Submittal APC Silcon 240kW/240kVA 480V Input / 208V Output ... · Submittal APC Silcon 240kW/240kVA...
Transcript of Submittal APC Silcon 240kW/240kVA 480V Input / 208V Output ... · Submittal APC Silcon 240kW/240kVA...
Submittal APC Silcon 240kW/240kVA 480V Input / 208V Output
UPS SYSTEM
Submitted to: Paul Egger Company: Microsoft Corporation DATE: May 1, 2001
CONTENTS
Section I: Bill of Materials…………... Proposed System Weights and Dimensions Section II: UPS Technical Description… Description of UPS and APC Services Section III: System Installation Data…. System Drawings and Infrastructure Planning Guide Section IV: Literature……………………… UPS, Accessories and Battery Solution
SECTION I
Bill of Materials
Includes:
• System Part Numbers • System Descriptions • System Dimensions • System Weights • Service Offerings
BILL OF MATERIALS
1 Battery solution uses 128 Power Battery TC-1290S batteries. Each battery contains 0.84 US gallons of electrolyte.
2 This service provides 1-year on-site warranty coverage on APC hardware including parts, batteries, labor, and travel expenses.
3 4-hour guaranteed response time to most major metropolitan areas.
Quantity Description Specifications
1 APC Silcon SL240KG UPS 480V, 240kW UPS 74.80”W x 31.50D” x 70.87”H 4432 lbs
1 MISC-BATT Battery Cabinet System1
(Provides 16 minutes of backup at 180kW Load) External Battery Cabinet
90”W x 33”D x 74”H 8708 lbs
1 MISC-SBP Service Bypass Panel 480V Input / 208V Output
44”W x 37”D x 75”H 2725 lbs
1 WSSP1-T11
Essential Power Reliability Package 2 APC Service
1 WUPC
4 Hour Response Upgrade 3 APC Service
1 On-Site Training (Concurrent With Start-Up) APC Service
1 Load Bank APC Service
SECTION II
UPS Technical Description
Includes:
• System Technical Description as reference only. Not necessary for installation. • UPS electrical performance data.
1
AMERICAN POWER CONVERSION DELTA CONVERSION ON-LINE
STATIC UNINTERRUPTIBLE POWER SUPPLY SECTION 16611
Section 1 - GENERAL
1.01 SUMMARY
This specification describes a three-phase, on-line, continuous operation, solid-state uninterruptible power supply (UPS). The UPS shall operate as an active power control system, working in conjunction with the building electrical system to provide power conditioning and on-line power protection for the critical loads.
1.02 SYSTEM DESCRIPTION A. Modes of operation: The UPS shall operate as an on-line system in the following modes:
1. Normal: The main inverter and the delta inverter shall operate in an on-line manner to continuously regulate the power to the critical load. The delta inverter and main inverter also shall derive power from the AC input source and supply DC power to float charge the battery.
2. Battery: Upon failure of the AC input source, the critical load shall continue being supplied
by the main inverter without any switching. The inverter shall obtain its power from the battery. There shall be no interruption in power to the critical load upon failure or restoration of the AC input source.
3. Recharge: Upon restoration of the AC input source, the delta inverter and main inverter
shall simultaneously recharge the battery and regulate the power to the critical load. 4. Bypass: The static bypass switch shall be used for transferring the critical load to input
supply without interruption. Automatic re-transfer to normal operation shall also be accomplished with no interruption in power to the critical load. The static bypass switch shall be capable of manual operation.
5. External maintenance bypass [optional]: The external maintenance bypass switch shall
be used for supplying the load directly from the mains supply, while the UPS is isolated for maintenance.
B. Future expansion: The UPS shall be capable of field-up-grade to allow parallel operation
with additional UPS modules for increased capacity or for redundant operation. The parallel systems shall be capable of operation on a common DC bus or with a separate DC bus for each system module and shall provide proportional load sharing between all available modules. To provide a true fault tolerant control system, any individual UPS module shall be capable of automatically assuming control of the entire system.
2
1.03 STANDARDS
A. Safety:
a. USA/Canada: UL Listed to UL1778 - Standards for Uninterruptible Power Supply Equipment. cUL Listed to CSA
b. Europe: En 50091-1
B. Emission and Immunity:
1. USA/CANADA: FCC Class A 2. Europe: EN 50091-2
C. CE-Mark. 50 Hertz Models
1.04 SUBMITTALS A. Proposal submittals:
1. As bid system bill of materials. 2. Product catalog sheets or equipment brochures. 3. Product guide specifications. 4. System single-line operation diagram. 5. Installation information, including weights and dimensions. 6. Information about terminal locations for power and control connections. 7. Drawings for requested optional accessories.
B. Delivery submittals: Submit 1 of the following:
1. Installation manual which includes instructions for storage, handling, examination, preparation, installation, and start-up of the UPS.
2. User manual which includes UPS operating instructions. 1.05 QUALIFICATIONS A. Manufacturer experience: The manufacturer shall have a minimum 25 years of
experience in the design, manufacture, and testing of UPS systems. B. ISO 9001 Certification: The manufacturer shall be ISO 9001 certified. 1.06 Environmental requirements: A. Storage ambient temperature: -58°F to 131°F (-50°C to 55°C).
3
B. Operating ambient temperature: 32°F to 104°F (0°C to 40°C). (68°F to 77°F (15°C to 25°C), is ideal for batteries). C. Relative humidity: 0 to 95%, non-condensing. 1.07 WARRRANTY A. UPS Module: The UPS manufacturer shall warrant the UPS module against defects in
workmanship and materials for 1 year from the date of retail sale or the date of delivery to the initial user, whichever occurs first, however not exceeding 18 months from date of delivery. The warranty shall include coverage of all internal parts, including internal batteries.
B. External Batteries: For batteries connected to the UPS, the battery manufacturer’s
standard warranty will apply.
Section 2 - PRODUCT 2.01 MANUFACTURER A. Provide American Power Conversion: APC Silcon series system. No substitutes will be
considered. 2.02 SYSTEM CONFIGURATION
Initially provided as a single module, non-redundant system. The UPS shall be field-upgradeable for additional capacity or for redundant operation.
2.03 SYSTEM RATINGS AND OPERATING CHARACTERISTICS A. System continuous rating: 240 kVA and 240 kW at unity power factor. B. Battery capacity: The system must be capable of providing 16 minutes of battery back-up
time at a 180 kW load and 10 minutes of battery back-up at 240 kW load. C. Input voltage rating: 480 volts, three-phase, three or four-wire grounded wye. D. Input voltage range: +15%, -15%. E. Input frequency: 60 Hz +/- 6% (other levels programmable). F. Magnetizing inrush current: NONE, if optional input isolating transformer is installed then
500% of nominal input current for less than one cycle. G. Power walk-in: 0 to 100% over a 10-second period (longer duration programmable). H. Input power factor: Min. 0.93 lagging at 25% load. Min. 0.99 lagging at 100% load.
4
I. Input current distortion: 5% THD maximum at full rated load and nominal input voltage
without additional harmonic filters. J. Output voltage rating: 208 volts, three-phase, three-wire plus ground (with output step-
down transformer). K. Output voltage regulation (at default parameter settings):
1. +/- 1% steady state for a static 100% balanced load. 2. +/- 3% steady state for a static 100% unbalanced load. 3. +/- 5% for a 0 to 100% load step.
L. Output frequency regulation: 60 Hz +/- 0.1 Hz free running (battery operation). Input
synchronized in normal operation. M. Output power factor range: 0.9 leading to 0.8 lagging at rated kVA. The unit’s kVA
capacity shall not require derating for a 1.0 load power factor. N. Output harmonic distortion:
1. 3% THD maximum and 1% any single harmonic for a 100% linear load. 2. 5% THD maximum for a 100% non-linear load (no crest factor limit), UPS 10-60kVA
and 120-500kVA. 3. 6% THD maximum for a 100% non-linear load, (no crest factor limit), UPS 80kVA.
O. Voltage transient response:
1. +/- 3% for a 50% load step. 2. +/- 5% for a 100% load step.
