lit.
(7) INV ON: When the load is supply by inverter output, the LED will be lit.
(8) INV OVERLOAD: When UPS is loaded over rated capacity, the LED will be lit.
(9) INV FAULT: When Inverter is abnormal, the LED will be lit.
(10) LOAD ON RES: When the load is supplied by reserve source, the LED will be lit.
(11) RES MAINS FAIL: When the voltage amplitude of reserve input is abnormal, the LED
will be lit.
(12) RES FREQ ABNORMAL: When the frequency of reserve input is abnormal, the LE
will be lit.
A. Test and adjustment:
a. VRR1~VRR3------Adjustment LCD display of output current.
b. VRR5----------------Adjustment LCD display of battery voltage.
c. VRR6~VRR11----Adjustment LCD display of input / output voltage.
d. VRR7~VRR14----Adjustment LCD display of input current (optional).
e. VRR15-------------- Adjustment LCD display of battery charge current.f. VRR16-------------- Adjustment LCD display of battery discharge current.
B. Troubleshooting:
a. Confirm that all signals and power lines are correctly connected with R board.
b. Confirm that CPU board is inserted correctly, and the EPROM is function correct.
c. Confirm that all LEDs status display normally.
2-14
-
8/10/2019 T Service Manual
30/65
2.13 S Board (Rectifier Drive Board)
A. Function:
a. Transmitting trigger signals generated from C board through isolation pulse transformer t
trigger thyristors.
b. When SCRs are switching, Snubber will absorb and suppress transient surge to protecfrom destroyed.
B. Troubleshooting:
a. Confirm that SCRs are normal.
b. Confirm that all connectors and wiring are connected properly.
c. Confirm that trigger signals transmitted from C board are correct.
d. Check pulse transformers and Zener diodes are normal.
e. Check components of the Snubber(resistors and capacitors) are not burnout.
2.14 T Board (Inverter Phase Board)
A. Function:
a. Short circuit protection of inverter output.
b. Feedback UPS output voltage to generate error voltage and error sine-wave signal.
c. Compare the error sine-wave signal and triangle wave to generate PWM trigger signal
that will be transmitted to G board to drive IGBT.
B. Test and adjustment:
a. VRT1-------Adjustment of output voltage amplitude.
b. VRT2-------Adjustment inverter over current protection level.
c. TPT5-------Feedback O/P current signals and compared with over current protecting
point (setting by VRT2), to generate output short circuit signals transmitted
to A board.
d. TPT7,8-----When UPS is single phase output, TPT7 and TPT8 are the detecting point
of current feedback signals on the secondary and primary of the outputtransformer for DC offset compensation to prevent transformer saturation.
TPT7 and TPT13 (DSINE) must be the same phase, TPT8 and TPT13 ant
phase .
2-15
-
8/10/2019 T Service Manual
31/65
e. TPT23,24---Triangle signals transmitted from A board, TPT23 and TPT24 are 180
phase shift.
f. TPT15~22---PWM trigger signals transmitted to G board for triggering IGBT,TPT15
and TPT16, TPT17 and TPT18,TPT19 and TPT20,TPT21 and TPT22 are
anti-phase.
C. Troubleshooting:
a. Over current protection abnormal:
(1). Confirm that detecting CT for protection is connected correctly.
(2). Confirm that O/P transformer and Inverter Choke both are not saturated.
(3). Confirm that VRT2 setting level for over current protection is correct.
b. PWM waveform abnormal:
(1). Confirm that triangle and error sine wave are correct.
(2). Confirm INV ON signal is normal.
(3). Confirm the dead time setting is correct. (Check the component specifications o
DT18~21, RT95~98, and CT4~7 are correct.)
2-16
TPT22
S1
TPT20
S2
-
8/10/2019 T Service Manual
32/65
2-17
TPT22
S1
TPT20
S2
TPT13
DSINE
TPT14
ERROR
VOLTAGE
-
8/10/2019 T Service Manual
33/65
2-18
TPT3
INVFB
TPT4
SINE
TPT3INVFB
TPT4
SINE
-
8/10/2019 T Service Manual
34/65
-
8/10/2019 T Service Manual
35/65
-
8/10/2019 T Service Manual
36/65
-
8/10/2019 T Service Manual
37/65
D
transfer to INV
false
false
?
false
?
false?
false
?
