http://www.delta.com.tw/industrialautomation/ 5011688601 2CQ1 - 201003-15 C2000 Series Installation Instruction Classical Field Oriented Control AC Motor Drive Please read this instruction sheet thoroughly before installation and keep this instruction sheet and CD shipped with the product at hand and distribute to all users for reference. To ensure the safety of operators and equipment, only qualified personnel familiar with AC motor drive are allowed to do installation, trial run and parameters settings. Always read this instruction thoroughly before using the AC Motor Drive, especially the WARNING, DANGER and CAUTION notes. If you have any question, please contact your dealer. PLEASE READ PRIOR TO INSTALLATION FOR SAFETY. DANGER The ground terminal of the AC motor drive must be grounded correctly. The grounding method must comply with the laws of the country where the AC motor drive is to be installed. After the power has been turned off, the AC motor drive may still contain the high voltage capacitors before POWER indicator of the AC motor drive is OFF. To prevent personal injury, please DO NOT touch the internal circuit and components until the voltage between +1 and – is less than 25VDC. Please wait at least 5 minutes for 22kW models to discharge to safe voltage level. (10 minutes for 30kW models). The CMOS IC on the internal circuit board of the AC motor drive is sensitive to static electricity. Please DO NOT touch the circuit board by your bare hands before taking anti-static measures. Never reassemble the internal components or circuit. If it needs to change wiring, please turn off the power of the AC motor drive before wiring. The capacitors of the internal DC needs time to discharge, if wiring before the voltage is discharged to the safe level, it may cause short circuit and fire. To ensure the personal safety, please wire with the safety voltage level. DO NOT install the AC motor drive in a place subjected to high temperature, direct sunlight and inflammables. Never apply the power into the output terminals U/T1, V/T2, W/T3 of the AC motor drive. Please stop operation immediately when fault occurs during operation of the AC motor drive and motor and refer to fault code for resetting the drive. DO NOT use Hi-pot test for internal components. The semi-conductor used in the AC motor drive is easily damaged by high-pressure. CA UT I O N When the motor cable between the AC motor drive and motor is too long, the layer insulation of the motor may be damaged. Please use a frequency inverter duty motor or add a reactor to prevent motor damage. The rated voltage for the AC motor drive must be 240V (480V for 460V models) and the mains supply current capacity must be 5000A RMS (10000A RMS for the 40hp (30kW) models). The AC motor drive must be placed in a clean, good ventilation and dry location free from corrosive gases or liquids. The AC motor drive must be stored within an ambient temperature range of –25~+75and relative humidity range of 0% to 90% without condensation. DO NOT place on the ground directly. It should be stored properly. Moreover, if the surrounding environment is humid, you should put exsiccator in the package. To prevent condensation and frost, please DO NOT store in an area with rapid changes in temperature. DO NOT install the AC motor drive in a place subjected to direct sunlight or vibration. If the AC motor drive is stored for more than 3 months, the temperature should not be higher than 30 °C. Storage longer than one year is not recommended, it could result in the degradation of the electrolytic capacitors. Please turn on the power after the front cover is installed. DO NOT operate with the humid hands. Make sure that the AC motor drive is unloaded. After the fault occurs, please wait 5 seconds after a fault has been cleared before pressing RESET key. NOTE To prevent personal injury, please make sure that the case and wiring are installed by this instruction. The figures in this instruction are only for reference, it may be slightly different from that one you have but it won’t affect your customers’ right. The content of this instruction sheet may be revised without prior notice. Please consult our distributors or download the most updated version at http://www.delta.com.tw/industrialautomation Installation Procedures 1. Make sure that the part number printed on the nameplate of the AC motor drive corresponds with the part number you ordered. 