Smoke&Gas With PLC Project1-Modified
-
Upload
arfaq-ahmed -
Category
Documents
-
view
8 -
download
3
description
Transcript of Smoke&Gas With PLC Project1-Modified
1
Smoke & Gas detection Monitoring and Control using PLC
(Programmable Logic Controller):
ACKNOWLEDGMENT:
This Project has been developed with the involvement and assistance
of several people who are responsible in the completion of this project.
Hereby we would like to acknowledge the effort of all the sources
(lecturer and our project guide) which were incorporated in our project.
We are thankful to the Head of our department Dr. M.P. Soni who has
been a source of inspiration to us right from the inspection of our
project, providing us with valuable suggestions and key notes in our
project seminar. His unending quench for maximizing the scope and
opportunities for the betterment of students has been inspiring to us to
do better in our project. We are also grateful to our project guide
Mr. Mohd. Abdul Muqeet for his valuable suggestions. His profound
knowledge on the subject of PLC and its Applications has been helpful
throughout. We owe our deepest gratitude to our faculty adviser
Mr. Shaik Abdul Qadeer for his immense faith in our project and also
for his support in providing us with technical as well as nontechnical
assistance. We would also like to thank our Lab Technician
Mr. A. David.F.Krishow for his support. Our project would not have
been possible without the support, guidance and assistance of
Mr. Ahmed M.A and Mr. Hanumantha Rao.C from Avidus
Engineering Pvt. Ltd, who has shown relentless efforts in educating
us throughout the process in various ways apart from working with us
in making our project success.
Lastly we would like to offer our regards to all those who have
supported us in any respect during the completion of our project.
ABSTRACT
Monitoring and Controlling of Smoke emission and Gas Leakage using PLC
2
The Project is to study Smoke and Gas detector Systems with PLC
(Programmable Logic Control).
Smoke Detector System:
Smoke detector system is essential for Industrial and Commercial
facilities. It detects accidental fire and spray water on the source of fire
to quench it. They include different type of smoke detectors, both
addressable and conventional and Fire Alarm Control Panel (FACP). In
the current project in place of FACP, Programmable Logic Controller
(PLC) used for Logic development.
Gas Detector System:
Gas detector system is essential for detecting flammable and
poisonous gases in Industrial facilities and HVAC (Heating Ventilation
Air Conditioning) systems.
Programmable Logic Controller:
Programmable Logic Controller is a digitally operated electronic
system, designed for use in an industrial environment, which uses a
programmable memory for the internal storage of user-orientated
instructions for implementing specific functions such as logic
sequencing, timing, counting, & arithmetic to control, through digital or
analog inputs & outputs, various types of machines or processes. Both
the PLC & its associated peripherals are designed so that they can be
easily integrated into an industrial control system & easily used in all
their intended functions.
Incoming control signals, or inputs, interact with instructions specified
in the user ladder program, which tells the PLC how to react with the
incoming signals. The user program also directs the PLC on how to
control field devices like motor starters, pilot lights, & solenoids. A
signal going out of the PLC to control a field device is called an Output.
TABLE OF CONTENTS
CHAPTER PAGE NUMBER
Monitoring and Controlling of Smoke emission and Gas Leakage using PLC
3
ACKNOWLEDGEMENT 1
ABSTRACT 2
Chapter 1: Introduction 9
1.1Project Overview 9
1.2 Introduction to Smoke Detector 12
1.2.1 Conventional type
1.2.2 Addressable type
12
1.3Introduction to Gas Detector 15
1.3.1 Gas hazarda
1.3.2 Typical areas that require gas detection
1.3.3 Gas detection
