WPDPI-000
INDEX OF DRAWINGS
SUBSET COVER SHEET
SUBSET 09 - TRACTION POWER
TRACTION POWER
SHEET
NUMBER
DRAWING
NUMBERDRAWING TITLE
SHEET
NUMBER
DRAWING
NUMBERDRAWING TITLE
DESIGNED BY: WSP USA INC.
09.01
09.02
09.03
09.04
09.05
09.06
09.07
09.08
09.09
09.10
09.11
09.12
09.13
09.14
09.15
PI-000
P-001
P-010
P-011
P-012
P-013
P-014
P-020
P-025
P-026
P-027
P-030
P-031
P-032
P-033
TRACTION POWER SUBSET COVER SHEET
TRACTION POWER SYMBOLS, NOTES AND ABBREVIATIONS
EXISTING SECTIONALIZING DIAGRAM
PROPOSED SECTIONALIZING DIAGRAM
TYPICAL NEUTRAL RETURN BONDING TAP AT POLE
NEUTRAL RETURN DETAIL
TYPICAL NEUTRAL RETURN BONDING AT CROSSOVER
NEUTRAL RETURN BONDING & GROUNDING INDEX PLAN
NEUTRAL RETURN BONDING & GROUNDING DETAILS
LAYOUT OF ELECTRICAL ISOLATION LIMITS
SECTIONALIZING DISCONNECT SWITCH AND FEEDER ARRANGEMENT
SNOW MELTER PLAN
SNOW MELTER CASE PANEL SCHEDULES
SNOW MELTER GROUNDING AND SWITCH HEATER DETAILS
SNOW MELTER MISCELLANEOUS DETAILS
JLW/JLD
09.01
301-0182
NEW HAVEN RAIL YARD
FACILITIES IMPROVEMENTS
NEW HAVEN
DEPARTMENT OF TRANSPORTATION
STATE OF CONNECTICUT
THE INFORMATION, INCLUDING ESTIMATED QUANTITIES OF WORK, SHOWN ON THESE SHEETS IS BASED ON LIMITED INVESTIGATIONS BY THE STATE AND ISIN NO WAY WARRANTED TO INDICATE THE CONDITIONS OF ACTUAL QUANTITIES OF WORK WHICH WILL BE REQUIRED.
REV. DATE REVISION DESCRIPTION SHEET NO. Filename: 22_PNLA_3010088_P-001.dgnPlotted Date: 10/24/2017
DESIGNER/DRAFTER:
CHECKED BY:
SIGNATURE/
BLOCK:
PROJECT NO.
DRAWING NO.
SHEET NO.
DRAWING TITLE:
TOWN:PROJECT TITLE:
EAST END CONNECTION
B.F.P-001
M.M./N.D.
THESE GENERAL NOTES ARE SUPPLEMENTED BY NOTES GIVEN ON INDIVIDUAL DRAWINGS.
DUCT BANK OR CONDUIT
THE CONTRACTOR SHALL PROTECT FROM DAMAGE ALL MONUMENTS, SURVEY POINTS, AND BENCH MARKS NOT DESIGNATED
FOR REMOVAL AND SHALL ESTABLISH OFFSET POINTS AS REQUIRED.
NEW HAVEN RAIL YARD CONSTRUCTION CONTRACT DESIGNATIONS
L
COPPER BUS BAR
BETWEEN RAILS
OR
CONNECTION
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
1.
12.
13.
14.
15.
AERIAL WIRE, 4/0 AWG BARE COPPER
THE CONTRACTOR SHALL FIELD VERIFY AND LOCATE ALL UNDERGROUND PUBLIC AND RAILROAD UTILITIES IN
COORDINATION WITH UTILITY COMPANIES PRIOR TO COMMENCEMENT OF THE WORK. ANY DAMAGE TO THE EXISTING
UTILITIES SHALL BE REPAIRED BY THE CONTRACTOR.
