Pusynas meniu 175x360mm sp...Title Pusynas_meniu_175x360mm_sp Created Date 11/25/2020 2:47:17 PM
Sp-47-27[Fire Fighting Equipment and Facilities]
Transcript of Sp-47-27[Fire Fighting Equipment and Facilities]
-
8/13/2019 Sp-47-27[Fire Fighting Equipment and Facilities]
1/17
NIOEC-SP-47-27(1)DOCUMENT CODE NO. OF PAGES:14
PLAN/PRJ/SUB UNIT PHASEDISCIPLAN
EDOCUMENT TYPE SERIAL NO. REV. NO. DATE
NIOEC 000 EG SF SP 4727 A1 OCTOBER, 2006
NATIONAL IRANIAN OIL REFINING & DISTRIBUTION COMPANY
NATIONAL IRANIAN OIL ENGINEERING
& CONSTRUCTION COMPANY
NIOEC SPECIFICATION
FOR
FIRE FIGHTING EQUIPMENT AND FACILITIES
FIRST EDITION
OCTOBER, 2006
THIS SPECIFICATION IS THE PROPERTY OF NATIONAL IRANIAN OIL ENGINEERING & CONSTRUCTION COMPANY. IT IS CONFIDENTIAL AND ALLRIGHTS RESERVED TO THE OWNER. NEITHER WHOLE NOR ANY PART OF THIS DOCUMENT MAY BE DISCLOSED TO ANY THIRD PARTY,REPRODUCTED, STORED IN ANY RETRIEVAL SYSTEM OR TRANSMITTED IN ANY FORM OR BY ANY MEANS WITHOUT THE PRIOR WRITTENCONSENT OF THE NATIONAL IRANIAN OIL ENGINEERING & CONSTRUCTION COMPANY
-
8/13/2019 Sp-47-27[Fire Fighting Equipment and Facilities]
2/17
OCTOBER, 2006 NIOEC-SP-47-27(1)
-
8/13/2019 Sp-47-27[Fire Fighting Equipment and Facilities]
3/17
OCTOBER, 2006 NIOEC-SP-47-27(1)
REVISION INDEX
REVPAGE 1 2 3 4 5
REVPAGE 1 2 3 4 5
REVPAGE 1 2 3 4 5
REVPAGE 1 2 3 4 5
1 X 26 51 762 27 52 773 28 53 784 X 29 54 795 X 30 55 806 X 31 56 817 X 32 57 828 X 33 58 839 X 34 59 8410 X 35 60 8511 X 36 61 8612 X 37 62 8713 X 38 63 8814 X 39 64 8915 40 65 9016 41 66 9117 42 67 9218 43 68 9319 44 69 9420 45 70 9521 46 71 9622 47 72 9723 48 73 9824 49 74 9925 50 75 100
NOTES:
1) THIS SHEET IS A RECORD OF ALL REVISIONS TO THIS SPECIFICATION.2) REMARKS RELATED TO EACH REVISION SHOW A BRIEF DESCRIPTION. THESE REMARKS SHALL BE
INTERPRETED IN CONJUNCTION WITH THE REVISED TEXT MARKED BY REVISION NUMBERS.
3) WHEN APPROVED EACH REVISION SHALL BE CONSIDERED AS A PART OF THE ORIGINALDOCUMENT.
4) NUMBER OF PAGES EXCLUDES THIS SHEET AND THE COVER SHEET.
54321
OCTOBER, 2006 M.KHEZRI M.R.FARZAM M.A.A.SAJEDI0 JULY, 2005 M.KHEZRI M.R.FARZAM M.A.A.SAJEDI
REV. DATE PREPARED CHECKED APPROVED AUTHORIZED
-
8/13/2019 Sp-47-27[Fire Fighting Equipment and Facilities]
4/17
OCTOBER, 2006 NIOEC-SP-47-27(1)
CONTENTS: PAGE NO.
1. SCOPE 22. REFERENCES 23. UNITS 34. DEFINITIONS & TERMINOLOGY 35. DESCRIPTION OF SYSTEM 36. DESIGN BASIS 57. DESIGN REQUIREMENTS 68. EQUIPMENT SPECIFICATION 119. INSPECTION & TESTS 1310.PREPARATION FOR SHIPMENT 13
1
-
8/13/2019 Sp-47-27[Fire Fighting Equipment and Facilities]
5/17
OCTOBER, 2006 NIOEC-SP-47-27(1)
1. SCOPE1.1This Specification covers the design basis of fire fighting facilities and fixed equipment to
be employed for the prevention, control and extinguishing of Refinery fires, it does not
cover fire resistant construction, insulation or fireproofing, trenching or fire-walling,
electric bonding or earthing, or general regulations affecting personnel or equipment.
