ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com. *LC377* LC377 Tranquility ® 20 High Efficiency ( TS ) Series Submittal Data Models TSD/H/V 006-070 60Hz - HFC-410A Rev.: May 26, 2020

Transcript of Submittal Data - Climate Master · The award winning Tranquility® Series raises the bar for...

Page 1: Submittal Data - Climate Master · The award winning Tranquility® Series raises the bar for water-source heat pump efficiencies, features and application flexibility. Not only does

ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.

*LC377* LC377

Tranquility® 20 High Efficiency (TS) SeriesSubmittal DataModels TSD/H/V 006-070 60Hz - HFC-410A

Rev.: May 26, 2020

Page 2: Submittal Data - Climate Master · The award winning Tranquility® Series raises the bar for water-source heat pump efficiencies, features and application flexibility. Not only does

ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.

Page ______ of ______LC377 - 2

Unit Features 4Selection Procedure 5

TS Series Nomenclature 7Performance Data – AHRI/ASHRAE/ISO 13256-1 8

Performance Data – Selection Notes 9Performance Data – TSH/V006 (PSC Blower) 10Performance Data – TSH/V009 (PSC Blower) 11Performance Data – TSH/V012 (PSC Blower) 12

Performance Data – TSH/V/D018 (PSC Blower) 13Performance Data – TSH/V/D018 (ECM Blower) 14Performance Data – TSH/V/D024 (PSC Blower) 15Performance Data – TSH/V/D024 (ECM Blower) 16Performance Data – TSH/V/D030 (PSC Blower) 17Performance Data – TSH/V/D030 (ECM Blower) 18Performance Data – TSH/V/D036 (PSC Blower) 19Performance Data – TSH/V/D036 (ECM Blower) 20Performance Data – TSH/V/D042 (PSC Blower) 21Performance Data – TSH/V/D042 (ECM Blower) 22Performance Data – TSH/V/D048 (PSC Blower) 23Performance Data – TSH/V/D048 (ECM Blower) 24Performance Data – TSH/V/D060 (PSC Blower) 25Performance Data – TSH/V/D060 (ECM Blower) 26Performance Data – TSH/V/D070 (PSC Blower) 27Performance Data – TSH/V/D070 (ECM Blower) 28

Performance Correction Tables 29Antifreeze Correction Table 30

Correction Tables - Water Pressure Drop Adder for Options 32Blower Performance Data – Standard Unit - No Reheat (PSC Motor) 33

Blower Performance Data – Units with ClimaDry® (PSC Motor) 34ECM Control 35

ECM Control Diagram 37Blower Performance Data – (ECM Motor) - Standard Unit - No Reheat 38

ClimaDry® II Option - Benefits and Application 39ClimaDry® II Option - Sequence of Operation 41

Physical Data 43

Table of Contents

TS High Efficiency Series

Document page number is shown next to part number (e.g. LC377 - 3 = page 3). Since not all pages are typically used in the submittals process, the page number in the lower right corner can still be used (page ____of_____).

Page 3: Submittal Data - Climate Master · The award winning Tranquility® Series raises the bar for water-source heat pump efficiencies, features and application flexibility. Not only does

ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.

Page ______ of ______LC377 - 3

Table of Contents

TS High Efficiency SeriesTS - Horizontal – Dimensional Data 44

TS - Horizontal Service Access 46TS - Vertical Upflow – Dimensional Data 47

TS - Vertical Service Access 49TS - Vertical Downflow – Dimensional Data 50

Corner Weights for TSH Series Units 52Electrical Data – PSC Motor & ClimaDry® 53

Electrical Data – High Static PSC Motor & ClimaDry® 54Electrical Data – ECM Motor & ClimaDry® 55

Electrical Data – PSC Motor & Secondary Pump 56Electrical Data – High Static PSC Motor & Secondary Pump 57

Electrical Data – ECM Motor & Secondary Pump 58TS Series Wiring Diagram Matrix 59

Typical Wiring Diagram – Single Phase TS Units with CXM Controller 60Typical Wiring Diagram – Three Phase TS Units with DXM2 Controller 61

Typical Wiring Diagram – Three Phase TS Units with CXM Controller and ECM Blower 62Typical Wiring Diagram – Single Phase TS Units with DXM2, MPC, and ECM Controller 63

Typical Wiring Diagram – Single Phase TS Units with ClimaDry® II and ECM Blower 64Engineering Specifications 65

Performance Sheet 75Revision Log 77

Page 4: Submittal Data - Climate Master · The award winning Tranquility® Series raises the bar for water-source heat pump efficiencies, features and application flexibility. Not only does

ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.

Page ______ of ______LC377 - 4

Unit Features

THE TranquiliTy® 20SinGlE-STaGE (TS) SEriES

The award winning Tranquility® Series raises the bar for water-source heat pump efficiencies, features and application flexibility. Not only does the Tranquility 20 far exceed ASHRAE 90.1 efficiencies, but it also uses EarthPure® (HFC-410A) zero ozone depletion refrigerant, making it an extremely environmentally-friendly option. Tranquility 20 is eligible for additional LEED® (Leadership in Energy and Environmental Design) points because of the “green” technology design.

Available in sizes 1/2 tons (1.76 kW) through 6 tons (21.1 kW) with multiple cabinet options (vertical upflow, vertical downflow and horizontal) the Tranquility 20 offers a wide range of units for most any installation. The Tranquility 20 has an extended range refrigerant circuit, capable of ground loop (geothermal) applications as well as water loop (boiler-tower) applications. Standard features are many. Copeland scroll compressors, microprocessor controls, galvanized steel cabinet, polyester powder coat paint, stainless steel drain pan and foil-backed air handler insulation are just some of the features of the Tranquility 20 Series.

ClimateMaster’s exclusive double isolation compressor mounting system makes the Tranquility 20 the quietest unit on the market. Compressors are mounted on specially engineered sound tested EPDM grommets to a heavy gauge mounting plate, which is then isolated from the cabinet base with rubber grommets for maximized vibration/sound attenuation. The unique low profile slanted control box makes installing and maintaining the unit easier than any other water-source heat pump currently in production.

Options such as ECM variable speed fan motor, coated air coil, DDC controls, internal pump and high efficiency MERV 11 two-inch (51mm) air filters allow customized design solutions. Optional high static fan motors help overcome some of the challenges associated with ductwork for retrofit installations.

The Tranquility 20 (TS) Series Water-Source Heat Pumpsare designed to meet the challenges of today’s HVAC demands with one of the most innovative productsavailable on the market.

uniT FEaTurES• Sizes 006 (1/2 ton, 1.76 kW) through 070 (6 tons,

21.1 kW)• EarthPure® (HFC-410A) refrigerant• Exceeds ASHRAE 90.1 efficiencies• Galvanized steel construction with attractive black matte

polyester powder coat paint• Stainless steel drain pan• Foil-backed insulation in air handler section• Unique double isolation compressor mounting with

vibration isolation for quiet operation• Insulated divider and separate compressor/air

handler compartments• Copeland scroll compressors• TXV metering device • Extended range (20 to 120°F, -6.7 to 48.9°C) operation• Microprocessor controls standard (optional DXM2 and/or

DDC controls)• LonWorks, BACnet, Modbus and Johnson N2

compatibility options for DDC controls• Field convertible discharge air arrangement for

horizontal units• High static blowers available• ECM variable speed fan motor available• Low profile slanted control box for easy access• Flush securely-mounted corner post water connections

(no backup wrench required)• Unit Performance Sentinel performance

monitoring system• Eight Safeties Standard• Wide variety of options including ClimaDry® modulating

reheat, coated air coils and internal pumps

Page 5: Submittal Data - Climate Master · The award winning Tranquility® Series raises the bar for water-source heat pump efficiencies, features and application flexibility. Not only does

ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.

Page ______ of ______LC377 - 5

Selection Procedure

Reference Calculations

LWT = EWT -HE

GPM x 500

LAT = EAT +HC

CFM x1.08

LWT = EWT +HR

GPM x 500

LAT (DB) = EAT (DB) - SCCFM x1.08

LC = TC - SC

S/T =SCTC

Heating Cooling

BTUH = BTU( British Thermal Unit) per hour CFM = airflow, cubic feet/minute COP = coefficient of performance = BTUH output/BTUH input DB = dry bulb temperature (°F) EAT = entering air temperature, Fahrenheit (dry bulb/wet bulb) EER = energy efficiency ratio = BTUH output/Watt input MPT = male pipe thread ESP = external static pressure (inches w.g.) EWT = entering water temperature GPM = water flow in U.S. gallons/minute HE = total heat of extraction, BTUH HC = air heating capacity, BTUH HR = total heat of rejection, BTUH

HWC = hot water generator (desuperheater) capacity, Mbtuh FPT = female pipe thread KW = total power unit input, kilowatts LAT = leaving air temperature, °F LC = latent cooling capacity, BTUH LWT = leaving water temperature, °FMBTUH = 1000 BTU per hour S/T = sensible to total cooling ratio SC = sensible cooling capacity, BTUH TC = total cooling capacity, BTUH WB = wet bulb temperature (°F) WPD = waterside pressure drop (psi & ft. of hd.) MWV = Motorized Water Valve

Legend and Glossary of Abbreviations

Conversion Table - to convert inch-pound (English) to S-I (Metric)Air Flow Water Flow Est Static Pressure Water Pressure Drop

Airfl ow (L/s) = CFM x 0.472 Water Flow (L/s) = gpm x 0.0631 ESP (Pa) = ESP (in of wg) x 249 PD (kPa) = PD (ft of hd) x 2.99

Page 6: Submittal Data - Climate Master · The award winning Tranquility® Series raises the bar for water-source heat pump efficiencies, features and application flexibility. Not only does

ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.

Page ______ of ______LC377 - 6

Selection Procedure

Step 1 Determine the actual heating and cooling loads at the desired dry bulb and wet bulb conditions.

Step 2 Obtain the following design parameters: Entering water temperature, water flow rate in GPM, air flow in CFM, water flow pressure drop and design wet and dry bulb temperatures. Air flow CFM should be between 300 and 450 CFM per ton. Unit water pressure drop should be kept as close as possible to each other to make water balancing easier. Go to the appropriate tables and find the proper indicated water flow and water temperature.

Step 3 Select a unit based on total and sensible cooling conditions. Select a unit which is closest to, but no larger than, the actual cooling load.

Step 4 Enter tables at the design water flow and water temperature. Read the total and sensible cooling capacities (Note: interpolation is permissible, extrapolation is not).

Step 5 Read the heating capacity. If it exceeds the design criteria it is acceptable. It is quite normal for water source heat pumps to be selected on cooling capacity only since the heating output is usually greater than the cooling capacity.

Step 6 Determine the correction factors associated with the variable factors of dry bulb and wet bulb.

Corrected Total Cooling = tabulated total cooling x wet bulb correction.

Corrected Sensible Cooling = tabulated sensible cooling x wet/dry bulb correction.

Step 7 Compare the corrected capacities to the load requirements. Normally if the capacities are within 10% of the loads, the equipment is acceptable. It is better to undersize than oversize, as undersizing improves humidity control, reduces sound levels and extends the life of the equipment.

Step 8 When completed, calculate water temperature rise and assess the selection. If the units selected are not within 10% of the load calculations, then review what effect changing the GPM, water temperature and/or air flow and air temperature would have on the corrected capacities. If the desired capacity cannot be achieved, select the next larger or smaller unit and repeat the procedure. Remember, when in doubt, undersize slightly for best performance.

Example Equipment Selection For CoolingStep 1 Load Determination:Assume we have determined that the appropriate cooling load at the desired dry bulb 80°F and wet bulb 65°F conditions is as follows:

Total Cooling...................................................23,000 BTUH

Sensible Cooling.............................................17,000 BTUH

Entering Air Temp.......80°F Dry Bulb / 65°F Wet Bulb

Step 2 Design Conditions:Similarly, we have also obtained the following design parameters:

Entering Water Temp...............................................................90°F

Water Flow (Based upon 10°F rise in temp.) .........6.0 GPM

Air Flow................................................................................690 CFM

Steps 3, 4 & 5 HP Selection:After making our preliminary selection (TS024), we enter the tables at design water flow and water temperature and read Total Cooling, Sens. Cooling and Heat of Rej. capacities:

Total Cooling...................................................25,200 BTUH

Sensible Cooling.............................................18,400 BTUH

Heat of Rejection.............................................31,100 BTUH

Steps 6 & 7 Entering Air and Airflow Corrections:Next, we determine our correction factors.

Table Ent Air Air Flow Corrected

Corrected Total Cooling = 25,200 x 0.9705 x 0.9724 = 23,782

Corrected Sens Cooling = 18,400 x 1.0809 x 0.8733 = 17,368

Corrected Heat of Reject = 31,100 x 0.9757 x 0.9728 = 29,519

Step 8 Water Temperature Rise Calculation and Assessment:

Actual Temperature Rise..............................................9.8°F

When we compare the Corrected Total Cooling and Corrected Sensible Cooling figures with our load requirements stated in Step 1, we discover that our selection is within +10% of our sensible load requirement. Furthermore, we see that our Corrected Total Cooling figure is within 1,000 Btuh of the actual indicated load.

Page 7: Submittal Data - Climate Master · The award winning Tranquility® Series raises the bar for water-source heat pump efficiencies, features and application flexibility. Not only does

ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.

Page ______ of ______LC377 - 7

TS Series Nomenclature

C0 2 4 CG 3 0 C L T4 5 6 7 8 9 10 11 12 13 14

Unit Size

Return Air

Voltage

Controls

Cabinet

Revision Level

Supply Air & Motor Option

TS1 2

TS = Tranquility® 20Single Stage Scroll

(Rotary: Size 006-012)

Model TypeV3

V = Vertical UpflowConfiguration

L = Left ReturnR = Right Return

0 = NoneWater Circuit Options2 = HWG (Coil Only)

6 = HWG (Coil Only) w/Auto Flow Regulator 2.5 GPM/Ton7 = HWG (Coil Only) w/Auto Flow Regulator 3.0 GPM/Ton8 = Auto Flow Regulator 2.5 GPM/Ton9 = Auto Flow Regulator 3.0 GPM/Ton

S15

S = StandardStandard

H = HorizontalD = Vertical Downflow

5 = Secondary Circulating Pump

Option Supply Configuration MotorTDB

TopDownBack

TSVTSDTSH

PSCPSCPSC

S Straight TSH PSCV TSV PSC Hi StaticU TSDY TSHZ TSH

TopDownBack

StraightK TSV ECMN TSD ECMP TSH ECMW TSH ECM

TopDownBack

Straight

PSC Hi StaticPSC Hi Static

PSC Hi Static

Heat Exchanger OptionsCXMDXM2CXM w/LONDXM2 w/LONCXM w/MPCDXM2 w/MPC

Control w/o Disconnect w/ DisconnectCDLMNP

ABEKRS

StandardClimaDry® Reheat

Non Coated Air Coil

Copper Cupro-Nickel Copper Cupro-NickelCE

NP

AD

JF

Motorized Valve T S U W

G = 208/230/60/1

H = 208/230/60/3 * N/A for Sizes 006-012E = 265/60/1

N = 575/60/3F = 460/60/3

AVAILABLEVOLTAGES

006 - E,G009 - E,G012 - E,G018 - E,G024 - E,F,G,H030 - E,F,G,H036 - E,F,G,H042 - E,F,G,H,N048 - E,F,G,H,N060 - E,F,G,H,N070 - F,G,H,N

OPTION

1AJK2CLM3ENP

1” FILTERRAILRANGE ULTRA

QUIET2” FILTER

RAIL1” FILTERFRAME

2” FILTERFRAME

4GRS

NO

YES

NO

YES

YES

YESYES

YESNO

NO

NONO

NONO

YES

YESYES

YESNO

NO

NONO

NONO

YES

YESYES

YESNO

NO

NONO

NONO

YES

YESYES

YESNO

NO

NONO

NONO

ClimaDry® reheat coil not coated*Microchannel On Sizes 024-048ClimaDry® units are equiped with DMX2

A = Current Revision Sizes 006-012 B = Current Revision Sizes 018

C = Current Revision Sizes 024-070

Tin Plated Air Coil /Microchannel Air Coil*

********

ClimaDry® II Option Notes:1. Unit must have DXM2 control option. 460 volt unit units require a four wire power supply with neutral.2. ClimaDry® II may not be combined with motorized water valve, internal secondary circulating pump, or automatic flow

regulator options.3. Unit minimum entering air temperature while in the dehumidification, cooling, or continuous fan modes is 65ºF DB/55ºF

WB. Operation below this minimum may result in nuisance faults. 4. A thermostat with dehumidification mode or thermostat and separate humidistat/dehumidistat is required for activation

and control of ClimaDry® II.5. Downflow and 575 volt units are not eligible for ClimaDry® II.

Page 8: Submittal Data - Climate Master · The award winning Tranquility® Series raises the bar for water-source heat pump efficiencies, features and application flexibility. Not only does

ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.

Page ______ of ______LC377 - 8

AHRI/ASHRAE/ISO 13256-1. Metric (S-I) Units

Cooling capacities based upon 80.6°F DB, 66.2°F WB entering air temperatureHeating capacities based upon 68°F DB, 59°F WB entering air temperatureAll ratings based upon operation at lower voltage of dual voltage rated models

Model FanMotor

Water Loop Heat Pump Ground Water Heat Pump Ground Loop Heat PumpCooling 86°F Heating 68°F Cooling 59°F Heating 50°F Cooling 77°F Heating 32°F

CapacityBtuh

EERBtuh/W

CapacityBtuh COP Capacity

BtuhEER

Btuh/WCapacity

Btuh COP CapacityBtuh

EERBtuh/W

CapacityBtuh COP

TSH/V006 PSC 6,300 15.7 8,000 5.4 7,400 25.5 6,300 4.4 6,700 18.5 4,800 3.4TSH/V009 PSC 9,300 15.3 11,100 4.8 11,100 25.2 9,400 4.3 10,000 18.1 7,100 3.4TSH/V012 PSC 11,700 15.4 13,800 4.5 13,300 24.6 11,800 4.0 12,300 18.1 9,500 3.5TSH/V/D

018PSC 18,600 15.0 23,000 5.2 21,300 24.8 18,600 4.5 19,500 18.4 14,500 3.6ECM 19,200 16.5 23,300 5.9 22,100 26.3 18,900 4.9 20,200 19.4 14,500 3.9

TSH/V/D024

PSC 23,800 16.9 30,800 5.9 26,500 24.9 24,100 5.0 25,300 18.9 19,200 4.0ECM 23,900 17.9 30,400 6.1 26,900 26.9 23,800 5.2 25,500 20.9 19,100 4.2

TSH/V/D030

PSC 28,000 16.3 35,500 5.5 31,000 24.9 28,400 4.7 29,200 18.5 22,200 3.9ECM 28,000 17.3 35,100 5.8 30,800 26.7 28,000 4.9 29,200 19.4 22,000 4.1

TSH/V/D036

PSC 33,400 17.0 40,400 5.6 35,400 23.2 33,200 4.7 34,300 19.2 25,900 4.1ECM 33,500 18.1 39,900 5.9 35,400 24.9 32,600 4.9 34,600 20.4 25,600 4.3

TSH/V/D042

PSC 38,500 17.2 46,300 5.6 43,700 25.4 36,200 4.7 40,100 19.4 28,700 3.8ECM 39,400 19.6 45,100 6.0 44,400 29.5 35,200 5.2 40,700 21.9 27,400 4.1

TSH/V/D048

PSC 47,100 14.8 58,000 4.7 53,600 21.3 47,500 4.0 49,600 16.8 36,600 3.4ECM 48,900 17.2 57,700 5.2 53,700 23.9 45,700 4.4 50,600 18.8 36,100 3.7

TSH/V/D060

PSC 62,400 15.9 73,900 5.0 68,500 23.1 58,200 4.2 63,900 17.2 46,900 3.7ECM 63,200 17.2 73,200 5.4 68,900 24.9 58,200 4.6 64,400 18.4 46,400 3.9

TSH/V/D070

PSC 71,000 14.6 82,100 4.6 78,000 21.1 66,100 4.0 72,900 16.2 53,800 3.4 ECM 71,100 15.7 82,000 4.8 78,100 23.0 65,200 4.1 73,000 17.2 53,000 3.6

Performance Data – AHRI/ASHRAE/ISO 13256-1

AHRI/ASHRAE/ISO 13256-1. English (I-P) Units

Cooling capacities based upon 27°C DB, 19°C WB entering air temperatureHeating capacities based upon 20°C DB, 15°C WB entering air temperatureAll ratings based upon operation at lower voltage of dual voltage rated models

Model FanMotor

Water Loop Heat Pump Ground Water Heat Pump Ground Loop Heat PumpCooling 30°C Heating 20°C Cooling 15°C Heating 10°C Cooling 25°C Heating 0°C

CapacitykW

EERW/W

CapacitykW COP Capacity

kWEER

WattsCapacity

kW COP CapacitykW

EERW/W

CapacitykW COP

TSH/V006 PSC 1.85 4.6 2.34 5.4 2.17 7.5 1.85 4.4 1.96 5.4 1.41 3.4

TSH/V009 PSC 2.74 4.5 3.26 4.8 3.26 7.4 2.76 4.3 2.94 5.3 2.09 3.4

TSH/V012 PSC 3.43 4.5 4.05 4.5 3.90 7.2 3.46 4.0 3.60 5.3 2.78 3.5

TSH/V/D018

PSC 5.47 4.4 6.76 5.2 6.26 7.3 5.45 4.5 5.74 5.4 4.27 3.6ECM 5.65 4.8 6.85 5.9 6.50 7.7 5.56 4.9 5.94 5.7 4.43 3.9

TSH/V/D024

PSC 6.98 4.9 9.03 5.9 7.77 7.3 7.06 5.0 7.42 5.5 5.63 4.0ECM 7.00 5.2 8.91 6.1 7.88 7.8 6.98 5.2 7.47 6.1 5.60 4.2

TSH/V/D030

PSC 8.21 4.8 10.40 5.5 9.09 7.3 8.32 4.7 8.56 5.4 6.51 3.9ECM 8.21 5.1 10.29 5.8 9.03 7.8 8.21 4.9 8.56 5.7 6.45 4.1

TSH/V/D036

PSC 9.79 5.0 11.84 5.6 10.38 6.8 9.73 4.7 10.05 5.6 7.59 4.1ECM 9.82 5.3 11.69 5.9 10.38 7.3 9.55 4.9 10.14 6.0 7.50 4.3

TSH/V/D042

PSC 11.28 5.0 13.57 5.6 12.81 7.4 10.61 4.7 11.75 5.7 8.41 3.8ECM 11.55 5.7 13.22 6.0 13.01 8.6 10.32 5.2 11.93 6.4 8.03 4.1

TSH/V/D048

PSC 13.80 4.3 17.00 4.7 15.71 6.2 13.92 4.0 14.54 4.9 10.73 3.4ECM 14.33 5.1 16.91 5.2 15.74 7.0 13.39 4.4 14.83 5.5 10.58 3.7

TSH/V/D060

PSC 18.29 4.7 21.66 5.0 20.08 6.8 17.06 4.2 18.73 5.0 13.75 3.7ECM 18.52 5.0 21.45 5.4 20.19 7.3 17.06 4.6 18.87 5.4 13.60 3.9

TSH/V/D070

PSC 20.81 4.3 24.06 4.6 22.86 6.2 19.37 4.0 21.37 4.8 15.77 3.4 ECM 20.84 4.6 24.03 4.8 22.89 6.7 19.10 4.1 21.40 5.0 15.53 3.6

Page 9: Submittal Data - Climate Master · The award winning Tranquility® Series raises the bar for water-source heat pump efficiencies, features and application flexibility. Not only does

ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.

Page ______ of ______LC377 - 9

Performance Data – Selection Notes

For operation in the shaded area when water is used in lieu of an antifreeze solution, the LWT (Leaving Water Temperature) must be calculated. Flow must be maintained to a level such that the LWT is maintained above 40°F [4.4°C] when the JW3 jumper is not clipped (see example below). Otherwise, appropriate levels of a proper antifreeze solution should be used in systems with leaving water temperatures of 40ºF [4.4°C] or below and the JW3 jumper should be clipped. This is due to the potential of the refrigerant temperature being as low as 32°F [0°C] with 40°F [4.4°C] LWT, which may lead to a nuisance cutout due to the activation of the Low Temperature Protection. JW3 should never be clipped for standard range equipment or systems without antifreeze.

Example:At 50°F EWT (Entering Water Temperature) and 1.5 gpm/ton, a 3 ton unit has a HE of 22,500 Btuh. To calculate LWT, rearrange the formula for HE as follows:

HE = TD x GPM x 500, where HE = Heat of Extraction (Btuh); TD = temperature difference (EWT - LWT) and GPM = U.S. Gallons per Minute.

TD = HE / (GPM x 500)

TD = 22,500 / (4.5 x 500)

TD = 10°F

LWT = EWT - TD

LWT = 50 - 10 = 40°F

In this example, as long as the EWT does not fall below 50°F, the system will operate as designed. For EWTs below 50°F, higher flow rates will be required (open loop systems, for example, require at least 2 gpm/ton when EWT is below 50°F).

20 5.5 3.9 9.0 N/A N/A N/A N/A N/A N/A N/A 450 11.5 1.31 7.3 94 2.57 20 5.5 3.9 9.0 N/A N/A N/A N/A N/A N/A N/A 600 11.8 1.20 7.8 88 2.89 30 2.8 0.7 1.6 450 19.8 11.3 0.57 0.74 22.3 26.9 450 12.8 1.34 8.5 96 2.80 30 2.8 0.7 1.6 600 20.6 13.5 0.65 0.76 23.2 27.1 600 13.1 1.23 9.0 90 3.14 30 4.1 2.1 4.9 450 20.0 11.3 0.56 0.71 22.4 28.1 450 13.2 1.35 8.9 97 2.87 30 4.1 2.1 4.9 600 20.8 13.5 0.65 0.73 23.3 28.3 600 13.6 1.23 9.4 91 3.23 30 5.5 3.5 8.1 450 20.2 11.3 0.56 0.70 22.6 28.8 450 13.5 1.35 9.1 98 2.92 30 5.5 3.5 8.1 600 21.0 13.6 0.65 0.73 23.5 29.0 600 13.8 1.24 9.7 91 3.27 40 2.8 0.6 1.4 450 20.3 11.7 0.58 0.80 23.0 25.5 450 14.7 1.38 10.2 100 3.14 40 2.8 0.6 1.4 600 21.1 14.0 0.66 0.82 23.9 25.7 600 15.1 1.26 10.9 93 3.52 40 4.1 2.0 4.6 450 20.4 11.7 0.57 0.76 23.0 26.8 450 15.3 1.39 10.8 101 3.23 40 4.1 2.0 4.6 600 21.3 14.0 0.66 0.79 24.0 27.0 600 15.7 1.27 11.4 94 3.63 40 5.5 3.2 7.4 450 20.6 11.8 0.57 0.75 23.1 27.6 450 15.6 1.39 11.0 102 3.29 40 5.5 3.2 7.4 600 21.5 14.1 0.66 0.77 24.1 27.8 600 16.0 1.27 11.7 95 3.69 50 2.8 0.5 1.2 450 19.9 11.7 0.59 0.89 22.9 22.3 450 16.8 1.41 12.1 105 3.49 50 2.8 0.5 1.2 600 20.7 14.0 0.68 0.92 23.8 22.4 600 17.2 1.29 12.9 97 3.92 50 4.1 1.7 3.9 450 20.3 11.8 0.58 0.84 23.1 24.1 450 17.5 1.42 12.8 106 3.61 50 4.1 1.7 3.9 600 21.1 14.2 0.67 0.87 24.1 24.3 600 18.0 1.30 13.5 98 4.05 50 5.5 2.8 6.5 450 20.4 11.8 0.58 0.82 23.2 25.0 450 17.9 1.43 13.1 107 3.67 50 5.5 2.8 6.5 600 21.3 14.2 0.67 0.84 24.1 25.2 600 18.3 1.30 13.9 98 4.12 60 2.8 0.3 0.7 450 19.0 11.4 0.60 1.00 22.4 19.1 450 18.9 1.44 14.1 109 3.84 60 2.8 0.3 0.7 600 19.8 13.7 0.69 1.03 23.3 19.2 600 19.4 1.32 14.9 100 4.32 60 4.1 1.5 3.5 450 19.5 11.6 0.59 0.94 22.7 20.9 450 19.7 1.45 14.8 111 3.98 60 4.1 1.5 3.5 600 20.3 13.9 0.68 0.97 23.6 21.0 600 20.3 1.33 15.7 101 4.47 60 5.5 2.6 6.0 450 19.8 11.7 0.59 0.91 22.9 21.8 450 20.2 1.46 15.2 112 4.05 60 5.5 2.6 6.0 600 20.6 14.0 0.68 0.94 23.8 22.0 600 20.7 1.33 16.2 102 4.55 70 2.8 0.3 0.7 450 17.8 11.0 0.62 1.11 21.6 16.1 450 21.0 1.47 16.0 113 4.19 70 2.8 0.3 0.7 600 18.6 13.2 0.71 1.15 22.5 16.2 600 21.6 1.34 17.0 103 4.71 70 4.1 1.4 3.2 450 18.5 11.3 0.61 1.05 22.1 17.7 450 22.0 1.48 16.9 115 4.34 70 4.1 1.4 3.2 600 19.3 13.5 0.70 1.08 22.9 17.8 600 22.5 1.36 17.9 105 4.87 70 5.5 2.4 5.5 450 18.8 11.4 0.60 1.01 22.3 18.5 450 22.5 1.49 17.3 116 4.42 70 5.5 2.4 5.5 600 19.6 13.6 0.70 1.05 23.1 18.7 600 23.1 1.36 18.4 106 4.96 80 2.8 0.2 0.5 450 16.6 10.6 0.64 1.23 20.8 13.5 450 23.1 1.50 18.0 118 4.52 80 2.8 0.2 0.5 600 17.3 12.7 0.73 1.27 21.6 13.6 600 23.7 1.37 19.1 107 5.08 80 4.1 1.2 2.8 450 17.3 10.8 0.63 1.16 21.2 14.8 450 24.1 1.51 18.9 120 4.68 80 4.1 1.2 2.8 600 18.0 13.0 0.72 1.20 22.1 14.9 600 24.8 1.38 20.0 108 5.25 80 5.5 2.2 5.1 450 17.6 10.9 0.62 1.13 21.5 15.6 450 24.6 1.52 19.4 121 4.76 80 5.5 2.2 5.1 600 18.3 13.1 0.72 1.17 22.3 15.7 600 25.3 1.39 20.5 109 5.34 85 2.8 0.2 0.5 450 16.0 10.4 0.65 1.29 20.4 12.3 450 24.1 1.51 18.9 120 4.68 85 2.8 0.2 0.5 600 16.6 12.5 0.75 1.34 21.2 12.4 600 24.8 1.38 20.0 108 5.25 85 4.1 1.2 2.7 450 16.6 10.6 0.64 1.23 20.8 13.5 450 25.1 1.52 19.8 122 4.83 85 4.1 1.2 2.7 600 17.3 12.7 0.73 1.27 21.6 13.6 600 25.8 1.39 21.0 110 5.43 85 5.5 2.1 4.9 450 17.0 10.7 0.63 1.20 21.0 14.2 450 25.6 1.53 20.3 123 4.91 85 5.5 2.1 4.9 600 17.7 12.8 0.73 1.24 21.9 14.3 600 26.3 1.40 21.5 111 5.52 90 2.8 0.2 0.5 450 15.3 10.2 0.67 1.36 20.0 11.3 450 25.1 1.52 19.8 122 4.83 90 2.8 0.2 0.5 600 16.0 12.2 0.77 1.40 20.8 11.4 600 25.8 1.39 21.0 110 5.43 90 4.1 1.1 2.5 450 16.0 10.4 0.65 1.29 20.4 12.4 450 26.1 1.54 20.7 124 4.99 90 4.1 1.1 2.5 600 16.6 12.5 0.75 1.33 21.2 12.5 600 26.8 1.40 22.0 111 5.60 90 5.5 2.0 4.6 450 16.3 10.5 0.64 1.26 20.6 13.0 450 26.6 1.54 21.2 125 5.06 90 5.5 2.0 4.6 600 17.0 12.6 0.74 1.30 21.4 13.1 600 27.4 1.41 22.5 112 5.68 100 2.8 0.2 0.5 450 14.1 9.9 0.70 1.48 19.2 9.5 N/A N/A N/A N/A N/A N/A 100 2.8 0.2 0.5 600 14.7 11.8 0.80 1.53 19.9 9.6 N/A N/A N/A N/A N/A N/A 100 4.1 1.1 2.5 450 14.7 10.0 0.68 1.42 19.5 10.3 N/A N/A N/A N/A N/A N/A 100 4.1 1.1 2.5 600 15.3 12.0 0.78 1.47 20.3 10.4 N/A N/A N/A N/A N/A N/A 100 5.5 1.9 4.4 450 15.0 10.1 0.67 1.39 19.7 10.8 N/A N/A N/A N/A N/A N/A 100 5.5 1.9 4.4 600 15.6 12.1 0.77 1.44 20.5 10.9 N/A N/A N/A N/A N/A N/A 110 2.8 0.1 0.2 450 13.1 9.7 0.74 1.61 18.6 8.1 N/A N/A N/A N/A N/A N/A 110 2.8 0.1 0.2 600 13.6 11.6 0.85 1.66 19.3 8.2 N/A N/A N/A N/A N/A N/A 110 4.1 0.9 2.1 450 13.5 9.7 0.72 1.55 18.8 8.7 N/A N/A N/A N/A N/A N/A 110 4.1 0.9 2.1 600 14.1 11.7 0.83 1.60 19.6 8.8 N/A N/A N/A N/A N/A N/A 110 5.5 1.7 3.9 450 13.8 9.8 0.71 1.52 19.0 9.1 N/A N/A N/A N/A N/A N/A 110 5.5 1.7 3.9 600 14.4 11.7 0.82 1.57 19.7 9.1 N/A N/A N/A N/A N/A N/A 120 2.8 0.1 0.2 450 12.3 9.7 0.79 1.73 18.2 7.1 N/A N/A N/A N/A N/A N/A 120 2.8 0.1 0.2 600 12.8 11.7 0.91 1.79 18.9 7.1 N/A N/A N/A N/A N/A N/A 120 4.1 0.8 1.8 450 12.6 9.7 0.77 1.68 18.3 7.5 N/A N/A N/A N/A N/A N/A 120 4.1 0.8 1.8 600 13.1 11.6 0.88 1.73 19.0 7.6 N/A N/A N/A N/A N/A N/A 120 5.5 1.6 3.7 450 12.8 9.7 0.76 1.65 18.4 7.8 N/A N/A N/A N/A N/A N/A 120 5.5 1.6 3.7 600 13.3 11.6 0.87 1.70 19.1 7.8 N/A N/A N/A N/A N/A N/A

EWT°F GPM

WPD Cooling - EAT 80/67°F Heating - EAT 70°F

PSI FT Airflow CFM TC SC Sens/Tot

Ratio kW HR EER Airflow CFM HC kW HE LAT COP

20 Operation not recommended

30

40

50

60

70

80

85

90

100

Operation not recommended110

120

Page 10: Submittal Data - Climate Master · The award winning Tranquility® Series raises the bar for water-source heat pump efficiencies, features and application flexibility. Not only does

ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.

