Specifying Fire Resistive Coatings
description
Transcript of Specifying Fire Resistive Coatings
![Page 1: Specifying Fire Resistive Coatings](https://reader036.fdocuments.in/reader036/viewer/2022062301/56815c33550346895dca1778/html5/thumbnails/1.jpg)
Specifying Fire Resistive CoatingsPresented by:
Jayson L. Helsel, P.E.KTA-Tator, Inc.
1
![Page 2: Specifying Fire Resistive Coatings](https://reader036.fdocuments.in/reader036/viewer/2022062301/56815c33550346895dca1778/html5/thumbnails/2.jpg)
Learning ObjectivesComprehension of the webinar will enable the participant to:
•Describe how intumescent coatings protect underlying steel from heat exposure
•List two fire rating classification tests that are used to qualify intumescent coatings for use in building construction
•Identify two primary resin types that are used to formulate intumescent coatings
•Explain how steel size and structure design affect specified thickness and number of coats
![Page 3: Specifying Fire Resistive Coatings](https://reader036.fdocuments.in/reader036/viewer/2022062301/56815c33550346895dca1778/html5/thumbnails/3.jpg)
Fire Resistive Coatings
• Sprayed Fire Resistive Materials (SFRM) are broad group of materials including:– Cementitious and gypsum based
materials– Intumescent coatings
(Note: There is a separate category for “Fire Retardent” coatings, which are not reviewed here)
![Page 4: Specifying Fire Resistive Coatings](https://reader036.fdocuments.in/reader036/viewer/2022062301/56815c33550346895dca1778/html5/thumbnails/4.jpg)
Fire Resistive Coatings
• Intumescent Coatings:– Are categorized as SFRMs– Similar to conventional coatings – Have unique fire resistant properties
![Page 5: Specifying Fire Resistive Coatings](https://reader036.fdocuments.in/reader036/viewer/2022062301/56815c33550346895dca1778/html5/thumbnails/5.jpg)
Intumescent Coatings
• How they function: – Intumescent coatings char and swell
when exposed to fire/heat– The charred layer acts to insulate the
steel from fire
![Page 6: Specifying Fire Resistive Coatings](https://reader036.fdocuments.in/reader036/viewer/2022062301/56815c33550346895dca1778/html5/thumbnails/6.jpg)
Intumescent Coatings
• Performance ratings– Coatings rated by how long steel is
protected at specified thickness– Ratings from 1 to 3 hours (at 30
minute intervals– Specific to shape/size of steel,
e.g. W10 x 49 column
![Page 7: Specifying Fire Resistive Coatings](https://reader036.fdocuments.in/reader036/viewer/2022062301/56815c33550346895dca1778/html5/thumbnails/7.jpg)
Fire Resistance Classifications
• Underwriters Laboratories (UL) is recognized authority that evaluates and approves intumescent coatings for a certain classification and fire rating
• Certifications can be verified online at www.ul.com
![Page 8: Specifying Fire Resistive Coatings](https://reader036.fdocuments.in/reader036/viewer/2022062301/56815c33550346895dca1778/html5/thumbnails/8.jpg)
![Page 9: Specifying Fire Resistive Coatings](https://reader036.fdocuments.in/reader036/viewer/2022062301/56815c33550346895dca1778/html5/thumbnails/9.jpg)
![Page 10: Specifying Fire Resistive Coatings](https://reader036.fdocuments.in/reader036/viewer/2022062301/56815c33550346895dca1778/html5/thumbnails/10.jpg)
Fire Resistance Classifications
• Certifications are “design” specific by coating manufacturer
• Numbering system defines an alphanumeric design number
![Page 11: Specifying Fire Resistive Coatings](https://reader036.fdocuments.in/reader036/viewer/2022062301/56815c33550346895dca1778/html5/thumbnails/11.jpg)
![Page 12: Specifying Fire Resistive Coatings](https://reader036.fdocuments.in/reader036/viewer/2022062301/56815c33550346895dca1778/html5/thumbnails/12.jpg)
![Page 13: Specifying Fire Resistive Coatings](https://reader036.fdocuments.in/reader036/viewer/2022062301/56815c33550346895dca1778/html5/thumbnails/13.jpg)
Fire Resistance Classifications
• Beams– W, M or S shaped steel sections (AISC)– Minimum beam size for fire resistance is
expressed as W/D ratio• W = weight of beam per lineal foot• D = perimeter of protection material
– Beams of same configuration with greater W/D ratio may be used in design
![Page 14: Specifying Fire Resistive Coatings](https://reader036.fdocuments.in/reader036/viewer/2022062301/56815c33550346895dca1778/html5/thumbnails/14.jpg)
Fire Resistance Classifications
• Columns– Minimum column size and configuration
specified in X and Y series designs– Same hourly rating applies when section
with equal or greater W/D ratio is substituted for same configuration
![Page 15: Specifying Fire Resistive Coatings](https://reader036.fdocuments.in/reader036/viewer/2022062301/56815c33550346895dca1778/html5/thumbnails/15.jpg)
Fire Resistance Classifications
• Beams and Columns– Required coating thickness increases as
weight of steel decreases• Lighter steel heats up more rapidly and
requires more protection
![Page 16: Specifying Fire Resistive Coatings](https://reader036.fdocuments.in/reader036/viewer/2022062301/56815c33550346895dca1778/html5/thumbnails/16.jpg)
Fire Resistance Classifications
• ANSI/UL 263– Used for resistance to cellulosic fire (e.g.
