Std. edition 12-7-07

24

Transcript of Std. edition 12-7-07

Page 1: Std. edition 12-7-07
Page 2: Std. edition 12-7-07

C6000 MIB- FS Series Operation & Maintenance Manual

(©Nov, 2007)

Air Technology Systems, Inc.

STULZ Air Technology Systems, Inc.Printed in the United States of America.All rights reserved.

12/07 Stulz Air Technology Systems, Inc.1572 Tilco DriveFrederick, MD 21704USA

Page 3: Std. edition 12-7-07

C6000/C7000 MIB- FS Series Operation & Maintenance Manual

Dec, 2007- Standard Edition i

TABLE OF CONTENTS

1.0 General Information ......................................................................................................1 1.1 Forward ...................................................................................................................................... 1 1.2 Safety ......................................................................................................................................... 1 1.2.1 General ...................................................................................................................................... 1 1.2.2 Safety Summary......................................................................................................................... 1 1.3 Product Warranty........................................................................................................................ 2

2.0 Description.....................................................................................................................3

3.0 Driver Scope of Supply .................................................................................................3 3.1 Supplied by FieldServer Technologies for this driver .................................................................. 3 3.2 Provided by the Supplier of 3rd Party Equipment........................................................................ 3 3.2.1 Required 3rd Party Hardware ..................................................................................................... 3 3.2.2 Required 3rd Party Configuration ............................................................................................... 3

4.0 Hardware Connections .................................................................................................4 4.1 Hardware Connection Tips / Hints .............................................................................................. 5

5.0 Installing New Firmware on a FieldServer...................................................................6

6.0 Configuring the FieldServer as a Stulz Client .............................................................8 6.1 Data Arrays/Descriptors.............................................................................................................. 8 6.2 Client Side Connection Descriptions........................................................................................... 9 6.3 Client Side Node Descriptors...................................................................................................... 9 6.4 Client Side Map Descriptors ..................................................................................................... 10 6.4.1 FieldServer Related Map Descriptor Parameters...................................................................... 10 6.4.2 Driver Related Map Descriptor Parameters .............................................................................. 10 6.4.3 Timing Parameters ................................................................................................................... 10 6.5 Map Descriptor Examples......................................................................................................... 11 6.5.1 The active read command ........................................................................................................ 11 6.5.2 Float and integer passive commands ....................................................................................... 11 6.5.3 Bit array passive commands..................................................................................................... 12

7.0 Product Support Group ..............................................................................................13 7.1.1 Technical Support..................................................................................................................... 13 7.2 Obtaining Warranty Parts ......................................................................................................... 13 7.3 Obtaining Spare/Replacement Parts......................................................................................... 13

APPENDICES

APPENDIX A Stulz Commands .......................................................................................... 14

APPENDIX B Troubleshooting Tips................................................................................... 18 Driver Limitations...................................................................................................... 18

APPENDIX C Glossary

Page 4: Std. edition 12-7-07

C6000/C7000 MIB- FS Series Operation & Maintenance Manual

1 Dec, 2007- Standard Edition

1.0 General Information

1.1 Forward

The C6000/C7000 MIB FS Series, (Multi Interface Board), covered by this manual is provided by Stulz Air Technology Systems, Inc. (SATS) using the latest, state-of-the-art control technology. Recognized as a world leader, SATS provides precision cooling systems and controls with the highest quality craftsmanship using the finest materials available in the industry. This device will provide years of trouble free service if installed and maintained in accordance with this manual. Damage to the unit from improper installation, operation or maintenance is not covered by the warranty.

This manual contains information for configuring, operating, and troubleshooting the MIB. STUDY the instructions contained in this manual. They must be followed to avoid difficulties. Spare parts are available from SATS to insure continuous operation. Using substitute parts or bypassing electrical components in order to continue operation is not recommended and will VOID THE WARRANTY. Due to technological advancements, components are subject to change without notice.

The FS Series Multi Interface Board is designed primarily to remotely interface with SATS models C6000™ or C7000™ controllers to manage an A/C system. Any use beyond this is deemed to be not intended. SATS is not liable for any damage resulting from improper use. All MIB’s are designed for indoor use.

