Prepared For: Engineering Applications EAI, LLC 726 Abbot Rd East Lansing, MI 48823
Date: May 07, 2015 Customer P.O. Number: To Follow
Sold To: State of Michigan DTMB P.O. Box 30026 Lansing, MI 48909
Job Name: SOM Jackson State Office Building
Trane U.S. Inc. is pleased to provide the enclosed submittal for your review and approval. Product Summary
Tag(s) Qty Product RTU-1 & 2 2 Commercial Rooftop Air Conditioning Units (Midrange)
Bill Antcliff Trane 3350 Pine Tree Road Lansing, MI 48911 Phone: (517) 337-6517 Cell: (517) 898-4068 Fax: (517) 337-9493
The attached information describes the equipment we propose to furnish for this project, and is submitted for your approval.
Submittal
J:\JOBS\70\27633\4\SOM Jackson State Office Building_Pre-Purchase RTU Package_Trane RTU Submittal For Approval.doc
X
BAK 5-29-2015
EAI Proj # 1521
Table Of Contents
Product Summary ........................................................................................................................... 1
Commercial Rooftop Air Conditioning Units (Midrange) (Item A1) ........................................... 3
Tag Data .................................................................................................................................................. 3
Product Data ............................................................................................................................................ 3
Performance Data .................................................................................................................................... 4
Mechanical Specifications ........................................................................................................................ 6
Unit Dimensions ..................................................................................................................................... 10
Fan Curve .............................................................................................................................................. 13
Weight, Clearance & Rigging Diagram ................................................................................................... 14
Accessory .............................................................................................................................................. 16
Field Installed Options - Part/Order Number Summary ............................................................ 24
Commercial Rooftop Air Conditioning Units (Midrange) ......................................................................... 24
SOM Jackson State Office Building May 07, 2015
FLD = Furnished by Trane U.S. Inc. / Installed by Others
Equipment Submittal Page 3 of 24
Commercial Rooftop Air Conditioning Units (Midrange) (Qty: 2) Item Tag(s) Qty Description Model Number
A1 RTU-1, RTU-2 2 70 Ton Packaged Industrial Rooftop Unit SXHLF704
Product Data
Item: A1 Qty: 2 Tag(s): RTU-1, RTU-2 DX Cooling Only w/ Extended Casing R410A Refrigerant 70 Nominal Ton Unit 460 / 3 / 60 100% Exhaust - 10 Hp w/ Statitrac 600 rpm – Exhaust Fan 0-100% Economize w/ Comparative Enthalpy Controls & DCV w/ Traq Flow Sensor Grease Lines & Filter Gauge 2.00" Spring Isolators MERV-8 Hi-Efficiency Throw Away Filter
Final Filter Rack w/ Cam Flo XLT 12” Pocket Filter 40 HP DDP 80W Supply Fan 2000 rpm - Supply fan VAV- Discharge Temp Control Supply & Exhaust Fan w/ VFD with Bypass Low Ambient Damper(s) Control cULus Non-Fused Unit Disconnect Switch EISA Std Motors w/ Shaft Grounding Ring Remote Human Interface (Fld) Ventilation Override Module Access Doors BACnet Communication Interface Module Supply Fan Piezometer Temperature Sensor (Fld) Factory-Powered 15A GFI Convenience Outlet Standard Flat Roof Curb (Fld, Ships Knocked Down) Duct Mounted CO2 Sensor (Fld) Start-Up Services 1
st Year Parts, Labor & Refrigerant Warranty
2nd
– 5th Year Parts & Refrigerant Warranty
Additional Field Services:
� 4-Hours of Owner Training
� 1st Year Maintenance Contract w/ 4-Quarterly Visits (12-Months From The Date of Start-Up)
� Filter Changes Per Contract Documents
SOM Jackson State Office Building May 07, 2015
FLD = Furnished by Trane U.S. Inc. / Installed by Others
Equipment Submittal Page 4 of 24
�
Performance Data
Tags RTU-1, RTU-2
Design airflow (cfm) 25000
Exhaust Airflow (cfm) 23000
Cooling EDB (F) 76.00
Cooling EWB (F) 62.00
Ambient DB (F) 95.00
Leaving Coil DB (F) 51.27
Leaving Coil WB (F) 50.74
Leaving Unit DB (F) 54.69
Leaving Unit WB (F) 52.20
Gross total capacity (MBh) 804.08
Gross sensible capacity (MBh) 711.15
Gross latent capacity (MBh) 92.93
Net total capacity (MBh) 709.28
Net sensible capacity (MBh) 616.35
Net sensible heat ratio (%) 86.90
Supply duct static pressure (in H2O) 3.265
Return duct static pressure (in H2O) 0.500
Component S.P. drop (in H2O) 1.715
Total static pressure (in H2O) 5.480
Supply motor BHP calculated (bhp) 34.66
Supply fan RPM calculated (rpm) 1981
Exhaust static pressure (in H2O) 0.507
Exhaust motor BHP calculated (bhp) 9.35
Exhaust fan RPM calculated (rpm) 623
System power (kW) 94.24
EER @ AHRI (EER) 10.6
Minimum circuit ampacity (A) 183.18
Maximum overcurrent protection (A) 200.00
Minimum disconnect switch size (A) 203.00
Recommended dual element (A) 200.00
Compressor 1 count (Each) 4.00
Compressor 1 RLA (A) 25.50
Supply fan motor FLA (A) 24.70
Supply motor count ( ) 2
Supply fan count (Each) 2.00
Condenser fan FLA (A) 10.80
Exhaust fan motor FLA (A) 12.60
Other FLA (A) 2.00
Evaporator face area (sq ft) 43.00
Min. unit operating weight (lb) 8970.0
Max. unit operating weight (lb) 12143.0
Fan motor heat (MBh) 94.80
SOM Jackson State Office Building May 07, 2015
FLD = Furnished by Trane U.S. Inc. / Installed by Others
Equipment Submittal Page 5 of 24
Tags RTU-1, RTU-2
Discharge duct - 63 Hz (dB) 98
Discharge duct - 125 Hz (dB) 96
Discharge duct - 250 Hz (dB) 91
Discharge duct - 500 Hz (dB) 89
Discharge duct - 1 kHz (dB) 86
Discharge duct - 2 kHz (dB) 82
Discharge duct - 4 kHz (dB) 80
Discharge duct - 8 kHz (dB) 77
Return duct - 63 Hz (dB) 90
Return duct - 125 Hz (dB) 91
Return duct - 250 Hz (dB) 84
Return duct - 500 Hz (dB) 80
Return duct - 1 kHz (dB) 77
Return duct - 2 kHz (dB) 75
Return duct - 4 kHz (dB) 71
Return duct - 8 kHz (dB) 68
Run acoustics Yes
Exhaust fan - 63 Hz (dB) 83
Exhaust fan - 125 Hz (dB) 82
Exhaust fan - 250 Hz (dB) 77
Exhaust fan - 500 Hz (dB) 75
Exhaust fan - 1 kHz (dB) 72
Exhaust fan - 2 kHz (dB) 70
Exhaust fan - 4 kHz (dB) 67
Exhaust fan - 8 kHz (dB) 62
Desired reheat set point (F) 70.00
EDB in HGRH (F) 73.00
EWB in HGRH (F) 64.00
Ambient DB in HGRH (F) 75.00
Ambient WB in HGRH (F) 68.00
Installed point load 1 (lb) 848.5
Installed point load 2 (lb) 928.2
Installed point load 3 (lb) 933.5
Installed point load 4 (lb) 1013.2
Installed point load 5 (lb) 1008.8
Installed point load 6 (lb) 1088.5
Installed point load 7 (lb) 1085.0
Installed point load 8 (lb) 1164.7
Installed point load 9 (lb) 1169.1
Installed point load 10 (lb) 1248.8
Total installed weight (lb) 10488.3
First X dimension (ft) 16.74
First Y dimension (ft) 5.01
Installed point load 1 - X (in) 4.000
Installed point load 1 - Y (in) 4.000
Installed point load 2 - X (in) 101.000
Installed point load 2 - Y (in) 112.000
Installed point load 3 - X (in) 187.000
Installed point load 4 - X (in) 274.000
Installed point load 5 - X (in) 370.000
Rated capacity at AHRI (tons) 67.50
HFCF-410A refrigerant charge - circuit 1 (lb) 41.5
HFCF-410A refrigerant charge - circuit 2 (lb) 39.8
IEER (EER) 15.4
Supply fan efficiency (%) 62.22
SOM Jackson State Office Building May 07, 2015
FLD = Furnished by Trane U.S. Inc. / Installed by Others
Equipment Submittal Page 6 of 24
