Page 1: StatCon – STATionDevice CONfiguration Tool - Siemens · StatCon – STATionDevice CONfiguration Tool User manual ... With StatCon application it is possible to configure the connection

A documentation by: Siemens. © Siemens AG 2015. All rights reserved.

StatCon – STATionDeviceCONfiguration Tool

User manual

Software application for configuring Station Controller, Sta-tion Gateway and IEC61850 Client library

Document Version: 1.0

Page 2: StatCon – STATionDevice CONfiguration Tool - Siemens · StatCon – STATionDevice CONfiguration Tool User manual ... With StatCon application it is possible to configure the connection

A documentation by: Siemens. © Siemens AG 2015. All rights reserved.

Documentation | StatCon – STATion Device CONfiguration Tool 2

Document History

Version Changes Date

1.0 First Release 2015/03/27

1.1 Station Gateway – IEC time settings 2015/11/12

Page 3: StatCon – STATionDevice CONfiguration Tool - Siemens · StatCon – STATionDevice CONfiguration Tool User manual ... With StatCon application it is possible to configure the connection

A documentation by: Siemens. © Siemens AG 2015. All rights reserved.

Documentation | StatCon – STATion Device CONfiguration Tool 3

Table of contents

1 General .................................................................................................. 6

1.1 Starting StatCon ................................................................................ 6

1.2 GUI – Panels ....................................................................................... 6

1.3 Settings.............................................................................................. 8

1.3.1 Language ........................................................................................ 8

1.4 Project Handling ................................................................................ 8

1.4.1 Project data structure ....................................................................... 8

1.4.2 Copying of projects .......................................................................... 9

1.4.3 Export of devices ............................................................................. 9

1.4.4 Import of a device .......................................................................... 10

2 Station Controller ................................................................................ 12

2.1 General ............................................................................................ 12

2.2 Add Station Controller ..................................................................... 12

2.3 Properties panel............................................................................... 12

2.4 External devices ............................................................................... 14

2.4.1 Add External devices ...................................................................... 14

2.4.2 IEC61850 server device properties view .......................................... 14

2.4.3 IEC61850 derver device data structure ............................................ 16

2.5 IEC61850 Client stack....................................................................... 17

2.5.1 IEC61850 client device ................................................................... 18

2.5.2 IEC61850 datasets tab.................................................................... 18

2.5.3 IEC61850 tag selection................................................................... 19

2.5.4 IEC61850 client stack details panel ................................................. 21

2.6 IEC61850 server stack ...................................................................... 22

2.6.1 IEC61850 server device .................................................................. 23

2.6.2 IEC61850 server tag ....................................................................... 24

2.6.3 IEC61850 server stack details panel ................................................ 25

Page 4: StatCon – STATionDevice CONfiguration Tool - Siemens · StatCon – STATionDevice CONfiguration Tool User manual ... With StatCon application it is possible to configure the connection

A documentation by: Siemens. © Siemens AG 2015. All rights reserved.

Documentation | StatCon – STATion Device CONfiguration Tool 4

2.6.4 IEC61850 server stack mapped tags tab .......................................... 26

2.7 IEC 60870 Slave stack ....................................................................... 26

2.7.1 IEC 60870 slave device ................................................................... 28

2.7.2 IEC61850 server tag ....................................................................... 28

2.8 S7-Mapping ...................................................................................... 30

2.8.1 Manual S7-Mapping ....................................................................... 30

2.8.2 Generate S7-Mapping .................................................................... 30

2.8.3 Reset S7-Mapping .......................................................................... 31

2.9 Download to devices ........................................................................ 31

2.10 Online and diagnostics .................................................................... 32

2.11 Example ........................................................................................... 34

2.11.1 Add IEC61850 tags to the IEC61850 client ...................................... 34

2.11.2 Configure IEC61850 server ............................................................. 38

2.11.3 Generate S7-Mapping .................................................................... 39

2.11.4 Save project ................................................................................... 40

2.11.5 Download configuration to StationController .................................. 40

2.11.6 Generate data block SCL source ...................................................... 41

3 Station Gateway .................................................................................. 43

3.1 General ............................................................................................ 43

3.2 Add Station Gateway ....................................................................... 43

3.3 Properties panel............................................................................... 43

3.4 Download to device ......................................................................... 46

3.5 Online and diagnostics .................................................................... 46

3.6 Copy IEC61850 tag address .............................................................. 48

4 IEC61850 Client Basic Library .............................................................. 50

4.1 General ............................................................................................ 50

4.2 Add IEC61850 Client Basic Library.................................................... 50

4.3 Copy IEC61850 tag address .............................................................. 50

Page 5: StatCon – STATionDevice CONfiguration Tool - Siemens · StatCon – STATionDevice CONfiguration Tool User manual ... With StatCon application it is possible to configure the connection

A documentation by: Siemens. © Siemens AG 2015. All rights reserved.

Documentation | StatCon – STATion Device CONfiguration Tool 5

5 Online mode ........................................................................................ 51

6 Accessible devices view ....................................................................... 52

Page 6: StatCon – STATionDevice CONfiguration Tool - Siemens · StatCon – STATionDevice CONfiguration Tool User manual ... With StatCon application it is possible to configure the connection

6

A documentation by: Siemens. © Siemens AG 2015. All rights reserved.

Documentation | StatCon – STATion Device CONfiguration Tool

StatCon – the StationDevice configuration tool – should be used for the following tasks:

- Create the configuration of the different protocol stacks of Station Controller

- Download the stack configurations to the Station Controller

- Update the StationController or Station Gateway firmware

- Diagnostic functions for the Station Controller

- Create IP settings for a Station Gateway*

- Download IP settings to the Station Gateway*

- Read back current device configuration of the Station Gateway*

*Please refer to the Station Gateway manual for further information

1.1 Starting StatCon

Starting StatCon the first time, a blank workspace is shown, because no project file hasbeen opened.

A new project will be created by choosing “File” à “New Project” from the main menu. Thisopens a new workspace, where all panels are blank. On a first step, the system environ-ment has to be configured for the new project.

1.2 GUI – Panels

The StatCon GUI (see Figure 1 - Application window with Project) consists of six differentPanels:

1. “StationDevices Panel”: contains all StationControllers and StationGateways of theproject;

2. “External devices Panel”: contains a list of all configured external IEDs of the pro-ject;

3. “Details Panel”: used to show detail information;

4. “Properties Panel”: used for displaying and editing properties of selected entity;

5. “Device data Panel”: makes the data structure of an selected IED accessible;

6. “Log Panel”: contains some logging information about executed actions. This panelis auto hidden by default and will be shown when moving the mouse over;

Shown panels can be hidden and hidden panels can be shown by using the appropriateitem within the “View” item from the main menu.

1 General

Page 7: StatCon – STATionDevice CONfiguration Tool - Siemens · StatCon – STATionDevice CONfiguration Tool User manual ... With StatCon application it is possible to configure the connection

7

A documentation by: Siemens. © Siemens AG 2015. All rights reserved.

Documentation | StatCon – STATion Device CONfiguration Tool

Figure 1 - Application window with Project

2

11

3

5

6

Page 8: StatCon – STATionDevice CONfiguration Tool - Siemens · StatCon – STATionDevice CONfiguration Tool User manual ... With StatCon application it is possible to configure the connection

8

A documentation by: Siemens. © Siemens AG 2015. All rights reserved.

Documentation | StatCon – STATion Device CONfiguration Tool

1.3 Settings

1.3.1 Language

The following languages are available: English (default), German.

The language can be switched by the main menu “Settings” à “Language” à desired lan-guage.

