Structural General Notes - 06.22.10... · indicated in the basis of design. 9. Dowel all vertical...

10
Structural General Notes General These drawings have been prepared by the Engineer of Record primarily to safeguard against major structural damage and loss of life, not to limit damage or maintain use of the structure. See the requirements of the current accepted building code, and as listed in the Basis for Design. Professional standards of care have been used in the preparation of these drawings, normally exercised under similar circumstances by reputable engineers in this, or similar localities. Design of non-structural elements (i.e. stairs, railings, non-load bearing walls, veneers, curtain walls, etc.) and their attachment is not included, and must be provided by others, unless specifically noted on these drawings. Design of pre-engineered structural products (i.e. wood trusses, steel joists, or pre-cast concrete elements, etc.) is not included and must be provided by others, unless specifically noted on these drawings. Specification references (i.e. ASTM, ACI, AWS, etc.) shall be the latest accepted version, where noted on these drawings. An experienced, licensed contractor, with a working knowledge of applicable codes and industry accepted standard practices, shall perform the work depicted in these drawings. All work shall conform to the minimum standards of the current accepted building code found in the Basis for Design, other codes, industry specific specifications, and standards listed herein. The contractor shall comply with requirements of all regulatory agencies with authority over any portion of the work. Work not specifically shown on these drawings shall conform to all applicable codes and accepted standard practices. The contractor shall verify all dimensions, elevations, and conditions on these drawings with the architectural drawings, and all other discipline drawings, prior to start of construction. Notify the Engineer of Record in writing before the start of construction regarding discrepancies, omissions, or variations, or they will become the sole responsibility of the contractor. Notes and the specific details on these drawings take precedence over the Structural General Notes, and General Details. 1. 2. 3. 4. 5. 6. 7. 8. Construction methods are not indicated on these drawings. The contractor shall be solely responsible for all methods, sequences, and procedures of construction. The contractor shall provide adequate shoring, bracing, formwork, etc. as required for the protection of life and property during construction. 9. Excavation procedures, including shoring and protection of adjacent property, structures, streets and utilities, shall be performed in compliance with local building codes, regulations and safety requirement, and shall be the contractor's responsibility. 10. Construction materials shall be spread out uniformly on structural systems, such that design live loads are not exceeded. 11. Structural members shall not have openings, pockets, etc. larger than 6" placed in them, unless specifically noted on these drawings. When drawings by others show items in structural members not shown in the structural drawings, the Engineer of Record shall be notified in writing to determine the appropriate solution. 12. Visits to the construction site by the Engineer of Record are a resource for the contractor and shall not be considered as special inspection. 13. Basis for Design Governing Building Code: 2006 International Building Code 1. Roof Loads: Pitched Roof Dead Load = 22 psf Live Load = 20 psf (reducible) Flat Roof Dead Load = 15 psf Live Load = 20 psf (reducible) 2. Floor Loads: Dead Load = 30 psf Live Load = 40 psf (Residential) 3. Wind Design: Basic Wind Speed = 90 mph Wind Exposure = B Importance Factor = 1.0 Mean Roof Height = 25.5 ft. 4. Seismic Design: Design Category = D Use Group = 1 Sds = 0.463 Sd1 = 0.233 Site Class = D Lateral Force Resisting System = Wood Shearwall R = 6.5 Analysis Procedure = Equivalent Method Base Shear coefficient = 0.051*W 5. Foundations Foundations were designed according to the minimum requirements of the current accepted building code as listed in the Basis for Design. A Geotechnical Engineer should be commission to provide a soils report prior to the completion of the structural design for this project. 5ive Engineering will not assume any liability beyond the minimum code requirements in the event that a Geotechnical Report is not provided. 1. Footings & Foundations: Allowable Soil Pressure (eq. fluid weight): = 1500 psf 2. All forms shall be properly braced to withstand the placement of fresh concrete. 3. Footing excavations shall be clean and free from loose debris, standing water, or un-compacted material at the time of concrete placement. 4. Trenches and excavations under or adjacent to foundations or slabs shall be properly backfilled and compacted. Utility trenching parallel to the foundation shall be located a minimum distance equal to the depth of the trench from the foundation. The trench may approach the foundation at 90 degrees to the structure and may not exceed two and one half feet wide. The trench approach to the foundation may not be located closer than 8 feet from a corner of the structure. 5. Concrete Compressive strength, f'c, shall be 4500 psi and a maximum water/cement ratio of 0.45 for concrete in contact with soil. All other structural concrete f'c shall be 3000 psi. Foundation design uses 2500 psi, therefore, special inspection is not required. 1. Materials Concrete mixes shall be designed by a certified concrete testing laboratory and approved by the engineer of record. 2. All concrete shall be normal weight 145 pcf with hard-rock aggregates. 3. Maximum slump shall be 5 inches, and the water shall be clean and potable. 4. Portland cement shall be ASTM C 150 type V for concrete in contact with soil. Type II cement may be used elsewhere. All cement in contact with soil shall comply to the table above regarding sulfate exposure. 5. Fly ash shall comply with ASTM C 618, class F, and shall be approved by the architect in writing prior to being used on the job. When used, fly ash content shall be 15%-25%. Water-cement ratio shall be based on total cementitious material. 6. Aggregates shall comply with ASTM C 33. Use 3/4 inch maximum aggregate in structural concrete. 1-1/2 inch maximum in slabs on grade and 3/8 inch pea gravel in grouts, unless specifically noted otherwise on the plans, or by written approval of the engineer of record. 7. Materials No more than 90 minutes shall elapse between concrete batching and placement of concrete unless approved in writing by the engineer of record. 8. Concrete mixing, placement and quality shall be per the current accepted code (listed in the basis for design). Mechanically vibrate all concrete. Vibrate slabs on grade around and under floor ducts or similar elements. 9. Control joints in slabs on grade shall be as noted in the general details. Saw-cut joints shall be cut to a minimum depth of t/4. Doweled joints shall be used where noted on plans. Do not joint post-tensioned concrete slabs on grade unless noted otherwise on plans. Space control joints as listed below: Slab thickness (t) Joint spacing (each way) 4" 10'-0" 5" 12'-6" 6" 15'-0" 10. Remove all debris from forms before placing concrete. Concrete shall be carefully placed in reinforced elements to avoid segregation of aggregates. Unconfined fall of concrete shall not exceed five feet, unless approved in writing by the engineer of record. 11. Reinforcing, dowels, bolts, anchors, sleeves, embeds, etc. shall be securely positioned in the forms prior to placement of concrete. 12. High early strength concrete may be used when requested by the contractor. Mix design data using field cured specimens shall be submitted for review and approval. 13. Protect concrete from damage or reduced strength due to cold or hot weather in accordance with ACI 305 and 306. Contractor shall take special curing precautions to minimize shrinkage cracking of concrete slabs. 14. Pipes and electrical conduits shall not be embedded in structural concrete except where specifically approved in writing by the engineer of record. Embedded items shall not impair the strength of the member. 15. Construction joints in structural elements (walls, beams, columns, elevated slabs, etc.) not specifically detailed on the plans require prior written approval from the engineer of record. Contractor shall submit shop drawings showing the proposed joint layout. 16. Concrete (cont.) Reinforcing Steel Reinforcing steel shall meet ASTM A615 and shall be grade 60 deformed bars for all bars #5 and larger. Reinforcing may be grade 40 deformed bars for all bars #4 and smaller. All reinforcing to be welded shall be ASTM A706, grade 60 low alloy weld-able steel. 1. Materials Welded wire fabric shall meet ASTM A185. Lap all welded wire fabric at least one row of wires plus 2 inches. 2. Placement All reinforcing steel dimensions are center to center of the steel unless noted as clear (CLR) cover. Minimum cover for reinforcing shall be as follows (unless noted otherwise on the plans): Exposure Min. Cover Cover Tolerance Cast against and permanently exposed to earth 3" +/- 3/8" Exposed to earth or weather #5 bar and smaller 1 1/2" +/- 3/8" #6 bar and larger 2" +/- 3/8" Not exposed to earth or weather Slabs, walls and joists #11 and smaller 3/4" +/- 3/8" #14-#18 1 1/2" +/- 3/8" Beams and columns Primary reinforcing, ties Stirrups, and spirals 1 1/2" +/- 3/8" Slabs on grade 1 1/2" +/- 3/8" 3. Lap splices in beams, slabs and footings shall be per current governing code or lap schedule where present. Stagger splices a minimum of one lap length. The tack welding of reinforcing bars shall not be allowed. Provide bent corner bars to match and lap with horizontal bars at all corners and intersections per general details. Vertical wall bars shall be spliced at or near floor lines. Splice top bars at center line of span and bottom bars at the support in spandrels, beams, grade beam, etc. unless noted otherwise on the plans. 4. Mechanical splice couplers shall have current testing report accepted by local building official and shall be capable of developing 125% of the strength of the bar. 5. All reinforcing shall be bent cold, one time only. Field bending of rebar shall not be allowed unless specifically noted on the plans. 6. Welding of reinforcing bars, metal inserts, and connections shall conform to AWS D1.4, and shall be made only at locations shown on plans or details. 7. All welds involving reinforcing bars shall be an E90 low hydrogen electrode. 8. Reinforcing bar spacing shown on the plans represents the maximum on center spacing. All bars shall be detailed and placed per the current governing code as indicated in the basis of design. 9. Dowel all vertical reinforcing to foundation, as specified on plans or details. Securely tie all bars in location prior to placement of the concrete. 10. Minimum clear spacing between parallel reinforcement shall be 1 1/2 times bar diameter, 1 1/2 times the max aggregate size, or 1 ½" (whichever is larger). 11. Anchor Bolts Sill plate anchorage at concrete or masonry shall be 1/2" diameter embedded anchor bolts @ 72" o.c. (U.N.O.). All anchor bolts (excluding bolts for holdowns) shall be embedded 7" minimum into the concrete. Anchor bolts for holdowns shall not be considered as part of the required sill plate anchor bolts, as specified in the shearwall schedule or Structural General Notes. Interior walls may be anchored to the concrete with the following (unless noted otherwise on plans): - Embedded anchor bolts - Concrete screw anchors - Expansion anchors - Powder driven fasteners (as specified below) 1. At all sill plates there shall be a minimum of two bolts per piece of plate with one bolt located not more than 12" or less than seven bolt diameters from each end of the piece of plate. A properly sized nut and washer shall be tightened on each bolt to the plate. For seismic design categories D-F, washers shall be a minimum or 0.229" thick by 3" square plate washer (refer to "Basis for Design" on this sheet for seismic design category) at exterior walls, shearwalls, and interior bearing walls where 2x sill plates are specified. Foundation plates and sills shall be the kind of wood specified in the current approved code as listed in the Basis for Design. 2. All shearwalls shall be anchored to the concrete per the shearwall schedule. 3. Where exterior wall embedded anchor bolts have been missed, damaged, or improperly located, one of the following retro-fit options may be used at the contractors discretion: 4. Provide (1) 1/2" diameter Simpson Titen Screw Anchors (ESR-1056 & ESR-2713) concrete screw anchor. Concrete screw anchors shall be embedded a minimum of 4 1/2". 4.1 Provide (2) 1/2" diameter expansion anchors for each 1/2" diameter embedded anchor bolt. Expansion anchors shall be installed not closer than 6 1/2" o.c. and shall be installed with a minimum of 4 1/8" embedment and spaced 1 3/4" from the edge of the slab. Expansion anchors being installed lass than 2" from the edge of the concrete shall be Hilti Kwik Bolt 3 per ESR-2302. Substitutions shall be approved with written approval of the engineer of record. 4.2 Epoxy bolts of the same diameter and spacing may be used in lieu of the embedded bolts. A 7" minimum embedment shall be provided for epoxy grouted bolts. 4.3 As an alternate, Simpson LMA or MAS anchors may be used in lieu of the embedded anchor bolts. The anchor spacing shall be as follows: Shearwall Mark LMA/MAS spacing Shearwall Mark LMA/MAS spacing SW1 28" o.c. SW5 14" o.c. SW2 18" o.c. SW6 10" o.c. SW3 16" o.c. SW7 10" o.c. SW4 16" o.c. SW8 8" o.c. 4.4 Where interior wall embedded anchor bolts have been missed, damaged, or improperly located, one of the following retro-fit options may be used at the contractors discretion. Interior anchor bolts shall be defined as anchor bolts that are located a minimum of 6" from slab edges, steps, turn-downs, openings, or similar discontinuities: 5. Provide (1) 1/2" diameter Simpson Titen Screw Anchors (ESR-1056) or 1/2" diameter ITW Ramset/RedHead LDT (ER 5890) concrete screw anchor. Concrete screw anchors shall be embedded a minimum of 4 1/2". 5.1 5.2 Epoxy bolts of the same diameter and spacing may be used in lieu of the embedded bolts. A 7" minimum embedment shall be provided for epoxy grouted bolts. 5.3 5.4 Interior non-load bearing partition walls may be anchored to the slab with a minimum 0.140" diameter shot pins at 32" o.c. maximum spacing. 6. Shot pins may be used (either Ramset 3500 series (ESR-1799) or Hilti (ESR-1663)) or any other ICBO approved powder driven fastener with at least 200# allowable shear resistance in 2000 psi concrete per the schedule below. Install all fasteneres per ICC-ES Evaluation Report and manufacturer's recommendations. Embedment shall be 1 1/4" minimum and the shot pins shall be installed such that the sill plate wood does not split. If splitting occurs, equivalent expansion bolts shall be installed per the requirements above. Shot Pin Required anchor bolt spacing 0.170 dia. 0.140 dia. 1/2" dia. bolts @ 72" o.c. 13" 10" 1/2" dia. bolts @ 60" o.c. 11" 8" 1/2" dia. bolts @ 48" o.c. 9" 6" 1/2" dia. bolts @ 40" o.c. 7" --- 1/2" dia. bolts @ 36" o.c. 6" --- 5/8" dia. bolts @ 72" o.c. 8 1/2" 6" 5/8" dia. bolts @ 60" o.c. 7" --- 5/8" dia. bolts @ 48" o.c. 5 1/2" --- 3/4" dia. bolts @ 72" o.c. 6" --- Expansion bolts of equal or greater diameter shall be installed per the manufacturer specifications. The bolts shall be one of the following ICC-ES Evaluation Reports: - Hilti Kwik Bolt 3 (ESR-2302) Equivalent expansion bolts may be used at the contractors discretion, provided that the alternate expansion anchors have greater shear and pullout values at equal embedment than those specified above. The expansion bolts shall have minimum embedment depths as follows: - 1/2" diameter bolts shall have 2 1/4" embedment minimum - 5/8" diameter bolts shall have 2 3/4" embedment minimum - 3/4" diameter bolts shall have 3 1/4" embedment minimum Anchor Bolts (cont.) Wood Structural sawn lumber design values shall comply with the latest edition of the grading rules of the Western Wood Products Association (WWPA) or the West Coast Lumber Inspection Bureau (WCLIB). All sawn lumber shall be stamped with the grade match of an approved lumber grading agency. Structural sawn lumber components shall have the following minimum grade (unless noted otherwise on plans): Use: Material 2x sill plates Treated Douglas Fir 2x top plates Douglas Fir Stud Grade 2x4 studs/blocking Douglas Fir Stud Grade 2x6 studs (up to 10'-0" in height) Douglas Fir Stud Grade 2x6 studs (over 10'-0" in height) Douglal Fir No. 2 Joists and all other sawn lumber Douglas Fir No. 2 6x beams and 6x posts Douglas fir No. 1 1. Materials Glue-Laminated beams (GLB)shall be Douglas Fir 24F-V4 unless noted otherwise on the plans. All cantilevered GLB beams shall be Douglas Fir 24F-V8. The GLB beams shall have the following minimum properties: E=1,800,000 psi Fb=2400 psi Fv=165 psi Fabrication and handling shall conform to the latest AITC and ASTM standards. Beams shall bear an apporpriate grade stamp clearly noting its design properties. Beams shall be manufactured with industry standard minimum camber (2000' radius) unless camber is specifically noted on the plans. 