1.2 Safety

1.2.1 General

Stulz Air Technology Systems, Inc. uses NOTES along with CAUTION and WARNING symbols to draw your attention to important operational and safety information.

A bold text NOTE marks a short message in the information to alert you to an important detail.

A bold text CAUTION safety alert appears with information that is important for protecting your equipment and performance. Be especially careful to read and follow all cautions that apply to your application.

A bold text WARNING safety alert appears with information that is important for protecting you from harm and the equipment from damage. Pay very close attention to all warnings that apply to your application.

A safety alert symbol accompanies a general WARNING or CAUTION safety statement.

A safety alert symbol accompanies an electrical shock hazard WARNING or CAUTION safety statement.

1.2.2 Safety Summary The following statements are general guidelines followed by warnings and cautions applicable throughout the manual.

CAUTION Prior to operating the unit, read and understand all instructions, recommendations and guidelines contained within this manual.

CAUTION All adjustments, maintenance and/or repairs must be performed by a qualified technician.

NOTE We recommend contacting SATS Product Support Group for assistance with adjusting or servicing your A/C unit.

WARNING If a fault occurs when operating the A/C unit or adjusting control parameters, it must be corrected immediately in accordance with the troubleshooting instructions for the A/C unit.

CAUTION Equipment may contain components subject to Electrostatic Discharge (ESD). Before attempting to mount or service these electronic devices, ensure you have no charge built up by touching a ground source. When possible, use a wrist-grounding strap when working on or near electronic devices.

Page 5: Std. edition 12-7-07

C6000/C7000 MIB- FS Series Operation & Maintenance Manual

Dec, 2007- Standard Edition 2

1.3 Product Warranty SATS offers a two year standard limited warranty as stated below.

2-Year Standard Limited Warranty:

Stulz Air Technology Systems, Inc., warrants to the original buyer of its products that the goods are free from defects in material and workmanship. Stulz Air Technology Systems, Inc.’s obligation under this warranty is to repair or replace, at its option, free of charge to the customer, any part or parts which are determined by Stulz Air Technology Systems Inc. to be defective for a period of 24 months from date of shipment when a completed start-up form has been submitted to Stulz Air Technology Systems, Inc. within 90 days from shipment. In the event that a completed start-up form is not received by Stulz Air Technology Systems, Inc. within 90 days from shipment, the company’s obligation will be for a period of 12 months from date of shipment. Parts repaired or replaced under this warranty are shipped FOB Factory, and warranted for the balance of the original warranty period or for 90 days from the date of installation, whichever is greater. Stulz Air Technology Systems, Inc.’s warranty does not cover failures caused by improper installation, abuse, misuse, misapplication, improper or lack of maintenance, negligence, accident, normal deterioration (including wear and tear), or the use of improper parts or improper repair. Purchaser’s remedies are limited to replacement or repair of non-conforming materials in accordance with the written warranty. This warranty does not include costs for transportation, costs for removal or reinstallation of equipment or labor for repairs or replacement made in the field. If any sample was shown to the buyer, such sample was used merely to illustrate the general type and quality of the product, and not to represent that the equipment would necessarily conform to the sample. This is the only warranty given by the seller, and such warranty is only given to buyers for commercial or industrial purposes. This warranty is not enforceable until the invoice(s) is paid in full. THE FOREGOING SHALL CONSTITUTE SATS’S ENTIRE LIABILITY AND YOUR EXCLUSIVE REMEDY. IN NO EVENT SHALL SATS BE LIABLE FOR ANY DIRECT, INDIRECT, SPECIAL, INCIDENTAL, CONSEQUENTIAL, OR EXEMPLARY DAMAGES, INCLUDING LOST PROFITS (EVEN IF ADVISED OF THE POSSIBILITY THEREOF) ARISING IN ANY WAY OUT OF THE INSTALLATION, USE OR MAINTENANCE OF THE EQUIPMENT. THIS WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE.

