T Service Manual

download T Service Manual

of 65

Transcript of T Service Manual

  • 8/10/2019 T Service Manual

    1/65

  • 8/10/2019 T Service Manual

    2/65

  • 8/10/2019 T Service Manual

    3/65

  • 8/10/2019 T Service Manual

    4/65

    1.2 Operation Instructions

    1.2.1 System Start-up Procedure

    Please check the following noticed items before UPS start-up:

    1. All circuit breakers and isolators are in OFF position and battery fuse is out.

    2. Ensure that neutral line and grounding are the same voltage level.

    3. Apply power to the AC input cables and check that input voltage, frequency and

    phase order are with in the machine specifications.

    When UPS comply with the above mentioned conditions, start-up UPS according to the

    following procedures:

    1. Close MANUAL BYPASS breaker, at the same time LCD display LOAD ON

    BYPASS .

    2. Close AC INPUT and RECTIFIER INPUT breakerwait 1520 seconds until

    BATT LOW LED behind the door is off.

    3. Close RESERVED INPUT breaker, at the same time LCD display LOAD ON

    RESERVE .

    4. Close UPS OUTPUT breaker.

    5. Open MANUAL BYPASS breaker.

    6. Close BATTERY FUSE ISOLATOR in battery cabinet.

    7. Press the inverter ON & button simultaneously, the load will be transferred

    from reserve to inverter automatically, at the same time LCD display LOAD ON

    INVERTER .

    Note: It must never turn on manual bypass circuit breaker when the

    inverter is turned on. It will damage the UPS owing to utility power

    parallel with inverter output.

    1.2.2 Maintenance Manual Bypass Procedure

    This procedures leave the critical load undisturbed and the UPS batteries will still be

    charged. The operating procedures are as follows:

    1-2

  • 8/10/2019 T Service Manual

    5/65

    1. Check MAIN FREQ ABNORMAL RES MAINS FAIL LEDS behind the door are

    all off.

    2. Press inverter OFF & button simultaneously. Check that INV ON LED

    behind the door is off.

    3. Close MANUAL BYPASS breaker.

    4. Open UPS OUTPUT breaker.

    5. Open RESERVE INPUT breaker.

    1.2.3 Return from Bypass to Normal Mode

    This operating procedures will transfer load from bypass to normal mode as follows:

    1. Check that INV ON LED behind the door is off.

    2. Close RESERVE INPUT breaker.

    3. Close UPS OUTPUT breaker.4. Open MANUAL BYPASS breaker.

    5. Press the inverter ON & button simultaneously.

    6. The load will be transferred from reserve to inverter automatically.

    1.2.4 System Shutdown Procedure

    This operating procedure can turn off power supply to UPS, please first confirm the load

    has been shutdown, the procedures as follows

    1. Press inverter OFF & button simultaneouslyCheck that INV ON LED

    behind the door is off.

    2. Close MANUAL BYPASS breaker.

    3. Open BATTERY FUSE ISOLATOR in battery cabinet.

    4. Open RECTIFIER INPUT breaker.

    5. Open RESERVE INPUT breaker.

    6. Open UPS OUTPUT breaker.

    7. Wait 5 mins for DC CAP to discharge.

    8. Open AC INPUT & MANUAL BYPASS breaker.

    1-3

  • 8/10/2019 T Service Manual

    6/65

    1.3 Technical Specifications

    1.3.1 Rectif ier Input Characterist ics

    (a) 380/220 Input

    3 input3 output 3 input1 output

    Power rating KVA (P.F.0.8) 10 15 20 30 40 50 60 80 100 120 150 10 15 20 30 40 50

    (1) Nominal voltage V 220/380() 220/380()

    (2) Voltage range % 20 20

    (3) Nominal frequency Hz 50 / 60 50 / 60

    (4) Frequency range % 5 5

    (5) Nominal input power

    (with charged battery)KVA Power rating120% Power rating120%

    (6) Input power factor cosq 0.7 0.7

    (7) Maximum input power

    (with battery under charge)KVA Power rating 135% Power rating 135%

    (8) Range input current A 18 28 37 55 73 90 108 144 180 215 270 18 28 37 55 73 90

    (9) Maximum input current A 26 39 52 78 103 127 152 203 253 304 376 26 39 52 78 103 127

    (10) Start-up time sec 20 20

    (11) Efficiency % 96 96

    1-4

    Item Spec.

  • 8/10/2019 T Service Manual

    7/65

    (b) 208/120 Input

    3 input3 output 3 input1 output

    Power rating KVA (P.F.0.8) 10 15 20 30 40 50 60 80 100 120 150 10 15 20 30 40 50

    1) Nominal voltage V 208/120() 208/120()

    2) Voltage range % 15 15

    3) Nominal frequency Hz 50 / 60 50 / 60

    4) Frequency range % 5 5

    5) Nominal input power

    (with charged battery)KVA Power rating120% Power rating120%

    6) Input power factor cosq 0.7 0.7

    7) Maximum input power

    (with battery undercharge)

    KVA Power rating 135% Power rating 135%

    8) Range input current A 33 51 68 101 134 165 198 264 330 394 495 33 51 68 101 134 165

    9) Maximum input current A 48 72 95 143 189 233 279 372 464 557 689 48 72 95 143 189 233

    10) Start-up time sec 20 20

    11) Efficiency % 96 96

    () The different voltage specification is available.

    1-5

    Item Spec.

  • 8/10/2019 T Service Manual

    8/65

    1.3.2 Rectif ier Output Characteristics

    3 input3 output 3 input1 output

    Power rating KVA (P.F.0.8) 10 15 20 30 40 50 60 80 100 120 150 10 15 20 30 40 50

    (1) DC voltage range V 300420 300420

    (2) Output voltage

    (with Ni-Cd battery)

    ---float charge V 393 393

    ---boost charge V 415 415

    (3) output voltage (with

    sealed lead acid battery)

    ---float charge V 393 393

    ---boost charge V 405 405

    (4) Voltage stability

    (for input voltage and

    output current change

    simultaneously)

    % 1 1

    (5) DC voltage ripple

    (Vrms/Vb100)% 2 2

    (6) Nominal current Adc 22 34 45 67 89 110 131 175 219 263 324 22 34 45 67 89 110

    (7) Maximum output current Adc 32 47 63 95 126 155 185 247 309 371 459 32 47 63 95 126 155

    (8) Maximum charge current Adc 7 10 13 19 25 31 37 49 62 74 92 7 10 13 19 25 31

    (9) Adjustable charging

    current

    Yes Yes

    (10) Battery charging system DIN 41773 DIN 41773

    1-6

    ItemSpec.

