UL Listed, FM Approved Fire Pump Sets

– Horizontal Split Case Pumps

• Flows from 200-5000 US GPM

– Vertical Turbine

• Flows to 5000 US GPM

– In-Line Pumps

• Flows to 750 US GPM

– End Suction

• Flows to 1500 US GPM

– Residential 13D

• Flows to 70 US GPM

All rights reserved by SPP Pumps Ltd All rights reserved by SPP Pumps Ltd

What’s new and coming up…

Grooved end jockey pumps – Already standard

Grooved increasers standard with NBG packs

– New standard

– Class 250# flanges

Grooved fire pumps – Spring 2013

All rights reserved by SPP Pumps Ltd All rights reserved by SPP Pumps Ltd

Types of Fire Pumps

Split Case Fire Pumps

Inline Fire Pumps

Vertical Turbine Fire Pumps

End Suction Fire Pumps

Residential 13D Fire pumps

All rights reserved by SPP Pumps Ltd All rights reserved by SPP Pumps Ltd

Everything you need to

know about fire pumps….

All rights reserved by SPP Pumps Ltd All rights reserved by SPP Pumps Ltd

Types of Fire Pumps

All rights reserved by SPP Pumps Ltd All rights reserved by SPP Pumps Ltd

HORIZONTAL SPLIT CASE ELECTRIC

All rights reserved by SPP Pumps Ltd All rights reserved by SPP Pumps Ltd

HORIZONTAL SPLIT CASE DIESEL

All rights reserved by SPP Pumps Ltd All rights reserved by SPP Pumps Ltd

Split Case Fire Pump Models

• Ease of Installation and Maintenance

• Longevity and Durability

• Serviceability

• Reliability

• Typical applications

• Warehouse

• Hospital

• Manufacturing plant

• University or large school

• Office High Rise

All rights reserved by SPP Pumps Ltd All rights reserved by SPP Pumps Ltd

VERTICAL INLINE (ELECTRIC ONLY)

All rights reserved by SPP Pumps Ltd All rights reserved by SPP Pumps Ltd

Vertical In-Line

Requires less space than split case pump of the same capacity

Typically Less expensive

Motor can be serviced without disconnecting suction & discharge flanges from piping

Typical applications

Small schools

Churches

Parking garages

All rights reserved by SPP Pumps Ltd All rights reserved by SPP Pumps Ltd

END SUCTION ELECTRIC

All rights reserved by SPP Pumps Ltd All rights reserved by SPP Pumps Ltd

END SUCTION DIESEL

All rights reserved by SPP Pumps Ltd All rights reserved by SPP Pumps Ltd

VERTICAL TURBINE ELECTRIC

All rights reserved by SPP Pumps Ltd All rights reserved by SPP Pumps Ltd

VERTICAL TURBINE DIESEL

All rights reserved by SPP Pumps Ltd All rights reserved by SPP Pumps Ltd

Vertical Turbine

Fire Pumps

All rights reserved by SPP Pumps Ltd All rights reserved by SPP Pumps Ltd

Vertical Turbine Design Features

No priming

Adaptability to water level

Adaptability to various driver combinations

Compact “footprint”

No alignment necessary

Minimal maintenance

All rights reserved by SPP Pumps Ltd All rights reserved by SPP Pumps Ltd

Vertical Turbine Applications

Vertical Turbines

Applications where city water is not available

Ponds and lakes to utilize water supply

Only pump approved for suction lift conditions

All rights reserved by SPP Pumps Ltd All rights reserved by SPP Pumps Ltd

90% rule…

90% of what drives a pump quote is?

Flow

Pressure

All rights reserved by SPP Pumps Ltd All rights reserved by SPP Pumps Ltd

Electric or Diesel?

Electric sets are typically used where there is a reliable source of power

What to ask.. – What voltage?

• 208? 230? 460?

– Transfer Switch? • Transfer switch is used when the source of power may not be reliable and/or

precaution.

