230 Peachtree Street NW, Suite 1250 Atlanta, GA 30303 Project Telephone #404.688.6233 230 Peachtree Hotel Conversion 260 - 23 60 00 - 2.7 Bulletin #4 - Fan Coil Units 05/05/15 Allie Creach [email protected] 1. Updates per Bulletin #4 The review of shop drawings does not relieve the Subcontractor/ Vendor from the requirements of the Contract Documents. Subcontractors/Vendors are hereby notified that any cost/schedule impacts caused by changes to a submittal must be reported to Holder Construction within (5) days as stated in Section 8 of Holder's subcontract. Subcontractors/Vendors failing to report, in writing, cost/schedule impacts within this time frame are fully responsible for such impacts. All changes or variations to the Contract Documents must be flagged and noted. Failure to do so leaves the responsibility for coordination any cost impacts caused from changes with that Subcontractor/Vendor. Holder Comments: A/E Comments: Holder Construction Company Submittal Project Name: Submittal Number: Submittal Description: Submittal Review Date: Submittal Reviewed By: Reviewed Reviewed as Noted Rejected

Transcript of Submittal...Cooling Coil: Package Code- Code: 25 (Manual Ball Valve with Memory Stop, Fixed Flow...

Page 1: Submittal...Cooling Coil: Package Code- Code: 25 (Manual Ball Valve with Memory Stop, Fixed Flow Control) (2.00 GPM) Cooling Coil: Unions Special Quote (SQ)# SQ 1625 600 PSI Unions

230 Peachtree Street NW, Suite 1250Atlanta, GA 30303

Project Telephone #404.688.6233

230 Peachtree Hotel Conversion

260 - 23 60 00 - 2.7

Bulletin #4 - Fan Coil Units

05/05/15

Allie Creach [email protected]

1. Updates per Bulletin #4

The review of shop drawings does not relieve the Subcontractor/ Vendor from the requirements of the Contract Documents.Subcontractors/Vendors are hereby notified that any cost/schedule impacts caused by changes to a submittal must be reported to

Holder Construction within (5) days as stated in Section 8 of Holder's subcontract. Subcontractors/Vendors failing to report, inwriting, cost/schedule impacts within this time frame are fully responsible for such impacts. All changes or variations to the

Contract Documents must be flagged and noted. Failure to do so leaves the responsibility for coordination any cost impactscaused from changes with that Subcontractor/Vendor.

Holder Comments:

A/E Comments:

Holder Construction Company Submittal

Project Name:

Submittal Number:

Submittal Description:

Submittal Review Date:

Submittal Reviewed By:

Reviewed

Reviewed as Noted

Rejected

Page 2: Submittal...Cooling Coil: Package Code- Code: 25 (Manual Ball Valve with Memory Stop, Fixed Flow Control) (2.00 GPM) Cooling Coil: Unions Special Quote (SQ)# SQ 1625 600 PSI Unions

JCI Submittal Package - Terminal Units 4/29/2015 Page 1 of 13

JCI Submittal Package - Terminal Units

230 Peachtree Street Hotel 4/29/2015

Fan Coil Units - Bulletin 4 1

JCI/York FWC and FHP fan coil units

236000.2.7

See attached performance.

See attached electrical characteristic details.

See attached for accessories details.

See attached for options details.

None.

Page 3: Submittal...Cooling Coil: Package Code- Code: 25 (Manual Ball Valve with Memory Stop, Fixed Flow Control) (2.00 GPM) Cooling Coil: Unions Special Quote (SQ)# SQ 1625 600 PSI Unions

EQUIPMENT SUBMITTAL FOR APPROVAL

PROJECT: 230 Peachtree Street Hotel

LOCATION: Atlanta GA

York Solution Indoor Air Handling Unit

EQUIPMENT FWC & FHP Fan Coil Unit UNIT TAGS FCU B1-7 ~ FCU B1-17 & 2-16 QUANTITY (5) & 7 existing

SOLD TO: Batchelor & Kimball Inc.

