7,3 ÷ 71,4 kW
Close control air conditioners with upflow or downflow air delivery,equipped with inverter driven scroll compressors.
technicalcatalogueT_NXTEVINV_0313_GB
8/10/2019 t Nxtevin 0313 Gb
http://slidepdf.com/reader/full/t-nxtevin-0313-gb 2/56
2 RC GROUP S.p.A. ● T_NXTEVINV_0313_ GB ● R410A
INDEX
GENERAL CHARACTERISTICS ................................................................................................. 3
SERIES IDENTIFICATION........................................................................................................... 3
MODEL IDENTIFICATION ............................................................ ............................................... 4
WORKING LIMITS ....................................................................................................................... 4
NEXT EVO INV DX MAIN COMPONENTS.......................................................................... ....... 5
OPTIONAL ACCESSORIES ........................................................................................................ 7
WORKING LOGIC ....................................................................................................................... 9
TECHNICAL DATA - NEXT EVO INV OVER / UNDER ......................................................... .. 13
ACCESSORIES TECHNICAL DATA - NEXT EVO INV DX OVER / UNDER.... ........................ 18
ELECTRICAL DATA .................................................................................................................. 19
MICROPROCESSOR CONTROL SYSTEM .............................................................................. 20
POSSIBLE AIR INTAKE FOR OVER VERSIONS ..................................................................... 22
OPTIONAL ACCESSORIES – REMOTE AIR COOLED CONDENSER .................................... 23
SERIES IDENTIFICATION......................................................................................................... 23
OPTIONAL ACCESSORIES - CONDENSATE DISCHARGE PUMP ......................................... 27
OPTIONAL ACCESSORIES - EXTRA CIRCUIT SYSTEM ........................................................ 28
OPTIONAL ACCESSORIES - FLOOR STAND ............................................................. ............. 29
OPTIONAL ACCESSORIES – OVER VERSION - BOTTOM PANEL ........................................ 30
OPTIONAL ACCESSORIES - SANDWICH PANEL ................................................................ ... 30
WITH THIS ACCESSORY IT IS POSSIBLE A NOISE INSULATION OF THE PANELS OFTHE AIR CONDITIONER ........................................................................................................... 30
OPTIONAL ACCESSORIES - NON RETURN MOTORIZED DAMPER .................................... 31
OPTIONAL ACCESSORIES - UNDER VERSION - AIR DELIVERY/INTAKE PLENUM ............ 32 THE ACCESSORIES IS NOT AVAILABLE FOR MACHINE SIZE E0. ....................................... 32
OPTIONAL ACCESSORIES - OVER VERSION - AIR DELIVERY PLENUM ............................ 33
OPTIONAL ACCESSORIES – DIRECT FREE-COOLING PLENUM ......................................... 34
MACHINE DRAWINGS .............................................................................................................. 36
TYPICAL INSTALLATION DIAGRAMS FOR DIRECT EXPANSION MACHINES WITHREMOTE AIR COOLED CONDENSER ..................................................................................... 50
EXAMPLE FOR MACHINES NOISE EMISSION CALCULATION ............................................. 52
AIR FILTERS REPLACEMENT FOR UNDER VERSION MACHINES ...................................... 54
8/10/2019 t Nxtevin 0313 Gb
http://slidepdf.com/reader/full/t-nxtevin-0313-gb 3/56
3RC GROUP S.p.A. ● T_NXTEVINV_0313_ GB ● R410A
GENERAL CHARACTERISTICSNEXT EVO INV: Close control air conditioners with upflow or downflow air delivery, equippedwith BLCD type inverter driven orbiting spiral (SCROLL) hermetic compressor and ON/OFFcompressors.
The machines are suitable for indoor installation only.
The constructive solutions and the internal lay-out allow high application flexibility and the frontalaccess to the main components for the inspection and routine maintenance.
Machines supply fully assembled with refrigerant charge and control systems. The installationrequires electrical and hydraulic /refrigerant connections only allowing high costs and timereduction.
Final assembly on all machines before shipment including running test, reading and monitoringof operating parameters, alarms simulation and visual check.
Design, assembly and test as per the Company Quality Assurance program in full compliancewith ISO 9001:2008. RC Group has been the first Italian company in its segment to get the ISO9001 in October 13
th, 1991 with certificate ICIM 0018.
The machines are in full compliance with European Directive 2006/42CE, 2006/95CE,2004/108CE, 97/23CE and subsequent amendments.
SERIES IDENTIFICATION
OVER VERSION
Frontal air suction and upflow air delivery.
UNDER VERSION
Air suction from the top and downflow air delivery.
NEXT EVO INV DX – COMMON CHARACTERISTICS: Direct expansion close control airconditioners for matching with remote air cooled condenser and equipped with BLCD typeinverter driven scroll compressors and ON/OFF compressors, Plug-fans with EC type electricmotor.
S version: with single refrigerant circuit- Sizes 007÷028: n°1 BLCD inverter driven compressor.
Cooling capacity: 7,3 ÷ 37,0 kW
- Sizes 034÷040: n°1 BLCD inverter driven compressor;n°1 ON/OFF compressor.
Cooling capacity: 16,9 ÷ 52,9 kW
- Sizes 053÷057: n°1 BLCD inverter driven compressor;n°2 ON/OFF compressors.
Cooling capacity 17,0 ÷ 71,4 kW
The compressors are connected to a single refrigerant circuit
8/10/2019 t Nxtevin 0313 Gb
http://slidepdf.com/reader/full/t-nxtevin-0313-gb 4/56
4 RC GROUP S.p.A. ● T_NXTEVINV_0313_ GB ● R410A
MODEL IDENTIFICATION
NEXT EVO INV DX S O 040 M 2 E5
NEXT EVO INV Series identification
DX Machine typeDX direct expansion – air cooled
S Version
S Single refrigerant circuit
O Air delivery
O upflowU downflow
040 Cooling capacity (kW) at nominal conditions
M Compressor type
M Modulating
2 Number of compressors
1 1 BLCD inverter driven compressor2 1 BLCD inverter driven compressor + 1 ON/OFF compressor3 1 BLCD inverter driven compressor + 2 ON/OFF compressors
E5 Cabinet size
WORKING LIMITS
Room air temperature:14°C minimum temperature with wet bulb.24°C maximum temperature with wet bulb.
35°C maximum temperature with dry bulb.
Room air humidity:20%RH minimum relative humidity.75%RH maximum relative humidity.
The values are indicative. The working temperatures are influenced by a series of variablesas:
Working conditions
Thermal load
Cleanness status of the condensing coils
Set of the microprocessor control
STORING TEMPERATURE
If the machine is not installed on receipt and is stored for a long time, store it in a protectedplace, at temperatures ranging between -30°C and 50°C in absence of superficialcondensation and direct sun light.
8/10/2019 t Nxtevin 0313 Gb
http://slidepdf.com/reader/full/t-nxtevin-0313-gb 5/56
5RC GROUP S.p.A. ● T_NXTEVINV_0313_ GB ● R410A
NEXT EVO INV DX MAIN COMPONENTS
FRAMEWORK
Base in aluminium extrusion, painted with epoxy powders.
Frame in galvanized steel sheet.
Galvanized steel sheet panels painted with epoxy powders, internally insulated withnoise absorption material and seals to ensure air tight with the panels.Hinged front panels with quick release removal system.Total front access for routine maintenance.Removable lateral and back side panels.
Colour: RAL 9005 for base and frame (black)RAL7016 for panels (anthracite gray)
OVER version- Air intake from the front through honeycomb type grille and air delivery from the
top.- Washable air pre-filters with G2 efficiency, with cells in synthetic fibre (size E0
excluded).
UNDER versionMachine size E0- Air intake from the front through honeycomb type grille and air delivery from the
bottom.Machine size E1, E2, E3, E4, E5, E6
- Air intake from the top and air delivery from the bottom.
INVERTER DRIVEN COMPRESSORS
SCROLL “BLDC” compressor type with spiral profile optimized for R410A refrigerant.
Synchronous brushless inverter driven motor.
Inverter for modulating capacity control.
Reactance for the reduction of electromagnetic noise and interference.
Crankcase heater.
Rubber supports.
Soundproof cap.
ON / OFF COMPRESSORS
SCROLL hermetic compressors with spiral profile optimized for R410A refrigerant.
2-pole 3-phase electric motor with direct on line starting.
Crankcase heater.
Rubber supports.
Soundproof cap.
FILTER SECTION
Size E0Washable air filters with G3 efficiency, with cells in synthetic fibre and metall ic frame(EN 779-2002).
Size E1, E2, E3, E4, E5, E6Washable air filters with G4 efficiency, with cells in synthetic fibre and metallic frame(EN 779-2002).
EVAPORATING SECTION
Heat exchanger coil with internally corrugated copper tubes and high efficiencyaluminium fins, specifically developed to provide high heat transfer and lowerpressure drops.
Frame in galvanized steel.
Condensate tray in peraluman with PVC flexible discharge pipe.
FANS SECTION
Centrifugal fans with backward curved blades with wing profile, single suction andwithout scroll housings (Plug-fans), directly coupled to external rotor electric motor.- Brushless type synchronous EC motor with integrated electronic commutated
system and continuous variation of the rotation speed.The motor rotation control is obtained with the EC system (ElectronicCommutation) that manage the motor according to the signal coming from themicroprocessor control.
Fans control through ModBus.
Temperature sensors on air intake and air delivery with control, regulation andlimitation functions.
Fan guard with rubber support (UNDER version)
8/10/2019 t Nxtevin 0313 Gb
http://slidepdf.com/reader/full/t-nxtevin-0313-gb 6/56
6 RC GROUP S.p.A. ● T_NXTEVINV_0313_ GB ● R410A
REFRIGERANT CIRCUITComponents for the single refrigerant circuit:
Electronic expansion valve.
Sight glass.
Filter dryer on liquid line.
Pressure transducers with indication, control and protection functions, on low andhigh refrigerant pressure.
High pressure safety switch with manual reset.Liquid receiver with accessories.
Refrigerant circuit with copper tubing with anticondensate insulation of the suctionline.
Plastic capillary hoses for pressure sensors connection.
R410A refrigerant charge.
Valves on gas delivery and liquid return for coupling to remote air cooled condenser.
0÷10V proportional signal to manage the condensing control system of the remote aircooled condenser.
Oil separator on gas discharge.
ELECTRICAL PANELIn accordance with EN60204-1 norms complete with:
Main switch with door lock safety.
Magnetothermic switches for fans.
Magnetothermic switches for compressors.
Contactors for each load. The inverter driven compressors and the EC fans don’trequire contactors.
Transformer for auxiliary circuit and microprocessor supply.
Terminals:OUTLETS- Voltage free deviating contact for General Alarm 1- Voltage free contact for machine operating status.INLETS- Emergency unit stop with signalling on display (external alarm).- External enabling.
Power supply 400/3/50+N
CONTROL SYSTEMMicroprocessor system with graphic display for control and monitor of operating andalarms status. The system includes:- Real time clock.- Predisposition for connectivity board housing ( RCcom MBUS/JBUS, LON,
BACnet for ethernet (SNMP- TCP/IP), BACnet for MS/TP).- Main components hour-meter.- Non-volatile “Flash” memory for data storage in case of power supply faulty and
for alarms status recording (2MB).- Menu with protection password.- LAN connection.