Mechanical Specifications - Commercial Rooftop Air Conditioning Units (Midrange) Item: A1 Qty: 2 Tag(s): RTU-1, RTU-2 General - R410A Units shall be specifically designed for outdoor rooftop installation on a roof curb and be completely factory assembled and tested, piped, internally wired, fully charged with R-410A compressor oil and shipped in one piece. Units shall be available for direct expansion cooling only, or direct expansion cooling with natural gas, electric, hot water or steam heating. Filters, outside air system, exhaust air system, optional non-fused disconnect switches and all operating and safety controls shall be furnished factory installed. All units shall be cULus approved and factory run tested. Cooling capacity shall be rated in accordance with AHRI Standard 360. All units shall have decals and tags to aid in service and indicate caution areas. Electrical diagrams shall be printed on long life water resistant material and shall ship attached to control panel doors. Casing Exterior panels shall be zinc coated galvanized steel, phosphatized and painted with a slate grey air-dry finish durable enough to withstand a minimum of 500 hours consecutive salt spray application in accordance with standard ASTM B117. Screws shall be coated with zinc-plus-zinc chromate. Heavy gauge steel hinged access panels with tiebacks to secure door in open position shall provide access to filters and heating sections. Refrigeration components, supply air fan and compressor shall be accessible through removable panels as standard. Unit control panel, filter section, and gas heating section shall be accessible through hinged access panels as standard. Optional Double Wall Construction hinged access doors shall provide access to filters, return/exhaust air, heating and supply fan section. All access doors and panels shall have neoprene gaskets. Interior surfaces or exterior casing members shall have 1/2" Tuf-Skin fiberglass insulation. Unit base shall be watertight with heavy gauge formed load bearing members, formed recess and curb overhang. Unit lifting lugs shall accept chains or cables for rigging. Lifting lugs shall also serve as unit tiedown points. Compressors - R410A The Trane 3-D Scroll compressors have a simple mechanical design with only three major moving parts. Scroll type compression provides inherently low vibration. The 3-D Scroll provides a completely enclosed compressor chamber with optimized scroll profiles which leads to increased efficiency. The 3-D Scroll includes a direct-drive, 3600 rpm, suction gas cooled hermetic motor. Dependent on the compressor model, motor protection is provided by either a patented motor cap and integral line break motor protector or an external 24 VAC module which provides protection against incorrect phase sequence, excess motor temperatures, over current protection, and phase loss. Trane 3-D compressor includes centrifugal oil pump, scroll tips seals, internal heat shield that lowers the heat transfer from discharge and suction gas, oil level sight glass and oil charge valve. Some compressor models also provide a dip tube that allows for oil draining, in addition to a low leakage internal discharge check valve to help prevent refrigerant migration. Each compressor shall have a crankcase heater installed, properly sized to minimize the amount of liquid refrigerant present in the oil sump during off cycles. Phase and Voltage Monitor - R410A Standard on 20-75T air-cooled, 24-89T evaporative condensing units. Protects 3-phase equipment from phase loss, phase reversal and low voltage. Any fault condition will produce a Failure Indicator LED and send the unit into an auto stop condition. cULus approved. Supply Fan Supply fan motors are either open drip-proof or enclosed fan cooled. All supply fans shall be dynamically balanced in factory. Supply fan shall be test run in unit and shall reach rated rpm. All 60 Hz supply fan motors meet the Energy Independence Security Act of 2007 (EISA). All 50 Hz supply fan motors meet the U.S. Energy Policy Act of 1992 (EPACT). Direct-Drive Plenum Supply Fan Supply fan shall be [one] [two] single width, single inlet 9-blade plenum fan. Fan blades shall be aluminum backward-inclined airfoil. Plenum fans shall be direct-driven. Entire assembly shall be completely isolated from unit and fan board by 2" deflection spring isolation. Multiple fan widths shall be available to optimize efficiency. Fan shall not require routine maintenance such as fan bearing lubrication, belt tensioning and replacement, sheave alignment, and setscrew torque checks. Evaporator Coil - R410A Internally enhanced copper tubing of 3/8" or 1/2" O.D. shall be mechanically bonded to heavyduty aluminum fins of configured design. All coils shall be equipped with thermal expansion valves and factory pressure and leak tested.
SOM Jackson State Office Building May 07, 2015
FLD = Furnished by Trane U.S. Inc. / Installed by Others
Equipment Submittal Page 7 of 24
Air-Cooled Condenser Coil - R410A Condenser coils shall have all Aluminum Microchannel coils. All coils shall be leak tested at the factory to ensure pressure integrity. The condenser coil is pressure tested to 650 psig. Subcooling circuit(s) shall be provided as standard. Supply Airflow Measurement (Piezometer) Plenum supply fan shall have an airflow measurement device to measure differential pressure and to calculate fan airflow. The device shall be capable of measuring airflow within + or - 5 percent total accuracy when operating within the stable operating region of the fan curve. Fan airflow performance and noise levels shall not be affected by the installation of the device. The fan inlet shall not be obstructed by the airflow measurement device Note: Transmitter must be customer-supplied & field installed. Condenser Fans and Motors All condenser fans shall be vertical discharge, direct drive fans, statically balanced, with steel blades and zinc plated steel hubs. Condenser fan motors shall be three-phase motors with permanently lubricated ball bearings, built-in current and thermal overload protection and weathertight slingers over motor bearings. Ventilation Override Module (VOM) With the Ventilation Override Module installed, the unit can be programmed to transition to up to 5 different programmed sequences for Smoke Purge, Evacuation, Pressurization, Purge, Purge with duct control sequence and Unit off. The transition occurs when a binary input on the VOM is closed (shorted); this would typically be a hard wired relay output from a smoke detector or fire control panel. <Enter Text Here> Unit Controller DDC microprocessor controls shall be provided to control all unit functions. The control system shall be suitable to control CV or VAV applications. The controls shall be factory-installed and mounted in the main control panel. All factory-installed controls shall be fully commissioned (run tested) at the factory. The unit shall have a Human Interface Panel with a 16 key keypad, a 2 line X 40 character clear English display as standard to provide the operator with full adjustment and display of control data functions. The unit controls shall be used as a stand-alone controller, or as part of a building management system involving multiple units. 1 The unit shall be equipped with a complete microprocessor control system. This system shall consist of temperature and pressure (thermistor and transducer) sensors, printed circuit boards (modules), and a unit mounted HumanInterface Panel. Modules (boards) shall be individually replaceable for ease of service. All microprocessors, boards and sensors shall be factory mounted, wired and tested. The microprocessor boards shall be stand-alone DDC controls not dependent on communications with an on-site PC or a Building Management Network. The microprocessors shall be equipped with on-board diagnostics, indicating that all hardware, software and interconnecting wiring are in proper operating condition. The modules (boards) shall be protected to prevent RFI and voltage transients from affecting the board's circuits. All field wiring shall be terminated at separate, clearly marked terminal strip. Direct field wiring to the I/O boards is not acceptable. The microprocessor's memory shall be non-volatile EEPROM type requiring no battery or capacitive backup, while maintaining all data. 2 Zone sensors shall be available in several combinations with selectable features depending on sensor. 3 The Human Interface Panel's keypad display character format shall be 40 characters x 2 lines. The character font shall be 5 x 7 dot matrix plus cursor. The display shall be Supertwist Liquid Crystal Display (LCD) with blue characters on a ray/green background which provides high visibility and ease of interface. The display format shall be in clear English. Two or three digit coded displays are not acceptable. 4 The keypad shall be equipped with 16 individual touch-sensitive membrane key switches. The switches shall be divided into four separate sections and be password protected from change by unauthorized personnel. The six main menus shall be STATUS, SETPOINTS, DIAGNOSTICS, SETUP, CONFIGURATION and SERVICE MODE.
