Specification for High Mast Lighting System for Black Oil...
Transcript of Specification for High Mast Lighting System for Black Oil...
VISAKH MARKETING INSTALLATION RESITEMENT
PROJECT BO / WO / LPG TERMINALS
Doc No: 254625-300-SP-ELE -011 Rev: C Page 1 of 26 ABCABCABCABC
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\04 Electrical\Documents\13 Specifications\High Mast\Rev. C - Issued for
tender\254625-300-SP-ELE-011--Rev C.doc
Mott MacDonald Consultants (India) Pvt. Ltd.
Kothari House, CTS No. 185
Off Andheri - Kurla Road
Andheri (East)
Mumbai 400 059
Hindustan Petroleum Corporation Ltd
Viskaha Dispatch Station
VR-ATP Area, Naval Base Post
Visakhapatnam - 530 014
Andhra Pradesh
Specification for High Mast Lighting System for Black Oil, White Oil &
LPG Terminals
VISAKH MARKETING INSTALLATION RESITEMENT
PROJECT BO / WO / LPG TERMINALS
Doc No: 254625-300-SP-ELE -011 Rev: C Page 3 of 26 ABCABCABCABC
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\04 Electrical\Documents\13 Specifications\High Mast\Rev. C - Issued for
tender\254625-300-SP-ELE-011--Rev C.doc
List of Contents Pages
1 Introduction ........................................................................................................................ 5
2 Location and Environmental Conditions............................................................................ 5
2.1 Plant Location..................................................................................................................... 5
2.2 Environmental Conditions.................................................................................................. 5
2.3 Electrical System Data ....................................................................................................... 5
3 Scope of Supply.................................................................................................................. 6
4 Codes and Standards .......................................................................................................... 7
5 Technical Requirements ..................................................................................................... 7
5.1 Electrical System................................................................................................................ 7
5.2 Design Requirement ........................................................................................................... 8
5.2.1 Mast Structure .................................................................................................................... 8
5.2.2 Head Frame ........................................................................................................................ 8
5.2.3 Lantern Carriage................................................................................................................. 9
5.2.4 Light Fittings ...................................................................................................................... 9
5.2.5 Winch Assembly .............................................................................................................. 10
5.2.6 Stainless Steel Wire rope.................................................................................................. 10
5.2.7 Power Tool for Winch Assembly..................................................................................... 10
5.2.8 Feeder Pillar ..................................................................................................................... 11
5.2.9 Local Control Station ....................................................................................................... 12
5.2.10 Junction Box..................................................................................................................... 12
5.2.11 Cables and Cable Connections......................................................................................... 12
5.2.12 Lightning final .................................................................................................................. 12
5.2.13 Earthing & Earthing Terminals ........................................................................................ 13
5.2.14 Hazardous Area Classification ......................................................................................... 13
5.3 Name Plates...................................................................................................................... 13
5.4 Makes of Components...................................................................................................... 13
5.5 Painting............................................................................................................................. 14
5.6 Civil Structural Work....................................................................................................... 14
5.6.1 Materials........................................................................................................................... 14
5.6.2 Concrete ........................................................................................................................... 15
5.6.3 Design of Foundation ....................................................................................................... 15
5.6.4 Loadings ........................................................................................................................... 15
6 Inspection, Testing and Acceptance at works .................................................................. 15
VISAKH MARKETING INSTALLATION RESITEMENT
PROJECT BO / WO / LPG TERMINALS
Doc No: 254625-300-SP-ELE -011 Rev: C Page 4 of 26 ABCABCABCABC
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\04 Electrical\Documents\13 Specifications\High Mast\Rev. C - Issued for
tender\254625-300-SP-ELE-011--Rev C.doc
7 Vendor Documentation .................................................................................................... 17
8 Statutory Approval ........................................................................................................... 17
Appendix-A: Table of Compliance .............................................................................................. 18
Appendix-B: Codes & Standards ............................................................................................... 20
Appendix-C: Requisition for Engineering Documents .............................................................. 22
Appendix-D: Guaranteed Technical Particulars......................................................................... 24
Appendix-E: Overall High Mast Lighting Layouts & Hazardous Area Classification drawings
for Black oil, White Oil & LPG Terminals .................................................................................. 25
Appendix-F: i) SOQ for Black Oil Terminal .............................................................................. 26
ii) SOQ for White Oil Terminal ................................................................................................... 26
iii) SOQ for LPG Terminal .......................................................................................................... 26
VISAKH MARKETING INSTALLATION RESITEMENT
PROJECT BO / WO / LPG TERMINALS
Doc No: 254625-300-SP-ELE -011 Rev: C Page 5 of 26 ABCABCABCABC
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\04 Electrical\Documents\13 Specifications\High Mast\Rev. C - Issued for
tender\254625-300-SP-ELE-011--Rev C.doc
1 Introduction
1.1 This specification covers the minimum requirements for the Design, Engineering, Preparation of
Drawings, Fabrication, Assembly, Painting, Inspection at manufacturers works, Supply &
Delivery to site, Erection, Testing and Commissioning of High Mast Lighting System with
lighting fixtures, accessories including supply of fixture cables etc. for “Black Oil, White Oil &
LPG Terminal Projects” of M/s. HPCL, located at Visakhapatnam, A.P., India.
Following are the definitions:
Owner / Purchaser Hindustan Petroleum Corporation Ltd.
Consultant Mott MacDonald Consultants (India) Pvt. Ltd.[MMCI]
Manufacturer / Vendor Supplier of High Mast Lighting System
Shall This is to be understood as mandatory in relation to the
requirements of this document.
Should This is to be understood as a strong recommendation to
comply with the requirements of this document.
Equipment This is to be understood as vendor supplied equipment
with all accessories.
1.2 The Vendor shall ensure that the design complies with the requirements of this specification and
standards. The Guaranteed Technical Particulars, which forms part of this specification, shall be
completed by the Vendor. The Vendor shall highlight any non-compliance at the offer stage in
the Table of Compliance, Appendix A. Not providing completed compliance table and
Guaranteed Technical Particulars can cause rejection of the offer. Failure to clearly identify
specific deviations shall be assumed by the Purchaser to be total compliance with the
specification.
1.3 This specification does not relieve the Vendor from final guarantee as to materials, apparatus,
workmanship and performance of the equipment supplied.
2 Location and Environmental Conditions
2.1 Plant Location
Black Oil, White Oil & LPG Terminal Projects of M/s. HPCL are located at Visakhapatnam,
A.P, India. The High Masts for the above mentioned terminals shall be located within the
respective terminal’s Plot.
2.2 Environmental Conditions
Refer Doc No.: 254625-300-SP-GEN-001 for details of Black Oil Terminal.
Refer Doc No: 254624-400-SP-GEN-001 for details of White Oil Terminal.
Refer Doc No: 256324-500-SP-GEN-001 for details of LPG Terminal.
2.3 Electrical System Data
Refer Doc No.: 254625-300-DS-ELE-001 for details of Black Oil Terminal.
Refer Doc No.: 254624-400-DS-ELE-001 for details of White Oil Terminal.
Refer Doc No.: 256324-500-DS-ELE-001 for details of LPG Terminal.
VISAKH MARKETING INSTALLATION RESITEMENT
PROJECT BO / WO / LPG TERMINALS
Doc No: 254625-300-SP-ELE -011 Rev: C Page 6 of 26 ABCABCABCABC
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\04 Electrical\Documents\13 Specifications\High Mast\Rev. C - Issued for
tender\254625-300-SP-ELE-011--Rev C.doc
3 Scope of Supply
3.1 Scope :
The High Mast Lighting System shall include following Equipment & Materials, in accordance
with this specification; standards stated herein & enclosed appendices.
• Equipment Supply
a) Decorative type High mast with Umbrella like structure at top.
b) High mast structure with lantern carriage [for Flood light fixtures & Aviation lights]
raising / lowering motorized Winch Assembly.
c) Flood light fixtures with lamps & Aviation obstruction lighting fixtures.
d) Power & control cables complete as required from feeder pillar to winch motor & light
fittings for power distribution shall be in Vendor’s scope.
e) Feeder pillar distribution boards which will house TPN isolator, starter for winch power
tool motor and outgoing feeders for the fixture.
f) Power tool for winch drive.
g) Wires / strips for complete earthing, lightning protection including supply & erection of
lightning spikes & earth pits.
h) GI / PVC conduits, GI pipes and supporting structures for feeder pillars.
i) All other accessories like branch/pull/junction boxes, cross arms brackets for supporting
light fixtures, distribution board etc., saddle / clamps and other miscellaneous items
required for the completeness and efficient working of the system whether explicitly
specified or not in this specification shall be included.
• Design Related
a) Quantity of High Mast mentioned in schedule of quantity is tentative. Vendor to validate
this design at offer stage based on following parameters:
� Required Illumination level of average 20 Lux & min.12 Lux.
� Vendor to maintain flood light fitting mounting height to 20mtr. For all three
projects.
� For White Oil & LPG terminal projects, vendor to restrict overall mast height to
22.5mtr. from FGL inclusive of fancy umbrella, aviation lamps & lightning
spike.
� 2x400W HPSV (SON-TP), maximum 12 Nos. of Flood Light fittings per High
mast.
b) The drawings/documents mentioned in Cl. No.7 of this specification shall be prepared by
the successful vendor.
• The scope of civil and structural foundation is included for Black Oil Terminal Project. The
scope includes design, detailing, supply and construction of foundation for High mast poles &
associated feeder pillars. Necessary design & drawings with load data as per IS: 875 shall be
prepared on standard size sheets & submitted for review/approval prior to execution of work.
The detail of civil structural work is described in Cl. 5.6 of the document
• Inspection and Testing as specified.
