2014-05-06 Software version Software Release Description DOL 53x / DOL 634 Version 4.2.3 Build 1 - 2017-03-09 Recommendations If upgrading a 2 house controller from a previous version 4.x the connections to terminal B2 and B15 must be moved. Now terminal B2 is used for house 1. And terminal B15 is used for house 2. Known Issues Central exhaust variants are limited to 6 MultiStep’s in this version It is possible to install install stepless tunnel fans in DOL 532 T, this is an error and will be removed in a later version. Changes and Error Corrections Stirfans are not uninstalled after power failure Version 4.2.2 Build 4 - 2017-01-16 Recommendations If upgrading a 2 house controller from a previous version 4.x the connections to terminal B2 and B15 must be moved. Now terminal B2 is used for house 1. And terminal B15 is used for house 2. Known Issues Central exhaust variants are limited to 6 MultiStep’s in this version It is possible to install install stepless tunnel fans in DOL 532 T, this is an error and will be removed in a later version. Changes and Error Corrections When resuming after alarm when feed buffer is not empty, it no longer starts filling the next destination Alarms can now be acknowledged from FOX Show connection and IO allocation is now updated for all changes to 'fans active at failure' state for MultiSteps It was not possible to change the extra ventilation temperature Manual control of flaps on Heat Recovery Unit is fixed The standalone heater active Yes/No menu disappeared if No was chosen. So it was not possible to activate the heating again.

Transcript of Software Release Description DOL 53x / DOL 634 - …cdn.skov.com/www/ControlSW/DOL 539...

Page 1: Software Release Description DOL 53x / DOL 634 - …cdn.skov.com/www/ControlSW/DOL 539 releases/4.2.3... · 4 Software Release Description ... Software version is available in the

2014-05-06

Software version

Software Release Description

DOL 53x / DOL 634

Version 4.2.3 Build 1 - 2017-03-09

Recommendations

If upgrading a 2 house controller from a previous version 4.x the connections to terminal B2 and B15 must be moved. Now terminal B2 is used for house 1. And terminal B15 is used for house 2.

Known Issues

Central exhaust variants are limited to 6 MultiStep’s in this version

It is possible to install install stepless tunnel fans in DOL 532 T, this is an error and will be removed in a later version.

Changes and Error Corrections

Stirfans are not uninstalled after power failure

Version 4.2.2 Build 4 - 2017-01-16

Recommendations

If upgrading a 2 house controller from a previous version 4.x the connections to terminal B2 and B15 must be moved. Now terminal B2 is used for house 1. And terminal B15 is used for house 2.

Known Issues

Central exhaust variants are limited to 6 MultiStep’s in this version

It is possible to install install stepless tunnel fans in DOL 532 T, this is an error and will be removed in a later version.

Changes and Error Corrections

When resuming after alarm when feed buffer is not empty, it no longer starts filling the next destination

Alarms can now be acknowledged from FOX

Show connection and IO allocation is now updated for all changes to 'fans active at failure' state for MultiSteps

It was not possible to change the extra ventilation temperature

Manual control of flaps on Heat Recovery Unit is fixed

The standalone heater active Yes/No menu disappeared if No was chosen. So it was not possible to activate the heating again.

Page 2: Software Release Description DOL 53x / DOL 634 - …cdn.skov.com/www/ControlSW/DOL 539 releases/4.2.3... · 4 Software Release Description ... Software version is available in the

2 Software Release Description

SRD

Version 4.2.1 Build 3 - 2016-10-24

Recommendations

If upgrading a 2 house controller from a previous version 4.x the connections to terminal B2 and B15 must be moved. Now terminal B2 is used for house 1. And terminal B15 is used for house 2.

New Functions

Known Issues

Central exhaust variants are limited to 6 MultiStep’s in this version

It is possible to install install stepless tunnel fans in DOL 532 T, this is an error and will be removed in a later version.