WARNINGIs necessary to provide the refrigerant and the lubricant oil charge for the connectionpipes and for the remote air cooled condenser.
8/10/2019 t Nxtevin 0313 Gb
http://slidepdf.com/reader/full/t-nxtevin-0313-gb 7/56
7RC GROUP S.p.A. ● T_NXTEVINV_0313_ GB ● R410A
OPTIONAL ACCESSORIES
The descriptions of these additional components can be found in Chapter OPTIONAL ACCESSORIES.
Remote air cooled condensers with axial fans series TEAM MATE, TEAM MATE PF.
Condensate drain system including pump with activation float and 10 linear meters longdischarge pipe. For machines size E0, E1, E2 and E3 the optional is supplied in mountingkit.
EXTRA CIRCUIT system (Size E0 excluded).Components:- Chilled water cooling coil with copper tubes, aluminium fins and galvanized steel
frame.- 2-way motorized valve for water flow regulation with 0÷10 VDC control actuator and
emergency manual control. Nominal operating pressure up to 1600 kPa and closingpressure (Δps) of 1400 kPa.
Unit floor stand with height adjusting rubber holders. It is not possible to match the unitfloor stand with plenum installed under the machine.
Unit base noise insulation with special bottom panel for OVER version (size E0excluded).
Sandwich panels with interposed mattress in soundproof material.
Non-return air damper driven by electric servomotor for installation on the machine airdelivery.
Air distribution plenum with double row adjustable grilles on three sides for OVERversion.
Air distribution plenum with double row adjustable grilles on front side and noiseabsorption partitions for OVER version (size E0 excluded).
Plenum with F6/F7/F9 efficiency filters on air delivery (size E0 excluded).
Plenum with noise absorption partitions on air delivery (size E0 excluded).
Plenum for direct free-cooling on air intake (size E0 excluded) . The optional foresee thecombined Temperature / Humidity sensor on machine air suction and the combinedTemperature / Humidity sensor for ambient air.
OTHER ACCESSORIES
Modulating steam humidifier with immersed electrodes fitted with safety and runningaccessories (temperature and humidity sensor on air intake is included).
Dehumidification systemComponents:- Temperature/humidity sensor on the air intake.- Electronic control system of the dew point temperature for the combined intervention
of cooling capacity and air flow.
Electric heater consisting of aluminium armoured elements with integral fins and safetythermostat.- Size E0, E1, E2: one working step.- Size E3: two working steps.- Size E4, E5, E6: three working steps.
Hot water heating system:Components:- Hot water cooling coil with copper tubes, aluminium fins and galvanized steel frame.- 2-way motorized valve for water flow regulation with 0÷10 VDC control actuator and
emergency manual control. Nominal operating pressure up to 1600 kPa and closing
pressure (Δps) of 1400 kPa. Automatic Summer/Winter changeover (for comfort working mode, optional accessoryavailable only with the hot water heating system).Components:- Ambient air temperature sensor.
Compressor capacitor for power factor - cos 0,9 (only for on/off compressors).
Phase sequence control relay for compressor (only for on/off compressors).
Automatic system for the air pressure control in the under floor / air delivery duct. Thesystem controls the supply fans rotation speed in order to keep constant the air pressurein the under floor / air delivery duct, or in general, the air delivery of the machine, via adifferential pressure transmitter connected to the microprocessor control.
Washable air filter with F5 efficiency (size E0 excluded).
Blind frontal panel for OVER version (size E0 excluded).The accessory allows the intake air from the bottom of the machine.
Differential pressure switch on the air side for clogged filters alarm signal.Underfloor water alarm through sensor to be placed on the floor.
Additional underfloor water sensor kit.
Combined Temperature / Humidity sensor on air.
Combined Temperature / Humidity sensor for outdoor installation.
8/10/2019 t Nxtevin 0313 Gb
http://slidepdf.com/reader/full/t-nxtevin-0313-gb 8/56
8 RC GROUP S.p.A. ● T_NXTEVINV_0313_ GB ● R410A
Combined Temperature / Humidity sensor for remote installation. The optional is added tothe standard sensor on machine air suction.
Microprocessor control accessories:- Remote terminal.- Serial port MBUS RS485/JBUS.- Serial port LON.- Serial port BACnet for Ethernet – SNMP – TCP/IP.
- Serial port BACnet for MS/TP.- Double serial port MBUS RS485/JBUS + BACnet for Ethernet – SNMP – TCP/IP.- Double serial port MBUS RS485/JBUS + BACnet for MS/TP.- Temporary microprocessor power supply. The system guarantees the
microprocessor power supply for a few minutes, in case of supply voltage failure.
WARNINGRC GROUP reserves the right to accept the matching of the optional installed on themachine.
8/10/2019 t Nxtevin 0313 Gb
http://slidepdf.com/reader/full/t-nxtevin-0313-gb 9/56
9RC GROUP S.p.A. ● T_NXTEVINV_0313_ GB ● R410A
WORKING LOGIC
COOLING CAPACITY CONTROLThe cooling capacity control is made on the air delivery temperature.
The inverter driven compressor can change the load continuously and the regulation of therefrigerant circuit can be easily adapted, without oscillations and transients, to the operatingconditions required.The system is highly efficient because it is supplying only the energy necessary to satisfy the
required thermal load; furthermore the system can supply cooling capacity even in case ofoverload conditions.
EQUIPMENTSmall size models are equipped with a single inverter driven orbiting spiral (SCROLL)hermetic compressor. Medium and big size models are equipped with one inverter drivenmain compressor and one or two ON/OFF orbiting spiral (SCROLL) hermetic compressors.
SERIES DESCRIPTIONModels: 007, 010, 016, 020, 028.
Units with single refrigerant circuit equipped with:Nr.1 inverter driven orbiting spiral (SCROLL) hermetic compressor.
OPERATING CONDITIONS AT INCREASING THERMAL LOADS1. BLCD inverter driven compressor start.
1.- 2. The compressor increases its rotation speed up to the maximum cooling capacityfollowing the increase of cooling demand.
2. Achievement of the maximum cooling capacity of the a/c unit.The compressor is at 100%.
OPERATING CONDITIONS AT DECREASING THERMAL LOADS2. Maximum cooling capacity of the a/c unit.
2.- 1. The compressor decreases its rotation speed down to the minimum cooling capacityfollowing the decrease of cooling demand.
1. Achievement of the minimum rotation speed of the compressor. Shut down of the
compressor.
100%
C1
C o m p r e s s o r ‘ s
c o o l i n g c a p a c i t y
( % )
TimeC1-ON
C1Inverter driven
1. 3.
Increasing thermal loads
Decreasing thermal loads
Off. Threshold Sup T (°C)
Cooling
Setpoint
Cooling req.
8/10/2019 t Nxtevin 0313 Gb
http://slidepdf.com/reader/full/t-nxtevin-0313-gb 10/56
10 RC GROUP S.p.A. ● T_NXTEVINV_0313_ GB ● R410A
Models: 034, 040.
Units with single refrigerant circuit equipped with:Nr.1 inverter driven orbiting spiral (SCROLL) hermetic compressor. Nr.1 ON/OFF orbiting spiral (SCROLL) hermetic compressor.
OPERATING CONDITIONS AT INCREASING THERMAL LOADS1. BLCD inverter driven compressor start.
1.- 2. The compressor increases its rotation speed up to the maximum cooling capacityfollowing the increase of cooling demand.
2. ON/OFF compressor start and consequent reduction of the BLCD inverter drivencompressor rotation speed to adapt itself to the changes in requested coolingcapacity.
2.- 3. The ON/OFF compressor is at 100%. The BLCD inverter driven compressorincreases its rotation speed up to the maximum cooling capacity following theincrease of cooling demand.
3. Achievement of the maximum cooling capacity of the a/c unit.Both compressors are at 100%.
OPERATING CONDITIONS AT DECREASING THERMAL LOADS3. Maximum cooling capacity of the machine; both compressors are at 100%.
3.- 2. The ON/OFF compressor is at 100%; the BLCD inverter driven compressordecreases its rotation speed down to the minimum cooling capacity following thedecrease of cooling demand.
2. ON/OFF compressor shut down and consequent increase of the BLCD inverterdriven compressor rotation speed to adapt itself to the changes in requested coolingcapacity.
2.- 1. The BLCD inverter driven compressor decreases its rotation speed down to theminimum cooling capacity following the decrease of cooling demand.
1. Achievement of the minimum rotation speed of the compressor. Shut down of thecompressor.
100%
C1
100%
C1+C2
TimeC1-ON
C2-OFF
C1-ON
C2-ON
C1Inverter driven
C2ON/OFF
C1Inverter driven C
o m p r e s s o r s
c o o l i n g c a p a c i t y ( % )
Increasing thermal loads
Decreasing thermal loads
1. 2. 3.
8/10/2019 t Nxtevin 0313 Gb
http://slidepdf.com/reader/full/t-nxtevin-0313-gb 11/56
11RC GROUP S.p.A. ● T_NXTEVINV_0313_ GB ● R410A
Models: 053, 057.
Units with single refrigerant circuit equipped with:Nr.1 inverter driven orbiting spiral (SCROLL) hermetic compressor. Nr.2 ON/OFF orbiting spiral (SCROLL) hermetic compressors.
OPERATION AT INCREASING THERMAL LOADS1. BLCD inverter driven compressor start.
1.- 2. The compressor increases its rotation speed up to the maximum cooling capacityfollowing the increase of cooling demand.
2. First ON/OFF compressor start and consequently reduction of the BLCD inverterdriven compressor rotation speed to adapt itself to the changes in requested cooling
capacity.2.- 3. The first ON/OFF compressor is at 100%. The BLCD inverter driven compressor
increases its rotation speed up to the maximum cooling capacity following theincrease of cooling demand.
3. Second ON/OFF compressor start and consequent reduction of the BLCD inverterdriven compressor rotation speed to adapt itself to the changes in requested coolingcapacity.
3.- 4. Both ON/OFF compressors are at 100%. The BLCD inverter driven compressorincreases its rotation speed up to the maximum cooling capacity following theincrease of cooling demand.
4. Achievement the maximum cooling capacity of the a/c unit; all the compressors areat 100%.
OPERATION AT DECREASING THERMAL LOADS4. Maximum cooling capacity of the machine; All the compressors are at 100%.
4.- 3. Both ON/OFF compressors are at 100%. The BLCD inverter driven compressordecreases its rotation speed down to the minimum cooling capacity following thedecrease of cooling demand.
3. Second ON/OFF compressor shut down with the first at 100% and consequentreduction of the BLCD inverter driven compressor rotation speed to adapt itself to thechanges in requested cooling capacity.
3.- 2. With the first ON/OFF compressor at 100%, the BLCD inverter driven compressordecreases its rotation speed down to the minimum cooling capacity following thedecrease of cooling demand.
2. First ON/OFF compressor shut down and consequent increase of the BLCD inverterdriven compressor rotation speed to adapt itself to the changes in requested coolingcapacity.
2.- 1. Both ON/OFF compressors are off; the BLCD inverter driven compressor decreasesits rotation speed down to the minimum cooling capacity following the decrease ofcooling demand.