6700 Tribble Street Lithonia, GA 30058

CONSULTING ENGINEER:

PerryCrabb 2987 Clairmont Road NE

Suite 400 Atlanta, GA 30329

PREPARED BY:

Allen J. Sirek Project Engineer

1350 Northmeadow Parkway Suite 100

Roswell, GA 30076

DATE: April 29, 2015

REVISION: 0

JCI Submittal Package - Terminal Units 4/29/2015 Page 2 of 13

JCI Submittal Package - Terminal Units

Page 4: Submittal...Cooling Coil: Package Code- Code: 25 (Manual Ball Valve with Memory Stop, Fixed Flow Control) (2.00 GPM) Cooling Coil: Unions Special Quote (SQ)# SQ 1625 600 PSI Unions

JCI Submittal Package - Terminal Units 4/29/2015 Page 3 of 13

JCI Submittal Package - Terminal Units

FCUs deleted - but can be re-used as FCUs FCU B1-7 ~ FCU B1-13

FCUs B1-14 ~ FCU B1-17 will be ordered also FCU 2-16

Bulletin 4 changes

Page 5: Submittal...Cooling Coil: Package Code- Code: 25 (Manual Ball Valve with Memory Stop, Fixed Flow Control) (2.00 GPM) Cooling Coil: Unions Special Quote (SQ)# SQ 1625 600 PSI Unions

Tag Airflow Qty ESP Model V/P/Hz EAT‐DB LAT‐DB Capacity Heating FLA V/P/Hz Steps 1 EAT‐DB/WB LAT‐DB/WBTotal 

CapacitySensible Capacity EWT/LWT Fluid Flow

FCU‐2‐16 241 1 0.15 FHP 277/1/60 70 96.2 2 7.22 277/1/60 1 75/63 54.6/52.9 7110 5450 45/53.8 1.6 GPMFCU‐B1‐7 566 1 0.2 FWC‐C 277/1/60 70 92.3 4 14.44 277/1/60 1 75/63 52.3/51.4 18790 14210 45/54.8 3.8 GPMFCU‐B1‐8 566 1 0.2 FWC‐C 277/1/60 70 92.3 4 14.44 277/1/60 1 75/63 52.3/51.4 18790 14210 45/54.8 3.8 GPMFCU‐B1‐9 566 1 0.2 FWC‐C 277/1/60 70 92.3 4 14.44 277/1/60 1 75/63 52.3/51.4 18790 14210 45/54.8 3.8 GPMFCU‐B1‐10 566 1 0.2 FWC‐C 277/1/60 70 92.3 4 14.44 277/1/60 1 75/63 52.3/51.4 18790 14210 45/54.8 3.8 GPMFCU‐B1‐11 566 1 0.2 FWC‐C 277/1/60 70 92.3 4 14.44 277/1/60 1 75/63 52.3/51.4 18790 14210 45/54.8 3.8 GPMFCU‐B1‐12 566 1 0.2 FWC‐C 277/1/60 70 92.3 4 14.44 277/1/60 1 75/63 52.3/51.4 18790 14210 45/54.8 3.8 GPMFCU‐B1‐13 566 1 0.2 FWC‐C 277/1/60 70 92.3 4 14.44 277/1/60 1 75/63 52.3/51.4 18790 14210 45/54.8 3.8 GPMFCU‐B1‐14 566 1 0.2 FWC‐C 277/1/60 70 92.3 4 14.44 277/1/60 1 75/63 52.3/51.4 18790 14210 45/54.8 3.8 GPMFCU‐B1‐15 566 1 0.2 FWC‐C 277/1/60 70 92.3 4 14.44 277/1/60 1 75/63 52.3/51.4 18790 14210 45/54.8 3.8 GPMFCU‐B1‐16 566 1 0.2 FWC‐C 277/1/60 70 92.3 4 14.44 277/1/60 1 75/63 52.3/51.4 18790 14210 45/54.8 3.8 GPMFCU‐B1‐17 566 1 0.2 FWC‐C 277/1/60 70 92.3 4 14.44 277/1/60 1 75/63 52.3/51.4 18790 14210 45/54.8 3.8 GPM

Notes and clarifications:1) Selections were based on mechanical drawings page M6‐02 (bulletin 4) and are dated 4/6/15.2) Bulletin 4 (4/6/15) deleted previous FCU‐1‐1 through FCU‐1‐7 fan coil units, and added the 12 new units however these deleted 7 units still meet the performance for the new B1 units and have been rerated.As a result only 5 additional terminal units will be required to be ordered (4 FWC‐C and 1 FHP).