Changes and Error Corrections

Number of decimals shown when calibrating a bird weigher is increased from 1 to 3 for bird weigher 5 to 12. Is already 3 for bird weigher 1 to 4.

Destination feeding: If empty sensor is not empty before 30 minutes a Filling alarm is activated and controller is put to Pause state.

Added missing auto/manual menu for Flex heaters

GUI: Corrected that return button can disappear when editing values from the front page.

Version 4.2.0 Build 85 - 2016-10-12

Recommendations

If upgrading a 2 house controller from a previous version 4.x the connections to terminal B2 and B15 must be moved. Now terminal B2 is used for house 1. And terminal B15 is used for house 2.

New Functions

All versions

New USB Installer made for program update. When inserting a USB stick the new installer will automatically popup

o Select program, push the green check mark and follow the guide

Page 3: Software Release Description DOL 53x / DOL 634 - …cdn.skov.com/www/ControlSW/DOL 539 releases/4.2.3... · 4 Software Release Description ... Software version is available in the

Software Release Description 3

SRD

Dynamic Air for 1 zone, 2 zone and central exhaust

Floor heating

Water leakage supervision and alarm

Water reference curve can be adjusted.

Spray cooling renamed to Side cooling (for side mode)

Nozzle cleaning added

Poultry versions

Flexible filling (filling of too small hoppers possible)

“Skip-a-day” is silent (no filling/feeding on manual days)

Feed separation shutter can be installed if 2 or more cross augers are installed (destination feeding)

Flexible filling – several filling periods with different amounts

Added 24H clock, feed weigher and interval timers to front view.

Feed supplement. Function to add sea shells (pan or chain feeding).

Natural Ventilation

o Wind angle limitation handling added.

o Windward curtain position handling added.

Climate only versions: Support for 1 24 hour clock and 1 water meter.

Pig versions

Central exhaust

o Dynamic pressure control for central exhaust

o Dynamic MultiStep for central exhaust

Maximum of 4 flaps controls for outlets (2+2 meaning 2 flap controls in each of the 2 stepless groups)

Spraying function

CombiDiffuse inlet added

Behaviour control added

Known Issues

Central exhaust variants are limited to 6 MultiStep’s in this version

It is possible to install install stepless tunnel fans in DOL 532 T, this is an error and will be removed in a later version.

Changes and Error Corrections

Day number synchronization could happen if a climate + production controller is set to use only climate.

Incorrect behavior of inspection light in manual mode

Litter quality is now only available in a Broiler version

Feed demand sensor is now read correctly.

A new Feed selection mode is added. The mode is used to choose between the existing mode(per Destination) where a feed type for each destination is set, and a fixed feed type per animal. When this mode is selected a feed type/mix can be selected for all female destinations and another feed type/mix can be selected for all male destinations.

Temperature selection text 'DOL 15/114' is changed to 'DOL 114'

Page 4: Software Release Description DOL 53x / DOL 634 - …cdn.skov.com/www/ControlSW/DOL 539 releases/4.2.3... · 4 Software Release Description ... Software version is available in the

4 Software Release Description

SRD

Heat recovery cleaning: the part made by the heat recovery unit before cleaning is ignored during cleaning. This is made to secure against low temperature during cleaning if the same ventilation demand was moved to side outlets.

Humidity ventilation in pure tunnel could be kept high (up to 30%) even though the humidity was below set point.

Minimum ventilation curve was not visible in pure tunnel setup

Catching is no longer reset after reboot or power loss. Furthermore uninstall then install is always performed when changing install type (button->key->button).

FarmOnline: AirSpeed and ventilation was not disabled in sidemode / tunnel mode

Zone controlled inlet is now also working within Heat Recovery Unit ventilation mode.

If alarm "No feed to feed weigher" is activated the silo auger stop in "Stop time silo auger" and then reactivate in "Runtime silo auger".

In combi tunnel systems with Dynamic MultiStep or FreeRange installed the tunnel fans would not run correct.

