STANDARD OPERATING PROCEDURE LUBRICATING OIL SYSTEM THERMAL POWER LIMITED

Transcript of Sop of turbine lubrication oil system

Page 1: Sop of turbine lubrication oil system

STANDARD OPERATING PROCEDURE

LUBRICATING OIL SYSTEM

THERMAL POWER LIMITED

Page 2: Sop of turbine lubrication oil system

SOP – Turbine Lubricating Oil System, Rev-0

2

The purpose of the SOP of Lube Oil System is to train and guide operating personnel for optimum performance of the system.

R E S P ON S I B I L I T Y Shift In-charge (Main plant) is responsible for implementation of this SOP so as to ensure safe

and efficient operation of the system.

GE NE RA L I NT RODU CTI ON

The Purpose of Lube Oil System is to lubricate the Bearings of Turbo-generator unit, supply sealing oil to Generator Hydrogen seal and Supply oil to Jacking oil pump.

The Oil supply of turbine lubricating oil system is in MOP-BOP mode. MOP is directly driven by turbine main shaft & discharge HP oil to drive BOP to run.The Specification of system oil is ISO-VG32 turbine oil.

The lubricating oil system performs three basic functions:

i. It r e du ce s f r i c t i o n between rotating and fixed elements of the turbine and generator such as occur in the journal bearings and thrust bearings. This reduces wear, reduces heat and improves efficiency.

ii. It r e m o v e s h ea t from the bearings. This heat may either be generated by friction within the bearing or by conduction along the shaft from the turbines.

iii. In mechanical hydraulic governing systems, it is used as a h y d r a u l i c p r e ss u r e f l u i d . In these governing systems, lubricating oil is used for both the pilot oil and power oil systems.

TE CHN I C A L S P E C IF I C AT I ON

Main Oil Tank

No. of Tank 1

Highest Oil Level +100mm

Operating Oil Temp. 35C

Shutdown Oil level -150mm

Lowest Oil level -100mm

Max. Operation Capacity 50.5m3

Normal Operation Capacity 34.9m3

Page 3: Sop of turbine lubrication oil system

Oil Cooler

No. of Cooler 2 (1W+ 1S)

Cooling Area 610m3

Cooling Oil Flow 290m3/h

Cooling Water Flow 500m3/h

Inlet/ Outlet Oil Temp. 65C/45C

Cooling Water Temp. 38C

Oil Fume SeparatorNo. of Separator 1

Power 60kW

Operating Pressure 1 MPa (10 kg/cm2)

Operating Temp. < 80 C

Electric Heater

No. of Heater 6

Supply AC

Heat the oil up to 35C

Heating surface not higher than 150C

Heating surface not Lower than 100C

Main Oil Pump

Design Head

Motor Power

Rated Flow

Working Speed

Rated Voltage AC 415V

Main Suction Pump

Design Head 22.4m

Motor Power 45kW

Rated Flow 6300 ltr/min.

Working Speed 1450 r/min.

Rated Voltage AC415V

SOP – Turbine Lubricating Oil System, Rev-0 3

Page 4: Sop of turbine lubrication oil system

SOP – Turbine Lubricating Oil System, Rev-0

1

Turbine Oil PumpDesign Head 35.8m

Motor Power 55kW

Rated Flow 4685 ltr/min.

Rated Voltage AC415V

Emergency Oil Pump

Design Head 31.4m

Motor Power 40kW

Rated Flow 3820 ltr./min.

Working Speed

Rated Voltage DC220V

Jacking Oil Pump

Design Head

Motor Power

Rated Flow 34.3 kg/cm2 ~ 180 kg/cm2

Rated Voltage

Booster Oil Pump

Design Head

Motor Power

Rated Flow

Rated Voltage

Q uali ty Re q uire me nts f or T ur bi ne Oi l

a) Excellent thermal and oxidation stability.

b) Good Viscosity-temperature characteristics and proper

viscosity. c) Good low temperature operating performance.

d) Excellent demulsibility.

e) Excellent defoaming performance.

f) Good rust and corrosion

Page 5: Sop of turbine lubrication oil system

SOP – Turbine Lubricating Oil System, Rev-0

2

resistance. g) Good air release

property.