2. Laminated Veneer Lumber (LVL) shall be Douglas fir and manufactured in accordance with TrusJoist Macmillan Corporation manufacturing standards as referenced in NER-481, or approved equal. All LVL members shall have the follwing minimum properties: E=1,800,000 psi Fb=2600 psi Fv=285 psi Fc(parallel)=2510 psi Fc(perpendicular)=750 psi When multiple LVL pieces are grouped together, they shall be fastened with (2) rows of 16d nails at 12" o.c. for member depths up to 14" in depth. LVL members greater than 14" in depth shall be used in built up sections only, and shall be fastened together with (3) rows of 16d nails at 12" o.c. 3. Parallel Strand Lumber (PSL) shall be Douglas fir and manufactured in accordance with TrusJoist Macmillan Corporation manufacturing standards as referenced in NER-481, or approved equal. All LVL members shall have the following minimum properties: E=2,000,000 psi Fb=2900 psi Fv=290 psi Fc(parallel)=2900 psi Fc(perpendicular)=750 psi 4. Framing All sills or plates resting on concrete or masonry shall be pressure treated Douglas Fir or other locally approved chemically treated lumber. 5. All beams shall be considered flush bottom unless noted otherwise on the plans. Girder trusses and beams shall have full bearing (for example a (3) ply girder truss shall have a minimum of (3) 2x studs carried to the foundation or carrying beam per plans) at each bearing point with (2)2x studs minumum. Nail studs together per typical nailing schedule. Beams and girder trusses ((2)ply or larger) bearing on the top plate shall be attached to the top plate with an A34 framing anchor or (2) 16d toenails each side of the structural member (unless noted otherwise on the plans). 6. Openings in a single level or top level of the structure shall be framed as follows: - Widths less than 6'-0" wide shall be framed with (1)2x king stud and (1) 2x trimmer stud each side of the opening (unless noted otherwise on the plans). - Widths greater than 6'-0" but less than 16'-0" shall have (2) 2x king studs and (1) 2x trimmer stud each side of the opening (unless noted otherwise on the plans). 7. In exterior walls, interior bearing partitions and shearwalls, any wood stud may be cut or notched to a depth not exceeding 25% of its width. Cutting or notching of the studs to a depth greater than 40% of the width of the stud is permitted in non-bearing partitions supporting no loads other than the weight of the partition. The cut or notched stud shall be mecnanically reinforced per the general detail. 8. A hole not greater in diameter than 40% of the stud width may be bored in any wood stud. Bored holes not greater than 60% of the width of the stud is permitted in non-bearing partitions or in any wall where each bored stud is doubled, provided not more than two such successive doubled studs are bored. In no case shall the edge of the bored hole be nearer than 5/8" to the edge of the stud. Bored holes shall not be located at the same section of stud as a cut or notch. Do not notch joists, rafters or beams, unless noted othewise on the plans. Approval for any holes or notches not indicated on the plans shall be provided by the engineer of record, in writing, prior to the work being done on the site. 9. All bolt shall be installed in holes bored with a bit 1/16" larger than the diameter of the bolt. Bolts and nuts seating on wood shall have cut steel washers under heads and nuts. Ding threads to prevent loosening. Lag bolts shall be installed in pre-drilled holes by hand turning with a wrench (not with an electric or pneumatic impact tool). 10. All nails (except 16d nails) shall be common nails unless specifically noted otherwise on the plans. 16d nails may be 16d sinker, 16d box, pneumatic (P-nail), or 12d common, unless noted otherwise on the plans. Nails shall be driven so that heads are flush with wood surface. Over or under driven nails will not be acceptable. Miscellaneous nailing shall be per the current approved code nailing schedule, or as listed below: Nail Size Shank diameter Length 16d common .162" 3 1/2" 16d sinker .148" 3 1/4" 16d box .135" 3 1/2" 12d common .148" 3 1/4" 10d .148" 3" 8d .131" 2 1/2" 11. The following staple equivalents may be substituted for the nails specified on the plans, where accepted by the local building department: 12. Equivalent Spacing of Approved Fasteners Nail Size Common Nail Spacing Staples and Nails Gauge 16 15 14 4" 6" 8" 10" 12" 6d 3 1/2" 4" 5" 5" 6" 7" 6 1/2" 8" 9 1/2" 8 1/2" 10" 12" 10" 12" 14 1/2" 4" 6" 8" 10" 12" 8d 2 1/2" 3 1/2" 4" 4" 5" 6" 5 1/2" 6 1/2" 8" 6 1/2" 8" 10" 8" 10" 12" 4" 6" 8" 10" 12" 10d 2" 2 1/2" 3" 3 1/2" 4" 5" 4 1/2" 5 1/2" 6 1/2" 5 1/2" 7" 8" 6 1/2" 8" 9 1/2" Note: Penetration is the required depth of embedment of the staple or nail into the main member to acheive its full shear capacity (1" minimum into main framing member). All plywood laid with face grain perpendicular to supports shall be C-D or C-C sheathing conforming to current adopted code as listed in the Basis for Design and shall coform to the following nominal thickness, span rating, and nailing pattern below (unless noted otherwise on the plans): 13. Nailing Pattern Thickness Span Rating Edge Nailing Field Nailing 3/8" 24/0 8d @ 6" o.c. 7/16" 15/32" 3/4" 1" 1 1/8" 24/16 32/16 48/24 60/48 48" o.c. 8d @ 6" o.c. 8d @ 6" o.c. 10d @ 6" o.c. 10d @ 6" o.c. 10d @ 6" o.c. 8d @ 12" o.c. 8d @ 12" o.c. 8d @ 12" o.c. 10d @ 12" o.c. 10d @ 12" o.c. 10d @ 12" o.c. 14. Shear panel blocking noted on plans or details shall be constructed of 2x solid framing with 3/8" minimumm plywood with 8d nails at 6" o.c. (unless noted otherwise on plans) and shall be nailed to adjacent trusses/joists with minimum (2) 16d at the top and bottom of truss or framing. 15. A.P.A. performance rated sheathing (O.S.B.) may be used as an alternate to plywood with prior approval of owner and/or architect. Rated sheathing shall comply with ICC-ES Evaluation Report No. ESR-2586, exposure 1, and shall have a span rating equivalent to or better than the plywood it replaces. Install per manufacturer's reccomendations. Wood (cont.) Wood Connection Hardware Manufactured hardware shall be Simpson Strong-tie products as noted on the drawings. Alternatives may be used at the discretion of the Engineer of Record. One manufacturer shall be used exclusively for each project. Only approved connectors listed below shall be used: a) Simpson Strong-Tie Company Inc, Brea California, (lCBO report No.1211, 1258, 4448, 4935, NER-209, 393, 413, 421, 422, 432, 443, 469). b) USP Lumber Connectors, 2150 Kitty Hawk Road, Livermore, California 94550, (lCBO report No. 2099, 2725, 3613, 5125, 5321, 5356, 5379, 5441, and NER-478, 505, 530) . 1. Tension holddown anchors and straps shall be installed as specified on the foundation and the roof framing plans. The following equivalent holddown anchors and straps substitutions may be used at the contractors discretion: Strap tie holddown Bolt type holdown PAHD42 HTT16, PHD2 HPAHD22 HTT22, PHD5 LSTHD8 HTT16, HD2A, PHD2 STHD8 HTT16, HD5A, PHD2 STHD10 HTT22, MTI28b, HD5A STHD14 PHD6, HD8A PA18, PA23 & PA28 HTT16 HPA28 HTT22 HPA35 PHD6,HD6A 2. Anchor bolt holddown anchorage shall have a standard hex head at the embedded end. The embedded anchor bolt diameter and depth of embedment or retrofit embedment shall be as follows: 3. Anchor Bolt Retro-fit Simpson Holddown Minimum Bolt Dia. Minimum Embedment All Thread Dia. Minimum Epoxy Grout Embedment Simpson SSTB mono- pour two- pour LTTI31 5/8" 7" 5/8" 10" SSTB16 SSTB20 HTT16 5/8" 7 1/4" 5/8" 10" SSTB16 SSTB20 HTT22 5/8" 9 3/4" 5/8" 10" SSTB24 --- MTT28B 5/8" 8 3/4" 5/8" 10" SSTB20 SSTB24 PHD2 5/8" 7 1/4" 5/8" 10" SSTB16 SSTB20 PHD5 5/8" 8 3/4" 5/8" 10" SSTB16 SSTB20 PHD6 7/8" 10 1/4" 7/8" 15" SSTB28 SSTB34 PHD8 7/8" 11 1/4" 7/8" 15" SSTB28 SSTB34 HDQ8 7/8" 11 3/4" 7/8" 15" SSTB28 SSTB34 HHDQ11 1" 18" --- --- --- --- HHDQ14 1" 18" --- --- --- --- HD10A 7/8" 14" 7/8" 20" SSTB28 SSTB34 HD14A 1" 17" --- --- --- --- 1 1/4" 17" --- --- --- --- HD15 1 1/4" 18 1/4" --- --- --- --- Holddown anchors may be anchored to concrete slab with epoxy-grouted all-thread bar in drilled hole. Alternate epoxy systems may be used provided ICBO reports are submitted and the alternate system have been approved by the EOR. Install per ICBO report and manufacturer's specifications. Special inspection is required during all epoxy anchored bolt installations. 4. Adhesives used to attach floor sheathing to the framing shall conform to the AFG-01 specification of the American Plywood Association (adhesives for field-gluing plywood to wood framing). The adhesive shall be certified as conforming to AFG-01 by a testing agency approved by the building official or accepted by the federal housing administration. Alternates may be used only with specific approval of the EOR and only upon submittal of a listing of adhesives to be substituted. 5. Where the truss manufacturer requires additional bearing an appropriately sized Truss Bearing Enhancer (TBE) connection shall be installed per the hardware manufacturer specifications. 6. Where the truss manufacture requires hardware to resist uplift forces per the truss calculations greater than # 250, the following straps shall be used: 7. Hardware for Uplift Forces Lateral Ties @ Top Plate Douglas Fir-Larch Southern Pine Spruce Pine Fir Vert. Loads Horiz. Loads Vert. Loads Horiz. Loads P1 P1 P2 P2 H1 165# 455#* 140# 400#* H2.5A 110# 480#* 110# 520#* LTS12 --- 720# --- 620# MTS12 --- 1000# --- 860# HTS16 --- 1260# --- 1085# HTS20 --- 1450# --- 1245# LGT2 --- 2050# --- 1785# * Use 10d in lieu of 8d nails Fasteners for preservative-treated and fire-retardant-treated wood shall be of hot dipped zinc-coated galvanized steel. 8. Wood Connection Hardware (cont.) Special Inspections All required special inspections shall be performed in accordance with current accepted building code. 1. In addition to standard inspection by the building official required per the building code, the owner shall employ one or more special inspectors who shall provide inspection during construction for the types of work listed below. 2. The Special Inspectors shall be a qualified person who shall demonstrate competence, to the satisfaction of the building official, for the inspection of the particular type ofconstruction or operation requiring special inspection. 3. The Special Inspector shall inspect the work assigned for conformance with the approved contract drawings and specifications. The Special Inspector shall furnish inspection reports to the building official, the EOR and other designated persons required by the governing building official. All discrepancies shall be brought to the immediate attention of the contractor for correction, and then if uncorrected in a reasonable period of time, the EOR and the building official shall be notified. The Special Inspector shall submit a final signed report stating whether the work requiring special inspection was, to the best of the inspectors knowledge, constructed in conformance with the approved plans and specifications and the applicable building code provisions. 4. Inspectors shall inspect from an approved set of contract drawings, shop drawings shall not be used in lieu of the approved contract drawings for inspection purposes. 5. Certificate of approval regarding materials and inspection of prefabricated items shall be provided in accordance with the current accepted building code. 6. Types of work to be inspected by the Special Inspector are as follows: 7. 7.1. Prior to and during the installation of concrete around bolts. 7.2. High-Load diaphragms and shearwalls, including all shearwall and diaphragms with nail spacing of 4" o.c. or less at panel edges. 7.3. Periodic special inspections for nailing, bolting, anchoring, and other fastening of components within the seismic-force-resisting system, including drag struts, braces, and holdowns. Deferred Submittals Prefabricated components, specialty items and design-build elements noted on the drawings, but which require the manufacturer or supplier to provide the design,shall be submitted to the Architect and/or the EOR for review as deferred submittals. Deferred submittals required by the EOR shall include, but not be limited to, the following: Stairs, handrails, guardrails and their components Wood trusses Engineered wood joists and beams 1. Deferred submittals shall include calculations and drawings prepared and stamped by an appropriately licensed engineer(specialty engineer) showing the location and magnitude of loads,configuration and size of members and compatibility of submittal items with the primary structural system. 2. The purpose of the EOR's review shall be limited to determining that the drawings and calculations have been properly sealed, that the load criteria are in general conformance with the structural drawings and with the current accepted building code as listed in the basis for design, that connections to the primary structure are compatible with the primary design, and that the primary structure is capable of supporting the imposed loads. 3. The EOR will rely upon the specialty engineer's seal as certification that the deferred submittal items designed by the specialty engineer comply with the criteria set forth in the structural drawings and applicable codes and standards. The EOR will not be responsible for the adequacy of designs provided by others. 4. Allow five (5) working days for the EOR's review. One copy of each submittal will be retained for the EOR's records. 5. Wood Trusses Prefabricated wood trusses shall be designed to support their self-weight, plus live load and superimposed dead loads including, but not limited to all mechanical and other equipment, and shall be designed to resist all drag forces, shearwall uplift and downward loads, and other special loads noted on the drawings or calculations. 1. The truss manufacturer shall design for span/240 total load deflection and span/360 live load deflection. The truss manufacturer shall account for differences between deflections of adjacent trusses at transitions in the framing system, with trusses designed to minimize differential deflection. 2. Bridging size and spacing shall be as designated by the truss manufacturer unless noted otherwise on the plans. 3. The contractor shall submit shop drawings, erection drawings and design calculations sealed by an appropriately registered engineer. Shop drawings shall show any special details required at bearing points. All connectors shall have current ICBO approval. A minimum of (4) sets of truss submittals shall be provided for review, with one set to be retained by the EOR. All information submitted is to be clear and legible. Shop drawings or truss layout drawings shall show all loads included in the truss designs. 4. Trusses may be over spanned to accommodate 30"x30" attic access provided that the roof sheathing panel edges are blocked and edge nailed at over span. 5. The truss manufacturer shall be responsible for specifying all hangers or other connection hardware required for truss installation. 6. Any proposed changes to the truss layout, connections, or design loads depicted on the EOR drawings must be approved in writing by the EOR prior to the submittal of truss construction documents for review. 7. Sheet Index Sheet Title S101 General Structural Notes S102 Abbreviations, General Details S201 Footing & Foundation Plan S301 Footing & Foundation Details S401 Floor & Low Roof Framing Plan S402 Roof Framing Plan S501 Framing Details S502 Framing Details Submittal Set (June 21, 2010) Indicates previously/currently issued sheet S103 General Details S503 Framing Details