Page 6: Std. edition 12-7-07

C6000/C7000 MIB- FS Series Operation & Maintenance Manual

3 Dec, 2007- Standard Edition

2.0 Description The Stulz driver allows the transfer of data from a Stulz device using the Stulz monitoring protocol version1.7. The Field Server can act as a Client. Currently, only the C6000 controller is supported as the protocol only specifies read capabilities on that unit. The Client is configurable to read all information into separate data points and supports writing to selected points as specified below. It supports the following formats:

• Float values

• Binary values

• Integer values

Max Nodes Supported

FieldServer Mode Remote nodes Comments

Client 32 The protocol supports one Client per system, but 32 devices can be read on the system.

3.0 Driver Scope of Supply

3.1 Supplied by FieldServer Technologies for this driver FieldServer Technologies PART # Description FS-8700-125 Driver Manual FS-8917-16 RJ45 to terminal connector cable

3.2 Provided by the Supplier of 3rd Party Equipment

3.2.1 Required 3rd Party Hardware Part # Description None

3.2.2 Required 3rd Party Configuration None

Page 7: Std. edition 12-7-07

C6000/C7000 MIB- FS Series Operation & Maintenance Manual

Dec, 2007- Standard Edition 4

4.0 Hardware Connections The FieldServer is connected to the Stulz device as shown in the connection drawing. Configure the Stulz C6000 according to manufacturer’s instructions.

Page 8: Std. edition 12-7-07

C6000/C7000 MIB- FS Series Operation & Maintenance Manual

5 Dec, 2007- Standard Edition

4.1 Hardware Connection Tips / Hints

• Connect the wire to bus 1on the Stulz device. Make sure that bus 1 is used as bus 2 is used by the device to communicate with its I/O devices.

• Use shielded twisted pair wire to make connections.

• Use terminating resistors. The Stulz device has terminating resistors which can be set with a jumper.

• Make sure that line is terminated at both ends to ensure maximum communication efficiency.

• Further information on the C6000 is provided at the following address: http://ats.stulz.com/download/controllers/c6000.pdf

Page 9: Std. edition 12-7-07

C6000/C7000 MIB- FS Series Operation & Maintenance Manual

Dec, 2007- Standard Edition 6

5.0 Installing New Firmware on a FieldServer

1) Open the install.zip file. This can be done directly from your mail client.

2) If you are using WinZip then press the “Install” button. If you do not have WinZip then extract the files to a temporary folder and run the setup.exe program

3) If you have only one FieldServer on your network, then the firmware install procedure will start automatically after pressing “Install”

4) If you have multiple FieldServers on your network, then select the FieldServer that requires the new firmware to be installed from the menu shown.

5) In order to download config file other than the one included in the Install.zip file do the following:

If you are using Winzip:

• Rename the file you want to download to the FieldServer as config.csv

• Click on “Add”

Page 10: Std. edition 12-7-07

C6000/C7000 MIB- FS Series Operation & Maintenance Manual

7 Dec, 2007- Standard Edition

� Now you can Browse and Select the config.csv file you want to send to the FieldServer.

� Then Click “Add”.

� Now Click on “Install” to install the config.csv file to the FieldServer. If you are not using WinZip:

Copy the config.csv file to the Install.zip NOTE The csv file which you add should be called config.csv If the Install.zip file contains more than one csv file, then only one csv file will be downloaded to the FieldServer. If config.csv, primserv.csv and secdserv.csv are present, then config.csv will be downloaded. If config.csv is not present, then primserv.csv will be downloaded and if config.csv and primserv.csv are not present, then secdserv.csv will be downloaded. Version: 1.00aA 11 Sep 02 BDW Created the eNote. 1.00bA 08 Oct 02 BDW Updated for WinZip Install use. 1.00bB 16 Oct 02 PKD Updated for adding new csv file to Install.zip

Page 11: Std. edition 12-7-07

C6000/C7000 MIB- FS Series Operation & Maintenance Manual

Dec, 2007- Standard Edition 8

6.0 Configuring the FieldServer as a Stulz Client For a detailed discussion on FieldServer configuration, please refer to the FieldServer Configuration Manual. The information that follows describes how to expand upon the factory defaults provided in the configuration files included with the FieldServer (See “.csv” sample files provided with the FieldServer). This section documents and describes the parameters necessary for configuring the FieldServer to communicate with a Stulz controller.

