Indoor, Instrument Signal Cables, Non-IS (items 1, 2, 3, 4)……………………………………………..……………………...………….Page 3
Indoor, Instrument Signal Cables, IS (items 5, 6, 7, 8)…………………………………………………...…...……………………..……….Page 5
Outdoor, Instrument Signal Cables, Non-IS (items 9, 10, 11, 12)……………………………….…..……………………...…………….Page 7
Outdoor, Instrument Signal Cables, IS (items 13, 14, 15, 16)………………………………………...…………………………..……….Page 9
Indoor, Fire Resistant Cables, Non-IS (items 17, 18, 19)…………………………………………………..……..…………………….……….Page 11
Outdoor, Fire Resistant Cables, Non-IS (items 20, 21, 22, 23)…………………………………………..…………………………..……….Page 12
Outdoor, Instrument Signal Cables, Non-IS, with individual and overall Shield (items 24, 25, 26, 27)…….…………...…Page 14
Outdoor, Instrument Signal Cables, with Ind and overall Shield, IS (items 28, 29, 30, 31)……..…..……………………...…Page 16
Fire Resistant Power Cables (items 32, 33, 34)…………………………………………………………………......…..……………….………Page 18
Instrument Standard Power Cables (items 35, 36, 37, 38)………………………………………………….......……………….………….Page 20
Fieldbus Cables (items 39, 40, 41)……………………………………………………………….………………………...……………….……………Page 22
Fiber Optic Cables (items 42, 43, 44)……………………………………………………………….…………………...……………..……………Page 23
Contents
Rev. 0 (July-2013) Page 2 of 24 Brunei Shell Petroleum Sdn. Bhd.
Standard BSP EFA Cables
Item SAP Material No. Simplified Cable Description Full Cable Specifications
1 1001694864 Indoor, Instrument Signal, Non-IS, 1 Pair, 0.5mm², Black
Fire spec non armoured electrical cable
Application NON IS INSTRUMENT SIGNAL, SINGLE PAIR, INDOOR
Flammability properties FLAME RETARDANT
Voltage 300 V
Max Operating Temp 90 DEGREE C
Design spec BS EN 50288-7 IEC 60754 & 61034 - LSZH
Construction XLPE, MS,OS, FR-LSZH
Mat, conductor wire ANNEALED COPPER WIRE
Mat spec, insulation CROSS-LINKED POLYETHYLENE
Mat spec, outer sheath FLAME RETARDANT -LOW SMOKE ZERO HALOGEN TO IEC 60754 & 61034
Colour, outer sheath BLACK
Screening OVERALL SCREEN ALUMUNIUM POLYESTER TAPE WITH TINNED COPPER DRAIN WIRE
Flame, propagation FLAME RETARDANT to IEC-60332-1 and IEC60332-3-22
Number, Pairs 1 PAIR, CONDUCTOR SIZE: 16/0.2
Pair Colour Identifications AS PER BS EN50288-7, BLACK AND WHITE WITH NUMBERS EMBOSSED FOR EACH PAIR.
Cross section, cores(mm2) 0.5 SQ. MM.
Diameter, OD, overall (mm) 7.00 MM, TOLERANCE AS PER EN50288-7.
Marking on the external surface of the outer sheath OUTER SHEATH TO BE EMBOSSED WITH BS NUMBER, CABLE SIZE, TYPE (FLAME RETARDANT REDUCED
TOXICITY) AND MANUFACTURER'S NAME.
Cable drum shall have fixed weatherproof identification of the following: SAP NUMBER, MANUFACTURER'S NAME AND YEAR OF MANUFACTURE, ORDER AND
ITEM NUMBER, CABLE TYPE AND SIZE, VOLTAGE GRADE AND MARKING FOR DIRECTION OF LAY.
Length Identification: CABLE DIAMETER 10 mm AND ABOVE SHOULD BE MARKED WITH LENGTH IDENTIFICATION AT REGULAR INTERVALS OF 1 METER,STARTING
FROM "0" END WHICH IS ATTACHED TO THE SPINDLE OF THE DRUM.
Routine and Type test reports: TEST CERTIFICATES TO BE SUPPLIED PER BATCH, IDENTIFYING APPLICABLE DRUMS.
Fire spec non armoured electrical cable CBL ELEC N-ARM FIRE
2 1001694865 Indoor, Instrument Signal, Non-IS, 2 Pairs, 0.5mm², Black
Fire spec non armoured electrical cable
Application NON IS INSTRUMENT SIGNAL, MULTIPAIR, INDOOR
Flammability properties FLAME RETARDANT
Voltage 300 V
Max Operating Temp 90 DEGREE C
Design spec BS EN 50288-7 IEC 60754 & 61034 - LSZH
Construction XLPE, MS, OS, FR-LSZH
Mat, conductor wire ANNEALED COPPER WIRE
Mat spec, insulation CROSS-LINKED POLYETHYLENE
Mat spec, outer sheath FLAME RETARDANT -LOW SMOKE ZERO HALOGEN TO IEC 60754 & 61034
Colour, outer sheath BLACK
Screening OVERALL SCREEN ALUMUNIUM POLYESTER TAPE WITH TINNED COPPER DRAIN WIRE
Flame, propagation FLAME RETARDANT to IEC-60332-1 and IEC60332-3-22
Number, Pairs 2 PAIRS, CONDUCTOR SIZE: 16/0.2
Pair Colour Identifications AS PER BS EN50288-7, BLACK AND WHITE WITH NUMBERS EMBOSSED FOR EACH PAIR.
Cross section, cores(mm2) 0.5 SQ. MM.
Diameter, OD, overall (mm) 7.90 MM, TOLERANCE AS PER EN50288-7.
Marking on the external surface of the outer sheath OUTER SHEATH TO BE EMBOSSED WITH BS NUMBER, CABLE SIZE, TYPE (FLAME RETARDANT REDUCED
TOXICITY) AND MANUFACTURER'S NAME.
Cable drum shall have fixed weatherproof identification of the following: SAP NUMBER, MANUFACTURER'S NAME AND YEAR OF MANUFACTURE, ORDER AND
ITEM NUMBER, CABLE TYPE AND SIZE, VOLTAGE GRADE AND MARKING FOR DIRECTION OF LAY.
Length Identification: CABLE DIAMETER 10 mm AND ABOVE SHOULD BE MARKED WITH LENGTH IDENTIFICATION AT REGULAR INTERVALS OF 1 METER,STARTING
FROM "0" END WHICH IS ATTACHED TO THE SPINDLE OF THE DRUM.
Routine and Type test reports: TEST CERTIFICATES TO BE SUPPLIED PER BATCH, IDENTIFYING APPLICABLE DRUMS.
Fire spec non armoured electrical cable CBL ELEC N-ARM FIRE
Rev. 0 (July-2013) Page 3 of 24 Brunei Shell Petroleum Sdn. Bhd.
Standard BSP EFA Cables
Item SAP Material No. Simplified Cable Description Full Cable Specifications
3 1001694866 Indoor, Instrument Signal, Non-IS, 10 Pairs, 0.5mm², Black
Fire spec non armoured electrical cable
Application NON IS INSTRUMENT SIGNAL, MULTIPAIR, INDOOR
Flammability properties FLAME RETARDANT
Voltage 300 V
Max Operating Temp 90 DEGREE C
Design spec BS EN 50288-7 IEC 60754 & 61034 - LSZH
Construction XLPE, MS, OS, FR-LSZH
Mat, conductor wire ANNEALED COPPER WIRE
Mat spec, insulation CROSS-LINKED POLYETHYLENE
Mat spec, outer sheath FLAME RETARDANT -LOW SMOKE ZERO HALOGEN TO IEC 60754 & 61034
Colour, outer sheath BLACK
Screening OVERALL SCREEN ALUMUNIUM POLYESTER TAPE WITH TINNED COPPER DRAIN WIRE
Flame, propagation FLAME RETARDANT to IEC-60332-1 and IEC60332-3-22
Number, Pairs 10 PAIRS,CONDUCTOR SIZE: 16/0.2
Pair Colour Identifications AS PER BS EN50288-7, BLACK AND WHITE WITH NUMBERS EMBOSSED FOR EACH PAIR.
Cross section, cores(mm2) 0.5 SQ. MM.
Diameter, OD, overall (mm) 17.2 MM, TOLERANCE AS PER EN50288-7.
Marking on the external surface of the outer sheath OUTER SHEATH TO BE EMBOSSED WITH BS NUMBER, CABLE SIZE, TYPE (FLAME RETARDANT REDUCED
TOXICITY) AND MANUFACTURER'S NAME.
Cable drum shall have fixed weatherproof identification of the following: SAP NUMBER, MANUFACTURER'S NAME AND YEAR OF MANUFACTURE, ORDER AND
ITEM NUMBER, CABLE TYPE AND SIZE, VOLTAGE GRADE AND MARKING FOR DIRECTION OF LAY.
Length Identification: CABLE DIAMETER 10 mm AND ABOVE SHOULD BE MARKED WITH LENGTH IDENTIFICATION AT REGULAR INTERVALS OF 1 METER,STARTING
FROM "0" END WHICH IS ATTACHED TO THE SPINDLE OF THE DRUM.
Routine and Type test reports: TEST CERTIFICATES TO BE SUPPLIED PER BATCH, IDENTIFYING APPLICABLE DRUMS.
Fire spec non armoured electrical cable CBL ELEC N-ARM FIRE
4 1001694867 Indoor, Instrument Signal, Non-IS, 20 Pairs, 0.5mm², Black
Fire spec non armoured electrical cable
Application NON IS INSTRUMENT SIGNAL, MULTIPAIR, INDOOR
Flammability properties FLAME RETARDANT
Voltage 300 V
Max Operating Temp 90 DEGREE C
Design spec BS EN 50288-7 IEC 60754 & 61034 - LSZH
Construction XLPE, MS, OS, FR-LSZH
Mat, conductor wire ANNEALED COPPER WIRE
Mat spec, insulation CROSS-LINKED POLYETHYLENE
Mat spec, outer sheath FLAME RETARDANT -LOW SMOKE ZERO HALOGEN TO IEC 60754 & 61034
Colour, outer sheath BLACK
Screening OVERALL SCREEN ALUMUNIUM POLYESTER TAPE WITH TINNED COPPER DRAIN WIRE
Flame, propagation FLAME RETARDANT to IEC-60332-1 and IEC60332-3-22
Number, Pairs 20 PAIRS,CONDUCTOR SIZE: 16/0.2
Pair Colour Identifications AS PER BS EN50288-7, BLACK AND WHITE WITH NUMBERS EMBOSSED FOR EACH PAIR.
Cross section, cores(mm2) 0.5 SQ. MM.
Diameter, OD, overall (mm) 22.3 MM, TOLERANCE AS PER EN50288-7.
Marking on the external surface of the outer sheath OUTER SHEATH TO BE EMBOSSED WITH BS NUMBER, CABLE SIZE, TYPE (FLAME RETARDANT REDUCED
TOXICITY) AND MANUFACTURER'S NAME.
Cable drum shall have fixed weatherproof identification of the following: SAP NUMBER, MANUFACTURER'S NAME AND YEAR OF MANUFACTURE, ORDER AND
ITEM NUMBER, CABLE TYPE AND SIZE, VOLTAGE GRADE AND MARKING FOR DIRECTION OF LAY.
Length Identification: CABLE DIAMETER 10 mm AND ABOVE SHOULD BE MARKED WITH LENGTH IDENTIFICATION AT REGULAR INTERVALS OF 1 METER,STARTING
FROM "0" END WHICH IS ATTACHED TO THE SPINDLE OF THE DRUM.
Routine and Type test reports: TEST CERTIFICATES TO BE SUPPLIED PER BATCH, IDENTIFYING APPLICABLE DRUMS.
Fire spec non armoured electrical cable CBL ELEC N-ARM FIRE
Rev. 0 (July-2013) Page 4 of 24 Brunei Shell Petroleum Sdn. Bhd.
Standard BSP EFA Cables
Item SAP Material No. Simplified Cable Description Full Cable Specifications
5 1001694868 Indoor, Instrument Signal, IS, 1 Pair, 0.5mm², Blue
Fire spec non armoured electrical cable
Application IS, INSTRUMENT SIGNAL, SINGLE PAIR, INDOOR
Flammability properties FLAME RETARDANT
Voltage 300 V
Max Operating Temp 90 DEGREE C
Design spec BS EN 50288-7 IEC 60754 & 61034 - LSZH
Construction XLPE, MS, OS, FR-LSZH
Mat, conductor wire ANNEALED COPPER WIRE
Mat spec, insulation CROSS-LINKED POLYETHYLENE
Mat spec, outer sheath FLAME RETARDANT -LOW SMOKE ZERO HALOGEN TO IEC 60754 & 61034
Colour, outer sheath BLUE, INTRINSICALLY SAFE
Screening OVERALL SCREEN ALUMUNIUM POLYESTER TAPE WITH TINNED COPPER DRAIN WIRE
Flame, propagation FLAME RETARDANT to IEC-60332-1 and IEC60332-3-22
Number, Pairs 1 PAIR, CONDUCTOR SIZE: 16/0.2
Pair Colour Identifications AS PER BS EN50288-7, BLACK AND WHITE WITH NUMBERS EMBOSSED FOR EACH PAIR.
Cross section, cores(mm2) 0.5 SQ. MM.
Diameter, OD, overall (mm) 7.00 MM, TOLERANCE AS PER EN50288-7.
Marking on the external surface of the outer sheath OUTER SHEATH TO BE EMBOSSED WITH BS NUMBER, CABLE SIZE, TYPE (FLAME RETARDANT REDUCED
TOXICITY) AND MANUFACTURER'S NAME.
Cable drum shall have fixed weatherproof identification of the following: SAP NUMBER, MANUFACTURER'S NAME AND YEAR OF MANUFACTURE, ORDER AND
ITEM NUMBER, CABLE TYPE AND SIZE, VOLTAGE GRADE AND MARKING FOR DIRECTION OF LAY.
Length Identification: CABLE DIAMETER 10 mm AND ABOVE SHOULD BE MARKED WITH LENGTH IDENTIFICATION AT REGULAR INTERVALS OF 1 METER,STARTING
FROM "0" END WHICH IS ATTACHED TO THE SPINDLE OF THE DRUM.
Routine and Type test reports: TEST CERTIFICATES TO BE SUPPLIED PER BATCH, IDENTIFYING APPLICABLE DRUMS.
Fire spec non armoured electrical cable CBL ELEC N-ARM FIRE
6 1001694869 Indoor, Instrument Signal, IS, 2 Pairs, 0.5mm², Blue
Fire spec non armoured electrical cable
Application IS, INSTRUMENT SIGNAL, MULTIPAIR, INDOOR
Flammability properties FLAME RETARDANT
Voltage 300 V
Max Operating Temp 90 DEGREE C
Design spec BS EN 50288-7 IEC 60754 & 61034 - LSZH
Construction XLPE, MS, OS, FR-LSZH
Mat, conductor wire ANNEALED COPPER WIRE
Mat spec, insulation CROSS-LINKED POLYETHYLENE
Mat spec, outer sheath FLAME RETARDANT -LOW SMOKE ZERO HALOGEN TO IEC 60754 & 61034
Colour, outer sheath BLUE, INTRINSICALLY SAFE
Screening OVERALL SCREEN ALUMUNIUM POLYESTER TAPE WITH TINNED COPPER DRAIN WIRE
Flame, propagation FLAME RETARDANT to IEC-60332-1 and IEC60332-3-22
Number, Pairs 2 PAIRS, CONDUCTOR SIZE: 16/0.2
Pair Colour Identifications AS PER BS EN50288-7, BLACK AND WHITE WITH NUMBERS EMBOSSED FOR EACH PAIR.
