Appendix Q Substation Lighting Specification Details

Transcript of Substation Lighting Specification Details - s3-eu-west-1 ... · Emergency, AutoTest and Scanlight...

Page 1: Substation Lighting Specification Details - s3-eu-west-1 ... · Emergency, AutoTest and Scanlight AT versions add 0.3kg to weights listed ... PROJECT NAME: Monaincha 38kV Substation

Appendix Q

Substation Lighting Specification Details

Page 2: Substation Lighting Specification Details - s3-eu-west-1 ... · Emergency, AutoTest and Scanlight AT versions add 0.3kg to weights listed ... PROJECT NAME: Monaincha 38kV Substation

Appendix Q1 – Lighting Specification Details for Substation

Page 3: Substation Lighting Specification Details - s3-eu-west-1 ... · Emergency, AutoTest and Scanlight AT versions add 0.3kg to weights listed ... PROJECT NAME: Monaincha 38kV Substation

Sonpak LX 15/25/40

96232644 SONPAK LX 150W 240V HST/E40/220 A/STimes New Roman

Thorn Lighting is constantly developing and improving its products. The right is reserved to change specifications without prior notification or public announcement. © Thorn Lighting

E40 150W HST

A range of easy to install performance floodlights supplied complete with lamp.

A redesigned robust and compact discharge floodlight with IP65 optical and gear compartment, SC1 class.black aluminium die casting alloy body with vandal resistant Flat Glass enclosure.mild steel painted black stirrup.Sonpak LX 15/25/40 uses aluminium - texturebrite asymmetrical reflector and is supplied complete with integral control gear and 150 W HST lamp.

Dimensions: 522 x 426 x 130 mmWeight: 8 kg.

TLG_SPK7_F_LX15.jpg

TLG_SPK7_M_LXLD15.wmf

30°30°

60°60°

90° 90°

120° 120°

150° 150°

180°

250500750

cd/klm

TLG_LA_SE00007.ldt

Lamp position: STD - standardLamps: 1 x HST / 150WTotal luminous flux: 15000 lmLuminaire efficacy: 62 lm/WColour Rendering Index min.: 20Ballast: 1x MAGConnected Load: 171 WLOR: 0,70 ULOR: 0,00 DLOR: 0,70

Page 4: Substation Lighting Specification Details - s3-eu-west-1 ... · Emergency, AutoTest and Scanlight AT versions add 0.3kg to weights listed ... PROJECT NAME: Monaincha 38kV Substation

ACCESSORIES

DESCRIPTION CAT. No.

Tamper-resistant screw kit including key CT 11699

PHOTOMETRIC GUIDE DIMENSIONS

CANDELAS PER 1000 LUMENS

50

100

150

200

CANDELAS PER 1000 LUMENS

420

420

280

280

140

140

CANDELAS PER 1000 LUMENS

420

420

280

280

140

140

340 dia. 115

220

22063

FIXINGS: 4 x Spot faces, drill as required

SIDE CONDUITENTRIES:

4 x Spot faces,drill as required

REAR CONDUITENTRY: 1 x Spot face,

drill as required.(For 2D versions)

REAR CONDUIT ENTRY: 1 x Spot face, drill as required. (For 26W TC-T version)

15/23W LED - PLAIN VERSION

Luminaire Lumen Output 15W = 1070lm 23W = 1450lm

18W LED - HOOD VERSION

Luminaire Lumen Output 18W = 720lm

38W 2D LAMP (Ceiling mounted) D.L.O.R. 59% U.L.O.R. 0%

Factor: 28W 2D OPAL = 0.75 38W 2D OPAL = 0.75 28W 2D SATIN = 1.03

OPTIONS

DESCRIPTION SUFFIX EXAMPLE

Photocell s PC CT 14441LPC

sHood / hood & grill versions only

216 www.thorlux.com/exterior Dec ‘12

Page 5: Substation Lighting Specification Details - s3-eu-west-1 ... · Emergency, AutoTest and Scanlight AT versions add 0.3kg to weights listed ... PROJECT NAME: Monaincha 38kV Substation