combustion of wood or building materials)
– Slower rise in temperature• 1000 F at 5 min.; 1550 F at 30 min.; 1700 F
at 60 min.; 1925 F at 180 min.; 2000 F at 240 min.
– Interior and exterior exposures
![Page 17: Specifying Fire Resistive Coatings](https://reader036.fdocuments.in/reader036/viewer/2022062301/56815c33550346895dca1778/html5/thumbnails/17.jpg)
Fire Resistance Classifications
• ANSI/UL 263 Classified Coatings– Typical use for structural steel in
commercial structures
![Page 18: Specifying Fire Resistive Coatings](https://reader036.fdocuments.in/reader036/viewer/2022062301/56815c33550346895dca1778/html5/thumbnails/18.jpg)
Fire Resistance Classifications
• ANSI/UL 1709– Used for resistance to a hydrocarbon fire– Rapid rise in temperature
• 2000 F at 5 minutes – Interior and exterior exposures
• Environmental tests include, accelerated aging, high humidity, salt spray, thermal cycling for exterior exposure
![Page 19: Specifying Fire Resistive Coatings](https://reader036.fdocuments.in/reader036/viewer/2022062301/56815c33550346895dca1778/html5/thumbnails/19.jpg)
Fire Resistance Classifications
• ANSI/UL 1709 Classified Coatings– Typical use for steel structures at
petrochemical facilities, e.g.• Chemical plant• Refineries• Offshore oil platforms
![Page 20: Specifying Fire Resistive Coatings](https://reader036.fdocuments.in/reader036/viewer/2022062301/56815c33550346895dca1778/html5/thumbnails/20.jpg)
![Page 21: Specifying Fire Resistive Coatings](https://reader036.fdocuments.in/reader036/viewer/2022062301/56815c33550346895dca1778/html5/thumbnails/21.jpg)
![Page 22: Specifying Fire Resistive Coatings](https://reader036.fdocuments.in/reader036/viewer/2022062301/56815c33550346895dca1778/html5/thumbnails/22.jpg)
![Page 23: Specifying Fire Resistive Coatings](https://reader036.fdocuments.in/reader036/viewer/2022062301/56815c33550346895dca1778/html5/thumbnails/23.jpg)
![Page 24: Specifying Fire Resistive Coatings](https://reader036.fdocuments.in/reader036/viewer/2022062301/56815c33550346895dca1778/html5/thumbnails/24.jpg)
![Page 25: Specifying Fire Resistive Coatings](https://reader036.fdocuments.in/reader036/viewer/2022062301/56815c33550346895dca1778/html5/thumbnails/25.jpg)
![Page 26: Specifying Fire Resistive Coatings](https://reader036.fdocuments.in/reader036/viewer/2022062301/56815c33550346895dca1778/html5/thumbnails/26.jpg)
Other Approvals• Intumescent coatings may also need
approval by city building codes• Coating manufacturers should
provide approvals as applicable
![Page 27: Specifying Fire Resistive Coatings](https://reader036.fdocuments.in/reader036/viewer/2022062301/56815c33550346895dca1778/html5/thumbnails/27.jpg)
![Page 28: Specifying Fire Resistive Coatings](https://reader036.fdocuments.in/reader036/viewer/2022062301/56815c33550346895dca1778/html5/thumbnails/28.jpg)
Generic Coating Types• Intumescent coatings are generally
the following generic resin types:– Acrylic/vinyl– Epoxy
• Intumescents are also generally categorized as “thin-film” or “thick-film” coatings
![Page 29: Specifying Fire Resistive Coatings](https://reader036.fdocuments.in/reader036/viewer/2022062301/56815c33550346895dca1778/html5/thumbnails/29.jpg)
Generic Coating Types• Acrylic/vinyl
• Thin-film coating• Solvent or water-based• Single component • Typically rated under UL 263
![Page 30: Specifying Fire Resistive Coatings](https://reader036.fdocuments.in/reader036/viewer/2022062301/56815c33550346895dca1778/html5/thumbnails/30.jpg)
Generic Coating Types• Acrylic/vinyl
• Applied in several coats• Time-frame for a complete application may
span several days• Additional time may be needed before
application of any required exterior finish coat.
