SPA-ZC22_EN_A

8
ON ON 1 2 3 4 5 6 7 8 1 2 3 4 Tx 1 2 3 4 5 Rx 1 2 3 4 5 _ L PE 1 2 3 4 5 6 N + S1 12345678 S2 1234 5 2 SPA-ZC 22 RS Ser. No 110/125/220 V DC 110/120/230/240 V AC RS 485 SPA OPTICAL REPEATER MASTER SLAVE 001111 110000 00 01 11 1 1 0111 1001 1001 SC 5B0M 4B1M 3B2M 2B3M 1B4M 1 0 S1 POWER AUX INT SERIAL PORT RS 232 SERIAL PORT SPA / RS 485 S2 UAUX 24/48/60 V DC SPA-ZC22 Bus connection module User´s manual and Technical description

Transcript of SPA-ZC22_EN_A

Page 1: SPA-ZC22_EN_A

ON ON

1 2 3 4 5 6 7 8 1 2 3 4

Tx 1 23 4 5

Rx1 23 4 5

_L PE

1 2 3 4 5 6N

+

S11 2 3 4 5 6 7 8

S21 2 3 4

52

SPA-ZC 22RSSer. No

110/125/220 V DC110/120/230/240 V AC

RS 485SPAOPTICAL REPEATERMASTERSLAVE

0 0 1 1 1 11 1 0 0 0 0

0 00 11 1

11

0 1 1 11 0 0 11 0 0 1

SC

5B0M4B1M3B2M2B3M1B4M

10

S1POWER AUXINT

SERIAL PORT

RS 232

SERIAL PORT

SPA / RS 485

S2

UAUX

24/48/60 V DC

SPA-ZC22Bus connection module

User´s manual and Technical description

Page 2: SPA-ZC22_EN_A

2

SPA-ZC22Bus connection module

1MRS 751288-MUM EN

Issued 99-05-19Version A (replaces 34 SPACOM 38 EN1)Checked EPApproved KR

Data subject to change without notice

The SPACOM devices, e.g. the relays and theannunciator units are connected to the fibre-optical SPA bus by means of bus connectionmodules. The bus connection module SPA-ZC22 converts the optical signals of the SPA busto RS 485, SPA (+5 V) or RS 232 signals andvice versa. The bus connection module isprovided with a built-in power unit allowing theSPACOM device to be disconnected from thebus connection module, for instance, for servicewithout interrupting the data communicationover the optical loop.

The bus connection module is provided withone 9-pin D type subminiature connector forRS 485 or SPA connections, one 25-pin D typeconnector for RS 232 connections and, according

to order, two or five opto-connector couples forfibre-optical cables. The fibre-optical links canbe based on glass fibre cables, plastic core cablesor both types mixed.

The bus connection module is mounted in asuitable place in the apparatus cabinet and theconnection cable of the module is plugged to theD-type connector on the rear panel of theSPACOM device. The bus connection moduletype SPA-ZC22 connects to any SPACOMdevice provided with a D-type connector. Thebus connection module can also be connected tothe master units, such as substation level unitsSACO 148D4 and SRIO 1000M, of the com-munication system.

Features

Page 3: SPA-ZC22_EN_A

3

Function The bus connection module is provided with abuilt-in power unit, which is to be suppliedfrom an external power source. The auxiliarysupply is galvanically isolated from the electroniccircuits of the module. The auxiliary supply forthose modules, which have only two opto-connector couples, can be taken from theSPACOM device alone.

Note! The auxiliary supply for the bus con-nection modules provided with five opto-connector couples must be taken from an ex-ternal power source.

The required data communication mode isselected with the DIP switches on the frontpanel of the bus connection module:

Switchgroup S1 S2

Switch number 1 2 3 4 5 6 7 8 1 2 3 4

Serial mode RS 485 0 0 1 1 1 1SPA-protocol mode 1 1 0 0 0 0Optical repeater 0 0 0 1 1 1Master device mode 0 1 1 0 0 1Slave device mode 1 1 1 0 0 1RS 232 DTR, delayed 0

Switches S1/1…S1/6 are used for determiningthe communication mode RS 485 or SPA forthe 9-pin connector. The communication modeof the protection relays is stated in the generalpart of the relay manual in section "Connec-tions".