P. Voltage transient recovery time : 50 milliseconds to nominal. Q. Phase displacement:
1. 120 degrees +/- 1 degree for balanced load. 2. 120 degrees +/- 1 degree for 50% unbalanced load. 3. 120 degrees +/- 3 degrees for 100% unbalanced load.
R. Overload capability:
1. 200% for 60 seconds in normal operation. 2. 125% for 10 minutes in normal operation. 3. 150% for 30 seconds in battery operation. 4. 125% continuously in bypass operation. 5. 1000% for 500 milliseconds in bypass operation.
S. Short circuit withstand: The UPS must withstand a bolted-fault short circuit on the output
without damage to the UPS module. T. System AC to AC efficiency: 95.1% at 100% linear load, nominal input voltage, with
batteries fully charged.
5
U. Acoustical noise: dB(A) of noise, typical, measured at 1 meter from the operator surface: 70% load: 100% load: 240kVA: 69 240kVA: 72 2.04 UPS DESIGN AND FABRICATION A. Modular sub-assemblies: For ease of maintenance and service, the UPS must have field-
replaceable modular sub-assemblies. B. Materials: All materials comprising the UPS module shall be new, of current manufacture,
and shall not have been in prior service except as required during factory testing. The UPS module shall contain no PCBs.
C. Inverter/Battery charger:
1. The delta inverter and main inverter shall be a high-speed insulated-gate bi-polar transistor switch module type (IGBT)and shall be controlled by a pulse-width modulation technique to precisely regulate system output voltage and battery charge current.
2. Output current limit: The main inverter shall be capable of supplying overload current
of 150% of the system rating for 30 seconds.
3. Temperature protection: The inverters shall be temperature protected. In case of inverter over temperature, the unit shall activate an alarm and automatically transfer to static bypass operation.
4. Charging operation modes:
a. Float charge: Under nominal operating conditions, the delta inverter and main
inverter shall provide a precisely regulated nominal DC bus voltage (programmable).
b. Boost charge: The delta inverter and main inverter shall provide a boost charge of
2.27 to 2.40 volts per cell (programmable) for a period of 1 to 24 hours (programmable).
5. Battery charging temperature compensation: For protection of the batteries, the unit
shall monitor the temperature of the batteries. To extend battery life, charge voltage must be compensated for changes in battery temperature.
6. Battery charge current limit: The battery charging current limit must be limited to 10% of
nominal DC discharge current (programmable to lower level). D. Static switch:
1. The static switch shall be solid state, rated for continuous duty and be provided with it’s
own dedicated, redundant power supply.
6
2. The static bypass switch shall automatically transfer the critical load to mains supply without interruption after the logic senses one of the following conditions:
a. Inverter overload beyond rating. b. Battery runtime expired and bypass available. c. Inverter failure. d. Battery circuit breaker open. e. Fatal error in control system.
3. The static bypass switch shall automatically retransfer from bypass to the delta inverter
and main inverter, when one of the following conditions occurs:
a. After an instantaneous overload-induced transfer has occurred and the load current has returned to less than 100% of the system rating.
b. The UPS delta inverter and main inverter are active (on).
2.05 BATTERY PLANT A. Battery type: Valve-regulated lead acid battery cells designed for UPS high rate
discharge.
B. Design Lifetime : 10 years C. DC ripple: Max. 0.2C. D. Low battery voltage protection: To prevent total discharge or damage to the battery, the
UPS shall transfer to standby operation when the battery voltage reaches a set minimum voltage level (programmable). If the AC input source has not returned within 10 minutes after low battery shutdown, the UPS shall electronically disconnect DC power from the battery to avoid deep discharge.
E. Battery monitor: A battery monitor function shall be capable of monitoring and defining
battery capacity. It shall be possible to program the unit to perform an automatic battery test every 90 days to test the condition of the battery.
G. Battery manufacturing controls: Each battery cell shall be clearly identified as to cell
type, voltage, and capacity. All cells in the battery have to be factory tested to verify 100% system capacity. The equipment shall be designed and manufactured under a quality assurance program which is controlled and documented by written policies, procedures, or instruction.
H. Battery cabinet assembly: A free-standing, cabinet that complements the appearance of
the UPS and is designed to allow for ease of maintenance. The battery cabinet assembly shall include battery disconnects to provide a positive means of isolating the battery from the rest of the system. The disconnects shall be capable of EPO operation
I. Battery disconnect: For units with external batteries in racks, provide a positive means of
isolating both the battery strings from the rest of the system.
7
2.06 DISPLAY AND CONTROLS A. Display unit: A microprocessor-controlled display unit shall be located at the front of the
UPS cabinet. The display unit shall consist of an alphanumeric display with backlight, an alarm LED, and a touch keypad.
B. UPS status messages: The display unit shall display the following UPS status messages:
1. Normal operation: load power [X]% 2. Battery operation: time [X] minutes. 3. Bypass operation 4. Standby 5. System off
B. Metered parameters: The display unit shall allow the user to display the following metered
parameters:
1. Year, Month, Day, Hour, Minute, Second 2. Source Input AC voltage (line-to-line, three-phase simultaneous) 3. Source Input AC current (line-to-neutral, three-phase
simultaneous) 4. Output AC voltage (line-to-line, three-phase simultaneous) 5. Output AC current (line-to-neutral, three-phase simultaneous) 6. Output frequency 7. Battery voltage 8. Battery current (charge/discharge) 9. Battery temperature
10. Output peak current D. Alarms: The display unit shall allow the user to display a log of all active alarms. A
minimum of 50 alarm conditions shall be monitored. E. Events log: The display unit shall allow the user to display a time- and date-stamped log of
the 250 most recent UPS status and alarm events. F. Controls: The following control or programming functions shall be accomplished with the
display unit:
1. Silence an audible alarm. 2. Set the alphanumeric display language to English or the alternate language. 3. Display or program the time and date. 4. Enable or disable the automatic restart feature. 5. Transfer to or from static bypass operation. 6. Program the unit for economy operation. 7. Program the battery charger. 8. Calculate battery back-up time. 9. Test battery condition on demand.
10. Program the unit to periodically test battery condition. 11. Program voltage and frequency windows. 12. Calibrate metered parameters.
8
13. Enable or disable adaptive slew rate. Set maximum slew rate. 14. Adjust set points for different alarms. 15. Program the remote shutdown contact (enable/disable remote shutdown, polarity,
delay). 16. Set the delay for the common fault contact. 17. Program the unit for soft start for use with a generator.
G. UPS On and Off push buttons: Momentary UPS on and off push buttons shall be
provided in a user-accessible compartment. Upon activation of the on push button, the UPS shall automatically connect the UPS output to the critical load. Upon activation of the off push button, the UPS shall remove power from the critical load.
H. Potential free contacts:
The UPS shall be equipped with two potential free (dry) contacts: 1. Common fault alarm. 2. Battery operation.
Other potential free (dry) contacts shall be available as option. I. Communication interface board: A communication interface board shall provide the
following communication ports, and it shall be possible to use two or more ports simultaneously.
1. RS232 serial port #1. 2. RS232 serial port #2. 3. COM-PORT with the following normally open or normally closed potential free (dry)
contacts:
a. UPS on. b. Static bypass operation. C. Battery operation. d. Battery low.
J. External maintenance bypass: The external maintenance bypass shall supply the load
from the bypass source while the UPS is isolated for maintenance. A UPS input, output, and bypass switch shall be housed in the same cabinet. Each switch must be monitored by the UPS via auxiliary contacts. The maintenance bypass must be housed in a wall mounted or freestanding enclosure that complements the appearance of the UPS.
K. Battery charger temperature compensation: For units with external batteries, the battery
charging temperature compensator shall monitor the temperature in one battery cabinet. L. Network Adapter:
The Ethernet/Token Ring SNMP adapter shall allow one or more network management systems (NMS) to monitor and manage the UPS in TCP/IP network environments. The management information base (MIB) shall be provided in DOS and UNIX tar formats. The SNMP interface adapter shall be connected to the UPS via the RS232 serial port on the standard communication interface board.