The application has to be restarted to adopt the new language setting.

1.4 Project Handling

The “Project” item from the main menu (see Figure 2 - Main menu "Project") offers thecommon commands for the project handling.

Only one project can be opened simultaneously.

Figure 2 - Main menu "Project"

1.4.1 Project data structure

As shown in Figure 3 - Project data structure example, the project data is stored accordingto the following data structure:

- “001_ExternalDevices”: contains a local description file for each external device;

- “002_StationControllers”: contains a subfolder for each Station Controller to storethe configurations of the different protocol stacks.

- “004_StationGateway”: contains a subfolder for each Station Gateway downloadeddata

- “project.xml”: This file is the entry point for each project. It is not allowed, to re-name this file manually. To open an existing project, choose this file within the se-lect file dialog.

Page 9: StatCon – STATionDevice CONfiguration Tool - Siemens · StatCon – STATionDevice CONfiguration Tool User manual ... With StatCon application it is possible to configure the connection

9

A documentation by: Siemens. © Siemens AG 2015. All rights reserved.

Documentation | StatCon – STATion Device CONfiguration Tool

Figure 3 - Project data structure example

1.4.2 Copying of projects

To copy or transfer StatCon projects, the project folder can be copied in the WindowsExplorer. Open projects cannot be copied, they have to be closed before.

1.4.3 Export of devices

It is possible to export all your devices, with all their appropriate settings and stacks, into afolder of your choice. This includes the configured StationControllers, IEDs of your devices,their corresponding stacks, and so on.

The settings will be exported into the CSV file, which can be later edited by spreadsheetprograms like MS Excel and then imported into StatCon back. This required e.g. for givingthe complex mapping rule for the mapped tags.

To export devices select the “Export project…” button in the “Project” menu (see Figure 4 -Project export, import example).

Figure 4 - Project export, import example

The function can also be called with the context menu of the “StationControllers Panel” orthe bar button (see Figure 5 – StationDevices Panel, export).

Page 10: StatCon – STATionDevice CONfiguration Tool - Siemens · StatCon – STATionDevice CONfiguration Tool User manual ... With StatCon application it is possible to configure the connection

10

A documentation by: Siemens. © Siemens AG 2015. All rights reserved.

Documentation | StatCon – STATion Device CONfiguration Tool

Figure 5 – StationDevices Panel, export

This opens the “Export project…” dialog (see Figure 6 - Export project dialog)where youcan select a folder of your choice and give the directory a name. Check the “Ignore defaultvalues” box if you want this enabled.

Figure 6 - Export project dialog

If “Ignore default values” checked, so all unused or unchanged properties of the tags willnot be exported into the CSV file.

By “Export project…” or “Export devices” function all stacks of all StationControllers will beexported into desired folder.

1.4.4 Import of a device

Exported server or client stacks can be integrated in one of your StationControllers withthe “Import device…” function (see Figure 7 - StationDevices Panel, import). All their set-tings will also be imported into your project. Select a device in the StationController panelwhich your imported device shall be assigned to.

Page 11: StatCon – STATionDevice CONfiguration Tool - Siemens · StatCon – STATionDevice CONfiguration Tool User manual ... With StatCon application it is possible to configure the connection

11

A documentation by: Siemens. © Siemens AG 2015. All rights reserved.

Documentation | StatCon – STATion Device CONfiguration Tool

Figure 7 - StationDevices Panel, import

Using the context menu or the “Import device…” button opens the “Import device…” dialog(see Figure 8 – Import device dialog). Select a folder which contains an exported serv-er/client device and press the “OK” button.

Figure 8 – Import device dialog

Your stack will then be assigned to your selected StationController.

You can import stack only if such a stack yet exists in the StationController.

If your selected StationController already has one stack and you are trying to import anexported server or client stack, a new dialog will be opened. StatCon will ask you if youwant to merge the old stack with the new one or if you want to overwrite the currentstack with the new stack (see Figure 9 – Merge stacks dialog). Choose the option accord-ing to your needs.

Figure 9 – Merge stacks dialog

Page 12: StatCon – STATionDevice CONfiguration Tool - Siemens · StatCon – STATionDevice CONfiguration Tool User manual ... With StatCon application it is possible to configure the connection

12

A documentation by: Siemens. © Siemens AG 2015. All rights reserved.

Documentation | StatCon – STATion Device CONfiguration Tool

2.1 General

With StatCon application it is possible to configure the connection properties and the tagmapping entries of multiple Station Controllers. Furthermore you can get some online in-formation’s and execute an update of the firmware or a restart of the device.

2.2 Add Station Controller

A Station Controller can be added to the project within the “Station Devices” panel. To adda new controller open the context on toolbar item “Add StationDevice” and select sub item“Add StationController”. A new Station Controller will be added to the project.

Figure 10 - Add new Station Controller

This creates the new StationController and shows the dialog inside the properties panel.

2.3 Properties panel

Selecting any StationController within the StationDevices panel opens the StationControl-ler properties within the properties panel.

In this panel the StationController has to be named unique within the project, e.g. “Sta-tionController” and the different protocol stacks of the Station Controller can be config-ured.

Selecting one of the stacks generates the appropriate MLFB automatically. The MLFB can-not be changed by hand.

The IP address of the StationController (X2, IE General) has to be configured for download-ing the configuration to the StationController later.

One data block number (e.g. 1000) will be required at least for the S7-Mapping. Datablock number can be defined as a comma separated list.

2 Station Controller

Page 13: StatCon – STATionDevice CONfiguration Tool - Siemens · StatCon – STATionDevice CONfiguration Tool User manual ... With StatCon application it is possible to configure the connection

13

A documentation by: Siemens. © Siemens AG 2015. All rights reserved.

Documentation | StatCon – STATion Device CONfiguration Tool

Figure 11 - Station Controller properties panel

The column M/O describes if the property is mandatory (M) or optional (O):

Property Description M/O

General

Name Any unique name, identifying the StationControllerwithin the project

M

License

MLFB / Available stacks Machine-Readable product designation (MLFB) of theStationController. The MLFB indicates the existing pro-tocol stacks within the StationController. The MLFB willbe generated by selecting the appropriate protocolstacks.

M

Firmware version The firmware version of the IEC Services within theStationController

O

Connection parameters

IP address (v4) The IP address of the StationController (version 4) tocommunicate between StatCon and StationController

M

MAC address The MAC address of the StationController O

Access data

Password The password for authentication (10/2012: predefined+ not editable)

M

Page 14: StatCon – STATionDevice CONfiguration Tool - Siemens · StatCon – STATionDevice CONfiguration Tool User manual ... With StatCon application it is possible to configure the connection

14

A documentation by: Siemens. © Siemens AG 2015. All rights reserved.

Documentation | StatCon – STATion Device CONfiguration Tool

Configuration parameters

Data block numbers Comma separated list of allowed data block numbersfor S7-Mappings. Up to 10 data block numbers are al-lowed. These data block numbers will be used, whengenerating new S7-Mappings and validating existingmappings.

M

Table 1 - StationController properties

2.4 External devices

2.4.1 Add External devices

An external device (e.g. SJ633) can be added to the project within the “External devices”panel. To add a new device, click “Add external IEC61850 server device” on toolbar. Thenew external device will be shown, as a new entry inside the external devices panel, refer-encing the new IEC61850 server device.

Figure 12 - Add new Station Controller

This opens the “IEC61850 server properties” dialog inside the properties panel for the newcreated external server device.