IP66 circular LED and compact fluorescent luminaires COBALT

l Strong die-cast LM2 aluminium body and cover frame. Graphite, full polyester powder finish as standardl Silver or white finish options l Two diffuser options - opal or high efficiency satin polycarbonatel Choice of cover stylesl Complies with M.O.D. JSP482 Chapter 8 Document for ‘Category C’ areasl Photocell optionl Fitted with lamp or 5000K/6000K LEDs

SPECIFICATION

IP66 IK10 LED2D

Hood & Grill

Plain Plain & GrillHood

PLAIN HOOD APPROX. PLAIN & GRILL HOOD & GRILL APPROX. LAMP VERSION VERSION kg VERSION VERSION kg

15W LED CT 14538L 3.0 CT 14540L 3.2 18W LED CT 14441L 3.0 CT 14504L 3.2 23W LED CT 14542L 3.0 CT 14544L 3.2

26W TC-T n CT 11572J u 3.3 CT 11581J u 3.5 28W 2D s CT 11573J 3.7 CT 11574J 3.9 38W 2D s CT 11575J 3.7 CT 11576J 3.9

26W TC-T n CT 11460J u 3.1 CT 11461J u 3.3 28W 2D s CT 11462J 3.5 38W 2D s CT 11464J 3.5

RANGEDIFFUSER OPTIONS

HIG

H E

FFIC

IEN

CY

SATI

N D

IFFU

SER

OPA

L D

IFFU

SER

s 3500K lamp fitted n 4000K lamp fitted u Photocell option

CIRCUIT TYPE - J - non-dimming (HF fluorescent) / L - non-dimming (LED)

COLOUR OPTIONS - add suffix: SV3 - Silver / W9 - White e.g. CT 14538LSV3 etc.

EMERGENCY VERSION - prefix catalogue number with: ECT - Emergency / TCT - AutoTest / DCT - Scanlight AT (LED versions only) e.g. ECT 14538L etc. Emergency, AutoTest and Scanlight AT versions add 0.3kg to weights listed

NOTE: Lamp more visible with High Efficiency Satin Diffuser than Opal Diffuser when lit

LED CHARACTERISTICSRa °K L70/B10 P/U % R/Rx PF LL/CW

15W Plain - 59.4 / Plain & Grill - 39.7 65 15/23W - 6000 60K P >90 R >0.95 23W Plain - 58.0 / Plain & Grill - 38.4 18W - 5000 18W Hood - 32.7 / Hood & Grill - 35.0

High Efficiency Satin Diffuser

Opal Diffuser

Dec ‘12 www.thorlux.com/exterior 217

TC-T

For LED characteristics explanation see www.thorlux.com/led-characteristics

Page 6: Substation Lighting Specification Details - s3-eu-west-1 ... · Emergency, AutoTest and Scanlight AT versions add 0.3kg to weights listed ... PROJECT NAME: Monaincha 38kV Substation

HS 502

Compact and understated: the HS 502

Halogen fl oodlight 502 is equipped with a DUO-sensor and multi-lens. The sensor has a reach of up to 12 metres with a coverage angle of 180° and an angle of aperture of 90°. It is the perfect choice specifi cally for sensitive common areas in which conventional lights are not bright enough. Reach is limited to about 5 metres quickly and easily by turning the two-zone multi-lens. Bezel, wall mount and floodlight enclosure are made of tough die-cast aluminium. This fl oodlight is rated for halogen lamps of up to 500 watts. Further loads can be connected at an additional switching output. Of timeless design, this compact floodlight is understated, making it suitable for any purpose.

Sensor-switched halogen floodlight 500 watts max. Tilting/turning refl ector head Connection of other loads at an additional switching output Head tilts through: 40° Head turns through: 30° Linear ECO halogen lamp is included

Page 7: Substation Lighting Specification Details - s3-eu-west-1 ... · Emergency, AutoTest and Scanlight AT versions add 0.3kg to weights listed ... PROJECT NAME: Monaincha 38kV Substation

HS 502 EAN black 4007841 632717

EAN white 4007841 632816

EAN silver 4007841 648510

Dimensions (h x w x d) 236 x 220 x 155 mm

Voltage 230 – 240 V / 50 Hz

Output 500 W max. / R7s 400 W ECO linear lamp (included)

Additional switching capacity - 500 W max. (resistive load, e.g. fi lament bulb)

- 300 W max. (uncorrected, inductive, cos ϕ = 0.5, e.g. fl uorescent lamps) - electronic ballasts, capacitive, e.g. low-energy lamps, no more than 2 each, ≤ 44 μF

Angle of coverage 180° with 90° angle of aperture

Reach Basic setting 1: 12 m max. Basic setting 2: 5 m max. + precision adjustment using shrouds; temperature-stabilised

Sensor system 10 detection levels (12 m), 9 detection levels (5 m), 504 switching zones (12 m), 412 switching zones (5 m)

Time setting 10 sec. – 15 min.