  • 8/10/2019 T Service Manual

    9/65

  • 8/10/2019 T Service Manual

    10/65

    1.3.5 Inverter Output Characteristics

    (a) 380/220 Output

    3 input3 output 3 input1 output

    Power rating KVA (P.F.0.8) 10 15 20 30 40 50 60 80 100 120 150 10 15 20 30 40 50

    (1) Nominal voltage V 220/380() 220()

    (2) Nominal current A 15 23 30 45 61 76 91 121 152 182 227 45 68 91 136 182 227

    (3) Nominal voltage

    adjustment range

    % 10 10

    (4) Waveform Sinusoid Sinusoid

    (5) T.H.D.(with linear load) % 3 3

    (6) Output voltage

    regulation (for input

    voltage and output loadchange simultaneously)

    % 1 1

    (7) Output voltage dynamic

    regulation for 0100%

    load variations% 5 5

    (8) Voltage symmetry with

    balanced load

    % 1 1

    (9) Voltage symmetry with

    100% unbalanced load % 1 1

    (10) Displacement angle

    between three phases1203 NA

    (11) Output frequency Hz 50 / 60 50 / 60

    (12) Phase lock range Hz 3 3

    (13) Frequency stability

    with internal oscillator

    with mains synchronize

    %

    %

    0.01

    1

    0.01

    1

    (14) Overload

    110%15 minutes

    125%10minutes

    150%1minutes200%

    110%15 minutes

    125%10minutes

    150%1minutes200%

    (15) Inverter efficiency % 88 90 91 92 93 94 94 94 94 94 94 88 90 91 92 93 94

    () The different voltage specification is available.

    1-8

    ItemSpec.

  • 8/10/2019 T Service Manual

    11/65

    (b) 208/120 Output

    3 input3 output 3 input1 output

    Power rating KVA (P.F.0.8) 10 15 20 30 40 50 60 80 100 120 150 10 15 20 30 40 50

    1) Nominal voltage V208/120(

    ) 110(

    )

    2) Nominal current A 28 42 55 83 112 139 167 222 279 334 417 91 136 182 273 364 455

    3) Nominal voltage

    adjustment range

    % 10 10

    4) Waveform Sinusoid Sinusoid

    5) T.H.D.(with linear load) % 3 3

    6) Output voltage regulation

    (for input voltage and

    output load change

    simultaneously)

    % 1 1

    7) Output voltage dynamic

    regulation for 0100%

    load variations% 5 5

    8) Voltage symmetry with

    balanced load

    % 1 1

    9) Voltage symmetry with

    100% unbalanced load % 1 1

    10) Displacement angle

    between three phases1203 NA

    11) Output frequency Hz 50 / 60 50 / 60

    12) Phase lock range Hz 3 3

    13) Frequency stability

    - with internal oscillator

    - with mains

    synchronize

    %

    %

    0.01

    1

    0.01

    1

    14) Overload

    110%15 minutes

    125%10minutes

    150%1minutes200%

    110%15 minutes

    125%10minutes

    150%1minutes200%

    15) Inverter efficiency % 86 87 88 89 90 90 90 91 91 91 91 87 88 89 90 91 91

    () The different voltage specification is available.

    1-9

    ItemSpec.

  • 8/10/2019 T Service Manual

    12/65

    1.3.6 Static Switch Input / Output Characteristics

    (a) 380/220 Input / Output

    3 input3 output 3 input1 output

    Power rating KVA (P.F.0.8) 10 15 20 30 40 50 60 80 100 120 150 10 15 20 30 40 50

    (1) Input / Output voltage V 380 220

    (2) Input / Output frequency Hz 4565 4565

    (3) Overload current

    --- 30 minutes

    --- 10 seconds

    --- 30 milliseconds

    %

    %

    %

    120

    500

    1000

    120

    500

    1000

    (4) Maximum transfer time

    - From inverter to reserve

    (a) inverter failure

    (b) inverter overload or

    manual operation

    - From reserve to inverter

    manual operation or

    automatic return

    msec

    msec

    msec

    1

    0

    0

    1

    0

    0

    (5) Efficiency (at nominal

    load)

    % 99.5 99.5

    (6) High / Low AC voltage

    transfer rate

    % 20 20

    (7) Slew rate Hz / sec 1 1

    1-10

    ItemSpec.

  • 8/10/2019 T Service Manual

    13/65

    (b) 208/120 Input / Output

    3 input3 output 3 input1 output

    Power rating KVA (P.F.0.8) 10 15 20 30 40 50 60 80 100 120 150 10 15 20 30 40 50

    1) Input / Output voltage V 208 120

    2) Input / Output frequency Hz 4565 4565

    3) Overload current

    --- 30 minutes

    --- 10 seconds

    --- 30 milliseconds

    %

    %

    %

    120

    500

    1000

    120

    500

    1000

    4) Maximum transfer time

    - From inverter to reserve

    a) inverter failure

    b) inverter overload or

    manual operation

    - From reserve to inverter

    manual operation or

    automatic return

    msec

    msec

    msec

    1

    0

    0

    1

    0

    0

    5) Efficiency (at nominal

    load)

    % 99.5 99.5

    6) High / Low AC voltage

    transfer rate

    % 20 20

    7) slew rate Hz / sec 1 1

    1-11

    ItemSpec.

  • 8/10/2019 T Service Manual

    14/65

    1.3.7 General Specif icat ion

    (a) 380/220 Input / Output

    Item Spec. 3 input3 output 3 input1 o

    Power rating KVA (P.F.0.8) 10 15 20 30 40 50 60 80 100 120 150 10 15 20 30

    (1) ACAC efficiency

    ---nominal load % 86 88 89 90 91 92 92 92 92 92 92 86 88 89 90

    ---75 % 84 86 87 88 89 90 90 90 90 90 90 84 86 87 88

    ---50 % 81 82 83 84 85 86 86 86 86 86 86 81 82 83 84

    ---25 % 73 74 75 77 79 81 82 82 82 82 82 73 74 75 77

    (2) Maximum dissipated

    power at nominal load kw 1.30 1.63 1.98 2.67 3.16 3.48 4.17 5.57 6.95 8.35 10.4 1.30 1.63 1.98 2.67

    (3) Audible noise(at a

    distance of 1.5 m)

    dB 60 65 60

    (4) Ambient temperature 040 040

    (5) Relative humidity % 90 90

    (6) Dimensions:

    --- Depth mm 800 800

    --- Width mm600 600 600 600 600 800 800 1200 1200 1200 1200 600

    --- Height mm 1700 1700

    (7) Weight kg 480 380 420 490 550 670 750 900 1050 1200 1400 460 350 390 450

    (8) Grade of protection IP20 IP20

    (9) Control cabinet color DELTA COOL GREY DELTA COOL

    1-12

  • 8/10/2019 T Service Manual

    15/65

    (b) 208/120 Input / Output

    Item Spec. 3 input3 output 3 input1 o

    Power rating KVA (P.F.0.8)

    10 15 20 30 40 50 60 80 100 120

    150

    10 15 20 30

    (1) ACAC efficiency

    ---nominal load % 85 86 87 88 89 90 90 90 90 90 90 85 86 87 88

    ---75 % 83 84 85 86 87 88 88 88 88 88 88 83 84 85 86

    ---50 % 80 81 81 82 83 84 84 84 84 84 84 80 81 81 82

    ---25 % 71 72 73 75 77 79 80 80 80 80 80 71 72 73 75

    (2) Maximum dissipated

    power at nominal load kw 1.41 1.95 2.39 3.27 3.96 4.44 5.33 7.11 8.89 10.7 13.4 1.41 1.95 2.39 3.27

    (3) Audible noise(at a

    distance of 1.5 m)

    dB 60 65 60

    (4) Ambient temperature 040 040

    (5) Relative humidity % 90 90

    (6) Dimensions:

    --- Depth mm 800 800

    --- Width mm 540 450 490 590 650 780 870 1050 1200 1400 1600 600

    --- Height mm 1700 1700

    (7) Weight kg 480 380 420 490 550 670 750 900 1050 1200 1400 540 420 460 540

    (8) Grade of protection IP20 IP20

    (9) Control cabinet color DELTA COOL GREY DELTA COOL

    1-13

  • 8/10/2019 T Service Manual

    16/65

    2. Introduction to PCB Function

    2.1 A Board (Inverter Control Board)

    A. Function:

    a. Generate three-phase sine-wave reference signal and triangle-wave which are transmitte

    to T board.

    b. Detect reserve AC voltage and frequency whether they are normal or not.

    c. Produce high frequency square-wave signals, P1 and P2 signals are transmitted to B

    board, SW+ and SW- signals to T board, and HF signals to P board.

    d. When the inverter short circuit, heatsink over temperature or fuse fail, the LED will show

    malfunction.

    e. Dip switch (SWA1) function setting are as follows:

    1 2 3 4 5 6 7 8

    OTFS OTFP OTFGT OTFGS SEL1 SEL2 D/Y

    (1) OTFS (Rectifier heatsink over temperature): When switch on, disable ove

    temperature function.

    (2) OTFP (Static switch heatsink over temperature): When switch on, disable ovetemperature function.

    (3) OTGT (Inverter heatsink over temperature, T phase): When switch on, disable ove

    temperature function.

    (4) OTGS (Inverter heatsink over temperature, S phase): When switch on, disable ove

    temperature function.

    (5) SEL1 and SEL2 are used to set Boost charge time, as following table:

    SEL1 SEL2 HRS

    OFF OFF 4

    OFF ON 8

    ON OFF 16

    ON ON 32

    (6) D/Y : If AC input is Y connection, setting the dip switch to ON, and if Dconnectio

    setting to OFF.

    2-1

  • 8/10/2019 T Service Manual

    17/65

    f. If the UPS loading is greater than 70%, the CPU will send control signal to B board focooling fan speed control.

    g. Press SWA2 push button switch that will reset BOOST CHARGE function, if the rectifier i

    in boost charge mode.

    B. Test and adjustment

    a. VRA1-----Amplitude adjustment of the triangle wave(6V).

    b. VRA2-----Amplitude adjustment of the reserve AC source(2.5V).

    c. VRA3----- phase-lock adjustment of the reserve AC source frequency.

    d. TPA2,3---The 30 kHz constant frequency square waves are transmitted to B and T board

    for switching signals.

    e. TPA4,5---Reserve AC source frequency (square wave) and amplitude test points.

    f. TPA6,7---Triangle wave signals test points, TPA6 and TPA7 are 180 phase shift.

    C. Troubleshooting:

    a. Confirm that CPU board and EPROM are inserted in right direction.

    b. Confirm that three-phase sine reference signals are normal.

    c. Confirm that amplitude and frequency of triangle wave are normal.d. Confirm that dip switch setting is correct.

    e. Confirm that +16VA, +12VA, +5VA and all wire connections are correct.

    2-2

  • 8/10/2019 T Service Manual

    18/65

  • 8/10/2019 T Service Manual

    19/65

    2.2 B Board (Power Supply Board)

    A. Function:

    a. Transfer AC main power from 200 VA transformer or DC bus voltage into 16VA, 16VB

    and +8VR, for the usage of other PCB.

    b. Battery ground fault detection.

    c. Control relay to drive cooling fan in high or low speed operation.d. Battery charge current limitation.

    e. High DC bus voltage detection.

    f. Battery current sensing.

    B. Test and adjustment:

    a. VRB1-----Adjustment of the battery charge current limitation. The following are the prese

    values.

    KVA 10 15 20 30 40 50 60 80 100 120 150

    A 3 5 7 10 14 17 20 22 25 30 36

    b. VRB2----- Adjustment of the High DC shutdown voltage level.

    c. TPB2,3---PWM drive signals for DC/DC converter, TPB2 and TPB3 are 180 phase shift.

    C. Troubleshooting:

    a. Confirm that TPB2, TPB3 are 30 kHz square waves, and indicators LEDB2~LEDB5 are

    emitted.

    b. When UPS loading over 70% rated power, confirm that FAN signal from A board is set highand relay is close correctly.

    c. After battery supplies power for a period of time and utility power is recovered, confirm tha

    battery charge current within tolerance(< 0.2C).

    d. Confirm that HIGH DC SHUTDOWN is set on correct level and function normally.

    2-4

  • 8/10/2019 T Service Manual

    20/65

    2.3 C Board (Rectifier Control Board)

    A. Function:

    a. Utility power low voltage level (-20%) detection.

    b. Rectifier over current.

    c. Shutdown protection of high DC bus voltage.d. Float charge and boost charge status setting.

    e. Three-phase input power phase sequence detection.

    f. Rectifier soft-start function.

    g. 12-pulse rectifier configuration with rectifier output current sharing .

    h. Battery temperature compensation and battery test function.