THE LOCATION OF EXISTING UTILITIES AND DUCT BANKS SHOWN ON THE SITE PLANS ARE APPROXIMATE.
THE CONTRACTOR SHALL VERIFY THE ACTUAL LOCATIONS PRIOR TO COMMENCEMENT OF THE WORK AND MODIFY
THE DUCT PLANS AS REQUIRED BASED ON SITE CONDITIONS.
THE CONTRACTOR SHALL PROTECT, PRESERVE, INCORPORATE, TEMPORARILY RELOCATE, AND, IF NECESSARY, SUPPORT
ALL EXISTING UTILITIES AND ITEMS TO REMAIN. THE CONTRACTOR SHALL REPAIR OR REPLACE ANY ITEM DAMAGED
DURING THE COURSE OF WORK TO THE SATISFACTION OF THE ENGINEER.
THE CONTRACTOR SHALL PROVIDE AND MAINTAIN SAFEGUARDS NECESSARY TO PROTECT PERSONS AND PROPERTY FROM
INJURY OR DAMAGE DURING PERFORMANCE OF THE WORK. OSHA, STATE, FRA, AND ALL MUNICIPAL CODES SHALL BE
FOLLOWED. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL LIABILITIES ARISING OUT OF ANY DAMAGES AT SITE.
APPROVAL, BY THE ENGINEER, OF SHOP DRAWINGS AND PROCEDURES FOR CONSTRUCTION AND TESTING SHALL NOT ABSOLVE THE
CONTRACTOR FROM ANY LIABILITY RESULTING FROM ITS OPERATIONS.
16.
17.
ALL EXCAVATIONS AND BACK FILL, SITE DRAIN LINES, ROAD SURFACE AND BED REPLACEMENT SHALL BE IN ACCORDANCE
WITH THE CONTRACT REQUIREMENTS. THE CONTRACTOR SHALL ENSURE THAT OPEN EXCAVATIONS ARE NOT LEFT UNPROTECTED
AT ANYTIME.
THE CONTRACTOR SHALL PROVIDE ALL COMPONENTS AND HARDWARE INSTALLATION IN ACCORDANCE WITH THE
MANUFACTURER’S RECOMMENDED PROCEDURES.
18.
IT SHALL BE THE CONTRACTOR’S RESPONSIBILITY TO SEE THAT IT HAS THE LATEST APPROVED SET OF DRAWINGS AND
SPECIFICATIONS BEFORE STARTING ANY PART OF THE WORK.
THE CONTRACTOR SHALL MAINTAIN A MINIMUM OF 9’-0" CLEARANCE FROM THE CENTERLINE OF TRACK TO ALL POLES, EQUIPMENT,
AND/OR EQUIPMENT DOOR IN OPEN 90 DEGREE POSITION.
ALL DUCT BANKS SHALL BE MINIMUM 18" BELOW GRADE AND 36" BELOW THE BOTTOM OF TIES IN ALL TRACK AREAS. PROVIDE
A 3" WIDE RED MARKER TAPE 12" ABOVE ALL DUCT BANKS. LABEL TAPE "CAUTION ELECTRICAL LINES BURIED BELOW".
THE CONTRACTOR SHALL FIELD VERIFY WITH THE ENGINEER ALL AERIAL WIRE TAP STRUCTURE LOCATIONS PRIOR TO
COMMENCEMENT OF WORK.
CABLE TERMINATIONS, TAPS, AND SPLICES ARE TO BE PERFORMED BY AN APPROVED CERTIFIED SPLICER.
19.
20.
THE CONTRACTOR SHALL PROVIDE AN APPROVED CABLE PULLING SCHEDULE AND SHALL DETERMINE AND IDENTIFY ALL AS-BUILT CABLE
OCCUPANCIES IN ALL UNDERGROUND DUCTS AND IDENTIFY SPARE DUCTS.