• Submission of documents as specified.
• Painting as specified.
VISAKH MARKETING INSTALLATION RESITEMENT
PROJECT BO / WO / LPG TERMINALS
Doc No: 254625-300-SP-ELE -011 Rev: C Page 7 of 26 ABCABCABCABC
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\04 Electrical\Documents\13 Specifications\High Mast\Rev. C - Issued for
tender\254625-300-SP-ELE-011--Rev C.doc
• Preservation, preparation of shipment and delivery to site.
• List of Spares for two years normal operation.
• Start-up spares and commissioning spares.
• List of special tools required (Vendor to provide list with the bid).
• Any other items, required to make system complete.
3.2 Engineering Services
The Vendor shall provide engineering services, which shall include, but not necessarily be
limited to, the following:
•••• Providing/coordinating detailed design of all equipment and components within the scope of
supply.
•••• Resolving engineering queries related to the equipment and components within the scope of
supply.
•••• Performing all relevant calculations pertaining to lighting design and equipment within the
scope of supply.
•••• Providing progress reports etc.
•••• Providing expediting services for all sub-vendors.
•••• Providing quality assurance, including all sub-vendors with respect to ISO 9000 or
equivalent.
•••• Quality Assurance.
•••• Supervision of Installation/erection and commissioning.
•••• Training of client’s personnel at site / Vendor’s shop.
3.3 Exclusions
•••• The scope of civil foundation for high mast & feeder pillar is excluded for White Oil &
LPG Terminal Projects, since piles will be provided to install the High Mast. Necessary
mounting detail drawings with load data should be furnished by the vendor for the design of
the piles (to be carried out by others).
4 Codes and Standards
The High Mast Lighting System shall meet the requirements of this specification and latest
edition of applicable standards listed in enclosed Appendix-B.
5 Technical Requirements
5.1 Electrical System
Each High mast shall have feeder pillar distribution board located near the mast (not integral
with mast). This feeder pillar will house a TPN isolator and starter for winch power tool motor
and will give supply to light fittings on High Mast and to motor. This feeder pillar will be
mounted separately near the High mast. Each feeder pillar will receive 3-phase 415 V TPN ( 4
wire)50 Hz supply from purchaser. Further distribution shall be in vendor's scope.
Lighting circuits shall be single phase and neutral and / or three phase & neutral, protected with
MCBs, but not to be loaded higher than 80% capacity. 20% spare MCB to be provided in each
feeder pillar.
Adjacent luminaries shall not be supplied from the same circuit, or in case of three phase
circuits, from the same phase.
VISAKH MARKETING INSTALLATION RESITEMENT
PROJECT BO / WO / LPG TERMINALS
Doc No: 254625-300-SP-ELE -011 Rev: C Page 8 of 26 ABCABCABCABC
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\04 Electrical\Documents\13 Specifications\High Mast\Rev. C - Issued for
tender\254625-300-SP-ELE-011--Rev C.doc
Indicative locations of high masts are indicated in attached Overall High Mast Lighting
drawings. However final locations of the high masts and the feeder pillars shall be decided by
vendor based on calculations. It shall be outside tank dykes so that they do not fall under the
hazardous zone. Also, the location of the masts shall be such that they do not put any hindrance
on the movement of the tankers and the vehicles on the roads neither do they foul with any
equipment, structure or buildings.
It is to be noted that the area allocated for each lighting mast is around 5m x 5m for piling,
foundations and for the general operational purpose taking into account the maintenance of the
lighting fittings and accessories after winching down.
5.2 Design Requirement
The high mast and other equipment & materials shall be of the best quality and shall conform to
the specification given under:
5.2.1 Mast Structure
a) The Mast base, structural & foundation design shall be designed in a manner so that it is
capable of withstanding external forces exerted on it by maximum wind speeds and
stresses specified in IS 875 Part 3-1987 along with load of the lantern carriage assembly.
The resonant frequency of Mast shall be less than 1Hz so that wind speed stresses which
arise at resonance are correspondingly low.
b) The mast shall be of continuously tapered, polygonal cross section presenting a good and
pleasing appearance based on proven intension design conforming to standards listed in
Appendix - B
c) The mast shall be fabricated from steel plates cut and folded to form a polygonal section.
The high Mast shall comprise of two sections of approx. equal lengths. Each mast section
shall not have any circumferential welding joint. Sections should be fitted together on site,
telescopically, in manner that does not require additional welding nor any bolted joints
acceptable. The minimum overlap distance shall be 1.5 times the diameter at penetration.
The welding shall be in accordance with BS 5135 / AWS
d) The mast shall be provided with fully penetrated flange, which shall be free from any
lamination or incursion. The welded connection of the base flange shall be fully developed
to the strength of the entire section. The base flange shall be provided with supplementary
gussets between the bolt holes to ensure elimination of helical stress concentration and
high tensile anchor bolts.
e) Both the inner & outer surface of entire fabricated mast shall be hot dip galvanized, having
a uniform thickness for bottom and top sections. The amount of galvanizing shall be 610
gm/m2. The mast shall accommodate integral power tool for winch drive. The mast shall
have a minimum design life of 25 years.
f) An adequate door opening shall be provided at the base of the mast to permit clear access
to equipment like power tool winch drive, cables, plug and socket etc and also facilitate
easy removal of the winch. The door shall be close fitting, dust and vermin proof and
provided with heavy-duty double locking arrangement. Size of door opening shall be such
as to avoid buckling of the mast section under heavy wind conditions.
5.2.2 Head Frame
a) The Head frame, designed to be capping unit of the mast shall be welded steel construction
and hot dip galvanised.
VISAKH MARKETING INSTALLATION RESITEMENT
PROJECT BO / WO / LPG TERMINALS
Doc No: 254625-300-SP-ELE -011 Rev: C Page 9 of 26 ABCABCABCABC
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\04 Electrical\Documents\13 Specifications\High Mast\Rev. C - Issued for
tender\254625-300-SP-ELE-011--Rev C.doc
b) The top pulleys shall be of a diameter, appropriately large enough to accommodate the
steel wire ropes and the multi-core electric cable. The material of construction of the
pulley blocks shall be non – corrosive and preferably made up die cast LM6 Al. alloy,
material such as plastic or PVC not acceptable The design shall ensure that operation of
pulleys shall be maintenance free. The pulleys will run on stainless steel shaft/spindles and
will be self lubricating type
c) Close fitting removable guards shall be provided over the pulleys to ensure correct location
of the ropes and cables in their grooves during operation. Guides and stops shall be
provided for docking the lantern carriage. The complete chassis assembly covered by
weather proof hot dip galvanised after fabrication
d) The whole head frame assembly shall be covered and protected by weather proof hot dip
galvanised canopy and secured to the frame by stainless steel bolts and nuts.
e) Specification for Umbrella :
Material: LM6 or GI with powder coating OR FRP/GRP with polyurethane paint.
Diameter: Umbrella shall extend 300mm [min.] beyond extreme edges of lighting fixtures
mounted on lantern carriage.
5.2.3 Lantern Carriage
a) The fabricated lantern carriages shall be provided for holding the desired number of
floodlight fittings, control gear box, junction boxes, aviation lights on each High Mast and
balance counter weights shall be provided wherever required.
b) The complete lantern carriage shall be of mild steel tubular ring type construction and hot
dip galvanized internal & external after assembly. The inner lining of the carriage shall be
provided with perfect self-balance arrangement so as to avoid swing and buffer
arrangement to prevent damage to mast surface or other installed parts, during
lowering/raising operation of carriage.
c) The carriage shall be supported / suspended by at least three wire ropes for better stability.
The lantern carriage assembly shall not touch the lower surface of the mast. At the lower
docking position, the lantern carriage will rest firmly at a maintainable height from the
ground level with the help of stoppers for easy maintenance.
d) All hardware like bolts, nuts etc. shall be stainless steel to avoid corrosion. The carriage
shall have weather protected (IP-55) cast aluminium junction box with required number of
terminals (phase, neutral and earth) for connection to the designed number of flood light
fittings and associated control gears fixed on the carriage. The carriage design and
fabrication shall be such that the lantern carriage will suit the lanterns and their control
gear boxes to be used in the work.
e) Lantern carriage shall be suitable for accommodating aviation lights, maximum 12
numbers of flood light fixtures & associated control gear box, junction boxes. The number,
wattage and type of lighting fixture of the high mast shall be decided by the High mast
lighting system vendor.
5.2.4 Light Fittings
a) The Non-Integral flood light fixtures shall have die cast aluminium body with facility for
lamp centering and focusing and shall be provided with angle indicator for aiming, and
also with anodized and polished aluminium reflector.
b) The vendor shall decide quantity of lighting mast and number of fixture per lighting mast
to achieve average illumination level of 20 LUX & Minimum of 12 Lux in the plant area.
The lighting fixtures shall be Non-Integral type flood light fixtures with preferably 2 x
400-watt HPSV (SON-TP) lamps.
C
VISAKH MARKETING INSTALLATION RESITEMENT
PROJECT BO / WO / LPG TERMINALS
Doc No: 254625-300-SP-ELE -011 Rev: C Page 10 of 26 ABCABCABCABC
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\04 Electrical\Documents\13 Specifications\High Mast\Rev. C - Issued for
tender\254625-300-SP-ELE-011--Rev C.doc
c) The Control gear shall be provided with di-cast aluminium & prewired wired with copper
ballast, Power factor improving capacitor, rewired fuses, electronic ignitor, Mains
connector & 2 Nos-earthing-one internal & one external.
d) Each high mast shall have aviation obstruction lighting fixture with two nos. of 40W neon
spiral type lamps of reliable design and reputed make. Aviation lights shall be mounted
above decorative umbrella. It shall be possible to bring down these lights located on
lantern carriage for maintenance purpose.
e) The luminaries shall be tested as per Indian standards and test reports shall be submitted
along with materials.