2. Please inspect the unit to assure it was not damaged during shipment after unpacking. 3. Make sure that the wire gauge is within the voltage range as indicated on the nameplate. 4. Please install the AC motor drive according to this instruction. 5. Please install accessories as requirement. 6. Connect to the motor and make sure that the connection and voltage are correct. 7. Please make sure that the power is OFF before wiring. 8. Setting parameters (refer to parameters manual for details). Minimum Mounting Clearances (Appearances in the following figures are only for reference) Figure 1. Single drive: independent installation (frame A-E) Figure 2. Multiple drives: independent installation (frame A-C) Figure 3. Multiple drives: independent installation (frame D-E) Figure 4. Multiple drives: side-by-side installation (frame A-C) & : airflow direction The mounting clearances shown in the left figure 1 to 4 are NOT for installing the drive in a confined space, such as electric box. Except the same minimum mounting clearances, it needs to have the ventilation equipment or air conditioner to keep the surrounding temperature lower than the operation temperature when installing in a confined space. (refer to the next page for details) Frame A-C Unit: mm [inch] Distance A: 60.0 [2.36] Distance B: 30.0 [1.18] Distance C: 10.0 [0.39] Frame D-E Unit: mm [inch] Distance A: 100.0 [3.94] Distance B: 50.0 [1.97] Figure 1~3 IP20/NEMA1/UL TYPE 1 [-10~+40 o C (14~104 o F)] without derating. Up to 60 o C (140 o F) with derating. Figure 4 IP20/UL Open-Type (Must remove Top cover—refer to figure 5) [-10~+40 o C(14~104 o F)] without derating. Up to 60 o C (140 o F) with derating. NOTE: For more installation instruction, please refer to simplified manual. Figure 5. How to remove top cover Frame A-B Frame C Install in a confined space (such as electric box) In the following table, it shows the required air volume and heat dissipation for installing single drive in a confined space. When installing the multiple drives, the required air volume should be the required air volume for single drive X the number of the drives. External: the required air volume for heat sink, Internal: the required air volume for internal drive Flow Rate (CFM) Flow Rate (CFM) Models VFD- External Internal Total Models VFD- External Internal Total 007C23A - - - 022C43A/E 13.6 - 13.6 015C23A 13.6 - 13.6 037C43A/E 10.2 - 10.2 022C23A 13.6 - 13.6 040C43A/E 10.2 - 10.2 037C23A 10.2 - 10.2 055C43A/E 40.0 - 54.5 055C23A 40.0 14.5 54.5 075C43A/E 65.8 14.5 80.3 075C23A 65.8 14.5 80.3 110C43A/E 58.2 14.5 72.6 110C23A 58.2 14.5 72.6 150C43A/E 99.0 14.5 119.8 150C23A 166.3 12.2 178.5 185C43A/E 99.0 20.8 119.8 185C23A 166.3 12.2 178.5 220C43A/E 126.2 20.8 147.0 220C23A 145.6 12.2 157.8 300C43A/E 179.2 20.8 209.0 300C23A 179.2 29.8 209.0 370C43A 179.2 29.8 209.0 370C23A 179.2 29.8 209.0 450C43A 179.2 29.8 209.0 450C23A 228.2 73.1 301.3 550C43A 186.3 29.8 216.1 550C23A 228.2 73.1 301.3 750C43A 256.9 29.8 330.0 750C23A 245.7 73.1 318.8 900C43A/E 223.1 73.1 296.2 007C43A/E - - - 1100C43A/E 13.6 73.1 13.6 Specifications for Wiring Terminals (refer to wiring diagram) control terminals Wire gauge: 26-16AWG(0.1281-1.318mm 2 ) Torque(±10%): 5kgf-cm[4.31 lbf-in.] (0.4905Nm) main circuit terminals Models VFD- Max. Wire Gauge Min. Wire Gauge Torque (±10%) Note 007C23A/E 14 AWG (2.1mm2) 015C23A/E 12 AWG (3.3mm2) 022C23A/E 10 AWG (5.3mm2) 037C23A 8 AWG (8.4mm2) 037C23E 10 AWG (5.3mm2) 007C43A/E 14 AWG (2.1mm2) 015C43A/E 14 AWG (2.1mm2) 022C43A/E 14 AWG (2.1mm2) 037C43A 10 AWG (5.3mm2) 037C43E 12 AWG (3.3mm2) 040C43A/E 10 AWG (5.3mm2) 055C43A/E 8 AWG (8.4mm2) 10 AWG (5.3mm2) M4 20kg-cm (17.4 lbf-in.) (1.962Nm) - 055C23A/E 8 AWG (8.4mm2) 075C23A/E 6 AWG (13.3mm2) 110C23A/E 4 AWG (21.2mm2) 075C43A 8 AWG (8.4mm2) 075C43E 10 AWG (5.3mm2) 110C43A/E 8 AWG (8.4mm2) 150C43A 6 AWG (13.3mm2) 150C43E 4 AWG (21.2mm2) 8 AWG (8.4mm2) M5 35kg-cm (30.4 lbf-in.) (3.4335Nm) Terminal D+[+2 & +1]Torque 45 Kg-cm [39.0 lbf-in.] (4.4145Nm) (±10%) 150C23A 1 AWG (42.4mm2) 150C23E 2 AWG (33.6mm2) 185C23A 1/0 AWG (53.5mm2) 185C23E 1 AWG (42.4mm2) 220C23A/E 1/0 AWG (53.5mm2) 185C43A 4 AWG (21.2mm2) 185C43E 6 AWG (13.3mm2) 220C43A/E 4 AWG (21.2mm2) 300C43A 2 AWG (33.6mm2) 300C43E 1/0 AWG (53.5mm2) 3 AWG (26.7mm2) M8 80kg-cm (69.4 lbf-in.) (7.848Nm) Terminal D+[+2 & +1]Torque 90 Kg-cm [78.2 lbf-in.] (8.829Nm) (±10%) 300C23A 4/0 AWG (107mm2) 370C23A 250MCM (126mm2) 370C43A 1/0 AWG (53.5mm2) 450C43A 2/0 AWG (67.4mm2) 550C43A 3/0 AWG (85mm2) 750C43A 300MCM (152mm2) 300MCM (152mm2) 300C23E 4/0 AWG (107mm2) 370C23E 4/0 AWG (107mm2) 370C43E 1/0 AWG (53.5mm2) 450C43E 2/0 AWG (67.4mm2) 550C43E 3/0 AWG (85mm2) 750C43E 4/0 AWG (107mm2) 4/0 AWG (107mm2) M8 200kg-cm (173 lbf-in.) (19.62Nm) Please use the specifications of insulated heat shrink tubing that comply with UL (600C, YDPU2). 