Guidelines for the safe use of flammable refrigerants in ...
Standards and Regulations Update for Flammable Refrigerants
Transcript of Standards and Regulations Update for Flammable Refrigerants
eurammon Symposium 2017
Standards and Regulations
Update for Flammable Refrigerants
Dr. Frank Rinne
Schaffhausen, 22nd/23rd June, 2017
2
Schaffhausen, 22nd / 23rd June, 2017 Page 2
Agenda
• Refrigerant Overview and Classification of Flammable Refrigerants
• Standards in the Context with Regulations
• EN378
• EN60335-2-89 Charge Extension & Safety Concept
• EN60335-2-40
• Summary
3
Schaffhausen, 22nd / 23rd June, 2017 Page 3
Refrigerant Overview
• F-Gas Regulation has an impact to the refrigerant selection
• System Architecture = f(Refrigerant Properties)
R-410A-like
R404A- &
R407A/F-like
R134a-like
GWP
< 1500
~600
150 - 300
1234yf/ze
R410A
R407C/A/F
0 500 1000 1500 2000
Co
oli
ng
ca
pa
cit
y / P
res
su
re
R32/ HFO blends(DR5, L41, ARM71)
R134a
CO2
R404A
R290
NH3
(3922)
HFO blendsXL20/40, HDR110, L20, ARM20)
R450A,R513A
Systems < 40kW &
SAV > 40 Mtons
CO2 equivalent
2020
Indirect Systems
2022
Raks > 40 kW
Hermetical seal
Systems
2022
2500
400-675
Middle
GWP2030 2024
R448A/R449A
A1 not flammable
A2L – low flammability
A3 – flammable
B2L – toxic, low flammability
4
Schaffhausen, 22nd / 23rd June, 2017 Page 4
Classification of Refrigerants (1)
Quelle: Daikin
5
Schaffhausen, 22nd / 23rd June, 2017 Page 5
Refrigerant Classification (2)
HDR110,
DR3,R32,
R1234yf,
R1234ze,
R143A
717
2L
11,12,13,13B1,14,22,23,113,114,
115,116,124,125,134a,218,227ea
,236fa,C318,401A,401B,401C,40
2A,402B,403B,404A,407A,407B,
407C,407D,407E,407F,408A,409
A,409B,410A,410B,414A,414B,4
16A,417A,417B,420A,421A,421B
,422A,422B,422C,422D,423A,42
4A,425A,426A,427A,428A,434A,
437A,438A,442A,500,501,502,50
3,504,507A,508A,508B,509A,403
A,411A,411B,412A,413A,418A,41
9A,744,
30,123,245fa
142b,152a,415
A,415B,406A,4
39A,440A,512
A
50,170,1150,290,
1270,E170,600,6
00a,601,601a,429
A,430A,431A,432
A,433A,433B,433
C,435A,436A,441
A,510A,511a
1 32
Quelle: Daikin
6
Schaffhausen, 22nd / 23rd June, 2017 Page 6
Safety Data sheet R32 vs R290
R32 R290=
Classification Rules defined in the Global Harmonized System (GHS).
Industry started an initiative to change the classification in GHS in order to
differentiate between A2L and A3
7
Schaffhausen, 22nd / 23rd June, 2017 Page 7
European Treaty
Art. 137
Single marketSafety of workers
Remark : Only minimum requirements
National regulations:
Dangerous Substances and Explosive Atmospheres Regulations
(DSEAR) : UK
Betriebs-Sicherheits-Verordnung (BetrSichV) : DE
TBT Technical Barriers of Trade
Product Harmonisation
PED/MD/LVD/EMC
…..