Transcript of Structural General Notes - 06.22.10... · indicated in the basis of design. 9. Dowel all vertical...

Page 1: Structural General Notes - 06.22.10... · indicated in the basis of design. 9. Dowel all vertical reinforcing to foundation, as specified on plans or details. Securely tie all bars

Structural General Notes

GeneralThese drawings have been prepared by the Engineer of Record primarily to safeguard against major structural damage and loss of life, not to limit damage or maintain use of the structure. See the requirements of the current accepted building code, and as listed in the Basis for Design.

Professional standards of care have been used in the preparation of these drawings, normally exercised under similar circumstances by reputable engineers in this, or similar localities.

Design of non-structural elements (i.e. stairs, railings, non-load bearing walls, veneers, curtain walls, etc.) and their attachment is not included, and must be provided by others, unless specifically noted on these drawings.

Design of pre-engineered structural products (i.e. wood trusses, steel joists, or pre-cast concrete elements, etc.) is not included and must be provided by others, unless specifically noted on these drawings.

Specification references (i.e. ASTM, ACI, AWS, etc.) shall be the latest accepted version, where noted on these drawings.

An experienced, licensed contractor, with a working knowledge of applicable codes and industry accepted standard practices, shall perform the work depicted in these drawings.

All work shall conform to the minimum standards of the current accepted building code found in the Basis for Design, other codes, industry specific specifications, and standards listed herein. The contractor shall comply with requirements of all regulatory agencies with authority over any portion of the work. Work not specifically shown on these drawings shall conform to all applicable codes and accepted standard practices.

The contractor shall verify all dimensions, elevations, and conditions on these drawings with the architectural drawings, and all other discipline drawings, prior to start of construction. Notify the Engineer of Record in writing before the start of construction regarding discrepancies, omissions, or variations, or they will become the sole responsibility of the contractor. Notes and the specific details on these drawings take precedence over the Structural General Notes, and General Details.

1.

2.

3.

4.

5.

6.

7.

8.

Construction methods are not indicated on these drawings. The contractor shall be solely responsible for all methods, sequences, and procedures of construction. The contractor shall provide adequate shoring, bracing, formwork, etc. as required for the protection of life and property during construction.

9.

Excavation procedures, including shoring and protection of adjacent property, structures, streets and utilities, shall be performed in compliance with local building codes, regulations and safety requirement, and shall be the contractor's responsibility.

10.

Construction materials shall be spread out uniformly on structural systems, such that design live loads are not exceeded.

11.

Structural members shall not have openings, pockets, etc. larger than 6" placed in them, unless specifically noted on these drawings. When drawings by others show items in structural members not shown in the structural drawings, the Engineer of Record shall be notified in writing to determine the appropriate solution.

12.

Visits to the construction site by the Engineer of Record are a resource for the contractor and shall not be considered as special inspection.

13.

Basis for DesignGoverning Building Code: 2006 International Building Code 1.

Roof Loads:Pitched Roof

Dead Load = 22 psfLive Load = 20 psf (reducible)

Flat RoofDead Load = 15 psfLive Load = 20 psf (reducible)

2.

Floor Loads:Dead Load = 30 psfLive Load = 40 psf (Residential)

3.

Wind Design:Basic Wind Speed = 90 mphWind Exposure = BImportance Factor = 1.0Mean Roof Height = 25.5 ft.

4.

Seismic Design:Design Category = DUse Group = 1Sds = 0.463Sd1 = 0.233Site Class = DLateral Force Resisting System = Wood ShearwallR = 6.5Analysis Procedure = Equivalent MethodBase Shear coefficient = 0.051*W

5.

FoundationsFoundations were designed according to the minimum requirements of the current accepted building code as listed in the Basis for Design. A Geotechnical Engineer should be commission to provide a soils report prior to the completion of the structural design for this project. 5ive Engineering will not assume any liability beyond the minimum code requirements in the event that a Geotechnical Report is not provided.

1.

Footings & Foundations:Allowable Soil Pressure (eq. fluid weight): = 1500 psf

2.

All forms shall be properly braced to withstand the placement of fresh concrete.3.

Footing excavations shall be clean and free from loose debris, standing water, or un-compacted material at the time of concrete placement.

4.

Trenches and excavations under or adjacent to foundations or slabs shall be properly backfilled and compacted. Utility trenching parallel to the foundation shall be located a minimum distance equal to the depth of the trench from the foundation. The trench may approach the foundation at 90 degrees to the structure and may not exceed two and one half feet wide. The trench approach to the foundation may not be located closer than 8 feet from a corner of the structure.

5.

Concrete

Compressive strength, f'c, shall be 4500 psi and a maximum water/cement ratio of 0.45 for concrete in contact with soil. All other structural concrete f'c shall be 3000 psi. Foundation design uses 2500 psi, therefore, special inspection is not required.

1.Materials

Concrete mixes shall be designed by a certified concrete testing laboratory and approved by the engineer of record.

2.

All concrete shall be normal weight 145 pcf with hard-rock aggregates.3.

Maximum slump shall be 5 inches, and the water shall be clean and potable.4.

Portland cement shall be ASTM C 150 type V for concrete in contact with soil. Type II cement may be used elsewhere. All cement in contact with soil shall comply to the table above regarding sulfate exposure.

5.

Fly ash shall comply with ASTM C 618, class F, and shall be approved by the architect in writing prior to being used on the job. When used, fly ash content shall be 15%-25%. Water-cement ratio shall be based on total cementitious material.

6.

Aggregates shall comply with ASTM C 33. Use 3/4 inch maximum aggregate in structural concrete. 1-1/2 inch maximum in slabs on grade and 3/8 inch pea gravel in grouts, unless specifically noted otherwise on the plans, or by written approval of the engineer of record.

7.

MaterialsNo more than 90 minutes shall elapse between concrete batching and placement of concrete unless approved in writing by the engineer of record.

8.

Concrete mixing, placement and quality shall be per the current accepted code (listed in the basis for design). Mechanically vibrate all concrete. Vibrate slabs on grade around and under floor ducts or similar elements.

9.

Control joints in slabs on grade shall be as noted in the general details. Saw-cut joints shall be cut to a minimum depth of t/4. Doweled joints shall be used where noted on plans. Do not joint post-tensioned concrete slabs on grade unless noted otherwise on plans. Space control joints as listed below:

Slab thickness (t) Joint spacing (each way)

4" 10'-0" 5" 12'-6" 6" 15'-0"

10.

Remove all debris from forms before placing concrete. Concrete shall be carefully placed in reinforced elements to avoid segregation of aggregates. Unconfined fall of concrete shall not exceed five feet, unless approved in writing by the engineer of record.

11.

Reinforcing, dowels, bolts, anchors, sleeves, embeds, etc. shall be securely positioned in the forms prior to placement of concrete.

12.

High early strength concrete may be used when requested by the contractor. Mix design data using field cured specimens shall be submitted for review and approval.

13.

Protect concrete from damage or reduced strength due to cold or hot weather in accordance with ACI 305 and 306. Contractor shall take special curing precautions to minimize shrinkage cracking of concrete slabs.

14.

Pipes and electrical conduits shall not be embedded in structural concrete except where specifically approved in writing by the engineer of record. Embedded items shall not impair the strength of the member.

15.

