PROJECT NARRATIVE: T-MOBILE ANTENNA SITE MODIFICATION

Site: #286 Water Tower at the Henry A. Wallace Beltsville Agricultural Research Center (BARC) located in Beltsville, Maryland. The BARC property covers over 6,500 acres. Other Federal facilities located adjacent to BARC property include the Patuxent Wildlife Research Center, the Goddard Space Flight Center, and the U.S. Secret Service James T. Rowley Training Center. The cities of College Park and Greenbelt are located south of BARC property. Background: This project is being undertaken by T-Mobile in an effort to update their sites within the Washington/Baltimore market. Proposal: T-Mobile proposes to replace three of nine existing panel antennas with new panel antennas in the same locations on the #286 Water Tower. They also propose to add three lines of hybrid cabling within their existing coaxial run. The dimensions of the existing AIR 21 antennas are 1422 x 307 x 200 (56” x 12” x 8”). The dimensions of the new AIR 32 antennas are 1439 x 327 x 220 (56.6” x 12.9” x 8.7”). The antennas will be painted to blend with the color of the Water Tower to minimize visibility. The Radio Frequency (RF) Site Compliance Report prepared by EBI Consulting indicates the antenna site would be in compliance with RF safety requirements. National Environmental Policy Act (NEPA): In accordance with the National Environmental Policy Act, BARC has determined that the modifications proposed by T-Mobile are a categorical exclusion under ARS regulations 7 CFR 520.5 (b) (1). National Historic Preservation Act (NHPA): On January 5, 2018, the Maryland Historical Trust concurred with the no adverse effect finding regarding this undertaking.

Page 4: T-Mobile Antenna Site

PROJECT LOCATION

TITLE SHEET

08\7

WA

S039C

.USD

A -

Lau

rel.C

D.R

EV

A.d

wg\

T-1

B

y: M

AY

LW

AR

D

REV DATE DESCRIPTION

SHEET TITLE :

DRAWNBY

CHECKEDBY

Customer Loyalty through Client Satisfactionw w w . m a s e r c o n s u l t i n g . c o m

PROTECT YOURSELF

Engineers Planners SurveyorsLandscape Architects Environmental Scientists

Copyright © 2017. Maser Consulting P.A. All Rights Reserved. This drawing and all the information

contained herein is authorized for use only by the party for whom the services were contracted orto whom it is certified. This drawing may not be copied, reused, disclosed, distributed or relied

upon for any other purpose without the express written consent of Maser Consulting, P.A.

Know what'sbelow.before you dig.Call

R

ALL STATES REQUIRE NOTIFICATION OF

EXCAVATORS, DESIGNERS, OR ANY PERSONPREPARING TO DISTURB THE EARTH'S

SURFACE ANYWHERE IN ANY STATE

Office Locations:

FOR STATE SPECIFIC DIRECT PHONE NUMBERS VISIT:WWW.CALL811.COM

C O N S U L T I N G P. A.

n Red Bank, NJn Clinton, NJn Hamilton, NJn Marmora, NJn Mt. Arlington, NJn Mt. Laurel, NJ

n Sterling, VAn Norfolk, VAn Albuquerque, NMn Albany, NYn Chestnut Ridge, NYn Newburgh, NY

n Hawthorne, NYn Lehigh Valley, PAn Exton, PAn Philadelphia, PAn Columbia, MDn Tampa, FL

IT IS A VIOLATION OF LAW FOR ANY PERSON, UNLESSTHEY ARE ACTING UNDER THE DIRECTION OF THE

RESPONSIBLE LICENSED PROFFESIONAL ENGINEER, TOALTER THIS DOCUMENT.

SITE NAME:

SCALE : JOB NUMBER :

SHEET NUMBER :

COLUMBIA OFFICE6240 Old Dobbin Lane,

Suite 150Columbia, MD 21045

Phone: 877.627.3772

7WAS039CUSDA-LAUREL

EDMONSTON RDGREENBELT, MD 20770

PRINCE GEORGE'S COUNTY

AS SHOWN 17958170

A 11/01/17 FOR REVIEW MCA NSB

. . . . .

. . . . .

. . . . .

. . . . .

. . . . .

. . . . .

. . . . .

_____________________________

MARYLAND PROFESSIONAL

NICHOLAS S. BERTE, P.E.

ENGINEER - LICENSE NUMBER: 37157"Professional Certification. I hereby certify that these documentswere prepared or approved by me, and that I am a duly licensedprofessional engineer under the laws of the State of Maryland,

License No. 0037157, Expiration Date: July 17, 2019"

12050 BALTIMORE AVENUE

BELTSVILLE, MD 20705

PHONE: (240) 264-8600

FAX: (240) 264-8610

T-MOBILE NORTHEAST LLC

SITE LINK WIRELESS, LLC3620 COMMERCE DRIVE

SUITE 707

BALTIMORE, MD 21227

CONTRACTOR SHALL VERIFY PLANS AND EXISTING DIMENSIONSAND CONDITIONS ON THE JOB SITE AND SHALL IMMEDIATELYNOTIFY THE ENGINEER IN WRITING OF ANY DISCREPANCIES BEFOREPROCEEDING WITH THE WORK OR BE RESPONSIBLE FOR SAME.

EXISTING MONOPOLE

EXISTING SILO

EXISTING TRANSMISSION TOWER

EXISTING WATER TANK

EXISTING BUILDING

RAW LAND

RBS 2106

SITE SUPPORT KIT

SITE SUPPORTCABINET

OUTDOOR

INDOOR

CONCRETE PAD

STEEL PLATFORM

PPC

PANELBOARD

SHEET DESCRIPTION REVISION

SHEET INDEX

HCS

THIS DRAWING AND ALL THE INFORMATION CONTAINED HEREIN IS AUTHORIZED FOR USE ONLY BY THE PARTY FOR WHOM THEWORK WAS CONTRACTED OR TO WHOM IT IS CERTIFIED. THIS DRAWING MAY NOT BE COPIED, REUSED, DISCLOSED, DISTRIBUTED ORRELIED UPON FOR ANY OTHER PURPOSE WITHOUT THE EXPRESS WRITTEN CONSENT OF MASER CONSULTING P.A.

1. THE CONTRACTOR SHALL GIVE ALL NOTICES AND COMPLYWITH ALL LAWS, ORDINANCES. RULES, REGULATIONS ANDLAWFUL ORDERS OF ANY PUBLIC AUTHORITY, MUNICIPAL

AND UTILITY COMPANY SPECIFICATIONS, AND LOCAL ANDSTATE JURISDICTIONAL CODES BEARING ON THEPERFORMANCE OF THE WORK. THE WORK PERFORMED ONTHE PROJECT AND THE MATERIALS INSTALLED SHALL BE INSTRICT ACCORDANCE WITH ALL APPLICABLE CODES,REGULATIONS AND ORDINANCES.

2. THE ARCHITECT/ENGINEER HAVE MADE EVERY EFFORT TO SETFORTH IN THE CONSTRUCTION AND CONSTRUCTDOCUMENTS THE COMPLETE SCOPE OF WORK. THECONTRACTOR BIDDING THE JOB IS NEVERTHELESSCAUTIONED THAT MINOR OMISSIONS OR ERRORS IN THEDRAWINGS AND OR SPECIFICATIONS SHALL NOT EXCUSE SAIDCONTRACTOR FROM COMPLETING THE PROJECT AND

IMPROVEMENTS IN ACCORDANCE WITH THE INTENT OFTHESE DOCUMENTS.

3. THE CONTRACTOR OR BIDDER SHALL BEAR THERESPONSIBILITY OF NOTIFYING (IN WRITING) THE T-MOBILEREPRESENTATIVE OF ANY CONFLICTS, ERRORS, OR OMISSIONSPRIOR TO THE SUBMISSION OF THE CONTRACTOR'S PROPOSALOR PERFORMANCE OF WORK. IN THE EVENT OF

DISCREPANCIES, THE CONTRACTOR SHALL PRICE THE MORECOSTLY OR EXPENSIVE WORK, UNLESS DIRECTED IN WRITINGOTHERWISE.

4. THE SCOPE OF WORK SHALL INCLUDE FURNISHING OF ALLMATERIALS, EQUIPMENT, LABOR AND ALL OTHER MATERIALSAND LABOR DEEMED NECESSARY TO COMPLETE THE

WORK/PROJECT AS DESCRIBED HEREIN.

5. THE CONTRACTOR SHALL VISIT THE JOB SITE PRIOR TO THESUBMISSION OF BIDS OR PERFORMING WORK TO FAMILIARIZEHIMSELF WITH THE FIELD CONDITIONS AND TO VERIFY THATTHE PROJECT CAN BE CONSTRUCTED IN ACCORDANCE WITHTHE CONTRACT DOCUMENTS.

6. THE CONTRACTOR SHALL OBTAIN AUTHORIZATION TO

PROCEED WITH CONSTRUCTION PRIOR TO STARTING WORKON ANY ITEM NOT CLEARLY DEFINED BY THE CONSTRUCTIONDRAWINGS/CONTRACT DOCUMENTS.

7. THE CONTRACTOR SHALL INSTALL ALL EQUIPMENT ANDMATERIALS ACCORDING TO THE MANUFACTURER'S/VENDOR'SSPECIFICATIONS UNLESS NOTED OTHERWISE OR WHERELOCAL CODES OR ORDINANCES TAKE PRECEDENCE.

8. THE CONTRACTOR SHALL PROVIDE A FULL SET OFCONSTRUCTION DOCUMENTS AT THE SITE UPDATED WITHTHE LATEST REVISIONS AND ADDENDUM OR CLARIFICATIONS

AVAILABLE FOR THE USE BY ALL PERSONNEL INVOLVED WITHTHE PROJECT.

9. THE CONTRACTOR SHALL SUPERVISE AND DIRECT THEPROJECT DESCRIBED HEREIN. THE CONTRACTOR SHALL BESOLELY RESPONSIBLE FOR ALL CONSTRUCTION MEANS,METHODS, TECHNIQUES, SEQUENCES, AND PROCEDURES AND

FOR COORDINATING ALL PORTIONS OF THE WORK UNDERCONTRACT.

10. THE CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAININGANY PERMITS AND INSPECTIONS WHICH ARE REQUIRED FORTHE WORK BY THE ARCHITECT/ENGINEER, THE STATE,COUNTY, OR LOCAL GOVERNMENT AUTHORITY.

11. THE CONTRACTOR SHALL MAKE NECESSARY PROVISIONS TO

PROTECT EXISTING IMPROVEMENTS, EASEMENTS, PAVING,CURBING, ETC., DURING CONSTRUCTION. UPONCOMPLETION OF WORK, THE CONTRACTOR SHALL REPAIRANY DAMAGE THAT MAY HAVE OCCURRED DUE TOCONSTRUCTION ON OR ABOUT THE PROPERTY.

12. THE CONTRACTOR SHALL KEEP THE GENERAL WORK AREACLEAN AND HAZARD FREE DURING CONSTRUCTION AND

DISPOSE OF ALL DIRT, DEBRIS, RUBBISH AND REMOVEEQUIPMENT NOT SPECIFIED AS REMAINING ON PROPERTY.PREMISES SHALL BE LEFT IN CLEAN CONDITION AND FREEFROM PAINT SPOTS, DUST, OR SMUDGES OF ANY NATURE.

13. THE CONTRACTOR SHALL COMPLY WITH ALL OSHAREQUIREMENTS, AS WELL AS THE LATEST EDITIONS OF ANY

PERTINENT STATE SAFETY REGULATIONS.

14. THE CONTRACTOR SHALL NOTIFY THE T-MOBILEREPRESENTATIVE WHERE A CONFLICT OCCURS ON ANY OFTHE CONTRACT DOCUMENTS. THE CONTRACTOR IS NOT TOORDER MATERIAL OR CONSTRUCT ANY PORTION OF THEWORK THAT IS IN CONFLICT UNTIL CONFLICT IS RESOLVED BYTHE T-MOBILE REPRESENTATIVE..

15. THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS,ELEVATIONS, PROPERTY LINES, ETC., ON THE JOB.

16. THE CONTRACTOR SHALL RETURN ALL DISTURBED AREAS TOTHEIR ORIGINAL CONDITION AT THE COMPLETION OF WORK.

SITE PLAN

RBS 3106

T-MOBILE NORTHEAST LLC PROPOSES THE MODIFICATION OF ANUNMANNED WIRELESS BROADBAND FACILITY.

- REMOVE (3) AIR21 ANTENNAS P3 ALL SECTORS

- INSTALL (3) AIR32 ANTENNAS P3 ALL SECTORS

- INSTALL (1) ONE 6 X 12 HYBRID CABLE

CODE INFORMATION:

APPLICABLE BUILDING CODE: INTERNATIONAL BUILDING CODE/ "IBC" 2015 W/ LOCAL AMENDMENTS

NATIONAL ELECTRICAL CODE/ "NEC" 2014 W/ LOCAL AMENDMENTSINTERNATIONAL FIRE PROTECTION ASSOCIATION FIRE SAFETY CODE 2015CONSTRUCTION TYPE: IIB NONCOMBUSTIBLE/UNPROTECTED

USE GROUP: U - UTILITY AND MISCELLANEOUS

T-MOBILE NORTHEAST

12050 BALTIMORE AVENUEBELTSVILLE, MD 20705

N 39.017000° / W -76.86086110°

IIB

U

DREW MONTGOMERY (443) 846-3946

MARK AYLWARDMASER CONSULTING PA6240 OLD DOBBIN LANESUITE 150COLUMBIA, MD 21045(703) 627-3772

ARCHITECT/ENGINEER:

PROJECT MANAGER:

USE GROUP:

CONSTRUCTION TYPE:

LAT./LONG.:PRINCE GEORGE COUNTYJURISDICTION:

APPLICANT:

SITE NUMBER:

SITE NAME:

SITE ADDRESS: EDMONSTON ROADGREENBELT, MD 20770

USDA-LAUREL

7WAS039C

T-1

PROJECT SUMMARY

PROJECT DESCRIPTION

CODE COMPLIANCE

COPYRIGHT © 2017, MASER CONSULTING P.A ALL RIGHTS RESERVED

GENERAL NOTESVICINITY MAP

DO NOT SCALE 11"x17" DRAWINGS

ZONING MAP

COMPOUND PLAN

TITLE SHEETT-1

C-1

C-2

C-5

E-1

N-1

A

A

A

AANTENNA RF SYSTEM SCHEDULE ANDORIENTATION

ELECTRICAL DETAILS

GENERAL AND ELECTRICAL NOTES

N

S

EW

NO

RT

H

EXISTING FLAG POLE

E-2 GROUNDING DETAILS

C-4 ELEVATION VIEW

C-3

C-6 ACONSTRUCTION DETAILS

A

A

A

A

A

DIRECTIONS FROM 12050 BALTIMORE AVE, BELTSVILLE, MD 20705:

HEAD SOUTHEAST TOWARD US-1 N; TURN RIGHT ONTO US-1S/BALTIMORE AVE; TURN LEFT ONTO POWDER MILL RD;

TURN RIGHT ONTO MD-201 S; TURN LEFT ONTO BEAVER DAM RD;

BEAVER DAM RD BELTSVILLE, MD 20705

T-MOBILE NORTHEAST LLC

EDMONSTON ROADGREENBELT, MD 20770

PRINCE GEORGE'S COUNTY

7WAS039C

USDA-LAUREL

WIRELESS BROADBAND FACILITY

CONSTRUCTION DRAWINGS

(792DB CONFIGURATION)

Page 5: T-Mobile Antenna Site

SITE PLAN

SITE PLAN0

( IN FEET )

(DO NOT SCALE 11"X17" DRAWINGS)

GRAPHIC SCALE

20010050100

SCALE: 1" = 100' FOR 24"X36" DRAWINGS

N

S

EW

NO

RT

H

C-1

08\7

WA

S039C

.USD

A -

Lau

rel.C

D.R

EV

A.d

wg\

C-1

B

y: M

AY

LW

AR

D

REV DATE DESCRIPTION

SHEET TITLE :

DRAWNBY

CHECKEDBY

Customer Loyalty through Client Satisfactionw w w . m a s e r c o n s u l t i n g . c o m

PROTECT YOURSELF

Engineers Planners SurveyorsLandscape Architects Environmental Scientists

Copyright © 2017. Maser Consulting P.A. All Rights Reserved. This drawing and all the information

contained herein is authorized for use only by the party for whom the services were contracted orto whom it is certified. This drawing may not be copied, reused, disclosed, distributed or relied

upon for any other purpose without the express written consent of Maser Consulting, P.A.