Electric Heat Chilled Water CoilUnit230 Peachtree Bulletin 4 FCU 4/27/15

JCI Submittal Package - Terminal Units 4/29/2015 Page 4 of 13

JCI Submittal Package - Terminal Units

Note: Only FCU B1-14 ~ FCU B1-17 and FCU 2-16 will be ordered.

Page 6: Submittal...Cooling Coil: Package Code- Code: 25 (Manual Ball Valve with Memory Stop, Fixed Flow Control) (2.00 GPM) Cooling Coil: Unions Special Quote (SQ)# SQ 1625 600 PSI Unions

Confirmations for Release FCU 2-16

1) Confirm 277/1/60 2) Confirm cooling coil left or right hand connection

FCU B1-14

3) Confirm 277/1/60 4) Confirm cooling coil left or right hand connection

FCU B1-15

5) Confirm 277/1/60 6) Confirm cooling coil left or right hand connection

FCU B1-16

7) Confirm 277/1/60 8) Confirm cooling coil left or right hand connection

FCU B1-17

9) Confirm 277/1/60 10) Confirm cooling coil left or right hand connection

JCI Submittal Package - Terminal Units 4/29/2015 Page 5 of 13

JCI Submittal Package - Terminal Units

Page 7: Submittal...Cooling Coil: Package Code- Code: 25 (Manual Ball Valve with Memory Stop, Fixed Flow Control) (2.00 GPM) Cooling Coil: Unions Special Quote (SQ)# SQ 1625 600 PSI Unions

Performance Data Sheet

Project Name: 230 Peachtree Bulletin 4 FCU Location: Consultant/Engineer: Contractor: Sold To: P.O. No: PO

JCI Contract No: Contract # Coil Version: 7.01d Printed Date: 4/29/2015 8:57:33 AM Selection Date: 4/24/2015 11:44:14 AM Last Revision Date: 4/24/2015 11:44:31 AM

Unit Tag Qty Model Air Flow Total Duty Sensible Duty FCU-2-16 1 FHP25 241 CFM 7,110 Btuh 5,450 Btuh

Unit Data Model Size

: 25

Type : Horizontal Low Profile

No. Fans : 1 (Motor) HP : (1) 1/15 Motor FLA : 0.45 Fan Speed : Medium Capacity : Std. Capacity

Filter : 1" Throwaway Filter (Qty) Size : 26x8.5x1 Filter Face Area [ft²] 1.54 Inlet Direction : Rear

Coil Tube Dia. [in.] 1/2 Tube Wall [in.] 0.016 Coil Face Area [ft²] 1.35 Weight* [lb] 77

Output Data Options

Altitude [Ft.] 0 Air Flow Rate [CFM] 241 ESP [in.wg] 0.15

Cooling Data EAT DB/WB [°F] 75.0/ 63.0 LAT DB/WB [°F] 54.6/ 52.9 Total Capacity [Btuh] 7,110 Sensible Capacity [Btuh] 5,450 EWT/LWT [°F] 45.0/ 53.9 Fluid Flow [gpm] 1.60 Fluid P.D [ft.wg] 6.60 Fluid Velocity [fps] 2.80 Rows / FPI / Circuits : 3 Row / 10 FPI / 1 Ckt Coil Connection Size: [in.] 0.875

Heating Data EAT DB [°F] - LAT DB [°F] - Sensible Capacity [Btuh] - Rows / FPI / Circuits : - / - / -

Electric Heat Data V/P/HZ : 277/1/60 KW : 2 Steps : 1-Stage Temp Rise [°F] 26.2 Amp Draw : 7.22