450C23A 1/0AWG*2 (53.5mm 2 *2) 550C23A 3/0AWG*2 (85mm 2 *2) 750C23A 4/0 AWG *2 (107mm 2 *2) When using the ring terminal, please comply with the following specification. 31MAX. 8 . 2 MI N. 26.5MAX. 70MAX. 16 +0 -4 Specification of grounding wire: 300MCM [152 mm 2 ] 8.2MIN . 65.0MAX. 17.0MAX. 28.0MAX. 900C43A 1/0AWG*2 (53.5mm 2 *2) 1100C43A 300MCM*2 (152mm 2 *2) 3/0AWG*2 (85mm 2 *2) 450C23E 1/0AWG*2 (53.5mm 2 *2) 550C23E 1/0AWG*2 (53.5mm 2 *2) 750C23E 3/0AWG*2 (85mm 2 *2) 900C43E 1/0AWG*2 (53.5mm 2 *2) 1100C43E 4/0 AWG*2 (107mm 2 *2) 2/0AWG*2 (67.4mm 2 *2) Please use the specifications of insulated heat shrink tubing that comply with UL (600C, YDPU2). 900C23A 300MCM*2 (152mm 2 *2) 1320C43A 4/0 AWG*2 (107mm 2 *2) 1600C43A 300MCM*2 (152mm 2 *2) 300MCM*2 (152mm 2 *2) 900C23E 4/0 AWG*2 (107mm 2 *2) 1320C43E 3/0AWG*2 (85mm 2 *2) 1600C43E 4/0 AWG*2 (107mm 2 *2) 4/0 AWG*2 (107mm 2 *2) When using the ring terminal, please comply with the following specification. 31MAX. 8 . 2 MI N. 26.5MAX. 70MAX. 16 +0 -4 2800C43A 4/0 AWG*4(107mm 2 *4) 3150C43A 300MCM*4 (152mm 2 *4) 3550C43A 300MCM*4 (152mm 2 *4) 2800C43E 3/0AWG*4 (85mm 2 *4) 3150C43E 4/0 AWG*4 (107mm 2 *4) 3550C43E 300MCM*4 (152mm 2 *4) 250MCM*4 (127mm 2 *4) When using the ring terminal, please comply with the following specification. Please use the specifications of insulated heat shrink tubing that comply with UL (600C, YDPU2). Main circuit terminals: R/L11, R/L12, S/L21, S/L22, T/L31, T/L32 1850C43A 2/0AWG*4 (67.4mm 2 *4) 2200C43A 3/0AWG*4 (85mm 2 *4) 1850C43E 1/0AWG*4 (53.5mm 2 *4) 2200C43E 300MCM*4 (152mm 2 *4) 2/0AWG*4 (67.4mm 2 *4) M8 200kg-cm (173 lbf-in.) (19.62Nm) When using the ring terminal, please comply with the following specification. 31MAX. 8 .2MIN. 26.5MAX. 70MAX. 16 +0 -4 Please use the specifications of insulated heat shrink tubing that comply with UL (600C, YDPU2). Main circuit terminals: U/T1, V/T2, W/T3, +1/DC+, -/DC- 1850C43A 400MCM*2 (203mm 2 *2) 2200C43A 500MCM*2 (253mm 2 *2) 1850C43E 300MCM*2 (152mm 2 *2) 2200C43E 500MCM*2 (253mm 2 *2) 400MCM*2 (203mm 2 *2) M10 408kg-cm (354 lbf-in.) (40Nm) When using the ring terminal, please comply with the following specification. 31MAX. 8.2 M IN. 26.5MAX. 70MAX. 16 +0 -4 Please use the specifications of insulated heat shrink tubing that comply with UL (600C, YDPU2). NOTE: UL installations must use 600V, 75or 90. Use copper wire only. NOTE: VFD110C23A, VFD2200C43A must use 90wire, if ambient temperature>45℃. NOTE: VFD220C23A, VFD900C23A/E must use 90wire, if ambient temperature>40℃. Environment for Operation, Storage and Transportation DO NOT expose the AC motor drive in the bad environment, such as dust, direct sunlight, corrosive/inflammable gasses, humidity, liquid and vibration environment. The salt in the air must be less than 0.01mg/cm 2 each year. Installation location IEC60364-1/IEC60664-1 Pollution degree 2, Indoor use only UL type1/IP20 -10~+ 40 o C without derating, Up to 60 o C with derating* Operation UL OPEN-TYPE/IP20 -10~+ 50 o C without derating (-10~+ 40°C for side by side removed top cover). Up to 60 o C with derating* Storage/ Transportation -25 o C ~ +70 o C Surrounding Temperature Non-condensation, non-frozen Operation Max. 90% Storage /Transportation Max. 95% Rated Humidity No condense water Operation 86 to 106 kPa Storage 86 to 106 kPa Air Pressure Transportation 70 to 106 kPa IEC721-3-3 Operation Class 3C2, Class 3S2 Storage Class 2C2, Class 2S2 Transportation Class 1C2, Class 1S2 Pollution Level No concentrate Environment Altitude Operation Airflow range is 0-1000m. It will reduce 1% for each increasing 100m during the altitude 1000-3000m. The airflow limit is 2000m at the network area “Corner Grounded”. Storage Package Drop Transportation ISTA procedure 1A(according to weight) IEC60068-2-31 Vibration IEC 60068-2-6 Impact IEC/EN 60068-2-27 Operation Position Max. allowed offset angle ±10 o (for normal installation position) 10 10