1. Achievement of the minimum rotation speed of the compressor. Shut down of thecompressor. All the compressor are off.
100%
C1
100%
C1+C2
100%
C1+C2+C3
C1Inverter driven
C1-ON
C2-OFF
C1-ON
C2-ON
C1-ON
C2-ON
C3-OFF C3-OFF C3-ON
C o m p r e s s o r s
c o o l i n g c a p a c i t y ( % )
Time
C1Inverter driven
C1Inverter driven
C3ON/OFF
C2ON/OFF
Increasing thermal loads
Decreasing thermal loads
1. 2. 3. 4.
8/10/2019 t Nxtevin 0313 Gb
http://slidepdf.com/reader/full/t-nxtevin-0313-gb 12/56
12 RC GROUP S.p.A. ● T_NXTEVINV_0313_ GB ● R410A
AIR FLOW CONTROL ACCORDING TO AIR RETURN TEMPERATUREThe plug fans modulate the air flow using as variable the distance from the temperaturesetpoint.It’s possible to define the minimum and maximum air flow through dedicated parameters.
A third level, lower than the minimum settable, can be reached by the unit in the followingoperating conditions:
"Standby" (the unit is ON, but without cooling request) with the target of granting the
minimum air flow necessary to allow correct ambient temperature reading at theprobes.
“Dehumidification” (dehumidification only operating condition) with the target ofamplifying the deumidification effect over the handled air.
AIR FLOW CONTROL AS FUNCTION OF THE UNDERFLOOR PRESSUREThe plug fans modulate the air flow using as variable the distance of a signal, coming from adifferential pressure probe, from the set point. It’s possible to define the minimum and maximum air flow through dedicated parameters.
Cooling req.
Air flow
SetpointHeating
threshold
Air flow
Coff diffHoff diff
Heating
Heating req.
Ret T (°C)
Air flow
Differential
Pressure (Pa)
Setpoint
8/10/2019 t Nxtevin 0313 Gb
http://slidepdf.com/reader/full/t-nxtevin-0313-gb 13/56
13RC GROUP S.p.A. ● T_NXTEVINV_0313_ GB ● R410A
TECHNICAL DATA - NEXT EVO INV Over / Under
MODEL 007M1 010M1S S
SIZE E0 E1COOLING CAPACITY (1) Min Nom Max Min Nom Max
Total kW 7,30 8,52 9,50 8,73 11,60 17,30Sensible kW 6,46 7,03 7,57 8,73 10,30 13,30Compressors operating power input kW 1,63 2,34 3,10 1,49 2,76 7,33Compressors operating current [OA] A 2,61 3,75 4,98 2,38 4,43 11,80
SUPPLY FANS n. 1 1 1 1 1 1 Air flow m /h 1800 1800 1800 2700 2700 2700Nominal external static pressure Over Pa 20 20 20 30 30 30Nominal external static pressure Under Pa 20 20 20 20 20 20Max external static pressure Pa 80 80 80 52 52 52Operating power input Over (2) kW 0,10 0,10 0,10 0,30 0,30 0,30Operating power input Under (2) kW 0,10 0,10 0,10 0,29 0,29 0,29Max power input kW 0,15 0,15 0,15 0,36 0,36 0,36Operating current Over [OA] A 0,81 0,81 0,81 1,87 1,87 1,87Operating current Under [OA] A 0,81 0,81 0,81 1,79 1,79 1,79Max operating current [FLA] A 1,23 1,23 1,23 2,20 2,20 2,20
COMPRESSORSINVERTER compressors number n. 1 1On/Off compressors number n. -- --Max current [FLA] A 5,6 14,9Total starting current [LRA] A 3,0 3,0Cooling Capacity Control modulating modulatingOPERATING CONDITIONSINVERTER compressor cps 40 50 60 40 60 120On/Off compressor – 1 -- -- -- -- -- --On/Off compressor – 2 -- -- -- -- -- --
AIR FILTERS n. 1 1Efficiency G2 G4
REFRIGERANT R410A R410ARefrigerant charge (3) kg 2,5 2,8Gas circuits n. 1 1
POWER SUPPLY V/Ph/Hz 400/3/50
400/3/50
ENERGY EFFICIENCY INDEXES (1)
EER – Energy Efficiency Ratio (4) kW/kW 3,69 3,17 2,75 4,00 3,36 2,16SOUND PRESSURE LEVEL – ISO 3744 (5)
On air delivery Over dB(A) 51,0 51,0 51,0 58,4 58,4 58,4On air delivery Under dB(A) 51,0 51,0 51,0 58,2 58,2 58,2On air intake Over dB(A) 45,1 45,1 45,1 47,3 47,3 47,3Irradiated Over dB(A) 35,0 35,0 35,0 40,3 40,3 40,3On air intake Under dB(A) 45,1 45,1 45,1 49,9 49,9 49,9On front side Under dB(A) 45,1 45,1 45,1 40,5 40,5 40,5
DIMENSIONSLength mm 655 650Width mm 445 675Height mm 1680 1925
NET WEIGHT Over kg 170 230NET WEIGHT Under kg 180 240REMOTE CONDENSER (6)
TEAM MATE n x Mod. 1 x M 11 1 x M 20TEAM MATE PF n x Mod. 1 x T 11 1 x T 21
REFRIGERANT CONNECTIONSGas delivery ODS Ø 12 12Liquid return ODS Ø 12 12
CONNECTIONS ISO 228/1-GCondensate discharge – rubber pipe F Ø 1/2" 1/2"
THE COOLING CAPACITY DOES NOT CONSIDER THE SUPPLY FAN MOTOR THERMAL LOAD1. Gross value - Characteristics referred to entering air at 24°C-50%RH; 35°C ambient temperature.2. Corresponding to the nominal external static pressure3. Unit refrigerant charge. Remote condenser, connections pipes and optional are excluded.4. The Energy Efficiency Index consider also the remote air cooled condenser as shown in the table.5. Noise level at 1 meter in free field (external static pressure at nominal conditions)6. For matching to other remote air cooled condensers please refer to RC WORLD selection program
8/10/2019 t Nxtevin 0313 Gb
http://slidepdf.com/reader/full/t-nxtevin-0313-gb 14/56
14 RC GROUP S.p.A. ● T_NXTEVINV_0313_ GB ● R410A
TECHNICAL DATA - NEXT EVO INV Over / Under
MODEL 016M1 020M1S S
SIZE E2 E3COOLING CAPACITY (1) Min Nom Max Min Nom Max
Total kW 13,50 18,00 21,30 15,20 22,50 31,00Sensible kW 13,40 16,40 18,10 15,20 21,30 26,60
Compressors operating power input kW 2,61 4,74 7,11 2,46 5,40 11,20Compressors operating current [OA] A 4,15 7,57 11,40 3,90 8,62 17,90
SUPPLY FANS n. 1 1 1 1 1 1 Air flow m /h 4000 4475 4475 5500 6000 6600Nominal external static pressure Over Pa 50 50 50 50 50 50Nominal external static pressure Under Pa 20 20 20 20 20 20Max external static pressure Pa 175 175 175 628 628 628Operating power input Over (2) kW 0,53 0,73 0,73 0,64 0,81 1,05Operating power input Under (2) kW 0,49 0,67 0,67 0,58 0,74 0,98Max power input kW 0,97 0,97 0,97 2,68 2,68 2,68Operating current Over [OA] A 0,94 1,28 1,28 0,96 1,22 1,58Operating current Under [OA] A 0,86 1,19 1,19 0,87 1,11 1,47Max operating current [FLA] A 1,70 1,70 1,70 4,18 4,18 4,18
COMPRESSORSINVERTER compressors number n. 1 1
On/Off compressors number n. -- --Max current [FLA] A 7,8 22,9Total starting current [LRA] A 4,0 4,0Cooling Capacity Control modulating modulatingOPERATING CONDITIONSINVERTER compressor cps 40 60 80 40 70 120On/Off compressor – 1 -- -- -- -- -- --On/Off compressor – 2 -- -- -- -- -- --
AIR FILTERS n. 1 2Efficiency G4 G4
REFRIGERANT R410A R410ARefrigerant charge (3) kg 3,1 3,7Gas circuits n. 1 1
POWER SUPPLY V/Ph/Hz 400/3/50
400/3/50 ENERGY EFFICIENCY INDEXES (1)
EER – Energy Efficiency Ratio (4) kW/kW 3,68 3,00 2,54 4,19 3,34 2,43SOUND PRESSURE LEVEL – ISO 3744 (5)
On air delivery Over dB(A) 61,1 63,3 63,3 61,1 62,9 64,9On air delivery Under dB(A) 60,6 63,0 63,0 60,8 62,6 64,7On air intake Over dB(A) 49,5 51,1 51,1 49,5 50,8 52,3Irradiated Over dB(A) 43,0 45,2 45,2 43,0 44,8 46,8On air intake Under dB(A) 52,3 54,5 54,5 52,4 54,2 56,1On front side Under dB(A) 42,9 45,1 45,1 43,0 44,8 46,7
DIMENSIONSLength mm 785 1085Width mm 675 775Height mm 1925 1925
NET WEIGHT Over kg 270 310NET WEIGHT Under kg 280 330REMOTE CONDENSER (6)
TEAM MATE n x Mod. 1 x M 25 1 x M 35TEAM MATE PF n x Mod. 1 x T 24 1 x T 33
REFRIGERANT CONNECTIONSGas delivery ODS Ø 16 16Liquid return ODS Ø 12 16
CONNECTIONS ISO 228/1-GCondensate discharge – rubber pipe F Ø 1/2" 1/2"
THE COOLING CAPACITY DOES NOT CONSIDER THE SUPPLY FAN MOTOR THERMAL LOAD1. Gross value - Characteristics referred to entering air at 24°C-50%RH; 35°C ambient temperature.2. Corresponding to the nominal external static pressure3. Unit refrigerant charge. Remote condenser, connections pipes and optional are excluded.4. The Energy Efficiency Index consider also the remote air cooled condenser as shown in the table.5. Noise level at 1 meter in free field (external static pressure at nominal conditions)6. For matching to other remote air cooled condensers please refer to RC WORLD selection program
8/10/2019 t Nxtevin 0313 Gb
http://slidepdf.com/reader/full/t-nxtevin-0313-gb 15/56
15RC GROUP S.p.A. ● T_NXTEVINV_0313_ GB ● R410A
TECHNICAL DATA - NEXT EVO INV Over / Under
MODEL 028M1 034M2S S
SIZE E4 E4COOLING CAPACITY (1) Min Nom Max Min Nom Max
Total kW 16,70 28,10 37,00 16,90 35,00 50,20Sensible kW 16,70 28,10 37,00 16,90 35,00 45,50
Compressors operating power input kW 2,42 6,30 10,80 2,35 7,25 16,30Compressors operating current [OA] A 3,81 9,99 17,20 3,69 12,80 27,40
SUPPLY FANS n. 1 1 1 1 1 1 Air flow m /h 7500 9500 12200 7500 11000 12200Nominal external static pressure Over Pa 50 50 50 50 50 50Nominal external static pressure Under Pa 20 20 20 20 20 20Max external static pressure Pa 131 131 131 258 258 258Operating power input Over (2) kW 0,60 1,10 2,16 0,60 1,63 2,16Operating power input Under (2) kW 0,44 0,86 1,77 0,44 1,31 1,77Max power input kW 2,77 2,77 2,77 2,77 2,77 2,77Operating current Over [OA] A 0,91 1,68 3,30 0,91 2,48 3,30Operating current Under [OA] A 0,72 1,39 2,85 0,72 2,11 2,85Max operating current [FLA] A 4,30 4,30 4,30 4,30 4,30 4,30
COMPRESSORSINVERTER compressors number n. 1 1
