Submittal...Cooling Coil: Package Code- Code: 25 (Manual Ball Valve with Memory Stop, Fixed Flow...
Transcript of Submittal...Cooling Coil: Package Code- Code: 25 (Manual Ball Valve with Memory Stop, Fixed Flow...
230 Peachtree Street NW, Suite 1250Atlanta, GA 30303
Project Telephone #404.688.6233
230 Peachtree Hotel Conversion
260 - 23 60 00 - 2.7
Bulletin #4 - Fan Coil Units
05/05/15
Allie Creach [email protected]
1. Updates per Bulletin #4
The review of shop drawings does not relieve the Subcontractor/ Vendor from the requirements of the Contract Documents.Subcontractors/Vendors are hereby notified that any cost/schedule impacts caused by changes to a submittal must be reported to
Holder Construction within (5) days as stated in Section 8 of Holder's subcontract. Subcontractors/Vendors failing to report, inwriting, cost/schedule impacts within this time frame are fully responsible for such impacts. All changes or variations to the
Contract Documents must be flagged and noted. Failure to do so leaves the responsibility for coordination any cost impactscaused from changes with that Subcontractor/Vendor.
Holder Comments:
A/E Comments:
Holder Construction Company Submittal
Project Name:
Submittal Number:
Submittal Description:
Submittal Review Date:
Submittal Reviewed By:
Reviewed
Reviewed as Noted
Rejected
JCI Submittal Package - Terminal Units 4/29/2015 Page 1 of 13
JCI Submittal Package - Terminal Units
230 Peachtree Street Hotel 4/29/2015
Fan Coil Units - Bulletin 4 1
JCI/York FWC and FHP fan coil units
236000.2.7
See attached performance.
See attached electrical characteristic details.
See attached for accessories details.
See attached for options details.
None.
EQUIPMENT SUBMITTAL FOR APPROVAL
PROJECT: 230 Peachtree Street Hotel
LOCATION: Atlanta GA
York Solution Indoor Air Handling Unit
EQUIPMENT FWC & FHP Fan Coil Unit UNIT TAGS FCU B1-7 ~ FCU B1-17 & 2-16 QUANTITY (5) & 7 existing
SOLD TO: Batchelor & Kimball Inc.
6700 Tribble Street Lithonia, GA 30058
CONSULTING ENGINEER:
PerryCrabb 2987 Clairmont Road NE
Suite 400 Atlanta, GA 30329
PREPARED BY:
Allen J. Sirek Project Engineer
1350 Northmeadow Parkway Suite 100
Roswell, GA 30076
DATE: April 29, 2015
REVISION: 0
JCI Submittal Package - Terminal Units 4/29/2015 Page 2 of 13
JCI Submittal Package - Terminal Units
JCI Submittal Package - Terminal Units 4/29/2015 Page 3 of 13
JCI Submittal Package - Terminal Units
FCUs deleted - but can be re-used as FCUs FCU B1-7 ~ FCU B1-13
FCUs B1-14 ~ FCU B1-17 will be ordered also FCU 2-16
Bulletin 4 changes
Tag Airflow Qty ESP Model V/P/Hz EAT‐DB LAT‐DB Capacity Heating FLA V/P/Hz Steps 1 EAT‐DB/WB LAT‐DB/WBTotal
CapacitySensible Capacity EWT/LWT Fluid Flow
