Star Delta Calculations

9
Star/Delta Connections

description

engineering

Transcript of Star Delta Calculations

Page 1: Star Delta Calculations

Star/Delta Connections

Page 2: Star Delta Calculations

Star Connection

pL II

pL VV 3

Vp

VL

VL

I p I p

I p

I L

I L

I L

Page 3: Star Delta Calculations

Delta Connection

PL VV I L

I L

I L

I p I p

I p

VL

Vp

PL II 3

Page 4: Star Delta Calculations

3 Phase Power

Single phase power

In a balanced 3 phase system the total power is equal to three times the power in any one phase

In star and delta, 3 phase power can be calculated using this formula

)(cos. fpIVP

)(cos.3 fpIVP PP

)(cos.3 fpIVP LL

Page 5: Star Delta Calculations

3 Phase Power Example 1

A balanced star connected 3 phase load of 10Ω per phase is supplied from a 400v 50hz mains supply at unity power factor

Calculate the phase voltage, the line current and the total power consumed

pL II

pL VV 3

3L

P

VV

VVP 9.2303

400

Page 6: Star Delta Calculations

3 Phase Power Example 1

A balanced star connected 3 phase load of 10Ω per phase is supplied from a 400v 50hz mains supply at unity power factor

Calculate the phase voltage, the line current and the total power consumed

pL II

R

VI

P

PPL R

VII

AII PL 2310

230

Page 7: Star Delta Calculations

3 Phase Power Example 1

A balanced star connected 3 phase load of 10Ω per phase is supplied from a 400v 50hz mains supply at unity power factor

Calculate the phase voltage, the line current and the total power consumed

)(cos.3 fpIVP LL

kWP 161234003

Page 8: Star Delta Calculations

Example 2

A 20kW 400v balanced delta connected load has a power factor of 0.8

Calculate the line current and the phase current

cos3

L

LV

PI

)(cos.3 fpIVP LL

8.04003

)(20000

wI L

AI L 36

Page 9: Star Delta Calculations

Example 2

A 20kW 400v balanced delta connected load has a power factor of 0.8

Calculate the line current and the phase current

AI L 36Delta connection therefore

PL II 3

3

36PI

3L

P

II

AI P 78.20