Twilight setting 2 – 2000 lux

Enclosure IP 44

Protection class I

Temperature range -20° to +40° C

Subject to technical modifications.

Detection zone

Page 8: Substation Lighting Specification Details - s3-eu-west-1 ... · Emergency, AutoTest and Scanlight AT versions add 0.3kg to weights listed ... PROJECT NAME: Monaincha 38kV Substation

Max. reach: 5 m, 12 m tangentially Angle of coverage: 180° Angle of aperture: 90°

Reach setting by means of swivelling multi-lens (5 m, 12 m)

Setting capabilities

Shrouds: restrict the angle of coverage and reach to suit requirements

Floodlight enclosure: cone of light can be precisely targeted by turning the enclosure (30° max.)…

…and tilting through 40°

Page 9: Substation Lighting Specification Details - s3-eu-west-1 ... · Emergency, AutoTest and Scanlight AT versions add 0.3kg to weights listed ... PROJECT NAME: Monaincha 38kV Substation

DATE: 11 April 2013DESIGNER: Pat O'DonoghuePROJECT No: W0042-1-D015PROJECT NAME: Monaincha 38kV Substation ESB Compound

Outdoor Lighting Report

Prepared using WRTL Reality (www.lightingreality.co.uk)Roadway and Outdoor Lighting Design Softwareissued under a Redistribution Licence assigned to:

WRTL Exterior Lighting Ltd. (www.wrtl.co.uk)Waterside Park Golds Hill Way Tipton DY4 0PUEmail: [email protected]

C:\Pats files\Pats World\Monaicha\Technical\Calculations\Lighting\Monaincha Lighting ESB.raa

Page 10: Substation Lighting Specification Details - s3-eu-west-1 ... · Emergency, AutoTest and Scanlight AT versions add 0.3kg to weights listed ... PROJECT NAME: Monaincha 38kV Substation

DATE: 11 April 2013DESIGNER: Pat O'DonoghuePROJECT No: W0042-1-D016PROJECT NAME: Monaincha 38kV Substation IPP Compound

Outdoor Lighting Report

Prepared using WRTL Reality (www.lightingreality.co.uk)Roadway and Outdoor Lighting Design Softwareissued under a Redistribution Licence assigned to:

WRTL Exterior Lighting Ltd. (www.wrtl.co.uk)Waterside Park Golds Hill Way Tipton DY4 0PUEmail: [email protected]

C:\Pats files\Pats World\Monaicha\Technical\Calculations\Lighting\Monaincha Lighting IPP.raa

Page 11: Substation Lighting Specification Details - s3-eu-west-1 ... · Emergency, AutoTest and Scanlight AT versions add 0.3kg to weights listed ... PROJECT NAME: Monaincha 38kV Substation

DATE: 11 April 2013 DESIGNER:PROJECT No: W0042-1-D016 PROJECT NAME:

Pat O'Donoghue Monaincha 38kV Substation IPP Compound

WRTL Exterior Lighting Ltd. Waterside Park Golds Hill Way Tipton West Midlands DY4 0PU Email:[email protected]

2009000000

Layout ReportGeneralData

Area 33.0m x 22.5mMaintenance Factor 0.65

Luminaires

Luminaire A Data Supplier

Type

Lamp(s)

Lamp Flux (klm)

File Name

Maintenance Factor

Imax70,80,90(cd/klm)

WRTL

MFMNA150TS

150W SON-TS

15.00

MFMNA150TSa.pmr

0.65

85.6, 1.6, 0.0

Luminaire C Data Supplier

Type

Lamp(s)

Lamp Flux (klm)

File Name

Maintenance Factor

Imax70,80,90(cd/klm)

