STL-Latest NEW30 july 2016 · Multiple module available with mullion. Applications : Sand Trap...
Transcript of STL-Latest NEW30 july 2016 · Multiple module available with mullion. Applications : Sand Trap...
S. No Description Page No
1 General Information 1
2 Various Models 2
3
4
5
6
7
8-13
13
14
3 STL - B-10 Series
4 STL - BC-20 Series
STL - B-30 Series
STL - B-40 Series
5
6
7
8
9
10 Installation Details
Multiple Assembly
Ordering Data
Table Of Contents
Engineering and Performance Data
LISTED
Sand Trap Louvers
Sand Trap Louver - STL
BETEC CAD. manufactures Sand Trap Louvers for fresh air intake in HVAC systems, which are designed to separate sand and dust particles at low and medium air velocities thus avoiding excessive dust loading on conventional secondary stage filters. They give excellent performance for air filtration and moderate pressure drops at low air velocities.
Drainage holes at the bottom of Sand Trap Louver makes it self cleaning and maintenance free.
Material Details • All types and models of Sand Trap Louvers are available in Galvanized Steel, Stainless Steel & Aluminium according to the design and application.
Sheet Metal Galvanized Steel (GI)Zinc coating Z-22 to Z-27 as per ASTM-A653 Standards.
Sheet Metal Aluminium (AL)Aluminium Sheet as per Alloy A1100 Standards. Extruded aluminium as per Alloy 6063 A Standards.
Sheet Metal Stainless Steel (SS)Stainless steel 304 / 316L.
Note:* Indicates BETEC CAD’s Standard Construction
Applications:
GI Construction : For HVAC commercial,Residential etc.AL Construction : For Hospitals,Labs,Green Building etc.SS Construction : For Offshore, Oil & Gas etc.
The respective alphabet indicates the type of materialG - Galvanized steel (GI)S - Stainless steel (SS) A - Aluminum (AL)
Alphabet indicates the type of installation. A - Wall Mouted. B - Duct Mounted. C - Flush Mounted.
Item Series Blade Width Model Material Options Blade
11-100* A-Exposed Plain*
B-Duct Mounted Filter
C-Flushed Filter+Damper
21-100 A-Exposed Plain*
B-Duct Mounted Filter
C-Flushed Filter+Damper
31-100* A-Exposed Plain*
B-Duct Mounted Filter
C-Flushed Filter+Damper
41-100* A-Exposed Plain*
B-Duct Mounted Filter
C-Flushed Filter+Damper
Standard Types and Models
12-130
B-40Heavy Duty 42-130
A*, G ,S
A*, G ,S
A*, G ,S
A*, G ,S
B-10
B-2022-130*
B-3032-150
Square
Square
Curved
Square
STL
1
BETEC CAD. Sand Trap louver's construction confirms to ADC 1602 standard and DW 142 class C.
STL-AB-11A
LISTED
Sand Trap Louvers
Sand Trap LouversBETEC CAD. Manufactures variety of models.B-10 Series 1. STL-AB-11A (AMCA500-L Tested) /12 A/BExposed type with square blade
2. STL-AB-11CFlushed type with square blade
B-20 Series 1. STL-AB-21/22 A/BExposed type with square blade
2. STL-AB-22C (AMCA500-L Tested) Flushed type with square blade
B-30 Series 1. STL-AB-31/32 A/BExposed type with curved blade
2. STL-AB-31/32 CFlushed type with curved blade
B-40 Series 1. STL-AB-41/42 A/BExposed type with square blade
2. STL-AB-41/42 CFlushed type with square blade
STL-AB-11A
STL-AB-21A
STL-AB-31A STL-AB-31C
STL-AB-41CSTL-AB-41A
STL-AB-22C
STL-AB-11C
LISTED
Sand Trap Louvers
2
AMCA500 - L Tested Sand Trap Louver B-10 Series
Standard ConstructionFrame1.2 mm thick extruded aluminum profile.Blade1.2 mm thick extruded aluminum profile.Blade OrientationVertical.Blade TypeU Shaped 100 mm.ScreenGalvanized Steel 0.4 mm thickness.FinishMill finish.
For Light / Medium duty applicationsModel: STL-AB-11A (AMCA 500-L); Blade Width: 1 – 100* mm; 2 – 130 mm Type : A - Wall Mounted; B - Duct Mounted ; C - Flush Mounted
BladeU Shaped 130 mm. ScreenS-3 SS Bird ScreenS-10 SS Fly Screen Filter13 / 25 mm thickness aluminum media filter.DamperControl DamperMounting AnglesMounting frame and angle flange.FinishAvailable with RAL powder coating, please specify color.