    B. Test and adjustment

    a. VRC1-----Adjustment of the utility power low voltage level.

    b. VRC2-----Float charge voltage adjustment, when battery in floating(393Vdc), LEDC3 will b

    lit.

    c. VRC3-----Boost charge voltage adjustment, when battery in boost(405Vdc), LEDC4 will b

    lit.

    d. VRC4-----Level adjustment of rectifier over current protection.

    e. VRC5-----Battery test rectifier output voltage adjustment, when battery in test mode, the

    rectifier will output constant voltage (335Vdc), LED5 will be lit.

    f. VRC6-----Battery temperature compensation voltage adjustment, If the battery temperatur

    is grater than 35, the rectifier output voltage will be reduced 5V(i.e. 388V in floatin

    charge).

    g. TPC17(RECT INH)---When utility power and rectifier operation are normal, this detectio

    point is low voltage level, the contrast is high and blocks rectifier.

    h. TPC8~TPC13---SCR trigger signals, transmitted to rectifier drive board (S board).

    i. TPC1~TPC3--- R, S, T phase sequence of the utility power.

    j. TPC16 (DC E/A OUT)---DC error voltage output, control SCR fire angle.

    C. Troubleshooting:

    a. RECT MAINS FAIL:

    (1) Confirm whether the utility power is normal or not. (Test point TPC17)

    (2) Confirm whether the utility phase sequence is normal or not. (Test point TPC1~TPC3)

    b. HIGH DC SHUTDOWN:

    (1) Confirm whether the DC capacitors are correct or not.

    (2) Confirm whether the HIGH DC SHUTDOWN adjustment (B board VRB22) is se

    correctly or not.

    (3) Confirm that rectifier over current protection is correct.

    2-5

  • 8/10/2019 T Service Manual

    21/65

    2-6

    TPC3

    R-SQ

    TPC1

    S-SQ

    TPC2

    T-SQ

    TPC5

    R-RAMP

    TPC6

    S-RAMP

    TPC7

    T-RAMP

  • 8/10/2019 T Service Manual

    22/65

    2-7

    TPC9

    S-

    TPC12

    T+

    TPC11

    T-

    TPC8

    R+

    TPC13

    R-

    TPC10

    S+

  • 8/10/2019 T Service Manual

    23/65

    2.4 E Board and AA Board (IGBT Snubber Board)

    A. Function:

    a. Suppress and absorb the transient voltage and current produced by IGBT switching.

    b. Connected to E board when using single IGBT module, and AA board when using paralleIGBT.

    B. Troubleshooting:

    a. Confirm whether the capacitors are fluid leakage or destructive.

    b. Confirm whether the diodes, resistors, and capacitors are normal or not.

    2.5 G Board (Inverter Drive Board)

    A. Function:

    a. System automatic shutdown protection when IGBT is over temperature( heatsin

    temperature greater than 70).

    b. Isolate and amplify the PWM signals generated by T board to drive IGBT.

    c. DC bus voltage level detection to determine the IGBT fuse fail.

    B. Test and adjustment:

    a. TPG1~4-----Inverter drive signal connected to terminals of IGBT module.

    b. SW+, SW- -----Generated from A board, as the power source control signals for IGBT

    driving.

    C. Troubleshooting:

    a. IGBT drive abnormal:

    (1) Confirm that IGBTs and fuses are normal.

    (2) Confirm that PWM waveforms are normal(TPG1 and TPG2 are 180phase shift, TPG

    and TPG4 are 180phase shift.)

    b. PWM waveform abnormal:(1) Confirm that PWM waveforms generated from T board are correct.

    (2) Confirm power supply (SW+, SW-) generated from A board is correct.

    2-8

  • 8/10/2019 T Service Manual

    24/65

    2-9

    TPG1PWM

    TPG2

    PWM

    TPG1

    PWM

    TPG2

    PWM

  • 8/10/2019 T Service Manual

    25/65

    2.6 H Board (Alarm Switch Board)

    A. Function:

    a. LED displays 4 status of alarm signals for users reference.

    b. Press SELECT key for LCD item inquiring.

    c. Press ENTER key for confirmation.

    B. Troubleshooting:

    a. Confirm that LEDs are not destroyed and buttons are in good contact.

    b. Confirm that connector are in good contact with lead.

    2.7 J Board and M Board (MOV Board)

    A. Function:

    a. Absorb high voltage surge from input terminal of the UPS.b. When input power is Dconnection using J board, and when Y connection using M Board.

    B. Troubleshooting:

    a. Confirm that the wiring is in good contact and tighten adequately.

    b. Confirm that MOV is not destroyed and choosing the correct MOV type.

    2.8 L Board (System LED Board)

    A. Function:

    a. Transfer twelveUPS status into system diagram and four LEDs driving signals.

    b. Transfer R board series in signals into parallel out signals by IC 74HC164 to drive LEDs.

    c. When pressing ON & CTRL key simultaneously, there is +5V voltage between them (INV

    ON).

    d. When pressing OFF & CTRL key simultaneously, there is +5V voltage between them

    (INV OFF).

    B. Troubleshooting:a.Confirm that LEDs are not destroyed and buttons are in good contact.

    b.Confirm that +5V power supply and IC 74H164 whether they are correct or no

    destroyed.

    c.If the LEDS are all lit, confirm that R board or EPROM on CPU board are correct.

    2-10

  • 8/10/2019 T Service Manual

    26/65

    2.9 N Board (Remote Panel Board) and Y Board (Switch Board)

    A. Function:

    a. Communicated with UPS for remote monitoring.

    b. Monitoring three sets of UPS at same time via RS485 interface.c. With 120V or 220V receptacles depends on UPS output.

    d. By communication, user can set inverter ON/OFF and alarm ON/OFF.

    e. Power supply:

    (1) +12V: Supplied to buzzer and LCD CCF.

    (2) -5V: Supplied to CPU board and RS485 Interface.

    (3) -12V: Supplied to LCD bias (contrast adjustment).

    f. The dip switch SWN1 setting is the same as SWR1 on R board, according to the input

    output voltage and KVA rating.

    B. Troubleshooting:

    a. Confirm whether the power supply and signals are normal or not.

    b. Confirm whether the LCD and push button are normal or not.

    2.10 P Board (Static Switch Board)

    A. Function:

    a. Generate SCR trigger signals for static switch transferring between Reserve and Inverte

    mode.

    b. Inverter output voltage abnormal detection. If the UPS output voltage is over or under 20%

    of nominal voltage, the SSOP fault signal will be generated and sent to A board.