FCU‐2‐16 241 1 0.15 FHP 277/1/60 70 96.2 2 7.22 277/1/60 1 75/63 54.6/52.9 7110 5450 45/53.8 1.6 GPMFCU‐B1‐7 566 1 0.2 FWC‐C 277/1/60 70 92.3 4 14.44 277/1/60 1 75/63 52.3/51.4 18790 14210 45/54.8 3.8 GPMFCU‐B1‐8 566 1 0.2 FWC‐C 277/1/60 70 92.3 4 14.44 277/1/60 1 75/63 52.3/51.4 18790 14210 45/54.8 3.8 GPMFCU‐B1‐9 566 1 0.2 FWC‐C 277/1/60 70 92.3 4 14.44 277/1/60 1 75/63 52.3/51.4 18790 14210 45/54.8 3.8 GPMFCU‐B1‐10 566 1 0.2 FWC‐C 277/1/60 70 92.3 4 14.44 277/1/60 1 75/63 52.3/51.4 18790 14210 45/54.8 3.8 GPMFCU‐B1‐11 566 1 0.2 FWC‐C 277/1/60 70 92.3 4 14.44 277/1/60 1 75/63 52.3/51.4 18790 14210 45/54.8 3.8 GPMFCU‐B1‐12 566 1 0.2 FWC‐C 277/1/60 70 92.3 4 14.44 277/1/60 1 75/63 52.3/51.4 18790 14210 45/54.8 3.8 GPMFCU‐B1‐13 566 1 0.2 FWC‐C 277/1/60 70 92.3 4 14.44 277/1/60 1 75/63 52.3/51.4 18790 14210 45/54.8 3.8 GPMFCU‐B1‐14 566 1 0.2 FWC‐C 277/1/60 70 92.3 4 14.44 277/1/60 1 75/63 52.3/51.4 18790 14210 45/54.8 3.8 GPMFCU‐B1‐15 566 1 0.2 FWC‐C 277/1/60 70 92.3 4 14.44 277/1/60 1 75/63 52.3/51.4 18790 14210 45/54.8 3.8 GPMFCU‐B1‐16 566 1 0.2 FWC‐C 277/1/60 70 92.3 4 14.44 277/1/60 1 75/63 52.3/51.4 18790 14210 45/54.8 3.8 GPMFCU‐B1‐17 566 1 0.2 FWC‐C 277/1/60 70 92.3 4 14.44 277/1/60 1 75/63 52.3/51.4 18790 14210 45/54.8 3.8 GPM
Notes and clarifications:1) Selections were based on mechanical drawings page M6‐02 (bulletin 4) and are dated 4/6/15.2) Bulletin 4 (4/6/15) deleted previous FCU‐1‐1 through FCU‐1‐7 fan coil units, and added the 12 new units however these deleted 7 units still meet the performance for the new B1 units and have been rerated.As a result only 5 additional terminal units will be required to be ordered (4 FWC‐C and 1 FHP).
Electric Heat Chilled Water CoilUnit230 Peachtree Bulletin 4 FCU 4/27/15
JCI Submittal Package - Terminal Units 4/29/2015 Page 4 of 13
JCI Submittal Package - Terminal Units
Note: Only FCU B1-14 ~ FCU B1-17 and FCU 2-16 will be ordered.
Confirmations for Release FCU 2-16
1) Confirm 277/1/60 2) Confirm cooling coil left or right hand connection
FCU B1-14
3) Confirm 277/1/60 4) Confirm cooling coil left or right hand connection
FCU B1-15
5) Confirm 277/1/60 6) Confirm cooling coil left or right hand connection
FCU B1-16
7) Confirm 277/1/60 8) Confirm cooling coil left or right hand connection
FCU B1-17
9) Confirm 277/1/60 10) Confirm cooling coil left or right hand connection
JCI Submittal Package - Terminal Units 4/29/2015 Page 5 of 13
JCI Submittal Package - Terminal Units
Performance Data Sheet
Project Name: 230 Peachtree Bulletin 4 FCU Location: Consultant/Engineer: Contractor: Sold To: P.O. No: PO
JCI Contract No: Contract # Coil Version: 7.01d Printed Date: 4/29/2015 8:57:33 AM Selection Date: 4/24/2015 11:44:14 AM Last Revision Date: 4/24/2015 11:44:31 AM
Unit Tag Qty Model Air Flow Total Duty Sensible Duty FCU-2-16 1 FHP25 241 CFM 7,110 Btuh 5,450 Btuh
Unit Data Model Size
: 25
Type : Horizontal Low Profile
No. Fans : 1 (Motor) HP : (1) 1/15 Motor FLA : 0.45 Fan Speed : Medium Capacity : Std. Capacity
Filter : 1" Throwaway Filter (Qty) Size : 26x8.5x1 Filter Face Area [ft²] 1.54 Inlet Direction : Rear
Coil Tube Dia. [in.] 1/2 Tube Wall [in.] 0.016 Coil Face Area [ft²] 1.35 Weight* [lb] 77
Output Data Options
Altitude [Ft.] 0 Air Flow Rate [CFM] 241 ESP [in.wg] 0.15