– Transfer switch for 2nd utility – Starting method?

• Full voltage?

– across the line • Reduced Voltage?

– Part winding

– Primary reactor

– Wye Delta Open

– Wye Delta closed

– Soft Start

– Auto Transformer

That’s all you need to know……. See rapid

All rights reserved by SPP Pumps Ltd All rights reserved by SPP Pumps Ltd

Typical Brands of Fire Pump Controllers

– Firetrol

– Master

– Metron

– Cutler Hammer

– Joslyn Clarke

– Tornatech

All rights reserved by SPP Pumps Ltd All rights reserved by SPP Pumps Ltd

Electric motors

Electric motors are used to drive

– Horizontal split case

– End suction

– Vertical inline

– Vertical turbine

Motors are selected based on

– Voltage

– HP required by the pump

– Frame size

– Configuration of pump (i.e. vertical or horizontal)

All rights reserved by SPP Pumps Ltd All rights reserved by SPP Pumps Ltd

Typical Brands of Electric Motors

– WEG Motors

– US Electric Motors

– Marathon

– GE

All rights reserved by SPP Pumps Ltd All rights reserved by SPP Pumps Ltd

Why Diesel?

Diesel units are used primarily where there is not a reliable source of power or by preference

Typical Engine Manufacturers – Clarke engines (John Deere)

– Cummins

– Caterpiller

Diesel units may drive – Horizontal split case

– Vertical turbine

– End suction

Engines are selected based on – HP of pump requirement

– RPM

– EPA emissions standards as stated on presentation below

All rights reserved by SPP Pumps Ltd All rights reserved by SPP Pumps Ltd

Diesel controllers

Diesel engine fire pumps are especially nice because of

how reliable they can be and by the inexpensive control

panel.

There are only a few options tend to be required on diesel

control panels. The most distinct difference is voltage of

the battery used to back up the engine

– 12 volt DC?

– 24 volt DC?

All rights reserved by SPP Pumps Ltd All rights reserved by SPP Pumps Ltd

What is a jockey pump?

A jockey pump is a pressure maintenance pump set so that in the event of slight fluctuations in sprinkler system pressure, the fire pump will not need to turn on.

Typically set 10 psi over the fire pump

Jockey pumps are replaced frequently and can be purchased from you….

What to ask? In order to sell a jockey pump, you will need to know. If the customer is replacing a jockey pump, you will at least need to know the following

– Boost pressure (can be found by adding at least 10 psi to the fire pump pressure setting

– HP (should be on the motor nameplate or jockey pump controller)

– Voltage (also on motor nameplate or jockey pump controller)

All rights reserved by SPP Pumps Ltd All rights reserved by SPP Pumps Ltd

Jockey Pumps

Regenerative Turbine Pumps

Vertical Multi-stage

All rights reserved by SPP Pumps Ltd All rights reserved by SPP Pumps Ltd

Jockey pump controller

Jockey pump controllers

very small and meant to

supply power exclusively to

the jockey pump

All rights reserved by SPP Pumps Ltd All rights reserved by SPP Pumps Ltd

Fire pump accessories and NFPA 20

NFPA 20 suggests minimum pipe and accessory sizes

based on flow. In the chart below, you can see how based

on the flow, you can select what size flow meter you might

need, what size suction and discharge pipe is needed and

what size test header etc… Thought you do not need to

memorize this chart, it is a helpful tool….

All rights reserved by SPP Pumps Ltd All rights reserved by SPP Pumps Ltd

Fire Pump Standards

NFPA-20 Minimum Pipe Sizes For Fire Systems

Based on NFPA-20, 1996 Edition

Pump Rating in Suction Discharge Relief Relief Valve Meter Number and Size of Hose Hose Header GPM In. In. Valve In. Discharge In. Device In. Valves In. Supply In.