1.2 Interchangeability of equipment within Refineries shall be a primary consideration.
1.3 An approved altering and communicating system is required with fire detector systems
for special risks.
2. REFERENCESThroughout this Specification the following dated and undated standards/codes are
referred to. These referenced documents shall, to the extent specified herein, form a part
of this Specification.For undated references, the latest edition of the referenced document (including any
supplements and amendments) applies. For dated references, the edition cited applies.
The applicability of changes in dated references that occur after the cited date shall
mutually be agreed upon by the company and the Vendor/Contractor.
ASME (AMERICAN SOCIETY OF MECHANICAL ENGINEERING)
ASME B16.5 Steel pipe flanges and flange fittings
NIOEC-SP (NIOEC SPECIFICATIONS)
NIOEC-SP-00-10 NIOEC Specification for Units
NIOEC-SP-00-66 NIOEC Specification for Liquid & Gas Transfer & Storage
NIOEC-SP-46-16 NIOEC Specification for Fire Water Pumps
NIOEC-SP-47-32 NIOEC Specification for Co2 Extinguishing System
NIOEC-SP-50-01 NIOEC Specification for General Piping, Process and
Utility Design, Equipment Layout and Drawing
Procedure
NIOEC-SP-90-52 NIOEC Specification for packing and packages
NIOEC-SD (NIOEC STANDARD DRAWINGS)NIOEC-SD- 5013-1/1 Standard DWG Underground & Misc. Piping Details
NFPA (NATIONAL FIRE PROTECTION ASSOCIATION CODES)
Code No. 10 Fire Extinguishers, Portable
Code No. 11 Low Expansion Foam and Combined Agent Systems
Code No. 12 Carbon Dioxide Extinguishing System
Code No. 14 Standpipe Private Hydrant and Hose Systems
Code No. 15 Water spray Fixed Systems for Fire Protection
Code No. 20 Fire Pumps, Centrifugal
Code No. 24 Private Fire Service Mains and their Appurtenances
2
http://../VOL.1(PROCESS)/SP-00(PROCESS)/NIOEC%20SPEC.FOR%20PROCESS/NIOEC-SP-00-10.pdfhttp://../VOL.1(PROCESS)/SP-00(PROCESS)/NIOEC%20SPEC.FOR%20PROCESS/NIOEC-SP-00-66.pdfhttp://../VOL.3(FIXED%20EQUIPMENT,%20MACHINERY%20&%20MISCELLANEOUS)/SP-46(MACHINARY)/NIOEC%20SPEC%20FOR%20MACHINARY/SP-46-16.pdfhttp://../VOL.1(PROCESS)/SP-00(PROCESS)/NIOEC%20SPEC.FOR%20PROCESS/SP-47-32.pdfhttp://../VOL.4(PIPING)/SP-50(PIPING)/NIOEC%20SPEC.%20FOR%20PIPING/SP-50-01.pdfhttp://../VOL.1(PROCESS)/SP-90(GENERAL)/NIOEC%20SPEC.%20FOR%20GENERAL/SP-90-52.pdfhttp://../VOL.8(NIOEC%20STANDARD%20DRAWINGS)/5000-PIPING%20STD.%20DWG/SERIES%205000/SD-5013-1(1)-1.dwghttp://../VOL.8(NIOEC%20STANDARD%20DRAWINGS)/5000-PIPING%20STD.%20DWG/SERIES%205000/SD-5013-1(1)-1.dwghttp://../VOL.1(PROCESS)/SP-90(GENERAL)/NIOEC%20SPEC.%20FOR%20GENERAL/SP-90-52.pdfhttp://../VOL.4(PIPING)/SP-50(PIPING)/NIOEC%20SPEC.%20FOR%20PIPING/SP-50-01.pdfhttp://../VOL.1(PROCESS)/SP-00(PROCESS)/NIOEC%20SPEC.FOR%20PROCESS/SP-47-32.pdfhttp://../VOL.3(FIXED%20EQUIPMENT,%20MACHINERY%20&%20MISCELLANEOUS)/SP-46(MACHINARY)/NIOEC%20SPEC%20FOR%20MACHINARY/SP-46-16.pdfhttp://../VOL.1(PROCESS)/SP-00(PROCESS)/NIOEC%20SPEC.FOR%20PROCESS/NIOEC-SP-00-66.pdfhttp://../VOL.1(PROCESS)/SP-00(PROCESS)/NIOEC%20SPEC.FOR%20PROCESS/NIOEC-SP-00-10.pdf -
8/13/2019 Sp-47-27[Fire Fighting Equipment and Facilities]
6/17
OCTOBER, 2006 NIOEC-SP-47-27(1)
BRITISH STANDARD
BS 336 Specification for fire hose couplings and ancillary equipment
3. UNITSInternational system of units (SI) shall be used in accordance with NIOEC-SP-00-10,
unless otherwise specified.