Page ______ of ______LC377 - 10

Performance Data – TSH/V006 (PSC Blower)

300 CFM Nominal AirflowPerformance capacities shown in thousands of Btuh

TSH/V006 PSC

EWT °F GPM

WPD COOLING - EAT 80.6/66.2 °F HEATING - EAT 68°F

PSI Ft TC SC KW HR EER HC KW HE LAT COP

20 2.0 3.2 7.4 Operation not recommended 3.9 0.4 2.5 83.1 2.7

30

1.0 0.3 0.7 6.9 5.0 0.3 7.8 25.5 4.7 0.4 3.2 86.1 3.1

1.5 1.6 3.7 7.1 5.0 0.3 8.0 26.8 4.9 0.4 3.4 86.9 3.2

2.0 3.0 6.9 7.2 5.1 0.3 8.1 27.6 5.0 0.4 3.5 87.3 3.3

40

1.0 0.3 0.7 7.2 5.3 0.3 8.2 24.7 5.6 0.5 4.0 89.5 3.6

1.5 1.5 3.5 7.2 5.3 0.3 8.2 25.8 5.8 0.5 4.2 90.3 3.7

2.0 2.8 6.5 7.3 5.3 0.3 8.2 26.6 5.9 0.5 4.3 90.8 3.8

50

1.0 0.3 0.7 7.1 5.5 0.3 8.2 22.1 6.3 0.5 4.7 92.4 4.0

1.5 1.4 3.2 7.2 5.5 0.3 8.3 23.8 6.6 0.5 5.0 93.3 4.1

2.0 2.6 6.0 7.3 5.5 0.3 8.3 24.6 6.7 0.5 5.1 93.7 4.2

60

1.0 0.2 0.5 6.9 5.6 0.4 8.1 19.4 7.0 0.5 5.4 95.0 4.4

1.5 1.3 3.0 7.1 5.6 0.3 8.2 21.0 7.3 0.5 5.7 96.0 4.5

2.0 2.4 5.5 7.1 5.7 0.3 8.3 21.9 7.4 0.5 5.8 96.5 4.6

70

1.0 0.2 0.5 6.5 5.5 0.4 7.9 16.4 7.7 0.5 6.1 97.6 4.7

1.5 1.2 2.8 6.8 5.6 0.4 8.0 18.0 8.0 0.5 6.3 98.7 4.9

2.0 2.2 5.1 6.9 5.6 0.4 8.1 18.8 8.1 0.5 6.5 99.3 5.0

80

1.0 0.2 0.5 6.1 5.3 0.4 7.6 13.7 8.4 0.5 6.8 100.3 5.1

1.5 1.1 2.5 6.3 5.4 0.4 7.8 15.0 8.8 0.5 7.1 101.7 5.3

2.0 2.0 4.6 6.4 5.5 0.4 7.8 15.8 9.0 0.5 7.3 102.5 5.4

90

1.0 0.2 0.5 5.6 5.1 0.5 7.3 11.3 9.2 0.5 7.5 103.4 5.6

1.5 1.0 2.3 5.8 5.2 0.5 7.4 12.4 9.7 0.5 8.0 105.2 5.8

2.0 1.8 4.2 6.0 5.3 0.5 7.5 13.0 10.0 0.5 8.3 106.3 6.0

100

1.0 0.1 0.2 5.1 4.8 0.6 6.9 9.2

Operation not recommended

1.5 0.8 1.8 5.3 4.9 0.5 7.1 10.1

2.0 1.6 3.7 5.4 5.0 0.5 7.2 10.6

110

1.0 0.1 0.2 4.5 4.4 0.6 6.6 7.5

1.5 0.7 1.6 4.8 4.6 0.6 6.8 8.2

2.0 1.4 3.2 4.9 4.6 0.6 6.8 8.6

120

1.0 0.1 0.2 4.1 4.1 0.7 6.3 6.1

1.5 0.6 1.4 4.3 4.2 0.6 6.4 6.6

2.0 1.2 2.8 4.4 4.3 0.6 6.5 6.9Interpolation is permissible; extrapolation is not.All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating. All performance data is based upon the lower voltage of dual voltage rated units.See performance correction tables for operating conditions other than those listed above..

Page 11: Submittal Data - Climate Master · The award winning Tranquility® Series raises the bar for water-source heat pump efficiencies, features and application flexibility. Not only does

ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.

Page ______ of ______LC377 - 11

Performance Data – TSH/V009 (PSC Blower)

300 CFM Nominal AirflowPerformance capacities shown in thousands of Btuh

TSH/V009 PSC

EWT °F GPM

WPD COOLING - EAT 80.6/66.2 °F HEATING - EAT 68°F

PSI Ft TC SC KW HR EER HC KW HE LAT COP

20 2.8 2.8 6.5 Operation not recommended 5.8 0.6 3.8 86.0 2.8

30

1.4 0.8 1.8 12.0 8.3 0.4 13.3 31.3 6.8 0.6 4.6 88.9 3.1

2.1 1.5 3.5 12.2 8.4 0.4 13.4 34.8 7.1 0.6 4.9 89.8 3.2

2.8 2.7 6.2 12.3 8.4 0.3 13.5 36.8 7.2 0.6 5.0 90.3 3.3

40

1.4 0.8 1.7 11.6 8.0 0.4 13.1 26.6 8.0 0.7 5.7 92.6 3.5

2.1 1.5 3.3 11.8 8.2 0.4 13.2 29.5 8.3 0.7 6.1 93.6 3.7

2.8 2.6 5.9 12.0 8.2 0.4 13.3 31.1 8.5 0.7 6.2 94.2 3.7

50

1.4 0.7 1.6 11.1 7.8 0.5 12.8 22.6 9.1 0.7 6.8 96.1 3.9

2.1 1.4 3.2 11.4 8.0 0.5 13.0 25.0 9.5 0.7 7.2 97.3 4.1

2.8 2.4 5.6 11.6 8.0 0.4 13.1 26.4 9.7 0.7 7.4 97.9 4.2

60

1.4 0.7 1.5 10.6 7.6 0.6 12.5 19.3 10.2 0.7 7.9 99.4 4.3

2.1 1.3 3.0 10.9 7.7 0.5 12.7 21.3 10.6 0.7 8.3 100.7 4.5

2.8 2.3 5.3 11.1 7.8 0.5 12.8 22.4 10.9 0.7 8.5 101.4 4.5

70

1.4 0.6 1.5 10.0 7.3 0.6 12.1 16.4 11.2 0.7 8.8 102.6 4.7

2.1 1.2 2.8 10.4 7.5 0.6 12.3 18.0 11.7 0.7 9.3 104.0 4.8

2.8 2.2 5.0 10.6 7.6 0.6 12.4 19.0 11.9 0.7 9.5 104.8 4.9

80

1.4 0.6 1.4 9.4 7.1 0.7 11.7 13.9 12.2 0.7 9.8 105.7 5.0

2.1 1.1 2.6 9.8 7.2 0.6 11.9 15.3 12.7 0.7 10.3 107.2 5.2

2.8 2.0 4.6 9.9 7.3 0.6 12.1 16.0 13.0 0.7 10.5 108.0 5.2

90

1.4 0.6 1.3 8.7 6.8 0.7 11.2 11.7 13.2 0.7 10.7 108.7 5.3

2.1 1.1 2.5 9.1 7.0 0.7 11.5 12.8 13.8 0.7 11.2 110.4 5.5

2.8 1.9 4.3 9.3 7.1 0.7 11.6 13.5 14.0 0.7 11.5 111.2 5.5

100

1.4 0.5 1.2 7.9 6.5 0.8 10.7 9.7

Operation not recommended

2.1 1.0 2.3 8.3 6.7 0.8 11.0 10.7

2.8 1.7 4.0 8.6 6.8 0.8 11.1 11.3

110

1.4 0.5 1.1 7.1 6.2 0.9 10.2 8.0

2.1 0.9 2.1 7.6 6.4 0.9 10.5 8.8

2.8 1.6 3.7 7.8 6.5 0.8 10.6 9.3

120

1.4 0.4 1.0 6.3 5.8 1.0 9.6 6.5

2.1 0.8 1.9 6.7 6.0 0.9 9.9 7.2

2.8 1.5 3.4 6.9 6.1 0.9 10.0 7.6Interpolation is permissible; extrapolation is not.All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating. All performance data is based upon the lower voltage of dual voltage rated units.See performance correction tables for operating conditions other than those listed above..

Page 12: Submittal Data - Climate Master · The award winning Tranquility® Series raises the bar for water-source heat pump efficiencies, features and application flexibility. Not only does

ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.

Page ______ of ______LC377 - 12

Performance Data – TSH/V012 (PSC Blower)

350 CFM Nominal AirflowPerformance capacities shown in thousands of Btuh

TSH/V012 PSC

EWT °F GPM

WPD COOLING - EAT 80.6/66.2 °F HEATING - EAT 68°F

PSI Ft TC SC KW HR EER HC KW HE LAT COP

20 3.5 4.0 9.2 Operation not recommended 8.0 0.8 5.3 89.1 2.9

30

1.8 0.6 1.4 12.5 8.2 0.5 14.2 24.3 9.2 0.8 6.3 92.2 3.2

2.6 2.1 4.8 12.7 8.3 0.5 14.4 25.8 9.5 0.8 6.7 93.2 3.3

3.5 3.8 8.8 13.1 8.6 0.5 14.7 27.2 9.8 0.8 6.9 93.8 3.4

40

1.8 0.6 1.3 13.1 8.7 0.6 15.0 23.2 10.6 0.9 7.7 96.0 3.6

2.6 2.0 4.6 13.2 8.7 0.5 15.0 24.7 11.0 0.9 8.0 97.1 3.7

3.5 3.6 8.3 13.3 8.8 0.5 15.1 25.6 11.2 0.9 8.2 97.7 3.7

50

1.8 0.5 1.1 13.1 8.8 0.6 15.2 21.0 11.9 0.9 8.8 99.3 3.9

2.6 1.9 4.3 13.2 8.8 0.6 15.2 22.5 12.2 0.9 9.1 100.3 4.0

3.5 3.4 7.9 13.3 8.9 0.6 15.3 23.3 12.4 0.9 9.3 100.8 4.0

60

1.8 0.4 1.0 12.9 8.7 0.7 15.3 18.6 12.9 0.9 9.7 102.0 4.1

2.6 1.8 4.0 13.1 8.8 0.7 15.3 20.1 13.2 0.9 10.0 102.8 4.1

3.5 3.2 7.4 13.2 8.8 0.6 15.4 20.9 13.3 0.9 10.1 103.2 4.2

70

1.8 0.4 0.9 12.3 8.5 0.8 15.0 16.0 13.6 0.9 10.4 103.9 4.2

2.6 1.6 3.8 12.7 8.6 0.7 15.1 17.5 13.8 1.0 10.6 104.5 4.3

3.5 3.0 6.9 12.8 8.7 0.7 15.2 18.2 13.9 1.0 10.7 104.8 4.3

80

1.8 0.3 0.7 11.6 8.2 0.9 14.5 13.6 14.1 1.0 10.8 105.2 4.3

2.6 1.5 3.5 12.0 8.4 0.8 14.8 14.9 14.2 1.0 10.9 105.5 4.3

3.5 2.8 6.5 12.2 8.4 0.8 14.9 15.6 14.3 1.0 11.0 105.7 4.3

90

1.8 0.3 0.6 10.7 7.9 0.9 14.0 11.4 14.3 1.0 11.0 105.8 4.4

2.6 1.4 3.3 11.2 8.1 0.9 14.3 12.6 14.3 1.0 11.0 105.8 4.4

3.5 2.6 6.0 11.5 8.2 0.9 14.4 13.2 14.3 1.0 11.1 105.9 4.4

100

1.8 0.2 0.5 9.8 7.6 1.0 13.3 9.4

Operation not recommended

2.6 1.3 3.0 10.3 7.8 1.0 13.7 10.4

3.5 2.4 5.6 10.5 7.8 1.0 13.8 11.0

110

1.8 0.1 0.3 8.8 7.3 1.1 12.6 7.7

2.6 1.2 2.7 9.3 7.4 1.1 13.0 8.5

3.5 2.2 5.1 9.5 7.5 1.1 13.1 9.0

120

1.8 0.1 0.2 7.7 6.9 1.2 11.9 6.2

2.6 1.1 2.5 8.2 7.1 1.2 12.3 6.9

3.5 2.0 4.6 8.45 7.19 1.16 12.42 7.27Interpolation is permissible; extrapolation is not.All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating. All performance data is based upon the lower voltage of dual voltage rated units.See performance correction tables for operating conditions other than those listed above..

Page 13: Submittal Data - Climate Master · The award winning Tranquility® Series raises the bar for water-source heat pump efficiencies, features and application flexibility. Not only does

ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.

Page ______ of ______LC377 - 13

Performance Data – TSH/V/D018 (PSC Blower)

600 CFM Nominal AirflowPerformance capacities shown in thousands of Btuh

TSH/V/D018 PSC

EWT °F GPM

WPD COOLING - EAT 80.6/66.2 °F HEATING - EAT 68°F

PSI Ft TC SC KW HR EER HC KW HE LAT COP

20 5.5 3.9 9.0 Operation not recommended 12.5 1.2 8.4 87.3 3.0

30

2.8 0.7 1.6 21.3 14.9 0.8 24.0 26.5 14.1 1.3 9.8 89.7 3.3

4.1 2.1 4.9 21.6 14.9 0.8 24.2 28.3 14.7 1.3 10.4 90.6 3.4

5.5 3.5 8.1 21.8 14.9 0.7 24.3 29.2 15.0 1.3 10.6 91.1 3.5

40

2.8 0.6 1.4 21.4 15.2 0.9 24.4 24.5 16.3 1.3 11.9 93.1 3.7

4.1 2.0 4.6 21.6 15.3 0.8 24.4 25.9 17.0 1.3 12.6 94.2 3.8

5.5 3.2 7.4 21.8 15.3 0.8 24.6 26.9 17.4 1.3 12.9 94.7 3.9

50

2.8 0.5 1.0 21.2 15.3 1.0 24.6 21.7 18.5 1.3 14.0 96.5 4.1

4.1 1.7 3.9 21.6 15.5 0.9 24.7 23.5 19.3 1.3 14.8 97.8 4.3

5.5 2.5 6.5 21.7 15.5 0.9 24.7 24.3 19.8 1.3 15.2 98.4 4.4

60

2.8 0.3 0.7 20.5 14.9 1.1 24.2 18.8 20.8 1.3 16.2 100.0 4.5

4.1 1.5 3.5 21.0 15.2 1.0 24.4 20.6 21.7 1.4 17.1 101.4 4.7

5.5 2.6 6.0 21.2 15.3 1.0 24.5 21.4 22.2 1.4 17.6 102.2 4.8

70

2.8 0.3 0.7 19.4 14.3 1.2 23.6 16.1 23.0 1.4 18.3 103.4 4.9

4.1 1.4 3.2 20.1 14.7 1.1 23.9 17.7 24.1 1.4 19.3 105.1 5.1

5.5 2.4 5.5 20.3 14.8 1.1 24.1 18.5 24.7 1.4 19.9 106.0 5.1

80

2.8 0.2 0.5 18.3 13.6 1.4 22.9 13.5 25.4 1.4 20.5 107.0 5.2

4.1 1.2 2.8 18.9 14.0 1.3 23.3 14.9 26.6 1.5 21.6 109.0 5.3

5.5 2.2 5.1 19.3 14.2 1.2 23.5 15.7 27.3 1.5 22.2 110.0 5.4

90

2.8 0.2 0.5 17.0 13.0 1.5 22.1 11.2 27.8 1.5 22.7 110.8 5.4

4.1 1.1 2.5 17.7 13.3 1.4 22.5 12.5 29.2 1.6 23.9 113.0 5.5

5.5 2.0 4.6 18.0 13.5 1.4 22.7 13.1 30.1 1.6 24.6 114.3 5.5

100

2.8 0.2 0.5 15.7 12.4 1.7 21.5 9.3

Operation not recommended

4.1 1.1 2.5 16.4 12.7 1.6 21.8 10.3

5.5 1.9 4.4 16.7 12.8 1.5 22.0 10.8

110

2.8 0.1 0.2 14.4 11.9 1.9 20.9 7.6

4.1 0.9 2.1 15.1 12.1 1.8 21.2 8.4

5.5 1.7 3.9 15.4 12.2 1.7 21.3 8.9

120

2.8 0.1 0.2 13.2 11.6 2.1 20.5 6.2

4.1 0.8 1.8 13.8 11.7 2.0 20.6 6.9

5.5 1.6 3.7 14.1 11.8 1.9 20.8 7.2Interpolation is permissible; extrapolation is not.All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating. All performance data is based upon the lower voltage of dual voltage rated units.See performance correction tables for operating conditions other than those listed above..

Page 14: Submittal Data - Climate Master · The award winning Tranquility® Series raises the bar for water-source heat pump efficiencies, features and application flexibility. Not only does

ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.

Page ______ of ______LC377 - 14

Performance Data – TSH/V/D018 (ECM Blower)

750 CFM Nominal AirflowPerformance capacities shown in thousands of Btuh

TSH/V/D018 ECM

EWT °F GPM

WPD COOLING - EAT 80.6/66.2 °F HEATING - EAT 68°F

PSI Ft TC SC KW HR EER HC KW HE LAT COP

20 5.5 3.9 9.0 Operation not recommended 12.3 1.1 8.5 83.2 3.2

30

2.8 0.7 1.6 20.9 15.3 0.8 23.6 26.5 13.7 1.2 9.7 84.9 3.4

4.1 2.1 4.9 21.3 15.5 0.8 23.9 28.3 14.2 1.2 10.2 85.5 3.5

5.5 3.5 8.1 21.9 15.9 0.7 24.4 29.7 14.5 1.2 10.4 85.8 3.6

40

2.8 0.6 1.4 21.3 15.9 0.9 24.3 24.8 15.9 1.2 11.7 87.5 3.9

4.1 2.0 4.6 21.9 16.1 0.8 24.6 26.9 16.5 1.2 12.4 88.4 4.0

5.5 3.2 7.4 22.1 16.2 0.8 24.8 27.8 16.9 1.2 12.8 88.8 4.1

50

2.8 0.5 1.0 21.8 16.6 0.9 25.1 23.1 18.2 1.2 14.0 90.4 4.4

4.1 1.7 3.9 22.1 16.6 0.9 25.1 24.8 19.0 1.2 14.8 91.4 4.5

5.5 2.5 6.5 22.2 16.7 0.9 25.2 25.7 19.5 1.2 15.3 92.0 4.6

60

2.8 0.3 0.7 21.2 16.7 1.1 24.8 20.2 20.5 1.2 16.3 93.3 4.9

4.1 1.5 3.5 21.7 16.8 1.0 25.1 22.0 21.5 1.2 17.3 94.5 5.1

5.5 2.6 6.0 21.9 16.8 1.0 25.2 22.9 22.1 1.3 17.8 95.2 5.2

70

2.8 0.3 0.7 20.2 16.5 1.2 24.2 17.2 22.9 1.3 18.6 96.2 5.3

4.1 1.4 3.2 20.8 16.7 1.1 24.6 19.0 24.0 1.3 19.6 97.6 5.5

5.5 2.4 5.5 21.1 16.7 1.1 24.7 19.9 24.6 1.3 20.2 98.3 5.6

80

2.8 0.2 0.5 18.9 16.1 1.3 23.4 14.4 25.2 1.3 20.7 99.1 5.6

4.1 1.2 2.8 19.7 16.4 1.2 23.9 16.0 26.4 1.3 21.8 100.5 5.7

5.5 2.2 5.1 20.0 16.5 1.2 24.1 16.8 27.0 1.4 22.3 101.2 5.8

90

2.8 0.2 0.5 17.6 15.7 1.5 22.7 11.9 27.4 1.4 22.6 101.7 5.8

4.1 1.1 2.5 18.4 15.9 1.4 23.1 13.3 28.5 1.5 23.5 103.1 5.7

5.5 2.0 4.6 18.7 16.1 1.3 23.3 14.0 29.0 1.5 23.9 103.8 5.7

100

2.8 0.2 0.5 16.3 15.2 1.7 22.0 9.8

Operation not recommended

4.1 1.1 2.5 17.0 15.4 1.6 22.3 10.9

5.5 1.9 4.4 17.4 15.6 1.5 22.5 11.5

110

2.8 0.1 0.2 15.1 14.7 1.9 21.6 8.0

4.1 0.9 2.1 15.7 15.0 1.8 21.8 8.9

5.5 1.7 3.9 16.1 15.1 1.7 21.9 9.4

120

2.8 0.1 0.2 14.2 14.2 2.1 21.5 6.6

4.1 0.8 1.8 14.6 14.5 2.0 21.5 7.3

5.5 1.6 3.7 14.9 14.7 1.9 21.5 7.7Interpolation is permissible; extrapolation is not.All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating. All performance data is based upon the lower voltage of dual voltage rated units.See performance correction tables for operating conditions other than those listed above..

Page 15: Submittal Data - Climate Master · The award winning Tranquility® Series raises the bar for water-source heat pump efficiencies, features and application flexibility. Not only does

ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.

Page ______ of ______LC377 - 15

Performance Data – TSH/V/D024 (PSC Blower)

950 CFM Nominal AirflowPerformance capacities shown in thousands of Btuh

TSH/V/D024 PSC

EWT °F GPM

WPD COOLING - EAT 80.6/66.2 °F HEATING - EAT 68°F

PSI Ft TC SC KW HR EER HWG Cap HC KW HE LAT COP HWG

Cap20 6.0 1.9 4.4 Operation not recommended 16.4 1.5 11.3 83.2 3.2 1.5

30

3.0 0.9 2.1 30.4 19.4 0.9 33.6 32.3 0.8 18.2 1.5 13.1 84.8 3.6 1.8

4.5 1.2 2.7 29.7 18.3 0.9 32.7 34.1 0.7 19.1 1.5 14.0 85.7 3.7 1.9

6.0 1.7 4.0 29.1 17.6 0.8 31.9 34.6 0.6 19.6 1.5 14.5 86.1 3.8 1.9

40

3.0 0.7 1.5 30.4 20.2 1.1 34.0 29.0 1.1 21.1 1.5 15.9 87.5 4.1 2.1

4.5 1.0 2.4 30.5 19.7 1.0 33.8 31.5 0.9 22.2 1.5 17.0 88.5 4.3 2.3

6.0 1.6 3.6 30.4 19.3 0.9 33.5 32.6 0.8 22.8 1.5 17.6 89.1 4.4 2.3

50

3.0 0.5 1.2 29.6 20.2 1.2 33.6 25.5 1.5 24.0 1.5 18.8 90.2 4.6 2.5

4.5 0.9 2.1 30.3 20.2 1.1 34.0 28.2 1.2 25.3 1.5 20.0 91.3 4.8 2.6

6.0 1.5 3.4 30.5 20.1 1.0 34.0 29.5 1.1 26.0 1.5 20.7 92.0 4.9 2.7

60

3.0 0.4 0.9 28.3 19.7 1.3 32.7 21.9 1.9 26.9 1.6 21.6 92.8 5.1 2.8

4.5 0.8 1.8 29.3 20.1 1.2 33.4 24.5 1.6 28.4 1.6 23.1 94.2 5.3 3.0

6.0 1.4 3.1 29.8 20.2 1.2 33.7 25.9 1.4 29.2 1.6 23.9 95.0 5.5 3.1

70

3.0 0.3 0.6 26.6 19.0 1.4 31.5 18.5 2.4 29.8 1.6 24.5 95.6 5.6 3.2

4.5 0.7 1.7 27.8 19.5 1.3 32.4 20.9 2.0 31.6 1.6 26.2 97.2 5.8 3.4

6.0 1.3 2.9 28.4 19.8 1.3 32.8 22.2 1.9 32.6 1.6 27.1 98.1 6.0 3.5

80

3.0 0.2 0.5 24.7 18.1 1.6 30.1 15.5 3.0 32.9 1.6 27.4 98.4 6.0 3.5

4.5 0.7 1.5 26.0 18.7 1.5 31.0 17.6 2.6 34.9 1.6 29.3 100.2 6.3 3.7

6.0 1.2 2.7 26.7 19.0 1.4 31.5 18.7 2.4 36.0 1.7 30.4 101.3 6.4 3.8

90

3.0 0.1 0.3 22.7 17.1 1.8 28.7 12.8 3.7 36.0 1.7 30.4 101.2 6.4 3.8

4.5 0.6 1.4 24.0 17.7 1.7 29.6 14.5 3.2 38.3 1.7 32.5 103.4 6.6 4.0

6.0 1.1 2.5 24.7 18.1 1.6 30.1 15.5 3.0 39.6 1.7 33.8 104.6 6.8 4.1

100

3.0 0.1 0.2 20.7 16.2 2.0 27.4 10.5 4.4

Operation not recommended

4.5 0.5 1.2 21.9 16.7 1.9 28.2 11.9 3.9

6.0 1.0 2.2 22.6 17.1 1.8 28.6 12.7 3.7

110

3.0 0.0 0.1 18.9 15.5 2.2 26.5 8.6 5.3

4.5 0.5 1.0 20.0 15.9 2.1 27.0 9.7 4.8

6.0 0.8 1.9 20.5 16.1 2.0 27.3 10.3 4.5

120

3.0 -0.0 0.1 17.5 15.1 2.5 26.0 7.1 6.3

4.5 0.3 0.8 18.3 15.3 2.3 26.2 7.9 5.7

6.0 0.6 1.5 18.7 15.4 2.2 26.4 8.4 5.4Interpolation is permissible; extrapolation is not.All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating. All performance data is based upon the lower voltage of dual voltage rated units.See performance correction tables for operating conditions other than those listed above..

Page 16: Submittal Data - Climate Master · The award winning Tranquility® Series raises the bar for water-source heat pump efficiencies, features and application flexibility. Not only does

ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.

Page ______ of ______LC377 - 16

Performance Data – TSH/V/D024 (ECM Blower)

950 CFM Nominal AirflowPerformance capacities shown in thousands of Btuh

TSH/V/D024 ECM

EWT °F GPM

WPD COOLING - EAT 80.6/66.2 °F HEATING - EAT 68°F

PSI Ft TC SC KW HR EER HWG Cap HC KW HE LAT COP HWG

Cap20 6.0 1.9 4.4 Operation not recommended 16.1 1.5 11.1 83.6 3.2 1.5

30

3.0 0.9 2.1 30.4 19.4 0.9 33.5 33.5 0.8 17.8 1.5 12.8 85.4 3.6 1.8

4.5 1.2 2.7 29.7 18.3 0.8 32.5 35.4 0.7 18.7 1.5 13.7 86.2 3.7 1.9

6.0 1.7 4.0 29.1 17.6 0.8 31.8 36.1 0.6 19.2 1.5 14.2 86.7 3.8 1.9

40

3.0 0.7 1.5 30.4 20.2 1.0 33.9 30.0 1.1 20.7 1.5 15.6 88.1 4.1 2.1

4.5 1.0 2.4 30.5 19.7 0.9 33.7 32.7 0.9 21.7 1.5 16.7 89.1 4.3 2.3

6.0 1.6 3.6 30.4 19.3 0.9 33.4 33.8 0.8 22.3 1.5 17.2 89.7 4.4 2.3

50

3.0 0.5 1.2 29.6 20.2 1.1 33.5 26.3 1.5 23.5 1.5 18.4 90.9 4.6 2.5

4.5 0.9 2.1 30.3 20.2 1.0 33.8 29.1 1.2 24.7 1.5 19.6 92.1 4.8 2.6

6.0 1.5 3.4 30.5 20.1 1.0 33.9 30.5 1.1 25.4 1.5 20.3 92.7 5.0 2.7

60

3.0 0.4 0.9 28.3 19.7 1.3 32.6 22.5 1.9 26.4 1.5 21.2 93.6 5.1 2.8

4.5 0.8 1.8 29.3 20.1 1.2 33.3 25.3 1.6 27.8 1.5 22.6 95.0 5.4 3.0

6.0 1.4 3.1 29.8 20.2 1.1 33.6 26.7 1.4 28.6 1.5 23.4 95.8 5.5 3.1

70

3.0 0.3 0.6 26.6 19.0 1.4 31.4 19.0 2.4 29.3 1.5 24.0 96.5 5.6 3.2

4.5 0.7 1.7 27.8 19.5 1.3 32.3 21.5 2.0 31.0 1.6 25.7 98.1 5.8 3.4

6.0 1.3 2.9 28.4 19.8 1.2 32.7 22.9 1.9 31.9 1.6 26.6 99.0 6.0 3.5

80

3.0 0.2 0.5 24.7 18.1 1.6 30.0 15.8 3.0 32.2 1.6 26.9 99.4 6.0 3.5

4.5 0.7 1.5 26.0 18.7 1.5 30.9 18.0 2.6 34.2 1.6 28.8 101.3 6.3 3.7

6.0 1.2 2.7 26.7 19.0 1.4 31.4 19.2 2.4 35.3 1.6 29.8 102.3 6.4 3.8

90

3.0 0.1 0.3 22.7 17.1 1.7 28.6 13.0 3.7 35.3 1.6 29.8 102.4 6.4 3.8

4.5 0.6 1.4 24.0 17.7 1.6 29.5 14.8 3.2 37.6 1.7 31.9 104.5 6.7 4.0

6.0 1.1 2.5 24.7 18.1 1.6 30.0 15.8 3.0 38.9 1.7 33.1 105.8 6.8 4.1

100

3.0 0.1 0.2 20.7 16.2 1.9 27.3 10.7 4.4

Operation not recommended

4.5 0.5 1.2 21.9 16.7 1.8 28.1 12.1 3.9

6.0 1.0 2.2 22.6 17.1 1.8 28.5 12.9 3.7

110

3.0 0.0 0.1 18.9 15.5 2.2 26.4 8.7 5.3

4.5 0.5 1.0 20.0 15.9 2.0 26.9 9.8 4.8

6.0 0.8 1.9 20.5 16.1 2.0 27.2 10.5 4.5

120

3.0 -0.0 0.1 17.5 15.1 2.4 25.8 7.2 6.3

4.5 0.3 0.8 18.3 15.3 2.3 26.1 8.0 5.7

6.0 0.6 1.5 18.7 15.4 2.2 26.3 8.5 5.4Interpolation is permissible; extrapolation is not.All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating. All performance data is based upon the lower voltage of dual voltage rated units.See performance correction tables for operating conditions other than those listed above..

Page 17: Submittal Data - Climate Master · The award winning Tranquility® Series raises the bar for water-source heat pump efficiencies, features and application flexibility. Not only does

ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.

