SUBMITTAL DATA: PCA-A42KA7 & PUY-A42NKA7(-BS) · Model Number Indoor Unit PCA-A42KA7 Outdoor Unit...

8
Job Name: System Reference: Date: Indoor Unit: PCA-A42KA7 Outdoor Unit: PUY-A42NKA7 PUY-A42NKA7-BS INDOOR UNIT FEATURES Airflow settings for high and low ceiling applications Knock-out for outside-air intake Optional i-see Sensor TM for air distribution and energy saving Auto fan speed mode Filter status indicator Easy-to-clean, washable filter Suspends from ceiling for quick and easy installation Ideal for larger retail stores, classrooms, and restaurants OUTDOOR UNIT FEATURES Variable speed INVERTER-driven compressor Power receiver pre-charged with refrigerant volume for piping length up to 100 ft (70 ft. for A12/18/24/30) Low ambient cooling down to -40ºF providing 100% capacity (only for PUY models with wind baffles installed) 24-hour continuous operation (cooling mode) High pressure protection Fast restarts in cooling mode (15 seconds for 12/18/36/42; 50 seconds for 24/30) Superior energy and operational efficiency SUBMITTAL DATA: PCA-A42KA7 & PUY-A42NKA7(-BS) 42,000 BTU/H CEILING-SUSPENDED AIR-CONDITIONING SYSTEM Specifications are subject to change without notice. © 2018 Mitsubishi Electric Trane HVAC US LLC. All rights reserved. P-SERIES

Transcript of SUBMITTAL DATA: PCA-A42KA7 & PUY-A42NKA7(-BS) · Model Number Indoor Unit PCA-A42KA7 Outdoor Unit...

Page 1: SUBMITTAL DATA: PCA-A42KA7 & PUY-A42NKA7(-BS) · Model Number Indoor Unit PCA-A42KA7 Outdoor Unit PUY-A42NKA7 PUY-A42NKA7-BS Indoor Unit Operating Temperature Range Cooling Intake

Job Name:

System Reference: Date:

Indoor Unit:PCA-A42KA7

Outdoor Unit:□ PUY-A42NKA7□ PUY-A42NKA7-BS

INDOOR UNIT FEATURES• Airflow settings for high and low ceiling applications• Knock-out for outside-air intake• Optional i-see SensorTM for air distribution and energy saving• Auto fan speed mode• Filter status indicator• Easy-to-clean, washable filter• Suspends from ceiling for quick and easy installation• Ideal for larger retail stores, classrooms, and restaurants

OUTDOOR UNIT FEATURES• Variable speed INVERTER-driven compressor• Power receiver pre-charged with refrigerant volume for piping length up to 100 ft (70 ft. for A12/18/24/30)• Low ambient cooling down to -40ºF providing 100% capacity (only for PUY models with wind baffles installed)• 24-hour continuous operation (cooling mode)• High pressure protection• Fast restarts in cooling mode (15 seconds for 12/18/36/42; 50 seconds for 24/30)• Superior energy and operational efficiency

SUBMITTAL DATA: PCA-A42KA7 & PUY-A42NKA7(-BS)42,000 BTU/H CEILING-SUSPENDED AIR-CONDITIONING SYSTEM

Specifications are subject to change without notice. © 2018 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.

P-SERIES

Page 2: SUBMITTAL DATA: PCA-A42KA7 & PUY-A42NKA7(-BS) · Model Number Indoor Unit PCA-A42KA7 Outdoor Unit PUY-A42NKA7 PUY-A42NKA7-BS Indoor Unit Operating Temperature Range Cooling Intake

