Job Name Location Purchaser Engineer Submitted to Reference Approval Construction Unit Designation Schedule # Schedule Control Function Through Web Browser • Up to 256 schedule settings • Weekly and daily schedule setting • Wireless/wired remote controller restriction setting • Digital outputs can be incorporated into scheduling External Contact Interface • Full indoor unit control with simple contact input (emergency/lock) • 8 additional digital input terminals for monitoring options • State output (operation/error) for synchronous control • 6 general purpose outputs to control other components (on: 12VDC out; off: no voltage) • Digital inputs and digital outputs can be incorporated into control logic. • Digital outputs can be incorporated into daily schedules to control other devices Energy Management / Power Distribution Function • The ability to monitor, track, and query energy use from indoor unit(s) and systems with MIM-B16 or MIM-B16N Electricity Meter Interface Module (purchased separately, requires 3rd party watt-hour meters with pulse output). • When used with SNET 3 software, detailed report generation is possible • User defined daily time periods for energy use reports to accommodate on/off peak energy billing. History Management • Storage of all operation commands from gateway and other system controls (saves to SD card purchased separately). • Storage of all error events for review (saves to SD card purchased separately). • Storage of all operation logic control events (saves to SD card purchased separately). • Error alerts via email that contain: error code, error explanation, units affected, time and date of error occurrence, and error status. Features BACnet Gateway • Control gateway that allows control and monitoring of Samsung HVAC systems via BACnet /IP Easy Control & Monitoring Through Web Browser • Individual/Group control of up to 256 indoor units including • Operation mode, temperature setting, airflow direction and fan speed. • Restriction on use of wireless/wired remote controllers, mode, temperature, and set point. • Outdoor and indoor unit cycle monitoring • Convenient digital display allows for easy set up • SD memory card slot for data storage and software updating (daily automatic backup, SD card purchased separately) • LAN connection for upper level control options • Available sophisticated control logic allows programming outputs based on various system inputs • Dynamic security management • Operation and error history management • Maximum current control of outdoor unit(s) to limit current (50% - 100% of design current) adjustable at outdoor unit or MIM-B17N. Web Server Function • Remote control with a public IP address via internet connection • No management software required – PC-independent management through web browser (optimized for Internet Explorer) • Multiple user accounts can be setup with the ability to specify what unit(s) each individual can monitor and control and what level of control permission is allowed. SUBMITTAL Page www.SamsungHVAC.com 888-699-6067 Samsung HVAC maintains a policy of ongoing development,specifications are subject to change without notice. 9 3/8" 2 1/2" 10" MIM-B17N 1 of 3 Samsung DVM S Series, BACnet Gateway QS-DVMS-102016A

Transcript of SUBMITTAL MIM-B17N Page Samsung DVM S Series, …€¦ · Specifications • MIM-B17N fixed port...

Page 1: SUBMITTAL MIM-B17N Page Samsung DVM S Series, …€¦ · Specifications • MIM-B17N fixed port number: 47808 (cannot be modified) • MIM-B17N network ID can be assigned 1-16 (this

Job Name LocationPurchaser EngineerSubmitted to Reference Approval ConstructionUnit Designation Schedule #

Schedule Control Function Through Web Browser• Up to 256 schedule settings• Weekly and daily schedule setting• Wireless/wired remote controller restriction setting• Digital outputs can be incorporated into scheduling

External Contact Interface• Full indoor unit control with simple contact input (emergency/lock)• 8 additional digital input terminals for monitoring options• State output (operation/error) for synchronous control• 6 general purpose outputs to control other components (on: 12VDC out; off: no voltage)• Digital inputs and digital outputs can be incorporated into control logic.• Digital outputs can be incorporated into daily schedules to control other devices

Energy Management / Power Distribution Function• The ability to monitor, track, and query energy use from indoor unit(s) and systems with MIM-B16 or MIM-B16N ElectricityMeter Interface Module (purchased separately, requires 3rd party watt-hour meters with pulse output).• When used with SNET 3 software, detailed report generation is possible• User defined daily time periods for energy use reports to accommodate on/off peak energy billing.