Cross section, cores(mm2) 0.5 SQ. MM.
Diameter, OD, overall (mm) 7.90 MM, TOLERANCE AS PER EN50288-7.
Marking on the external surface of the outer sheath OUTER SHEATH TO BE EMBOSSED WITH BS NUMBER, CABLE SIZE, TYPE (FLAME RETARDANT REDUCED
TOXICITY) AND MANUFACTURER'S NAME.
Cable drum shall have fixed weatherproof identification of the following: SAP NUMBER, MANUFACTURER'S NAME AND YEAR OF MANUFACTURE, ORDER AND
ITEM NUMBER, CABLE TYPE AND SIZE, VOLTAGE GRADE AND MARKING FOR DIRECTION OF LAY.
Length Identification: CABLE DIAMETER 10 mm AND ABOVE SHOULD BE MARKED WITH LENGTH IDENTIFICATION AT REGULAR INTERVALS OF 1 METER,STARTING
FROM "0" END WHICH IS ATTACHED TO THE SPINDLE OF THE DRUM.
Routine and Type test reports: TEST CERTIFICATES TO BE SUPPLIED PER BATCH, IDENTIFYING APPLICABLE DRUMS.
Fire spec non armoured electrical cable CBL ELEC N-ARM FIRE
Rev. 0 (July-2013) Page 5 of 24 Brunei Shell Petroleum Sdn. Bhd.
Standard BSP EFA Cables
Item SAP Material No. Simplified Cable Description Full Cable Specifications
7 1001694870 Indoor, Instrument Signal, IS, 10 Pairs, 0.5mm², Blue
Fire spec non armoured electrical cable
Application IS, INSTRUMENT SIGNAL, MULTIPAIR, INDOOR
Flammability properties FLAME RETARDANT
Voltage 300 V
Max Operating Temp 90 DEGREE C
Design spec BS EN 50288-7 IEC 60754 & 61034 - LSZH
Construction XLPE, MS, OS, FR-LSZH
Mat, conductor wire ANNEALED COPPER WIRE
Mat spec, insulation CROSS-LINKED POLYETHYLENE
Mat spec, outer sheath FLAME RETARDANT -LOW SMOKE ZERO HALOGEN TO IEC 60754 & 61034
Colour, outer sheath BLUE, INTRINSICALLY SAFE
Screening OVERALL SCREEN ALUMUNIUM POLYESTER TAPE WITH TINNED COPPER DRAIN WIRE
Flame, propagation FLAME RETARDANT to IEC-60332-1 and IEC60332-3-22
Number, Pairs 10 PAIRS,CONDUCTOR SIZE: 16/0.2
Pair Colour Identifications AS PER BS EN50288-7, BLACK AND WHITE WITH NUMBERS EMBOSSED FOR EACH PAIR.
Cross section, cores(mm2) 0.5 SQ. MM.
Diameter, OD, overall (mm) 17.2 MM, TOLERANCE AS PER EN50288-7.
Marking on the external surface of the outer sheath OUTER SHEATH TO BE EMBOSSED WITH BS NUMBER, CABLE SIZE, TYPE (FLAME RETARDANT REDUCED
TOXICITY) AND MANUFACTURER'S NAME.
Cable drum shall have fixed weatherproof identification of the following: SAP NUMBER, MANUFACTURER'S NAME AND YEAR OF MANUFACTURE, ORDER AND
ITEM NUMBER, CABLE TYPE AND SIZE, VOLTAGE GRADE AND MARKING FOR DIRECTION OF LAY.
Length Identification: CABLE DIAMETER 10 mm AND ABOVE SHOULD BE MARKED WITH LENGTH IDENTIFICATION AT REGULAR INTERVALS OF 1 METER,STARTING
FROM "0" END WHICH IS ATTACHED TO THE SPINDLE OF THE DRUM.
Routine and Type test reports: TEST CERTIFICATES TO BE SUPPLIED PER BATCH, IDENTIFYING APPLICABLE DRUMS.
Fire spec non armoured electrical cable CBL ELEC N-ARM FIRE
8 1001694871 Indoor, Instrument Signal, IS, 20 Pairs, 0.5mm², Blue
Fire spec non armoured electrical cable
Application IS, INSTRUMENT SIGNAL, MULTIPAIR, INDOOR
Flammability properties FLAME RETARDANT
Voltage 300 V
Max Operating Temp 90 DEGREE C
Design spec BS EN 50288-7 IEC 60754 & 61034 - LSZH
Construction XLPE, MS, OS, FR-LSZH
Mat, conductor wire ANNEALED COPPER WIRE
Mat spec, insulation CROSS-LINKED POLYETHYLENE
Mat spec, outer sheath FLAME RETARDANT -LOW SMOKE ZERO HALOGEN TO IEC 60754 & 61034
Colour, outer sheath BLUE, INTRINSICALLY SAFE
Screening OVERALL SCREEN ALUMUNIUM POLYESTER TAPE WITH TINNED COPPER DRAIN WIRE
Flame, propagation FLAME RETARDANT to IEC-60332-1 and IEC60332-3-22
Number, Pairs 20 PAIRS,CONDUCTOR SIZE: 16/0.2
Pair Colour Identifications AS PER BS EN50288-7, BLACK AND WHITE WITH NUMBERS EMBOSSED FOR EACH PAIR.
Cross section, cores(mm2) 0.5 SQ. MM.
Diameter, OD, overall (mm) 22.3 MM, TOLERANCE AS PER EN50288-7.
Marking on the external surface of the outer sheath OUTER SHEATH TO BE EMBOSSED WITH BS NUMBER, CABLE SIZE, TYPE (FLAME RETARDANT REDUCED
TOXICITY) AND MANUFACTURER'S NAME.
Cable drum shall have fixed weatherproof identification of the following: SAP NUMBER, MANUFACTURER'S NAME AND YEAR OF MANUFACTURE, ORDER AND
ITEM NUMBER, CABLE TYPE AND SIZE, VOLTAGE GRADE AND MARKING FOR DIRECTION OF LAY.
Length Identification: CABLE DIAMETER 10 mm AND ABOVE SHOULD BE MARKED WITH LENGTH IDENTIFICATION AT REGULAR INTERVALS OF 1 METER,STARTING
FROM "0" END WHICH IS ATTACHED TO THE SPINDLE OF THE DRUM.
Routine and Type test reports: TEST CERTIFICATES TO BE SUPPLIED PER BATCH, IDENTIFYING APPLICABLE DRUMS.
Fire spec non armoured electrical cable CBL ELEC N-ARM FIRE
Rev. 0 (July-2013) Page 6 of 24 Brunei Shell Petroleum Sdn. Bhd.
Standard BSP EFA Cables
Item SAP Material No. Simplified Cable Description Full Cable Specifications
9 1001694872 Outdoor, Instrument Signal, Non-IS, 1 Pair, 0.5mm², Black
Fire spec armoured electrical cable
Application NON IS, INSTRUMENT SIGNAL, SINGLEPAIR, OUTDOOR
Flammability properties FLAME RETARDANT
Voltage 300 V
Max Operating Temp 90 DEGREE C
Design spec BS EN 50288-7 IEC 60754 & 61034 - LSZH
Construction XLPE, MS, FR-LSZH, OS, SWA, FR-LSZH-UV Resistant
Mat, conductor wire ANNEALED COPPER WIRE
Mat spec, insulation CROSS-LINKED POLYETHYLENE
Mat spec, inner sheath FLAME RETARDANT -LOW SMOKE ZERO HALOGEN TO IEC 60754 & 61034
Armouring SINGLE LAYER OF GALVANISED STEEL WIRE
Mat spec, outer sheath FLAME RETARDANT - LOW SMOKE ZERO HALOGEN TO IEC 60754 & 61034, U.V RESISTANT
Colour, outer sheath BLACK
Screening OVERALL SCREEN ALUMUNIUM POLYESTER TAPE WITH TINNED COPPER DRAIN WIRE
Flame, propagation FLAME RETARDANT to IEC-60332-1 and IEC60332-3-22
Number, Pairs 1 PAIR, CONDUCTOR SIZE: 16/0.2
Pair Colour Identifications AS PER BS EN50288-7, BLACK AND WHITE WITH NUMBERS EMBOSSED FOR EACH PAIR.
Cross section, cores(mm2) 0.5 SQ. MM.
Diameter, OD, overall (mm) 11.4 MM, TOLERANCE AS PER EN50288-7.
UV Resistant ACCORDING TO UL1581 – SECT 1200
Marking on the external surface of the outer sheath OUTER SHEATH TO BE EMBOSSED WITH BS NUMBER, CABLE SIZE, TYPE (FLAME RETARDANT REDUCED
TOXICITY) AND MANUFACTURER'S NAME.
Cable drum shall have fixed weatherproof identification of the following: SAP NUMBER, MANUFACTURER'S NAME AND YEAR OF MANUFACTURE, ORDER AND
ITEM NUMBER, CABLE TYPE AND SIZE, VOLTAGE GRADE AND MARKING FOR DIRECTION OF LAY.
Length Identification: CABLE DIAMETER 10 mm AND ABOVE SHOULD BE MARKED WITH LENGTH IDENTIFICATION AT REGULAR INTERVALS OF 1 METER,STARTING
FROM "0" END WHICH IS ATTACHED TO THE SPINDLE OF THE DRUM.
Routine and Type test reports: TEST CERTIFICATES TO BE SUPPLIED PER BATCH, IDENTIFYING APPLICABLE DRUMS.
Fire spec armoured electrical cable CBL ELEC ARM FIRE
10 1001694873 Outdoor, Instrument Signal, Non-IS, 2 Pairs, 0.5mm², Black
Fire spec armoured electrical cable
Application NON IS, INSTRUMENT SIGNAL, MULTIPAIR, OUTDOOR
Flammability properties FLAME RETARDANT
Voltage 300 V
Max Operating Temp 90 DEGREE C
Design spec BS EN 50288-7 IEC 60754 & 61034 - LSZH
Construction XLPE, MS, FR-LSZH, OS, SWA, FR-LSZH-UV Resistant
Mat, conductor wire ANNEALED COPPER WIRE
Mat spec, insulation CROSS-LINKED POLYETHYLENE
Mat spec, inner sheath FLAME RETARDANT -LOW SMOKE ZERO HALOGEN TO IEC 60754 & 61034
Armouring SINGLE LAYER OF GALVANISED STEEL WIRE
Mat spec, outer sheath FLAME RETARDANT - LOW SMOKE ZERO HALOGEN TO IEC 60754 & 61034, U.V RESISTANT
Colour, outer sheath BLACK
Screening OVERALL SCREEN ALUMUNIUM POLYESTER TAPE WITH TINNED COPPER DRAIN WIRE
Flame, propagation FLAME RETARDANT to IEC-60332-1 and IEC60332-3-22
Number, Pairs 2 PAIRS, CONDUCTOR SIZE: 16/0.2
Pair Colour Identifications AS PER BS EN50288-7, BLACK AND WHITE WITH NUMBERS EMBOSSED FOR EACH PAIR.
Cross section, cores(mm2) 0.5 SQ. MM.
Diameter, OD, overall (mm) 12.3 MM, TOLERANCE AS PER EN50288-7.
UV Resistant ACCORDING TO UL1581 – SECT 1200
Marking on the external surface of the outer sheath OUTER SHEATH TO BE EMBOSSED WITH BS NUMBER, CABLE SIZE, TYPE (FLAME RETARDANT REDUCED
TOXICITY) AND MANUFACTURER'S NAME.
Cable drum shall have fixed weatherproof identification of the following: SAP NUMBER, MANUFACTURER'S NAME AND YEAR OF MANUFACTURE, ORDER AND
ITEM NUMBER, CABLE TYPE AND SIZE, VOLTAGE GRADE AND MARKING FOR DIRECTION OF LAY.
Length Identification: CABLE DIAMETER 10 mm AND ABOVE SHOULD BE MARKED WITH LENGTH IDENTIFICATION AT REGULAR INTERVALS OF 1 METER,STARTING
FROM "0" END WHICH IS ATTACHED TO THE SPINDLE OF THE DRUM.
Routine and Type test reports: TEST CERTIFICATES TO BE SUPPLIED PER BATCH, IDENTIFYING APPLICABLE DRUMS.
Fire spec armoured electrical cable CBL ELEC ARM FIRE
Rev. 0 (July-2013) Page 7 of 24 Brunei Shell Petroleum Sdn. Bhd.
Standard BSP EFA Cables
Item SAP Material No. Simplified Cable Description Full Cable Specifications
11 1001694874 Outdoor, Instrument Signal, Non-IS, 10 Pairs, 0.5mm², Black
Fire spec armoured electrical cable
Application NON IS, INSTRUMENT SIGNAL, MULTIPAIR, OUTDOOR
Flammability properties FLAME RETARDANT
Voltage 300 V
Max Operating Temp 90 DEGREE C
Design spec BS EN 50288-7 IEC 60754 & 61034 - LSZH
Construction XLPE, MS, FR-LSZH, OS, SWA, FR-LSZH-UV Resistant
Mat, conductor wire ANNEALED COPPER WIRE
Mat spec, insulation CROSS-LINKED POLYETHYLENE
Mat spec, inner sheath FLAME RETARDANT -LOW SMOKE ZERO HALOGEN TO IEC 60754 & 61034
Armouring SINGLE LAYER OF GALVANISED STEEL WIRE
Mat spec, outer sheath FLAME RETARDANT - LOW SMOKE ZERO HALOGEN TO IEC 60754 & 61034, U.V RESISTANT
Colour, outer sheath BLACK
Screening OVERALL SCREEN ALUMUNIUM POLYESTER TAPE WITH TINNED COPPER DRAIN WIRE
Flame, propagation FLAME RETARDANT to IEC-60332-1 and IEC60332-3-22
Number, Pairs 10 PAIRS,CONDUCTOR SIZE: 16/0.2
Pair Colour Identifications AS PER BS EN50288-7, BLACK AND WHITE WITH NUMBERS EMBOSSED FOR EACH PAIR.
Cross section, cores(mm2) 0.5 SQ. MM.
Diameter, OD, overall (mm) 22.9 MM, TOLERANCE AS PER EN50288-7.
UV Resistant ACCORDING TO UL1581 – SECT 1200
Marking on the external surface of the outer sheath OUTER SHEATH TO BE EMBOSSED WITH BS NUMBER, CABLE SIZE, TYPE (FLAME RETARDANT REDUCED
TOXICITY) AND MANUFACTURER'S NAME.
Cable drum shall have fixed weatherproof identification of the following: SAP NUMBER, MANUFACTURER'S NAME AND YEAR OF MANUFACTURE, ORDER AND
ITEM NUMBER, CABLE TYPE AND SIZE, VOLTAGE GRADE AND MARKING FOR DIRECTION OF LAY.
Length Identification: CABLE DIAMETER 10 mm AND ABOVE SHOULD BE MARKED WITH LENGTH IDENTIFICATION AT REGULAR INTERVALS OF 1 METER,STARTING
FROM "0" END WHICH IS ATTACHED TO THE SPINDLE OF THE DRUM.
Routine and Type test reports: TEST CERTIFICATES TO BE SUPPLIED PER BATCH, IDENTIFYING APPLICABLE DRUMS.