6.1 Data Arrays/Descriptors The configuration file tells the FieldServer about its interfaces, and the routing of data required. In order to enable the FieldServer for Stulz communications, the driver independent FieldServer buffers need to be declared in the “Data Arrays” section, the destination device addresses need to be declared in the “Client Side Nodes” section, and the data required from the Servers needs to be mapped in the “Client Side Map Descriptors” section. Details on how to do this can be found below. Note that in the tables, *indicates an optional parameter, with the bold legal value being the default.

Section Title

Data_Arrays

Column Title Function Legal Values

Data_Array_Name Provide name for Data Array Up to 15 alphanumeric characters

Data_Array_Format Provide data format. Each Data Array can only take on one format.

Float, SInt16, Packed_Bit, Byte

Data_Array_Length

Number of Data Objects. Must be larger than the data storage area required by the Map Descriptors for the data being placed in this array.

1-10,000

Example

//Data Arrays

Data_Arrays Data_Array_Name, Data_Array_Format, Data_Array_Length DA_ACTIVE, Byte, 200 DA_AI_01, Float, 200 DA_AO_01, Float, 200 DA_DI_01, Packed_Bit, 200 DA_DO_01, Packed_Bit, 200

Page 12: Std. edition 12-7-07

C6000/C7000 MIB- FS Series Operation & Maintenance Manual

9 Dec, 2007- Standard Edition

6.2 Client Side Connection Descriptions Section Title

Connections

Column Title Function Legal Values

Port Specify which port the device is connected to the FieldServer R1R21

Protocol Specify protocol used Stulz

Baud* Specify baud rate 9600 - The baud rate is limited by the Stulz bus being only 9600

Parity* Specify parity None

Data_Bits* Specify data bits 8

Stop_Bits* Specify stop bits 1

Handshaking* Specify hardware handshaking None

Poll_Delay* Time between internal polls 0-32,000seconds, 0.05 seconds

Example

/ / Client Side Connections Connections Port Protocol Baud Parity Handshaking Poll_Delay R1 STULZ 9600 None None 0.100s

6.3 Client Side Node Descriptors Section Title Nodes Column Title Function Legal Values Node_Name Provide name for node Up to 32 alphanumeric characters

Node_ID Modbus station address of physical Server node 1-32

Protocol Specify protocol used Stulz

Connection Specify which port the device is connected to the FieldServer R1-R21

Example

// Client Side Nodes Nodes Node_Name Node_ID Protocol Connection SATS1 1 Stulz R1

1 Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction manual for details of the ports available on specific hardware.

Page 13: Std. edition 12-7-07

C6000/C7000 MIB- FS Series Operation & Maintenance Manual

Dec, 2007- Standard Edition 10

6.4 Client Side Map Descriptors

6.4.1 FieldServer Related Map Descriptor Parameters Column Title Function Legal Values

Map_Descriptor_Name Name of this Map Descriptor Up to 32 alphanumeric characters

Data_Array_Name Name of Data Array where data is to be stored in the FieldServer

One of the Data Array names from “Data Array” section above

Data_Array_Offset Starting location in Data Array 0 to maximum specified in “Data Array” section above

Function Function of Client Map Descriptor RDBC, PASSIVE_CLIENT, WRBC, WRBX

6.4.2 Driver Related Map Descriptor Parameters Column Title Function Legal Values

Node_Name Name of Node to fetch data from One of the node names specified in “Client Node Descriptor” above

Length Length of Map Descriptor PASSIVE_CLIENT–1 Active Map Descriptors up to 232, depending on command

Stulz_Command Specifies the command to be read from the device. In order to read data a legal LS command is needed

Specified in the table in Appendix A

6.4.3 Timing Parameters Column Title Function Legal Values Scan_Interval Rate at which data is polled ≥0.001s

Page 14: Std. edition 12-7-07

C6000/C7000 MIB- FS Series Operation & Maintenance Manual

11 Dec, 2007- Standard Version

6.5 Map Descriptor Examples This driver uses one command to read all data from the device. None of the data is stored in this Map Descriptor’s Data Array, but is stored in the passive Map Descriptors’ Data Arrays. To write data to the device, make sure the command supports writing in Appendix A and write to the passive command’s data point.

