STAMI (ST Advanced Metering Interface) Web Tool for the advanced management of LV Network...

22
STAMI (ST Advanced Metering Interface) Web Tool for the advanced management of LV Network Trends in Power Industry in the European Context VIII Antonello Buondonno Head of Europe and Americas Business Development Enel Infrastructures and Network Division Spindleruv Mlin, April 18 th 2013

description

STAMI (ST Advanced Metering Interface) Web Tool for the advanced management of LV Network Trends in Power Industry in the European Context VIII. Antonello Buondonno Head of Europe and Americas Business Development Enel Infrastructures and Network Division - PowerPoint PPT Presentation

Transcript of STAMI (ST Advanced Metering Interface) Web Tool for the advanced management of LV Network...

Page 1: STAMI (ST  Advanced  Metering Interface) Web Tool for the advanced  management  of LV  Network Trends in  Power Industry  in the  European Context  VIII

STAMI (ST Advanced Metering Interface)Web Tool for the advanced management of LV NetworkTrends in Power Industry in the European Context VIII

Antonello BuondonnoHead of Europe and Americas Business DevelopmentEnel Infrastructures and Network Division

Spindleruv Mlin, April 18th 2013

Page 2: STAMI (ST  Advanced  Metering Interface) Web Tool for the advanced  management  of LV  Network Trends in  Power Industry  in the  European Context  VIII

Uso: Aziendale

STAMI: ST Advanced Metering InterfaceAgenda

• ST Web Applications

• STAMI

• System Architecture

• Main features and tools for the LV Operation Management

Page 3: STAMI (ST  Advanced  Metering Interface) Web Tool for the advanced  management  of LV  Network Trends in  Power Industry  in the  European Context  VIII

Uso: Aziendale

ST Web ApplicationsRemote Control and automation system – ST Web Applications

HV

LV

MV

Network Metering System

STUX/STM

ST Remote Control and Automation

System

ST Web Applications

Other Company applications

Page 4: STAMI (ST  Advanced  Metering Interface) Web Tool for the advanced  management  of LV  Network Trends in  Power Industry  in the  European Context  VIII

Uso: Aziendale

ST Web ApplicationsRemote Control and automation system – ST Web Applications

Measurements

Systems Statistics

and Performances

Management Of the Active Grid

Maintenance

GIS & Network SchemesEventsSTAMI – ST Advanced

Metering Interface

Page 5: STAMI (ST  Advanced  Metering Interface) Web Tool for the advanced  management  of LV  Network Trends in  Power Industry  in the  European Context  VIII

Uso: Aziendale

STAMI: ST Advanced Metering InterfaceWeb Tool for the advanced Network Management

STAMI: dedicated Web Interface to collect (on demand and real time) specific high quality data stored in smart meters for network management purposes.

STAMI main applications:

Customer Service Network Operations Electricity Regulation Compliance Energy Balance and fraud detection

The European Utility Award for 2010 has been awarded to Enel for STAMI

Network Control Center

Workstations

Web Client

STAMI interface On field

installed Smart Meters

Page 6: STAMI (ST  Advanced  Metering Interface) Web Tool for the advanced  management  of LV  Network Trends in  Power Industry  in the  European Context  VIII

Uso: Aziendale

STAMI: ST Advanced Metering InterfaceWeb Tool for the advanced Network Management

STAMI: dedicated Web Interface to collect (on demand and real time) specific high quality data stored in smart meters for network management purposes.

STAMI allows to access to the following data stored in Smart Meters:

The European Utility Award for 2010 has been awarded to Enel for STAMI

Network Control Center

Workstations

Web Client

STAMI interface On field

installed Smart Meters

Voltage Quality Voltage Outages

Load Profile

Daily consumption

Monthly consumption

Power threshold

Page 7: STAMI (ST  Advanced  Metering Interface) Web Tool for the advanced  management  of LV  Network Trends in  Power Industry  in the  European Context  VIII

Uso: Aziendale

STAMI: Advanced Metering InterfaceArchitecture

DMZ

Remote Control LANCompany IP Network

LVC

GSM/GPRS or

PSTN

LV network

Users send requests through STAMI interfaceInterface available on Enel Intranet and on the workstations installed in Network Control Centers

1

Requests are forwarded to STAMI WS which interacts with Server ZEUS

2Server Zeus processes requests directly connecting with Smart meters through concentrators in secondary substation.Security to read meters is managed by Zeus Itself