Page ______ of ______LC377 - 17

Performance Data – TSH/V/D030 (PSC Blower)

1,000 CFM Nominal AirflowPerformance capacities shown in thousands of Btuh

TSH/V/D030 PSC

EWT °F GPM

WPD COOLING - EAT 80.6/66.2 °F HEATING - EAT 68°F

PSI Ft TC SC KW HR EER HWG Cap HC KW HE LAT COP HWG

Cap20 7.5 2.7 6.2 Operation not recommended 19.4 1.8 13.2 85.9 3.1 1.5

30

3.8 0.9 2.0 34.4 21.4 1.2 38.5 28.6 0.8 21.6 1.9 15.2 88.0 3.4 1.7

5.6 1.6 3.7 33.4 20.4 1.1 37.2 29.5 0.7 22.6 1.9 16.2 88.9 3.5 1.8

7.5 2.5 5.7 32.6 19.7 1.1 36.4 29.8 0.6 23.1 1.9 16.7 89.3 3.6 1.9

40

3.8 0.8 1.9 34.7 22.1 1.3 39.2 26.2 1.1 25.0 1.9 18.5 91.1 3.8 2.0

5.6 1.5 3.4 34.6 21.7 1.2 38.9 27.9 0.9 26.2 1.9 19.6 92.2 4.0 2.2

7.5 2.3 5.3 34.4 21.3 1.2 38.5 28.6 0.8 26.8 1.9 20.3 92.8 4.1 2.3

50

3.8 0.8 1.8 34.0 22.1 1.5 39.0 23.4 1.4 28.4 1.9 21.8 94.2 4.3 2.4

5.6 1.4 3.2 34.6 22.2 1.4 39.3 25.4 1.2 29.8 2.0 23.1 95.5 4.5 2.6

7.5 2.2 5.0 34.7 22.1 1.3 39.2 26.3 1.0 30.6 2.0 23.9 96.2 4.6 2.7

60

3.8 0.7 1.7 32.6 21.6 1.6 38.1 20.3 1.8 31.8 2.0 25.1 97.4 4.7 2.7

5.6 1.3 3.1 33.7 22.0 1.5 38.8 22.4 1.5 33.4 2.0 26.6 98.9 4.9 2.9

7.5 2.1 4.8 34.1 22.1 1.5 39.0 23.5 1.4 34.3 2.0 27.5 99.7 5.0 3.0

70

3.8 0.7 1.7 30.8 20.9 1.8 36.8 17.4 2.3 35.2 2.0 28.4 100.5 5.1 3.0

5.6 1.3 3.0 32.1 21.4 1.7 37.7 19.4 2.0 37.0 2.0 30.1 102.2 5.3 3.3

7.5 2.0 4.7 32.7 21.7 1.6 38.1 20.4 1.8 38.0 2.0 31.0 103.1 5.5 3.4

80

3.8 0.7 1.7 28.7 19.9 2.0 35.4 14.7 2.9 38.6 2.1 31.6 103.6 5.5 3.4

5.6 1.3 3.0 30.1 20.5 1.8 36.3 16.4 2.5 40.6 2.1 33.5 105.5 5.7 3.6

7.5 2.0 4.6 30.8 20.9 1.8 36.8 17.4 2.3 41.7 2.1 34.5 106.5 5.8 3.7

90

3.8 0.7 1.7 26.5 18.9 2.2 33.9 12.2 3.6 41.9 2.1 34.7 106.7 5.8 3.7

5.6 1.3 2.9 27.9 19.5 2.0 34.8 13.7 3.2 44.1 2.2 36.8 108.7 6.0 3.9

7.5 2.0 4.5 28.6 19.9 2.0 35.3 14.5 3.0 45.3 2.2 37.8 109.8 6.1 4.1

100

3.8 0.7 1.7 24.3 18.0 2.4 32.5 10.1 4.3

Operation not recommended

5.6 1.3 2.9 25.6 18.5 2.3 33.3 11.3 3.9

7.5 1.9 4.5 26.3 18.8 2.2 33.7 12.0 3.7

110

3.8 0.7 1.7 22.4 17.3 2.7 31.5 8.4 5.2

5.6 1.2 2.9 23.5 17.7 2.5 32.0 9.3 4.7

7.5 1.9 4.4 24.0 17.9 2.4 32.4 9.9 4.5

120

3.8 0.7 1.6 20.9 17.0 3.0 31.1 7.0 6.2

5.6 1.2 2.8 21.7 17.1 2.8 31.2 7.7 5.6

7.5 1.9 4.3 22.1 17.2 2.7 31.4 8.1 5.4Interpolation is permissible; extrapolation is not.All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating. All performance data is based upon the lower voltage of dual voltage rated units.See performance correction tables for operating conditions other than those listed above..

Page 18: Submittal Data - Climate Master · The award winning Tranquility® Series raises the bar for water-source heat pump efficiencies, features and application flexibility. Not only does

ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.

Page ______ of ______LC377 - 18

Performance Data – TSH/V/D030 (ECM Blower)

1,000 CFM Nominal Airflow Cooling, 1,100 CFM NominaAirflow HeatingPerformance capacities shown in thousands of Btuh

TSH/V/D030 ECM

EWT °F GPM

WPD COOLING - EAT 80.6/66.2 °F HEATING - EAT 68°F

PSI Ft TC SC KW HR EER HWG Cap HC KW HE LAT COP HWG

Cap20 7.5 2.7 6.2 Operation not recommended 19.7 1.9 13.3 86.2 3.1 1.5

30

3.8 0.9 2.0 34.4 21.4 1.2 38.4 29.5 0.8 21.9 1.9 15.4 88.2 3.4 1.7

5.6 1.6 3.7 33.4 20.3 1.1 37.1 30.6 0.7 22.9 1.9 16.4 89.1 3.5 1.8

7.5 2.5 5.7 32.6 19.7 1.1 36.2 30.9 0.6 23.4 1.9 16.9 89.6 3.6 1.9

40

3.8 0.8 1.9 34.7 22.1 1.3 39.1 27.0 1.1 25.3 1.9 18.7 91.4 3.8 2.0

5.6 1.5 3.4 34.6 21.7 1.2 38.7 28.9 0.9 26.5 2.0 19.9 92.5 4.0 2.2

7.5 2.3 5.3 34.4 21.3 1.2 38.3 29.6 0.8 27.2 2.0 20.5 93.1 4.1 2.3

50

3.8 0.8 1.8 34.0 22.1 1.4 38.9 24.0 1.4 28.7 2.0 22.0 94.6 4.3 2.4

5.6 1.4 3.2 34.6 22.2 1.3 39.1 26.2 1.2 30.2 2.0 23.4 95.9 4.5 2.6

7.5 2.2 5.0 34.7 22.1 1.3 39.1 27.2 1.0 31.0 2.0 24.2 96.6 4.6 2.7

60

3.8 0.7 1.7 32.7 21.6 1.6 38.0 20.9 1.8 32.2 2.0 25.4 97.7 4.7 2.7

5.6 1.3 3.1 33.7 22.0 1.5 38.7 23.0 1.5 33.8 2.0 26.9 99.2 4.9 2.9

7.5 2.1 4.8 34.1 22.1 1.4 38.9 24.1 1.4 34.7 2.0 27.8 100.1 5.0 3.0

70

3.8 0.7 1.7 30.8 20.9 1.7 36.7 17.8 2.3 35.6 2.0 28.7 100.9 5.1 3.0

5.6 1.3 3.0 32.1 21.4 1.6 37.6 19.8 2.0 37.4 2.1 30.4 102.6 5.3 3.3

7.5 2.0 4.7 32.7 21.7 1.6 38.0 20.9 1.8 38.5 2.1 31.4 103.5 5.5 3.4

80

3.8 0.7 1.7 28.7 19.9 1.9 35.2 15.0 2.9 39.0 2.1 31.9 104.0 5.5 3.4

5.6 1.3 3.0 30.1 20.6 1.8 36.2 16.8 2.5 41.0 2.1 33.9 105.9 5.7 3.6

7.5 2.0 4.6 30.8 20.9 1.7 36.7 17.8 2.3 42.1 2.1 34.9 106.9 5.8 3.7

90

3.8 0.7 1.7 26.5 18.9 2.1 33.8 12.5 3.6 42.4 2.1 35.1 107.2 5.8 3.7

5.6 1.3 2.9 27.9 19.6 2.0 34.7 14.0 3.2 44.6 2.2 37.2 109.2 6.0 3.9

7.5 2.0 4.5 28.6 19.9 1.9 35.2 14.8 3.0 45.8 2.2 38.2 110.3 6.1 4.1

100

3.8 0.7 1.7 24.3 18.0 2.4 32.4 10.3 4.3

Operation not recommended

5.6 1.3 2.9 25.6 18.5 2.2 33.2 11.5 3.9

7.5 1.9 4.5 26.3 18.8 2.2 33.6 12.2 3.7

110

3.8 0.7 1.7 22.4 17.3 2.6 31.4 8.5 5.2

5.6 1.2 2.9 23.5 17.7 2.5 31.9 9.5 4.7

7.5 1.9 4.4 24.1 17.9 2.4 32.2 10.0 4.5

120

3.8 0.7 1.6 20.9 17.0 3.0 31.0 7.1 6.2

5.6 1.2 2.8 21.7 17.1 2.8 31.1 7.8 5.6

7.5 1.9 4.3 22.12 17.21 2.68 31.28 8.2 5.4Interpolation is permissible; extrapolation is not.All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating. All performance data is based upon the lower voltage of dual voltage rated units.See performance correction tables for operating conditions other than those listed above..

Page 19: Submittal Data - Climate Master · The award winning Tranquility® Series raises the bar for water-source heat pump efficiencies, features and application flexibility. Not only does

ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.

Page ______ of ______LC377 - 19

Performance Data – TSH/V/D036 (PSC Blower)

1,200 CFM Nominal AirflowPerformance capacities shown in thousands of Btuh

TSH/V/D036 PSC

EWT °F GPM

WPD COOLING - EAT 80.6/66.2 °F HEATING - EAT 68°F

PSI Ft TC SC KW HR EER HWG Cap HC KW HE LAT COP HWG

Cap20 9.0 4.3 9.9 Operation not recommended 23.3 2.1 16.1 86.0 3.2 2.1

30

4.5 1.2 2.8 35.8 21.9 1.4 40.5 25.9 1.0 25.5 2.1 18.2 87.6 3.5 2.4

6.8 2.4 5.5 33.7 20.2 1.3 38.2 25.6 0.8 26.5 2.1 19.2 88.4 3.6 2.6

9.0 3.8 8.8 32.5 19.4 1.3 36.9 25.1 0.8 27.1 2.1 19.8 88.8 3.7 2.7

40

4.5 1.0 2.3 37.8 23.9 1.5 42.9 24.9 1.3 29.2 2.2 21.8 90.5 4.0 2.9

6.8 2.1 4.8 36.8 22.8 1.4 41.6 25.7 1.1 30.5 2.2 23.1 91.5 4.1 3.1

9.0 3.4 7.9 36.0 22.1 1.4 40.8 25.9 1.0 31.3 2.2 23.8 92.1 4.2 3.2

50

4.5 0.9 2.0 38.3 25.0 1.7 44.0 22.9 1.8 33.2 2.2 25.6 93.5 4.4 3.4

6.8 1.9 4.4 38.1 24.4 1.6 43.4 24.3 1.5 34.8 2.2 27.2 94.8 4.6 3.6

9.0 3.2 7.3 37.8 24.0 1.5 43.0 24.9 1.3 35.8 2.3 28.1 95.5 4.7 3.7

60

4.5 0.8 1.9 37.7 25.4 1.9 44.0 20.4 2.5 37.3 2.3 29.6 96.7 4.8 3.9

6.8 1.8 4.1 38.2 25.2 1.7 44.1 22.1 2.0 39.2 2.3 31.4 98.2 5.0 4.1

9.0 3.0 6.9 38.3 25.0 1.7 44.0 22.9 1.8 40.3 2.3 32.4 99.0 5.1 4.2

70

4.5 0.8 1.8 36.3 25.3 2.0 43.3 17.8 3.3 41.4 2.3 33.5 99.9 5.2 4.4

6.8 1.7 3.9 37.3 25.5 1.9 43.8 19.5 2.7 43.5 2.4 35.4 101.5 5.4 4.6

9.0 2.9 6.6 37.6 25.4 1.9 44.0 20.4 2.5 44.6 2.4 36.5 102.4 5.5 4.7

80

4.5 0.8 1.8 34.5 24.7 2.3 42.2 15.2 4.2 45.3 2.4 37.1 102.9 5.5 4.8

6.8 1.7 3.8 35.7 25.1 2.1 42.9 16.8 3.6 47.5 2.4 39.1 104.5 5.7 5.1

9.0 2.8 6.4 36.3 25.3 2.1 43.3 17.7 3.3 48.5 2.5 40.1 105.4 5.8 5.2

90

4.5 0.8 1.8 32.3 23.8 2.5 40.8 12.9 5.2 48.9 2.5 40.5 105.6 5.8 5.3

6.8 1.6 3.8 33.7 24.4 2.4 41.7 14.3 4.6 50.8 2.5 42.3 107.1 6.0 5.5

9.0 2.7 6.3 34.3 24.7 2.3 42.1 15.1 4.2 51.75 2.52 43.16 107.8 6 5.7

100

4.5 0.8 1.8 30.0 22.6 2.8 39.4 10.8 6.4

Operation not recommended

6.8 1.6 3.7 31.4 23.3 2.6 40.2 12.0 5.7

9.0 2.7 6.2 32.1 23.7 2.5 40.7 12.7 5.3

110

4.5 0.7 1.7 27.6 21.2 3.1 38.1 9.0 7.7

6.8 1.6 3.6 29.0 22.0 2.9 38.8 10.0 7.0

9.0 2.6 6.1 29.7 22.4 2.8 39.2 10.6 6.6

120

4.5 0.6 1.5 25.5 19.9 3.4 37.0 7.6 9.2

6.8 1.5 3.4 26.6 20.6 3.2 37.5 8.3 8.4

9.0 2.5 5.9 27.28 21.02 3.1 37.87 8.8 8Interpolation is permissible; extrapolation is not.All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating. All performance data is based upon the lower voltage of dual voltage rated units.See performance correction tables for operating conditions other than those listed above..

Page 20: Submittal Data - Climate Master · The award winning Tranquility® Series raises the bar for water-source heat pump efficiencies, features and application flexibility. Not only does

ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.

Page ______ of ______LC377 - 20

Performance Data – TSH/V/D036 (ECM Blower)

1,200 CFM Nominal AirflowPerformance capacities shown in thousands of Btuh

TSH/V/D036 ECM

EWT °F GPM

WPD COOLING - EAT 80.6/66.2 °F HEATING - EAT 68°F

PSI Ft TC SC KW HR EER HWG Cap HC KW HE LAT COP HWG

Cap20 9.0 4.3 9.9 Operation not recommended 22.7 1.9 16.3 85.5 3.6 2.1

30

4.5 1.2 2.8 36.9 22.7 1.1 40.8 32.5 1.0 24.8 1.9 18.4 87.1 3.9 2.4

6.8 2.4 5.5 34.8 20.6 1.1 38.4 32.7 0.8 25.8 1.9 19.4 87.9 4.0 2.6

9.0 3.8 8.8 33.5 19.5 1.0 37.0 32.5 0.8 26.4 1.9 20.0 88.3 4.1 2.7

40

4.5 1.0 2.3 39.0 25.3 1.3 43.3 30.5 1.3 28.5 1.9 22.0 90.0 4.4 2.9

6.8 2.1 4.8 37.9 23.9 1.2 41.9 31.9 1.1 29.9 1.9 23.3 91.0 4.5 3.1

9.0 3.4 7.9 37.2 23.0 1.2 41.1 32.4 1.0 30.6 1.9 24.0 91.6 4.6 3.2

50

4.5 0.9 2.0 39.4 26.7 1.4 44.3 27.5 1.8 32.5 2.0 25.8 93.0 4.9 3.4

6.8 1.9 4.4 39.3 25.9 1.3 43.8 29.5 1.5 34.1 2.0 27.4 94.3 5.1 3.6

9.0 3.2 7.3 39.0 25.4 1.3 43.4 30.4 1.3 35.0 2.0 28.2 95.0 5.2 3.7

60

4.5 0.8 1.9 38.9 27.2 1.6 44.3 24.1 2.5 36.6 2.0 29.7 96.1 5.3 3.9

6.8 1.8 4.1 39.3 27.0 1.5 44.4 26.3 2.0 38.5 2.0 31.5 97.6 5.5 4.1

9.0 3.0 6.9 39.4 26.7 1.4 44.4 27.4 1.8 39.5 2.1 32.5 98.4 5.6 4.2

70

4.5 0.8 1.8 37.5 27.0 1.8 43.6 20.8 3.3 40.6 2.1 33.5 99.3 5.7 4.4

6.8 1.7 3.9 38.5 27.2 1.7 44.2 22.9 2.7 42.7 2.1 35.5 100.9 5.9 4.6

9.0 2.9 6.6 38.8 27.2 1.6 44.3 24.1 2.5 43.8 2.1 36.6 101.7 6.0 4.7

80

4.5 0.8 1.8 35.6 26.3 2.0 42.5 17.6 4.2 44.5 2.1 37.2 102.3 6.1 4.8

6.8 1.7 3.8 36.8 26.8 1.9 43.3 19.6 3.6 46.6 2.2 39.2 103.9 6.3 5.1

9.0 2.8 6.4 37.4 27.0 1.8 43.6 20.7 3.3 47.7 2.2 40.3 104.7 6.4 5.2

90

4.5 0.8 1.8 33.3 25.2 2.3 41.0 14.8 5.2 48.1 2.2 40.6 105.0 6.4 5.3

6.8 1.6 3.8 34.7 25.9 2.1 41.9 16.5 4.6 50.1 2.2 42.5 106.6 6.6 5.5

9.0 2.7 6.3 35.4 26.2 2.0 42.4 17.4 4.2 51.0 2.3 43.4 107.3 6.7 5.7

100

4.5 0.8 1.8 30.9 24.0 2.5 39.5 12.3 6.4

Operation not recommended

6.8 1.6 3.7 32.4 24.7 2.4 40.4 13.7 5.7

9.0 2.7 6.2 33.1 25.1 2.3 40.9 14.5 5.3

110

4.5 0.7 1.7 28.4 22.6 2.8 38.0 10.1 7.7

6.8 1.6 3.6 29.8 23.4 2.6 38.8 11.3 7.0

9.0 2.6 6.1 30.6 23.8 2.6 39.3 12.0 6.6

120

4.5 0.6 1.5 26.1 21.4 3.1 36.8 8.3 9.2

6.8 1.5 3.4 27.3 22.1 3.0 37.4 9.3 8.4

9.0 2.5 5.9 28.0 22.4 2.9 37.8 9.8 8.0Interpolation is permissible; extrapolation is not.All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating. All performance data is based upon the lower voltage of dual voltage rated units.See performance correction tables for operating conditions other than those listed above..

Page 21: Submittal Data - Climate Master · The award winning Tranquility® Series raises the bar for water-source heat pump efficiencies, features and application flexibility. Not only does

ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.

Page ______ of ______LC377 - 21

Performance Data – TSH/V/D042 (PSC Blower)

1,400 CFM Nominal AirflowPerformance capacities shown in thousands of Btuh

TSH/V/D042 PSC

EWT °F GPM

WPD COOLING - EAT 80.6/66.2 °F HEATING - EAT 68°F

PSI Ft TC SC KW HR EER HWG Cap HC KW HE LAT COP HWG

Cap20 10.5 3.7 8.6 Operation not recommended 27.2 2.5 18.8 86.0 3.2 3.3

30

5.3 1.0 2.3 42.7 27.1 1.4 47.6 30.1 1.8 30.0 2.5 21.6 87.8 3.6 3.5

7.9 2.0 4.6 39.4 23.7 1.3 43.9 29.5 1.9 31.3 2.4 23.0 88.6 3.8 3.6

10.5 3.4 7.9 37.4 21.8 1.3 41.8 28.8 1.9 32.0 2.4 23.7 89.1 3.8 3.6

40

5.3 0.9 2.0 45.7 30.7 1.6 51.1 29.0 1.9 34.5 2.4 26.2 90.8 4.2 3.8

7.9 1.9 4.3 44.2 28.8 1.5 49.3 29.9 1.8 36.1 2.4 27.8 91.8 4.3 3.8

10.5 3.2 7.5 43.1 27.5 1.4 48.0 30.1 1.8 37.1 2.4 28.7 92.5 4.5 3.9

50

5.3 0.8 1.9 46.2 32.0 1.8 52.2 26.4 2.3 39.2 2.5 30.9 93.9 4.7 4.1

7.9 1.7 4.0 46.1 31.4 1.6 51.7 28.2 2.0 41.2 2.5 32.8 95.2 4.9 4.2

10.5 3.1 7.1 45.8 30.8 1.6 51.2 28.9 2.0 42.3 2.5 33.9 95.9 5.0 4.2

60

5.3 0.8 1.8 45.1 31.9 1.9 51.7 23.3 2.8 44.1 2.5 35.6 97.1 5.2 4.4

7.9 1.7 3.9 46.0 32.1 1.8 52.1 25.4 2.5 46.4 2.5 37.9 98.6 5.4 4.6

10.5 3.0 6.9 46.2 32.0 1.8 52.2 26.4 2.3 47.7 2.5 39.2 99.5 5.6 4.7

70

5.3 0.8 1.7 43.0 30.8 2.1 50.3 20.1 3.5 49.0 2.5 40.4 100.3 5.7 4.8

7.9 1.6 3.8 44.5 31.6 2.0 51.3 22.2 3.1 51.8 2.6 43.0 102.1 5.9 5.0

10.5 2.9 6.8 45.1 31.9 1.9 51.7 23.3 2.8 53.3 2.6 44.4 103.1 6.0 5.1

80

5.3 0.8 1.8 40.4 29.2 2.4 48.5 17.0 4.4 54.0 2.6 45.1 103.7 6.1 5.3

7.9 1.6 3.7 42.1 30.2 2.2 49.7 18.9 3.8 57.1 2.7 48.0 105.7 6.3 5.5

10.5 2.9 6.7 42.9 30.7 2.2 50.3 19.9 3.6 58.8 2.7 49.6 106.8 6.3 5.7

90

5.3 0.8 1.8 37.5 27.4 2.6 46.5 14.2 5.4 59.1 2.7 49.8 107.0 6.4 5.8

7.9 1.6 3.7 39.2 28.5 2.5 47.7 15.9 4.8 62.5 2.8 52.9 109.2 6.5 6.1

10.5 2.9 6.6 40.1 29.0 2.4 48.3 16.8 4.5 64.4 2.9 54.6 110.5 6.6 6.3

100

5.3 0.8 1.8 34.6 25.8 2.9 44.6 11.8 6.7

Operation not recommended

7.9 1.6 3.7 36.2 26.7 2.8 45.7 13.1 5.9

10.5 2.8 6.5 37.1 27.2 2.7 46.2 13.9 5.6

110

5.3 0.8 1.7 32.2 24.6 3.3 43.4 9.8 8.1

7.9 1.6 3.6 33.5 25.2 3.1 44.0 10.8 7.3

10.5 2.8 6.4 34.2 25.5 3.0 44.4 11.4 6.9

120

5.3 0.7 1.6 30.5 24.3 3.7 43.1 8.2 9.8

7.9 1.5 3.5 31.3 24.3 3.5 43.1 9.0 8.8

10.5 2.7 6.3 31.8 24.4 3.4 43.2 9.5 8.4Interpolation is permissible; extrapolation is not.All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating. All performance data is based upon the lower voltage of dual voltage rated units.See performance correction tables for operating conditions other than those listed above..

Page 22: Submittal Data - Climate Master · The award winning Tranquility® Series raises the bar for water-source heat pump efficiencies, features and application flexibility. Not only does

ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.

Page ______ of ______LC377 - 22

Performance Data – TSH/V/D042 (ECM Blower)

1,400 CFM Nominal AirflowPerformance capacities shown in thousands of Btuh

TSH/V/D042 ECM

EWT °F GPM

WPD COOLING - EAT 80.6/66.2 °F HEATING - EAT 68°F

PSI Ft TC SC KW HR EER HWG Cap HC KW HE LAT COP HWG

Cap20 10.5 3.7 8.6 Operation not recommended 25.6 2.3 17.7 84.9 3.3 3.3

30

5.3 1.0 2.3 42.6 27.0 1.3 47.0 33.7 1.8 28.3 2.3 20.5 86.6 3.6 3.5

7.9 2.0 4.6 39.3 23.6 1.2 43.3 33.3 1.9 29.4 2.3 21.6 87.4 3.8 3.6

10.5 3.4 7.9 37.3 21.8 1.1 41.2 32.6 1.9 30.0 2.3 22.3 87.8 3.9 3.6

40

5.3 0.9 2.0 45.7 30.7 1.4 50.5 32.1 1.9 32.5 2.3 24.8 89.5 4.2 3.8

7.9 1.9 4.3 44.2 28.7 1.3 48.7 33.4 1.8 34.0 2.3 26.2 90.4 4.4 3.8

10.5 3.2 7.5 43.1 27.5 1.3 47.5 33.7 1.8 34.8 2.3 27.0 91.0 4.5 3.9

50

5.3 0.8 1.9 46.2 32.0 1.6 51.6 29.0 2.3 37.0 2.3 29.2 92.4 4.7 4.1

7.9 1.7 4.0 46.1 31.4 1.5 51.2 31.1 2.0 38.8 2.3 31.0 93.6 4.9 4.2

10.5 3.1 7.1 45.7 30.7 1.4 50.6 32.0 2.0 39.8 2.3 31.9 94.3 5.1 4.2

60

5.3 0.8 1.8 45.1 31.9 1.8 51.2 25.4 2.8 41.6 2.3 33.7 95.5 5.3 4.4

7.9 1.7 3.9 46.0 32.1 1.7 51.6 27.8 2.5 43.8 2.3 35.8 96.9 5.5 4.6

10.5 3.0 6.9 46.2 32.0 1.6 51.6 29.0 2.3 45.0 2.4 36.9 97.7 5.6 4.7

70

5.3 0.8 1.7 43.1 30.8 2.0 49.8 21.7 3.5 46.4 2.4 38.3 98.6 5.7 4.8

7.9 1.6 3.8 44.5 31.6 1.9 50.8 24.1 3.1 48.9 2.4 40.6 100.3 5.9 5.0

10.5 2.9 6.8 45.1 31.9 1.8 51.2 25.3 2.8 50.3 2.4 41.9 101.2 6.0 5.1

80

5.3 0.8 1.8 40.4 29.2 2.2 48.0 18.2 4.4 51.3 2.5 42.8 101.8 6.1 5.3

7.9 1.6 3.7 42.1 30.2 2.1 49.2 20.4 3.8 54.1 2.5 45.5 103.7 6.3 5.5

10.5 2.9 6.7 42.9 30.7 2.0 49.7 21.5 3.6 55.7 2.6 46.9 104.7 6.4 5.7

90

5.3 0.8 1.8 37.5 27.4 2.5 46.0 15.1 5.4 56.2 2.6 47.4 105.1 6.4 5.8

7.9 1.6 3.7 39.3 28.5 2.3 47.2 16.9 4.8 59.4 2.7 50.3 107.2 6.5 6.1

10.5 2.9 6.6 40.2 29.1 2.2 47.8 17.9 4.5 61.1 2.7 51.8 108.3 6.6 6.3

100

5.3 0.8 1.8 34.7 25.8 2.8 44.2 12.5 6.6

Operation not recommended

7.9 1.6 3.7 36.3 26.7 2.6 45.2 13.9 5.9

10.5 2.8 6.5 37.1 27.2 2.5 45.7 14.8 5.6

110

5.3 0.8 1.7 32.2 24.6 3.1 42.9 10.3 8.1

7.9 1.6 3.6 33.5 25.2 2.9 43.5 11.4 7.3

10.5 2.8 6.4 34.2 25.6 2.8 43.9 12.1 6.9

120

5.3 0.7 1.6 30.5 24.2 3.5 42.6 8.6 9.8

7.9 1.5 3.5 31.3 24.3 3.3 42.6 9.5 8.8

10.5 2.7 6.3 31.8 24.5 3.2 42.7 9.9 8.4Interpolation is permissible; extrapolation is not.All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating. All performance data is based upon the lower voltage of dual voltage rated units.See performance correction tables for operating conditions other than those listed above..

Page 23: Submittal Data - Climate Master · The award winning Tranquility® Series raises the bar for water-source heat pump efficiencies, features and application flexibility. Not only does

ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.

Page ______ of ______LC377 - 23

Performance Data – TSH/V/D048 (PSC Blower)

1,600 CFM Nominal AirflowPerformance capacities shown in thousands of Btuh

TSH/V/D048 PSC

EWT °F GPM

WPD COOLING - EAT 80.6/66.2 °F HEATING - EAT 68°F

PSI Ft TC SC KW HR EER HWG Cap HC KW HE LAT COP HWG

Cap20 12.0 4.2 9.6 Operation not recommended 36.1 3.4 24.6 88.9 3.1 3.3

30

6.0 1.1 2.6 51.7 31.0 2.1 58.9 24.5 1.8 39.0 3.4 27.6 90.5 3.4 3.5

9.0 2.3 5.3 48.0 27.7 2.0 54.7 24.6 1.9 40.7 3.4 29.2 91.5 3.5 3.5

12.0 3.8 8.7 45.9 25.9 1.9 52.3 24.4 1.9 41.6 3.4 30.1 92.0 3.6 3.6

40

6.0 0.9 2.2 54.8 34.5 2.4 62.8 23.3 2.0 44.2 3.4 32.7 93.5 3.8 3.7

9.0 2.1 4.8 53.1 32.4 2.2 60.5 24.3 1.8 46.3 3.4 34.7 94.7 4.0 3.8

12.0 3.5 8.0 51.8 31.1 2.1 59.0 24.5 1.8 47.5 3.4 35.8 95.4 4.1 3.9

50

6.0 0.8 1.9 55.4 36.0 2.6 64.3 21.4 2.4 49.7 3.5 37.9 96.7 4.2 4.0

9.0 1.9 4.4 55.2 35.1 2.4 63.5 22.8 2.1 52.2 3.5 40.3 98.1 4.4 4.1

12.0 3.3 7.6 54.7 34.4 2.3 62.7 23.4 2.0 53.6 3.5 41.6 98.9 4.5 4.2

60

6.0 0.8 1.8 54.4 36.3 2.9 64.1 19.1 2.9 55.3 3.6 43.2 99.9 4.6 4.3

9.0 1.8 4.2 55.3 36.2 2.7 64.4 20.7 2.5 58.2 3.6 45.9 101.6 4.7 4.5

12.0 3.1 7.3 55.4 36.0 2.6 64.2 21.5 2.3 59.8 3.6 47.4 102.5 4.8 4.6

70

6.0 0.8 1.7 52.3 35.6 3.1 63.0 16.7 3.7 61.0 3.7 48.5 103.2 4.9 4.7

9.0 1.8 4.1 53.9 36.1 2.9 63.9 18.4 3.1 64.2 3.7 51.5 105.1 5.1 5.0

12.0 3.1 7.1 54.5 36.3 2.8 64.2 19.2 2.9 66.0 3.8 53.2 106.1 5.1 5.1

80

6.0 0.8 1.7 49.4 34.3 3.4 61.2 14.4 4.6 66.6 3.8 53.8 106.5 5.2 5.2

9.0 1.7 4.0 51.5 35.2 3.2 62.5 16.0 3.9 70.1 3.9 57.0 108.5 5.3 5.5

12.0 3.0 7.0 52.4 35.6 3.1 63.0 16.8 3.6 72.0 3.9 58.8 109.6 5.4 5.6

90

6.0 0.8 1.8 46.2 32.7 3.8 59.1 12.2 5.7 72.1 3.9 58.9 109.7 5.4 5.7

9.0 1.7 4.0 48.4 33.8 3.6 60.5 13.6 4.9 75.8 4.0 62.3 111.8 5.6 6.0

12.0 3.0 6.9 49.5 34.3 3.4 61.2 14.4 4.6 77.8 4.0 64.1 112.9 5.7 6.2

100

6.0 0.8 1.7 42.8 31.0 4.2 57.1 10.2 6.9

Operation not recommended

9.0 1.7 3.9 45.0 32.1 3.9 58.4 11.5 6.1

12.0 3.0 6.8 46.1 32.7 3.8 59.1 12.2 5.7

110

6.0 0.7 1.7 39.5 29.4 4.6 55.3 8.5 8.4

9.0 1.7 3.9 41.5 30.4 4.3 56.3 9.6 7.5

12.0 2.9 6.7 42.6 30.9 4.2 57.0 10.1 7.0

120

6.0 0.7 1.5 36.6 28.2 5.2 54.2 7.1 10.0

9.0 1.6 3.7 38.3 28.9 4.8 54.8 7.9 9.0

12.0 2.8 6.5 39.3 29.3 4.7 55.2 8.4 8.5Interpolation is permissible; extrapolation is not.All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating. All performance data is based upon the lower voltage of dual voltage rated units.See performance correction tables for operating conditions other than those listed above..