Transcript of Specifications for Wiring Terminals (refer to wiring diagram)...

Page 1: Specifications for Wiring Terminals (refer to wiring diagram) …mat.transtechnik.fr/DELTA/documentation/Inverters/VFD-C2000/Quick... · C2000 Series Installation Instruction ...

http://www.delta.com.tw/industrialautomation/ 5011688601 2CQ1-

201003-15

C2000 Series Installation Instruction Classical Field Oriented Control AC Motor Drive

Please read this instruction sheet thoroughly before installation and keep this instruction sheet and CD shipped with the product at hand and distribute to all users for reference.

To ensure the safety of operators and equipment, only qualified personnel familiar with AC motor drive are allowed to do installation, trial run and parameters settings. Always read this instruction thoroughly before using the AC Motor Drive, especially the WARNING, DANGER and CAUTION notes. If you have any question, please contact your dealer.

PLEASE READ PRIOR TO INSTALLATION FOR SAFETY.

DANGER

The ground terminal of the AC motor drive must be grounded correctly. The grounding method must comply with the laws of the country where the AC motor drive is to be installed.

After the power has been turned off, the AC motor drive may still contain the high voltage capacitors before POWER indicator of the AC motor drive is OFF. To prevent personal injury, please DO NOT touch the internal circuit and components until the voltage between +1 and – is less than 25VDC. Please wait at least 5 minutes for ≦22kW models to discharge to safe voltage level. (10 minutes for ≧30kW models).

The CMOS IC on the internal circuit board of the AC motor drive is sensitive to static electricity. Please DO NOT touch the circuit board by your bare hands before taking anti-static measures. Never reassemble the internal components or circuit.

If it needs to change wiring, please turn off the power of the AC motor drive before wiring. The capacitors of the internal DC needs time to discharge, if wiring before the voltage is discharged to the safe level, it may cause short circuit and fire. To ensure the personal safety, please wire with the safety voltage level.

DO NOT install the AC motor drive in a place subjected to high temperature, direct sunlight and inflammables.

Never apply the power into the output terminals U/T1, V/T2, W/T3 of the AC motor drive. Please stop operation immediately when fault occurs during operation of the AC motor drive and motor and refer to fault code for resetting the drive.

DO NOT use Hi-pot test for internal components. The semi-conductor used in the AC motor drive is easily damaged by high-pressure.

CA UTION

When the motor cable between the AC motor drive and motor is too long, the layer insulation of the motor may be damaged. Please use a frequency inverter duty motor or add a reactor to prevent motor damage.

The rated voltage for the AC motor drive must be ≤ 240V (≤ 480V for 460V models) and the mains supply current capacity must be ≤ 5000A RMS (≤10000A RMS for the ≥ 40hp (30kW) models).

The AC motor drive must be placed in a clean, good ventilation and dry location free from corrosive gases or liquids. The AC motor drive must be stored within an ambient temperature range of –25℃~+75℃ and relative humidity range of 0%

to 90% without condensation. DO NOT place on the ground directly. It should be stored properly. Moreover, if the surrounding environment is humid, you

should put exsiccator in the package. To prevent condensation and frost, please DO NOT store in an area with rapid changes in temperature. DO NOT install the AC motor drive in a place subjected to direct sunlight or vibration.

If the AC motor drive is stored for more than 3 months, the temperature should not be higher than 30 °C. Storage longer than one year is not recommended, it could result in the degradation of the electrolytic capacitors.

Please turn on the power after the front cover is installed. DO NOT operate with the humid hands. Make sure that the AC motor drive is unloaded. After the fault occurs, please wait 5 seconds after a fault has been cleared before pressing RESET key.

NOTE To prevent personal injury, please make sure that the case and wiring are installed by this instruction. The figures in this instruction are only for reference, it may be slightly

different from that one you have but it won’t affect your customers’ right.

The content of this instruction sheet may be revised without prior notice. Please consult our distributors or download the most updated version at http://www.delta.com.tw/industrialautomation

Installation Procedures 1. Make sure that the part number printed on the nameplate of the AC motor drive corresponds with the part number you ordered. 2. Please inspect the unit to assure it was not damaged during shipment after unpacking. 3. Make sure that the wire gauge is within the voltage range as indicated on the nameplate. 4. Please install the AC motor drive according to this instruction. 5. Please install accessories as requirement. 6. Connect to the motor and make sure that the connection and voltage are correct. 7. Please make sure that the power is OFF before wiring. 8. Setting parameters (refer to parameters manual for details).