ATEX (94/9/EC)
(product) - IEC/EN 60079
ATEX (99/92/EC)
(workplace)- TRBS-2152
Art. 95
European Regulations & Standards
CustomerOEM
8
Schaffhausen, 22nd / 23rd June, 2017 Page 8
Euro
pean
levelIn
ternatio
nal level
TC 86 SC1
ISO (DIS) 5149
plus others
TC 61 SC 61C
IEC 60335-2-24,
IEC 60335-2-89
TC 61 SC 61D
IEC 60335-2-40
TC 182
EN 378
plus others
CLC 61
EN 60335-2-40
EN 60335-2-24
EN 60335-2-89
International and European Committees and Standards
9
Schaffhausen, 22nd / 23rd June, 2017 Page 9
Household Appliances Or Similar Use - Commercial Systems
- Industrial SystemsEN 60335 series
-2-24 -2-89 -2-40
D
o
m
e
s
t
i
c
C
o
m
m
e
r
c
i
a
l
H
e
a
t
p
u
m
p
s
/
A
C
MD
MD
MD
PED
Horizontal Standard For All Ref. Systems: EN378 (Horizontal Standard Covers Fundamental Principles, Concepts, Terminology Or Technical Characteristics)
Standards Update for A2L /A3
• EN 378 is harmonized with ISO 5149
• EN 60335-2-40
• Voting 2017 for A2L
• WG started, A2/A3 Charge Ext. 2017
• EN60335-2-89
• WG A2/A3 started Charge Ext. 2018Target: Refrigerant Charge up to 0,5 kg
Horizontal & Vertical Safety Standards
10
Schaffhausen, 22nd / 23rd June, 2017 Page 10
EN378 in the Context with Other Regulations & Standards
EN 378
Building
standards
ADR
GHS(safety data
sheet)
MD TRBS
ATEX
PED
EN 60335
11
Schaffhausen, 22nd / 23rd June, 2017 Page 11
Scope EN378: Normative References
EN378
Part 1: Basic
requirements,
definitions,
classification and
selection criteria
Part 3 Part 4
EN 12263
EN14276-2
ISO817
EN 13445…
EN 13480…
EN 14276…
EN 60335…
EN 837…
EN 60079 (Explosive Atmospheres, ATEX harmonized)…
EN 1363
EN 1364
EN 1365
…..
ISO 11650
ISO 13043
EN 60335-2-104
Part 2: Design,
construction, testing,
marking and
documentation(only this part is
harmonized with PED and
has legal character)
Part 3: Installation
site and personal
protection
Part 4: Operation,
maintenance, repair
and recovery
I guess all documents are more than 1000 pages, not so easy!
12
Schaffhausen, 22nd / 23rd June, 2017 Page 12
What is new in EN378
Part 1: Basic Requirements, Definitions & Classifications
• Vocabulary
o Separate Machinery Room
o Access Category
o Open Air
• Flammability Class 2L
• Additional Calculation for human comfort
• Alternative risk managment for occupied space
• Refrigerant tables updates
13
Schaffhausen, 22nd / 23rd June, 2017 Page 13
Determine the charge based on flammability
a
general
access
b
Superv.
access
c
Author.
access
I = Occupied space
II Comp. In
mach.-
room / open air
14
Schaffhausen, 22nd / 23rd June, 2017 Page 14
EN378 has 3 Levels of Refrigerant Charge
1. m1 = 4 [m3] * LFL [kg/m3] (-> small kitchen)
2. m2 = 26 [m3] * LFL [kg/m3]
3. m3 = 130 [m3] * LFL [kg/m3]
• Additional risk assessment and additional ventilation
Examples:
Propane, A3, LFL = 0,038 kg/m3
m1 = 4 m3 * 0,038 kg/m3 = 0,150 kg
m2 = 26 m3 * 0,038 kg/m3 = 0,988 kg
m3 = 130 m3 * 0,038 kg/m3 = 4,94 kg
R32, A2L, LFL = 0,307 kg/m3
m1 = 4 m3 * 0,307 kg/m3 * 1,5* = 1,8 kg
m2 = 26 m3 * 0,307 kg/m3 * 1,5 = 11,97 kg
m3 = 130 m3 * 0,307 kg/m3 * 1,5 = 59,87 kg
* 50% more refrigerant charge than A2
15
Schaffhausen, 22nd / 23rd June, 2017 Page 15
C.2 Charge Limit Calculation
mmax= 2,5 × LFL 5/4 × h0 × A1/2 (C.1)
Amin = m2/(2,5 × LFL5/4 × h0)2 (C.2)
16
Schaffhausen, 22nd / 23rd June, 2017 Page 16
Alternative for risk management of ref.- systems in occupied spaces (C.3) - Increase the Charge
• These alternative provisions can only be used for an occupied space which fulfils all of the following conditions:
17
Schaffhausen, 22nd / 23rd June, 2017 Page 17
System Design for Mulitsplit Units according Risk Assessment C.3
Each piping is not oversized, in
case of leakage of one
evaporator the other evaporators
will still work and limit the leak
amount -> preferred design
If the main pipe is installed in
occupied space, the complete
gas will leak, this design is not
allowed.
18
Schaffhausen, 22nd / 23rd June, 2017 Page 18
What is new in EN378 2(2)
Part 3: Installation site and personal protection
• Separate machinery room
• Requirements for A2L´s
• Equipment not in occupied space nor in machinery room
• Sprinkler in ammonia machinery rooms
Part 4: Operation, maintenance, repair
and recovery
• New text for evacuating procedure
• Testing halocarbon for moisture
• Handling Ammonia during service
o When to dispose as hazordous
waste
o When to vent into water
o How to dispose water
Part 2: Design, construction, testing,
marking and documentation
• Aligned with PED and MD
• Flowchart updated
• 4 new Annexes
o Stress corrosion cracking
o Leak simulation testing
o Comissioning procedure
o Ignition sources
19
Schaffhausen, 22nd / 23rd June, 2017 Page 19
Seite 19/11
Ice-cream
dispensers
Applicable types of equipment related to the IEC 60335-2-89
20
Schaffhausen, 22nd / 23rd June, 2017 Page 20
150 g ?