Fire spec armoured electrical cable CBL ELEC ARM FIRE
12 1001694875 Outdoor, Instrument Signal, Non-IS, 20 Pairs, 0.5mm², Black
Fire spec armoured electrical cable
Application NON IS, INSTRUMENT SIGNAL, MULTIPAIR, OUTDOOR
Flammability properties FLAME RETARDANT
Voltage 300 V
Max Operating Temp 90 DEGREE C
Design spec BS EN 50288-7 IEC 60754 & 61034 - LSZH
Construction XLPE, MS, FR-LSZH, OS, SWA, FR-LSZH-UV Resistant
Mat, conductor wire ANNEALED COPPER WIRE
Mat spec, insulation CROSS-LINKED POLYETHYLENE
Mat spec, inner sheath FLAME RETARDANT -LOW SMOKE ZERO HALOGEN TO IEC 60754 & 61034
Armouring SINGLE LAYER OF GALVANISED STEEL WIRE
Mat spec, outer sheath FLAME RETARDANT - LOW SMOKE ZERO HALOGEN TO IEC 60754 & 61034, U.V RESISTANT
Colour, outer sheath BLACK
Screening OVERALL SCREEN ALUMUNIUM POLYESTER TAPE WITH TINNED COPPER DRAIN WIRE
Flame, propagation FLAME RETARDANT to IEC-60332-1 and IEC60332-3-22
Number, Pairs 20 PAIRS,CONDUCTOR SIZE :16/0.2
Pair Colour Identifications AS PER BS EN50288-7, BLACK AND WHITE WITH NUMBERS EMBOSSED FOR EACH PAIR.
Cross section, cores(mm2) 0.5 SQ. MM.
Diameter, od, overall (mm) 29.1 MM, TOLERANCE AS PER EN50288-7.
UV Resistant ACCORDING TO UL1581 – SECT 1200
Marking on the external surface of the outer sheath OUTER SHEATH TO BE EMBOSSED WITH BS NUMBER, CABLE SIZE, TYPE (FLAME RETARDANT REDUCED
TOXICITY) AND MANUFACTURER'S NAME.
Cable drum shall have fixed weatherproof identification of the following: SAP NUMBER, MANUFACTURER'S NAME AND YEAR OF MANUFACTURE, ORDER AND
ITEM NUMBER, CABLE TYPE AND SIZE, VOLTAGE GRADE AND MARKING FOR DIRECTION OF LAY.
Length Identification: CABLE DIAMETER 10 mm AND ABOVE SHOULD BE MARKED WITH LENGTH IDENTIFICATION AT REGULAR INTERVALS OF 1 METER,STARTING
FROM "0" END WHICH IS ATTACHED TO THE SPINDLE OF THE DRUM.
Routine and Type test reports: TEST CERTIFICATES TO BE SUPPLIED PER BATCH, IDENTIFYING APPLICABLE DRUMS.
Fire spec armoured electrical cable CBL ELEC ARM FIRE
Rev. 0 (July-2013) Page 8 of 24 Brunei Shell Petroleum Sdn. Bhd.
Standard BSP EFA Cables
Item SAP Material No. Simplified Cable Description Full Cable Specifications
13 1001694876 Outdoor, Instrument Signal, IS, 1 Pair, 0.5mm², Blue
Fire spec armoured electrical cable
Application IS, INSTRUMENT SIGNAL, SINGLEPAIR, OUTDOOR
Flammability properties FLAME RETARDANT
Voltage 300 V
Max Operating Temp 90 DEGREE C
Design spec BS EN 50288-7 IEC 60754 & 61034 - LSZH
Construction XLPE, MS, FR-LSZH, OS, SWA, FR-LSZH-UV Resistant
Mat, conductor wire ANNEALED COPPER WIRE
Mat spec, insulation CROSS-LINKED POLYETHYLENE
Mat spec, inner sheath FLAME RETARDANT -LOW SMOKE ZERO HALOGEN TO IEC 60754 & 61034
Armouring SINGLE LAYER OF GALVANISED STEEL WIRE
Mat spec, outer sheath FLAME RETARDANT - LOW SMOKE ZERO HALOGEN TO IEC 60754 & 61034, U.V RESISTANT
Colour, outer sheath BLUE, INTRINSICALLY SAFE
Screening OVERALL SCREEN ALUMUNIUM POLYESTER TAPE WITH TINNED COPPER DRAIN WIRE
Flame, propagation FLAME RETARDANT to IEC-60332-1 and IEC60332-3-22
Number, Pairs 1 PAIR, CONDUCTOR SIZE: 16/0.2
Pair Colour Identifications AS PER BS EN50288-7, BLACK AND WHITE WITH NUMBERS EMBOSSED FOR EACH PAIR.
Cross section, cores(mm2) 0.5 SQ. MM.
Diameter, OD, overall (mm) 11.4 MM, TOLERANCE AS PER EN50288-7.
UV Resistant ACCORDING TO UL1581 – SECT 1200
Marking on the external surface of the outer sheath OUTER SHEATH TO BE EMBOSSED WITH BS NUMBER, CABLE SIZE, TYPE (FLAME RETARDANT REDUCED
TOXICITY) AND MANUFACTURER'S NAME.
Cable drum shall have fixed weatherproof identification of the following: SAP NUMBER, MANUFACTURER'S NAME AND YEAR OF MANUFACTURE, ORDER AND
ITEM NUMBER, CABLE TYPE AND SIZE, VOLTAGE GRADE AND MARKING FOR DIRECTION OF LAY.
Length Identification: CABLE DIAMETER 10 mm AND ABOVE SHOULD BE MARKED WITH LENGTH IDENTIFICATION AT REGULAR INTERVALS OF 1 METER,STARTING
FROM "0" END WHICH IS ATTACHED TO THE SPINDLE OF THE DRUM.
Routine and Type test reports: TEST CERTIFICATES TO BE SUPPLIED PER BATCH, IDENTIFYING APPLICABLE DRUMS.
Fire spec armoured electrical cable CBL ELEC ARM FIRE
14 1001708906 Outdoor, Instrument Signal, IS, 2 Pairs, 0.5mm², Blue
Fire spec armoured electrical cable
Application IS, INSTRUMENT SIGNAL, MULTIPAIR, OUTDOOR
Flammability properties FLAME RETARDANT
Voltage 300 V
Max Operating Temp 90 DEGREE C
Design spec BS EN 50288-7 IEC 60754 & 61034 - LSZH
Construction XLPE, MS, FR-LSZH, OS, SWA, FR-LSZH-UV Resistant
Mat, conductor wire ANNEALED COPPER WIRE
Mat spec, insulation CROSS-LINKED POLYETHYLENE
Mat spec, inner sheath FLAME RETARDANT -LOW SMOKE ZERO HALOGEN TO IEC 60754 & 61034
Armouring SINGLE LAYER OF GALVANISED STEEL WIRE
Mat spec, outer sheath FLAME RETARDANT - LOW SMOKE ZERO HALOGEN TO IEC 60754 & 61034, U.V RESISTANT
Colour, outer sheath BLUE, INTRINSICALLY SAFE
Screening OVERALL SCREEN ALUMUNIUM POLYESTER TAPE WITH TINNED COPPER DRAIN WIRE
Flame, propagation FLAME RETARDANT to IEC-60332-1 and IEC60332-3-22
Number, Pairs 2 PAIRS, CONDUCTOR SIZE: 16/0.2
Pair Colour Identifications AS PER BS EN50288-7, BLACK AND WHITE WITH NUMBERS EMBOSSED FOR EACH PAIR.
Cross section, cores(mm2) 0.5 SQ. MM.
Diameter, OD, overall (mm) 12.3 MM, TOLERANCE AS PER EN50288-7.
UV Resistant ACCORDING TO UL1581 – SECT 1200
Marking on the external surface of the outer sheath OUTER SHEATH TO BE EMBOSSED WITH BS NUMBER, CABLE SIZE, TYPE (FLAME RETARDANT REDUCED
TOXICITY) AND MANUFACTURER'S NAME.
Cable drum shall have fixed weatherproof identification of the following: SAP NUMBER, MANUFACTURER'S NAME AND YEAR OF MANUFACTURE, ORDER AND
ITEM NUMBER, CABLE TYPE AND SIZE, VOLTAGE GRADE AND MARKING FOR DIRECTION OF LAY.
Length Identification: CABLE DIAMETER 10 mm AND ABOVE SHOULD BE MARKED WITH LENGTH IDENTIFICATION AT REGULAR INTERVALS OF 1 METER,STARTING
FROM "0" END WHICH IS ATTACHED TO THE SPINDLE OF THE DRUM.
Routine and Type test reports: TEST CERTIFICATES TO BE SUPPLIED PER BATCH, IDENTIFYING APPLICABLE DRUMS.
Fire spec armoured electrical cable CBL ELEC ARM FIRE
Rev. 0 (July-2013) Page 9 of 24 Brunei Shell Petroleum Sdn. Bhd.
Standard BSP EFA Cables
Item SAP Material No. Simplified Cable Description Full Cable Specifications
15 1001694878 Outdoor, Instrument Signal, IS, 10 Pairs, 0.5mm², Blue
Fire spec armoured electrical cable
Application IS, INSTRUMENT SIGNAL, MULTIPAIR, OUTDOOR
Flammability properties FLAME RETARDANT
Voltage 300 V
Max Operating Temp 90 DEGREE C
Design spec BS EN 50288-7 IEC 60754 & 61034 - LSZH
Construction XLPE, MS, FR-LSZH, OS, SWA, FR-LSZH-UV Resistant
Mat, conductor wire ANNEALED COPPER WIRE
Mat spec, insulation CROSS-LINKED POLYETHYLENE
Mat spec, inner sheath FLAME RETARDANT -LOW SMOKE ZERO HALOGEN TO IEC 60754 & 61034
Armouring SINGLE LAYER OF GALVANISED STEEL WIRE
Mat spec, outer sheath FLAME RETARDANT - LOW SMOKE ZERO HALOGEN TO IEC 60754 & 61034, U.V RESISTANT
Colour, outer sheath BLUE, INTRINSICALLY SAFE
Screening OVERALL SCREEN ALUMUNIUM POLYESTER TAPE WITH TINNED COPPER DRAIN WIRE
Flame, propagation FLAME RETARDANT to IEC-60332-1 and IEC60332-3-22
Number, Pairs 10 PAIRS,CONDUCTOR SIZE: 16/0.2
Pair Colour Identifications AS PER BS EN50288-7, BLACK AND WHITE WITH NUMBERS EMBOSSED FOR EACH PAIR.
Cross section, cores(mm2) 0.5 SQ. MM.
Diameter, OD, overall (mm) 22.9 MM, TOLERANCE AS PER EN50288-7.
UV Resistant ACCORDING TO UL1581 – SECT 1200
Marking on the external surface of the outer sheath OUTER SHEATH TO BE EMBOSSED WITH BS NUMBER, CABLE SIZE, TYPE (FLAME RETARDANT REDUCED
TOXICITY) AND MANUFACTURER'S NAME.
Cable drum shall have fixed weatherproof identification of the following: SAP NUMBER, MANUFACTURER'S NAME AND YEAR OF MANUFACTURE, ORDER AND
ITEM NUMBER, CABLE TYPE AND SIZE, VOLTAGE GRADE AND MARKING FOR DIRECTION OF LAY.
Length Identification: CABLE DIAMETER 10 mm AND ABOVE SHOULD BE MARKED WITH LENGTH IDENTIFICATION AT REGULAR INTERVALS OF 1 METER,STARTING
FROM "0" END WHICH IS ATTACHED TO THE SPINDLE OF THE DRUM.
Routine and Type test reports: TEST CERTIFICATES TO BE SUPPLIED PER BATCH, IDENTIFYING APPLICABLE DRUMS.
Fire spec armoured electrical cable CBL ELEC ARM FIRE
16 1001694879 Outdoor, Instrument Signal, IS, 20 Pairs, 0.5mm², Blue
Fire spec armoured electrical cable
Application IS, INSTRUMENT SIGNAL, MULTIPAIR, OUTDOOR
Flammability properties FLAME RETARDANT
Voltage 300 V
Max Operating Temp 90 DEGREE C
Design spec BS EN 50288-7 IEC 60754 & 61034 - LSZH
Construction XLPE, MS, FR-LSZH, OS, SWA, FR-LSZH-UV Resistant
Mat, conductor wire ANNEALED COPPER WIRE
Mat spec, insulation CROSS-LINKED POLYETHYLENE
Mat spec, inner sheath FLAME RETARDANT -LOW SMOKE ZERO HALOGEN TO IEC 60754 & 61034
Armouring SINGLE LAYER OF GALVANISED STEEL WIRE
Mat spec, outer sheath FLAME RETARDANT - LOW SMOKE ZERO HALOGEN TO IEC 60754 & 61034, U.V RESISTANT
Colour, outer sheath BLUE, INTRINSICALLY SAFE
Screening OVERALL SCREEN ALUMUNIUM POLYESTER TAPE WITH TINNED COPPER DRAIN WIRE
Flame, propagation FLAME RETARDANT to IEC-60332-1 and IEC60332-3-22
Number, Pairs 20 PAIRS,CONDUCTOR SIZE :16/0.2
Pair Colour Identifications AS PER BS EN50288-7, BLACK AND WHITE WITH NUMBERS EMBOSSED FOR EACH PAIR.
Cross section, cores(mm2) 0.5 SQ. MM.
Diameter, OD, overall (mm) 29.1 MM, TOLERANCE AS PER EN50288-7.
UV Resistant ACCORDING TO UL1581 – SECT 1200
Marking on the external surface of the outer sheath OUTER SHEATH TO BE EMBOSSED WITH BS NUMBER, CABLE SIZE, TYPE (FLAME RETARDANT REDUCED
TOXICITY) AND MANUFACTURER'S NAME.
Cable drum shall have fixed weatherproof identification of the following: SAP NUMBER, MANUFACTURER'S NAME AND YEAR OF MANUFACTURE, ORDER AND
ITEM NUMBER, CABLE TYPE AND SIZE, VOLTAGE GRADE AND MARKING FOR DIRECTION OF LAY.
Length Identification: CABLE DIAMETER 10 mm AND ABOVE SHOULD BE MARKED WITH LENGTH IDENTIFICATION AT REGULAR INTERVALS OF 1 METER,STARTING
FROM "0" END WHICH IS ATTACHED TO THE SPINDLE OF THE DRUM.
Routine and Type test reports: TEST CERTIFICATES TO BE SUPPLIED PER BATCH, IDENTIFYING APPLICABLE DRUMS.
Fire spec armoured electrical cable CBL ELEC ARM FIRE
Rev. 0 (July-2013) Page 10 of 24 Brunei Shell Petroleum Sdn. Bhd.
Standard BSP EFA Cables
Item SAP Material No. Simplified Cable Description Full Cable Specifications
17 1001694860 Indoor, Fire Resistant Cable, Non-IS, 2 Cores, 1.5mm², Black
Fire spec armoured electrical cable
Application INSTRUMENT SIGNAL, MULTI CORE, INDOOR
Flammability properties FIRE RESISTANT
Voltage 300 V
Max Operating Temp 90 DEGREE C
Design spec BS EN 50288-7 IEC 60754 & 61034 - LSZH
Construction FRI, XLPE, MS, FR-LSZH
Mat, conductor wire ANNEALED COPPER WIRE
Design spec, conductor GLASS MICA TAPE APPLIED OVER CONDUCTOR
Mat spec, insulation CROSS-LINKED POLYETHYLENE
Mat spec, outer sheath FLAME RETARDANT -LOW SMOKE ZERO HALOGEN TO IEC 60754 & 61034
Colour, outer sheath BLACK
Screening OVERALL SCREEN ALUMUNIUM POLYESTER TAPE WITH TINNED COPPER DRAIN WIRE
Flame, propagation FLAME RETARDANT to IEC-60332-1 and IEC60332-3-22
Resistance, fire FIRE RESISTANT TO IEC 60331-21 and BS6387 Cat-C
Number, cores 2 CORES
Core Colour Identifications AS PER BS EN50288-7, WHITE WITH NUMBERS
Cross section, cores (mm2) 1.5 SQ. MM.