Cooling Data EAT DB/WB [°F] 75.0/ 63.0 LAT DB/WB [°F] 54.6/ 52.9 Total Capacity [Btuh] 7,110 Sensible Capacity [Btuh] 5,450 EWT/LWT [°F] 45.0/ 53.9 Fluid Flow [gpm] 1.60 Fluid P.D [ft.wg] 6.60 Fluid Velocity [fps] 2.80 Rows / FPI / Circuits : 3 Row / 10 FPI / 1 Ckt Coil Connection Size: [in.] 0.875
Heating Data EAT DB [°F] - LAT DB [°F] - Sensible Capacity [Btuh] - Rows / FPI / Circuits : - / - / -
Electric Heat Data V/P/HZ : 277/1/60 KW : 2 Steps : 1-Stage Temp Rise [°F] 26.2 Amp Draw : 7.22
BC07 24V, Unit S/S & Fan Op. Relay, 3-Spd Fan Relay & Transformer OC011 Drain Pan Float Switch OC013 Non-Fused Door Interlocking Disconnect Switch - 40 Amps Stainless Steel Unit Drain Pan Cooling Coil: Piping Package Size - 1/2" Cooling Coil: 2-Way Control Valve Cooling Coil: Factory Provided (2-Position Close-Off, Normally Closed) Cooling Coil: Galvanized Casing Cooling Coil: Left Hand Connection Cooling Coil: Manual Air Vent Cooling Coil: P/T Ports Cooling Coil: Package Code- Code: 25 (Manual Ball Valve with Memory Stop, Fixed Flow Control) (2.00 GPM) Cooling Coil: Unions
Special Quote (SQ)# SQ 1625 600 PSI Unions
Special Quote (SQ)# SQ 2841 Y strainer on FH with cleanout
Special Quote (SQ)# Special Quote (SQ)#
Electrical Data V/P/HZ : 277/1/60 Total Full Load Amps : 7.67 MCA / MSCP : 9.59 / 15.00 Fan Power Input [Watts] 120
* Unit weight includes unit with wet coil(s) as selected. (Does not include accessories)
•
Unit pressure drop and air flow based upon dry coil as required by AHRI-440.
•
Total sound power level data based on Horizontal Concealed Plenum Return Model with fan air flow at corresponding motor tap with 115/1/60 volt PSC motor, 4 row coil, 1" throwaway filter, 0.0" external static pressure and standard rated internal pressure losses.
•
Sound data tested in accordance with AHRI-350-2000.•Scheduled motor information is for Fan Input Power at High Speed.•For 0' altitude the coil selection has been made at Standard Conditions.•
Sound power By Octave Band (dB Re 1012 Watts)
Speed 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz Medium 53 53 49 45 41 34 29
Page 1 of 1Performance Data Sheet
4/29/2015http://webselect.johnsoncontrols.com/submittals/perfreport/PerformanceDataSheet.aspx?ch...
JCI Submittal Package - Terminal Units 4/29/2015 Page 6 of 13
JCI Submittal Package - Terminal Units
* Weight does not include accessories.
Fan selection and performance is shown at elevation of 0 ft.
Unit data is certified in accordance with AHRI-440. Sound data tested in accordance with AHRI-350-2000.
Total sound power level data based on Horizontal Concealed Plenum Return Model with fan CFM at corresponding motor tap with 115/1/60 volt PSC motor, 4 row coil, 1" throwaway filter, 0.0" external static pressure and standard rated internal pressure losses.
Unit pressure drop and CFM based upon dry coil as required by AHRI-440. Scheduled motor information is for Hi Speed. The coil selection has been made at Standard conditions. Outside Airflow is a user input value for scheduling purposes.