BC07 24V, Unit S/S & Fan Op. Relay, 3-Spd Fan Relay & Transformer OC011 Drain Pan Float Switch OC013 Non-Fused Door Interlocking Disconnect Switch - 40 Amps Stainless Steel Unit Drain Pan Cooling Coil: Piping Package Size - 1/2" Cooling Coil: 2-Way Control Valve Cooling Coil: Factory Provided (2-Position Close-Off, Normally Closed) Cooling Coil: Galvanized Casing Cooling Coil: Left Hand Connection Cooling Coil: Manual Air Vent Cooling Coil: P/T Ports Cooling Coil: Package Code- Code: 25 (Manual Ball Valve with Memory Stop, Fixed Flow Control) (2.00 GPM) Cooling Coil: Unions

Special Quote (SQ)# SQ 1625 600 PSI Unions

Special Quote (SQ)# SQ 2841 Y strainer on FH with cleanout

Special Quote (SQ)# Special Quote (SQ)#

Electrical Data V/P/HZ : 277/1/60 Total Full Load Amps : 7.67 MCA / MSCP : 9.59 / 15.00 Fan Power Input [Watts] 120

* Unit weight includes unit with wet coil(s) as selected. (Does not include accessories)

Unit pressure drop and air flow based upon dry coil as required by AHRI-440.

Total sound power level data based on Horizontal Concealed Plenum Return Model with fan air flow at corresponding motor tap with 115/1/60 volt PSC motor, 4 row coil, 1" throwaway filter, 0.0" external static pressure and standard rated internal pressure losses.

Sound data tested in accordance with AHRI-350-2000.•Scheduled motor information is for Fan Input Power at High Speed.•For 0' altitude the coil selection has been made at Standard Conditions.•

Sound power By Octave Band (dB Re 1012 Watts)

Speed 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz Medium 53 53 49 45 41 34 29

Page 1 of 1Performance Data Sheet

4/29/2015http://webselect.johnsoncontrols.com/submittals/perfreport/PerformanceDataSheet.aspx?ch...

JCI Submittal Package - Terminal Units 4/29/2015 Page 6 of 13

JCI Submittal Package - Terminal Units

Page 8: Submittal...Cooling Coil: Package Code- Code: 25 (Manual Ball Valve with Memory Stop, Fixed Flow Control) (2.00 GPM) Cooling Coil: Unions Special Quote (SQ)# SQ 1625 600 PSI Unions

* Weight does not include accessories.

Fan selection and performance is shown at elevation of 0 ft.

Unit data is certified in accordance with AHRI-440. Sound data tested in accordance with AHRI-350-2000.

Total sound power level data based on Horizontal Concealed Plenum Return Model with fan CFM at corresponding motor tap with 115/1/60 volt PSC motor, 4 row coil, 1" throwaway filter, 0.0" external static pressure and standard rated internal pressure losses.

Unit pressure drop and CFM based upon dry coil as required by AHRI-440. Scheduled motor information is for Hi Speed. The coil selection has been made at Standard conditions. Outside Airflow is a user input value for scheduling purposes.

Project Name: 230 Peachtree Bulletin 4 FCU Ship Cycle: Standard Shipment Line #: 4 Tag: FCU-2-16 Selection Method: Fixed ESP/Nominal Airflow Elevation: 0 ft. Selection Date: 4/24/2015 11:44:15 AM Printed Date: 4/29/2015 8:56:02 AM ET Coil Version: 7.01d Notes: This field is for user purposes only and will not transfer to the order form.

General

Mfg Model Unit Size

Unit Capacity

Airflow (cfm)

OA (cfm)

ESP (in.wc)

Motor (Hp)

Motor RPM

Fan Full Load

Amps

Total Full Load

AmpsMCA MSCP Fan

WattsFan Qty V/P/Hz Motor

SpeedWeight*

(lb) Filter Type

Johnson Controls FHP 25 Standard 241 0 0.15 (1) 1/15 1450 0.45 7.67 9.59 15 120 1 277/1/60 Medium 77 1"

Throwaway

Electric Heat Coil

EAT DB (deg.F) LAT DB (deg.F) Capacity (kW) Heating Full Load Amps Volts/Phase/Hz. Steps Air PD (in.wc)

70 96.2 2 7.22 277/1/60 1 0.01

Chilled Water Coil

EAT DB/WB (deg.F)

LAT DB/WB (deg.F)

Total Capacity (Btuh)

Sensible Capacity (Btuh)

EWT/LWT (deg.F)

Fluid Flow (gpm) Fluid PD (ft.)