M. Unattended Graceful Operating system, Shutdown and Remote monitoring:
9
• Server Shutdown:
1. The UPS, in conjunction with a network interface card, shall be able to gracefully shutdown one or more operating systems during an on battery situation (Ethernet TCP/IP networks).
2. The UPS shall also be able to use an RS232 port to communicate over a DB9
serial cable and gracefully shutdown one or more operating systems during an on battery situation.
• Remote UPS monitoring
Remote UPS monitoring shall be possible in three ways: 1. Web monitoring: Remote UPS monitoring shall be possible via a web browser
such as Internet explorer or Netscape Navigator. 2. RS232 monitoring: Remote UPS monitoring shall be possible via either RS-232 or
contact closure of the UPS.
3. Out of Band Management: Out of Band remote UPS monitoring shall be possible via either RS-232 in conjunction with a Hayes compatible modem.
The UPS manufacturer shall have available software to support graceful shutdown and remote monitoring for the following systems:
a. Microsoft Windows 3.1, 3.11 b. Microsoft Windows 95 c. Microsoft Windows NT d. OS/2 e. Netware 3.12, 4.1, 4.11 f. Apple d. DEC VMS g. DG-UX h. Silicon Graphics i. DEC OSF/1 j. SCO UNIX k. SCO XENIX l. SVR4 m. Interactive n. Unix Ware o. SUN Solaris p. SUN OS q. IBM AIX r. HP-UX
M. Parallel operation: UPS modules shall be capable of running in parallel operation for
increased capacity or for redundant operation. The parallel board shall ensure proper control of parallel units and proper load sharing. One parallel board shall be provided for each unit connected in parallel.
10
2.07 MECHANICAL DESIGN A. Enclosure: The UPS shall be housed in a freestanding enclosure. The enclosure shall be
designed to blend into a computer room environment. The cabinet shall be equipped for fork truck lifting. The UPS cabinet shall be painted with the manufacturers standard color. All service access shall be from the front and top for 10-40kVA. 60kVA – 500kVA models require front access for field wiring terminations.
B. UPS module dimensions: Height x Width x Depth. 240kVA/kW 480V = 70.87 x 74.80 x 31.50 in. (1800 x 1900 x 800 mm);
C. Ventilation: The UPS shall be cooled by forced air and shall be equipped with fan
monitoring circuits. External battery systems shall be cooled by free-air ventilation and convection.
Section 3 – EXECUTION
3.01 FACTORY ASSISTED START-UP [Optional]
If a factory assisted UPS start-up is requested, factory trained service personnel shall perform the following inspections, test procedures, and on-site training:
A. Visual Inspection:
1. Inspect equipment for signs of damage. 2. Verify installation per manufacturer s instructions. 3. Inspect cabinets for foreign objects. 4. Verify correct electrolyte level of flooded cells (if applicable). 5. Inspect battery cases. 6. Inspect batteries for proper polarity. 7. Verify all printed circuit boards are properly configured.
B. Mechanical Inspection:
1. Check all UPS, external maintenance bypass cabinet, and DC disconnect switch
internal control wiring connections. 2. Check all UPS, external maintenance bypass cabinet, and DC disconnect switch
internal power wiring connections. 3. Check all UPS, external maintenance bypass cabinet, and DC disconnect switch
terminal screws, nuts, and/or spade lugs for tightness. C. Electrical Inspection:
1. Check all UPS fuses for continuity. 2. Verify correct input and bypass voltage. 3. Verify correct phase rotation. 4. Verify correct UPS control wiring and terminations. 5. Verify correct termination and voltage of battery strings.
11
6. Verify neutral and ground conductors are properly configured. 7. Inspect external maintenance bypass switch for proper terminations and phasing.
C. Site Testing:
1. Ensure proper system start-up. 2. Verify proper firmware control functions. 3. Verify proper firmware bypass operation. 4. Verify proper maintenance bypass switch operation. 5. Verify system set points. 6. Verify proper inverter operation and regulation circuits. 7. Simulate utility power failure. 8. Verify proper charger operation. 9. Document, sign, and date all test results.
D. On-Site Operational Training: During the factory assisted start-up, operational training for
site personnel shall include key pad operation, LED indicators, start-up and shutdown procedures, maintenance bypass and AC disconnect operation, and alarm information.
3.02 MANUFACTURER FIELD SERVICE A. Worldwide service: The UPS manufacturer shall have a worldwide service organization
available consisting of factory trained field service personnel to perform start-up, preventative maintenance, and service of the UPS system and power equipment. The service organization shall offer a 24 hours a day, 7 days a week, 365 days a year service support.
B. Replacement parts: Parts shall be available through the worldwide service organization
24 hours a day, 7 days a week, 365 days a year. The worldwide service organization shall be capable of shipping parts within 4 working hours or on the next available flight, so that the parts may be delivered to the customer site within 24 hours.
3.03 MAINTENANCE CONTRACTS
A complete offering of preventative and full service maintenance contracts for the UPS system and the battery system shall be available. Contract work shall be performed by factory trained service personnel.
3.04 TRAINING
UPS service training workshop: A UPS service training workshop shall be available from the UPS manufacturer. The service training workshop shall include a combination of lecture and practical instruction with hands-on laboratory sessions. The service training workshop shall include instruction about safety procedures, UPS operational theory, sub-assembly identification and operation, system controls and adjustment, preventative maintenance, and troubleshooting.
Rev.01
SECTION III
System Installation Data
Includes:
• Complete set of system drawings for evaluation and installation of the UPS system.
• Planning matrix to provide minimum requirements to install the APC UPS system. Consult with certified Professional Engineer(s) for site-specific application requirements.
• Planning Guide includes notes making specific references. Familiarization with these note is
important.
Notes:1. Nominal (Nom) Input current based on rated load.
2. Maximum (Max.) Input current based on full battery recharge + nominal load.
3. Recommendation: Input and Output cables run in separate conduits.
4. Suggested Input overcurrent protection based on continuous full load Maximum Input current.
Suggested Load Side Overcurrent Protection based on Nominal current. Breakers sized per
NEC 220-3 and NEC 240-3(b). 80% rated breakers assumed. Trip rating based on NEC 240-6(a)
standard breaker sizes.
5. Nominal battery voltage assumed to be 2.0 volts/cell (lead technology).
6. Recommendation: All cables should be sized in accordance with NEC 210-19 FPN No. 4 branch
feeder voltage drop of 3%. Voltage drop not considered in above chart. Application specific
Input Cable ampacities may vary from above chart. DC Cable Voltage drop not to exceed 1Vdc
in discharge mode.
7. Breaker selection based on Nom input current is acceptable provided battery recharge time is
short. Consult factory for application specific assistance.
8. Grounding conductor ampacities: Refer to NEC Article 250-122 and NEC Table 250-122. Neutral
conductors ampacities: Refer to NEC Article 310-15.
9. All wiring to be in accordance with all applicable national and/or local electrical codes.
10. Minimum access clearance per UPS drawings.
11. Cable entry per installation guide.
12. Heat rejection calculated at nominal full load capacity.
13. All lugs provided by others.
A. Not more than 3 current carrying conductors in raceway assumed; ambi-
ent temperature of 30 ∞C (86 ∞F) assumed. Cable ampacity next size
above Overcurrent Protection provided by others.
B. Temperature rating of conductors: 90 ∞C (194 ∞F). Reference Table 310-16
of NEC, 75 ∞C column, using copper conductors. 75 ∞C (167 ∞F) cable ter-
minal connectors assumed.