2.4.2 IEC61850 server device properties view

Selecting any external device of type IEC61850 server within the External Devices panelopens the IEC61850 server device properties within the properties panel:

In this panel the IEC61850 server device can be configured.

The new IEC61850 server device has to be named unique within the project, e.g. “SJ633”.

Import the corresponding ICD file of the server device and select afterwards the desiredIED name within the dropdown list. All appropriate parameters, defined inside the ICD file,will be filled in automatically.

Import the corresponding ICD file of the IEC device and set its IP address.

With button “Apply template” you can apply the configuration to your external device andall appropriate parameters, defined inside the ICD file, will be filled in automatically. Fur-thermore the object structure of the IEC device will be created in “data structure” panel.

The “Max. connections” parameter defines the maximum number of connections to theIEC61850 server device, allowed to be configured by StatCon. Thus, one connection willbe required at least, to setup one IEC61850 client communicating with this server device.

Page 15: StatCon – STATionDevice CONfiguration Tool - Siemens · StatCon – STATionDevice CONfiguration Tool User manual ... With StatCon application it is possible to configure the connection

15

A documentation by: Siemens. © Siemens AG 2015. All rights reserved.

Documentation | StatCon – STATion Device CONfiguration Tool

Figure 13 - External server properties Panel

Page 16: StatCon – STATionDevice CONfiguration Tool - Siemens · StatCon – STATionDevice CONfiguration Tool User manual ... With StatCon application it is possible to configure the connection

16

A documentation by: Siemens. © Siemens AG 2015. All rights reserved.

Documentation | StatCon – STATion Device CONfiguration Tool

Property Description M/O

General

Device name Any unique name, identifying the server device withinthe project

M

Device description

ICD file IED capability description (ICD) file of the IED M

IED name The name of the IED, selected from the ICD file M

Connection parameters

IP address (v4) The IP address of the IED M

Device parameters

Max. connections The maximum number of possible connections for theserver device to IEC61850 clients (e.g. 5 for Siprotecdevices)

M

Time offset Variable offset, must be -720 to 720 minutes, default:0 min

O

SW offset Summer-/wintertime offset, must be -60 to 60minutes, default: 0 min; value will be added if S7 sup-ports SW time

O

Authentication

Authentication password O

Authentication type O

OSI parameters

OSI-AP-Title IEC communication parameter – usually retrieved fromicd file

O

OSI-AE-Qualifier IEC communication parameter – usually retrieved fromicd file

O

OSI-PSEL IEC communication parameter – usually retrieved fromicd file

O

OSI-SSEL IEC communication parameter – usually retrieved fromicd file

O

OSI-TSEL IEC communication parameter – usually retrieved fromicd file

O

Table 2 - External IEC61850 server device properties

2.4.3 IEC61850 derver device data structure

In the „Data structure“ panel you can select one of the configured external devices via thecombo box. The tree view inside shows the structure of the IEC device if its configurationwas applied via the button in “Properties” panel.

Page 17: StatCon – STATionDevice CONfiguration Tool - Siemens · StatCon – STATionDevice CONfiguration Tool User manual ... With StatCon application it is possible to configure the connection

17

A documentation by: Siemens. © Siemens AG 2015. All rights reserved.

Documentation | StatCon – STATion Device CONfiguration Tool

All IEC objects like Logical Devices (LD), Logical Nodes (LN), Data Objects (DO) and DataAttributes (DA) are represented as node in the tree view. By drag & drop the Data Attrib-utes can be added to the tag selection of the Station Controller.

Figure 14 - "Data structure" Panel

2.5 IEC61850 Client stack

The IEC61850 client stack properties consist of two different tab items (see Figure 15 -IEC61850 client stack properties General view):

- “General” tab: Properties of all connections to IEC61850 server devices within theIEC61850 client stack (see IEC61850 client device);

- “Datasets” tab: IEC61850 dataset management of the IEC61850 client stack (seeIEC61850 datasets tab);

Figure 15 - IEC61850 client stack properties General view

Page 18: StatCon – STATionDevice CONfiguration Tool - Siemens · StatCon – STATionDevice CONfiguration Tool User manual ... With StatCon application it is possible to configure the connection

18

A documentation by: Siemens. © Siemens AG 2015. All rights reserved.

Documentation | StatCon – STATion Device CONfiguration Tool

2.5.1 IEC61850 client device

Each IEC61850 server device, connected to the IEC61850 client stack, is referenced by anIEC61850 client device. The “General”-tab of the IEC61850 client properties contains a listof all IEC61850 servers, used by the IEC61850 client stack.

Selecting any IEC61850 server device within that list, opens the IEC61850 client deviceproperties (see Figure 15 - IEC61850 client stack properties General view).

Property Description M/O

General

IEC61850 server Name of referenced IEC61850 server -

Device parameters

Connect timeout O

Read timeout O

Write timeout O

GI timeout O

Time offset Variable offset, must be -720 to 720 minutes, de-fault: 0 min

O

SW offset Summer-/wintertime offset, must be -60 to 60minutes, default: 0 min; value will be added if S7supports SW time

O

Configuration parameters

Period Period in ms, how often tags without dataset will bepolled

O

S7-Mapping

DataBlock-Number Number of data block, where the connection datawill be mapped to

M

DataBlock-Offset Offset within the referenced data block, where theconnection data will be mapped to

M

S7-Mapping for new tags Activates “S7-Mapping designated” by default fornew IEC61850 Tags

Table 3 - IEC61850 client device properties

2.5.2 IEC61850 datasets tab

The “Datasets”-tab references all IEC61850 datasets of all IEC61850 server devices used byany IEC61850 client device of the IEC61850 client stack. Inside that tab, it’s possible toadd new datasets and to edit or to delete existing datasets.

Selecting any IEC61850 dataset within the listed datasets opens its properties:

Page 19: StatCon – STATionDevice CONfiguration Tool - Siemens · StatCon – STATionDevice CONfiguration Tool User manual ... With StatCon application it is possible to configure the connection

19

A documentation by: Siemens. © Siemens AG 2015. All rights reserved.

Documentation | StatCon – STATion Device CONfiguration Tool

Figure 16 - IEC61850 client stack properties datasets view

Property Description M/O

General

Dataset name Name of dataset, has to be unique within theIEC61850 server device

M

Dataset type Static (predefined by IEC61850 server device) or dy-namic (created by IEC61850 client device during con-nection setup)

Optional: used for float values, i.e. new float valueswill be assigned to this dataset by default.

-

Dataset mechanism Polling or reporting -

Reporting parameters Only visible by selecting “reporting” as Dataset mechanism

Report control block Report control block used by this dataset M

Buffer time Buffer time in ms O

Integrity period Integrity period in ms O

Polling parameters Only visible by selecting “polling” from Dataset Mechanism

Period Time in ms, how often the variables are requested bythe IEC61850 client device

O

Logical device Logical device inside the IEC61850 server device wherethe dataset resides

M

Logical node Logical node inside the IEC61850 server device wherethe dataset resides

M

Table 4 - IEC61850 dataset properties

2.5.3 IEC61850 tag selection

The IEC61850 client stack details view lists all IEC61850 tags, referenced by the clientstack, line by line.

Page 20: StatCon – STATionDevice CONfiguration Tool - Siemens · StatCon – STATionDevice CONfiguration Tool User manual ... With StatCon application it is possible to configure the connection

20

A documentation by: Siemens. © Siemens AG 2015. All rights reserved.