WRTL

PT1181RB POST TOP -

100W SON/T

10.70

INR6120.pmr

0.65

123.3, 126.7, 126.0

Layout

No. Type X Y Height Angle Tilt Cant Out-

reach

Target

X

Target

Y

Target

Z

1 A 10.94 5.25 2.00 178.00 45.00 0.00 0.00

2 A 18.79 17.52 3.00 272.00 45.00 0.00 0.00

3 A 10.91 13.32 2.00 178.00 45.00 0.00 0.00

4 C 5.00 20.00 2.00 270.00 0.00 0.00 0.00

5 C 2.50 2.50 2.00 49.00 0.00 0.00 0.00

6 A 16.46 20.12 2.00 178.00 45.00 0.00 0.00

2

Page 12: Substation Lighting Specification Details - s3-eu-west-1 ... · Emergency, AutoTest and Scanlight AT versions add 0.3kg to weights listed ... PROJECT NAME: Monaincha 38kV Substation

DATE: 11 April 2013 DESIGNER:PROJECT No: W0042-1-D016 PROJECT NAME:

Pat O'Donoghue Monaincha 38kV Substation IPP Compound

WRTL Exterior Lighting Ltd. Waterside Park Golds Hill Way Tipton West Midlands DY4 0PU Email:[email protected]

2009000000

Horizontal Illuminance (lux)

80

8080

80

80

80

80

80

80

50

50

50

50

50

50

50

50

50

50

50

25

25

25

25

25

2525

25

15

15

15

15

15

15

15

10

10

10

10

1010

8.0

8.0

8.0

8.0

8.0

8.0

4.0

4.0

4.0

4.0

A

A

A

C

C

A

22.50

0.00 0.00 33.00

Results Eav

Emin

Emax

Emin/Emax

Emin/Eav

62.05

4.22

244.54

0.02

0.07

3

Page 13: Substation Lighting Specification Details - s3-eu-west-1 ... · Emergency, AutoTest and Scanlight AT versions add 0.3kg to weights listed ... PROJECT NAME: Monaincha 38kV Substation

DATE: 11 April 2013 DESIGNER:PROJECT No: W0042-1-D016 PROJECT NAME:

Pat O'Donoghue Monaincha 38kV Substation IPP Compound

WRTL Exterior Lighting Ltd. Waterside Park Golds Hill Way Tipton West Midlands DY4 0PU Email:[email protected]

2009000000

Horizontal Illuminance (lux)

0 61 122 183 245

80

8080

80

80

80

80

80

80

50

50

50

50

50

50

50

50

50

50

50

25

25

25

25

25

2525

25

15

15

15

15

15

15

15

10

10

10

10

1010

8.0

8.0

8.0

8.0

8.0

8.0

4.0

4.0

4.0

4.0

A

A

A

C

C

A

22.50

0.00 0.00 33.00

Results Eav

Emin

Emax

Emin/Emax

Emin/Eav

62.05

4.22

244.54

0.02

0.07

4

Page 14: Substation Lighting Specification Details - s3-eu-west-1 ... · Emergency, AutoTest and Scanlight AT versions add 0.3kg to weights listed ... PROJECT NAME: Monaincha 38kV Substation

DATE: 11 April 2013 DESIGNER:PROJECT No: W0042-1-D016 PROJECT NAME:

Pat O'Donoghue Monaincha 38kV Substation IPP Compound

WRTL Exterior Lighting Ltd. Waterside Park Golds Hill Way Tipton West Midlands DY4 0PU Email:[email protected]

2009000000

Horizontal Illuminance (lux)