Know what'sbelow.before you dig.Call

R

ALL STATES REQUIRE NOTIFICATION OF

EXCAVATORS, DESIGNERS, OR ANY PERSONPREPARING TO DISTURB THE EARTH'S

SURFACE ANYWHERE IN ANY STATE

Office Locations:

FOR STATE SPECIFIC DIRECT PHONE NUMBERS VISIT:WWW.CALL811.COM

C O N S U L T I N G P. A.

n Red Bank, NJn Clinton, NJn Hamilton, NJn Marmora, NJn Mt. Arlington, NJn Mt. Laurel, NJ

n Sterling, VAn Norfolk, VAn Albuquerque, NMn Albany, NYn Chestnut Ridge, NYn Newburgh, NY

n Hawthorne, NYn Lehigh Valley, PAn Exton, PAn Philadelphia, PAn Columbia, MDn Tampa, FL

IT IS A VIOLATION OF LAW FOR ANY PERSON, UNLESSTHEY ARE ACTING UNDER THE DIRECTION OF THE

RESPONSIBLE LICENSED PROFFESIONAL ENGINEER, TOALTER THIS DOCUMENT.

SITE NAME:

SCALE : JOB NUMBER :

SHEET NUMBER :

COLUMBIA OFFICE6240 Old Dobbin Lane,

Suite 150Columbia, MD 21045

Phone: 877.627.3772

7WAS039CUSDA-LAUREL

EDMONSTON RDGREENBELT, MD 20770

PRINCE GEORGE'S COUNTY

AS SHOWN 17958170

A 11/01/17 FOR REVIEW MCA NSB

. . . . .

. . . . .

. . . . .

. . . . .

. . . . .

. . . . .

. . . . .

_____________________________

MARYLAND PROFESSIONAL

NICHOLAS S. BERTE, P.E.

ENGINEER - LICENSE NUMBER: 37157"Professional Certification. I hereby certify that these documentswere prepared or approved by me, and that I am a duly licensedprofessional engineer under the laws of the State of Maryland,

License No. 0037157, Expiration Date: July 17, 2019"

12050 BALTIMORE AVENUE

BELTSVILLE, MD 20705

PHONE: (240) 264-8600

FAX: (240) 264-8610

T-MOBILE NORTHEAST LLC

SITE LINK WIRELESS, LLC3620 COMMERCE DRIVE

SUITE 707

BALTIMORE, MD 21227

SUBJECT PROPERTY LINE

LEGEND

ADJACENT PROPERTY LINE

FENCE LINE X X

TREELINE

LIGHT LINE WORK INDICATESEXISTING CONDITION

HEAVY LINE WORK INDICATESPROPOSED CONDITION

ACCESS ROUTE TO SITE

SEC. 27-445.04. - ANTENNAS, MONOPOLES, AND RELATED EQUIPMENT BUILDINGS FOR WIRELESSTELECOMMUNICATIONS.

(a) ANTENNAS, MONOPOLES, AND RELATED EQUIPMENT BUILDINGS PERMITTED (P) IN THE TABLE

OF USES SHALL BE SUBJECT TO THE FOLLOWING REQUIREMENTS:

(1) THE ANTENNA SHALL COMPLY WITH THE FOLLOWING STANDARDS:

(A) UNLESS OTHERWISE PROHIBITED BELOW, IT SHALL BE CONCEALED WITHIN THEOPAQUE EXTERIOR OF A STRUCTURE OR BE ATTACHED TO A PUBLIC UTILITY,RADIO, TELEVISION, OR TELECOMMUNICATIONS BROADCASTINGTOWER/MONOPOLE; A LIGHT POLE; A MULTIFAMILY DWELLING AT LEAST FIVE (5)

STORIES IN HEIGHT; A STRUCTURE OWNED BY A MUNICIPALITY, THE BOARD OFEDUCATION FOR PRINCE GEORGE'S COUNTY, OR BY PRINCE GEORGE'S COUNTY;OR A STRUCTURE OWNED AND PRIMARILY USED BY A GOVERNMENT AGENCYTHAT IS EXEMPT FROM THE REQUIREMENTS OF THIS SUBTITLE;

(B) IT SHALL NOT EXTEND MORE THAN FIFTEEN (15) FEET ABOVE THE HEIGHT OF THETOWER OR STRUCTURE TO WHICH IT IS ATTACHED;

(C) IT SHALL NOT EXCEED THE FOLLOWING DIMENSIONS:

(i) TWENTY (20) FEET IN LENGTH AND SEVEN (7) INCHES IN DIAMETER FOR WHIPS;

(ii) TEN (10) FEET IN LENGTH AND TWO (2) FEET IN WIDTH FOR PANELS;

(iii) SEVEN (7) FEET IN LENGTH AND ONE (1) FOOT IN DIAMETER FOR CYLINDERS;OR

(iv) SEVEN (7) FEET IN DIAMETER FOR PARABOLIC DISHES; AND

(D) ON PRIVATELY OWNED LAND, IT SHALL NOT SUPPORT LIGHTS OR SIGNS UNLESSREQUIRED FOR AIRCRAFT WARNING OR OTHER SAFETY REASONS.

(2) THE RELATED TELECOMMUNICATIONS EQUIPMENT BUILDING OR ENCLOSURE SHALLCOMPLY WITH THE FOLLOWING STANDARDS:

(A) IT SHALL NOT EXCEED FIVE HUNDRED SIXTY (560) SQUARE FEET OF GROSS FLOORAREA OR TWELVE (12) FEET IN HEIGHT;

(B) THE BUILDING OR ENCLOSURE SHALL BE SCREENED BY MEANS OF LANDSCAPING ORBERMING TO ONE HUNDRED PERCENT (100%) OPACITY FROM ANY ADJOINING

LAND IN A RESIDENTIAL ZONE (OR LAND PROPOSED TO BE USED FOR RESIDENTIALPURPOSES ON AN APPROVED BASIC PLAN FOR A COMPREHENSIVE DESIGN ZONE,OR ANY APPROVED CONCEPTUAL OR DETAILED SITE PLAN);

(C) WHEN ATTACHED TO AN EXISTING BUILDING, IT SHALL MATCH THECONSTRUCTION MATERIAL AND COLOR(S) OF THAT BUILDING;

(D) WHEN CONSTRUCTED AS A FREESTANDING BUILDING, IT SHALL BE CONSTRUCTEDOF BRICK AND ITS DESIGN SHALL COORDINATE WITH THE DESIGN OF ANY

EXISTING MAIN BUILDING ON THE SAME LOT OR ON AN ADJOINING LOT; AND

(E) THE BUILDING OR ENCLOSURE SHALL BE UNMANNED, WITH INFREQUENT (FOUR (4)OR FEWER PER YEAR) VISITS BY MAINTENANCE PERSONNEL, AND WITH ACCESSAND PARKING FOR NO MORE THAN ONE (1) VEHICLE.

(3) THE MONOPOLE SHALL COMPLY WITH THE FOLLOWING STANDARDS:

(A) THE MAXIMUM HEIGHT SHALL BE ONE HUNDRED NINETY-NINE (199) FEET WHENLOCATED ON PUBLIC PROPERTY OR VOLUNTEER FIRE DEPARTMENT (VFD)

PROPERTY, OR ONE HUNDRED (100) FEET WHEN LOCATED ON ALL OTHERPROPERTIES;

(B) FOR PRIVATELY OWNED LAND, THE MINIMUM SETBACK FROM ALL ADJOINING LANDAND DWELLING UNITS SHALL BE EQUAL TO THE HEIGHT OF THE STRUCTUREMEASURED FROM ITS BASE; FOR PUBLICLY OWNED LAND OR VOLUNTEER FIREDEPARTMENT (VFD) PROPERTY, THE MINIMUM SETBACK SHALL BE ONE-HALF (1/2)

OF THE HEIGHT OF THE STRUCTURE MEASURED FROM THE BASE TO THEADJOINING PROPERTY LINES;

(C) FOR PRIVATELY OWNED LAND, THE MINIMUM AREA REQUIRED SHALL BE TWO ANDONE-HALF ACRES (2 ½);

(D) ON PRIVATELY OWNED LAND, THE STRUCTURE SHALL NOT SUPPORT LIGHTS ORSIGNS UNLESS REQUIRED FOR AIRCRAFT WARNING OR OTHER SAFETY REASONS;

(E) THE STRUCTURE SHALL BE DESIGNED, GALVANIZED, AND/OR PAINTED IN A MANNER

WHICH IS HARMONIOUS WITH SURROUNDING PROPERTIES;

(F) THE APPLICANT SHALL PROVIDE CERTIFICATION FROM A REGISTERED ENGINEERTHAT THE STRUCTURE WILL MEET THE APPLICABLE DESIGN STANDARDS FOR WINDLOADS OF THE ELECTRONIC INDUSTRIES ASSOCIATION (EIA) FOR PRINCE GEORGE'SCOUNTY; AND

(G) ANY MONOPOLE WHICH IS NO LONGER USED FOR TELECOMMUNICATIONS

PURPOSES FOR A CONTINUOUS PERIOD OF ONE (1) YEAR SHALL BE REMOVED BYTHE MONOPOLE OWNER AT OWNER'S EXPENSE.

(CB-61-1988; CB-81-1993; CB-123-1994; CB-103-1997; CB-13-1998; CB-65-2000; CB-33-2007; CB-9-2014)

PG COUNTY TELECOMMUNICATIONS REGULATIONS

1. UNITED STATES OF AMERICA - #2410819; #2410827

PROPERTY OWNER & TAX ACCOUNT #:

BEAVER DAM ROAD

BA

LT

IMO

RE W

ASH

ING

TO

N P

AR

KW

AY

SEE ROOF PLANON SHEET C-3

1

Page 6: T-Mobile Antenna Site

ZONING MAP

N

S

EW

NO

RT

H

C-2

08\7

WA

S039C

.USD

A -

Lau

rel.C

D.R

EV

A.d

wg\

C-2

B

y: M

AY

LW

AR

D

REV DATE DESCRIPTION

SHEET TITLE :

DRAWNBY

CHECKEDBY

Customer Loyalty through Client Satisfactionw w w . m a s e r c o n s u l t i n g . c o m

PROTECT YOURSELF

Engineers Planners SurveyorsLandscape Architects Environmental Scientists

Copyright © 2017. Maser Consulting P.A. All Rights Reserved. This drawing and all the information

contained herein is authorized for use only by the party for whom the services were contracted orto whom it is certified. This drawing may not be copied, reused, disclosed, distributed or relied

upon for any other purpose without the express written consent of Maser Consulting, P.A.

Know what'sbelow.before you dig.Call

R

ALL STATES REQUIRE NOTIFICATION OF

EXCAVATORS, DESIGNERS, OR ANY PERSONPREPARING TO DISTURB THE EARTH'S

SURFACE ANYWHERE IN ANY STATE

Office Locations:

FOR STATE SPECIFIC DIRECT PHONE NUMBERS VISIT:WWW.CALL811.COM

C O N S U L T I N G P. A.

n Red Bank, NJn Clinton, NJn Hamilton, NJn Marmora, NJn Mt. Arlington, NJn Mt. Laurel, NJ

n Sterling, VAn Norfolk, VAn Albuquerque, NMn Albany, NYn Chestnut Ridge, NYn Newburgh, NY

n Hawthorne, NYn Lehigh Valley, PAn Exton, PAn Philadelphia, PAn Columbia, MDn Tampa, FL

IT IS A VIOLATION OF LAW FOR ANY PERSON, UNLESSTHEY ARE ACTING UNDER THE DIRECTION OF THE

RESPONSIBLE LICENSED PROFFESIONAL ENGINEER, TOALTER THIS DOCUMENT.

SITE NAME:

SCALE : JOB NUMBER :

SHEET NUMBER :

COLUMBIA OFFICE6240 Old Dobbin Lane,

Suite 150Columbia, MD 21045

Phone: 877.627.3772

7WAS039CUSDA-LAUREL

EDMONSTON RDGREENBELT, MD 20770

PRINCE GEORGE'S COUNTY

AS SHOWN 17958170

A 11/01/17 FOR REVIEW MCA NSB

. . . . .

. . . . .

. . . . .

. . . . .

. . . . .

. . . . .

. . . . .

_____________________________

MARYLAND PROFESSIONAL

NICHOLAS S. BERTE, P.E.

ENGINEER - LICENSE NUMBER: 37157"Professional Certification. I hereby certify that these documentswere prepared or approved by me, and that I am a duly licensedprofessional engineer under the laws of the State of Maryland,

License No. 0037157, Expiration Date: July 17, 2019"

12050 BALTIMORE AVENUE

BELTSVILLE, MD 20705

PHONE: (240) 264-8600

FAX: (240) 264-8610

T-MOBILE NORTHEAST LLC

SITE LINK WIRELESS, LLC3620 COMMERCE DRIVE

SUITE 707

BALTIMORE, MD 21227

ZONING MAP

0

( IN FEET )

(DO NOT SCALE 11"X17" DRAWINGS)

GRAPHIC SCALE

400200100200

SCALE: 1" = 200' FOR 24"X36" DRAWINGS

SEE ROOF PLAN

ON SHEET C-3

A STRUCTURAL ANALYSIS TO DETERMINE IF THE PROPOSEDINSTALLATION CAN BE ADEQUATELY SUPPORTED HAS NOTBEEN PREPARED/ANALYZED MASER CONSULTING PA AND ISPENDING EVALUATION.

BA

LT

IMO

RE/W

ASH

INT

ON

PA

RK

WA

Y

R-O-S: RESERVED OPEN SPACE - PROVIDES FOR PERMANENT MAINTENANCE OF CERTAIN AREAS OF LAND IN ANUN-DEVELOPED STATE, WITH THE CONSENT OF THE PROPERTY OWNERS; ENCOURAGES PRESERVATION OF LARGE

AREAS OF TREES AND OPEN SPACE; DESIGNED TO PROTECT SCENIC AND ENVIRONMENTALLY SENSITIVE AREAS AND

ENSURE RETENTION OF LAND FOR NONINTENSIVE ACTIVE OR PASSIVE RECREATIONAL USES; PROVIDES FOR VERY LOWDENSITY RESIDENTIAL DEVELOPMENT AND A LIMITED RANGE OF PUBLIC, RECREATIONAL, AND AGRICULTURAL USES.

R-R: RURAL RESIDENTIAL - PERMITS APPROXIMATELY ONE-HALF-ACRE

RESIDENTIAL LOTS; SUBDIVISION LOT SIZES DEPEND ON DATE OF

RECORDATION; ALLOWS A NUMBER OF NONRESIDENTIAL SPECIAL EXCEPTIONUSES.

O-S: OPEN SPACE - PROVIDES FOR AREAS OF LOW-INTENSITY RESIDENTIAL (5 ACRE) DEVELOPMENT;

PROMOTES THE ECONOMIC USE AND CONSERVATION OF LAND FOR AGRICULTURE, NATURAL

RESOURCE USE, LARGE-LOT RESIDENTIAL ESTATES, NONINTENSIVE RECREATIONAL USE.