Model Number

Indoor Unit PCA-A42KA7

Outdoor UnitPUY-A42NKA7

PUY-A42NKA7-BS

Cooling1

Maximum Capacity Btu/h 42,000

Rated Capacity Btu/h 42,000

Minimum Capacity Btu/h 16,000

Maximum Power Input W 4,110

Rated Power Input W 4,110

Moisture Removal Pints/h 11.70

Sensible Heat Factor 0.69

Power Factor % 95.60

EfficiencySEER 17.60

EER1 10.20

Electrical

Voltage, Phase, Frequency 208 / 230V, 1-phase, 60 Hz

Guaranteed Voltage Range V AC 198 – 253

Voltage: Indoor - Outdoor, S1-S2 V AC 208 / 230

Voltage: Indoor - Outdoor, S2-S3 V DC 24

Voltage: Indoor - Remote controller V DC 12

Recommended Fuse/Breaker Size A 30

Recommended Wire Size (Indoor - Outdoor) AWG 14

Indoor Unit

MCA A 2.00

MOCP A 15.00

Fan Motor Full Load Amperage A 0.97

Fan Motor Output W 160

Airflow Rate, Dry CFM 810-885-955-1025

Airflow Rate, Wet CFM 740-810-885-955

External Static Pressure in.WG n/a

Sound Pressure Level dB(A) 39-41-43-45

Drain Pipe Size In. (mm) 1-1/32 (26)

Condensate Lift Mechanism, Max. Distance In. (mm) n/a

Heat Exchanger Type Plate fin coil

External Finish Color White Munsell 6.4Y 8.9/0.4

Unit Dimensions

W: In. (mm) 63 (1600)

D: In. (mm) 26-3/4 (680)

H: In. (mm) 9-1/16 (230)

Package Dimensions

W: In. 53-2/16

D: In. 29-15/16

H: In. 13-12/16

Unit Weight Lbs. (kg) 86 (39)

Package Weight Lbs. 102

SPECIFICATIONS: PCA-A42KA7 & PUY-A42NKA7(-BS)

Specifications are subject to change without notice. © 2018 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.

Page 3: SUBMITTAL DATA: PCA-A42KA7 & PUY-A42NKA7(-BS) · Model Number Indoor Unit PCA-A42KA7 Outdoor Unit PUY-A42NKA7 PUY-A42NKA7-BS Indoor Unit Operating Temperature Range Cooling Intake

Model Number

Indoor Unit PCA-A42KA7

Outdoor UnitPUY-A42NKA7

PUY-A42NKA7-BS

Indoor Unit OperatingTemperature Range

Cooling Intake Air Temp (Maximum / Minimum) °F 90 DB, 73 WB / 66 DB, 59 WB

Outdoor Unit

MCA A 25

MOCP A 31

Fan Motor Full Load Amperage A 0.5 + 0.5

Fan Motor Output W 74 + 74

Airflow Rate CFM 3,880

Refrigerant Control Electronic Expansion Valve

Heat Exchanger Type Cross fin

Sound Pressure Level, Cooling1 dB(A) 52

Compressor Type INVERTER-driven twin rotary

Compressor Model MNB33FBRMC-L

Compressor Rated Load Amps A 8

Compressor Locked Rotor Amps A 13

Compressor Oil Type // Charge oz. FV50S // 45

External Finish Color Ivory Munsell 3Y 7.8/1.1

Base Pan Heater n/a

Unit Dimensions

W: In. (mm) 41-5/16 (1050)

D: In. (mm) 13+1-3/16 (330 + 30)

H: In. (mm) 52-11/16 (1338 )

Package Dimensions

W: In. 42-15/16

D: In. 17-11/16

H: In. 56-4/16

Unit Weight Lbs. (kg) 211 (96)

Package Weight Lbs. (kg) 243 (110)

Outdoor Unit OperatingTemperature Range

Cooling Intake Air Temp (Maximum / Minimum) °F 115 DB / -40* DB

RefrigerantType R410A

Charge Lbs, oz 10 lbs, 6 oz

Piping

Gas Pipe Size O.D. (Flared) In.(mm) 5/8 (15.88)

Liquid Pipe Size O.D. (Flared) In.(mm) 3/8 (9.52)

Maximum Piping Length Ft. (m) 225 (69)

Maximum Height Difference Ft. (m) 100 (30)

Maximum Number of Bends 15

SPECIFICATIONS: PCA-A42KA7 & PUY-A42NKA7(-BS)

Specifications are subject to change without notice. © 2018 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.