Manual allocation of outside temperature allocation is no longer showing 0-10 volt inputs as an option

Weather station could not be installed as DOL 58

Added popup to alarm log. Press on an alarm to see the details

Trend curve on Pressure in Central Exhaust

Spray cooling is renamed to 'Side cooling'

Software update stability increased

Faster USB stick mount/unmount

Improved CAN communication

Simplified time synchronization so only NTP server needs to be configured

Fixed so SD card is no longer considered bad when writing large files. As a consequence of this fix the EMERGENCY MODE has been dropped.

Program update no longer available via normal user interface (new programs will be delivered with a program updater on the USB stick)

Fixed error with feed mixture and feed mixture 1, enable handler corrected.

Calibration of relay controlled winch motors will now always open the flaps.

Some settings of manual stepless-to-step could cause reboots every 18-20 minutes.

Automatic silo change when using electronic silos has been corrected.

If an automatic bird weigher is selected the user can now select Inspection weight instead of manual weight.

"Tip weigher log" renamed to "Feed counter" and "Tip weigher impulse" renamed to "Weigher impulse"

When restoring settings then it will also restore the active silos.

Corrected that destination feed hangs if resume and skip next destination.

Added "Program description" to CPU module menu

All bird weigher search limits are set to 10 % when a Breeder version is defaulted

All bird weigher correction factor values are set to 100 % when a Breeder version is defaulted.

Added reference values for water if broiler (ROSS 308 2014 As hatched)

If the silo auger is stopped because of a function in the controller, it is shown in the menu line "Feed supply state"

Corrected refill of destination feeding

Page 5: Software Release Description DOL 53x / DOL 634 - …cdn.skov.com/www/ControlSW/DOL 539 releases/4.2.3... · 4 Software Release Description ... Software version is available in the

Software Release Description 5

SRD

Network setup was not working

Shutter control for shared weigher has been updated to set correct position if in manual mode.

CO2 sensor option is now in-depended of the variant parameter of the CO2 minimum ventilation control

We only disable Dynamic Air control mode if NO dynamic Air is active.

Natural ventilation does now support half house brooding

Minimum air speed is no longer viewed in pure tunnel setups (like DOL 532 T). In stead the setting 'Stop cycle timer' is viewed.

Corrected that ghost objects are created when pulling a controller into FarmOnline.

Egg counters can use I/O cards type 15 and type 10

0-10 volt control of tunnel stepless is working

Removed problem with climate controllers that subscribed to production objects and got 250.000 objects (but a production controller on a similar network will still be troubled by many objects)

In 2-house controllers the use of Main I/O board terminal B2 and B15 is corrected. Now house 1 uses terminal B2. And house 2 uses terminal B15.

Version 4.1.0 Build 29 - 2015-12-17

Recommendations

New Functions

DOL 532T variant

Pressure control is optional in tunnel mode

Calibration of relay controlled winch motors without feedback is now made on a specified time of day

Qwerty keyboard introduced for entering texts (house name, file names etc)

Feed separation shutter for destination feedingNew mode for shared Feed weigher: “Shared without shutter”. Only possible to select when destination feeding.

Known Issues

Changes and Error Corrections

A total of 8 time hour clocks for breeder software

Relay controlled winch motors without feedback:

o Maximum runs before calibration of can be 999

o Calibration is done to the closest end position (calibrating to closed if opening is less than 50%, else calibration goes to fully open)

An explanation text is added to the popup dialogue “Emergency opening”, like “Emergency opening, high temperature” / “Emergency opening, high humidity”

It is now possible to selected the same icon on different pages when configuring user views.

Fixed error: More silos with the same feed type are selected after a change from Drum weigher to electronic silo weigher.