Diameter, OD, overall (mm) 11 MM, TOLERANCE AS PER EN50288-7.
Marking on the external surface of the outer sheath OUTER SHEATH TO BE EMBOSSED WITH BS NUMBER, CABLE SIZE, TYPE (FLAME RETARDANT REDUCED
TOXICITY) AND MANUFACTURER'S NAME.
Cable drum shall have fixed weatherproof identification of the following: SAP NUMBER, MANUFACTURER'S NAME AND YEAR OF MANUFACTURE, ORDER AND
ITEM NUMBER, CABLE TYPE AND SIZE, VOLTAGE GRADE AND MARKING FOR DIRECTION OF LAY.
Length Identification: CABLE DIAMETER 10 mm AND ABOVE SHOULD BE MARKED WITH LENGTH IDENTIFICATION AT REGULAR INTERVALS OF 1 METER,STARTING
FROM "0" END WHICH IS ATTACHED TO THE SPINDLE OF THE DRUM.
Routine and Type test reports: TEST CERTIFICATES TO BE SUPPLIED PER BATCH, IDENTIFYING APPLICABLE DRUMS.
Fire spec non armoured electrical cable CBL ELEC N-ARM FIRE
18 1001694841 Indoor, Fire Resistant Cable, Non-IS, 4 Cores, 1.5mm², Black
Fire spec armoured electrical cable
Application INSTRUMENT SIGNAL, MULTI CORE, INDOOR
Flammability properties FIRE RESISTANT
Voltage 300 V
Max Operating Temp 90 DEGREE C
Design spec BS EN 50288-7 IEC 60754 & 61034 - LSZH
Construction FRI, XLPE, MS, FR-LSZH
Mat, conductor wire ANNEALED COPPER WIRE
Design spec, conductor GLASS MICA TAPE APPLIED OVER CONDUCTOR
Mat spec, insulation CROSS-LINKED POLYETHYLENE
Mat spec, outer sheath FLAME RETARDANT -LOW SMOKE ZERO HALOGEN TO IEC 60754 & 61034
Colour, outer sheath BLACK
Screening OVERALL SCREEN ALUMUNIUM POLYESTER TAPE WITH TINNED COPPER DRAIN WIRE
Flame, propagation FLAME RETARDANT to IEC-60332-1 and IEC60332-3-22
Resistance, fire FIRE RESISTANT TO IEC 60331-21 and BS6387 Cat-C
Number, cores 4 CORES
Core Colour Identifications AS PER BS EN50288-7, WHITE WITH NUMBERS
Cross section, cores (mm2) 1.5 SQ. MM.
Diameter, OD, overall (mm) XX MM, TOLERANCE AS PER EN50288-7.
Marking on the external surface of the outer sheath OUTER SHEATH TO BE EMBOSSED WITH BS NUMBER, CABLE SIZE, TYPE (FLAME RETARDANT REDUCED
TOXICITY) AND MANUFACTURER'S NAME.
Cable drum shall have fixed weatherproof identification of the following: SAP NUMBER, MANUFACTURER'S NAME AND YEAR OF MANUFACTURE, ORDER AND
ITEM NUMBER, CABLE TYPE AND SIZE, VOLTAGE GRADE AND MARKING FOR DIRECTION OF LAY.
Length Identification: CABLE DIAMETER 10 mm AND ABOVE SHOULD BE MARKED WITH LENGTH IDENTIFICATION AT REGULAR INTERVALS OF 1 METER,STARTING
FROM "0" END WHICH IS ATTACHED TO THE SPINDLE OF THE DRUM.
Routine and Type test reports: TEST CERTIFICATES TO BE SUPPLIED PER BATCH, IDENTIFYING APPLICABLE DRUMS.
Fire spec non armoured electrical cable CBL ELEC N-ARM FIRE
Rev. 0 (July-2013) Page 11 of 24 Brunei Shell Petroleum Sdn. Bhd.
Standard BSP EFA Cables
Item SAP Material No. Simplified Cable Description Full Cable Specifications
19 1001694842 Indoor, Fire Resistant Cable, Non-IS, 10 Cores, 1.5mm², Black
Fire spec armoured electrical cable
Application INSTRUMENT SIGNAL, MULTI CORE, INDOOR
Flammability properties FIRE RESISTANT
Voltage 300 V
Max Operating Temp 90 DEGREE C
Design spec BS EN 50288-7 IEC 60754 & 61034 - LSZH
Construction FRI, XLPE, MS, FR-LSZH
Mat, conductor wire ANNEALED COPPER WIRE
Design spec, conductor GLASS MICA TAPE APPLIED OVER CONDUCTOR
Mat spec, insulation CROSS-LINKED POLYETHYLENE
Mat spec, outer sheath FLAME RETARDANT -LOW SMOKE ZERO HALOGEN TO IEC 60754 & 61034
Colour, outer sheath BLACK
Screening OVERALL SCREEN ALUMUNIUM POLYESTER TAPE WITH TINNED COPPER DRAIN WIRE
Flame, propagation FLAME RETARDANT to IEC-60332-1 and IEC60332-3-22
Resistance, fire FIRE RESISTANT TO IEC 60331-21 and BS6387 Cat-C
Number, cores 10 CORES
Core Colour Identifications AS PER BS EN50288-7, WHITE WITH NUMBERS
Cross section, cores (mm2) 1.5 SQ. MM.
Diameter, OD, overall (mm) XX MM, TOLERANCE AS PER EN50288-7.
Marking on the external surface of the outer sheath OUTER SHEATH TO BE EMBOSSED WITH BS NUMBER, CABLE SIZE, TYPE (FLAME RETARDANT REDUCED
TOXICITY) AND MANUFACTURER'S NAME.
Cable drum shall have fixed weatherproof identification of the following: SAP NUMBER, MANUFACTURER'S NAME AND YEAR OF MANUFACTURE, ORDER AND
ITEM NUMBER, CABLE TYPE AND SIZE, VOLTAGE GRADE AND MARKING FOR DIRECTION OF LAY.
Length Identification: CABLE DIAMETER 10 mm AND ABOVE SHOULD BE MARKED WITH LENGTH IDENTIFICATION AT REGULAR INTERVALS OF 1 METER,STARTING
FROM "0" END WHICH IS ATTACHED TO THE SPINDLE OF THE DRUM.
Routine and Type test reports: TEST CERTIFICATES TO BE SUPPLIED PER BATCH, IDENTIFYING APPLICABLE DRUMS.
Fire spec non armoured electrical cable CBL ELEC N-ARM FIRE
20 1001694843 Outdoor, Fire Resistant Cable, Non-IS, 2 Cores, 1.5mm², Black
Fire spec armoured electrical cable
Application INSTRUMENT SIGNAL, MULTI CORE, OUTDOOR
Flammability properties FIRE RESISTANT
Voltage 300 V
Max Operating Temp 90 DEGREE C
Design spec BS EN 50288-7 IEC 60754 & 61034 - LSZH
Construction FRI, XLPE, MS, FR-LSZH, SWA, FR-LSZH - UV Resistant
Mat, conductor wire ANNEALED COPPER WIRE
Mat spec, insulation CROSS-LINKED POLYETHYLENE
Design spec, conductor GLASS MICA TAPE APPLIED OVER CONDUCTOR
Resistance, fire FIRE RESISTANT TO IEC 60331-21 and BS6387 Cat-C
Screening OVERALL SCREEN ALUMUNIUM POLYESTER TAPE WITH TINNED COPPER DRAIN WIRE
Mat spec, inner sheath FLAME RETARDANT -LOW SMOKE ZERO HALOGEN TO IEC 60754 & 61034
Armouring SINGLE LAYER OF GALVANISED STEEL WIRE
Mat spec, outer sheath FLAME RETARDANT - LOW SMOKE ZERO HALOGEN TO IEC 60754 & 61034, U.V RESISTANT
Colour, outer sheath BLACK
Flame, propagation FLAME RETARDANT to IEC-60332-1 and IEC60332-3-22
Number, cores 2 CORES
Core Colour Identifications AS PER BS EN50288-7, WHITE WITH NUMBERS
Cross section, cores (mm2) 1.5 SQ. MM.
Diameter, od, overall (mm) 14.0 MM, TOLERANCE AS PER EN50288-7.
UV Resistant ACCORDING TO UL1581 – SECT 1200
Marking on the external surface of the outer sheath OUTER SHEATH TO BE EMBOSSED WITH BS NUMBER, CABLE SIZE, TYPE (FLAME RETARDANT REDUCED
TOXICITY) AND MANUFACTURER'S NAME.
Cable drum shall have fixed weatherproof identification of the following: SAP NUMBER, MANUFACTURER'S NAME AND YEAR OF MANUFACTURE, ORDER AND
ITEM NUMBER, CABLE TYPE AND SIZE, VOLTAGE GRADE AND MARKING FOR DIRECTION OF LAY.
Length Identification: CABLE DIAMETER 10 mm AND ABOVE SHOULD BE MARKED WITH LENGTH IDENTIFICATION AT REGULAR INTERVALS OF 1 METER,STARTING
FROM "0" END WHICH IS ATTACHED TO THE SPINDLE OF THE DRUM.
Routine and Type test reports: TEST CERTIFICATES TO BE SUPPLIED PER BATCH, IDENTIFYING APPLICABLE DRUMS.
Fire spec armoured electrical cable CBL ELEC ARM FIRE
Rev. 0 (July-2013) Page 12 of 24 Brunei Shell Petroleum Sdn. Bhd.
Standard BSP EFA Cables
Item SAP Material No. Simplified Cable Description Full Cable Specifications
21 1001694844 Outdoor, Fire Resistant Cable, Non-IS, 4 Cores, 1.5mm², Black
Fire spec armoured electrical cable
Application INSTRUMENT SIGNAL, MULTI CORE, OUTDOOR
Flammability properties FIRE RESISTANT
Voltage 300 V
Max Operating Temp 90 DEGREE C
Design spec BS EN 50288-7 IEC 60754 & 61034 - LSZH
Construction FRI, XLPE, MS, FR-LSZH, SWA, FR-LSZH - UV Resistant
Mat, conductor wire ANNEALED COPPER WIRE
Mat spec, insulation CROSS-LINKED POLYETHYLENE
Design spec, conductor GLASS MICA TAPE APPLIED OVER CONDUCTOR
Resistance, fire FIRE RESISTANT TO IEC 60331-21 and BS6387 Cat-C
Screening OVERALL SCREEN ALUMUNIUM POLYESTER TAPE WITH TINNED COPPER DRAIN WIRE
Mat spec, inner sheath FLAME RETARDANT -LOW SMOKE ZERO HALOGEN TO IEC 60754 & 61034
Armouring SINGLE LAYER OF GALVANISED STEEL WIRE
Mat spec, outer sheath FLAME RETARDANT - LOW SMOKE ZERO HALOGEN TO IEC 60754 & 61034, U.V RESISTANT
Colour, outer sheath BLACK
Flame, propagation FLAME RETARDANT to IEC-60332-1 and IEC60332-3-22
Number, cores 4 CORES
Core Colour Identifications AS PER BS EN50288-7, WHITE WITH NUMBERS
Cross section, cores (mm2) 1.5 SQ. MM.
Diameter, od, overall (mm) 16.0 mm, TOLERANCE AS PER EN50288-7.
UV Resistant ACCORDING TO UL1581 – SECT 1200
Marking on the external surface of the outer sheath OUTER SHEATH TO BE EMBOSSED WITH BS NUMBER, CABLE SIZE, TYPE (FLAME RETARDANT REDUCED
TOXICITY) AND MANUFACTURER'S NAME.
Cable drum shall have fixed weatherproof identification of the following: SAP NUMBER, MANUFACTURER'S NAME AND YEAR OF MANUFACTURE, ORDER AND
ITEM NUMBER, CABLE TYPE AND SIZE, VOLTAGE GRADE AND MARKING FOR DIRECTION OF LAY.
Length Identification: CABLE DIAMETER 10 mm AND ABOVE SHOULD BE MARKED WITH LENGTH IDENTIFICATION AT REGULAR INTERVALS OF 1 METER,STARTING
FROM "0" END WHICH IS ATTACHED TO THE SPINDLE OF THE DRUM.
Routine and Type test reports: TEST CERTIFICATES TO BE SUPPLIED PER BATCH, IDENTIFYING APPLICABLE DRUMS.
Fire spec armoured electrical cable CBL ELEC ARM FIRE
22 1001694845 Outdoor, Fire Resistant Cable, Non-IS, 10 Cores, 1.5mm², Black
Fire spec armoured electrical cable
Application INSTRUMENT SIGNAL, MULTI CORE, OUTDOOR
Flammability properties FIRE RESISTANT
Voltage 300 V
Max Operating Temp 90 DEGREE C
Design spec BS EN 50288-7 IEC 60754 & 61034 - LSZH
Construction FRI, XLPE, MS, FR-LSZH, SWA, FR-LSZH - UV Resistant
Mat, conductor wire ANNEALED COPPER WIRE
Mat spec, insulation CROSS-LINKED POLYETHYLENE
Design spec, conductor GLASS MICA TAPE APPLIED OVER CONDUCTOR
Resistance, fire FIRE RESISTANT TO IEC 60331-21 and BS6387 Cat-C
Screening OVERALL SCREEN ALUMUNIUM POLYESTER TAPE WITH TINNED COPPER DRAIN WIRE
Mat spec, inner sheath FLAME RETARDANT -LOW SMOKE ZERO HALOGEN TO IEC 60754 & 61034
Armouring SINGLE LAYER OF GALVANISED STEEL WIRE
Mat spec, outer sheath FLAME RETARDANT - LOW SMOKE ZERO HALOGEN TO IEC 60754 & 61034, U.V RESISTANT
Colour, outer sheath BLACK
Flame, propagation FLAME RETARDANT to IEC-60332-1 and IEC60332-3-22
Number, cores 10 CORES
Core Colour Identifications AS PER BS EN50288-7, WHITE WITH NUMBERS
Cross section, cores (mm2) 1.5 SQ. MM.
Diameter, od, overall (mm) 19.8 mm, TOLERANCE AS PER EN50288-7.
UV Resistant ACCORDING TO UL1581 – SECT 1200
Marking on the external surface of the outer sheath OUTER SHEATH TO BE EMBOSSED WITH BS NUMBER, CABLE SIZE, TYPE (FLAME RETARDANT REDUCED
TOXICITY) AND MANUFACTURER'S NAME.
Cable drum shall have fixed weatherproof identification of the following: SAP NUMBER, MANUFACTURER'S NAME AND YEAR OF MANUFACTURE, ORDER AND
ITEM NUMBER, CABLE TYPE AND SIZE, VOLTAGE GRADE AND MARKING FOR DIRECTION OF LAY.
Length Identification: CABLE DIAMETER 10 mm AND ABOVE SHOULD BE MARKED WITH LENGTH IDENTIFICATION AT REGULAR INTERVALS OF 1 METER,STARTING
FROM "0" END WHICH IS ATTACHED TO THE SPINDLE OF THE DRUM.
Routine and Type test reports: TEST CERTIFICATES TO BE SUPPLIED PER BATCH, IDENTIFYING APPLICABLE DRUMS.
Fire spec armoured electrical cable CBL ELEC ARM FIRE
Rev. 0 (July-2013) Page 13 of 24 Brunei Shell Petroleum Sdn. Bhd.