Construction joints in structural elements (walls, beams, columns, elevated slabs, etc.) not specifically detailed on the plans require prior written approval from the engineer of record. Contractor shall submit shop drawings showing the proposed joint layout.

16.

Concrete (cont.)

Reinforcing Steel

Reinforcing steel shall meet ASTM A615 and shall be grade 60 deformed bars for all bars #5 and larger. Reinforcing may be grade 40 deformed bars for all bars #4 and smaller. All reinforcing to be welded shall be ASTM A706, grade 60 low alloy weld-able steel.

1.Materials

Welded wire fabric shall meet ASTM A185. Lap all welded wire fabric at least one row of wires plus 2 inches.

2.

PlacementAll reinforcing steel dimensions are center to center of the steel unless noted as clear (CLR) cover. Minimum cover for reinforcing shall be as follows (unless noted otherwise on the plans):

Exposure Min. Cover Cover Tolerance

Cast against and permanently exposed to earth 3" +/- 3/8"

Exposed to earth or weather#5 bar and smaller 1 1/2" +/- 3/8"#6 bar and larger 2" +/- 3/8"

Not exposed to earth or weatherSlabs, walls and joists

#11 and smaller 3/4" +/- 3/8"#14-#18 1 1/2" +/- 3/8"

Beams and columnsPrimary reinforcing, tiesStirrups, and spirals 1 1/2" +/- 3/8"

Slabs on grade 1 1/2" +/- 3/8"

3.

Lap splices in beams, slabs and footings shall be per current governing code or lap schedule where present. Stagger splices a minimum of one lap length. The tack welding of reinforcing bars shall not be allowed. Provide bent corner bars to match and lap with horizontal bars at all corners and intersections per general details. Vertical wall bars shall be spliced at or near floor lines. Splice top bars at center line of span and bottom bars at the support in spandrels, beams, grade beam, etc. unless noted otherwise on the plans.

4.

Mechanical splice couplers shall have current testing report accepted by local building official and shall be capable of developing 125% of the strength of the bar.

5.

All reinforcing shall be bent cold, one time only. Field bending of rebar shall not be allowed unless specifically noted on the plans.

6.

Welding of reinforcing bars, metal inserts, and connections shall conform to AWS D1.4, and shall be made only at locations shown on plans or details.

7.

All welds involving reinforcing bars shall be an E90 low hydrogen electrode.8.

Reinforcing bar spacing shown on the plans represents the maximum on center spacing. All bars shall be detailed and placed per the current governing code as indicated in the basis of design.

9.

Dowel all vertical reinforcing to foundation, as specified on plans or details. Securely tie all bars in location prior to placement of the concrete.

10.

Minimum clear spacing between parallel reinforcement shall be 1 1/2 times bar diameter, 1 1/2 times the max aggregate size, or 1 ½" (whichever is larger).

11.

Anchor BoltsSill plate anchorage at concrete or masonry shall be 1/2" diameter embedded anchor bolts @ 72" o.c. (U.N.O.). All anchor bolts (excluding bolts for holdowns) shall be embedded 7" minimum into the concrete. Anchor bolts for holdowns shall not be considered as part of the required sill plate anchor bolts, as specified in the shearwall schedule or Structural General Notes. Interior walls may be anchored to the concrete with the following (unless noted otherwise on plans):

- Embedded anchor bolts- Concrete screw anchors- Expansion anchors- Powder driven fasteners (as specified below)

1.

At all sill plates there shall be a minimum of two bolts per piece of plate with one bolt located not more than 12" or less than seven bolt diameters from each end of the piece of plate. A properly sized nut and washer shall be tightened on each bolt to the plate. For seismic design categories D-F, washers shall be a minimum or 0.229" thick by 3" square plate washer (refer to "Basis for Design" on this sheet for seismic design category) at exterior walls, shearwalls, and interior bearing walls where 2x sill plates are specified. Foundation plates and sills shall be the kind of wood specified in the current approved code as listed in the Basis for Design.

2.

All shearwalls shall be anchored to the concrete per the shearwall schedule.3.

Where exterior wall embedded anchor bolts have been missed, damaged, or improperly located, one of the following retro-fit options may be used at the contractors discretion:

4.

Provide (1) 1/2" diameter Simpson Titen Screw Anchors (ESR-1056 & ESR-2713) concrete screw anchor. Concrete screw anchors shall be embedded a minimum of 4 1/2".

4.1

Provide (2) 1/2" diameter expansion anchors for each 1/2" diameter embedded anchor bolt. Expansion anchors shall be installed not closer than 6 1/2" o.c. and shall be installed with a minimum of 4 1/8" embedment and spaced 1 3/4" from the edge of the slab. Expansion anchors being installed lass than 2" from the edge of the concrete shall be Hilti Kwik Bolt 3 per ESR-2302. Substitutions shall be approved with written approval of the engineer of record.

4.2

Epoxy bolts of the same diameter and spacing may be used in lieu of the embedded bolts. A 7" minimum embedment shall be provided for epoxy grouted bolts.

4.3

As an alternate, Simpson LMA or MAS anchors may be used in lieu of the embedded anchor bolts. The anchor spacing shall be as follows:

Shearwall Mark LMA/MAS spacing Shearwall Mark LMA/MAS spacing

SW1 28" o.c. SW5 14" o.c.SW2 18" o.c. SW6 10" o.c.SW3 16" o.c. SW7 10" o.c.SW4 16" o.c. SW8 8" o.c.

4.4

Where interior wall embedded anchor bolts have been missed, damaged, or improperly located, one of the following retro-fit options may be used at the contractors discretion. Interior anchor bolts shall be defined as anchor bolts that are located a minimum of 6" from slab edges, steps, turn-downs, openings, or similar discontinuities:

5.

Provide (1) 1/2" diameter Simpson Titen Screw Anchors (ESR-1056) or 1/2" diameter ITW Ramset/RedHead LDT (ER 5890) concrete screw anchor. Concrete screw anchors shall be embedded a minimum of 4 1/2".

5.1

5.2

Epoxy bolts of the same diameter and spacing may be used in lieu of the embedded bolts. A 7" minimum embedment shall be provided for epoxy grouted bolts.

5.3

5.4

Interior non-load bearing partition walls may be anchored to the slab with a minimum 0.140" diameter shot pins at 32" o.c. maximum spacing.

6.

Shot pins may be used (either Ramset 3500 series (ESR-1799) or Hilti (ESR-1663)) or any other ICBO approved powder driven fastener with at least 200# allowable shear resistance in 2000 psi concrete per the schedule below. Install all fasteneres per ICC-ES Evaluation Report and manufacturer's recommendations. Embedment shall be 1 1/4" minimum and the shot pins shall be installed such that the sill plate wood does not split. If splitting occurs, equivalent expansion bolts shall be installed per the requirements above.

Shot PinRequired anchor bolt spacing 0.170 dia. 0.140 dia. 1/2" dia. bolts @ 72" o.c. 13" 10" 1/2" dia. bolts @ 60" o.c. 11" 8" 1/2" dia. bolts @ 48" o.c. 9" 6" 1/2" dia. bolts @ 40" o.c. 7" --- 1/2" dia. bolts @ 36" o.c. 6" ---

5/8" dia. bolts @ 72" o.c. 8 1/2" 6" 5/8" dia. bolts @ 60" o.c. 7" --- 5/8" dia. bolts @ 48" o.c. 5 1/2" ---

3/4" dia. bolts @ 72" o.c. 6" ---

Expansion bolts of equal or greater diameter shall be installed per the manufacturer specifications. The bolts shall be one of the following ICC-ES Evaluation Reports:

- Hilti Kwik Bolt 3 (ESR-2302)

Equivalent expansion bolts may be used at the contractors discretion, provided that the alternate expansion anchors have greater shear and pullout values at equal embedment than those specified above. The expansion bolts shall have minimum embedment depths as follows:

- 1/2" diameter bolts shall have 2 1/4" embedment minimum- 5/8" diameter bolts shall have 2 3/4" embedment minimum- 3/4" diameter bolts shall have 3 1/4" embedment minimum

Anchor Bolts (cont.)

Wood

Structural sawn lumber design values shall comply with the latest edition of the grading rules of the Western Wood Products Association (WWPA) or the West Coast Lumber Inspection Bureau (WCLIB). All sawn lumber shall be stamped with the grade match of an approved lumber grading agency. Structural sawn lumber components shall have the following minimum grade (unless noted otherwise on plans):

Use: Material2x sill plates Treated Douglas Fir2x top plates Douglas Fir Stud Grade2x4 studs/blocking Douglas Fir Stud Grade2x6 studs (up to 10'-0" in height) Douglas Fir Stud Grade2x6 studs (over 10'-0" in height) Douglal Fir No. 2Joists and all other sawn lumber Douglas Fir No. 26x beams and 6x posts Douglas fir No. 1

1.Materials

Glue-Laminated beams (GLB)shall be Douglas Fir 24F-V4 unless noted otherwise on the plans. All cantilevered GLB beams shall be Douglas Fir 24F-V8. The GLB beams shall have the following minimum properties:

E=1,800,000 psiFb=2400 psiFv=165 psi

Fabrication and handling shall conform to the latest AITC and ASTM standards. Beams shall bear an apporpriate grade stamp clearly noting its design properties. Beams shall be manufactured with industry standard minimum camber (2000' radius) unless camber is specifically noted on the plans.

2.

Laminated Veneer Lumber (LVL) shall be Douglas fir and manufactured in accordance with TrusJoist Macmillan Corporation manufacturing standards as referenced in NER-481, or approved equal. All LVL members shall have the follwing minimum properties:

E=1,800,000 psiFb=2600 psiFv=285 psiFc(parallel)=2510 psiFc(perpendicular)=750 psi

When multiple LVL pieces are grouped together, they shall be fastened with (2) rows of 16d nails at 12" o.c. for member depths up to 14" in depth. LVL members greater than 14" in depth shall be used in built up sections only, and shall be fastened together with (3) rows of 16d nails at 12" o.c.

3.

Parallel Strand Lumber (PSL) shall be Douglas fir and manufactured in accordance with TrusJoist Macmillan Corporation manufacturing standards as referenced in NER-481, or approved equal. All LVL members shall have the following minimum properties:

E=2,000,000 psiFb=2900 psiFv=290 psiFc(parallel)=2900 psiFc(perpendicular)=750 psi

4.

FramingAll sills or plates resting on concrete or masonry shall be pressure treated Douglas Fir or other locally approved chemically treated lumber.

5.

All beams shall be considered flush bottom unless noted otherwise on the plans. Girder trusses and beams shall have full bearing (for example a (3) ply girder truss shall have a minimum of (3) 2x studs carried to the foundation or carrying beam per plans) at each bearing point with (2)2x studs minumum. Nail studs together per typical nailing schedule. Beams and girder trusses ((2)ply or larger) bearing on the top plate shall be attached to the top plate with an A34 framing anchor or (2) 16d toenails each side of the structural member (unless noted otherwise on the plans).

6.

Openings in a single level or top level of the structure shall be framed as follows:

- Widths less than 6'-0" wide shall be framed with (1)2x king stud and (1) 2x trimmer stud each side of the opening (unless noted otherwise on the plans).

- Widths greater than 6'-0" but less than 16'-0" shall have (2) 2x king studs and (1) 2x trimmer stud each side of the opening (unless noted otherwise on the plans).

7.

In exterior walls, interior bearing partitions and shearwalls, any wood stud may be cut or notched to a depth not exceeding 25% of its width. Cutting or notching of the studs to a depth greater than 40% of the width of the stud is permitted in non-bearing partitions supporting no loads other than the weight of the partition. The cut or notched stud shall be mecnanically reinforced per the general detail.

8.

A hole not greater in diameter than 40% of the stud width may be bored in any wood stud. Bored holes not greater than 60% of the width of the stud is permitted in non-bearing partitions or in any wall where each bored stud is doubled, provided not more than two such successive doubled studs are bored. In no case shall the edge of the bored hole be nearer than 5/8" to the edge of the stud. Bored holes shall not be located at the same section of stud as a cut or notch. Do not notch joists, rafters or beams, unless noted othewise on the plans. Approval for any holes or notches not indicated on the plans shall be provided by the engineer of record, in writing, prior to the work being done on the site.

9.

All bolt shall be installed in holes bored with a bit 1/16" larger than the diameter of the bolt. Bolts and nuts seating on wood shall have cut steel washers under heads and nuts. Ding threads to prevent loosening. Lag bolts shall be installed in pre-drilled holes by hand turning with a wrench (not with an electric or pneumatic impact tool).

10.

All nails (except 16d nails) shall be common nails unless specifically noted otherwise on the plans. 16d nails may be 16d sinker, 16d box, pneumatic (P-nail), or 12d common, unless noted otherwise on the plans. Nails shall be driven so that heads are flush with wood surface. Over or under driven nails will not be acceptable. Miscellaneous nailing shall be per the current approved code nailing schedule, or as listed below:

Nail Size Shank diameter Length16d common .162" 3 1/2"16d sinker .148" 3 1/4"16d box .135" 3 1/2"12d common .148" 3 1/4"10d .148" 3"8d .131" 2 1/2"

11.