THE ENGINEER WILL ADMINISTER THE WORK TO BE PERFORMED UNDER THIS CONTRACT IN ACCORDANCE WITH THE CONTRACT DRAWINGS
AND SPECIFICATIONS INCLUDING ROADWAY WORKER PROTECTION, ACCESS AND PROTECTION FOR THE CONTRACTOR REGARDING THE
FACILITIES OF THE RAILROAD, COORDINATION OF TRACK OUTAGES, AND THE REMOVAL FROM SERVICE AND PLACEMENT INTO SERVICE OF
ELECTRICAL CIRCUITS.
THE CONTRACTOR IS MADE AWARE THAT THE ARRANGEMENT OF THE CONDUITS AS SHOWN ON THE PLANS MAY HAVE TO BE MODIFIED
IN ORDER TO ALLOW FOR THE NEW DUCT BANKS TO CROSS THE EXISTING DUCT BANK IN ORDER TO MINIMIZE OR ELIMINATE
ROCK EXCAVATION OR TO SUIT SITE SPECIFIC REQUIREMENTS.
TRACTION POWER SYMBOLS,
NOTES AND ABBREVIATIONS
ALL WORK SHALL BE PERFORMED IN STRICT ACCORDANCE WITH REQUIREMENTS OF RELEVANT SPECIFICATIONS,
NATIONAL ELECTRICAL CODE (2014), NATIONAL ELECTRICAL SAFETY CODE (2017), AND AREMA MANUAL FOR
RAILWAY ENGINEERING (CURRENT EDITION).
ALL CONDUITS SHALL HAVE LARGE RADIUS BENDS, MINIMUM 36", EXCEPT WHERE SPECIFICALLY NOTED OTHERWISE.
ALL UNDERGROUND DUCT WORK SHOWN SHALL BE FURNISHED AND INSTALLED BY THE CONTRACTOR.
THE CONTRACTOR SHALL FURNISH AND INSTALL A NYLON PULL-CORD IN ALL CONDUITS.
GROUND
A, AMP
AC
AWG
C
CLR
CONC
COND
CONST
CU
CP
CTR
DB
DC
DISC
DR
DWG
EF
EOT
EXIST
GND
HH
ID
IJ
J
KCMIL
MIN
MNR
N
NC
NEC
NESC
NO
NTS
OC
PS
PSI
PVC
RGS
SMC
SMH
SW
TK
TP
TPSS
TYP
UON
V
W
AMPERE
ALTERNATING CURRENT
AMERICAN WIRE GAGE
CENTERLINE
CLEARANCE
CONCRETE
CONDUIT
CONSTRUCTION
COPPER
CART PATH
CENTER
DUCT BANK
DIRECT CURRENT
DISCONNECT
DERAIL
DRAWING
EACH FACE
END OF TRACK
EXISTING
GROUND
HAND HOLE
INNER DIAMETER
INSULATING JOINT
JUMPER
THOUSAND CIRCULAR MILS
MINIMUM
METRO NORTH RAILROAD
NEUTRAL
NORMALLY CLOSED
NATIONAL ELECTRICAL CODE
NATIONAL ELECTRICAL SAFETY CODE
NORMALLY OPEN
NOT TO SCALE
ON CENTER
POINT OF SWITCH
POUNDS PER SQUARE INCH
POLYVINYL CHLORIDE
RIGID GALVANIZED STEEL
SNOW MELTER CABINET
SNOW MELTER HEATER
SWITCH
TRACK
TRACTION POWER
TRACTION POWER SUBSTATION
TYPICAL
UNLESS OTHERWISE NOTED
VOLTS
WATTS
300-0131 M-8 ACCEPTANCE FACILITY
300-0137 EMU AND CSR CAR SHOP IMPROVEMENTS
300-0138 WEST END YARD
300-0139 INDEPENDENT WHEEL TRUE FACILITY
301-0097 FUELING FACILITY
301-0106 COMPONENT CHANGE OUT SHOP
301-0110 DIESEL STORAGE YARD
301-0111 STORES BUILDING DEMOLITION
301-0121 CENTRAL DISTRIBUTION WAREHOUSE
301-0183 PEDESTRIAN BRIDGE OVERPASS NORTH
301-0124 MAINTENANCE OF WAY BUILDING
301-0144 YARD POWER UPGRADE
301-0182 EAST END CONNECTION
GROUNDING LOOP
09.02
09.03
09.04
09.05
09.06
09.07
09.08
09.09
09.10
09.11
301-0182
30 600
SCALE IN FEET
NEW HAVEN RAIL YARD
FACILITIES IMPROVEMENTS
NEW HAVEN
DEPARTMENT OF TRANSPORTATION
STATE OF CONNECTICUT
THE INFORMATION, INCLUDING ESTIMATED QUANTITIES OF WORK, SHOWN ON THESE SHEETS IS BASED ON LIMITED INVESTIGATIONS BY THE STATE AND ISIN NO WAY WARRANTED TO INDICATE THE CONDITIONS OF ACTUAL QUANTITIES OF WORK WHICH WILL BE REQUIRED.