Switches S1/7, S1/8 and S2/1…S2/3 are usedfor selecting the function of the bus connectionmodule:

- Master device function:The master device mode is used when the busconnection module is connected to a devicefunctioning as a master in the system.

- Slave device function:The slave device mode is used when the busconnection module is connected to a devicefunctioning as a slave in the system.

- Optical repeaterAn optical repeater is a system where a masterdevice is connected to the system by means ofan optical connection. In this case, the masterdevice must be connected to Tx1/Rx1. Theslaves are connected to Tx2/Rx2, Tx3/Rx3, etc.

Switch S2/4 is used for selecting a special functionfor the DTR signal of the RS 232 port. Normallyswitch S2/4 is to be in position 1. When S2/4 isin position 1, the DTR signal is permanentlyactive and the serial interface works in thenormal way. When S2/4 is in position 0, a timedelay function is activated which, if thecommunication through the bus communicationmodule is interrupted, inhibits the DTR signalafter about 15 minutes. As soon as the datacommunication starts again, the DTR signal isactivated again. This function can be used inapplications involving the dis-turbance recordermodule SPCR 8C 27.

The bus connection module SPA-ZC22 isprovided with diagnostic LED's. The LEDmarked "POWER AUX" indicates that theauxiliary voltage is supplied by an external powersource and that the power unit is operatingproperly. The LED marked "POWER INT" islit when the auxiliary voltage is supplied by thehost device and the power unit is operatingproperly. The LED(s) marked "SC" flashes atthe rate of the data communication.

Page 4: SPA-ZC22_EN_A

4

Mechanicalconstruction

The bus connection module comprises one ortwo circuit boards, depending on the number ofopto-connector couples included. The module isusually mounted on the wall inside the apparatuscabinet by means of two M4 screws. The opticalfibres are anchored to the plastic clip at the upperedge of the bus connection module and connected

to the transmitter terminals Tx and the receiverterminals Rx. The specific features of the fibre-optic cables must be noted, when the cables arebeing handled, mounted and connected. Detai-led information is given in the user’s manual 34SPA 13 EN1 A ”Plastic-core fibre optic cables.Features and instructions for mounting”.

1 2 3 4 5 3 4 5 1 2

Rx Tx

SPA-ZC22

Uaux 9 25

RS485 TTL RS232

Fig. 1. Block diagram of the bus connection module SPA-ZC 22. The opto-connector coupleswithin the area defined by the dashed line are included in some types only.

182,6

45

173,

3

Tx 1 23 4 5

Rx1 23 4 5

_L PE

1 2 3 4 5 6N

+

S11 2 3 4 5 6 7 8

S21 2 3 4

52

SPA-ZC 22RSSer. No

110/125/220 V DC110/120/230/240 V AC

RS 485SPAOPTICAL REPEATERMASTERSLAVE

0 0 1 1 1 11 1 0 0 0 0

0 00 11 1

11

0 1 1 11 0 0 11 0 0 1

SC

5B0M4B1M3B2M2B3M1B4M

10

S1POWER AUXINT

SERIAL PORT

RS 232

SERIAL PORT

SPA / RS 485

S2

ON ON

1 2 3 4 5 6 7 8 1 2 3 4

24/48/60 V DC

160,5

140,

3

10,8

27,5

Ø5

UAUX

Fig. 2. Dimensional drawing of the bus connection module SPA-ZC22.

Page 5: SPA-ZC22_EN_A

5

The optical connections are based on plasticcore or glass fibre cables or on both cable typesmixed as required.

The SPA-, RS 485- and RS 232 modes are usedfor communication between the SPACOMdevices and the bus connection module. Fromone bus connection module to the other theinformation is routed via the fibre-optical cables.

The connection cable is provided with male Dtype connectors in both ends. One end is furtherprovided with an earthing wire, which isconnected with a 6 mm M3 screw to the fixinghole close to the D type connector on the rearpanel of the device, see Fig. 3.