Material Thickness Material Thickness
STL-AB-11/12A/B/C AL 1.2* mm AL 1.2* mmSTL-GB-11/12A/B/C GI 1.2 mm GI 0.9 mm
STL-SB-11/12A/B/C SS 1.2 mm SS 0.9 mm
Frame Blade
Model
B-10 Series Model Details
Optional Fittings
Optional Construction DetailsFrame : Thickness up to 4 mmBlade : Thickness up to 4 mm
Alphabet indicates the type of installationA - Wall MountedB - Duct MountedC - Flush Mounted
Note : Please contact BETEC CAD. for customized design and specification.
Applications :Sand Trap Louvers B-11 Light duty and B-12 Medium duty model construction, are suitable for the duct or wall mounting applications in HVAC systems, where excessive intake air filtration is required for ventilation purpose.
Sand Trap Louvers fitted with filters and dampers are suitable for the AHU's applications for fresh air intake.
•
•
Note: Maximum single module construction - 3 x 1.8 metersMultiple module available with mullion.
STL-AB10-A/B STL-AB10-A+F STL-AB10-A+F+DSTL-AB10-C+F
3
Any Combination of W x H
W in Inchs 4" 6" 8" 10" 12" 14" 16" 18" 20" 22" 24" 26" 28" 30"
H in inches 4" 6" 8" 10" 12" 14" 16" 18" 20" 22" 24" 26" 28" 30"
STL-AB-11/12
LISTED
Sand Trap Louvers
AMCA500 - L Tested Sand Trap Louver B-20 Series
Standard ConstructionFrame1.5 mm thick aluminium roll formed profile.Blade1.2 mm thick aluminium roll formed profile.Blade OrientationVertical.Blade TypeU Shaped 130 mm.ScreenGalvanized Steel 0.4 mm thickness.FinishMill finish.
For Light / Medium duty applicationsModel: STL-AB-22C (AMCA 500-L); Blade Width: 1 – 100 mm; 2 – 130* mm Type : A - Wall Mounted ; B - Duct Mounted; C - Flush Mounted
Optional Fittings
BladeU Shaped 100 mm.ScreenS-3 SS Bird ScreenS-10 SS Fly Screen Filter13 / 25 mm thickness aluminum media filter.DamperControl DamperMounting AnglesMounting frame and angle flange.FinishAvailable with RAL powder coating, please specify color.
Note: Maximum single module construction - 3 x 2 metersMultiple module available with mullion.
Applications :Sand Trap Louvers AB-21 Light duty and AB-22 Medium duty model construction, are suitable for the duct or wall mounting applications in HVAC systems, where excessive intake air filtration is required for ventilation purpose.
Sand Trap Louvers fitted with filters and dampers are suitable for the AHU's applications for fresh air intake.
•
•
Note : Please contact BETEC CAD. for customized design and specification.
STL-AB-20C STL-AB-20C
4
Any Combination of W x H
W in Inchs 4" 6" 8" 10" 12" 14" 16" 18" 20" 22" 24" 26" 28" 30"
H in inches 4" 6" 8" 10" 12" 14" 16" 18" 20" 22" 24" 26" 28" 30"
STL-AB-21/22
LISTED
Sand Trap Louvers
Material Thickness Material Thickness
STL-AB-21/22A/B/C AL 1.5* mm AL 1.2* mmSTL-GB-21/22A/B/C GI 1.5 mm GI 1.2 mm
STL-SB-2122A/B/C SS 1.2 mm SS 0.9 mm
Frame Blade
Model
B-20 Series Model Details
Alphabet indicates the type of installationA - Wall MountedB - Duct MountedC - Flush Mounted
Sand Trap Louver B-30 Series
Standard ConstructionFrame1.2 mm thick extruded aluminum profile.Blade0.9 mm thick roll formed aluminum curved profile.Blade OrientationVertical.Blade TypeCurved type 100 mm. ScreenGalvanized Steel 0.4 mm thickness.FinishMill finish.