1.3.4 Location of Sensors
15
18
22
26
1.4 Control systems and Mitigation 27
1.4.1 Fire alarm Control Panels 30
1.5 PLC(PROGRAMMABLE LOGIC CONTROLLER) 44
1.5.1 Introduction to PLC
1.5.2 PLC Advantages and Disadvantage
44
45
1.5.3 Allen Bradley PLC Micrologic 1200 Controller 46
CHAPTER 2: HARDWARE DESCRIPTION 52
2.1 Block Diagram 52
2.2 Wiring Diagram 55
2.3 Smoke Sensor 56
Monitoring and Controlling of Smoke emission and Gas Leakage using PLC
4
2.3.1 Product Introduction
2.3.2 Product profile
56
56
2.4 Gas Detector 57
2.4.1 Sensitivity
2.4.2 Specifications
2.4.3 Gases Detected
57
58
58
2.5 Pump, Solenoid Valve, Fan, Relays 58
CHAPTER 3: PLC PROGRAMMING 60
3.1 Introduction 60
3.2Programming Languages 63
3.3 Ladder Logic Structure 67
3.4 Ladder Logic Programming Basic Instructions 69
CHAPTER 4:LOGIC DEVELOPMENT 73
4.1 Electrical circuit-Logic diagram relationship 77
4.2 Introduction 78
4.3 Ladder Diagram Symbols 78
4.4 Developing a ladder diagram 81
4.5 Automatic Mode of Operation 83
4.6 Ladder Diagram Analysis 85
4.7 Developing the PLC Program Logic 86
4.8 Power Supply Section 87
4.9.1Full Wave Rectifier 87
Monitoring and Controlling of Smoke emission and Gas Leakage using PLC
5
4.9.2 Full Wave Bridge Rectifier 89
CHAPTER 5: PROJECT PICTORIAL REPRESENTATION 95
5.1 Project PLC Programming Pictorial Representation
101
CHAPTER 6: ADVANTAGES AND LIMITATIONS 106
6.1 Advantages 106
6.2 Limitations 107
6.3 Conclusion 108
BIBLOGRAPHY 109
LIST OF FIGURES:
Figure Page number
Fig 1: Inside view of Smoke Detector 10
Fig 2: Observation Relays 11
Fig 3: Smoke Detector Installation 12
Fig 4: Installation and placement 14
Monitoring and Controlling of Smoke emission and Gas Leakage using PLC
6
Fig 5: Horn & Beacon 28
Fig: 6 Wiring Diagram 32
Fig: 7 Addressable FACP 33
Fig: 8 System Functions 37
Fig 9: Fire alarm panel, showing drill switch 38
Fig 10: Allen Bradley PLC Architecture 49
Fig11: Block Diagram 52
Fig 12: Project Perspective-1 53
Fig 13: Project Perspective-2 54
Fig 14: Wiring Diagram 55
Fig 15: LPG Gas Detector 57
Fig 16: PLC Rack 61
Fig 17: PLC Operatation 62
Fig 18: Basic Components of SFC Lanuguage 65
Fig 19: Basic Components of FBD Language 67
Fig 20: Timer & Counter 70
Fig 21: Three types of Logic representation 72
Fig 22: Positive Logic 74
Fig 23: AND Symbol 75
Fig 24: OR Symbol 76
Fig 25: Inverting Circuit 77
Fig 26: Reset Operation 77
Fig 27: Electrical Interlock Circuit 78
Fig 28: Symbol used Ladder Diagrams 80
Fig 29: Automatic Control of a pressurized water
tank
82
Fig 30: Full Wave Rectifier Circuit 88
Monitoring and Controlling of Smoke emission and Gas Leakage using PLC
7
Fig 31: Diode Bridge Rectifier 90
Fig 32: Positive Half-Cycle 90
Fig 33: Negative Half-cycle 91
Fig 34: Typical Bridge Rectifier 91
Fig 35: Full-wave Rectifier with Smoothing
Capacitor
92
Fig 36: Full wave Rectifier 93
Fig 37: Project Model with PLC 95
Fig 38: Project Model View-1 96
Fig 39: Project Model View-2 97
Fig 40: PLC Trainer 98
Fig 41: Project Model View-3 99
Fig 42: Project Model View-4 100
Fig 43: Programming Screen Shot-1 101
Fig 44: Programming Sreen Shot-2 102
Fig 45: Programming Screen Shot-3 103
Fig 46: Programming Screen Shot-4 104
Fig 47: Programming Screen Shot-5 105
Chapter1: Introduction:
1.1 Project Overview:
The Project is the study of Smoke and Gas detector systems with PLC
(Programmable Logic Controller).
The Project includes Smoke and Gas detectors, fan, pump, and
solenoid valve activation. The logic is developed in the Allen Bradley
PLC (Programmable Logic Controller).
Monitoring and Controlling of Smoke emission and Gas Leakage using PLC
8
A Smoke detector was installed on a chamber, when it senses the
smoke; it actuates a water pump and solenoid valve to spray water at
the smoke emanating area to extinguish if any fire is there.
A Gas detector was installed in a chamber. When it detects the gas, it
actuates a exhaust fan to remove all the poisonous or flammable gas
from the chamber.
