Instrument Signal Connections SIL Surge Protection Devices ...
Surge Impedance Loading (Sil)
-
Upload
vijaypshinde -
Category
Documents
-
view
2.303 -
download
0
Transcript of Surge Impedance Loading (Sil)
Surge impedance of a line, Zo 'LC
.
SIL '(kVLL)2
Zo
, (MW)
I 2XL'V 2
Xc
, or, V 2
I 2'XLXc '
TLTC
, or, VI'
LC'Zo'Load impedance
SURGE IMPEDANCE LOADING (SIL)
A transmission line loaded to its surge impedance loading:
(i) has no net reactive power flow into or out of the line, and(ii) will have approximately a flat voltage profile along its length.
For (i) to hold:
This means that there will be no net reactive power flow at surge-impedanceloading.
Vs'AVr%BIr ; Is'CVr%DIr ,
And, Vs' (A%BZo
)Vr' (cos 2BR8
% j sin 2BR8
)Vr'Vrptan&1 2BR8
,
Is' (CZo%D)Ir' ( jsin 2BR8
%cos 2BR8
)Ir' Irptan&1 2BR8
At surge&impedance loading ,Vr
Ir
'Zo .
Then, A'D'cos 2BR8
; B' jZosin 2BR8
; C' jsin 2BR
8Zo
ZY' jTR LC'jTR<c
' j 2BfRf8
' j 2BR8
where, A'D'cosh ZY ; B'Zosinh ZY ; C'sinh ZY
Zo
; Z' jTLR ; Y' jTCR
For (ii) to hold:
This means that the line will have a flat voltage profile, i.e., no voltage drop.
LOADABILITY CURVES
Loadability of a line is limited by :
(i) thermal limitation (I R losses)2
(ii) voltage regulation(iii) stability limitation
(EPRI Publication EL-2500)