Page 7: T-Mobile Antenna Site

COMPOUND PLAN

COMPOUND PLAN

0

( IN FEET )

(DO NOT SCALE 11"X17" DRAWINGS)

GRAPHIC SCALE

2010510

SCALE: 1" = 10' FOR 24"X36" DRAWINGS

C-3

08\7

WA

S039C

.USD

A -

Lau

rel.C

D.R

EV

A.d

wg\

C-3

B

y: M

AY

LW

AR

D

REV DATE DESCRIPTION

SHEET TITLE :

DRAWNBY

CHECKEDBY

Customer Loyalty through Client Satisfactionw w w . m a s e r c o n s u l t i n g . c o m

PROTECT YOURSELF

Engineers Planners SurveyorsLandscape Architects Environmental Scientists

Copyright © 2017. Maser Consulting P.A. All Rights Reserved. This drawing and all the information

contained herein is authorized for use only by the party for whom the services were contracted orto whom it is certified. This drawing may not be copied, reused, disclosed, distributed or relied

upon for any other purpose without the express written consent of Maser Consulting, P.A.

Know what'sbelow.before you dig.Call

R

ALL STATES REQUIRE NOTIFICATION OF

EXCAVATORS, DESIGNERS, OR ANY PERSONPREPARING TO DISTURB THE EARTH'S

SURFACE ANYWHERE IN ANY STATE

Office Locations:

FOR STATE SPECIFIC DIRECT PHONE NUMBERS VISIT:WWW.CALL811.COM

C O N S U L T I N G P. A.

n Red Bank, NJn Clinton, NJn Hamilton, NJn Marmora, NJn Mt. Arlington, NJn Mt. Laurel, NJ

n Sterling, VAn Norfolk, VAn Albuquerque, NMn Albany, NYn Chestnut Ridge, NYn Newburgh, NY

n Hawthorne, NYn Lehigh Valley, PAn Exton, PAn Philadelphia, PAn Columbia, MDn Tampa, FL

IT IS A VIOLATION OF LAW FOR ANY PERSON, UNLESSTHEY ARE ACTING UNDER THE DIRECTION OF THE

RESPONSIBLE LICENSED PROFFESIONAL ENGINEER, TOALTER THIS DOCUMENT.

SITE NAME:

SCALE : JOB NUMBER :

SHEET NUMBER :

COLUMBIA OFFICE6240 Old Dobbin Lane,

Suite 150Columbia, MD 21045

Phone: 877.627.3772

7WAS039CUSDA-LAUREL

EDMONSTON RDGREENBELT, MD 20770

PRINCE GEORGE'S COUNTY

AS SHOWN 17958170

A 11/01/17 FOR REVIEW MCA NSB

. . . . .

. . . . .

. . . . .

. . . . .

. . . . .

. . . . .

. . . . .

_____________________________

MARYLAND PROFESSIONAL

NICHOLAS S. BERTE, P.E.

ENGINEER - LICENSE NUMBER: 37157"Professional Certification. I hereby certify that these documentswere prepared or approved by me, and that I am a duly licensedprofessional engineer under the laws of the State of Maryland,

License No. 0037157, Expiration Date: July 17, 2019"

12050 BALTIMORE AVENUE

BELTSVILLE, MD 20705

PHONE: (240) 264-8600

FAX: (240) 264-8610

T-MOBILE NORTHEAST LLC

SITE LINK WIRELESS, LLC3620 COMMERCE DRIVE

SUITE 707

BALTIMORE, MD 21227

NS

E

W

NORTH

PROPOSED 6 X 12 HYBRID CABLETO RUN UP WATER TANKTO PROPOSED ANTENNA

Page 8: T-Mobile Antenna Site

ELEVATION VIEW

C-4

08\7

WA

S039C

.USD

A -

Lau

rel.C

D.R

EV

A.d

wg\

C-4

B

y: M

AY

LW

AR

D

REV DATE DESCRIPTION

SHEET TITLE :

DRAWNBY

CHECKEDBY

Customer Loyalty through Client Satisfactionw w w . m a s e r c o n s u l t i n g . c o m

PROTECT YOURSELF

Engineers Planners SurveyorsLandscape Architects Environmental Scientists

Copyright © 2017. Maser Consulting P.A. All Rights Reserved. This drawing and all the information

contained herein is authorized for use only by the party for whom the services were contracted orto whom it is certified. This drawing may not be copied, reused, disclosed, distributed or relied

upon for any other purpose without the express written consent of Maser Consulting, P.A.

Know what'sbelow.before you dig.Call

R

ALL STATES REQUIRE NOTIFICATION OF

EXCAVATORS, DESIGNERS, OR ANY PERSONPREPARING TO DISTURB THE EARTH'S

SURFACE ANYWHERE IN ANY STATE

Office Locations:

FOR STATE SPECIFIC DIRECT PHONE NUMBERS VISIT:WWW.CALL811.COM

C O N S U L T I N G P. A.

n Red Bank, NJn Clinton, NJn Hamilton, NJn Marmora, NJn Mt. Arlington, NJn Mt. Laurel, NJ

n Sterling, VAn Norfolk, VAn Albuquerque, NMn Albany, NYn Chestnut Ridge, NYn Newburgh, NY

n Hawthorne, NYn Lehigh Valley, PAn Exton, PAn Philadelphia, PAn Columbia, MDn Tampa, FL

IT IS A VIOLATION OF LAW FOR ANY PERSON, UNLESSTHEY ARE ACTING UNDER THE DIRECTION OF THE

RESPONSIBLE LICENSED PROFFESIONAL ENGINEER, TOALTER THIS DOCUMENT.

SITE NAME:

SCALE : JOB NUMBER :

SHEET NUMBER :

COLUMBIA OFFICE6240 Old Dobbin Lane,

Suite 150Columbia, MD 21045

Phone: 877.627.3772

7WAS039CUSDA-LAUREL

EDMONSTON RDGREENBELT, MD 20770

PRINCE GEORGE'S COUNTY

AS SHOWN 17958170

A 11/01/17 FOR REVIEW MCA NSB

. . . . .

. . . . .

. . . . .

. . . . .

. . . . .

. . . . .

. . . . .

_____________________________

MARYLAND PROFESSIONAL

NICHOLAS S. BERTE, P.E.

ENGINEER - LICENSE NUMBER: 37157"Professional Certification. I hereby certify that these documentswere prepared or approved by me, and that I am a duly licensedprofessional engineer under the laws of the State of Maryland,

License No. 0037157, Expiration Date: July 17, 2019"

12050 BALTIMORE AVENUE

BELTSVILLE, MD 20705

PHONE: (240) 264-8600

FAX: (240) 264-8610

T-MOBILE NORTHEAST LLC

SITE LINK WIRELESS, LLC3620 COMMERCE DRIVE

SUITE 707

BALTIMORE, MD 21227

ELEVATION VIEW

0

( IN FEET )

(DO NOT SCALE 11"X17" DRAWINGS)

GRAPHIC SCALE

2010510

SCALE: 1" = 10' FOR 24"X36" DRAWINGS

PROPOSED 6 X 12 HYBRID CABLETO RUN UP WATER TANKTO PROPOSED ANTENNA

PROPOSED AIR32 ANTENNATO BE INSTALLED

(TYP. 3 TOTAL, 1 PER SECTOR)

CENTERLINE OF PROPOSEDT-MOBILE WIRELESS ANTENNA

@ 135'± (A.G.L.)

ELEVATION VIEW

0

( IN FEET )

(DO NOT SCALE 11"X17" DRAWINGS)

GRAPHIC SCALE

2010510

SCALE: 1" = 10' FOR 24"X36" DRAWINGS

N

S

EW

NO

RT

H

Page 9: T-Mobile Antenna Site

ANTENNA RF SYSTEM

SCHEDULE AND ORIENTATION

C-5

08\7

WA

S039C

.USD

A -

Lau

rel.C

D.R

EV

A.d

wg\

C-5

B

y: M

AY

LW

AR

D

REV DATE DESCRIPTION

SHEET TITLE :

DRAWNBY

CHECKEDBY

Customer Loyalty through Client Satisfactionw w w . m a s e r c o n s u l t i n g . c o m

PROTECT YOURSELF

Engineers Planners SurveyorsLandscape Architects Environmental Scientists

Copyright © 2017. Maser Consulting P.A. All Rights Reserved. This drawing and all the information

contained herein is authorized for use only by the party for whom the services were contracted orto whom it is certified. This drawing may not be copied, reused, disclosed, distributed or relied

upon for any other purpose without the express written consent of Maser Consulting, P.A.

Know what'sbelow.before you dig.Call

R

ALL STATES REQUIRE NOTIFICATION OF

EXCAVATORS, DESIGNERS, OR ANY PERSONPREPARING TO DISTURB THE EARTH'S

SURFACE ANYWHERE IN ANY STATE

Office Locations:

FOR STATE SPECIFIC DIRECT PHONE NUMBERS VISIT:WWW.CALL811.COM

C O N S U L T I N G P. A.

n Red Bank, NJn Clinton, NJn Hamilton, NJn Marmora, NJn Mt. Arlington, NJn Mt. Laurel, NJ

n Sterling, VAn Norfolk, VAn Albuquerque, NMn Albany, NYn Chestnut Ridge, NYn Newburgh, NY

n Hawthorne, NYn Lehigh Valley, PAn Exton, PAn Philadelphia, PAn Columbia, MDn Tampa, FL

IT IS A VIOLATION OF LAW FOR ANY PERSON, UNLESSTHEY ARE ACTING UNDER THE DIRECTION OF THE

RESPONSIBLE LICENSED PROFFESIONAL ENGINEER, TOALTER THIS DOCUMENT.

SITE NAME:

SCALE : JOB NUMBER :

SHEET NUMBER :

COLUMBIA OFFICE6240 Old Dobbin Lane,

Suite 150Columbia, MD 21045

Phone: 877.627.3772

7WAS039CUSDA-LAUREL

EDMONSTON RDGREENBELT, MD 20770

PRINCE GEORGE'S COUNTY

AS SHOWN 17958170

A 11/01/17 FOR REVIEW MCA NSB

. . . . .

. . . . .

. . . . .

. . . . .

. . . . .

. . . . .

. . . . .

_____________________________

MARYLAND PROFESSIONAL

NICHOLAS S. BERTE, P.E.

ENGINEER - LICENSE NUMBER: 37157"Professional Certification. I hereby certify that these documentswere prepared or approved by me, and that I am a duly licensedprofessional engineer under the laws of the State of Maryland,

License No. 0037157, Expiration Date: July 17, 2019"

12050 BALTIMORE AVENUE

BELTSVILLE, MD 20705

PHONE: (240) 264-8600

FAX: (240) 264-8610

T-MOBILE NORTHEAST LLC

SITE LINK WIRELESS, LLC3620 COMMERCE DRIVE

SUITE 707

BALTIMORE, MD 21227

METALLIC TAG NOTES:

1. TWO METALLIC TAGS SHALL BE ATTACHED AT EACHEND OF EVERY CABLE LONGER THAN (3) THREE FEET.

2. CABLES LESS THAN (3) THREE FEET WILL HAVE TWOMETALLIC TAGS ATTACHED AT THE CENTER OF THECABLE.

3. TAGS WILL BE FASTENED WITH STAINLESS STEEL ZIP TIESAPPROPRIATE FOR CABLE DIAMETER.

4. STANDARDIZED METALLIC TAG KITS WILL BE ASSEMBLEDWITH TAGS ALREADY ENGRAVED TO ACCOMMODATEALL CONFIGURATIONS.

COLOR CODING NOTES:

R - RED - GSMG - GREEN - UMTS 1900B - BLUE - UMTS AWSY - YELLOW - LTEO - ORANGE - FIBER CABLE

EXISTING ANTENNA ORIENTATION PLANNOT TO SCALE

1

N

S

EW

NO

RT

H

A1

A2

A3

B1B2

B3

C1

C2

C3

A1

A2

A3

B1B2

B3

C1

C2

C3

GAM

MA SEC

TO

R

AZ = 325°

PRO

POSED

AN

TEN

NA M

OD

EL:

AIR32 B66A

/B2A

ALPHA SECTOR

AZ = 70°

PROPOSED ANTENNA MODEL:

AIR32 B66A/B2P

BET

A S

EC

TO

R

AZ

=180°

PR

OPO

SED

AN

TEN

NA

MO

DEL:

AIR

32 B

66A

/B2P

PROPOSED AIR32 ANTENNATO BE INSTALLED

(TYP. 3 TOTAL, 1 PER SECTOR)

PROPOSED ANTENNA ORIENTATION PLANNOT TO SCALE

2

NOTES:1. ALL CHANGES TO THIS SCHEDULE SHALL BE APPROVED BY T-MOBILE RF ENGINEERING.2. BASED ON ANTENNA DESIGN DATED ON 08/22/17

3. CONTRACTOR TO VERIFY ANTENNA INFORMATION WITH CONSTRUCTION MANAGER BEFORE PURCHASING EQUIPMENT4. CONTRACTOR TO TEST COAX PER T-MOBILE SWEEP STANDARDS

Page 10: T-Mobile Antenna Site

CONSTRUCTION DETAILS

C-6

ANTENNA DETAILS NOT TO SCALE

1

08\7

WA

S039C

.USD

A -

Lau

rel.C

D.R

EV

A.d

wg\

C-6

B

y: M

AY

LW

AR

D

REV DATE DESCRIPTION

SHEET TITLE :

DRAWNBY

CHECKEDBY

Customer Loyalty through Client Satisfactionw w w . m a s e r c o n s u l t i n g . c o m

PROTECT YOURSELF

Engineers Planners SurveyorsLandscape Architects Environmental Scientists

Copyright © 2017. Maser Consulting P.A. All Rights Reserved. This drawing and all the information

contained herein is authorized for use only by the party for whom the services were contracted orto whom it is certified. This drawing may not be copied, reused, disclosed, distributed or relied

upon for any other purpose without the express written consent of Maser Consulting, P.A.

Know what'sbelow.before you dig.Call

R

ALL STATES REQUIRE NOTIFICATION OF

EXCAVATORS, DESIGNERS, OR ANY PERSONPREPARING TO DISTURB THE EARTH'S

SURFACE ANYWHERE IN ANY STATE

Office Locations:

FOR STATE SPECIFIC DIRECT PHONE NUMBERS VISIT:WWW.CALL811.COM

C O N S U L T I N G P. A.

n Red Bank, NJn Clinton, NJn Hamilton, NJn Marmora, NJn Mt. Arlington, NJn Mt. Laurel, NJ

n Sterling, VAn Norfolk, VAn Albuquerque, NMn Albany, NYn Chestnut Ridge, NYn Newburgh, NY

n Hawthorne, NYn Lehigh Valley, PAn Exton, PAn Philadelphia, PAn Columbia, MDn Tampa, FL

IT IS A VIOLATION OF LAW FOR ANY PERSON, UNLESSTHEY ARE ACTING UNDER THE DIRECTION OF THE

RESPONSIBLE LICENSED PROFFESIONAL ENGINEER, TOALTER THIS DOCUMENT.

SITE NAME:

SCALE : JOB NUMBER :

SHEET NUMBER :

COLUMBIA OFFICE6240 Old Dobbin Lane,

Suite 150Columbia, MD 21045

Phone: 877.627.3772

7WAS039CUSDA-LAUREL

EDMONSTON RDGREENBELT, MD 20770

PRINCE GEORGE'S COUNTY

AS SHOWN 17958170

A 11/01/17 FOR REVIEW MCA NSB

. . . . .