Page 6: Sop of turbine lubrication oil system

SOP – Turbine Lubricating Oil System, Rev-0

3

L ube oil sys te m - Star t- up C he c ks be f or e Oper ati on

1. Any PTW is not pending for Turbine Lubrication System equipment such as MOP, TOP, MSP, EOP, JOP, BOP, Oil Fume Separator, Exhauster, Oil Cooler etc and related equipments.

2. Lube oil in the main oil tank must be clean and free from debris.

3. Lube oil tank level > 100 mm.

4. Check that oil temperature in the tank must be 35C.

5. Check and confirm that the vacuum of the main oil tank is satisfactory.

6. The power supply of all the electric accessories is correct.

7. The instrument air system has been put into operation and the supply air pressure to the instrument and control system is normal.

8. The entire local indication instrument (Pressure Gauge, Temperature gauge, Differential pressure gauge) are calibrated & functioning properly.

9. All isolation valves of pressure gauges, temperature gauges and temp. switches are open.

10. Check from the observation hole that the oil flow at the oil cooler shell side is normal.

11. Check and confirm that the lube oil system does not leak oil.

12. Valve Checks -

a) Check and confirm that all the drain valves close.

b) Operate the oil cooler changeover valve to select the operating oil

cooler. c) Close the oil cooler water chamber oil drain valve.

d) Open the water chamber vent valve.

e) Open the cooling water inlet/outlet valves.

f) When water overflows from the water chamber, close the water chamber vent valve.

13. Oil Cooler Changeover valve test -

a) Open the isolating valve on the oil cooler oil filling pipe.

b) Check from the observation hole that the oil flow at the two shell sides of the oil

cooler. c) Use the oil cooler changeover valve to change over the oil cooler.

d) Restore the oil cooler changeover valve to the original state.

Page 7: Sop of turbine lubrication oil system

SOP – Turbine Lubricating Oil System, Rev-0

6

I ni tial S tar t up

1. Prior to start up; confirm that all the system start up checks are completed.

2. Start the main oil tank fume extractor & exhaust fan.

3. When the oil temperature in the oil tank is lower than 20OC, turn off the cooling water of oil cooler heat the oil to 35OC.

4. When the Oil Temperature is 35C (Maintained by Electric Heater in MOT) then Start Turbine Oil pumps (TOP), & Operate the Oil system for circulation.

5. Due to oil circulation in the pipe line temperature of the oil will increase & when it is up to 38 C, then put the oil cooler in service.

6. When the suction Pressure of Jacking Oil Pump is adequate i.e. … . then start the JOP & observe the Discharge pressure. When the discharge pressure of JOP is adequate i . e . 18 M P a ( 180 k g/c m 2 ) then pressurized oil will lift up the journals of each bearing to the design height at least 0 . 02 mm m i n . & 0 . 1 m m m a x at each bearing.

7. Now, the turning gear can be operated, and the unit oil system is ready for start.

{The turning motor is not allowed to start until the bearing oil supply pressure exceeds 0.137 MPa(1.37 kg/cm2) and jacking oil pump oil pressure exceeds 7 MPa (70 kg/cm2)}.

8. Start the MSP (Main Suction Pump), when the impulse starting speed of the unit is 2000 rpm, stop the JOP.

9. During the unit speed up, MSP and TOP should operate normally to supply lubricating oil to the unit.

10. When the Turbine speed is 2850 rpm then MOP will be in operation and observe the MOP suction oil pressure before the turbine front bearing housing should be approx. 0.1 MPa (1 kg/cm2).

11. With the rising of turbine main shaft speed MOP starts to deliver oil. The oil supply pump will operate according to the oil flow of MOP so that the output oil pressure is low. This low pressure will last till the Booster oil Pump (BOP) supplies oil together with the oil supply pump and finally take the place of it.

12. The operation of the pumps should be monitored during the turbine main shaft rotating speed rises to the rated speed till the final adjustment of the system is completed.