5.2.5 Winch Assembly
a) For Installation & maintenance of luminaries & lamps, it will necessary to lower and raise
of lantern carriage assembly, a winch arrangement shall be fixed in the base of the mast.
This shall have provision to operate both manually and electrically. The winch shall be
suitable to handle the weight of the lantern carriage assembly with lighting fixtures and all
other accessories, with appropriate factor of safety. Minimum two number of winch drum
shall be provided for the winch assembly. A handle shall also be provided for hand
operation of the winches.
b) The winch shall be of self-sustaining type with positive locking arrangement without the
need for brake shoe, springs, or clutches. The winch shall be capable of handling
maximum anticipated load with sufficient safety margin.
c) The winches shall be of self –lubricating type by means of an oil bath and the lubrication
shall be of recommended quality. The double drum winch shall use an arrangement of
minimum two independent ropes and each rope shall have one end clamped to winch drum
and the other end attached to the lantern carriage. Termination of the ropes of the winch
shall be in such a way, that it does not involve distortion or twisting of the rope
configuration. At least one full layer of rope shall remain on the drum when the lantern
carriage is fully lowered.
d) The mast shall be fitted with flexible stranded high tensile strength stainless steel wire
ropes, which shall have a factor of safety not less than five times the safe working load of
winch. Particular care shall be exercised in all aspects of design, manufacture, testing and
installation arrangements of the system to ensure safety under all operation conditions.
e) The capacity, operating speed, safe working load, recommended lubrication and serial
number of the winch shall be clearly marked on each winch.
f) A test certificate shall be supplied along with each winch in support of the maximum load
operated by the winch and for the safety of operation at the full load rotation.
5.2.6 Stainless Steel Wire rope
All wire ropes shall be made from stainless steel confirming to IS 2365,1963 & IS-
3457,1977.Stainless steel wire ropes shall be of 7 / 19 construction of min.6 mm diameter. There
shall not be any intermediate joints on the ropes between winch and lantern carriage. The end for
connection to the winch drum shall be fitted with thimbles and the thimbles shall be secured by
copper compression splices.
5.2.7 Power Tool for Winch Assembly
VISAKH MARKETING INSTALLATION RESITEMENT
PROJECT BO / WO / LPG TERMINALS
Doc No: 254625-300-SP-ELE -011 Rev: C Page 11 of 26 ABCABCABCABC
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\04 Electrical\Documents\13 Specifications\High Mast\Rev. C - Issued for
tender\254625-300-SP-ELE-011--Rev C.doc
a) A suitable, high power, electrically driven, internally mounted power tool, with manual
override shall be supplied for raising and lowering of the lantern carriage for maintenance
purposes. The power tool shall be single speed, provided with a motor of the required
rating. The capacity and speed of the electrical motor used in the power tool shall be
suitable for the lifting of the design load installed in the lantern carriage with design
margin of minimum 20%.
b) The power tool mounting shall be so designed that it shall not only self sustaining but also
aligns the power tool perfectly with respect to the winch spindle during the operations.
c) The power drive shall be connected to the winch via a match coupler. It shall incorporate
torque limiter to protect the wire ropes from over stretches /over load. The torque limiter
shall trip the load when it exceeds the adjusted limits. There shall be suitable provision for
warning the operator once the load is tripped off. Electrical overload tripping of the power
tool with visual indication of motor tripping is also acceptable.
d) The electric driven tool shall be single speed, reversible three phase, 415V, 50Hz & hand
operated motor.
e) Manual handle shall be provided for hand operation of the winches in case of power
failure or for minor adjustment of the lantern carriage.
f) For High Mast located in Hazardous Area winch motor shall be of flame proof type
construction suitable for area classification as per attached layouts in Appendix-D
5.2.8 Feeder Pillar
a) Each high mast shall be supplied with one feeder pillar distribution box which shall be
located near it. The feeder pillar box shall be metal enclosed, free standing type, Dust &
Vermin Proof, made out of 2mm thick MS sheet steel, epoxy painted and IP-55 weather
protected. Additional canopy for rain protection shall be provided as an integral part of
feeder pillar distribution box.
b) The feeder pillar shall contain incomer Switch fuse/MCB, ELCB, motor starters for winch
drive, MCB for lighting control and a 3 pin 5/15A socket with 15A MCB. Motor starter
shall be complete with switch fuse, contactor and bimetal relay with single phasing
preventor. Feeder pillar incomer shall have three number LEDS for indication of three
phase power supply. The cable entry shall be from bottom.
c) The power supply to lighting fixtures shall be manual as well as in auto mode. An
Auto/manual/Off selector switch shall be used. In Auto mode the switching operation shall
be controlled though clock timer /photocell controller.
d) Feeder pillar shall have adequate space to receive incoming and outgoing cable
terminations for 415V, TPN supply loop in and loop out arrangement. Adequately rated
space heater with switch fuse, thermostat shall be provided for the feeder pillars. The
feeder pillar box shall be complete with double compression nickel plated brass cable
glands and tinned copper lugs. The feeder pillar shall have two numbers external earthing
terminal.
e) The feeder pillar-box shall have required wiring interface for taking signals from hand
held external control push button station. The feeder pillar box shall be installed on a
raised concrete foundation block and foundation shall be up to the level of minimum
300mm above ground level.
f) Suitable Name plates and danger board shall be provided on the feeder pillar. The feeder
pillar shall be mounted on raised concrete foundation near to the lighting mast structure.
g) For High Mast located in Hazardous Area, feeder Pillar Box shall be of flame proof type
construction suitable for area classification as per attached layouts in Appendix-D
VISAKH MARKETING INSTALLATION RESITEMENT
PROJECT BO / WO / LPG TERMINALS
Doc No: 254625-300-SP-ELE -011 Rev: C Page 12 of 26 ABCABCABCABC
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\04 Electrical\Documents\13 Specifications\High Mast\Rev. C - Issued for
tender\254625-300-SP-ELE-011--Rev C.doc
5.2.9 Local Control Station
Spring return type hand held control pushbutton shall be provided for the purpose- for raising the
lantern carriage and lowering the lantern carriage. Also it shall have emergency stop push button.
The hand held control Push Button station shall be supplied with minimum of 5 meters length of
5*2.5 sq mm flexible cable and cable type shall be with copper conductor, PVC insulation, metal
braiding and overall PVC sheath. The hand held control station and associated cable shall be
kept inside feeder pillar box when not in use and suitable arrangement shall be provided for the
same.
5.2.10 Junction Box
Weather proof junction box made of Cast Aluminium shall be provided on the Carriage
Assembly as required from which the interconnections to the designed number of flood light
luminaries and associated control gears on the lantern carriage.
5.2.11 Cables and Cable Connections
a) All power & control cable including flexible trailing cables shall be supplied, laid &
terminated by high mast vendor.
b) The cable shall be flexible, round, multi-core, copper conductor power cable with 2 Nos
spare cores. The cable shall be suitable sized to ensure proper flow of current & reputed
make
c) The electrical connection from base compartment to the junction box shall be made
through special multicore trailing cable of min 4 sq mm copper conductor, EPR (ethylene
polyethylene rubber) insulated, metal braided and sheathed in heavy duty poly chloroprene
(PCI).
d) Separate core shall be used for lighting fixtures, aviation fixtures and one dedicated core
shall be kept for earthing. Suitable chemicals shall also be added to outer sheath to protect
cable against birds, rodent and termite attack. The cable shall be suitable sized to ensure
proper flow of current & reputed make.
e) Connections from the junction box to individual luminaries shall be made by using 3C x
2.5 sq-mm copper conductor, PVC insulated, armoured and outer flexible PVC sheath
cable. The system shall have in-built facilities for testing the luminaries while in lowered
position.
f) Power cable from the feeder pillar to the base compartment of the lighting mast shall be
taken through the PVC conduit laid in the foundation / shall be laid directly buried
trenches.
g) The trailing cable shall be terminated by means of metal cased plug and socket which shall
be provided at the base compartment to enable easy disconnection. The exposed end of
trailing cable at the top shall be taken in flexible metal conduit. Connection to the power
tool motor inside mast at the bottom shall be through metal cased plug and socket
arrangement to enable easy disconnection.
5.2.12 Lightning final
Lightning protection shall be provided on the high mast. One number heavy duty hot dip
galvanised lightning finial shall be provided for each mast. The lightning finial shall be
minimum 1.2 m in length and shall be provided at the centre of the head frame. It shall be bolted
solidly to the head frame to get a direct conducting path to the earth through the mast. . The
lightning finial shall not be provided on the lantern carriage under any circumstances in view of
safety of the system. Down Lead conductor along with lightning earth pits shall be supplied by
vendor.
VISAKH MARKETING INSTALLATION RESITEMENT
PROJECT BO / WO / LPG TERMINALS
Doc No: 254625-300-SP-ELE -011 Rev: C Page 13 of 26 ABCABCABCABC
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\04 Electrical\Documents\13 Specifications\High Mast\Rev. C - Issued for
tender\254625-300-SP-ELE-011--Rev C.doc
5.2.13 Earthing & Earthing Terminals
a) Suitable earth terminal using 12 mm diameter stainless steel hexagonal head bolts shall be
provided at convenient location at base of the mast for lightning and electrical earthing of
the mast. The mast shall be provided with duplicate earthing including necessary 2 Nos.
earth pits. Earth Pits shall be G.I Pipe electrode type of min. 40mm dia. and shall be as per
IS 3043.
b) The earth resistance of each electrode (earth station) will be measured by an approved earth
testing apparatus and recorded. In case the earth resistance is more than the required
value, additional earth pits, as required shall be made and inter connected by the
contractor. The value of earth resistance for Housing units shall not be more than 5 ohms.
c) The earthing ring shall be made by GI strip / insulated single core cable of specified size.