![Page 31: Specifying Fire Resistive Coatings](https://reader036.fdocuments.in/reader036/viewer/2022062301/56815c33550346895dca1778/html5/thumbnails/31.jpg)
Generic Coating Types• Epoxy
• Thick-film coating• Applied by plural component spray
equipment in one or two coats• Rapid cure• Typically rated under UL 1709
![Page 32: Specifying Fire Resistive Coatings](https://reader036.fdocuments.in/reader036/viewer/2022062301/56815c33550346895dca1778/html5/thumbnails/32.jpg)
Generic Coating Types• Epoxy
• May require mesh reinforcement (e.g. metal, fiberglass, carbon)
• Typically requires the use of applicators licensed or approved by the coating manufacturer
![Page 33: Specifying Fire Resistive Coatings](https://reader036.fdocuments.in/reader036/viewer/2022062301/56815c33550346895dca1778/html5/thumbnails/33.jpg)
Generic Coating ComparisonCoating
TypeRequired Thickness
(mils)
Number of Coats
Recoat Time (between
coats) @50F
Time to Finish Coat
@50FSolvent based acrylic
130 5 24 hours 25 days
Solvent based vinyl
375 4 4 hours 20+ days
Water based acrylic
180 6 8 hours 10+ days
Epoxy 180 1 n/a 24 hours
Epoxy w/mesh
340 1-2 n/a 48 hours
33
![Page 34: Specifying Fire Resistive Coatings](https://reader036.fdocuments.in/reader036/viewer/2022062301/56815c33550346895dca1778/html5/thumbnails/34.jpg)
Testing for Coating Cure• Intumescents may require testing for
proper cure• Typical test is Durometer Hardness
(Shore D)– Resistance of coating film to indentation
by Durometer instrument– ASTM D2240, “Standard Test Method for
Rubber Property-Durometer Hardness”
![Page 35: Specifying Fire Resistive Coatings](https://reader036.fdocuments.in/reader036/viewer/2022062301/56815c33550346895dca1778/html5/thumbnails/35.jpg)
Testing for Coating Cure
![Page 36: Specifying Fire Resistive Coatings](https://reader036.fdocuments.in/reader036/viewer/2022062301/56815c33550346895dca1778/html5/thumbnails/36.jpg)
Coating Appearance• Intumescents generally have a rough
or orange peel appearance• Methods to improve include:
• Back rolling following spray application• Sanding (not recommended)• Finish coat application (may be required)
• Test sections recommended
![Page 37: Specifying Fire Resistive Coatings](https://reader036.fdocuments.in/reader036/viewer/2022062301/56815c33550346895dca1778/html5/thumbnails/37.jpg)
![Page 38: Specifying Fire Resistive Coatings](https://reader036.fdocuments.in/reader036/viewer/2022062301/56815c33550346895dca1778/html5/thumbnails/38.jpg)
![Page 39: Specifying Fire Resistive Coatings](https://reader036.fdocuments.in/reader036/viewer/2022062301/56815c33550346895dca1778/html5/thumbnails/39.jpg)
![Page 40: Specifying Fire Resistive Coatings](https://reader036.fdocuments.in/reader036/viewer/2022062301/56815c33550346895dca1778/html5/thumbnails/40.jpg)
Coating Systems• Intumescent design approvals
typically include a primer and/or finish coat– When included in design primer/finish
must be applied to meet fire rating• Primer/finish must be endorsed by
intumescent coating manufacturer– Preference always for same
manufacturer
![Page 41: Specifying Fire Resistive Coatings](https://reader036.fdocuments.in/reader036/viewer/2022062301/56815c33550346895dca1778/html5/thumbnails/41.jpg)
Use of Primers• Intumescent coating manufacturer
may have approved list of primers– Types include alkyd, acrylic, epoxy and
zinc-rich– Application thickness important
![Page 42: Specifying Fire Resistive Coatings](https://reader036.fdocuments.in/reader036/viewer/2022062301/56815c33550346895dca1778/html5/thumbnails/42.jpg)
Primers• Function of primer
– Provides adhesion to substrate – Provides suitable surface for
intumescent– Provides additional barrier protection
• Can also provide inhibitive or sacrificial protection
![Page 43: Specifying Fire Resistive Coatings](https://reader036.fdocuments.in/reader036/viewer/2022062301/56815c33550346895dca1778/html5/thumbnails/43.jpg)
Use of Finish Coat• May be required in design approval