3

STAMI Interface

Web ServerZeus Web interface for TelegestoreAMM

Page 8: STAMI (ST  Advanced  Metering Interface) Web Tool for the advanced  management  of LV  Network Trends in  Power Industry  in the  European Context  VIII

Uso: Aziendale

Main features and tools for the Operation Management Main Features and related benefits

Customer Service: Improvement of Customer Service and LV operation activity related to customer request

Network Operations: Optimization of Work Force Activities

Electricity Regulator Compliance: Provide reliable and immediate data related to LV continuity and quality of supply

Energy Balance: Effectively localize energy fraud & theft

Page 9: STAMI (ST  Advanced  Metering Interface) Web Tool for the advanced  management  of LV  Network Trends in  Power Industry  in the  European Context  VIII

Uso: Aziendale

Main features and tools for the Operation Management Customer Service

Support the Control Center Operator in case of customer request:

VOLTAGE INTERRUPTIONS

VOLTAGE QUALITY

10POWER THRESHOLD (%)

STAMI operator can give immediate feedback in case of customer service anomalies

Customer satisfaction improvement

STAMI allows to check the power threshold available to the customer to immediately localize a bad payer

Immediately check defaulting customer

Throw STAMI it is possible to check voltage presence and voltage quality at the supply terminal without involving a crew for verification on field

Real time response from field installed equipment

1

234

Page 10: STAMI (ST  Advanced  Metering Interface) Web Tool for the advanced  management  of LV  Network Trends in  Power Industry  in the  European Context  VIII

Uso: Aziendale

Main features and tools for the Operation Management Operations

STAMI support daily Low Voltage Network Operations Activity:

In case of LV customer warning call, STAMI operator is able to real time check the condition of the LV network supplying the electronic meter.

Low Voltage Network supervising

In case of LV network fault, STAMI operator may immediately verify the origin of the anomaly and program the activity on field.

Optimization of Work Force activities

LV line fault

Electronic Meter fault

VOLTAGE INTERRUPTIONS

VOLTAGE QUALITY

Page 11: STAMI (ST  Advanced  Metering Interface) Web Tool for the advanced  management  of LV  Network Trends in  Power Industry  in the  European Context  VIII

Uso: Aziendale

Main features and tools for the Operation Management Electricity Regulator Compliance

Throw STAMI It is possible to directly see voltage outages without waiting for documentation

Reliable and immediate data related to LV supply

Quality of service data related to MV/LV TR and LV lines available throw STAMI may be used for reporting

Quality of service monitoring

Thanks to STAMI it is possible to identify LV outages with the exact indication of the beginning and the end

Voltage Interruptions recording

On field technician

Low voltage faults and interruptions

form

Date/Hour/Time....

Interruption....

Fault....

Username....

VOLTAGE INTERRUPTIONS

STAMI operator

Page 12: STAMI (ST  Advanced  Metering Interface) Web Tool for the advanced  management  of LV  Network Trends in  Power Industry  in the  European Context  VIII

Uso: Aziendale

Main features and tools for the Operation Management Energy Balance

Acquisition of load profile and daily consumptions to support fraud detection

Effectively localize energy fraud & theft

STAMI operators are able to perform detailed analysis on the LV network, providing support to the crews in the identification of frauds

By accurate analysis, it allows to identify precisely the customers to be checked on field

Energy Balance

Load profile

DAILY CONSUMPTIONS

Central access

IntranetEnel

On field accessMV/LV

Energy Balance meter

For more accurate analysis, STAMI allows to upload and analyze data coming from portable energy balance meters (ALVIN)

Page 13: STAMI (ST  Advanced  Metering Interface) Web Tool for the advanced  management  of LV  Network Trends in  Power Industry  in the  European Context  VIII

Uso: Aziendale

Thank you

Antonello BuondonnoHead of Europe and Americas

Business DevelopmentEnel Infrastructure and Network Division

[email protected]

Page 14: STAMI (ST  Advanced  Metering Interface) Web Tool for the advanced  management  of LV  Network Trends in  Power Industry  in the  European Context  VIII

Uso: Aziendale

Backup

Page 15: STAMI (ST  Advanced  Metering Interface) Web Tool for the advanced  management  of LV  Network Trends in  Power Industry  in the  European Context  VIII

Uso: Aziendale

STAMI: Advanced Metering InterfaceWeb Interface: main operations

Information ViewingIt makes possible to quickly access and

download the results coming from user requests

Data requestUsed to send data requests: it is possible to directly ask about a Meter, a Concentrator, a customized group of meters

Status of transactionsUsed to display all the data requests and to

check their status.