    B. Test and adjustment:

    a. VRP1, TPP3-----High voltage level adjustment of inverter output.

    b. VRP2, TPP2-----Low voltage level adjustment of inverter output. The following are th

    different nominal output voltage and VRP1, VRP2 preset values.Nominal voltage 380/220 400/230 415/240

    TPP3 5.1V 5.3V 5.6V

    TPP2 2.7V 2.9V 3.0V

    c. TPP4---------------When transfer signal (transmitted from A board) is from low going to

    high level, it means UPS is transferred from Reserve mode to Inverter

    mode, at the same time.

    2-11

  • 8/10/2019 T Service Manual

    27/65

    C. Troubleshooting:

    a. Confirm that all wire terminals and static switches are connected correctly.

    b. Confirm whether VRP1 and VRP2 are adjusted correctly(When Inverter output voltage i

    abnormal, SSOP signal is low level).

    c. Confirm that reserve and inverter SCR, only one set is triggered at any time.

    2-12

    ZDP5

    (+)

    ZDP3

    (+)

  • 8/10/2019 T Service Manual

    28/65

    2.11 Q Board (Dry Contact Board)

    A. Function:

    Generate four sets of dry contact signals output as follows:

    a. Load on inverter (P1,P2 are closed at that time).

    b. Load on reserve(P3,P4 are closed at that time).c. Warning Message ( RES MAINS FAIL, RES FREQ ABNORMAL, RECT MAINS

    FAIL, BATT LOW,INV OVERLOAD, BATT LOW STOP, Load on bypass) (P5,P6 ar

    closed at that time).

    d. Fault Messages ( RECT HI DC STOP, OVERTEMP/FUSE FAULT, BATT GND

    FAULT, INV FAULT) (P7,P8 are closed at that time).

    B. Troubleshooting:

    a. Confirm that +12V power supply and relay are normal.

    b. Confirm that signals transmitted from R board are all normal.

    2.12 R Board (Display Board)

    A. Function:

    a. Transfer the signals from A board into twelve UPS status for LED display, and to fron

    panel for users reference.

    b. Display the Input / Output voltage, current, and frequency, battery voltage and curren

    and loading percentage, by feedback voltage and current signals to CPU.

    c. Provide RS485 interface.

    d. The power supply of LCD lamp is provided from R board INVR1 (DC/AC

    12V30KHz/250V), and the character contrast is controlled by -12.6V supply.

    e. According to Input / Output voltage and KVA rating, the dip switch SWR1 must be set a

    follows:

    SWR1-1 SWR1-2 I / P Voltage O / P Voltage

    ON ON 3f4W 3f4W

    OFF ON 1f3W 1f3W

    ON OFF 3f4W 1f2W

    OFF OFF

    2-13

  • 8/10/2019 T Service Manual

    29/65

    SWR1-3 SWR1-4 KVA-1 KVA-2 KVA-3 KVA-4

    ON ON 5 30 70 120

    OFF ON 10 40 80 150

    ON OFF 15 50 90

    OFF OFF 20 60 100

    f. The 12 LEDs on R board (from left to right), status explanations are as follows:

    (1) RECT MAINS FAIL: When utility power is under voltage (less than 20% rating), th

    LED will be lit.

    (2) RECT HI DC STOP: When DC bus voltage is too high, the LED will be lit.

    (3) OVERTEMP/FUSE FAIL: When the heatsink is over temperature or fuse fail, the LED

    will be lit.

    (4) BATT LOW/STOP: When UPS in back-up mode and DC bus voltage below 330V, th

    LED will flash, and when DC bus voltage below 300V, the LED will be lit.

    (5) LOAD LEVEL: When UPS in normal mode, the LED will flash, and the flashing ratdepends on loading percentage.

    (6) BATT GND FAULT: When the battery is shorted with ground, the LED will be lit.

    (7) INV ON: When the load is supply by inverter output, the LED will be lit.

    (8) INV OVERLOAD: When UPS is loaded over rated capacity, the LED will be lit.

    (9) INV FAULT: When Inverter is abnormal, the LED will be lit.

    (10) LOAD ON RES: When the load is supplied by reserve source, the LED will be lit.

    (11) RES MAINS FAIL: When the voltage amplitude of reserve input is abnormal, the LED

    will be lit.

    (12) RES FREQ ABNORMAL: When the frequency of reserve input is abnormal, the LE

    will be lit.

    A. Test and adjustment:

    a. VRR1~VRR3------Adjustment LCD display of output current.

    b. VRR5----------------Adjustment LCD display of battery voltage.

    c. VRR6~VRR11----Adjustment LCD display of input / output voltage.

    d. VRR7~VRR14----Adjustment LCD display of input current (optional).

    e. VRR15-------------- Adjustment LCD display of battery charge current.f. VRR16-------------- Adjustment LCD display of battery discharge current.

    B. Troubleshooting:

    a. Confirm that all signals and power lines are correctly connected with R board.

    b. Confirm that CPU board is inserted correctly, and the EPROM is function correct.

    c. Confirm that all LEDs status display normally.

    2-14

  • 8/10/2019 T Service Manual

    30/65

    2.13 S Board (Rectifier Drive Board)

    A. Function:

    a. Transmitting trigger signals generated from C board through isolation pulse transformer t

    trigger thyristors.

    b. When SCRs are switching, Snubber will absorb and suppress transient surge to protecfrom destroyed.

    B. Troubleshooting:

    a. Confirm that SCRs are normal.

    b. Confirm that all connectors and wiring are connected properly.

    c. Confirm that trigger signals transmitted from C board are correct.

    d. Check pulse transformers and Zener diodes are normal.

    e. Check components of the Snubber(resistors and capacitors) are not burnout.

    2.14 T Board (Inverter Phase Board)

    A. Function:

    a. Short circuit protection of inverter output.

    b. Feedback UPS output voltage to generate error voltage and error sine-wave signal.

    c. Compare the error sine-wave signal and triangle wave to generate PWM trigger signal

    that will be transmitted to G board to drive IGBT.

    B. Test and adjustment:

    a. VRT1-------Adjustment of output voltage amplitude.

    b. VRT2-------Adjustment inverter over current protection level.

    c. TPT5-------Feedback O/P current signals and compared with over current protecting

    point (setting by VRT2), to generate output short circuit signals transmitted

    to A board.

    d. TPT7,8-----When UPS is single phase output, TPT7 and TPT8 are the detecting point

    of current feedback signals on the secondary and primary of the outputtransformer for DC offset compensation to prevent transformer saturation.

    TPT7 and TPT13 (DSINE) must be the same phase, TPT8 and TPT13 ant

    phase .