For Light / Medium duty applicationsModel: STL-AB-31A; Blade Width: 1 – 100* mm; 2 – 150 mm Type : A - Wall Mounted; B - Duct Mounted; C - Flush Mounted
Optional Fittings
Optional Construction DetailsFrame : Thickness up to 4 mm Blade : Thickness up to 4 mm
Alphabet indicates the type of installationA - Wall MountedB - Duct MountedC - Flush Mounted
BladeCurved type 150 mm. ScreenS-3 SS Bird ScreenS-10 SS Fly Screen Filter13 / 25 mm thickness aluminum media filter.DamperControl Damper.Mounting AnglesMounting frame and angle flange.FinishAvailable with RAL powder coating, please specify color.
Material Thickness Material Thickness
STL-AB-31/32A/B/C AL 1.2 mm AL 0.9 mmSTL-GB-31/32A/B/C GI 1.2 mm GI 0.9 mm
STL-SB-31/32A/B/C SS 1.2 mm SS 0.9 mm
Frame Blade
Model
B-30 Series Model Details
Applications :Sand Trap Louvers B-31 Light duty and B-32 Medium duty model construction, are suitable for the duct or wall mounting applications in HVAC systems, where excessive intake air filtration is required for ventilation purpose.
Sand Trap Louvers fitted with filters and dampers are suitable for the AHU's applications for fresh air intake.
•
•
Note: Maximum single module construction - 3 x 1.5 metersMultiple module available with mullion.
Note : Please contact BETEC CAD. for customized design and specification.
STL-AB-30A/B STL-AB-30A+F STL-AB-30C+F STL-AB-30A+F+D
5
Any Combination of W x H
W in Inchs 4" 6" 8" 10" 12" 14" 16" 18" 20" 22" 24" 26" 28" 30"
H in inches 4" 6" 8" 10" 12" 14" 16" 18" 20" 22" 24" 26" 28" 30"
STL-AB-31/32
LISTED
Sand Trap Louvers
Sand Trap Louver B-40 Series
Standard ConstructionFrame2 mm thick extruded aluminum profile.Blade2 mm thick extruded aluminum profile.Blade OrientationVerticalBlade TypeU Shaped 100 mm ScreenGalvanized Steel 0.4 mm thickness.FinishMill finish.
For Heavy duty applicationsModel: STL-AB-41A; Blade Width: 1 – 100* mm; 2 – 130 mm Type : A - Wall Mounted; B - Duct Mounted; C - Flush Mounted
Optional Fittings
BladeU Shaped 130 mm ScreenS-3 SS Bird ScreenS-10 SS Fly Screen Filter13 / 25 mm thickness aluminum media filter.DamperControl DamperMounting AnglesMounting frame and angle flange.FinishAvailable with powder coating, please specify color.
Alphabet indicates the type of installationA - Wall MountedB - Duct MountedC - Flush Mounted
Note: Maximum single module construction - 3 x 2.5 metersMultiple module available with mullion.
150
STL -AB-40A/B/C STL -AB-40A+F STL -AB-40C+F STL -AB-40A+F+D
FilterFilter
6
Note : Please contact BETEC CAD. for customized design and specification.
Material Thickness Material Thickness
STL-AB-41/42A/B/C AL 2 mm AL 2 mmSTL-GB-41/42A/B/C GI 2 mm GI 2 mm
STL-SB-41/42A/B/C SS 2 mm SS 2 mm
Frame Blade
Model
B-40 Series Model Details
Optional Construction DetailsFrame : Thickness up to 4 mm Blade : Thickness up to 4 mm Any Combination of W x H
W in Inchs 4" 6" 8" 10" 12" 14" 16" 18" 20" 22" 24" 26" 28" 30"
H in inches 4" 6" 8" 10" 12" 14" 16" 18" 20" 22" 24" 26" 28" 30"
STL-AB-41/42
Applications :Sand Trap Louvers B-41 and B-42 Heavy duty model construction, are suitable for the duct or wall mounting applications in HVAC systems, where excessive intake air filtration is required for ventilation purpose.
Sand Trap Louvers fitted with filters and dampers are suitable for the AHU's applications for fresh air intake.
•
•
LISTED
Sand Trap Louvers
Sand Trap Louver - STL B-10/20/30/40 SeriesOptional Constructions - Model : STL-B-10/20/30/40 + F1+D+F2+F3
Stage Sand Particle in Microns (µ) % Efficiency
Stage 1 150 - 700 60 - 75%
Stage 2 75 - 150 75%
Stage 3 75 - 150 75%
Stage 4 25 - 100 90%
Stage 5 10 - 50 96%
Note : Stage 3 will not effect filtration of sand particles & efficiency.