. . . . .

. . . . .

. . . . .

. . . . .

. . . . .

. . . . .

_____________________________

MARYLAND PROFESSIONAL

NICHOLAS S. BERTE, P.E.

ENGINEER - LICENSE NUMBER: 37157"Professional Certification. I hereby certify that these documentswere prepared or approved by me, and that I am a duly licensedprofessional engineer under the laws of the State of Maryland,

License No. 0037157, Expiration Date: July 17, 2019"

12050 BALTIMORE AVENUE

BELTSVILLE, MD 20705

PHONE: (240) 264-8600

FAX: (240) 264-8610

T-MOBILE NORTHEAST LLC

SITE LINK WIRELESS, LLC3620 COMMERCE DRIVE

SUITE 707

BALTIMORE, MD 21227

ANTENNA MODEL:ERICSSON WIRELESS: AIR32 DB

WEIGHT WITHOUT MOUNTING BRACKET= 132.2 LBS

FRONT SIDE

12.9" 8.7"

56.6

"

PROPOSED 2" SCH 40(2.375" O.D.) AT 96"

TALL PIPE MAST(TO REPLACE EXISTING

AS NEEDED)

PROPOSED ANTENNAMOUNTING BRACKET (TYP.)

PROPOSED T-MOBILEAIR ANTENNA

AIR ANTENNA MOUNTING DETAILNOT TO SCALE

2

Page 11: T-Mobile Antenna Site

E-1

ELECTRIC DETAILS

08\7

WA

S039C

.USD

A -

Lau

rel.C

D.R

EV

A.d

wg\

E-1

B

y: M

AY

LW

AR

D

REV DATE DESCRIPTION

SHEET TITLE :

DRAWNBY

CHECKEDBY

Customer Loyalty through Client Satisfactionw w w . m a s e r c o n s u l t i n g . c o m

PROTECT YOURSELF

Engineers Planners SurveyorsLandscape Architects Environmental Scientists

Copyright © 2017. Maser Consulting P.A. All Rights Reserved. This drawing and all the information

contained herein is authorized for use only by the party for whom the services were contracted orto whom it is certified. This drawing may not be copied, reused, disclosed, distributed or relied

upon for any other purpose without the express written consent of Maser Consulting, P.A.

Know what'sbelow.before you dig.Call

R

ALL STATES REQUIRE NOTIFICATION OF

EXCAVATORS, DESIGNERS, OR ANY PERSONPREPARING TO DISTURB THE EARTH'S

SURFACE ANYWHERE IN ANY STATE

Office Locations:

FOR STATE SPECIFIC DIRECT PHONE NUMBERS VISIT:WWW.CALL811.COM

C O N S U L T I N G P. A.

n Red Bank, NJn Clinton, NJn Hamilton, NJn Marmora, NJn Mt. Arlington, NJn Mt. Laurel, NJ

n Sterling, VAn Norfolk, VAn Albuquerque, NMn Albany, NYn Chestnut Ridge, NYn Newburgh, NY

n Hawthorne, NYn Lehigh Valley, PAn Exton, PAn Philadelphia, PAn Columbia, MDn Tampa, FL

IT IS A VIOLATION OF LAW FOR ANY PERSON, UNLESSTHEY ARE ACTING UNDER THE DIRECTION OF THE

RESPONSIBLE LICENSED PROFFESIONAL ENGINEER, TOALTER THIS DOCUMENT.

SITE NAME:

SCALE : JOB NUMBER :

SHEET NUMBER :

COLUMBIA OFFICE6240 Old Dobbin Lane,

Suite 150Columbia, MD 21045

Phone: 877.627.3772

7WAS039CUSDA-LAUREL

EDMONSTON RDGREENBELT, MD 20770

PRINCE GEORGE'S COUNTY

AS SHOWN 17958170

A 11/01/17 FOR REVIEW MCA NSB

. . . . .

. . . . .

. . . . .

. . . . .

. . . . .

. . . . .

. . . . .

_____________________________

MARYLAND PROFESSIONAL

NICHOLAS S. BERTE, P.E.

ENGINEER - LICENSE NUMBER: 37157"Professional Certification. I hereby certify that these documentswere prepared or approved by me, and that I am a duly licensedprofessional engineer under the laws of the State of Maryland,

License No. 0037157, Expiration Date: July 17, 2019"

12050 BALTIMORE AVENUE

BELTSVILLE, MD 20705

PHONE: (240) 264-8600

FAX: (240) 264-8610

T-MOBILE NORTHEAST LLC

SITE LINK WIRELESS, LLC3620 COMMERCE DRIVE

SUITE 707

BALTIMORE, MD 21227

1

EXISTING MGB (BUSSBAR #1)

PROPOSED FIBER GROUNDING KIT(COMMSCOPE PART #UG12158-15B4-T)

GROUNDING SCHEDULE

EXISTING EQUIPMENT GROUNDING

NOTES:A. PROVIDE #2AWG GROUNDING

CONDUCTOR, U.O.N.

B. DO NOT INSTALL GROUND KIT AT BEND.DIRECT GROUND WIRE DOWN TOANTENNA BUSSBAR.

C. PROVIDE GROUNDING ELECTRODES INQUANTITY, TYPE AND SIZE AS INDICATEDON SITE GROUNDING PLAN.

D. ADD COAX GROUND KIT CONNECTION TOBUSSBAR WHEN LENGTH OF COAX RUN(FROM EQUIPMENT TO ANTENNA) ISGREATER THAN 20'-0".

23

EXISTING SECTOR GROUND BAR45

GROUND PROPOSED ANTENNA PER MANUFACTURES SPECS

UTILITY DIAGRAMNOT TO SCALE

1

NOT TO SCALE2

PANEL SCHEDULE

PROPOSED AIR32 ANTENNATO BE INSTALLED(TYP. 3 TOTAL, 1 PER SECTOR)

(CONTRACTOR TO VERIFY GROUND RINGWIRE SIZE PER NEC SECTION 250.52-4-A

AND CONNECTION TO GROUND RINGPER NEC 250-66 (C))

NEC SECTION 250.52 - GROUNDING ELECTRODES

(A) ELECTRODES PERMITTED FOR GROUNDING

(4) GROUND RING

A GROUND RING ENCIRCLING THE BUILDING OR STRUCTURE, IN DIRECTCONTACT WITH THE EARTH CONSISTING OF AT LEAST 6.0 M (20 FT ) OF BARECOPPER CONDUCTOR NOT SMALLER THAN 2 AWG.

NEC SECTION 250-66-C

(C) CONNECTIONS TO GROUND RINGS

IF THE GROUNDING ELECTRODE CONDUCTOR OR BONDING JUMPER CONNECTEDTO A GROUND RING AS DESCRIBED IN 250.52 (A) (4), DOES NOT EXTEND ON TO

OTHER TYPES OF ELECTRODES THAT REQUIRE A LARGER SIZE OF CONDUCTOR, THEGROUNDING ELECTRODE CONDUCTOR SHALL NOT BE REQUIRED TO BE LARGERTHAN THE CONDUCTOR USED FOR THE GROUND RING.

Page 12: T-Mobile Antenna Site

E-2

GROUNDING DETAILS

08\7

WA

S039C

.USD

A -

Lau

rel.C

D.R

EV

A.d

wg\

E-2

B

y: M

AY

LW

AR

D

REV DATE DESCRIPTION

SHEET TITLE :

DRAWNBY

CHECKEDBY

Customer Loyalty through Client Satisfactionw w w . m a s e r c o n s u l t i n g . c o m

PROTECT YOURSELF

Engineers Planners SurveyorsLandscape Architects Environmental Scientists

Copyright © 2017. Maser Consulting P.A. All Rights Reserved. This drawing and all the information

contained herein is authorized for use only by the party for whom the services were contracted orto whom it is certified. This drawing may not be copied, reused, disclosed, distributed or relied

upon for any other purpose without the express written consent of Maser Consulting, P.A.

Know what'sbelow.before you dig.Call

R

ALL STATES REQUIRE NOTIFICATION OF

EXCAVATORS, DESIGNERS, OR ANY PERSONPREPARING TO DISTURB THE EARTH'S

SURFACE ANYWHERE IN ANY STATE

Office Locations:

FOR STATE SPECIFIC DIRECT PHONE NUMBERS VISIT:WWW.CALL811.COM

C O N S U L T I N G P. A.

n Red Bank, NJn Clinton, NJn Hamilton, NJn Marmora, NJn Mt. Arlington, NJn Mt. Laurel, NJ

n Sterling, VAn Norfolk, VAn Albuquerque, NMn Albany, NYn Chestnut Ridge, NYn Newburgh, NY

n Hawthorne, NYn Lehigh Valley, PAn Exton, PAn Philadelphia, PAn Columbia, MDn Tampa, FL

IT IS A VIOLATION OF LAW FOR ANY PERSON, UNLESSTHEY ARE ACTING UNDER THE DIRECTION OF THE

RESPONSIBLE LICENSED PROFFESIONAL ENGINEER, TOALTER THIS DOCUMENT.

SITE NAME:

SCALE : JOB NUMBER :

SHEET NUMBER :

COLUMBIA OFFICE6240 Old Dobbin Lane,

Suite 150Columbia, MD 21045

Phone: 877.627.3772

7WAS039CUSDA-LAUREL

EDMONSTON RDGREENBELT, MD 20770

PRINCE GEORGE'S COUNTY

AS SHOWN 17958170

A 11/01/17 FOR REVIEW MCA NSB

. . . . .

. . . . .

. . . . .

. . . . .

. . . . .

. . . . .

. . . . .

_____________________________

MARYLAND PROFESSIONAL

NICHOLAS S. BERTE, P.E.

ENGINEER - LICENSE NUMBER: 37157"Professional Certification. I hereby certify that these documentswere prepared or approved by me, and that I am a duly licensedprofessional engineer under the laws of the State of Maryland,

License No. 0037157, Expiration Date: July 17, 2019"

12050 BALTIMORE AVENUE

BELTSVILLE, MD 20705

PHONE: (240) 264-8600

FAX: (240) 264-8610

T-MOBILE NORTHEAST LLC

SITE LINK WIRELESS, LLC3620 COMMERCE DRIVE

SUITE 707

BALTIMORE, MD 21227

TYPE-BD18G92

TYPE-YAC3L-2TC38TYPE-KC TO

FLAT SURFACETYPE-KC TO PIPE

TYPE-YGIBS

TYPE GSTUD-HYTYPE YGHC-C

TYPE YGHC-CCABLE TO CABLE

TYPE GAR-BU & GAR3902CABLE TO PIPE

APPLICATION

TYPE BRG BRAID

FLEXIBLE SPLICEAPPLICATIONTYPE GAR-BUAPPLICATION

TAP CONNECTORCOMPRESSION GROUND

TYPE YGHR58C2W-3

CABLE TO ROD TO STEELTYPE GSTUD-HY

TAP CONNECTOR

TYPE YGHP58C2W-2COMPRESSION GROUND

TYPE TA

TYPE GT

TYPE VVTYPE VN

TYPE GY

TYPE VSTYPE NC

TYPE GRTYPE VB

TYPE SS

SOLI

D #

2 TIN

NED

CO

PPER

A, C, OR D

C

C

B OR C

B OR C

#2/O STRANDED GRNDGELECTRODE CONDUCTOR

STRUCTURAL OR TOWER STEEL

MASTER GROUND BAR

GROUND RING

TERMINATION TYPES:

A. MECHANICAL COMPRESSION LUGB. DOUBLE BARRELL COMPRESSION CONNECTORC. EXOTHERMIC TERMINATIOND. BEAM CLAMP

SOLID #2 TINNED COPPER

#6 GROUND LEAD

A

A, C, OR DA, C, OR D

C

A A

A, C, OR DA

C

BLD

G S

ERVIC

E EN

TR

OR G

RN

D R

ING

STRU

CTU

RA

L O

R

TO

WER

STEE

L

MA

STER

GRN

D B

AR

#2/

O S

TRA

ND

ED

MA

IN D

OW

N

C

ON

DU

CTO

R

#6

GRO

UN

D L

EAD

B OR C

A, C, OR D

A, C, OR DC

A

GRO

UN

D R

OD

C

1. OXIDE INHIBITING COMPOUND TO BE USED AT ALL LOCATIONS.

NOTES:

1'-8"

4"

6"

MIN

.

SECTION "A-A"

ELEVATION

2" MIN.1"

LUG NOTES:1. ALL HARDWARE IS 18-8 STAINLESS STEEL,

INCLUDING LOCK WASHERS.

2. ALL HARDWARE SHALL BE S.S. 38"Ø OR LARGER.

3. FOR GROUND BOND TO STEEL ONLY: INSERTA DRAGON TOOTH WASHER BETWEEN LUGAND STEEL. COAT ALL SURFACES WITHANTI-OXIDIZATION COMPOUND PRIOR TOMATING.

1/4" (TYP)

1/4

"

1/2

"

4"

MAIN GROUND BAR HOLE CONFIGURATION

BARE #2 IN 3 4" CTO GROUND RING

#6 FROM COAX CABLEGROUNDING KITS (TYP)

TYPE GLTYPE PT

#2 BARE SOLID-TINNED COPPERCONDUCTOR TO GROUNDBUS

516"(TYP)

1116"

NOTES:1. ALL HARDWARE STAINLESS STEEL COAT ALL SURFACES WITH

KOPR-SHIELD BEFORE MATING.

2. FOR GROUND BOND TO STEEL ONLY: INSERT A TOOTH WASHERBETWEEN LUG AND STEEL, COAT ALL SURFACES WITH KOPR-SHIELD.

3. ALL HOLES ARE COUNTERSUNK 116".

112"(TYP)

34"

1 3 4"

NEW COPPER GROUND BAR INSTALLED BYGENERAL CONTRACTOR.

NEW COAXIAL GROUND KITS WITH LONG BARRELCOMPRESSION LUGS WITH TWO (2) 3/8"Ø BOLTS AND LOCKWASHERS SIMILAR TO ANDREW 3241088-9.

#2AWG WITH LONG BARREL COMPRESSION LUGS, USE STAR WASHERS,LOCKWASHERS, AND STAINLESS STEEL HARDWARE TO SECURE TOEXTERNAL GROUND BAR BY GENERAL CONTRACTOR.

FLAT WASHER (TYP)

12"x11

2" HEX BOLT

GROUND BAR

GROUNDING CABLE

NUT (TYP)

STAR WASHER (TYP)

EXPOSED BARE COPPER TO BE KEPT TOABSOLUTE MINIMUM, NO INSULATIONALLOWED WITHIN THE COMPRESSIONTERMINAL (TYP.)

STAINLESS STEEL HARDWARE

TWO HOLE COPPERCOMPRESSION TERMINAL

GROUNDING CABLE

GROUND BAR

INSULATORS ON BRACKETSMOUNTED TO MONOPOLE

MAIN GROUND BAR(HERGER CAT. NO TGBI142220G)

HOLE FORMOUNTING BRACKET

EXOTHERMICALLY WELD(2) #2 TO MAIN GROUND

BAR

LABEL

S.S. NUT

S.S. LOCK WASHER

S.S. BOLT

S.S. FLAT WASHER

GROUND BAR

HEAT SHRINK

A

A

BURNDY GROUNDING DETAILSNOT TO SCALE

1

BURNDY GROUNDING PRODUCTSNOT TO SCALE

2

CALWELD GROUNDING PRODUCTSNOT TO SCALE

3

GROUNDING TERMINATION MATRIXNOT TO SCALE

4

TYPICAL GROUND BAR CONNECTIONS DETAILNOT TO SCALE

5GROUND BAR DETAILNOT TO SCALE

6

Page 13: T-Mobile Antenna Site

N-1

GENERAL AND

ELECTRICAL NOTES

08\7

WA

S039C

.USD

A -

Lau

rel.C

D.R

EV

A.d

wg\

N-1

B

y: M

AY

LW

AR

D

REV DATE DESCRIPTION

SHEET TITLE :

DRAWNBY

CHECKEDBY

Customer Loyalty through Client Satisfactionw w w . m a s e r c o n s u l t i n g . c o m

PROTECT YOURSELF

Engineers Planners SurveyorsLandscape Architects Environmental Scientists

Copyright © 2017. Maser Consulting P.A. All Rights Reserved. This drawing and all the information

contained herein is authorized for use only by the party for whom the services were contracted orto whom it is certified. This drawing may not be copied, reused, disclosed, distributed or relied

upon for any other purpose without the express written consent of Maser Consulting, P.A.