Page 24: Submittal Data - Climate Master · The award winning Tranquility® Series raises the bar for water-source heat pump efficiencies, features and application flexibility. Not only does

ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.

Page ______ of ______LC377 - 24

Performance Data – TSH/V/D048 (ECM Blower)

1,550 CFM Nominal Airflow Cooling, 1,650 CFM Nominal Airflow HeatingPerformance capacities shown in thousands of Btuh

TSH/V/D048 ECM

EWT °F GPM

WPD COOLING - EAT 80.6/66.2 °F HEATING - EAT 68°F

PSI Ft TC SC KW HR EER HWG Cap HC KW HE LAT COP HWG

Cap20 12.0 4.2 9.6 Operation not recommended 33.1 3.1 22.7 86.5 3.2 3.3

30

6.0 1.1 2.6 51.5 30.9 1.8 57.7 28.6 1.8 36.0 3.1 25.5 88.1 3.4 3.5

9.0 2.3 5.3 47.9 27.6 1.7 53.5 29.0 1.9 37.4 3.1 26.9 88.9 3.6 3.5

12.0 3.8 8.7 45.7 25.8 1.6 51.1 28.9 1.9 38.2 3.1 27.7 89.4 3.6 3.6

40

6.0 0.9 2.2 54.7 34.4 2.1 61.7 26.7 2.0 40.9 3.1 30.3 90.9 3.9 3.7

9.0 2.1 4.8 53.0 32.3 1.9 59.4 28.1 1.8 42.7 3.1 32.0 91.9 4.0 3.8

12.0 3.5 8.0 51.7 31.0 1.8 57.9 28.5 1.8 43.7 3.1 33.0 92.5 4.1 3.9

50

6.0 0.8 1.9 55.4 36.0 2.3 63.2 24.2 2.4 46.0 3.2 35.2 93.8 4.2 4.0

9.0 1.9 4.4 55.2 35.1 2.1 62.4 26.0 2.1 48.2 3.2 37.3 95.0 4.4 4.1

12.0 3.3 7.6 54.7 34.3 2.0 61.6 26.8 2.0 49.4 3.2 38.4 95.7 4.5 4.2

60

6.0 0.8 1.8 54.5 36.3 2.6 63.2 21.4 2.9 51.4 3.3 40.2 96.8 4.6 4.3

9.0 1.8 4.2 55.3 36.2 2.4 63.4 23.4 2.5 53.9 3.3 42.6 98.2 4.8 4.5

12.0 3.1 7.3 55.4 36.0 2.3 63.2 24.3 2.3 55.3 3.4 43.9 99.0 4.8 4.6

70

6.0 0.8 1.7 52.4 35.6 2.8 62.0 18.5 3.7 56.8 3.4 45.3 99.8 4.9 4.7

9.0 1.8 4.1 53.9 36.1 2.6 62.9 20.5 3.1 59.7 3.4 47.9 101.4 5.1 5.0

12.0 3.1 7.1 54.5 36.3 2.5 63.2 21.5 2.9 61.2 3.5 49.4 102.3 5.2 5.1

80

6.0 0.8 1.7 49.6 34.3 3.1 60.2 15.8 4.6 62.2 3.5 50.2 102.8 5.2 5.2

9.0 1.7 4.0 51.5 35.3 2.9 61.5 17.6 3.9 65.3 3.6 53.1 104.6 5.4 5.5

12.0 3.0 7.0 52.5 35.6 2.8 62.1 18.6 3.6 67.0 3.6 54.7 105.5 5.5 5.6

90

6.0 0.8 1.8 46.3 32.8 3.5 58.2 13.3 5.7 67.4 3.6 55.1 105.8 5.5 5.7

9.0 1.7 4.0 48.5 33.8 3.3 59.6 14.9 4.9 70.7 3.7 58.2 107.6 5.6 6.0

12.0 3.0 6.9 49.6 34.4 3.1 60.3 15.8 4.6 72.5 3.7 59.8 108.6 5.7 6.2

100

6.0 0.8 1.7 42.9 31.0 3.9 56.1 11.1 6.9

Operation not recommended

9.0 1.7 3.9 45.1 32.1 3.6 57.4 12.5 6.1

12.0 3.0 6.8 46.2 32.7 3.5 58.1 13.2 5.7

110

6.0 0.7 1.7 39.6 29.4 4.3 54.4 9.2 8.4

9.0 1.7 3.9 41.6 30.4 4.0 55.4 10.3 7.5

12.0 2.9 6.7 42.7 30.9 3.9 56.0 11.0 7.0

120

6.0 0.7 1.5 36.7 28.2 4.8 53.2 7.6 10.0

9.0 1.6 3.7 38.4 28.9 4.5 53.8 8.5 9.0

12.0 2.8 6.5 39.3 29.3 4.4 54.2 9.0 8.5Interpolation is permissible; extrapolation is not.All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating. All performance data is based upon the lower voltage of dual voltage rated units.See performance correction tables for operating conditions other than those listed above..

Page 25: Submittal Data - Climate Master · The award winning Tranquility® Series raises the bar for water-source heat pump efficiencies, features and application flexibility. Not only does

ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.

Page ______ of ______LC377 - 25

Performance Data – TSH/V/D060 (PSC Blower)

1,950 CFM Nominal AirflowPerformance capacities shown in thousands of Btuh

TSH/V/D060 PSC

EWT °F GPM

WPD COOLING - EAT 80.6/66.2 °F HEATING - EAT 68°F

PSI Ft TC SC KW HR EER HWG Cap HC KW HE LAT COP HWG

Cap20 15.0 7.2 16.6 Operation not recommended 41.2 4.0 27.7 87.5 3.1 3.8

30

7.5 1.3 3.0 74.0 51.3 2.5 82.6 29.2 2.0 44.9 4.1 31.1 89.3 3.3 4.0

11.3 3.5 8.1 71.4 49.0 2.4 79.5 30.0 1.8 46.8 4.1 32.8 90.2 3.4 4.1

15.0 6.1 14.1 69.5 47.6 2.3 77.4 30.0 1.8 47.8 4.1 33.8 90.7 3.4 4.1

40

7.5 0.9 2.0 75.1 52.8 2.8 84.6 27.1 2.3 51.5 4.2 37.3 92.4 3.6 4.3

11.3 2.9 6.7 74.5 51.8 2.6 83.4 28.8 2.0 54.0 4.2 39.6 93.6 3.7 4.4

15.0 5.3 12.2 73.7 51.0 2.5 82.3 29.4 1.9 55.4 4.3 40.9 94.2 3.8 4.5

50

7.5 0.6 1.4 74.1 52.9 3.0 84.5 24.4 2.9 58.7 4.3 44.0 95.8 4.0 4.6

11.3 2.5 5.7 75.0 52.9 2.8 84.7 26.5 2.4 61.8 4.4 46.9 97.3 4.1 4.8

15.0 4.7 10.9 75.1 52.7 2.7 84.4 27.4 2.3 63.5 4.4 48.5 98.1 4.2 4.9

60

7.5 0.5 1.1 71.7 52.2 3.3 83.1 21.4 3.6 66.2 4.4 51.0 99.3 4.4 5.0

11.3 2.2 5.1 73.6 52.8 3.1 84.2 23.7 3.1 69.9 4.5 54.5 101.1 4.5 5.2

15.0 4.3 10.0 74.3 53.0 3.0 84.6 24.8 2.8 71.9 4.5 56.4 102.1 4.6 5.3

70

7.5 0.5 1.1 68.3 50.8 3.7 80.9 18.5 4.5 73.8 4.6 58.2 103.0 4.7 5.4

11.3 2.1 4.8 70.9 51.9 3.4 82.6 20.6 3.8 78.1 4.7 62.2 105.0 4.9 5.7

15.0 4.1 9.5 72.0 52.3 3.3 83.3 21.8 3.5 80.4 4.7 64.4 106.1 5.0 5.9

80

7.5 0.5 1.1 64.4 49.1 4.1 78.3 15.7 5.6 81.5 4.7 65.4 106.6 5.1 5.9

11.3 2.0 4.6 67.2 50.4 3.8 80.2 17.7 4.8 86.1 4.8 69.7 108.8 5.2 6.3

15.0 4.0 9.2 68.6 51.0 3.7 81.1 18.7 4.4 88.7 4.9 72.0 110.0 5.3 6.5

90

7.5 0.5 1.2 60.2 47.3 4.6 75.8 13.2 6.8 88.9 4.9 72.3 110.1 5.3 6.5

11.3 2.0 4.5 63.1 48.6 4.2 77.5 14.9 6.0 93.8 5.0 76.8 112.5 5.5 6.9

15.0 3.9 9.1 64.5 49.2 4.1 78.5 15.8 5.5 96.4 5.1 79.1 113.7 5.6 7.1

100

7.5 0.5 1.1 56.1 45.5 5.1 73.5 11.0 8.3

Operation not recommended

11.3 1.9 4.5 58.8 46.7 4.7 75.0 12.4 7.3

15.0 3.9 9.0 60.2 47.3 4.6 75.8 13.2 6.8

110

7.5 0.4 0.8 52.5 44.2 5.7 72.1 9.2 9.9

11.3 1.8 4.2 54.8 45.0 5.3 72.9 10.3 8.8

15.0 3.8 8.8 56.1 45.5 5.1 73.5 11.0 8.3

120

7.5 0.1 0.3 49.8 43.7 6.5 71.9 7.7 11.9

11.3 1.6 3.8 51.4 43.9 6.0 71.8 8.6 10.6

15.0 3.7 8.5 52.4 44.2 5.8 72.0 9.1 10.0Interpolation is permissible; extrapolation is not.All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating. All performance data is based upon the lower voltage of dual voltage rated units.See performance correction tables for operating conditions other than those listed above..

Page 26: Submittal Data - Climate Master · The award winning Tranquility® Series raises the bar for water-source heat pump efficiencies, features and application flexibility. Not only does

ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.

Page ______ of ______LC377 - 26

Performance Data – TSH/V/D060 (ECM Blower)

1,950 CFM Nominal Airflow Cooling, 2,050 CFM Nominal Airflow HeatingPerformance capacities shown in thousands of Btuh

TSH/V/D060 ECM

EWT °F GPM

WPD COOLING - EAT 80.6/66.2 °F HEATING - EAT 68°F

PSI Ft TC SC KW HR EER HWG Cap HC KW HE LAT COP HWG

Cap20 15.0 7.2 16.6 Operation not recommended 40.2 3.6 27.8 85.7 3.3 3.8

30

7.5 1.3 3.0 74.0 51.3 2.5 82.6 29.2 2.0 43.9 3.7 31.3 87.3 3.5 4.0

11.3 3.5 8.1 71.4 49.0 2.4 79.5 30.0 1.8 45.7 3.7 33.0 88.1 3.6 4.1

15.0 6.1 14.1 69.5 47.6 2.3 77.4 30.0 1.8 46.7 3.7 34.0 88.6 3.7 4.1

40

7.5 0.9 2.0 75.1 52.8 2.8 84.6 27.1 2.3 50.4 3.8 37.5 90.2 3.9 4.3

11.3 2.9 6.7 74.5 51.8 2.6 83.4 28.8 2.0 52.9 3.8 39.8 91.3 4.1 4.4

15.0 5.3 12.2 73.7 51.0 2.5 82.3 29.4 1.9 54.2 3.9 41.1 91.9 4.1 4.5

50

7.5 0.6 1.4 74.1 52.9 3.0 84.5 24.4 2.9 57.5 3.9 44.2 93.3 4.3 4.6

11.3 2.5 5.7 75.0 52.9 2.8 84.7 26.5 2.4 60.6 4.0 47.2 94.7 4.5 4.8

15.0 4.7 10.9 75.1 52.7 2.7 84.4 27.4 2.3 62.4 4.0 48.8 95.4 4.6 4.9

60

7.5 0.5 1.1 71.7 52.2 3.3 83.1 21.4 3.6 65.0 4.0 51.3 96.6 4.7 5.0

11.3 2.2 5.1 73.6 52.8 3.1 84.2 23.7 3.1 68.7 4.1 54.8 98.2 4.9 5.2

15.0 4.3 10.0 74.3 53.0 3.0 84.6 24.8 2.8 70.8 4.1 56.7 99.1 5.0 5.3

70

7.5 0.5 1.1 68.3 50.8 3.7 80.9 18.5 4.5 72.7 4.2 58.5 100.0 5.1 5.4

11.3 2.1 4.8 70.9 51.9 3.4 82.6 20.6 3.8 76.9 4.2 62.4 101.8 5.3 5.7

15.0 4.1 9.5 72.0 52.3 3.3 83.3 21.8 3.5 79.2 4.3 64.6 102.8 5.4 5.9

80

7.5 0.5 1.1 64.4 49.1 4.1 78.3 15.7 5.6 80.2 4.3 65.5 103.3 5.5 5.9

11.3 2.0 4.6 67.2 50.4 3.8 80.2 17.7 4.8 84.7 4.4 69.7 105.3 5.6 6.3

15.0 4.0 9.2 68.6 51.0 3.7 81.1 18.7 4.4 87.2 4.5 72.0 106.3 5.7 6.5

90

7.5 0.5 1.2 60.2 47.3 4.6 75.8 13.2 6.8 87.4 4.5 72.2 106.5 5.7 6.5

11.3 2.0 4.5 63.1 48.6 4.2 77.5 14.9 6.0 92.1 4.6 76.4 108.5 5.9 6.9

15.0 3.9 9.1 64.5 49.2 4.1 78.5 15.8 5.5 94.4 4.6 78.6 109.5 6.0 7.1

100

7.5 0.5 1.1 56.1 45.5 5.1 73.5 11.0 8.3

Operation not recommended

11.3 1.9 4.5 58.8 46.7 4.7 75.0 12.4 7.3

15.0 3.9 9.0 60.2 47.3 4.6 75.8 13.2 6.8

110

7.5 0.4 0.8 52.5 44.2 5.7 72.1 9.2 9.9

11.3 1.8 4.2 54.8 45.0 5.3 72.9 10.3 8.8

15.0 3.8 8.8 56.1 45.5 5.1 73.5 11.0 8.3

120

7.5 0.1 0.3 49.8 43.7 6.5 71.9 7.7 11.9

11.3 1.6 3.8 51.4 43.9 6.0 71.8 8.6 10.6

15.0 3.7 8.5 52.4 44.2 5.8 72.0 9.1 10.0Interpolation is permissible; extrapolation is not.All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating. All performance data is based upon the lower voltage of dual voltage rated units.See performance correction tables for operating conditions other than those listed above..

Page 27: Submittal Data - Climate Master · The award winning Tranquility® Series raises the bar for water-source heat pump efficiencies, features and application flexibility. Not only does

ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.

Page ______ of ______LC377 - 27

Performance Data – TSH/V/D070 (PSC Blower)

2,100 CFM Nominal AirflowPerformance capacities shown in thousands of Btuh

TSH/V/D070 PSC

EWT °F GPM

WPD COOLING - EAT 80.6/66.2 °F HEATING - EAT 68°F

PSI Ft TC SC KW HR EER HWG Cap HC KW HE LAT COP HWG

Cap20 18.0 9.5 22.0 Operation not recommended 47.9 4.8 31.6 89.1 2.9 5.0

30

9.0 2.7 6.3 82.5 51.0 3.4 94.2 24.0 3.7 52.1 4.8 35.6 90.9 3.2 5.3

13.5 5.2 12.0 80.9 48.7 3.3 92.0 24.8 3.7 54.0 4.9 37.4 91.8 3.3 5.4

18.0 8.1 18.8 79.6 47.3 3.2 90.5 25.0 3.7 55.1 4.9 38.4 92.2 3.3 5.5

40

9.0 2.1 4.9 83.0 52.9 3.7 95.7 22.2 3.9 59.3 5.0 42.3 94.1 3.5 5.8

13.5 4.4 10.1 82.8 51.8 3.5 94.9 23.5 3.7 61.8 5.0 44.7 95.2 3.6 6.0

18.0 7.1 16.4 82.4 50.9 3.4 94.1 24.0 3.7 63.2 5.1 46.0 95.8 3.7 6.1

50

9.0 1.7 4.0 81.7 53.4 4.1 95.6 20.1 4.5 67.1 5.1 49.6 97.5 3.8 6.4

13.5 3.8 8.8 82.8 53.2 3.8 95.8 21.6 4.1 70.2 5.2 52.4 98.9 4.0 6.7

18.0 6.4 14.8 83.0 52.8 3.7 95.7 22.3 3.9 71.9 5.2 54.0 99.6 4.0 6.8

60

9.0 1.6 3.6 79.2 52.9 4.4 94.4 17.8 5.5 75.1 5.3 57.0 101.0 4.1 7.1

13.5 3.5 8.1 81.1 53.4 4.2 95.3 19.4 4.8 78.7 5.4 60.3 102.6 4.3 7.5

18.0 5.9 13.7 81.9 53.4 4.1 95.7 20.2 4.5 80.6 5.4 62.1 103.5 4.4 7.7

70

9.0 1.5 3.5 75.8 51.7 4.9 92.4 15.6 6.7 83.1 5.5 64.3 104.5 4.4 8.0

13.5 3.3 7.7 78.3 52.6 4.6 93.8 17.1 5.8 87.0 5.6 67.9 106.3 4.6 8.5

18.0 5.7 13.1 79.4 52.9 4.4 94.5 17.9 5.4 89.0 5.6 69.8 107.2 4.6 8.7

80

9.0 1.5 3.5 71.7 50.0 5.4 90.0 13.4 8.3 90.7 5.7 71.3 107.9 4.7 9.0

13.5 3.2 7.5 74.6 51.2 5.0 91.7 14.9 7.2 94.7 5.8 74.9 109.7 4.8 9.6

18.0 5.5 12.7 75.9 51.7 4.9 92.5 15.6 6.7 96.7 5.8 76.8 110.5 4.9 9.9

90

9.0 1.6 3.6 67.3 48.1 5.9 87.4 11.4 10.2 97.7 5.9 77.7 111.0 4.9 10.1

13.5 3.2 7.4 70.3 49.4 5.5 89.1 12.7 8.9 101.4 6.0 81.0 112.6 5.0 10.8

18.0 5.5 12.6 71.7 50.0 5.4 90.0 13.4 8.3 103.1 6.0 82.6 113.4 5.0 11.3

100

9.0 1.6 3.6 62.8 46.2 6.5 85.0 9.7 12.4

Operation not recommended

13.5 3.2 7.4 65.7 47.4 6.1 86.5 10.8 10.9

18.0 5.4 12.5 67.2 48.0 5.9 87.4 11.4 10.2

110

9.0 1.4 3.3 58.5 44.5 7.2 83.0 8.1 14.9

13.5 3.1 7.1 61.2 45.5 6.8 84.2 9.1 13.3

18.0 5.3 12.3 62.6 46.1 6.5 84.9 9.6 12.5

120

9.0 1.2 2.7 54.5 43.3 8.0 81.8 6.8 17.8

13.5 2.9 6.6 56.8 44.0 7.5 82.4 7.6 16.0

18.0 5.2 11.9 58.1 44.4 7.3 82.9 8.0 15.1Interpolation is permissible; extrapolation is not.All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating. All performance data is based upon the lower voltage of dual voltage rated units.See performance correction tables for operating conditions other than those listed above..

Page 28: Submittal Data - Climate Master · The award winning Tranquility® Series raises the bar for water-source heat pump efficiencies, features and application flexibility. Not only does

ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.

Page ______ of ______LC377 - 28

Performance Data – TSH/V/D070 (ECM Blower)

1,950 CFM Nominal Airflow Cooling, 2,050 CFM Nominal Airflow HeatingPerformance capacities shown in thousands of Btuh

TSH/V/D070 ECM

EWT °F GPM

WPD COOLING - EAT 80.6/66.2 °F HEATING - EAT 68°F

PSI Ft TC SC KW HR EER HWG Cap HC KW HE LAT COP HWG

Cap20 18.0 9.5 22.0 Operation not recommended 46.7 4.4 31.6 89.0 3.1 5.0

30

9.0 2.7 6.3 83.2 52.7 3.0 93.5 27.6 3.7 50.9 4.5 35.5 90.9 3.3 5.3

13.5 5.2 12.0 82.1 51.3 2.8 91.6 29.2 3.7 52.7 4.5 37.3 91.8 3.4 5.4

18.0 8.1 18.8 81.1 50.3 2.7 90.4 30.0 3.7 53.8 4.6 38.2 92.2 3.5 5.5

40

9.0 2.1 4.9 83.4 53.6 3.3 94.7 25.1 3.9 58.0 4.7 42.2 94.1 3.7 5.8

13.5 4.4 10.1 83.5 53.1 3.1 94.0 26.9 3.7 60.5 4.7 44.5 95.3 3.8 6.0

18.0 7.1 16.4 83.2 52.7 3.0 93.4 27.7 3.7 61.9 4.7 45.8 95.9 3.8 6.1

50

9.0 1.7 4.0 82.0 53.5 3.7 94.5 22.4 4.5 65.8 4.8 49.4 97.6 4.0 6.4

13.5 3.8 8.8 83.1 53.7 3.4 94.8 24.3 4.1 68.9 4.9 52.2 99.0 4.1 6.7

18.0 6.4 14.8 83.4 53.6 3.3 94.7 25.2 3.9 70.6 4.9 53.8 99.8 4.2 6.8

60

9.0 1.6 3.6 79.5 52.5 4.0 93.2 19.8 5.5 73.8 5.0 56.8 101.3 4.3 7.1

13.5 3.5 8.1 81.3 53.2 3.8 94.2 21.6 4.8 77.4 5.1 60.1 102.9 4.5 7.5

18.0 5.9 13.7 82.1 53.5 3.6 94.5 22.6 4.5 79.3 5.1 61.9 103.8 4.5 7.7

70

9.0 1.5 3.5 76.2 51.0 4.4 91.3 17.2 6.7 81.8 5.2 64.1 104.9 4.6 8.0

13.5 3.3 7.7 78.5 52.1 4.1 92.7 19.0 5.8 85.7 5.3 67.7 106.6 4.8 8.5

18.0 5.7 13.1 79.6 52.5 4.0 93.3 19.9 5.4 87.8 5.3 69.6 107.6 4.8 8.7

80

9.0 1.5 3.5 72.3 49.2 4.9 89.0 14.8 8.3 89.5 5.4 71.1 108.3 4.9 9.0

13.5 3.2 7.5 74.9 50.4 4.6 90.6 16.4 7.2 93.5 5.5 74.7 110.1 5.0 9.6

18.0 5.5 12.7 76.2 51.0 4.4 91.3 17.2 6.7 95.5 5.6 76.5 111.0 5.0 9.9

90

9.0 1.6 3.6 68.0 47.3 5.4 86.6 12.5 10.2 96.5 5.6 77.4 111.5 5.0 10.1

13.5 3.2 7.4 70.8 48.5 5.1 88.2 13.9 8.9 100.2 5.7 80.6 113.2 5.1 10.8

18.0 5.5 12.6 72.2 49.2 4.9 89.0 14.7 8.3 102.0 5.8 82.1 113.9 5.1 11.3

100

9.0 1.6 3.6 63.6 45.3 6.1 84.3 10.5 12.4

Operation not recommended

13.5 3.2 7.4 66.4 46.5 5.7 85.7 11.7 10.9

18.0 5.4 12.5 67.8 47.2 5.5 86.5 12.4 10.2

110

9.0 1.4 3.3 59.2 43.6 6.8 82.4 8.7 14.9

13.5 3.1 7.1 61.9 44.6 6.3 83.5 9.8 13.3

18.0 5.3 12.3 63.3 45.2 6.1 84.1 10.4 12.5

120

9.0 1.2 2.7 55.2 42.2 7.6 81.1 7.3 17.8

13.5 2.9 6.6 57.6 43.0 7.1 81.8 8.1 16.0

18.0 5.2 11.9 58.9 43.4 6.8 82.2 8.6 15.1Interpolation is permissible; extrapolation is not.All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating. All performance data is based upon the lower voltage of dual voltage rated units.See performance correction tables for operating conditions other than those listed above..

Page 29: Submittal Data - Climate Master · The award winning Tranquility® Series raises the bar for water-source heat pump efficiencies, features and application flexibility. Not only does

ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.

Page ______ of ______LC377 - 29

Performance Correction Tables

Airflow Corr Heating Cooling% of Nominal Htg Cap Power Heat of Ext Total Cap Sens Cap S/T Power Heat of Rej

60 0.933 1.216 0.907 0.878 0.774 0.882 0.936 0.920

72 0.957 1.124 0.942 0.925 0.850 0.919 0.951 0.950

80 0.973 1.072 0.963 0.954 0.903 0.946 0.966 0.968

88 0.984 1.037 0.979 0.974 0.941 0.966 0.977 0.982

96 0.995 1.010 0.994 0.992 0.981 0.989 0.992 0.995

100 1.000 1.000 1.000 1.000 1.000 1.000 1.000 1.000

104 1.005 0.993 1.006 1.007 1.018 1.011 1.009 1.005

112 1.012 0.986 1.015 1.017 1.052 1.035 1.027 1.013

120 1.019 0.990 1.022 1.023 1.082 1.058 1.047 1.019

* = Sensible capacity equals total capacityAHRI/ASHRAE/ISO 13256-1 uses entering air conditions of Cooling - 80.6° F DB/66.2° F WB, 1 and Heating - 68° F DB/59° F WB entering air temperatureFor ClimaDry® equipped units the minimum entering air temperature when cooling is 65º F DB / 55º F WB. Operation below this minimum may result in nuisance faults.

Airflow

Entering Air Heating

Entering Air Cooling

EAT Heating CorrectionsEnt Air DB F Htg Cap Power Heat of Ext

45 1.032 0.777 1.089

50 1.029 0.817 1.077

55 1.025 0.859 1.062

60 1.018 0.903 1.044

65 1.010 0.950 1.024

70 1.000 1.000 1.000

75 0.988 1.052 0.974

80 0.974 1.107 0.944

120 1.019 0.990 1.022

Cooling CorrectionsSensible Clg Cap Multipliers - Entering DB °F

Ent Air WB F Total Clg Cap 60 65 70 75 80 85 90 95 100 Power Heat of Rej

45 0.6634 * * * * * * * * * 0.9856 0.7829

50 0.7399 0.7663 * * * * * * * * 0.9889 0.8322

55 0.8164 0.5937 0.8724 1.0816 * * * * * * 0.9921 0.8816

60 0.8929 0.6709 0.8826 1.1211 * * * * * 0.9954 0.9309

65 0.9694 0.6624 0.8850 1.0986 * * * * 0.9987 0.9803

67 1.0000 0.5685 0.7879 1.0000 1.1891 1.3838 * * 1.0000 1.0000

70 1.0459 0.6391 0.8521 1.0361 1.2347 1.4461 * 1.0020 1.0296

75 1.1224 0.6056 0.7783 0.9861 1.2256 1.4690 1.0052 1.0789

Page 30: Submittal Data - Climate Master · The award winning Tranquility® Series raises the bar for water-source heat pump efficiencies, features and application flexibility. Not only does

ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.

Page ______ of ______LC377 - 30

Antifreeze Correction Table

Table Continued on Next Page

EWT AntifreezeType Antifreeze % Cooling Heating WPDTotal Cap Sensible Cap Watts Total Cap Watts

90

Water 0% 1 1 1 1 1 1

Ethanol

5% 0.998 0.998 1.002 0.996 0.999 1.02510% 0.996 0.996 1.003 0.991 0.997 1.04815% 0.994 0.994 1.005 0.987 0.996 1.09820% 0.991 0.991 1.006 0.982 0.994 1.14225% 0.986 0.986 1.009 0.972 0.991 1.20730% 0.981 0.981 1.012 0.962 0.988 1.26535% 0.977 0.977 1.015 0.953 0.985 1.31240% 0.972 0.972 1.018 0.943 0.982 1.3745% 0.966 0.966 1.023 0.931 0.978 1.43150% 0.959 0.959 1.027 0.918 0.974 1.494

Ethylene Glycol

5% 0.998 0.998 1.002 0.996 0.999 1.02110% 0.996 0.996 1.003 0.991 0.997 1.0415% 0.994 0.994 1.004 0.987 0.996 1.07920% 0.991 0.991 1.005 0.982 0.995 1.11425% 0.988 0.988 1.008 0.976 0.993 1.14630% 0.985 0.985 1.01 0.969 0.99 1.17535% 0.982 0.982 1.012 0.963 0.988 1.20840% 0.979 0.979 1.014 0.956 0.986 1.24345% 0.976 0.976 1.016 0.95 0.984 1.27850% 0.972 0.972 1.018 0.943 0.982 1.314

Methanol

5% 0.997 0.997 1.002 0.993 0.998 1.03910% 0.993 0.993 1.004 0.986 0.996 1.07515% 0.99 0.99 1.007 0.979 0.994 1.11620% 0.986 0.986 1.009 0.972 0.991 1.15425% 0.982 0.982 1.012 0.964 0.989 1.18930% 0.978 0.978 1.014 0.955 0.986 1.22135% 0.974 0.974 1.017 0.947 0.984 1.26740% 0.97 0.97 1.02 0.939 0.981 1.3145% 0.966 0.966 1.023 0.93 0.978 1.35350% 0.961 0.961 1.026 0.92 0.975 1.398

Propylene Glycol

5% 0.995 0.995 1.003 0.99 0.997 1.06510% 0.99 0.99 1.006 0.98 0.994 1.11915% 0.986 0.986 1.009 0.971 0.991 1.15220% 0.981 0.981 1.012 0.962 0.988 1.18225% 0.978 0.978 1.014 0.956 0.986 1.22730% 0.975 0.975 1.016 0.95 0.984 1.26735% 0.972 0.972 1.018 0.944 0.982 1.31240% 0.969 0.969 1.02 0.938 0.98 1.35645% 0.965 0.965 1.023 0.929 0.977 1.40250% 0.96 0.96 1.026 0.919 0.974 1.45

Page 31: Submittal Data - Climate Master · The award winning Tranquility® Series raises the bar for water-source heat pump efficiencies, features and application flexibility. Not only does

ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.

Page ______ of ______LC377 - 31

Antifreeze Correction Table

Table Continued from Previous Page

EWT AntifreezeType Antifreeze % Cooling Heating WPDTotal Cap Sensible Cap Watts Total Cap Watts

30

Water 0% 1 1 1 1 1 1

Ethanol

5% 0.991 0.991 1.006 0.981 0.994 1.1410% 0.981 0.981 1.012 0.961 0.988 1.24215% 0.973 0.973 1.018 0.944 0.983 1.29520% 0.964 0.964 1.024 0.927 0.977 1.34325% 0.959 0.959 1.028 0.917 0.974 1.36330% 0.954 0.954 1.031 0.907 0.97 1.38335% 0.949 0.949 1.035 0.897 0.967 1.46840% 0.944 0.944 1.038 0.887 0.964 1.52345% 0.94 0.94 1.041 0.88 0.962 1.5850% 0.936 0.936 1.043 0.872 0.959 1.639

Ethylene Glycol

5% 0.997 0.997 1.002 0.993 0.998 1.0410% 0.993 0.993 1.004 0.986 0.996 1.07515% 0.99 0.99 1.006 0.98 0.994 1.12220% 0.987 0.987 1.008 0.973 0.992 1.16325% 0.983 0.983 1.011 0.966 0.99 1.19530% 0.979 0.979 1.013 0.958 0.987 1.22535% 0.976 0.976 1.016 0.951 0.985 1.27940% 0.972 0.972 1.018 0.943 0.982 1.32445% 0.969 0.969 1.021 0.937 0.98 1.37150% 0.966 0.966 1.023 0.93 0.978 1.419

Methanol

5% 0.995 0.995 1.004 0.989 0.997 1.06910% 0.989 0.989 1.007 0.978 0.993 1.12715% 0.984 0.984 1.011 0.968 0.99 1.16420% 0.979 0.979 1.014 0.957 0.986 1.19725% 0.975 0.975 1.017 0.949 0.984 1.21630% 0.971 0.971 1.019 0.941 0.981 1.23535% 0.967 0.967 1.022 0.933 0.979 1.28640% 0.963 0.963 1.025 0.924 0.976 1.32345% 0.959 0.959 1.028 0.917 0.974 1.3650% 0.955 0.955 1.03 0.91 0.971 1.399

Propylene Glycol

5% 0.995 0.995 1.004 0.989 0.997 1.07110% 0.989 0.989 1.007 0.978 0.993 1.1315% 0.985 0.985 1.01 0.968 0.99 1.20620% 0.98 0.98 1.013 0.958 0.987 1.2725% 0.974 0.974 1.017 0.947 0.983 1.35930% 0.968 0.968 1.021 0.935 0.979 1.43335% 0.963 0.963 1.025 0.924 0.976 1.52240% 0.957 0.957 1.029 0.913 0.972 1.61445% 0.949 0.949 1.034 0.898 0.967 1.71250% 0.941 0.941 1.039 0.882 0.962 1.816

Page 32: Submittal Data - Climate Master · The award winning Tranquility® Series raises the bar for water-source heat pump efficiencies, features and application flexibility. Not only does

ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.