The ring shall be laid in the cable trench along with lighting cable and connected to all the
earthing pits.
d) The Feeder Pillar shall be provided with two separate earth terminals. An earth busbar of
appropriate cross section shall be provided inside the feeder pillar and connected to the
earth terminals provided on either side of the feeder pillar
Adequate number of holes / terminals shall be provided on earth bus with suitable provision
for terminating the earth wire.
GI strip / GI wire insulated single core cable of suitable size shall be used for earthing by
connecting the two earth terminals separately to the earthing main in the shop / earth pit.
e) The single core PVC insulated wire/ bare copper wire or 14 SWG GI wire and the third
core of the flexible wiring cable shall be used for earthing the light fixtures.
f) Not less than 14 SWG GI wire or suitable size PVC insulated copper wire shall be used
for earthing all metal boxes and brackets.
5.2.14 Hazardous Area Classification
As far as possible, high masts shall be located only in safe areas. If mast is to be installed in
classified areas, construction shall be suitable for applicable area classification. Hazardous area
masts shall comply to construction requirements of IS 5572.
5.3 Name Plates
5.3.1 Permanent non-corrosive nameplate with engraved white letters on black background indicating
the High Mast lighting system designation shall be fixed. The nameplate shall indicate the
following :
First line : Equipment Item No.
Second line : Equipment Description
Nameplates shall be provided for each equipment (lamps, Local control stations, winch drive,
starter, feeder pillar box etc.) mounted on the High mast. Danger labels shall have black letters
on a yellow background.
5.4 Makes of Components
5.4.1 Manufacturer shall furnish standard list of components makes for the complete the High Mast
Lighting system. This list must be included with the offer.
5.4.2 Preferred Make of Components shall be
• High Mast : Philips/ Crompton /Bajaj
• Lighting fixture & lamps : Philips/ Crompton / Bajaj
VISAKH MARKETING INSTALLATION RESITEMENT
PROJECT BO / WO / LPG TERMINALS
Doc No: 254625-300-SP-ELE -011 Rev: C Page 14 of 26 ABCABCABCABC
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\04 Electrical\Documents\13 Specifications\High Mast\Rev. C - Issued for
tender\254625-300-SP-ELE-011--Rev C.doc
• Feeder Pillar : Reputed Make
• Contactors : Siemens/ABB/ L&T
• Selector Switch : Kaycee / Recom
• Fuse/Link : Siemens/GE
• Timer : L & T /Siemens
• Push button / Local control station : Siemens/L&T
• Switch/MCB : Siemens/MDS
• Terminals : Elmex / Connectwell
• PVC insulated Copper wires : Polycab / Finolex
Items for which preferred makes are not indicated shall be procured only after approval of the make
by owner/consultant
5.5 Painting
5.5.1 All metal surfaces shall be thoroughly cleaned and degreased, pickled and phosphatised.
Thereafter, a coat of phosphate paint and a coat of zinc chromate primer shall be applied. After
removing all imperfections, all metal surfaces shall be sprayed with two coats of final paint as
per colour shade Silver grey No. 628 (IS-5). Final coat shall be of epoxy based heavy duty finish
coat. All unpainted parts shall be plated to prevent corrosion.
5.6 Civil Structural Work
The scope of work includes design, detailing, supply and construction of foundations for high
mast & feeder pillar works for Black Oil Terminal. The work shall in general be executed as per
IS and all referred codes herein.
5.6.1 Materials
i) Cement
The cement used shall be any one of the following unless otherwise specified in project data
sheet:
• 33 Grade ordinary Portland cement conforming to IS 269 : 1989
• 43 Grade ordinary Portland cement conforming to IS: 8112. : 1989
• Portland slag cements conforming to IS 455: 1989.
• Sulphate resisting Portland cement conforming to IS 12330:1988.
ii) Aggregates
• Only natural existing aggregates conforming to IS 383: 1989 shall be used.
• Coarse aggregate shall be 20mm down graded as per IS 383: 1989.
• Fine aggregate shall be graded evenly from fine to coarse as per Zones II and III of IS: 383.
Zone IV aggregate shall not be used.
iii) Water
Water used for manufacture and curing of concrete shall be clean and free from injurious
amounts of oils, acids, alkalis, salts, sugar, organic materials or other substances that may be
deleterious to concrete or steel as specified in IS 456: 2000. Potable water shall be considered
satisfactory
iv) Chemical Admixtures
VISAKH MARKETING INSTALLATION RESITEMENT
PROJECT BO / WO / LPG TERMINALS
Doc No: 254625-300-SP-ELE -011 Rev: C Page 15 of 26 ABCABCABCABC
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\04 Electrical\Documents\13 Specifications\High Mast\Rev. C - Issued for
tender\254625-300-SP-ELE-011--Rev C.doc
• Chemical admixtures, if used, shall conform to IS 9103: 1999.
• Criteria of use of chemical admixtures shall be as per IS 456: 2000.
v) Reinforcing Steel
• Only high strength deformed steel bars of grade Fe-415 conforming to IS 1786: 2000 shall be
used.
• Minimum diameter of main reinforcing bars in foundation and pedestal shall be 12mm. Links
shall be of minimum 8mm diameter
vi) Anchor / Foundation Bolts
Mild steel bars for turning anchor bolts shall conform to IS 432 : 1982 Grade 1 and/or IS: 2062
Grade A. Nuts shall conform to IS 1363 : 2002, IS 1367 : 2002 and IS:3138: 1966
vii) Grout
Premix free-flow non-shrink cementations grout, with a minimum compressive strength of
40N/mm2 at 28 days, shall be used.
5.6.2 Concrete
The concrete shall be design mix of min. grade M25 and other requirements as mentioned in
project data sheet. 75mm thick lean concrete shall be provided under the structural foundation of
proportion 1:4:8 using 40mm down aggregates. The mud mat of lean concrete shall project
75mm beyond all sides of the structural foundation slab.
5.6.3 Design of Foundation
a) The foundation shall be placed minimum 2.0 metres below Finished Grade Level (FGL)
or Natural Ground Level (NGL), whichever is lower.
b) Ground water table shall be considered at FGL/NGL, whichever is higher.
c) Factor of safety against overturning and sliding shall be considered as 2.0 and 1.5,
respectively. Only 50% of the overburden weight of backfilled soil over base slab of the
foundation shall be accounted for checking of over-turning and sliding. All design
parameters for foundation shall be as per IS:456 and referred BIS codes. Limit state
method shall be used.
d) Safe Bearing capacity of Soil (SBC) shall be as per the Data sheet/Soil investigation
report.
5.6.4 Loadings
Loading in general shall be as per IS: 875. The basic wind speed shall be as per the Project/site
location and as called for in IS: 875. k1 and k2 factors shall be unity. k3 shall be appropriate to
topography but not less than 1.22 for Black Oil Terminal.
6 Inspection, Testing and Acceptance at works
6.1 During fabrication, the High mast lighting system shall be subject to inspection by
Owner/Consultant, or by an agency authorized by the Owner, to assess the progress of work, as
well as to ascertain that only proven raw material is used. The manufacturer shall furnish all
necessary information /data concerning the supply to Owner’s/Consultant’s inspectors. The
vendor shall give at least 15 days notice to the purchaser regarding the date of testing to enable
him or his representative to witness the tests
VISAKH MARKETING INSTALLATION RESITEMENT
PROJECT BO / WO / LPG TERMINALS
Doc No: 254625-300-SP-ELE -011 Rev: C Page 16 of 26 ABCABCABCABC
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\04 Electrical\Documents\13 Specifications\High Mast\Rev. C - Issued for
tender\254625-300-SP-ELE-011--Rev C.doc
6.2 Tests shall be carried out at the manufacturer's works under his care and expense. All routine
tests as specified by the applicable standard codes shall be conducted. Type test certificates for
the high mast lighting system equipments used shall be furnished of a recognized testing
organization.
6.3 Routine Test shall be carried out on motor for winch drive.
6.4 All tests shall be conducted as per relevant applicable standards. Vendor shall furnish valid Type
Test Certificates of similar models along with the offer. Fresh type tests for the equipment are
not needed, provided the Manufacturer can submit certificates that the equipment complies with
all type tests as prescribed by IEC/IS Standard specifying the test requirements for that
equipment.
VISAKH MARKETING INSTALLATION RESITEMENT
PROJECT BO / WO / LPG TERMINALS
Doc No: 254625-300-SP-ELE -011 Rev: C Page 17 of 26 ABCABCABCABC
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\04 Electrical\Documents\13 Specifications\High Mast\Rev. C - Issued for
tender\254625-300-SP-ELE-011--Rev C.doc
7 Vendor Documentation
7.1 All information listed below is to be furnished along with the offer as a minimum
(a) Clause wise comments / deviations on specification in `Table of Compliance’ [enclosed
Appendix A]. If not furnished, compliance to all requirements in specifications will be
binding on the Vendor.
(b) Typical drawing of proposed decorative type High Mast with Umbrella.
(c) The layout of High Masts, Feeder Pillar. Lighting fixtures showing the illumination level
for the area.
(d) Lighting calculation based on average illumination level of 20lux & Min. of 12 lux for high
mast lighting system for Black oil, White Oil & LPG terminals.
(e) Duly filled up Guaranteed Technical Particulars [enclosed Appendix-D].
(f) List of major components with Makes.
(g) List of recommended spares for two years normal operation with itemised rates.
(h) Type test certificates.
(i) Technical Catalogues.
(j) List of clientele for similar equipment in last 5 years.