Fluid Velocity

(fps)

Air PD (in.wc)

Coil Rows

Coil FPI

No. Circuits

Tube Wall

75 / 63 54.6 / 52.9 7110 5450 45 / 53.8 1.60 6.6 2.8 0.05 3 10 1 0.016 in.

Sound Power By Octave Band (dB Re 10-12 Watts)

Band 2 3 4 5 6 7 8

Frequency 125 250 500 1000 2000 4000 8000

Total 53 53 49 45 41 34 29

Page 1 of 1Johnson Controls - Selection Summary

4/29/2015http://webselect.johnsoncontrols.com/Selection/fcu.asp?action=printallselections&projectI...

JCI Submittal Package - Terminal Units 4/29/2015 Page 7 of 13

JCI Submittal Package - Terminal Units

Page 9: Submittal...Cooling Coil: Package Code- Code: 25 (Manual Ball Valve with Memory Stop, Fixed Flow Control) (2.00 GPM) Cooling Coil: Unions Special Quote (SQ)# SQ 1625 600 PSI Unions

JCI Submittal Package - Terminal Units 4/29/2015 Page 8 of 13

JCI Submittal Package - Terminal Units

Page 10: Submittal...Cooling Coil: Package Code- Code: 25 (Manual Ball Valve with Memory Stop, Fixed Flow Control) (2.00 GPM) Cooling Coil: Unions Special Quote (SQ)# SQ 1625 600 PSI Unions

Performance Data Sheet

Project Name: 230 Peachtree Bulletin 4 FCU Location: Consultant/Engineer: Contractor: Sold To: P.O. No: PO

JCI Contract No: Contract # Coil Version: 4.28a Printed Date: 4/29/2015 9:02:05 AM Selection Date: 4/24/2015 11:37:34 AM Last Revision Date: 4/24/2015 11:38:02 AM

Unit Tag Qty Model Air Flow Total Duty Sensible Duty FCU-B1-7 1 FWC-C12 566 CFM 18,790 Btuh 14,210 Btuh

Unit Data Model Size

: 12

Type : Vertical Floor - Series C

No. Fans : 4 (Motor) HP : (2) 1/20 Motor FLA : 0.84 Fan Speed : High Capacity : Std. Capacity

Filter : 1" Throwaway Filter (Qty) Size : (3) 9.25 X 21.75 X 1 Filter Face Area [ft²] 4.19

Coil Tube Dia. [in.] 1/2 Tube Wall [in.] 0.016 Coil Face Area [ft²] 4.03 Weight* [lb] 166

Output Data Options

Altitude [Ft.] 0 Air Flow Rate [CFM] 566 ESP [in.wg] 0.20

Cooling Data EAT DB/WB [°F] 75.0/ 63.0 LAT DB/WB [°F] 52.3/ 51.5 Total Capacity [Btuh] 18,790 Sensible Capacity [Btuh] 14,210 EWT/LWT [°F] 45.0/ 54.8 Fluid Flow [gpm] 3.80 Fluid P.D [ft.wg] 3.38 Fluid Velocity [fps] 2.20 Rows / FPI / Circuits : 3 Row / 10 FPI / 3 Ckt Coil Connection Size: [in.] 0.625

Heating Data EAT DB [°F] - LAT DB [°F] - Sensible Capacity [Btuh] - Rows / FPI / Circuits : - / - / -

Electric Heat Data V/P/HZ : 277/1/60 KW : 4 Steps : 1-Stage Temp Rise [°F] 22.3 Amp Draw : 14.44