Minimum Mounting Clearances (Appearances in the following figures are only for reference) Figure 1. Single drive: independent installation (frame A-E)

Figure 2. Multiple drives: independent installation (frame A-C)

Figure 3. Multiple drives: independent installation (frame D-E)

Figure 4. Multiple drives: side-by-side installation (frame A-C)

& : airflow direction

The mounting clearances shown in the left figure 1 to 4 are NOT for installing the drive in a confined space, such as electric box. Except the same minimum mounting clearances, it needs to have the ventilation equipment or air conditioner to keep the surrounding temperature lower than the operation temperature when installing in a confined space. (refer to the next page for details) Frame A-C Unit: mm [inch] Distance A: 60.0 [2.36] Distance B: 30.0 [1.18] Distance C: 10.0 [0.39] Frame D-E Unit: mm [inch] Distance A: 100.0 [3.94] Distance B: 50.0 [1.97] Figure 1~3 IP20/NEMA1/UL TYPE 1 [-10~+40 oC (14~104oF)] without derating. Up to 60 oC (140

oF) with derating. Figure 4 IP20/UL Open-Type (Must remove Top cover—refer to figure 5) [-10~+40oC(14~104 oF)] without derating. Up to 60 oC (140

oF) with derating. NOTE: For more installation instruction, please refer to simplified manual.

Figure 5. How to remove top cover Frame A-B

Frame C

Install in a confined space (such as electric box)

In the following table, it shows the required air volume and heat dissipation for installing single drive in a confined space. When installing the multiple drives, the required air volume should be the required air volume for single drive X the number of the drives. External: the required air volume for heat sink, Internal: the required air volume for internal drive

Flow Rate (CFM) Flow Rate (CFM) Models VFD- External Internal Total

Models VFD- External Internal Total

007C23A - - - 022C43A/E 13.6 - 13.6 015C23A 13.6 - 13.6 037C43A/E 10.2 - 10.2 022C23A 13.6 - 13.6 040C43A/E 10.2 - 10.2 037C23A 10.2 - 10.2 055C43A/E 40.0 - 54.5 055C23A 40.0 14.5 54.5 075C43A/E 65.8 14.5 80.3 075C23A 65.8 14.5 80.3 110C43A/E 58.2 14.5 72.6 110C23A 58.2 14.5 72.6 150C43A/E 99.0 14.5 119.8 150C23A 166.3 12.2 178.5 185C43A/E 99.0 20.8 119.8 185C23A 166.3 12.2 178.5 220C43A/E 126.2 20.8 147.0 220C23A 145.6 12.2 157.8 300C43A/E 179.2 20.8 209.0 300C23A 179.2 29.8 209.0 370C43A 179.2 29.8 209.0 370C23A 179.2 29.8 209.0 450C43A 179.2 29.8 209.0 450C23A 228.2 73.1 301.3 550C43A 186.3 29.8 216.1 550C23A 228.2 73.1 301.3 750C43A 256.9 29.8 330.0 750C23A 245.7 73.1 318.8 900C43A/E 223.1 73.1 296.2

007C43A/E - - - 1100C43A/E 13.6 73.1 13.6

Specifications for Wiring Terminals (refer to wiring diagram) control terminals Wire gauge: 26-16AWG(0.1281-1.318mm2) Torque(±10%): 5kgf-cm[4.31 lbf-in.] (0.4905Nm)

main circuit terminals

Models VFD- Max. Wire Gauge Min. Wire Gauge Torque

(±10%) Note

007C23A/E 14 AWG (2.1mm2) 015C23A/E 12 AWG (3.3mm2) 022C23A/E 10 AWG (5.3mm2) 037C23A 8 AWG (8.4mm2) 037C23E 10 AWG (5.3mm2)

007C43A/E 14 AWG (2.1mm2) 015C43A/E 14 AWG (2.1mm2) 022C43A/E 14 AWG (2.1mm2) 037C43A 10 AWG (5.3mm2) 037C43E 12 AWG (3.3mm2)

040C43A/E 10 AWG (5.3mm2) 055C43A/E

8 AWG (8.4mm2)

10 AWG (5.3mm2)

M4 20kg-cm

(17.4 lbf-in.)(1.962Nm)

-

055C23A/E 8 AWG (8.4mm2) 075C23A/E 6 AWG (13.3mm2)

※110C23A/E 4 AWG (21.2mm2) 075C43A 8 AWG (8.4mm2) 075C43E 10 AWG (5.3mm2)

110C43A/E 8 AWG (8.4mm2) 150C43A 6 AWG (13.3mm2) 150C43E

4 AWG (21.2mm2)

8 AWG (8.4mm2)

M5 35kg-cm

(30.4 lbf-in.)(3.4335Nm)

Terminal D+[+2 & +1]: Torque 45 Kg-cm [39.0 lbf-in.] (4.4145Nm) (±10%)

150C23A 1 AWG (42.4mm2) 150C23E 2 AWG (33.6mm2) 185C23A 1/0 AWG (53.5mm2)185C23E 1 AWG (42.4mm2)

※220C23A/E 1/0 AWG (53.5mm2)185C43A 4 AWG (21.2mm2) 185C43E 6 AWG (13.3mm2)

220C43A/E 4 AWG (21.2mm2) 300C43A 2 AWG (33.6mm2) 300C43E

1/0 AWG (53.5mm2)

3 AWG (26.7mm2)

M8 80kg-cm

(69.4 lbf-in.)(7.848Nm)