Page ______ of ______LC377 - 32

Correction Tables – Water Pressure Drop Adder for Options

Motorized Water Valve Option Corrections

Model WPD AddersGPM PSI FT

018 2.8 0.77 1.774.1 1.65 3.80

024 4.0 1.57 3.626.0 3.53 8.14

030 4.0 0.69 1.596.0 1.55 3.58

036 4.5 0.87 2.026.8 1.99 4.60

042 5.5 1.30 3.018.3 6.75 15.58

048 6.0 1.55 3.589.0 3.49 8.06

060 7.5 1.49 3.4511.3 3.39 7.82

0708.3 1.83 4.2212.4 4.08 9.42

Model Cv MOPDWPD Adders

GPM PSI FT

0064.9 150 1.0 0.04 0.104.9 150 1.5 0.09 0.224.9 150 2.0 0.17 0.38

0094.9 150 1.4 0.08 0.194.9 150 2.1 0.18 0.424.9 150 2.8 0.33 0.75

0124.9 150 1.8 0.13 0.314.9 150 2.6 0.28 0.654.9 150 3.5 0.51 1.18

01810.3 125 2.8 0.07 0.1610.3 125 4.1 0.16 0.3710.3 125 5.5 0.29 0.66

02410.3 125 4.0 0.15 0.3510.3 125 6.0 0.34 0.7810.3 125 8.0 0.60 1.39

03010.3 125 4.0 0.15 0.3510.3 125 6.0 0.34 0.7810.3 125 8.0 0.60 1.39

03610.3 125 4.5 0.19 0.4410.3 125 6.8 0.43 0.9910.3 125 9.0 0.76 1.76

04210.3 125 5.5 0.29 0.6610.3 125 8.3 0.64 1.4810.3 125 11.0 1.14 2.63

04810.3 125 6.0 0.34 0.7810.3 125 9.0 0.76 1.7610.3 125 12.0 1.36 3.14

0608.9 125 7.5 0.71 1.648.9 125 11.3 1.60 3.698.9 125 15.0 2.84 6.56

0708.9 125 8.3 0.86 1.988.9 125 12.4 1.93 4.478.9 125 16.5 3.44 7.94

ClimaDry® II Option Corrections(When Operating in Non-ClimaDry® Mode)

Page 33: Submittal Data - Climate Master · The award winning Tranquility® Series raises the bar for water-source heat pump efficiencies, features and application flexibility. Not only does

ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.

Page ______ of ______LC377 - 33

Blower Performance Data – Standard Unit, No Reheat (PSC Blower)

Airflow in CFM with wet coil and clean air filter

Model Fan Speed

Rated Airflow

Min CFM

Airflow (cfm) at External Static Pressure (in. wg)0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00

006HI

240 150317 305 285 271 250 230 203 168

MED 260 245 230 214 190 167LO 216 201 189 156

009HI

300 225393 378 364 346 325 253

MED 366 353 341 326 310 230LO 326 316 303 290 274

012HI

350 300520 500 479 453 403 347 312

MED 459 447 428 411 368 317LO 371 368 358 345 315

018HI

600 450704 711 693 690 675 640 598 515

MED 602 599 581 585 573 547 492LO 531 527 517 506 495 462

018HS

HS HI600 450

894 877 841 812 760 728 659HS MED 765 755 738 711 668 640 602HS LO 683 661 636 596 571 549

024HI

950 6551111 1105 1066 1006 934 854 765 662 635

MED 890 879 854 818 770 708 686 623LO 759 745 730 704 662 627

024 HS

HS HI950 655

1374 1351 1296 1228 1159 1090 1016 919 775HS MED 1146 1151 1128 1091 1047 997 934 844 705HS LO 1011 1015 999 945 911 863 785 656

030HI

1000 6851374 1351 1296 1228 1159 1090 1016 919 775

MED 1146 1151 1128 1091 1047 997 934 844 705LO 1011 1015 999 945 911 863 785

030 HS

HS HI1000 685

1342 1316 1249 1166 1083 1006 927 830 688HS MED 1298 1250 1183 1110 1039 969 894 796 652HS LO 1213 1172 1112 1046 982 919 850 758 623

036HI

1200 8251375 1387 1377 1350 1307 1251 1182 1099 1003 890

MED 992 1013 1013 1002 986 967 941 900 832 719LO 887 900 897 886 872 853 826 785

036 HS

HS HI1200 825

1751 1717 1664 1592 1503 1399 1285 1163 1039 919HS MED 1538 1520 1485 1432 1361 1271 1165 1049 926 804HS LO 1321 1294 1263 1226 1182 1130 1064 980 871 729

042HI

1400 9601808 1759 1723 1680 1617 1524 1399 1247 1075

MED 1537 1518 1494 1459 1408 1338 1247 1134 1001LO 1323 1309 1284 1246 1192 1122 1036 936 824

042HS

HS HI1400 960

1805 1791 1760 1720 1674 1620 1552 1457 1318 1116HS MED 1296 1297 1299 1299 1293 1276 1240 1176 1072 915HS LO 991 998 1013 1019 1004 963 894 804 705

048HI

1600 11001805 1791 1760 1720 1674 1620 1552 1457 1318 1116

MED 1296 1297 1299 1299 1293 1276 1240 1176 1072 915LO Operation not recommended

048HS

HS HI1600 1100

1871 1889 1873 1833 1777 1706 1617 1504 1353 1150HS MED 1663 1680 1686 1678 1650 1599 1520 1409 1262 1075HS LO 1479 1508 1521 1516 1492 1446 1376 1249 1148 981

060HI

1950 15002311 2300 2279 2257 2209 2140 2088 1990 1901 1856 1752

MED 2058 2039 2016 1983 1949 1920 1874 1807 1750 1670 1582LO 1868 1858 1858 1838 1806 1792 1749 1699 1636 1570

060HS

HS HI1950 1500

2510 2486 2455 2424 2377 2318 2247 2161 2078 1986 1855HS MED 2171 2162 2162 2153 2117 2085 2024 1971 1891 1823 1691HS LO 2010 2006 2006 2006 1977 1947 1892 1851 1782 1705 1600

070HI

2100 18002510 2486 2455 2424 2377 2318 2247 2161 2078 1986 1855

MED 2171 2162 2162 2153 2117 2085 2024 1971 1891 1823LO 2010 2006 2006 2006 1977 1947 1892 1851

Black areas denote ESP where operation is not recommended.Units factory shipped on medium speed. Other speeds require field selection.All airflow is rated and shown above at the lower voltage if unit is dual voltage rated, e.g. 208V for 208-230V units.Only two speed fan (H & M) available on 575V units.Performance stated is at the rated power supply, performance may vary as the power supply varies from the rated.HS = High static fan option

Page 34: Submittal Data - Climate Master · The award winning Tranquility® Series raises the bar for water-source heat pump efficiencies, features and application flexibility. Not only does

ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.

Page ______ of ______LC377 - 34

Blower Performance Data – Units with ClimaDry® (PSC Blower)

Coil FaceVelocity

FPM

TSH/V/D with Reheat ESP Loss

TSH/V/D018

In. of Water

TSH/V/D024, 030

In. of Water

TSH/V/D036

In. of Water

TSH/V/D042, 048

In. of Water

TSH/V/D060, 070

In. of Water

200 0.037 0.033 0.031 0.028 0.026

250 0.052 0.046 0.042 0.038 0.034

300 0.077 0.066 0.059 0.051 0.044

350 0.113 0.096 0.085 0.073 0.061

400 0.181 0.160 0.145 0.131 0.117

450 0.242 0.226 0.215 0.205 0.194

500 0.360 0.345 0.335 0.326 0.316

For TS units with ClimaDry® Reheat coil applications, calculate face velocity of the entering air. From the table above, fi nd ESP for Reheat application. The loss includes wet coil loss.

Example:Reheat coil loss can be determined from the above table.

Coil velocity (FPM) = Airfl ow (CFM) / Face Area (sq. ft.)

1. TSH036 has a face area of 4.86 sq. ft. (see physical data table).2. At 1,100 cfm, coil velocity (FPM) = 1,100 / 4.86 = 226 FPM3. From above table, it will be necessary to subtract 0.037 from the blower

performance ESP.4. On medium speed, the TSH036 (without reheat - see blower table) can deliver 1,100

CFM at 0.28 in. wg. with the standard PSC motor; with the reheat coil, it now delivers 1,085 CFM at 0.28 in. wg. or 1,100 CFM at 0.24 in. wg.

5. If the decrease in airfl ow is acceptable, no changes are necessary. Otherwise, high speed fan should be used to overcome the pressure drop of the reheat coil.

Page 35: Submittal Data - Climate Master · The award winning Tranquility® Series raises the bar for water-source heat pump efficiencies, features and application flexibility. Not only does

ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.

Page ______ of ______LC377 - 35

ECM Control

The ECM fan is controlled by an interface board that converts thermostat inputs and field selectable CFM settings to signals used by the ECM motor controller. Fan speeds are selected with a DIP switch setting. To take full advantage of the ECM motor features, a multi-stage thermostat should be used (2-stage heat/2-stage cool or 3-stage heat/2-stage cool).

Note: Power must be off to the unit for at least three seconds before the ECM motor will recognize a speed change. The motor will recognize a change in the CFM Adjust or dehumidification mode settings while the unit is powered.

There are four different airflow settings from lowest airflow rate (speed tap 1) to the highest airflow rate (speed tap 4). The charts below indicate settings for the ECM interface board, followed by detailed information for each set.

WARNING! When the disconnect switch is closed, high voltage is present in some areas of the electrical panel. Exercise caution when working with energized equipment.

Only DIP switch numbers 1 to 4 and 7 to 9 are used

Cooling Settings: The cooling setting determines the cooling (normal) CFM for all units with ECM motor. Cooling (normal) setting is used when the unit is not in dehumidification mode. Tap 1 is the lowest CFM setting, while tap 4 is the highest CFM setting. To avoid air coil freeze-up, tap 1 may not be used if the dehumidification mode is selected. Consult submittal data or specifications catalog for the specific unit series and model to correlate speed tap setting to airflow in CFM.

Heating Settings: The heating setting determines the heating CFM. Tap 1 is the lowest CFM setting, while tap 4 is the highest CFM setting. Consult submittal data or specifications catalog for the specific unit series and model to correlate speed tap setting to airflow in CFM.

CFM Adjust Settings: The CFM adjust setting allows four selections. The NORM setting is the factory default position. The + or – settings adjust the airflow by +/- 5%. The +/- settings are used to “fine tune” airflow adjustments. The TEST setting runs the ECM motor at 400 cfm/ton, which causes the motor to operate like a standard PSC motor, and disables the CFM counter.

Page 36: Submittal Data - Climate Master · The award winning Tranquility® Series raises the bar for water-source heat pump efficiencies, features and application flexibility. Not only does

ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.

Page ______ of ______LC377 - 36

ECM Control

Dehumidification Mode Settings: The dehumidification mode setting provides field selection of humidity control. When operating in the normal mode, the cooling airflow settings are determined by the cooling tap setting above. When dehumidification is enabled there is a reduction in airflow in cooling to increase the moisture removal of the heat pump. Consult submittal data or specifications catalog for the specific unit series and model to correlate speed tap to airflow in CFM. The dehumidification mode can be enabled in two ways. 1. Constant Dehumidification Mode: When the

dehumidification mode is selected (via DIP switch), the ECM motor will operate with a multiplier applied to the cooling CFM settings (approx. 20-25% lower airflow). Any time the unit is running in the cooling mode, it will operate at the lower airflow to improve latent capacity. The “DEHUM” LED will be illuminated at all times. Heating airflow is not affected. NOTE: Do not select dehumidification mode if cooling setting is tap 1.

2. Automatic (Humidistat-controlled) Dehumidification Mode: When the dehumidification mode is selected (via DIP switch) AND a humidistat is connected to terminal DH, the cooling airflow will only be reduced when the humidistat senses that additional dehumidification is required. The DH terminal is reverse logic. Therefore, a humidistat (not dehumidistat) is required. The “DEHUM” LED will be illuminated only when the humidistat is calling for dehumidification mode. Heating airflow is not affected. NOTE: Do not select dehumidification mode if cooling setting is tap 1.

The ECM motor includes “soft start” and “ramp down” features. The soft start feature is a gentle increase of motor rpm at blower start up. This creates a much quieter blower start cycle.

The ramp down feature allows the blower to slowly decrease rpm to a full stop at the end of each blower cycle. This creates a much quieter end to each blower cycle and adds overall unit efficiency.

The ramp down feature may be eliminated during an ESD (Emergency Shut Down) situation when using a DXM2 unit controller. A relay is required to break the line voltage to the ECM motor during ESD. This relay can be wired as shown below to eliminate the ramp down (and operation) of the ECM blower.

Page 37: Submittal Data - Climate Master · The award winning Tranquility® Series raises the bar for water-source heat pump efficiencies, features and application flexibility. Not only does

ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.

Page ______ of ______LC377 - 37

ECM Control Diagram

To ‘E

SD’ o

n D

XM2

To ‘R

’ on

DXM

2

ESD

Sig

nal

(�el

d in

put)

GN

D o

r C

Page 38: Submittal Data - Climate Master · The award winning Tranquility® Series raises the bar for water-source heat pump efficiencies, features and application flexibility. Not only does

ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.

Page ______ of ______LC377 - 38

Blower Performance Data – Standard Unit - No Reheat (ECM Blower)

TranquiliTy® 20 (TS) SERIES WITH CLIMADRY® REHEAT OPTION (ECM MOTOR)All Tranquility® 20 (TS) units with optional ECM fan motor automatically adjusts for the reheat coil. The small additional pressure drop of the reheat coil causes the ECM motor to slightly increase RPM to overcome the added pressure drop, and maintain selected CFM up to the maximum ESP.

ResidentialUnits Only

Model Max ESP (in. wg)

Fan Motor (hp)

Tap Setting

Cooling Mode Dehumid Mode Heating Mode AUX CFM

Aux/ EmergModeStg 1 Stg 2 Fan Stg 1 Stg 2 Fan Stg 1 Stg 2 Fan

018 1.0 1/2

4 640 800 400 500 620 400 640 800 400 4 800

3 600 750 375 470 590 375 600 750 375 3 750

2 525 650 330 400 500 330 525 650 330 2 6501 450 550 280 450 550 280 1 650

024 1.0 1/2

4 900 1100 470 610 740 470 900 1100 470 4 11003 780 950 420 540 660 420 780 950 420 3 9502 670 825 360 490 600 360 670 825 390 2 8201 550 675 300 550 675 340 1 690

030 1.0 1/2

4 920 1130 560 720 880 560 1000 1230 560 4 12303 820 1000 500 640 780 500 900 1100 500 3 11002 740 900 450 580 700 450 800 950 450 2 9501 660 800 400 640 780 400 1 780

036 0.90 1/2

4 1150 1400 700 900 1090 700 1150 1400 700 4 14003 1020 1250 630 800 980 630 1020 1250 630 3 13502 890 1080 540 690 840 540 890 1080 540 2 13501 740 900 450 750 920 450 1 1350

042 0.90 1/2

4 1290 1580 790 1010 1230 790 1290 1580 790 4 1580

3 1150 1400 700 900 1090 700 1150 1400 700 3 14002 1050 1280 640 820 1000 640 1020 1240 640 2 13501 920 1120 560 900 1080 560 1 1350

048 1.0 1

4 1420 1730 870 1110 1350 870 1520 1850 865 4 18503 1270 1550 780 990 1210 780 1350 1650 775 3 16502 1180 1440 720 920 1120 720 1110 1350 720 2 13501 1050 1280 640 980 1250 640 1 1200

060 0.75 1

4 1680 2050 1030 1310 1600 1030 1870 2280 1030 4 22803 1500 1830 910 1170 1420 910 1680 2050 910 3 20502 1400 1700 850 1090 1330 850 1480 1800 850 2 18001 1300 1580 790 1270 1550 790 1 1550

070 0.75 1

4 1830 2230 1100 1420 1740 1100 1830 2230 1100 4 22303 1600 1950 980 1250 1520 980 1720 2100 980 3 21002 1440 1750 880 1120 1360 880 1670 1950 880 2 19501 1200 1580 790 1460 1780 790 1 1780

See ECM control section for details on setting taps.Bold numbers indicate factory settings. During Auxiliary operation the CFM will run at the higher of the Heating (Delay jumper) or AUX settings.Airflow is controlled within 5% up to the Max ESP shown with wet coil.Do not select Dehumidification mode if HP CFM is on setting 1.All units AHRI/ISO/ASHRAE 13256-1 rated HP CFM Setting 3.

Airflow in CFM with wet coil and clean air filter

Page 39: Submittal Data - Climate Master · The award winning Tranquility® Series raises the bar for water-source heat pump efficiencies, features and application flexibility. Not only does

ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.

Page ______ of ______LC377 - 39

ClimaDry® II Option – Benefits and Application

ClimaDry® II Modulating Reheat OptionClimateMaster’s patented ClimaDry® II Dehumidification option is an innovative means of providing modulating reheat without the complication of refrigeration controls. ClimaDry II is hot gas generated reheat, which utilizes one of the biggest advantages of a Water-Source Heat Pump (WSHP), the transfer of energy through the water piping system. ClimaDry II simply diverts condenser water through a water-to-air coil that is placed after the evaporator coil. If condenser water is not warm enough, the internal “run-around” loop increases the water temperature with each pass through the condenser coil (see figure 1, below).

ClimaDry® II BenefitsClimaDry® II is like no other reheat option on the market. Proportional reheat is controlled to the desired leaving air temperature setpoint (factory setpoint of 72°F, 22°C), no matter what the water loop temperature is. Since dehumidification operation will occur under less than full load cooling conditions a good percentage of the time, it is important to have a reheat function that provides 100% reheat in the spring and fall when the water loop is cool. Supply air temperature is field adjustable to +/- 3°F [+/- 1.7°C] for even greater flexibility with the optional potentiometer. It is recommended that the ClimaDry supply air temperature be set to match the space cooling setpoint so that ClimaDry does not impact room temperature. Competitors without ClimaDry II typically use an on/off (non-modulating) refrigeration based reheat circuit, typically referred to as “Hot gas reheat” (HGR). HGR needs higher condensing temperatures to work well, typically 85°F [29°C] entering water temperature (EWT).

With HGR, cooler water temperatures produce cooler supply air temperatures, which could overcool the space, requiring additional space heating from another source or a special auto-change-over relay to allow the unit to switch back and forth between reheat and heating. Rarely does HGR provide 100% reheat, like ClimaDry II. ClimaDry II has a simple and easy to troubleshoot refrigerant circuit. No switching valves or hard to diagnose leaky check valves are utilized. No unusual refrigerant pressures occur during the reheat mode. The ClimaDry II refrigerant circuit is like every other ClimateMaster unit (without reheat), so everything the technician already knows applies to troubleshooting the ClimaDry II refrigeration circuit. Plus, the water loop portion of the ClimaDry II option is easy to understand and diagnose.

ClimaDry® II ApplicationsClimaDry® II can be applied to a number of common applications, such as:

• Classrooms.• Condominiums.• Apartments.• Computer rooms.• Spaces with high latent loads like auditoriums,

theaters, convention centers, etc.• Most applications where humidity is a problem. (Note: ClimaDry® is not for use in high fraction

outdoor air applications or in applications with corrosive atmospheres, such as pool rooms.)

Figure 1: ClimaDry® II Schematic

COAX

Note:All components shownare internal to the heatpump unit.

(TO WATER LOOP)

(FROM WATER LOOP)

MODULATINGMIXING VALVE

ENTERING AIR

INTERNALPUMP

EVAPORATOR COIL

LEAVING AIR

REHEAT COIL

REFRIGERANT OUT(COOLING)

REFRIGERANT IN(COOLING)

WATER IN

WATER OUT

Page 40: Submittal Data - Climate Master · The award winning Tranquility® Series raises the bar for water-source heat pump efficiencies, features and application flexibility. Not only does

ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.

Page ______ of ______LC377 - 40

ClimaDry® II Option – Benefits and Application

With the ClimaDry II option, return air from the space is cooled by the air-to-refrigerant (evaporator) coil, and then reheated by the water-to-air (reheat) coil to dehumidify the air, but maintain the same space temperature (thus operating as a dehumidifier).

The moisture removal capability of the heat pump is determined by the unit’s latent capacity rating. Latent capacity equals Total capacity minus Sensible capacity. Using unit performance data from submittals (http://www.climatemaster.com/) select the correct model, use your maximum entering water temperature (EWT) and flow rate to select TC and SC. For example, at 80° F [26.7° C] EWT and 6.8 GPM, the moisture removal capability (latent capacity) of a ClimateMaster TS036 is 8.1 Mbtuh [2.4 kW] as shown below.

Dividing the latent capacity by 1,069 BTU/LB of water vapor at 80° F DB and 67° F WB [26.7° C DB and 19.4° C WB] moist air enthalpy, converts the amount of moisture removal to pounds per hour (multiply pounds per hour by 0.4536 to obtain kg/hr). Calculations are shown below.

Most ClimateMaster water source heat pumps have a sensible-to-total (S/T) ratio of 0.72 to 0.82. Therefore, approximately, 25% of the cooling capacity is dedicated to latent cooling capacity (moisture removal). When selecting a unit with ClimaDry II, the space sensible and latent loads should be calculated. If the unit will be used for space cooling, a unit with at least enough capacity to satisfy the building sensible load should be selected. If the latent cooling load is not satisfied by the selection, a larger unit with enough latent capacity will be required. If the unit will be used for dehumidification purposes only, the latent capacity is the only consideration necessary. In this case, sensible load is immaterial.

EWT °F GPM

WPD Cooling - EAT 80/67°F Heating - EAT 70°F

PSI FT Airflow CFM TC SC Sens/Tot Ratio kW HR EER Airflow CFM HC kW HE LAT COP

70

4.5 1.1 2.5 940 32.8 21.0 0.64 2.06 39.9 15.9 940 37.9 2.65 28.9 107 4.194.5 1.1 2.5 1250 34.2 25.1 0.73 2.13 41.4 16.0 1250 38.9 2.42 30.6 99 4.706.8 2.9 6.7 940 34.0 21.4 0.63 1.96 40.7 17.4 940 39.7 2.68 30.5 109 4.336.8 2.9 6.7 1250 35.4 25.6 0.72 2.02 42.3 17.5 1250 40.7 2.45 32.3 100 4.87

80

4.5 1.0 2.3 940 30.8 20.2 0.65 2.25 38.5 13.7 940 41.6 2.72 32.2 111 4.484.5 1.0 2.3 1250 32.1 24.1 0.75 2.32 40.0 13.8 1250 42.7 2.48 34.2 102 5.046.8 2.8 6.5 940 32.0 20.6 0.64 2.13 39.3 15.0 940 43.6 2.75 34.1 113 4.646.8 2.8 6.5 1250 33.4 24.7 0.74 2.21 40.9 15.1 1250 44.8 2.52 36.1 103 5.21

85

4.5 1.0 2.2 940 29.8 19.8 0.66 2.36 37.9 12.7 940 43.4 2.75 33.9 113 4.634.5 1.0 2.2 1250 31.1 23.7 0.76 2.44 39.4 12.8 1250 44.6 2.52 36.0 103 5.206.8 2.7 6.2 940 31.0 20.2 0.65 2.24 38.6 13.9 940 45.6 2.79 35.9 115 4.796.8 2.7 6.2 1250 32.3 24.2 0.75 2.31 40.2 14.0 1250 46.8 2.55 38.1 105 5.38

90

4.5 0.9 2.1 940 28.9 19.4 0.67 2.47 37.3 11.7 940 45.3 2.79 35.6 115 4.774.5 0.9 2.1 1250 30.1 23.3 0.77 2.55 38.8 11.8 1250 46.5 2.55 37.8 104 5.356.8 2.6 6.0 940 30.0 19.8 0.66 2.34 38.0 12.8 940 47.6 2.83 37.7 117 4.936.8 2.6 6.0 1250 31.2 23.7 0.76 2.42 39.5 12.9 1250 48.9 2.59 40.0 106 5.54

Example: TS036 PSC Blower Performance

Dividing the latent capacity by 1,069 BTU/LB of water vapor at 80° F DB and 67° F WB [26.7° C DB and 19.4° C WB] moist air enthalpy, converts the amount of moisture removal to pounds per hour (multiply pounds per hour by 0.4536 to obtain kg/hr).

Note: Minimum entering air temperature

LC = TC - SC = 32.3 - 24.2 = 8.1 Mbtuh8,100 Btuh ÷ 1069 = 7.6 lbs/hr

Page 41: Submittal Data - Climate Master · The award winning Tranquility® Series raises the bar for water-source heat pump efficiencies, features and application flexibility. Not only does

ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.

Page ______ of ______LC377 - 41

ClimaDry® II Option – Sequence of Operation

Table 1: Humidistat/Dehumidistat Logic and DXM2 (2.1, 2.2., 2.3) DIP SettingsSensor 2.1 2.2 2.3 Logic Reheat (ON) - H Reheat (OFF) - H

Humidistat OFF OFF OFF Reverse 0 VAC 24 VAC

Dehumidistat OFF ON OFF Standard 24 VAC 0 VAC

1 Cooling input takes priority over dehumidify input.2 DXM2 is programmed to ignore the H demand when the unit is in heating mode.3 N/A for single stage units; Full load operation for dual capacity units.4 ON/OFF = Either ON or OFF.

ModeInput Output

O G Y1 Y23 H O G Y1 Y23 Reheat

No Demand ON/OFF OFF OFF OFF OFF ON/OFF OFF OFF OFF OFF

Fan Only ON/OFF ON OFF OFF OFF ON/OFF ON OFF OFF OFF

Cooling 1st Stage ON ON ON OFF OFF ON ON ON OFF OFF

Cooling 2nd Stage ON ON ON ON OFF ON ON ON ON OFF

Cooling & Dehumidistat1 ON ON ON ON/OFF ON ON ON ON ON/OFF OFF

Dehumidistat Only ON/OFF OFF OFF OFF ON ON ON ON ON ON

Heating 1st Stage OFF ON ON OFF OFF OFF ON ON OFF OFF

Heating 2nd Stage OFF ON ON ON OFF OFF ON ON ON OFF

Heating & Dehumidistat2 OFF ON ON ON/OFF ON OFF ON ON ON/OFF OFF

Table 2: ClimaDry® II Operating Modes

ClimaDry® II Sequence of OperationA heat pump equipped with ClimaDry® II can operate in three modes; cooling, cooling with reheat (dehumidification), and heating. The cooling/heating modes are like any other ClimateMaster WSHP. The reversing valve (“O” signal) is energized in cooling, along with the compressor contactor(s) and blower relay. In the heating mode the reversing valve is de-energized. Almost any thermostat will activate the heat pump in heating or cooling modes. The DXM2 microprocessor board, which is required with the ClimaDry II option, will accept either heat pump (Y,O) thermostats or non-heat pump (Y,W) thermostats. The reheat mode requires either a separate humidistat/dehumidistat or a thermostat that has an integrated dehumidification function for activation. The DXM2 board is configured to work with either a humidistat or dehumidistat input to terminal “H”. Upon receiving an “H” input, the DXM2 board will activate the cooling mode and engage reheat. Table 2 shows the relationship between thermostat input signals and unit operation.There are four operational inputs for single stage units and six operational inputs for dual stage units:

-Fan Only-1st Stage Cooling-2nd Stage Cooling-1st Stage Heating-2nd Stage Heating-Reheat Mode

Fan Only: A (G) call from the thermostat to the (G) terminal of the DXM2 control board will bring the unit on in fan only mode.

1st Stage Cooling: A simultaneous call from (G), (Y1), and (O) to the (G), (Y1), (O/W2) terminals of the DXM2 control board will bring the unit on in 1st Stage Cooling.

2nd Stage Cooling: A simultaneous call from (G), (Y1), (Y2), and (O) to the (G), (Y1), (Y2), and (O/W2) terminals of the DXM2 control board will bring the unit on in 2nd Stage Cooling. When the call is satisfied at the thermostat the unit will continue to run in 1st Stage Cooling until the 1st Stage Cooling call is removed or satisfied, shutting down the unit. NOTE: Not all units have two-stage cooling functionality.

Page 42: Submittal Data - Climate Master · The award winning Tranquility® Series raises the bar for water-source heat pump efficiencies, features and application flexibility. Not only does

ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.

Page ______ of ______LC377 - 42

ClimaDry® II Option – Sequence of Operation

1st Stage Heating: A simultaneous call from (G) and (Y1) to the (G) and (Y1) terminals of the DXM2 control board will bring the unit on in 1st Stage Heating.

2nd Stage Heating: A simultaneous call from (G), (Y1), and (Y2) to the (G), (Y1), and (Y2) terminals of the DXM2 control board will bring the unit on in 2nd Stage Heating. When the call is satisfied at the thermostat the unit will continue to run in 1st Stage Heating until the call is removed or satisfied, shutting down the unit. NOTE: Not all units have two-stage heating functionality (e.g. TLV084-150 units).

Reheat Mode: A call from the Humidistat/Dehumidistat to the (H) terminal of the DXM2 control board will bring the unit on in Reheat Mode if there is no call for cooling at the thermostat. When the Humidistat/Dehumidification call is removed or satisfied the unit will shut down. NOTE: Cooling always overrides Reheat Mode. In the Cooling mode, the unit cools and dehumidifies. If the cooling thermostat is satisfied but there is still a call for dehumidification, the unit will continue to operate in Reheat Mode.

Note: Care must be taken when using a humidistat to operate ClimaDry® II. When the DIP switch on the DXM2 controller is set for ‘humidistat’ it reverses the control logic so that an “open” control circuit initiates a ClimaDry II run cycle. If a humidistat is not connected, or if a manual switch on the humidistat is set to “off”, ClimaDry II will see the open circuit and call for dehumidification.

ClimaDry® II Component FunctionsThe ClimaDry® II option consists of the following components:

Motorized Valve/Proportional ControllerSupply Air SensorLoop PumpHydronic CoilLow Air Temperature Switch

The Proportional Controller operates on 24 VAC power supply and automatically adjusts the water valve based upon the Supply Air Sensor. The Supply Air Sensor senses supply air temperature at the blower inlet providing the input signal necessary for the proportional control to drive the motorized valve during the reheat mode of operation. The Motorized Valve is a proportional actuator/three-way

valve combination used to divert the condenser water from the coax to the hydronic reheat coil during the reheat mode of operation. The proportional controller signals the motorized valve based on the supply air temperature of the supply air sensor.

The Loop Pump circulates condenser water through the hydronic reheat coil during the reheat mode of operation. In this application, the loop pump is only energized during the reheat mode of operation. The Hydronic Coil is utilized during the reheat mode of operation to reheat the air to the setpoint of the proportional controller. Condenser water is diverted by the motorized valve and pumped through the hydronic coil by the loop pump in proportion to the control setpoint. The amount of reheating is dependent on the setpoint and how far from setpoint the supply air temperature is. The factory setpoint is 72° F [22° C], generally considered “neutral” air.

ClimaDry® II Application ConsiderationsThe reheat coil adds a small amount of resistance to the air stream. In some cases the high static option may be required for applications with higher static ductwork. Consult the submittal data or the Installation/Operation/Maintenance (I.O.M.) manual for the specific heat pump to review blower tables.

Unlike most hot gas reheat options, the ClimaDry® II option will operate over a wide range of EWTs. Special flow regulation (water regulating valve) is not required for low EWT conditions.

Unit minimum entering air temperature while in the dehumidification, cooling, or continuous fan modes is 65ºF DB/55ºF WB. Operation below this minimum may result in nuisance faults.

Water-source heat pumps with ClimaDry II should not be used as make-up air units. These applications should use equipment specifically designed for make-up air.

Page 43: Submittal Data - Climate Master · The award winning Tranquility® Series raises the bar for water-source heat pump efficiencies, features and application flexibility. Not only does

ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.

