    SynapSensePower Metering

    Technical Data Sheet

    Overview

    SynapSensePower Metering offers 3-phase AC power metering for wye or delta loads. It uses the

    SquareD PowerLogic ION 6200 meter to provide an adjustable display for easy to read energy, power,

    current, voltage, power factor, and harmonic data. The meters high accuracy is revenue grade and

    compatible with a wide range of solid or split core current transducers (CTs) from 50 amp up to 4000 amp

    models.

    The meter comes pre-installed in a wall-mount, single High Density Meter (HDM) enclosure. The HDM

    enclosure includes and knockouts for conduit connections. Terminal blocks for 3-phase AC wiring,

    CTs, ground, and Modbus RS422/RS485 connections are pre-wired to the meter.

    Power Metering works in tandem with the SynapSense Web Console. The Web Console is configured

    with a wye or delta and enables you to visually see the 3-phase current, voltage, demand power, power

    factor, total harmonic distortion, and energy data including summary information. The Web Console also

    enables you to track historical information from the power meter, using the historical data graphs.

    Power Metering GeneralSpecifications

    SynapSense Power Metering shown in an HDMEnclosure

    Features 3-phase power metering

    Per phase data

    Meter display provides local dataaccess; the Web Consoleprovides up to 21 data points withhistorical charting

    Available with split core CTsranging from 50 to 4000 amp in avariety of models

    Power MeterType

    PowerLogic ION6200

    RevenueCertification

    ANSI and Measurement Canadaoptions

    Factory-sealed version availablein Canada

    Communications RS-422/485 Modbus RTU forintegration with SynapSense WebConsole

    Pulse Outputs Optional: kWh summary informationavailable via the SynapSense WirelessSensor Network (WSN)

    3-PhaseMetering

    100 to 480 VAC L-L (50 to 60 Hz)

  • 8/11/2019 Synapsense Power Metering Data Sheet

    2/4

    copyright 2011 SynapSense Corporation Page2Rev A-5-2014

    SynapSense Proprietary & Confidential

    Power Meter Overview

    The SquareD ION 6200 Energy Meter features:

    64 samples per cycle

    IEC 60687 class 0.5 compliant

    Four quadrant energy and demand 49 real-time, true RMS electrical parameters

    Per phase voltage, current, peak current,

    demand, watts, VARs, kWh, and more

    Neutral current, Total Harmonic Distortion

    (THD), frequency, power factor

    Power Meter Accuracy

    Accuracy Speci ficati on

    Voltage L-N 0.3% reading, L-L 0.5% reading

    Frequency 0.1 Hz

    Current >= 5% of full scale: 0.3% reading

  • 8/11/2019 Synapsense Power Metering Data Sheet

    3/4

    copyright 2011 SynapSense Corporation Page3Rev A-5-2014

    SynapSense Proprietary & Confidential

    Veris CT General Specifications

    Specification Description

    Overview The H681x-xxx series of 5 Ampsplit-core current transformersprovide secondary amperage

    proportional to the primary(sensed) current. For use withpower meters, data loggers,chart recorders, and otherinstruments.

    Leads 18AWG, 600VAC, 6' standardlength

    OperatingTemperature Range

    15 to 60C (5 to 140F)

    Storage TemperatureRange

    -40 to 70C (-40 to 158)

    Humidity Range 0-95% non-condensing

    Max. Voltage L-N

    Sensed Conductor

    600VAC (basic insulationrating)

    Frequency Range 50/60 Hz

    Altitude of Operation 3km maximum

    Installation Category Cat II or Cat III

    Veris CT Ratings

    Model Sensing

    Current

    (A)

    Frequency

    (Hz)

    Output

    (A)

    Weight

    (kg)

    H6810 0 to 300 50/60 0 to 5 0.340

    H6811 0 to 800 50/60 0 to 5 0.580

    H6812 0 to 2400 50/60 0 to 5 0.870

    Veris CT Accuracy

    Model # F.S. Accuracy

    (96%)

    Burden

    Capacity (VA)

    H6810-100A-5A 4 .07

    H6810-200A-5A 1 2.5

    H6810-300A-5A 1 2.5

    H6811-400A-5A 1 5.0

    H6811-600A-5A 1 5.0

    H6811-800A-5A 1 12.5

    H6812-800A-5A 1 5.0

    H6812-1200A-5A 1 22.5

    H6812-1600A-5A 1 22.5

    H6812-2400A-5A 1 22.5

    Veris CT Mechanical Dimensions

  • 8/11/2019 Synapsense Power Metering Data Sheet

    4/4

    copyright 2011 SynapSense Corporation Page4Rev A-5-2014

    SynapSense Proprietary & Confidential

    High Density Metering Enclosure

    Specification Description

    Overview One or four High Density MeterEnclosure with ION6200meters; ideal for outdoor as well

    as indoor applications at allvoltage levels including 600Vdelta and 347/600V wyesystems

    Meter Series ION6200

    Voltage 12, 4T*

    Phasing 3

    Enclosure Size 1 or 4

    # Meters 1 to 4**

    Enclosure Rating R*** or 1

    *Voltage Ordering Notes

    12 = 208Y/120V wye; 240V delta

    48 = 480Y/277V wye; (PM210/PM750)

    4T = with provided 2.5:1 CTP (control power transformer);

    480Y/277V wye (6200)

    ** # Meters Ordering Notes

    Please indicate the number of meters to be pre-installed

    when placing your order. You may order any number of

    meters in the enclosure between one and the maximum

    number of meters each enclosure will hold.

    ***Please enter R as the last digit for Type 3R outdoor on

    one or four HDM enclosures with the 6200 series meter.