Master password did not work

Page 6: Software Release Description DOL 53x / DOL 634 - …cdn.skov.com/www/ControlSW/DOL 539 releases/4.2.3... · 4 Software Release Description ... Software version is available in the

6 Software Release Description

SRD

Preheating setpoint could not be adjusted in batch stop mode

Negative Pressure Adjustment with active pressure set-up is simplified to use only 1 curve

Default values for Dynamic multistep changed from 5 – 5 volt to 10 – 0 volt (for fan stopped – running maximum)

Heat recovery cleaning: the ventilation part made by the heat recovery unit before cleaning is ignored during cleaning. This is made to secure against low temperature during cleaning if the same ventilation demand was moved to the side outlets.

Version 4.0.0 Build 36 - 2015-09-03

Recommendations

New Functions

2 house controller

Floor heating

Reference curves for Pigs

Minimum ventilation in percent

Daily/advanced user screens are replaced by one level user screens that can be activated from the front

The user screens are automatic set to

o large icons if 6 or less icons are selected to the screen

o small icons if 7 to 16 icons are selected to the screen

The look of the icons are changed to a flat design

Software version is available in the first level of the service menu

User interface is updated to a flat icon design and general layout changes to header, text color and etc.

Adjusted eggs function added

Discarded eggs function added

Litter quality function added

New mode for shared Feed weigher: “Shared without shutter”. Only possible to select when destination feeding.

Known Issues

The front screen will sometimes shows three small icons where it should show 3 large icons

Changes and Error Corrections

I/O allocation of flaps did not work correctly in a 2 house controller

Fixed update problem (removed splash screen command)

Upgrade is now possible on CPU modules before version I

Page 7: Software Release Description DOL 53x / DOL 634 - …cdn.skov.com/www/ControlSW/DOL 539 releases/4.2.3... · 4 Software Release Description ... Software version is available in the

Software Release Description 7

SRD

Version 3.1.0 Build 77 - 2016-01-18

New Functions

Option to manually enter discarded eggs (breeder version)

Option to enter adjusted eggs and litter quality

Option to use cooling relay for humidification

Side cooling can be started before maximum ventilation, if outside temperature is above the set point for the house

PI control introduced on side cooling

Catching mode

o By a turnkey or a menu button

o Timing settings to stop feeding, set window for activation

o Settings for ventilation system during catching

o Settings for feeding, light during catching

Added support for DOL 58 weather sensor

Relay heat is synchronized with cycletimer on minimum inlet position

Minimum airspeed in tunnel is made as a batch curve

User offsets added to climate and production menu’s for all setpoint including a batch curve

Added 2 more 24 hour clocks to Breeder

Added 24 hour clock setting stop on time. The setting is user selectable to be set either to "on time" (relative) or "stop time" (absolute).

Feed eaten by dead birds are calculated.

Calculation of feed / animals corrected for feed eaten by birds that are now dead.

Calculation of weight of all birds added.

New matrix to support stop time in 24 hour clock.

Added individual search limits for bird weighers

Known Issues

Tunnel cooling type, mode and ratio’s must be checked after an upgrade.

o Type must be set to PAD or SPRAY, this is new to version 3.0. The default setting is PAD, which is the most used tunnel cooling type. But this type reset the mode to parallel.

o Mode must be set to parallel or sequence (sequence is only available if type is spray).

o Ratio of each tunnel cooling relay must be checked/set.

NOTE regarding heat recovery unit: When updating from a version 1.x or 2.x the negative pressure curve for heat recovery unit must be set manually (because the curve structure has changed)

In between functions do not activate the correct ventilation demand if heat recovery unit is set to active

Changes and Error Corrections

Side cooling can be synchronized with minimum inlet cycle timer

Page 8: Software Release Description DOL 53x / DOL 634 - …cdn.skov.com/www/ControlSW/DOL 539 releases/4.2.3... · 4 Software Release Description ... Software version is available in the

8 Software Release Description

SRD

If synchronization of humidification or cooling is active they are also kept OFF until delay time has elapsed (they could go ON if the demand was high enough).

Humidification is now stopped if temperature is below heat setpoint (it was ventilation setpoint before).