Standard BSP EFA Cables
Item SAP Material No. Simplified Cable Description Full Cable Specifications
23 1001694846 Outdoor, Fire Resistant Cable, Non-IS, 20 Cores, 1.5mm², Black
Fire spec armoured electrical cable
Application INSTRUMENT SIGNAL, MULTI CORE, OUTDOOR
Flammability properties FIRE RESISTANT
Voltage 300 V
Max Operating Temp 90 DEGREE C
Design spec BS EN 50288-7 IEC 60754 & 61034 - LSZH
Construction FRI, XLPE, MS, FR-LSZH, SWA, FR-LSZH - UV Resistant
Mat, conductor wire ANNEALED COPPER WIRE
Mat spec, insulation CROSS-LINKED POLYETHYLENE
Design spec, conductor GLASS MICA TAPE APPLIED OVER CONDUCTOR
Resistance, fire FIRE RESISTANT TO IEC 60331-21 and BS6387 Cat-C
Screening OVERALL SCREEN ALUMUNIUM POLYESTER TAPE WITH TINNED COPPER DRAIN WIRE
Mat spec, inner sheath FLAME RETARDANT -LOW SMOKE ZERO HALOGEN TO IEC 60754 & 61034
Armouring SINGLE LAYER OF GALVANISED STEEL WIRE
Mat spec, outer sheath FLAME RETARDANT - LOW SMOKE ZERO HALOGEN TO IEC 60754 & 61034, U.V RESISTANT
Colour, outer sheath BLACK
Flame, propagation FLAME RETARDANT to IEC-60332-1 and IEC60332-3-22
Number, cores 20 CORES
Core Colour Identifications AS PER BS EN50288-7, WHITE WITH NUMBERS
Cross section, cores (mm2) 1.5 SQ. MM.
Diameter, od, overall (mm) XX mm, TOLERANCE AS PER EN50288-7.
UV Resistant ACCORDING TO UL1581 – SECT 1200
Marking on the external surface of the outer sheath OUTER SHEATH TO BE EMBOSSED WITH BS NUMBER, CABLE SIZE, TYPE (FLAME RETARDANT REDUCED
TOXICITY) AND MANUFACTURER'S NAME.
Cable drum shall have fixed weatherproof identification of the following: SAP NUMBER, MANUFACTURER'S NAME AND YEAR OF MANUFACTURE, ORDER AND
ITEM NUMBER, CABLE TYPE AND SIZE, VOLTAGE GRADE AND MARKING FOR DIRECTION OF LAY.
Length Identification: CABLE DIAMETER 10 mm AND ABOVE SHOULD BE MARKED WITH LENGTH IDENTIFICATION AT REGULAR INTERVALS OF 1 METER,STARTING
FROM "0" END WHICH IS ATTACHED TO THE SPINDLE OF THE DRUM.
Routine and Type test reports: TEST CERTIFICATES TO BE SUPPLIED PER BATCH, IDENTIFYING APPLICABLE DRUMS.
Fire spec armoured electrical cable CBL ELEC ARM FIRE
24 1001694847 Outdoor, Instrument Signal, Non-IS, with Ind and overall Shield, 1 Pair, 0.5mm², Black
Fire spec armoured electrical cable
Application NON IS, INSTRUMENT SIGNAL, SINGLEPAIR, OUTDOOR
Flammability properties FLAME RETARDANT
Voltage 300 V
Max Operating Temp 90 DEGREE C
Design spec BS EN 50288-7 IEC 60754 & 61034 - LSZH
Construction XLPE, IS, MS, FR-LSZH, OS, SWA, FR-LSZH-UV Resistant
Mat, conductor wire ANNEALED COPPER WIRE
Mat spec, insulation CROSS-LINKED POLYETHYLENE
Mat spec, inner sheath FLAME RETARDANT -LOW SMOKE ZERO HALOGEN TO IEC 60754 & 61034
Armouring SINGLE LAYER OF GALVANISED STEEL WIRE
Mat spec, outer sheath FLAME RETARDANT - LOW SMOKE ZERO HALOGEN TO IEC 60754 & 61034, U.V RESISTANT
Colour, outer sheath BLACK
Screening INDIVIDUAL AND OVERALL SCREEN WITH ALUMUNIUM POLYESTER TAPE WITH TINNED COPPER DRAIN WIRE
Flame, propagation FLAME RETARDANT to IEC-60332-1 and IEC60332-3-22
Number, Pairs 1 PAIR, CONDUCTOR SIZE: 16/0.2
Pair Colour Identifications AS PER BS EN50288-7, BLACK AND WHITE WITH NUMBERS EMBOSSED FOR EACH PAIR.
Cross section, cores(mm2) 0.5 SQ. MM.
Diameter, OD, overall (mm) XX MM, TOLERANCE AS PER EN50288-7.
UV Resistant ACCORDING TO UL1581 – SECT 1200
Marking on the external surface of the outer sheath OUTER SHEATH TO BE EMBOSSED WITH BS NUMBER, CABLE SIZE, TYPE (FLAME RETARDANT REDUCED
TOXICITY) AND MANUFACTURER'S NAME.
Cable drum shall have fixed weatherproof identification of the following: SAP NUMBER, MANUFACTURER'S NAME AND YEAR OF MANUFACTURE, ORDER AND
ITEM NUMBER, CABLE TYPE AND SIZE, VOLTAGE GRADE AND MARKING FOR DIRECTION OF LAY.
Length Identification: CABLE DIAMETER 10 mm AND ABOVE SHOULD BE MARKED WITH LENGTH IDENTIFICATION AT REGULAR INTERVALS OF 1 METER,STARTING
FROM "0" END WHICH IS ATTACHED TO THE SPINDLE OF THE DRUM.
Routine and Type test reports: TEST CERTIFICATES TO BE SUPPLIED PER BATCH, IDENTIFYING APPLICABLE DRUMS.
Fire spec armoured electrical cable CBL ELEC ARM FIRE
Rev. 0 (July-2013) Page 14 of 24 Brunei Shell Petroleum Sdn. Bhd.
Standard BSP EFA Cables
Item SAP Material No. Simplified Cable Description Full Cable Specifications
25 1001694848 Outdoor, Instrument Signal, Non-IS, with Ind and overall Shield, 2 Pairs, 0.5mm², Black
Fire spec armoured electrical cable
Application NON IS, INSTRUMENT SIGNAL, MULTIPAIR, OUTDOOR
Flammability properties FLAME RETARDANT
Voltage 300 V
Max Operating Temp 90 DEGREE C
Design spec BS EN 50288-7 IEC 60754 & 61034 - LSZH
Construction XLPE, IS, MS, FR-LSZH, OS, SWA, FR-LSZH-UV Resistant
Mat, conductor wire ANNEALED COPPER WIRE
Mat spec, insulation CROSS-LINKED POLYETHYLENE
Mat spec, inner sheath FLAME RETARDANT -LOW SMOKE ZERO HALOGEN TO IEC 60754 & 61034
Armouring SINGLE LAYER OF GALVANISED STEEL WIRE
Mat spec, outer sheath FLAME RETARDANT - LOW SMOKE ZERO HALOGEN TO IEC 60754 & 61034, U.V RESISTANT
Colour, outer sheath BLACK
Screening INDIVIDUAL AND OVERALL SCREEN WITH ALUMUNIUM POLYESTER TAPE WITH TINNED COPPER DRAIN WIRE
Flame, propagation FLAME RETARDANT to IEC-60332-1 and IEC60332-3-22
Number, Pairs 2 PAIRS, CONDUCTOR SIZE: 16/0.2
Pair Colour Identifications AS PER BS EN50288-7, BLACK AND WHITE WITH NUMBERS EMBOSSED FOR EACH PAIR.
Cross section, cores(mm2) 0.5 SQ. MM.
Diameter, OD, overall (mm) XX MM, TOLERANCE AS PER EN50288-7.
UV Resistant ACCORDING TO UL1581 – SECT 1200
Marking on the external surface of the outer sheath OUTER SHEATH TO BE EMBOSSED WITH BS NUMBER, CABLE SIZE, TYPE (FLAME RETARDANT REDUCED
TOXICITY) AND MANUFACTURER'S NAME.
Cable drum shall have fixed weatherproof identification of the following: SAP NUMBER, MANUFACTURER'S NAME AND YEAR OF MANUFACTURE, ORDER AND
ITEM NUMBER, CABLE TYPE AND SIZE, VOLTAGE GRADE AND MARKING FOR DIRECTION OF LAY.
Length Identification: CABLE DIAMETER 10 mm AND ABOVE SHOULD BE MARKED WITH LENGTH IDENTIFICATION AT REGULAR INTERVALS OF 1 METER,STARTING
FROM "0" END WHICH IS ATTACHED TO THE SPINDLE OF THE DRUM.
Routine and Type test reports: TEST CERTIFICATES TO BE SUPPLIED PER BATCH, IDENTIFYING APPLICABLE DRUMS.
Fire spec armoured electrical cable CBL ELEC ARM FIRE
26 1001694850 Outdoor, Instrument Signal, Non-IS, with Ind and overall Shield, 10 Pairs, 0.5mm², Black
Fire spec armoured electrical cable
Application NON IS, INSTRUMENT SIGNAL, MULTIPAIR, OUTDOOR
Flammability properties FLAME RETARDANT
Voltage 300 V
Max Operating Temp 90 DEGREE C
Design spec BS EN 50288-7 IEC 60754 & 61034 - LSZH
Construction XLPE, IS, MS, FR-LSZH, OS, SWA, FR-LSZH-UV Resistant
Mat, conductor wire ANNEALED COPPER WIRE
Mat spec, insulation CROSS-LINKED POLYETHYLENE
Mat spec, inner sheath FLAME RETARDANT -LOW SMOKE ZERO HALOGEN TO IEC 60754 & 61034
Armouring SINGLE LAYER OF GALVANISED STEEL WIRE
Mat spec, outer sheath FLAME RETARDANT - LOW SMOKE ZERO HALOGEN TO IEC 60754 & 61034, U.V RESISTANT
Colour, outer sheath BLACK
Screening INDIVIDUAL AND OVERALL SCREEN WITH ALUMUNIUM POLYESTER TAPE WITH TINNED COPPER DRAIN WIRE
Flame, propagation FLAME RETARDANT to IEC-60332-1 and IEC60332-3-22
Number, Pairs 10 PAIRS,CONDUCTOR SIZE: 16/0.2
Pair Colour Identifications AS PER BS EN50288-7, BLACK AND WHITE WITH NUMBERS EMBOSSED FOR EACH PAIR.
Cross section, cores(mm2) 0.5 SQ. MM.
Diameter, OD, overall (mm) XX MM, TOLERANCE AS PER EN50288-7.
UV Resistant ACCORDING TO UL1581 – SECT 1200
Marking on the external surface of the outer sheath OUTER SHEATH TO BE EMBOSSED WITH BS NUMBER, CABLE SIZE, TYPE (FLAME RETARDANT REDUCED
TOXICITY) AND MANUFACTURER'S NAME.
Cable drum shall have fixed weatherproof identification of the following: SAP NUMBER, MANUFACTURER'S NAME AND YEAR OF MANUFACTURE, ORDER AND
ITEM NUMBER, CABLE TYPE AND SIZE, VOLTAGE GRADE AND MARKING FOR DIRECTION OF LAY.
Length Identification: CABLE DIAMETER 10 mm AND ABOVE SHOULD BE MARKED WITH LENGTH IDENTIFICATION AT REGULAR INTERVALS OF 1 METER,STARTING
FROM "0" END WHICH IS ATTACHED TO THE SPINDLE OF THE DRUM.
Routine and Type test reports: TEST CERTIFICATES TO BE SUPPLIED PER BATCH, IDENTIFYING APPLICABLE DRUMS.
Fire spec armoured electrical cable CBL ELEC ARM FIRE
Rev. 0 (July-2013) Page 15 of 24 Brunei Shell Petroleum Sdn. Bhd.
Standard BSP EFA Cables
Item SAP Material No. Simplified Cable Description Full Cable Specifications
27 1001694849 Outdoor, Instrument Signal, Non-IS, with Ind and overall Shield, 20 Pairs, 0.5 mm², Black
Fire spec armoured electrical cable
Application NON IS, INSTRUMENT SIGNAL, MULTIPAIR, OUTDOOR
Flammability properties FLAME RETARDANT
Voltage 300 V
Max Operating Temp 90 DEGREE C
Design spec BS EN 50288-7 IEC 60754 & 61034 - LSZH
Construction XLPE, IS, MS, FR-LSZH, OS, SWA, FR-LSZH-UV Resistant
Mat, conductor wire ANNEALED COPPER WIRE
Mat spec, insulation CROSS-LINKED POLYETHYLENE
Mat spec, inner sheath FLAME RETARDANT -LOW SMOKE ZERO HALOGEN TO IEC 60754 & 61034
Armouring SINGLE LAYER OF GALVANISED STEEL WIRE
Mat spec, outer sheath FLAME RETARDANT - LOW SMOKE ZERO HALOGEN TO IEC 60754 & 61034, U.V RESISTANT
Colour, outer sheath BLACK
Screening INDIVIDUAL AND OVERALL SCREEN WITH ALUMUNIUM POLYESTER TAPE WITH TINNED COPPER DRAIN WIRE
Flame, propagation FLAME RETARDANT to IEC-60332-1 and IEC60332-3-22
Number, Pairs 20 PAIRS,CONDUCTOR SIZE :16/0.2
Pair Colour Identifications AS PER BS EN50288-7, BLACK AND WHITE WITH NUMBERS EMBOSSED FOR EACH PAIR.
Cross section, cores(mm2) 0.5 SQ. MM.
Diameter, od, overall (mm) XX MM, TOLERANCE AS PER EN50288-7.
UV Resistant ACCORDING TO UL1581 – SECT 1200
Marking on the external surface of the outer sheath OUTER SHEATH TO BE EMBOSSED WITH BS NUMBER, CABLE SIZE, TYPE (FLAME RETARDANT REDUCED
TOXICITY) AND MANUFACTURER'S NAME.
Cable drum shall have fixed weatherproof identification of the following: SAP NUMBER, MANUFACTURER'S NAME AND YEAR OF MANUFACTURE, ORDER AND
ITEM NUMBER, CABLE TYPE AND SIZE, VOLTAGE GRADE AND MARKING FOR DIRECTION OF LAY.
Length Identification: CABLE DIAMETER 10 mm AND ABOVE SHOULD BE MARKED WITH LENGTH IDENTIFICATION AT REGULAR INTERVALS OF 1 METER,STARTING
FROM "0" END WHICH IS ATTACHED TO THE SPINDLE OF THE DRUM.
Routine and Type test reports: TEST CERTIFICATES TO BE SUPPLIED PER BATCH, IDENTIFYING APPLICABLE DRUMS.
Fire spec armoured electrical cable CBL ELEC ARM FIRE
28 1001694851 Outdoor, Instrument Signal, with Ind and overall Shield, IS, 1 Pair, 0.5mm², Blue
Fire spec armoured electrical cable
Application IS, INSTRUMENT SIGNAL, SINGLEPAIR, OUTDOOR
Flammability properties FLAME RETARDANT
Voltage 300 V
Max Operating Temp 90 DEGREE C
Design spec BS EN 50288-7 IEC 60754 & 61034 - LSZH
Construction XLPE, IS, MS, FR-LSZH, OS, SWA, FR-LSZH-UV Resistant
Mat, conductor wire ANNEALED COPPER WIRE
Mat spec, insulation CROSS-LINKED POLYETHYLENE
Mat spec, inner sheath FLAME RETARDANT -LOW SMOKE ZERO HALOGEN TO IEC 60754 & 61034
Armouring SINGLE LAYER OF GALVANISED STEEL WIRE
Mat spec, outer sheath FLAME RETARDANT - LOW SMOKE ZERO HALOGEN TO IEC 60754 & 61034, U.V RESISTANT
Colour, outer sheath BLUE, INTRINSICALLY SAFE
Screening INDIVIDUAL AND OVERALL SCREEN WITH ALUMUNIUM POLYESTER TAPE WITH TINNED COPPER DRAIN WIRE
Flame, propagation FLAME RETARDANT to IEC-60332-1 and IEC60332-3-22
Number, Pairs 1 PAIR, CONDUCTOR SIZE: 16/0.2
Pair Colour Identifications AS PER BS EN50288-7, BLACK AND WHITE WITH NUMBERS EMBOSSED FOR EACH PAIR.