KEY
?
No
No
No
No
SOPFAULT
Yes
SCFAULT
Yes
OTFAULT
Yes
HIDCFAULT
Yes
OFFAULT
Yes
F
E
No
3-3
-
8/10/2019 T Service Manual
38/65
F
check
check
reset key
check
time check
check
BATFAULT
Main Loop
OVLFAULT
Check overload %
Time out
?
No
No
Yes
Yes
3-4
-
8/10/2019 T Service Manual
39/65
SOPFAULT
false
SINEWAVE O/P OFF
false
false
?
Transfer to RES
Ture
?
Transfer to RES
Ture
wait 7 sec
SINEWAVE O/P ON
No
Yes
Yes
No
RE-START
3-5
-
8/10/2019 T Service Manual
40/65
-
8/10/2019 T Service Manual
41/65
OTFAULT
false
SINEWAVE O/P OFF
false false
?
Transfer to RES
Ture
?
Transfer to RES
Ture
wait 20 sec
SINEWAVE O/P ON
No
Yes
disappear
?No
Yes
No
LED ON
Yes
RE-START
3-7
-
8/10/2019 T Service Manual
42/65
-
8/10/2019 T Service Manual
43/65
OFFAULT
false
SINEWAVE O/P OFF
false
false
?
Transfer to RES
Ture
KEY
?
UPS on mode
SINEWAVE O/P ON
Yes
NoNo
KEY
?
No
Yes
UPS on normal mode
RE-START
Yes
3-9
-
8/10/2019 T Service Manual
44/65
-
8/10/2019 T Service Manual
45/65
OVLFAULT
false
SINEWAVE O/P OFF
false
false
?
Transfer to RES
Ture
?
Transfer to RES
Ture
wait 20 sec
SINEWAVE O/P ON
No
Yes
?
Yes
No
RE-START
Yes
No
OFFAULT
cancel
re-start
?
No
Yes
3-11
-
8/10/2019 T Service Manual
46/65
3.2 Flow Chart for System Display
START
INITIALI/O_PIN
ALLSYS_LED=
TESTLCM:DELTA
ALLSYS_LED=
/TESTLCM:Sys. Diag.
MAIN
INITIAL RAM
SET_UPRS232/TIMER
INT1/EI
CALLINI_LCM
OR MODE
GRAPHIC ON
SET CURSOR
GRAPHAREA
HOMEADDRESS
DATA AUTOWRITE MODE
INI_LCM
RET
3-12
-
8/10/2019 T Service Manual
47/65
MAIN
CALL
INI_LCM
CALL
STSLED
STSLCM
READ
UPS
STATUS
KEYNM>9
CLEAR
MAIN
Measure
TRUE_POWER
Vrms X Irms
UPDATE
R/S/T_V R/S/T_i
VRMS
CLEAR
SQUARE
BUFFER
RMSVI
RET
CALL
RMSVI
LCM
DISPLAY
3-13
-
8/10/2019 T Service Manual
48/65
TIMER/500us
INTERRUPT
ENT RY SCAN MODERD AN0-3 ->
BUFCR0_3
4502 AN_SW
AV ERAG EBAT_V,BAT_i
4502 AN_SW
SQ R/S/T_V,i
SQ R-S-T_V
MEM V n, In
4502 AN_SW
SCANED
UP/DO WN_ K
TIM:20MS
LEDSIO
BUZZER
TIME:2SEC
TIME_OUT->
RS232/CHK_S
CALL
UART _ T RX
RET I
R ET
INTTM1
UART_TRX
txbgn.f
FSR.f
PASER
RX_BUF
error
IN C
TRX_INDEX
CLEAR
CHECK_SUM
TRX_INDEX
SETUP
TX_FRAME
TXBGN.F
TRX_INDEX
BUF.FULL
NO YES
R ET R ET
R ETYE S
FST.f
NO
NO
UART X
UART X
R ET
PASER
TRX_INDEX
EN D
NO
YE S
TXB
-
8/10/2019 T Service Manual
49/65
INT1
AC_SYNC
I_FREQ =
N_FC - O_FC
UPDATE->
O_FC=N_FC
I_FREQ
? =
F_BUF
FREQCT = 0
UPDATE
AC_CYC
INC.