    2-15

  • 8/10/2019 T Service Manual

    31/65

    e. TPT23,24---Triangle signals transmitted from A board, TPT23 and TPT24 are 180

    phase shift.

    f. TPT15~22---PWM trigger signals transmitted to G board for triggering IGBT,TPT15

    and TPT16, TPT17 and TPT18,TPT19 and TPT20,TPT21 and TPT22 are

    anti-phase.

    C. Troubleshooting:

    a. Over current protection abnormal:

    (1). Confirm that detecting CT for protection is connected correctly.

    (2). Confirm that O/P transformer and Inverter Choke both are not saturated.

    (3). Confirm that VRT2 setting level for over current protection is correct.

    b. PWM waveform abnormal:

    (1). Confirm that triangle and error sine wave are correct.

    (2). Confirm INV ON signal is normal.

    (3). Confirm the dead time setting is correct. (Check the component specifications o

    DT18~21, RT95~98, and CT4~7 are correct.)

    2-16

    TPT22

    S1

    TPT20

    S2

  • 8/10/2019 T Service Manual

    32/65

    2-17

    TPT22

    S1

    TPT20

    S2

    TPT13

    DSINE

    TPT14

    ERROR

    VOLTAGE

  • 8/10/2019 T Service Manual

    33/65

    2-18

    TPT3

    INVFB

    TPT4

    SINE

    TPT3INVFB

    TPT4

    SINE

  • 8/10/2019 T Service Manual

    34/65

  • 8/10/2019 T Service Manual

    35/65

  • 8/10/2019 T Service Manual

    36/65

  • 8/10/2019 T Service Manual

    37/65

    D

    transfer to INV

    false

    false

    ?

    false

    ?

    false?

    false

    ?

    KEY

    ?

    No

    No

    No

    No

    SOPFAULT

    Yes

    SCFAULT

    Yes

    OTFAULT

    Yes

    HIDCFAULT

    Yes

    OFFAULT

    Yes

    F

    E

    No

    3-3

  • 8/10/2019 T Service Manual

    38/65

    F

    check

    check

    reset key

    check

    time check

    check

    BATFAULT

    Main Loop

    OVLFAULT

    Check overload %

    Time out

    ?

    No

    No

    Yes

    Yes

    3-4

  • 8/10/2019 T Service Manual

    39/65

    SOPFAULT

    false

    SINEWAVE O/P OFF

    false

    false

    ?

    Transfer to RES

    Ture

    ?

    Transfer to RES

    Ture

    wait 7 sec

    SINEWAVE O/P ON

    No

    Yes

    Yes

    No

    RE-START

    3-5

  • 8/10/2019 T Service Manual

    40/65

  • 8/10/2019 T Service Manual

    41/65

    OTFAULT

    false

    SINEWAVE O/P OFF

    false false

    ?

    Transfer to RES

    Ture

    ?

    Transfer to RES

    Ture

    wait 20 sec

    SINEWAVE O/P ON

    No

    Yes

    disappear

    ?No

    Yes

    No

    LED ON

    Yes

    RE-START

    3-7

  • 8/10/2019 T Service Manual

    42/65

  • 8/10/2019 T Service Manual

    43/65

    OFFAULT

    false

    SINEWAVE O/P OFF

    false

    false

    ?

    Transfer to RES

    Ture

    KEY

    ?

    UPS on mode

    SINEWAVE O/P ON

    Yes

    NoNo

    KEY

    ?

    No

    Yes

    UPS on normal mode

    RE-START

    Yes

    3-9

  • 8/10/2019 T Service Manual

    44/65

  • 8/10/2019 T Service Manual

    45/65

    OVLFAULT

    false

    SINEWAVE O/P OFF

    false

    false

    ?

    Transfer to RES

    Ture

    ?

    Transfer to RES

    Ture

    wait 20 sec

    SINEWAVE O/P ON

    No

    Yes

    ?

    Yes

    No

    RE-START

    Yes

    No

    OFFAULT

    cancel

    re-start

    ?

    No

    Yes

    3-11

  • 8/10/2019 T Service Manual

    46/65

    3.2 Flow Chart for System Display

    START

    INITIALI/O_PIN

    ALLSYS_LED=

    TESTLCM:DELTA

    ALLSYS_LED=

    /TESTLCM:Sys. Diag.

    MAIN

    INITIAL RAM

    SET_UPRS232/TIMER

    INT1/EI

    CALLINI_LCM

    OR MODE

    GRAPHIC ON

    SET CURSOR

    GRAPHAREA

    HOMEADDRESS

    DATA AUTOWRITE MODE

    INI_LCM

    RET

    3-12

  • 8/10/2019 T Service Manual

    47/65

    MAIN

    CALL

    INI_LCM

    CALL

    STSLED

    STSLCM

    READ

    UPS

    STATUS

    KEYNM>9

    CLEAR

    MAIN

    Measure

    TRUE_POWER

    Vrms X Irms

    UPDATE

    R/S/T_V R/S/T_i

    VRMS

    CLEAR

    SQUARE

    BUFFER

    RMSVI

    RET

    CALL

    RMSVI

    LCM

    DISPLAY

    3-13

  • 8/10/2019 T Service Manual

    48/65

    TIMER/500us

    INTERRUPT

    ENT RY SCAN MODERD AN0-3 ->

    BUFCR0_3

    4502 AN_SW

    AV ERAG EBAT_V,BAT_i

    4502 AN_SW

    SQ R/S/T_V,i

    SQ R-S-T_V

    MEM V n, In

    4502 AN_SW

    SCANED

    UP/DO WN_ K

    TIM:20MS

    LEDSIO

    BUZZER

    TIME:2SEC

    TIME_OUT->

    RS232/CHK_S

    CALL

    UART _ T RX

    RET I

    R ET

    INTTM1

    UART_TRX

    txbgn.f

    FSR.f

    PASER

    RX_BUF

    error

    IN C

    TRX_INDEX

    CLEAR

    CHECK_SUM

    TRX_INDEX

    SETUP

    TX_FRAME

    TXBGN.F

    TRX_INDEX

    BUF.FULL

    NO YES

    R ET R ET

    R ETYE S

    FST.f

    NO

    NO

    UART X

    UART X

    R ET

    PASER

    TRX_INDEX

    EN D

    NO

    YE S

    TXB

  • 8/10/2019 T Service Manual

    49/65

    INT1

    AC_SYNC

    I_FREQ =

    N_FC - O_FC

    UPDATE->

    O_FC=N_FC

    I_FREQ

    ? =

    F_BUF

    FREQCT = 0

    UPDATE

    AC_CYC

    INC.