Page 4: SUBMITTAL DATA: PCA-A42KA7 & PUY-A42NKA7(-BS) · Model Number Indoor Unit PCA-A42KA7 Outdoor Unit PUY-A42NKA7 PUY-A42NKA7-BS Indoor Unit Operating Temperature Range Cooling Intake

Notes

AHRI Rated Conditions (Rated data isdetermined at a fixed compressorspeed)

1Cooling (Indoor // Outdoor) °F 80 DB, 67 WB // 95 DB, 75 WB

*Wind baffles required to operate below 23F DB in cooling mode. For PUY models, wind baffles can be utilized to extend the cooling operation range to-40F. Please refer to the wind baffle submittals to determine which baffles are required to meet the desired operation range.**System cuts out in heating mode to avoid thermistor error and automatically restarts at these temperatures.

SEACOAST PROTECTION• External Outer Panel: Phosphate coating + Acrylic-Enamel coating• Fan Motor Support: Epoxy resin coating (at edge face)• Separator Assembly; Valve Bed: Epoxy resin coating (at edge face)• “Blue Fin” treatment is an anti-corrosion treatment that is applied to the condenser coil to protect it against airborne contaminants.

SPECIFICATIONS: PCA-A42KA7 & PUY-A42NKA7(-BS)

Specifications are subject to change without notice. © 2018 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.

Page 5: SUBMITTAL DATA: PCA-A42KA7 & PUY-A42NKA7(-BS) · Model Number Indoor Unit PCA-A42KA7 Outdoor Unit PUY-A42NKA7 PUY-A42NKA7-BS Indoor Unit Operating Temperature Range Cooling Intake

High Efficiency (MERV 8) Filter Element □ PAC-SE81KF-E

High-efficiency Filter Element □ PAC-SH90KF-E

Signal Receiver □ PAR-SA9CA-E

Wireless Remote Controller □ PAR-FL32MA-E

Wireless Remote Receiver □ PAR-FA32MA-E

Controller Kit (Sender & Receiver) □ PAR-SL93B-E

Controller Kit with i-see Sensor □ PAR-SA92MW-E

Backlit, Wall-mounted, Wireless Controller □ MHK1

Portable Central Controller □ MCCH1

Wired MA Controller □ PAR-33MAA

Simple MA Controller □ PAC-YT53CRAU

Touch MA Controller □ PAR-CT01MAU-SB

Lockdown Bracket for Wireless, Hand-held, Remote Controller □ RCMKP1CB

Wireless Temperature and Humidity Sensor □ PAC-USWHS003-TH-1

Outside Air Sensor for MHK1 □ MOS1

Flush Mount Remote Temperature Sensor □ PAC-USSEN001-FM-1

Wireless Interface □ PAC-USWHS002-WF-1

Thermostat Interface □ PAC-US444CN-1

kumo station® □ PAC-WHS01HC-E

USNAP Interface □ PAC-WHS01UP-E

IT Extender □ PAC-WHS01IE-E

BACnet® and MODBUS® Interface □ PAC-UKPRC001-CN-1

External Fan / Heater Control Relay Adapter □ CN24RELAY-KIT-CM3

Remote Operation Adapter (with wire terminals for remote ON/OFF and operation status/ error)1 □ PAC-SF40RM-E

i-see Sensor™ □ PAC-SH91MK-E

External Drain Pump □ PAC-SH84DM-E

Blue Diamond Sensor Extension Cable—15 Ft. □ C13-103

MegaBlue Advanced Blue Diamond Condensate Pump w/ Reservoir & Sensor □ X87-835 - 110 to 250V