Tunnel cooling will start up with a (converted) side cooling demand if desert control is active. Conversion rate is 3:1

When switching from Natural mode to side or HRU the starting ventilation demand in side/HRU is set 25% or 75%. If Natural is stopped because of low outside temperature the side ventilation demand will be 25%. If Natural is stopped because high outside temperature or high CO2 the side ventilation demand will be 75%.

Hysteresis on the natural ventilation inlets and outlets are now working as +/- hysteresis, so that they don’t move on every sample.

After a power fail Pan feeding and Chain feeding will wait for the cross augers to fill before starting.

Dynamic MultiStep signals (0-10 volt and stop relays) could not be controlled in manual

In BASIC mode the pressure controlled inlets was not controlled during correct during minimum ventilation. They are now controlled according to pressure with active fans and closed with fans stopped.

In some situation winch motors would change position frequently up and down around the required position (due to float compare without hysteresis)

Tunnel cooling 'blocked by' information is set to temperature if control form is by temperature and the airspeed (temperature) is too low.

Default value for CO2 control is 10000 ppm as in version 3.0

Text for weather station 'offset to north' is changed to 'offset from north'

Daynumber could increase by 2 at nidnight

Tunnel cooling setup as 'based on air speed' started too early if the user had reduced maximum airspeed. In that case the cooling would start on the user set maximum airspeed, even if cooling start speed was higher.

Drum weigher and DOL 9940 has been optimized for speed.

Feed weighing with DOL 99B is now just as quick as a with a DOL 95.

Minimum ventilation curve is was visible in pure tunnel setup

Day number synchronization could happen if a climate + production controller is set to use only climate (i.e. the day number could change to a false day number every hour).

In combi tunnel systems with Dynamic MultiStep installed the tunnel fans would not run correct.

Version 3.0.1 Build 1 - 2015-10-21

New Functions

Known Issues

Tunnel cooling type, mode and ratio’s must be checked after an upgrade.

o Type must be set to PAD or SPRAY, this is new to version 3.0. The default setting is PAD, which is the most used tunnel cooling type. But this type reset the mode to parallel.

o Mode must be set to parallel or sequence (sequence is only available if type is spray).

o Ratio of each tunnel cooling relay must be checked/set.

Page 9: Software Release Description DOL 53x / DOL 634 - …cdn.skov.com/www/ControlSW/DOL 539 releases/4.2.3... · 4 Software Release Description ... Software version is available in the

Software Release Description 9

SRD

Negative pressure curve for heat recovery unit must be set after an upgrade. When updating from a version 1.x or 2.x the negative pressure curve for heat recovery unit must be set manually (because the curve structure has changed)

Feed, water and light programmes

o If a program must end at midnight then program it to end 24:00 and not 00:00

Lacking translation of new functions (they will be shown in English)

o Production alarm relay

o Load stepless fan settings

o Adjustment of dimmed backlight level

o Changed setup of preheating

o Water/feed last week

o Humidification stop day

It requires BigFarmNet Manager 3.1 or newer to display the ventilation mode properly.

Changes and Error Corrections

Tunnel cooling setup as 'based on air speed' started too early if the user had reduced maximum airspeed. In that case the cooling would start on the user set maximum airspeed, even if cooling start speed was higher.

Version 3.0.0 Build 107 - 2015-09-04

New Functions

FreeRange functionality as part of MultiStep system (with natural / active fans)

Breeder variant supports up to 24 water meters (or same number as available destinations)

Weather station as option

‘Production alarm relay’ as option

Possibility to load settings for stepless fan curves

Load settings from USB can be done as

o Settings alone

o User views alone

o Both user views and settings

Option to stop humidification after a specific day number

Synchronization of humidification with fans during cycle timer on side inlets

Desert control on tunnel cooling:

o If side cooling is active before start of tunnel mode pads can be rinsed

o Effect curve introduced to linearize the pad cooling

Added possibility to adjust the dimmed backlight intensity

Page 10: Software Release Description DOL 53x / DOL 634 - …cdn.skov.com/www/ControlSW/DOL 539 releases/4.2.3... · 4 Software Release Description ... Software version is available in the