FREQCT
FREQCT
> 5
CLEAR
FREQCT
F_BUF=I_FREQ
RETI
RETI
YES
NO
YES
NO
3-15
-
8/10/2019 T Service Manual
50/65
4. Troubleshooting
4.1 Test Procedures of The System
1. Check PCB all connectors are connected correctly and the right wiring.
2. Check all Breakers in OFF position and make sure the correct input power (Dtype U, V, Wor Y type R, S, T, N) by meter, when UPS is connected to power and battery cabinet.
3. Check all screws of the UPS are tightened.
4. Turn on BYPASS breaker and then measure PCB power supply.
5. If LEDA1 and LEDA2 on A board are lit that represents 12V in normal function. If LEDB2
LEDB3, LEDB4, and LEDB5 on B board are lit that represents 16V in normal function
Measure TPB12 and TPB13 on B board whether 8V is normal or not. If LEDC1 an
LEDC2 on C board, LEDT1 and LEDT2 on T board are all lit, that represents 12V in norma
function.
6. Turn A board dip switch (DSWA1) and R board dip switch (DSWR1) into moderate position.
7. Triangular amplitude adjustment: Turn on BYPASS breaker, and connect CH1 and CH
with oscilloscope probes to A board TPA6 and TPA7. Adjust varistor (VRA1) to make th
amplitude of triangular waveform to 6V, and check its frequency whether equals to 7.8KHzand TPA6, TPA7 with 180 phase shift.
4-1
-
8/10/2019 T Service Manual
51/65
8. High-low limit adjustment of INV output voltage: Turn on BYPASS breaker, then adjust th
varistor (VRP2) to make TPP2 (Low Ref.) to 2.5V and adjust the VRP3 to make TPP3 (High
Ref.) to 4.5V.
9. Driving signal test of power board: Turn on BYPASS breaker, and connect CH1 and CH
with oscilloscope probes to B board TPB2 and TPB3. Check the amplitude of squar
waveform equals to +12V, frequency to 30 kHz, TPB2 and TPB3 with 180 phase shift.
10. Test of reference sine wave: Turn on BYPASS breaker, then press ON and OFF buttons o
the front panel simultaneously. Check reference sine wave signals (top of RA70-R phase
top of RA68-S phase, top of RA69-T phase) are 120 phase shift.
11. Test of IGBT driving signals: Turn on BYPASS breaker, then press ON and OFF button
simultaneously. Check the amplitudes of PWM waveform on G board (S1, S2), (S1, S2
(S3, S4), and (S3, S4) are +14V/-5V, and the dead time is about 3.5 ~ 5 us.
4-2
-
8/10/2019 T Service Manual
52/65
12. Adjustment of reserve input detection: Turn on BYPASS and RESERVE breakers, the
connect CH1 of oscilloscope probe to TPA5 and adjust varistor VRA2 to the amplitude abou
2.3~2.5V.
13. Test of rectifier driving signals: Pull out CNC4 connector on C board, turn off BYPASS an
RECT breakers, and connect CH1 and CH2 with oscilloscope probes to TPC8/TPC13
TPC9/TPC10, TPC11/TPC12. Check whether TPC8 and TPC13, TPC9 and TPC10, TPC1
and TPC12 are 180 phase shift.
14. Adjustment of DC bus voltage: Connect back the CNC4 connector on C board, adjust VRC
clockwise to end, and turn on BYPASS and RECT breakers, the LEDC3 on C board will be l
Adjust VRC2 counterclockwise slowly until the DC bus voltage equals to 393V. Then, tur
off RECT breaker waiting for DC bus voltage down to zero.
15. Adjustment of HIGH DC SHUTDOWN voltage: Turn on BYPASS and RECT breakerwaiting until DC bus voltage reaches 393V. Adjust VRC2 counterclockwise till DC bu
voltage equals to 415V. Then, adjust VRB2 on B board clockwise until buzzer is beep, an
HI DC SHUTDOWN LED on R board is lit at the same time. Finally, adjust DC bus voltag
back to 393V.