25 1 1 3/4 1 1-1/4 (1) 1-1/2 1

50 1-1/2 1-1/4 1-1/4 1-1/2 2 (1) 1-1/2 1-1/2

100 2 2 1-1/2 2 2-1/2 (1) 2-1/2 2-1/2

150 2-1/2 2-1/2 2 2-1/2 3 (1) 2-1/2 2-1/2

200 3 3 2 2-1/2 3 (1) 2-1/2 2-1/2

250 3-1/2 3 2 2-1/2 3-1/2 (1) 2-1/2 3

300 4 4 2-1/2 3-1/2 3-1/2 (1) 2-1/2 3

400 4 4 3 5 4 (2) 2-1/2 4

450 5 5 3 5 4 (2) 2-1/2 4

500 5 5 3 5 5 (2) 2-1/2 4

750 6 6 4 6 5 (3) 2-1/2 6

1000 8 6 4 8 6 (4) 2-1/2 6

1250 8 8 6 8 6 (6) 2-1/2 8

1500 8 8 6 8 8 (6) 2-1/2 8

2000 10 10 6 10 8 (6) 2-1/2 8

2500 10 10 6 10 8 (8) 2-1/2 10

3000 12 12 8 12 8 (12) 2-1/2 10

3500 12 12 8 12 10 (12) 2-1/2 12

4000 14 12 8 14 10 (16) 2-1/2 12

All rights reserved by SPP Pumps Ltd All rights reserved by SPP Pumps Ltd

Fire Pump System Components

Electric Fire Pumps

• Pump, base, coupling & guard

• Electric motor

• Controller - motor

• Suction and discharge gauges

• Automatic air release valve

• Casing relief valve

All rights reserved by SPP Pumps Ltd All rights reserved by SPP Pumps Ltd

Fire Pump System Components

Diesel Fire Pumps

• Pump, base, coupling & guard

• Diesel engine & fuel tank

• Controller - engine

• Suction and discharge gauges

• Automatic air release valve

• Batteries, racks & cables

• Cooling loop

• Commercial grade muffler, flexible exhaust connector & fittings

All rights reserved by SPP Pumps Ltd All rights reserved by SPP Pumps Ltd

Accessories for Fire Pump

ClaVal 55L Casing relief Valve

ClaVal 2050B-4KG Main Relief

Valve

ClaVal 90G-21 Pressure

Reducing Valve

All rights reserved by SPP Pumps Ltd All rights reserved by SPP Pumps Ltd

Additional Accessories for fire pump

Suction side eccentric reducer

Discharge side concentric increaser

Test Header

Hose valves caps and chains

All rights reserved by SPP Pumps Ltd All rights reserved by SPP Pumps Ltd

Residential 13D

The Resistream comes in 2 styles both the open unit with

corrosion resistant base for mounting as well as the fully

enclosed unit for simple and complete installation.

Both units are available in either 115 or 220 volt single phase

power depending on horsepower

All rights reserved by SPP Pumps Ltd All rights reserved by SPP Pumps Ltd

All rights reserved by SPP Pumps Ltd All rights reserved by SPP Pumps Ltd

Suction Piping

All rights reserved by SPP Pumps Ltd All rights reserved by SPP Pumps Ltd

Pump Rotation

All rights reserved by SPP Pumps Ltd All rights reserved by SPP Pumps Ltd

How well do you know Fire Pumps?

Fill in the blanks

The first thing to ask when looking for a fire pump quote is the

required ________________ and __________________

What are the 4 main types of fire pumps?

– Horizontal ___________ __________

– Vertical _______

– ___________ Turbine

– End ___________

Is the pump set driven by ____________ motor or

_________________ Engine

Do you need a __________ __________ (hint adds $13,000)

What is the site _____________? (hint 208/230/460)

All rights reserved by SPP Pumps Ltd All rights reserved by SPP Pumps Ltd

I need a 1000 gpm at 90 psi fire pump, what size jockey do I need?

What are the 3 points on a NFPA 20 pump curve? – ______________ (no flow)

– _______________ %

– _______________ %

You have a 500 gpm fire pump, what is the flow at 100%? – ______________________