    FREQCT

    FREQCT

    > 5

    CLEAR

    FREQCT

    F_BUF=I_FREQ

    RETI

    RETI

    YES

    NO

    YES

    NO

    3-15

  • 8/10/2019 T Service Manual

    50/65

    4. Troubleshooting

    4.1 Test Procedures of The System

    1. Check PCB all connectors are connected correctly and the right wiring.

    2. Check all Breakers in OFF position and make sure the correct input power (Dtype U, V, Wor Y type R, S, T, N) by meter, when UPS is connected to power and battery cabinet.

    3. Check all screws of the UPS are tightened.

    4. Turn on BYPASS breaker and then measure PCB power supply.

    5. If LEDA1 and LEDA2 on A board are lit that represents 12V in normal function. If LEDB2

    LEDB3, LEDB4, and LEDB5 on B board are lit that represents 16V in normal function

    Measure TPB12 and TPB13 on B board whether 8V is normal or not. If LEDC1 an

    LEDC2 on C board, LEDT1 and LEDT2 on T board are all lit, that represents 12V in norma

    function.

    6. Turn A board dip switch (DSWA1) and R board dip switch (DSWR1) into moderate position.

    7. Triangular amplitude adjustment: Turn on BYPASS breaker, and connect CH1 and CH

    with oscilloscope probes to A board TPA6 and TPA7. Adjust varistor (VRA1) to make th

    amplitude of triangular waveform to 6V, and check its frequency whether equals to 7.8KHzand TPA6, TPA7 with 180 phase shift.

    4-1

  • 8/10/2019 T Service Manual

    51/65

    8. High-low limit adjustment of INV output voltage: Turn on BYPASS breaker, then adjust th

    varistor (VRP2) to make TPP2 (Low Ref.) to 2.5V and adjust the VRP3 to make TPP3 (High

    Ref.) to 4.5V.

    9. Driving signal test of power board: Turn on BYPASS breaker, and connect CH1 and CH

    with oscilloscope probes to B board TPB2 and TPB3. Check the amplitude of squar

    waveform equals to +12V, frequency to 30 kHz, TPB2 and TPB3 with 180 phase shift.

    10. Test of reference sine wave: Turn on BYPASS breaker, then press ON and OFF buttons o

    the front panel simultaneously. Check reference sine wave signals (top of RA70-R phase

    top of RA68-S phase, top of RA69-T phase) are 120 phase shift.

    11. Test of IGBT driving signals: Turn on BYPASS breaker, then press ON and OFF button

    simultaneously. Check the amplitudes of PWM waveform on G board (S1, S2), (S1, S2

    (S3, S4), and (S3, S4) are +14V/-5V, and the dead time is about 3.5 ~ 5 us.

    4-2

  • 8/10/2019 T Service Manual

    52/65

    12. Adjustment of reserve input detection: Turn on BYPASS and RESERVE breakers, the

    connect CH1 of oscilloscope probe to TPA5 and adjust varistor VRA2 to the amplitude abou

    2.3~2.5V.

    13. Test of rectifier driving signals: Pull out CNC4 connector on C board, turn off BYPASS an

    RECT breakers, and connect CH1 and CH2 with oscilloscope probes to TPC8/TPC13

    TPC9/TPC10, TPC11/TPC12. Check whether TPC8 and TPC13, TPC9 and TPC10, TPC1

    and TPC12 are 180 phase shift.

    14. Adjustment of DC bus voltage: Connect back the CNC4 connector on C board, adjust VRC

    clockwise to end, and turn on BYPASS and RECT breakers, the LEDC3 on C board will be l

    Adjust VRC2 counterclockwise slowly until the DC bus voltage equals to 393V. Then, tur

    off RECT breaker waiting for DC bus voltage down to zero.

    15. Adjustment of HIGH DC SHUTDOWN voltage: Turn on BYPASS and RECT breakerwaiting until DC bus voltage reaches 393V. Adjust VRC2 counterclockwise till DC bu

    voltage equals to 415V. Then, adjust VRB2 on B board clockwise until buzzer is beep, an

    HI DC SHUTDOWN LED on R board is lit at the same time. Finally, adjust DC bus voltag

    back to 393V.

    4-3

  • 8/10/2019 T Service Manual

    53/65

    16. Adjustment of BOOST CHARGE voltage: Turn on BYPASS and RECT breakers waitin

    until DC bus voltage attains to 393V, and short C board JPC3 with short pin, then LEDC4 wi

    be lit at that time. Adjust VRC3 until DC bus voltage reaches 405V, then take out short pin

    and DC bus voltage will down to 393V automatically.

    17. INV ON test: Turn on BYPASS and RECT breakers until DC BUS voltage is about 30V~40Vthen turn off RECT breaker. Connect CH1 and CH2 with oscilloscope probes to T boar

    TPT3 and TPT4, then press ON and OFF buttons simultaneously and check the waveform

    should be anti-phase.

    18. INV ON test: Turn on BYPASS and RECT breakers, then adjust VRC2 until DC bus voltag

    attains to 393V. Connect CH1 and CH2 with oscilloscope probes to T board TPT3 an

    TPT4, press ON and OFF buttons simultaneously. Using voltage meter to check the

    phase output voltage whether they are coincidence with the specifications or not. If no

    adjust VRT1 on T board to meet the specifications.

    19. Phase-lock adjustment: Turn on BYPASS and RECT breakers until DC bus voltage attain

    to 393V, then turn on RESERVE and O/P breakers, turn off BYPASS breaker, press ON an

    OFF buttons simultaneously (the above procedures means transferring UPS to INV outpu

    mode). Connect CH1 and CH2 with oscilloscope probes to static switch SCR, then chec

    reserve power and INV output whether they are phase-lock or not. If no, adjust A boar

    VRA3 till phase-lock.

    4-4

  • 8/10/2019 T Service Manual

    54/65

    20. Adjustment of the LCD display: Transfer UPS to INV output mode, adjust VRR5~VRR11 o

    R board for the LCD display of I/P, O/P, and DC bus voltage and current to meet the actua

    value.

    21. Adjustment of 200% Ipeak protection level: Connect CH1 with an oscilloscope probe to T

    board TPT5, take on resistive load and check whether there is an waveform on the scope

    If yes, change to computer load, and adjust T board VRT2 counter-clockwise to 200% Ipea

    protection point.

    4-5

  • 8/10/2019 T Service Manual

    55/65

    22. BATT GND FAULT test: Connect one terminal of wire to UPS GND, the other side to touc

    with battery terminal, then R board LEDR6 will be lit, and alarm will beep.

