SynapSense Three Phase Wireless Current Sensor Data Sheet
description
Transcript of SynapSense Three Phase Wireless Current Sensor Data Sheet
copyright ©2011 SynapSense Corporation
Page 1
Copyright 2011. All Rights Reserved. SynapSense Corporation. SynapSense®, the SynapSense logo, and SynapSoft™ are trademarks of SynapSense Corporation. All third-party brand and product names are the trademarks of their respective owners and are used solely for informational purposes.
Overview
The SynapSense® Three-Phase Wireless Current Sensor provides True RMS AC Current without
requiring service interruption. The SynapSense Constellation Node calculates the average current over a
five-minute collection interval and wirelessly reports this data to the host server via the SynapSense
Wireless Sensor Network (WSN). The use of non-intrusive Split Core Current Transducers (CTs) enables
sensors to be installed without having to disable the equipment being monitored.
SynapSense offers a wide range of CTs available from 100 to 4000amps in a wide range of sizes. The kit
includes three Split Core CTs, a Constellation Node, cable assemblies, and a 100 to 240VAC power
adapter for powering the CTs and node.
Three-Phase Wire Current Sensor General Specifications
Features Split-core design allows installation without service disruption
High accuracy
600VAC safety ratings
Wide range of CTs offer 100 to 4000amp sensing
Bundled with Constellation Node
Range Optional up to 4000amp CTs
Frequency 50 to 60 Hz
Accuracy ±1.0% Full Scale
Applications Load trending equipment (current monitoring)
Load trending building current consumption
Rates for industrial use
Maintenance & Calibration
Factory calibrated; requires no field maintenance
Software Requirements
SynapSoft™
Release 5.3.1 or newer
SynapSense® Three-Phase Wireless Current Sensor
Technical Data Sheet
Three circuit wire current sensor with Constellation Node
copyright ©2011 SynapSense Corporation Page 2 Rev J-8-2011
SynapSense Proprietary & Confidential
ACI or Veris Current Transducers (CTs)
Component Specification
Sensor Supply Voltage (Vs)
24 VDC (kit includes 100 to 240VAC 50/60Hz AC/DC adapter)
Accuracy Sensors ± 1.0% FS Constellation Node: ±1.15%
Overall: 2.15%
Amperage Rating Up to 4000 amps available
CT Output 4-20mA, two-wire, loop powered
Operating Temp -15 to 400C (5 to 1040F)
Operating Humidity Range
0 to 95% RH, non-condensing
Response Time <75mS
Veris Current Transducer
Available CT Models
Manufacturer Model Available CT Range Sensor Output
Housing
ACI A/SCTA-200-VFD 100, 150, 200
(Jumper Selectable)
4-20mA Split-core Veris H221 100 to 300A
Veris H321 300 to 800A
Veris H421 1000 to 2400A