ALVIN ManagementUsed to upload and analyze data coming from

portable energy balance meters (ALVIN)

Page 16: STAMI (ST  Advanced  Metering Interface) Web Tool for the advanced  management  of LV  Network Trends in  Power Industry  in the  European Context  VIII

Uso: Aziendale

STAMI: Advanced Metering InterfaceData availability from Electronic Meters

Period, Instantaneous Voltage value, VMIN and VMAX for each phase, number of samples in the allowed range (230V+-10%), number of samples out of allowed range. Electronics meters record a value every ten minutes: 1008 samples a week available.

Voltage Quality

Voltage Outages

Period, onset time, duration of the interruption, affected phase, electric line involved

Monthly consumption

Date, energy consumption value in a billing period on T1, T2 and T3

Page 17: STAMI (ST  Advanced  Metering Interface) Web Tool for the advanced  management  of LV  Network Trends in  Power Industry  in the  European Context  VIII

Uso: Aziendale

STAMI: Advanced Metering InterfaceData availability from Electronic Meters

Graph and list of active and reactive power consumption and active power feeding the grid (in case of active customers).Electronic Meter stores Power average value every 15 minutes

Load Profile

Power threshold

Percentage of contractual power available to the customer

Daily consumption

Date and daily value of energy consumption

Page 18: STAMI (ST  Advanced  Metering Interface) Web Tool for the advanced  management  of LV  Network Trends in  Power Industry  in the  European Context  VIII

Uso: Aziendale

STAMI: Advanced Metering InterfaceViewing information menu: Power Threshold

Defaulting CustomerIn case of a customer's phone call,

Enel doesn’t need to send a technician on site to check if he is

a bad payer.

Page 19: STAMI (ST  Advanced  Metering Interface) Web Tool for the advanced  management  of LV  Network Trends in  Power Industry  in the  European Context  VIII

Uso: Aziendale

STAMI: Advanced Metering InterfaceViewing information menù: Voltage Outages

The fault can affect one or more

phases

Page 20: STAMI (ST  Advanced  Metering Interface) Web Tool for the advanced  management  of LV  Network Trends in  Power Industry  in the  European Context  VIII

Uso: Aziendale

STAMI: Advanced Metering InterfaceLoad Profile

Active Customer Load Profile: set of graphs available for each meter.

A Load Profile Request returns to the operator a set of graphs with the average active and reactive power consumption profile and, in case of active customers, the active power feeding the grid.

Instead of a graphic representation it is also possible to display the list of the average power consumption values stored in the smart meter every 15 minutes.

It is possible to send a Load Profile request for a single Smart Meter or a whole MT/bt Transformer. In this case STAMI returns the load profile of each Smart Meter, the Load profile, in a unique curve, of the sum of al the smart meters connected to the TR and the load profile of the energy balance meter installed in the secondary substation.

It is possible draw the Load profile of each LV line feed by the Transformer, to create any customized group of meters of which the operator wants to draw the Load Curve, to upload and display the Load curve recorded by ALVIN, the portable energy balance meter.

Page 21: STAMI (ST  Advanced  Metering Interface) Web Tool for the advanced  management  of LV  Network Trends in  Power Industry  in the  European Context  VIII

Uso: Aziendale

STAMI: Advanced Metering InterfaceLoad Profile

Transformer Load Profile

Measured Energy Balance Meter

Aggregation of customers’ Load

Profiles Sum of Energy measured by

each Smart Meter

Probable energy fraudBetween 9.00 am to 6.00 pm the difference between the 2 curves is greater

than the expected technical losses: a verification on field is needed

Page 22: STAMI (ST  Advanced  Metering Interface) Web Tool for the advanced  management  of LV  Network Trends in  Power Industry  in the  European Context  VIII

Uso: Aziendale

Metering activitiesRules and Obligations: Italian Timebased Tariff Regulation

Following the introduction of the Telegestore, the Italian Regulator established specific metering rules depending on the characteristic of the customer:

For HV, MV and LV customers with power installed >55 kW it is mandatory a meter reading each hour.

For LV customers with power installed <55 kW the reading is done per consumption timeslots, F1, F2, F3, compliant with the timebased tariff regulation.

Peak Mid peak Off peak

F3

F3

Mon-Fri

Sat

Sun

00:00

F2 F107:00 08:00 19:00 23:00 24:00

F2

F3 F2 F3

F3

00:00 07:00 23:00 24:00

00:00 24:00