MaxiBlue Advanced Blue Diamond Mini Condensate Pump w/ Reservoir & Sensor (208/230V) up to 48,000 Btu/h[recommended]

□ X87-721 - 208/230V

Drain Pan Level Sensor (Control for indoor unit shut off to prevent drain pan overflow) □ DPLS2

3 Pole Disconnect Switch (30A/600VUL) [fits 2"X4" utility] - Black □ TAZ-MS303

3 Pole Disconnect Switch (30A/600VUL) [fits 2"X4" utility] - White □ TAZ-MS303W1 Unable to use with wireless remote controller

ACCESSORIES: PCA-A42KA7

Specifications are subject to change without notice. © 2018 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.

Page 6: SUBMITTAL DATA: PCA-A42KA7 & PUY-A42NKA7(-BS) · Model Number Indoor Unit PCA-A42KA7 Outdoor Unit PUY-A42NKA7 PUY-A42NKA7-BS Indoor Unit Operating Temperature Range Cooling Intake

Air Outlet Guide □ PAC-SH96SG-E (two pieces arerequired)

Front Wind Baffle □ WB-PA3 (two pieces arerequired)

Side Advanced Wind Baffle □ WB-SD6

Rear Advanced Wind Baffle □ WB-RE6

Drain Socket □ PAC-SG61DS-E

M-NET Converter □ PAC-SF83MA-E

M-NET Converter □ PAC-SJ95MA-E

Control/Service Tool □ PAC-SK52ST

Condensing Unit Mounting Pad 24" x 42" x 3" □ ULTRILITE2

Outdoor Unit Stand—12" High □ QSMS1202M

Outdoor Unit Stand—18" High □ QSMS1802M

Outdoor Unit Stand—24"High □ QSMS2402M

Heavy Duty Wall Mounting Bracket for Outdoor Units—Coated Steel □ QSWB2000M-1

Heavy Duty Wall Mounting Bracket for Outdoor Units—316 Series Stainless Steel □ QSWBSS

3/8" x 5/8" x 10' / 1/2" Lineset (Twin-Tube Insulation) □ MPLS385812T-10

3/8" x 5/8" x 15' / 1/2" Lineset (Twin-Tube Insulation) □ MPLS385812T-15

3/8" x 5/8" x 30' / 1/2" Lineset (Twin-Tube Insulation) □ MPLS385812T-30

3/8" x 5/8" x 50' / 1/2" Lineset (Twin-Tube Insulation) □ MPLS385812T-50

3/8" x 5/8" x 65' / 1/2" Lineset (Twin-Tube Insulation) □ MPLS385812T-65

3/8" x 5/8" x 100' / 1/2" Lineset (Twin-Tube Insulation) □ MPLS385812T-100

ACCESSORIES: PUY-A42NKA7(-BS)

Specifications are subject to change without notice. © 2018 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.

Page 7: SUBMITTAL DATA: PCA-A42KA7 & PUY-A42NKA7(-BS) · Model Number Indoor Unit PCA-A42KA7 Outdoor Unit PUY-A42NKA7 PUY-A42NKA7-BS Indoor Unit Operating Temperature Range Cooling Intake

PCA-A42KA7

15

When drain socket is installed

9-3/16(233)

When drain socket is installed

Drainage9-11/16(246)

14

NOTES.1.Use M10 or W3/8 screw for anchor bolt.2.Please be sure when installing the drain pump (option parts),

refrigerant pipe will be only upward.