13. When the unit speed is 3000 rpm and the system oil pressure are stabilized

i.e a) MOP Suction pressure - 0.1 - 0.15 MPa (1 kg/cm2 1.5

kg/cm2)

b) MOP discharge pressure - 1.205 MPa. (12.05 kg/cm2)

Page 8: Sop of turbine lubrication oil system

SOP – Turbine Lubricating Oil System, Rev-0

6

c) Bearing Inlet pressure - 0.14 - 0.18 MPa. (1.4 kg/cm2 -1.8

kg/cm2) Then first stop the MSP & after that stop the TOP.

Page 9: Sop of turbine lubrication oil system

SOP – Turbine Lubricating Oil System, Rev-0

1

14. When the MOP is in service & Lube Oil system pressure is stabilized. Then put the system inAUTO MODE.(i.e. Turn control switch to AUTO for TOP, EOP & MSP)

Nor mal O per ati on (AUT O M ODE )

1. When the turbine Speed is 3000 rpm, MOP (Discharge pressure-1.205Mpa) will supply the lube oil to all the bearings. (Inlet bearing pressure is 0.14 - 0.18 MPa.).

2. In case of any abnormality following valves on the oil turbine should be adjusted and be locked after adjustment.

• Power oil throttle valve.

• Bypass valve.

• Over flow valve

The above valves should be adjusted according to the following procedure at the rated turbine speed before the TOP & Start up pump (MSP) are stopped.

a) Adjust the power throttle valve so that the main oil pump suction reaches the design value at the front bearing housing of the steam turbine.

b) Check the bearing oil supply manifold and through overflow valve overflow amount.

c) At the same time adjust bypass valve and power oil throttle valve so that the bearing oil supply manifold and overflow valve release amount reach the required value.

3. If the oil pressure drop to 0.115 Mpa or the outlet pressure of MOP is lower than 1.205 MPa, it gives alarm & start TOP (Meanwhile Check for the cause of oil pressure drop)

4. When the Oil pressure still drops after TOP has started, EOP should start when Oil pressure drops to 0.105MPa.

5. When the Suction pressure of MOP or Oil pressure drop is lower than 0.07MPa, the MSP starts and Shutdown the Unit.

C he c ks d ur i ng Oper at i on

1. Check from the observation hole that all bearing oil drains are satisfactory.

2. Check and confirm that the bearing lube oil temperature is in the allowable range.

3. When the oil temperature in the Oil tank below 20C, turn off the cooling water of Oil cooler &heat the oil to 35C by Electric heater.(When the surface temp. is higher than 150C, stop heating and if Temperature is decreased to

100C, Restart heating)

4. Oil level at tank level should between the highest level (+100 mm) & lowest level (-100 mm).

Page 10: Sop of turbine lubrication oil system

SOP – Turbine Lubricating Oil System, Rev-0

2

5. Unit bearings requires inlet oil temperature of 40-45C and normal return oil temperature of less than 75C. (Normally the water flow through the oil coolers should be adjusted according to the oil temperature in the lube oil header to ensure bearing inlet oil temperature is in accordance with requirement.)

S hutd own C onditi on

1. In case of normal or emergency shutdown (hand trip or unit trip), the auxiliary oil pump (TOP) &startup oil pump (MSP) must start automatically before the turbine decelerates to 2850 rpm.

2. Shaft Jacking device (JOP) starts when the turbine decelerates to 2000 rpm.

3. In case of Auxiliary pump failure, EOP should be interlocked to ensure safe shutdown.

4. Stop the Jacking oil pump (JOP) and TOP oil pump only after the turning gear stops.

5. After check, stop the turning gear and then stop the jacking oil pump and finally stop the TOP Pump.

6. Confirm that emergency oil pump can start automatically.

7. Stop the emergency oil pump.

8. Close the oil cooler cooling water inlet and outlet valves.

9. Stop the turbine oil purifier.

10. If necessary, stop the oil tank fume extractor.

P r oce d ur e ide ntif icati on

Procedure Title: Standard Operating Procedure of Turbine Lube Oil system

Prepared by: Ajit Kumar