Cross section, cores(mm2) 0.5 SQ. MM.
Diameter, OD, overall (mm) XX MM, TOLERANCE AS PER EN50288-7.
UV Resistant ACCORDING TO UL1581 – SECT 1200
Marking on the external surface of the outer sheath OUTER SHEATH TO BE EMBOSSED WITH BS NUMBER, CABLE SIZE, TYPE (FLAME RETARDANT REDUCED
TOXICITY) AND MANUFACTURER'S NAME.
Cable drum shall have fixed weatherproof identification of the following: SAP NUMBER, MANUFACTURER'S NAME AND YEAR OF MANUFACTURE, ORDER AND
ITEM NUMBER, CABLE TYPE AND SIZE, VOLTAGE GRADE AND MARKING FOR DIRECTION OF LAY.
Length Identification: CABLE DIAMETER 10 mm AND ABOVE SHOULD BE MARKED WITH LENGTH IDENTIFICATION AT REGULAR INTERVALS OF 1 METER,STARTING
FROM "0" END WHICH IS ATTACHED TO THE SPINDLE OF THE DRUM.
Routine and Type test reports: TEST CERTIFICATES TO BE SUPPLIED PER BATCH, IDENTIFYING APPLICABLE DRUMS.
Fire spec armoured electrical cable CBL ELEC ARM FIRE
Rev. 0 (July-2013) Page 16 of 24 Brunei Shell Petroleum Sdn. Bhd.
Standard BSP EFA Cables
Item SAP Material No. Simplified Cable Description Full Cable Specifications
29 1001694852 Outdoor, Instrument Signal, with Ind and overall Shield, IS, 2 Pairs, 0.5mm², Blue
Fire spec armoured electrical cable
Application IS, INSTRUMENT SIGNAL, MULTIPAIR, OUTDOOR
Flammability properties FLAME RETARDANT
Voltage 300 V
Max Operating Temp 90 DEGREE C
Design spec BS EN 50288-7 IEC 60754 & 61034 - LSZH
Construction XLPE, IS, MS, FR-LSZH, OS, SWA, FR-LSZH-UV Resistant
Mat, conductor wire ANNEALED COPPER WIRE
Mat spec, insulation CROSS-LINKED POLYETHYLENE
Mat spec, inner sheath FLAME RETARDANT -LOW SMOKE ZERO HALOGEN TO IEC 60754 & 61034
Armouring SINGLE LAYER OF GALVANISED STEEL WIRE
Mat spec, outer sheath FLAME RETARDANT - LOW SMOKE ZERO HALOGEN TO IEC 60754 & 61034, U.V RESISTANT
Colour, outer sheath BLUE, INTRINSICALLY SAFE
Screening INDIVIDUAL AND OVERALL SCREEN WITH ALUMUNIUM POLYESTER TAPE WITH TINNED COPPER DRAIN WIRE
Flame, propagation FLAME RETARDANT to IEC-60332-1 and IEC60332-3-22
Number, Pairs 2 PAIRS, CONDUCTOR SIZE: 16/0.2
Pair Colour Identifications AS PER BS EN50288-7, BLACK AND WHITE WITH NUMBERS EMBOSSED FOR EACH PAIR.
Cross section, cores(mm2) 0.5 SQ. MM.
Diameter, OD, overall (mm) XX MM, TOLERANCE AS PER EN50288-7.
UV Resistant ACCORDING TO UL1581 – SECT 1200
Marking on the external surface of the outer sheath OUTER SHEATH TO BE EMBOSSED WITH BS NUMBER, CABLE SIZE, TYPE (FLAME RETARDANT REDUCED
TOXICITY) AND MANUFACTURER'S NAME.
Cable drum shall have fixed weatherproof identification of the following: SAP NUMBER, MANUFACTURER'S NAME AND YEAR OF MANUFACTURE, ORDER AND
ITEM NUMBER, CABLE TYPE AND SIZE, VOLTAGE GRADE AND MARKING FOR DIRECTION OF LAY.
Length Identification: CABLE DIAMETER 10 mm AND ABOVE SHOULD BE MARKED WITH LENGTH IDENTIFICATION AT REGULAR INTERVALS OF 1 METER,STARTING
FROM "0" END WHICH IS ATTACHED TO THE SPINDLE OF THE DRUM.
Routine and Type test reports: TEST CERTIFICATES TO BE SUPPLIED PER BATCH, IDENTIFYING APPLICABLE DRUMS.
Fire spec armoured electrical cable CBL ELEC ARM FIRE
30 1001694853 Outdoor, Instrument Signal, with Ind and overall Shield, IS, 10 Pairs, 0.5mm², Blue
Fire spec armoured electrical cable
Application IS, INSTRUMENT SIGNAL, MULTIPAIR, OUTDOOR
Flammability properties FLAME RETARDANT
Voltage 300 V
Max Operating Temp 90 DEGREE C
Design spec BS EN 50288-7 IEC 60754 & 61034 - LSZH
Construction XLPE, IS, MS, FR-LSZH, OS, SWA, FR-LSZH-UV Resistant
Mat, conductor wire ANNEALED COPPER WIRE
Mat spec, insulation CROSS-LINKED POLYETHYLENE
Mat spec, inner sheath FLAME RETARDANT -LOW SMOKE ZERO HALOGEN TO IEC 60754 & 61034
Armouring SINGLE LAYER OF GALVANISED STEEL WIRE
Mat spec, outer sheath FLAME RETARDANT - LOW SMOKE ZERO HALOGEN TO IEC 60754 & 61034, U.V RESISTANT
Colour, outer sheath BLUE, INTRINSICALLY SAFE
Screening INDIVIDUAL AND OVERALL SCREEN WITH ALUMUNIUM POLYESTER TAPE WITH TINNED COPPER DRAIN WIRE
Flame, propagation FLAME RETARDANT to IEC-60332-1 and IEC60332-3-22
Number, Pairs 10 PAIRS,CONDUCTOR SIZE: 16/0.2
Pair Colour Identifications AS PER BS EN50288-7, BLACK AND WHITE WITH NUMBERS EMBOSSED FOR EACH PAIR.
Cross section, cores(mm2) 0.5 SQ. MM.
Diameter, OD, overall (mm) XX MM, TOLERANCE AS PER EN50288-7.
UV Resistant ACCORDING TO UL1581 – SECT 1200
Marking on the external surface of the outer sheath OUTER SHEATH TO BE EMBOSSED WITH BS NUMBER, CABLE SIZE, TYPE (FLAME RETARDANT REDUCED
TOXICITY) AND MANUFACTURER'S NAME.
Cable drum shall have fixed weatherproof identification of the following: SAP NUMBER, MANUFACTURER'S NAME AND YEAR OF MANUFACTURE, ORDER AND
ITEM NUMBER, CABLE TYPE AND SIZE, VOLTAGE GRADE AND MARKING FOR DIRECTION OF LAY.
Length Identification: CABLE DIAMETER 10 mm AND ABOVE SHOULD BE MARKED WITH LENGTH IDENTIFICATION AT REGULAR INTERVALS OF 1 METER,STARTING
FROM "0" END WHICH IS ATTACHED TO THE SPINDLE OF THE DRUM.
Routine and Type test reports: TEST CERTIFICATES TO BE SUPPLIED PER BATCH, IDENTIFYING APPLICABLE DRUMS.
Fire spec armoured electrical cable CBL ELEC ARM FIRE
Rev. 0 (July-2013) Page 17 of 24 Brunei Shell Petroleum Sdn. Bhd.
Standard BSP EFA Cables
Item SAP Material No. Simplified Cable Description Full Cable Specifications
31 1001694854 Outdoor, Instrument Signal, with Ind and overall Shield, IS, 20 Pairs, 0.5mm², Blue
Fire spec armoured electrical cable
Application IS, INSTRUMENT SIGNAL, MULTIPAIR, OUTDOOR
Flammability properties FLAME RETARDANT
Voltage 300 V
Max Operating Temp 90 DEGREE C
Design spec BS EN 50288-7 IEC 60754 & 61034 - LSZH
Construction XLPE, IS, MS, FR-LSZH, OS, SWA, FR-LSZH-UV Resistant
Mat, conductor wire ANNEALED COPPER WIRE
Mat spec, insulation CROSS-LINKED POLYETHYLENE
Mat spec, inner sheath FLAME RETARDANT -LOW SMOKE ZERO HALOGEN TO IEC 60754 & 61034
Armouring SINGLE LAYER OF GALVANISED STEEL WIRE
Mat spec, outer sheath FLAME RETARDANT - LOW SMOKE ZERO HALOGEN TO IEC 60754 & 61034, U.V RESISTANT
Colour, outer sheath BLUE, INTRINSICALLY SAFE
Screening INDIVIDUAL AND OVERALL SCREEN WITH ALUMUNIUM POLYESTER TAPE WITH TINNED COPPER DRAIN WIRE
Flame, propagation FLAME RETARDANT to IEC-60332-1 and IEC60332-3-22
Number, Pairs 20 PAIRS,CONDUCTOR SIZE :16/0.2
Pair Colour Identifications AS PER BS EN50288-7, BLACK AND WHITE WITH NUMBERS EMBOSSED FOR EACH PAIR.
Cross section, cores(mm2) 0.5 SQ. MM.
Diameter, OD, overall (mm) XX MM, TOLERANCE AS PER EN50288-7.
UV Resistant ACCORDING TO UL1581 – SECT 1200
Marking on the external surface of the outer sheath OUTER SHEATH TO BE EMBOSSED WITH BS NUMBER, CABLE SIZE, TYPE (FLAME RETARDANT REDUCED
TOXICITY) AND MANUFACTURER'S NAME.
Cable drum shall have fixed weatherproof identification of the following: SAP NUMBER, MANUFACTURER'S NAME AND YEAR OF MANUFACTURE, ORDER AND
ITEM NUMBER, CABLE TYPE AND SIZE, VOLTAGE GRADE AND MARKING FOR DIRECTION OF LAY.
Length Identification: CABLE DIAMETER 10 mm AND ABOVE SHOULD BE MARKED WITH LENGTH IDENTIFICATION AT REGULAR INTERVALS OF 1 METER,STARTING
FROM "0" END WHICH IS ATTACHED TO THE SPINDLE OF THE DRUM.
Routine and Type test reports: TEST CERTIFICATES TO BE SUPPLIED PER BATCH, IDENTIFYING APPLICABLE DRUMS.
Fire spec armoured electrical cable CBL ELEC ARM FIRE
32 1001694855 Fire Resistant Power Cable, 2 Cores, 2.5mm², Black
Fire spec armoured electrical cable
Application FIRE RESISTANT POWER, MULTICORE, OUTDOOR
Flammability properties FLAME RETARDANT
Voltage 600V/1000V
Max Operating Temp 90 DEGREE C
Design spec IEC-60502-1 IEC 60754 & 61034 - LSZH
Construction FRI/XLPE/FRLSZH/SWB/FRLSZH/UV RESISTANT
Mat, conductor wire ANNEALED COPPER WIRE
Mat spec, insulation CROSS-LINKED POLYETHYLENE
Design spec, conductor GLASS MICA TAPE APPLIED OVER CONDUCTOR
Mat spec, inner sheath FLAME RETARDANT -LOW SMOKE ZERO HALOGEN TO IEC 60754 & 61034
Armouring SINGLE LAYER OF GALVANISED STEEL WIRE BRAIDED
Mat spec, outer sheath FLAME RETARDANT - LOW SMOKE ZERO HALOGEN TO IEC 60754 & 61034, U.V RESISTANT
Colour, outer sheath BLACK, UV RESISTANT
Flame, propagation FLAME RETARDANT to IEC-60332-1 and IEC60332-3-22
Resistance, fire FIRE RESISTANT TO IEC 60331-21 and BS6387 Cat-C
Number, Cores 2 CORES ,CONDUCTOR SIZE :XX
Core Colour Identifications BROWN AND BLUE WITH NUMBERS EMBOSSED FOR EACH CORE.
Cross section, cores(mm2) 2.5 SQ. MM.
Diameter, OD, overall (mm) 15.5 MM, TOLERANCE AS PER IEC-60502-1.
UV Resistant ACCORDING TO UL1581 – SECT 1200
Marking on the external surface of the outer sheath OUTER SHEATH TO BE EMBOSSED WITH BS NUMBER, CABLE SIZE, TYPE (FLAME RETARDANT REDUCED
TOXICITY) AND MANUFACTURER'S NAME.
Cable drum shall have fixed weatherproof identification of the following: SAP NUMBER, MANUFACTURER'S NAME AND YEAR OF MANUFACTURE, ORDER AND
ITEM NUMBER, CABLE TYPE AND SIZE, VOLTAGE GRADE AND MARKING FOR DIRECTION OF LAY.
Length Identification: CABLE DIAMETER 10 mm AND ABOVE SHOULD BE MARKED WITH LENGTH IDENTIFICATION AT REGULAR INTERVALS OF 1 METER,STARTING
FROM "0" END WHICH IS ATTACHED TO THE SPINDLE OF THE DRUM.
Routine and Type test reports: TEST CERTIFICATES TO BE SUPPLIED PER BATCH, IDENTIFYING APPLICABLE DRUMS.
Fire spec armoured electrical cable CBL ELEC ARM FIRE
Rev. 0 (July-2013) Page 18 of 24 Brunei Shell Petroleum Sdn. Bhd.
Standard BSP EFA Cables
Item SAP Material No. Simplified Cable Description Full Cable Specifications
33 1001694856 Fire Resistant Power Cable, 4 Cores, 2.5mm², Black
Fire spec armoured electrical cable
Application Fire Resistant Power Cable OUTDOOR
Flammability properties FLAME RETARDANT
Voltage 600/1000 V
Max Operating Temp 90 DEGREE C
Design spec IEC-60502-1 IEC 60754 & 61034 - LSZH
Construction FRI/XLPE/FRLSZH/SWB/FRLSZH/UV-RESISTANT
Mat, conductor wire ANNEALED COPPER WIRE
Mat spec, insulation CROSS-LINKED POLYETHYLENE
Design spec, conductor GLASS MICA TAPE APPLIED OVER CONDUCTOR
Mat spec, inner sheath FLAME RETARDANT -LOW SMOKE ZERO HALOGEN TO IEC 60754 & 61034
Armouring SINGLE LAYER OF GALVANISED STEEL WIRE BRAIDED
Mat spec, outer sheath FLAME RETARDANT - LOW SMOKE ZERO HALOGEN TO IEC 60754 & 61034, U.V RESISTANT
Colour, outer sheath BLACK, UV RESISTANCE
Flame, propagation FLAME RETARDANT to IEC-60332-1 and IEC60332-3-22
Resistance, fire FIRE RESISTANT TO IEC 60331-21 and BS6387 Cat-C
Number, Cores 4 CORES,CONDUCTOR SIZE :16/0.2
Core Colour Identifications BROWN, BLACK, GREY AND BLUE WITH NUMBERS EMBOSSED FOR EACH CORE.
Cross section, cores(mm2) 2.5 SQ. MM.
Diameter, OD, overall (mm) 17 MM, TOLERANCE AS PER IEC-60502-1.