4-3
-
8/10/2019 T Service Manual
53/65
16. Adjustment of BOOST CHARGE voltage: Turn on BYPASS and RECT breakers waitin
until DC bus voltage attains to 393V, and short C board JPC3 with short pin, then LEDC4 wi
be lit at that time. Adjust VRC3 until DC bus voltage reaches 405V, then take out short pin
and DC bus voltage will down to 393V automatically.
17. INV ON test: Turn on BYPASS and RECT breakers until DC BUS voltage is about 30V~40Vthen turn off RECT breaker. Connect CH1 and CH2 with oscilloscope probes to T boar
TPT3 and TPT4, then press ON and OFF buttons simultaneously and check the waveform
should be anti-phase.
18. INV ON test: Turn on BYPASS and RECT breakers, then adjust VRC2 until DC bus voltag
attains to 393V. Connect CH1 and CH2 with oscilloscope probes to T board TPT3 an
TPT4, press ON and OFF buttons simultaneously. Using voltage meter to check the
phase output voltage whether they are coincidence with the specifications or not. If no
adjust VRT1 on T board to meet the specifications.
19. Phase-lock adjustment: Turn on BYPASS and RECT breakers until DC bus voltage attain
to 393V, then turn on RESERVE and O/P breakers, turn off BYPASS breaker, press ON an
OFF buttons simultaneously (the above procedures means transferring UPS to INV outpu
mode). Connect CH1 and CH2 with oscilloscope probes to static switch SCR, then chec
reserve power and INV output whether they are phase-lock or not. If no, adjust A boar
VRA3 till phase-lock.
4-4
-
8/10/2019 T Service Manual
54/65
20. Adjustment of the LCD display: Transfer UPS to INV output mode, adjust VRR5~VRR11 o
R board for the LCD display of I/P, O/P, and DC bus voltage and current to meet the actua
value.
21. Adjustment of 200% Ipeak protection level: Connect CH1 with an oscilloscope probe to T
board TPT5, take on resistive load and check whether there is an waveform on the scope
If yes, change to computer load, and adjust T board VRT2 counter-clockwise to 200% Ipea
protection point.
4-5
-
8/10/2019 T Service Manual
55/65
22. BATT GND FAULT test: Connect one terminal of wire to UPS GND, the other side to touc
with battery terminal, then R board LEDR6 will be lit, and alarm will beep.
23. High-low transfer voltage test: Transfer UPS to INV output mode, connect battery cabine
and shut off AC input power. Then, using autotransformer to change AC input voltage tUPS, adjust C board VRC1 for rectifier input low-level transfer point (nominal voltage -15%)
and VRP1, VRP2 on P board for reserve input high-level and low-level transfer poin
(nominal voltage 20%).
24. OVERTEMP/FUSE FAULT test: Transfer UPS to INV output mode, pull out CNP
connector on P board or CNG6 connector on G board, the alarm will beep and LEDR3 on R
board will be lit at that time.
25. Cooling fan test: Transfer UPS to INV output mode and take on 70% loading. Check th
cooling fan whether rotate faster or not.
26. Overload test: Transfer UPS to INV output mode and take on 110% loading. The R boar
LEDR8 will be lit and buzzer will beep at the same time. 15 minutes later, INV output mod
will be transferred to RES output mode automatically and INV OVERLOAD LED on R board
will be lit. If take off the over loading, after 20 seconds, RES mode will be transferred bac
to INV mode again automatically.
27. 125% overload test: The test procedures are similar to Item 26, but the loading leve
changes to 125% and overload time to 5 minutes.
28. 150% overload test: The test procedure are similar to Item 26, but the loading leve
changes to 150% and overload time to 30 seconds.
29. BATT LOW & BATT LOW STOP test: Transfer UPS to INV output mode, connect batter
cabinet, take on nominal load, and shut off AC input power. When DC bus voltage goe
down to 330V, the LEDR4 on R board will flash and buzzer will beep faster. When DC bu
voltage goes down to 300V, LEDR4 will be lit and shutdown UPS.