Project Name: 230 Peachtree Bulletin 4 FCU Ship Cycle: Standard Shipment Line #: 4 Tag: FCU-2-16 Selection Method: Fixed ESP/Nominal Airflow Elevation: 0 ft. Selection Date: 4/24/2015 11:44:15 AM Printed Date: 4/29/2015 8:56:02 AM ET Coil Version: 7.01d Notes: This field is for user purposes only and will not transfer to the order form.
General
Mfg Model Unit Size
Unit Capacity
Airflow (cfm)
OA (cfm)
ESP (in.wc)
Motor (Hp)
Motor RPM
Fan Full Load
Amps
Total Full Load
AmpsMCA MSCP Fan
WattsFan Qty V/P/Hz Motor
SpeedWeight*
(lb) Filter Type
Johnson Controls FHP 25 Standard 241 0 0.15 (1) 1/15 1450 0.45 7.67 9.59 15 120 1 277/1/60 Medium 77 1"
Throwaway
Electric Heat Coil
EAT DB (deg.F) LAT DB (deg.F) Capacity (kW) Heating Full Load Amps Volts/Phase/Hz. Steps Air PD (in.wc)
70 96.2 2 7.22 277/1/60 1 0.01
Chilled Water Coil
EAT DB/WB (deg.F)
LAT DB/WB (deg.F)
Total Capacity (Btuh)
Sensible Capacity (Btuh)
EWT/LWT (deg.F)
Fluid Flow (gpm) Fluid PD (ft.)
Fluid Velocity
(fps)
Air PD (in.wc)
Coil Rows
Coil FPI
No. Circuits
Tube Wall
75 / 63 54.6 / 52.9 7110 5450 45 / 53.8 1.60 6.6 2.8 0.05 3 10 1 0.016 in.
Sound Power By Octave Band (dB Re 10-12 Watts)
Band 2 3 4 5 6 7 8
Frequency 125 250 500 1000 2000 4000 8000
Total 53 53 49 45 41 34 29
Page 1 of 1Johnson Controls - Selection Summary
4/29/2015http://webselect.johnsoncontrols.com/Selection/fcu.asp?action=printallselections&projectI...
JCI Submittal Package - Terminal Units 4/29/2015 Page 7 of 13
JCI Submittal Package - Terminal Units
JCI Submittal Package - Terminal Units 4/29/2015 Page 8 of 13
JCI Submittal Package - Terminal Units
Performance Data Sheet
Project Name: 230 Peachtree Bulletin 4 FCU Location: Consultant/Engineer: Contractor: Sold To: P.O. No: PO
JCI Contract No: Contract # Coil Version: 4.28a Printed Date: 4/29/2015 9:02:05 AM Selection Date: 4/24/2015 11:37:34 AM Last Revision Date: 4/24/2015 11:38:02 AM
Unit Tag Qty Model Air Flow Total Duty Sensible Duty FCU-B1-7 1 FWC-C12 566 CFM 18,790 Btuh 14,210 Btuh
Unit Data Model Size
: 12
Type : Vertical Floor - Series C
No. Fans : 4 (Motor) HP : (2) 1/20 Motor FLA : 0.84 Fan Speed : High Capacity : Std. Capacity
Filter : 1" Throwaway Filter (Qty) Size : (3) 9.25 X 21.75 X 1 Filter Face Area [ft²] 4.19
Coil Tube Dia. [in.] 1/2 Tube Wall [in.] 0.016 Coil Face Area [ft²] 4.03 Weight* [lb] 166
Output Data Options
Altitude [Ft.] 0 Air Flow Rate [CFM] 566 ESP [in.wg] 0.20
Cooling Data EAT DB/WB [°F] 75.0/ 63.0 LAT DB/WB [°F] 52.3/ 51.5 Total Capacity [Btuh] 18,790 Sensible Capacity [Btuh] 14,210 EWT/LWT [°F] 45.0/ 54.8 Fluid Flow [gpm] 3.80 Fluid P.D [ft.wg] 3.38 Fluid Velocity [fps] 2.20 Rows / FPI / Circuits : 3 Row / 10 FPI / 3 Ckt Coil Connection Size: [in.] 0.625
Heating Data EAT DB [°F] - LAT DB [°F] - Sensible Capacity [Btuh] - Rows / FPI / Circuits : - / - / -
Electric Heat Data V/P/HZ : 277/1/60 KW : 4 Steps : 1-Stage Temp Rise [°F] 22.3 Amp Draw : 14.44