(k) Complete list of special tools (if required)
(l) Documents as per RED Form.
7.2 The Manufacturer shall furnish the drawings and documents as per enclosed Requisition for
Engineering Documents - RED Form [Appendix-C].
7.3 The Owner/Consultant will review drawings submitted by Vendor & return to the Vendor one
copy of drawings with comments to carry out necessary changes, if any, during the engineering
/ manufacturing stage.
7.4 The documents required by the Third Party Inspection Agency are not covered under this
specification. The Vendor shall provide all the drawings and documents required by the Third
Party Inspection agency in compliance with the applicable codes and standards.
8 Statutory Approval
The High Mast supplied shall be acceptable to local Electrical Inspectorate and changes
required, if any, shall be carried out by the vendor without any extra cost. Vendor to ensure that
the maximum height of high mast clearance from concerned statutory authority before
procurement & execution of work.
.
VISAKH MARKETING INSTALLATION RESITEMENT
PROJECT BO / WO / LPG TERMINALS
Doc No: 254625-300-SP-ELE -011 Rev: C Page 18 of 26 ABCABCABCABC
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\04 Electrical\Documents\13 Specifications\High Mast\Rev. C - Issued for
tender\254625-300-SP-ELE-011--Rev C.doc
Appendix-A: Table of Compliance
The Vendor shall confirm that clauses of the specification have been complied with/accepted or further
clarifications are desired, or Vendor has taken a deviation with reason thereto.
CLIENT :
M/s. Hindustan Petroleum Corporation Ltd.
Black Oil Terminal Project
VENDOR REF.
Spec. Clause
No.
Conforms
Yes/No
Alternative
Yes/No Clarification
1
2
3
4
5
5.1
5.2
5.2.1
5.2.2
5.2.3
5.2.4
5.2.5
5.2.6
5.2.7
5.2.8
5.2.9
5.2.10
5.2.11
5.2.12
5.2.13
5.2.14
5.3
5.4
5.5
5.6
VISAKH MARKETING INSTALLATION RESITEMENT
PROJECT BO / WO / LPG TERMINALS
Doc No: 254625-300-SP-ELE -011 Rev: C Page 19 of 26 ABCABCABCABC
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\04 Electrical\Documents\13 Specifications\High Mast\Rev. C - Issued for
tender\254625-300-SP-ELE-011--Rev C.doc
CLIENT :
M/s. Hindustan Petroleum Corporation Ltd.
Black Oil Terminal Project
VENDOR REF.
Spec. Clause
No.
Conforms
Yes/No
Alternative
Yes/No Clarification
6
7
8
Appendix A:
Appendix B:
Appendix C:
Appendix D:
Appendix E:
VISAKH MARKETING INSTALLATION RESITEMENT
PROJECT BO / WO / LPG TERMINALS
Doc No: 254625-300-SP-ELE -011 Rev: C Page 20 of 26 ABCABCABCABC
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\04 Electrical\Documents\13 Specifications\High Mast\Rev. C - Issued for
tender\254625-300-SP-ELE-011--Rev C.doc
Appendix-B: Codes & Standards
IS 6665 : 1972 : Code of practice for Industrial lighting
IS 10322 : Luminaries –Part 1: General requirements
IS 5216-1982 : Guide for safety procedures and practice in electrical
work
IS 325 : 1996 : Three Phase Induction Motors
IS-4691 : 1985 Degree of protection provided by enclosure for
rotating electrical machinery
IS 732 : 1982 : Code of practice for electrical wiring installation
IS 2667-1988 : Fittings for rigid steel conduits for electrical wiring
IS 9537
Part 1 – 1980
Part 2 – 1981
Part 3 – 1983
Part 4 – 1983
Reaffirmed 1990
: Conduits for Electrical installation
General requirements
Rigid steel conduits
Rigid plain conduits of insulating material
Pliable self recovering
Conduits
IS 694 : 1990 PVC insulated cables for working voltages up to &
including 1100 volts.
IS 9046 : 1978 : AC contactors of voltage above 1000 V upto and
including 11000 V.
IS 1554 :1988 : PVC Insulated (heavy duty) electrical cables : Part I
for working voltages up to & including 1100V
IS 4289 : Flexible cables for lifts and other flexible
connections-Part 1 Elastomer Insulated Cables
IS 3618 : Phosphate treatment of iron and steel for protection
against corrosion
IS 2675 : Enclosed distribution fuse boards and cut outs for
voltages not exceeding 1000 volts
IS 13947 : 1993
Low voltage switchgear and control gear: General
rules
IS 3043 : 1987 : Code of practice for Earthing
IS 2309 : 1989 : Code of practice for the protection of buildings and
allied structures against lightning.
IS 2551-1982
First Rev. Reaffirmed 1990
: Danger boards
I. E Rules : Indian Electricity rules-1956
• In case of imported equipment standards of the country of origin shall be applicable, if these
standards are equivalent or stringent than the applicable Indian standards.
VISAKH MARKETING INSTALLATION RESITEMENT
PROJECT BO / WO / LPG TERMINALS
Doc No: 254625-300-SP-ELE -011 Rev: C Page 21 of 26 ABCABCABCABC
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\04 Electrical\Documents\13 Specifications\High Mast\Rev. C - Issued for
tender\254625-300-SP-ELE-011--Rev C.doc
• In case Indian standards are not available for any equipment, standards issued by IEC/BS/
VDE/ IEEE/NEMA or equivalent agency shall be applicable.
• In case of any contradiction between various referred standards/specifications/data sheet and
statutory regulations the following order of priority shall govern:
a) Statutory regulations
b) Project data sheets
c) Job specification
d) This specification
e) Codes and standards
VISAKH MARKETING INSTALLATION RESITEMENT
PROJECT BO / WO / LPG TERMINALS
Doc No: 254625-300-SP-ELE -011 Rev: C Page 22 of 26 ABCABCABCABC
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\04 Electrical\Documents\13 Specifications\High Mast\Rev. C - Issued for
tender\254625-300-SP-ELE-011--Rev C.doc
Appendix-C: Requisition for Engineering Documents
RED Form
Owner’s Office Distribution Office
M/s. Hindustan Petroleum Corporation Ltd.
Viskaha Dispatch Station
VR-ATP Area, Naval Base Post
Visakhapatnam – 530 014
Mott MacDonald Consultants(I) Pvt. Ltd
Kothari House, CTS No. 185
Off Andheri – Kurla Road
Andheri ( East), Mumbai 400059, India
SPECIAL INSTRUCTIONS Prints Documents shall be sent to:
Production Schedule 5 The Purchasing Office via courier service
Manufacturing, inspection & testing sequence plan 5 The Purchasing Office via courier service
DRAWINGS Required number for TIMING FOR SUBMITTAL
OFFER APPROVAL FINAL - for approval 2 weeks after order date
Approval drawings / Final drawings to be submitted
under cover of an ADS form / FDS form respectively
Prints Prints Disk Prints - final issue 2 weeks after approval date
Documents shall be submitted to:
Submission of Following not limited to:
Guaranteed Technical Particulars dully filled up( Refer
Appendix-D)
2
Layout drawing with location of mast on plot plan 2 5 2 10
General Arrangement Drawing of mast with umbrella,
Fixing bolt detail.
2 5 2 10
Light fitting catalogues 2 5 2 10
Name Plate Drawing 5 2 10
Foundation Loading Plan along with support reactions
at underside of base plate, Self Wt/dead load of lamp
post high mast, Wind base shear in ton & Wind base
moment in T.m
5 2 10
Bill of material for total system 2 5 2 10
Details of winch, wire rope, lantern carriage, junction
box.
5 2 10
SLD, GA diagram, fixing details and circuit diagram of
feeder pillars.
5 2 10
Main & Control Circuit Schematic Diagrams for all
motors
5 2 10
Design calculations & report 2 5 2 10
Make of Each Components 2 5 2 10
Type Test, Routine Test Certificates for :
• Steel plates used for fabrication of mast
• Steel wire rope
• Winch
• Hot dip galvanising
2 5 2 10
Operating manuals, incorporating installation,
commissioning, operating & maintenance instructions
and fault finding procedures
5 2 10
Spares List for two Years Operation 2 5 2 10
As Built Drawing 5 2 10 Purchasing Office via courier service
SPARE PARTS DOCUMENTS 2 10 ESPIR forms including 1 transparency
TEST AND INSPECTION DOCUMENTS Prints
Documents to be submitted under transmittal Documents shall be submitted to:
Manufacturing report 2 10
Test Report / Data Curves 2 10
Calibration Certificates for testing Instruments. 2 10 Purchasing Office via courier service within 4 weeks
Bought out Equipments Certificates. 2 10 Of relevant test / inspection.
OPERATING DOCUMENTS Purchasing Office via courier service not later than time
of Dispatch of equipment.
Installation instructions 2 10
Operating instructions 2 10 Combine into one manual
VISAKH MARKETING INSTALLATION RESITEMENT
PROJECT BO / WO / LPG TERMINALS
Doc No: 254625-300-SP-ELE -011 Rev: C Page 23 of 26 ABCABCABCABC
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\04 Electrical\Documents\13 Specifications\High Mast\Rev. C - Issued for
tender\254625-300-SP-ELE-011--Rev C.doc
Maintenance instructions 2 10
ADDITIONAL REQUIREMENTS
1. Referenced standards / codes shall be the latest issue unless otherwise stated.
REMARKS
Invoice must certify that the drawings and engineering documents specified
above have been dispatched to all parties concerned.
Any deviation from the timing for submittal of documents shall be notified
to the Approval / Distribution Offices by fax or E mail.
Shop fabrication shall not be started before the required approval drawings
have been released for construction by the party concerned, unless
otherwise stated on the "Approval Drawing Specification".