On/Off compressors number n. -- 1Max current [FLA] A 22,9 36,0Total starting current [LRA] A 4,0 62,8Cooling Capacity Control modulating modulatingOPERATING CONDITIONSINVERTER compressor cps 40 80 120 40 40 120On/Off compressor – 1 -- -- -- off on onOn/Off compressor – 2 -- -- -- -- -- --
AIR FILTERS n. 3 3Efficiency G4 G4
REFRIGERANT R410A R410ARefrigerant charge (3) kg 4,9 5,2Gas circuits n. 1 1
POWER SUPPLY V/Ph/Hz 400/3/50+N 400/3/50+NENERGY EFFICIENCY INDEXES (1)
EER – Energy Efficiency Ratio (4) kW/kW 4,39 3,44 2,69 4,19 3,51 2,57SOUND PRESSURE LEVEL – ISO 3744 (5)
On air delivery Over dB(A) 59,4 64,1 69,3 59,4 67,1 69,3On air delivery Under dB(A) 57,7 62,8 68,2 57,7 65,9 68,2On air intake Over dB(A) 48,5 51,7 56,2 49,6 54,5 56,3Irradiated Over dB(A) 41,3 46,0 51,2 41,5 49,0 51,2On air intake Under dB(A) 49,7 54,3 59,6 50,0 57,5 59,6On front side Under dB(A) 40,3 44,9 50,2 40,7 48,0 50,2
DIMENSIONSLength mm 1305 1305Width mm 930 930Height mm 1980 1980
NET WEIGHT Over kg 420 460NET WEIGHT Under kg 430 470REMOTE CONDENSER (6)
TEAM MATE n x Mod. 1 x M 45 1 x M 60TEAM MATE PF n x Mod. 1 x T 44 1 x T 58
REFRIGERANT CONNECTIONSGas delivery ODS Ø 16 18Liquid return ODS Ø 16 16
CONNECTIONS ISO 228/1-GCondensate discharge – rubber pipe F Ø 1/2" 1/2"
THE COOLING CAPACITY DOES NOT CONSIDER THE SUPPLY FAN MOTOR THERMAL LOAD1. Gross value - Characteristics referred to entering air at 24°C-50%RH; 35°C ambient temperature.2. Corresponding to the nominal external static pressure3. Unit refrigerant charge. Remote condenser, connections pipes and optional are excluded.4. The Energy Efficiency Index consider also the remote air cooled condenser as shown in the table.5. Noise level at 1 meter in free field (external static pressure at nominal conditions)6. For matching to other remote air cooled condensers please refer to RC WORLD selection program
8/10/2019 t Nxtevin 0313 Gb
http://slidepdf.com/reader/full/t-nxtevin-0313-gb 16/56
16 RC GROUP S.p.A. ● T_NXTEVINV_0313_ GB ● R410A
TECHNICAL DATA - NEXT EVO INV Over / Under
MODEL 040M2 053M3S S
SIZE E5 E5COOLING CAPACITY (1) Min Nom Max Min Nom Max
Total kW 16,80 40,80 52,90 17,00 54,20 69,10Sensible kW 16,80 40,80 52,70 17,00 53,00 60,30
Compressors operating power input kW 2,34 9,45 16,60 2,25 11,80 20,30Compressors operating current [OA] A 3,69 16,40 27,90 3,56 21,30 35,20
SUPPLY FANS n. 2 2 2 2 2 2 Air flow m /h 6500 12500 15500 6500 15500 15500Nominal external static pressure Over Pa 50 50 50 50 50 50Nominal external static pressure Under Pa 20 20 20 20 20 20Max external static pressure Pa 775 775 775 520 520 520Operating power input Over (2) kW 0,29 1,41 2,54 0,29 2,54 2,54Operating power input Under (2) kW 0,21 1,28 2,38 0,21 2,38 2,38Max power input kW 5,36 5,36 5,36 5,36 5,36 5,36Operating current Over [OA] A 0,43 2,12 3,82 0,43 3,82 3,82Operating current Under [OA] A 0,32 1,93 3,59 0,32 3,59 3,59Max operating current [FLA] A 8,36 8,36 8,36 8,36 8,36 8,36
COMPRESSORSINVERTER compressors number n. 1 1
On/Off compressors number n. 1 2Max current [FLA] A 36,0 49,1Total starting current [LRA] A 62,8 75,9Cooling Capacity Control modulating modulatingOPERATING CONDITIONSINVERTER compressor cps 40 60 120 40 40 120On/Off compressor – 1 off on on off on onOn/Off compressor – 2 -- -- -- off on on
AIR FILTERS n. 3 3Efficiency G4 G4
REFRIGERANT R410A R410ARefrigerant charge (3) kg 7,5 7,6Gas circuits n. 1 1
POWER SUPPLY V/Ph/Hz 400/3/50+N 400/3/50+NENERGY EFFICIENCY INDEXES (1)
EER – Energy Efficiency Ratio (4) kW/kW 4,53 3,42 2,62 4,12 3,40 2,83SOUND PRESSURE LEVEL – ISO 3744 (5)
On air delivery Over dB(A) 53,0 66,1 70,7 53,0 70,7 70,7On air delivery Under dB(A) 52,1 66,0 70,6 52,1 70,6 70,6On air intake Over dB(A) 47,8 53,7 57,6 48,7 57,7 57,7Irradiated Over dB(A) 37,0 48,0 52,6 37,5 52,6 52,6On air intake Under dB(A) 46,3 57,5 62,0 46,8 62,0 62,0On front side Under dB(A) 37,2 48,1 52,6 37,7 52,6 52,6
DIMENSIONSLength mm 1630 1630Width mm 930 930Height mm 1980 1980
NET WEIGHT Over kg 540 590NET WEIGHT Under kg 550 600REMOTE CONDENSER (6)
TEAM MATE n x Mod. 1 x M 60 1 x M 95TEAM MATE PF n x Mod. 1 x T 69 1 x T 86
REFRIGERANT CONNECTIONSGas delivery ODS Ø 18 18Liquid return ODS Ø 18 18
CONNECTIONS ISO 228/1-GCondensate discharge – rubber pipe F Ø 1/2" 1/2"
THE COOLING CAPACITY DOES NOT CONSIDER THE SUPPLY FAN MOTOR THERMAL LOAD1. Gross value - Characteristics referred to entering air at 24°C-50%RH; 35°C ambient temperature.2. Corresponding to the nominal external static pressure3. Unit refrigerant charge. Remote condenser, connections pipes and optional are excluded.4. The Energy Efficiency Index consider also the remote air cooled condenser as shown in the table.5. Noise level at 1 meter in free field (external static pressure at nominal conditions)6. For matching to other remote air cooled condensers please refer to RC WORLD selection program
8/10/2019 t Nxtevin 0313 Gb
http://slidepdf.com/reader/full/t-nxtevin-0313-gb 17/56
17RC GROUP S.p.A. ● T_NXTEVINV_0313_ GB ● R410A
TECHNICAL DATA - NEXT EVO INV Over / Under
MODEL 057M3S
SIZE E6COOLING CAPACITY (1) Min Nom Max
Total kW 17,70 60,60 71,40Sensible kW 17,70 59,70 65,30
Compressors operating power input kW 2,27 14,00 20,60Compressors operating current [OA] A 3,56 24,90 35,60
SUPPLY FANS n. 2 2 2 Air flow m /h 8000 18000 18000Nominal external static pressure Over Pa 50 50 50Nominal external static pressure Under Pa 20 20 20Max external static pressure Pa 511 511 511Operating power input Over (2) kW 0,36 2,80 2,80Operating power input Under (2) kW 0,27 2,62 2,62Max power input kW 5,80 5,80 5,80Operating current Over [OA] A 0,54 4,18 4,18Operating current Under [OA] A 0,41 3,90 3,90Max operating current [FLA] A 8,86 8,86 8,86
COMPRESSORSINVERTER compressors number n. 1
On/Off compressors number n. 2Max current [FLA] A 49,1Total starting current [LRA] A 75,9Cooling Capacity Control modulatingOPERATING CONDITIONSINVERTER compressor cps 40 60 120On/Off compressor – 1 off on onOn/Off compressor – 2 off on on
AIR FILTERS n. 4Efficiency G4
REFRIGERANT R410ARefrigerant charge (3) kg 8,2Gas circuits n. 1
POWER SUPPLY V/Ph/Hz 400/3/50+NENERGY EFFICIENCY INDEXES (1)
EER – Energy Efficiency Ratio (4) kW/kW 4,19 3,30 2,86SOUND PRESSURE LEVEL – ISO 3744 (5)
On air delivery Over dB(A) 50,8 67,8 67,8On air delivery Under dB(A) 50,3 67,9 67,9On air intake Over dB(A) 48,5 55,3 55,3Irradiated Over dB(A) 36,7 49,7 49,7On air intake Under dB(A) 46,1 59,3 59,3On front side Under dB(A) 37,0 49,9 49,9
DIMENSIONSLength mm 1875Width mm 930Height mm 1980
NET WEIGHT Over kg 630NET WEIGHT Under kg 640REMOTE CONDENSER (6)
TEAM MATE n x Mod. 1 x M 95TEAM MATE PF n x Mod. 1 x T 86
REFRIGERANT CONNECTIONSGas delivery ODS Ø 18Liquid return ODS Ø 18
CONNECTIONS ISO 228/1-GCondensate discharge – rubber pipe F Ø 1/2"
THE COOLING CAPACITY DOES NOT CONSIDER THE SUPPLY FAN MOTOR THERMAL LOAD1. Gross value - Characteristics referred to entering air at 24°C-50%RH; 35°C ambient temperature.2. Corresponding to the nominal external static pressure3. Unit refrigerant charge. Remote condenser, connections pipes and optional are excluded.4. The Energy Efficiency Index consider also the remote air cooled condenser as shown in the table.5. Noise level at 1 meter in free field (external static pressure at nominal conditions)6. For matching to other remote air cooled condensers please refer to RC WORLD selection program
8/10/2019 t Nxtevin 0313 Gb
http://slidepdf.com/reader/full/t-nxtevin-0313-gb 18/56
18 RC GROUP S.p.A. ● T_NXTEVINV_0313_ GB ● R410A
ACCESSORIES TECHNICAL DATA - NEXT EVO INV DX Over / Under
MODEL 007M1 010M1 016M1 020M1 028M1S S S S S
SIZE E0 E1 E2 E3 E4ELECTRIC HEATER
Capacity kW 2,5 5,1 5,1 6 9
Operating current [OA] A 11,0 7,4 7,4 8,7 13Capacity steps n. 1 1 1 2 3HUMIDIFIER
Steam capacity kg/h 2 3 3 3 8Power input kW 1,4 2,3 2,3 2,3 6Operating current [OA] A 6,1 3,2 3,2 3,2 8,7Max operating current [FLA] A 8,8 8,8 8,8 8,8 12,4
EXTRA CIRCUIT COIL (1)Total cooling capacity kW - 11,0 18,1 24,7 39,0Sensible cooling capacity kW - 10,0 16,5 22,4 35,4Water flow rate m /h - 1,72 2,83 3,86 6,09dP coil + valve kPa - 18 50 36 27Water volume l - 4,2 5,3 7,8 13,8
HEATING COIL (2)Heating capacity kW 12,6 24,1 36,2 50,5 81,4
Water flow rate m /h 0,74 1,41 2,12 2,96 4,77dP coil + valve kPa 15 28 27 29 15Water volume l 0,7 2,1 2,6 3,9 6,9
CONNECTIONS ISO 228/1-GExtra Circuit inlet/outlet M Ø - 1" 1" 1+1/4" 1+1/2"Hot water Inlet/outlet M Ø 3/4" 3/4" 3/4" 1" 1+1/4"Humidifier filling F Ø 3/4" 3/4" 3/4" 3/4" 3/4"
MODEL 034M2 040M2 053M3 057M3S S S S
SIZE E4 E5 E5 E6ELECTRIC HEATER
Capacity kW 9,0 13,5 13,5 13,5Operating current [OA] A 13,0 19,5 19,5 19,5Capacity steps n. 3 3 3 3