Terminal D+[+2 & +1]: Torque 90 Kg-cm [78.2 lbf-in.] (8.829Nm) (±10%)

300C23A 4/0 AWG (107mm2) 370C23A 250MCM (126mm2)370C43A 1/0 AWG (53.5mm2)450C43A 2/0 AWG (67.4mm2)550C43A 3/0 AWG (85mm2) 750C43A

300MCM (152mm2)

300MCM (152mm2)300C23E 4/0 AWG (107mm2) 370C23E 4/0 AWG (107mm2) 370C43E 1/0 AWG (53.5mm2) 450C43E 2/0 AWG (67.4mm2) 550C43E 3/0 AWG (85mm2) 750C43E

4/0 AWG (107mm2)

4/0 AWG (107mm2)

M8 200kg-cm

(173 lbf-in.)(19.62Nm)

Please use the specifications of insulated heat shrink tubing that comply with UL (600C, YDPU2).

450C23A 1/0AWG*2 (53.5mm2*2)

550C23A 3/0AWG*2 (85mm2*2)

750C23A 4/0 AWG *2 (107mm2*2)

When using the ring terminal, please comply with the following specification.

31MAX.

8.2MIN.

26.5MAX.

70M

AX

.16

+0 -4

Specification of grounding wire: 300MCM [152 mm2]

8.2MIN.

65.0

MAX

.

17.0

MA

X.

28.0MAX.

900C43A 1/0AWG*2 (53.5mm2*2)1100C43A

300MCM*2 (152mm2*2)

3/0AWG*2 (85mm2*2)450C23E 1/0AWG*2 (53.5mm2*2)550C23E 1/0AWG*2 (53.5mm2*2)750C23E 3/0AWG*2 (85mm2*2)900C43E 1/0AWG*2 (53.5mm2*2)

1100C43E

4/0 AWG*2 (107mm2*2)

2/0AWG*2 (67.4mm2*2)

Please use the specifications of insulated heat shrink tubing that comply with UL (600C, YDPU2).

※900C23A 300MCM*2 (152mm2*2)

1320C43A 4/0 AWG*2 (107mm2*2)

1600C43A

300MCM*2 (152mm2*2)

300MCM*2 (152mm2*2)

900C23E 4/0 AWG*2 (107mm2*2)1320C43E 3/0AWG*2 (85mm2*2)

1600C43E

4/0 AWG*2 (107mm2*2)

4/0 AWG*2 (107mm2*2)

When using the ring terminal, please comply with the following specification.

31MAX.

8.2MIN.

26.5MAX.

70M

AX

.16

+0 -4

2800C43A 4/0 AWG*4(107mm2*4)3150C43A 300MCM*4 (152mm2*4)3550C43A 300MCM*4 (152mm2*4)2800C43E 3/0AWG*4 (85mm2*4)3150C43E 4/0 AWG*4 (107mm2*4)

3550C43E

300MCM*4 (152mm2*4)

250MCM*4 (127mm2*4)

When using the ring terminal, please comply with the following specification.

Please use the specifications of insulated heat shrink tubing that comply with UL (600C, YDPU2).

Main circuit terminals: R/L11, R/L12, S/L21, S/L22, T/L31, T/L32

1850C43A 2/0AWG*4 (67.4mm2*4)

2200C43A 3/0AWG*4 (85mm2*4)

1850C43E 1/0AWG*4 (53.5mm2*4)

2200C43E

300MCM*4 (152mm2*4)

2/0AWG*4 (67.4mm2*4)

M8 200kg-cm

(173 lbf-in.)(19.62Nm)

When using the ring terminal, please comply with the following specification.

31MAX.

8.2MIN.

26.5MAX.

70M

AX.

16+0 -4

Please use the specifications of insulated heat shrink tubing that comply with UL (600C, YDPU2).

Main circuit terminals: U/T1, V/T2, W/T3, +1/DC+, -/DC-

1850C43A 400MCM*2 (203mm2*2)

2200C43A 500MCM*2 (253mm2*2)

1850C43E 300MCM*2 (152mm2*2)

2200C43E

500MCM*2 (253mm2*2)

400MCM*2 (203mm2*2)

M10 408kg-cm

(354 lbf-in.)(40Nm)

When using the ring terminal, please comply with the following specification.

31MAX.

8.2MIN.

26.5MAX.

70M

AX.

16+0 -4

Please use the specifications of insulated heat shrink tubing that comply with UL (600C, YDPU2).

NOTE: UL installations must use 600V, 75℃ or 90℃. Use copper wire only.

NOTE: VFD110C23A, VFD2200C43A must use 90℃ wire, if ambient temperature>45℃. NOTE: VFD220C23A, VFD900C23A/E must use 90℃ wire, if ambient temperature>40℃.

Environment for Operation, Storage and Transportation DO NOT expose the AC motor drive in the bad environment, such as dust, direct sunlight, corrosive/inflammable gasses, humidity, liquid and vibration environment. The salt in the air must be less than 0.01mg/cm2 each year.