14 19 26 37 49 55 51 43 40 41 49 64 83 80 56 47

17 24 36 56 77 81 76 59 47 46 55 75 108 121 97 116

17 25 41 68 61 28 82 67 50 46 53 71 101 115 119 245

19 29 47 74 70 31 86 70 53 48 56 76 108 122 113 215

21 30 45 67 89 96 85 65 53 48 54 72 98 97 79 77

21 28 39 54 71 81 80 66 53 51 49 56 65 51 38 32 7.2 24 40 40 9.1 4.2

20 27 36 46 59 72 85 90 70 63 52 36 31 21 26 24 34 86 119 105 53 27

20 26 34 43 55 72 96 118 105 92 63 18 14 15 19 26 43 68 81 74 52 35

20 25 33 41 52 70 97 130 132 133 144

21 26 33 40 51 66 91 119 120 160 239

22 27 34 41 51 68 95 126 119 122 100

23 29 36 43 52 64 82 94 77 68 32

23 30 38 46 55 63 68 59 40 34 14

24 30 39 46 55 62 63 47 33 26 10

25 32 39 46 52 60 70 75 53 40 27

27 34 41 46 54 66 87 108 95 82 57

31 39 47 53 59 70 92 121 123 131 178

32 51 65 71 71 76 94 119 119 154 241

43 58 92 97 91 88 102 127 118 114 91

55 86 48 57 103 89 90 94 75 65 34

55 84 33 55 98 78 68 55 35 32 14

45 69 86 89 52 55 40 25 20 13 7.3

32 45 56 56 45 24 20 16 11 7.6 5.9

80

8080

80

80

80

80

80

80

50

50

50

50

50

50

50

50

50

50

50

25

25

25

25

25

2525

25

15

15

15

15

15

15

15

10

10

10

10

1010

8.0

8.0

8.0

8.0

8.0

8.0

4.0

4.0

4.0

4.0

A

A

A

C

C

A

22.50

0.00 0.00 33.00

Results Eav

Emin

Emax

Emin/Emax

Emin/Eav

62.05

4.22

244.54

0.02

0.07

5

Page 15: Substation Lighting Specification Details - s3-eu-west-1 ... · Emergency, AutoTest and Scanlight AT versions add 0.3kg to weights listed ... PROJECT NAME: Monaincha 38kV Substation

DATE: 11 April 2013 DESIGNER:PROJECT No: W0042-1-D015 PROJECT NAME:

Pat O'Donoghue Monaincha 38kV Substation ESB Compound

WRTL Exterior Lighting Ltd. Waterside Park Golds Hill Way Tipton West Midlands DY4 0PU Email:[email protected]

2009000000

Layout ReportGeneralData

Area 33.0m x 22.5mMaintenance Factor 0.65

Luminaires

Luminaire A Data Supplier

Type

Lamp(s)

Lamp Flux (klm)

File Name

Maintenance Factor

Imax70,80,90(cd/klm)

WRTL

MFMNA150TS

150W SON-TS

15.00

MFMNA150TSa.pmr

0.65

85.6, 1.6, 0.0

Luminaire C Data Supplier

Type

Lamp(s)

Lamp Flux (klm)

File Name

Maintenance Factor

Imax70,80,90(cd/klm)

WRTL

PT1181RB POST TOP -

100W SON/T

10.70

INR6120.pmr

0.65

123.3, 126.7, 126.0

Layout

No. Type X Y Height Angle Tilt Cant Out-

reach

Target

X

Target

Y

Target

Z

1 A 10.75 2.38 2.00 355.00 45.00 0.00 0.50

2 A 28.84 17.52 3.00 333.00 45.00 0.00 0.00

3 A 10.78 12.78 2.00 357.00 45.00 0.00 0.50

4 A 28.84 20.31 3.00 2.00 45.00 0.00 0.00

5 A 10.78 7.28 2.00 0.00 45.00 0.00 0.50

6 A 24.21 17.46 2.00 291.00 45.00 0.00 0.00

2

Page 16: Substation Lighting Specification Details - s3-eu-west-1 ... · Emergency, AutoTest and Scanlight AT versions add 0.3kg to weights listed ... PROJECT NAME: Monaincha 38kV Substation

DATE: 11 April 2013 DESIGNER:PROJECT No: W0042-1-D015 PROJECT NAME:

Pat O'Donoghue Monaincha 38kV Substation ESB Compound

WRTL Exterior Lighting Ltd. Waterside Park Golds Hill Way Tipton West Midlands DY4 0PU Email:[email protected]

2009000000

Horizontal Illuminance (lux)

80

80

80

80

80

80

80

80

50

50

50

5050

50

50

50

2525

25

25

25

25

25

1515

15

15

15

15

1010

10

10

10

8.08.0

8.0

8.0

8.0

4.0

4.0

4.0

4.0

A

A

A

A

A

A

22.50

0.00 0.00 33.00

Results Eav

Emin

Emax

Emin/Emax

Emin/Eav

58.68

5.32

248.44

0.02

0.09

3

Page 17: Substation Lighting Specification Details - s3-eu-west-1 ... · Emergency, AutoTest and Scanlight AT versions add 0.3kg to weights listed ... PROJECT NAME: Monaincha 38kV Substation