4. DEFINITIONS AND TERMINOLOGY4.1 Company: Means National Iranian Oil Engineering & Construction Company.
4.2 Purchaser: Means National Iranian Oil Engineering and Construction Company in cases
where this Specification is part of direct order by NIOEC and contractor where this
Specification is part of contract Documents.
5. DESCRIPTION OF SYSTEMS5.1 The philosophy adopted in the design of fire fighting facilities shall be that Fire Fighting
facilities shall be sized adequately and designed for fighting two major fires
simultaneously occurring in the refinery and/or tankage area.
Fire fighting activities may be carried out on the burning facility using monitors, hose
reels, hydrant nozzles, foam system, fire water, CO2system, portable fire extinguishers,
steam extinguishing means, mobile fire fighting equipment (fire trucks), etc.
The following fire protection systems shall be provided for the project.
- Fire water storage and fire water pumping/distribution systems (including outdoor
water hydrants, fixed and portable water monitors and outdoor/indoor hose reels).- Semi fixed foam extinguishing system complete with CF3I ream seal protection
system (sub-surface and top pouring foam extinguishing system) for tanks
containing flammable liquids.
- Fixed water cooling system for tanks containing hydrocarbons.- Fixed water spray system for LPG spheres, bullets and large separators containing
light oils likely to cause BLEVE (Boiling Liquid Expanded Vapor Explosion).
- CO2 extinguishing system for substations and Gas Turbine Generators. CO2extinguishing system shall also be provided for Battery Room of substation
.Where under floor cable void is provided, CO2distribution piping shall be extended
to the cable void, no fire detectors are required in the cable voids but CO2extraction
fan is required. For Remote Instrument Buildings (RIB) the same philosophy of
substations should be applied.
- Steam extinguishing system (Snuffing steam)- Fire extinguishers- Fire training area including all facilities and connections
3
-
8/13/2019 Sp-47-27[Fire Fighting Equipment and Facilities]
7/17
OCTOBER, 2006 NIOEC-SP-47-27(1)
5.1.1 The fire water system shall provide water for fire fighting and fire protection for the
process units, utility area, tankage area, buildings, other off-site areas, etc...
Water shall be available for mechanical Foam systems and also, for the cooling of
equipment and structures near a fire. Water for fire fighting shall be provided by an
independent fire ring main fed by the fire pumps and normally cross connected to
the Refinery cooling water system. The fire water pumps shall have suction lineaccess to the raw water line and raw water tanks for emergency purposes and shall
be located at least 30 m from fire water tanks. Provision should be made for
pumping from storage tanks or other reliable sources. Adequate supply of water
must be made available in accordance with National Fire Code, and company,
requirements and approval.
The fire water system shall be sized adequately and designed for fighting two major
fires simultaneously occurring in the refinery and/or tankage area (the most cases of
two major fires in the refinery, or one major fire in the refinery and one major fire in
the tankage area).
Note that each process unit, a tank bounded area or a LPG scheme is considered as a
single hazard. Sizing of main fire water-distribution line shall be based an all linesbeing in service. Basically, the flow velocity in the piping system shall not exceed
1.83 m/sec at 10.35 barg discharge pressure of fire water pumps (for design
purpose).
The system design shall conform to NFPA code No. 24, using a Hazen-Williams
coefficient of 100 for carbon steel pipe and Hardy Cross formula.
5.1.2 Water shall be applied by means of hose and branch pipes using jet, spray or fog
nozzles, or by fixed or portable monitors preferably with interchangeable nozzles
for water or foam jets.
5.1.3 The installed main pumping capacity shall be based on the total consumption in any
one process area (defined as an area in which the fire can be confined without
significant danger of the fire spreading to an adjacent area) of 818 m3/h at 10.35
barg simultaneously with the required flow rate at 10.35 barg to any group of tanks.
The required flow rate to be supplied to the tankage area shall be min. 818 m3/h and
shall be determined on the basis of the total consumption as needed for cooling of
the adjacent tanks next to the tank under fire with inclusion of sprinkler waters.
Each main pump shall have a pumping capacity of 818 m3/h. Standby pumps diesel
driven with total capacity same as the main pumps shall also be supplied. All pump
drivers shall have totally independent power supply.
Driver of main and standby pump shall be sized at 110% of the maximum powerabsorbed by pumps at full load to avoid overloading if there is a pressure drop in the
system at full capacity.
A building of adequate size shall be provided to house fire water pumps. Adequite
space for maintenance and suitable overhead crane with adequate capacity for
heaviest load shall be provided.