Know what'sbelow.before you dig.Call

R

ALL STATES REQUIRE NOTIFICATION OF

EXCAVATORS, DESIGNERS, OR ANY PERSONPREPARING TO DISTURB THE EARTH'S

SURFACE ANYWHERE IN ANY STATE

Office Locations:

FOR STATE SPECIFIC DIRECT PHONE NUMBERS VISIT:WWW.CALL811.COM

C O N S U L T I N G P. A.

n Red Bank, NJn Clinton, NJn Hamilton, NJn Marmora, NJn Mt. Arlington, NJn Mt. Laurel, NJ

n Sterling, VAn Norfolk, VAn Albuquerque, NMn Albany, NYn Chestnut Ridge, NYn Newburgh, NY

n Hawthorne, NYn Lehigh Valley, PAn Exton, PAn Philadelphia, PAn Columbia, MDn Tampa, FL

IT IS A VIOLATION OF LAW FOR ANY PERSON, UNLESSTHEY ARE ACTING UNDER THE DIRECTION OF THE

RESPONSIBLE LICENSED PROFFESIONAL ENGINEER, TOALTER THIS DOCUMENT.

SITE NAME:

SCALE : JOB NUMBER :

SHEET NUMBER :

COLUMBIA OFFICE6240 Old Dobbin Lane,

Suite 150Columbia, MD 21045

Phone: 877.627.3772

7WAS039CUSDA-LAUREL

EDMONSTON RDGREENBELT, MD 20770

PRINCE GEORGE'S COUNTY

AS SHOWN 17958170

A 11/01/17 FOR REVIEW MCA NSB

. . . . .

. . . . .

. . . . .

. . . . .

. . . . .

. . . . .

. . . . .

_____________________________

MARYLAND PROFESSIONAL

NICHOLAS S. BERTE, P.E.

ENGINEER - LICENSE NUMBER: 37157"Professional Certification. I hereby certify that these documentswere prepared or approved by me, and that I am a duly licensedprofessional engineer under the laws of the State of Maryland,

License No. 0037157, Expiration Date: July 17, 2019"

12050 BALTIMORE AVENUE

BELTSVILLE, MD 20705

PHONE: (240) 264-8600

FAX: (240) 264-8610

T-MOBILE NORTHEAST LLC

SITE LINK WIRELESS, LLC3620 COMMERCE DRIVE

SUITE 707

BALTIMORE, MD 21227

WORK INCLUDED1. INCLUDE ALL LABOR, MATERIALS, EQUIPMENT, PLANT SERVICES AND ADMINISTRATIVE

TASKS REQUIRED TO COMPLETE AND MAKE OPERABLE THE ELECTRICAL WORK SHOWNON THE DRAWINGS AND SPECIFIED HEREIN, INCLUDING BUT NOT LIMITED TO THEFOLLOWING:

A. PREPARE AND SUBMIT SHOP DRAWINGS, DIAGRAMS AND ILLUSTRATIONS.

B. PROCURE ALL NECESSARY PERMITS AND APPROVALS AND PAY ALL REQUIRED FEESAND CHARGES IN CONNECTION WITH THE WORK OF THIS CONTRACT.

C. SUBMIT AS-BUILT DRAWINGS, OPERATING AND MAINTENANCE INSTRUCTIONSAND MANUALS. EXECUTE ALL CUTTING, DRILLING, ROUGH AND FINISH PATCHINGOF EXISTING OR NEWLY INSTALLED CONSTRUCTION REQUIRED FOR THE WORKOF THIS CONTRACT. FOR SLAB

D. PENETRATIONS THROUGH POST TENSION SLABS, X-RAY EXACT AREA OFPENETRATION PRIOR TO PERFORMING WORK. COORDINATE ALL X-RAY WORKWITH BUILDING ENGINEER.

E. PROVIDE HANGERS, SUPPORTS, FOUNDATIONS, STRUCTURAL FRAMING SUPPORTS,AND BASES FOR CONDUIT AND EQUIPMENT PROVIDED OR INSTALLED UNDER THEWORK OF HIS CONTRACT. PROVIDE COUNTER FLASHING, SLEEVES AND SEALS FORFLOOR AND WALL PENETRATIONS.

F. MAINTAIN ALL EXISTING ELECTRICAL SERVICES IN THE BUILDING AREAS NOTAFFECTED BY THE ALTERATION DURING THE PROGRESS OF THE WORKINCLUDING PROVIDING ALL TEMPORARY JUMPERS, CONDUITS, CAPS, PROTECTIVEDEVICES, CONNECTIONS AND EQUIPMENT REQUIRED. PROVIDE TEMPORARYLIGHT AND POWER FOR CONSTRUCTION PURPOSES.

2. IT IS THE INTENT OF THESE DRAWINGS AND SPECIFICATIONS TO CALL FOR ANINSTALLATION THAT IS COMPLETE IN EVERY RESPECT. IT IS NOT THE INTENT TO GIVEEVERY DETAIL ON THE DRAWINGS AND IN THE SPECIFICATIONS. IF AN ITEM OF WORKIS INDICATED IN THE DRAWINGS, IT IS CONSIDERED SUFFICIENT FOR INCLUSION IN THECONTRACT. FURNISH AND INSTALL ALL MATERIAL AND EQUIPMENT USUALLYFURNISHED OR NEEDED TO MAKE A COMPLETE INSTALLATION WHETHER OR NOTSPECIFICALLY MENTIONED IN THE CONTRACT DOCUMENTS.

GENERAL REQUIREMENTS1. PROVIDE ALL WORK IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE (NEC)

AND LOCAL AND STATE ELECTRICAL CODES.

2. THE ELECTRICAL PLANS ARE DIAGRAMMATIC ONLY. REFER TO THE ARCHITECTURALPLANS FOR THE EXACT DIMENSIONS OF THE BUILDING.

3. LOAD CALCULATIONS ARE BASED ON EXISTING BUILDING INFORMATION/DRAWINGSPROVIDED TO ENGINEERING. CONTRACTOR IS TO VERIFY ALL EXISTING RATINGS ANDLOADS PRIOR TO PURCHASING OF SPECIFIED EQUIPMENT FOR COMPLIANCE TO NEC.CONTRACTOR TO NOTIFY ENGINEER OF ANY DISCREPANCIES AND REQUEST FURTHERDIRECTION BY ENGINEER.

4. EXISTING BUILDING EQUIPMENT IS NOTED ON THE DRAWINGS. NEW OR RELOCATEDEQUIPMENT IS SHOWN WITH SOLID LINES. FUTURE EQUIPMENT (NOT IN THISCONTRACT) IS DEPICTED WITH SHADED LINES. REQUEST CLARIFICATION OFDRAWINGS OR OF SPECIFICATIONS PRIOR TO PRICING OR INSTALLATION.

5. GENERALA. AFTER CAREFULLY STUDYING THE DRAWINGS AND SPECIFICATIONS, AND BEFORE

SUBMITTING THE PROPOSAL, MAKE A MANDATORY SITE VISIT TO ASCERTAINCONDITIONS OF THE SITE, AND THE NATURE AND EXACT QUANTITY OF WORKTO BE PERFORMED. NO EXTRA COMPENSATION WILL BE ALLOWED FOR FAILURETO NOTIFY THE OWNER, IN WRITING, OF ANY DISCREPANCIES THAT MAY HAVEBEEN NOTED BETWEEN THE EXISTING CONDITIONS AND THE DRAWINGS ANDSPECIFICATIONS.

B. VERIFY ALL MEASUREMENTS AT THE SITE AND BE RESPONSIBLE FOR CORRECTNESSOF SAME.

6. QUALITY, WORKMANSHIP, MATERIALS AND SAFETYA. PROVIDE NEW MATERIALS AND EQUIPMENT OF A DOMESTIC MANUFACTURER BY

THOSE REGULARLY ENGAGED IN THE PRODUCTION AND MANUFACTURE OFSPECIFIED MATERIALS AND EQUIPMENT. WHERE UL, OR OTHER AGENCY, HASESTABLISHED STANDARDS FOR MATERIALS, PROVIDE MATERIALS WHICH ARELISTED AND LABELED ACCORDINGLY. THE COMMERCIALLY STANDARD ITEMS OFEQUIPMENT AND THE SPECIFIC NAMES MENTIONED HEREIN ARE INTENDED FORTHE PROPER FUNCTIONING OF THE WORK.

B. WORK SHALL BE PERFORMED BY WORKMEN SKILLED IN THE TRADE REQUIRED FORTHE WORK. INSTALL MATERIALS AND EQUIPMENT TO PRESENT A NEATAPPEARANCE WHEN COMPLETED AND IN ACCORDANCE WITH THE APPROVEDRECOMMENDATIONS OF THE MANUFACTURER AND IN ACCORDANCE WITHCONTRACT DOCUMENTS.

C. PROVIDE LABOR, MATERIALS, APPARATUS AND APPLIANCES ESSENTIAL TO THEFUNCTIONING OF THE SYSTEMS DESCRIBED OR INDICATED HEREIN, OR WHICHMAY BE REASONABLY IMPLIED AS ESSENTIAL WHENEVER MENTIONED IN THECONTRACT DOCUMENT OR NOT.

D. MAKE WRITTEN REQUESTS FOR SUPPLEMENTARY INSTRUCTIONS TOARCHITECT/ENGINEER IN CASE OF DOUBT AS TO WORK INTENDED OR IN EVENTOF NEED FOR EXPLANATION THEREOF.

E. PERFORMANCE AND MATERIAL REQUIREMENTS SCHEDULED OR SPECIFIED AREMINIMUM STANDARD ACCEPTABLE. THE RIGHT TO JUDGE THE QUALITY OFEQUIPMENT THAT DEVIATES FROM THE CONTRACT DOCUMENT REMAINS SOLELYWITH ARCHITECT/ENGINEER. CONTRACT DOCUMENT OR NOT.

GUARANTEE1. GUARANTEE MATERIALS, PARTS AND LABOR FOR WORK FOR ONE YEAR FROM THE

DATE OF ISSUANCE OF OCCUPANCY PERMIT. DURING THAT PERIOD, MAKE GOODFAULTS OR IMPERFECTIONS THAT MAY ARISE DUE TO DEFECTS OR OMISSIONS INMATERIALS OR WORKMANSHIP WITH NO ADDITIONAL COMPENSATION AND ASDIRECTED BY ARCHITECT.

CLEANING1. REMOVE ALL CONSTRUCTION DEBRIS RESULTING FROM THE WORK.

2. CLEAN EQUIPMENT AND SYSTEMS FOLLOWING THE COMPLETION OF THE PROJECT TOTHE SATISFACTION OF THE ENGINEER.

COORDINATION AND SUPERVISION1. CAREFULLY LAY OUT ALL WORK IN ADVANCE TO AVOID UNNECESSARY CUTTING,

CHANNELING, CHASING OR DRILLING OF FLOORS, WALLS, PARTITIONS, CEILINGS OROTHER SURFACES. WHERE SUCH WORK IS NECESSARY, HOWEVER, PATCH AND REPAIRTHE WORK IN AN APPROVED MANNER BY SKILLED MECHANICS AT NO ADDITIONALCOST TO THE OWNER. RENDER FULL COOPERATION TO OTHER TRADES WHEREWORK WILL BE INSTALLED IN CLOSE PROXIMITY TO WORK OF OTHER TRADES. ASSISTIN WORKING OUT SPACE CONDITIONS. IF WORK IS INSTALLED BEFORECOORDINATION WITH OTHER TRADES, OR CAUSES INTERFERENCE, MAKE CHANGESNECESSARY TO CORRECT CONDITIONS WITHOUT EXTRA CHARGE.

SUBMITTALS1. AS-BUILT DRAWINGS:

A. UPON COMPLETION OF THE WORK, FURNISH TO THE OWNER "AS-BUILT"DRAWINGS.

2. SERVICE MANUALS:

A. UPON COMPLETION OF THE WORK, FULLY INSTRUCT T-MOBILE AS TO THEOPERATION AND MAINTENANCE OF ALL MATERIAL, EQUIPMENT AND SYSTEMS.

B. PROVIDE 3 COMPLETE BOUND SETS OF INSTRUCTIONS FOR OPERATING ANDMAINTAINING ALL SYSTEMS AND EQUIPMENT.

CUTTING AND PATCHING1. PROVIDE ALL CUTTING, DRILLING, ROUGH AND FINISH PATCHING REQUIRED TO

COMPLETE THE WORK.

2. OBTAIN OWNER APPROVAL PRIOR TO CUTTING THROUGH FLOORS OR WALLS FORPIPING OR CONDUIT.

TESTS, INSPECTION AND APPROVAL1. BEFORE ENERGIZING ANY ELECTRICAL INSTALLATION, INSPECT EACH UNIT IN DETAIL.

TIGHTEN ALL BOLTS AND CONNECTIONS (TORQUE-TIGHTEN WHERE REQUIRED) ANDDETERMINE THAT ALL COMPONENTS ARE ALIGNED, AND THE EQUIPMENT IS IN SAFE,OPERATIONAL CONDITION.

2. PROVIDE THE COMPLETE ELECTRICAL SYSTEM FREE OF GROUND FAULTS AND SHORTCIRCUITS SUCH THAT THE SYSTEM WILL OPERATE SATISFACTORILY UNDER FULL LOADCONDITIONS, WITHOUT EXCESSIVE HEATING AT ANY POINT IN THE SYSTEM.

SPECIAL REQUIREMENTS1. DO NOT LEAVE ANY WORK INCOMPLETE NOR ANY HAZARDOUS SITUATIONS

CREATED WHICH WILL AFFECT THE LIFE OR SAFETY OF THE PUBLIC AND/OR BUILDINGOCCUPANTS. DO NOT INTERFERE WITH OR CUTOFF ANY OF THE EXISTING SERVICESWITHOUT THE OWNER'S WRITTEN PERMISSION.

2. WHEN NECESSARY TO TEMPORARILY DISCONNECT ANY EXISTING BUILDING UTILITIESAND SERVICE SYSTEMS, INCLUDING FEEDER OR BRANCH CIRCUITING SUPPLYINGEXISTING FACILITIES, CONFER WITH THE OWNER AND ARRANGE THE PERIOD OFINTERRUPTION FOR A TIME MUTUALLY AGREED UPON.

SHUTDOWN NOTE: SCHEDULE AND NOTIFY OWNER 48 HOURS PRIOR TOSHUTDOWN. ALL SHUTDOWN WORK TO BE SCHEDULED AT A TIME CONVENIENTTO OWNER.

GROUNDING1. ROUTE ALL GROUNDING CONDUCTORS AS SHOWN ON CONDUIT/GROUNDING RISER.

2. ROUTE 500 KCMIL CU. THHN CONDUCTOR FROM THE MGB LOCATION TO BUILDINGSTEEL. VERIFY BUILDING STEEL IS EFFECTIVELY GROUNDED PER NEC TO THE MAINSERVICE GROUNDING ELECTRODE CONDUCTOR (GEC).