SOM Jackson State Office Building May 07, 2015
FLD = Furnished by Trane U.S. Inc. / Installed by Others
Equipment Submittal Page 8 of 24
Modulating 100 Percent Exhaust Fan with Statitrac Control Two, double-inlet, forward-curved fans shall be mounted on a common shaft with fixed sheave drive. All fans shall be dynamically balanced and tested in factory before being installed in unit. Exhaust fan shall be test run as part of unit final run test. Unit shall reach rated rpm before fan shaft passes through first critical speed. Fan shaft shall be mounted on two grease lubricated ball bearings designed for 200,000-hour average life. Optional extended grease lines shall be provided to allow greasing of bearings from unit filter section. Fan motor and assembly shall be mounted on common base to allow consistent belt tension with no relative motion between fan and motor shafts. Entire assembly shall be completely isolated from unit and fan board by double deflection, rubber in shear isolators or spring isolation on motor sizes larger than five hp. For both CV and VAV rooftops, the 100 percent modulating exhaust discharge dampers (or VFD) shall be modulated in response to building pressure. A differential pressure control system, (Statitrac), shall use a differential pressure transducer to compare indoor building pressure to outdoor ambient atmospheric pressure. The FC exhaust fan shall be turned on when required to lower building static pressure setpoint. The (Statitrac) control system shall then modulate the discharge dampers (or VFD) to control the building pressure to within the adjustable, specified dead band that shall be adjustable at the Human Interface Panel. All 60 Hz exhaust fan motors meet the Energy Independence Security Act of 2007 (EISA). Variable Frequency Drive General Description: The AC Drive and all associated optional equipment are UL listed according to Power Conversation Equipment cULus. The AC Drive is designed, constructed and tested in accordance with NEMA ICS, NFPA, and IEC standards. The Drive is housed in a metal NEMA 1 enclosure. All standard and optional features are included within the Drive enclosure, unless otherwise specified. The Drive converts incoming fixed frequency three-phase AC power into a variable frequency and voltage for controlling the speed of three-phase AC motors. DC link reactors are provided on both the positive and negative rails of the DC bus equal to 3% impedance to minimize power line harmonics. Full load amp ratings meet or exceed NEC Table 430-150. The Drive provides full rated output current continuously, 110% of rated current for 60 seconds and 160% of rated current for up to 0.5 second while starting. Isolation is provided between the Drive's power circuitry and control circuitry to ensure operator safety and to protect connected electronic control equipment from damage caused by voltage spikes, current surges, and ground loop currents. Audible motor noise is minimized through the use of an adjustable carrier frequency. Carrier frequency is automatically adjusted to optimize motor and AC Drive efficiencies while reducing motor noise. Operating range, ambient temperature, -10 to 50C (14 to 104F), 0 to 95% relative humidity, non-condensing, AC line voltage variation, -10 to +10% of nominal with full output Protective Features Class 10 I2t electronic motor overload protection for single motor applications is provided. Protection against input transients, loss of AC line phase, output short circuit, output ground fault, over-voltage, under voltage, AC Drive over-temperature and motor over-temperature. All faults are displayed in plain English. Protection from AC Drive sustained power or phase loss. Full rated output with an input voltage as low as 90% of nominal. Continuous operation with reduced output with an input voltage as low as 164 V AC for 208/230 volt units, 313 V AC for 460 volt units, and 394 volts for 600 volts units. Semi-conductor rated input fuses to protect power components. A "signal loss detection" circuit senses the loss of an analog input signal such as 4 to 20 mA or 0 to 10 V DC, and is programmable to react as desired in such an instance. Default: After 10-second time out the Drive will shut off. Will function normally when the keypad is removed while the AC Drive is running and continue to follow remote commands. AC Drive catches rotating motor operating forward or reverse up to full speed. The AC Drive is rated for 100,000 amperes interrupting capacity (AIC). Includes current sensors on three output phases to detect and report phase loss to the motor. Identifies which of the output phases is low or lost. Continues to operate without faulting until input voltage reaches 300 V AC on 208/230 volt units, 539 V AC on 460 volt units, and 690 volts on 600 volt units Interface Features Off/Stop and Auto/Start selector switches provided to start and stop the AC Drive and determine the speed reference. On units with bypass, an AC Drive/Off/Bypass Hand selector switch will be provided in the unit control box. In case of an external current overload, a normally closed dry contact will stop the motor whether in DRIVE or BYPASS mode. In DRIVE mode speed reference is provided by a 0 to 10 V DC analog input. The display is programmable to display in 9 languages including English, Spanish and French. The display has four lines, with 20 characters on three lines and eight large characters on one line. The following points are controlled and/or accessible: AC Drive Start/Stop. Speed reference, Fault diagnostics, Meter points to include - Motor power in HP, Motor power in kW, Motor kW-hr, Motor current, Motor voltage, Hours run, DC link voltage, Thermal load on motor, Thermal load on AC Drive and Heatsink temperature. The AC Drive stores in memory the last 10 faults and related operational data. Four simultaneous displays are available, frequency or speed, run time, output amps and output power. The following displays are accessible from the keypad. Reference Signal Value, Output Frequency in Hz or percent, Output Amps, Motor HP, Motor kW, kW hour, Output Voltage, DC Bus Voltage, AC Drive Temperature in degrees, and Motor Speed in RPM.
SOM Jackson State Office Building May 07, 2015
FLD = Furnished by Trane U.S. Inc. / Installed by Others
Equipment Submittal Page 9 of 24
Bypass control Provides full nominal airflow in the event of drive failure. Internal Shaft Grounding Ring Motors have internal bearing protection for use with VFDs. Economizer Control with Comparative Enthalpy Used with the fresh air economizer, two enthalpy sensors are provided to compare total heat content of the indoor air and outdoor air to determine the most efficient air source when economizing. TRAQ (Outside Air Measurement) TRAQ shall include Ventilation Control Module (VCM). The VCM shall be linked to the Intellipak UCM to control the minimum fresh air entering the unit. Using a velocity pressure sensing ring, the VCM monitors and controls the quantity of fresh air entering the unit. This allows it to control to the minimum outside airflow setpoint. An optional temperature sensor can be connected to the VCM which enables it to control a field installed fresh air preheater; and an optional carbon dioxide sensor can be connected to the VCM to control the carbon dioxide reset. Option is cULus approved. Economizer Control with Dry Bulb Used with the fresh air economizer, an outdoor temperature sensor is included for comparing the outdoor dry bulb temperature to a locally adjustable temperature setpoint. The setpoint is programmed at the human interface, or remote human interface, to determine if outdoor air temperature is suitable for economizer operation. Temperature Sensor Bullet or pencil type sensor that could be used for temperature input such as return air duct temperature. Remote Human Interface Panel (RHI) Remote Human Interface Panel can perform all the same functions as unit mounted Human Interface Panel, except for the Service Mode. Up to 4 rooftop units can be monitored and controlled with a single Remote Human Interface Panel. This panel uses the same attractive enclosure as our Tracker¿ building control panel. With features such as a 2 line X 40 character clear English display, a red LED light to indicate an alarm condition (alarm also shown on the two line display), a simple 16 key keypad that is used in conjunction with the display, to prompt the infrequent user when making desired changes and an attractive hinged door makes the RHI very suitable for mounting on any wall. The RHI can be mounted inside a building, up to 5,000 feet from the unit. The RHI is wired to the IPCB mounted in the rooftop with twisted wire pair communication wiring and 24V control wiring. BACnet Communication Interface Module Provides control and monitoring of the rooftop by Tracer SC or a 3rd party building management system utilizing BACnet protocol. Demand Control Ventilation Provide demand control ventilation (DCV) system fully integrated with unit economizer. Controller shall minimize fresh air intake during periods of low occupancy based on parts per million space CO2 in response to a customer defined parts per million CO2 setpoint. CO2 setpoint, and minimum DCV fresh air damper position shall be programmable at the human interface, or building management system Note: CO2 sensor used with Demand Control Ventilation must be powered from an external power source or separate 24 VAC transformer. BAYSENS016 -Temperature Thermistor The temperature thermistor is used to communicate temperature changes in either the Zone, Return Air, Supply Air or Outside Ambient. Equipment manufactured by Trane that includes required start-up and sold in North America will not be warranted by Trane unless Trane or its authorized independent Trane commercial sales office performs the startup on the equipment. Differential Pressure Gauge A factory-installed, dial-type, differential pressure gauge shall be piped to both sides of the filter to indicate status. Gauge shall maintain a +/- 5 percent accuracy within operating temperature limits of -20°F to 120°F. Gauge shall be flush-mounted with casing outer wall. Filter sections consisting of pre- and post-filters shall have a gauge for each.
SOM Jackson State Office Building May 07, 2015
FLD = Furnished by Trane U.S. Inc. / Installed by Others
Equipment Submittal Page 10 of 24
Unit Dimensions - Commercial Rooftop Air Conditioning Units (Midrange) Item: A1 Qty: 2 Tag(s): RTU-1, RTU-2
EX
HA
US
T
2.
LO
W A
MB
IEN
T D
AM
PE
R O
NLY
CO
ME
S W
ITH
SE
LE
CT
ED
UN
IT
3. O
VE
RA
LL U
NIT
WID
TH
IN
CR
EA
SE
S 5
/8"
BE
YO
ND
LIF
TIN
G L
UG
WIT
H U
LT
RA
LO
W L
EA
K P
OW
ER
E
XH
AU
ST
DA
MP
ER
S.
69
3/8
"
39
4 9
/16
"
11
9 3
/8"
39
8 1
3/1
6"
14
4 1
/8"
114
3/8
"
92
9/1
6"
7 1
/16
" 29"
238
5/1
6"
22
1/8
"
20
3/8
"
17
7/8
"
15 7
/8"
9 7
/8"
8 1
5/1
6"
7 1
5/1
6"
10 1
/4"
70
3/8
"8
7 1
/4"
92
3/1
6"
53
3/8
"
5 1
3/1
6"
5 1
3/1
6"
94 3
/16
"8
1 1
/16"
119
3/8
"
18
4 5
/16
"
SU
PP
LY
60/7
0/7
5 T
ON
LE
FT
SID
E V
IEW
LIF
TIN
G P
OIN
TS
X 6
60/7
0/7
5 T
ON
PL
AN
VIE
W
4 1
/8"
CO
NN
. T
HR
U
BA
SE
FO
R P
OW
ER
SU
PP
LY
1 1
/8"
CO
ND
UIT
D.C
CO
NT
RO
L C
IRC
UIT
1 1
/8"
CO
ND
UIT
A.C
CO
NT
RO
L C
IRC
UIT
1 1
/8"
CO
ND
UIT
AC
&
DC
CO
NT
RO
L C
IRC
UIT
1 3
/8"
DR
AIN
HO
LE
S
(BO
TH
SID
E)
60
/70
/75
TO
N F
RO
NT
VIE
W
OP
TIO
NA
L L
OW
AM
BIE
NT
DA
MP
ER
SE
E N
OT
E 2
60
/70
/75
TO
N P
LA
N V
IEW
OF
UN
IT
NO
TE
S:
1.