The motor driven main pumps shall come into service automatically and diesel
driven pumps shall have on and off switches at the fire station and power station
room (utility board).The jockey pumps shall maintain the pressure in the fire water
line system to 10.35 barg, automatically. If a jockey pump is used in refinery, it
shall be "spared" and both pumps shall have a capacity of 113m3/h (500 gal/min) to
compensate for leakages. (For pump station the capacity of jockey pump shall be15m3/h)
4
-
8/13/2019 Sp-47-27[Fire Fighting Equipment and Facilities]
8/17
OCTOBER, 2006 NIOEC-SP-47-27(1)
5.1.4 For design purposes the flow velocity in the piping system shall not exceed
1.83m/s@ 10.35 barg. Fire hydrants shall be maximum 45 meters apart in process
and utility area and maximum 60 meters apart in the off-site area, but their location
generally will be determined in relation to the plant to be protected; all hydrants
must be easily accessible.
5.1.5 Fire hose reels shall be located in each process unit and utility (Boiler area)
normally 30-45m apart at certain strategic points. In general, hose reels are not
required for protection of elevated platform or fin fans containing hydrocarbons.
These areas will be protected by fixed water monitors. Outdoor hose reels shall be
mounted on a frame to facilitate waist level operation.
5.1.6 In locations, such as LPG Storage and bullets, hydrogen plants, etc., where very
large quantities of water in jet or fog forms are required, fixed monitors,
permanently secured to monitor hydrants shall be installed. All fixed water monitors
shall be placed at ground level in order to enable easy operation and so as to provide
effective cooling. All fixed water monitors shall be carefully placed to avoid
unnecessary obstructions like pipe lines and support columns. However, monitors
shall be at least 15m away from equipment to be protected. Use of portable water
monitors is recommended in combination with fixed water monitors. Clear access
must be provided for all fixed water monitors. The fire water system shall be
pressurized and maintained at a pressure of 10.35 barg by jockey pump.
5.1.7 Fixed water fog systems may be employed, extinguishing, cooling or restricting a
fire in areas of high fire risk where immediate action is necessary.
6.
DESIGN BASIS
6.1 Fire Water Demand
Maximum firewater demand for process units and tank farm area is calculated on the
hereunder basis:
Fire water requirements in tank farmIt shall be calculated as follows:
a.Water requirement for cooling of tanks, maximum three tanks other than tank underfire, shall be considered.
- Half of the surface of the adjacent tanks, if the exposure tank is in the middleof two tanks.
- One third of surface of the adjacent tanks, if the exposure tank is in the centerof three tanks.
b. Water flow calculated for applying foam on a single largest tank under fire shall be
considered.
c.Firewater flow rate for supplementary stream shall be based on using two singlehydrants outlet and two monitors.
Total water requirement for tank farm area shall be (a) + (b) + (c).
5
-
8/13/2019 Sp-47-27[Fire Fighting Equipment and Facilities]
9/17
OCTOBER, 2006 NIOEC-SP-47-27(1)
Firewater requirement in process unitsFirewater demand shall be calculated as follows:
a. Water requirement of spray system in a process segment.
b. Water requirement for monitors to cover a process segment (minimum two monitors)
plus two single outlet hydrants at a time.
Total water requirement for process units shall be (a) + (b).
6.2 Firewater Application Rate
6.2.1 Process Unit
Manual operated water spray system shall be provided for the following equipment:
Pumps handling hot hydrocarbon operating at a temperature higher than flashpoint. Only the mechanical part of the pump, which contains hydrocarbons, shall
be deluged. The water spray should be designed to envelope, as a minimum, theentire pump including the shaft, seals, and other critical parts. Optionally, the
spray envelope may be extended 0.6 m beyond the pump periphery, and include
suction and discharge parting flanges, check valves, gage connections, block
valves, balance lines, and lubrication connections. The applications rate shall be
not less than 20.4 l/min/m2of the projected envelope area at grade level. NFPA 15
should be consulted for other design requirements.
Pressure vessels, drums and reactors. Firewater flow rate shall be 10.2 l/min/m2ofdeveloped surface.
6.2.2 Tank Farm Area
The LPG pressure storage spheres, bullets and large separators shall be protectedby automatic water spray system. Firewater rate shall be 12.0 l/min/m2 of
protected surfaces.
Water application density for tank cooling shall be 4.1 l/min/m2of tank surface.6.2.3Hydrant and Monitors
One single Hydrant outlet: 60m
3
/h (950 l/m)
One monitor: 120 m3/h (1900 l/m).7. DESIGN REQUIREMENTS
7.1 Piping
7.1.1 The Piping Specification shall cover the piping layout, including water rates, size of
lines, location of block and flushing valves, general location of hydrants, fire pump
location, and design conditions.
7.1.2 Connection shall not be provided for permanent use of fire water other than for fire
fighting.