1 kg or more
150 g OK
Relevant standards and resulting amount of low GWP refrigerants
21
Schaffhausen, 22nd / 23rd June, 2017 Page 21
Title of committee/working group:
TC61/SC61C/WG 4
Task of TC61/SC61C/WG4:
IEC 60335-2-89-A2/Ed2: Household and similar electrical appliances -
Safety - Part 2-89: Particular requirements for commercial refrigerating
appliances with an incorporated or remote refrigerant unit or compressor
To define the maximum flammable refrigerant amount for appliances
according to IEC 60335-2-89 and measures to maintain the equivalent
safety level as for the present limit.
Members of the WG4:
26 Members out of 13 countries
(AT, BE, BR, CZ, DE, FI, GB, IT, JO, JP, NZ, SK and US)
Title of committee/working group and task
22
Schaffhausen, 22nd / 23rd June, 2017 Page 22
EN378 vs EN 60335-2-89
Standard Supermarket System
• OEM Building the System• EN378
• PED
• MD
• LVD
• EMC
• ATEX Standards
• Installation on site• RISK ASSESSMENT
• Workplace Safety
Integrated Display Cabinet
• OEM Building the Cabinet• EN60335-2-89
• PED
• MD
• LVD
• EMC
• ATEX Standards
• Leak Simulation Test
• Type Approval Notified Body
• Installation on site
23
Schaffhausen, 22nd / 23rd June, 2017 Page 23
The risk with 500g flammable refrigerant (R290)
must be the same as we have with the current limit of 150 g
In detail and out of the proposal from WG4 and comments of NC:
• Refrigerants which are lighter than air (e.g. R50) should be excluded
For appliances with more than 150 g flammable refrigerant…
• Determination of gas concentration might be necessary
• Minimum air flow for appliances between 151 g and 13 x LFL flammable
refrigerant could be required or necessary
• The airflow should be guaranteed in any operating conditions
• No refrigerant-containing parts should be exposed to the outside of the appliance
• Low temperature solder alloys will be not accepted for pipe connections
• All electrical components should be non-sparking electrical apparatus
• Application should have a tested tightness control level of less than 3 grams per
year
What direction is TC61/SC61C/WG4 going
24
Schaffhausen, 22nd / 23rd June, 2017 Page 24
Leak Simulation Test
25
Schaffhausen, 22nd / 23rd June, 2017 Page 25
Time scale for including the WG4 proposal into the IEC 60335-2-89:
• October 2016: WG4 meeting and SC61C meeting in week 40 (4th to 8th of
October 2016) with work on the compilation of comments on the WG4
proposal – 61C/671/DC
• Q4_2016: Creation of a DC out of the compilated comments
• Q3_2017: Creation of a CDV out of the latest DC
• Q1_2018: Discussion of CDV and creation of a FDIS
• Q2_2018: Publishing of the 3rd edition from the IEC 60335-2-89
standard
Possible time scale of TC61/SC61C/WG4
26
Schaffhausen, 22nd / 23rd June, 2017 Page 26
Residential & Commercial Comfort EN60335-2-40
• EN 60335-2-40
– Household and similar electrical appliances. Safety. Particular requirements for electrical heat pumps, air-conditioners and dehumidifiers
• A2L Refrigerants in current version NOT included
• A3 Refrigerants can be used up to 1,5 kg only in indirect systems
• EN 60335-2-40 Revison will be launched end of 2017/ early 2018
– Taylored for A2L refrigerants with a maximum charge of 80 kg A2L
– Separate Working Group to increase charge limits for A3 refrigerants, driven by China for small Split Systems up to 500g, release not before 2018
Propane Air/Water HP
up to 1,5 kg charge
27
Schaffhausen, 22nd / 23rd June, 2017 Page 27
Summary
• A2L and A3 Refrigerants are considered in PED, MD and ATEX equally
(H220-extremly flammable)
• EN378 propose big differentiations in the charge limits for A2L and A3
• Human comfort for A2L´s can use higher refrigerant charge as refrigeration
• Flammable refrigerants can be used only in appropriate systems, which
are designed for flammable refrigerants (EN60079 – ATEX)
• Work place safety (TRBS) to be considered for installation site
Contact:
Dr. Frank Rinne
Emerson Commercial & Residential Solutions
Pascalstrasse 65, 52076 Aachen
Germany