APPLICATIONCat. No. 3800 devices are designed for mounting in standard equipment cabinets where transient volt-age surge suppression is desired for the enclosed equipment. The MOV-based circuit design of eachmodule provides Normal Mode and Common Mode protection for line to neutral, line to ground and neu-tral to ground. The 3800 modules feature compact “black box” styling. Three modules are available:DIN-rail mounting, terminal block wiring or wire leads.

STANDARDS SPECIFICATIONSThe Cat No. 3800 Equipment-Cabinet Surge Protective Devices (SPD) are designed for use on 120Vsingle-phase AC power lines. The 3800-OWM, DIN and OEM modules feature a green LED monitor toindicate loss of protection. (Light out indicates that protection is lost, replace unit.) In the event protec-tion is lost, unit will continue to provide power to connected loads. These devices are UL RecognizedComponent TVSS 1449 Standard. The Cat. No. 3800 is backed by Leviton’s limited five year warranty.

R

SPECIFIER PRODUCT INFORMATION

CAT. NO. 3800 EQUIPMENT-CABINET SURGE PROTECTIVE DEVICES

UL 1449 Transient Voltage Surge Suppressors

GENERAL DATA FOR CAT. NO. 3800

Specification Data Applicable To All

Rated line voltage 120V (VRMS)

Maximum continuous 135Voperating voltage

Max. single-pulse transient current 13000A (L-N)(8x20 µs, Amps peak) 6500A (L-G)

6500A (N-G)

Rated single-pulse transient energy 280 Joules(10x1000 µs, impulse)

Noise rejection @ 5kHz-5MHz -35 dB

Dat

e of

Iss

ue:

Oct

ober

, 19

96N61

Page 2: Spec 3800

Cat. No. 3800-DIN

©1996 Leviton Manufacturing Co., Inc. All Rights Reserved C-481/J6

R

SPECIFIER PRODUCT INFORMATIONN62

Specification 3800-OWM, DIN 3800-OEM*

UL Standard 1449 L-N: 500V Peak L-N: 600 Peak

Permanently-wired L-G: 500V Peak L-G: 600 Peak

Test (8x20 µs, 3000A) N-G: 500V Peak N-G: 600 Peak

Operating Temperature Range: -10°C to 60°C

Storage Temperature Range: -20°C to 85°C

Wiring Means:

Nos. 3800-DIN, 3800-OWM Terminal block accepts 22 AWG to 12 AWG conductors

No. 3800-OEM #16 AWG leads, 6” long, stripped 1/2”

Agency Approvals All devices UL Recognized Component TVSS1449 Standard, CSA Certified

LIGHT ONSURGE

PROTECTED

1.66 (42.16mm)

0.83(21.08mm)

2.69

(68

.33m

m)

3.28

(83

.31m

m)

3.78

(96

.01m

m)

0.625(15.88mm)

TERMINAL BLOCK

1.41

(35

.81m

m)

NOTE: WIRES ENTERFROM THIS SIDE

0.73(18.54mm)

0.85 (21.59mm)

DIN RAIL CLIP

CLAMPING PERFORMANCE

PHYSICAL SPECIFICATIONS

SUPPRESSION MODULES FOR EQUIPMENT CABINETS

*3800-OEM rating tested with 6” lead length

Cat. No. Description

3800-DIN For DIN rail mounting, with terminal block

3800-OWM Screw mounting, with terminal block

3800-OEM Screw mounting, with pigtail wire leads