HUMIDIFIERSteam capacity kg/h 8 8 8 8Power input kW 6 6 6 6Operating current [OA] A 8,7 8,7 8,7 8,7Max operating current [FLA] A 12,4 12,4 12,4 12,4
EXTRA CIRCUIT COIL (1)Total cooling capacity kW 43,3 55,4 64,2 69,5Sensible cooling capacity kW 39,4 49,7 59,0 63,3Water flow rate m /h 6,76 8,65 10,00 10,80dP coil + valve kPa 33 41 54 34Water volume l 13,8 18,1 18,1 21,2
HEATING COIL (2)
Heating capacity kW 89,8 109,0 126,0 148,0Water flow rate m /h 5,26 6,38 7,37 8,66dP coil + valve kPa 18 29 38 55Water volume l 6,9 9,1 9,1 10,6
CONNECTIONS ISO 228/1-GExtra Circuit inlet/outlet M Ø 1+1/2" 2" 2" 2"Hot water Inlet/outlet M Ø 1+1/4" 1+1/2" 1+1/2" 1+1/2"Humidifier filling F Ø 3/4" 3/4" 3/4" 3/4"
THE COOLING/HEATING CAPACITY DOES NOT CONSIDER THE SUPPLY FAN MOTOR THERMAL LOAD1. Characteristics referred to entering air at 24°C 50%RH with chiller water at 7/12,5 °C and 0% glycol2. Characteristics referred to entering air at 20°C with hot water at 75/60°C
WARNINGAccessories technical data referred to nominal conditions
8/10/2019 t Nxtevin 0313 Gb
http://slidepdf.com/reader/full/t-nxtevin-0313-gb 19/56
19RC GROUP S.p.A. ● T_NXTEVINV_0313_ GB ● R410A
ELECTRICAL DATA
MAXIMUM ELECTRICAL ABSORPTION CALCULATIONThis chapter has the aim to explain the calculation of the maximum absorbed current by theunit (A), corresponding to extreme working conditions.
Example in cooling mode for unit NEXT EVO INV DX S U 010 M 1 E1
COOLING (1)- Main fans (FLA) A 2,2 +- Compressor (FLA) A 14,9 +- Electric heaters (OA) A 7.4 =Absorbed current A 24,5
COOLING (2)- Main fans (FLA) A 2,2 +- Compressor (FLA) A 14,9 +- Humidifier (FLA) A 8,8 =Absorbed current A 25,9
HEATING (3)- Main fans (FLA) A 2,2 +
- Electric heaters (OA) A 7.4 +- Humidifier (FLA) A 8,8 =Absorbed current A 18,4
The COOLING (2) working condition corresponds to the unit maximum electric absorption.
IMPORTANTFor the fans, the current nominal values have been considered equal to the data platevalues. For this reason, the nominal current and the data plate current are the same.Actually, the real absorbed current is normally lower than the data plate value.These values depend on the unit working conditions and on the type of control of theplant.
8/10/2019 t Nxtevin 0313 Gb
http://slidepdf.com/reader/full/t-nxtevin-0313-gb 20/56
20 RC GROUP S.p.A. ● T_NXTEVINV_0313_ GB ● R410A
MICROPROCESSOR CONTROL SYSTEM
The microprocessor control system is equipped with 6 keys terminal and back lighted graphicdisplay on which all information in different languages or easily identifiable symbols aredisplayed.The system disposes of a “flash” memory that preserves the information even in absence ofpower supply.
KEYBOARD FUNCTIONS
Stops the alarm acoustic signal and displays the alarms screen.By pressing "2" or "4" keys all the alarms that may be present will be displayed.The flashing red backlighting of the key indicates the presence of an alarm.
Scrolls the pages of each menu and allows the modification of the numeric and/oralphanumeric values of the control.By pressing “2” or “4” key, from the main screen, the information screen of theinstalled software is displayed.
Shifts the cursor in the editable fields of the screen.Confirm the new value and leave the menu.
Scrolls the pages of each menu and allows the modification of the numeric and/oralphanumeric values of the control.By pressing “2” or “4” key, from the main screen, the information screen of theinstalled software is displayed.
Esc keyDisplays the main screen.
Allows the access to the screen scrolling menu. Scrolling menu by pressing keys “2”or “4”. Confirm the selection by pressing key “3”. Manu and control list:
Machine working status
Set-points
Alarms reset
Service parameter sets (protected by password)
Intervened alarms history
Manual operation of the main components (protected by password)
Date and time setCommunication system set
Machine switch On/Off
LAN network set
8/10/2019 t Nxtevin 0313 Gb
http://slidepdf.com/reader/full/t-nxtevin-0313-gb 21/56
21RC GROUP S.p.A. ● T_NXTEVINV_0313_ GB ● R410A
REMOTE CONTROLS/ALARMS
INLETS
1 External enabling • 2 Heating enabling • 3 Extra circuit enabling •
4 Emergency machine stop with external alarm signalling • 5 Power supply from UPS •
OUTLETS
1 Configurable general alarm – deviating contact •• 2 Configurable general alarm – deviating contact •• 3 Machine operating status ••
• controls/alarms for remotization •• voltage free controls/alarms for remotization
8/10/2019 t Nxtevin 0313 Gb
http://slidepdf.com/reader/full/t-nxtevin-0313-gb 22/56
22 RC GROUP S.p.A. ● T_NXTEVINV_0313_ GB ● R410A
8 0
2 5 0
70 7070 A
1 2 5
1 3 0
70 A70
POSSIBLE AIR INTAKE FOR OVER VERSIONS
AIR INTAKE FROM THE BOTTOM(Size E0 excluded)Thanks to the particular basement design, it is possible to have the unit air intake from thebottom side.With this solution it is necessary to foresee the frontal panels without grilles.
AIR INTAKE FROM THE BACK SIDE(Size E0 excluded)It is possible to have the unit air intake from the back side.The air intake hole has to be made by Customer during installation.
NEXT EVO INV DX E0 E1 E2 E3 E4 E5 E6
A mm -- 510 645 945 1165 1490 1735Max air flow m
3/h -- 2300 2900 4250 1500 2200 3450
AIR INTAKE FROM THE BACK SIDE
Back side view
NEXT EVO INV OVER
E1 – E2 – E3
NEXT EVO INV OVER
E4 – E5 – E6
8/10/2019 t Nxtevin 0313 Gb
http://slidepdf.com/reader/full/t-nxtevin-0313-gb 23/56
23RC GROUP S.p.A. ● T_NXTEVINV_0313_ GB ● R410A
OPTIONAL ACCESSORIES – REMOTE AIR COOLED CONDENSER
Remote air cooled condenser series TEAM MATE with horizontal air flow, vertical air flow withsupporting leg kit (optional accessories) from coil to fan.
The machines are made with weather resistant materials and suitable for outdoor installation.
Design, assembly and test as per the Company Quality Assurance program in full compliancewith ISO 9001. RC Group has been the first Italian company in its segment to get the ISO9001 in October 13
th, 1991 with certificate ICIM 0018.
The machines are in full compliance with European Norms 2006/42CE, 2006/95CE,2004/108CE, 97/23CE and subsequent amendments.
SERIES IDENTIFICATION
TEAM MATE remote air cooled condensers equipped with axialfans.Nominal capacity : 12,1 ÷ 99,4 kW
The TEAM MATE series is available in 3 versions:
TEAM MATE STD - No air flow and sound levelreduction
TEAM MATE LNO – Air flow reduction at 85% withconsequent sound level reduction.
TEAM MATE ELN – Air flow reduction at 70% withfurther sound level reduction.
TEAM MATE PF remote air cooled condensers equipped withplug fans.Nominal capacity : 12,1 ÷ 91,0 kW
The TEAM MATE series is available in 3 versions:
TEAM MATE PF STD - No air flow and sound levelreduction
TEAM MATE PF LNO – Air flow reduction at 85% withconsequent sound level reduction.
TEAM MATE PF ELN – Air flow reduction at 70% withfurther sound level reduction.
TEAM MATE
TEAM MATE PF
8/10/2019 t Nxtevin 0313 Gb
http://slidepdf.com/reader/full/t-nxtevin-0313-gb 24/56
24 RC GROUP S.p.A. ● T_NXTEVINV_0313_ GB ● R410A
MAIN COMPONENTS
FRAMEWORK
Base, self supporting frame and panelling in steel plate with protective surfacestreatment in compliance with UNI ISO 9227/ASTMB117 and ISO 7253, and paintedwith epoxy powders.
Colour: RAL 9002
FANS SECTION – TEAM MATE
Axial fans with sickle-shaped blades, fan guard and optimized for low noise levels.
External rotor electric motor with stepless variable speed for condensing pressurecontrol.The motor rotation control is obtained according to the 0÷10V proportional signalcoming from the internal unit microprocessor control.
IP54 enclosure class.
FANS SECTION – TEAM MATE PF
Centrifugal fans with backward curved blades with wing profile, single suction andwithout scroll housings (Plug-fans).
Brushless type synchronous EC motor with integrated electronic commutated systemand continuous variation of the rotation speed.
The motor rotation control is obtained with the EC system (Electronic Commutation)that manage the motor according to the 0÷10V proportional signal coming from theinternal unit microprocessor control.
Maintenance-free bearings
IP54 enclosure class.
CONDENSING COIL
Heat exchanger coil with internally corrugated copper tubes and high efficiencyaluminium fins, specifically developed to provide high heat transfer and lowerpressure drops. The combination of two factors, special tubes and fins, allow tooptimally combine the following aspects:- Maximum capacity relative to the size of the exchanger.- Minimum charge of refrigerant.- Reduction of the air flow required for the heat exchange.
Frame in galvanized steel.
REFRIGERANT CIRCUIT
Valves on gas and liquid line for coupling to refrigerant pipe. The valves are suppliednot installed. The condenser is supplied with nitrogen seal.