VE
RIF
Y W
EIG
HT
, C
ON
NE
CT
ION
, A
ND
ALL
DIM
EN
SIO
N
WIT
H I
NS
TA
LLE
R
DO
CU
ME
NT
S B
EF
OR
E IN
ST
ALL
AT
ION
SE
E N
OT
E 3
1"
NP
T-F
CO
ND
EN
SA
TE
DR
AIN
(B
OT
H S
IDE
)1"
NP
T-F
CO
ND
EN
SA
TE
DR
AIN
(B
OT
H S
IDE
)
(NO
T U
SE
D O
N U
NIT
S
WIT
H D
DP
FA
NS
)
SOM Jackson State Office Building May 07, 2015
FLD = Furnished by Trane U.S. Inc. / Installed by Others
Equipment Submittal Page 11 of 24
Unit Dimensions - Commercial Rooftop Air Conditioning Units (Midrange) Item: A1 Qty: 2 Tag(s): RTU-1, RTU-2
1"
5 5/8"
3 5/8"
1"
5 13/16"
5/8"1"
90°
30°
3"
9/16"
1 5/8"
5/8"
4 13/16"
2 3/4"1"
5/8" 1/2"
2 1/2"
3"
3"
2 1/2"
3/8"
DETAIL
TYPICAL ROOF CURB AND BASE PAN DETAIL
SHIPS WITH CURB
FIELD INSTALLED
GASKET
TYPICAL PEDESTAL AND BASE PAN DETAIL
DETAIL
PEDESTAL
UNIT BASE
LIFTING LUG
4" LONG
LIFTING LUG
4" LONG
2" X 4" NAILER
(FURNISHED WITH KIT)
ROOF CURB
TYPICAL PEDESTAL AND BASE
DIMENSION DRAWING
SOM Jackson State Office Building May 07, 2015
FLD = Furnished by Trane U.S. Inc. / Installed by Others
Equipment Submittal Page 12 of 24
Unit Dimensions - Commercial Rooftop Air Conditioning Units (Midrange) Item: A1 Qty: 2 Tag(s): RTU-1, RTU-2
110.012.6
61.010.8
SXHLF70 (70Ton)
414-506460603
N/AN/AN/AN/A
ELECTRICAL / GENERAL DATA
TONS
COMPRESSOR
SUPPLY FAN MOTOR
CONDENSER FAN MOTOR FILTERS - TYPE
REFRIGERANT TYPE
EXHAUST / RETURN FAN MOTOR
ELECTRIC HEATER
GAS HEATING - PERFORMANCE
Notes:
1. LOAD 1=Current of the largest motor (compressor or fan motor); LOAD 2=Sum of the currents of all remaining motors; LOAD 3 =Current of electric heaters
LOAD 4 =Control Power Transformer (20-40 and 24-48 ton units add 3 FL amps for wire sizing formula, 50-75 and 59 - 89 ton units add 6 FL amps)
2. For Electric Heat MCA, MOP, RDE values, calculate for both cooling and heating modes. (When determining LOADS, the compressors
do not operate when the unit is in heating mode) (On 70-89 ton single source units, heating Load 4 = 12 amps on 200,230 volt units and
9 amps on 460,575 volt units)
3. If selected Max Over Cur is less than the Min CIr Amp, then select the lowest maximum fuse size which is equal to or larger than the Min Cir
Amp, provided the selected fuse size does not exceed 800 amps.
4. If the selected Recommended Dual Element fuse size is greater than the selected Max Over Cur Protection value, then select the Recommended Dual
Element fuse size value to equal the Max Over Protection value.
5. Compressor KW at AHRI rating conditions of 80/67 -95
6. Refrigerant charge is an approx. value. For a more precise value, see unit nameplate and service instructions.
7. Sump Heater is an optional feature.
Model (Tonnage):
Unit Operating Voltage Range:
Unit Primary Voltage:
Unit Hertz:
Unit Phase:
EER:
IEER:
HEATING - GENERAL DATA
Heating Input:
Heating Output:
Capacity Steps:
Gas inlet pressure: (in w.c.)
Gas Pipe Connection Size:
Compressor 1 Count:
Compressor 1 RLA:
Compressor 2 Count:
Compressor 2 RLA:
Compressor 3 Count:
Compressor 3 RLA:
Electric Heater Kw:
Electric Heater Full Load Amps:
Number of Fans:
Number of Motors:
Horsepower (Each):
Supply Fan Motor Full Load Amps:
Supply Fan Efficiency:
Number:
Horsepower (each):
Condenser Fan Motor Full Load Amps (Total):
Number:
Horsepower (Each):
Exhaust Fan Motor Full Load Amps:
Type:
Furnished:
Number:
Recommended Size:
Charge Type:
Factory Charge (Circuit #1):
Factory Charge (Circuit #2):
PREFILTERS
Furnished:
Number:
Recommended Size:
10.6 EER15.4 EER
R-410A
EVAPORATIVE CONDENSER
Pump Horsepower:
Pump Full Load Amps:
Sump Heater Full Load Amps:
Sump Heater kW:
(7)
(6)
41.5 lb39.8 lb
2.00 Each2 40 HP DDP 80W24.70 A62.22 %
4.00 Each25.50 AValue not availableValue not availableValue not availableValue not available
FINAL FILTERS - TYPE
Type:
Furnished:
Number:
Recommended Size:
PREFILTERS
Furnished:
Number:
Recommended Size:
SOM Jackson State Office Building May 07, 2015
FLD = Furnished by Trane U.S. Inc. / Installed by Others
Equipment Submittal Page 13 of 24
Fan Curve - Commercial Rooftop Air Conditioning Units (Midrange) Item: A1 Qty: 2 Tag(s): RTU-1, RTU-2
7.
50
b
hp
10
.0
0
bh
p
15
.0
0
bh
p
20
.0
0
bh
p
25
.0
0
bh
p
30
.0
0
bh
p
40
.0
0
bh
p
50
.0
0
bh
p
1000 RPM
1100 RPM
1200 RPM
1300 RPM
1400 RPM
1500 RPM
1600 RPM
1700 RPM
1800 RPM
1900 RPM
2000 RPM
2100 RPM
44 %WO 50 %WO
60 %WO
70 %WO
80 %WO
90 %WO
UnitSize:
Operating Airflow: 25000.00 cfm
Operating Static Pressure: 5.48 in H2O
Operating RPM: 1981.00
Operating Brake Horse Power: 34.66 bhp
Altitude: 0.00
Design Temp: 76.00 F
Date: 5/7/15
0
1
2
3
4
5
6
7
8
9
10
11
12
0 5000 10000 15000 20000 25000 30000 35000 40000 45000
2-2707DPLA01FN
To
tal
Sta
tic
Pr
es
su
re
(in
H2
O)
Airflow (cfm)
63Hz 125Hz 250Hz 500Hz 1 kHz 2 kHz 4 kHz 8 kHz
Discharge duct: 98 96 91 89 86 82 80 77Return duct: 90 91 84 80 77 75 71 68Exhaust fan: 83 82 77 75 72 70 67 62
SOM Jackson State Office Building May 07, 2015
FLD = Furnished by Trane U.S. Inc. / Installed by Others
Equipment Submittal Page 14 of 24
Weight, Clearance & Rigging Diagram - Commercial Rooftop Air Conditioning Units (Midrange) Item: A1 Qty: 2 Tag(s): RTU-1, RTU-2
48"
72"
96"
96"
96"
144"
CLEARANCE
CLEARANCE
CLE
AR
AN
CE
CL
EA
RA
NC
E
CLEARANCE
RIGGING AND CLEARANCE
AIR COOLED DRAWING
SOM Jackson State Office Building May 07, 2015
FLD = Furnished by Trane U.S. Inc. / Installed by Others
Equipment Submittal Page 15 of 24
Weight, Clearance & Rigging Diagram - Commercial Rooftop Air Conditioning Units (Midrange) Item: A1 Qty: 2 Tag(s): RTU-1, RTU-2
N/A2. Double wall :
29"
96"
194 5/16"
0,0
X
Y
Center of Gravity X: 16.74 ftCenter of Gravity Y: 5.01 ft
Point Load 1: 848.5 lbPoint Load 2: 928.2 lbPoint Load 3: 933.5 lbPoint Load 4: 1013.2 lbPoint Load 5: 1008.8 lbPoint Load 6: 1088.5 lbPoint Load 7: 1085.0 lbPoint Load 8: 1164.7 lbPoint Load 9: 1169.1 lbPoint Load 10: 1248.8 lb
Total Weight: 10488.3 lb
PL 2, X1 PL 4, X2 PL 6, X3 PL 8, X4 PL 10, X5
PL 1, X1 PL 3, X2 PL 5, X3 PL 7, X4 PL 9, X5
Added Weight
1. IRU:
Notes:
1. The actual weight is stamped on the unit nameplate.
2. The weight shown represent the typical unit operating weights for the unit selected.
3. Add weight to the total unit weight.
4. Most Design Special weights are not displayed.
(3)
(3)
Point load X location 1: 4.000 inPoint load X location 2: 101.000 inPoint load X location 3: 187.000 inPoint load X location 4: 274.000 inPoint load X location 5: 370.000 inPoint load X location 6: N/APoint load X location 7: N/APoint load X location 8: N/APoint load X location 9: N/APoint load X location 10: N/APoint load Y location 1: 4.000 inPoint load Y location 2: 112.000 in
CENTER OF GRAVITY AND INSTALL WEIGHT X-Y POINTS
AIR COOLED DRAWING
Y
X
SOM Jackson State Office Building May 07, 2015
FLD = Furnished by Trane U.S. Inc. / Installed by Others
Equipment Submittal Page 16 of 24
Accessory - Commercial Rooftop Air Conditioning Units (Midrange) Item: A1 Qty: 2 Tag(s): RTU-1, RTU-2
L1
117 119
L3
L3L1
CIRCUIT #2
ELECTRIC HEAT 200V/230V/60 HZ
UNITS ONLY
L2
4TB2, 4S15
118
L2
LINE VOLTAGE
CIRCUIT #1
MAIN UNIT CONTROL
1 2 3
L1 L2 L3
L3L2L1
1TB1 OR1S14
LINE VOLTAGE
4U15
HYDRONIC HEAT
ACTUATOR
CONNECT STEAM OR
HOT WATER VALVE AS
SHOWN WHEN REQUIRED
HEATINGSECTION
CONDENSERSECTION
37M 36AL
T1 T2
483A484A
(-)(+)
BLK WHT
SPLICE SPLICE
4
3 3
ADVERTENCIAiVOLTAJE PELIGROSO!
DESCONECTE TODA LA ENERGIA ELECTRICA,
INCLUSO LAS DESCONEXIONES REMOTAS Y
SIGA LOS PROCEDIMIENTOS DE CIERRE Y
ETIQUETADO ANTES DE PROCEDER AL
SERVICIO. ASEGURESE DE QUE TODOS
LOS CAPACITORES DEL MOTOR HAYAN
DESCARGADO EL VOLTAJE ALMACENADO.
PARA LAS UNIDADES CON EJE DE
DIRECCION DE VELOCIDAD VARIABLE,
CONSULTE LAS INSTRUCCIONES PARA LA
DESCARGA DEL CONDENSADOR.
EL NO REALIZAR LO ANTERIORMENTE
INDICADO, PODRIA OCASIONAR LA MUERTE
O SERIAS LESIONES PERSONALES.
DO NOT ENERGIZE UNIT
UNTIL CHECK-OUT AND
START-UP PROCEDURE HAS
BEEN COMPLETED.
IMPORTANT!
HAZARDOUS VOLTAGE!
WARNING AVERTISSEMENTTENSION DANGEREUSE!
SI NO LO HACE, PUEDE OCASIONAR DANO AL
DISENADAS PARA ACEPTAR OTROS TIPOS DE
LAS TERMINALES DE LA UNIDAD NO ESTAN
IUTILICE UNICAMENTE CONDUCTORES DE
PEUT ENDOMMAGER L'EQUIPEMENT.
L'UTILISATION DE TOUT AUTRE CONDUCTEUR
EQUIPO.
PRECAUCION
CONDUCTORES.
COBRE!
FAILURE TO DO SO MAY CAUSE DAMAGE TO
ACCEPT OTHER TYPES OF CONDUCTORS.
UNIT TERMINALS ARE NOT DESIGNED TO
CONCUES POUR RECEVOIR D'AUTRES TYPES
LES BORNES DE L'UNITE NE SONT PAS
N'UTILISER QUE DES CONDUCTEURS EN
THE EQUIPMENT.
ATTENTION
DE CONDUCTEURS.
CUIVRE!
CAUTIONUSE COPPER CONDUCTORS ONLY!
COUPER TOUTES LES TENSIONS ET
OUVRIR LES SECTIONNEURS A DISTANCE,
PUIS SUIVRE LES PROCEDURES DE
VERROUILLAGE ET DES ETIQUETTES AVANT
TOUTE INTERVENTION. VERIFIER QUE TOUS
LES CONDENSATEURS DES MOTEURS SONT
DECHARGES. DANS LE CAS D'UNITES
COMPORTANT DES ENTRAINEMENTS A
VITESSE VARAIBLE, SE REPORTER AUX
INSTRUCTIONS DE L'ENTRAINEMENT POUR
DECHARGER LES CONDENSATEURS.
NE PAS RESPECTER CES MESURES DE
PRECAUTION PEUT ENTRAINER DES
BLESSURES GRAVES POUVANT ETRE
MORTELLES.
DISCONNECT ALL ELECTRIC POWER
INCLUDING REMOTE DISCONNECTS
AND FOLLOW LOCK OUT AND TAG
PROCEDURES BEFORE SERVICING.
INSURE THAT ALL MOTOR
CAPACITORS HAVE DISCHARGED
STORED VOLTAGE. UNITS WITH
VARIABLE SPEED DRIVE, REFER
TO DRIVE INSTRUCTIONS FOR
CAPACITOR DISCHARGE.
FAILURE TO DO THE ABOVE
BEFORE SERVICING COULD RESULT
IN DEATH OR SERIOUS INJURY.
Note:
All wiring and components shown dashed to be
supplied and installed by the customer in
accordance with local electrical codes.
EXTERNAL FIELD MOUNTED DEVICE
INSIDE UNIT CONTROL BOX
DEVICE PREFIX LOCATION CODE
CONDENSER SECTION
AIR HANDLER SECTION
LOCATION
5
HEATING SECTION4
3
2
1
AREA
SOM Jackson State Office Building May 07, 2015
FLD = Furnished by Trane U.S. Inc. / Installed by Others
Equipment Submittal Page 17 of 24
Accessory - Commercial Rooftop Air Conditioning Units (Midrange) Item: A1 Qty: 2 Tag(s): RTU-1, RTU-2
268 1/2"
2"
2"
110 5/16"
119 15/16"
7"
94 1/16"
14 1/16"
12 11/16"
1 1/8"
12 11/16"
6 3/16"
2 3/8"
91 3/4"
29 5/16"24" 42"
94 5/16"
268 1/8"
1 13/16"
121 7/16"
7 1/2"
6"
1 13/16" 6"
22 5/8"
233"
60/70/75 TON PLAN VIEW
60/70/75 TON ISOMETRIC VIEW
RETURN /
EXHAUST
OPENING
SUPPLY
OPENING
PEDESTAL
PEDESTAL
RETURN / EXHAUST OPENING
SUPPLY OPENING
SOM Jackson State Office Building May 07, 2015
FLD = Furnished by Trane U.S. Inc. / Installed by Others
Equipment Submittal Page 18 of 24
Accessory - Commercial Rooftop Air Conditioning Units (Midrange) Item: A1 Qty: 2 Tag(s): RTU-1, RTU-2
ALL WIRING AND COMPONENTS SHOWN DASHED TO BE SUPPLIED AND INSTALLED BY THE
CUSTOMER IN ACCORDANCE WITH LOCAL ELECTRICAL CODES.
CUSTOMER CONNECTIONS - MAIN UNIT CONTROL (CIRCUIT #1) - ARE LOCATED IN THE
CONDENSER SECTION FOR 20 THRU 75 TON UNITS.
SEE CUSTOMER CONNECTION WIRE RANGE TABLE FOR ACCEPTABLE WIRE SIZES FOR
CONNECTION TO MAIN UNIT TERMINAL BLOCK (1TB1/4TB2) OR DISCONNECT
SWITCH (1S14/4S15).
WIRES TO THE OPTIONAL STEAM AND/OR HOT WATER HEAT VALVE ARE SUPPLIED WITH
THE UNIT. WIRE CONNECTIONS TO THE VALVE TO BE MADE BY THE CUSTOMER.
OPTIONAL 5U57 REMOTE ZONE TEMP SENSOR IS USED FOR UNOCCUPIED HEAT/COOL
TEMP CONTROL SENSING.
WHEN 5U69 REMOTE ZONE TEMP SENSOR IS USED, REMOVE 5U58 INTERGRAL ZONE
TEMP SENSOR ATTACHED TO TERMINALS S1 AND S2.
WIRES USE SHIELDED TWISTED PAIR WIRE.
USE SHIELDED TWISTED PAIR WIRE. WRAP SHIELDS WITH TAPE TO PREVENT CONTACT
WITH GROUND.
REMOVE JUMPER (1TB4-15 & 1TB4-16) AND INSTALL HIGH DUCT TEMP T-STAT /OR
FIELD SUPPLIED DEVICE.