6.5.1 The Active Read Command // Client Side Map Descriptors Map_Descriptors Map_Descriptor_Name Data_Array_Name Data_Array_Offset Function Node_Name Stulz_Command Length Scan_Interval Active_read DA_ACTIVE 0 RDBC Node_A ls 1 5

6.5.2 Float and Integer Passive Commands // Client Side Map Descriptors Map_Descriptors Map_Descriptor_Name, Data_Array_Name Data_Array_Offset Function Node_Name Stulz_Command Length Scan_Interval A1, DA_AI3 0 Passive_Client Node_A sett 1 5

The ls command should point to a Data Array of type BYTE.

This Data Array is where the data will be stored and to which a write can be performed (if it is supported-see Appendix A)

On the ls command, use RDBC for continuous reading or RDB for once-off reading.

In order to read any data, a ls command with a RDBC is required. Every time it is read, the data will be stored according to the passive Clients.

Use length 1 for the ls command.

These commands must always be passive (for read only) or passive Client (for read and write) or WRBX (write only). RDBC is not supported for these commands.

The length for these commands must always be 1.

Page 15: Std. edition 12-7-07

C6000/C7000 MIB- FS Series Operation & Maintenance Manual

12 Dec, 2007- Standard Edition

6.5.3 Bit array passive commands // Client Side Map Descriptors Map_Descriptors Map_Descriptor_Name Data_Array_Name Data_Array_Offset Function Node_namen Stulz_Command Length Scan Interval B1 DA_BI3 0 Passive_Client Node_A gst1 1 5

The bit array commands should always point to packed_bit Data Array for easiest use.

The offset should point to the first bit of a byte i.e. 0, 8, 16, 24 etc. These commands use 8 bit spaces in this array.

These commands must always be passive (for read only) or passive Client (for read and write) or WRBX (write only). RDBC is not supported for these commands.

The length for these commands must always be 1.

Page 16: Std. edition 12-7-07

C6000/C7000 MIB- FS Series Operation & Maintenance Manual

13 Dec, 2007- Standard Edition

7.0 Product Support Group SATS provides to its customers a Product Support Group (PSG) which not only provides technical support and parts but the following additional services, as requested: performance evaluations, start-up assistance and training.

7.1.1 Technical Support The SATS Product Support Group is dedicated to the prompt reply and solution to any problem encountered with a unit. Should a problem develop that cannot be resolved using this manual, you may contact PSG at (240) 529-1399 Monday through Friday from 8:00 a.m. to 5:00 p.m. EST. If a problem occurs after business hours, dial the page number (301) 414-4514 and follow the steps below: 1. Wait for the dial tone. 2. Dial your telephone number (including area code). 3. Press the pound (#) key. 4. Wait for a busy signal. 5. Hang up the telephone. One of our service technicians will return your call. When calling to obtain support, it is vital to have the following information readily available, (information is found on unit's nameplate): • Unit Model Number • SATS Item Number • Unit Serial Number • Description of Problem

7.2 Obtaining Warranty Parts Warranty inquires are to be made through the Product Support Group at (240) 529-1399 Monday through Friday from 8:00 a.m. to 5:00 p.m. EST. A service technician at SATS will troubleshoot the system over the telephone with a field service technician to determine the defect of the part. If it is determined that the part may be defective a replacement part will be sent UPS ground. If the customer requests that warranty part(s) be sent by any other method than UPS ground the customer is responsible for the shipping charges. If you do not have established credit with SATS you must provide a freight carrier account number.

A written (or faxed) purchase order is required on warranty parts and must be received prior to 12:00 p.m. for same day shipment. The purchase order must contain the following items: • Purchase Order Number • Date of Order • SATS Stated Part Price (obtained from PSG) • Customer Billing Address • Shipping Address • Customer's Telephone and Fax Numbers • Contact Name • Unit Model No., Serial No. & SATS Item No.