Documentation | StatCon – STATion Device CONfiguration Tool

Figure 17 - IEC61850 client stack tag selection

The IEC61850 tag properties are shown inside the properties view by selecting the tag:

Figure 18 - IEC61850 Tag Properties View

Property Description M/O

General

DAI Path Path of referenced instantiated data attribute (DAI) -

Equipment identificationcode

User defined identifier, has to be unique within thewhole project

M

Description Description of the tag

Mapping

Variable-Type Variable type M

Length Variable length (Bits or Bytes, depends on variabletype)

M

S7-Mapping designated S7-Mapping will be generated if activated, otherwisetag will be ignored during generation of S7-Mapping

-

Page 21: StatCon – STATionDevice CONfiguration Tool - Siemens · StatCon – STATionDevice CONfiguration Tool User manual ... With StatCon application it is possible to configure the connection

21

A documentation by: Siemens. © Siemens AG 2015. All rights reserved.

Documentation | StatCon – STATion Device CONfiguration Tool

DataBlock-Address -1 = not yet defined, i.e. will be set when S7-Mappingis generated

O

DataBlock-Offset -1 = not yet defined, i.e. will be set when S7-Mappingis generated

O

Dataset

Dataset Referenced IEC6180 dataset O

Configuration parameters

Use Substitution Value O

Interlock O

Synchrocheck O

Ctrl model O

Table 5 - IEC61850 tag properties

2.5.4 IEC61850 client stack details panel

The client stack details panel offers the possibility to quick edit the “equipment identifica-tion code” and the “Variable type” of the different IEC61850 tags. All IEC61850 tag proper-ties can be shown and edited by selecting them.

IEC61850 tags can be deleted by pressing the delete key, while the tag is selected or usingthe delete function in the context menu.

Figure 19 - IEC61850 client stack tag selection

The listed IEC61850 tags can be sorted or grouped by each column, using the functionalities of-fered by the context menu of each column header.

Page 22: StatCon – STATionDevice CONfiguration Tool - Siemens · StatCon – STATionDevice CONfiguration Tool User manual ... With StatCon application it is possible to configure the connection

22

A documentation by: Siemens. © Siemens AG 2015. All rights reserved.

Documentation | StatCon – STATion Device CONfiguration Tool

Figure 20 - Customize IEC61850 tag list

2.6 IEC61850 server stack

The IEC61850 server stack properties has only one tab item:

- “General”-Tab: Shows the properties of the selected IEC61850 server.

Figure 21 - IEC61850 Server Stack Properties tab items

Page 23: StatCon – STATionDevice CONfiguration Tool - Siemens · StatCon – STATionDevice CONfiguration Tool User manual ... With StatCon application it is possible to configure the connection

23

A documentation by: Siemens. © Siemens AG 2015. All rights reserved.

Documentation | StatCon – STATion Device CONfiguration Tool

2.6.1 IEC61850 server device

The “General”-tab of the IEC61850Server properties contains only the name of the select-ed server device, because the server has no references to other devices.

Selecting the IEC61850 server device within that list, opens the properties:

Property Description M/O

General

Device name Name of the IEC61850 server -

IED name Name of the IED file

Description Description of the IEC61850 server

Device description

ICD file IED capability description (ICD) file of the IED, use thebrowse button to select a file from your hard drive

O

IED name The name of the IED, selected from the ICD file. Pressthe “Apply template” button to apply the IED template

O

Connection parameters

IP address (v4) IP address of the server, must be unique O

OSI-AP-Title O

OSI-AE-Qualifier O

OSI-PSEL

OSI-SSEL

OSI-TSEL

S7-Mapping

Data block number Number of data block, where the connection data willbe mapped to

O

Data block offset Offset within the referenced data block, where theconnection data will be mapped to

S7-Mapping for new tags Activates “S7-Mapping designated” by default for newIEC61850 Tags

Device parameters

Max. connections The maximum number of possible connections for theserver device to IEC61850 clients

M

Time offset Variable offset, must be -720 to 720 minutes, default:0 min

M

SW offset Summer-/wintertime offset, must be -60 to 60minutes, default: 0 min; value will be added if S7 sup-ports SW time

-

Authentication

Page 24: StatCon – STATionDevice CONfiguration Tool - Siemens · StatCon – STATionDevice CONfiguration Tool User manual ... With StatCon application it is possible to configure the connection

24

A documentation by: Siemens. © Siemens AG 2015. All rights reserved.

Documentation | StatCon – STATion Device CONfiguration Tool

Activate authentication Check the box to activate authentication for the server

Authentication password Create a authentication password

Authentication type

Table 6 - IEC61850 server device properties

2.6.2 IEC61850 server tag

The IEC61850 server stack details view lists all IEC61850 tags, which the server contains,line by line.

Figure 22 - IEC61850 server stack tag selection

The IEC61850 tags have a descending command structure (see Figure 22).

1. Logical device

2. Logical node

3. Function constraint

4. Object

5. SubObject or attribute

Each of these tags has his own properties. They will be displayed in the properties view,after selecting them. The properties can be:

Property Description M/O

General

IEC61850 path Path of referenced IED -

Name Name of the tag M

Node type

12345

Page 25: StatCon – STATionDevice CONfiguration Tool - Siemens · StatCon – STATionDevice CONfiguration Tool User manual ... With StatCon application it is possible to configure the connection

25

A documentation by: Siemens. © Siemens AG 2015. All rights reserved.

Documentation | StatCon – STATion Device CONfiguration Tool

Description Description of the tag

Details Only available for SubObjects or attributes

S7-Mapping Check the box to enable the Mapping properties M

Equipment identificationcode

User defined identifier, has to be unique within thewhole project

Mapping Only available after checking S7-Mapping in ‘Details’

Length Variable length (bits/bytes, depends on variable type) M

S7-Mapping designated S7-Mapping will be generated if activated, otherwisetag will be ignored during generation of S7-Mapping

-

Data block address -1 = not yet defined, i.e. will be set when S7-Mappingis generated

O

Data block offset -1 = not yet defined, i.e. will be set when S7-Mappingis generated

O

Table 7 - IEC61850 server tag properties

2.6.3 IEC61850 server stack details panel

All IEC61850 tag properties can be shown and edited in the properties view by selectingthem.

IEC61850 tags can be deleted by pressing the delete key, while the tag is selected or usingthe delete function in the context menu.

A listed IEC61850 tag can be fully expanded or collapsed by using the context menu of aselected tag. It is also possible to just show the mapped tags per the “Show mapped tags”function of the context menu (see Figure 23 - Server stack context menu).

Figure 23 - Server stack context menu

Page 26: StatCon – STATionDevice CONfiguration Tool - Siemens · StatCon – STATionDevice CONfiguration Tool User manual ... With StatCon application it is possible to configure the connection

26

A documentation by: Siemens. © Siemens AG 2015. All rights reserved.

Documentation | StatCon – STATion Device CONfiguration Tool

2.6.4 IEC61850 server stack mapped tags tab

Selecting the “Mapped tags” tab will show you a detailed view of your current mappedtags (see Figure 24 - Server stack mapped tags).

Figure 24 - Server stack mapped tags

The tags can be modified and sorted with the same options that are present in theIEC61850 client stack details view (see IEC61850 client stack details panel) for furthersorting and grouping instructions.

2.7 IEC 60870 Slave stack

The IEC 60870 slave stack properties has only one tab item:

- “General”-Tab: Shows the properties of the selected IEC 60870 slave:

Page 27: StatCon – STATionDevice CONfiguration Tool - Siemens · StatCon – STATionDevice CONfiguration Tool User manual ... With StatCon application it is possible to configure the connection

27

A documentation by: Siemens. © Siemens AG 2015. All rights reserved.