C. Reference: NEC handbook 1999. Consult local codes for possible variations.
D. ALL CABLE AND BREAKER RATINGS ARE SUPPLIED AS GUIDELINES
ONLY. THESE GUIDELINES ARE MINIMUM RECOMMENDATIONS ONLY
NOT SUBSTITUTES FOR REVIEW AND COMPLIANCE WITH NEC AND
LOCAL CODES. CONSULT WITH YOUR LICENSED ENGINEER FOR SITE
SPECIFIC APPLICATIONS
Service Bypass Panel
Load (480V, 3 Phase,
3 or 4 Wire)
UPS Module
External Battery System
Field Wiring*
Main Input Breaker*
Service (480V, 3 Phase,
3 or 4 wire Grounded Wye)
* Supplied by others
Field Wiring*
Bypass Input Breaker*
120 120 1 480 60 126.8 140.0 152.5 168.0 1 x 4/0 225AT 2 x 384 127.0 194.8 144.0 200AT 70.87x62.99x31.50 3080 9.35 23.202
160 160 1 480 60 167.5 186.0 201.5 224.0 1 x 350 mcm 300AT 2 x 384 168.8 258.9 192.0 250AT 70.87x62.99x31.50 3080 9.35 25.590
240 240 1 480 60 252.9 280.0 304.2 336.0 1x700mcm or 2x4/0 450AT 2 x 384 252.1 386.7 289.0 400AT 70.87x74.80x31.50 4432 13.46 44.015
320 320 1 480 60 334.4 373.0 402.2 448.0 2 x 350 mcm 600AT 2 x 384 335.4 514.4 385.0 500AT 70.87x74.80x31.50 4432 13.46 49.133
400 400 1 480 60 415.8 460.0 500.1 560.0 2 x 500 mcm 700AT 2 x 384 421.9 647.1 482.0 600AT 70.87x94.49x31.50 5512 13.39 53.910
500 500 1 480 60 519.2 574.0 624.5 700.0 2x700 or 3x350mcm 900AT 2 x 384 525.8 806.4 602.0 800AT 70.87x94.49x31.50 5512 13.39 65.510
Note 1 2 3,6,8,13,A,B,C,D 4,7,9,D 5,13 6 1 4,6,8,11,13,D 10,11 12
kW kVA Pf V Hz Nom. Max. Nom. Max.
PowerRating Source P (kW) I (A) Minimum
Input Cable(per phase)
ServiceOvercurrentProtection1
Vn(V)
Full LoadP (kW)
IMaxDisch (A)
Battery Systemde
AC Input (480V)
In(A)
Load SideOvercurrentProtection 1
DimensionsHxWxD (in)
Weight(lbs)
FloorLoading(lbs/in2)#
Heat RejectionkBTU/hr
AC Output (208V)
1 Provided by others
SECTION IV
Literature
• Includes applicable brochures for reference only.
Enterprise andIndustrialPowerSolutionsSilcon® SeriesDelta Conversion On-line™
power protection for datacenter,facilities, and other mission-critical applications
BasicProtection
99.999%Availability
10-500kVA208/480V
Table of contents
Features and benefits 4
Customer testimonials 6
Accessories 8
Services 9
Specifications 10
HIGH AVAILABILITY
• Parallel for redundancy full kW range
• (kVA=kW) n+1, n+2
• Less stress on components
• Fewer components needed when
paralleling four or less units
• Maintenance bypass switch
• Dual inputs*
*On select models
INCREASED MANAGEABILITY
• SmartSlot - Built-in accessory slot
• Software configurable features
• SNMP Ready for Manageability
• Intelligent Battery Management
• PowerChute Network monitoring
WORLD-CLASS SERVICE
• Turn key solution - APC Service
• Consultants
• 7x24 Service
• 4 Global call centers
• 4 hour response available
• Award-winning customer service
WARRANTY
• 1 year warranty
• Parts and Labor
2
Introduction
APC delivers the new wave of 3-phase power protection
What makes a hot technology “hot”? In the eyes of an enterprise customer, “hot”
means a technology that’s convenient and easy to use, and efficient and trouble-
free to operate. A “hot” product is manufactured of high quality materials and as
a result of its superior design, inherently carries a low cost of ownership.
All of these characteristics define APC’s Silcon® Series Delta Conversion On-line™
machines. The unique architecture of the APC Silcon Series introduces a new cat-
egory of power protection: the highly efficient 3-phase UPS.
Customers who install APC Silcon Series systems immediately begin to realize
benefits in the form of dramatic reductions in energy consumption costs, instal-
lation and wiring costs, air conditioning costs, harmonic distortion costs and
maintenance costs. More importantly, the APC Silcon Series units excel at their
primary function: to supply clean 3-phase power to critical applications, datacen-
ters and facilities regardless of power failures, sags, surges, brownouts, line
noise, high voltage spikes, frequency variations and switching transients.
A perfect fit for critical high availability applications
High availability of systems is today a responsibility shared by both information
systems departments and facilities departments. Industry statistics show unan-
ticipated power events to be one of the main causes of unscheduled downtime.
The unique design of the APC Silcon Series machines offer an elegant and inex-
pensive solution to customers who seek the peace of mind of redundant UPS sys-
tems. APC Silcon Series units configured in redundant mode can help eliminate
the weak link of a substandard and unpredictable power supply.
Backed by world-class service and support
The APC Silcon Series is designed to proactively identify and correct power prob-
lems to prevent downtime. APC’s Global Services Organization will supplement
your Silcon Series power protection solution with a world-wide network of
trained personnel and automated support systems designed to quickly diagnose
and resolve problems. A wide variety of installation, implementation and main-
tenance packages are available to meet any customer requirement.
3
25 Years of 3-phase ExperienceWith the purchase of Silcon Power
Electronics in 1998, APC acquired a supe-
rior 3-phase technology 25 years in the
making. A manufacturer of traditional
double-conversion 3-phase UPSs in the
early seventies, Silcon evolved to a sec-
ond generation single conversion archi-
tecture and then, in the late nineties,
developed an even more efficient third
generation Delta Conversion On-line™
technology. Today customers require a
solution that combines the best of double
conversion without the unpleasant and
costly side effects of input harmonics.
This makes APC Silcon Series your new
choice for a low cost/high efficiency
3-phase solution.
Features and benefits
Additional savingsDue to the high efficiencyand the power factor corrected input, the SilconSeries requires smallerinstallation cables andfuses, and smaller air condition systems.
Silcon Series
Traditional UPS system
AvailabilityCustomers can now enjoy the benefits of redundant UPSs by configuring and installing multiple 20kVAunits. For example, if kVA requirements are high, up to 9 500kVA UPSs can be paralleled to supply the loadwith the energy it needs. Up to four units can be configured in parallel mode without requiring the instal-lation of expensive external static switches.
Advanced power managementSilcon’s intelligent control can be programmed to maximize the overall efficiency of parallel DeltaConversion On-line systems. By designating as “active” only the systems needed to supply the load, theother systems can be held in “stand by” mode, ready to start up without interruption when required.Furthermore, to reduce stress and improve reliability, the load can be switched between the parallel sys-tems in preprogrammed sequences.
Lower cost of ownershipThe Silcon Series is higher in effi-ciency that other online technolo-gies. The Delta Conversion On-line units simply do not consumelarge quantities of energy andalso produce much less heat.Customers need not oversize anair conditioning unit to compen-sate for the heat loss which tra-ditional UPSs generate.
Lower installation costThe Silcon Delta Conversion On-line UPS has a power factor cor-rected input, ensuring that theinput power factor is always one,regardless of load and utility volt-age. A power factor of one mini-mizes installation costs by requiringsmaller cables and smaller fuses.
Total Savings in US Dollars = $18,730 Per Year
1 year Energy price = .08/kWh240kW load
Total Costs
$30,504
$11,773
$22,935
$8,852$7,569
$2,921
UPS Operating Costs Air ConditioningOperating Costs
Legacy Double ConversionOn-line UPS
Silcon Delta ConversionOn-line UPS
4
100
90
80
20
25 50 75 100
Efficiency %
Load
10
For more information about Silcon Series, go to www.apcc.com
Efficiency, environmental design andindustry-leading technology makethe Silcon Series the clear choice forenterprise power protection.
1.0
0.9
0.8
0.3
25 50 75 100
Input power factor
Load (kW)0.1
0.2
Built-in power factor correctionmaintains a constant level of one,which minimizes installation costs.
Complient with power supplies, for the present and the future (kVA = kW)Over the past three years, more and more computer manufacturers have built Power Factor Corrected (PFC)power supplies into their servers. In order to avoid unnecessary wear and tear on computer components, theVolt-Amps (VA) requirements of all the computers that make up the load need to equal the Watts (W) capacityof the UPS.