The smoke detector powered by 9 V battery and gives analog signal of
15mA when it detects the smoke. It is connected to PLC
(Programmable Logic Controller) as analog input.
The Gas detector powered by 9v battery and gives potential free
contact (Normally open NO) as digital input to PLC (Programmable
Logic Controller). When it detects the gas the NO contact closes.
1.2 Introduction to Smoke Detector
Smoke detector
A smoke detector is a device that detects smoke, typically as an
indicator of fire. Commercial, industrial, and mass residential devices
issue a signal to a fire alarm system, while household detectors, known
as smoke alarms, generally issue a local audible or visual alarm from
the detector itself.
Smoke detectors are typically housed in a disk-shaped plastic
enclosure about 150 millimeters (6 in) in diameter and 25 millimeters
(1 in) thick, but the shape can vary by manufacturer or product line.
Most smoke detectors work either by optical detection (photoelectric)
or by physical process (ionization), while others use both detection
methods to increase sensitivity to smoke. Sensitive alarms can be used
to detect, and thus deter, smoking in areas where it is banned such as
toilets and schools. Smoke detectors in large commercial, industrial,
and residential buildings are usually powered by a central fire alarm
system, which is powered by the building power with a battery backup.
Monitoring and Controlling of Smoke emission and Gas Leakage using PLC
9
However, in many single family detached and smaller multiple family
housings, a smoke alarm is often powered only by a single disposable
battery.
Fig1: Inside view of Smoke Detector
Inside a basic ionization smoke detector. The black, round structure at
the right is the ionization chamber. The white, round structure at the
upper left is the piezoelectric buzzer that produces the alarm sound
An ionization type smoke detector is generally cheaper to manufacture
than an optical smoke detector; however, it is sometimes rejected
because it is more prone to false (nuisance) alarms than photoelectric
smoke detectors.[2][3] It can detect particles of smoke that are too small
to be visible. It includes about 37 kBq or 1 µCi of radioactive
element americium-241 (241Am), corresponding to about 0.3 µg of the
isotope. The radiation passes through an ionization chamber, an air-
filled space between two electrodes, and permits a small,
constant current between the electrodes. Any smoke that enters the
chamber absorbs the alpha particles, which reduces the ionization and
interrupts this current, setting off the alarm.
An alpha emitter, has a half-life of 432 years. Alpha radiation, as
opposed to beta and gamma, is used for two additional reasons: Alpha
particles have high ionization, so sufficient air particles will be ionized
Monitoring and Controlling of Smoke emission and Gas Leakage using PLC
10
for the current to exist, and they have low penetrative power, meaning
they will be stopped by the plastic of the smoke detector or the air.
Obscuration is a unit of measurement that has become the standard
definition of smoke detector sensitivity. Obscuration is the effect that
smoke has on reducing sensor visibility; higher concentrations of
smoke result in higher obscuration levels.
Typical smoke detector obscuration ratings[9]
Type of
DetectorObscuration Level
Ionization 2.6–5.0% obs/m (0.8–1.5% obs/ft)
Photoelectric 6.5–13.0% obs/m (2–4% obs/ft)
Beam 3% obs/m (0.9% obs/ft)[citation needed]
Aspirating0.005–20.5% obs/m (0.0015–6.25%
obs/ft)
Laser 0.06–6.41% obs/m (0.02–2.0% obs/ft)[10]
Fig 2: Observation Relays
Commercial smoke detectors are either conventional or analog
addressable, and are wired up to security monitoring systems or fire
alarm control panels (FACP). These are the most common type of
detector, and usually cost a lot more than a household smoke alarms.
They exist in most commercial and industrial facilities, such as high
rises, ships and trains. These detectors don't need to have built in
alarms, as alarm systems can be controlled by the connected FACP,
which will set off relevant alarms, and can also implement complex
functions such as a staged evacuation.
1.2.1Conventional
Monitoring and Controlling of Smoke emission and Gas Leakage using PLC
11
The word "conventional" is slang used to distinguish the method used
to communicate with the control unit from that used by addressable
detectors whose methods were unconventional at the time of their
introduction. So called “Conventional Detectors” cannot be individually
identified by the control unit and resemble an electrical switch in their
information capacity. These detectors are connected in parallel to the
signaling path or (initiating device circuit) so that the current flow is
monitored to indicate a closure of the circuit path by any connected
detector when smoke or other similar environmental stimulus
sufficiently influences any detector. The resulting increase in current
flow is interpreted and processed by the control unit as a confirmation
of the presence of smoke and a fire alarm signal is generated.
