HVS Subcommittee Fall 2012
Switch Loadability
IEEE C37.30.1 Annex C
![Page 2: Switch Loadability - IEEE Web Hosting...C37.30.1 Table C – Temperature Limitations HVS Subcommittee Fall 2012 ACCC Designation • Allowable Continuous Current Class • Identified](https://reader036.fdocuments.in/reader036/viewer/2022071609/61474893afbe1968d379f584/html5/thumbnails/2.jpg)
HVS Subcommittee Fall 2012
C37.30.1 Table C – Temperature Limitations
![Page 3: Switch Loadability - IEEE Web Hosting...C37.30.1 Table C – Temperature Limitations HVS Subcommittee Fall 2012 ACCC Designation • Allowable Continuous Current Class • Identified](https://reader036.fdocuments.in/reader036/viewer/2022071609/61474893afbe1968d379f584/html5/thumbnails/3.jpg)
HVS Subcommittee Fall 2012
ACCC Designation
• Allowable Continuous Current Class • Identified on air switch nameplate • Code for composite curve of limiting switch part
classes • Majority of current air switches are DO6
• Combination of DO4 and FO6 curves • DO curve from 60°C to 25°C • O6 curve from 25°C to -30°C
![Page 4: Switch Loadability - IEEE Web Hosting...C37.30.1 Table C – Temperature Limitations HVS Subcommittee Fall 2012 ACCC Designation • Allowable Continuous Current Class • Identified](https://reader036.fdocuments.in/reader036/viewer/2022071609/61474893afbe1968d379f584/html5/thumbnails/4.jpg)
HVS Subcommittee Fall 2012
Allowable Continuous Current
![Page 5: Switch Loadability - IEEE Web Hosting...C37.30.1 Table C – Temperature Limitations HVS Subcommittee Fall 2012 ACCC Designation • Allowable Continuous Current Class • Identified](https://reader036.fdocuments.in/reader036/viewer/2022071609/61474893afbe1968d379f584/html5/thumbnails/5.jpg)
HVS Subcommittee Fall 2012
![Page 6: Switch Loadability - IEEE Web Hosting...C37.30.1 Table C – Temperature Limitations HVS Subcommittee Fall 2012 ACCC Designation • Allowable Continuous Current Class • Identified](https://reader036.fdocuments.in/reader036/viewer/2022071609/61474893afbe1968d379f584/html5/thumbnails/6.jpg)
HVS Subcommittee Fall 2012
2000 A Switch Rating with “D06” LF Applied
Ambient (°C) LF Rating (Amps) -30 1.60 3200 -20 1.54 3080 -10 1.47 2940 0 1.41 2820 10 1.34 2680 20 1.27 2540 30 1.18 2360 40 1.08 2160 50 0.96 1920
![Page 7: Switch Loadability - IEEE Web Hosting...C37.30.1 Table C – Temperature Limitations HVS Subcommittee Fall 2012 ACCC Designation • Allowable Continuous Current Class • Identified](https://reader036.fdocuments.in/reader036/viewer/2022071609/61474893afbe1968d379f584/html5/thumbnails/7.jpg)
HVS Subcommittee Fall 2012
Emergency Ratings
![Page 8: Switch Loadability - IEEE Web Hosting...C37.30.1 Table C – Temperature Limitations HVS Subcommittee Fall 2012 ACCC Designation • Allowable Continuous Current Class • Identified](https://reader036.fdocuments.in/reader036/viewer/2022071609/61474893afbe1968d379f584/html5/thumbnails/8.jpg)
HVS Subcommittee Fall 2012
![Page 9: Switch Loadability - IEEE Web Hosting...C37.30.1 Table C – Temperature Limitations HVS Subcommittee Fall 2012 ACCC Designation • Allowable Continuous Current Class • Identified](https://reader036.fdocuments.in/reader036/viewer/2022071609/61474893afbe1968d379f584/html5/thumbnails/9.jpg)
HVS Subcommittee Fall 2012
2000 A Switch Rating with “D06” LE1 Applied
Ambient (°C) LE1 (24 hr) Rating (Amps) -30 1.71 3420 -20 1.65 3300 -10 1.60 3200 0 1.54 3080 10 1.47 2940 20 1.41 2820 30 1.34 2680 40 1.27 2540 50 1.18 2360
![Page 10: Switch Loadability - IEEE Web Hosting...C37.30.1 Table C – Temperature Limitations HVS Subcommittee Fall 2012 ACCC Designation • Allowable Continuous Current Class • Identified](https://reader036.fdocuments.in/reader036/viewer/2022071609/61474893afbe1968d379f584/html5/thumbnails/10.jpg)
HVS Subcommittee Fall 2012
![Page 11: Switch Loadability - IEEE Web Hosting...C37.30.1 Table C – Temperature Limitations HVS Subcommittee Fall 2012 ACCC Designation • Allowable Continuous Current Class • Identified](https://reader036.fdocuments.in/reader036/viewer/2022071609/61474893afbe1968d379f584/html5/thumbnails/11.jpg)
HVS Subcommittee Fall 2012
2000 A Switch Rating with LE2 Applied
Ambient (°C) LE2 Rating (Amps) -30 1.65 3200 -20 1.60 3300 -10 1.54 3080 0 1.47 2940 10 1.41 2820 20 1.34 2680 30 1.27 2540 40 1.18 2360 50 1.08 2160
![Page 12: Switch Loadability - IEEE Web Hosting...C37.30.1 Table C – Temperature Limitations HVS Subcommittee Fall 2012 ACCC Designation • Allowable Continuous Current Class • Identified](https://reader036.fdocuments.in/reader036/viewer/2022071609/61474893afbe1968d379f584/html5/thumbnails/12.jpg)
HVS Subcommittee Fall 2012
![Page 13: Switch Loadability - IEEE Web Hosting...C37.30.1 Table C – Temperature Limitations HVS Subcommittee Fall 2012 ACCC Designation • Allowable Continuous Current Class • Identified](https://reader036.fdocuments.in/reader036/viewer/2022071609/61474893afbe1968d379f584/html5/thumbnails/13.jpg)
HVS Subcommittee Fall 2012
User Information and Precautions
• LF ≥ 1.0 only on new or properly maintained equipment • LF ≤ 2.0 regardless of the ambient temperature • Consult switch manufacturer if ACCC designation is not
known • IEEE C37.30-1962 or earlier switches
• ACCC = AO1 for non-enclosed switches • ACCC = NO1 for enclosed switches
• Switch inspection is recommended after severe emergency overload