6
-
8/13/2019 Sp-47-27[Fire Fighting Equipment and Facilities]
10/17
OCTOBER, 2006 NIOEC-SP-47-27(1)
7.1.3 Sufficient isolating valves and cross links shall be provided so that a section of the
fire main can be taken out of service without interrupting supplies of water. In each
process unit area, utility area, and bund wall area isolation should be such that at
least 50% of hydrants and hose reels remain in service.
7.1.4 All main block valves shall be operable from grade and shall be mounted inunderground valve boxes, per Standard drawing no. NIOEC-SD-5013-1/1. Hand
wheel extension details shall be according to standard drawing no. NIOEC-SD-
5013-1/1. Valve boxes shall be filled with removable insulating material to protect
valve and pipe from frost. Valve boxes shall be large enough for easy access to
valves for repair and removal.
7.1.5 Fire water distribution network shall be of loop and ring design.
7.2 Foam
7.2.1 Foam generators shall be based on mechanical air foam generation only. This
system may comprise either a fixed installation or portable equipment.
7.2.2 All fixed foam installations should be designed to reduce time lag in charging
service lines to a minimum, and provision made for draining all services after use.
7.2.3 Semi-fixed sub-surface foam injection system shall be provided for fixed roof tanks
containing flammable liquids. Semi-fixed top pouring foam extinguishing system
shall be provided for covered floating roof tanks containing flammable liquids and
tanks containing high-viscosity hydrocarbons (such as refinery fuel oil)and slop oil .
The system shall consist of foam discharge outlets, foam generators, lateral foampipes extended from outside bound walls. The lateral pipes shall be terminated with
foam solution inlet-hose connections (2-1/2" British Instantaneous Coupling male)
outside bound wall. Foam solution will be distributed from the system by fire
truck(s).
Semi-fixed sub surface and top pouring foam extinguishing system shall be
designed and installed in accordance with NFPA Code No.11.
Basically, one lateral pipe shall be provided for every two foam discharge outlets on
the covered floating roof tanks. Piping inside the bound wall shall be above grade
and foam solution inlet hose connections outside bound wall shall be at least 15m
away from the tank to be protected.
Foam generators of sub surface foam system shall be mounted on mobile fire trucks.Fixed RIMSEAL pouring foam extinguishing system shall be provided for floating
roof tanks containing flammable liquids. This system shall complete with CF3I rim
seal protection system.
7.2.4 For aviation fuel storage tanks with internal floating screen subsurface foam
injection shall be used combined with inert gas blanketing.
7.2.5 In case of floating roof tanks, 45m dia. and above, hand railing shall be installed to
wind girders for the safety of fire fighters when fighting rim fires.
7.3 Utility Stations
7
-
8/13/2019 Sp-47-27[Fire Fighting Equipment and Facilities]
11/17
OCTOBER, 2006 NIOEC-SP-47-27(1)
7.3.1 Utility Stations for steam, water and air shall be located throughout the operating
areas, per NIOEC-SP-50-01. At least, one (1) water hose and one (1) steam hose
shall be provided for each two (2) utility stations. Length of each hose shall be
minimum 15 meters.
7.3.2 Steam lance hose assemblies should be carried on a suitable rack adjacent to the
steam point. The hoses should be suitable for use with high pressure steam (20 barsteam) and should be electrically continuous or both ends of hoses bonded against
static electricity.
7.3.3 The steam hoses shall be 3/4" size and 15m in length. They shall have a protective
outer covering of woven wire mesh. They shall be suitable for 20 barg steam
pressure and be provided with 3/4" standard pipe thread male couplings on both
ends. 3/4"- 300#. integral seat steel unions shall be used to join hoses to the 3/4"
supply line. The same union is used to join hose lengths.
7.4 Steam Systems
Snuffing steam shall be made available at furnace header boxes and fire boxes.
7.5 Storage tanks
7.5.1 Floating Roof Tanks: These shall be equipped with earth bonds from floating deck
to tank shells.
7.5.2 Fixed water cooling system shall be provided for all tanks containing hydrocarbon
in order to provide exposure protection against radiant heat from the fire, in addition
to adequate spacing between tanks.
The system shall consist of water cooling ring(s) with open cooling spray nozzles onthe tank shell surface and on the top of fixed roof tanks, gated lateral pipes which is
extended from the outside of bound wall and is branched off from the fire water
main distribution line.
Crude storage tanks only will be provided with the cooling ring divided in two
sections.
The system shall be manually activated. Shut-off valve(s) shall be placed at the
outside of the bound wall and at least 15m away from the tank shell to be protected.
Asphalt storage tanks shall not be equipped with any permanent fire fighting
facilities, except for available high pressure water streams for cooling purposes.