Auxiliary Drip Pan- Plastic, Double Wall BC03 24V, Unit S/S Relay / Fan Op. Relay & Transformer Coil Casing- Galvanized Casing OC011 Drain Pan Float Switch OC013 Non-Fused Door Interlocking Disconnect Switch - 40 Amps Paint Options- Pearl White Satin Remote Mounted Thermostat Return Air Options- Return: Open Toe Space Stainless Steel Unit Drain Pan Supply Air Options- Supply: Duct Collar Cooling Coil: Piping Package Size - 1/2" Cooling Coil: 2-Way Control Valve Cooling Coil: Factory Mounted Piping Package Cooling Coil: Factory Provided (2-Position Close-Off, Normally Closed) Cooling Coil: Left Hand Connection Cooling Coil: Manual Air Vent Cooling Coil: Manual Ball valve w/ Memory Stop, fixed flow control (4.00 GPM) Cooling Coil: P/T Ports Cooling Coil: Unions Cooling Coil: Y-Strainer- Y-Strainer with Blowdown

Special Quote (SQ)# SQ 1625 600 PSI Unions

Special Quote (SQ)# Special Quote (SQ)# Special Quote (SQ)#

Electrical Data V/P/HZ : 277/1/60 Total Full Load Amps : 15.28 MCA / MSCP : 19.10 / 20.00 Fan Power Input [Watts] 154

* Unit weight includes unit with wet coil(s) as selected. (Does not include accessories)

Unit pressure drop and air flow based upon dry coil as required by AHRI-440.

Total sound power level data based on Vertical Floor Exposed Model with fan air flow at corresponding motor tap with 115/1/60 volt PSC motor, 4 row coil, 1" throwaway filter, 0.0" external static pressure and standard rated internal pressure losses.

Sound data tested in accordance with AHRI-350-2000.•Scheduled motor information is for Fan Input Power at High Speed.•For 0' altitude the coil selection has been made at Standard Conditions.•

Sound power By Octave Band (dB Re 1012 Watts)

Speed 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz High 62 64 65 56 50 44 35

Page 1 of 11Performance Data Sheet

4/29/2015http://webselect.johnsoncontrols.com/submittals/perfreport/PerformanceDataSheet.aspx?ch...

JCI Submittal Package - Terminal Units 4/29/2015 Page 9 of 13

JCI Submittal Package - Terminal Units

FCU-B1-7 ~ FCU-B1-17 (11 total)

Page 11: Submittal...Cooling Coil: Package Code- Code: 25 (Manual Ball Valve with Memory Stop, Fixed Flow Control) (2.00 GPM) Cooling Coil: Unions Special Quote (SQ)# SQ 1625 600 PSI Unions

* Weight does not include accessories.

Fan selection and performance is shown at elevation of 0 ft.

Unit data is certified in accordance with AHRI-440. Sound data tested in accordance with AHRI-350-2000.

Total sound power level data based on Vertical Floor Exposed model with fan CFM at corresponding motor tap with 115/1/60 volt PSC motor, 4 row coil, 1" throwaway filter, 0.0" external static pressure and standard rated internal pressure losses.

Unit pressure drop and CFM based upon dry coil as required by AHRI-440. Scheduled motor information is for Hi Speed. The coil selection has been made at Standard conditions. Outside Airflow is a user input value for scheduling purposes.

Project Name: 230 Peachtree Bulletin 4 FCU Ship Cycle: Standard Shipment Line #: 5 Tag: FCU-B1-7 Selection Method: Fixed ESP/Nominal Airflow Elevation: 0 ft. Selection Date: 4/24/2015 11:37:35 AM Printed Date: 4/29/2015 9:01:05 AM ET Coil Version: 4.28a Notes: This field is for user purposes only and will not transfer to the order form.

General

Mfg Model Unit Size

Unit Capacity

Airflow (cfm)

OA (cfm)

ESP (in.wc)

Motor (Hp)

Motor RPM

Fan Full Load

Amps

Total Full Load

AmpsMCA MSCP Fan

WattsFan Qty V/P/Hz Motor

SpeedWeight*

(lb) Filter Type

Johnson Controls FWC-C 12 Standard 566 0 0.2 (2)

1/20 2 @

1050 0.84 15.28 19.1 20 154 4 277/1/60 High 166 1" Throwaway

Chilled Water Coil

EAT DB/WB (deg.F)

LAT DB/WB (deg.F)

Total Capacity

(Btuh)

Sensible Capacity

(Btuh)

EWT/LWT (deg.F)

Fluid Flow (gpm) Fluid PD (ft.) Fluid

Velocity (fps)Air PD (in.wc)

Coil Rows

Coil FPI

No. Circuits

Tube Wall

75 / 63 52.3 / 51.4 18790 14210 45 / 54.8 3.80 3.38 2.2 0.04 3 10 3 0.016 in.