10 Software Release Description

SRD

Known Issues

NOTE regarding heat recovery unit: When updating from a version 1.x or 2.x the negative pressure curve for heat recovery unit must be set manually (because the curve structure has changed)

Feed, water and light programs

o If a program must end at midnight then program it to end 24:00 and not 00:00

Lacking translation of new functions (they will be shown in English)

o Production alarm relay

o Load stepless fan settings

o Adjustment of dimmed backlight level

o Changed setup of preheating

o Water/feed last week

o Humidification stop day

If the controller cannot see an USB stick, the problem can be resolved by switching power off and on. The symptom are that the USB is detected but no mounted or unmouted message is displayed.

It requires FarmOnline Explorer 3.1 or newer to display the ventilation mode properly.

Changes and Error Corrections

The batch curves can operate with negative numbers, to be used for prestart/preheating

Minimum ventilation by CO2 is no longer limited to 25% of curve value the first 10 days of the batch

The name of the function ‘Night setback’ is changed to ‘Day-and-night adjustment’.

It is made harder to restore to factory settings (so that it is done in the same way as batch end/start). This is changed to secure against unwanted defaults.

The filling settings (matrix) is now available for the advanced user view

Individual egg counters can now be selected for the advanced user view

FarmOnline connection is made more robust

The possibility for setting up the controller as only a climate or production controller is re-introduced

Humidity ventilation could exceed maximum ventilation (if added up with temperature ventilation, alone it did not exceed max ventilation)

Removed false alarms on tunnel cooling pump

Zone controlled side inlets are no longer left open in tunnel mode

Humidification set point cannot be closer than 5 %RH to the humidity set point

Fixed error where advanced comfort was not added to the heat setpoint

Stir fans now work with House Heaters with individual sensor

‘Reset to default’ is now resetting language to English

Password timeout is changed to 1 minute after user view (daily or advanced) has been activated

Password level is removed for all none edit user menus (Climate, Production, Management and Alarm).

Password level for user menus (climate, production, management, alarms) are changed.

o Climate, production, management in general to daily user, with a few having no password (dead birds) and some more advanced user settings having advanced user level.

o Alarms to advanced user.

Page 11: Software Release Description DOL 53x / DOL 634 - …cdn.skov.com/www/ControlSW/DOL 539 releases/4.2.3... · 4 Software Release Description ... Software version is available in the

Software Release Description 11

SRD

Password level for technical menus (Setup, Calibration, Service information, Service, Use password) are changed

o Service, Service information, Manual/Auto to advanced user level

o Remaining technical menus are set to Service level

Cleaning program for heat recovery unit includes 3 programs with 1-3 starts in each program

Menus for pre heating are changed, to

o Pre heating setpoint

o Pre heating at batch stop

Negative pressure curve for heat recovery unit is changed to

o Ventilation 10-70-72-73-74-75-76-78-79-80 o HRU demand 100-80-50-50-50-50-50-50-10-0

Tunnel outlets can modulate during side mode (used with low ventilation in house with few or none fans in side mode)

Limitation of CO2 ventilation is changed from 1.0° below heat set point to 2.0° in order to give the heat control more room to operate and keep the temperature up

Sometimes chain feeding would not start

Hysteresis for leaving tunnel is changed from 2° to 1° C. This is changed to reduce the factor of ‘double hysteresis’ on tunnel start and stop.

Chill effect is now 0.0° C with inside temperatures at 38° C or more

Upgrade of software problems solved

If a USB stick with a program update is not boot ice formatted, the controller will ask if it should format the USB stick but did not format the USB correctly

Detection of USB stick is improved

SDK updated to handle early hardware version (before revision I)

Feed update from an electronic silo or day silo was not registered, after the destination target was reached. When target is reached feed demand is removed and the silo system recalculates the consumption made.