3. MAKE ALL GROUND CONNECTIONS FROM MGB TO ELECTRICAL EQUIPMENT WITH 2HOLE, CRIMP TYPE, BURNDY COMPRESSION TERMINATIONS, SIZED AS REQUIRED.

4. USE 1 HOLE, CRIMP TYPE, BURNDY COMPRESSIONS TERMINATIONS, SIZED AS REQUIRED,AT EQUIPMENT GROUND CONNECTIONS.

5. HIRE AN INDEPENDENT LAB TO PERFORM THE SPECIFIED OHMS TESTING. PROVIDE 4SETS OF THE CERTIFIED DOCUMENTS TO THE OWNER FOR VERIFICATION PRIOR TOTHE PROJECT COMPLETION.

RACEWAYS1. ALL WIRING TO BE INSTALLED IN CONDUIT SYSTEMS IN ACCORDANCE WITH THE

FOLLOWING:A. EXTERIOR FEEDERS AND CONTROL, WHERE UNDERGROUND, TO BE IN SCH 40

PVC.

B. EXTERIOR, ABOVE GROUND POWER CONDUITS TO BE GALVANIZED RIGID STEEL(RGS).

C. ALL TELECOMMUNICATION CONDUITS, INTERIOR/EXTERIOR, TO BE EMT.

D. INSTALL PULL ROPES IN ALL NEW EMPTY CONDUITS INSTALLED ON THIS PROJECT.

E. ALL TELECOM CONDUITS AND PULL BOXES INSTALLED ON THIS PROJECT TO BELABELED "T-MOBILE". OWNER WILL PROVIDE LABELS FOR CONTRACTOR TOINSTALL.

F. INTERIOR FEEDERS TO BE INSTALLED IN E.M.T. WITH STEEL COMPRESSION FITTINGS.

G. MINIMUM SIZE CONDUIT TO BE 3 4" TRADE SIZE UNLESS OTHERWISE INDICATED ONTHE DRAWINGS.

H. FINAL CONNECTIONS TO MOTORS AND VIBRATING EQUIPMENT TO BE INSTALLEDIN LIQUID-TIGHT FLEXIBLE METAL CONDUIT.

I. CONDUIT TO BE RUN CONCEALED IN CEILINGS, FINISHED AREAS OR DRYWALLPARTITIONS, UNLESS OTHERWISE NOTED.

J. THE ROUTING OF CONDUITS INDICATED ON THE DRAWINGS IS DIAGRAMMATIC.BEFORE INSTALLING ANY WORK, EXAMINE THE WORKING LAYOUTS AND SHOPDRAWINGS OF THE OTHER TRADES TO DETERMINE THE EXACT LOCATIONS ANDCLEARANCES.

K. ALL EXTERIOR MOUNTING HARDWARE TO BE GALVANIZED STEEL. COORDINATEWITH BUILDING ENGINEER PRIOR TO ATTACHING TO BUILDING STRUCTURE.

L. PENETRATIONS OF WALLS, FLOORS AND ROOFS, FOR THE PASSAGE OFELECTRICAL RACEWAYS, TO BE PROPERLY SEALED AFTER INSTALLATION OFRACEWAYS SO AS TO MAINTAIN THE STRUCTURAL OR WATERPROOF INTEGRITYOF THE WALL, FLOOR OR ROOF SYSTEM TO BE PENETRATED. SEAL ALL CONDUITPENETRATIONS THROUGH FIRE OR SMOKE RATED WALLS, CEILINGS OR SMOKETIGHT CORRIDOR PARTITIONS TO MAINTAIN PROPER RATING OF WALL ORCEILING.

M. PROVIDE ALL CONDUIT ENDS WITH INSULATED METALLIC GROUNDINGBUSHINGS.

N. CONDUIT TO BE SUPPORTED AT MAXIMUM DISTANCE OF 8'-0", OR AS REQUIREDBY NEC, IN HORIZONTAL AND VERTICAL DIRECTIONS.

O. PROVIDE STAINLESS STEEL BLANK COVER PLATES FOR ALL JUNCTION BOXESAND/OR OUTLET BOXES NOT USED IN EXPOSED AREAS. PROVIDE ALL OTHERUNUSED BOXES WITH STANDARD STEEL COVER PLATES.

P. WHERE APPLICABLE, PROVIDE ROOFTOP CONDUIT SUPPORT SYSTEM,CONFORMING TO ROOFTOP WARRANTY REQUIREMENTS, PER BUILDING.

WIRES AND CABLES1. CONTRACTOR TO COORDINATE WITH EQUIPMENT SUPPLIER AND VENDOR FOR

EXACT EQUIPMENT OVER-CURRENT PROTECTION VOLTAGE, WIRE SIZE AND PLUGCONFIGURATION, IF APPLICABLE, PRIOR TO BID.

2. ALL EQUIPMENT/DEVICES TO BE PROVIDED WITH INSULATED GROUND CONDUCTOR.

3. ALL WIRE AND CABLE TO BE 600VOLT, COPPER, WITH THWN/ THHN INSULATION,EXCEPT AS NOTED.

4. WIRE FOR POWER AND LIGHTING WILL NOT BE LESS THAN NO. 12AWG. ALL WIRE NO.8 AND LARGER TO BE STRANDED.

5. CONTROL WIRING IS NOT TO BE LESS THAN NO. 14AWG, FLEXIBLE IN SINGLECONDUCTORS OR MULTI-CONDUCTOR CABLES. CONTROL WIRING WILL CONSIST OFMULTI-CONDUCTOR CABLES WHEREVER POSSIBLE. CABLES TO BE PROVIDED WITH ANOVERALL FLAME-RETARDANT, EXTRUDED JACKET AND RATED FOR PLENUM USE. ALLCONTROL WIRE TO BE 600VOLT RATED.

6. WIRE PREVIOUSLY PULLED INTO CONDUIT IS CONSIDERED USED AND IS NOT TO BE RE-PULLED.

7. HOME RUNS AND BRANCH CIRCUIT WIRING FOR 20A, 120V CIRCUITS: LENGTH (FT.) HOME RUN WIRE SIZE 0 TO 50 NO. 12 51 TO 100 NO. 10 101 TO 150 NO. 88. VOLTAGE DROP IS NOT TO EXCEED 3%.

9. MAKE ALL CONNECTIONS WITH UL APPROVED, SOLDERLESS, PRESSURE TYPE INSULATEDCONNECTORS: SCOTCHLOK OR AND APPROVED EQUAL.

WIRING DEVICES1. ALL RECEPTACLES INSTALLED IN THIS PROJECT TO BE GROUNDING TYPE, WITH

GROUNDING PIN SLOT CONNECTED TO DEVICE GROUND SCREW FOR GROUND WIRECONNECTION.

DISCONNECT SWITCHES AND FUSES1. DISCONNECT SWITCHES TO BE VOLTAGE-RATED TO SUIT THE CHARACTERISTICS OF

THE SYSTEM FROM WHICH THEY ARE SUPPLIED.

2. PROVIDE HEAVY-DUTY, METAL-ENCLOSED, EXTERNALLY-OPERATED DISCONNECTSWITCHES, FUSED OR UNFUSED, OF SUCH TYPE AND SIZE AS REQUIRED TO PROPERLYPROTECT OR DISCONNECT THE LOAD FOR WHICH THEY ARE INTENDED.

3. PROVIDE NEMA 1 DISCONNECT SWITCHES FOR INTERIOR INSTALLATION, NEMA 3R FOREXTERIOR INSTALLATION.

4. DISCONNECT SWITCHES TO BE MANUFACTURED BY:

A. GENERAL ELECTRIC COMPANY

B. SQUARE-D

5. PROVIDE RK-1 TYPE FUSES, UNLESS NOTED OTHERWISE.

INSTALLATION1. INSTALL DISCONNECT SWITCHES WHERE INDICATED ON DRAWINGS.

2. INSTALL FUSES IN FUSIBLE DISCONNECT SWITCHES. FUSES MUST MATCH IN TYPE ANDRATING.

3. FUSES TO BE MOUNTED SO THAT THE LABELS SHOWING THEIR RATINGS CAN BE READWITHOUT REQUIRING FUSE REMOVAL.

4. FURNISH AND DEPOSIT SPARE FUSES AT THE JOB SITE AS FOLLOWS:

A. THREE SPARES FOR EACH TYPE AND SIZE, IN EXCESS OF 60A, USED FOR INITIALFUSING.

B. TEN PERCENT SPARES FOR EACH TYPE AND SIZE, UP TO AND INCLUDING 60A,USED FOR INITIAL FUSING. IN NO CASE WILL LESS THAN THREE FUSES OF ONEPARTICULAR TYPE AND SIZE BE FURNISHED.

GENERAL NOTES:INTENT1. THESE SPECIFICATIONS AND CONSTRUCTION DRAWINGS ACCOMPANYING THEM

DESCRIBE THE WORK TO BE DONE AND THE MATERIALS TO BE FURNISHED FORCONSTRUCTION.

2. THE DRAWINGS AND SPECIFICATIONS ARE INTENDED TO BE FULLY EXPLANATORYAND SUPPLEMENTARY. HOWEVER, SHOULD ANYTHING BE SHOWN, INDICATED, ORSPECIFIED ON ONE AND NOT THE OTHER, IT SHALL BE DONE THE SAME AS IF SHOWN,INDICATED OR SPECIFIED IN BOTH.

3. THE INTENTION OF THE DOCUMENTS IS TO INCLUDE ALL LABOR AND MATERIALSREASONABLY NECESSARY FOR THE PROPER EXECUTION AND COMPLETION OF THEWORK AS STIPULATED IN THE CONTRACT.

4. THE PURPOSE OF THE SPECIFICATIONS IS TO INTERPRET THE INTENT OF THEDRAWINGS AND TO DESIGNATE THE METHOD OF THE PROCEDURE, TYPE ANDQUALITY OF MATERIALS REQUIRED TO COMPLETE THE WORK.

5. MINOR DEVIATIONS FROM THE DESIGN LAYOUT ARE ANTICIPATED AND SHALL BECONSIDERED AS PART OF THE WORK. NO CHANGES THAT ALTER THE CHARACTER OFTHE WORK WILL BE MADE OR PERMITTED BY THE OWNER WITHOUT ISSUING ACHANGE ORDER.

CONFLICTS1. THE CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFICATIONS OF ALL MEASUREMENTS

AT THE SITE BEFORE ORDERING ANY MATERIALS OR DOING ANY WORK. NO EXTRACHARGE OR COMPENSATION SHALL BE ALLOWED DUE TO DIFFERENCE BETWEENACTUAL DIMENSIONS AND DIMENSIONS INDICATED ON THE CONSTRUCTIONDRAWINGS. ANY SUCH DISCREPANCY IN DIMENSION WHICH MAY BE FOUND SHALL BESUBMITTED TO THE OWNER FOR CONSIDERATION BEFORE THE CONTRACTORPROCEEDS WITH THE WORK IN THE AFFECTED AREAS.

2. THE BIDDER, IF AWARDED THE CONTRACT, WILL NOT BE ALLOWED ANY EXTRACOMPENSATION BY REASON OF ANY MATTER OR THING CONCERNING SUCH BIDDERMIGHT HAVE FULLY INFORMED THEMSELVES PRIOR TO THE BIDDING.

3. NO PLEA OF IGNORANCE OF CONDITIONS THAT EXIST, OR OF DIFFICULTIES ORCONDITIONS THAT MAY BE ENCOUNTERED, OR OF ANY OTHER RELEVANT MATTERCONCERNING THE WORK TO BE PERFORMED IN THE EXECUTION OF THE WORK WILLBE ACCEPTED AS AN EXCUSE FOR ANY FAILURE OR OMISSION ON THE PART OF THECONTRACTOR TO FULFILL EVERY DETAIL OF ALL THE REQUIREMENTS OF THECONTRACT DOCUMENTS GOVERNING THE WORK.

CONTRACTS AND WARRANTIES1. CONTRACTOR IS RESPONSIBLE FOR APPLICATION AND PAYMENT OF CONTRACTOR

LICENSES AND BONDS.

2. SEE MASTER CONTRACTION SERVICES AGREEMENT FOR ADDITIONAL DETAILS.

STORAGE1. ALL MATERIALS MUST BE STORED IN A LEVEL AND DRY FASHION AND IN A MANNER

THAT DOES NOT NECESSARILY OBSTRUCT THE FLOW OF OTHER WORK. ANY STORAGEMETHOD MUST MEET ALL RECOMMENDATIONS OF THE ASSOCIATED MANUFACTURER.

CLEANUP1. THE CONTRACTORS SHALL, AT ALL TIMES, KEEP THE SITE FREE FROM ACCUMULATION

OF WASTE MATERIALS OR RUBBISH CAUSED BY THEIR EMPLOYEES AT WORK AND ATTHE COMPLETION OF THE WORK. THEY SHALL REMOVE ALL RUBBISH FROM ANDABOUT THE BUILDING AREA, INCLUDING ALL THEIR TOOLS, SCAFFOLDING ANDSURPLUS MATERIALS AND SHALL LEAVE THEIR WORK CLEAN AND READY TO USE.

2. EXTERIOR

A. VISUALLY INSPECT EXTERIOR SURFACES AND REMOVE ALL TRACES OF SOIL, WASTEMATERIALS, SMUDGES AND OTHER FOREIGN MATTER.

B. REMOVE ALL TRACES OF SPLASHED MATERIALS FROM ADJACENT SURFACES.

C. IF NECESSARY, TO ACHIEVE A UNIFORM DEGREE OF CLEANLINESS, HOSE DOWNTHE EXTERIOR OF THE STRUCTURE.

3. INTERIORA. VISUALLY INSPECT INTERIOR SURFACE AND REMOVE ALL TRACES OF SOIL, WASTE

MATERIALS, SMUDGES AND OTHER FOREIGN MATTER FROM WALLS, FLOOR, ANDCEILING.

B. REMOVE ALL TRACES OF SPLASHED MATERIALS FROM ADJACENT SURFACES.

C. REMOVE PAINT DROPPINGS, SPOTS, STAINS, AND DIRT FROM FINISHED SURFACES.

CHANGE ORDER PROCEDURE1. REFER TO SECTION 17 OF SIGNED MCSA: SEE PROFESSIONAL SERVICE AGREEMENT FOR

MCSA.

RELATED DOCUMENTS AND COORDINATION1. GENERAL CARPENTRY, ELECTRICAL AND ANTENNA DRAWINGS ARE INTERRELATED. IN

PERFORMANCE OF THE WORK, THE CONTRACTOR MUST REFER TO ALL DRAWINGS.ALL COORDINATION TO BE THE RESPONSIBILITY OF THE CONTRACTOR.

SHOP DRAWINGS1. CONTRACTOR SHALL SUBMIT SHOP DRAWINGS AS REQUIRED AND LISTED IN THESE

SPECIFICATIONS TO THE OWNER FOR APPROVAL.

2. ALL SHOP DRAWINGS SHALL BE REVIEWED, CHECKED AND CORRECTED BYCONTRACTOR PRIOR TO SUBMITTAL TO THE OWNER.

PRODUCTS AND SUBSTITUTIONS1. SUBMIT 3 COPIES OF EACH REQUEST FOR SUBSTITUTION. IN EACH REQUEST, IDENTIFY

THE PRODUCT OR FABRICATION OR INSTALLATION METHOD TO BE REPLACED BY THESUBSTITUTION. INCLUDE RELATED SPECIFICATION SECTION AND DRAWING NUMBERSAND COMPLETE DOCUMENTATION SHOWING COMPLIANCE WITH THE REQUIREMENTSFOR SUBSTITUTIONS.