The following staple equivalents may be substituted for the nails specified on the plans, where accepted by the local building department:

12.

Equivalent Spacing of Approved FastenersNail Size Common Nail

SpacingStaples and Nails Gauge

16 15 144"6"8"

10"12"

6d

3 1/2" 4" 5"5" 6" 7"

6 1/2" 8" 9 1/2"8 1/2" 10" 12"

10" 12" 14 1/2"4"6"8"

10"12"

8d

2 1/2" 3 1/2" 4"4" 5" 6"

5 1/2" 6 1/2" 8"6 1/2" 8" 10"

8" 10" 12"4"6"8"

10"12"

10d

2" 2 1/2" 3"3 1/2" 4" 5"4 1/2" 5 1/2" 6 1/2"5 1/2" 7" 8"6 1/2" 8" 9 1/2"

Note: Penetration is the required depth of embedment of the staple or nail into the main member to acheive its full shear capacity (1" minimum into main framing member).

All plywood laid with face grain perpendicular to supports shall be C-D or C-C sheathing conforming to current adopted code as listed in the Basis for Design and shall coform to the following nominal thickness, span rating, and nailing pattern below (unless noted otherwise on the plans):

13.

Nailing PatternThickness Span Rating Edge Nailing Field Nailing

3/8" 24/0 8d @ 6" o.c.7/16"

15/32"3/4"1"

1 1/8"

24/1632/1648/2460/48

48" o.c.

8d @ 6" o.c.8d @ 6" o.c.

10d @ 6" o.c.10d @ 6" o.c.10d @ 6" o.c.

8d @ 12" o.c.8d @ 12" o.c.8d @ 12" o.c.10d @ 12" o.c.10d @ 12" o.c.10d @ 12" o.c.

14.

Shear panel blocking noted on plans or details shall be constructed of 2x solid framing with 3/8" minimumm plywood with 8d nails at 6" o.c. (unless noted otherwise on plans) and shall be nailed to adjacent trusses/joists with minimum (2) 16d at the top and bottom of truss or framing.

15.

A.P.A. performance rated sheathing (O.S.B.) may be used as an alternate to plywood with prior approval of owner and/or architect. Rated sheathing shall comply with ICC-ES Evaluation Report No. ESR-2586, exposure 1, and shall have a span rating equivalent to or better than the plywood it replaces. Install per manufacturer's reccomendations.

Wood (cont.)

Wood Connection HardwareManufactured hardware shall be Simpson Strong-tie products as noted on the drawings. Alternatives may be used at the discretion of the Engineer of Record. One manufacturer shall be used exclusively for each project. Only approved connectors listed below shall be used:

a) Simpson Strong-Tie Company Inc, Brea California, (lCBO report No.1211, 1258, 4448, 4935, NER-209, 393, 413, 421, 422, 432, 443, 469).

b) USP Lumber Connectors, 2150 Kitty Hawk Road, Livermore, California 94550, (lCBO report No. 2099, 2725, 3613, 5125, 5321, 5356, 5379, 5441, and NER-478, 505, 530) .

1.

Tension holddown anchors and straps shall be installed as specified on the foundation and the roof framing plans. The following equivalent holddown anchors and straps substitutions may be used at the contractors discretion:

Strap tie holddown Bolt type holdown PAHD42 HTT16, PHD2 HPAHD22 HTT22, PHD5 LSTHD8 HTT16, HD2A, PHD2 STHD8 HTT16, HD5A, PHD2STHD10 HTT22, MTI28b, HD5A STHD14 PHD6, HD8A PA18, PA23 & PA28 HTT16 HPA28 HTT22 HPA35 PHD6,HD6A

2.

Anchor bolt holddown anchorage shall have a standard hex head at the embedded end. The embedded anchor bolt diameter and depth of embedment or retrofit embedment shall be as follows:

3.

Anchor Bolt Retro-fit

SimpsonHolddown

MinimumBolt Dia.

MinimumEmbedment

All ThreadDia.

MinimumEpoxy GroutEmbedment

Simpson SSTBmono-pour

two-pour

LTTI31 5/8" 7" 5/8" 10" SSTB16 SSTB20HTT16 5/8" 7 1/4" 5/8" 10" SSTB16 SSTB20HTT22 5/8" 9 3/4" 5/8" 10" SSTB24 ---

MTT28B 5/8" 8 3/4" 5/8" 10" SSTB20 SSTB24PHD2 5/8" 7 1/4" 5/8" 10" SSTB16 SSTB20PHD5 5/8" 8 3/4" 5/8" 10" SSTB16 SSTB20PHD6 7/8" 10 1/4" 7/8" 15" SSTB28 SSTB34PHD8 7/8" 11 1/4" 7/8" 15" SSTB28 SSTB34HDQ8 7/8" 11 3/4" 7/8" 15" SSTB28 SSTB34

HHDQ11 1" 18" --- --- --- ---HHDQ14 1" 18" --- --- --- ---HD10A 7/8" 14" 7/8" 20" SSTB28 SSTB34HD14A 1" 17" --- --- --- ---

1 1/4" 17" --- --- --- ---HD15 1 1/4" 18 1/4" --- --- --- ---

Holddown anchors may be anchored to concrete slab with epoxy-grouted all-thread bar in drilled hole. Alternate epoxy systems may be used provided ICBO reports are submitted and the alternate system have been approved by the EOR. Install per ICBO report and manufacturer's specifications. Special inspection is required during all epoxy anchored bolt installations.

4.

Adhesives used to attach floor sheathing to the framing shall conform to the AFG-01 specification of the American Plywood Association (adhesives for field-gluing plywood to wood framing). The adhesive shall be certified as conforming to AFG-01 by a testing agency approved by the building official or accepted by the federal housing administration. Alternates may be used only with specific approval of the EOR and only upon submittal of a listing of adhesives to be substituted.

5.

Where the truss manufacturer requires additional bearing an appropriately sized Truss Bearing Enhancer (TBE) connection shall be installed per the hardware manufacturer specifications.

6.

Where the truss manufacture requires hardware to resist uplift forces per the truss calculations greater than # 250, the following straps shall be used:

7.

Hardware for Uplift Forces

Lateral Ties@ Top Plate

Douglas Fir-LarchSouthern Pine Spruce Pine Fir

Vert. Loads Horiz. Loads Vert. Loads Horiz. LoadsP1 P1P2 P2

H1 165# 455#* 140# 400#*H2.5A 110# 480#* 110# 520#*LTS12 --- 720# --- 620#MTS12 --- 1000# --- 860#HTS16 --- 1260# --- 1085#HTS20 --- 1450# --- 1245#LGT2 --- 2050# --- 1785#

* Use 10d in lieu of 8d nails

Fasteners for preservative-treated and fire-retardant-treated wood shall be of hot dipped zinc-coated galvanized steel.

8.

Wood Connection Hardware (cont.)

Special InspectionsAll required special inspections shall be performed in accordance with current accepted building code.

1.

In addition to standard inspection by the building official required per the building code, the owner shall employ one or more special inspectors who shall provide inspection during construction for the types of work listed below.

2.

The Special Inspectors shall be a qualified person who shall demonstrate competence, to the satisfaction of the building official, for the inspection of the particular type ofconstruction or operation requiring special inspection.

3.

The Special Inspector shall inspect the work assigned for conformance with the approved contract drawings and specifications. The Special Inspector shall furnish inspection reports to the building official, the EOR and other designated persons required by the governing building official. All discrepancies shall be brought to the immediate attention of the contractor for correction, and then if uncorrected in a reasonable period of time, the EOR and the building official shall be notified. The Special Inspector shall submit a final signed report stating whether the work requiring special inspection was, to the best of the inspectors knowledge, constructed in conformance with the approved plans and specifications and the applicable building code provisions.

4.

Inspectors shall inspect from an approved set of contract drawings, shop drawings shall not be used in lieu of the approved contract drawings for inspection purposes.

5.

Certificate of approval regarding materials and inspection of prefabricated items shall be provided in accordance with the current accepted building code.

6.

Types of work to be inspected by the Special Inspector are as follows: 7.

7.1. Prior to and during the installation of concrete around bolts.

7.2. High-Load diaphragms and shearwalls, including all shearwall and diaphragms with nail spacing of 4" o.c. or less at panel edges.

7.3. Periodic special inspections for nailing, bolting, anchoring, and other fastening of components within the seismic-force-resisting system, including drag struts, braces, and holdowns.

Deferred SubmittalsPrefabricated components, specialty items and design-build elements noted on the drawings, but which require the manufacturer or supplier to provide the design,shall be submitted to the Architect and/or the EOR for review as deferred submittals. Deferred submittals required by the EOR shall include, but not be limited to, the following:

Stairs, handrails, guardrails and their components Wood trusses Engineered wood joists and beams

1.

Deferred submittals shall include calculations and drawings prepared and stamped by an appropriately licensed engineer(specialty engineer) showing the location and magnitude of loads,configuration and size of members and compatibility of submittal items with the primary structural system.

2.

The purpose of the EOR's review shall be limited to determining that the drawings and calculations have been properly sealed, that the load criteria are in general conformance with the structural drawings and with the current accepted building code as listed in the basis for design, that connections to the primary structure are compatible with the primary design, and that the primary structure is capable of supporting the imposed loads.

3.

The EOR will rely upon the specialty engineer's seal as certification that the deferred submittal items designed by the specialty engineer comply with the criteria set forth in the structural drawings and applicable codes and standards. The EOR will not be responsible for the adequacy of designs provided by others.

4.

Allow five (5) working days for the EOR's review. One copy of each submittal will be retained for the EOR's records.

5.

Wood TrussesPrefabricated wood trusses shall be designed to support their self-weight, plus live load and superimposed dead loads including, but not limited to all mechanical and other equipment, and shall be designed to resist all drag forces, shearwall uplift and downward loads, and other special loads noted on the drawings or calculations.

1.

The truss manufacturer shall design for span/240 total load deflection and span/360 live load deflection. The truss manufacturer shall account for differences between deflections of adjacent trusses at transitions in the framing system, with trusses designed to minimize differential deflection.

2.

Bridging size and spacing shall be as designated by the truss manufacturer unless noted otherwise on the plans.

3.

The contractor shall submit shop drawings, erection drawings and design calculations sealed by an appropriately registered engineer. Shop drawings shall show any special details required at bearing points. All connectors shall have current ICBO approval. A minimum of (4) sets of truss submittals shall be provided for review, with one set to be retained by the EOR. All information submitted is to be clear and legible. Shop drawings or truss layout drawings shall show all loads included in the truss designs.

4.

Trusses may be over spanned to accommodate 30"x30" attic access provided that the roof sheathing panel edges are blocked and edge nailed at over span.

5.

The truss manufacturer shall be responsible for specifying all hangers or other connection hardware required for truss installation.

6.

Any proposed changes to the truss layout, connections, or design loads depicted on the EOR drawings must be approved in writing by the EOR prior to the submittal of truss construction documents for review.

7.

Sheet Index

Sheet TitleS101 General Structural NotesS102 Abbreviations, General Details

S201 Footing & Foundation PlanS301 Footing & Foundation DetailsS401 Floor & Low Roof Framing PlanS402 Roof Framing PlanS501 Framing DetailsS502 Framing Details

Submittal Set (June 21, 2010)

Indicates previously/currently issued sheet

S103 General Details

S503 Framing Details

Page 2: Structural General Notes - 06.22.10... · indicated in the basis of design. 9. Dowel all vertical reinforcing to foundation, as specified on plans or details. Securely tie all bars

A.C.I.A.I.S.C.

American Concrete InstituteAmerican Institute of Steel Construction

A.I.S.I. American Iron & Steel InstituteT.O.F.T.O.J.

Top of FootingTop of Joist

T.O.L. Top of LedgerALT AlternateA.S.T.M. American Society for Testing & MaterialsCont. ContinuousDia. DiameterEQ. EqualE.W. Each WayF.F. Finish Floorft FootGa GaugeGLB Glu-lam Beam

S.G.N. Structural General Notes

HSS Hollow Structural SectionI.B.C. International Building Codek Kip (1,000 lbs)

Mfr. ManufacturerMax MaximumMin MinimumMisc. MiscellaneousN.T.S. Not to Scaleo.c. On Centerplf Pounds per Linear Footpsf Pounds per Square Footpsi Pounds per Square Inch

Sim SimilarSpec SpecificationStd Standard

ksi Kips per Square Inch

Tongue & GrooveT&GT.O. Top of

T.O.M. Top of MasonryT.O.S. Top of SteelT.O.W. Top of WallTyp TypicalU.B.C. Uniform Building CodeU.N.O. Unless Noted OtherwiseVert Vertical

Horiz. Horizontal

T.O.D. Top of Deck

lbs Pounds

01

SWXL=X'-X" XXXXXX

4x10

(2)2x_ Trimmer(1)2x_ K.S.