Model : STL-B-10/20/30/40 + F1+D+F2+F3Sand Filtration Efficiency at different stages at face velocity Vf = 1mt/sec. For STL with Multiple Assembly Construction.
7LISTED
Sand Trap Louvers
Sand Trap Louver - STL B-10 SeriesEngineering and Performance Data
Selection table for Model : STL-AB-11A
Model : STL-AB-11A Pressure Drop V/S Face Velocity Graph. as per AMCA500-L
AMCA Standard 500-L Water Penetration Test (15 minutes Test Duration )
The Beginning point of water penetration is 375 fpm. Setup for Size: 48” x 48”
AMCA Standard 500-L Intake / Exhaust Test
Data is corrected to standard air density.
Pres
sure
(in.
wg)
0.01
0.3
0 100 200 300 400 450 500 550 600 650
Wat
er P
enet
ratio
n (o
z. w
tr./s
q.ft
free
are
a)
Free Area Velocity (fpm)
0.2
0.1
*
350
Setup for Size: 48” x 48”
8LISTED
Sand Trap Louvers
W/H 300 450 600 750 900 1050 1200 1500 1800 2100 2400
300 0.010 0.018 0.025 0.033 0.040 0.048 0.055 0.070 0.085 0.100 0.115450 0.020 0.035 0.050 0.065 0.080 0.095 0.110 0.140 0.170 0.200 0.230600 0.030 0.053 0.075 0.098 0.120 0.143 0.165 0.210 0.255 0.300 0.345750 0.040 0.070 0.100 0.130 0.160 0.190 0.220 0.280 0.340 0.400 0.460900 0.050 0.088 0.125 0.163 0.200 0.238 0.275 0.350 0.425 0.500 0.5751050 0.060 0.105 0.150 0.195 0.240 0.285 0.330 0.420 0.510 0.600 0.6901200 0.070 0.123 0.175 0.228 0.280 0.333 0.385 0.490 0.595 0.700 0.8051500 0.091 0.158 0.226 0.293 0.361 0.428 0.496 0.630 0.765 0.900 1.0351800 0.111 0.193 0.276 0.358 0.441 0.523 0.606 0.771 0.936 1.101 1.2652100 0.131 0.228 0.326 0.423 0.521 0.618 0.716 0.911 1.106 1.301 1.4962400 0.151 0.264 0.376 0.488 0.601 0.713 0.826 1.051 1.276 1.501 1.726
1220 x 1200 mm Louver free area 0.385 Sq.mt
Free area Ak in mt2 For Model : STL-AB-11A AMCA500-L Tested.
Inta
keEx
haus
t
Sand Trap Louver - STL B-20 SeriesEngineering and Performance Data
Selection table for Model : STL-AB-22C
Model : ST L-AB-22C Pressure Drop V/S Face Velocity Graph. as per AMCA500 - L
Data is corrected to standard air density.
AMCA Standard 500-L Water Penetration Test (15 minutes Test Duration )
The Beginning point of water penetration is 656 fpm.
0.01
0.3
600 650 700 750 800 850 900 950 1000 1050
Wat
er P
enet
ratio
n (o
z. w
tr./s
q.ft
free
are
a)
Free Area Velocity (fpm)
0.2
0.1
Pres
sure
(in.
wg)
9.9999998
1
0.1
0.01 100 1000 10000
*
Figure 5.6 Setup for Size: 48” x 48” Figure 5.5 Setup for Size: 48” x 48”
9
W / H 300 450 600 750 900 1050 1200 1350 1500
300 0.016 0.024 0.033 0.041 0.049 0.057 0.065 0.073 0.081
450 0.024 0.037 0.049 0.061 0.073 0.085 0.098 0.110 0.122
600 0.033 0.049 0.065 0.081 0.098 0.114 0.130 0.146 0.163
750 0.041 0.061 0.081 0.102 0.122 0.142 0.163 0.183 0.203
900 0.049 0.073 0.098 0.122 0.146 0.171 0.195 0.219 0.244
1050 0.057 0.085 0.114 0.142 0.171 0.199 0.228 0.256 0.284
1200 0.065 0.098 0.130 0.163 0.195 0.228 0.260 0.293 0.325
1350 0.073 0.110 0.146 0.183 0.219 0.256 0.293 0.329 0.366
1500 0.081 0.122 0.163 0.203 0.244 0.284 0.325 0.366 0.406
1220 x 1220 mm Louver free area 0.260 Sq.mt
Free area Ak in mt2 For Model : STL-AB-22C AMCA500-L Tested.