REMOVE JUMPER (1TB4-17 & 1TB4-18) WHEN FIELD SUPPLIED
EXTERNAL AUTO/STOP SWITCH (5S67) IS INSTALLED.
CHANGEOVER (5K87) AVAILABLE ONLY ON HYDRONIC HEAT UNITS OR MODULATING
GAS HEAT UNITS.
ALARM OUTPUT SWITCHES ON ANY MANUAL RESET DIAGNOSTIC.
OPTIONAL HEAT MODULE AUX. TEMP (5RT16) IS USED FOR MORNING WARM-UP
CONTROL ON UNITS WITH HEATING OPTION.
TERMINAL BLOCK 1TB17 AND ASSOCIATED WIRING REQUIRED WITH GBAS (1U51) OPTION.
DEMAND LIMIT RELAY (5K89) TO BE PROVIDED BY CUSTOMER.
VENTILATION OVERRIDE MODE CONTACTS RATED 12MA @ 24VDC MINIMUM
(5K90 - 5K91 - 5K92 - 5K93 - 5K94) TO BE PROVIDED BY CUSTOMER.
WIRE NODES 533 & 534 REQUIRED WITH BAS/NETWORK COMM MODULE (1U54) OPTION.
USE SHIELDED TWISTED PAIR WIRE.
FIELD CONNECTIONS TO DRIVE VAV BOXES FULL OPEN DURING NIGHT SETBACK MODE.
15A FUSE REPLACEMENT IS REQUIRED FOR 50 THRU 60 TON - 0.50 KVA TRANSFORMER
WITH 200V - 230V - 460V OR 575V UNIT VOLTAGE.
20A FUSE REPLACEMENT IS REQUIRED FOR 50 THRU 60 TON - 0.50 KVA TRANSFORMER
WITH 380V OR 415V UNIT VOLTAGE.
CONTACTS RATED 12 MA @ 24VDC MINIMUM.
CONNECT TO 24VAC CLASS 2 CIRCUITS ONLY.
REMOVE JUMPER WHEN OPTIONAL FIELD SUPPLIED OUTSIDE AIR SENSOR
(3RT3) IS INSTALLED AND THE UNIT DOES NOT HAVE ECONOMIZER.
FIELD SUPPLIED AND INSTALLED OCCUPIED/UNOCCUPIED CONTACTS (5K86)
FOR USE ON UNITS WITHOUT REMOTE PANEL WITH NIGHT SETBACK (5U58).
GBAS 0-5V OPTION CONNECTIONS.
GBAS 0-10V OPTION CONNECTIONS.
FOR GBAS INPUTS AI1-AI4, "GBAS 0-5V" REQUIRES 0-5V VDC
AND "GBAS 0-10V" REQUIRES 0-10VDC.
"ACTIVE DIAGNOSTICS (BO5)" APPEARS WITH BOTH "GBAS 0-5V" AND "GBAS 0-10V".
SEE FUSE REPLACEMENT TABLE ON VFD PANEL FOR VFD POWER FUSES (F40, F41, F42).
SWITCH A53, LOCATED ON THE VFD, MUST BE SET TO "U" (OFF).
NOTES:
1
2
3
4
6
7
8
9
10
11
13
14
15
16
17
19
21
22
23
24
25
26
27
28
29
30
12
18
SOM Jackson State Office Building May 07, 2015
FLD = Furnished by Trane U.S. Inc. / Installed by Others
Equipment Submittal Page 19 of 24
Accessory - Commercial Rooftop Air Conditioning Units (Midrange) Item: A1 Qty: 2 Tag(s): RTU-1, RTU-2
CUSTOMER CONNECTION WIRE RANGE
NOTES: UNITS WITH MAIN POWER
TERMINAL BLOCK (ALL VOLTAGES)
UNITS WITH MAIN POWER
DISCONNECT SWITCH (ALL VOLTAGES)A. BLOCK SIZE & DISCONNECT SIZE
ARE
CALCULATED BY SELECTING THE
SIZE
GREATER THAN OR EQUAL TO 1.15 X
(SUM OF UNIT LOADS). SEE UNIT
LITERATURE FOR UNIT LOAD
VALUES.
335 AMP (1) #6 - 350 MCM 100 AMP (1) #14 - 1/0
760 AMP (2) #4 - 500 MCM 250 AMP (1) #4 - 350 kcmil
840 AMP (2) #2 - 600 MCM 400 AMP (1) OR #1 - 600 kcmil OR
(2) #1 - 250 kcmil
600 AMP (2) 250 - 500 MCM
1000 AMP (3) 3/0 - 500 kcmil
FUSE REPLACEMENT TABLE
CONDENSER FAN FUSE
1F1 THRU 1F6 CLASS RK5
UNIT VOLTAGE 200 230 380 415 460 575
TIME DELAY 25A 25A 15A 15A 15A 15A
CONTROL POWER FUSE
CONTROL (1T1) TRANSFORMER RATING0.25
KVA
0.30
KVA
0.50
KVA
0.75
KVA
1.00
KVA
1.50
KVA
1F7
CLASS CC - TYPE
FNQ-R
20-30 TON 6.25A 6.25A -- 10A -- --
40 TON 15A 20A -- 20A -- --
50-60 TON -- -- 15A -- 20A --
70-75 TON -- -- -- -- 15A 20A
ELECTRIC HEAT FUSE 4F19 THRU 4F36, 4F46, 47, 48 CLASS K5 60A
COMPRESSOR PROTECTION FUSE 1F44 & 1F45 TYPE MTH 6A
TRANSFORMER CIRCUIT FUSE 1F72 THRU 1F74 TYPE FNQ-R 15A
STANDARD MOTORS
UNIT
VOLTAGE
FUSE
RATING1.5 HP 3 HP 5 HP 7.5 HP 10 HP 15 HP 20 HP 25 HP 30 HP 40 HP
200V/60/3 600V 15A 35A 45A 70A 100A 150A 175A 225A 225A 400A
230V/60/3 600V 15A 25A 45A 70A 80A 125A 150A 200A 225A 350A
380V/50/3 600V 10A 15A 30A 50A 60A 90A 110A 125A 125A N/A
415V/50/3 600V 10A 15A 30A 45A 50A 90A 100A 125A 125A N/A
460V/60/3 600V 10A 15A 25A 35A 40A 70A 80A 100A 125A 175A
575V/60/3 600V 10A 15A 15A 25A 30A 40A 50A 60A 90A 100A
HIGH EFFICIENCY MOTORS
UNIT
VOLTAGE
FUSE
RATING1.5 HP 3 HP 5 HP 7.5 HP 10 HP 15 HP 20 HP 25 HP 30 HP 40 HP
200V/60/3 600V N/A 40A 45A 80A 100A 125A 175A 225A 225A 350A
230V/60/3 600V N/A 25A 45A 60A 90A 125A 150A 175A 225A 300A
460V/60/3 600V N/A 15A 25A 35A 45A 60A 90A 110A 125A 150A
575V/60/3 600V 10A 15A 15A 25A 30A 40A 50A 60A 90A 100A
OPTIONAL CONVENIENCE OUTLET FUSE
1F55 AND 1F56 (TIME DELAY TYPE FNQ-R FUSE)
200V/60/3 230V/60/3 380V/50/3 415V/50/3 460V/60/3 575V/60/3
12A 10A N/A N/A 5A 4A
VFD PROTECTION FUSES
----------------
OPTIONAL SUPPLY FAN
20 THRU 75 TON
1F57-1F62
-----------------
OPTIONAL EXHAUST /
RETURN
FAN
20 THRU 75 TON
1F63-1F65
(CLASS "T" FUSES)
BLOCK SIZE WIRE QTY CONNECTOR WIRE RANGE DISCONNECT SIZE WIRE QTY CONNECTOR WIRE RANGE
SOM Jackson State Office Building May 07, 2015
FLD = Furnished by Trane U.S. Inc. / Installed by Others
Equipment Submittal Page 20 of 24
Accessory - Commercial Rooftop Air Conditioning Units (Midrange) Item: A1 Qty: 2 Tag(s): RTU-1, RTU-2
411
409
HEAT 7
COOL 8
SYS ON 9
SERVICE 10
GND 11
COMM (+) 12
COMMON
1
5S71
EMERGENCY
STOP SWITCH
435 431
J1-1 (+)
436
537
538
408 1
J1-3
2
5U57
REMOTE
ZONE
TEMP
SENSOR
408
409
403
436
537
538
5U66
REMOTE
HUMAN
INTERFACE
MODULEJ2-1 (+)
J1-2 (-)
J2-2 (-) J2-3
EARTH
GROUND
1
2
ZONE
TEMP
4 MODE
5U68
ZONE PANEL
417
416
415
414
413
418
5U58
REMOTE PANEL
WITH NSB
5K86
OCCUPIED/
UNOCCUPIED
CONTACTS
408
5U61
ZONE
RESET
TEMP
SENSOR
424425
5U59
REMOTE
PANEL
7 HEAT
9 SYS ON
10 SERVICE
6 GND
413
414
415
416
417
8 COOL
409
412
1
2
3
4
12
13
14
15
5
6
7
8
9
16
17
18
19
20
10
11
21
22
1TB4
410
412
413
414
415
416
417
425
424
403
435
437
431
434
438
437
438
5S67
EXTERNAL AUTO/STOP
SWITCH
434 438
410 3 SA CSP
VAV ZONE
RESET OPTION
5U69
REMOTE
ZONE TEMP
SENSOR
S1
S2
40324 VAC 14
418
8
7
24
21
21112110
10
11
7
9
6
ADVERTENCIAiVOLTAJE PELIGROSO!