Documentation | StatCon – STATion Device CONfiguration Tool

Figure 25 – IEC 60870 slave stack Properties tab items

Page 28: StatCon – STATionDevice CONfiguration Tool - Siemens · StatCon – STATionDevice CONfiguration Tool User manual ... With StatCon application it is possible to configure the connection

28

A documentation by: Siemens. © Siemens AG 2015. All rights reserved.

Documentation | StatCon – STATion Device CONfiguration Tool

2.7.1 IEC 60870 slave device

The “General”-tab of the IEC 60870 slave properties contains the following properties:

Property Description M/O

General

Device name Name of the IEC 60870 slave

Description Description of the IEC 60870 slave

Originator Address Originator Address for telegrams

Connection parameters

IP address (v4) IP address of the server, must be unique M

Port Port Number

Connect Timeout Connect Timeout (default 30000ms)

Send Timeout Send Timeout (default 15000ms)

No Data Timeout No Data Timeout (default 10000ms)

Long Timeout Long Timeout (default 20000ms)

Parameter K Parameter K (default 12)

Parameter W Parameter W (default 8)

S7-Mapping

Data block number Number of data block, where the connection data willbe mapped to

Data block offset Offset within the referenced data block, where theconnection data will be mapped to

Device parameters

Max. connections The maximum number of possible master connectionsfor the slave device.

M

Time offset Variable offset, must be -720 to 720 minutes, default:0 min

M

SW offset Summer-/wintertime offset, must be -60 to 60minutes, default: 0 min; value will be added if S7 sup-ports SW time

-

Table 8 – IEC 60870 slave properties

2.7.2 IEC61850 server tag

The IEC 60870 slave details view lists all IEC60870 ASDUs and tags of the slave device.

Page 29: StatCon – STATionDevice CONfiguration Tool - Siemens · StatCon – STATionDevice CONfiguration Tool User manual ... With StatCon application it is possible to configure the connection

29

A documentation by: Siemens. © Siemens AG 2015. All rights reserved.

Documentation | StatCon – STATion Device CONfiguration Tool

Figure 26 – IEC 60870 slave tags

To add new ASDUs and tags, right click into the view and click “add ASDU”, “add tag”.

Figure 27 - add ASDU

The properties of the ASDUs/tags can be configured in the properties view of the AS-DU/tag.

Page 30: StatCon – STATionDevice CONfiguration Tool - Siemens · StatCon – STATionDevice CONfiguration Tool User manual ... With StatCon application it is possible to configure the connection

30

A documentation by: Siemens. © Siemens AG 2015. All rights reserved.

Documentation | StatCon – STATion Device CONfiguration Tool

2.8 S7-Mapping

The S7-Mapping defines a data block number and offset for any entity within the configu-ration of any protocol stack, where its data will be mapped to by the IEC services.

Entity Mapped data M/O

IEC61850 client stack

IEC61850 client device Communication data M

IEC61850 tag Tag value, status, … O

Table 9 - S7 mappable entities

2.8.1 Manual S7-Mapping

S7-Mapping can be defined manually inside the entity properties.

2.8.2 Generate S7-Mapping

There is the possibility to auto generate the required S7-Mappings for all entities on Sta-tionController basis. This means, that…

- Existing S7-Mappings will be preserved and validated. Errors will be reported insidethe log view.

- Unspecified S7-Mappings will be defined, filling up the gaps inside the defineddata blocks of the respective StationController.

S7-Mapping can be auto generated for all StationControllers at once by the main menu“Configuration” à “Generate S7-Mapping for all StationControllers” (see Figure 28 - Mainmenu "Configuration").

Figure 28 - Main menu "Configuration"

Furthermore it is possible to auto generate S7-Mapping for any single StationController byits context menu „Generate S7-Mapping“(see Figure 29 - StationController context menu).

Page 31: StatCon – STATionDevice CONfiguration Tool - Siemens · StatCon – STATionDevice CONfiguration Tool User manual ... With StatCon application it is possible to configure the connection

31

A documentation by: Siemens. © Siemens AG 2015. All rights reserved.

Documentation | StatCon – STATion Device CONfiguration Tool

Figure 29 - StationController context menu

2.8.3 Reset S7-Mapping

S7-Mapping can be reset on StationController basis. This means, that all existing S7-Mappings will be reset to unspecified values.

This can be done for all StationControllers at once by the main menu “Configuration” à“Reset S7-Mapping for all StationControllers” (see Figure 28 - Main menu "Configuration")and for any single StationController by its context menu “Reset S7-Mapping” (see Figure 29- StationController context menu).

2.9 Download to devices

For opening the “Download configuration” panel, select the corresponding device in “Sta-tionDevices” panel and click the icon on toolbar.

Figure 30 - Open "Download configuration" panel

Downloading the configured connection properties and the tag mapping entries can byexecuted by the download button.

If the SCL source code of the Data block(s) should be displayed after download, the check-box “Show data blocks after generation” must be activated.

If the NTP settings were modified, the NTP service needs to be restarted. This can be donevia the checkbox “Restart NTP service after download”.

The checkbox “Use custom files” should only be used if a configuration created outside ofStatCon (e.g. in xml file) should be downloaded.

Page 32: StatCon – STATionDevice CONfiguration Tool - Siemens · StatCon – STATionDevice CONfiguration Tool User manual ... With StatCon application it is possible to configure the connection

32

A documentation by: Siemens. © Siemens AG 2015. All rights reserved.

Documentation | StatCon – STATion Device CONfiguration Tool

Figure 31 - Station Controller download configuration panel

2.10 Online and diagnostics

In “Online & diagnostics” panel the current online values of the selected Station Controllerare displayed. Furthermore you can execute the online actions of the Station Controller viathe control buttons.

For opening the “Online & diagnostics” panel, select the corresponding device in “Sta-tionDevices” panel and click the icon on toolbar.

Figure 32 - Open "Online & diagnostics" panel

If the panel was opened, it directly connects to the device and reads out all availableonline values.

To load the data from the Station Controller press “Refresh informations”.

A new firmware can be downloaded via “Update Firmware”. Note that the Station Con-troller has to be put into STOP mode via the physical mode switch.

Create Diagnose ZIP uploads all LOG files from the Station Controller and ZIPs them intothe project folder.

Page 33: StatCon – STATionDevice CONfiguration Tool - Siemens · StatCon – STATionDevice CONfiguration Tool User manual ... With StatCon application it is possible to configure the connection

33

A documentation by: Siemens. © Siemens AG 2015. All rights reserved.

Documentation | StatCon – STATion Device CONfiguration Tool

Figure 33 – Station Controller online & diagnostics panel

Property Description

StationController

Name The name of the Station Controller in the project

MLFB The MLFB of the Station Controller

IP address (v4) The IP address of the Station Controller in the project. Theapplication tries to connect to this address to get the onlineinformations

Firmware

IEC service version The current version of the IEC service on Station Controller

IEC service build date The build date of the IEC service on Station Controller

IEC service started at The date and time when IEC service was started on StationController

Updater service version The current version of the updater service on Station Control-ler

Updater service started at The date and time when Updater service was started on Sta-tion Controller

Stack configuration

Page 34: StatCon – STATionDevice CONfiguration Tool - Siemens · StatCon – STATionDevice CONfiguration Tool User manual ... With StatCon application it is possible to configure the connection

34

A documentation by: Siemens. © Siemens AG 2015. All rights reserved.

Documentation | StatCon – STATion Device CONfiguration Tool

The license and configuration status of the different stacks inthe connected Station Controller.