7.5.3 Storage tank spacing shall be per NIOEC-SP-00-66 requirements.
7.6 General Stores (Work shop & ware House, Administration Buildings and Laboratories)
Hose reels shall be connected to fire water mains and mounted on swivel or other suitable
fittings on the basis of NFPA code 14.
Each indoor hose reel shall consist of a cabinet, recess mounted for the Administration
and surface mounted for other buildings, with 30 meters hose reel equipped with 1 1/2"
hose and a 19mm nozzle.
Each hose reel assembly shall incorporate a quick opening Lever operating on/off ball
valve and terminate in a-1/2" gunmetal NST (National Fire Hose Connection screw
Threads) female coupling.
7.7Chemical Stores, Acid and Chemical Plants
8
-
8/13/2019 Sp-47-27[Fire Fighting Equipment and Facilities]
12/17
OCTOBER, 2006 NIOEC-SP-47-27(1)
Included in this general reference are all cases where the specified nature of the products
and the system of segregation and storage adopted necessitates application of specific fire
protection methods.
7.8 CO2extinguishing system
CO2Extinguishing System shall be provided for Gas Turbine Generator and Substation
Building, the Gas Turbine enclosure in accordance with NFPA code No. 12 and on thebasis of Specification NIOEC-SP-47-32. CO2 extinguishing system shall also be
provided for Battery Room of substation .Where, under floor cable void is provided,
CO2 distribution piping shall be extended to the cable void, no fire detectors are
required in the cable voids but CO2extraction fan is required. For Remote Instrument
Buildings (RIB) the same philosophy of substations should be applied.
7.9 Detection and Alarm System
Fire detection system and alarm system shall be provided for Gas Turbine Generator and
enclosure and the substation buildings with CO2Extinguishing system described in article
6.8. The indication of Fire alarm signal from CO2Extinguishing system shall be made
nearest control room.Emergency warning and communication with the Fire Station will be made through Fire
Telephone System for which separate design basis will be provided and therefore,
excluded from this Specification.
Fire detection system shall be provided for rim seal space of floating roof tank.
7.10 Fixed Water Spray System
Fixed water spray system shall be provided for LPG spheres, bullets and large
separators containing light oils likely to cause BLEVE (Boiling Liquid Expanded Vapor
Explosion).
The system shall consist of water spray ring with open spray nozzles; gated lateral pipes
branched off from the fire water main distribution line.
Water application density shall be 12.0 1/min/m2of protected surfaces, on the basis of
NFPA Code No. 15.
The automatically actuated spray system shall be provided with pressure storage
spheres and bullets. Dedicated system will be provided for each storage sphere and LPG
bullets for which respectively only one system will be provided. The system shall also
be manually activated. Shut-off valve(s) shall be placed at least 15m away from the
equipment to be protected.
7.11 Fire Extinguishers
7.11.1 Extinguisher shall be furnished as follows:
Fire class Extinguisher Size and Type
A (ordinary combustible) 4kg multi-purpose dry chemical
B (flammable liquids and gases) 9kg and/or 50kg wheeled
Potassium bicarbonate dry chemical
C (energized electrical equipment) 4kg multipurpose dry
Chemical (6kg CO2 for power
Station instead of BCF)
9
-
8/13/2019 Sp-47-27[Fire Fighting Equipment and Facilities]
13/17
OCTOBER, 2006 NIOEC-SP-47-27(1)
Each portable and wheeled extinguisher located outside shall be provided with a
cover sheet suitable for direct sunshine.
Based on experience from the existing refinery, the capacity of dry chemical
extinguishers may be changed.
7.11.2 The various types of extinguishers to be provided in different areas of the refinery
shall be as follows:
1)General
Extinguishers shall be mounted on walls, columns, etc. unless the extinguishers
are of wheeled type. They shall be installed on the hangers or in the brackets
supplied.
Extinguisher units weighting less than 18.2 kg shall be mounted so that the
extinguisher top is not more than 1.2m above the floor.
Extinguishers shall be located so that the basic maximum travel distance to
extinguishers (a) applicable to flammable liquids, oils, gases, etc. is 15.25m;
(b) applicable to ordinary combustible materials is 22.7m.
2) Process, utility areas shall be protected as follows:
9kg dry chemical extinguishers shall be provided along main access ways. On
overhead structures, the extinguisher locations shall be near stairway landings.
9kg dry chemical extinguishers shall also be provided on overhead main
platform with stairway access.
9kg dry chemical extinguishers shall be located in pump and compressor areas.
50kg wheeled type dry chemical extinguishers shall be located at suitable
points as well as the installation of portable extinguishers.
3) Buildings and shelters shall be protected as follows:
4kg multi-purpose dry chemical extinguishers shall be located according to
Para. (1) above.