ELECTRICAL PANELIn accordance with EN60204-1 norms, suitable for outdoor installation, IP54 enclosure class,complete with:
Terminals for power supply (from network).- 400/3/50+N for models “T” - 230/1/50 for models “M”.
Terminals for 0÷10V signal for condensing control system (connect to indoormachine).
Terminals for alarm signal (connect to indoor machine).Fans speed regulator for condensing control (only for TEAM MATE with axial fans).
OPTIONAL ACCESSORY
Support legs for vertical air flow (not available for TEAM MATE PF).
8/10/2019 t Nxtevin 0313 Gb
http://slidepdf.com/reader/full/t-nxtevin-0313-gb 25/56
25RC GROUP S.p.A. ● T_NXTEVINV_0313_ GB ● R410A
TECHNICAL DATA - TEAM MATE
MODELLO M11 M20 M25 M 35 M 45 M 60 M 95
TEAM MATE STD
AXIAL FANS n. 1 1 1 1 2 2 3 Air flow m³/h 4900 6400 9600 9100 12000 16000 28200
Operating power input kW 0,3 0,4 0,5 0,5 0,8 1,1 1,6Max operating current (FLA) A 1,2 1,8 2,9 2,9 3,6 5,7 8,5SOUND PRESSURELEVEL (1) dB(A) 63,0 65,0 67,0 67,0 67,4 69,4 70,5
TEAM MATE LNO
AXIAL FANS n. 1 1 1 1 2 2 3 Air flow m³/h 4165 5440 8160 7735 10200 13600 23970Operating power input kW 0,2 0,3 0,5 0,5 0,7 0,9 1,4Max operating current (FLA) A 1,2 1,2 2,9 2,9 3,6 5,7 8,5SOUND PRESSURELEVEL (1) dB(A) 59,1 61,1 63,1 63,1 63,6 65,5 66,6
TEAM MATE ELN
AXIAL FANS n. 1 1 1 1 2 2 3 Air flow m³/h 3430 4480 6720 6370 8400 11200 19740Operating power input kW 0,2 0,3 0,4 0,4 0,6 0,8 1,1Max operating current (FLA) A 1,2 1,2 2,9 2,9 3,6 5,7 8,5SOUND PRESSURELEVEL (1) dB(A) 54,5 56,5 58,5 58,5 58,9 60,8 61,9
COMMON DATA
POWER SUPPLY V/ph/Hz 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50REFRIGERANT CHARGE (2) kg 0,8 1,7 2,0 4,0 4,7 5,5 8,7DIMENSIONS
Length mm 875 1200 1400 1400 1600 1850 3490Width mm 540 540 665 665 665 665 690Height mm 726 726 1026 1026 1026 1026 1140
NET WEIGHT kg 51,0 72,0 102,0 120,0 153,0 188,0 240,0
1. Sound pressure level [Lp] 1m far according to ISO EN 3744.2. The condenser is supplied with nitrogen seal. For the refrigerant charge consider, in addition to
the these value, even the refrigerant pipes for the connection to the indoor machine andlubricant oil in 10% ratio of charged refrigerant.
ACOUSTIC DATA – TEAM MATE
TEAM MATE STD
MODEL M11 M20 M25 M 35 M 45 M 60 M 95Sound power level [Lw] (1) dB(A) 76,8 79,1 81,8 81,8 82,4 84,5 86,9Sound pressure level at 1m [Lp] (2) dB(A) 63,0 65,0 67,0 67,0 67,4 69,4 70,5Sound pressure level at 5m [Lp] (3) dB(A) 51,3 53,5 56,1 56,1 56,6 58,7 60,6Sound pressure level at 10m [Lp] (3) dB(A) 45,6 47,9 50,5 50,5 51,1 53,2 55,3
TEAM MATE LNO
MODEL M11 M20 M25 M 35 M 45 M 60 M 95
Sound power level [Lw] (1) dB(A) 72,9 75,2 77,9 77,9 78,5 80,7 83,0Sound pressure level at 1m [Lp] (2) dB(A) 59,1 61,1 63,1 63,1 63,6 65,5 66,6Sound pressure level at 5m [Lp] (3) dB(A) 47,4 49,7 52,2 52,2 52,7 54,8 56,7Sound pressure level at 10m [Lp] (3) dB(A) 41,7 44,0 46,6 46,6 47,2 49,3 51,4
TEAM MATE ELN
MODEL M11 M20 M25 M 35 M 45 M 60 M 95Sound power level [Lw] (1) dB(A) 68,2 70.6 73,3 77,9 73,9 76,0 78,4Sound pressure level at 1m [Lp] (2) dB(A) 54,5 56,5 58,5 63,1 58,9 60,8 61,9Sound pressure level at 5m [Lp] (3) dB(A) 42,8 45,0 47,5 52,2 48,1 50,2 52,1Sound pressure level at 10m [Lp] (3) dB(A) 37,1 39,4 42,0 46,6 42,6 44,7 46,8
1. Sound power level [Lw] according to ISO EN 9614 - 2.2. Sound pressure level [Lp] according to ISO EN 37443. Sound pressure level [Lp] in free field contition
IMPORTANT
For further information about units acoustic data, please refer to “The Noise” bulletinof RC GROUP technical literature.
8/10/2019 t Nxtevin 0313 Gb
http://slidepdf.com/reader/full/t-nxtevin-0313-gb 26/56
26 RC GROUP S.p.A. ● T_NXTEVINV_0313_ GB ● R410A
TECHNICAL DATA – TEAM MATE PF
MODELLO T11 T21 T24 T 33 T 44 T 58 T 69 T 86
TEAM MATE PF STD
PLUG FANS n. 1 1 1 1 1 2 2 3 Air flow m³/h 4900 4900 6400 8000 10000 16000 16000 24000External static pressure Pa 50 50 50 50 50 50 50 50Max esternal static pressure Pa 375 290 748 474 268 552 512 542Operating power input kW 0,38 0,52 0,64 1,3 1,2 2,2 2,4 3,3Plate current (FLA) A 1,6 1,6 4,3 4,3 3,6 8,6 8,6 12,9SOUND PRESSURELEVEL (1) dB(A) 61,6 61,5 67,1 72,0 71,3 77,3 77,4 80,3
TEAM MATE PF LNO
PLUG FANS n. 1 1 1 1 1 2 2 3 Air flow m³/h 4165 4165 5440 6800 8500 13600 13600 20400External static pressure Pa 50 50 50 50 50 50 50 50Max esternal static pressure Pa 375 290 748 474 268 552 512 542Operating power input kW 0,26 0,34 0,42 0,83 0,80 1,40 1,51 2,15Plate current (FLA) A 1,6 1,6 4,3 4,3 3,6 8,6 8,6 12,9SOUND PRESSURELEVEL (1) dB(A) 57,7 57,6 63,2 68,1 67,4 73,4 73,5 76,4
TEAM MATE PF ELN
PLUG FANS n. 1 1 1 1 1 2 2 3 Air flow m³/h 3430 3430 4480 5600 7000 11200 11200 16800External static pressure Pa 50 50 50 50 50 50 50 50Max esternal static pressure Pa 375 290 748 474 268 552 512 542Operating power input kW 0,16 0,21 0,26 0,50 0,48 0,84 0,92 1,29Plate current (FLA) A 1,6 1,6 4,3 4,3 3,6 8,6 8,6 12,9SOUND PRESSURELEVEL (1) dB(A) 53,1 53,0 58,6 63,5 62,8 68,8 68,9 71,8
COMMON DATA
POWER SUPPLY V/ph/Hz 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50REFRIGERANT CHARGE (2) kg 0,8 2,6 2,5 3,8 6,4 5,9 8,8 10,2DIMENSIONSLength mm 890 890 1190 1190 1390 1840 1840 2290Width mm 880 880 880 880 880 880 880 880Height mm 900 900 900 900 1300 1300 1300 1300
NET WEIGHT kg 143 163 210 222 310 387 421 515
1. Sound pressure level [Lp] according to ISO EN 37442. The condenser is supplied with nitrogen seal. For the refrigerant charge consider, in addition to
the these value, even the refrigerant pipes for the connection to the indoor machine andlubricant oil in 10% ratio of charged refrigerant.
ACOUSTIC DATA – TEAM MATE PF
TEAM MATE PF STD
MODEL T11 T21 T24 T33 T 44 T 58 T 69 T 86
Sound power level [Lw] (1) dB(A) 76,2 76,1 82,5 87,4 86,8 93,4 93,5 96,9Sound pressure level at 1m [Lp] (2) dB(A) 61,6 61,5 67,1 72,0 71,3 77,3 77,4 80,3Sound pressure level at 5m [Lp] (3) dB(A) 50,5 50,4 56,5 61,4 60,9 67,2 67,3 70,6Sound pressure level at 10m [Lp] (3) dB(A) 44,9 44,8 51,1 56,0 55,4 61,9 62,0 65,3
TEAM MATE PF LNOMODEL T11 T21 T24 T33 T 44 T 58 T 69 T 86
Sound power level [Lw] (1) dB(A) 72,3 72,2 78,6 83,5 82,9 89,5 89,6 93,0Sound pressure level at 1m [Lp] (2) dB(A) 57,7 57,6 63,2 68,1 67,4 73,4 73,5 76,4Sound pressure level at 5m [Lp] (3) dB(A) 46,6 46,5 52,7 57,6 57,0 63,4 63,5 66,7Sound pressure level at 10m [Lp] (3) dB(A) 41,0 40,9 47,2 52,1 51,5 58,0 58,1 61,4
TEAM MATE PF ELN
MODEL T11 T21 T24 T33 T 44 T 58 T 69 T 86
Sound power level [Lw] (1) dB(A) 67,6 67,5 73,9 78,8 78,3 84,8 84,9 88,3Sound pressure level at 1m [Lp] (2) dB(A) 53,1 53,0 58,6 63,5 62,8 68,8 68,9 71,8Sound pressure level at 5m [Lp] (3) dB(A) 42,0 41,9 48,0 52,9 52,4 58,7 58,8 62,1Sound pressure level at 10m [Lp] (3) dB(A) 36,4 36,3 42,6 47,5 46,9 53,3 53,4 56,8
1. Sound power level [Lw] according to ISO EN 9614 - 2.
2. Sound pressure level [Lp] according to ISO EN 37443. Sound pressure level [Lp] in free field condition
IMPORTANTFor further information about units acoustic data, please refer to “The Noise” bulletinof RC GROUP technical literature.
8/10/2019 t Nxtevin 0313 Gb
http://slidepdf.com/reader/full/t-nxtevin-0313-gb 27/56
27RC GROUP S.p.A. ● T_NXTEVINV_0313_ GB ● R410A
OPTIONAL ACCESSORIES - CONDENSATE DISCHARGE PUMP
A plastic case contains the vertical type pump, the water tank with float plus safety switch andhydraulic and electric connection.Together the pump 10 linear meters anti-crushing plastic discharge spiral tube is suppliedThe optional has to be installed as shown in the documentation delivered together with theunit.Wiring includes power supply and an alarm, displayed on microprocessor, that includes motor
pump thermal protection and tank overflow.The condensate discharge pump operation is fully automatic.