The Silcon Series units are PFC compliant. Without derating the unit, double conversion 3-phase UPS systemsare not PFC compliant. Therefore, as more and more PFC computers enter into your datacenter, the probabilitybecomes greater that the legacy double conversion 3-phase UPSs becomes overloaded. With Silcon Series units,this problem is eliminated because the kVA rating of the Silcon Series unit equals the kW rating.
5
Utility input
Utility voltage Utility current
Load output
Double Conversion On-line APC Delta Conversion On-line
Utility voltage Utility current
Utility input Load output
Eliminates wear and tear on electrical infrastructureUtilities and power distributors are creating standards to limit the harmonic distortion produced by users.Violating these standards can be very costly. Many double conversion 3-phase systems produce a level ofharmonic distortion high enough to negatively impact the utility and its customers. To remedy the situa-tion, customer are obliged to install large expensive filters. These filters further diminish the overall effi-ciency of the double conversion machine. The Silcon Delta Conversion On-line technology, which main-tains a sinusoidal utility current, eliminates this 3-phase double conversion topology problem.
For more information about Silcon Series, go to www.apcc.com
Delta Conversion On-line™ : The ultimate UPS
IT professional:Over the years, you have come to recog-
nize APC as a reliability, manageability,
and technology leader. As your require-
ments evolve and your business expands,
APC is positioned to grow with you. APC
power protection is available today from
laptop to datacenter to industrial facility.
6
APC 3-phase:Solutions for both IT . . .
Clear Channel Communicationsvalues APC Silcon® reliability,service and support“The knowledge and support of Sterling Oakes Services,
our APC Power Specialist, is a key to our uptime success.”
- Phil Walter, Data Center ManagerClear Channel Communications
“Our current datacenter supports the corporate financial pack-
ages, Web site hosting servers, E-mail servers and ad servers
for our radio station Web sites. Our ad servers distribute ban-
ner ads to our radio station Web sites and track the revenue
from those ads. Downtime is not an option for us.
We contacted our APC Power Specialist, Jeffrey Oakes of
Sterling Oakes Services, in Houston, Texas (www.sterlin-
goakes.com). After recommending the APC Silcon Series, Jeff
then helped us to acquire and install the unit to support our
datacenter. This highly efficient 3-phase solution is just what
we needed. It provides us with an extremely clean, cool
power source within a very small footprint. We had already
installed a 20kW Generator and Automatic Transfer Switch
that feeds two 2.5 ton single phase air conditioning units and
approximately 11kW worth of critical load. The unique design
topology of the APC Silcon unit presented us with a number
of advantages. First, the unity power factor of the box elimi-
nated the possibility of harmonic distortion impacting our load
or back feeding on the utility line. Second, the high efficiency
of the machine could help us to significantly cut operational
costs. And third, the APC Silcon Series UPS is the only UPS
that could reliably support our load in this type of application.
In the near future, we will be doubling the size of our server
room. We are looking forward to purchasing two more APC
Silcon Seriess. As we upgrade our radio, TV and outdoor
sites, we will be looking for additional power protection solu-
tions. We are confident that this investment will provide us
with the clean reliable power we require as we go forward
into the 21st Century.”
For more information about Silcon Series, go to www.apcc.com
Facilities professional:For over 30 years, your 3-phase power
protection choices have been limited. Low
efficiency and high heat generated by
double conversion have increased your
operating costs. Delta Conversion On-
line™ technology offers you a reliable,
efficient and low cost alternative.
7
Boston Edison lauds APC SilconSeries service and support“I now have peace of mind knowing that our facility is
protected by the professionals from APC‘s Global
Services Group and their APC Silcon Series.”
- Franco Pasquale, Simulator Team LeaderBoston Edison, Chiltonville Training Center
“Boston Edison is the leading electric utility company in eastern
Massachusetts. We serve a customer base of 650,000 indi-
viduals throughout 40 cities and towns including Boston.
Boston Edison’s annual revenues exceed $1.6 billion. As
Simulator Team Leader at Boston Edison’s Chiltonville Training
Center, one of my responsibilities is to manage the operation
of our nuclear power plant control room simulator. We have
been an APC customer for a number of years. Our facility has
a number of Smart-UPS® as well as Matrix-UPS™ devices.
“Historically, power conditions at our site have been marginal,
and, ironically, Boston Edison does not provide power to the
site. Power fluctuations have caused a number of equipment
failures in the control room simulator, resulting in downtime to
effectuate repairs.
“APC sent teams of experts from the APC Global Services
Group on two separate occasions in order to take measure-
ments and verify total power used by the system. The profes-
sionalism and thoroughness exhibited by the representatives
of APC’s Global Services Group in explaining all facets of the
transition sold me on the APC solution. Power Associates, Inc.
determined the extent of the work to be performed and began
to estimate the cost in dollars, as well as the time required to
perform the ‘cut-over’ to full UPS power.
“Today, the APC Silcon Series supports the entire simulator
complex, including file servers and mini computers that are
used to mirror the operation of Boston Edison’s Pilgrim
Nuclear Power Plant control room. The training facility can
simulate any condition, real or imagined, and present it to their
students for evaluation and solution. I now have peace of
mind knowing that our facility is protected by the profession-
als from APC’s Global Services Group and the APC Silcon
Series.”
For more information about Silcon Series, go to www.apcc.com
. . . and facilities.
Power Accessories
External Battery SolutionsExternal Battery Solutions are available when runtimes of 15 minutes or greater are required. Partnumbers are assigned to the runtime which you need thereby eliminating any lengthy calculations.
External Service By-pass PanelThe External Service By-pass Panel allows for the performance of proactive maintenance on theUPS without dropping the load. This prevents unwanted interruptions and maintenance techni-cians avoid the risk of electric shock.
Management Accessories
PowerChute® Network ShutdownPowerChute Network Shutdown allows for safe shutdown of servers, notification of end-users,running command files and logging of events. This shutdown software is available for a variety ofoperating systems including Windows NT, NetWare, HP-UX, Linux, Solaris, and others.
Web/SNMP Management CardThe Silcon Web/SNMP Card allows monitoring of the Silcon Delta Conversion On-Line UPS fromany Web browser. The Silcon Delta Conversion On-Line UPS can also be monitored via Telnet,SNMP (NMS Management Scheme), and the Web.
MasterSwitch™
The MasterSwitch network power controller can easily reboot remote servers, internetworkingequipment, or banks of modems to prevent on-site service calls. MasterSwitch allows remote con-trol of up to eight (8) independent power channels.
Out-of-band Management CardThe Out-of-band Management Card provides remote access to detailed UPS information, gives youremote paging upon power events, and remote safe reboot of attached equipment via user-suppliedmodem. Users have the ability to communicate with the UPS even during power outages or whenthe server is down. The out-of-band management card allows remote power management via seri-al or modem link.
Environmental Monitoring CardThe Environmental Monitoring Card will remotely monitor temperature, humidity, and other envi-ronmental conditions via PowerChute plus software, Out-of-band management card, Web/SNMPManagement Card, or SNMP Agents.
Accessories
8
PowerChute Network Shutdowngraphical user interface
APC Web SNMP Management Card
For more information about Silcon Series, go to www.apcc.com
Out-of-band Management Card
Environmental Monitoring Card
External Service By-pass Panel
APC MasterSwitch
Our APC Power Quality Engineers, Power Specialists, High PowerPartners, and Professional Services personnel guarantee complete sat-isfaction with any APC service. When it comes to power management,you deserve the Legendary Reliability™ and peace of mind that only APCGlobal Services can provide.
Start-UP ServiceAPC’s Start-UP Service provides APC authorized service personnel onsite to confirm proper wiring of installation, power-up the APC hard-ware, and system training. Labor and travel expenses are included inthis program. Standard service is offered during normal business hours,excluding holidays.
Essential Power Reliability Package This offering features a baseline maintenance package for APC’s 3-phase UPS systems. The package includes Start-Up Service, one yearnext business day on-site repair service including parts, batteries (inter-nal only,) labor, and travel expenses. It also provides a preventativemaintenance visit and 7x24 telephone technical support, with one hourtelephone response time.