The customer is responsible for the shipping cost incurred for returning the defective part(s) back to SATS. Return of defective part(s) must be within 30 days at which time an evaluation of the part(s) is conducted and if the part is found to have a manufacturing defect a credit will be issued.

When returning defective part(s) complete the Return Material Authorization Tag and the address label received with the replacement part.

See SATS Standard Warranty located in section one of this manual.

7.3 Obtaining Spare/Replacement Parts

Spare and replacement parts requests are to be made through the Product Support Group by fax (301) 620-1396, telephone (240) 529-1399 or E-mail ([email protected]). Quotes are given for specified listed parts for a specific unit. SATS accepts Visa and MasterCard. SATS may extend credit to its customers; a credit application must be prepared and approved (this process could take one week). A 25% minimum restocking charge will be applied on returned stocked parts that were sold as spare/replacement parts. If the returned part is not a stocked item, a 50% restocking charge may be applied. Additionally a Return Material Authorization Number is required when returning parts. To receive credit for returned repair/replacement parts, the parts must be returned to SATS within 30 days of the purchase date. Spare part sales over 30 days old will be considered final and the parts will remain the sole property of the ordering party.

Page 17: Std. edition 12-7-07

C6000/C7000 MIB- FS Series Operation & Maintenance Manual

Dec, 2007- Standard Edition 14

Appendix A- Stulz Commands

2 These commands’ structure match the m1o1 structure 3 These commands’ structure match the m1o2 structure

FieldServer as a Client Command Descriptions and Supported Status Command Description Data_Type Signed Range Units C6000

Active Commands Ls Long state request Byte N - r m1fss Module 1 fan speed setpoint Integer N 0..100 % r/w m2fss Module 2 fan speed setpoint Integer N 0..100 % r/w

Passive Client commands wt Water temperature Float Y 50..50 C r rat Return air temperature Float N 0..100 C r sat Supply air temperature Float N 0..100 C r rah Return air humidity Float N 0..100 % r sah Supply air humidity Float N 0..100 % r m1o1 Module 1digital out status byte 1 Packed Bit r

0 Reheat 1 Bit r 1 Compressor 1 Bit r 2 Humidification1 Bit r 3 Dehumidification 1 Bit r 4 Fan 1 Bit r 5 Drycooler Bit r 6 Alarm relays 1(1=no alarm) Bit r 7 PWW Bit r

m1o2 Module 1 digital out status byte 2 Packed Bit r 0 Reheat 2 Bit r 1 Glycol pump Bit r 2 Louver (0=closed, 1=open) Bit r 3 Alarm relays 2 (1=no alarm) Bit r 4 Alarm relays 3 (1=no alarm) Bit r 5 Alarm relays 4 (1=no alarm) Bit r 6 Alarm relays 5 (1=no alarm) Bit r 7 Glycol pump ½ select Bit r

m2o12 Module 2 digital out status byte 1 Packed Bit r m2o23 Module 2 digital out status byte 2 Packed Bit r

Page 18: Std. edition 12-7-07

C6000/C7000 MIB- FS Series Operation & Maintenance Manual

15 Dec, 2007- Standard Edition

FieldServer as a Client Command Descriptions and Supported Status

Command Description Data_Type Signed Range Units C6000 m1i1 Module 1 digital in status byte 1 Packed Bit r

0 Compressor low pressure Bit r 1 Compressor high pressure Bit r 2 Reheat 1 failure Bit r 3 Humidification failure Bit r 4 Air flow failure Bit r 5 Filter clogged Bit r 6 Aux alarm 1 Bit r 7 Reheat 2 alarm Bit r

m1i2 Module 1 digital in status byte 2 Packed Bit r 0 Conductivity too high Bit r 1 Ultrasonic failure Bit r 2 Glycol pump 1 failure Bit r 3 Glycol pump 2 failure Bit r 4 Drycooler failure Bit r 5 Water detector Bit r 6 Aux alarm 2 Bit r 7 Aux alarm 3 Bit r