4kg multi-purpose dry chemical extinguishers shall be located in the electrical
substation and 6kg CO2extinguishers shall be located in the power station, and
at least 9kg dry chemical extinguishers shall be provided outside the fenced
enclosure gate for oil immersed transformers.
4) In the oil storage tank area, two (2) 9kg dry chemical extinguishers and one (1)
wheeled type dry chemical extinguisher shall be provided for each corner of a
dike except a small bounded area and be located outside the dike.
5) Extinguishers shall be provided for truck loading racks. One 9kg portable dry
chemical extinguisher shall be provided for each island. One 50kg dry chemical
extinguisher shall be provided for every four bays.
7.12Special Applications
Applications of fire-fighting systems to plants, areas or equipment not specially
mentioned above shall be determined by their particular requirements as defined in
Subsection 5, "Description of Systems". In this connection, the distance factor in the
piping characteristics of each system should be considered.
Such applications cover systems for operation in cases of general fire.
10
-
8/13/2019 Sp-47-27[Fire Fighting Equipment and Facilities]
14/17
OCTOBER, 2006 NIOEC-SP-47-27(1)
7.13Fire Station and Mobile Equipment
Fire station shall be designed and constructed in accordance with the Contract
requirement. Mobile equipment shall also be provided in accordance with the Contract
requirements.
7.14Fire Training Area and Facilities
Fire training area shall be installed in order to provide training exercise against simulated
incidents. Equipment in fire training area shall be furnished and installed by contractor.
Arrangement of equipment shall be approved by NIOEC.
8. EQUIPMENT SPECIFICATIONThe following fire protection equipment used with water or air foam systems shall be
purchased, where such equipment is specified, subject to Companys approval.
8.1 Fire Fighting Equipment
8.1.1Fire Hydrants
A.All hydrants shall be Freeze-proof unless otherwise minimum temperature of site
condition never reaches below zero. Hydrants shall be Standard American Darling
Valve and Manufacturing Company, Model B-50-B (M.E.S.C. 96.25.10.701.1) or
equivalent.
B. Fire hydrants shall be cast iron (5 inch main valve), standard trim, compression
type, self draining with two 2 1/2"-8NPT-MALE hose nozzle connections 180 apart and one 5" pumper connection. Pumper connection to be female round
thread, complete with cap and chain, in accordance with British Standard B. S.
S. 336. Final inlet flange of the hydrant shall be 6" 250 Ib R. F.(ASME B
16.5) on the side flanged base (as per hydrants to be suitable for 14 barg
working pressure with automatic drain valve, suitable for freezing condition.
Operating stem nut to be pentagon, 1-1/2" point to flat. With suitable wrench.
Operating steam nut to open left (counter clockwise). Trench depth to be 1.67
meters. Each fire hydrant and hydrant with monitor shall be equipped with 1"
drain pipe to sewer line or other (as per note 4 of Standard drawing No. NIOEC-
SD-5013-1/1).
C. The 2-1/2" and 5" connections shall be located so that the distances between the
bottom of the connection caps and finished grade are a minimum of 0.5m and
0.25m respectively. The 5" pumper connection shall face the roadway wherever
installed and shall be at right angles to the hose nozzle connection.
D. Fire hydrants shall be installed in pits as per Standard drawing No. NIOEC-SD-
5013-1/1 and pits filled with removable, suitable insulating material to protect
the hydrant and pipe from frost.
E. Hydrants shall be located on the road side of all pipe lines or drainage ditches.
The length of the 5" suction hose required between the hydrants and fire truckshall not exceed 4.5m where large pipe bends or drainage ditches may hinder
access from hydrants to process areas or tank farms. Hydrants shall be located
11
-
8/13/2019 Sp-47-27[Fire Fighting Equipment and Facilities]
15/17
OCTOBER, 2006 NIOEC-SP-47-27(1)
near access ways or walkways across such obstructions. Where located on
roadsides simple vertical crash posts shall be erected between road and hydrant.
F. In tankage areas where fixed air foam laterals are installed, hydrants shall be
located in relation to terminus of air foam laterals so that the total length of hose
from hydrant to fire truck and from fire truck to foam lateral does not exceed
38m.
8.1.2 Valves for Fire Hydrants
Valves for 2 1/2" outlet fire hydrants shall be of gunmetal, single outlet, suitable for
above ground installation, solid wedge gate type, outside screw and yoke. Inlet shall
be 2 1/2" NPT FEMALE Compatible with 2 1/2" hose nozzle connection of each
hydrant, Outlet to be 2 1/2", single lug instantaneous pressure release FEMALE
coupling.
8.1.3 Hose Reel Hydrants For Climates Subject to Freezing Weather
A. Freeze-proof, self-drain hose reel hydrants shall be No. 140 National Type "A"American Foundry and Manufacturing Co. or equivalent. Fire Hose reel
hydrants shall be 2" sizing throughout.