Premium Power Reliability Package This offering provides customers with a turnkey solution for criticalcomputing environments. The package provides all of the benefits ofthe Essential Reliability Package, plus Site Positioning Services forproper delivery and placement of your UPS into your environment andInstallation Consulting Services to provide guidance on the electricalwiring and installation of your system.
The total offering includes Start-UP Service, one yearnext business day on-site repair service includingparts, batteries (internal only), travel expenses, a pre-ventative maintenance visit, Site Positioning Services,Installation Consulting Services, and 7x24 telephonetechnical support with one hour telephone responsetime. For the higher availability systems, a four-hourresponse option is also available as an upgrade to thisservice.
Enterprise Power Reliability PackageThis package features the highest level service andsupport available from APC. The Enterprise PowerReliability Package includes all of the features of thePremium Power Reliability Package, plus an initialPowerAudit®, four hour response on-site repair serviceand a yearly PowerAudit Review. The EnterpriseReliability Package is tailored for mission critical envi-ronments where maximum uptime is required. This pro-gram provides one year four hour response on-siterepair service including all parts, batteries (internal only),labor and travel expenses. Under the Enterprise PowerReliability Package, telephone technical support, Start-Up services and Preventative Maintenance services areprovided on a 7x24 basis. For the higher availability sys-tems, a four-hour response option is also available asan upgrade to this service.
Annual Maintenance ProgramFor customers with APC Silcon 3-phase systems installed, it is recom-mended that an annual maintenance service contract be considered.APC’s service policy is to prevent potential problems from occurring.The 3-phase systems contain components and parts which will wearout over time. It is important that only specially trained staff, who arefamiliar with the inner workings of the APC Silcon 3-phase machines dothe maintenance work. These parts must be checked regularly andreplaced when appropriate. Regular maintenance helps you to avoidunnecessary downtime.
Under the Annual Maintenance Program APC guarantees next busi-ness day on-site repair service and delivery of spare parts for all APCUPS and Power Array™ systems, a thorough annual inspection and testof the system, and 7 x 24 telephone technical support. This servicecontract assures that your APC hardware solution is always in workingcondition to protect your critical applications against power failure.Contract is renewed yearly and includes all parts, batteries (internalonly), labor and travel expenses.
Remote Monitoring ServiceAPC’s Remote Monitoring Service is an outsourced remote monitoringsolution that proactively monitors UPSs and the surrounding environment7 x 24 to enhance high availability in networking and facilities environ-ments. With the ability to uniquely profile each customer, APC is able tospontaneously react during UPS events in the same manner that yoursystems personnel would.
Services
9For more information about Silcon Series, go to www.apcc.com
7 x 24 Global Support
For more information about Silcon Series, go to www.apcc.com
SpecificationsGeneral Specifications
Static bypass switch Built-in
Communication Interface Built-in
Backfeed protection Built-in
Ambient temperature 32-104˚F (Above 77˚F the battery lifetime is reduced)
Humidity Max 95%, non-condensing
Protection class NEMA 1
Safety UL 1778, EN50091-1
Emission and Immunity EN50091-2
Advanced Batt. Monitoring Programmable
Auto restart Programmable
Options Parallel operation board, NEMA 12 Enclosure, Terminals for external batteries, Alarm relay board
Power Accessories Isolation transformer, Service bypass panel (line up and match), Remote display, External battery cubicle (lineup and match) ,Static Switch
Management Accessories PowerChute Network Shutdown, Web/SNMP Card, MasterSwitch™, Environmental Monitoring Card, Out-of-band Management Card.
Please note: General specifications and Input and output specifications are identical for both 208V and 480V Silcon units.
Input and Output Specifications
Input voltage 3 x 208V or 3 x 480V
Input operation tolerance ±15%
Input bypass tolerance ±10% (standard), ±4, 6, 8% (programmable)
Input frequency 60Hz (standard), ±0.5-8% (programmable)
Input PF load 25% min. 0.97, load 100% min. 0.99
Output voltage 3x208V, 3 x 480V
Voltage tolerance ±1% static, sym. load, ±3% static, asym. load, ±5% 1-100% load step
Voltage distortion max 3%, linear load, max 5%, non-linear load
Load power factor 0.9 lead to 0.8 lag
Output frequency 60Hz (mains synchronized), ±0.1% free running
Overload capacity Mains operation 200% - 60 secs; Mains operation 125% - 10 mins.; Battery operation 150% - 30 secs.; Bypass operation125% - cont., 1000% - 500ms
1Unit with one internal battery (add 385 lbs. to total weight)
2Unit with two internal batteries (add 770 lbs. to total weight).
3Weights given for units without internal batteries.
10
208V Solutions
Type SL10KF SL15KF SL20KF SL30KF SL40KF SL60KF SL80KFSL10KFB11 SL15KFB11 SL20KFB11 SL30KFB22 SL40KFB22
SL15KFB22 SL20KFB22
Output power 10kW/10kVA 15kW/15kVA 20kW/20kVA 30kW/30kVA 40kW/40kVA 60kW/60kVA 80kW/80kVA
Full load output current 27.8A 41.6A 55.5A 83.3A 110.0A 166.5A 222.1A
Max input current 37.5A 56.3A 75.0A 113.0A 150.0A 225.0A 300.0A
Efficiency AC to AC: 100% load 93.6% 93.6% 94.5% 94.7% 95.0% 95.0% 95.1%50% load 91.9% 90.5% 92.0% 92.6% 93.8% 94.0% 94.8%
Heat dissipation, nominal load 2388 BTU 3412 BTU 4094 BTU 5800 BTU 7165 BTU 10918 BTU 13989 BTU
Audible noise 70-100% load 55/55dB(A) 55/65dB(A) 55/65dB(A) 55/65dB(A) 55/65dB(A) 65/75dB(A) 65/75dB(A)
Height 55.12 in. 55.12 in. 55.12 in. 55.12 in. 55.12 in. 59.06 in. 59.06 in.
Width 23.62 in. 39.37 in. 39.37 in. 39.37 in. 39.37 in. 39.37 in. 39.37 in.
Depth 31.50 in. 31.50 in. 31.50 in. 31.50 in. 31.50 in. 31.50 in. 31.50 in.
Weight3 803 lbs 902 lbs. 902 lbs. 1430 lbs. 1430 lbs. 1165 lbs. 1165 lbs.
480V Solutions—10kW/10kVA - 80kW/80kVA
Type SL10KG SL15KG SL20KG SL30KG SL40KG SL60KG SL80KGSL10KGB11 SL15KGB11 SL20KGB11 SL30KGB22 SL40KGB22
SL15KGB22
Output power 10kW/10kVA 15kW/15kVA 20kW/20kVA 30kW/30kVA 40kW/40kVA 60kW/60kVA 80kW/80kVA
Full load output current 12.0A 18.0A 24.1A 36.1A 48.1A 72.2A 96.2A
Max input current 15.6A 23.5A 31.3A 47.0A 62,5A 94.0A 125.0A
Efficiency AC to AC 100% load 94.3% 94.3% 94.9% 94.3% 95.0% 94.0% 95.0%
50% load 91.3% 92.0% 93.3% 91.5% 92.9% 90.3% 92.3%
Heat dissipation, nominal load 2047 BTU 3071 BTU 3753 BTU 6142 BTU 7165 BTU 12966 BTU 14330 BTU
Audible noise 70-100% load 55/55dB(A) 55/65dB(A) 55/65dB(A) 55/65dB(A) 55/65dB(A) 65/75dB(A) 65/75dB(A)
Height 55.12 in. 55.12 in. 55.12 in. 55.12 in. 55.12 in. 55.12 in. 55.12 in.
Width 23.62 in. 23.62 in. 23.62 in. 39.37 in. 39.37 in. 39.37 in. 39.37 in.
Depth 31.50 in. 31.50 in. 31.50 in. 31.50 in. 31.50 in. 31.50 in. 31.50 in.
Weight3 869 lbs. 990 lbs. 990 lbs. 1606 lbs. 1606 lbs. 1122 lbs. 1166 lbs.