m2i14 Module 2 digital in status byte 1 Packed Bit r m2i25 Module 2 digital in status byte 2 Packed Bit r m1gecw Module 1 analogue out GE/CW Float N 0..100 r m2gecw Module 2 analogue out GE/CW Float N 0..100 r m1pww Module 1 analogue out PWW Float N 0..100 r m2pww Module 2 analogue out PWW Float N 0..100 r m1aoh Module 1 analogue out humidifier Float N 0..100 r m2aoh Module 2 analogue out humidifier Float N 0..100 r m1aosv Module 1 analogue out suction valve Float N 0..100 r m2aosv Module 2 analogue out suction valve Float N 0..100 r m16doc2 Module 1-6 digital out compressor 2 Packed Bit r

0 Module 1 compressor 2 Bit r 1 Module 2 compressor 2 Bit r

4 These commands’ structure match the m1i1 structure 5 These commands’ structure match the m1i2 structure

Page 19: Std. edition 12-7-07

C6000/C7000 MIB- FS Series Operation & Maintenance Manual

Dec, 2007- Standard Edition 16

FieldServer as a Client Command Descriptions and Supported Status Command Description Data_Type Signed Range Units C6000

2 Module 3 compressor 2 Bit r 3 Module 4 compressor 2 Bit r 4 Module 5 compressor 2 Bit r 5 Module 6 compressor 2 Bit r 6 Not used Bit r 7 Not used Bit r

m14dic2 Module 1-4 digital in compressor 2 Packed_Bit r 0 Module 1 compressor 2 low pressure Bit r 1 Module 1 compressor 2 high pressure Bit r 2 Module 2 compressor 2 low pressure Bit r 3 Module 2 compressor 2 high pressure Bit r 4 Module 3 compressor 2 low pressure Bit r 5 Module 3 compressor 2 high pressure Bit r 6 Module 4 compressor 2 low pressure Bit r 7 Module 4 compressor 2 high pressure Bit r

m56dic2 Module 5-6 digital in compressor 2 Packed_Bit r 0 Module 5 compressor 2 low pressure Bit r 1 Module 5 compressor 2 high pressure Bit r 2 Module 6 compressor 2 low pressure Bit r 3 Module 6 compressor 2 high pressure Bit r 4 not used Bit r 5 not used Bit r 6 not used Bit r 7 not used Bit r

sett Setpoint temperature Float N 10..35 C r/w seth Setpoint humidity Integer N 10..90 % r/w year Date–Year Integer N 0..99 r/w month Date–Month Integer N 1..12 r/w day Date–Day Integer N 1..31 r/w hour Time–Hour Integer N 0..23 r/w minute Time–Minute Integer N 0..59 r/w ratha Return air temperature too high alarm Integer N 0..30 C r/w satha Supply air temperature too high alarm Integer N 0..30 C r/w ratla Return air temperature too low alarm Integer N 0..30 C r/w satla Supply air temperature too low alarm Integer N 0..30 C r/w wtha Water temperature too high alarm Integer N 0..50 C r/w wtla Water temperature too low alarm Integer Y 50..30 C r/w rahha Return air humidity too high alarm Integer N 0..90 % r/w sahha Supply air humidity too high alarm Integer N 0..90 % r/w rahla Return air humidity too low alarm Integer N 0..90 % r/w sahla Supply air humidity too low alarm Integer N 0..90 % r/w

Module1 5gecwvs GE/CW valve start temperature Float N 0..10 r/w 5gecwvpb GE/CW valve proportional band Float N 0..10 r/w

Page 20: Std. edition 12-7-07

C6000/C7000 MIB- FS Series Operation & Maintenance Manual

17 Dec, 2007- Standard Edition

FieldServer as a Client Command Descriptions and Supported Status

Command Description Data_Type Signed Range Units C6000 gst1 General status byte 1 Packed_Bit