LISTED
Sand Trap Louvers
Inta
keEx
haus
t
AMCA Standard 500-L Intake / Exhaust Test
Sand Trap Louver - STL B-10/20 SeriesEngineering and Performance Data
0%
20%
40%
60%
80%
100%
120%
0.00 1.00 2.00 3.00 4.00
Rej
ecte
d sa
nd %
Face velocity m/s
Effectiveness of Louv re with Simulated sand with Filter
0%
20%
40%
60%
80%
100%
120%
0.00 1.00 2.00 3.00 4.00
Rej
ecte
d sa
nd %
Face velocity m/s
Effectiveness of Louv re with Simulated sand without Filter
0%
10%
20%
30%
40%
50%
60%
70%
80%
90%
100%
0.00 1.00 2.00 3.00 4.00
Rej
ecte
d sa
nd %
Face velocity m/s
Effectiveness of Louver with Simulated sand
0%
10%
20%
30%
40%
50%
60%
70%
80%
90%
100%
0.00 1.00 2.00 3.00 4.00
Rej
ecte
d sa
nd %
Face velocity m/s
Effectiveness of Louver with Simulated sand without Filterwith Filter
Model : STL-AB-11A Sand Rejection V/S Face Velocity Graph. (as per BSRIA)
Model : STL-BC-22C Sand Rejection V/S Face Velocity Graph. (as per BSRIA)
Description
Face Velocity 0.5 mt /s 1.0 mt /s 0.5 mt /s 1.0 mt /s 0.5 mt /s 1.0 mt /s
Partical Size 150-700 150-700 75-150 75-150 75-150 75-150
% Efficiency 89% 75% 92% 78% 98% 96%
STL
Sand Rejection Efficiency (as per BSRIA) Model : STL-BC-22CSTL + F1 STL+F1+D+F2+F3
Sand Rejection Efficiency (as per BSRIA) Model : STL-AB-11
Description STL STL + F1 STL+F1+D+F2+F3
Face Velocity 0.5 mt /s 1.0 mt /s 0.5 mt /s 1.0 mt /s 0.5 mt /s 1.0 mt /s
Partical Size 150-700 150-700 75-150 75-150 75-150 75-150
% Efficiency 92% 75% 95% 77% 98% 96%
10LISTED
Sand Trap Louvers
Sand Trap Louver - STL B-30 Series
W X H 300 450 600 750 900 1050 1200 1350 1500
300 0.045 0.068 0.090 0.113 0.135 0.158 0.176 0.198 0.221
450 0.068 0.101 0.135 0.169 0.203 0.236 0.265 0.298 0.331
600 0.090 0.135 0.180 0.225 0.270 0.315 0.353 0.397 0.441
750 0.113 0.169 0.225 0.281 0.338 0.394 0.441 0.496 0.551
900 0.135 0.203 0.270 0.338 0.405 0.473 0.529 0.595 0.662
1050 0.158 0.236 0.135 0.394 0.473 0.551 0.617 0.695 0.772
1200 0.176 0.265 0.353 0.441 0.529 0.617 0.706 0.794 0.882
1350 0.198 0.298 0.397 0.496 0.595 0.695 0.794 0.893 0.992
1500 0.221 0.331 0.441 0.551 0.662 0.772 0.882 0.992 1.103
Free area Ak in mt2 For Model : STL-AB-30
Pres
sure
(in.
wg)
9.9999998
1
0.1
0.01 100 1000 10000
0%
10%
20%
30%
40%
50%
60%
70%
80%
90%
100%
0.00 1.00 2.00 3.00 4.00
Rej
ecte
d sa
nd %
Face velocity m/s
Effectiveness of Louvre with Simulated sand with filter
0%
10%
20%
30%
40%
50%
60%
70%
80%
90%
100%
0.00 1.00 2.00 3.00 4.00
Rej
ecte
d sa
nd %
Face velocity m/s
Effectiveness of Louvre with Simulated sand without filter
Engineering and Performance DataSelection table for Model : STL-AB-30
Model : STL-AB-30 Sand Rejection V/S Face Velocity Graph. Model : STL-AB-30 Pressure Drop V/S Face Velocity Graph.