11For more information about Silcon Series, go to www.apcc.com
480V Solutions—120kW/120kVA - 500kW/500kVA
Type SL120KG SL160KG SL240KG SL320KG SL400KG SL500KG
Output power 120kW/120kVA 160kW/160kVA 240kW/240kVA 320kW/320kVA 400kW/400kVA 500kW/500kVA
Full load output current 144A 192A 289A 385A 481A 601A
Max input current 188A 250A 375A 500A 625A 782A
Audible Noise (nominal max.) 72dB(A) 72dB(A) 73dB(A) 73dB(A) 78dB(A) 78dB(A)
Efficiency AC to AC typically at nominal load 94.6% 95.5% 94.9% 95.7% 96.2% 96.3%
Heat dissipation, nominal load 23202 BTU 25590 BTU 44015 BTU 49133 BTU 53910 BTU 65510 BTU
Height 70.9 in. 70.9 in. 70.9 in. 70.9 in. 70.9 in. 70.9 in.
Width 63 in. 63 in. 74.8 in. 74.8 in. 94.5 in. 94.5 in.
Depth 31.5 in. 31.5 in. 31.5 in. 31.5 in. 31.5 in. 31.5 in.
Weight 3080 lbs. 3080 lbs. 4432 lbs. 4432 lbs. 5512 lbs. 5512 lbs.
APC Service Bypass Panel Quick Reference Guide - Single Mains Input
UPS Configs. Cap. x1 Cap. x2 Cap. x3 Cap. x4 Red. x2 Red. x3 Red. x4
SL10KF SL0901482 - - - SL091485 - -
SL10KG SL0901482 - - - SL091485 - -
SL15KF SL0901483 - - - SL091486 - -
SL15KG SL0901482 - - - SL091485 - -
SL20KF SL0901483 - - - SL091486 - -
SL20KG SL0901482 - - - SL091485 - -
SL30KF SL0901484 - - - SL091487 - -
SL30KG SL0901483 - - - SL091486 - -
SL40KF SL0901484 - - - SL091487 - -
SL40KG SL0901483 - - - SL091486 - -
SL60KF SL0901625 - - - - - -
SL60KG SL0901484 - - - SL091487 - -
SL80KF SL0901625 - - - - - -
SL80KG SL0901484 - - - SL091487 - -
SL120KG SBP-0120C1G10 SBP-0120C2G10 SBP-0120C3G10 SBP-0120C4G10 SBP-0120R2G10 SBP-0120R3G10 SBP-0120R4G10
SL160KG SBP-0160C1G10 SBP-0160C2G10 SBP-0160C3G10 SBP-0160C4G10 SBP-0160R2G10 SBP-0160R3G10 SBP-0160R4G10
SL240KG SBP-0240C1G10 SBP-0240C2G10 SBP-0240C3G10 SBP-0240C4G10 SBP-0240R2G10 SBP-0240R3G10 SBP-0240R4G10
SL320KG SBP-0320C1G10 SBP-0320C2G10 SBP-0320C3G10 SBP-0320C4G10 SBP-0320R2G10 SBP-0320R3G10 SBP-0320R4G10
SL400KG SBP-0400C1G10 SBP-0400C2G10 SBP-0400C3G10 SBP-0400C4G10 SBP-0420R2G10 SBP-0420R3G10 SBP-0420R4G10
SL500KG SBP-0500C1G10 SBP-0500C2G10 SBP-0500C3G10 SBP-0500C4G10 SBP-0500R2G10 SBP-0500R3G10 SBP-0500R4G10
APC Service Bypass Panel Quick Reference Guide -Dual Mains Input
UPS Configs. Cap. x1 Cap. x2 Cap. x3 Cap. x4 Red. x2 Red. x3 Red. x4
SL120KG SBP-0120C1G20 SBP-0120C2G20 SBP-0120C3G20 SBP-0120C4G20 SBP-0120R2G20 SBP-0120R3G20 SBP-0120R4G20
SL160KG SBP-0160C1G120 SBP-0160C2G20 SBP-0160C3G20 SBP-0160C4G20 SBP-0160R2G20 SBP-0160R3G20 SBP-0160R4G20
SL240KG SBP-0240C1G20 SBP-0240C2G20 SBP-0240C3G20 SBP-0240C4G20 SBP-0240R2G20 SBP-0240R3G20 SBP-0240R4G20
SL320KG SBP-0320C1G20 SBP-0320C2G20 SBP-0320C3G20 SBP-0320C4G20 SBP-0320R2G20 SBP-0320R3G20 SBP-0320R4G20
SL400KG SBP-0400C1G20 SBP-0400C2G20 SBP-0400C3G20 SBP-0400C4G20 SBP-0420R2G20 SBP-0420R3G20 SBP-0420R4G20
SL500KG SBP-0500C1G20 SBP-0500C2G20 SBP-0500C3G20 SBP-0500C4G20 SBP-0500R2G20 SBP-0500R3G20 SBP-0500R4G20
Please note: 10-80kW systems include parallel board; 120-500kW systems include parallel board and relay board.
Go the Web now for more informationabout the Silcon Series atwww.apcc.com/products/silcon_dp300efor in-depth information, Silcon video,and Installation and User guides (avail-able for download in pdf format.)
©2000 APC. All rights reserved. All APC trademarks are property of American Power Conversion. Other trademarks are property of their respective owners. Specifications are subject to change without notice. PART# 996-1318FBSI Certification 7OD0005US rev.03
ForSilcon information pleasecall 1-877-4-SILCONTel: 800-800-4APC - US & CanadaTel: 401-789-0204- World wide
APC Corporate132 Fairgrounds RoadWest Kingston, RI 02892Call: 800-800-4APCPowerFax: 800-347-FAXX
APC EuropeAPC IrelandBallybrit Business ParkGalway, IrelandCall: (+35)391 702000Fax: (+35)391 756909
APC Asia PacificAPC AustraliaLevel 27 Northpoint100 Miller StreetNorth Sydney, NSW2060Call: +61-2-9955-9366Fax: +61-2-9955-2844
Visit: www.apcc.comE-mail: [email protected] Support: support.apcc.comCall: 401-789-0204Fax: 401-789-3710
APC’s qualitysystem is certified byISO 9002 standards
APC Battery Cabinet Quick Reference Guide
Runtime Options 5-7 min. 8-14 min. 15-19 min. 20-29 min. 30-39 min. 40-49 min. 50-75 min. >75 min.
SL10KF - - - - - BDP2010J41-1CO BDP2010J70-1CO BDP20102H-1CO
SL10KG - - - - - - - BDP2010J2H-1CO
SL15KF - - BDP2015J24-1CO - BDP2015J41-1CO BDP2015J63-1CO -
SL15KG - - - - - - BDP4015J62-1CO -
SL20KF - - BDP2020J15-1CO - BDP2020J28-1CO BDP2020J47-1CO BDP2020J72-1CO -
SL20KG - - - - - BDP4020J42-1CO BDP4020J72-1CO -
SL30KF BDP2030J8-1CO - BDP2030J16-1CO BDP2030J27-1CO - BDP2030J44-1CO BDP2030J61-1CO -
SL30KG - - - BDP4030J24-1CO - BDP4030J40-1CO BDP4030J68-1CO -
SL40KF - BDP2040J10-1CO BDP2040J18-1CO - BDP2040J30-1CO BDP2040J44-1CO BDP2040J59-1CO -
SL40KG - - BDP4040J15-1CO BDP4040J28-1CO - BDP4040J46-1CO BDP4040J73-2CO -
SL60KF - BDP2060J8-1CO BDP2060J16-1CO BDP2060J25-1CO BDP2060J36-1CO - BDP2060J59-2CO -
SL60KG - BDP4060J8-1CO BDP4060J15-1CO BDP4060J26-1CO - BDP4060J42-2CO BDP4060J60-2CO -
SL80KF - BDP2080J9-1CO BDP2080J17-1CO BDP2080J22-1CO BDP2080J36-2CO BDP2080J43-2CO BDP2080J59-2CO -
SL80KG - BDP4080J10-1CO BDP4080J17-1CO BDP4080J29-2CO BDP4080J35-2CO BDP4080J42-2CO BDP4080J59-2CO -
SL120KG BDP4120J5-1CO BDP4120J8-1CO BDP4120J15-2CO BDP4120J25-2CO BDP4120J35-2CO BDP4120J44-4CO - -
SL160KG BDP4160J5-1CO BDP4160J9-2CO BDP4160J16-2CO BDP4160J22-2CO BDP4160J42-4CO - - -
SL240KG BDP4240J6-2CO BDP4240J9-2CO BDP4240J16-4CO BDP4240J25-4CO BDP4240J35-4CO - - -
SL320KG BDP4320J5-2CO BDP4320J13-4CO BDP4320J22-4CO BDP4320J29-6CO - - - -
SL400KG BDP4400J7-4CO BDP4400J12-4CO BDP4400J15-4CO BDP4400J22-6CO BDP4400J30-6CO - - -
SL500KG BDP4500J5-4CO BDP4500J8-4CO BDP4500J15-6CO BDP4500J20-6CO BDP4500J33-8CO - - -
High Availability on WheelsFacilities and consulting electrical engineers can now viewthe latest in UPS technology without leaving their offices.