Auxiliary Drip Pan- Plastic, Double Wall BC03 24V, Unit S/S Relay / Fan Op. Relay & Transformer Coil Casing- Galvanized Casing OC011 Drain Pan Float Switch OC013 Non-Fused Door Interlocking Disconnect Switch - 40 Amps Paint Options- Pearl White Satin Remote Mounted Thermostat Return Air Options- Return: Open Toe Space Stainless Steel Unit Drain Pan Supply Air Options- Supply: Duct Collar Cooling Coil: Piping Package Size - 1/2" Cooling Coil: 2-Way Control Valve Cooling Coil: Factory Mounted Piping Package Cooling Coil: Factory Provided (2-Position Close-Off, Normally Closed) Cooling Coil: Left Hand Connection Cooling Coil: Manual Air Vent Cooling Coil: Manual Ball valve w/ Memory Stop, fixed flow control (4.00 GPM) Cooling Coil: P/T Ports Cooling Coil: Unions Cooling Coil: Y-Strainer- Y-Strainer with Blowdown
Special Quote (SQ)# SQ 1625 600 PSI Unions
Special Quote (SQ)# Special Quote (SQ)# Special Quote (SQ)#
Electrical Data V/P/HZ : 277/1/60 Total Full Load Amps : 15.28 MCA / MSCP : 19.10 / 20.00 Fan Power Input [Watts] 154
* Unit weight includes unit with wet coil(s) as selected. (Does not include accessories)
•
Unit pressure drop and air flow based upon dry coil as required by AHRI-440.
•
Total sound power level data based on Vertical Floor Exposed Model with fan air flow at corresponding motor tap with 115/1/60 volt PSC motor, 4 row coil, 1" throwaway filter, 0.0" external static pressure and standard rated internal pressure losses.
•
Sound data tested in accordance with AHRI-350-2000.•Scheduled motor information is for Fan Input Power at High Speed.•For 0' altitude the coil selection has been made at Standard Conditions.•
Sound power By Octave Band (dB Re 1012 Watts)
Speed 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz High 62 64 65 56 50 44 35
Page 1 of 11Performance Data Sheet
4/29/2015http://webselect.johnsoncontrols.com/submittals/perfreport/PerformanceDataSheet.aspx?ch...
JCI Submittal Package - Terminal Units 4/29/2015 Page 9 of 13
JCI Submittal Package - Terminal Units
FCU-B1-7 ~ FCU-B1-17 (11 total)
* Weight does not include accessories.
Fan selection and performance is shown at elevation of 0 ft.
Unit data is certified in accordance with AHRI-440. Sound data tested in accordance with AHRI-350-2000.
Total sound power level data based on Vertical Floor Exposed model with fan CFM at corresponding motor tap with 115/1/60 volt PSC motor, 4 row coil, 1" throwaway filter, 0.0" external static pressure and standard rated internal pressure losses.
Unit pressure drop and CFM based upon dry coil as required by AHRI-440. Scheduled motor information is for Hi Speed. The coil selection has been made at Standard conditions. Outside Airflow is a user input value for scheduling purposes.
Project Name: 230 Peachtree Bulletin 4 FCU Ship Cycle: Standard Shipment Line #: 5 Tag: FCU-B1-7 Selection Method: Fixed ESP/Nominal Airflow Elevation: 0 ft. Selection Date: 4/24/2015 11:37:35 AM Printed Date: 4/29/2015 9:01:05 AM ET Coil Version: 4.28a Notes: This field is for user purposes only and will not transfer to the order form.