B. Hose reel hydrants shall be all bronze (2" valve opening), compression type, self
draining with one 2" NPT FEMALE hose reel nozzle connection and one 2"
NPT FEMALE inlet. Hydrants to be suitable for 14 barg working pressure,
suitable for freezing conditions, hand wheel operation, counter-clockwise valve
opening. Trench depth to be 1.67meter.
8.1.4 Pumps and Drivers
A. Fire pumps shall be according to NIOEC-SP-46-16 and designed for 10.35 barg
min. discharge pressure at rated capacity. The pressure rise at shut-off should
not exceed 20 percent or 14 barg. Where the pressure can build up to exceed the
design rating of the lines, a pressure relief valve discharging into the suction or
source of supply shall be provided. Pumps shall be of horizontal construction.
B. For diesel engine drivers for fire pumps, the fuel tank shall have sufficient
capacity of 24 hours of continuous operation. The radiator should be equipped
with a special electrical heater for winter time. Diesel driven pumps shall be
installed indoors at a safe location.
C. Continuous positive pump suction or a means of priming shall be provided.
D. Suitable suction strainer shall be provided. The screen shall be cleanable with the
pumps in service.
E. The main firewater pumps should be equipped for automatic and manual starting;
the standby pump shall be push button start.
8.1.5 Hoses and Couplings
Outdoor useHose coupling shall be standardized as follows:
12
-
8/13/2019 Sp-47-27[Fire Fighting Equipment and Facilities]
16/17
OCTOBER, 2006 NIOEC-SP-47-27(1)
1) All outlet coupling shall be female and inlet coupling male, both conforming toBS-336.
2) Pressure connections for collapsible hose shall be 65= (2-1/2") conforming to
BS-336 British Instantaneous Coupling (hereinafter called BIC) only.
Hose coupling shall be of gunmetal alloy construction.
Loose hose shall be provided in standard lengths and preoccupied as follows:65mm collapsible hose in 25m lengths, with precompiled male and female
65mm BIC couplings.
Buildings fire hose reel, rayon braid neoprene, working pressure 15.5 barg shall
be connected directly to fire water supply in the buildings.
Size I.D. Hose Length
In mm m
1-1/2 64 25
8.1.6 Fire Hose Reels for Yard Hydrants
Hose reels shall be floor mounted, similar to the American Reeling devices # R-175-25 without crank, with 1 1/2" B2, 1 MALE pipe thread connections, complete
with 25 meters of 1 1/2" I.D., x2 rayon braid neoprene tube and cover, 15.5 barg
working pressure U.S. Rubber Style P999 general purpose hose and Powhatan brass
250B adjustable fog nozzle. Metal cover shall be 1mm steel, painted red.
8.1.7 Fixed Type Monitors
Fixed type monitors shall have deluge fog and jet nozzle assemblies of the lever
type. The main valve of the monitor hydrant shall be hand wheel operated. All
monitors shall be hand wheel operated. All monitors shall be gun metal construction
with a locking device suitable for unattended operation of the monitor; they shall be
furnished with a combination straight stream fog nozzle with a water capacity of
120 m3/h at 7 barg inlet pressure.
Fire hydrants with monitor shall be equipped with a 5 inch main valve, standard
trim, self draining valve, two 2 1/2" 8 NPT MALE hose nozzle connections 180 apart and 2 1/2" outlet hydrant valves with instantaneous coupling, confirming BS-
336, a 4" , 250 Ib R.F flanged monitor outlet and elbow, valve, etc. as per NIOEC-
SD-5013-1/1.
Except the above, paragraph 7.1.1 and 7.1.2 shall be applied for the design of
monitor hydrant.
9. INSPECTION & TESTS9.1The material fabrication and testing of all equipment shall be subject to inspection by the
Purchaser and/or his designated representative.
9.2The Purchaser's Inspectors shall have free entry to the Vendor's Shop at all times during
fabrication or testing.
10.PREPARATION FOR SHIPMENT- Preparation for shipment shall be in accordance with the following and Manufacture'sstandards. The manufacturer shall be solely responsible for the adequacy of the
Preparation for Shipment employed in respect of materials and application, to provide
13
-
8/13/2019 Sp-47-27[Fire Fighting Equipment and Facilities]
17/17
OCTOBER, 2006 NIOEC-SP-47-27(1)
materials to their destination in ex-works condition and handled by commercial carrier
systems.
NIOEC-SP-90-52 : NIOEC Specification for packing and packages
Note:Requirement of guarantee will be indicated in the Specification of individual fire
fighting equipment for purchasing. This Specification shall not be used for
purchasing work, accordingly.