History Management• Storage of all operation commands from gateway and other system controls (saves to SD card purchased separately).• Storage of all error events for review (saves to SD card purchased separately).• Storage of all operation logic control events (saves to SD card purchased separately).• Error alerts via email that contain: error code, error explanation, units affected, time and date of error occurrence, and error status.

Features

BACnet Gateway• Control gateway that allows control and monitoring of Samsung HVAC systems viaBACnet /IP

Easy Control & Monitoring Through Web Browser• Individual/Group control of up to 256 indoor units including• Operation mode, temperature setting, airflow direction and fan speed.• Restriction on use of wireless/wired remote controllers, mode, temperature, and set point.• Outdoor and indoor unit cycle monitoring• Convenient digital display allows for easy set up• SD memory card slot for data storage and software updating (daily automatic backup, SDcard purchased separately)• LAN connection for upper level control options• Available sophisticated control logic allows programming outputs based on various systeminputs• Dynamic security management• Operation and error history management• Maximum current control of outdoor unit(s) to limit current (50% - 100% of design current)adjustable at outdoor unit or MIM-B17N.

Web Server Function• Remote control with a public IP address via internet connection• No management software required – PC-independent management through web browser(optimized for Internet Explorer)• Multiple user accounts can be setup with the ability to specify what unit(s) each individualcan monitor and control and what level of control permission is allowed.

SUBMITTAL Page

www.SamsungHVAC.com888-699-6067

Samsung HVAC maintains a policy of ongoing development,specifications are subject to change without notice.

9 3/8" 2 1/2"

10"

MIM-B17N 1 of 3

Samsung DVM S Series, BACnet Gateway

QS-DVMS-102016A

Page 2: SUBMITTAL MIM-B17N Page Samsung DVM S Series, …€¦ · Specifications • MIM-B17N fixed port number: 47808 (cannot be modified) • MIM-B17N network ID can be assigned 1-16 (this

Specifications

• MIM-B17N fixed port number: 47808 (cannot be modified)

• MIM-B17N network ID can be assigned 1-16 (this number will determine device ID of gateway and all equipment)

• MIM-B17N shall support BCAnet/IP and provide functions to monitor status and control Samsung DVM S (AM***F****/AA), CAC (AC0****CH/AA,and FJM (AJ0******CH/AA, with MIM-N01 Interface Module) systems.

• MIM-B17N shall monitor status and control Samsung DVM S (AM***F****/AA), CAC (AC0****CH/AA, and FJM (AJ0******CH/AA, with MIM-N01Interface Module) systems via web client and/or Samsung SNET 3 software.

• Connection of DVM Plus III equipment or earlier models will require a communication interface module adapter

• DC 12V, 3A power provided by AC/DC adapter (input 110-240VAC 50/60Hz, provided with MIM-B17N)

• Communication connection ON/OFF Controller(s) (MCM-A202DN) and direct connection to DVM S series outdoor units

• 16 AWG X 2 shielded cable between Samsung equipment and controls is necessary for proper operation

• Maximum number of RS485 connections:- Maximum 75 ON/OFF Controllers (MCM-A202DN) to 1 MIM-B17N- Maximum 15 ON/OFF Controllers (MCM-A202DN)- Maximum 16 DVM S Series outdoor units to a single channel (5 total)- Maximum 80 DVM S systems connected direct (5 ports, 16 systems per port), 256 through ON/OFF Controllers (MCM-A202DN)- Maximum 128 indoor units on a single MIM-B17N channel- Maximum 256 indoor units (air handlers & Samsung ERV's) to one MIM-B17N- Maximum 8 MIM-B16 Energy Meter Interface Modules per MIM-B17N- Maximum 32 MIM-B16N (available late 201 ) Energy Meter Interface Modules per MIM-B17N

• Digital inputs and outputs:- DI terminals (X 10): 12VDC, maximum 10 mA- DO terminals (X 8): 12VDC, maximum 200 mA

• Segment capability- Segment requests supported window size: 1476- Segment responses supported window size: 1476