0 0=PC STOP (monitoring), 1= on Bit r/w 1 0=REMOTE STOP (contact), 1= on Bit r 2 0=LOCAL STOP (key), 1=on Bit r 3 0=TIMER STOP (weekly oper.), 1= on Bit r 4 Seq. Start/Stop (0= No, 1= Yes) Bit r 5 WARM UP STOP Bit r 6 Remote UPS1 = UPS active Bit r 7 LocalUPS1= UPS active Bit r

gst2 General status byte 2 Packed_Bit 0 G/CW mode; G:1, CW:0 Bit r/w 1 CW Valve OR/AND selector Bit r 2 not used 3 not used 4 not used 5 not used 6 not used 7 not used

err1 Error byte 1 Packed_Bit 0 Return air temp. too high alarm Bit r 1 Return air humid. too high alarm Bit r 2 Supply air temp. too high alarm Bit r 3 Supply air humid. too high alarm Bit r 4 Water temp. too high alarm Bit r 5 Return air temp. too low alarm Bit r 6 Return air humid. too low alarm Bit r 7 Supply air temp. too low alarm Bit r

err2 Error byte 2 Packed_Bit 0 Supply air humid. too low alarm Bit r 1 Water temp. too low alarm Bit r 2 Supervisor failure Bit r 3 Freeze alarm Bit r 4 Fire/smoke detector Bit r 5 Sensor failure Bit r 6 Controller failure Bit r 7 IO board transmission failure Bit r

ar6 Alarm reset None w 6 Writing any value to this command will reset the alarms on the Stulz unit.

Page 21: Std. edition 12-7-07

C6000/C7000 MIB- FS Series Operation & Maintenance Manual

Dec, 2007- Standard Edition 18

Appendix B- Troubleshooting Tips

Appendix B.1- Driver Limitations

• Only 9600 baud is supported by the Stulz devices.

• Server Side Supported Protocols - BACnet IP - BACnet Ethernet - BACnet MSTP - LonWorks - Johnson Controls Metasys N1 - Modbus TCP

• The Following Protocols Require Device FS 20 - BACnet IP - BACnet Ethernet

• The Following Protocols Require Device FS 30 - BACnet MSTP - Modbus TCP - Johnson Controls - LonWorks

Page 22: Std. edition 12-7-07

C6000/C7000 MIB- FS Series Operation & Maintenance Manual

Dec, 2007- Standard Edition

NOTES

__________________________________________________________________________

__________________________________________________________________________

__________________________________________________________________________

__________________________________________________________________________

__________________________________________________________________________

__________________________________________________________________________

__________________________________________________________________________

__________________________________________________________________________

__________________________________________________________________________

__________________________________________________________________________

__________________________________________________________________________

__________________________________________________________________________

__________________________________________________________________________

__________________________________________________________________________

__________________________________________________________________________

__________________________________________________________________________

__________________________________________________________________________

__________________________________________________________________________

__________________________________________________________________________

__________________________________________________________________________

__________________________________________________________________________

__________________________________________________________________________

__________________________________________________________________________

__________________________________________________________________________

__________________________________________________________________________

__________________________________________________________________________

__________________________________________________________________________

__________________________________________________________________________

__________________________________________________________________________

__________________________________________________________________________

__________________________________________________________________________

__________________________________________________________________________

Page 23: Std. edition 12-7-07

C6000/C7000 MIB- FS Series Operation & Maintenance Manual

Dec, 2007

Air Technology Systems, Inc.

Appendix C- Glossary

Definition of Terms and Abbreviations

A/C- Air Conditioner

BMS - Building Management System

BTU/Hr - British Thermal Units Per Hour

ºC - Degrees Centigrade

CW - Chilled Water

DX - Direct Expansion

ESD - Electrostatic Discharge

ºF - Degrees Fahrenheit

FOB - Freight on Board

ft. - Feet

GE - Water Glycol (WG)

in. - Inches

°K - Degrees Kelvin

MIB - Multi Interface Board

PSG - Product Support Group

PSI - Pounds per Square Inch

PSIG - Pounds per Square Inch Gauge

°R - Degrees Rankine

R.H.- Relative Humidity

SATS - Stulz Air Technology Systems,Inc.

TeleCompTrol™ - Software Program; InterfacesMIB to a BMS or PC

V - Volt

VAC - Volt, Alternating Current

W/G - Water Glycol (GE)

Page 24: Std. edition 12-7-07