Licensed: License existingConfigured: Configuration file existing for stackConfiguration at: Date and Time of configuration change

Software status

WinAC status The status of the WinAC on Station Gateway

IEC service started The status of the IEC process on Station Gateway

Control

Refresh informations Reloading the online informations

Update firmware Updating the Station Controller firmware

Enable Remote Desktop Enable the Remote Desktop Service of the embedded Con-troller

Create diagnose ZIP Loading all diagnose files from Station Controller and save aszip file on local system

Restart IEC service Executes a restart of the IEC service on Station Controller

Restart StationGateway Restarting the Station Controller

Table 10 - Station Controller online and diagnostics

2.11 Example

2.11.1 Add IEC61850 tags to the IEC61850 client

New tags will always be added to the selected protocol stack.

Selecting the desired protocol stack within the StationDevices panel, e.g. “StationControl-ler” à “IEC61850 Client”, opens its tag list inside the details panel. Only StationControllercan have a protocol stack.

All available IEC61850 server devices are listed in the dropdown list inside the Device Datapanel. The data structure of the chosen server device will be shown below the dropdownlist as a tree view. Any data attribute of the server device can be added as an IEC61850 tagto the selected IEC61850 client. Therefore choose “Add” from the context menu of the se-lected data attribute within the tree view or press the Enter key. This step is shown in Fig-ure for the controllable data attribute “IED_0002CTRL/Q0CSWI1$CO$Pos$Oper$ctlVal”(Control of circuit breaker).

Page 35: StatCon – STATionDevice CONfiguration Tool - Siemens · StatCon – STATionDevice CONfiguration Tool User manual ... With StatCon application it is possible to configure the connection

35

A documentation by: Siemens. © Siemens AG 2015. All rights reserved.

Documentation | StatCon – STATion Device CONfiguration Tool

Figure 34 - Add data attribute to IEC61850 client stack

There is another way to add the tag to the protocol stack. You can select a tag and drag itwith the mouse into the details panel (see Figure).

Figure 35 – Add a tag with drag and drop

If possible, the new IEC61850 tag will be listed now within the tag list of the selected pro-tocol stack (see Figure).

Page 36: StatCon – STATionDevice CONfiguration Tool - Siemens · StatCon – STATionDevice CONfiguration Tool User manual ... With StatCon application it is possible to configure the connection

36

A documentation by: Siemens. © Siemens AG 2015. All rights reserved.

Documentation | StatCon – STATion Device CONfiguration Tool

Figure 36 - Newly created IEC61850 tag

The equipment identification code (EIC), assigned to the tag by default, consist of the dataattribute name and any ID. It’s recommended to change the EIC to any context specificvalue, e.g. “Ctrl0”. This can be done by editing the EIC directly inside the tag list (see Fig-ure 37) or by editing the tag properties.

Figure 37 - Edit the equipment identification code

Afterwards, the measured value “IED_0002MEAS/MMXU1$MX$A$phsA$cVal$mag$f” canbe added in the same way. Selecting the value within the tag list, opens its properties in-side the properties panel (see Figure 38).

Change the EIC to e.g. “Current” and select “StatusFloat” as variable-type, to receive thequality and timestamp of the measured value as well.

Page 37: StatCon – STATionDevice CONfiguration Tool - Siemens · StatCon – STATionDevice CONfiguration Tool User manual ... With StatCon application it is possible to configure the connection

37

A documentation by: Siemens. © Siemens AG 2015. All rights reserved.

Documentation | StatCon – STATion Device CONfiguration Tool

Figure 38 - IEC61850 tag properties

As shown in Figure 38, the S7-Mapping parameters (Data block number, Data block offset)are set to “-1” by default. This implies that the S7-Mapping is still unspecified. These pa-rameters will be adapted during S7-Mapping generation (see 2.11.3).

Furthermore it can be seen, that an IEC61850 dataset (“NewDataset1_F”) had been creat-ed and assigned to the tag by default. “_F” within the name of the dataset indicates thatthis dataset will be preferred for float values. All further dataset details can be looked upand edited within the properties of the IEC61850 client stack of the StationController (seeFigure 39).

Page 38: StatCon – STATionDevice CONfiguration Tool - Siemens · StatCon – STATionDevice CONfiguration Tool User manual ... With StatCon application it is possible to configure the connection

38

A documentation by: Siemens. © Siemens AG 2015. All rights reserved.

Documentation | StatCon – STATion Device CONfiguration Tool

Figure 39 - IEC61850 dataset properties

2.11.2 Configure IEC61850 server

This chapter describes the configuration of the IEC 61850 server stack. This is not requiredif you use only the IEC 61850 client.

To start work with the IEC61850 server stack make sure the IEC61850 Server checkbox(see Figure 11 - Station Controller properties panel) is checked.

2.11.2.1 Add IEC61850 tree nodes to the IEC61850 server

Server devices accept different tree node types in comparison to client devices. First it isnecessary to add the whole logical device (e.g. TEMPLATE_Minimal) to the controller. Thiscan be done by selecting a correspond node and dragging it to the object tree (see Figure41). After that the logical nodes of the logical device can be inserted, deleted and config-ured as they are needed.

Figure 40 - IEC61850 server object tree, new node

At this step you should create a final tree structure for your selected server device. At anycase you have the possibility to modify the tree later.

Page 39: StatCon – STATionDevice CONfiguration Tool - Siemens · StatCon – STATionDevice CONfiguration Tool User manual ... With StatCon application it is possible to configure the connection

39

A documentation by: Siemens. © Siemens AG 2015. All rights reserved.

Documentation | StatCon – STATion Device CONfiguration Tool

Tags can be chosen from the “Data structure” panel. You can choose either an externaldevice with a defined ICD file or a template from the drop down menu. For further info seechapter “2.4 External devices”

Modifying the tags and nodes works the same way as it would with tags in a client device,see chapter “2.11.1 Add IEC61850 tags to the IEC61850 clientAdd IEC61850 tags to theIEC61850 client” for further information. You cannot the structure of the logical objects.You cannot delete or insert single attributes for example “stVal” or “q”.

2.11.3 Generate S7-Mapping

The S7-Mapping can be auto generated for the StationController using “Generate S7-Mapping” from the StationControllers context menu (see Figure 41).

Figure 41 - Generate S7-Mapping

This means that all mappable entities, where the S7-Mapping parameters are still unspeci-fied, will be mapped to the data blocks, specified within the StationController properties.

The progress of this process can be viewed inside the log panel (see Figure 42). Existingmapping definitions will be kept unchanged but validated before new mappings will beset. All errors, found during the validation, will be listed in the log panel as well.

Figure 42 - Log panel with S7-Mapping result

When the S7-Mapping is done, the result can be seen inside the entity properties, wherethe appropriate mapping parameters are set (see Figure 43 for e.g. the “Ctrl0” tag).

Page 40: StatCon – STATionDevice CONfiguration Tool - Siemens · StatCon – STATionDevice CONfiguration Tool User manual ... With StatCon application it is possible to configure the connection

40

A documentation by: Siemens. © Siemens AG 2015. All rights reserved.

Documentation | StatCon – STATion Device CONfiguration Tool

Figure 43 - IEC61850 tag properties with specified S7-Mapping parameters

2.11.4 Save project

Before downloading the configuration to the StationController, the project has to besaved. The project will be saved by choosing “Project” à “Save Project” from the mainmenu. This opens the “Save Project As …” dialog, where the project location has to be se-lected and the project name has to be defined. These settings will be applied by pressingthe “OK”-Button and the project will be saved according to the data structure described in“1.4.1 Project data structure”.