2. SUBMIT ALL NECESSARY PRODUCT DATA AND CUT SHEETS WHICH PROPERLY INDICATEAND DESCRIBE THE ITEMS, PRODUCTS AND MATERIALS BEING INSTALLED. THECONTRACTOR SHALL, IF DEEMED NECESSARY BY THE OWNER, SUBMIT ACTUAL SAMPLESTO THE OWNER FOR APPROVAL IN LIEU OF CUT SHEETS.

QUALITY ASSURANCE1. ALL WORK SHALL BE IN ACCORDANCE WITH APPLICABLE LOCAL, STATE AND FEDERAL

REGULATIONS. THESE SHALL INCLUDE, BUT NOT BE LIMITED TO THE APPLICABLE CODESSET FORTH BY THE LOCAL GOVERNING BODY. SEE "CODE COMPLIANCE" T-1.

ADMINISTRATION1. BEFORE THE COMMENCEMENT OF ANY WORK, THE CONTRACTOR WILL ASSIGN A

PROJECT MANAGER WHO WILL ACT AS A SINGLE POINT OF CONTACT FOR ALLPERSONNEL INVOLVED IN THIS PROJECT. THIS PROJECT MANAGER WILL DEVELOP AMASTER SCHEDULE FOR THE PROJECT WHICH WILL BE SUBMITTED TO THE OWNERPRIOR TO THE COMMENCEMENT OF ANY WORK.

2. SUBMIT A BAR TYPE PROGRESS CHART, NOT MORE THAN 3 DAYS AFTER THE DATEESTABLISHED FOR COMMENCEMENT OF THE WORK ON THE SCHEDULE, INDICATING ATIME BAR FOR EACH MAJOR CATEGORY OR UNIT OF WORK TO BE PERFORMED AT THESITE, PROPERLY SEQUENCED AND COORDINATED WITH OTHER ELEMENTS OF WORKAND SHOWING COMPLETION OF THE WORK SUFFICIENTLY IN ADVANCE OF THE DATEESTABLISHED FOR SUBSTANTIAL COMPLETION OF THE WORK.

3. PRIOR TO COMMENCING CONSTRUCTION, THE OWNER SHALL SCHEDULE AN ON-SITEMEETING WITH ALL MAJOR PARTIES. THIS WOULD INCLUDE, BUT NOT LIMITED TO, THEOWNER, PROJECT MANAGER, CONTRACTOR, LAND OWNER REPRESENTATIVE, LOCALTELEPHONE COMPANY, TOWER ERECTION FOREMAN (IF SUBCONTRACTED).

4. CONTRACTOR SHALL BE EQUIPPED WITH SOME MEANS OF CONSTANTCOMMUNICATIONS, SUCH AS A MOBILE PHONE OR A BEEPER. THIS EQUIPMENT WILLNOT BE SUPPLIED BY THE OWNER, NOR WILL WIRELESS SERVICE BE ARRANGED.

5. DURING CONSTRUCTION, CONTRACTOR MUST ENSURE THAT EMPLOYEES ANDSUBCONTRACTORS WEAR HARD HATS AT ALL TIMES. CONTRACTOR WILL COMPLYWITH ALL WPCS SAFETY REQUIREMENTS IN THEIR AGREEMENT.

6. PROVIDE WRITTEN DAILY UPDATES ON SITE PROGRESS TO THE OWNER.

7. COMPLETE INVENTORY OF CONSTRUCTION MATERIALS AND EQUIPMENT IS REQUIREDPRIOR TO START OF CONSTRUCTION.

8. NOTIFY THE OWNER/PROJECT MANAGER IN WRITING NO LESS THAN 48 HOURS INADVANCE OF CONCRETE POURS, TOWER ERECTIONS, AND EQUIPMENT CABINETPLACEMENTS.

INSURANCE AND BONDS1. CONTRACTOR, AT THEIR OWN EXPENSE, SHALL CARRY AND MAINTAIN, FOR THE

DURATION OF THE PROJECT, ALL INSURANCE, AS REQUIRED AND LISTED, AND SHALLNOT COMMENCE WITH THEIR WORK UNTIL THEY HAVE PRESENTED AN ORIGINALCERTIFICATE OF INSURANCE STATING ALL COVERAGES TO THE OWNER. REFER TO THEMASTER AGREEMENT FOR REQUIRED INSURANCE LIMITS.

2. THE OWNER SHALL BE NAMED AS AN ADDITIONAL INSURED ON ALL POLICIES.

3. CONTRACTOR MUST PROVIDE PROOF OF INSURANCE.

AT

CABINET

AND

CEILING

DRAWINGEACH

Ø

ADJ

&APPROX@BTSCABCLGCONCCONTDIA OR DWGEAELECELEV

AGL

EQUAL

EXISTING

GAUGE

GROUNDLONG

MINIMUM

EQEQUIPEGB

(E)EXTFFGAGALVGCGRNDLGMAXMECH

MFRMGBMIN

NEW

SHEETSIMILAR

STEEL

(N)NICNTSOCOPP

(P)PCS

SFSHTSIMSSSTLTOCTOM

PPC

METALMTL

ADJUSTABLE

APPROXIMATE

BASE TRANSMISSION STATION

CONCRETECONTINUOUSDIAMETER

ELECTRICALELEVATION

EQUIPMENTEQUIPMENT GROUND BAR

EXTERIORFINISHED FLOOR

GALVANIZEDGENERAL CONTRACTOR

MAXIMUMMECHANICAL

MANUFACTURER

MASTER GROUND BAR

NOT IN CONTRACTNOT TO SCALEON CENTEROPPOSITE

PROPOSEDPERSONAL COMMUNICATION SYSTEM

SQUARE FOOT

STAINLESS STEEL

TOP OF CONCRETETOP OF MASONRY

ABOVE GROUND LINE

POWER PROTECTION CABINET

ABBREVIATIONS

WITH

VIFUONWWFW/

VERIFY IN FIELDUNLESS OTHERWISE NOTEDWELDED WIRE FABRIC

TYPICALTYP

MW MICROWAVE DISH

Page 14: T-Mobile Antenna Site
Page 15: T-Mobile Antenna Site
Page 16: T-Mobile Antenna Site

1

Kelli Crowe

From: [email protected]: Friday, January 05, 2018 3:15 PMTo: [email protected]: Section 106 Notification of SHPO/THPO Concurrence- Email ID #2682454

This is to notify you that the Lead SHPO/THPO has concurred with the following filing: Date of Action: 01/05/2018 Direct Effect: No Effect on Historic Properties in APE Visual Effect: No Adverse Effect on Historic Properties in APE Comment Text: None File Number: 0008026299 TCNS Number: 163834 Purpose: Collocation Submission Packet Notification Date: 7AM EST 12/12/2017 Applicant: T-Mobile Northeast, LLC. Consultant: Advantage Environmental Consultants, LLC Positive Train Control Filing Subject to Expedited Treatment Under Program Comment: No Site Name: 7WAS039C Site Address: Edmonston Road Detailed Description of Project: No ground disturbance Site Coordinates: 39-1-1.2 N, 76-51-39.1 W City: Greenbelt County: PRINCE GEORGE'S State:MD Lead SHPO/THPO: Maryland Historical Trust NOTICE OF FRAUDULENT USE OF SYSTEM, ABUSE OF PASSWORD AND RELATED MISUSE Use of the Section 106 system is intended to facilitate consultation under Section 106 of the National Historic Preservation Act and may contain information that is confidential, privileged or otherwise protected from disclosure under applicable laws. Any person having access to Section 106 information shall use it only for its intended purpose. Appropriate action will be taken with respect to any misuse of the system.

Page 17: T-Mobile Antenna Site

RF‐EME Theoretical MPE Summary Introduction

EBI Consulting was directed to analyze the proposed T-Mobile water tank facility (7WAS039C) located at Edmonston Road in Greenbelt, Maryland for the purpose of determining whether the emissions from the proposed T-Mobile Antenna Installation located on this property are within specified federal limits.

MPE Calculations

Calculations were done for the proposed T-Mobile Wireless antenna water tank facility located at Edmonston Road in Greenbelt, Maryland using worst-case analysist to predict possible areas of exceedance of FCC RF emissions levels.

The anticipated maximum composite MPE value for this site is 1.7% of the allowable FCC established general public limit (0.34% of the FCC occupational limit). This is based upon worst case modeling performed on the ground.

Signage

Signs are the primary means for control of access to areas where RF exposure levels may exceed the MPE limits. In order to meet FCC requirements, the signs must:

Be posted at a conspicuous point; Be posted at the appropriate locations; Be readily visible; and Make the reader aware of the potential risks prior to entering the affected area.

Report Prepared by:

James Speed RF Project Manager EBI Consulting

21 B StreetBurlington, MA, 01803

Tel: (781) 273-2500Fax: (781) 273-3311

Page 18: T-Mobile Antenna Site

Radio Frequency – Electromagnetic Energy (RF-EME) Compliance Report (L1900)

T-Mobile Proposed Facility

Site ID: 7WAS039C USDA-Laurel

Edmonston Road, Greenbelt, Maryland 20770

June 7, 2018

EBI Project Number: 6218004108

Status: Compliant

Remarks: No additional mitigation is required.

Prepared by:

Page 19: T-Mobile Antenna Site

2 EBI Consulting � 21 B Street � Burlington, MA 01803 � 1.800.786.2346

TABLE OF CONTENTS

1.0 Executive Summary ............................................................................................................3

2.0 MPE Calculations ................................................................................................................4

3.0 Site and Vicinity Survey ......................................................................................................5

4.0 T-Mobile Antenna Inventory ..............................................................................................6

5.0 Summary and Conclusions .................................................................................................7

Attachment 1: MPE Analysis and Recommended Signage .......................................................8

Appendix A: Certifications ....................................................................................................... 10

Appendix B: Federal Communications Commission (FCC) Requirements ....................... 12

Appendix C: Antenna Inventory.............................................................................................. 14

Appendix D: Photographs ........................................................................................................ 16

Appendix E: Site Plan with Monitoring Locations................................................................. 17

Appendix F: Site Survey Data ................................................................................................. 18

Page 20: T-Mobile Antenna Site

3 EBI Consulting � 21 B Street � Burlington, MA 01803 � 1.800.786.2346

1.0 Executive Summary

EnviroBusiness Inc. (dba EBI Consulting) has been contracted by T-Mobile to conduct radio frequency

electromagnetic (RF-EME) monitoring and modeling for T-Mobile Site 7WAS039C located at Edmonston

Road in Greenbelt, Maryland to determine RF-EME exposure levels from proposed T-Mobile wireless

communications equipment at this site. As described in detail in Appendix B of this report, the Federal

Communications Commission (FCC) has developed Maximum Permissible Exposure (MPE) Limits for

general public exposures and occupational exposures. This report summarizes the results of RF-EME

monitoring and modeling in relation to relevant FCC RF-EME compliance standards for limiting human

exposure to RF-EME fields. EBI field personnel visited this site on June 04, 2018. This report contains a

detailed summary of the RF EME analysis for the site.

This document addresses the compliance of T-Mobile’s proposed transmitting facilities independently

and in relation to all existing collocated facilities at the site.

The Maximum Composite Emissions Value is 2.7000% of the FCC’s general public limit (0.5400% of the

FCC’s occupational limit) at the ground. The proposed site is in compliance with Federal regulations

regarding (radio frequency) RF Emissions.

Based on worst-case predictive modeling, there are no modeled exposures on any accessible ground-

level walking/working surface related to T-Mobile’s equipment in the area that exceed the FCC’s

occupational and/or general public exposure limits at this site. There are no modeled areas on the

ground that exceed the FCC’s limits for general public or occupational exposure in front of the other

carrier antennas.

Signage is not required at the site as presented in Attachment 1. The site is compliant with FCC rules

and regulations.

Page 21: T-Mobile Antenna Site

4 EBI Consulting � 21 B Street � Burlington, MA 01803 � 1.800.786.2346

2.0 MPE Calculations

Calculations were completed for the proposed T-Mobile Wireless antenna water tank facility located at

Edmonston Road in Greenbelt, Maryland using the equipment information listed below. All calculations

were performed per the specifications under FCC OET 65. Because of the short wavelength of PCS

services, the antennas require line-of-site paths for good propagation, and are typically installed a

distance above ground level. Antennas are constructed to concentrate energy towards the horizon, with

as little energy as possible scattered towards the ground or the sky. This design, combined with the low

power of PCS facilities, generally results in no possibility for exposure to approach Maximum

Permissible Exposure (MPE) levels, with the exception of in areas in the immediate vicinity of the

antennas.

In accordance with T-Mobile’s RF Exposure policy, EBI performed theoretical modeling using

RoofView® software to estimate the worst-case power density at the site ground-level resulting from

operation of the antennas.

For this report, EBI utilized antenna and power data provided by T-Mobile and compared the resultant

worst-case MPE levels to the FCC’s occupational/controlled exposure limits outlined in OET Bulletin 65.

EBI has performed theoretical worst case modeling using RoofView® to estimate the maximum

potential power density from each proposed antenna based on worst-case assumptions for the number

of antennas and power. All radios at the proposed installation were considered to be running at full

power and were uncombined in their RF transmission paths per carrier prescribed configuration. In

addition, Sprint proposes the installation of XXX (#) microwave dishes at the site.

The assumptions used in the modeling are based upon information collected during the site survey andinformation provided by T-Mobile in the supplied drawings and known configuration values information gathered from other sources to approximate each additional carrier’s contribution.

The Maximum Emissions Value for the additional carriers included in the modeling is 1.80% of the FCC

general public limit (0.36% of the FCC occupational limit) at the ground walking/working surfaces.

The data for all T-Mobile antennas used in this analysis is shown in Section 4.0. Actual antenna gains for each antenna were used per manufacturer’s specifications. All calculations were done with respect to uncontrolled and general public threshold limits.

Page 22: T-Mobile Antenna Site

5 EBI Consulting � 21 B Street � Burlington, MA 01803 � 1.800.786.2346

3.0 Site and Vicinity Survey

EBI performed a ground level RF-EME survey on June 4, 2018. The antenna inventory (based upon the

site survey) and site photos taken from ground level are presented in Appendices A and B, respectively.

Monitoring was performed using a Narda NBM-550 Electromagnetic Radiation Survey Meter, Serial #E-

0451 with a Narda EA5091-shaped probe with a frequency range of 300kHz-50 GHz. The meter was

last calibrated on August 18, 2017. This meter was programmed to measure the total power density for

all electromagnetic radiation within the 300kHz-50GHz frequency range and report the power density

as a percent of the FCC’s controlled MPE. During this survey, no spatially averaged readings above

0.0761% of the FCC’s occupational MPE (0.3805% of the general public MPE) were encountered on any

ground surface. This maximum spatially averaged reading was measured at ground level outside of the

compound gate to the east, as shown in the monitoring site plan in Appendix E. A site plan depicting

monitoring locations and measurements of power density can be found in Appendix E. Appendix F

contains notes from the site survey.

Access to this site is accomplished by approaching the unsecured water tank at ground level. To be

conservative and to comply with T-Mobile’s corporate policy, the modeling results are reported as

though the general public is able to access the water tank.

At the time of the site survey, it was noted that there was a yellow “Guidelines” sign and a blue

“Notice” sign on the access gate indicating the presence of RF emitting equipment at the site.

This analysis report contains both theoretical modeling calculations as well as actual onsite Power

Density measurements. The theoretical modeling calculations will typically show a worst case scenario

as it is typically modeled after the largest channel grouping and power level possible at the site. Onsite

Monitoring will give a snapshot of the composite RF field levels at the time the survey was completed.

Due to this, there is a possibility that large differences may be seen between the modeled RF conditions

and those observed in the field. Additionally, this becomes a multiplier effect if multiple carriers are

modeled at maximum powers.