The APC Mobile Availability Center (MAC) is a traveling train-ing and demonstration laboratory designed to assist IT andfacilities professionals in identifying appropriate solutions toincrease power availability. The APC MAC houses a broadselection of APC power protection and management solutionsincluding APC's Silcon™ DP300E series, Symmetra® PowerArray™, the newest Smart-UPS® solutions, as well as a vari-ety of accessories and UPS management software, all whichhelp increase the availability of essential business processes.
The APC MAC is equipped to seat visitors in a classroom stylesetting.An APC application engineer will conduct presenta-tions and lead attendees in question and answer sessions.The APC MAC presentation includes a number of productdemonstrations focused on promoting power and systemavailability of datacenters and facilities. This traveling roadshow reinforces APC's commitment to partner with its cus-tomers to help ensure that the total solution effectivelyaddresses the customer's availability needs.
1.60 2810 2084 1608 1316 975 782 720 659 574 418
1.67 2714 2045 1590 1304 968 777 716 656 571 417
1.70 2673 2030 1580 1296 964 775 715 655 570 414
1.75 2534 1911 1523 1271 955 768 708 649 565 413
– Gas recombination greater than 99%.– Operates at a low internal pressure.– Never needs watering, minimal maintenance.– 99.7% pure lead calcium grids.– Shock absorbent thick wall construction.– Cold forged non-porous terminal bushings,
eliminate post leakage.– Thermally welded case to cover bond,
eliminates both acid and electrical leaks.– Over-sized, through the partition inter-cell
welds provide low resistance connections,with minimal power loss.
– Each cell has a low pressure safety release venting system, recognized per U.L. 924.
– Measured high vacuum acid fill, reduces electrical variability between cells.
– 100% recyclable materials.
– The TC-1290S battery has a flame retardant polypropylene case and cover compliant with UL 1778; with an oxygen index greater than 28%.
– Terminal covers and custom inter-connecting battery cables.
S Y S T E M
– Surface transport. Classified as non-hazardous material as relates to DOT-CFR Title 49 part 171-189.
– Water transport. Per IMDG amendment 27.– Air transport. Complies with IATA / ICAO, special provision A67.
Cells per unit 6Nominal voltage 12Maximum discharge current 500 ampsShort circuit current 3209 ampsImpedance @ 77ºF 25ºC 4.30 milliohmsWeight lbs / kgs 60.6 / 27.5Electrolyte (S.G.) 1.300Capacity @ 77°F 75.8 AH (20 hrs)(25°C) to 1.75 V.P.C. 68.6 AH (8 hrs)Ideal operating +68ºF (20ºC) totemperature range +77ºF (25ºC)Extended operating Discharge: -40ºF (-40ºC) totemperature range +140ºF (60ºC)
Charge: -40ºF (-40ºC) to+122ºF (50ºC)
Float Voltage 13.5 to 13.8 @ 77ºF (25ºC)Maximum C4 amperes at 100% dischargecharging current Unlimited at partial discharge.AC ripple from charging source 1.5% peak to peak of float
charge voltageStorage 6 months at 77ºF (25ºC)
U . S . A . H E A D Q U A R T E R S 2 5 M c l e a n B l v d . , P a t e r s o n , N J 0 7 5 1 4 - 1 5 0 7 , P h o n e : ( 9 7 3 ) 5 2 3 - 8 6 3 0 , F a x : ( 9 7 3 ) 5 2 3 - 3 0 2 3C A N A D I A N H E A D Q U A RT E R S 7 7 0 , A v e . T h o m a s , I b e r v i l l e ( Q u é b e c ) J 2 X 5 E 7 , P h o n e : ( 4 5 0 ) 3 4 6 - 3 2 7 3 , F a x : ( 4 5 0 ) 3 4 6 - 8 0 0 3EUROPEAN HEADQUARTERS POWER BATTERIES LTD. Premier Way,Abbey Park Industrial Estate, Romsey, Hampshire, SO51 9AQ, Phone: +44(0) 1794 835900, Fax: +44(0) 1794 835910
Lead Pb, PbO2, PbSO4 7439-92-1 65-75 % 0.050 mg/m3 <500 mg/kg <20 mg/m3 n/a
Sulfuric Acid 7664-93-9 17-30 % 1 mg/m3 2.140 kg/kg 18 mg/m3 135 mg/kg
Lead 11.34 gm/cm3 621.5 0F none none Silver-gray metal
Lead Sulfate 06.20 gm/cm3 2133 0F .43 mg/l none White powder
Lead Dioxide 9.375 gm/cm3 d 554 0F none none Brown powder
Sulfuric Acid 1.290 gm/cm3 1 235 0F 100% none Clear liquid
Lead none none Use “ABC” Type fire extinguisher for battery fires
Sulfuric acid none none
Hydrogen <00F 4%-74.2% POWER batteries can emit hydrogen only if overcharged (float voltage 2.40 VPC or greater)
The toxic effects of lead are accumulative, and slow to appear. It affects the kidneys, reproductive, and central nervous systems.Thesymptoms of lead over exposure are anemia, vomiting, headache, stomach pain (lead colic), dizziness, loss of appetite and muscles and jointspain. Exposure to lead from a battery most often occurs during lead reclaim operation through the breathing or ingestion of lead dusts andfumes. This sheet must be passed to any scrap dealer or smelter when the battery is resold.
Sulfuric acid is a strong corrosive. Contact with the acid can cause severe burns to the skin and eyes. Ingestion of sulfuricacid will cause gastro intestinal tract bruns.
Skin contact: Flush with water, see physician if contact area is large, or if blisters form.Eye contact: Call physician immediately, flush with water until physician arrives.Ingestion: Call physician DO NOT INDUCE VOMITING. DO NOT GIVE ANYTHING TO AN UNCONSCIOUS PERSON.
Sulfuric acid – Stable at all temperatures – will not polymerize.Reactive metals, strong bases, most organic compounds.
Sulfur Dioxide, Sulfur Trioxide, Hydrogen Sulfide, Hydrogen.Smoking, sparks, flames, ect., from battery charging area. Mixing acid with other chemicals.
If sulfuric acid is spilled from a battery, neutralize the acid with sodium bicarbonate (baking soda), sodium carbonate (soda ash) or calcium oxide (lime). Flush the area... and dispose of as hazardous waste.
1) Spent lead acid batteries are disposed of using three (3) acceptable methods: send the batteries to: (a) licensedsecondary lead smelters for recycling (b) reputable battery handlers (c) reputable scrap dealers. 2) If the user has to transport thesebatteries to the smelters, the user must follow department of transportation (DOT) regulations.A copy of this material safety data sheet must be supplied to any scrap dealer or secondary lead smelter.Follow applicable Federal, State, and Local regulations.
Skin – rubber gloves, apron – protective equipment must be worn if the battery is cracked or otherwise damaged.HEPA respirator should be worn during reclaim operations, if the OSHA PEL is exceeded. – safety goggles, face shield.
due to the low internal resistance of POWER batteries and high power density, high levels of short circuit current can be developed across the battery terminals. Do not rest tools or cables on the battery. Use insulated tools only. Follow any installation instructions and diagrams when installing or maintaining battery systems.