6

8026

-3/4

(680

)

12-5

/8(3

20)

61-5/16(1557) (Suspension bolt pitch)

11/1

6(18

)

140

62

5-7/

8(15

0) 2-7/165-1/2

3-1/8

Air outlet

58-3/4(1493)

1/16(2) 63(1600)

9-1/

16(2

30)

7-11

/16(

195)

3-7/

16(8

8)3-

5/16

(84)

[FRONT VIEW] 51

1-7/8(48)5/16(8)

9-3/16(233)

1-13

/16(

46)

18-1/8(461)

4-7/

8(12

4)3(7

6)

7-1/

2(19

0)

Φ4-1

5/16(

Φ125

)

4-3/

4(12

1) 11/16(18)

3 Electrical boxCeiling

8In case of the rear pipe arrangement, make sure to remove the shaded portions from the independent piece.Then put the independent piece back in initialposition.(The heat exchanger might be clogged because of dust)

4-15

/16(

126)

5-7/16(138)

1-7/

16(3

7)

7-1/

2(19

0)

1/16

(1)

10-1/4(260)

1/16(2)

When electrical boxis pulled down

2-15/16(75)

21-1/2(38)

7

4

3-3/8(85)

3-3/8(86)

15-1/4(387)

2

Electrical box

Air intake59-3/4(1518)

26-3

/4(6

80)

18-3

/4(4

76)

57

182 857-3/16 3-3/8

2-1/

4

In case of wireless remote controllerand i-see sensor(Optional Parts)

Emergency operation switch <Heating>

Operation lampReceiver

Emergency operation switch <Cooling>

DEFROST/STAND BY lamp

9-5/

16(2

36)

liquid Φ3/8(Φ9.52)gas Φ5/8(Φ15.88)

Drainage

7-7/8(200)

9-11/16(246)

2(51)3/8(10)3/16(5)

9/16

In case of wireless remote controllerand i-see sensor(Optional Parts)

1/16(2)

1

120°

2-15/16(75)

10(2

54)

7-1/16(180)

Knockout hole for upper drain pipe arrangementKnockout hole for fresh air intake Φ3-15/16(Φ100)Knockout hole for wiring arrangement Φ7/8(Φ22)Accessory...Drain socket (1(26mm)I.D.)

Drainage pipe connection(1(26mm)I.D.)Drainage pipe connection(for the left arrangement)Knockout hole for left drain-piping arrangementRefrigerant-pipe connection(gas pipe side/flared connection)Refrigerant-pipe connection(liquid pipe side/flared connection)

876

5

43211

Unit: in (mm)

DIMENSIONS: PCA-A42KA7 & PUY-A42NHA7 (-BS)

Specifications are subject to change without notice. © 2018 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.

Page 8: SUBMITTAL DATA: PCA-A42KA7 & PUY-A42NKA7(-BS) · Model Number Indoor Unit PCA-A42KA7 Outdoor Unit PUY-A42NKA7 PUY-A42NKA7-BS Indoor Unit Operating Temperature Range Cooling Intake

PUY-A42NKA7(-BS)

16

PUZ-A

36NK

A7

PUZ-A

42NK

A7

PUY-A

36NK

A7

PUY-A

42NK

A7

PUZ-A

36NK

A7-B

S PU

Z-A42N

KA

7-BS

PUY-A

36NK

A7-B

S PU

Y-A42N

KA

7-BS

Bottom piping hole(Knockout)

Drain hole(5-ø33<1-5/16>)

154

<6-1

/16>

136

<5-1

1/32

>

81 <3-3/16>

45 <1-25/32>

110 <14-11/32>160

<6-5/16>160

<6-5/16>160

<6-5/16>

86<3

-3/8

>

Rear Air Intake

Handle for moving

Handle for moving

Side Air Intake

12

Handle for moving

Handle for moving

Service panel

Earth terminal Terminal connectionLeft ... Power supply wiringRight ... Indoor/Outdoor wiring

*1 4

42<1

7-2/

5>

1063

<41-

7/8>

632

<24-

7/8>

*1 4

50<1

7-23

/32>

26<1

-1/3

2>36

9<1

4-17

/32>

1338

<52-

11/1

6>

362 <14-1/4>1050 <41-11/32>

Air intake

Front piping cover

Rear piping cover

2-12×36 Oval holes(Foundation Bolt M10<W3/8>)