Installation location IEC60364-1/IEC60664-1 Pollution degree 2, Indoor use only

UL type1/IP20 -10~+ 40oC without derating, Up to 60 oC with derating* Operation

UL OPEN-TYPE/IP20 -10~+ 50 oC without derating (-10~+ 40°C for side by side removed top cover). Up to 60 oC with derating*

Storage/ Transportation -25 oC ~ +70 oC

Surrounding Temperature

Non-condensation, non-frozen Operation Max. 90% Storage

/Transportation Max. 95% Rated Humidity

No condense water Operation 86 to 106 kPa Storage 86 to 106 kPa Air Pressure

Transportation 70 to 106 kPa IEC721-3-3

Operation Class 3C2, Class 3S2 Storage Class 2C2, Class 2S2

Transportation Class 1C2, Class 1S2 Pollution Level

No concentrate

Environment

Altitude Operation Airflow range is 0-1000m. It will reduce 1% for each increasing 100m during the altitude 1000-3000m. The airflow limit is 2000m at the network area “Corner Grounded”.

Storage Package Drop Transportation

ISTA procedure 1A(according to weight) IEC60068-2-31

Vibration IEC 60068-2-6 Impact IEC/EN 60068-2-27

Operation Position Max. allowed offset angle ±10o (for normal installation position)

10 10

Page 2: Specifications for Wiring Terminals (refer to wiring diagram) …mat.transtechnik.fr/DELTA/documentation/Inverters/VFD-C2000/Quick... · C2000 Series Installation Instruction ...

Wiring Diagram

Fuse/NFB(No Fuse Breaker)

R (L1)S(L2)T(L3)

R (L1)S(L2)T(L3)

Motor

* Provide 3-phase input power

U (T1)V(T2)

W(T3)IM3~

For fr ame D and above

+1/D C+ -/DC -

* Prov ide 3-phase input pow erFuse/NFB(No Fuse Breaker)

For f rame G and frame H

R

S

T

R/L11R/L21S/L12S/L22T/L13T/L23

R/L11

S/L22T/L23

R

S

TR/L21

S/L12T/L13

Y

* Prov ide 12-phase input pow er

250Vac/5A (N.O.)250Vac/3A (N.C.)

NOTE

AFM1

ACM

I/O & Relay extension card

Option Slot 1

RA1RB1

RC1

AVI

ACM

+10V

5K3

21

0 to 10V

ACIAUI

4~20mA

-10~+10V

-10V

+10V/20mA

-10V/20mA

MO2

MCM

FWD

REVMI1

MI3

MI4MI5

MI6

MI7

DCM

MI2

MI8

power removal safety funct ion for EN954-1 and IEC/EN61508

SCM

8 1Option Slot 3

Option Slot 2Modbus RS-485 8 1

DFM

MO1

SG+

SG-

COM

S148V/50mA

AFM2

RA2RB2

RC2

DCM

+24V

Pin 1~2, 6, 8: reservedPin 3, 7:GNDPin 4:SG-Pin 5:SG+

30Vdc/5A (N.O.)30Vdc/3A (N.C.)

250Vac/1.2A (N.C.)Est imate at COS (0.4)

250Vac/2A (N.O.)Est imate at COS (0.4)

Analog Signal common

Analog Signal Common

* Don't apply the mains voltage direct ly to above terminals.* MI8 can input pulses 100kHz

FWD/STOPREV/STOPE.F.

Multi-step 1Multi-step 2Multi-step 3Multi-step 4

Accel/Decel prohibitRESET

Digital Signal Common

JOG

Factory setting: NPN (SINK) ModePlease refer tofollowing figure for wiring of NPN mode and PNP mode.

Factorysetting

Digital Signal Common Mult i-funct ion Photocoulper Output

Mult i-funct ion output f requency terminals 30V30mA 100kHz

Analog Mult i-functionOutput Terminal 0~10VDC/2mA

Analog Mult i-functionOutput Terminal 0~10VDC/4-20mA

Main circuit (power) terminals

Control terminals

Shielded leads & Cable

R(L1)S(L2)T(L3)

R(L1)S(L2)T(L3)

U(T1)V(T2)W(T3)

IM3~

Frame A~C

Fuse/NFB(No Fuse Breaker)Motor

* It provide 3-phase power

+2 B1 B2+1-

Jum per Brak e res istor (opt ional)D C c hok e (opt ional)

Multi-function output terminals

Mult i-funct ion output f requency terminals

PG extension card

communication extension card

Dimensions (Following figures are used to mark the dimensions and the appearance is only for reference)

Frame A VFD007C23A/E; VFD007C43A/E; VFD015C23A/E; VFD015C43A/E; VFD022C23A/E; VFD022C43A/E; VFD037C23A/E; VFD037C43A/E; VFD040C43A/E; VFD055C43A/E; W H D W1 H1 D1 S1,S2 ψ1 ψ2 ψ3

mm 130.0 250.0 170.0 116.0 236.0 45.8 6.2 22.2 34.0 28.0 inch 5.12 9.84 6.69 4.57 9.29 1.80 0.24 0.87 1.34 1.10

Frame B VFD055C23A/E; VFD75C23A/E; VFD075C43A/E; VFD110C23A/E; VFD11C43A/E; VFD150C43A/E; W H D W1 H1 D1 S1,S2 ψ1 ψ2 ψ3

Mm 190.0 320.0 190.0 173.0 303.0 77.9 8.5 22.2 34.0 43.8 Inch 7.48 12.60 7.48 6.81 11.93 3.07 0.33 0.87 1.34 1.72