General
Mfg Model Unit Size
Unit Capacity
Airflow (cfm)
OA (cfm)
ESP (in.wc)
Motor (Hp)
Motor RPM
Fan Full Load
Amps
Total Full Load
AmpsMCA MSCP Fan
WattsFan Qty V/P/Hz Motor
SpeedWeight*
(lb) Filter Type
Johnson Controls FWC-C 12 Standard 566 0 0.2 (2)
1/20 2 @
1050 0.84 15.28 19.1 20 154 4 277/1/60 High 166 1" Throwaway
Chilled Water Coil
EAT DB/WB (deg.F)
LAT DB/WB (deg.F)
Total Capacity
(Btuh)
Sensible Capacity
(Btuh)
EWT/LWT (deg.F)
Fluid Flow (gpm) Fluid PD (ft.) Fluid
Velocity (fps)Air PD (in.wc)
Coil Rows
Coil FPI
No. Circuits
Tube Wall
75 / 63 52.3 / 51.4 18790 14210 45 / 54.8 3.80 3.38 2.2 0.04 3 10 3 0.016 in.
Electric Heat Coil
EAT DB (deg.F) LAT DB (deg.F) Capacity (kW) Heating Full Load Amps Volts/Phase/Hz. Steps Air PD (in.wc)
70 92.3 4 14.44 277/1/60 1 0.01
Sound Power By Octave Band (dB Re 10-12 Watts)
Band 2 3 4 5 6 7 8
Frequency 125 250 500 1000 2000 4000 8000
Total 62 64 65 56 50 44 35
Page 1 of 11Johnson Controls - Selection Summary
4/29/2015http://webselect.johnsoncontrols.com/Selection/fcu.asp?action=printallselections&projectI...
JCI Submittal Package - Terminal Units 4/29/2015 Page 10 of 13
JCI Submittal Package - Terminal Units
FCU-B1-7 ~ FCU-B1-17 (11 total)
Project: 230 Peachtree Street Hotel 1 Submittal
Equipment Release Approval Form
Product Type: Non-Stacker Fan Coil Units
Unit Tags: Various
The following table must be completed prior to releasing the equipment for fabrication. Please initial the column indicating the information contained in this submittal has been verified, or indicate to refer to a marked-up page.
SUBMITTAL VERIFICATION
Purchaser InitialsElectrical voltage and electrical connections arecompatible with jobsite requirements.
Piping / Ductwork connections shown in this submittal are correct.
Unit tag designations are correct.
Equipment dimensions (length, width, and height) and weights have been verified to comply with jobsite conditions and rigging requirements. Please indicate approval by your initials on all included drawings.
JCI Submittal Package - Terminal Units 4/29/2015 Page 11 of 13
JCI Submittal Package - Terminal Units
Project: 230 Peachtree Street Hotel 2 Submittal
Important Notes:
1) Actual fabrication release cannot commence until this form is signed by the customer and returned to JCI along with a release notification want date and ship to address.
2) Equipment "lead-time" does not start until confirmed release documentation is received, and the order is actually released to the factory.
3) Modifications to equipment configurations after fabrication release may impact cost and lead-time.
4) Attached configurations are as shown in the approved equipment submittals or as defined in superseding customer correspondence.
5) FS Fan Coil Units "Side" / "Hand" orientation is relative to a person with air hitting the back of your head.
6) Note that once this document is confirmed, the equipment configurations defined by this document take precedence over all other documents.
7) "Want date" and/or "ship to address" changes made after this document is confirmed may impact cost and lead-time.
JCI Submittal Package - Terminal Units 4/29/2015 Page 12 of 13
JCI Submittal Package - Terminal Units
Project: 230 Peachtree Street Hotel 3 Submittal
Please fill out the following table and refer to the receiving/rigging instructions in this submittal to help ensure a smooth delivery and installation of the equipment.
DELIVERY INFORMATION
Please fill out information below
Contact name for coordinating delivery of equipment with transportation company
Contact phone number
Advance notice required from transportation company prior to delivering equipment (typically 48 hours)
Ship to address:
Other special shipping instructions or requirements
CUSTOMER APPROVAL:
Customer Name:
Signature (*)
Date:
JCI Submittal Package - Terminal Units 4/29/2015 Page 13 of 13
JCI Submittal Package - Terminal Units