DATE: 11 April 2013 DESIGNER:PROJECT No: W0042-1-D015 PROJECT NAME:

Pat O'Donoghue Monaincha 38kV Substation ESB Compound

WRTL Exterior Lighting Ltd. Waterside Park Golds Hill Way Tipton West Midlands DY4 0PU Email:[email protected]

2009000000

Horizontal Illuminance (lux)

0 62 124 186 248

80

80

80

80

80

80

80

80

50

50

50

5050

50

50

50

2525

25

25

25

25

25

1515

15

15

15

15

1010

10

10

10

8.08.0

8.0

8.0

8.0

4.0

4.0

4.0

4.0

A

A

A

A

A

A

22.50

0.00 0.00 33.00

Results Eav

Emin

Emax

Emin/Emax

Emin/Eav

58.68

5.32

248.44

0.02

0.09

4

Page 18: Substation Lighting Specification Details - s3-eu-west-1 ... · Emergency, AutoTest and Scanlight AT versions add 0.3kg to weights listed ... PROJECT NAME: Monaincha 38kV Substation

DATE: 11 April 2013 DESIGNER:PROJECT No: W0042-1-D015 PROJECT NAME:

Pat O'Donoghue Monaincha 38kV Substation ESB Compound

WRTL Exterior Lighting Ltd. Waterside Park Golds Hill Way Tipton West Midlands DY4 0PU Email:[email protected]

2009000000

Horizontal Illuminance (lux)

7.5 41 48 43 51

30 99 74 56 59

40 124 91 69 64

39 106 103 81 75

27 74 112 86 85

70 107 76 48 31 52 132 120 83 85

205 235 125 72 43 67 127 93 72 74

111 123 121 105 75 78 89 71 66 65

8.1 88 81 100 96 68 48 36 29 29 39 62 110 128 120 118 90 84 71 62 66 64

82 218 114 122 105 73 54 42 35 34 37 70 107 116 96 88 79 69 61 59 63 62

87 228 118 121 105 78 60 49 41 36 40 67 82 84 70 62 59 54 49 51 55 54

14 114 108 133 128 97 73 55 45 38 41 55 61 60 54 47 44 42 38 42 46 45

8.0 71 83 125 136 104 77 59 47 39 41 47 48 46 42 38 35 33 30 31 36 36

8.3 87 95 128 138 105 78 60 48 41 40 42 40 38 35 31 28 26 24 23 26 28

43 188 120 136 124 96 75 60 50 43 40 38 35 32 29 25 23 20 19 18 19 21

88 248 121 125 110 84 70 60 52 45 39 35 31 27 24 21 19 17 16 15 15 16

20 143 116 138 124 97 77 62 52 45 37 32 28 24 21 18 16 14 13 12 12 12

6.6 80 93 122 137 107 81 63 51 42 35 29 25 21 18 16 14 12 11 11 10 10

7.5 91 96 125 138 107 80 61 48 39 32 26 22 19 16 14 13 11 10 9.3 8.7 8.5

67 203 120 136 125 96 73 57 45 36 29 24 20 17 15 13 11 10.09.0 8.3 7.7 7.4

89 241 118 120 103 75 59 48 40 33 26 21 18 15 13 12 10 9.0 8.1 7.4 6.9 6.6

20 127 104 125 101 69 51 40 34 28 23 19 16 14 12 10 9.2 8.2 7.4 6.7 6.2 5.9

8.1 56 65 91 85 61 44 34 28 24 20 17 14 12 11 9.4 8.3 7.4 6.7 6.1 5.7 5.3

80

80

80

80

80

80

80

80

50

50

50

5050

50

50

50

2525

25

25

25

25

25

1515

15

15

15

15

1010

10

10

10

8.08.0

8.0

8.0

8.0

4.0

4.0

4.0

4.0

A

A

A

A

A

A

22.50

0.00 0.00 33.00

Results Eav

Emin

Emax

Emin/Emax

Emin/Eav

58.68

5.32

248.44

0.02

0.09

5