2.11.5 Download configuration to StationController

The configuration can be downloaded to the StationController using “Download to device”from the StationDevices context menu (see Figure 44). It’s required to save the projectbefore downloading the configuration to the StationController.

Figure 44 - Download to device command

Page 41: StatCon – STATionDevice CONfiguration Tool - Siemens · StatCon – STATionDevice CONfiguration Tool User manual ... With StatCon application it is possible to configure the connection

41

A documentation by: Siemens. © Siemens AG 2015. All rights reserved.

Documentation | StatCon – STATion Device CONfiguration Tool

This opens the “Download Configuration to StationController” dialog inside the detailspanel (see Figure 45). Inside this dialog, the protocol stacks, which shall be downloaded,have to be selected. All stacks are selected by default.

The download can be started by the “Download configuration to StationController” button.The state of the download will be shown by an icon inside the column “State” and by ap-propriate entries inside the log panel.

Figure 45 - Download configuration to StationController

2.11.6 Generate data block SCL source

The S7 user program requires the SCL source of the data block, matching the generatedS7-Mapping. This data block SCL source code can be generated by the “Write data blockSCL description [..]” button above the “Download configuration [..]” button (see Figure45).

This writes the SCL source code for each data block, used by the S7-Mapping, to a SCL file(e.g. “DB1000.scl”) inside the folder of the corresponding StationController (<project fold-er>/002_StationControllers/StationController<x>/). The exact path of each successful gen-erated SCL file will be given inside the log panel (see Figure 46).

Figure 46 - SCL done inside log panel

Figure 47 - generated SCL code of data block DB1000 shows the SCL source code of thedata block DB1000 matching the configuration of the previous chapters.

Page 42: StatCon – STATionDevice CONfiguration Tool - Siemens · StatCon – STATionDevice CONfiguration Tool User manual ... With StatCon application it is possible to configure the connection

42

A documentation by: Siemens. © Siemens AG 2015. All rights reserved.

Documentation | StatCon – STATion Device CONfiguration Tool

Figure 47 - generated SCL code of data block DB1000

Page 43: StatCon – STATionDevice CONfiguration Tool - Siemens · StatCon – STATionDevice CONfiguration Tool User manual ... With StatCon application it is possible to configure the connection

43

A documentation by: Siemens. © Siemens AG 2015. All rights reserved.

Documentation | StatCon – STATion Device CONfiguration Tool

3.1 General

With StatCon application the connection properties of multiple Station Gateways can beconfigured and loaded to the device. Furthermore you can get some online information’sand execute an update of the firmware or a restart of the device.

For further information about the connection properties, please refer to the manuals ofthe Station Gateway.

NOTE: Just properties settings will be downloaded to the Station Gateway. IEC61850client settings will not be downloaded. The IEC61850 pathes must be configured inthe S7 program.

3.2 Add Station Gateway

A Station Gateway can be added to the project within the “Station Devices” panel. To add anew gateway open the context on toolbar item “Add StationDevice” and select sub item“Add StationGateway”. A new Station Gateway will be added to the project.

Figure 48 - Add new Station Gateway

3.3 Properties panel

Selecting any StationGateway within the “StationDevices” panel opens the StationGatewayproperties within the “Properties” panel.

In this panel the connection properties of the gateway can be configured.

3 Station Gateway

Page 44: StatCon – STATionDevice CONfiguration Tool - Siemens · StatCon – STATionDevice CONfiguration Tool User manual ... With StatCon application it is possible to configure the connection

44

A documentation by: Siemens. © Siemens AG 2015. All rights reserved.

Documentation | StatCon – STATion Device CONfiguration Tool

Figure 49: Station Gateway properties Panel

Page 45: StatCon – STATionDevice CONfiguration Tool - Siemens · StatCon – STATionDevice CONfiguration Tool User manual ... With StatCon application it is possible to configure the connection

45

A documentation by: Siemens. © Siemens AG 2015. All rights reserved.

Documentation | StatCon – STATion Device CONfiguration Tool

Property Description M/O

General

Name Any unique name, identifying the StationGatewaywithin the project

M

IEC 61850 port

IP address (v4) The IP address of the IEC 61850 port M

Subnet mask The Subnet mask of the IEC 61850 port M

S7 port

IP address (v4) The IP address of the S7 port. This is used to communi-cate between StatCon and the StationGateway

M

Subnet mask The Subnet mask of the S7 port M

Redundancy port

IP address (v4) The IP of the redundancy port, either 10.10.12.1 or10.10.12.2 can be chosen.

O

SNTP-/IP-forwarding

SNTP routing The SNTP routing allows time synchronization of pro-tection devices with any SNTP server through the Sta-tion Gateway

O

IP address SNTP Server(v4)

The IP address for SNTP routing O

IP forwarding The IP forwarding opens the Station Gateway for for-warding IP packets. If SNTP routing is enabled, the IPforwarding is also enabled automatically

O

IEC61850 report settings

Trigger options The trigger options in the station gateway. If you useIEC devices with limited support of trigger options.

O

Integrity period The integrity period for setting the cycle time of buff-ered reports

O

IEC61850 time settings

Reconnect timeout Interval between connection lost and next connectionattempt. Between all following connection attempts isthe same time interval.

O

Connect timeout Timeout for connect response (TCP level) O

Initiate timeout Timeout for connect response (MMS level) O

Disconnect timeout Timeout for disconnect response (MMS level) O

Read list timeout Timeout for read dataset members list O

Read attribute timeout Timeout for read dataset members list O

Data set timeout Timeout for read dataset values O

Read timeout Timeout for read single value O

Page 46: StatCon – STATionDevice CONfiguration Tool - Siemens · StatCon – STATionDevice CONfiguration Tool User manual ... With StatCon application it is possible to configure the connection

46

A documentation by: Siemens. © Siemens AG 2015. All rights reserved.

Documentation | StatCon – STATion Device CONfiguration Tool

Write timeout Timeout for write requests (enabling of report controlblocks is write request too)

O

Control timeout Timeout for total control workflow (ReadAttributes +Select + Operate)

O

Table 11 - StationGateway properties

3.4 Download to device

For opening the “Download configuration” panel, select the corresponding device in “Sta-tionDevices” panel and click the icon on toolbar.

Figure 50 - Open "Download configuration" panel

If the panel was opened, the configured IP address of the S7 port is set as download con-nection IP address by default.

Via button “browse” the application is searching for all available Station Gateways in theconnected network. The Station Gateways, which was detected by the search, will belisted in the table. Selecting one of the Station Gateways in the list will set its IP address asdownload connection IP address in the text box.

Downloading the configured properties can by executed by the download button.

Figure 51 – Station Gateway download configuration panel

3.5 Online and diagnostics

In “Online & diagnostics” panel the current online values of the selected Station Gatewayare displayed. Furthermore you can execute the online actions of the Station Gateway viathe control buttons.

For opening the “Online & diagnostics” panel, select the corresponding device in “Sta-tionDevices” panel and click the icon on toolbar.

Page 47: StatCon – STATionDevice CONfiguration Tool - Siemens · StatCon – STATionDevice CONfiguration Tool User manual ... With StatCon application it is possible to configure the connection

47

A documentation by: Siemens. © Siemens AG 2015. All rights reserved.

Documentation | StatCon – STATion Device CONfiguration Tool

Figure 52 - Open "Online & diagnostics" panel

If the panel was opened, it directly connects to the device and reads out all availableonline values.