REV. DATE REVISION DESCRIPTION SHEET NO. Filename: 22_PSMP_3010088_P-030.dgnPlotted Date: 10/24/2017
DESIGNER/DRAFTER:
CHECKED BY:
SIGNATURE/
BLOCK:
PROJECT NO.
DRAWING NO.
SHEET NO.
DRAWING TITLE:
TOWN:PROJECT TITLE:
EAST END CONNECTION
KEY PLAN
P-030
M.M./N.D.
R.L.
SNOW MELTER
SMH-EEC1
(BY MNR)
SMHH-EEC1
2-5" PVC SNOW MELTER DUCT
BANK, 2-6 AWG & 1-6 AWG GND
FROM EXIST SMC-1
SMH-EEC2
(BY MNR)
EXIST SM HH
EXIST SMC-3
EXIST SMC-1
1-2" PVC DIRECT BURIED
CONDUIT, 2-6 AWG &
1-6 AWG GND (BY MNR)
2-4 AWG & 1-6 AWG GND
FROM EXIST SMC-3 IN EXIST
SPARE CONDUIT
1-2" PVC DIRECT BURIED
CONDUIT, 2-4 AWG &
1-6 AWG GND FROM EXIST
SM HH (BY MNR)
PLAN 09.12
09.13
09.14
3’-
0"
PLAN VIEW
COVER LIFTING
EYE (TYP)
4" PVC PIPE
NO 6 CRUSHED STONE
APPROX 8"
COVER AND FRAME
FRAME
SOLID COVER
SECTION
-A
-
A
FINISHED
GRADE
THERMITE WELD
(TYP)
P-033
M.M/S.B.
B.F.
SNOW MELTER
MISCELLANEOUS DETAILS
SNOW
MELTER
GROUND CONNECTION
TO DUCT BANK REBAR
(TYP)
3’-0" SQ
3/4 " X 10’ COPPER CLAD
STEEL GROUND ROD
BOND TO ALL METAL
PARTS WITH 4/0 MIN
BARE COPPER WIREKNOCKOUTS-ALL SIDES
(SIZE VARIES)
SNOW MELTER HANDHOLE
SE
E
NO
TE
S
12" NO 6 CRUSHED
STONE (TYP)
8" 8"
8"
8"
3"
MIN
EF
(TY
P)
CLASS "C" CONCRETE
REINFORCEMENT RODS
(4)#5 CONTINUOUS
(TYP)
2-5" DUCT BANK
FINISHED GRADE
WARNING TAPE W/METAL
TRACER (SEE NOTES)
SUITABLE BACKFILL
MATERIAL (SEE NOTES)
REBAR #4 STIRRUPS
24" OC
(TYP)
9"
PVC CONDUIT
SCHEDULE 80
(TYP)
DUCT BANK 25"x 16"
HORIZONTAL TRENCH LIMIT
(SEE NOTES)
VERTICAL
TRENCH LIMIT
(SEE NOTES)
SNOW MELTER TRENCH AND DUCT BANK
CROSS SECTION
HANDHOLE NOTES:
1. PROVIDE CONTINUOUS COAT OF WATERPROOFING ON ALL SIDES OF
HANDHOLES.