Each document shall bear the item / tag and order reference number and be
dispatched by air mail, unless other instructions are stated on the RED.
Units / dimensions to be used on Engineering documents shall be SI.
The documents shall be in English. Description on drawings and similar documents
may be in other languages provided English translations are also given.
Drawings and documents shall be suitable for microfilming and comply with
accepted national or international standards for the preparation of technical
drawings. Only the following standard sizes should be used: A4, A3, A2, and A1.
VISAKH MARKETING INSTALLATION RESITEMENT
PROJECT BO / WO / LPG TERMINALS
Doc No: 254625-300-SP-ELE -011 Rev: C Page 24 of 26 ABCABCABCABC
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\04 Electrical\Documents\13 Specifications\High Mast\Rev. C - Issued for
tender\254625-300-SP-ELE-011--Rev C.doc
Appendix-D: Guaranteed Technical Particulars
[Doc. No. 254625-300-DS-ELE-011]
VISAKH MARKETING INSTALLATION REISTEMENT
PROJECT BLACK OIL,WHITE OIL & LPG TERMINALS
Doc No:254625-300-DS-ELE-011 Rev: C Page 1 of 2 ABCABCABCABC
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\04 Electrical\Documents\13 Specifications\High Mast\Rev. C - Issued for
tender\254625-300-DS-ELE-011-Rev C.doc
Appendix D: GUARANTEED TECHNICAL PARTICULARS
(Vendor to Furnish filled in data for Black Oil, White Oil & LPG Terminals Separately)
Sr.
No Description Unit To be filled in by Vendor
1. Make of High Mast
2. Overall Height of the mast with respect to
FGL Mtr.
3. Quantity of Lighting Mast considered No.
4. No. of Section per High mast No.
5. Length of Individual Sections Mtr.
6. Type of joints
7. Weight of the Mast Kgs.
8. Max. wind speed & gust considered for design
9. Mounting HT for Light Fittings Mtr.
10.
Type of Light Fittings with catalogue number
& Make
11. No. of lighting fixtures considered per lighting
mast No.
12. Wattage of each light Fitting W
13.
List of Equipment mounted on Lantern
carriage
14. Aviation Lights provided Yes / No
15. Location of Aviation Lights
16. Type of Maintenance facility provided for
Aviation Lights
17. Lightning protection provided Yes / No
18 No. and dimension of Steel wire ropes
19. Breaking load of wire rope
20. Make of winch
21. Capacity rating and speed of winch motor Volts / kW /
Rpm
22. Material of Head Frame
23. Feeder Pillar
• Degree Of Protection
• Painting Shade
• Incomer Switch & Its Rating
• Motor starter provided? Yes/No
• Feeder Pillar Support Provided? Yes/No
VISAKH MARKETING INSTALLATION REISTEMENT
PROJECT BLACK OIL,WHITE OIL & LPG TERMINALS
Doc No:254625-300-DS-ELE-011 Rev: C Page 2 of 2 ABCABCABCABC
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\04 Electrical\Documents\13 Specifications\High Mast\Rev. C - Issued for
tender\254625-300-DS-ELE-011-Rev C.doc
Sr.
No Description Unit To be filled in by Vendor
• Location of Feeder Pillar
24. Data required for design of Foundation
• Vertical load
• Load due to Tension
• Moment /lateral Load if any
VISAKH MARKETING INSTALLATION RESITEMENT
PROJECT BO / WO / LPG TERMINALS
Doc No: 254625-300-SP-ELE -011 Rev: C Page 25 of 26 ABCABCABCABC
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\04 Electrical\Documents\13 Specifications\High Mast\Rev. C - Issued for
tender\254625-300-SP-ELE-011--Rev C.doc
Appendix-E: Overall High Mast Lighting Layouts & Hazardous Area Classification
drawings for Black oil, White Oil & LPG Terminals
Drawings for Overall High Mast Lighting:
i) 254625-300-ELE-4605……..Black Oil Terminal
ii) 254624-400-ELE-4604……..White Oil Terminal
iii) 256324-500-ELE-4604……..LPG Terminal
Drawings for Hazardous Area Classification:
i) 254625-300-PIP-A0-3001……..Black Oil Terminal
ii) 254624-400-PIP-A0-3001……..White Oil Terminal
iii) 256324-500- PIP-A0-3050……..LPG Terminal
VISAKH MARKETING INSTALLATION RESITEMENT
PROJECT BO / WO / LPG TERMINALS
Doc No: 254625-300-SP-ELE -011 Rev: C Page 26 of 26 ABCABCABCABC
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\04 Electrical\Documents\13 Specifications\High Mast\Rev. C - Issued for
tender\254625-300-SP-ELE-011--Rev C.doc
Appendix-F: i) SOQ for Black Oil Terminal
ii) SOQ for White Oil Terminal
iii) SOQ for LPG Terminal
{Document No.: i) 254625-300-SC-ELE-011
ii) 254624-400-SC-ELE-011
iii) 256324-500-SC-ELE-011 }
Mott MacDonald Consultants (India) Pvt. Ltd. Hindustan Petroleum Corporation Ltd
Kothari House, CTS No. 185 Visakha Dispatch Station
Off Andheri - Kurla Road VR-ATP Area, Naval Base Post
Andheri (East) Visakhapatnam - 530 014
Mumbai - 400 059 Andhra Pradesh
SCHEDULE OF QUANTITIES
SUPPLY OF HIGH MASTS SYSTEM
VISAKH MARKETING INSTALLATION RESITEMENT
PROJECT - BLACK OIL TERMINAL
Rev: CDoc No:254625-300-SC-ELE-011
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\04 Electrical\Documents\13 Specifications\High Mast\Rev. C - Issued for tender\Black Oil --SOQ for High
Mast Lighting System--RevC Page 1 of 6
%Amount
Rs.%
Amount
Rs.
1 2 3 4 5 9 10 11
Design, Engineering, Preparation of
Drawings, Fabrication, Assembly,
painting, Inspection at Manufacturers
work,supply & Delivery to site, Erection,
Testing & Commissioning with lighting
fixures, accessories, including supply of
fixures cable, Earthing Material &
Lightning finaletc. inclusive of civil &
structural foundation of the following of
High Mast Lighting System as per scope
for Black oil terminal mentioned in the
specification: 254625-300-SP-ELE-011
1
Decorative type High mast system: Mast
shall be with decorative umbrella, in two
sections, hot dip galvanised and suitable
for wind velocity as per IS:875, part-3. It
shall also include accessories for high
mast including head frame, steel wire
rope double drum winch, galvanised
lantern carriage arrangement suitable for
required no. of luminaires, its control gear
boxes & junction boxes, aviation
obstruction light, Feeder Pillar Boxes,
lightning finial,Cables & Cable
Connections,cable gland,earthing&
Lightning system including Earthpits as
pere IS 3043 . The mast shall have an
integral power tool for its operation. ( Qty.-
Black Oil Terminal 11 Nos. + 2 Nos. for
External Tank Truck Parking Area) The
scope also includes following:
Nos. 13
VISAKH MARKETING INSTALLATION RESITEMENT
PROJECT - BLACK OIL TERMINAL
Doc No:254625-300-SC-ELE-011 Rev: C
Unit Qty
Sales TaxTotal Amount (F.O.R.
Site Total Price)
(4 x 10),
Rs.
An
y O
the
r L
ev
y
Fre
igh
t F
OR
Sit
e
Un
loa
din
g a
nd
Sta
ck
ing
at
sit
e
SUPPLY OF HIGH MAST SYSTEM : SCHEDULE OF QUANTITIES, UNITS AND PRICES
Unit Rate for
Supply Ex.
including
Packaging &
Forwarding
Rs.
6 7
Total F.O.R. Site Unit
Price (5+6+7+8+9).
Rs.
8
Excise duty
Sl.
No.Description
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\04 Electrical\Documents\13 Specifications\High Mast\Rev. C - Issued for tender\Black Oil --SOQ for High Mast Lighting System--RevC Page 3 of 6
%Amount
Rs.%
Amount
Rs.
1 2 3 4 5 9 10 11
VISAKH MARKETING INSTALLATION RESITEMENT
PROJECT - BLACK OIL TERMINAL
Doc No:254625-300-SC-ELE-011 Rev: C
Unit Qty
Sales TaxTotal Amount (F.O.R.
Site Total Price)
(4 x 10),
Rs.
An
y O
the
r L
ev
y
Fre
igh
t F
OR
Sit
e
Un
loa
din
g a
nd
Sta
ck
ing
at
sit
e
SUPPLY OF HIGH MAST SYSTEM : SCHEDULE OF QUANTITIES, UNITS AND PRICES
Unit Rate for
Supply Ex.
including
Packaging &
Forwarding
Rs.
6 7
Total F.O.R. Site Unit
Price (5+6+7+8+9).
Rs.
8
Excise duty
Sl.
No.Description
- Design, detailing,supply & construction
of foundation for Highmast & feeder pillar
along with Supports. Foundation bolts
manufactured from special steel along
with nuts, washers, anchor plates and
templates.
- Aviation obstruction lighting fixture
with 2 Nos. of 40w neon lamps. (1 fitting
per mast is necessary if no taller
structures are in near vicinity).
- Outdoor Feeder Pillar box with canopy
for rain water protection confirming to
IP:55 which housing suitable Motor starter
with switch fuse,Contactor & bimetal relay
with single phasing preventor,
timercontactor circuit for automatic switch
on and switch off of the mast of a pre-set
time, Auto/Manual/ off selector switch and
necessary control MCB. The cable entry
shall be from Bottom.Feeder pillar support
& foundation for mounting shall be
included
Nos. 13
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\04 Electrical\Documents\13 Specifications\High Mast\Rev. C - Issued for tender\Black Oil --SOQ for High Mast Lighting System--RevC Page 4 of 6
%Amount
Rs.%
Amount
Rs.