Light dimmer did not work in manual mode

Default value for CO2 control is changed to a P band of 10.000 ppm

Heat recovery cleaning program fixed, it did only use program number 1

Heat recovery unit did not open side inlet during anti icing if 'Use side curve for side inlets' was selected

Pressure control in basic mode with cycling fans

Version 2.2.1 Build 3 - 2015-01-16

Known Issues

Water program does not work if start time is higher than stop time.

Changes and Error Corrections

Negative pressure curve for tunnel could not be adjusted.

If the inlets for front / rear was installed as analogue their minimum/maximum voltages could not be adjusted (they was fixed on 0 and 10 volt).

Page 12: Software Release Description DOL 53x / DOL 634 - …cdn.skov.com/www/ControlSW/DOL 539 releases/4.2.3... · 4 Software Release Description ... Software version is available in the

12 Software Release Description

SRD

Version 2.2.0 Build 150 - 2014-09-23

New Functions

Full integration of breeder data with FarmOnline

Added climate reference settings for breeder and broiler

Daily/Advanced views are now saved so upgrades to newer versions will restore the views. When upgrading to this version the daily/advanced are not restored Restore of User Views are now possible from version to version ( no support for settings from version 1.5, 1.6, 2.0 or 2.1)

Time controlled feed weight now handles silo empty sensor.

Time controlled feed weight is now able to give an alarm for "No feed to feed weigher".

Silo empty sensor is handled so that the silo auger is not set if the sensor is empty.

Added button for auto zoom to trend curves

Known Issues

Water program does not work if start time is higher than stop time.

Negative pressure curve for tunnel cannot be adjusted

Minimum/maximum voltages for analog controlled inlets can not be adjusted in 2 zone setups, they are fixed on 0 and 10 volt.

Changes and Error Corrections

In some situations extra ventilation would not start (typically if spray cooling was started before first extra ventilation step)

Save and restore settings from SD card could read wrong settings.

Chain feeding would not always work correctly if the start time was at 0:00 or the feeding period crosses midnight.

Egg counter trend graph was not working.

Destination feeding: If more silos was installed with the same feed type, it would always take from the silo with the highest number, instead of the silo that was selected.

All feed weighers (except DOL 99B and DOL 9940): If more silos was installed with same feed type, then when selecting Automatic change, the parameters for setting time and amount for the change, could not be seen.

Comfort and chill factor is now available for daily and advanced user menu's

It is now possible to specify the actual sex of the birds in both Broiler and Breeder (in the Setup / Adjustment / Production menu).

Feed offset can now be adjusted with a precision of 0.1 g / bird

The order of culled reasons has been adjusted so the most frequently used culled reasons are at the top

I/O Type 6 and I/O Type 7 only works on position 1 to 6, so it is fixed so they cannot be selected on position 7 and upwards.

It is now possible to enter “Inspection weight” – if a manual bird weigher is installed together with an electronic bird weigher

Page 13: Software Release Description DOL 53x / DOL 634 - …cdn.skov.com/www/ControlSW/DOL 539 releases/4.2.3... · 4 Software Release Description ... Software version is available in the

Software Release Description 13

SRD

The feed column in the “Destinations setup” menu in Setup / Adjustment / Production has been removed – it is available in the Production / Filling / Destinations menu

Default values for production alarms has been adjusted to better match what is required in typical installations

Fix of automatic silo change from silo 2 to silo 1

Nightly backup of settings has been fixed and the settings can be restored using Technical / Service / Settings / Restore settings from backup.

Fix so PC Sim (the PC simulator) do not crash when IO type 6 and IO Type 7 are selected.

“Show connection” has been fixed so for IO Type 10 it is now shown when an external resistor is required.

Version 2.1.3 Build 2 - 2014-06-27

Recommendations

Customers with version 2.0.0 Build 72 or 2.1.0 Build 16 should upgrade to this version.

