STRESSING DETAILS. U.T.S.OF 15.2mm H.T.STRAND : 26.56 TONS TENSIONING AREA OF VSIL JACK : 53.2 SQ.CM DESIGNED PRESTRESSING FORCE 70% OF UTS: 18.59 TONS ACTUAL PRESSURE TO BE APPLIED AT SITE 18.59 X 1000 / 53.2 = 349 KG/ SQ CM SAY 350 KG/ SQ CM. AS PER CODE 5% +/- TOLERANCE IS ACCEPTABLE IN PRESSURE READING. KINDLY NOTE PRESSURE IS A CRITERIA FOR STRESSING ELONGATION IS TO BE NOTED AS ACTUAL. FOR M/s.VSIL
-