DESCONECTE TODA LA ENERGIA ELECTRICA,
INCLUSO LAS DESCONEXIONES REMOTAS Y
SIGA LOS PROCEDIMIENTOS DE CIERRE Y
ETIQUETADO ANTES DE PROCEDER AL
SERVICIO. ASEGURESE DE QUE TODOS
LOS CAPACITORES DEL MOTOR HAYAN
DESCARGADO EL VOLTAJE ALMACENADO.
PARA LAS UNIDADES CON EJE DE
DIRECCION DE VELOCIDAD VARIABLE,
CONSULTE LAS INSTRUCCIONES PARA LA
DESCARGA DEL CONDENSADOR.
EL NO REALIZAR LO ANTERIORMENTE
INDICADO, PODRIA OCASIONAR LA MUERTE
O SERIAS LESIONES PERSONALES.
DO NOT ENERGIZE UNIT
UNTIL CHECK-OUT AND
START-UP PROCEDURE HAS
BEEN COMPLETED.
IMPORTANT!
HAZARDOUS VOLTAGE!
WARNING AVERTISSEMENTTENSION DANGEREUSE!
SI NO LO HACE, PUEDE OCASIONAR DANO AL
DISENADAS PARA ACEPTAR OTROS TIPOS DE
LAS TERMINALES DE LA UNIDAD NO ESTAN
IUTILICE UNICAMENTE CONDUCTORES DE
PEUT ENDOMMAGER L'EQUIPEMENT.
L'UTILISATION DE TOUT AUTRE CONDUCTEUR
EQUIPO.
PRECAUCION
CONDUCTORES.
COBRE!
FAILURE TO DO SO MAY CAUSE DAMAGE TO
ACCEPT OTHER TYPES OF CONDUCTORS.
UNIT TERMINALS ARE NOT DESIGNED TO
CONCUES POUR RECEVOIR D'AUTRES TYPES
LES BORNES DE L'UNITE NE SONT PAS
N'UTILISER QUE DES CONDUCTEURS EN
THE EQUIPMENT.
ATTENTION
DE CONDUCTEURS.
CUIVRE!
CAUTIONUSE COPPER CONDUCTORS ONLY!
COUPER TOUTES LES TENSIONS ET
OUVRIR LES SECTIONNEURS A DISTANCE,
PUIS SUIVRE LES PROCEDURES DE
VERROUILLAGE ET DES ETIQUETTES AVANT
TOUTE INTERVENTION. VERIFIER QUE TOUS
LES CONDENSATEURS DES MOTEURS SONT
DECHARGES. DANS LE CAS D'UNITES
COMPORTANT DES ENTRAINEMENTS A
VITESSE VARAIBLE, SE REPORTER AUX
INSTRUCTIONS DE L'ENTRAINEMENT POUR
DECHARGER LES CONDENSATEURS.
NE PAS RESPECTER CES MESURES DE
PRECAUTION PEUT ENTRAINER DES
BLESSURES GRAVES POUVANT ETRE
MORTELLES.
DISCONNECT ALL ELECTRIC POWER
INCLUDING REMOTE DISCONNECTS
AND FOLLOW LOCK OUT AND TAG
PROCEDURES BEFORE SERVICING.
INSURE THAT ALL MOTOR
CAPACITORS HAVE DISCHARGED
STORED VOLTAGE. UNITS WITH
VARIABLE SPEED DRIVE, REFER
TO DRIVE INSTRUCTIONS FOR
CAPACITOR DISCHARGE.
FAILURE TO DO THE ABOVE
BEFORE SERVICING COULD RESULT
IN DEATH OR SERIOUS INJURY.
Note:
All wiring and components shown dashed to be
supplied and installed by the customer in
accordance with local electrical codes.
EXTERNAL FIELD MOUNTED DEVICE
INSIDE UNIT CONTROL BOX
DEVICE PREFIX LOCATION CODE
CONDENSER SECTION
AIR HANDLER SECTION
LOCATION
5
HEATING SECTION4
3
2
1
AREA
SOM Jackson State Office Building May 07, 2015
FLD = Furnished by Trane U.S. Inc. / Installed by Others
Equipment Submittal Page 21 of 24
Accessory - Commercial Rooftop Air Conditioning Units (Midrange) Item: A1 Qty: 2 Tag(s): RTU-1, RTU-2
3RT3
OPTIONAL
OUTSIDE
AIR
SENSOR
427
426
5K92
VENTILATION
OVERRIDE
MODE C CONTACTS
5K93
VENTILATION
OVERRIDE
MODE D CONTACTS
489 490
5K94
VENTILATION
OVERRIDE
MODE E CONTACTS
5K91
VENTILATION
OVERRIDE
MODE B CONTACTS
5K89
DEMAND
LIMIT
CONTACTS
426427
489
490 476
533
534
5RT16
HEAT
MODULE
AUX TEMP
BLU
WHT
5U70
REMOTE
MINIMUM
POSITION
POTENTIOMETER
475 476
TRACER
COMMUNICATIONS
533534
549
550
5K87
CHANGEOVER
CONTACTS
1TB5
443
444
1
444
443
2
3
4
12
13
14
15
5
6
7
8
9
16
17
18
19
20
10
11
21
22
475
523
524
525
526
527
549
550
528
529
530
531
532
528
5K90
VENTILATION
OVERRIDE
MODE A CONTACTS
524523
527
526
525
532
531
529 530
RED
}
16 15
21
16
14
16
16
16
17
21
12
2316
23
ADVERTENCIAiVOLTAJE PELIGROSO!
DESCONECTE TODA LA ENERGIA ELECTRICA,
INCLUSO LAS DESCONEXIONES REMOTAS Y
SIGA LOS PROCEDIMIENTOS DE CIERRE Y
ETIQUETADO ANTES DE PROCEDER AL
SERVICIO. ASEGURESE DE QUE TODOS
LOS CAPACITORES DEL MOTOR HAYAN
DESCARGADO EL VOLTAJE ALMACENADO.
PARA LAS UNIDADES CON EJE DE
DIRECCION DE VELOCIDAD VARIABLE,
CONSULTE LAS INSTRUCCIONES PARA LA
DESCARGA DEL CONDENSADOR.
EL NO REALIZAR LO ANTERIORMENTE
INDICADO, PODRIA OCASIONAR LA MUERTE
O SERIAS LESIONES PERSONALES.
DO NOT ENERGIZE UNIT
UNTIL CHECK-OUT AND
START-UP PROCEDURE HAS
BEEN COMPLETED.
IMPORTANT!
HAZARDOUS VOLTAGE!
WARNING AVERTISSEMENTTENSION DANGEREUSE!
SI NO LO HACE, PUEDE OCASIONAR DANO AL
DISENADAS PARA ACEPTAR OTROS TIPOS DE
LAS TERMINALES DE LA UNIDAD NO ESTAN
IUTILICE UNICAMENTE CONDUCTORES DE
PEUT ENDOMMAGER L'EQUIPEMENT.
L'UTILISATION DE TOUT AUTRE CONDUCTEUR
EQUIPO.
PRECAUCION
CONDUCTORES.
COBRE!
FAILURE TO DO SO MAY CAUSE DAMAGE TO
ACCEPT OTHER TYPES OF CONDUCTORS.
UNIT TERMINALS ARE NOT DESIGNED TO
CONCUES POUR RECEVOIR D'AUTRES TYPES
LES BORNES DE L'UNITE NE SONT PAS
N'UTILISER QUE DES CONDUCTEURS EN
THE EQUIPMENT.
ATTENTION
DE CONDUCTEURS.
CUIVRE!
CAUTIONUSE COPPER CONDUCTORS ONLY!
COUPER TOUTES LES TENSIONS ET
OUVRIR LES SECTIONNEURS A DISTANCE,
PUIS SUIVRE LES PROCEDURES DE
VERROUILLAGE ET DES ETIQUETTES AVANT
TOUTE INTERVENTION. VERIFIER QUE TOUS
LES CONDENSATEURS DES MOTEURS SONT
DECHARGES. DANS LE CAS D'UNITES
COMPORTANT DES ENTRAINEMENTS A
VITESSE VARAIBLE, SE REPORTER AUX
INSTRUCTIONS DE L'ENTRAINEMENT POUR
DECHARGER LES CONDENSATEURS.
NE PAS RESPECTER CES MESURES DE
PRECAUTION PEUT ENTRAINER DES
BLESSURES GRAVES POUVANT ETRE
MORTELLES.