Page ______ of ______LC377 - 43

Physical Data

Model 006 009 012 018 024 030 036 042 048 060 070Compressor (1 Each) Rotary Scroll

Factory ChargeHFC-410A (oz) [kg] 24 [0.68] 32 [0.91] 34 [0.96] 50 [1.13] 41 [1.16] 41 [1.16] 48 [1.36] 68 [1.93] 68 [1.93] 136 [3.86] 141 [4.0]

ECM Fan Motor & Blower

Blower Wheel Size(dia x w) - (in) [mm] N/A N/A N/A 9 x 7

[229 x 178]9 x 7

[229 x 178]9 x 7

[229 x 178]11 x 10

[279 x 254]11 x 10

[279 x 254]11 x 10

[279 x 254]11 x 10

[279 x 254]11 x 10

[279 x 254]

PSC Fan Motor & Blower (3 Speeds)Blower Wheel Size(dia x w) - (in) [mm]

6 X 5[152 X 127]

6 X 5[152 X 127]

6 X 5[152 X 127]

9 x 7[229 x 178]

9 x 7[229 x 178]

9 x 7[229 x 178]

10 x 10[254 x 254]

10 x 10[254 x 254]

10 x 10[254 x 254]

11 x 10[279 x 254]

11 x 10[279 x 254]

Water Connection SizeFPT (in) 1/2” 1/2” 1/2” 3/4” 3/4” 3/4” 3/4” 1” 1” 1” 1”

HWG Connection SizeFPT (in) N/A N/A N/A 1/2” 1/2” 1/2” 1/2” 1/2” 1/2” 1/2” 1/2”

Coax VolumeVolume (US Gallons)

[liters] 0.17 [0.64] 0.29 [1.10] 0.45 [1.70] 0.56 [2.12] 0.76 [2.88] 0.76 [2.88] 0.92 [3.48] 1.24 [4.69] 1.24 [4.69] 1.56 [5.91] 1.56 [5.91]

Vertical Upfl ow/Downfl ow

Air Coil Dimensions (h x w) - (in) [mm]

16 x 16[406 x 406]

Upfl ow Only

16 x 16[406 x 406]

Upfl ow Only

16 x 16[406 x 406]

Upfl ow Only

24 x 20[610 x 508]

28 x 20[711 x 508]

28 x 20[711 x 508]

28 x 25[711 x 635]

32 x 25[813 x 635]

32 x 25[813 x 635]

36 x 25[914 x 635]

36 x 25[914 x 635]

Standard Filter - 1” [25.4mm]

Throwaway,qty (in) [mm]

16 x 20[406 x 508]

16 x 20[406 x 508]

16 x 20[406 x 508]

24 x 24[610 x 610]

28 x 24[711 x 610]

28 x 24[711 x 610]

28 x 30[711 x 762]

2 - 16 x 30[2 - 406 x 762]

2 - 16 x 30[2 - 406 x 762]

1 - 16 x 30; 1 - 20 x 30

[1 - 406 x 762;1 - 508 x 762]

1 - 16 x 30; 1 - 20 x 30

[1 - 406 x 762;1 - 508 x 762]

Weight - Operating, (lbs) [kg] 136 [62] 156 [71] 160 [73] 257 [117] 266 [121] 268 [122] 327 [148] 414 [188] 416 [189] 441 [200] 443 [201]

Weight - Packaged, (lbs) [kg] 146 [66] 166 [75] 170 [77] 267 [121] 276 [125] 278 [126] 337 [153] 424 [192] 426 [193] 451 [205] 453 [205]

HorizontalAir Coil Dimensions

(h x w) - (in) [mm]16 x 16

[406 x 406]16 x 16

[406 x 406]16 x 16

[406 x 406]18 x 27

[457 x 686]18 x 31

[457 x 787]18 x 31

[457 x 787]20 x 35

[508 x 889]20 x 40

[508 x 1016]20 x 40

[508 x 1016]20 x 45

[508 x 1143]20 x 45

[508 x 1143]

Standard Filter - 1” [25.4mm]

Throwaway,qty (in) [mm]

16 x 20[406 x 508]

16 x 20[406 x 508]

16 x 20[406 x 508]

2 - 18 x 18[2 - 457 x

457]

2 - 18 x 18[2 - 457 x

457]

2 - 18 x 18[2 - 457 x 457]

1 - 12 x 20; 1- 20 x 25

[1 - 305 x 508;1 - 508 x 635]

1 - 18 x 20;1 - 20 x 24

[1 - 457 x 508;1 - 508 x 610]

1 - 18 x 20;1 - 20 x 24

[1 - 457 x 508;1 - 508 x 610]

2 - 20 x 24[2 - 508 x 610]

2 - 20 x 24[2 - 508 x 610]

Weight - Operating, (lbs) [kg] 136 [62] 156 [71] 160 [73] 257 [117] 266 [121] 268 [122] 327 [148] 414 [188] 416 [189] 441 [200] 443 [201]

Weight - Packaged, (lbs) [kg] 146 [66] 166 [75] 170 [77] 267 [121] 276 [125] 278 [126] 337 [153] 424 [192] 426 [193] 451 [205] 453 [205]

Notes:All units have TXV expansion device and 1/2” & 3/4” electrical knockouts.575 volt motors are two speed.For units with ClimaDry® II option add 66lbs (30kg) to weights.

Unit Maximum Water Working Pressure

Options Max Pressure PSIG [kPa]

Base Unit 500 [3,447]

Internal Secondary Pump (ISP) 145 [999]

ClimaDry® 145 [999]

Internal Motorized Water Valve (MWV) 300 [2,068]

Internal Auto Flow Valve 300 [2,068]Use the lowest maximum pressure rating when multiple options are combined.

Page 44: Submittal Data - Climate Master · The award winning Tranquility® Series raises the bar for water-source heat pump efficiencies, features and application flexibility. Not only does

ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.

Page ______ of ______LC377 - 44

TS Horizontal – Dimensional Data

notes:1. While clear access to all removable panels is not required, installer

should take care to comply with all building codes and allow adequate clearance for future field service.

2. Horizontal units shipped with filter bracket only. This bracket should be removed for return duct connection

3. Discharge flange and hanger brackets are factory installed.4. Condensate is 3/4” NPT.5. CCP and BSP requires 2’ service access.6. Blower service access is through back panel on straight discharge

units or through panel opposite air coil on back discharge units.

Legend:CCP = Control/Compressor Access Panel BSP = Blower Service Panel*ASP = Additional Service Panel (not required)

note: *ASP are removable panels that provide additional access to the units interior. Clear access to ASP panels is not required and they are not to be used in place of the mandatory CCP and BSP panels.

HorizontalModel

Overall Cabinet

*AWidth

BLength

CHeight

006 -012

incm

22.456.8

43.1107.8

17.343.1

018 incm

22.456.8

62.2158.0

19.348.9

024 - 030 incm

22.456.8

62.2158.0

19.348.9

036 incm

25.464.5

71.2180.8

21.354.0

042 - 048 incm

25.464.5

76.2193.5

21.354.0

060 - 070 incm

25.464.5

81.2206.2

21.354.0

HorizontalModel

Water Connections

1 2 3 4 5

LoopInD

Loop OutE

HWGInF

HWGOutG

HWaterLoopFPT

HWGFPT

006 - 012 incm

3.79.3

9.724.2 N/A N/A 0.8

2.0 1/2” N/A

018 incm

2.15.2

10.025.4

13.935.2

16.942.9

0.61.5 3/4” 1/2”

024 - 030 incm

2.15.2

10.025.4

13.935.2

16.942.9

0.61.5 3/4” 1/2”

036 incm

3.48.6

10.827.5

15.639.7

18.947.9

0.61.5 3/4” 1/2”

042 - 048 incm

3.48.6

10.827.5

15.639.7

18.947.9

0.61.5 1” 1/2”

060 - 070 incm

3.48.6

10.827.5

15.639.7

18.947.9

0.61.5 1” 1/2”

HorizontalModel

Electrical Knockouts

J1/2”

K1/2”

L3/4”

LowVoltage

ExternalPump

PowerSupply

006 -012

incm

3.89.4

6.315.6

8.821.9

018 incm

3.69.2

6.115.6

8.621.9

024 - 030 incm

3.69.2

6.115.6

8.621.9

036 incm

3.69.2

6.115.6

8.621.9

042 - 048 incm

3.69.2

6.115.6

8.621.9

060 - 070 incm

3.69.2

6.115.6

8.621.9

Water Connections - Units with ClimaDry®

1 2

LoopIn D

Loop Out E

N/A N/A

2.15.2

10.025.4

5.9615.14

13.1333.35

5.9615.14

13.1333.35

5.9615.14

13.1333.35

5.9615.14

13.1333.35

*Does not include air filter supports. Add 2 in. (5.1 cm) when a 1 in. (25.4 mm) filter is used, add 3 in. (7.6 cm) when a 2 in. (50.8 mm) filter is used.

Page 45: Submittal Data - Climate Master · The award winning Tranquility® Series raises the bar for water-source heat pump efficiencies, features and application flexibility. Not only does

ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.

Page ______ of ______LC377 - 45

TS Horizontal – Dimensional Data

Right Return Straight DischargeFront

NP

BlowerOutlet

M

O

Right Return

StraightDischarge5

ASP*

BackDischarge

Condensate3 / 4” NPT

H

Front-View

43

21

A

CCP

BSP

Right Return Right View -Air Coil Opening

Air Coil

C

VU

B

ASP* T

S

Front

P

BlowerOutlet

M

O

Left Return Straight DischargeFront

BSP

LEFT RETURN RIGHT RETURN

Air Coil

ASP*

Front

Left Return Left View -Air Coil Opening

1.1 [27.9mm]

C

V

T

SU

B

Unit Hanger Detail

X

Y

Fron

t

Z

Right Return Back Discharge

A

Air C

oil S

ide

C

RP

BlowerOutlet

Q

O

ASP* ASP*

BSP

FrontFront

Left Return

H

Condensate3 / 4” NPT

ASP*

ASP* ASP*CCPCCP

Air C

oil S

ide

O

A

C

Left Return Back Discharge

P

BlowerOutlet

Q

R

BSP

N

GF

DE

3.25[82.6mm] 3.25

[82.6mm]

1.6 [40.6mm]

Model X Y Zin. cm. in. cm. in. cm.

018-030 62.1 157.7 24.5 62.2 20.3 51.5036 71.1 180.6 27.5 69.9 23.3 59.1042-048 76.1 193.3 27.5 69.9 23.3 59.1060-070 81.1 206.0 27.5 69.9 23.3 59.1

KL

J

1.6 [40.6mm]

006-012 43.1 109.5 24.5 62.2 20.3 51.5

Power Supply3 / 4” [19.1mm] Knockout

1 / 2” [12.7mm]Knockout

Low Voltage1 / 2” [12.7mm]

Knockout

5StraightDischarge

BackDischargeNote: Choose either

back or straight dischargeNote: Choose either

back or straight discharge

Filter Rails RemovedSee A� ---- for accessory air �lter frame with duct collar

Note: *ASP are removable panels that provide additional access to the units interior. Clear access to ASP panels is not required and they are not to be used in placeof the mandatory CCP and BSP panels.

CCPCCP

HorizontalModel

Discharge ConnectionDuct Flange Installed

Return ConnectionUsing Return Air Opening

Return ConnectionUsing Optional Air Filter Frame

M NO

SupplyHeight

PSupplyWidth

Q RS

ReturnWidth

TReturnHeight

U VS

ReturnWidth

TReturnHeight

U V

006 - 012 incm

5.313.4

4.110.3

9.022.5

9.022.5

5.313.4

4.110.3

17.143.4

15.338.9

2.15.3

1.02.5

17.745.0

14.236.1

2.35.8

1.74.3

018 incm

3.69.3

2.05.1

15.539.4

12.531.8

3.69.2

2.05.2

28.171.4

17.343.9

6.215.7

1.02.5

33.885.8

16.241.0

2.35.8

1.74.3

024 - 030 incm

3.69.3

2.05.1

15.539.4

12.531.8

3.69.2

2.05.2

32.181.5

17.343.9

2.35.8

1.02.5

33.885.8

16.241.0

2.35.8

1.74.3

036 incm

*3.1 7.9

1.23.1

19.048.3

17.544.5

*3.1 7.9

1.02.6

36.191.7

19.349.0

2.35.7

1.02.5

34.888.3

18.246.1

3.17.8

1.74.3

042 - 048 incm

3.17.9

1.23.1

19.048.3

17.544.5

3.17.9

1.02.6

41.1104.4

19.349.0

2.35.7

1.02.5

39.8101.0

18.246.1

3.17.8

1.74.3

060 - 070 incm

3.17.9

1.23.1

19.048.3

17.544.5

3.17.9

1.02.6

46.1117.1

19.349.0

2.357

1.02.5

44.8113.7

18.246.1

3.17.8

1.74.3

*For units with modulating reheat option this dimension is 2.9 in. (7.4 cm). All dimensions +/- 0.20 in. (5.1 mm).

Page 46: Submittal Data - Climate Master · The award winning Tranquility® Series raises the bar for water-source heat pump efficiencies, features and application flexibility. Not only does

ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.

Page ______ of ______LC377 - 46

TS Horizontal – Service Access

Left Return Back Discharge Right Return Back DischargeSupply Air Flow

Supply Air Flow

Return Air Flow

Return Air Flow

Air C

oil

Air C

oil

Air C

oil

Air C

oil

Front Front

Front Front

BSP BSP

ASPASP ASP ASP

ASP ASP ASPASP

CCP CCP

CCP CCP

BSP BSP

Return Air Flow

Return Air Flow

Supply Air Flow

Supply Air Flow

Left Return Straight Discharge Right Return Straight Discharge

= mandatory 2′ service access

= (optional) additional 2′ service access

notes:1. While clear access to all removable panels is not required, installer should take care to comply with all building codes and allow adequate clearance for future field service. 2. CCP and BSP requires 2’ service access.3. Blower service access is through back panel on straight discharge units or through panel opposite air coil on back discharge units.4. ASP are removable panels that provide additional access to the units interior. Clear access to ASP panels is not required and they are not to be used in place of the mandatory CCP and BSP panels.

Legend:CCP = Control/Compressor Access Panel BSP = Blower Service PanelASP = Additional Service Panel (not required)

Page 47: Submittal Data - Climate Master · The award winning Tranquility® Series raises the bar for water-source heat pump efficiencies, features and application flexibility. Not only does

ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.

Page ______ of ______LC377 - 47

TS Vertical Upflow – Dimensional Data

notes:1. While clear access to all removable panels is not required,

installer should take care to comply with all building codes and allow adequate clearance for future field service.

2. Front & Side access is preferred for service access. However, all components may be serviced from the front access panel if side access is not available.

3. Discharge flange is field installed.4. Condensate is 3/4” NPT.

Legend:CCP = Control/Compressor Access Panel BSP = Blower Service PanelASP = Additional Service Panel (not required)

VerticalUpflowModel

Overall Cabinet

*AWidth

BDepth

CHeight

006 - 012

incm

22.456.8

21.654.9

34.587.6

018 incm

22.456.8

25.665.1

44.6113.3

024 - 030

incm

22.456.8

25.665.1

48.5123.2

036 incm

25.464.5

30.677.8

50.5128.3

042 - 048

incm

25.464.5

30.677.8

54.5138.4

060 - 070

incm

25.464.5

30.677.8

58.5148.6

VerticalUpflowModel

Water Connections

1 2 3 4 5

LoopInD

Loop OutE

HWGInF

HWGOutG

HWaterLoopFPT

HWGFPT

006 - 012

incm

3.79.4

9.724.6 N/A N/A 7.4

18.7 1/2” N/A

018 incm

2.15.2

10.025.4

13.935.2

16.942.9

7.819.8 3/4” 1/2”

024 - 030

incm

2.15.2

10.025.4

13.935.2

16.942.9

7.819.8 3/4” 1/2”

036 incm

3.48.6

10.827.5

15.639.7

18.947.9

7.819.8 3/4” 1/2”

042 - 048

incm

3.48.6

10.827.5

15.639.7

18.947.9

7.819.8 1” 1/2”

060 - 070

incm

3.48.6

10.827.5

15.639.7

18.947.9

7.819.8 1” 1/2”

VerticalUpflowModel

Electrical Knockouts

J1/2”

K1/2”

L3/4”

LowVoltage

ExternalPump

PowerSupply

006 - 012

incm

3.89.5

6.315.9

8.822.2

018 incm

3.69.2

6.115.6

8.621.9

024 - 030

incm

3.69.2

6.115.6

8.621.9

036 incm

3.69.2

6.115.6

8.621.9

042 - 048

incm

3.69.2

6.115.6

8.621.9

060 - 070

incm

3.69.2

6.115.6

8.621.9

*Does not include air filter supports. Add 2 in. (5.1 cm) when a 1 in. (25.4 mm) filter is used, add 3 in. (7.6 cm) when a 2 in. (50.8 mm) filter is used.

Air C

oil Side

Front

‡ † 1”

1”1”

6”

*Recommended Minimum Installation Clearances for Vertical Units*

1”Back of unit

Side opposite return air

6” Front if hard piped

Return Air Side

1”

Ducted return

- ‡ *Add for duct width

- † Add 2” for 1” filter frame/rail or 3” for 2” filter frame/rail

Free (open) return - calculate required dimension for a maximum velocity of 600 fpm

*Field installed accessories (hoses, air cleaners, etc.) and factory WSE option will require additional space. Top supply air is shown, the same clearances apply to bottom supply air units.

Page 48: Submittal Data - Climate Master · The award winning Tranquility® Series raises the bar for water-source heat pump efficiencies, features and application flexibility. Not only does

ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.

Page ______ of ______LC377 - 48

TS Vertical Upflow – Dimensional Data

Top View-Left ReturnTop View-Right Return

U

R S IsometricView

Left Return Left View- Air Coil Opening

T

CPower Supply

3 / 4" [19.1mm]HV Knockout

1 / 2" [12.7mm]Knockout

Low Voltage1 / 2" [12.7mm]

LV Knockout

Condensate3/4" FPT

Front-View

K

1.00 [25.4 mm]

G

J HE

F

DL

Air Coil

Field InstalledDischarge Flange

FrontBack

U

RS

C

BackFront

Right Return Right View- Air Coil Opening

BSP

CCP

Filter Rails

ASP*

Air Coil

Front

P N

O

Q

Fron

t

NB

P

AO

M

1.68 [42.7 mm]

1.18 [30.0 mm]

1.63[41.4 mm]

(Left Return)

1

2

5

34

ASP*

CCP

ASP*ASP*

ASP*

Air Coil

Air Coil SideAir Coil Side

Filter Rails RemovedSee A� ---- for accessory air �lter frame with duct collar

T

Note: *ASP are removable panels that provide additional access to the units interior. Clear access to ASP panels is not required and they are not to be used in place of the mandatory CCP and BSP panels.

H

VerticalUpflowModel

Discharge ConnectionDuct Flange Installed

Return ConnectionUsing Return Air Opening

Return Connection Using Optional Air Filter Frame

M NO

SupplyWidth

PSupplyDepth

Q RS

ReturnDepth

TReturnHeight

U RS

ReturnDepth

TReturnHeight

U

006 - 012 incm

6.717.0

6.316.0

9.022.9

9.022.9

6.717.0

2.35.8

17.143.3

15.338.9

1.02.5

1.74.3

17.745.0

14.236.1

1.74.3

018 incm

7.218.3

5.814.8

14.035.6

14.035.6

4.912.4

2.35.8

21.153.6

23.760.2

1.02.5

1.74.3

22.256.4

22.266.5

1.74.3

024 - 030 incm

7.218.3

5.814.8

14.035.6

14.035.6

4.912.4

2.35.8

21.153.6

27.770.4

1.02.5

1.74.3

22.256.4

26.266.5

1.74.3

036 incm

6.416.1

6.316.0

18.045.7

18.045.7

5.313.5

2.35.8

26.166.3

27.770.4

1.02.5

1.74.3

27.269.1

26.266.5

1.74.3

042 - 048 incm

6.416.1

6.316.0

18.045.7

18.045.7

5.313.5

2.35.8

26.166.3

30.577.5

1.02.5

1.74.3

27.269.1

30.276.7

1.74.3

060 - 070 incm

6.416.1

6.316.0

18.045.7

18.045.7

5.313.5

2.35.8

26.166.3

35.790.7

1.02.5

1.74.3

27.269.1

34.286.9

1.74.3

All dimensions +/- .20 in, (+/- 5.1 mm).

Page 49: Submittal Data - Climate Master · The award winning Tranquility® Series raises the bar for water-source heat pump efficiencies, features and application flexibility. Not only does

ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.

Page ______ of ______LC377 - 49

TS Vertical – Service Access

Vertical Units

Left Return

Right Return

= mandatory 2′ service access

= (optional) additional 2′ service access

ASPASPAi

r Coi

l

Front

CCP and BSP

Supply Air Opening

ASPASP

Air C

oil

Front

CCP and BSP

Supply Air Opening

notes:1. While clear access to all removable panels is not required, installer should take care to comply with all building codes and allow adequate clearance for future field service. 2. Front & Side access is preferred for service access. However, all components may be serviced from the front access panel if side access is not available.3. ASP are removable panels that provide additional access to the units interior. Clear access to ASP panels is not required and they are not to be used in place of the mandatory CCP and BSP panels.4. Top supply air is shown, the same clearances apply to bottom supply air units.

Legend:CCP = Control/Compressor Access Panel BSP = Blower Service PanelASP = Additional Service Panel (not required)

Page 50: Submittal Data - Climate Master · The award winning Tranquility® Series raises the bar for water-source heat pump efficiencies, features and application flexibility. Not only does

ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.

Page ______ of ______LC377 - 50

TS Vertical Downflow – Dimensional Data

VerticalDownflow

Model

Water Connections

1 2 3 4 5

LoopInD

Loop OutE

HWGInF

HWGOutG

HWaterLoopFPT

HWGFPT

018 incm

17.243.7

9.323.6

5.413.7

2.46.1

3.69.2 3/4” 1/2”

024 - 030 incm

17.945.5

10.526.7

5.714.5

2.46.1

3.69.2 3/4” 1/2”

036 incm

17.945.5

10.526.7

5.714.5

2.46.1

3.69.2 3/4” 1/2”

042 - 048 incm

17.945.5

10.526.7

5.714.5

2.46.1

3.69.2 1” 1/2”

060 - 070 incm

17.945.5

10.526.7

5.714.5

2.46.1

3.69.2 1” 1/2”

VerticalDownflow

Model

Electrical Knockouts

J1/2”

K1/2”

L3/4”

LowVoltage

ExternalPump

PowerSupply

018 incm

3.69.2

6.115.6

8.621.9

024 - 030 incm

3.69.2

6.115.6

8.621.9

036 incm

3.69.2

6.115.6

8.621.9

042 - 048 incm

3.69.2

6.115.6

8.621.9

060 - 070 incm

3.69.2

6.115.6

8.621.9

VerticalDownflow

Model

Overall Cabinet

*AWidth

BDepth

CHeight

018 incm

22.456.8

25.665.1

48.4122.9

024 - 030 incm

22.456.8

25.665.1

52.5133.4

036 incm

25.464.5

30.677.8

54.5138.4

042 - 048 incm

25.464.5

30.677.8

58.5148.6

060 - 070 incm

25.464.5

30.677.8

62.5158.8

*Does not include air filter supports. Add 2 in. (5.1 cm) when a 1 in. (25.4 mm) filter is used, add 3 in. (7.6 cm) when a 2 in. (50.8 mm) filter is used.

Recommended Minimum Installation Clearances for Vertical Units*

1”Back of unit

Side opposite return air

6” Front if hard piped

Return Air Side

1”

Ducted return

- ‡ *Add for duct width

- † Add 2” for 1” filter frame/rail or 3” for 2” filter frame/rail

Free (open) return - calculate required dimension for a maximum velocity of 600 fpm

*Field installed accessories (hoses, air cleaners, etc.) and factory WSE option will require additional space. Top supply air is shown, the same clearances apply to bottom supply air units.

Air C

oil Side

Front

‡ † 1”

1”1”

6”

*

Page 51: Submittal Data - Climate Master · The award winning Tranquility® Series raises the bar for water-source heat pump efficiencies, features and application flexibility. Not only does

ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.

Page ______ of ______LC377 - 51

TS Vertical Downflow – Dimensional Data

Air Coil Side

G F

D

K JL 4

3

2

1

5

CCP

T

U

R S

Air Coil

ASP*

FrontBackFront-View

BSP

Left Return Left View- Air Coil Opening

Condensate3 / 4” FPT Left Return

Condensate3 / 4” FPT Right Return

5

1.1 [27.9mm]1.6 [40.6 mm]

T

U

S

Air Coil

FrontBack

Right Return Right View- Air Coil Opening

R

ASP*

Front

P

O

N

M

BlowerOpening

H

C

B

AFront

P

O

N

Q

BlowerOpening

B

A

Right Return DischargeFloor Foot Print

Left Return DischargeFloor Foot Print

Isometric View(Right Return)

Condensate 3/4”FPT

ASP*

ASP*CCP

BSP

Filter Rail

ASP*

E

Air Coil Side

1.6 [40.6 mm]Power Suppl y3 / 4” [19.1 mm]HV Knockout1 / 2” [12.7 mm]

KnockoutLow Voltage

1 / 2” [12.7 mm]LV Knockout

Filter Rails RemovedSee A� ---- for accessory air �lter frame

with duct collar

Notes:1. While clear access to all removable panels is not required,

installer should take care to comply with all building codes and allow adequate clearance for future field service.

2. Front & Side access is preferred for service access. However, all components may be serviced from the front access panel if side access is not available.

3. Condensate is 3/4” FPT PVC.4. ASP are removable panels that provide additional access to the

units interior. Clear access to ASP panels is not required and they are not to be used in place of the mandatory CCP and BSP panels.

Legend:CCP = Control/Compressor Access Panel BSP = Blower Service PanelASP = Additional Service Panel (not required)

VerticalDownflow

Model

Discharge ConnectionDuct Flange Installed

Return ConnectionUsing Return Air Opening

Return ConnectionUsing Optional Air Filter Frame

M NO

SupplyWidth

PSupplyDepth

Q RS

ReturnDepth

TReturnHeight

U RS

ReturnDepth

TReturnHeight

U

018 incm

6.717.1

8.421.4

10.125.7

9.123.0

10.827.4

2.25.6

21.153.6

23.760.2

21.253.8

1.74.3

22.256.4

22.256.4

21.955.6

024 - 030 incm

6.717.1

8.421.4

10.125.7

9.123.0

10.827.4

2.25.6

21.153.6

27.770.4

21.253.8

1.74.3

22.256.4

26.266.5

21.955.6

036 incm

7.218.3

9.022.9

13.434.0

12.932.7

10.426.5

2.25.6

26.166.3

27.770.4

23.258.9

1.74.3

27.269.1

26.266.5

23.960.7

042 - 048 incm

7.218.3

9.022.9

13.434.0

12.932.7

10.426.5

2.25.6

26.166.3

30.577.5

23.258.9

1.74.3

27.269.1

30.276.7

23.960.7

060 - 070 incm

7.218.3

9.022.9

13.434.0

12.932.7

10.426.5

2.25.6

26.166.3

35.790.7

23.258.9

1.74.3

27.269.1

34.286.9

23.960.7

All dimensions +/- .20 in, (+/- 5.1 mm).

Page 52: Submittal Data - Climate Master · The award winning Tranquility® Series raises the bar for water-source heat pump efficiencies, features and application flexibility. Not only does

ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.

Page ______ of ______LC377 - 52

Corner Weights for TSH Series Unit

Model Total Left-Front* Right-Front* Left-Back* Right-Back*

006Lbs 136 45.0 30.0 33.0 28.0

kg 62 20.4 13.6 15.0 12.7

009Lbs 156 55.0 33.0 36.0 32.0

kg 71 24.9 15.0 16.3 14.5

012Lbs 160 56.0 34.0 37.0 33.0

kg 73 25.4 15.4 16.8 15.0

018Lbs 257 78.1 64.6 66.2 47.5

kg 117 35.4 29.3 30.0 21.6

024Lbs 266 78.8 67.2 69.9 50.2

kg 122 35.7 30.5 31.7 22.7

030Lbs 268 79.4 67.7 70.4 50.5

kg 122 36.0 30.7 31.9 22.9

036Lbs 327 104.4 74.9 83.7 64.0

kg 148 47.4 34.0 38.0 29.0

042Lbs 414 144.3 92.1 97.7 79.9

kg 188 65.4 41.8 44.3 36.2

048Lbs 416 145.0 92.6 98.1 80.3

kg 189 65.8 42.0 44.5 36.4

060Lbs 441 182.3 72.5 78.4 107.8

kg 200 82.7 32.9 35.6 48.9

070Lbs 443 183.1 72.8 78.8 108.3

kg 201 83.1 33.0 35.7 49.1*Front is control box end.

Page 53: Submittal Data - Climate Master · The award winning Tranquility® Series raises the bar for water-source heat pump efficiencies, features and application flexibility. Not only does

ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.

Page ______ of ______LC377 - 53

Electrical Data – PSC Motor & ClimaDry®

All TS Units with Standard PSC Motor TS Units (PSC) TS Units with PSC Fan Motor and ClimaDry®

Model Voltage Code

Rated Voltage

Voltage Min/Max

Compressor Fan Motor FLA

Total Unit FLA

Min Circuit Amp

Max Fuse/ HACR

ReheatPumpFLA

Total Unit FLA

Min Circuit Amp

Max Fuse/ HACRQTY RLA LRA

018G 208/230/60/1 197/254 1 9.0 48.0 1.0 10.0 12.3 20 0.8 10.8 13.1 20E 265/60/1 239/292 1 8.4 40.0 0.9 9.3 11.4 15 0.7 10.0 12.1 20

024

G 208/230/60/1 197/254 1 13.5 58.3 1.6 15.1 18.5 30 0.8 15.9 19.3 30E 265/60/1 239/292 1 9 54.0 1.1 10.1 12.4 20 0.7 10.8 13.1 20H 208/230/60/3 197/254 1 7.1 55.4 1.6 8.7 10.5 15 0.8 9.5 11.3 15F* 460/60/3* 414/506 1 3.5 28.0 0.9 4.4 5.3 15 0.7 5.1 6.0 15

030

G 208/230/60/1 197/254 1 12.8 64.0 1.8 14.6 17.8 30 0.8 15.4 18.6 30E 265/60/1 239/292 1 10.9 60.0 1.4 12.3 15.0 25 0.7 13.0 15.7 25H 208/230/60/3 197/254 1 8.3 58.0 1.8 10.1 12.2 20 0.8 10.9 13.0 20F* 460/60/3* 414/506 1 5.1 28.0 1.0 6.1 7.4 15 0.7 6.8 8.1 15

036

G 208/230/60/1 197/254 1 16.0 77.0 1.8 17.8 21.8 35 0.8 18.6 22.6 35E 265/60/1 239/292 1 12.2 72.0 2.0 14.2 17.3 25 0.7 14.9 18.0 30H 208/230/60/3 197/254 1 10 71.0 1.8 11.8 14.3 20 0.8 12.6 15.1 25F* 460/60/3* 414/506 1 4.7 38.0 1.0 5.7 6.9 15 0.7 6.4 7.6 15

042

G 208/230/60/1 197/254 1 16.7 79.0 2.2 18.9 23.1 35 0.8 19.7 23.9 40E 265/60/1 239/292 1 13.5 72.0 1.7 15.2 18.6 30 0.7 15.9 19.3 30H 208/230/60/3 197/254 1 10.4 73.0 2.2 12.6 15.2 25 0.8 13.4 16.0 25F* 460/60/3* 414/506 1 5.8 38.0 1.0 6.8 8.3 15 0.7 7.5 9.0 15N 575/60/3 518/633 1 3.8 36.5 0.8 4.6 5.6 15 N/A N/A N/A N/A

048

G 208/230/60/1 197/254 1 21.8 117.0 2.7 24.5 30.0 50 1.1 25.6 31.0 50E 265/60/1 239/292 1 16.3 98.0 2.9 19.2 23.3 35 1.3 20.5 24.6 40H 208/230/60/3 197/254 1 13.7 83.1 2.7 16.4 19.8 30 1.1 17.5 20.9 30F* 460/60/3* 414/506 1 6.2 41.0 1.7 7.9 9.5 15 1.3 9.0 10.6 15N 575/60/3 518/633 1 4.8 33.0 1.4 6.2 7.4 15 N/A N/A N/A N/A

060

G 208/230/60/1 197/254 1 26.4 134.0 3.8 30.2 36.8 60 1.1 31.3 37.9 60H 208/230/60/3 197/254 1 16 110.0 3.8 19.8 23.8 35 1.1 20.9 24.9 40F* 460/60/3* 414/506 1 7.8 52.0 1.3 9.1 11.1 15 1.3 10.4 12.4 20N 575/60/3 518/633 1 5.7 38.9 2.2 7.9 9.3 15 N/A N/A N/A N/A

070

G 208/230/60/1 197/254 1 30.8 178.0 4.0 34.8 42.5 70 1.1 35.9 43.6 70H 208/230/60/3 197/254 1 19.6 138.0 4.0 23.6 28.5 45 1.1 24.7 29.6 45F* 460/60/3* 414/506 1 8.2 66.1 2.6 10.8 12.9 20 1.3 12.1 14.2 20N 575/60/3 518/633 1 6.6 55.3 1.5 8.1 9.8 15 N/A N/A N/A N/A

* NEUTRAL CONNECTION REQUIRED! All F Voltage (460 vac) units with ClimaDry® require a four wire power supply with neutral. Reheat pump is rated 265 vac and is wired between one hot leg and neutral.

Page 54: Submittal Data - Climate Master · The award winning Tranquility® Series raises the bar for water-source heat pump efficiencies, features and application flexibility. Not only does

ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.