Figure 53 – Station Gateway online & diagnostics panel

Property Description

StationGateway

Name The name of the Station Gateway in the project

Connection status The status of the connection

Page 48: StatCon – STATionDevice CONfiguration Tool - Siemens · StatCon – STATionDevice CONfiguration Tool User manual ... With StatCon application it is possible to configure the connection

48

A documentation by: Siemens. © Siemens AG 2015. All rights reserved.

Documentation | StatCon – STATion Device CONfiguration Tool

Firmware version The installed firmware version

Type The type of the hardware

Trigger options The trigger options in the Station Gateway as hex number

Integrity period (ms) The integrity period in the Station Gateway in ms

Reconnect timeout The Reconnect timeout in the Station Gateway

Connect timeout The Connect timeout in the Station Gateway

Initiate timeout The Initiate timeout in the Station Gateway

Disconnect timeout The Disconnect timeout in the Station Gateway

Read list timeout The Read list timeout in the Station Gateway

Read attribute timeout The Read attribute timeout in the Station Gateway

Data set timeout The Data set timeout in the Station Gateway

Read timeout The Read timeout in the Station Gateway

Write timeout The Write timeout in the Station Gateway

Control timeout The Control timeout in the Station Gateway

SNTP routing The status of SNTP routing. If SNTP routing is enabled, theused SNTP server IP is displayed. Otherwise status is disa-bled.

IP forwarding The status of IP forwarding

StationGateway configurations

Lists all Station Gateway adapters and its connection settings

Software status

IEC service started The status of the IEC process on Station Gateway

Uptime Information about, how long the system has been runningand how many users are logged on

Control

Refresh informations Reloading the online informations

Update firmware Updating the Station Gateway firmware

Create diagnose ZIP Loading all diagnose files from Station gateway and save aszip file on local system

Restart StationGateway Restarting the Station Gateway

Table 12 - Station Gateway online and diagnostics

3.6 Copy IEC61850 tag address

The Station Gateway addresses of IEC61850 Data Attributes must be projected in the S7program. StatCon can help you to configure the correct address to the S7 blocks.

Therefore your IEC device should be added to your StatCon project (see External devices).

Page 49: StatCon – STATionDevice CONfiguration Tool - Siemens · StatCon – STATionDevice CONfiguration Tool User manual ... With StatCon application it is possible to configure the connection

49

A documentation by: Siemens. © Siemens AG 2015. All rights reserved.

Documentation | StatCon – STATion Device CONfiguration Tool

If your IEC device exists you can select the Data Attribute which should be configured onS7 block and transfer it by drag & drop to the tag list of the Station Gateway.

Figure 54 - Drag Data Attribute to tag list

If the Data Attributes was added to the tag list, you can select one of the entries and openits context by a right click on mouse. In the context you can choose entry “Copy address toclipboard” and after this you can paste address to your block in S7 program.

NOTE: The addresses of the same tags in different types of station devices are notequal, because the address separators of the IEC objects are not the same. So, it isnot possible to use the address of a Station Gateway in a Station Controller.

Figure 55 - Copy tag address

Page 50: StatCon – STATionDevice CONfiguration Tool - Siemens · StatCon – STATionDevice CONfiguration Tool User manual ... With StatCon application it is possible to configure the connection

50

A documentation by: Siemens. © Siemens AG 2015. All rights reserved.

Documentation | StatCon – STATion Device CONfiguration Tool

4.1 General

Station devices of type IEC61850 Client Basic Library just should help users which workwith an IEC61850 Client library for PCS7 or TIA Portal to project the correct Data Attributeaddresses of their IEC devices.

Therefore Station devices of this type have no hardware configuration and no online func-tionality. Only the IEC tags can be configured and their addresses can be copied to theblocks to an S7 or TIA Portal program.

4.2 Add IEC61850 Client Basic Library

An IEC61850 Client Basic Library can be added to the project within the “Station Devices”panel. To add a new controller open the context on toolbar item “Add StationDevice” andselect sub item “Add IEC61850 Client Basic Library”. A new library will be added to the pro-ject.

Figure 56 - Add new IEC61850 Client Basic Library

4.3 Copy IEC61850 tag address

The practice of copying tag addresses is the same as described for Station Gateways. Youcan follow the instructions in the Station Gateway chapter (see Copy IEC61850 tag ad-dress).

NOTE: The tag addresses of an IEC61850 Client Basic Library are not equal to the tagaddresses of a Station Gateway because of the different IEC object separators. Forusing the addresses with IEC61850 Client Basic Library the addresses are separatedwith sign “$$”. So, addresses from a tag in Station Gateway will not work on a blockof the IEC61850 Client Basic Library.

4 IEC61850 Client Basic Library

Page 51: StatCon – STATionDevice CONfiguration Tool - Siemens · StatCon – STATionDevice CONfiguration Tool User manual ... With StatCon application it is possible to configure the connection

51

A documentation by: Siemens. © Siemens AG 2015. All rights reserved.

Documentation | StatCon – STATion Device CONfiguration Tool

The online mode is a feature that allows you to read tag values in real time from a client orserver stack and display them in StatCon. Once activated it will connect to your devicewith the IP address that is configured in your StationController and try to read your tagvalues also if possible the quality code. It can be activated by using the “Go online” buttonin the “Online” menu or the corresponding button in the tab menu (see Figure 57 - Acti-vate online mode).

Figure 57 - Activate online mode

Activating the online mode changes the color of the log panel to orange and displays atext in the title to signal its activation. Be aware that it is not possible to edit your projectwhile this mode is active, like modifying your tag values, adding new tags, deleting tagsand so on.

To deactivate this mode, use the “Go offline” button in the “Online” menu, just below the“Go offline” button (see Figure 58 - Deactivate online mode).

Figure 58 - Deactivate online mode

The stack details view of your server or client device will display two new columns withactive online mode: “Tag value” and “Quality code”. These columns will be automaticallyrefreshed every 3 seconds with the values that are in your assigned DB’s at the currentmoment. A message will be displayed in case of errors or connection problems.

Figure 59 - A client stack details view with active online mode

5 Online mode

Page 52: StatCon – STATionDevice CONfiguration Tool - Siemens · StatCon – STATionDevice CONfiguration Tool User manual ... With StatCon application it is possible to configure the connection

52

A documentation by: Siemens. © Siemens AG 2015. All rights reserved.

Documentation | StatCon – STATion Device CONfiguration Tool

The accessible devices view allows you to browse your network for devices that are able tocommunicate per DCP protocol. The located devices are then presented in a list view withtheir specific parameters and attributes. It is possible to access the view with the “Accessi-ble devices” button in the “Online” menu or the corresponding button in the tab menu(see Figure 60 - Activate accessible devices view).

Figure 60 - Activate accessible devices view

The accessible devices that are found can be partially edited. It is possible to change the IPconfiguration of a found device by changing the corresponding attribute and selecting theapply button.

Figure 61 - Accessible devices list

The view can be expanded by deselecting the “Only show supported DCP devices” check-box.

Your stack will then be assigned to your selected StationController.

6 Accessible devices view

Page 53: StatCon – STATionDevice CONfiguration Tool - Siemens · StatCon – STATionDevice CONfiguration Tool User manual ... With StatCon application it is possible to configure the connection

53

A documentation by: Siemens. © Siemens AG 2015. All rights reserved.

Documentation | StatCon – STATion Device CONfiguration Tool

www.siemens.com

[email protected]

Phone: +49 (0) 721/595 - 7522

All rights reserved. All trademarks usedare owned by Siemens or their respective owners.

© Siemens AG 2015

Siemens AG

DF PL DS TS DELSiemensallee 8476187 KarlsruheGERMANY