Page 23: T-Mobile Antenna Site

6 EBI Consulting � 21 B Street � Burlington, MA 01803 � 1.800.786.2346

4.0 T-Mobile Antenna Inventory

• This table contains an inventory of only T-Mobile Antennas and Power Values. Note that EBI uses an assumed set of antenna specifications and powers for unknown and other carrier antennas for modeling purposes as detailed in Section 2.0.

Sector Antenna Number Antenna Make Antenna Model

Height (ft) Above Nearest Walking Surface

Azimuth (°) Technology Frequency Band Power Per Channel (W)

Number of Channels

ERP (W)

A 1 Ericsson AIR21 B2A/B4P 132.7 70 UMTS/GSM PCS - 1900 MHz 30 2 2057

A 2 Commscope LNX-6515DS-A1M 131.0 70 LTE 700 MHz 30 2 1433

A 3 Ericsson AIR32 132.7 70 LTE AWS - 2100 MHz 60 2 4615

A 3 Ericsson AIR32 132.7 70 LTE PCS - 1900 MHz 60 2 4113

B 1 Ericsson AIR21 B2A/B4P 132.7 180 LTE PCS - 1900 MHz 30 2 2057

B 2 Commscope LNX-6515DS-A1M 131.0 180 LTE 700 MHz 30 2 1433

B 3 Ericsson AIR32 132.7 180 LTE AWS - 2100 MHz 60 2 4615

B 3 Ericsson AIR32 132.7 180 #REF! #REF! 30 4 4113

C 1 Ericsson AIR21 B2A/B4P 132.7 320 UMTS/GSM PCS - 1900 MHz 30 2 2057

C 2 Commscope LNX-6515DS-A1M 131.0 325 LTE 700 MHz 30 2 1433

C 3 Ericsson AIR32 132.7 320 LTE AWS - 2100 MHz 60 2 4615

C 3 Ericsson AIR32 132.7 320 LTE PCS - 1900 MHz 60 2 4113

Page 24: T-Mobile Antenna Site

7 EBI Consulting � 21 B Street � Burlington, MA 01803 � 1.800.786.2346

5.0 Summary and Conclusions

All calculations performed for this analysis yielded results that were within the allowable limits for exposure to RF Emissions. Based on predictive modeling, there are no modeled exposures on any accessible ground-level walking/working surface related to T-Mobile’s equipment in the area that exceed the FCC’s occupational and/or general public exposure limits at this site. There are no modeled areas on the ground that exceed the FCC’s limits for general public or occupational exposure in front of the other carrier antennas. Installation of mitigation measures will bring the proposed site into compliance. The anticipated maximum contribution from each sector of the proposed T-Mobile facility is 1.2% of the

allowable FCC established general public limit (0.24% of the FCC occupational limit). This was

determined through calculations along a radial from each sector taking full power values into account as

well as actual vertical plane antenna gain values per the manufacturers supplied specifications for gain.

The anticipated maximum composite MPE value for this site is 2.7% of the allowable FCC established

general public limit (0.54% of the FCC occupational limit). This is based upon worst-case modeling

performed on the ground taking emissions contributions from all carriers present into account. This

value will determine whether the proposed site will be in compliance with regards to electromagnetic

emissions. Microwave dish antennas are designed for point-to-point operations at the elevations of the

installed equipment rather than ground level coverage. RoofView® is not suitable for modeling them.

However, formulas for OET Bulletin 65 were used to calculate a worst-case prediction of the maximum

power density (MPE) at ground level and nearest walking surfaces for the Sprint microwave dishes.

Power density estimates used for the microwave dishes proposed for installation at this site are included

in Appendix B. At the nearest walking/working surfaces to the Sprint microwave dishes, the maximum

power density generated by the Sprint microwave dishes is approximately 1.20 percent of the FCC’s

general population limit (0.24 percent of the FCC’s occupational limit).

A site is considered out of compliance with FCC regulations if there are areas that exceed the FCC

exposure limits and there are no RF hazard mitigation measures in place. Any carrier which has an

installation that contributes more than 5% of the applicable MPE must participate in mitigating these RF

hazards. For this facility, the composite values calculated were within the allowable 100% threshold

standard per the federal government. Based on the FCC criteria, there are no measured areas on any accessible ground-level walking/working surface related to the existing site conditions that exceed the FCC’s occupational and general public exposure limits at this site.

Signage is not required because there is no access within 30 feet of an antenna. To reduce the risk of

exposure and/or injury, EBI recommends that access to the water tank or areas associated with the

active antenna installation be restricted and secured where possible.

Page 25: T-Mobile Antenna Site

T-Mobile

Antennas

Other Carrier

Antennas

Water Tank

T-Mobile

Sector A

Access Gate

T-Mobile

Sector B

T-Mobile

Sector C

*For Clarity, Other

Carrier Antennas are

Not Shown.

Signage is not required

because there is no access

within 30 feet of an antenna.

Attachment 1: MPE Analysis and Recommended Signage

Page 26: T-Mobile Antenna Site

Sign Sign Count Description Posting Instructions

N/A

Blue Notice Sign Used to notify individuals they are entering an area where the power density emitted from transmitting

antennas may exceed the FCC’s MPE limit for the general public or

occupational exposures.

Signage is not required because there is no

access within 30 feet of an antenna.

N/A

Guidelines

Informational sign used to notify

workers that there are active antennas

installed and provide guidelines for

working in RF environments.

Signage is not required because there is no access within 30 feet of an antenna.

N/A

Yellow Caution Sign Used to notify individuals that they are entering a hot spot where either the general public or occupational FCC’s MPE limit is or could be exceeded.

Signage not required.

N/A

Red Warning Sign Used to notify individuals that they are entering a hot zone where either the general public or occupational FCC’s

MPE limit has been exceeded.

Signage not required.

Notes:

The proposed site will be compliant with the installation of the mitigation measures.

The actual number of access points may vary based on documentation provided and/or if a survey

was conducted. Recommended signage locations are based on T-Mobile’s guidance for the worst-

case scenario in each sector. The actual signage installation is dependent on accessibility of the

facility and antennas. Locations deemed inaccessible due to OSHA safety standards (proximity to

unprotected roof edge or slope, etc.) will be compliant upon installation of recommended signage

at the closest accessible point.

Page 27: T-Mobile Antenna Site

10 EBI Consulting � 21 B Street � Burlington, MA 01803 � 1.800.786.2346

Appendix A: Certifications

Page 28: T-Mobile Antenna Site

11 EBI Consulting � 21 B Street � Burlington, MA 01803 � 1.800.786.2346

Preparer Certification

I, Andrew Simpson, state that:

� I am an employee of EnviroBusiness Inc. (d/b/a EBI Consulting), which provides RF-EME safety and compliance services to the wireless communications industry.

� I have successfully completed RF-EME safety training, and I am aware of the potential hazards from RF-EME and would be classified “occupational” under the FCC regulations.

� I am fully aware of and familiar with the Rules and Regulations of both the Federal Communications Commissions (FCC) and the Occupational Safety and Health Administration (OSHA) with regard to Human Exposure to Radio Frequency Radiation.

� I have been trained on RF-EME modeling using RoofView® modeling software.

� I have reviewed the data collected during the site survey and provided by the client and incorporated it into this Site Compliance Report such that the information contained in this report is true and accurate to the best of my knowledge.

Page 29: T-Mobile Antenna Site
Page 30: T-Mobile Antenna Site

12 EBI Consulting � 21 B Street � Burlington, MA 01803 � 1.800.786.2346

Appendix B: Federal Communications Commission (FCC) Requirements

Page 31: T-Mobile Antenna Site

13 EBI Consulting � 21 B Street � Burlington, MA 01803 � 1.800.786.2346

All information used in this report was analyzed as a percentage of current Maximum Permissible

Exposure (% MPE) as listed in the FCC OET Bulletin 65 Edition 97-01and ANSI/IEEE Std C95.1. The

FCC regulates Maximum Permissible Exposure in units of microwatts per square centimeter (µW/cm2).

The number of µW/cm2 calculated at each sample point is called the power density. The exposure limit

for power density varies depending upon the frequencies being utilized. Wireless Carriers and Paging

Services use different frequency bands each with different exposure limits, therefore it is necessary to

report results and limits in terms of percent MPE rather than power density.

All results were compared to the FCC (Federal Communications Commission) radio frequency

exposure rules, 47 CFR 1.1307(b)(1) – (b)(3), to determine compliance with the Maximum Permissible

Exposure (MPE) limits for General Population/Uncontrolled environments as defined below.

General population/uncontrolled exposure limits apply to situations in which the general public may be

exposed or in which persons who are exposed as a consequence of their employment may not be made

fully aware of the potential for exposure or cannot exercise control over their exposure. Therefore,

members of the general public would always be considered under this category when exposure is not

employment related, for example, in the case of a telecommunications tower that exposes persons in a

nearby residential area.

Public exposure to radio frequencies is regulated and enforced in units of microwatts per square

centimeter (µW/cm2). The general population exposure limit for the 700 and 800 MHz Bands is 467

µW/cm2 and 567 µW/cm2 respectively, and the general population exposure limit for the PCS and AWS

bands is 1000 µW/cm2. Because each carrier will be using different frequency bands, and each frequency

band has different exposure limits, it is necessary to report percent of MPE rather than power density.

Occupational/controlled exposure limits apply to situations in which persons are exposed as a

consequence of their employment and in which those persons who are exposed have been made fully

aware of the potential for exposure and can exercise control over their exposure.

Occupational/controlled exposure limits also apply where exposure is of a transient nature as a result of

incidental passage through a location where exposure levels may be above general

population/uncontrolled limits (see below), as long as the exposed person has been made fully aware of

the potential for exposure and can exercise control over his or her exposure by leaving the area or by

some other appropriate means.

A site is considered out of compliance with FCC regulations if there are areas that exceed the FCC

exposure limits and there are no RF hazard mitigation measures in place. Any carrier which has an

installation that contributes more than 5% of the applicable MPE must participate in mitigating these RF

hazards.

Additional details can be found in FCC OET 65.

Page 32: T-Mobile Antenna Site

14 EBI Consulting � 21 B Street � Burlington, MA 01803 � 1.800.786.2346

Appendix C: Antenna Inventory

Page 33: T-Mobile Antenna Site

15 EBI Consulting � 21 B Street � Burlington, MA 01803 � 1.800.786.2346

Below in the Appendix C Table are the technical specifications of the antennas located at the site.

Physical verification was made to ensure technical specification accuracy. Antenna specifications

presented herein are based on direct evidence from an antenna or transmitter cabinet, information from

the site manager or building manager, information from the licensees, educated estimates by the field

technician or a combination of some or all of these sources. “N/A” (not available) is used if any of the

following information was not obtainable or verifiable to an acceptable certainty.

Ant #

Type Manufacturer/Model Azimuth

(°)

Height Above Nearest Walking Surface (feet)

Carrier

1 Panel Ericsson/AIR 21 70 132.7 T-Mobile

2 Panel Andrew/LNX-6515DS-A1M 70 132 T-Mobile

3 Panel Ericsson/AIR 32 70 132.7 T-Mobile

4 Panel Ericsson/AIR 21 180 132.7 T-Mobile

5 Panel Andrew/LNX-6515DS-A1M 180 132 T-Mobile

6 Panel Ericsson/AIR 32 180 132.7 T-Mobile

7 Panel Ericsson/AIR 21 325 132.7 T-Mobile

8 Panel Andrew/LNX-6515DS-A1M 325 132 T-Mobile

9 Panel Ericsson/AIR 32 325 132.7 T-Mobile

10 Panel Unknown 0 97 AT&T

11 Panel Unknown 0 97 AT&T

12 Panel Unknown 180 97 AT&T

13 Panel Unknown 180 97 AT&T

14 Panel Unknown 270 97 AT&T

15 Panel Unknown 270 97 AT&T

16 Panel Unknown 60 103 Sprint

17 Panel Unknown 180 103 Sprint

18 Panel Unknown 270 103 Sprint

19 Microwave N/A 180 103 Unknown

Page 34: T-Mobile Antenna Site

16 EBI Consulting � 21 B Street � Burlington, MA 01803 � 1.800.786.2346

Appendix D: Photographs

Page 35: T-Mobile Antenna Site

EBI Consulting

1. Site Overview

2. T-Mobile Sector A (top), AT&T Sector A (bottom), and Sprint Sector A (middle)

3. T-Mobile Sector A Transmitting Direction

4. T-Mobile Sector B (top), AT&T Sector B (bottom), and Sprint Sector B (middle)

5. T-Mobile Sector B Transmitting Direction

6. T-Mobile Sector C (top), AT&T Sector C (bottom), and Sprint Sector C (middle)

Page 36: T-Mobile Antenna Site

EBI Consulting

7. T-Mobile Sector C Transmitting Direction

8. Access Gate with Existing Signage

9. T-Mobile Equipment

10. AT&T Equipment Shelter

11. Sprint Equipment

12. Compound Overview Looking Southeast

Page 37: T-Mobile Antenna Site

17 EBI Consulting � 21 B Street � Burlington, MA 01803 � 1.800.786.2346

Appendix E: Site Plan with Monitoring Locations

Page 38: T-Mobile Antenna Site

Site Plan with Monitoring Results

Facility Operator: T-Mobile

Site Number: 7WAS039C

Site Name: USDA-Laurel

Site Visit Date: June 4, 2018

Sector A

Sector B

Sector C

*For clarity, other carrier antennas

not shown

Access Gate

♦ 0.0620

LEGEND

T-Mobile Antennas

♦ Green numbers are Spatially-Averaged Measurements

% FCC General Public Limit

0.0035 ♦

♦ 0.0045

♦ 0.0025

♦ 0.0570

♦ 0.0055

♦ 0.0405

♦ 0.0025

♦ 0.0030

♦ 0.0135

♦ 0.0005

♦ 0.0190

♦ 0.1660

♦ 0.3660

♦ 0.3020♦ 0.3805

Page 39: T-Mobile Antenna Site

18 EBI Consulting � 21 B Street � Burlington, MA 01803 � 1.800.786.2346

Appendix F: Site Survey Data

Page 40: T-Mobile Antenna Site

19 EBI Consulting � 21 B Street � Burlington, MA 01803 � 1.800.786.2346

Surveyor Name Andrew Simpson Site Visit Date June 4, 2018

Site Information

USDA-Laurel Edmonston Road Greenbelt, Maryland 20770

Site Coordinates (NAD83): 39.017000; -76.860861

MONITOR INFORMATION PROBE INFORMATION

Monitor Model # NBM-550 Probe Model # EA5091

Monitor Serial # E-0451 Probe Serial # 1077

Calibration Date 08/18/17 Calibration Date 08/21/17

CLIMATE INFORMATION

Temperature (°F) 62

Sunny / Overcast / Cloudy Overcast

No Wind / Mild Breeze / Windy No Wind

Rain / Drizzle / Fog / Snow N/A

Other noteworthy weather factors that might influence readings

N/A

ACCESS INFORMATION

Type of facility Water Tank

Property owner and contact information Security - (301) 504-8131

Who manages access? (e.g. security, landlord, no one)

No one

How is access managed? (locks, sign-in, etc.)

Unlocked Gate

Ease of access, in general (e.g. ease of breaching any physical access controls)

Uncontrolled

Page 41: T-Mobile Antenna Site
Page 42: T-Mobile Antenna Site
Page 43: T-Mobile Antenna Site
Page 44: T-Mobile Antenna Site
Page 45: T-Mobile Antenna Site
Page 46: T-Mobile Antenna Site
Page 47: T-Mobile Antenna Site
Page 48: T-Mobile Antenna Site
Page 49: T-Mobile Antenna Site
Page 50: T-Mobile Antenna Site
Page 51: T-Mobile Antenna Site