Description
Face Velocity 0.5 mt /s 1.0 mt /s 0.5 mt /s 1.0 mt /s 0.5 mt /s 1.0 mt /s
Partical Size 150-700 150-700 75-150 75-150 75-150 75-150
% Efficiency 89% 75% 92% 78% 98% 96%
STL
Sand Rejection Efficiency Model : STL-AB-30STL + F1 STL+F1+D+F2+F3
11LISTED
Sand Trap Louvers
Inta
keEx
haus
t
Sand Trap Louver - STL B-40 SeriesEngineering and Performance DataSelection table for Model : STL-AB-40
W/H 300 450 600 750 900 1050 1200 1500
300 0.007 0.014 0.021 0.029 0.036 0.043 0.050 0.065
450 0.014 0.029 0.043 0.058 0.072 0.087 0.101 0.130
600 0.021 0.043 0.065 0.087 0.108 0.130 0.152 0.195
750 0.029 0.058 0.087 0.116 0.145 0.174 0.203 0.261
900 0.036 0.072 0.108 0.145 0.181 0.217 0.253 0.326
1050 0.043 0.087 0.130 0.174 0.217 0.261 0.304 0.391
1200 0.050 0.101 0.152 0.203 0.253 0.304 0.355 0.456
1500 0.065 0.130 0.195 0.261 0.326 0.391 0.456 0.587
Free area Ak in mt2 For Model: STL-AB-40
Model : STL-AB-40 Sand Rejection V/S Face Velocity Graph. Model : STL-AB-40 Pressure Drop V/S Face Velocity Graph.
9.9999998
1
0.1
0.01 100 1000 10000
0%
10%
20%
30%
40%
50%
60%
70%
80%
90%
100%
0.00 1.00 2.00 3.00 4.00
Rej
ecte
d sa
nd %
Face velocity m/s
Effectiveness of Louver with Simulated sand with filter
0%
10%
20%
30%
40%
50%
60%
70%
80%
90%
100%
0.00 1.00 2.00 3.00 4.00
Rej
ecte
d sa
nd %
Face velocity m/s
Effectiveness of Louver with Simulated sand without filter
Sand Rejection Efficiency Model : STL-AB-40Description STL STL + F1 STL+F1+D+F2+F3
Face Velocity 0.5 mt /s 1.0 mt /s 0.5 mt /s 1.0 mt /s 0.5 mt /s 1.0 mt /s
Partical Size 150-700 150-700 75-150 75-150 75-150 75-150
% Efficiency 92% 75% 95% 77% 98% 96%
12LISTED
Sand Trap Louvers
Inta
keEx
haus
t
Pres
sure
(in.
wg)
Sand Trap Louver - STL B-10/20/30/40 SeriesEngineering and Performance DataPerformance data includes Air volume Qv, Effective free area Ak, Total pressure drop and corresponding Face velocities Vf .
Qv = Air volume in m³ /sec.
Vf = Face velocity in m/s.
Vk = Free area velocity in m/s
Ak = Free area in m²
Af = Face area in m²
Pt = Pressure drop in inch. w.g
______________________
Where;Face area (m²) = width (m) x height (m)
For known free area, face area is calculated as follows :
Face area (m²) = Freee area (m²) x 3
For known quantity of airflow, Face area is calculated as fllows :
Face area (m³/sec) = Air Volume Qv (m³ /sec.) Face velocity Vf(m³ /sec.)
STL
G
S
A
G
A
S
B
10
20
30
40
1
2
A
B
C
X X X X XFrame
MaterialBlade
Material SeriesBlade Type
Blade OperationSTL B
Sand Trap Louver Heavy Duty
Sand Trap Louver Curved Blades
Up to 100 mm Blade
Up to 150 mm Blade
Exposed / Wall mounting Type
Duct Mounting Type
Flush Mounting Type
Sand Trap Louver
Galvanized Steel
Stainless Steel
Aluminium
Galvanized
Aluminium
Stainless Steel
BETEC CAD.Sand Trap Louver ( AMCA 500-L)
Sand Trap Louver ( AMCA 500-L)
Ordering Data
13LISTED
Sand Trap Louvers
Note : 1) For blade type, add Series to blade type. For example: STL-AB-(10+1=11) A =STL-AB-11A.
2) If frame and blade material is same, use single alphabet. Example : STL-AB-11-A , where A = Aluminium Frame and Blade. STL-GB-11-A , where G = Galvanized Frame and Blade.
Sand Trap Louver - STL B-10/20/30/40 Series
Installation Details
Note : Fixing Details - Standard supply type screw fixingRecommended for side wall applications.
14LISTED
Sand Trap Louvers