1.2.2Addressable
Fig 3: Smoke Detector Installation
An addressable Simplex smoke detector
This type of installation gives each detector on a system an individual
number, or address. Thus, addressable detectors allow an FACP, and
therefore fire fighters, to know the exact location of an alarm where
the address is indicated on a diagram.
Monitoring and Controlling of Smoke emission and Gas Leakage using PLC
12
Analog addressable detectors provide information about the amount of
smoke in their detection area, so that the FACP can decide itself, if
there is an alarm condition in that area (possibly considering day/night
time and the readings of surrounding areas). These are usually more
expensive than autonomous deciding detectors
Standalone smoke alarms
The main function of a standalone smoke alarm is to alert persons at
risk. Several methods are used and documented in industry
specifications published by Underwriters Laboratories [12] Alerting
methods include:
Audible tones
Usually around 3200 Hz due to component constraints (Audio
advancements for persons with hearing impairments have been
made;
85 dB A at 10 feet
Spoken voice alert
Visual strobe lights
110 candela output
Monitoring and Controlling of Smoke emission and Gas Leakage using PLC
13
Fig:4 Installation and placement
In new construction, minimum requirements are typically more
stringent. All smoke detectors must be hooked directly to the electrical
wiring, be interconnected and have a battery backup. In addition,
smoke detectors are required either inside or outside every bedroom,
depending on local codes. Smoke detectors on the outside will detect
fires more quickly; assuming the fire does not begin in the bedroom,
but the sound of the alarm will be reduced and may not wake some
people. Some areas also require smoke detectors in stairways,
main hallways and garages.
Monitoring and Controlling of Smoke emission and Gas Leakage using PLC
14
1.3Introduction to Gas Detector
What is gas?
The name gas comes from the word chaos. Gas is a swarm of
molecules moving randomly and chaotically, constantly colliding with
each other and anything else around it. Gases fill any available volume
and due to the very high speed at which they move will mix rapidly
into any atmosphere in which they are released.
Industrial processes increasingly involve the use and manufacture of
highly dangerous substances, particularly flammable, toxic and oxygen
gases. Inevitably, occasional escapes of gas occur, which create a
potential hazard to the industrial plant, its employees and people living
nearby. Worldwide incidents, involving asphyxiation, explosions and
loss of life, are a constant reminder of this problem.
In most industries, one of the key parts of any safety plan for reducing
risks to personnel and plant is the use of early-warning devices such as
gas detectors. These can help to provide more time in which to take
remedial or protective action. They can also be used as part of a total,
integrated monitoring and safety system for an industrial plant.
1.3.1Gas Hazards
There are three main types of gas hazard: Flammable, Toxic and
Asphyxiant
Flammable Gas Hazards
Combustion is a fairly simple chemical reaction in which oxygen is
combined rapidly with another substance resulting in the release of
energy. This energy appears mainly as heat – sometimes in the form of
flames. The igniting substance is normally, but not always, a
Hydrocarbon compound and can be solid, liquid, vapor or gas.
However, only gases and vapors are considered in this publication.
Monitoring and Controlling of Smoke emission and Gas Leakage using PLC
15
Flammable Limit
There is only a limited band of gas/air concentration which will produce
a combustible mixture. This band is specific for each gas and vapor
and is bounded by an upper level, known as the Upper Explosive Limit
(or the UEL) and a lower level, called the Lower Explosive Limit (LEL).
At levels below the LEL, there is insufficient gas to produce an
explosion (i.e. the mixture is too ‘lean’), whilst above the UEL, the
mixture has insufficient oxygen (i.e. the mixture is too ‘rich’). The
flammable range therefore falls between the limits of the LEL and UEL
for each individual gas or mixture of gases. Outside these limits, the
mixture is not capable of combustion. The Flammable Gases Data in
section 2.4 indicates the limiting values for some of the better-known
combustible gases and compounds. The data is given for gases and
vapors at normal conditions of pressure and temperature. An increase
in pressure, temperature or oxygen content will generally broaden the
flammability range. In the average industrial plant, there would
normally be no gases leaking into the surrounding area or, at worst,
only a low background level of gas present. Therefore 5 Flammable
Gas Hazards Flammable Limit There is only a limited band of gas/air
concentration which will produce a combustible mixture. This band is
specific for each gas and vapor and is bounded by an upper level,
known as the Upper Explosive Limit (or the UEL) and a lower level,
called the Lower Explosive Limit (LEL). the detecting and early warning
system will only be required to detect levels from zero percent of gas
up to the lower explosive limit. By the time this concentration is
reached, shut-down procedures or site clearance should have been put
into operation. In fact this will typically take place at a concentration of
less than 50 percent of the LEL value, so that an adequate safety
margin is provided.