DS-RP-B Data Sharing-ReadProperty-BDS-RPM-B Data Sharing-ReadPropertyMultiple-BDS-WP-B Data Sharing-WriteProperty-BDS-WPM-B Data Sharing-WritePropertyMultiple-BDS-COV-B Data Sharing-COV-B

DM-DDB-B Dynamic Device Binding-BDM-DOB-B Dynamic Object Binding-BDM-TS-B Time Synchronization-B

Object Types*

Analog Input

Analog Output

Binary Input

Binary Output

Device

Indoor temperature, lower limit temperature, upper limit temperature, electric value after baseline, indoor usage after baseline, electric value within the period, electric value within period, indoor unit error code, centralized controller error code, interface module error code, SIM interface module error code, gateway status, gateway error code, current discharge air temperature

*Some objects listed are only not available for all models of equipment.

Description

BACnet Protocol Implementation Conformance

Standard Object Types

Data Sharing

Device and Network Management

Multi-state Input Operation mode status, fan speed status, air direction status, cooling only/heating only/restriction cancelation status, control allowing/stopping remote control/level 1

Multi-state Output Control Operation mode, control fan speed, control air flow direction, setting cooling only/heating only/restriction cancelation, control allowing/stopping remote control/level 1

Set temperature, setting lower limit temperature, setting upper limit temperature, discharge cooling setting temperature, discharge heating setting temperature

Power on/off status, filter alert status, lower limit function toggle status, upper limit function toggle status, "Digital Input"

DMS2.0, Samsung DVM S A/C indoor unit, Samsung ERV, SIM, ON/OFF Controller (MCM-A202DN), Interface Module Communication Converter, DMS2.0 DI/DO

Power on/off control, filter reset control, setting lower limit function toggle status, setting upper limit function toggle status, "Digital Output"

www.SamsungHVAC.com

SUBMITTAL Page

Samsung HVAC maintains a policy of ongoing development,specifications are subject to change without notice.

MIM-B17N 2 of 3

Samsung DVM S Series, BACnet Gateway

Page 3: SUBMITTAL MIM-B17N Page Samsung DVM S Series, …€¦ · Specifications • MIM-B17N fixed port number: 47808 (cannot be modified) • MIM-B17N network ID can be assigned 1-16 (this

F1 F2 R1 R2

F1F2

R1

R2

0 0

1 1

F F

www.SamsungHVAC.com

SUBMITTAL Page

MIM-B17N

R1/R

2R1

/R2

R1/R

2R1

/R2

R1/R

2

R1/R

2

R1/R

2R1

/R2

F1/F2

F1/F2

F1/F2R1/R2

R1/R2

R1/R2

Electrical Panel

Watt-hour Meter

Watt-hour

R1/R2

R1/R2

MIM-B17N (BOTTOM)

MCM-A202DN (ON/OFF Controller)

DVM S Outdoor Unit

DVM S Outdoor Unit

DVM S Outdoor Unit

DVM S Outdoor Unit

DVM S Outdoor Unit

DVM S Outdoor Unit DVM S Outdoor Unit

DVM S Outdoor Unit

Installation with MIM-B16 / MIM-B16N - Energy Management

Installation with Direct Connection to DVM S Outdoor Units

Installation with Centralized Controller and Direct Outdoor Connection

LAN Web Browser or SNET 3

Web Browser or SNET 3

Maximum 16 per MIM-B17N channel

Maximum 16 per MIM-B17N channel

DMS-2.0

R1/R2

R1/R2

Maximum 16

Maximum15 Systems per ON/OFF Controller

Maximum15 Systems per ON/OFF Controller

Maximum 16 CentralizedControllers per MIM-B17N

Samsung HVAC maintains a policy of ongoing development,specifications are subject to change without notice.The diagrams on this page are for reference only. Refer to installation manual for wiring and installation instructions. Other configurations may be possible.

Pulse Input Module

MCM-A202DN (ON/OFF Controller)

MCM-A202DN (ON/OFF Controller)

per MIM-B17N channel

BMS

MIM-B17N 3 of 3

Samsung DVM S Series, BACnet Gateway