WARNINGFor machines size E0, E1, E2 and E3 in UNDER/OVER version, the optional is suppliedin mounting kit.
TECHNICAL DATAPower supply 230/1/50Power input W 75
Absorbed current A 0,5Capacity tank l 2Discharge pipe Ø mm 10/16Maximum water flow l/h 300
Minimum water flow l/h 3Discharge head- with min. water flow mH2O 4,5- with max. water flow mH2O 0,3
CONDENSATE DISCHARGE PUMP
Condensate discharge 3/8”
Condensate inlet28
8/10/2019 t Nxtevin 0313 Gb
http://slidepdf.com/reader/full/t-nxtevin-0313-gb 28/56
28 RC GROUP S.p.A. ● T_NXTEVINV_0313_ GB ● R410A
1
3
2 4
5
6
OPTIONAL ACCESSORIES - EXTRA CIRCUIT SYSTEM
(size E0 excluded)This system consists of one chilled water cooling coil and one motorized valve directly drivenby the microprocessor control system.The chilled water cooling coil is installed in the return air stream just before the main coolingcoil.In this way the air is partially or totally cooled before entering the main cooling coil.
WORKING LOGICThe installation of the EXTRA CIRCUIT on the machine allows to obtain a dual source coolingsystems.Thanks to the EXTRA CIRCUIT and to the microprocessor control system, the machine canrun either as a modulating chilled water system or as a direct expansion system, or as acombination of both.With this system it is possible, with a limited use of space, to solve several plant problemssuch as:- EXTRA CIRCUIT fed with chilled water or mains water as a stand-by of the main cooling
circuit.- Main cooling circuit as a stand-by for the EXTRA CIRCUIT operation achieved via remote
water chillers.- EXTRA CIRCUIT operation during office hours by connection to the central chilled water
plant with main cooling circuit operation during the remaining hours.- Main cooling circuit working as a back up to the EXTRA CIRCUIT to balance possible
peaks of the room load.
EXTRA-CIRCUIT SYSTEM
PRINCIPLE DIAGRAM
1) Compressor 2) Main cooling coil3) Expansion valve 4) Extra-Circuit coil5) Extra-Circuit valve6) Microprocessor
Extra-Circuit water circuit
Liquid line
Airflow
Discharge gas line
8/10/2019 t Nxtevin 0313 Gb
http://slidepdf.com/reader/full/t-nxtevin-0313-gb 29/56
29RC GROUP S.p.A. ● T_NXTEVINV_0313_ GB ● R410A
8 2
H
63 63 A
8 2
H
175 175 A==
8 2
H
175 175 A
OPTIONAL ACCESSORIES - FLOOR STAND
It is not possible to match the unit floor stand with plenum installed under the machine.For a correct installation of the air conditioner we suggest you to utilize a gasket between thefloor stand and the unit base.The floor stand is available in 3 different heights.
SIZE E0 E1 E2 E3 E4 E5 E6
A mm 460 690 690 790 945 945 945
MODEL 230 330 390
H minimum height mm 255 355 400
H maximum height mm 350 450 510
FLOOR STANDSIZE E0 - E1 – E2 – E3
SIZE E6
SIZE E4 – E5
8/10/2019 t Nxtevin 0313 Gb
http://slidepdf.com/reader/full/t-nxtevin-0313-gb 30/56
30 RC GROUP S.p.A. ● T_NXTEVINV_0313_ GB ● R410A
1
2
4
3
OPTIONAL ACCESSORIES – OVER VERSION - BOTTOM PANEL
Available for OVER units (size E0 excluded).With this accessory it is possible a noise insulation of the air conditioner, when the machine isinstalled directly on particular floor as raised floor, wood floor etc.The accessory includes:• Panel in galvanized steel sheet.• Noise insulation with special soundproof material.
The bottom panel is supplied assembled inside the unit base and does not modify the unitdimensions.
OPTIONAL ACCESSORIES - SANDWICH PANEL
With this accessory it is possible a noise insulation of the panels of the air conditioner The accessory includes:• External part as standard panel.• Internal part in galvanized steel sheet.• Noise insulation with special soundproof material.
The accessory increase the unit weight:
1. Add this value to the total unit weight
OVER VERSION
Size E0 E1 E2 E3 E4 E5 E6
Weight increasing (1) kg 25 30 42 48 64 72 86
UNDER VERSION
Size E0 E1 E2 E3 E4 E5 E6
Weight increasing (1) kg 25 26 48 55 70 86 110
BOTTOM PANEL
1) Air conditioner2) Air conditioner base3) Bottom panel4) Insulation with special sound soundproof material
8/10/2019 t Nxtevin 0313 Gb
http://slidepdf.com/reader/full/t-nxtevin-0313-gb 31/56
31RC GROUP S.p.A. ● T_NXTEVINV_0313_ GB ● R410A
D
=
=
B
A
1 7 0
F C E G
OPTIONAL ACCESSORIES - NON RETURN MOTORIZED DAMPER
(size E0 excluded) Accessory to install on units air delivery and it can be matched to air conditioner, plenums andfloor stand. For OVER version the damper is provided with connecting flange for the airdelivery duct.For a correct installation we suggest you to utilize a gasket between the damper and the unitor the plenum or the floor stand..
1. Add this value to the total unit weight
Size E0 E1 E2 E3 E4 E5 E6
A mm -- 650 785 1085 1305 1630 1873
B mm -- 650 650 750 905 905 905C mm -- 300 450 750 850 1100 1250
D mm -- 510 510 610 710 710 710
E mm -- 231 216 216 167 204 250,5
F mm -- 73 73 73 228 265 311,5
G mm -- 46 46 46 61 61 61
Weight (1) kg -- 20 23 30 40 50 58
NON RETURN MOTORIZED DAMPER
1) Non return damper2) Gasket3) Air conditioner
8/10/2019 t Nxtevin 0313 Gb
http://slidepdf.com/reader/full/t-nxtevin-0313-gb 32/56
32 RC GROUP S.p.A. ● T_NXTEVINV_0313_ GB ● R410A
A
A
OPTIONAL ACCESSORIES - UNDER VERSION - AIR DELIVERY/INTAKE
PLENUM
The accessories is not available for machine size E0. The plenums have same technical characteristics and base dimensions of the machinecabinet and can contain:
- Noise absorption partitions
- F6/F7/F9 high efficiency filters
It is not possible to foresee both optional accessories in the same plenum
1. Add this value to the total unit weight
FOR ALL PLENUMS
WARNINGIn UNDER version units the hydraulic and/or cooling piping and inside the machine.The air delivery plenums sometime don’t allow the extension of the pipes downwards.
In special cases, to keep the connections inside the machine, a plenum 200mm higherthan the standard one is necessary.
Grandezza E0 E1 E2 E3 E4 E5 E6
Plenum (1) kg 18 20 21 20 30 40 45
Plenum con filtri (1) kg -- 26 27 27 45 55 65
Plenum con setti (1) kg -- 25 27 30 45 50 65
Grandezza E0 E1 E2 E3 E4 E5 E6
A mm 490 490 490 490 510 510 510
NEXT UNDER PLENUMRemove this panel to extract air filters
8/10/2019 t Nxtevin 0313 Gb
http://slidepdf.com/reader/full/t-nxtevin-0313-gb 33/56
33RC GROUP S.p.A. ● T_NXTEVINV_0313_ GB ● R410A
A
A
A
OPTIONAL ACCESSORIES - OVER VERSION - AIR DELIVERY PLENUM
The plenums have same technical characteristics and base dimensions of the machinecabinet.
1. Add this value to the total unit weight
FOR ALL PLENUMS
Grandezza E0 E1 E2 E3 E4 E5 E6
Plenum (1) kg 18 20 21 20 30 45 55
Plenum con filtri (1) kg -- 26 27 27 45 60 70Plenum con setti (1) kg -- 25 27 30 45 60 70
Grandezza E0 E1 E2 E3 E4 E5 E6
Plenum con griglie (1) kg 15,5 23 26 28 39 50 65
Plenum con griglie e setti (1) kg -- 30 30 37 67 72 78
Grandezza E0 E1 E2 E3 E4 E5 E6
Plenum con griglie (1) kg 15 21 23 30 45 50 65
Grandezza E0 E1 E2 E3 E4 E5 E6
A mm 490 490 490 490 510 510 510
NEXT EVO INV OVER PLENUM
Plenum for ducting
Plenum for ducting with F6/F7/F9efficiency filters
Plenum for ducting with noise absorptionpartitions
• Plenum with grille for frontal airdistribution into the room andnoise absorption partitions
• Plenum with grilles on 3 sides, fordirect air distribution into the room.
8/10/2019 t Nxtevin 0313 Gb
http://slidepdf.com/reader/full/t-nxtevin-0313-gb 34/56
34 RC GROUP S.p.A. ● T_NXTEVINV_0313_ GB ● R410A
OPTIONAL ACCESSORIES – DIRECT FREE-COOLING PLENUM
(size E0 excluded)The plenums have same technical characteristics and base dimensions of the machinecabinet.The optional allow to obtain free-cooling by direct ambient air intake into the room.The dampers are proportionally managed by the microprocessor control, that regulates thequantity of the ambient air to put in the room according to the set-point.
COMPONENTS:- Housing consisting of painted aluminium profile frame, jointed with reinforced PVC
corners and galvanized steel sheet panels externally coated with PVC film.- Motorized dampers on room air / ambient air intake with safety nets.- Terminals for electric connection to the unit.- Combined Temperature / Humidity sensor on machine air suction.- Combined Temperature / Humidity sensor for outdoor installation..
WARNINGFor a correct installation we suggest you to utilize a gasket between the plenum andthe unit.IT IS COMPULSORY TO INSTALL INTO THE ROOM AN APPROPRIATELY SIZEDOVERPRESSURE DAMPER TO ALLOW THE ROOM AIR EXHAUSTION DURING FREE-
COOLING WORKING MODE.
1. Add this value to the total unit weight
Size E0 E1 E2 E3 E4 E5 E6
A mm -- 650 785 1085 1305 1630 1873
B mm -- 490 490 490 630 630 630
C mm -- 650 650 750 905 905 905
D mm -- 30 30 30 40 40 40
E mm -- 430 430 430 550 550 550
F mm -- 590 725 1025 835 1135 1435
G mm -- -- -- -- 235 235 219Weight (1) kg -- 24 27 35 53 61 78
NEXT EVO INV OVER: FREE-COOLING PLENUM
NEXT EVO INV OVER E1 / E2 / E3
NEXT EVO INV OVER E4 / E5 / E6
8/10/2019 t Nxtevin 0313 Gb
http://slidepdf.com/reader/full/t-nxtevin-0313-gb 35/56
35RC GROUP S.p.A. ● T_NXTEVINV_0313_ GB ● R410A
1. Add this value to the total unit weight
Size E0 E1 E2 E3 E4 E5 E6
A mm -- 650 785 1085 1305 1630 1873
B mm -- 490 490 490 630 630 630
C mm -- 650 650 750 905 905 905
D mm -- 30 30 30 40 40 40
E mm -- 430 430 430 550 550 550
F mm -- 590 725 1025 835 1135 1435
G mm -- -- -- -- 235,5 247,5 219H mm -- -- -- -- 275 275 275
Weight (1) kg -- 24 27 35 53 61 78
NEXT EVO INV UNDER: FREE-COOLING PLENUM
NEXT EVO INV UNDER E1 / E2 / E3
NEXT EVO INV UNDER E4 / E5 / E6
INSTALLATION EXAMPLE
NOTE:Ducting are at Customer
care.We suggest you to installa rain-proof grille onambient air intake.