Monitoring and Controlling of Smoke emission and Gas Leakage using PLC
16
However, it should always be remembered that in enclosed or
unventilated areas, a concentration in excess of the UEL can
sometimes occur. At times of inspection, therefore, special care needs
to be taken when operating hatches or doors, since the ingress of air
from outside can dilute the gases to a hazardous, combustible mixture.
Flammable Gas Properties Ignition Temperature:
Flammable gases also have a temperature where ignition will take
place, even without an external ignition source such as a spark or
flame. This temperature is called the Ignition Temperature. Apparatus
for use in a hazardous area must not have a surface temperature that
exceeds the ignition temperature. Apparatus is therefore marked with
a maximum surface temperature or T rating.
Toxic Gas Hazards
Some gases are poisonous and can be dangerous to life at very low
concentrations. Some toxic gases have strong smells like the
distinctive ‘rotten eggs’ smell of H2S. The measurements most often
used for the concentration of toxic gases are parts per million (ppm)
and parts per billion (ppb). For example 1ppm would be equivalent to a
room filled with a total of 1 million balls and 1 of those balls being red.
The red ball would represent 1ppm. More people die from toxic gas
exposure than from explosions caused by the ignition of flammable
gas. (It should be noted that there is a large group of gases which are
both combustible and toxic, so that even detectors of toxic gases
sometimes have to carry hazardous area approval). The main reason
for treating flammable and toxic gases separately is that the hazards
and regulations involved and the types of sensor required are different.
Hygiene Monitoring
The term ‘hygiene monitoring’ is generally used to cover the area of
industrial health monitoring associated with the exposure of
employees to hazardous conditions of gases, dust, noise etc. In other
Monitoring and Controlling of Smoke emission and Gas Leakage using PLC
17
words, the aim is to ensure that levels in the workplace are below the
statutory limits. This subject covers both area surveys (profiling of
potential exposures) and personal monitoring, where instruments are
worn by a worker and sampling is carried out as near to the breathing
zone as possible. This ensures that the measured level of
contamination is truly representative of that inhaled by the worker.
1.3.2Typical Areas that Require Gas Detection
There are many different applications for flammable, toxic and oxygen
gas detection. Industrial processes increasingly involve the use and
manufacture of highly dangerous substances, particularly toxic and
combustible gases. Inevitably, occasional escapes of gas occur, which
create a potential hazard to the industrial plant, its employees and
people living nearby. Worldwide incidents involving asphyxiation,
explosions and loss of life, are a constant reminder of this problem.
In most industries, one of the key parts of the safety plan for reducing
the risks to personnel and plant is the use of early warning devices
such as gas detectors. These can help to provide more time in which to
take remedial or protective action. They can also be used as part of a
total integrated monitoring and safety system for an industrial plant.
Oil & Gas
The oil and gas industry covers a large number of upstream activities
from the on and offshore exploration and production of oil and gas to
its transportation, storage and refining. The large amount of highly
flammable Hydrocarbon gases involved are a serious explosive risk
and additionally toxic gases such as Hydrogen Sulfide are often
present.
Typical Applications:
Exploration Drilling Rigs
Production Platforms
Onshore oil and gas terminals
Monitoring and Controlling of Smoke emission and Gas Leakage using PLC
18
Refineries
Typical Gases:
Flammable: Hydrocarbon gases
Toxic: Hydrogen Sulfide, Carbon Monoxide
Typical Applications:
Around the boiler pipe work and burners
In and around turbine packages
In coal silos and conveyor belts in older coal/oil fired stations
Typical Gases:
Flammable: Natural Gas, Hydrogen
Toxic: Carbon Monoxide, SOx, NOx and Oxygen deficiency.
Waste Water Treatment Plants
Waste Water Treatment Plants are a familiar site around many cities
and towns.
Sewage naturally gives off both Methane and H2S. The ‘rotten eggs’
smell of H2S can often be noticed as the nose can detect it at less than
0.1ppm.
Typical Applications:
Digesters
Plant sumps
H2S Scrubbers
Pumps
Typical Gases:
Flammable: Methane, Solvent vapors
Toxic: Hydrogen Sulfide, Carbon Dioxide, Chlorine, Sulfur Dioxide,
Ozone.