(2)2x_ Trimmer(1)2x_ K.S.

FCxxCWx

xxx

Wood Wall

Shearwall per Shearwall Schedule

Shearwall Callout

Holddown anchor per plan

Wood Beam

Wood Beam Callout

Wood Post/Trimmer/King Stud

Wood Post/Trimmer/King Stud Callout

Bearing Wall

Concrete Footing

Concrete Wall

Concrete Footing Callout

Concrete Wall Callout

Detail Reference

02

03

12D

4D(2

1/2

" MIN

)

6D(3" MIN)

Finished bend dia. = 6D for #8 bar &

"D" = bar diameter

smaller, 9D for #9, #10 & #11 bars, & 11D for #14 & #18 bars

Finished bend dia. for stirrups & ties = 4D for #5 bars & smaller & 6D for #6 bars & larger

Extension = 6D for #5 bars & smaller, 12D for #6 bars & larger

NOTES:A. All dimensions per C.R.S.I. manual of standard practice & A.C.I. 318.

B. All bars to be bent cold.

C. Do not bend or straighten bars in a manner that will damage the material.

D. Do not bend bars partially embedded in concrete or masonry.

04

Slab on grade per plan

Control joint per plan or Structrual General Notes

Sawcut depth to be approximately 1/4 of the slab thickness

at joint

Tape or grease one end of dowel to break bond to concrete

NOTES:A. Doweled joints req'd @ pour stop or slab slope transition only.

B. Tooled joint or joint form (zip strip) may be used as an alternate to sawcut joint.

#4x12" long Dowel @ 18" o.c. centered

05

Utility pipe as occurs

Concrete footing per plan

Backfill & recompact trench per soils report

18" min. unless noted otherwise in soils report. For pipes located less than 18"

A

B

C

below footing see details B & C

Pipe sleve with inside dia. to allow 1/2" clearance between pipe and sleeve on all sides

Concrete fill to match footing width. See Structural General Notes for concrete mix specifications

6" min. to allow top reinforcing and embedded items to maintain min. concrete coverage per Structural General Notes

Top footing reinforcing per plan or (2) #4 x 48" min. centered over pipe

Thicken footing @ sleeve (6" min.) such that dimension above (per ) plus thickened dimesion equals or exceeds min. footing thickness per plan

Provide bent bars as necessary for bottom footing reinforcement to be continuous below pipe sleeve. Lap per Structural General Notes

Dimension to equal or exceed 2 times outside diameter of sleeve (12" min.)

NOTES:A. All backfill operations per detail A to be completed and approved by

B. Notify engineer 48 hours min. prior to placing concrete where detail C is req'd.

geotechnical engineer prior to placing concrete footings.

06

(20) 16d nails min unless noted otherwise on plans

Double 2x top plate splice. Center splices over studs

Wood wall per plan

Simpson CMSTC16 strap at splice (6'-0" min)

07

Intersecting Wall

2x Stud

16d @ 8" o.c.

Edge nailing per Shearwall Schedule

Shearwall per plan

08

Wood header per plan

Trimmer studs per plan

King studs per plan

Double 2x top plate

2x cripple studs @ 16" o.c. full length of header

09

Field nailing per Stuctural General Notes

4'-0" x 8'-0" wood structural panel

Diaphragm boundry

Diaphragm edge nailing per StructuralGeneral Notes

Panel edge nailing per Structrual General Notes

Continuous panel joint

Floor or roof joists/trusses

11

2x framing

(2)16d @ connection

3/8" plywood sheathing one side of framing with 8d @ 6" o.c.

Pre-fabricated block by truss mf'r with plated connection

NOTES:A. Shearwall condition applies along entire length of wall at interior shear lines and exterior walls

B. Non-shearwall condition may be used for perpendicular to wall (end wall) conditions and over interior bearing walls at not-shearwall conditions only

10

Page 3: Structural General Notes - 06.22.10... · indicated in the basis of design. 9. Dowel all vertical reinforcing to foundation, as specified on plans or details. Securely tie all bars

S

Edge nailing per Structural

Roof sheathing per plan

Roof truss top chord or rafter. Truss

2x6 ridge joist

2x4 minimum overbuild rafter @ 24" o.c.

General Notes

2x6 continuous valley plate with (3)16d

manufacturer shall design for 150# poinload from support post or valley plate

2x blocking

nails @ each truss or rafter

2x4 support post @ each truss with (2)16d each end

NOTE:Premanufactured trusses may be used in lieu of conventional framing. Truss should be designed to bear at each intermediate perpendicular truss.

Field nailing per plan

13

Edge nailing per Shearwall Schedule

Shearwall sheathing per shearwall

Holddown as occurs per plan

schedule. Sheathing may be placed vertically or horizontally

Field nailing per shearwall schedule

Blocking @ all panel edges

Sill plate thickness per shearwall schedule

1/8" gap @ end joints

1/16" gap @ side joints

Adjoining panel edge member per shearwall schedule

Anchor bolt diameter & spacing per shearwall schedule

Min (2) full height studs @ all holddowns or as noted on plans

Concrete footing/stem wall per plan

12

14

Page 4: Structural General Notes - 06.22.10... · indicated in the basis of design. 9. Dowel all vertical reinforcing to foundation, as specified on plans or details. Securely tie all bars

Floor & Low Roof Framing PlanSCALE = 3/16"=1'-0"

Casita Roof Framing PlanSCALE = 3/16"=1'-0"

Slope perArch'l

FS36

FS40FS26

FS40

FS46

FS40

FS26

FS20 FS20

FS20

FS20

FS30FS56

Footing and Foundation Plan Notes

Verify all dimensions with architect prior to start of construction.1.

Concrete slab on grade shall be 4" thick over 2" sand over 6 mil. visqueen (vapor barrier) over 6" type II aggregate base material. As an option, 8 mil visqueen may be place below the type II and the sand eliminated. The base material shall be moistened (but not saturated) prior to the placement of the concrete. Recommended reinforcement of the concrete slab should be #3 bars at 18" o.c. each way or 6 x 6 - W2.1 x W2.1 welded wire fabric, centered in slab thickness.

3.

Anchor bolts and holddowns shall be secured in place prior to the placement of concrete, and shall be installed per the manufacturers specifications and the General Notes.

4.

All site walls, sidewalks, or other architectural features shall be by others (unless noted otherwise).

5.

Verify locations of all inserts in slab with the architectural, mechanical, plumbing, and electrical plans prior to the placement of concrete slab.

2.

The finished surface of the slab on grade shall be noted as 100'-0" (elevation) unless noted otherwise on the footing and foundation plan.

6.

Size and reinforcement of isolated and continuous footings shall be per the footing schedule below.

7.

Continuous and Isolated Footing ScheduleContinuous Footings

Mark WidthLengthDepth Crosswise Reinforcing Longitudinal ReinforcingNo. Size LengthSpacing No. Size LengthSpacing Keynote

FC-Ex

Isolated Footings2'-0" 12" 3 #4 1'-6" Equal -FS202'-6" 12" 4 #4 2'-0" Equal -FS263'-0" 12" 5 #4 2'-6" Equal -FS303'-6" 12" 6 #4 3'-0" Equal -FS364'-0" 12" 6 #4 3'-6" Equal -FS404'-6" 4'-6" 12" 7 #4 4'-0" Equal -FS46

2'-0"2'-6"3'-0"3'-6"4'-0"

3 #4 1'-6" Equal4 #4 2'-0" Equal5 #4 2'-6" Equal6 #4 3'-0" Equal6 #4 3'-6" Equal7 #4 4'-0" Equal

Existing Concrete Footing

FC-Ex

FC-Ex

FC-Ex

FC-Ex

FC-Ex

FC-Ex

FC-Ex

FC-E

x

FC-E

x

FC-E

x

FC-E

x

FC-E

x

1'-0" Cont. 12" - - - - 2 #4 Cont. Equal -FC101'-4" Cont. 12" - - - - 2 #4 Cont. Equal -FC14

FC10

FC10

FC10

FC10

FC10

FC10

FC10

FC14

FC14

FC-E

x

FC-Ex

FC-Ex

FC-E

x

FC-E

x

5'-6" 5'-6" 12" 9 #4 5'-0" Equal -FS56 9 #4 5'-0" Equal

8. All exterior footings shall bear at least 18" below the lowest adjacent final compacted subgrade.

HDU2 HDU2

HDU4

HDU4

HDU4

HDU4

SW1L=16'-0"

SW2L=16'-0"

SW2L=16'-0"

SW1L=16'-0"

SW1

L=16

'-0"

SW1

L=14

'-0"

SW4

L=3'

-4"

SW4

L=3'

-4"

Plywood Shearwall Schedule and NotesMark Sheathing Thickness Edge Nailing A.B. Spacing at Foundation

Bottom Plate Nails at Floor *Min. Sill Plate

Thickness

SW1 8d at 6" o.c. 1/2" dia. A.B. at 32" o.c.16d at 6" o.c. 2x3/8" Plywood Blk'd

One Side of Wall

SW23/8" Plywood Blk'dOne Side of Wall

3" Nominal Framing at Panel Edges

8d at 4" o.c.Staggered

1/2" dia. A.B. at 12" o.c.16d at 5" o.c.

2x

3x1/2" dia. A.B. at 24" o.c.

SW33/8" Plywood Blk'dOne Side of Wall

3" Nominal Framing at Panel Edges

8d at 3" o.c.Staggered

1/2" dia. A.B. at 10" o.c.16d at 3" o.c. 2x

3x1/2" dia. A.B. at 20" o.c.

SW43/8" Plywood Blk'dOne Side of Wall

3" Nominal Framing at Panel Edges

8d at 2" o.c.Staggered

1/2" dia. A.B. at 8" o.c.

1/4" dia. x 6" long screwsat 6" o.c. 3x

15/32" Plywood Blk'dOne Side of Wall

3" Nominal Framingat Panel Edges

3x

SW6 3x1/2" dia. A.B. at 12" o.c. or

5/8" A.B. at 18" o.c.

1/4" dia. x 6" long screwsat 5" o.c.

1/2" dia. A.B. at 16" o.c.

1/4" dia. x 5" long screwsat 6" o.c.

8d at 2" o.c.Staggered

15/32" Plywood Blk'dOne Side of Wall

3" Nominal Framingat Panel Edges

10d at 2" o.c.Staggered

SW5

3/8" Plywood Blk'dBoth Sides of Wall

3" Nominal Framingat Panel Edges

3x

5/8" dia. A.B. at 16" o.c.

1/4" dia. x 5" long screwsat 4" o.c.

8d at 3" o.c.StaggeredSW7

15/32" Plywood Blk'dBoth Sides of Wall

3" Nominal Framingat Panel Edges

3x

5/8" dia. A.B. at 12" o.c.

1/4" dia. x 5" long screwsat 3" o.c.

10d at 4" o.c.StaggeredSW8

* Where 1 1/8" plywood is used for floor sheathing, use" 1/4 x 4" screws in lieu of 16d nails.

Notes:Shearwall studs shall be placed at 16" o.c. maximum. Framing and blocking at panel edges (where noted above) shal be 2x minimum, U.N.O.

A.

Provide (2) full height studs (minimum) at ends of shearwall, unless noted otherwise on plans, details, or holddown requirements. Shearwalls without holddowns require (1) stud at each end of shearwall (minimum). Trimmer stud may be counted as an end stud at non-bearing walls.

B.

Plywood may be installed either horizontally or vertically, U.N.O.C.

Use A.B. (Anchor Bolts) noted per S.G.N., details, and this schedule for bottom sill plate attachment at foundation. Use staggered nails as noted in this schedule for bottom plate attachment at elevated shearwalls. See S.G.N. for optional shot-pins and epoxy bolts where allowed by S.G.N.

D.

Use A.B. (Anchor Bolts) noted per S.G.N., details, and this schedule for bottom sill plate attachment at foundation. Use staggered nails as noted in this schedule for bottom plate attachment at elevated shearwalls. See S.G.N. for optional shot-pins and epoxy bolts where allowed by S.G.N.

E.

Where sheathing is interupted by intersecting wall, provide continuity channel per General Details.

F.

Multiple 2x studs at holddowns shall be stitch-nailed together with 16d sinkers at 6" o.c. (staggered).

G.

All field nailing shall be at 12" o.c. with the same size nail specified for egde nailing.

H.

2x

At existing footings, Simpson Titen HD screw anchors may be used in lieu of the anchor bolts indicated above. Provide 8" long Titen HD screw anchor of the same diameter and spacing as the anchor bolts indicated in the Plywood Shearwall Schedule above.