Page ______ of ______LC377 - 54

Electrical Data – High Static PSC Motor & ClimaDry®

All TS Units with High Static PSC Fan Motor TS (H.S. PSC) Units TS Units with H.S. PSC Fan Motorand ClimaDry®

Model Voltage Code

Rated Voltage

Voltage Min/Max

Compressor Fan Motor FLA

Total Unit FLA

Min Circuit Amp

Max Fuse/ HACR

ReheatPumpFLA

Total Unit FLA

Min Circuit Amp

Max Fuse/ HACRQTY RLA LRA

018G 208/230/60/1 197/254 1 9.0 48.0 1.1 10.1 12.4 20 0.8 10.9 13.2 20

E 265/60/1 239/292 1 8.4 40.0 0.9 9.3 11.4 15 0.7 10.0 12.1 20

024

G 208/230/60/1 197/254 1 13.5 58.3 1.8 15.3 18.7 30 0.8 16.1 19.5 30

E 265/60/1 239/292 1 9 54.0 1.4 10.4 12.7 20 0.7 11.1 13.4 20

H 208/230/60/3 197/254 1 7.1 55.4 1.8 8.9 10.7 15 0.8 9.7 11.5 15

F* 460/60/3* 414/506 1 3.5 28.0 1 4.5 5.4 15 0.7 5.2 6.1 15

030

G 208/230/60/1 197/254 1 12.8 64.0 2.2 15.0 18.2 30 0.8 15.8 19.0 30

E 265/60/1 239/292 1 10.9 60.0 1.7 12.6 15.3 25 0.7 13.3 16.0 25

H 208/230/60/3 197/254 1 8.3 58.0 2.2 10.5 12.6 20 0.8 11.3 13.4 20

F* 460/60/3* 414/506 1 5.1 28.0 1.0 6.1 7.4 15 0.7 6.8 8.1 15

036

G 208/230/60/1 197/254 1 16.0 77.0 2.2 18.2 22.2 35 0.8 19.0 23.0 35

E 265/60/1 239/292 1 12.2 72.0 1.7 13.9 17.0 25 0.7 14.6 17.7 25

H 208/230/60/3 197/254 1 10 71.0 2.2 12.2 14.7 25 0.8 13.0 15.5 25

F* 460/60/3* 414/506 1 4.7 38.0 1.0 5.7 6.9 15 0.7 6.4 7.6 15

042

G 208/230/60/1 197/254 1 16.7 79.0 2.7 19.4 23.6 35 0.8 20.2 24.4 40

E 265/60/1 239/292 1 13.5 72.0 2.9 16.4 19.8 30 0.7 17.1 20.5 30

H 208/230/60/3 197/254 1 10.4 73.0 2.7 13.1 15.7 25 0.8 13.9 16.5 25

F* 460/60/3* 414/506 1 5.8 38.0 1.7 7.5 9.0 15 0.7 8.2 9.7 15

N 575/60/3 518/633 1 3.8 36.5 1.4 5.2 6.2 15 N/A N/A N/A N/A

048

G 208/230/60/1 197/254 1 21.8 117.0 2.6 24.4 29.9 50 1.1 25.5 31.0 50

H 208/230/60/3 197/254 1 13.7 83.1 2.6 16.3 19.7 30 1.1 17.4 20.8 30

F* 460/60/3* 414/506 1 6.2 41.0 1.8 8.0 9.6 15 1.3 9.3 10.9 15

N 575/60/3 518/633 1 4.8 33.0 1.4 6.2 7.4 15 N/A N/A N/A N/A

060

G 208/230/60/1 197/254 1 26.4 134.0 4.0 30.4 37.0 60 1.1 31.5 38.1 60

H 208/230/60/3 197/254 1 16 110.0 4.0 20.0 24.0 35 1.1 21.1 25.1 40

F* 460/60/3* 414/506 1 7.8 52.0 2.6 10.4 12.4 15 1.3 11.7 13.7 20

N 575/60/3 518/633 1 5.7 38.9 1.5 7.2 8.6 15 N/A N/A N/A N/A

* NEUTRAL CONNECTION REQUIRED! All F Voltage (460 vac) units with ClimaDry® require a four wire power supply with neutral. Reheat pump is rated 265 vac and is wired between one hot leg and neutral.

Page 55: Submittal Data - Climate Master · The award winning Tranquility® Series raises the bar for water-source heat pump efficiencies, features and application flexibility. Not only does

ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.

Page ______ of ______LC377 - 55

Electrical Data – ECM Motor & ClimaDry®

All TS Units with ECM Fan Motor TS Units (ECM) TS Units with ECM Fan Motor and ClimaDry®

Model Voltage Code

Rated Voltage

Voltage Min/Max

Compressor Fan Motor FLA

Total Unit FLA

Min Circuit Amp

Max Fuse/ HACR

ReheatPumpFLA

Total Unit FLA

Min Circuit Amp

Max Fuse/ HACRQTY RLA LRA

018G 208/230/60/1 197/254 1 9.0 48.0 3.9 12.9 15.2 20 0.8 13.7 16.0 20

E 265/60/1 239/292 1 8.4 40.0 3.2 11.6 13.7 20 0.7 12.3 14.4 20

024

G 208/230/60/1 197/254 1 13.5 58.3 3.9 17.4 20.8 30 0.8 18.2 21.6 35

E 265/60/1 239/292 1 9 54.0 3.2 12.2 14.5 20 0.7 12.9 15.2 20

H 208/230/60/3 197/254 1 7.1 55.4 3.9 11.0 12.8 15 0.8 11.8 13.6 20

F* 460/60/3* 414/506 1 3.5 28.0 3.2 6.7 7.6 15 0.7 7.4 8.3 15

030

G 208/230/60/1 197/254 1 12.8 64.0 3.9 16.7 19.9 30 0.8 17.5 20.7 30

E 265/60/1 239/292 1 10.9 60.0 3.2 14.1 16.8 25 0.7 14.8 17.5 25

H 208/230/60/3 197/254 1 8.3 58.0 3.9 12.2 14.3 20 0.8 13.0 15.1 20

F* 460/60/3* 414/506 1 5.1 28.0 3.2 8.3 9.6 15 0.7 9.0 10.3 15

036

G 208/230/60/1 197/254 1 16.0 77.0 3.9 19.9 23.9 35 0.8 20.7 24.7 40

E 265/60/1 239/292 1 12.2 72.0 3.2 15.4 18.5 30 0.7 16.1 19.2 30

H 208/230/60/3 197/254 1 10 71.0 3.9 13.9 16.4 25 0.8 14.7 17.2 25

F* 460/60/3* 414/506 1 4.7 38.0 3.2 7.9 9.1 15 0.7 8.6 9.8 15

042

G 208/230/60/1 197/254 1 16.7 79. 3.9 20.6 24.8 40 0.8 21.4 25.6 40

E 265/60/1 239/292 1 13.5 72.0 3.2 16.7 20.1 30 0.7 17.4 20.8 30

H 208/230/60/3 197/254 1 10.4 73.0 3.9 14.3 16.9 25 0.8 15.1 17.7 25

F* 460/60/3* 414/506 1 5.8 38.0 3.2 9.0 10.5 15 0.7 9.7 11.2 15

048

G 208/230/60/1 197/254 1 21.8 117.0 6.9 28.7 34.2 50 1.1 29.8 35.3 50

E 265/60/1 239/292 1 16.3 98.0 6.0 22.3 26.4 40 1.3 23.6 27.7 40

H 208/230/60/3 197/254 1 13.7 83.1 6.9 20.6 24.0 35 1.1 21.7 25.1 35

F* 460/60/3* 414/506 1 6.2 41.0 6.0 12.2 13.8 20 1.3 13.5 15.1 20

060

G 208/230/60/1 197/254 1 26.4 134.0 6.9 33.3 39.9 60 1.1 34.4 41.0 60

E 265/60/1 239/292 1 19.9 130.0 6.0 25.9 30.9 50 1.3 27.2 32.2 50

H 208/230/60/3 197/254 1 16 110.0 6.9 22.9 26.9 40 1.1 24.0 28.0 40

F* 460/60/3* 414/506 1 7.8 52.0 6.0 13.8 15.8 20 1.3 15.1 17.1 20

070

G 208/230/60/1 197/254 1 30.8 178.0 6.9 37.7 45.4 70 1.1 37.9 45.6 70

H 208/230/60/3 197/254 1 19.6 138.0 6.9 26.5 31.4 50 1.1 27.6 32.5 50

F* 460/60/3* 414/506 1 8.2 66.1 6.0 14.2 16.3 20 1.3 15.5 17.6 25

* NEUTRAL CONNECTION REQUIRED! All F Voltage (460 vac) units with ECM motors/ClimaDry® require a four wire power supply with neutral. ECM motors/reheat pumps are rated 265 vac and are wired between one hot leg and neutral.

Page 56: Submittal Data - Climate Master · The award winning Tranquility® Series raises the bar for water-source heat pump efficiencies, features and application flexibility. Not only does

ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.

Page ______ of ______LC377 - 56

Electrical Data – PSC Motor & Secondary Pump

All TS Units with Standard PSC Motor TS Units (PSC) TS Units with PSC Fan Motor and Secondary Pump

Model Voltage Code

Rated Voltage

Voltage Min/Max

Compressor Fan Motor FLA

Total Unit FLA

Min Circuit Amp

Max Fuse/ HACR

PumpFLA

Total Unit FLA

Min Circuit Amp

Max Fuse/ HACRQTY RLA LRA

006G 208/230/60/1 197/254 1 3.1 17.7 0.4 3.5 4.3 15 0.4 3.9 4.7 15

E 265/60/1 239/292 1 2.6 13.5 0.4 3.0 3.6 15 0.7 3.7 4.3 15

009G 208/230/60/1 197/254 1 3.9 21.0 0.4 4.3 5.3 15 0.4 4.7 5.7 15

E 265/60/1 239/292 1 3.7 22.0 0.4 4.1 5.0 15 0.7 4.8 5.7 15

012G 208/230/60/1 197/254 1 5.0 25.0 0.7 5.7 7.0 15 0.4 6.1 7.4 15

E 265/60/1 239/292 1 4.5 22.0 0.7 5.2 6.4 15 0.7 5.9 7.0 15

018G 208/230/60/1 197/254 1 9.0 48.0 1.0 10.0 12.3 20 0.4 10.4 12.7 20

E 265/60/1 239/292 1 8.4 40.0 0.9 9.3 11.4 15 0.7 10.0 12.1 20

024

G 208/230/60/1 197/254 1 13.5 58.3 1.6 15.1 18.5 30 0.4 15.5 18.9 30

E 265/60/1 239/292 1 9 54.0 1.1 10.1 12.4 20 0.7 10.8 13.1 20

H 208/230/60/3 197/254 1 7.1 55.4 1.6 8.7 10.5 15 0.4 9.13 10.9 15

F* 460/60/3* 414/506 1 3.5 28.0 0.9 4.4 5.3 15 0.7 5.1 6.0 15

030

G 208/230/60/1 197/254 1 12.8 64.0 1.8 14.6 17.8 30 0.8 15.4 18.6 30

E 265/60/1 239/292 1 10.9 60.0 1.4 12.3 15.0 25 0.7 13.0 15.7 25

H 208/230/60/3 197/254 1 8.3 58.0 1.8 10.1 12.2 20 0.8 10.9 13.0 20

F* 460/60/3* 414/506 1 5.1 28.0 1.0 6.1 7.4 15 0.7 6.8 8.1 15

036

G 208/230/60/1 197/254 1 16.0 77.0 1.8 17.8 21.8 35 0.8 18.6 22.6 35

E 265/60/1 239/292 1 12.2 72.0 2.0 14.2 17.3 25 0.7 14.9 18.0 30

H 208/230/60/3 197/254 1 10 71.0 1.8 11.8 14.3 20 0.8 12.6 15.1 25

F* 460/60/3* 414/506 1 4.7 38.0 1.0 5.7 6.9 15 0.7 6.4 7.6 15

042

G 208/230/60/1 197/254 1 16.7 79.0 2.2 18.9 23.1 35 0.8 19.7 23.9 40

E 265/60/1 239/292 1 13.5 72.0 1.7 15.2 18.6 30 0.7 15.9 19.3 30

H 208/230/60/3 197/254 1 10.4 73.0 2.2 12.6 15.2 25 0.8 13.4 16.0 25

F* 460/60/3* 414/506 1 5.8 38.0 1.0 6.8 8.3 15 0.7 7.5 9.0 15

N 575/60/3 518/633 1 3.8 36.5 0.8 4.6 5.6 15 N/A N/A N/A N/A

048

G 208/230/60/1 197/254 1 21.8 117.0 2.7 24.5 30.0 50 0.8 25.3 30.8 50

E 265/60/1 239/292 1 16.3 98.0 2.9 19.2 23.3 35 0.7 19.9 24.0 40

H 208/230/60/3 197/254 1 13.7 83.1 2.7 16.4 19.8 30 0.8 17.2 20.6 30

F* 460/60/3* 414/506 1 6.2 41.0 1.7 7.9 9.5 15 0.7 8.6 10.2 15

N 575/60/3 518/633 1 4.8 33.0 1.4 6.2 7.4 15 N/A N/A N/A N/A

060

G 208/230/60/1 197/254 1 26.4 134.0 3.8 30.2 36.8 60 1.1 31.3 37.9 60

H 208/230/60/3 197/254 1 16 110.0 3.8 19.8 23.8 35 1.1 20.9 24.9 40

F* 460/60/3* 414/506 1 7.8 52.0 1.3 9.1 11.1 15 1.3 10.4 12.4 20

N 575/60/3 518/633 1 5.7 38.9 2.2 7.9 9.3 15 N/A N/A N/A N/A

070

G 208/230/60/1 197/254 1 30.8 178.0 4.0 34.8 42.5 70 1.1 35.9 43.6 70

H 208/230/60/3 197/254 1 19.6 138.0 4.0 23.6 28.5 45 1.1 24.7 29.6 45

F* 460/60/3* 414/506 1 8.2 66.1 2.6 10.8 12.9 20 1.3 12.1 14.2 20

N 575/60/3 518/633 1 6.6 55.3 1.5 8.1 9.8 15 N/A N/A N/A N/A

* NEUTRAL CONNECTION REQUIRED! All F Voltage (460 vac) units with internal secondary circulators require a four wire power supply with neutral. Internal secondary circulators are rated 265 vac and are wired between one hot leg and neutral.

Page 57: Submittal Data - Climate Master · The award winning Tranquility® Series raises the bar for water-source heat pump efficiencies, features and application flexibility. Not only does

ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.

Page ______ of ______LC377 - 57

Electrical Data – High Static PSC Motor & Secondary Pump

All TS Units with High Static PSC Fan Motor TS (H.S. PSC) Units TS Units with H.S. PSC Fan Motor and Secondary Pump

Model Voltage Code

Rated Voltage

Voltage Min/Max

Compressor Fan Motor FLA

Total Unit FLA

Min Circuit Amp

Max Fuse/ HACR

PumpFLA

Total Unit FLA

Min Circuit Amp

Max Fuse/ HACRQTY RLA LRA

018G 208/230/60/1 197/254 1 9.0 48.0 1.1 10.1 12.4 20 0.4 10.5 12.8 20

E 265/60/1 239/292 1 8.4 40.0 0.9 9.3 11.4 15 0.7 10.0 12.1 20

024

G 208/230/60/1 197/254 1 13.5 58.3 1.8 15.3 18.7 30 0.4 15.7 19.1 30

E 265/60/1 239/262 1 9 54.0 1.4 10.4 12.7 20 0.7 11.1 13.4 20

H 208/230/60/3 197/254 1 7.1 55.4 1.8 8.9 10.7 15 0.4 9.3 11.1 15

F* 460/60/3* 414/506 1 3.5 28.0 1 4.5 5.4 15 0.7 5.2 6.1 15

030

G 208/230/60/1 197/254 1 12.8 64.0 2.2 15.0 18.2 30 0.8 15.8 19.0 30

E 265/60/1 239/292 1 10.9 60.0 1.7 12.6 15.3 25 0.7 13.3 16.0 25

H 208/230/60/3 197/254 1 8.3 58.0 2.2 10.5 12.6 20 0.8 11.3 13.4 20

F* 460/60/3* 414/506 1 5.1 28.0 1.0 6.1 7.4 15 0.7 6.8 8.1 15

036

G 208/230/60/1 197/254 1 16.0 77.0 2.2 18.2 22.2 35 0.8 19.0 23.0 35

E 265/60/1 239/292 1 12.2 72.0 1.7 13.9 29.2 25 0.7 14.6 17.7 25

H 208/230/60/3 197/254 1 10 71.0 2.2 12.2 14.7 25 0.8 13.0 15.5 25

F* 460/60/3* 414/506 1 4.7 38.0 1.0 5.7 6.9 15 0.7 6.4 7.6 15

042

G 208/230/60/1 197/254 1 16.7 79.0 2.7 19.4 23.6 35 0.8 20.2 24.4 40

E 265/60/1 239/292 1 13.5 72.0 2.9 16.4 19.8 30 0.7 17.1 20.5 30

H 208/230/60/3 197/254 1 10.4 73.0 2.7 13.1 15.7 25 0.8 13.9 16.5 25

F* 460/60/3* 414/506 1 5.8 38.0 1.7 7.5 9.0 15 0.7 8.2 9.7 15

N 575/60/3 518/633 1 3.8 36.5 1.4 5.2 6.2 15 N/A N/A N/A N/A

048

G 208/230/60/1 197/254 1 21.8 117.0 2.6 24.4 29.9 50 0.8 25.2 30.7 50

H 208/230/60/3 197/254 1 13.7 83.1 2.6 16.3 19.7 30 0.8 17.1 20.5 30

F* 460/60/3* 414/506 1 6.2 41.0 1.8 8.0 9.6 15 0.7 8.7 10.3 15

N 575/60/3 518/633 1 4.8 33.0 1.4 6.2 7.4 15 N/A N/A N/A N/A

060

G 208/230/60/1 197/254 1 26.4 134.0 4.0 30.4 37.0 60 1.1 31.5 38.1 60

H 208/230/60/3 197/254 1 16 110.0 4.0 20.0 24.0 35 1.1 21.1 25.1 40

F* 460/60/3* 414/506 1 7.8 52.0 2.6 10.4 12.4 15 1.3 11.7 13.7 20

N 575/60/3 518/633 1 5.7 38.9 1.5 7.2 8.6 15 N/A N/A N/A N/A

* NEUTRAL CONNECTION REQUIRED! All F Voltage (460 vac) units with internal secondary circulators require a four wire power supply with neutral.Internal secondary circulators are rated 265 vac and are wired between one hot leg and neutral.

Page 58: Submittal Data - Climate Master · The award winning Tranquility® Series raises the bar for water-source heat pump efficiencies, features and application flexibility. Not only does

ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.

Page ______ of ______LC377 - 58

Electrical Data – ECM Motor & Secondary Pump

All TS Units with ECM Fan Motor TS Units (ECM) TS Units with ECM Fan Motor and Secondary Pump

Model Voltage Code

Rated Voltage

Voltage Min/Max

Compressor Fan Motor FLA

Total Unit FLA

Min Circuit Amp

Max Fuse/ HACR

PumpFLA

Total Unit FLA

Min Circuit Amp

Max Fuse/ HACRQTY RLA LRA

018G 208/230/60/1 197/254 1 9.0 48.0 3.9 12.9 15.2 20 0.4 13.3 15.6 20

E 265/60/1 239/292 1 8.4 40.0 3.2 11.6 13.7 20 0.7 12.3 14.4 20

024

G 208/230/60/1 197/254 1 13.5 58.3 3.9 17.4 20.8 30 0.4 17.8 21.2 30

E 265/60/1 239/292 1 9 54.0 3.2 12.2 14.5 20 0.7 12.9 15.2 20

H 208/230/60/3 197/254 1 7.1 55.4 3.9 11.0 12.8 15 0.4 11.4 13.2 20

F* 460/60/3* 414/506 1 3.5 28.0 3.2 6.7 7.6 15 0.7 7.4 8.3 15

030

G 208/230/60/1 197/254 1 12.8 64.0 3.9 16.7 19.9 30 0.8 17.5 20.7 30

E 265/60/1 239/292 1 10.9 60.0 3.2 14.1 16.8 25 0.7 14.8 17.5 25

H 208/230/60/3 197/254 1 8.3 58.0 3.9 12.2 14.3 20 0.8 13.0 15.1 20

F* 460/60/3* 414/506 1 5.1 28.0 3.2 8.3 9.6 15 0.7 9.0 10.3 15

036

G 208/230/60/1 197/254 1 16.0 77.0 3.9 19.9 23.9 35 0.8 20.7 24.7 40

E 265/60/1 239/292 1 12.2 72.0 3.2 15.4 30.7 30 0.7 16.1 19.2 30

H 208/230/60/3 197/254 1 10 71.0 3.9 13.9 16.4 25 0.8 14.7 17.2 25

F* 460/60/3* 414/506 1 4.7 38.0 3.2 7.9 9.1 15 0.7 8.6 9.8 15

042

G 208/230/60/1 197/254 1 16.7 79.0 3.9 20.6 24.8 40 0.8 21.4 25.6 40

E 265/60/1 239/292 1 13.5 72.0 3.2 16.7 20.1 30 0.7 17.4 20.8 30

H 208/230/60/3 197/254 1 10.4 73.0 3.9 14.3 16.9 25 0.8 15.1 17.7 25

F* 460/60/3* 414/506 1 5.8 38.0 3.2 9.0 10.5 15 0.7 9.7 11.2 15

048

G 208/230/60/1 197/254 1 21.8 117.0 6.9 28.7 34.2 50 0.8 29.5 35.0 50

E 265/60/1 239/292 1 16.3 98.0 6.0 22.3 26.4 40 0.7 23. 27.1 40

H 208/230/60/3 197/254 1 13.7 83.1 6.9 20.6 24.0 35 0.8 21.4 24.8 35

F* 460/60/3* 414/506 1 6.2 41.0 6.0 12.2 13.8 20 0.7 12.9 14.5 20

060

G 208/230/60/1 197/254 1 26.4 134.0 6.9 33.3 39.9 60 1.1 34.4 41.0 60

E 265/60/1 239/292 1 19.9 130.0 6.0 25.9 30.9 50 1.3 27.2 32.2 50

H 208/230/60/3 197/254 1 16 110.0 6.9 22.9 26.9 40 1.1 24.0 28.0 40

F* 460/60/3* 414/506 1 7.8 52.0 6.0 13.8 15.8 20 1.3 15.1 17.1 20

070

G 208/230/60/1 197/254 1 30.8 178.0 6.9 37.7 45.4 70 1.1 37.9 45.6 70

H 208/230/60/3 197/254 1 19.6 138.0 6.9 26.5 31.4 50 1.1 27.6 32.5 50

F* 460/60/3* 414/506 1 8.2 66.1 6.0 14.2 16.3 20 1.3 15.5 17.6 25

* NEUTRAL CONNECTION REQUIRED! All F Voltage (460 vac) units with ECM motors/internal secondary circulators require a four wire power supply with neutral. ECM motors/internal secondary circulators are rated 265 vac and are wired between one hot leg and neutral.

Page 59: Submittal Data - Climate Master · The award winning Tranquility® Series raises the bar for water-source heat pump efficiencies, features and application flexibility. Not only does

ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.

Page ______ of ______LC377 - 59

TS Series Wiring Diagram Matrix

All current diagrams can be located online at climatemaster.com. Click ‘Commercial Professional’ (go to ‘Resources/literature/wiring diagrams’ in the upper right), use part numbers below to lookup wiring diagrams

Model Refrigerant Wiring DiagramPart Number Electrical Control DDC Fan

Motor

TS SeriesSinglePhase

EarthPure®

HFC-410A

96B0308N06

208/230-60-1265-60-1

CXM

-

ECM96B0308N07 LON

96B0308N08 MPC

96B0308N01 -

PSC96B0308N02 LON

96B0308N03 MPC

96B0309N06

DXM2

-

ECM96B0309N07 LON

96B0309N08 MPC

96B0309N15 ClimaDry®

96B0309N01 -

PSC96B0309N02 LON

96B0309N03 MPC

96B0309N11 ClimaDry®

TS SeriesThreePhase

(230 Style)

EarthPure®

HFC-410A

96B0310N06

208/230-60-3

CXM

-

ECM96B0310N07 LON

96B0310N08 MPC

96B0310N01 -

PSC96B0310N02 LON

96B0310N03 MPC

96B0311N06

DXM2

-

ECM96B0311N07 LON

96B0311N08 MPC

96B0311N15 ClimaDry®

96B0311N01 -

PSC96B0311N02 LON

96B0311N03 MPC

96B0311N11 ClimaDry®

TS SeriesThreePhase

(460 Style)

EarthPure®

HFC-410A

96B0312N06

460-60-3…

CXM

-

ECM96B0312N07 LON

96B0312N08 MPC

96B0312N01 -

PSC96B0312N02 LON

96B0312N03 MPC

96B0313N06

DXM2

-

ECM96B0313N07 LON

96B0313N08 MPC

96B0313N15 ClimaDry®

96B0313N01 -

PSC96B0313N02 LON

96B0313N03 MPC

97B0313N11 ClimaDry®

All wiring diagrams available at climatemaster.com.

Note: Contact ClimateMaster applications support for assistance with diagrams not listed here.

Page 60: Submittal Data - Climate Master · The award winning Tranquility® Series raises the bar for water-source heat pump efficiencies, features and application flexibility. Not only does

ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.

Page ______ of ______LC377 - 60

Typical Wiring Diagram – Single Phase TS Unitswith CXM Controller

Page 61: Submittal Data - Climate Master · The award winning Tranquility® Series raises the bar for water-source heat pump efficiencies, features and application flexibility. Not only does

ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.

Page ______ of ______LC377 - 61

Typical Wiring Diagram – Three Phase TS Unitswith DXM2 Controller

Page 62: Submittal Data - Climate Master · The award winning Tranquility® Series raises the bar for water-source heat pump efficiencies, features and application flexibility. Not only does

ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.

Page ______ of ______LC377 - 62

Typical Wiring Diagram – Three Phase TS Unitswith CXM Controller and ECM Blower

Page 63: Submittal Data - Climate Master · The award winning Tranquility® Series raises the bar for water-source heat pump efficiencies, features and application flexibility. Not only does

ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.

Page ______ of ______LC377 - 63

Typical Wiring Diagram – Single Phase TS Unitswith DXM2, MPC, and ECM Controller

Page 64: Submittal Data - Climate Master · The award winning Tranquility® Series raises the bar for water-source heat pump efficiencies, features and application flexibility. Not only does

ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.

Page ______ of ______LC377 - 64

Typical Wiring Diagram – Single Phase TS Unitswith ClimaDry® II and ECM Blower

Page 65: Submittal Data - Climate Master · The award winning Tranquility® Series raises the bar for water-source heat pump efficiencies, features and application flexibility. Not only does

ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.

Page ______ of ______LC377 - 65

Tranquility® 20 (TS) Series 60 HzEngineering Specifications – Page 1

General:Furnish and install ClimateMaster Tranquility® “TS” Water Source Heat Pumps, as indicated on the plans. Equipment shall be completely assembled, piped and internally wired. Capacities and characteristics as listed in the schedule and the specifications that follow.

Units shall be supplied completely factory built capable of operating over an entering water temperature range from 20° to 120° F (-6.7° to 48.9° C) as standard. Equivalent units from other manufacturers may be proposed provided approval to bid is given 10 days prior to bid closing. All equipment listed in this section must be rated and certified in accordance with Air-Conditioning, Heating and Refrigeration Institute/International Standards Organization (AHRI/ISO 13256-1). All equipment must be tested, investigated, and determined to comply with the requirements of the standards for Heating and Cooling Equipment UL-1995 for the United States and CAN/CSA-C22.2 NO.236 for Canada, by Intertek Testing Laboratories (ETL). The units shall have AHRI/ISO and ETL-US-C labels.

All units shall pass a factory acceptance test. The quality control system shall automatically perform factory acceptance test via computer. A detailed report card from the factory acceptance test shall ship with each unit. (Note: If unit fails the factory acceptance test, it shall not be allowed to ship. Unit serial number shall be recorded by factory acceptance test and furnished on report card for ease of unit warranty status.)

Basic Construction:Horizontal Units shall have one of the following air flow arrangements: Left Inlet/Straight (Right) Discharge; Right Inlet/Straight (Left) Discharge; Left Inlet/Back Discharge; or Right Inlet/Back Discharge as shown on the plans. Units must have the ability to be field convertible from straight to back or back to straight discharge with no additional parts or unit structure modification. Horizontal units will have factory installed hanger brackets with rubber isolation grommets packaged separately.

Vertical Units shall have one of the following air flow arrangements: Left Return/Top Discharge, Right Return/Top Discharge, Left Return/Bottom Discharge, Right Return/Bottom Discharge as shown on the plans.

If units with these arrangements are not used, the contractor is responsible for any extra costs incurred by other trades. All units (horizontal and vertical) must have a minimum of three access panels for serviceability of compressor compartment. Units having only one access panel to compressor/heat exchangers/expansion device/refrigerant piping shall not be acceptable.

Compressor section interior surfaces shall be lined with 1/2 inch (12.7 mm) thick, 1-1/2 lb/ft3 (24 kg/m3) acoustic type glass fiber insulation. Air handling section interior surfaces shall be lined with 1/2 inch (12.7 mm) thick, 1-1/2 lb/ft3 (24 kg/m3) foil faced fiber insulation for ease of cleaning. Insulation placement shall be designed in a manner that will eliminate any exposed edges to prevent the introduction of glass fibers into the air stream. Units without foil faced insulation in the air handling section will not be accepted.

The heat pumps shall be fabricated from heavy gauge galvanized steel with powder coat paint finish. Both sides of the steel shall be painted for added protection.

Standard cabinet panel insulation must meet NFPA 90A requirements, air erosion and mold growth limits of UL-181, stringent fungal resistance test per ASTM-C1071 and ASTM G21, and shall meet zero level bacteria growth per ASTM G22. Unit insulation must meet these stringent requirements or unit(s) will not be accepted.

All horizontal units to have factory installed 1inch (25.4 mm) discharge air duct collars, 1inch (25.4 mm) filter rails with 1inch (25.4 mm) filters factory installed, and factory installed unit-mounting brackets. Vertical units to have field installed discharge air duct collar, shipped loose and 1inch (25.4 mm) filter rails with 1inch (25.4 mm) filters factory installed. If units with these factory-installed

Page 66: Submittal Data - Climate Master · The award winning Tranquility® Series raises the bar for water-source heat pump efficiencies, features and application flexibility. Not only does

ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.

Page ______ of ______LC377 - 66

Tranquility® 20 (TS) Series 60 HzEngineering Specifications – Page 2

provisions are not used, the contractor is responsible for any extra costs to field install these provisions, and/or the extra costs for his sub-contractor to install these provisions.

All units must have an insulated panel separating the fan compartment from the compressor compartment. Units with the compressor in the air stream are not acceptable. Units shall have a factory installed 1 inch (25.4 mm) wide filter bracket for filter removal from either side. Units shall have a 1 inch (25.4 mm) thick throwaway type glass fiber filter. The contractor shall purchase one spare set of filters and replace factory shipped filters on completion of start-up. Filters shall be standard sizes. If units utilize non-standard filter sizes, then the contractor shall provide 12 spare filters for each unit.

Cabinets shall have separate holes and knockouts for entrance of line voltage and low voltage control wiring. All factory-installed wiring passing through factory knockouts and openings shall be protected from sheet metal edges at openings by plastic ferrules. Supply and return water connections shall be copper FPT fittings and shall be securely mounted flush to the cabinet corner post allowing for connection to a flexible hose without the use of a back-up wrench. Water connections that protrude through the cabinet or require the use of a backup wrench shall not be allowed. All water connections and electrical knockouts must be in the compressor compartment corner post as to not interfere with the serviceability of unit. Contractor shall be responsible for any extra costs involved in the installation of units that do not have this feature. Contractor must ensure that units can be easily removed for servicing and coordinate locations of electrical conduit and lights with the electrical contractor.

Option: Contractor shall install 2 inch (50.8 mm) filter racks with removable access door and 2 inch (50.8 mm) MERV11 pleated throwaway filters on all units.

Option: UltraQuiet package (available on TS018-070 Units) shall consist of high technology sound attenuating material that is strategically applied to the compressor and air handling compartment casings and fan scroll in addition to the standard ClimaQuiet system design, to further dampen and attenuate sound transmissions.

Option: The unit will be supplied with internally factory mounted two-way water valve for variable speed pumping requirements. A factory-mounted or field-installed high pressure switch shall be installed in the water piping to disable compressor operation in the event water pressures build due to water freezing in the piping system.

Option: The unit will be supplied with internally factory mounted automatic water flow regulators.

Option: The unit will be supplied with internally mounted secondary pump for primary/secondary applications, including one-pipe systems.

Option: The unit shall be supplied with extended range insulation option, which adds closed cell insulation to internal water lines, and provides insulation on suction side refrigeration tubing including refrigerant to water heat exchanger.

Fan and Motor Assembly:Blower shall have inlet rings to allow removal of wheel and motor from one side without removing housing. Units shall have a direct-drive centrifugal fan. The fan motor shall be 3-speed (2-speed for 575 V), permanently lubricated, PSC type, with internal thermal overload protection. Units supplied without permanently lubricated motors must provide external oilers for easy service. The fan motor on small and medium size units (006-048) shall be isolated from the fan housing by a torsionally flexible motor mounting system with rubber type grommets to inhibit vibration induced high noise levels associated with “hard wire belly band” motor mounting. The fan

Page 67: Submittal Data - Climate Master · The award winning Tranquility® Series raises the bar for water-source heat pump efficiencies, features and application flexibility. Not only does

ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.