UV Resistant ACCORDING TO UL1581 – SECT 1200
Marking on the external surface of the outer sheath OUTER SHEATH TO BE EMBOSSED WITH BS NUMBER, CABLE SIZE, TYPE (FLAME RETARDANT REDUCED
TOXICITY) AND MANUFACTURER'S NAME.
Cable drum shall have fixed weatherproof identification of the following: SAP NUMBER, MANUFACTURER'S NAME AND YEAR OF MANUFACTURE, ORDER AND
ITEM NUMBER, CABLE TYPE AND SIZE, VOLTAGE GRADE AND MARKING FOR DIRECTION OF LAY.
Length Identification: CABLE DIAMETER 10 mm AND ABOVE SHOULD BE MARKED WITH LENGTH IDENTIFICATION AT REGULAR INTERVALS OF 1 METER,STARTING
FROM "0" END WHICH IS ATTACHED TO THE SPINDLE OF THE DRUM.
Routine and Type test reports: TEST CERTIFICATES TO BE SUPPLIED PER BATCH, IDENTIFYING APPLICABLE DRUMS.
Fire spec armoured electrical cable CBL ELEC ARM FIRE
34 1001708908 Fire Resistant Power Cable, 12 Cores, 2.5mm², Black
Fire spec armoured electrical cable
Application Fire Resistant Power Cable OUTDOOR
Flammability properties FLAME RETARDANT
Voltage 600/1000 V
Max Operating Temp 90 DEGREE C
Design spec IEC-60502-1 IEC 60754 & 61034 - LSZH
Construction FRI/XLPE/FRLSZH/SWB/FRLSZH/UV RESISTANT
Mat, conductor wire ANNEALED COPPER WIRE
Mat spec, insulation CROSS-LINKED POLYETHYLENE
Design spec, conductor GLASS MICA TAPE APPLIED OVER CONDUCTOR
Mat spec, inner sheath FLAME RETARDANT -LOW SMOKE ZERO HALOGEN TO IEC 60754 & 61034
Armouring SINGLE LAYER OF GALVANISED STEEL WIRE BRAIDED
Mat spec, outer sheath FLAME RETARDANT - LOW SMOKE ZERO HALOGEN TO IEC 60754 & 61034, U.V RESISTANT
Colour, outer sheath BLACK, UV RESISTANCE
Flame, propagation FLAME RETARDANT to IEC-60332-1 and IEC60332-3-22
Resistance, fire FIRE RESISTANT TO IEC 60331-21 and BS6387 Cat-C
Number, Cores 12 CORES, CONDUCTOR SIZE :16/0.2
Core Colour Identifications WHITE WITH NUMBERS EMBOSSED FOR EACHCORE.
Cross section, cores(mm2) 2.5 SQ. MM.
Diameter, OD, overall (mm) XX MM, TOLERANCE AS PER IEC-60502-1.
UV Resistant ACCORDING TO UL1581 – SECT 1200
Marking on the external surface of the outer sheath OUTER SHEATH TO BE EMBOSSED WITH BS NUMBER, CABLE SIZE, TYPE (FLAME RETARDANT REDUCED
TOXICITY) AND MANUFACTURER'S NAME.
Cable drum shall have fixed weatherproof identification of the following: SAP NUMBER, MANUFACTURER'S NAME AND YEAR OF MANUFACTURE, ORDER AND
ITEM NUMBER, CABLE TYPE AND SIZE, VOLTAGE GRADE AND MARKING FOR DIRECTION OF LAY.
Length Identification: CABLE DIAMETER 10 mm AND ABOVE SHOULD BE MARKED WITH LENGTH IDENTIFICATION AT REGULAR INTERVALS OF 1 METER,STARTING
FROM "0" END WHICH IS ATTACHED TO THE SPINDLE OF THE DRUM.
Routine and Type test reports: TEST CERTIFICATES TO BE SUPPLIED PER BATCH, IDENTIFYING APPLICABLE DRUMS.
Fire spec armoured electrical cable CBL ELEC ARM FIRE
Rev. 0 (July-2013) Page 19 of 24 Brunei Shell Petroleum Sdn. Bhd.
Standard BSP EFA Cables
Item SAP Material No. Simplified Cable Description Full Cable Specifications
35 1001694857 Instrument Standard Power cable, 2 Cores, 2.5mm², Black
Fire spec armoured electrical cable
Application INSTRUMENT POWER MULTICORE, OUTDOOR
Flammability properties FLAME RETARDANT
Voltage 600/1000 V
Max Operating Temp 90 DEGREE C
Design spec IEC-60502-1 IEC 60754 & 61034 - LSZH
Construction XLPE/FRLSZH/SWB/FRLSZH-UV RESISTANCE
Mat, conductor wire ANNEALED COPPER WIRE
Mat spec, insulation CROSS-LINKED POLYETHYLENE
Mat spec, inner sheath FLAME RETARDANT -LOW SMOKE ZERO HALOGEN TO IEC 60754 & 61034
Armouring SINGLE LAYER OF GALVANISED STEEL WIRE BRAIDED
Mat spec, outer sheath FLAME RETARDANT - LOW SMOKE ZERO HALOGEN TO IEC 60754 & 61034, U.V RESISTANT
Colour, outer sheath BLACK, UV RESISTANCE
Screening INDIVIDUAL AND OVERALL SCREEN WITH ALUMUNIUM POLYESTER TAPE WITH TINNED COPPER DRAIN WIRE
Flame, propagation FLAME RETARDANT to IEC-60332-1 and IEC60332-3-22
Number, Cores 2 CORES, CONDUCTOR SIZE: 16/0.2
Core Colour Identifications BROWN AND BLUE WITH NUMBERS EMBOSSED FOR EACH CORE.
Cross section, cores(mm2) 2.5 SQ. MM.
Diameter, OD, overall (mm) XX MM, TOLERANCE AS PER IEC-60502-1.
UV Resistant ACCORDING TO UL1581 – SECT 1200
Marking on the external surface of the outer sheath OUTER SHEATH TO BE EMBOSSED WITH BS NUMBER, CABLE SIZE, TYPE (FLAME RETARDANT REDUCED
TOXICITY) AND MANUFACTURER'S NAME.
Cable drum shall have fixed weatherproof identification of the following: SAP NUMBER, MANUFACTURER'S NAME AND YEAR OF MANUFACTURE, ORDER AND
ITEM NUMBER, CABLE TYPE AND SIZE, VOLTAGE GRADE AND MARKING FOR DIRECTION OF LAY.
Length Identification: CABLE DIAMETER 10 mm AND ABOVE SHOULD BE MARKED WITH LENGTH IDENTIFICATION AT REGULAR INTERVALS OF 1 METER,STARTING
FROM "0" END WHICH IS ATTACHED TO THE SPINDLE OF THE DRUM.
Routine and Type test reports: TEST CERTIFICATES TO BE SUPPLIED PER BATCH, IDENTIFYING APPLICABLE DRUMS.
Fire spec armoured electrical cable CBL ELEC ARM FIRE
36 1001694858 Instrument Standard Power cable, 4 Cores, 2.5mm², Black
Fire spec armoured electrical cable
Application INSTRUMENT POWER MULTICORE, OUTDOOR
Flammability properties FLAME RETARDANT
Voltage V 600/1000
Max Operating Temp 90 DEGREE C
Design spec IEC-60502-1 IEC 60754 & 61034 - LSZH
Construction XLPE/FRLSZH/SWB/FRLSZH-UV RESISTANCE
Mat, conductor wire PLAIN ANNEALED COPPER WIRE
Mat spec, insulation CROSS-LINKED POLYETHYLENE
Mat spec, inner sheath FLAME RETARDANT -LOW SMOKE ZERO HALOGEN TO IEC 60754 & 61034
Armouring BRAIDED GALVANISED STEEL WIRE
Mat spec, outer sheath FLAME RETARDANT - LOW SMOKE ZERO HALOGEN TO IEC 60754 & 61034, U.V RESISTANT
Colour, outer sheath BLACK, UV RESISTANCE
Screening INDIVIDUAL AND OVERALL SCREEN WITH ALUMUNIUM POLYESTER TAPE WITH TINNED COPPER DRAIN WIRE
Flame, propagation FLAME RETARDANT to IEC-60332-1 and IEC60332-3-22
Number, Cores 4 CORES, CONDUCTOR SIZE: XX
Core Colour Identifications BROWN, BLACK, GREY AND BLUE WITH NUMBERS EMBOSSED FOR EACH CORE.
Cross section, cores(mm2) 2.5 SQ. MM.
Diameter, OD, overall (mm) 15 MM, TOLERANCE AS PER IEC-60502-1.
UV Resistant ACCORDING TO UL1581 – SECT 1200
Marking on the external surface of the outer sheath OUTER SHEATH TO BE EMBOSSED WITH BS NUMBER, CABLE SIZE, TYPE (FLAME RETARDANT REDUCED
TOXICITY) AND MANUFACTURER'S NAME.
Cable drum shall have fixed weatherproof identification of the following: SAP NUMBER, MANUFACTURER'S NAME AND YEAR OF MANUFACTURE, ORDER AND
ITEM NUMBER, CABLE TYPE AND SIZE, VOLTAGE GRADE AND MARKING FOR DIRECTION OF LAY.
Length Identification: CABLE DIAMETER 10 mm AND ABOVE SHOULD BE MARKED WITH LENGTH IDENTIFICATION AT REGULAR INTERVALS OF 1 METER,STARTING
FROM "0" END WHICH IS ATTACHED TO THE SPINDLE OF THE DRUM.
Routine and Type test reports: TEST CERTIFICATES TO BE SUPPLIED PER BATCH, IDENTIFYING APPLICABLE DRUMS.
Fire spec armoured electrical cable CBL ELEC ARM FIRE
Rev. 0 (July-2013) Page 20 of 24 Brunei Shell Petroleum Sdn. Bhd.
Standard BSP EFA Cables
Item SAP Material No. Simplified Cable Description Full Cable Specifications
37 1001694859 Instrument Standard Power cable, 12 Cores, 2.5mm², Black
Fire spec armoured electrical cable
Application INSTRUMENT POWER MULTICORE, OUTDOOR
Flammability properties FLAME RETARDANT
Voltage V 600/1000
Max Operating Temp 90 DEGREE C
Design spec IEC-60502-1 IEC 60754 & 61034 - LSZH
Construction XLPE/FRLSZH/SWB/FRLSZH-UV RESISTANCE
Mat, conductor wire PLAIN ANNEALED COPPER WIRE
Mat spec, insulation CROSS-LINKED POLYETHYLENE
Mat spec, inner sheath FLAME RETARDANT -LOW SMOKE ZERO HALOGEN TO IEC 60754 & 61034
Armouring SINGLE LAYER OF GALVANISED STEEL WIRE BRAIDED
Mat spec, outer sheath FLAME RETARDANT - LOW SMOKE ZERO HALOGEN TO IEC 60754 & 61034, U.V RESISTANT
Colour, outer sheath BLACK, UV RESISTANCE
Screening INDIVIDUAL AND OVERALL SCREEN WITH ALUMUNIUM POLYESTER TAPE WITH TINNED COPPER DRAIN WIRE
Flame, propagation FLAME RETARDANT to IEC-60332-1 and IEC60332-3-22
Number, Cores 12 CORES CONDUCTOR SIZE: XX
Core Colour Identifications WHITE WITH NUMBERS EMBOSSED FOR EACHCORE.
Cross section, cores(mm2) 2.5 SQ. MM.
Diameter, OD, overall (mm) XX MM, TOLERANCE AS PER IEC-60502-1.
UV Resistant ACCORDING TO UL1581 – SECT 1200
Marking on the external surface of the outer sheath OUTER SHEATH TO BE EMBOSSED WITH BS NUMBER, CABLE SIZE, TYPE (FLAME RETARDANT REDUCED
TOXICITY) AND MANUFACTURER'S NAME.
Cable drum shall have fixed weatherproof identification of the following: SAP NUMBER, MANUFACTURER'S NAME AND YEAR OF MANUFACTURE, ORDER AND
ITEM NUMBER, CABLE TYPE AND SIZE, VOLTAGE GRADE AND MARKING FOR DIRECTION OF LAY.
Length Identification: CABLE DIAMETER 10 mm AND ABOVE SHOULD BE MARKED WITH LENGTH IDENTIFICATION AT REGULAR INTERVALS OF 1 METER,STARTING
FROM "0" END WHICH IS ATTACHED TO THE SPINDLE OF THE DRUM.
Routine and Type test reports: TEST CERTIFICATES TO BE SUPPLIED PER BATCH, IDENTIFYING APPLICABLE DRUMS.
Fire spec armoured electrical cable CBL ELEC ARM FIRE
38 1001708907 Instrument Standard Power cable, 27 Cores, 2.5mm², Black
Fire spec armoured electrical cable
Application INSTRUMENT POWER MULTICORE, OUTDOOR
Flammability properties FLAME RETARDANT
Voltage 600/1000 V
Max Operating Temp 90 DEGREE C
Design spec IEC-60502-1, IEC 60754 & 61034 - LSZH
Construction XLPE/FRLSZH/SWB/FRLSZH-UV RESISTANCE
Mat, conductor wire ANNEALED COPPER WIRE
Mat spec, insulation CROSS-LINKED POLYETHYLENE
Mat spec, inner sheath FLAME RETARDANT -LOW SMOKE ZERO HALOGEN TO IEC 60754 & 61034
Armouring SINGLE LAYER OF GALVANISED STEEL WIRE BRAIDED
Mat spec, outer sheath FLAME RETARDANT - LOW SMOKE ZERO HALOGEN TO IEC 60754 & 61034, U.V RESISTANT
Colour, outer sheath BLACK, UV RESISTANCE
Screening INDIVIDUAL AND OVERALL SCREEN WITH ALUMUNIUM POLYESTER TAPE WITH TINNED COPPER DRAIN WIRE
Flame, propagation FLAME RETARDANT to IEC-60332-1 and IEC60332-3-22
Number, Cores 27 CORES, CONDUCTOR SIZE: XX
Core Colour Identifications WHITE WITH NUMBERS EMBOSSED FOR EACHCORE.
Cross section, cores(mm2) 2.5 SQ. MM.
Diameter, OD, overall (mm) XX MM, TOLERANCE AS PER IEC-60502-1.
UV Resistant ACCORDING TO UL1581 – SECT 1200
Marking on the external surface of the outer sheath OUTER SHEATH TO BE EMBOSSED WITH BS NUMBER, CABLE SIZE, TYPE (FLAME RETARDANT REDUCED
TOXICITY) AND MANUFACTURER'S NAME.
Cable drum shall have fixed weatherproof identification of the following: SAP NUMBER, MANUFACTURER'S NAME AND YEAR OF MANUFACTURE, ORDER AND
ITEM NUMBER, CABLE TYPE AND SIZE, VOLTAGE GRADE AND MARKING FOR DIRECTION OF LAY.
Length Identification: CABLE DIAMETER 10 mm AND ABOVE SHOULD BE MARKED WITH LENGTH IDENTIFICATION AT REGULAR INTERVALS OF 1 METER,STARTING
FROM "0" END WHICH IS ATTACHED TO THE SPINDLE OF THE DRUM.
Routine and Type test reports: TEST CERTIFICATES TO BE SUPPLIED PER BATCH, IDENTIFYING APPLICABLE DRUMS.
Fire spec armoured electrical cable CBL ELEC ARM FIRE
Rev. 0 (July-2013) Page 21 of 24 Brunei Shell Petroleum Sdn. Bhd.