J.

101

101

101

102

102

103

104

104

105

105

105

104

106

106

106

106

107

107

108typ

109typ

9. Where holddown anchors are to be installed in existing footing, drill & epoxy threaded rod for holddown into existing footing with Simpson Set-XP epoxy per mf'r specs. Provide 8" min embedment.

109typ

No changes to the shearwalls have been made to the Casita, therefore, no additional lateral analysis is required.

10.

FS30

FS30

Page 5: Structural General Notes - 06.22.10... · indicated in the basis of design. 9. Dowel all vertical reinforcing to foundation, as specified on plans or details. Securely tie all bars

8" m

in.

10" m

in.

Concrete footing (see plan for size & reinforcing)

Wood wall per plan

Concrete slab on grade (see Structural General Notes for thickness & reinforcement)

Steel Reinforcing per plan

#4 dowel @ 48" o.c. at optional cold joint

or

Optional cold joint

NOTES:For optional cold joint, place one dowel on each side of all holddowns within 8" of holddown

101

Concrete footing (see plan for size & reinforcing)

Wood wall per plan

Concrete slab on grade (see Structural General Notes for thickness & reinforcement)

Steel Reinforcing per plan

#4 dowel @ 48" o.c. at optional cold joint

or

Optional cold joint

10" m

in.

6" m

ax

6" min

10" m

in.

18" m

ax

6" min

#4 dowels vertically @ 12" o.c.

#4 continuous @ top of curb

10" m

in.

6" min

Optional cold joint between curb and slab. Slope as shown

#4 dowel @ 24" o.c. at optional cold joint @ footing condition. (3

24"pour system)

Field bend bar one time only to center in slab. Maintain min. bend radius per standard detail. Locate bend away fromconcrete interface

#4 dowel @ 24" o.c. at two pour system alternate only

NOTES:A. See engineer where curb height exceds 18"

B. See detail 101 for additional information

102

Concrete footing (see plan for size & reinforcing)

Concrete slab on grade (see Structural General Notes for thickness & reinforcement)

Steel Reinforcing per plan

#4 dowel @ 48" o.c. at optional cold joint

or

Optional cold joint

103

Existing concrete footing

Existing wood wall per plan

Concrete slab on grade (see Structural General Notes for thickness & reinforcement)

Drill & epoxy reinforcing dowel into existing footing with Simpson Set-XP epoxy per manufacturers specifications. Provide 6" min. embedment.

104

Existing concrete footing

Existing wood wall per plan

Concrete slab on grade (see Structural General Notes for thickness & reinforcement)

Drill & epoxy reinforcing dowel into existing footing with Simpson Set-XP epoxy per manufacturers specifications. Provide 6" min. embedment.

105

Concrete footing (see plan for size & reinforcing)

Existing concrete footing

Drill & epoxy reiniforcing into existing footing with Simpson SET epoxy. Provide 4" min. embedment.

106

New concrete footing (see plan for size and reinforcing)

Wood wall per plan

Existing concrete slab on grade

#4 dowels @ 24" o.c.

Drill & epoxy into existing slab with Simpson SET. Provide 4" min embedment

107

Wood post per plan (where post is

Simpson post base (as occurs)

3" clr

3" c

lr

Concrete footing (see plan for size & reinforcing)

Footing embedment per plan or

Existing concrete slab on grade

Structural General Notes

#4 dowel (18" long). Drill & epoxy into existing slab with Simpson SET epoxy. Provide 6" embedment onto existing slab.

Saw cut slab for new footing

incorporated into wall, post base may be eliminated)

108

Simpson HDU type holddown with

Framing per plan

anchor per plan

Bottom plate attachment per plan or S.G.N.

See S.G.N. for anchor bolt diameter and embedment

109

Page 6: Structural General Notes - 06.22.10... · indicated in the basis of design. 9. Dowel all vertical reinforcing to foundation, as specified on plans or details. Securely tie all bars

Floor & Low Roof Framing PlanSCALE = 3/16"=1'-0"

Floor and Low Roof Framing Plan Notes

Roof sheathing shall be 15/32" A.P.A. rated sheathing. See General Details for diaphragm attachment.

1.

Roof framing members shown on plan indicate manufactured roof trusses spaced per the manufacturer (24" o.c. typical).

3.

Typical joint splice of the perimeter (2) 2x top plate shall have a minimum of 4'-0" overlap with (20) 16d each side of the joint. Nails shall be staggered and evenly spaced (see General Details). Top plate splice shall be located away from marked shearwalls. Where it is not feasible to overlap the top plate as indicated, a Simpson MST37 strap shall be installed, centered on the splice, and fully nailed.

4.

All exterior walls, and interior bearing walls, shall be framed with 2x6 studs at 16" o.c. unless noted otherwise on the plans. Provide (1) trimmer stud and (1) king stud at all openings in wood framed wall.

5.

"D=xxx#" indicates drag load to be included in the appropriate load combinations by the truss manufacturer.

6.

Floor and Low Roof Framing Plan Keynotes

2x blocking at top chord of truss with Simpson CMSTC16 strap over sheathing. Extend strap beyond end of blocking onto panel blocking / truss / beam / etc. 30" with maximum nailing required by strap manufacturer.

1

Sheath and strap with Simpson CMSTC16 strap above and below window opening per Large Opening In Shearwall detail (See General Details).

2

Floor sheathing shall be 3/4" or 1 1/8" A.P.A. rated sheathing. See General Details for diaphragm attachment.

2.

7. indicates dead & live loading to be included in the appropriate load combinations by the truss manufacturer.

DL=xxx#

LL=xxx#

8. indicates short term load to be included in the appropriate load combinations by the truss manufacturer. May act up or down.

ST=xxx#

Casita Roof Framing PlanSCALE = 3/16"=1'-0"

DL=715#LL=450#

3

Roof/Floor combination trusses.3

DL=1707#

LL=1732#

DL=2233#LL=2438#

DL=2403#LL=2584#

DL=1743#LL=1726#

DL=522#LL=405#

4x blocking - Provide 4x6 blocking at top chord of truss with Simpson HU46TF hangers at each end.

4

4 4 4 4

4 4

3 3

Overbuild framing per general details.5

5

Girder Truss Girder Truss

Gird

er Tr

uss

4x66x8

6x10

6x8

6x8

6x6

4x10

6x10

6x8

6x12

6x12

6x10

518x9 GLB

51 8x10

1 2 GLB

1214x24 GLB10

34x

221 2 G

LB

(3)1114" LVL (cant'l)

(2)16" LVL

(3)2x6(3)2x6

(2)2x6 TS(3)2x6 KS

(2)2x6 TS(3)2x6 KS

(4)2x6

(4)2x6

(4)2x6 TS(3)2x6 KS

(3)2x6 TS(3)2x6 KS

(5)2x4

(3)2x4

Parallam column - provide a 7x7 Level 1 Wolmanized Parallam column.

6

6

(4)2x4

(4)2x6 (3)2x6(3)2x6

(2)2x6(3)2x6

(3)2x6

(3)2x6

(3)2x6

(3)2x6

(3)2x6

6x12 6x8 6x8 6x8

6x6 6x6

6x6

6x8

SW1L=16'-0"

SW2L=16'-0"

SW2L=16'-0"

SW1L=16'-0"

SW1

L=16

'-0"

SW1

L=14

'-0"

SW4

L=3'

-4"

SW4

L=3'

-4"

CS16 CS16

Plywood Shearwall Schedule and NotesMark Sheathing Thickness Edge Nailing A.B. Spacing at Foundation

Bottom Plate Nails at Floor *Min. Sill Plate

Thickness

SW1 8d at 6" o.c. 1/2" dia. A.B. at 32" o.c.16d at 6" o.c. 2x3/8" Plywood Blk'd

One Side of Wall

SW23/8" Plywood Blk'dOne Side of Wall

3" Nominal Framing at Panel Edges

8d at 4" o.c.Staggered

1/2" dia. A.B. at 12" o.c.16d at 5" o.c. 2x

3x1/2" dia. A.B. at 24" o.c.

SW33/8" Plywood Blk'dOne Side of Wall

3" Nominal Framing at Panel Edges

8d at 3" o.c.Staggered

1/2" dia. A.B. at 10" o.c.16d at 3" o.c.

2x

3x1/2" dia. A.B. at 20" o.c.

SW43/8" Plywood Blk'dOne Side of Wall

3" Nominal Framing at Panel Edges

8d at 2" o.c.Staggered

1/2" dia. A.B. at 8" o.c.

1/4" dia. x 6" long screwsat 6" o.c. 3x

15/32" Plywood Blk'dOne Side of Wall

3" Nominal Framingat Panel Edges

3x

SW6 3x1/2" dia. A.B. at 12" o.c. or

5/8" A.B. at 18" o.c.

1/4" dia. x 6" long screwsat 5" o.c.

1/2" dia. A.B. at 16" o.c.

1/4" dia. x 5" long screwsat 6" o.c.

8d at 2" o.c.Staggered

15/32" Plywood Blk'dOne Side of Wall

3" Nominal Framingat Panel Edges

10d at 2" o.c.Staggered

SW5

3/8" Plywood Blk'dBoth Sides of Wall

3" Nominal Framingat Panel Edges

3x

5/8" dia. A.B. at 16" o.c.

1/4" dia. x 5" long screwsat 4" o.c.

8d at 3" o.c.StaggeredSW7

15/32" Plywood Blk'dBoth Sides of Wall

3" Nominal Framingat Panel Edges

3x

5/8" dia. A.B. at 12" o.c.

1/4" dia. x 5" long screwsat 3" o.c.

10d at 4" o.c.StaggeredSW8

* Where 1 1/8" plywood is used for floor sheathing, use" 1/4 x 4" screws in lieu of 16d nails.

Notes:Shearwall studs shall be placed at 16" o.c. maximum. Framing and blocking at panel edges (where noted above) shal be 2x minimum, U.N.O.

A.

Provide (2) full height studs (minimum) at ends of shearwall, unless noted otherwise on plans, details, or holddown requirements. Shearwalls without holddowns require (1) stud at each end of shearwall (minimum). Trimmer stud may be counted as an end stud at non-bearing walls.

B.

Plywood may be installed either horizontally or vertically, U.N.O.C.

Use A.B. (Anchor Bolts) noted per S.G.N., details, and this schedule for bottom sill plate attachment at foundation. Use staggered nails as noted in this schedule for bottom plate attachment at elevated shearwalls. See S.G.N. for optional shot-pins and epoxy bolts where allowed by S.G.N.

D.

Use A.B. (Anchor Bolts) noted per S.G.N., details, and this schedule for bottom sill plate attachment at foundation. Use staggered nails as noted in this schedule for bottom plate attachment at elevated shearwalls. See S.G.N. for optional shot-pins and epoxy bolts where allowed by S.G.N.

E.

Where sheathing is interupted by intersecting wall, provide continuity channel per General Details.

F.

Multiple 2x studs at holddowns shall be stitch-nailed together with 16d sinkers at 6" o.c. (staggered).

G.

All field nailing shall be at 12" o.c. with the same size nail specified for egde nailing.

H.

2x

At existing footings, Simpson Titen HD screw anchors may be used in lieu of the anchor bolts indicated above. Provide 8" long Titen HD screw anchor of the same diameter and spacing as the anchor bolts indicated in the Plywood Shearwall Schedule above.

J.

201

201

201

201

301

302

303

304

305

304

305

306

307

308 308309 309

310

310

311sim

312sim

313sim

314sim

311sim

Where existing framing conditions differ from plans & details, the engineer of record shall be contacted to provide additional framing & detailing information.

9.

315typ

WNP610

HUSC410

WNP68

WNP610 WNP610

315typ

316typ

317typ

Wood ledger - provide 2x12 wood ledger with (9) 16d nails @ 16" o.c.

7

7

7

No changes to the shearwalls have been made to the Casita, therefore, no additional lateral analysis is required.

10.

Wood trellis per arch'l8

8

Page 7: Structural General Notes - 06.22.10... · indicated in the basis of design. 9. Dowel all vertical reinforcing to foundation, as specified on plans or details. Securely tie all bars

Roof Framing Plan Notes

Roof sheathing shall be 15/32" A.P.A. rated sheathing. See General Details for diaphragm attachment.

1.

Roof framing members shown on plan indicate manufactured roof trusses spaced per the manufacturer (24" o.c. typical).

2.

Typical joint splice of the perimeter (2) 2x top plate shall have a minimum of 4'-0" overlap with (20) 16d each side of the joint. Nails shall be staggered and evenly spaced (see General Details). Top plate splice shall be located away from marked shearwalls. Where it is not feasible to overlap the top plate as indicated, a Simpson MST37 strap shall be installed, centered on the splice, and fully nailed.

3.