for exterior exposure• Intumescent coating manufacturer
must endorse finish material– Types include 100% acrylic and aliphatic
urethane coatings• May affect/improve appearance
![Page 44: Specifying Fire Resistive Coatings](https://reader036.fdocuments.in/reader036/viewer/2022062301/56815c33550346895dca1778/html5/thumbnails/44.jpg)
Finish Coats• Function of topcoat
– Color and gloss– Abrasion resistance– Chemical resistance– Washability– Resistance to the environment
![Page 45: Specifying Fire Resistive Coatings](https://reader036.fdocuments.in/reader036/viewer/2022062301/56815c33550346895dca1778/html5/thumbnails/45.jpg)
Finish Coats• Acrylics
– Advantages• Single component• Ease of application• Color & gloss retention• Flexibility• Low VOC content for waterbased
![Page 46: Specifying Fire Resistive Coatings](https://reader036.fdocuments.in/reader036/viewer/2022062301/56815c33550346895dca1778/html5/thumbnails/46.jpg)
Finish Coats• Acrylics
– Limitations• Limited alkali and solvent resistance• Moderate abrasion resistance• Application temperature >50ºF for
waterbased
![Page 47: Specifying Fire Resistive Coatings](https://reader036.fdocuments.in/reader036/viewer/2022062301/56815c33550346895dca1778/html5/thumbnails/47.jpg)
Finish Coats• Urethanes
– Advantages• Color & gloss retention (aliphatic)• Adhesion• Acid, alkali resistant• Chemical resistant• Impact/abrasion resistant
![Page 48: Specifying Fire Resistive Coatings](https://reader036.fdocuments.in/reader036/viewer/2022062301/56815c33550346895dca1778/html5/thumbnails/48.jpg)
Finish Coats• Urethanes
– Limitations• Multi-component• Short recoat intervals• Limited pot life• Moisture sensitive during cure• Difficult to recoat
![Page 49: Specifying Fire Resistive Coatings](https://reader036.fdocuments.in/reader036/viewer/2022062301/56815c33550346895dca1778/html5/thumbnails/49.jpg)
Fire Resistive Coating Inspection
• Technical Manual 12-B– Published by Association of the Wall and
Ceiling Industries (AWCI International)– Individual measurement = average of 3
gauge readings (similar to SSPC-PA 2)– Testing frequency one bay per floor or
one test per 10,000 square feet (further defines required shapes)
![Page 50: Specifying Fire Resistive Coatings](https://reader036.fdocuments.in/reader036/viewer/2022062301/56815c33550346895dca1778/html5/thumbnails/50.jpg)
![Page 51: Specifying Fire Resistive Coatings](https://reader036.fdocuments.in/reader036/viewer/2022062301/56815c33550346895dca1778/html5/thumbnails/51.jpg)
Fire Resistive Coating Inspection• Technical Manual 12-B
– Scope– General Information– Substrate Conditions– Site Conditions– Inspection Procedures– Method of Tests– Conditions of Finished Application– Patching
![Page 52: Specifying Fire Resistive Coatings](https://reader036.fdocuments.in/reader036/viewer/2022062301/56815c33550346895dca1778/html5/thumbnails/52.jpg)
Fire Resistive Coating Inspection
• Intumescent (and Mastic) Coatings– Coating thickness specification in a
design is minimum average thickness measured in accordance with Technical Manual 12-B• Average thickness should not exceed
maximum thickness published (if listed) in individual designs
• No individual measurement <80% of specified design thickness
![Page 53: Specifying Fire Resistive Coatings](https://reader036.fdocuments.in/reader036/viewer/2022062301/56815c33550346895dca1778/html5/thumbnails/53.jpg)
![Page 54: Specifying Fire Resistive Coatings](https://reader036.fdocuments.in/reader036/viewer/2022062301/56815c33550346895dca1778/html5/thumbnails/54.jpg)
Summary of Key Points• When specifying intumescents
consider:– Required UL approval– City building code approval– Include required primer and finish coats– Applicator certification if needed (e.g.
plural component materials)– Include test sections to evaluate
appearance
![Page 55: Specifying Fire Resistive Coatings](https://reader036.fdocuments.in/reader036/viewer/2022062301/56815c33550346895dca1778/html5/thumbnails/55.jpg)
Specifying Fire Resistive Coatings