Standard BSP EFA Cables
Item SAP Material No. Simplified Cable Description Full Cable Specifications
39 1001694921 Fieldbus, 1 Pair, 0.8mm², Black
Fieldbus cable per IEC 61558-2
Application H1 Fieldbus- TYPE A, OUTDOOR
Flammability properties FLAME RETARDANT
Voltage 300 V
Max Operating Temp 90 DEGREE C
Design spec IEC-60502-1, IEC 60754 & 61034 - LSZH
Construction XLPE/ IS/FRLSZH/OS/SWA/FRLSZH-UV RESISTANCE
Mat, conductor wire STRANDED BARE COPPER
Mat spec, insulation CROSS-LINKED POLYETHYLENE
Mat spec, inner sheath FLAME RETARDANT -LOW SMOKE ZERO HALOGEN TO IEC 60754 & 61034
Armouring SINGLE LAYER OF GALVANISED STEEL WIRE ARMOUR
Mat spec, outer sheath FLAME RETARDANT - LOW SMOKE ZERO HALOGEN TO IEC 60754 & 61034, U.V RESISTANT
Colour, outer sheath BLACK, UV RESISTANCE
Screening INDIVIDUAL AND OVERALL SCREEN WITH ALUMUNIUM POLYESTER TAPE WITH TINNED COPPER DRAIN WIRE
Flame, propagation FLAME RETARDANT to IEC-60332-1 and IEC60332-3-22
Number, Pairs 1 PAIR, CONDUCTOR SIZE: XX
Pair Colour Identifications AS PER BS IEC-60502-1, BLUE AND ORANGE WITH NUMBERS EMBOSSED FOR EACH PAIR.
Cross section, cores(mm2) 0.8 SQ. MM.
Diameter, OD, overall (mm) TOLERANCE AS PER IEC-60502-1.
UV Resistant ACCORDING TO UL1581 – SECT 1200
Maximum conductor resistance 22 OHMS/KM
Impedance @ 31.25kHz 100 OHMS +/- 20%
Maximum attenuation @ 39kHz 3 DB/KM
Maximum Capacitive unbalance to shield 150 pF/KM
Marking on the external surface of the outer sheath OUTER SHEATH TO BE EMBOSSED WITH BS NUMBER, CABLE SIZE, TYPE (FLAME RETARDANT REDUCED
TOXICITY) AND MANUFACTURER'S NAME.
Cable drum shall have fixed weatherproof identification of the following: SAP NUMBER, MANUFACTURER'S NAME AND YEAR OF MANUFACTURE, ORDER AND
ITEM NUMBER, CABLE TYPE AND SIZE, VOLTAGE GRADE AND MARKING FOR DIRECTION OF LAY.
Length Identification: CABLE DIAMETER 10 mm AND ABOVE SHOULD BE MARKED WITH LENGTH IDENTIFICATION AT REGULAR INTERVALS OF 1 METER,STARTING
FROM "0" END WHICH IS ATTACHED TO THE SPINDLE OF THE DRUM.
Outer sheath to be marked with "FIELDBUS CABLE" label.
Routine and Type test reports: TEST CERTIFICATES TO BE SUPPLIED PER BATCH, IDENTIFYING APPLICABLE DRUMS.
Fire spec armoured electrical cable CBL ELEC ARM FIRE
40 1001694922 Fieldbus, 2 Pairs, 0.8mm², Black
Fieldbus cable per IEC 61558-2
Application H1 Fieldbus- TYPE A, OUTDOOR
Flammability properties FLAME RETARDANT
Voltage 300 V
Max Operating Temp 90 DEGREE C
Design spec IEC-60502-1, IEC 60754 & 61034 - LSZH
Construction XLPE/ IS/FRLSZH/OS/SWA/FRLSZH-UV RESISTANCE
Mat, conductor wire STRANDED BARE COPPER
Mat spec, insulation CROSS-LINKED POLYETHYLENE
Mat spec, inner sheath FLAME RETARDANT -LOW SMOKE ZERO HALOGEN TO IEC 60754 & 61034
Armouring SINGLE LAYER OF GALVANISED STEEL WIRE ARMOUR
Mat spec, outer sheath FLAME RETARDANT - LOW SMOKE ZERO HALOGEN TO IEC 60754 & 61034, U.V RESISTANT
Colour, outer sheath BLACK, UV RESISTANCE
Screening INDIVIDUAL AND OVERALL SCREEN WITH ALUMUNIUM POLYESTER TAPE WITH TINNED COPPER DRAIN WIRE
Flame, propagation FLAME RETARDANT to IEC-60332-1 and IEC60332-3-22
Number, Pairs 2 PAIRS, CONDUCTOR SIZE: XX
Pair Colour Identifications AS PER BS IEC-60502-1, BLUE AND ORANGE WITH NUMBERS EMBOSSED FOR EACH PAIR.
Cross section, cores(mm2) 0.8 SQ. MM.
Diameter, OD, overall (mm) TOLERANCE AS PER IEC-60502-1.
UV Resistant ACCORDING TO UL1581 – SECT 1200
Maximum conductor resistance 22 OHMS/KM
Impedance @ 31.25kHz 100 OHMS +/- 20%
Maximum attenuation @ 39kHz 3 DB/KM
Maximum Capacitive unbalance to shield 150 pF/KM
Marking on the external surface of the outer sheath OUTER SHEATH TO BE EMBOSSED WITH BS NUMBER, CABLE SIZE, TYPE (FLAME RETARDANT REDUCED
TOXICITY) AND MANUFACTURER'S NAME.
Cable drum shall have fixed weatherproof identification of the following: SAP NUMBER, MANUFACTURER'S NAME AND YEAR OF MANUFACTURE, ORDER AND
ITEM NUMBER, CABLE TYPE AND SIZE, VOLTAGE GRADE AND MARKING FOR DIRECTION OF LAY.
Length Identification: CABLE DIAMETER 10 mm AND ABOVE SHOULD BE MARKED WITH LENGTH IDENTIFICATION AT REGULAR INTERVALS OF 1 METER,STARTING
FROM "0" END WHICH IS ATTACHED TO THE SPINDLE OF THE DRUM.
Outer sheath to be marked with "FIELDBUS CABLE" label.
Routine and Type test reports: TEST CERTIFICATES TO BE SUPPLIED PER BATCH, IDENTIFYING APPLICABLE DRUMS.
Fire spec armoured electrical cable CBL ELEC ARM FIRE
Rev. 0 (July-2013) Page 22 of 24 Brunei Shell Petroleum Sdn. Bhd.
Standard BSP EFA Cables
Item SAP Material No. Simplified Cable Description Full Cable Specifications
41 1001694923 Fieldbus, 10 Pairs, 0.8mm², Black
Fieldbus cable per IEC 61558-2
Application H1 Fieldbus- TYPE A, OUTDOOR
Flammability properties FLAME RETARDANT
Voltage 300 V
Max Operating Temp 90 DEGREE C
Design spec IEC-60502-1, IEC 60754 & 61034 - LSZH
Construction XLPE/ IS/FRLSZH/OS/SWA/FRLSZH-UV RESISTANCE
Mat, conductor wire STRANDED BARE COPPER
Mat spec, insulation CROSS-LINKED POLYETHYLENE
Mat spec, inner sheath FLAME RETARDANT -LOW SMOKE ZERO HALOGEN TO IEC 60754 & 61034
Armouring SINGLE LAYER OF GALVANISED STEEL WIRE ARMOUR
Mat spec, outer sheath FLAME RETARDANT - LOW SMOKE ZERO HALOGEN TO IEC 60754 & 61034, U.V RESISTANT
Colour, outer sheath BLACK, UV RESISTANCE
Screening INDIVIDUAL AND OVERALL SCREEN WITH ALUMUNIUM POLYESTER TAPE WITH TINNED COPPER DRAIN WIRE
Flame, propagation FLAME RETARDANT to IEC-60332-1 and IEC60332-3-22
Number, Pairs 10 PAIRS, CONDUCTOR SIZE: XX
Pair Colour Identifications AS PER BS IEC-60502-1, BLUE AND ORANGE WITH NUMBERS EMBOSSED FOR EACH PAIR.
Cross section, cores(mm2) 0.8 SQ. MM.
Diameter, OD, overall (mm) TOLERANCE AS PER IEC-60502-1.
UV Resistant ACCORDING TO UL1581 – SECT 1200
Maximum conductor resistance 22 OHMS/KM
Impedance @ 31.25kHz 100 OHMS +/- 20%
Maximum attenuation @ 39kHz 3 DB/KM
Maximum Capacitive unbalance to shield 150 pF/KM
Marking on the external surface of the outer sheath OUTER SHEATH TO BE EMBOSSED WITH BS NUMBER, CABLE SIZE, TYPE (FLAME RETARDANT REDUCED
TOXICITY) AND MANUFACTURER'S NAME.
Cable drum shall have fixed weatherproof identification of the following: SAP NUMBER, MANUFACTURER'S NAME AND YEAR OF MANUFACTURE, ORDER AND
ITEM NUMBER, CABLE TYPE AND SIZE, VOLTAGE GRADE AND MARKING FOR DIRECTION OF LAY.
Length Identification: CABLE DIAMETER 10 mm AND ABOVE SHOULD BE MARKED WITH LENGTH IDENTIFICATION AT REGULAR INTERVALS OF 1 METER,STARTING
FROM "0" END WHICH IS ATTACHED TO THE SPINDLE OF THE DRUM.
Outer sheath to be marked with "FIELDBUS CABLE" label.
Routine and Type test reports: TEST CERTIFICATES TO BE SUPPLIED PER BATCH, IDENTIFYING APPLICABLE DRUMS.
Fire spec armoured electrical cable CBL ELEC ARM FIRE
42 1001694861 Fiber Optic, 12 Cores, Single Mode, Black
Fiber Optic Cable
Application Ethernet / VoIP/ Data/ CCTV/ Instrument Signal, Multi core
Flammability properties Flame Retardant, Low Smoke Zero Halogen
Design spec IEC 60793, IEC 60794 Part 3, IEC 60754 & IEC 61034 - LSZH
Construction Strength member, Fiber, Loose tube, moisture barrier sheath, PE inner sheath, SWA, PE outer sheath
Mat spec, Central Strength member Fiber Glass
Core Cladding Material/ Filling PBT Loose Tubes/ Jelly Filled
Mat spec, inner sheath Polyethylene, LSZH
Mat spec, outer sheath PE, LSZH
Colour, outer sheath Black
Armouring Single Layer of Galvanised Steel Wire
Flame, propagation FLAME RETARDANT to IEC-60332-1 and IEC60332-3-22
Number, cores 12 cores
UV Resistant According To UL1581 – Sect 1200
Optical Fibre Type : Single Mode
Max Attenuation 0.4 dB/km @ wavelength 1300nm
Core Diameter: 8.7± 0.5µm
Cladding Diameter for Each core: 125 ± 2 µm
Outer Diameter: Max 16mm
Connector Type: FC
Cable characteristics IEC 60793-1
Cable drum shall have fixed weatherproof identification of the following: Cable Drum shall be labeled with Manufacturer Name, Applicable IEC Standard,
Number(s) and type(s) of Fiber (s), Total Cable Length, Year of Manufacture, Manufacturing sequence order (Batch Number)
Length Identification: CABLE DIAMETER 10 mm AND ABOVE SHOULD BE MARKED WITH LENGTH IDENTIFICATION AT REGULAR INTERVALS OF 1 METER,STARTING
FROM "0" END WHICH IS ATTACHED TO THE SPINDLE OF THE DRUM.
Routine and Type test reports: TEST CERTIFICATES TO BE SUPPLIED PER BATCH, IDENTIFYING APPLICABLE DRUMS.
Rev. 0 (July-2013) Page 23 of 24 Brunei Shell Petroleum Sdn. Bhd.
Standard BSP EFA Cables
Item SAP Material No. Simplified Cable Description Full Cable Specifications
43 1001694862 Fiber Optic, 16 Cores, Single Mode, Black
Fiber Optic Cable
Application Ethernet / VoIP/ Data/ CCTV/ Instrument Signal, Multi core
Flammability properties Flame Retardant, Low Smoke Zero Halogen
Design spec IEC 60793, IEC 60794 Part 3, IEC 60754 & IEC 61034 - LSZH
Construction Strength member, Fiber, Loose tube, moisture barrier sheath, PE inner sheath, SWA, PE outer sheath
Mat spec, Central Strength member Fiber Glass
Core Cladding Material/ Filling PBT Loose Tubes/ Jelly Filled
Mat spec, inner sheath Polyethylene, LSZH
Mat spec, outer sheath PE, LSZH
Colour, outer sheath Black
Armouring Single Layer of Galvanised Steel Wire
Flame, propagation FLAME RETARDANT to IEC-60332-1 and IEC60332-3-22
Number, cores 16 cores
UV Resistant According To UL1581 – Sect 1200
Optical Fibre Type : Single Mode
Max Attenuation 0.4 dB/km @ wavelength 1300nm
Core Diameter: 8.7± 0.5µm
Cladding Diameter for Each core: 125 ± 2 µm
Outer Diameter: Max XXmm
Connector Type: FC
Cable characteristics IEC 60793-1
Cable drum shall have fixed weatherproof identification of the following: Cable Drum shall be labeled with Manufacturer Name, Applicable IEC Standard,
Number(s) and type(s) of Fiber (s), Total Cable Length, Year of Manufacture, Manufacturing sequence order (Batch Number)
Length Identification: CABLE DIAMETER 10 mm AND ABOVE SHOULD BE MARKED WITH LENGTH IDENTIFICATION AT REGULAR INTERVALS OF 1 METER,STARTING
FROM "0" END WHICH IS ATTACHED TO THE SPINDLE OF THE DRUM.
Routine and Type test reports: TEST CERTIFICATES TO BE SUPPLIED PER BATCH, IDENTIFYING APPLICABLE DRUMS.
44 1001694863 Fiber Optic, 24 Cores, Single Mode, Black
Fiber Optic Cable
Application Ethernet / VoIP/ Data/ CCTV/ Instrument Signal, Multi core
Flammability properties Flame Retardant, Low Smoke Zero Halogen
Design spec IEC 60793, IEC 60794 Part 3, IEC 60754 & IEC 61034 - LSZH
Construction Strength member, Fiber, Loose tube, moisture barrier sheath, PE inner sheath, SWA, PE outer sheath
Mat spec, Central Strength member Fiber Glass
Core Cladding Material/ Filling PBT Loose Tubes/ Jelly Filled
Mat spec, inner sheath Polyethylene, LSZH
Mat spec, outer sheath PE, LSZH
Colour, outer sheath Black
Armouring Single Layer of Galvanised Steel Wire
Flame, propagation FLAME RETARDANT to IEC-60332-1 and IEC60332-3-22
Number, cores 24 cores
UV Resistant According To UL1581 – Sect 1200
Optical Fibre Type : Single Mode
Max Attenuation 0.4 dB/km @ wavelength 1300nm
Core Diameter: 8.7± 0.5µm
Cladding Diameter for Each core: 125 ± 2 µm
Outer Diameter: Max XXmm
Connector Type: FC
Cable characteristics IEC 60793-1
Cable drum shall have fixed weatherproof identification of the following: Cable Drum shall be labeled with Manufacturer Name, Applicable IEC Standard,
Number(s) and type(s) of Fiber (s), Total Cable Length, Year of Manufacture, Manufacturing sequence order (Batch Number)
Length Identification: CABLE DIAMETER 10 mm AND ABOVE SHOULD BE MARKED WITH LENGTH IDENTIFICATION AT REGULAR INTERVALS OF 1 METER,STARTING
FROM "0" END WHICH IS ATTACHED TO THE SPINDLE OF THE DRUM.
Routine and Type test reports: TEST CERTIFICATES TO BE SUPPLIED PER BATCH, IDENTIFYING APPLICABLE DRUMS.
Rev. 0 (July-2013) Page 24 of 24 Brunei Shell Petroleum Sdn. Bhd.