All exterior walls, and interior bearing walls, shall be framed with 2x6 studs at 16" o.c. unless noted otherwise on the plans. Provide (1) trimmer stud and (1) king stud at all openings in wood framed wall.

4.

"D=xxx#" indicates drag load to be included in the appropriate load combinations by the truss manufacturer.

5.

Roof Framing Plan Keynotes

2x blocking at top chord of truss with Simpson CMSTC16 strap over sheathing. Extend strap beyond end of blocking onto panel blocking / truss / beam / etc. 30" with maximum nailing required by strap manufacturer.

1

Sheath and strap with Simpson CMSTC16 strap above and below window opening per Large Opening In Shearwall detail (See General Details).

2

Plywood Shearwall Schedule and NotesMark Sheathing Thickness Edge Nailing A.B. Spacing at Foundation

Bottom Plate Nails at Floor *Min. Sill Plate

Thickness

SW1 8d at 6" o.c. 1/2" dia. A.B. at 32" o.c.16d at 6" o.c.

2x3/8" Plywood Blk'dOne Side of Wall

SW23/8" Plywood Blk'dOne Side of Wall

3" Nominal Framing at Panel Edges

8d at 4" o.c.Staggered

1/2" dia. A.B. at 12" o.c.16d at 5" o.c.

2x

3x1/2" dia. A.B. at 24" o.c.

SW33/8" Plywood Blk'dOne Side of Wall

3" Nominal Framing at Panel Edges

8d at 3" o.c.Staggered

1/2" dia. A.B. at 10" o.c.16d at 3" o.c. 2x

3x1/2" dia. A.B. at 20" o.c.

SW43/8" Plywood Blk'dOne Side of Wall

3" Nominal Framing at Panel Edges

8d at 2" o.c.Staggered

1/2" dia. A.B. at 8" o.c.

1/4" dia. x 6" long screwsat 6" o.c. 3x

15/32" Plywood Blk'dOne Side of Wall

3" Nominal Framingat Panel Edges

3x

SW6 3x1/2" dia. A.B. at 12" o.c. or

5/8" A.B. at 18" o.c.

1/4" dia. x 6" long screwsat 5" o.c.

1/2" dia. A.B. at 16" o.c.

1/4" dia. x 5" long screwsat 6" o.c.

8d at 2" o.c.Staggered

15/32" Plywood Blk'dOne Side of Wall

3" Nominal Framingat Panel Edges

10d at 2" o.c.Staggered

SW5

3/8" Plywood Blk'dBoth Sides of Wall

3" Nominal Framingat Panel Edges

3x

5/8" dia. A.B. at 16" o.c.

1/4" dia. x 5" long screwsat 4" o.c.

8d at 3" o.c.StaggeredSW7

15/32" Plywood Blk'dBoth Sides of Wall

3" Nominal Framingat Panel Edges

3x

5/8" dia. A.B. at 12" o.c.

1/4" dia. x 5" long screwsat 3" o.c.

10d at 4" o.c.StaggeredSW8

* Where 1 1/8" plywood is used for floor sheathing, use" 1/4 x 4" screws in lieu of 16d nails.

Notes:Shearwall studs shall be placed at 16" o.c. maximum. Framing and blocking at panel edges (where noted above) shal be 2x minimum, U.N.O.

A.

Provide (2) full height studs (minimum) at ends of shearwall, unless noted otherwise on plans, details, or holddown requirements. Shearwalls without holddowns require (1) stud at each end of shearwall (minimum). Trimmer stud may be counted as an end stud at non-bearing walls.

B.

Plywood may be installed either horizontally or vertically, U.N.O.C.

Use A.B. (Anchor Bolts) noted per S.G.N., details, and this schedule for bottom sill plate attachment at foundation. Use staggered nails as noted in this schedule for bottom plate attachment at elevated shearwalls. See S.G.N. for optional shot-pins and epoxy bolts where allowed by S.G.N.

D.

Use A.B. (Anchor Bolts) noted per S.G.N., details, and this schedule for bottom sill plate attachment at foundation. Use staggered nails as noted in this schedule for bottom plate attachment at elevated shearwalls. See S.G.N. for optional shot-pins and epoxy bolts where allowed by S.G.N.

E.

Where sheathing is interupted by intersecting wall, provide continuity channel per General Details.

F.

Multiple 2x studs at holddowns shall be stitch-nailed together with 16d sinkers at 6" o.c. (staggered).

G.

All field nailing shall be at 12" o.c. with the same size nail specified for egde nailing.

H.

2x

Roof Framing PlanSCALE = 3/16"=1'-0"

Girder Truss

Girder Truss

Girder Truss

Gird

er Tr

uss

Gird

er Tr

uss

Gird

er Tr

uss

Gird

er Tr

uss

Gird

er Tr

uss

Gird

er Tr

uss

Gird

er Tr

uss

6x6

6x10

6x6 6x12

6x6 6x6

6x6

6x6

6x6

518x101

2 GLB

518x101

2 GLB 518x101

2 GLB

6x6

(3)2x6 (3)2x6

(3)2x6

(3)2x6

(3)2x6(3)2x6

(3)2x6

(3)2x6 (3)2x6

(3)2x6 (3)2x6

(3)2x6

(3)2x6

Skylight

(3)2x6

(3)2x6

(3)2x6

201

201

201

201

201

201

201high

204low

202high

202high

203low

203low

205

205

205

206

207

SW1L=16'-0"

SW1L=16'-0"

SW1L=7'-9"

SW1

L=12

'-0"

SW1

L=16

'-0"

SW1

L=8'

-0"

Sheath entire rotunda pony wall with SW1 per Plywood Shearwall Schedule below.

3

3

3

208sim

209typ

209typ

Page 8: Structural General Notes - 06.22.10... · indicated in the basis of design. 9. Dowel all vertical reinforcing to foundation, as specified on plans or details. Securely tie all bars

Edge nailing per StructuralGeneral Notes

Roof sheathing per plan

Roof truss per plan

Full height 2x blocking

Simpson LTP4 (or A35) @ each

Wood pony wall per plan

NOTES:Simpson A35 may be used in lieu of Simpson LTP4 at the builders

Build up top plate with 3/4"

block

plywood.

discretion

202

Edge nailing per Structural

Roof sheathing per plan

General Notes

Roof trusses per plan

Wood pony wall per plan

Bottom plate attachment per G.S.N.

Girder Truss per plan

Hanger per truss manufacturer

203

Edge nailing per Structural

Roof sheathing per plan

General Notes

Roof truss per plan

2x blocking

2x4 ledger with (2)16d nailsat 16" o.c. & (3)16d nails at each block

Wood pony wall per plan

Wood beam per plan

204

D=4

'-0" m

ax2/

3D

11

Edge nailing per StructuralGeneral Notes

Roof sheathing per plan

Manufactured flat roof truss

Simpson LTP4 @ each panel block

Wood wall per plan

Wood panel blocking per general details

Wood parapet wall. Sheathe both sides of wall per SW1 per shearwall schedule

2x4 kicker @ 48" o.c.

(3)16d nails

Simpson A34each side of each kicker

Continuous 2x member with (2)16d nails into top chord of truss (24" o.c.)

205

4'-0

" max

Edge nailing per StructuralGeneral Notes

Roof sheathing per plan

Flat roof trusses per plan

2x blocking

2x4 ledger with (2)16d nailsat 16" o.c. & (3)16d nails at each block

Wood wall per plan

206

Edge nailing per Structural

Roof sheathing per plan

General Notes

Roof truss per plan

Exisitng roof framing

2x blocking

Simpson LTP4 @ each block

Wood wall per plan

Overbuild framing per general detail

207

Edge nailing per StructuralGeneral Notes

Roof sheathing per plan

Roof truss per plan

Full height 2x blocking or panel blocking

Simpson LTP4 (or A35) @ each block

Wood wall per plan

Wood beam per plan

A B

NOTES:Simpson A35 may be used in lieu of Simpson LTP4 at the builders discretion

Truss tails per arch'l (as occurs)

201

.

Wood beam per plan

Wood post per plan

Simpson concealed flange hanger

208

Wood beam per plan

Wood wall per plan

Simpson ST6236 beam to top plate

(2) 2x post (minimum) unless noted otherwise on plan

(2) 2x king stud (minimum)

209

Page 9: Structural General Notes - 06.22.10... · indicated in the basis of design. 9. Dowel all vertical reinforcing to foundation, as specified on plans or details. Securely tie all bars

Edge nailing per StructuralGeneral Notes

Floor sheathing per plan

Floor truss per plan

Wood wall per plan

Simpson A35 brace to top chord

Simpson H2.5 (panel block to top chord

Simpson H2.5 (block to top chord)

2x blocking @ 48" o.c.

Panel blocking per general details

(3)16d nails brace to ladder truss

(4)16d @ 6" o.c.

301

Edge nailing per StructuralGeneral Notes

Floor sheathing per plan

Floor truss per plan

2x blocking

Wood wall per plan

Bottom plate attachment per plan or S.G.N.

Panel Blocking per general details

16d nails @ 4" o.c.

Continuous 2x let-in

8d nails @ 6" o.c.

SW1 sheathing per Shearwall Schedule

302

Floor truss per plan

Shear panel blocking per general details

Wood wall per plan

NOTES:Floor sheathing and edge nailing not shown for clarity. Provide edge nailing through sheathing into panel blocking

303

Edge nailing per StructuralGeneral Notes

Floor sheathing per plan

Floor truss per plan

Panel blocking per general details

Wood wall per plan

304

Edge nailing per StructuralGeneral Notes

Floor sheathing per plan

Floor truss per plan

2x blocking

Simpson A35 @ each block

Wood beam per plan

Additional framing as occurs

End of truss (beyond)

305

Edge nailing per StructuralGeneral Notes

Floor sheathing per plan

Floor truss per plan

Wood wall per plan

Wood beam per plan

306

Roof sheathing per plan

Floor sheathing per plan

Edge nailing per StructuralGeneral Notes

Roof/floor combo truss per plan

2x4 blocking with (3) 16d nails at each block

4x6 blocking with Simpson HU46TF hanger at each end of block

Wood pony wall/railing per plan

307

Edge nailing per StructuralGeneral Notes

Floor sheathing per plan

Floor truss per plan

Hanger per truss manufacturer

Wood wall per plan

2x4 blocking with (3) 16d nails at each block

2x blocking

Wood beam/Girder Truss per plan

Wood cripple wall. Sheath cripple wall with SW1 per shearwall schedule

308

Edge nailing per StructuralGeneral Notes

Floor sheathing per plan

Floor truss per plan

Wood cripple wall per plan. Sheath cripple wall with SW1 per

Wood beam/Girder Truss per plan

shearwall schedule

309

Page 10: Structural General Notes - 06.22.10... · indicated in the basis of design. 9. Dowel all vertical reinforcing to foundation, as specified on plans or details. Securely tie all bars

d)

Edge nailing per StructuralGeneral Notes

Roof sheathing per plan

Floor sheathing per plan

Roof truss per plan

Floor truss per plan

Hanger per truss manufacturer

2x4 blocking with (3) 16d nails at each block

Wood wall per plan

Wood beam/Girder Truss per plan

Wood cripple wall. Sheath cripplewall with SW1 per shearwallschedule

310

Edge nailing per StructuralGeneral Notes

Existing roof sheathing

Floor sheathing per plan

Existing roof truss

Floor truss per plan

Hanger per truss manufacturer

2x blocking

2x4 ledger with (2)16d nailsat 16" o.c. & (3)16d nails at each block

Wood wall per plan

Ledger per plan

Shear panel blocking per general details

311

Edge nailing per StructuralGeneral Notes

Existing roof sheathing

Floor sheathing per plan

Existing roof truss

Floor truss per plan

Hanger per truss manufacturer

2x blocking

2x4 ledger with (2)16d nailsat 16" o.c. & (3)16d nails at each block

Wood wall per plan

Ledger per plan

NOTES:See Detail 301 for additional detailing information

312

Edge nailing per Structural

Roof sheathing per plan

Floor sheathing per plan

Roof truss per plan

Floor truss per plan

General Notes

2x blocking

2x4 ledger with (2)16d nailsat 16" o.c. & (3)16d nails at each block

Wood wall per plan

313

Edge nailing per StructuralGeneral Notes

Roof sheathing per plan

Floor sheathing per plan

Roof truss per plan

Floor truss per plan

Wood wall per plan

Wood beam per plan

Wood cripple wall. Sheath cripplewall with SW1 per shearwallschedule (as occurs)

2x blocking

2x4 ledger with (2)16d nailsat 16" o.c. & (3)16d nails at each block

314

Wood beam per plan

Simpson hanger per plan

315

Wood wall per plan

Wood beam per plan

Wood post per plan

Simpson MSTC48 strap beam to beam

Simpson LTP4 @ each side

316

Wood wall per plan

Wood beam per plan

Wood post per plan

Simpson A35 each side of beam

317