Page ______ of ______LC377 - 67

Tranquility® 20 (TS) Series 60 HzEngineering Specifications – Page 3

motor on larger units (060 & 070) shall be isolated with flexible rubber type isolation grommets only. The fan and motor assembly must be capable of overcoming the external static pressures as shown on the schedule. Airflow/Static pressure rating of the unit shall be based on a wet coil and a clean filter in place. Ratings shall NOT be acceptable based on a dry coil and/or no air filter.

Option: ECM motors (sizes 018 to 070): The fan motor shall be an ECM variable speed ball bearing type motor. The ECM fan motor shall provide soft starting, maintain constant CFM over its static operating range and provide airflow adjustment on its control board. The fan motor shall be isolated from the housing by rubber grommets. The motor shall be permanently lubricated and have thermal overload protection. A special dehumidification mode shall be provided to allow lower airflows in cooling for better dehumidification. The dehumidification mode shall be selectable via a dip switch on the control board or may be controlled externally from a humidistat.

Option: High static PSC motors (sizes 018-060).

Refrigerant Circuit: All units shall contain an EarthPure® (HFC-410A) sealed refrigerant circuit including a high efficiency scroll or rotary compressor designed for heat pump operation, a thermostatic expansion valve for refrigerant metering, an enhanced corrugated aluminum lanced fin and rifled copper tube or all aluminum micro channel refrigerant to air heat exchanger, reversing valve, coaxial (tube in tube) refrigerant to water heat exchanger, and safety controls including a high pressure switch, low pressure switch (loss of charge), water coil low temperature sensor, and air coil low temperature sensor. Access fittings shall be factory installed on high and low pressure refrigerant lines to facilitate field service. Activation of any safety device shall prevent compressor operation via a microprocessor lockout circuit. The lockout circuit shall be reset at the thermostat or at the contractor supplied disconnect switch. Units that cannot be reset at the thermostat shall not be acceptable.

Hermetic compressors shall be internally sprung. The compressor shall have a dual level vibration isolation system. The compressor will be mounted on specially engineered sound-tested EPDM vibration isolation grommets to a large heavy gauge compressor mounting plate, which is then isolated from the cabinet base with rubber grommets for maximized vibration attenuation. All units (except units with rotary compressors) shall include a discharge muffler to further enhance sound attenuation. Compressor shall have thermal overload protection. Compressor shall be located in an insulated compartment away from air stream to minimize sound transmission.

Refrigerant to air heat exchangers shall utilize enhanced corrugated lanced aluminum fins and rifled copper tube or all aluminum micro channel construction rated to withstand 625 PSIG (4309 kPa) refrigerant working pressure. Refrigerant to water heat exchangers shall be of copper inner water tube and steel refrigerant outer tube design, rated to withstand 625 PSIG (4309 kPa) working refrigerant pressure and 500 PSIG (3445 kPa) working water pressure. The refrigerant to water heat exchanger shall be “electro-coated” with a low cure cathodic epoxy material a minimum of 0.4 mils thick (0.4 – 1.5 mils range) on all surfaces. The black colored coating shall provide a minimum of 1,000 hours salt spray protection per ASTM B117-97 on all external steel and copper tubing. The material shall be formulated without the inclusion of any heavy metals and shall exhibit a pencil hardness of 2H (ASTM D3363-92A), crosshatch adhesion of 4B-5B (ASTM D3359-95), and impact resistance of 160 in-lbs (184 kg-cm) direct (ASTM D2794-93).

Refrigerant metering shall be accomplished by thermostatic expansion valve only. Expansion valves shall be dual port balanced types with external equalizer for optimum refrigerant metering. Units shall be designed and tested for operating ranges of entering water temperatures from 20° to 120° F (-6.7° to 48.9° C). Reversing valve shall be four-way solenoid activated refrigerant valve, which shall default to heating mode should the solenoid fail to function. If the reversing valve solenoid defaults to cooling mode, an additional low temperature thermostat must be provided to prevent over-cooling an already cold room.

Page 68: Submittal Data - Climate Master · The award winning Tranquility® Series raises the bar for water-source heat pump efficiencies, features and application flexibility. Not only does

ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.

Page ______ of ______LC377 - 68

Tranquility® 20 (TS) Series 60 HzEngineering Specifications – Page 4

Option: The unit shall be supplied with a hot water generator (desuperheater).

Option: The unit will be supplied with cupro-nickel coaxial water to refrigerant heat exchanger.

Option: The refrigerant to air heat exchanger shall be coated.

Option: Unit shall include ClimaDry®II reheat option. Only modulating reheat that will adjust capacity based upon supply air temperature to provide “neutral” (72º F, 22.2º C) constant air temperature will be accepted. “Neutral” supply air temperature shall be provided regardless of entering loop water temperatures (above 55º F, 12.8º C) or refrigerant condensing pressures. Control of reheat must be accomplished via a humidistat or dehumidistat contact closure. Refrigerant circuit must be AHRI certified. Approved equal manufacturers may provide pre-engineered integrated modulating hot gas reheat within the unit cabinet, or the installing contractor in conjunction with the “approved equal” unit manufacturer can provide for approval (during the submittal phase) an engineered system consisting of: a duct mounted hot water coil, small circulating pump, modulating control valve, and associated piping using the discharge condenser water off of the unit as the heating medium. All design costs and costs of field installed items including additional power wiring to pump, and control wiring to and from pump and control valve to unit shall be borne by mechanical contractor. Refrigerant circuits that are not AHRI certified when the reheat option is applied will not be accepted.

Drain Pan:The drain pan shall be constructed of 201LN Stainless Steel to inhibit corrosion. This corrosion protection system shall meet the stringent 1,000 hour salt spray test per ASTM B117. If plastic type material is used, it must be HDPE (High Density Polyethylene) to avoid thermal cycling shock stress failure over the lifetime of the unit. Drain pan shall be fully insulated. Drain outlet shall be located at pan as to allow unobstructed drainage of condensate. Drain outlet for horizontal units shall be connected from pan directly to FPT fitting. No hidden internal tubing extensions from pan outlet extending to unit casing (that can create drainage problems) will be accepted. The unit as standard will be supplied with solid-state electronic condensate overflow protection. Mechanical float switches will NOT be accepted.

Vertical units shall be furnished with a PVC FPT condensate drain connection and an internal factory installed condensate trap. If units without an internal trap are used, the contractor is responsible for any extra costs to field install these provisions, and/or the extra costs for his sub-contractor to install these provisions.

Electrical:A control box shall be located within the unit compressor compartment and shall contain a 50 VA transformer, 24 Volt activated, 2 or 3 pole compressor contactor, terminal block for thermostat wiring and solid-state controller for complete unit operation. Reversing valve and fan motor wiring shall be routed through this electronic controller. Units shall be name-plated for use with time delay fuses or HACR circuit breakers. Unit controls shall be 24 Volt and provide heating or cooling as required by the remote thermostat/sensor.

Option: Units shall be supplied with factory installed non-fused electrical service disconnect switch.

Solid State Control System (CXM):Units shall have a solid-state control system. Units utilizing electro-mechanical control shall not be acceptable. The control system microprocessor board shall be specifically designed to protect against building electrical system noise contamination, EMI, and RFI interference. The control system shall interface with a heat pump type thermostat. The control system shall have the following features:

Page 69: Submittal Data - Climate Master · The award winning Tranquility® Series raises the bar for water-source heat pump efficiencies, features and application flexibility. Not only does

ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.

Page ______ of ______LC377 - 69

Tranquility® 20 (TS) Series 60 HzEngineering Specifications – Page 5

a. Anti-short cycle time delay on compressor operation.b. Random start on power up mode.c. Low voltage protection.d. High voltage protection.e. Unit shutdown on high or low refrigerant pressures.f. Unit shutdown on low water temperature.g. Condensate overflow electronic protection.h. Option to reset unit at thermostat or disconnect.i. Automatic intelligent reset. Unit shall automatically reset the unit 5 minutes after trip if the fault has cleared. If a fault occurs 3

times sequentially without thermostat meeting temperature, then lockout requiring manual reset will occur.j. Ability to defeat time delays for servicing.k. Light emitting diode (LED) on circuit board to indicate high pressure, low pressure, low voltage, high voltage, low water/air

temperature cut-out, condensate overflow, and control voltage status.l. The low-pressure switch shall not be monitored for the first 120 seconds after a compressor start command to prevent nuisance

safety trips.m. 24 V output to cycle a motorized water valve or other device with compressor contactor.n. Unit Performance Sentinel (UPS). The UPS warns when the heat pump is running inefficiently.o. Water coil low temperature sensing (selectable for water or antifreeze).p. Air coil low temperature sensing.

NOTE: Units not providing the 8 safety protections of anti-short cycle, low voltage, high voltage, high refrigerant pressure, low pressure (loss of charge), air coil low temperature cut-out, water coil low temperature cut-out, and condensate overflow protections will not be accepted.

Solid State ECM Fan Control Board (60 Hz Units with ECM Fan Option Only):Airflow selection shall be accomplished via 3 jumper switches on the ECM control board. Actual airflow shall be indicated by the CFM LED with each 100 CFM being represented by one flash of the LED. Airflow shall be automatically maintained (±5%) by the ECM motor regardless of external static pressure up to its maximum output capacity. A jumper shall allow selection of a special dehumidification mode, which reduces airflow in cooling by 25% to increase the latent capacity of the unit. A terminal shall be provided on the control board to allow an external humidistat to activate dehumidification mode.

Option: Enhanced Solid State Control System (DXM2)This control system is a communicating controller; also features two stage control of cooling and two stage control of heating mode for exacting temperature and dehumidification purposes.

This control system, coupled with a multi-stage thermostat, will better dehumidify room air by automatically running the heat pump’s fan at lower speed on the first stage of cooling thereby implementing low sensible heat ratio cooling. On the need for higher cooling performance, the system will activate the second stage of cooling and automatically switch the fan to the higher fan speed setting. This system may be further enhanced with a humidistat. Units not having automatic low sensible heat ratio cooling will not be accepted; as an alternative, a hot gas reheat coil may be provided with control system for automatic activation.

Control shall have the above-mentioned features of the CXM control system along with the following expanded features:

a. Removable thermostat connector.b. Night setback control.c. Random start on return from night setback.

Page 70: Submittal Data - Climate Master · The award winning Tranquility® Series raises the bar for water-source heat pump efficiencies, features and application flexibility. Not only does

ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.

Page ______ of ______LC377 - 70

Tranquility® 20 (TS) Series 60 HzEngineering Specifications – Page 6

d. Minimized reversing valve operation (Unit control logic shall only switch the reversing valve when cooling is demanded for the first time. The reversing valve shall be held in this position until the first call for heating, ensuring quiet operation and increased

valve life).e. Override temperature control with 2-hour timer for room occupant to override setback temperature at the thermostat.f. Dry contact night setback output for digital night setback thermostats.g. Ability to work with heat pump or heat/cool (Y, W) type thermostats.h. Ability to work with heat pump thermostats using O or B reversing valve control.i. Emergency shutdown contacts.j. Boilerless system heat control at low loop water temperature.k. Ability to allow up to 3 units to be controlled by one thermostat.l. Relay to operate an external damper.m. Ability to automatically change fan speed from multi-stage thermostatn. Relay to start system pump.o. 75 VA control transformer. Control transformer shall have load side short circuit and overload protection via a built-in circuit breaker.

NOTE: Units not providing the 8 safety protections of anti-short cycle, low voltage, high voltage, high refrigerant pressure, low pressure (loss of charge), air coil low temperature cut-out, water coil low temperature cut-out, and condensate overflow protection for both drain pans will not be accepted.

When DXM2 is connected to either ACDU service tool or ATC32U thermostat, the installer/service technician can; check and set CFM and check DIP switch S1, S2, and S3 settings; run operation modes manually; check all physical inputs from thermostat and refrigerant pressure switches status, (Y1, Y2, W, O, G, H, ESD, NSB, OR, HP switch, and LOC switch); current or at time of fault the following temperatures -LT1, LT2, compressor discharge, leaving air, leaving water, entering water and control voltage; record last five faults, list possible reasons, and clear faults.

Digital Night Setback with Pump Restart (DXM2 w/ ATP32U03C/04C, ATC32U03C):The unit will be provided with a Digital Night Setback feature using an accessory relay on the DXM2 controller with an ATP32U03C/04C thermostat and an external, field-provided time clock. The external time clock will initiate and terminate the night setback period. The thermostat will have a night setback override feature with a programmable override time period. An additional accessory relay on the unit DXM2 controller will energize the building loop pump control for the duration of the override period. (Note: This feature requires additional low voltage wiring. Consult Application Drawings for details.)

Remote Service Sentinel (CXM/DXM2):Solid state control system shall communicate with thermostat to display (at the thermostat) the unit status, fault status, and specific fault condition, as well as retrieve previously stored fault that caused unit shutdown. The Remote Service Sentinel allows building maintenance personnel or service personnel to diagnose unit from the wall thermostat. The control board shall provide a signal to the thermostat fault light, indicating a lockout. Upon cycling the G (fan) input 3 times within a 60 second time period, the fault light shall display the specific code as indicated by a sequence of flashes. A detailed flashing code shall be provided at the thermostat LED to display unit status and specific fault status such as over/under voltage fault, high pressure fault, low pressure fault, low water temperature fault, condensate overflow fault, etc. Units that do not provide this remote service sentinel shall not be acceptable.

Option: Lonworks Interface SystemUnits shall have all the features listed above (either CXM or DXM2) and the control board will be supplied with a LONWORKS interface board, which is LONMark certified. This will permit all units to be daisy chained via a 2-wire twisted pair shielded cable. The following points must be available at a central or remote computer location:

Page 71: Submittal Data - Climate Master · The award winning Tranquility® Series raises the bar for water-source heat pump efficiencies, features and application flexibility. Not only does

ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.

Page ______ of ______LC377 - 71

Tranquility® 20 (TS) Series 60 HzEngineering Specifications – Page 7

a. space temperature b. leaving water temperaturec. discharge air temperatured. command of space temperature setpointe. cooling statusf. heating statusg. low temperature sensor alarmh. low pressure sensor alarmi. high pressure switch alarmj. condensate sensor alarmk. hi/low voltage alarml. fan “ON/AUTO” position of space thermostat as specified abovem. unoccupied/occupied commandn. cooling commando. heating commandp. fan “ON/AUTO” commandq. fault reset commandr. itemized fault code revealing reason for specific shutdown fault (any one of 7)

This option also provides the upgraded 75 VA control transformer with load side short circuit and overload protection via a built-in circuit breaker.

Option: MPC (Multiple Protocol Control) Interface SystemUnits shall have all the features listed above (either CXM or DXM2) and the control board will be supplied with a Multiple Protocol interface board. Available protocols are BACnet MS/TP, Modbus, or Johnson Controls N2. The choice of protocol shall be field selectable/changeable via the use of a simple selector switch. Protocol selection shall not require any additional programming or special external hardware or software tools. This will permit all units to be daisy chain connected by a 2-wire twisted pair shielded cable. The following points must be available at a central or remote computer location:

a. space temperature b. leaving water temperaturec. discharge air temperatured. command of space temperature setpointe. cooling statusf. heating statusg. low temperature sensor alarmh. low pressure sensor alarmi. high pressure switch alarmj. condensate overflow alarmk. hi/low voltage alarml. fan “ON/AUTO” position of space thermostat as specified abovem. unoccupied / occupied commandn. cooling commando. heating commandp. fan “ON/AUTO” command

Page 72: Submittal Data - Climate Master · The award winning Tranquility® Series raises the bar for water-source heat pump efficiencies, features and application flexibility. Not only does

ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.

Page ______ of ______LC377 - 72

Tranquility® 20 (TS) Series 60 HzEngineering Specifications – Page 8

q. fault reset commandr. itemized fault code revealing reason for specific shutdown fault (any one of 7)

This option also provides the upgraded 75 VA control transformer with load side short circuit and overload protection via a built-in circuit breaker.

Warranty:ClimateMaster shall warranty equipment for a period of 12 months from start up or 18 months from shipping (whichever occurs first).

Option: Extended 4-year compressor warranty covers compressor for a total of 5 years.

Option: Extended 4-year refrigeration circuit warranty covers coils, reversing valve, expansion valve and compressor for a total of 5 years.

Option: Extended 4-year control board warranty covers the CXM/DXM2 control board for a total of 5 years.

FIELD INSTALLED OPTIONS

Hose Kits:All units shall be connected with hoses. The hoses shall be 2 feet (61 cm) long, braided stainless steel; fire rated hoses complete with adapters. Only fire rated hoses will be accepted.

Valves:The following valves are available and will be shipped loose:

a. Ball valve; bronze material, standard port full flow design, FPT connections.b. Ball valve with memory stop and PT port.c. “Y” strainer with blowdown valve; bronze material, FPT connections.d. Motorized water valve; slow acting, 24 v, FPT connections.

Hose Kit Assemblies:The following assemblies ship with the valves already assembled to the hose described:

a. Supply and return hoses having ball valve with PT port.b. Supply hose having ball valve with PT port; return hose having automatic flow regulator valve with PT ports, and ball valve.c. Supply hose having “Y” strainer with blowdown valve, and ball valve with PT port; return hose having automatic flow regulator

with PT ports, and ball valve.d. Supply hose having “Y” strainer with blowdown valve, and ball valve with PT port; return hose having ball valve with PT port.

Thermostats:The thermostat shall be a ClimateMaster mechanical or electronic type thermostat as selected below with the described features:

a. Single-Stage Standard Manual Changeover (ATM11C11) Thermostat shall be a single-stage, horizontal mount, manual changeover with HEAT-OFF-COOL system switch and fan ON-

AUTO switch. Thermostat shall have a mechanical temperature set point indicator. Thermostat shall only require 4 wires for connection. Mercury bulb thermostats are not acceptable.

Page 73: Submittal Data - Climate Master · The award winning Tranquility® Series raises the bar for water-source heat pump efficiencies, features and application flexibility. Not only does

ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.

Page ______ of ______LC377 - 73

Tranquility® 20 (TS) Series 60 HzEngineering Specifications – Page 9

b. Single-Stage Digital Auto or Manual Changeover (ATA11U01) Thermostat shall be a single-stage, digital, auto or manual changeover with HEAT-OFF-COOL-AUTO system switch and fan ON-

AUTO switch. Thermostat shall have an LCD display with temperature and set-point(s) in ºF or ºC. The thermostat shall provide permanent memory of set-point(s) without batteries. A fault LED shall be provided to display specific fault condition. Thermostat shall provide temperature display offset for custom applications.

c. Single-Stage Digital Auto or Manual Changeover and Manual Two Fan Speed Selections (ATA11U03) Thermostat shall be a single-stage, digital, auto or manual changeover with HEAT-OFF-COOL-AUTO system settings, high and

low fan settings and fan ON-AUTO settings. Thermostat shall have an LCD display with temperature, setpoint(s), mode, and status indication. The temperature indication shall be selectable for ºF or ºC. The thermostat shall provide permanent memory of setpoint(s) without batteries. Thermostat shall provide heating setpoint range limit, cooling setpoint range limit, temperature display offset, keypad lockout, dead-band range setting, and inter-stage differential settings. Thermostat shall allow the use of an accessory remote temperature sensor (17B0008N05). Thermostat navigation shall be accomplished via 4 push buttons.

d. Multi-stage Digital Automatic Changeover (ATA22U01) Thermostat shall be multi-stage (2H/2C), manual or automatic changeover with HEAT-OFF-COOL-AUTO-EM HEAT system

settings and fan ON-AUTO settings. Thermostat shall have an LCD display with temperature, set-point(s), mode, and status indication. The temperature indication shall be selectable for ºF or ºC. The thermostat shall provide permanent memory of set-point(s) without batteries. A fault LED shall be provided to indicate specific fault condition(s). Thermostat shall provide temperature display offset for custom applications. Thermostat shall allow unit to provide better dehumidification with optional DXM2 controller by automatically using lower fan speed on stage 1 cooling (higher latent cooling) as main cooling mode, and automatically shifting to high speed fan on stage 2 cooling.

e. Multi-stage Manual Changeover Programmable 5/2 Day (ATP21U01) Thermostat shall be 5 day/2 day programmable (with up to 4 set points per day), multi-stage (2H/1C), manual changeover with

HEAT-OFF-COOL-EM HEAT system settings and fan ON-AUTO settings. Thermostat shall have an LCD display with temperature, set-point(s), mode, and status indication. The temperature indication shall be selectable for ºF or ºC. The thermostat shall provide permanent memory of set-point(s) without batteries. Thermostat shall provide convenient override feature to temporarily change setpoint.

f. Multi-stage Automatic or Manual Changeover Programmable 7 Day (ATP32U03C) Thermostat shall be 7 day programmable (with up to 4 set points per day), multi-stage (3H/2C), automatic or manual changeover

with HEAT-OFF-COOL-AUTO-EM HEAT system settings and fan ON-AUTO settings. Thermostat shall have a blue backlit dot matrix LCD display with temperature, set-points, mode, and status indication. The temperature indication shall be selectable for ºF or ºC. Time display shall be selectable for 12 or 24 hour clock. Fault identification shall be provided (when used with ClimateMaster CXM or DXM2 controls) to simplify troubleshooting by providing specific unit fault at the thermostat with red backlit LCD during unit lockout. The thermostat shall provide permanent memory of set-points without batteries. Thermostat shall provide heating set-point range limit, cooling set-point range limit, temperature display offset, keypad lockout, dead-band range setting, and inter-stage differential settings. Thermostat shall provide progressive recovery to anticipate time required to bring space temperature to the next programmed event. Thermostat shall provide an installer setup for configuring options and for setup of servicing contractor name and contact information. Thermostat shall allow the use of an accessory remote and/or outdoor temperature sensor (AST008). Thermostat navigation shall be accomplished via five buttons (up/down/right/left/select) with menu-driven selections for ease of use and programming.

g. Multi-stage Automatic or Manual Changeover Programmable 7 Day with Humidity Control (ATP32U04C) Thermostat shall be 7 day programmable (with up to 4 set points per day), multi-stage (3H/2C), automatic or manual

Page 74: Submittal Data - Climate Master · The award winning Tranquility® Series raises the bar for water-source heat pump efficiencies, features and application flexibility. Not only does

ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.

Page ______ of ______LC377 - 74

Tranquility® 20 (TS) Series 60 HzEngineering Specifications – Page 10

changeover with HEAT-OFF-COOL-AUTO-EM HEAT system settings and fan ON-AUTO settings. Separate dehumidification and humidification set points shall be configurable for discreet outputs to a dehumidification option and/or an external humidifier. Installer configuration mode shall allow thermostat dehumidification mode to operate with ClimaDry® reheat or with ECM fan dehumidification mode via settings changes. Thermostat shall have a blue backlit dot matrix LCD display with temperature, relative humidity, set-points, mode, and status indication. The temperature indication shall be selectable for ºF or ºC. Time display shall be selectable for 12 or 24 hour clock. Fault identification shall be provided (when used with ClimateMaster CXM or DXM2 controls) to simplify troubleshooting by providing specific unit fault at the thermostat with red backlit LCD during unit lockout. The thermostat shall provide permanent memory of set-points without batteries. Thermostat shall provide heating set-point range limit, cooling set-point range limit, temperature display offset, keypad lockout, dead-band range setting, and inter-stage differential settings. Thermostat shall provide progressive recovery to anticipate time required to bring space temperature to the next programmed event. Thermostat shall provide an installer setup for configuring options and for setup of servicing contractor name and contact information. Thermostat shall allow the use of an accessory remote and/or outdoor temperature sensor (AST008). Thermostat navigation shall be accomplished via five buttons (up/down/right/left/select) with menu-driven selections for ease of use and programming.

h. Thermostat (communicating) (ATC32U03C) An electronic communicating LCD thermostat shall be provided. The thermostat shall offer three stage of heating and two stages

of cooling with precise temperature control and have a four-wire connection to the unit. The thermostat shall be capable of manual or automatic change-over operation and shall operate in standard or programmable move. An integrated humidity control feature shall be included to control a humidifier and/or a dehumidifier. The thermostat shall include a utility demand reduction feature to be initiated by an independent time program or an external point. The thermostat shall display system faults with probable cause and troubleshooting guidance. Comprehensive service diagnostics menus shall display; system inputs, system outputs configuration settings, Geo source inlet and outlet temperatures, compressor discharge line temperature, liquid line temperature, and leaving air temperature. The thermostat shall allow for immediate manual control of all DXM2 outputs at the thermostat for rapid troubleshooting.

DDC Sensors:ClimateMaster wall mounted DDC sensor to monitor room temperature and interfaces with optional interface system described above. Several types as described below:

a. Sensor only with no display (LON and MPC).b. Sensor with override (LON only).c. Sensor with setpoint adjustment and override (MPC only).d. Sensor with setpoint adjustment and override, LCD display, status/fault indication (LON and MPC).

NOTICE! This product specification document is furnished as a means to copy and paste ClimateMaster product information into project specification. It is not intended to be a complete list of product requirements. This document is an excerpt from the product submittal and must not be used without consulting the complete product submittal. For complete product installation and application requirements, please consult the complete product submittal. ClimateMaster is not responsible for misuse of this document or a failure to adequately review specific requirements in the product submittal.

Page 75: Submittal Data - Climate Master · The award winning Tranquility® Series raises the bar for water-source heat pump efficiencies, features and application flexibility. Not only does

ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.

Page ______ of ______LC377 - 75

Submittal Data - i-P uNitS

Unit Designation:

Job Name:

Architect:

Engineer:

Contractor:

PERFORmaNCE Data

Cooling Capacity: Btuh

EER:

Heating Capacity: Btuh

COP:

Ambient Air Temp: °F

Entering Water Temp (Clg): °F

Entering Air Temp (Clg): °F

Entering Water Temp (Htg): °F

Entering Air Temp (Htg): °F

Airflow: CFM

Fan Speed or Motor/RPM/Turns:

Operating Weight: (lb)

ElECtRiCal Data

Power Supply: Volts

Phase Hz

Minimum Circuit Ampacity:

Maximum Overcurrent Protection:

Submittal Data - S-i uNitS

Unit Designation:

Job Name:

Architect:

Engineer:

Contractor:

PERFORmaNCE Data

Cooling Capacity: kW

EER:

Heating Capacity: kW

COP:

Ambient Air Temp: °C

Entering Water Temp (Clg): °C

Entering Air Temp (Clg): °C

Entering Water Temp (Htg): °C

Entering Air Temp (Htg): °C

Airflow: l/s

Fan Speed or Motor/RPM/Turns:

Operating Weight: (kg)

ElECtRiCal Data

Power Supply: Volts

Phase Hz

Minimum Circuit Ampacity:

Maximum Overcurrent Protection:

Performance Sheet

Page 76: Submittal Data - Climate Master · The award winning Tranquility® Series raises the bar for water-source heat pump efficiencies, features and application flexibility. Not only does

ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.

Page ______ of ______LC377 - 76

notes

Page 77: Submittal Data - Climate Master · The award winning Tranquility® Series raises the bar for water-source heat pump efficiencies, features and application flexibility. Not only does

ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.

Page ______ of ______LC377 - 77

Revision History

Date: Item: Action:05/26/20 Pgs 10-28, pg 30 Updated Performance Data Tables and Antifreeze Correction Table01/29/20 page 29 Updated Performance Correction Tables01/17/20 page 8 Update Table10/03/19 ALL Update for DXM209/20/17 Page 59 Update Wiring Diagram Matrix06/14/17 Page 37 Update drawing11/1/16 Updated Document Design Updated

10/16/16 Page 37 Added ClimaDry Note03/4/16 Pages 35 to 37 and 64 Edits to ECM control and run test

10/22/15 Pages 48 and 51 Edited dimensions “T” on sizes 42,48

08/04/15 Engineering Specifications and Unit Features Updated, ECM Options Text, Edited Compressors Mount Text, Fan and Motor Assembly Text

07/22/15 Page 13 & 14 Updated HWC Data06/17/15 Decoder - Page 7; Tables - Pages 13 & 53-58 Updated03/25/15 Table - Page 43 Updated Maximum Working Water Pressure03/05/15 Decoder - Page 7 Updated01/23/15 Table - Page 56 Updated12/16/14 Edits - Page 45 & 47 Updated09/30/14 Text Edit - Page 67 Updated08/15/14 TS060 E Voltage Elec. Tables Added ECM with ISP and CWR06/12/14 Rev. C Size 036 E Voltage Added05/12/14 Air Coil Description page 66-67 Updated03/31/14 Illustration - Page 48 Updated03/24/14 ECM Blower Data - Page 38 Updated Max ESP02/10/14 Page 41 Updated Table 201/27/14 All Updated Sizes 024-070 to Rev. C, added service clearances7/17/13 EAT Minimum Limit ClimaDry Updated

02/26/13 AHRI Table Size 018 PSC Updated

01/07/13Physical Data TableTS Vertical Upflow - Dimensional Data - TSV Right Return

UpdatedUpdated Blower Orientation

09/27/12EAT LimitsRecommended Minimum Installation Clearances for Vertical Units *

Updated

02/20/12 Engineering Specifications Updated02/02/12 ClimaDry® II option Information Merge data from ClimaDry® II Submittal12/14/11 ECM Control Updated CFM adjust settings11/02/11 Decoder Updated10/19/11 Dimensional Data, Optional Filter Frame Added08/09/11 Unit Maximum Working Water Pressure Updated to Reflect New Safeties

08/03/11 Engineering Specifications Added Digital Night Setback with Pump Restart (DXM w/ AT-P32U03/04)

06/17/11 Coated Air Coil Option Changed Description05/16/11 Electrical Data 018E and 024F ISP Added04/07/11 Engineering Specification NOTICE Updated02/11/11 Performance Data Selection Notes Updated01/03/11 Format - All Pages Updated09/29/10 ECM Electrical Data Updated09/28/10 Engineering Specifications Updated09/07/10 ECM Blower Control Added Ramp Down Feature09/01/10 Engineering Specifications Updated 08/24/10 Horizontal Units Supply Air Dimension M and Q updated07/26/10 Wiring Diagrams Updated07/26/10 Compressor Mounting Information and Graphics Updated to Reflect Spring/Grommet Change

Page 78: Submittal Data - Climate Master · The award winning Tranquility® Series raises the bar for water-source heat pump efficiencies, features and application flexibility. Not only does

ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.

Page ______ of ______LC377 - 78

Revision History

7300 S.W. 44th StreetOklahoma City, OK 73179

Phone: 405-745-6000climatemaster.com

Date Item: Action:06/11/10 Format - All Pages Updated06/11/10 Engineering Specifications Updated06/01/10 TSH S.A. Dimensions Dimension M & Q changed03/30/10 Performance Data/Blower Data Size 018 data changes05/27/09 Stand-Alone and Big Book Submittals Consolidated

04/29/09 Electrical Data Table (High Static PSC Motor & Secondary Pump) 036 E Data Corrected

04/29/09 Performance Data IP Table Corrected11/17/08 TS Horizontal Data Table Data Corrected09/19/08 Engineering Specifications ClimaDry® Note Added08/26/08 Physical Data Table Max Working Pressure Table Added08/01/08 Electrical Data Table Asterisks Added08/0407 All Added Sizes 006, 009, & 01205/14/07 All Updated Size 018 for Rev.: B04/19/07 Table of Contents Added Table of Contents04/19/07 Specifications Updated Specifications for new Safety Agency12/14/06 Dimensional Data Corrected TSH18-030 Supply dimensions11/16/06 Electrical Data Various updates11/16/06 Dimensional Data Updated dimensional data to new format11/16/06 Performance Data/Blower Data Added new rated voltage note11/19/06 Specifications Updated thermostat offering11/19/06 Wiring Diagrams Added pressure switch for motorized valve option

07/19/06 Electrical Data Added secondary pump data, updated ClimaDry® data, various format-ting changes

07/19/06 ECM Blower Performance Updated CFM data07/19/06 Performance Data Added low temperature selection notes12/23/05 Motorized Valves Added Cv, MOPD, and WPD data11/30/05 Tables Updated all tables to new format11/30/05 Dimensional data Added new dimensional drawings and installation and service notes11/30/05 Physical Data Added Coax volumes11/30/05 Blower Data, Electrical Data, Unit Specifications Added ClimaDry® Reheat option08/15/05 Correction Factors Updated verbiage - No data changes08/15/05 Physical Data Added Coax volume chart08/15/05 Dimensional Data Added corner weights - Horizontal units08/15/05 Electrical Data Updated 030 “E” voltage total unit FLA & MCA08/15/05 Specifications Updated verbiage in CXM section06/20/05 Entire Document Updated to Adobe Acrobat 7.006/20/05 Electrical Data Removed TS024 265V data06/20/05 ECM Motor Added Information on new interface board06/20/05 Specifications Updated specs to include mufflers03/30/05 Electrical Data Updated 018, 024, 03003/30/05 Horizontal Dimensions Updated dim. “H”03/30/05 Added Revision Log