    23. High-low transfer voltage test: Transfer UPS to INV output mode, connect battery cabine

    and shut off AC input power. Then, using autotransformer to change AC input voltage tUPS, adjust C board VRC1 for rectifier input low-level transfer point (nominal voltage -15%)

    and VRP1, VRP2 on P board for reserve input high-level and low-level transfer poin

    (nominal voltage 20%).

    24. OVERTEMP/FUSE FAULT test: Transfer UPS to INV output mode, pull out CNP

    connector on P board or CNG6 connector on G board, the alarm will beep and LEDR3 on R

    board will be lit at that time.

    25. Cooling fan test: Transfer UPS to INV output mode and take on 70% loading. Check th

    cooling fan whether rotate faster or not.

    26. Overload test: Transfer UPS to INV output mode and take on 110% loading. The R boar

    LEDR8 will be lit and buzzer will beep at the same time. 15 minutes later, INV output mod

    will be transferred to RES output mode automatically and INV OVERLOAD LED on R board

    will be lit. If take off the over loading, after 20 seconds, RES mode will be transferred bac

    to INV mode again automatically.

    27. 125% overload test: The test procedures are similar to Item 26, but the loading leve

    changes to 125% and overload time to 5 minutes.

    28. 150% overload test: The test procedure are similar to Item 26, but the loading leve

    changes to 150% and overload time to 30 seconds.

    29. BATT LOW & BATT LOW STOP test: Transfer UPS to INV output mode, connect batter

    cabinet, take on nominal load, and shut off AC input power. When DC bus voltage goe

    down to 330V, the LEDR4 on R board will flash and buzzer will beep faster. When DC bu

    voltage goes down to 300V, LEDR4 will be lit and shutdown UPS.

    30. Adjustment of the battery charge current: Continuously from Item 29 last step, turn on th

    AC input power to UPS and connect current probe to battery + terminal, then adjust B boar

    VRB3 for battery charge current (< 0.2C).

    4-6

  • 8/10/2019 T Service Manual

    56/65

  • 8/10/2019 T Service Manual

    57/65

    2. RESERVE FREQUENCY ABNORMAL

    R

    board

    LED12

    lit

    Rboard

    RESMAINSFF

    ="LO"(RR26)

    Aboard

    RESS-W

    (TPA4)OK

    RESFreq.

    OK

    CheckRESI/P

    &50/60Hzsetting

    END

    ReplaceRboard

    ReplaceCPUboard

    onAboard

    ReplaceAboard

    NO

    NO

    NO

    YES

    YES

    YES

    4-8

  • 8/10/2019 T Service Manual

    58/65

    3. RESERVE MAINS FAIL

    RboardLEDR11lit

    Rboard

    RESMAINSFF

    ="LO"(UR31.1)

    Aboard

    RESMAG

    =2.3~2.5V

    (TPA5)

    AboardRESvoltage

    detect

    OK

    CheckUPSwiring

    END

    ReplaceRboard

    Replace

    CPU board

    onAboard

    Aboard

    RES amplitude

    settingOK

    Adjust

    A

    board

    VRA2

    ReplaceAboard

    NO

    NO

    NO

    YES

    YES

    YES

    NO

    YES

    4-9

  • 8/10/2019 T Service Manual

    59/65

    4. INVERTER FAULT

    R board LEDR9 lit

    R board

    INV SC="HI"

    (UR31.5)

    A board

    SCR,SCS,SCT

    = "HI"

    Ipeak level

    setting OK

    (TPT6)

    Check Ipeak CT OK

    END

    Replace R board

    Replace A board

    Adjust T board

    VRT2

    NO

    NO

    Yes

    No

    YES

    YES

    4-10

  • 8/10/2019 T Service Manual

    60/65

    5.INVERTER OVERLOAD

    R board LEDR8 lit

    R boardINV OL= "LO"

    (UR31.6)

    A board

    LOAD(CNA6.20)Freq. OK

    R boardPIOBL(UR30.2)

    Freq. OK

    Overload

    CT OK

    Check UPS wiring

    END

    Replace R board

    Replace CPU boardon A board

    Replace A board

    Replace R board

    NO

    NO

    NO

    NO

    YES

    YES

    YES

    YES

    4-11

  • 8/10/2019 T Service Manual

    61/65

    6. BATTERY GROUND FAULT

    R board LEDR6 lit

    R board

    BGF= "LO"

    (UR32.2)

    BATT wiring

    correct

    Correct BATT Wiring& replace bad BATT

    END

    Replace R board

    Replace B board

    NO

    NO

    YES

    YES

    4-12

  • 8/10/2019 T Service Manual

    62/65

    7. BATTERY LOW / STOP

    R board LEDR5 lit

    Replace R board

    R board

    PIOSD="LO"

    (UR31.1)

    DC BUS 330V

    Replace C board& check RECT SCR

    END

    Replace CPU board

    on R board

    NO

    NO

    YES

    YES

    4-13

  • 8/10/2019 T Service Manual

    63/65

    8888.... OVERTEMPERATURE / FUSE FAIL

    R board LEDR3 lit

    R board

    OTF ="LO"

    (UR31.3)

    A board

    OTFG,OTFP,

    OTFS= "LO"

    Check thermal switchon heatsink

    END

    Replace R board

    Replace A board

    NO

    NO

    YES

    YES

    4-14

  • 8/10/2019 T Service Manual

    64/65

    9. RECTIFIER HIGH DC STOP

    RboardLEDR2lit

    Rboard

    HDCSDR="LO"

    (UR32.1)

    DCBUS415V

    Cboard

    TPC8.9.10,11,

    12.13OK

    ReplaceCboard

    CheckRECTSCR

    wiring

    ReplaceRboard

    END

    ReplaceBboard

    Bboard

    VRB2setting

    correct

    AdjustBboardVRB2

    NO

    NO

    NO

    YES

    YES

    YES

    NO

    YES

    4-15

  • 8/10/2019 T Service Manual

    65/65

    10. RECTIFIER MAINS FAIL

    R board LEDR1 lit

    R board

    RMF= "LO"(UR31.4)

    A boardRMF5= "LO"(CNA46.22)

    C board

    (TPC1~TPC3)OK

    Check I/P powerphase & wiring

    END

    C board VRC1

    setting OK

    Replace Rboard

    Replace A

    board

    Adjust C board VRC1

    Replace C

    board

    NO

    NO

    NO NO

    YES YES

    YES

    YES