1 2 3 4 5 9 10 11
VISAKH MARKETING INSTALLATION RESITEMENT
PROJECT - BLACK OIL TERMINAL
Doc No:254625-300-SC-ELE-011 Rev: C
Unit Qty
Sales TaxTotal Amount (F.O.R.
Site Total Price)
(4 x 10),
Rs.
An
y O
the
r L
ev
y
Fre
igh
t F
OR
Sit
e
Un
loa
din
g a
nd
Sta
ck
ing
at
sit
e
SUPPLY OF HIGH MAST SYSTEM : SCHEDULE OF QUANTITIES, UNITS AND PRICES
Unit Rate for
Supply Ex.
including
Packaging &
Forwarding
Rs.
6 7
Total F.O.R. Site Unit
Price (5+6+7+8+9).
Rs.
8
Excise duty
Sl.
No.Description
- 2x 400w (SON-TP) HPSV Non-integral
Flood light fitting suitable for highmast
lighting with control gear boxes,
Asymmetrical distribution, electro
chemically brightened, polished and
anodised aluminium reflector, heat
resistant, clear, toughened glass cover
hinged to the housing with rubber gaskets
and stainless steel toggles. The Light
fittings shall be Philips make Ref. No.:
MVF480 NB 2xSON-TP 400w or
equivallent
Nos. 117
3 Spares for 2 years normal operation Lot 1
Note:1.List of spares along with item wise price shall be submitted separately in sealed cover
TOTAL -(1+2+3)
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\04 Electrical\Documents\13 Specifications\High Mast\Rev. C - Issued for tender\Black Oil --SOQ for High Mast Lighting System--RevC Page 5 of 6
Unit Rate
RsTotal Rs
1 3 4 5 6
1 Nos 13
No. 117
- 2x 400w (SON-TP) HPSV Non-integral Flood light fitting
suitable for highmast lighting with control gear boxes. The
Light fittings shall be Philips make Ref. No.: MVF480 NB
2xSON-TP 400w or equivallent
- construction of foundation for Highmast & feeder pillar
along with Supports & Foundation bolts manufactured from
special steel along with nuts, washers, anchor plates and
templates.
- Suitable foundation with m-25 concrete for the high mast
considering the safe soil bearing capacity.
High mast system with its accessories. High Mast
foundation shall be included The scope also includes
following.
- Aviation obstruction lighting fixture with 2 Nos. of 40w
neon lamps. (1 fitting per mast is necessary if no taller
structures are in near vicinity).
VISAKH MARKETING INSTALLATION RESITEMENT
PROJECT - BLACK OIL TERMINAL
Doc No:254625-300-SC-ELE-011 Rev: C
2
Unit Qty
CIVIL WORKS, INSTALLATION AND COMMISSIONING OF HIGH MASTS
SCHEDULE OF QUANTITIES, UNITS AND PRICES
CIVIL WORKS, INSTALLTION,
TESTING & COMMISSIONINGSl.
No.Description
- Pipe earthing station for high mast (2 per mast is
mandatory) with min.40mm dia as per IS 3043 connecting
GI earth strips upto earth stations and interconnection of
earth station,painting etc., including supply of all materials as
per specification.
Receipt ,storage and transportation to the place of erection
at site ,assembling,cabling, erection, testing, commissioning
and final painting of the High masts , structures,fastners,
handling, labour, consumables and erection &
commissioning spares as per specifications and drawings.
- Cabling from feeder pillar to light fitting including supply
of required cables,associated cable glands and GI pipes.
- Outdoor Feeder Pillar distribution board with canopy .
Feeder pillar support & foundation for mounting shall be
included
C
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\04 Electrical\Documents\13 Specifications\High Mast\Rev. C - Issued for tender\Black Oil --SOQ for High Mast Lighting System--RevC Page 6 of 6
Mott MacDonald Consultants (India) Pvt. Ltd. Hindustan Petroleum Corporation Ltd
Kothari House, CTS No. 185 Visakha Dispatch Station
Off Andheri - Kurla Road VR-ATP Area, Naval Base Post
Andheri (East) Visakhapatnam - 530 014
Mumbai - 400 059 Andhra Pradesh
SCHEDULE OF QUANTITIES
SUPPLY OF HIGH MASTS SYSTEM
VISAKH MARKETING INSTALLATION RESITEMENT
PROJECT - WHITE OIL TERMINAL
Rev: CDoc No:254624-400-SC-ELE-011
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\04 Electrical\Documents\13 Specifications\High Mast\Rev. C - Issued for tender\White Oil - SOQ for High
Mast Lighting System--RevC Page 1 of 6
%Amount
Rs.%
Amount
Rs.
1 2 3 4 5 9 10 11
Design, Engineering, Preparation of
Drawings, Fabrication, Assembly,
painting, Inspection at Manufacturers
work,supply & Delivery to site, Erection,
Testing & Commissioning with lighting
fixures, accessories, including supply of
fixures cable,Earthing Material & lightning
final etc.inclusive of required foundation
bolts & nuts for the following of High Mast
Lighting System as per scope for
mentioned in the specification: 254625-
300-SP-ELE-011
1 Decorative type High mast system: Mast
shall be with decorative umbrella, in two
sections, hot dip galvanised and suitable
for wind velocity as per IS:875, part-3. It
shall also include accessories for high
mast including head frame, steel wire
rope double drum winch, galvanised
lantern carriage arrangement suitable for
required no. of luminaires, its control gear
boxes & junction boxes, aviation
obstruction light, Feeder Pillar Boxes,
lightning finial,Cables & Cable
Connections, cable gland,earthing&
Lightning system including Earthpits as
pere IS 3043 . The mast shall have an
integral power tool for its operation. The
scope also includes following:
Nos. 23
SUPPLY OF HIGH MAST SYSTEM : SCHEDULE OF QUANTITIES, UNITS AND PRICES
VISAKH MARKETING INSTALLATION RESITEMENT
PROJECT - WHITE OIL TERMINAL
Doc No:254624-400-SC-ELE-011 Rev: C
Sales TaxTotal Amount (F.O.R.
Site Total Price)
(4 x 10),
Rs.
An
y O
the
r L
ev
y
Fre
igh
t F
OR
Sit
e
Un
loa
din
g a
nd
Sta
ck
ing
at
sit
e
Sl.
No.Description Unit Qty
Unit Rate for
Supply Ex.
including
Packaging &
Forwarding
Rs.
6 7
Total F.O.R. Site Unit Price
(5+6+7+8+9).
Rs.
8
Excise duty
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\04 Electrical\Documents\13 Specifications\High Mast\Rev. C - Issued for tender\White Oil - SOQ for High Mast Lighting System--RevC Page5 of 6
%Amount
Rs.%
Amount
Rs.
1 2 3 4 5 9 10 11
SUPPLY OF HIGH MAST SYSTEM : SCHEDULE OF QUANTITIES, UNITS AND PRICES
VISAKH MARKETING INSTALLATION RESITEMENT
PROJECT - WHITE OIL TERMINAL
Doc No:254624-400-SC-ELE-011 Rev: C
Sales TaxTotal Amount (F.O.R.
Site Total Price)
(4 x 10),
Rs.
An
y O
the
r L
ev
y
Fre
igh
t F
OR
Sit
e
Un
loa
din
g a
nd
Sta
ck
ing
at
sit
e
Sl.
No.Description Unit Qty
Unit Rate for
Supply Ex.
including
Packaging &
Forwarding
Rs.
6 7
Total F.O.R. Site Unit Price
(5+6+7+8+9).
Rs.
8
Excise duty
- Aviation obstruction lighting fixture
with 2 Nos. of 40w neon lamps. (1 fitting
per mast is necessary if no taller
structures are in near vicinity).
- Outdoor Feeder Pillar box with
canopy for rain water protection
confirming to IP:55 which housing
suitable Motor starter with switch
fuse,Contactor & bimetal relay with single
phasing preventor, timercontactor circuit
for automatic switch on and switch off of
the mast of a pre-set time,
Auto/Manual/Off selector switch and
necessary control MCB . The cable entry
shall be from Bottom.Feeder pillar base
frame & neccessary accessories to mount
feeder pillar on piles.
Note: Piles shall be provided by Owner
Nos. 23
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\04 Electrical\Documents\13 Specifications\High Mast\Rev. C - Issued for tender\White Oil - SOQ for High Mast Lighting System--RevC Page6 of 6
%Amount
Rs.%
Amount
Rs.
1 2 3 4 5 9 10 11
SUPPLY OF HIGH MAST SYSTEM : SCHEDULE OF QUANTITIES, UNITS AND PRICES
VISAKH MARKETING INSTALLATION RESITEMENT
PROJECT - WHITE OIL TERMINAL
Doc No:254624-400-SC-ELE-011 Rev: C
Sales TaxTotal Amount (F.O.R.
Site Total Price)
(4 x 10),
Rs.
An
y O
the
r L
ev
y
Fre
igh
t F
OR
Sit
e
Un
loa
din
g a
nd
Sta
ck
ing
at
sit
e
Sl.
No.Description Unit Qty
Unit Rate for
Supply Ex.
including
Packaging &
Forwarding
Rs.
6 7
Total F.O.R. Site Unit Price
(5+6+7+8+9).
Rs.