The cable delivery set includes a screw, a contactwasher and a nut. The nut is not needed if theearthing wire is connected to the earthing hole.

Optical /electricalconnection

Fig. 3. Earthing of the connection cable.

SPACOM-device

SPA-ZC22

ScrewLock washer

41

+L

-L

PE

1 Uaux

2

3 Uaux

4

5

6 PE

Auxiliary powerconnection

9-pin D-type SPA- bus connector (female)

6789

12345

GND

+8 V in

TxD inRxD out

SPA

DATA ADATA BRTS ARTS B

RS 485

25-pin D-type RS232 C bus connector (female)

14151617

12345

TxD inRxD out

6789

10111213

1819202122232425

DTRGND

Fig. 4. Auxiliary supply terminals and pin configuration of the connectors.

Page 6: SPA-ZC22_EN_A

6

Type designationkey

Type designation Tx1/Rx1 Tx2/Rx2 Tx3/Rx3 Tx4/Rx4 Tx5/Rx5 Aux. volt.

SPA-ZC22C2B0M Plastic/Plastic Plastic/Plastic CSPA-ZC22C1B1M Glass/Glass Plastic/Plastic CSPA-ZC22C1B1M/B Plastic/Glass Plastic/Glass CSPA-ZC22C1B1M/M Glass/Plastic Glass/Plastic CSPA-ZC22C0B2M Glass/Glass Glass/Glass C

SPA-ZC22A2B0M Plastic/Plastic Plastic/Plastic ASPA-ZC22A1B1M Glass/Glass Plastic/Plastic ASPA-ZC22A1B1M/B Plastic/Glass Plastic/Glass ASPA-ZC22A1B1M/M Glass/Plastic Glass/Plastic ASPA-ZC22A0B2M Glass/Glass Glass/Glass A

SPA-ZC22C5B0M Plastic/Plastic Plastic/Plastic Plastic/Plastic Plastic/Plastic Plastic/Plastic CSPA-ZC22C4B1M Glass/Glass Plastic/Plastic Plastic/Plastic Plastic/Plastic Plastic/Plastic CSPA-ZC22C3B2M Glass/Glass Glass/Glass Plastic/Plastic Plastic/Plastic Plastic/Plastic CSPA-ZC22C2B3M Plastic/Plastic Plastic/Plastic Glass/Glass Glass/Glass Glass/Glass CSPA-ZC22C1B4M Glass/Glass Plastic/Plastic Glass/Glass Glass/Glass Glass/Glass CSPA-ZC22C0B5M Glass/Glass Glass/Glass Glass/Glass Glass/Glass Glass/Glass C

SPA-ZC22A5B0M Plastic/Plastic Plastic/Plastic Plastic/Plastic Plastic/Plastic Plastic/Plastic ASPA-ZC22A4B1M Glass/Glass Plastic/Plastic Plastic/Plastic Plastic/Plastic Plastic/Plastic ASPA-ZC22A3B2M Glass/Glass Glass/Glass Plastic/Plastic Plastic/Plastic Plastic/Plastic ASPA-ZC22A2B3M Plastic/Plastic Plastic/Plastic Glass/Glass Glass/Glass Glass/Glass ASPA-ZC22A1B4M Glass/Glass Plastic/Plastic Glass/Glass Glass/Glass Glass/Glass ASPA-ZC22A0B5M Glass/Glass Glass/Glass Glass/Glass Glass/Glass Glass/Glass A

SPA-ZC 22 A 3B 2M

Number of opto-connector couples for glass fibre cables

Number of opto-connector couples for plastic core cables

External auxiliary voltage supply:

A: 110/120/230/240 V ac, +10%…-15%, 50/60 Hz110/125/220 V dc +25%…-20%

C: 24/48/60 V dc, +25%…-20%

Product

Selection table

Page 7: SPA-ZC22_EN_A

7

Page 8: SPA-ZC22_EN_A

1MR

S 7

5128

8-M

UM

E

N

ABB Substation Automation OyP.O.Box 699FIN-65101 VAASAFinlandTel. +358 (0)10 22 4000Fax.+358 (0)10 22 41094www.abb.com/substationautomation