2. PROVIDE WATERTIGHT SEAL AROUND THE GROUND RODS AND ALL
CONDUIT PENETRATIONS.
3. PROVIDE 8" OF NO 6 CRUSHED STONE BELOW HANDHOLES.
4. ALL SPLICES MUST BE APPROVED FOR SUBMERSIBLE LOCATIONS.
5. ALL HANDHOLES SHALL BE DESIGNED BY A CT LICENSED ENGINEER
FOR HS-20 LOADINGS.
6. SNOW MELTER HANDHOLES SHALL BE PAID FOR UNDER ITEM "ELECTRIC
HANDHOLE".
DUCT BANK NOTES:
1. PLACE COMPACTED GRANULAR FILL TO SEASONAL HIGH GROUND WATER ELEV 5.0.
2. SEE DEWATERING SPECIFICATION FOR DEWATERING REQUIREMENTS.
3. SUITABLE BACKFILL MATERIAL SHALL BE ANY MATERIAL EXCAVATED FROM THE
RESPECTIVE TRENCH THAT IS ACCEPTABLE TO THE ENGINEER. GRANULAR FILL
SHALL BE USED IN THE ABSENCE OF SUITABLE BACKFILL MATERIAL AS DIRECTED
BY THE ENGINEER.
4. FOR GENERAL CONDITIONS, THE MINIMUM BURIAL DEPTH FROM FINISHED GRADE
TO TOP OF CONCRETE IS 18". FOR SPECIAL CONDITIONS (UNDER TRACKS) THE MINIMUM
BURIAL DEPTH FROM THE BOTTOM OF TIE TO TOP OF CONCRETE IS 36".
5. WARNING TAPE WITH METAL TRACER SHALL BE LAID 12" ABOVE TOP OF DUCT BANK.
6. THE HORIZONTAL LIMITS FOR TRENCH EXCAVATION SHALL BE THE DUCT BANK WIDTH
PLUS 24".
7. THE VERTICAL LIMITS FOR TRENCH EXCAVATION SHALL BE 12" BELOW THE BOTTOM OF
DUCT BANK.
8. ALL EMPTY OR UNUSED CONDUITS SHALL HAVE PLASTIC PULL ROPES INSTALLED.
NOT TO SCALE
301-0182
NEW HAVEN RAIL YARD
FACILITIES IMPROVEMENTS
NEW HAVEN
DEPARTMENT OF TRANSPORTATION
STATE OF CONNECTICUT
THE INFORMATION, INCLUDING ESTIMATED QUANTITIES OF WORK, SHOWN ON THESE SHEETS IS BASED ON LIMITED INVESTIGATIONS BY THE STATE AND ISIN NO WAY WARRANTED TO INDICATE THE CONDITIONS OF ACTUAL QUANTITIES OF WORK WHICH WILL BE REQUIRED.
CONNECTICU
T
DE
PA
RT
ME
NT
O F TRANS
PO
RT
ATI
ON
REV. DATE REVISION DESCRIPTION SHEET NO. Filename: 22_PMDS_3010088_P-033.dgnPlotted Date: 10/24/2017
DESIGNER/DRAFTER:
CHECKED BY:
SIGNATURE/
BLOCK:
PROJECT NO.
DRAWING NO.
SHEET NO.
DRAWING TITLE:
TOWN:PROJECT TITLE:
10/2
4/2
017
T:\
18
96
5-N
HR
YF
I\C
TD
OT
_P
roje
cts
\30
1_
00
88
\Co
ntr
act_
Sh
eet_
Fil
es\2
2\0
9-T
racti
on
Po
wer\
22
_P
MD
S_
30
10
08
8_
P-0
33
.dg
n
2:2
5:5
1 P
M
EAST END CONNECTION 09.15