IT IS COMPULSORY TOINSTALL ANOVERPRESSUREDAMPER TO ALLOWTHE ROOM AIREXHAUSTION DURINGFREE-COOLINGWORKING MODE.
NEXT EVO INV
UNDER
NEXT EVO INV
OVER
R e m o v e t h i s p a n e l t o
e x t r a c t a i r f i l t e r s
8/10/2019 t Nxtevin 0313 Gb
http://slidepdf.com/reader/full/t-nxtevin-0313-gb 36/56
36 RC GROUP S.p.A. ● T_NXTEVINV_0313_ GB ● R410A
MACHINE DRAWINGSDimensions in mm
NEXT EVO INV DX U M1 E0
8/10/2019 t Nxtevin 0313 Gb
http://slidepdf.com/reader/full/t-nxtevin-0313-gb 37/56
37RC GROUP S.p.A. ● T_NXTEVINV_0313_ GB ● R410A
MACHINE DRAWINGSDimensions in mm
NEXT EVO INV DX U M1 E1
8/10/2019 t Nxtevin 0313 Gb
http://slidepdf.com/reader/full/t-nxtevin-0313-gb 38/56
38 RC GROUP S.p.A. ● T_NXTEVINV_0313_ GB ● R410A
MACHINE DRAWINGSDimensions in mm
NEXT EVO INV DX U M1 E2
8/10/2019 t Nxtevin 0313 Gb
http://slidepdf.com/reader/full/t-nxtevin-0313-gb 39/56
39RC GROUP S.p.A. ● T_NXTEVINV_0313_ GB ● R410A
MACHINE DRAWINGSDimensions in mm
NEXT EVO INV DX U M1 E3
8/10/2019 t Nxtevin 0313 Gb
http://slidepdf.com/reader/full/t-nxtevin-0313-gb 40/56
8/10/2019 t Nxtevin 0313 Gb
http://slidepdf.com/reader/full/t-nxtevin-0313-gb 41/56
41RC GROUP S.p.A. ● T_NXTEVINV_0313_ GB ● R410A
MACHINE DRAWINGSDimensions in mm
NEXT EVO INV DX U M2 E5, DX U M3 E5
8/10/2019 t Nxtevin 0313 Gb
http://slidepdf.com/reader/full/t-nxtevin-0313-gb 42/56
42 RC GROUP S.p.A. ● T_NXTEVINV_0313_ GB ● R410A
MACHINE DRAWINGSDimensions in mm
NEXT EVO INV DX U M3 E6
8/10/2019 t Nxtevin 0313 Gb
http://slidepdf.com/reader/full/t-nxtevin-0313-gb 43/56
43RC GROUP S.p.A. ● T_NXTEVINV_0313_ GB ● R410A
MACHINE DRAWINGSDimensions in mm
NEXT EVO INV DX O M1 E0
8/10/2019 t Nxtevin 0313 Gb
http://slidepdf.com/reader/full/t-nxtevin-0313-gb 44/56
44 RC GROUP S.p.A. ● T_NXTEVINV_0313_ GB ● R410A
MACHINE DRAWINGSDimensions in mm
NEXT EVO INV DX O M1 E1
8/10/2019 t Nxtevin 0313 Gb
http://slidepdf.com/reader/full/t-nxtevin-0313-gb 45/56
45RC GROUP S.p.A. ● T_NXTEVINV_0313_ GB ● R410A
MACHINE DRAWINGSDimensions in mm
NEXT EVO INV DX O M1 E2
8/10/2019 t Nxtevin 0313 Gb
http://slidepdf.com/reader/full/t-nxtevin-0313-gb 46/56
46 RC GROUP S.p.A. ● T_NXTEVINV_0313_ GB ● R410A
MACHINE DRAWINGSDimensions in mm
NEXT EVO INV DX O M1 E3
8/10/2019 t Nxtevin 0313 Gb
http://slidepdf.com/reader/full/t-nxtevin-0313-gb 47/56
47RC GROUP S.p.A. ● T_NXTEVINV_0313_ GB ● R410A
MACHINE DRAWINGSDimensions in mm
NEXT EVO INV DX O M1 E4, DX O M2 E4
8/10/2019 t Nxtevin 0313 Gb
http://slidepdf.com/reader/full/t-nxtevin-0313-gb 48/56
48 RC GROUP S.p.A. ● T_NXTEVINV_0313_ GB ● R410A
MACHINE DRAWINGSDimensions in mm
NEXT EVO INV DX O M2 E5, DX O M3 E5
8/10/2019 t Nxtevin 0313 Gb
http://slidepdf.com/reader/full/t-nxtevin-0313-gb 49/56
49RC GROUP S.p.A. ● T_NXTEVINV_0313_ GB ● R410A
MACHINE DRAWINGSDimensions in mm
NEXT EVO INV DX O M3 E6
8/10/2019 t Nxtevin 0313 Gb
http://slidepdf.com/reader/full/t-nxtevin-0313-gb 50/56
50 RC GROUP S.p.A. ● T_NXTEVINV_0313_ GB ● R410A
TYPICAL INSTALLATION DIAGRAMS FOR DIRECT EXPANSION MACHINES
WITH REMOTE AIR COOLED CONDENSER
WARNINGIt is necessary to provide the refrigerant charge for the connection pipes and for theremote air cooled condenser.
Charge refrigerant in the suitable quantity and lubricant oil in 10% ratio of chargedrefrigerant.Lubricant oil must be the same type as the charged one as shown on the compressorplate.
1) Air conditioner2) Remote air cooled condenser3) Gas discharge line4) Liquid line
5) Trap. Foresee a trap every 5m of the rising pipe.6) Additional liquid receiver external to the conditioner with valves and safety valve.Suggested part in the following cases:a) refrigerant line longer than 25-30mb) plant operation with ambient temperature lower than 0°C with refrigerant line any lengthInstall the liquid receiver close to the air conditioner.
7) Solenoid valve of the liquid line. It is an optional accessory of the air conditioner for refrigeration plants withrefrigerant pipe longer than 10m
THIS DIAGRAM APPLIES TO EACH REFRIGERANT CIRCUIT OF THE UNIT.
8/10/2019 t Nxtevin 0313 Gb
http://slidepdf.com/reader/full/t-nxtevin-0313-gb 51/56
51RC GROUP S.p.A. ● T_NXTEVINV_0313_ GB ● R410A
TYPICAL INSTALLATION DIAGRAMS FOR DIRECT EXPANSION MACHINES WITHREMOTE AIR COOLED CONDENSER
WARNINGIt is necessary to provide the refrigerant charge for the connection pipes and for the
remote air cooled condenser.Charge refrigerant in the suitable quantity and lubricant oil in 10% ratio of chargedrefrigerant.Lubricant oil must be the same type as the charged one as shown on the compressorplate.
1) Air conditioner2) Remote air cooled condenser3) Gas discharge line4) Liquid line5) Non - return valve.6) Additional liquid receiver external to the conditioner with valves and safety valve.
Install the liquid receiver close to the air conditioner.7) Solenoid valve of the liquid line. It is an optional accessory of the air conditioner for refrigeration plants with
refrigerant pipe longer than 10m
THIS DIAGRAM APPLIES TO EACH REFRIGERANT CIRCUIT OF THE UNIT.
8/10/2019 t Nxtevin 0313 Gb
http://slidepdf.com/reader/full/t-nxtevin-0313-gb 52/56
52 RC GROUP S.p.A. ● T_NXTEVINV_0313_ GB ● R410A
EXAMPLE FOR MACHINES NOISE EMISSION CALCULATION
NEXT UNDER WITH DUCT ON AIR INTAKE
Duct
Lp A = Front side Under catalogue value
Lp B = Air delivery Under catalogue value
Lp C = Air intake Under catalogue value
The points B and C do not influence the point A
NEXT UNDER WITH PLENUM ON AIR DELIVERY
Lp A = Front side Under catalogue value
Lp B = Air delivery Under catalogue value –plenum noise reduction
Lp C = Air intake Under catalogue value
Lp A+C = 10 log10(10 +10 )
The point B do not influence the point A
LpA10
LpC10
NEXT UNDER WITH PLENUM ON AIR INTAKE
Lp A = Front side Under catalogue value
Lp B = Air delivery Under catalogue value
Lp C = Air intake Under catalogue value – plenum noise reduction
Lp A+C = 10 log10(10 +10 )
The point B do not influence the point A
LpA10
LpC10
NEXT OVER WITH DUCT
Lp A = Air intake Over catalogue value
Lp B = Air delivery Over catalogue value
The point B do not influence the point A
8/10/2019 t Nxtevin 0313 Gb
http://slidepdf.com/reader/full/t-nxtevin-0313-gb 53/56
53RC GROUP S.p.A. ● T_NXTEVINV_0313_ GB ● R410A
EXAMPLE FOR MACHINES NOISE EMISSION CALCULATION
IMPORTANTThe declared noise levels are intended in free field conditions.The noise pressure level of an installed unit is affected by the room acousticcharacteristics.Please consider an average noise increase of +4/+6 dB(A).
NEXT OVER WITH PLENUM ON AIR DELIVERY
Lp A = Air intake Over catalogue value
Lp B = Air delivery Over catalogue value – plenum noise reduction
Lp A+B = 10 log10(10 +10 )LpA10
LpC10
NEXT OVER WITH DUCT AND PLENUM ON AIR DELIVERY
Lp A = Radiated Over catalogue value
Lp B = Air delivery Over catalogue value
Lp C = Lp A + 6dB(A) – plenum noise reduction
Lp A+C = 10 log10(10 +10 )
The point B do not influence the point A+C
LpA10
LpC10
NEXT OVER WITH DUCT AND PLENUM ON AIR DELIVERY
Lp A = Radiated Over catalogue value
Lp B = Air delivery Over catalogue value
Lp C = Lp D = Lp A + 6 dB(A) – plenum noise reduction
The points B, C and D do not influence the point A
Blind front panel
Blind front panel
8/10/2019 t Nxtevin 0313 Gb
http://slidepdf.com/reader/full/t-nxtevin-0313-gb 54/56
54 RC GROUP S.p.A. ● T_NXTEVINV_0313_ GB ● R410A
AIR FILTERS REPLACEMENT FOR UNDER VERSION MACHINES
Installation with an
obstacle on the top
4 5 0 m m
m i n i m u m
Installation with an airintake plenum with
noise partitions
Installation with a Free-
Cooling plenum
Installation with an
air intake duct
4 5 0 m m
m i n i m u m
8/10/2019 t Nxtevin 0313 Gb
http://slidepdf.com/reader/full/t-nxtevin-0313-gb 55/56
8/10/2019 t Nxtevin 0313 Gb
http://slidepdf.com/reader/full/t-nxtevin-0313-gb 56/56
The continuous improvement of products may imply changes in the data shown in this catalogue.