8
Excise duty
- 2x 400w (SON-TP) HPSV Non-integral
Flood light fitting suitable for highmast
lighting with control gear boxes,
Asymmetrical distribution, electro
chemically brightened, polished and
anodised aluminium reflector, heat
resistant, clear, toughened glass cover
hinged to the housing with rubber gaskets
and stainless steel toggles. The Light
fittings shall be Philips make of ef. No.:
MVF480 NB 2xSON-TP 400w or
equivallent
Nos. 207
3 Spares for 2 years normal operationLot 1
Note:1.List of spares along with item wise price shall be submitted separately in sealed cover
TOTAL -(1+2+3)
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\04 Electrical\Documents\13 Specifications\High Mast\Rev. C - Issued for tender\White Oil - SOQ for High Mast Lighting System--RevC Page7 of 6
Unit Rate
RsTotal Rs
1 3 4 5 6
1
Nos 23
Nos. 207
- 2x 400w (SON-TP) HPSV Non-integral Flood light fitting
suitable for highmast lighting with control gear boxes. The
Light fittings shall be Philips make Ref. No.: MVF480 NB
2xSON-TP 400w or equivallent
High mast system with its accessories.High Mast base Plate
& neccessary accessories to mount Mast on piles.
Note: Piles shall be provided by Owner
The scope also includes installation & Commissioning of
following.
- Aviation obstruction lighting fixture with 2 Nos. of 40w
neon lamps. (1 fitting per mast is necessary if no taller
structures are in near vicinity).
- Pipe earthing station for high mast (2 per mast is
mandatory ) with min.40 mm dia as per IS 3043 connecting
GI earth strips upto earth stations and interconnection of
earth station,painting etc., including supply of all materials
- Cabling from feeder pillar to light fitting including supply
of required cables,associated cable glands and GI pipes.
- Outdoor Feeder Pillar box with canopy.Feeder pillar
base frame & neccessary accessories to mount feeder pillar
on piles
Note: Piles shall be provided by Owner
SCHEDULE OF QUANTITIES, UNITS AND PRICES
VISAKH MARKETING INSTALLATION RESITEMENT
PROJECT - WHITE OIL TERMINAL
Doc No:254624-400-SC-ELE-011 Rev: C
INSTALLATION AND COMMISSIONING OF HIGH MASTS
Receipt ,storage and transportation to the place of erection
at site ,assembling,cabling, erection, testing, commissioning
and final painting of the High masts , structures,fastners,
handling, labour, consumables and erection &
commissioning spares as per specifications and drawings.
INSTALLATION, TESTING & COMMISSIONINGSl.
No.Description
2
Unit Qty
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\04 Electrical\Documents\13 Specifications\High Mast\Rev. C - Issued for tender\White Oil - SOQ for High Mast Lighting System--RevC Page 11 of 6
Mott MacDonald Consultants (India) Pvt. Ltd. Hindustan Petroleum Corporation Ltd
Kothari House, CTS No. 185 Visakha Dispatch Station
Off Andheri - Kurla Road VR-ATP Area, Naval Base Post
Andheri (East) Visakhapatnam - 530 014
Mumbai - 400 059 Andhra Pradesh
VISAKH MARKETING INSTALLATION RESITEMENT
PROJECT - LPG TERMINAL
Doc No:256324-500-SC-ELE-011 Rev: C
SCHEDULE OF QUANTITIES
SUPPLY OF HIGH MASTS SYSTEM
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\04 Electrical\Documents\13 Specifications\High Mast\Rev. C - Issued for tender\LPG - SOQ for
High Mast Lighting System--RevC Page 1 of 6
%Amount
Rs.%
Amount
Rs.
1 2 3 4 5 9 10 11
Design, Engineering, Preparation of
Drawings, Fabrication, Assembly,
painting, Inspection at Manufacturers
work,supply & Delivery to site, Erection,
Testing & Commissioning with lighting
fixures, accessories, including supply of
fixures cable,Earthing Material & lightning
final etc.inclusive of required foundation
bolts & nuts for the following of High Mast
Lighting System as per scope for
mentioned in the specification: 254625-
300-SP-ELE-011
1 Decorative type High mast system: Mast
shall be with decorative umbrella, in two
sections, hot dip galvanised and suitable
for wind velocity as per IS:875, part-3. It
shall also include accessories for high
mast including head frame, steel wire
rope double drum winch, galvanised
lantern carriage arrangement suitable for
required no. of luminaires, its control gear
boxes & junction boxes, aviation
obstruction light, Feeder Pillar Boxes,
lightning finial,Cables & Cable
Connections,cable gland,earthing&
Lightning system including Earthpits as
pere IS 3043 . The mast shall have an
integral power tool for its operation. The
scope also includes following:
- Aviation obstruction lighting fixture
with 2 Nos. of 40w neon lamps. (1 fitting
per mast is necessary if no taller
structures are in near vicinity).
Nos. 11
SUPPLY OF HIGH MAST SYSTEM : SCHEDULE OF QUANTITIES, UNITS AND PRICES
Unit Rate for
Supply Ex.
including
Packaging &
Forwarding
Rs.
Sales TaxTotal Amount (F.O.R.
Site Total Price)
(4 x 10),
Rs.
Sl.
No.Description Unit Qty
6 7
Total F.O.R. Site Unit Price
(5+6+7+8+9).
Rs.
8
Excise duty
Un
loa
din
g a
nd
Sta
ck
ing
at
sit
e
An
y O
the
r L
ev
y
Fre
igh
t F
OR
Sit
e
VISAKH MARKETING INSTALLATION RESITEMENT
PROJECT - LPG TERMINAL
Doc No:256324-500-SC-ELE-011 Rev: C
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\04 Electrical\Documents\13 Specifications\High Mast\Rev. C - Issued for tender\LPG - SOQ for High Mast Lighting System--RevC 5 of 6
%Amount
Rs.%
Amount
Rs.
1 2 3 4 5 9 10 11
SUPPLY OF HIGH MAST SYSTEM : SCHEDULE OF QUANTITIES, UNITS AND PRICES
Unit Rate for
Supply Ex.
including
Packaging &
Forwarding
Rs.
Sales TaxTotal Amount (F.O.R.
Site Total Price)
(4 x 10),
Rs.
Sl.
No.Description Unit Qty
6 7
Total F.O.R. Site Unit Price
(5+6+7+8+9).
Rs.
8
Excise duty
Un
loa
din
g a
nd
Sta
ck
ing
at
sit
e
An
y O
the
r L
ev
y
Fre
igh
t F
OR
Sit
e
VISAKH MARKETING INSTALLATION RESITEMENT
PROJECT - LPG TERMINAL
Doc No:256324-500-SC-ELE-011 Rev: C
- Outdoor Feeder Pillar box with
canopy for rain water protection
confirming to IP:55 which housing
suitable Motor starter with switch
fuse,Contactor & bimetal relay with single
phasing preventor, timercontactor circuit
for automatic switch on and switch off of
the mast of a pre-set time,
Auto/Manual/Off selector switch and
necessary control MCB . The cable entry
shall be from Bottom.Feeder pillar base
frame & neccessary accessories to mount
feeder pillar on piles.
Note: Piles shall be provided by Owner
Nos. 11
- 2x 400w (SON-TP) HPSV Non-integral
Flood light fitting suitable for highmast
lighting with control gear boxes,
Asymmetrical distribution, electro
chemically brightened, polished and
anodised aluminium reflector, heat
resistant, clear, toughened glass cover
hinged to the housing with rubber gaskets
and stainless steel toggles. The Light
fittings shall be Philips make Ref. No.:
MVF480 NB 2xSON-TP 400w or
equivallent
Nos. 99
3 Spares for 2 years normal operationLot 1
Note:1.List of spares along with item wise price shall be submitted separately in sealed cover
TOTAL -(1+2+3)
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\04 Electrical\Documents\13 Specifications\High Mast\Rev. C - Issued for tender\LPG - SOQ for High Mast Lighting System--RevC 6 of 6
Unit Rate
RsTotal Rs
1 3 4 5 6
1
Nos 11
Nos. 99
- 2x 400w (SON-TP) HPSV Non-integral Flood light fitting
suitable for highmast lighting with control gear boxes. The
Light fittings shall be Philips make, Ref. No.: MVF480 NB
2xSON-TP 400w or equivallent
- Aviation obstruction lighting fixture with 2 Nos. of 40w
neon lamps. (1 fitting per mast is necessary if no taller
structures are in near vicinity).
- Pipe earthing station for high mast (2 per mast is
mandatory ) with min. 40mm dia as per IS 3043 connecting
GI earth strips upto earthstations and interconnection of
earth station,painting etc., including supply of all materials
as per the specification
- Cabling from feeder pillar to light fitting including supply
of required cables,associated cable glands and GI pipes.
- Outdoor Feeder Pillar box with canopy .Feeder pillar
base frame & neccessary accessories to mount feeder
pillar on piles
Note: Piles shall be provided by Owner
INSTALLATION AND COMMISSIONING OF HIGH MASTS
SCHEDULE OF QUANTITIES, UNITS AND PRICES
VISAKH MARKETING INSTALLATION RESITEMENT
PROJECT - LPG TERMINAL
Doc No:256324-500-SC-ELE-011 Rev: C
Sl.
No.Description
2
Unit
Receipt ,storage and transportation to the place of erection
at site ,assembling,cabling, erection, testing,
commissioning and final painting of the High masts ,
structures,fastners, handling, labour, consumables and
erection & commissioning spares as per specifications and
drawings.
INSTALLATION, TESTING & COMMISSIONING
Qty
High mast system with its accessories. High Mast base
plate & neccessary accessories to mount mast on piles
Note: Piles shall be provided by Owner
The scope also includes installation & Commissioning of
following.
P:\Andheri\IndiaProject\254625 HPCL- Black Oil Terminal\04 Electrical\Documents\13 Specifications\High Mast\Rev. C - Issued for tender\LPG - SOQ for High Mast Lighting System--RevC 9 of 6