30. Adjustment of the battery charge current: Continuously from Item 29 last step, turn on th
AC input power to UPS and connect current probe to battery + terminal, then adjust B boar
VRB3 for battery charge current (< 0.2C).
4-6
-
8/10/2019 T Service Manual
56/65
-
8/10/2019 T Service Manual
57/65
2. RESERVE FREQUENCY ABNORMAL
R
board
LED12
lit
Rboard
RESMAINSFF
="LO"(RR26)
Aboard
RESS-W
(TPA4)OK
RESFreq.
OK
CheckRESI/P
&50/60Hzsetting
END
ReplaceRboard
ReplaceCPUboard
onAboard
ReplaceAboard
NO
NO
NO
YES
YES
YES
4-8
-
8/10/2019 T Service Manual
58/65
3. RESERVE MAINS FAIL
RboardLEDR11lit
Rboard
RESMAINSFF
="LO"(UR31.1)
Aboard
RESMAG
=2.3~2.5V
(TPA5)
AboardRESvoltage
detect
OK
CheckUPSwiring
END
ReplaceRboard
Replace
CPU board
onAboard
Aboard
RES amplitude
settingOK
Adjust
A
board
VRA2
ReplaceAboard
NO
NO
NO
YES
YES
YES
NO
YES
4-9
-
8/10/2019 T Service Manual
59/65
4. INVERTER FAULT
R board LEDR9 lit
R board
INV SC="HI"
(UR31.5)
A board
SCR,SCS,SCT
= "HI"
Ipeak level
setting OK
(TPT6)
Check Ipeak CT OK
END
Replace R board
Replace A board
Adjust T board
VRT2
NO
NO
Yes
No
YES
YES
4-10
-
8/10/2019 T Service Manual
60/65
5.INVERTER OVERLOAD
R board LEDR8 lit
R boardINV OL= "LO"
(UR31.6)
A board
LOAD(CNA6.20)Freq. OK
R boardPIOBL(UR30.2)
Freq. OK
Overload
CT OK
Check UPS wiring
END
Replace R board
Replace CPU boardon A board
Replace A board
Replace R board
NO
NO
NO
NO
YES
YES
YES
YES
4-11
-
8/10/2019 T Service Manual
61/65
6. BATTERY GROUND FAULT
R board LEDR6 lit
R board
BGF= "LO"
(UR32.2)
BATT wiring
correct
Correct BATT Wiring& replace bad BATT
END
Replace R board
Replace B board
NO
NO
YES
YES
4-12
-
8/10/2019 T Service Manual
62/65
7. BATTERY LOW / STOP
R board LEDR5 lit
Replace R board
R board
PIOSD="LO"
(UR31.1)
DC BUS 330V
Replace C board& check RECT SCR
END
Replace CPU board
on R board
NO
NO
YES
YES
4-13
-
8/10/2019 T Service Manual
63/65
8888.... OVERTEMPERATURE / FUSE FAIL
R board LEDR3 lit
R board
OTF ="LO"
(UR31.3)
A board
OTFG,OTFP,
OTFS= "LO"
Check thermal switchon heatsink
END
Replace R board
Replace A board
NO
NO
YES
YES
4-14
-
8/10/2019 T Service Manual
64/65
9. RECTIFIER HIGH DC STOP
RboardLEDR2lit
Rboard
HDCSDR="LO"
(UR32.1)
DCBUS415V
Cboard
TPC8.9.10,11,
12.13OK
ReplaceCboard
CheckRECTSCR
wiring
ReplaceRboard
END
ReplaceBboard
Bboard
VRB2setting
correct
AdjustBboardVRB2
NO
NO
NO
YES
YES
YES
NO
YES
4-15
-
8/10/2019 T Service Manual
65/65
10. RECTIFIER MAINS FAIL
R board LEDR1 lit
R board
RMF= "LO"(UR31.4)
A boardRMF5= "LO"(CNA46.22)
C board
(TPC1~TPC3)OK
Check I/P powerphase & wiring
END
C board VRC1
setting OK
Replace Rboard
Replace A
board
Adjust C board VRC1
Replace C
board
NO
NO
NO NO
YES YES
YES
YES