Frame C VFD150C23A/E; VFD185C23A/E; VFD185C43A/E; VFD220C23A/E; VFD220C43A/E; VFD300C43A/E; W H D W1 H1 D1 S1,S2 ψ1 ψ2 ψ3

mm 250.0 400.0 210.0 231.0 381.0 92.9 8.5 22.2 34.0 50.0 inch 9.84 15.75 8.27 9.09 15.00 3.66 0.33 0.87 1.34 1.97

D1:Flange mounting W D

D1

H3HH1

W1

Frame D D1:VFD300C23A; VFD370C23A; VFD370C43A; VFD450C43A; VFD550C43A; VFD750C43A; D2:VFD300C23E; VFD370C23E; VFD370C43E; VFD450C43E; VFD550C43E; VFD750C43E;

Frame W H D W1 H1 H2 H3 D1 ψ ψ1 ψ2 ψ3 D 330.0

[12.99] 550.0[20.65]

275.0[10.83]

285.0[11.22]

525.0[20.67]

492.0[19.37]

107.0[4.22]

11.0[0.43]

34.0[1.34]

22.0 [0.87]

11.0 [0.43]

D1 330.0 [12.99]

550.0[20.65]

275.0[10.83]

285.0[11.22]

525.0[20.67]

688.3[27.10]

492.0[19.37]

107.0[4.22]

11.0[0.43]

34.0[1.34]

22.0 [0.87]

11.0 [0.43]

Frame E E1:VFD450C23A; VFD550C23A; VFD750C23A; VFD900C43A; VFD110C43A; E2:VFD450C23E; VFD550C23E; VFD750C23E; VFD900C43E; VFD110C43E; Frame W H D W1 H1 H2 H3 D1 ψ ψ1 ψ2 ψ3 ψ4

E 370.0 [14.57]

589[23.19]

300.0[11.81]

335.0[13.19

560.0[22.05]

528.0[20.80]

143.0[5.63]

13.0[0.51]

22.0[0.87]

34.0 [1.34]

76.0 [2.99]

92.0 [3.62]

E1 370.0 [14.57]

589[23.19]

300.0[11.81]

335.0[13.19

560.0[22.05]

715.8[28.18]

528.0[20.80]

143.0[5.63]

13.0[0.51]

22.0[0.87]

34.0 [1.34]

76.0 [2.99]

92.0 [3.62]

D1:Flange mounting mm[inch]

HH

1H

2

S1 S1

D2

WW1

DD1

S3

S2

Frame F F1:VFD900C23A; VFD1320C43A; VFD1600C43A; F2:VFD900C23E; VFD1320C43E; VFD1600C43E; Frame W H D W1 H1 H2 H3 D1 D2 S1 S2 S3

F1 420.0 [16.54]

300.0[11.81]

380.0[14.96]

800.0[31.50]

770.0[30.32]

492.0[19.37]

124.0[4.88]

18.0[0.71]

13.0[0.51]

25.0 [0.98]

18.0 [0.71]

F2 420.0 [16.54]

940.0[37.00]

300.0[11.81]

380.0[14.96]

800.0[31.50]

770.0[30.32]

492.0[19.37]

124.0[4.88]

18.0[0.71]

13.0[0.51]

25.0 [0.98]

18.0 [0.71]

Frame G G1:VFD1850C43A; VFD2200C43A; G2:VFD1850C43E; VFD2200C43E; Frame W H D W1 H1 H2 H3 Φ Φ1 Φ2 Φ3

G1 500.0 [19.69]

397.0[15.63]

440.0[217.32]

1000.0[39.37]

963.0[37.91]

913.6[35.97]

13.0 [0.51]

G2 500.0 [19.69]

1240.2[48.83]

397.0[15.63]

440.0[217.32]

1000.0[39.37]

963.0[37.91]

913.6[35.97]

13.0 [0.51]

22.0 [0.87]

34.0 [1.34]

117.5 [4.63]

D1:Flange mounting mm[inch]

Frame H H1:VFD1850C43A; VFD2200C43A; H2:VFD1850C43E; VFD2200C43E; Frame W H D W1 W2 W3 W4 W5 H1 H2 D1 D2

H1 700.0 [27.56]

1435.0[56.5]

398.0[15.67]

630.0[24.8]

290.0[11.42]

1358.0[53.46] - 1347.0

[53.03]1403.0[55.24]

1347.0 [53.03] - -

H2 700.0 [27.56]

1745.0[68.7]

404.0[15.9]

630.0[24.8]

500.0[19.69]

1358.0[53.46]

1577.0[62.08]

1347.0[53.03]

1729.0[68.07]

1702.0 [67.0]

38.0 [1.5]

103.0 [4.06]

Frame D3 D4 D5 D6 Φ Φ1 Φ2 Φ3

H1 - - - - 13.0 [0.51] - - -

H2 307.0 [12.09]

68.0 [2.68]

206.0[8.07]

342.0[13.46]

13.0 [0.51]

22.0 [0.87]

34.0 [1.34]

117.5[4.63]