The error fixed in this version was introduced in version 2.0.0 Build 72.

Known Issues

In a simple production variant (P variant) it is not possible to install a light sensor.

Changes and Error Corrections

Fixed alarm for “No feed to feed weigher”.

Trend menu for Water 24h is corrected (Management/Trend curves/Production/Water 24h)

Trend menu for Feed 24h is corrected (Management/Trend curves/Production/ Feed 24h)

Version 2.1.0 Build 16 - 2014-05-27

New Functions

ServiceAccess from FarmOnline to controller. Access the controller’s user interface.

New variant fields for Breeder: Max number of destinations and max number of egg counters.

Known Issues

Trend menu for Water 24h does not work (Management/Trend curves/Production/Water 24h)

Trend menu for Feed 24h does not work (Management/Trend curves/Production/ Feed 24h)

Changes and Error Corrections

Chain feeding resumes a running chain feeding after a power failure.

Light controlled by sensor corrected.

Installation and setup of shared silos corrected

HRU cleaning is not active in batch stop.

Page 14: Software Release Description DOL 53x / DOL 634 - …cdn.skov.com/www/ControlSW/DOL 539 releases/4.2.3... · 4 Software Release Description ... Software version is available in the

14 Software Release Description

SRD

Version 2.0.1 Build 5 - 2014-04-28

New Functions

OEM variant structure implemented (name in the header of the controller DOL 539 / OEM)

Version 2.0.0 Build 72 - 2014-03-21

New Functions

Climate features:

o Batch start day can be changed from -1 (to e.g. -5 for pre heating, 126 for breeders)

o Available MultiStep increased from 14 to 16

Production (breeder) features

o Same new features as Broiler except it only support 6 water meters.

o Destination feeding can increase feeding amount next day after a manual day.

o DOL 9940 can be used for destination feeding

o Destination feeding can be “paused” / “resumed” / “resumed and skip current destination”

o 2 feed mix can be setup for destination feeding (if drum scale or DOL 9940).

o 32 Egg counters.

o Manual entering eggs (floor eggs and system eggs).

o 6 generic manual entering’s (name, unit can be selected)

o 6 24 hour clocks

o 6 slave lights

o 6 Interval timers – follow a program (main light, slave light 1 …6, 24 hour clock 1 …6)

Changes and Error Corrections

Feed mixing adjustments was reset after power failure

Offset to number of chain runs was set to 0 after a power fail

Version 1.6.1 Build 3 - 2014-01-06

Changes and Error Corrections

Error correction on heating: heating could be blocked by a zero ventilation demand that was not actual zero (rounded off to something extreme close to zero, but not zero)

The application for logging data to trend curves, water alarms etc. could be exhausted and after that stopped

Page 15: Software Release Description DOL 53x / DOL 634 - …cdn.skov.com/www/ControlSW/DOL 539 releases/4.2.3... · 4 Software Release Description ... Software version is available in the

Software Release Description 15

SRD

Version 1.6.0 Build 138 - 2013-11-06

Recommendations

If the existing DOL 535/539 is used for destination feeding, it is important to avoid an update to this 1.6.0 SW, as the 1.6.0 SW does not include support for destination feeding.

New Functions

Climate features

o Heat recovery unit support

o Dynamic MultiStep support

Production features

o 5 silos (previously 4 silos was supported)

o Alarm for empty silo (using a sensor)

o Combine feed weigher and silo weiger

o Shared silo – two house may use the same silo an the actual content can be read on both computers

o Alarm is feed consumption decreases

o 24 water meters supported

o Improved water leakage alarms

o Inspection light

o Dawn/dusk has gained an extra level

o Light sources can be named by the user

o Boost feature to support old light systems

o Light intensity controlled by a sensor

Known Issues

Destination feeding: Destination feeding will no longer be available in this version of the software. Ultimo 2013 a new DOL 535/539Breeder computer is launched which include support for 24 destinations and 3 cross augers.