Installation Feet

2-U Shaped notched holes(Foundation Bolt M10<W3/8>)

225 <8-27/32>

42 <1-21/32>60 <2-3/8>

25<3

1/32

>33

0<1

3>

225 <8-27/32>600 <23-5/8>

70 <2-3/4>

417

<16-

13/3

2>

28<1

-3/3

2>37

0<1

4-9/

16>

19<3

/4>

40 <1-9/16> 53 <2-3/32>

56 <2-7/32>

0

Conduit hole(ø 24<15/16>knockout)

Conduit hole(ø 37<1-15/32>knockout)

Rear trunking hole(Knockout)

Rear piping hole(Knockout)

75 <2-15/16>

92 <3-5/8>

73<2

-7/8

>60

<2-3

/8>

5<3/

16>

26<1

-1/3

2>

27<1

-1/1

6>55

<2-3

/16>

55 <2-3/16> 60 <2-3/8>

ø 92<3-5/8>

Conduit hole(ø 24<15/16>knockout)

Front piping hole(Knockout)

Front trunking hole(Knockout)

Conduit hole(ø 37<1-15/32>knockout)

26<1

-1/3

2>

92 <3-5/8> 27<1

-1/1

6>55

<2-3

/16>

73<2

-7/8

>

75 <2-15/16>

55 <2-3/16>60 <2-3/8>

ø 92<3-5/8>

Right trunking hole(Knockout)

Conduit hole(ø 37<1-15/32>knockout)

Conduit hole(ø 24<15/16>knockout)

Right piping hole(Knockout)

73<2

-7/8

>61

<2-3

/8>

5<3/

16>

29 <1-5/32>

27<1

-1/1

6>26

<1-1

/32>

92<3

-5/8

>

53 <2-3/32> 60 <2-3/8>

55 <2-3/16>

92 <3-5/8>

ø 92<3-5/8>

Min.

Min.

Min.

Min.

Service space Min.

150

<5-2

9/32

>50

0<1

9-11

/16>

500<19-11/16>

15 <3/5>

50<2> Ma

x.30

<1-3

/16>

( )

21 ... Refrigerant GAS pipe connection (FLARE) ø15.88(5/8F)

... Refrigerant LIQUID pipe connection (FLARE) ø9.52(3/8F)

*1 ... Indication of STOP VALVE connection location.

Piping Knockout Hole Details

Example of Notes

FREE

Min. 15mm<3/5>

Min. 15mm<3/5>

Min. 1000mm<39-3/8>

Min. 150mm<5-29/32>

Piping and wiring connectionscan be made from 4 directions:FRONT, Right, Rear and Below.

4 PIPING-WIRING DIRECTIONS3 FOUNDATION BOLTS2 SERVICE SPACE1 FREE SPACE (Around the unit)Please secure the unit firmlywith 4 foundation (M10<W3/8>) bolts.(Bolts and washers must be purchased locally.)

Dimensions of space neededfor service access areshown in the below diagram.

The diagram below shows a basic example.Explantion of particular details aregiven in the installation manuals etc.

<Foundation bolt height>

Air Discharge

Rear Air Intake

Side Air Intake

1/2 Conduitattachment

ø 22.2<7/8>ø 27.8<1-3/32>

When installing the conduit.Set the attachment to the inner side of each panel.

3/4 Conduitattachment

Scale 1:5

60 <2-3/8> 22.5 <7/8>

5<3/

16>

24.7

<31/

32>

100<3-15/16>

FOUNDATION

OC

H636

Unit: mm<in>

FORM# PCA-A42KA7 / PUY-A42NKA7(-BS) - 201810

1340 Satellite Boulevard, Suwanee, GA 30024Toll Free: 800-433-4822 www.mehvac.com

DIMENSIONS: PCA-A42KA7 & PUY-A42NHA7 (-BS)

Specifications are subject to change without notice. © 2018 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.