DISCONNECT ALL ELECTRIC POWER
INCLUDING REMOTE DISCONNECTS
AND FOLLOW LOCK OUT AND TAG
PROCEDURES BEFORE SERVICING.
INSURE THAT ALL MOTOR
CAPACITORS HAVE DISCHARGED
STORED VOLTAGE. UNITS WITH
VARIABLE SPEED DRIVE, REFER
TO DRIVE INSTRUCTIONS FOR
CAPACITOR DISCHARGE.
FAILURE TO DO THE ABOVE
BEFORE SERVICING COULD RESULT
IN DEATH OR SERIOUS INJURY.
Note:
All wiring and components shown dashed to be
supplied and installed by the customer in
accordance with local electrical codes.
EXTERNAL FIELD MOUNTED DEVICE
INSIDE UNIT CONTROL BOX
DEVICE PREFIX LOCATION CODE
CONDENSER SECTION
AIR HANDLER SECTION
LOCATION
5
HEATING SECTION4
3
2
1
AREA
SOM Jackson State Office Building May 07, 2015
FLD = Furnished by Trane U.S. Inc. / Installed by Others
Equipment Submittal Page 22 of 24
Accessory - Commercial Rooftop Air Conditioning Units (Midrange) Item: A1 Qty: 2 Tag(s): RTU-1, RTU-2
450
509
543
542
543 VO
RELAY
OUTPUT
NO
COM
NC
NO
COM
NC
508
NC
COM
NO
509 NC
507
COM
508
NO507
545
546
1
2
3
4
12
13
14
15
5
6
7
8
9
16
17
18
19
20
10
11
21
22
1TB16
445
446
447
448
449
HEAT MODE RELAY OUTPUT
(HYDRONIC HEAT OR MODULATING
GAS HEAT)
NC
544
545
546
COM
NO
541
542
544
447
446
445
448
449
450
ALARM
OUTPUT
(24 VAC MAX)
541
DIRTY
FILTER
(BO1)
VAV BOX
RELAY
24 VAC MAX
612
613
612
613 (-)
(+)
5U108
SPACE
HUMIDITYSENSOR
614
615
616
NC
COM
615
616
NO 614
HUMIDIFICATION
}}
{{{
}}
508 (-)0-10 VDC
(AO1)}509 (+)
22
22
18
22
13
22
22
25
22
26
ADVERTENCIAiVOLTAJE PELIGROSO!
DESCONECTE TODA LA ENERGIA ELECTRICA,
INCLUSO LAS DESCONEXIONES REMOTAS Y
SIGA LOS PROCEDIMIENTOS DE CIERRE Y
ETIQUETADO ANTES DE PROCEDER AL
SERVICIO. ASEGURESE DE QUE TODOS
LOS CAPACITORES DEL MOTOR HAYAN
DESCARGADO EL VOLTAJE ALMACENADO.
PARA LAS UNIDADES CON EJE DE
DIRECCION DE VELOCIDAD VARIABLE,
CONSULTE LAS INSTRUCCIONES PARA LA
DESCARGA DEL CONDENSADOR.
EL NO REALIZAR LO ANTERIORMENTE
INDICADO, PODRIA OCASIONAR LA MUERTE
O SERIAS LESIONES PERSONALES.
DO NOT ENERGIZE UNIT
UNTIL CHECK-OUT AND
START-UP PROCEDURE HAS
BEEN COMPLETED.
IMPORTANT!
HAZARDOUS VOLTAGE!
WARNING AVERTISSEMENTTENSION DANGEREUSE!
SI NO LO HACE, PUEDE OCASIONAR DANO AL
DISENADAS PARA ACEPTAR OTROS TIPOS DE
LAS TERMINALES DE LA UNIDAD NO ESTAN
IUTILICE UNICAMENTE CONDUCTORES DE
PEUT ENDOMMAGER L'EQUIPEMENT.
L'UTILISATION DE TOUT AUTRE CONDUCTEUR
EQUIPO.
PRECAUCION
CONDUCTORES.
COBRE!
FAILURE TO DO SO MAY CAUSE DAMAGE TO
ACCEPT OTHER TYPES OF CONDUCTORS.
UNIT TERMINALS ARE NOT DESIGNED TO
CONCUES POUR RECEVOIR D'AUTRES TYPES
LES BORNES DE L'UNITE NE SONT PAS
N'UTILISER QUE DES CONDUCTEURS EN
THE EQUIPMENT.
ATTENTION
DE CONDUCTEURS.
CUIVRE!
CAUTIONUSE COPPER CONDUCTORS ONLY!
COUPER TOUTES LES TENSIONS ET
OUVRIR LES SECTIONNEURS A DISTANCE,
PUIS SUIVRE LES PROCEDURES DE
VERROUILLAGE ET DES ETIQUETTES AVANT
TOUTE INTERVENTION. VERIFIER QUE TOUS
LES CONDENSATEURS DES MOTEURS SONT
DECHARGES. DANS LE CAS D'UNITES
COMPORTANT DES ENTRAINEMENTS A
VITESSE VARAIBLE, SE REPORTER AUX
INSTRUCTIONS DE L'ENTRAINEMENT POUR
DECHARGER LES CONDENSATEURS.
NE PAS RESPECTER CES MESURES DE
PRECAUTION PEUT ENTRAINER DES
BLESSURES GRAVES POUVANT ETRE
MORTELLES.
DISCONNECT ALL ELECTRIC POWER
INCLUDING REMOTE DISCONNECTS
AND FOLLOW LOCK OUT AND TAG
PROCEDURES BEFORE SERVICING.
INSURE THAT ALL MOTOR
CAPACITORS HAVE DISCHARGED
STORED VOLTAGE. UNITS WITH
VARIABLE SPEED DRIVE, REFER
TO DRIVE INSTRUCTIONS FOR
CAPACITOR DISCHARGE.
FAILURE TO DO THE ABOVE
BEFORE SERVICING COULD RESULT
IN DEATH OR SERIOUS INJURY.
Note:
All wiring and components shown dashed to be
supplied and installed by the customer in
accordance with local electrical codes.
EXTERNAL FIELD MOUNTED DEVICE
INSIDE UNIT CONTROL BOX
DEVICE PREFIX LOCATION CODE
CONDENSER SECTION
AIR HANDLER SECTION
LOCATION
5
HEATING SECTION4
3
2
1
AREA
SOM Jackson State Office Building May 07, 2015
FLD = Furnished by Trane U.S. Inc. / Installed by Others
Equipment Submittal Page 23 of 24
Accessory - Commercial Rooftop Air Conditioning Units (Midrange) Item: A1 Qty: 2 Tag(s): RTU-1, RTU-2
DANFOSS VARIABLE FREQUENCY DRIVE
PROGRAMMING PARAMETERS
MENU PARAMETER DESCRIPTION SETTING
LOAD/MOTOR
1-21 MOTOR POWER
SET ONLY FOR
APPLICATIONS USING
3HP HIGH EFFICIENCY
MOTORS
1-22 MOTOR VOLTAGE
SET ONLY FOR
200/230V 60HZ
380/415V 50HZ
APPLICATIONS
1-24 MOTOR CURRENTSET BASED ON
MOTOR NAMEPLATE
1-25 MOTOR NOMINAL SPEED 1800 RPM
1-73 FLYING START ENABLED
BRAKES 2-01 DC BRAKE CURRENT 0%
REFERENCE/
RAMPS
3-15 REFERENCE 1 SOURCE ANALOG INPUT 53
3-41 RAMP 1 RAMP UP TIME 30 SECONDS
3-42 RAMP 1 RAMP DOWN TIME 30 SECONDS
LIMITS/
WARNINGS
4-12 MOTOR SPEED LOW LIMIT 22HZ
4-18 CURRENT LIMIT 100% RATED CURRENT
DIGITAL
IN/OUT
5-40[0] FUNCTION RELAY 1 NO ALARM
5-40[1] FUNCTION RELAY 2 RUNNING
SPECIAL
FUNCTIONS
14-01 SWITCHING FREQUENCY 4.5KHZ
14-12FUNCTION AT MAINS
IMBALANCEDERATE
14-20 RESET MODE AUTOMATIC RESET X 3
14-60FUNCTION AT OVER
TEMPERATUREDERATE
30
SOM Jackson State Office Building May 07, 2015
FLD = Furnished by Trane U.S. Inc. / Installed by Others
Equipment Submittal Page 24 of 24
Field Installed Options - Part/Order Number Summary
This is a report to help you locate field installed options that arrive at the jobsite. This report provides part or order numbers for each field installed option, and references it to a specific product tag. It is NOT intended as a bill of material for the job.
Product Family - Commercial Rooftop Air Conditioning Units (Midrange)
Item Tag(s) Qty Description Model Number
A1 RTU-1, RTU-2 2 70 Ton Packaged Industrial Rooftop Unit SXHLF704
Field Installed Option Description Part/Ordering Number
Remote human interface
Temperature sensor
Flat roof curb 0368-0165-0100
Duct mounted CO2 sensor BAYCO2K012A