Overview
SynapSensePower Metering offers 3-phase AC power metering for wye or delta loads. It uses the
SquareD PowerLogic ION 6200 meter to provide an adjustable display for easy to read energy, power,
current, voltage, power factor, and harmonic data. The meters high accuracy is revenue grade and
compatible with a wide range of solid or split core current transducers (CTs) from 50 amp up to 4000 amp
models.
The meter comes pre-installed in a wall-mount, single High Density Meter (HDM) enclosure. The HDM
enclosure includes and knockouts for conduit connections. Terminal blocks for 3-phase AC wiring,
CTs, ground, and Modbus RS422/RS485 connections are pre-wired to the meter.
Power Metering works in tandem with the SynapSense Web Console. The Web Console is configured
with a wye or delta and enables you to visually see the 3-phase current, voltage, demand power, power
factor, total harmonic distortion, and energy data including summary information. The Web Console also
enables you to track historical information from the power meter, using the historical data graphs.
Power Metering GeneralSpecifications
SynapSense Power Metering shown in an HDMEnclosure
Features 3-phase power metering
Per phase data
Meter display provides local dataaccess; the Web Consoleprovides up to 21 data points withhistorical charting
Available with split core CTsranging from 50 to 4000 amp in avariety of models
Power MeterType
PowerLogic ION6200
RevenueCertification
ANSI and Measurement Canadaoptions
Factory-sealed version availablein Canada
Communications RS-422/485 Modbus RTU forintegration with SynapSense WebConsole
Pulse Outputs Optional: kWh summary informationavailable via the SynapSense WirelessSensor Network (WSN)
3-PhaseMetering
100 to 480 VAC L-L (50 to 60 Hz)
-
8/11/2019 Synapsense Power Metering Data Sheet
2/4
copyright 2011 SynapSense Corporation Page2Rev A-5-2014
SynapSense Proprietary & Confidential
Power Meter Overview
The SquareD ION 6200 Energy Meter features:
64 samples per cycle
IEC 60687 class 0.5 compliant
Four quadrant energy and demand 49 real-time, true RMS electrical parameters
Per phase voltage, current, peak current,
demand, watts, VARs, kWh, and more
Neutral current, Total Harmonic Distortion
(THD), frequency, power factor
Power Meter Accuracy
Accuracy Speci ficati on
Voltage L-N 0.3% reading, L-L 0.5% reading
Frequency 0.1 Hz
Current >= 5% of full scale: 0.3% reading
-
8/11/2019 Synapsense Power Metering Data Sheet
3/4
copyright 2011 SynapSense Corporation Page3Rev A-5-2014
SynapSense Proprietary & Confidential
Veris CT General Specifications
Specification Description
Overview The H681x-xxx series of 5 Ampsplit-core current transformersprovide secondary amperage
proportional to the primary(sensed) current. For use withpower meters, data loggers,chart recorders, and otherinstruments.
Leads 18AWG, 600VAC, 6' standardlength
OperatingTemperature Range
15 to 60C (5 to 140F)
Storage TemperatureRange
-40 to 70C (-40 to 158)
Humidity Range 0-95% non-condensing
Max. Voltage L-N
Sensed Conductor
600VAC (basic insulationrating)
Frequency Range 50/60 Hz
Altitude of Operation 3km maximum
Installation Category Cat II or Cat III
Veris CT Ratings
Model Sensing
Current
(A)
Frequency
(Hz)
Output
(A)
Weight
(kg)
H6810 0 to 300 50/60 0 to 5 0.340
H6811 0 to 800 50/60 0 to 5 0.580
H6812 0 to 2400 50/60 0 to 5 0.870
Veris CT Accuracy
Model # F.S. Accuracy
(96%)
Burden
Capacity (VA)
H6810-100A-5A 4 .07
H6810-200A-5A 1 2.5
H6810-300A-5A 1 2.5
H6811-400A-5A 1 5.0
H6811-600A-5A 1 5.0
H6811-800A-5A 1 12.5
H6812-800A-5A 1 5.0
H6812-1200A-5A 1 22.5
H6812-1600A-5A 1 22.5
H6812-2400A-5A 1 22.5
Veris CT Mechanical Dimensions
-
8/11/2019 Synapsense Power Metering Data Sheet
4/4
copyright 2011 SynapSense Corporation Page4Rev A-5-2014
SynapSense Proprietary & Confidential
High Density Metering Enclosure
Specification Description
Overview One or four High Density MeterEnclosure with ION6200meters; ideal for outdoor as well
as indoor applications at allvoltage levels including 600Vdelta and 347/600V wyesystems
Meter Series ION6200
Voltage 12, 4T*
Phasing 3
Enclosure Size 1 or 4
# Meters 1 to 4**
Enclosure Rating R*** or 1
*Voltage Ordering Notes
12 = 208Y/120V wye; 240V delta
48 = 480Y/277V wye; (PM210/PM750)
4T = with provided 2.5:1 CTP (control power transformer);
480Y/277V wye (6200)
** # Meters Ordering Notes
Please indicate the number of meters to be pre-installed
when placing your order. You may order any number of
meters in the enclosure between one and the maximum
number of meters each enclosure will hold.
***Please enter R as the last digit for Type 3R outdoor on
one or four HDM enclosures with the 6200 series meter.