Electric Heat Coil

EAT DB (deg.F) LAT DB (deg.F) Capacity (kW) Heating Full Load Amps Volts/Phase/Hz. Steps Air PD (in.wc)

70 92.3 4 14.44 277/1/60 1 0.01

Sound Power By Octave Band (dB Re 10-12 Watts)

Band 2 3 4 5 6 7 8

Frequency 125 250 500 1000 2000 4000 8000

Total 62 64 65 56 50 44 35

Page 1 of 11Johnson Controls - Selection Summary

4/29/2015http://webselect.johnsoncontrols.com/Selection/fcu.asp?action=printallselections&projectI...

JCI Submittal Package - Terminal Units 4/29/2015 Page 10 of 13

JCI Submittal Package - Terminal Units

FCU-B1-7 ~ FCU-B1-17 (11 total)

Page 12: Submittal...Cooling Coil: Package Code- Code: 25 (Manual Ball Valve with Memory Stop, Fixed Flow Control) (2.00 GPM) Cooling Coil: Unions Special Quote (SQ)# SQ 1625 600 PSI Unions

Project: 230 Peachtree Street Hotel 1 Submittal

Equipment Release Approval Form

Product Type: Non-Stacker Fan Coil Units

Unit Tags: Various

The following table must be completed prior to releasing the equipment for fabrication. Please initial the column indicating the information contained in this submittal has been verified, or indicate to refer to a marked-up page.

SUBMITTAL VERIFICATION

Purchaser InitialsElectrical voltage and electrical connections arecompatible with jobsite requirements.

Piping / Ductwork connections shown in this submittal are correct.

Unit tag designations are correct.

Equipment dimensions (length, width, and height) and weights have been verified to comply with jobsite conditions and rigging requirements. Please indicate approval by your initials on all included drawings.

JCI Submittal Package - Terminal Units 4/29/2015 Page 11 of 13

JCI Submittal Package - Terminal Units

Page 13: Submittal...Cooling Coil: Package Code- Code: 25 (Manual Ball Valve with Memory Stop, Fixed Flow Control) (2.00 GPM) Cooling Coil: Unions Special Quote (SQ)# SQ 1625 600 PSI Unions

Project: 230 Peachtree Street Hotel 2 Submittal

Important Notes:

1) Actual fabrication release cannot commence until this form is signed by the customer and returned to JCI along with a release notification want date and ship to address.

2) Equipment "lead-time" does not start until confirmed release documentation is received, and the order is actually released to the factory.

3) Modifications to equipment configurations after fabrication release may impact cost and lead-time.

4) Attached configurations are as shown in the approved equipment submittals or as defined in superseding customer correspondence.

5) FS Fan Coil Units "Side" / "Hand" orientation is relative to a person with air hitting the back of your head.

6) Note that once this document is confirmed, the equipment configurations defined by this document take precedence over all other documents.

7) "Want date" and/or "ship to address" changes made after this document is confirmed may impact cost and lead-time.

JCI Submittal Package - Terminal Units 4/29/2015 Page 12 of 13

JCI Submittal Package - Terminal Units

Page 14: Submittal...Cooling Coil: Package Code- Code: 25 (Manual Ball Valve with Memory Stop, Fixed Flow Control) (2.00 GPM) Cooling Coil: Unions Special Quote (SQ)# SQ 1625 600 PSI Unions

Project: 230 Peachtree Street Hotel 3 Submittal

Please fill out the following table and refer to the receiving/rigging instructions in this submittal to help ensure a smooth delivery and installation of the equipment.

DELIVERY INFORMATION

Please fill out information below

Contact name for coordinating delivery of equipment with transportation company

Contact phone number

Advance notice required from transportation company prior to delivering equipment (typically 48 hours)

Ship to address:

Other special shipping instructions or requirements

CUSTOMER APPROVAL:

Customer Name:

Signature (*)

Date:

JCI Submittal Package - Terminal Units 4/29/2015 Page 13 of 13