Boiler Rooms
Monitoring and Controlling of Smoke emission and Gas Leakage using PLC
19
Boiler Rooms come in all shapes and sizes. Small buildings may have a
single boiler whereas larger buildings often have large boiler rooms
housing several large boilers.
Typical Applications:
Flammable gas leaks from the incoming gas main
Leaks from the boiler and surrounding gas piping
Carbon Monoxide given off badly maintained boiler
Typical Gases:
Flammable: Methane
Toxic: Carbon Monoxide
Hospitals
Hospitals may use many different flammable and toxic substances,
particularly in their laboratories. Additionally, many are very large and
have onsite utility supplies and backup power stations.
Typical Applications:
Laboratories
Refrigeration plants
Boiler rooms
Typical Gases:
Flammable: Methane, Hydrogen
Toxic: Carbon Monoxide, Chlorine, Ammonia, Ethylene oxide and
0Oxygen deficiency
Tunnels/Car Parks
Car Tunnels and enclosed Car Parks need to be monitored for the toxic
gases from exhaust fumes. Modern tunnels and car parksuse this
monitoring to control the ventilation fans. Tunnels may also need to be
monitored for the build up of natural gas.
Typical Applications:
Monitoring and Controlling of Smoke emission and Gas Leakage using PLC
20
Car tunnels
Underground and enclosed car parks
Access tunnels
Ventilation control
Typical Gases:
Flammable: Methane (natural gas), LPG, LNG, Petrol Vapor.
Toxic: Carbon Monoxide, Nitrogen Dioxide
Principles of Detection
Many people have probably seen a flame safety lamp at some time
and know something about its use as an early form of ‘firedamp’ gas
detector in underground coal mines and sewers. Although originally
intended as a source of light, the device could also be used to estimate
the level of combustible gases- to an accuracy of about 25-50%,
depending on the user’s experience, training, age, colour perception
etc. Modern combustible gas detectors have to be much more
accurate, reliable and repeatable than this and although various
attempts were made to overcome the safety lamp’s subjectiveness of
measurement (by using a flame temperature sensor for instance), it
has now been almost entirely superseded by more modern, electronic
devices.
Nevertheless, today’s most commonly used device, the catalytic
detector, is in some respects a modern development of the early flame
safety lamp, since it also relies for its operation on the combustion of a
gas and its conversion to carbon dioxide and water.
A further improvement in stable operation can be achieved by the use
of poison resistant sensors. These have better resistance to
degradation by substances such as silicones, sulfur and lead
compounds which can rapidly de-activate (or ‘poison’) other types of
catalytic sensor.
Monitoring and Controlling of Smoke emission and Gas Leakage using PLC
21
To achieve the necessary requirements of design safety, the catalytic
type of sensor has to be mounted in a strong metal housing behind a
flame arrestor. This allows the gas/ air mixture to diffuse into the
housing and on to the hot sensor element, but will prevent the
propagation of any flame to the outside atmosphere. The flame
arrestor slightly reduces the speed of response of the sensor but, in
most cases the electrical output will give a reading in a matter of
seconds after gas has been detected. However, because the response
curve is considerably flattened as it approaches the final reading, the
response time is often specified in terms of the time to reach 90
percent of its final reading and is therefore known as the T90 value.
T90 values for catalytic sensors are typically between 20 and 30
seconds.
1.3.3Gas Detection
In general, gas detection is divided into combustible gas detection and
toxic gas detection. This is a broad separation that breaks down in
some cases, e.g. some gases are both toxic and combustible in the
concentrations expected. Historically there has also been a separation
in technology between combustible and toxic detection. Below are
some of the issues you need to consider when choosing gas detectors.
Most devices used in the oil and gas industry are set to detect
methane (CH 4) or hydrogen sulphide (H2S). Many detectors show cross-
sensitivity; i.e. a detector for detecting one gas will also detect
another, at different readings. So at the time of purchase it is
important to specify the gas that is to be detected and consider other
gases that may be present that may affect the readings. The nature of
the gas should be considered – e.g. H2S is heavier than air, methane
rises, propane sinks. However they may not behave like that under a
high pressure discharge. Altitude affects the readings of some
Monitoring and Controlling of Smoke emission and Gas Leakage using PLC
22
detectors. Portable personal gas detectors, set for multiple gasses may
be used in areas where toxic gases may be present.
Combustible Gas Detection
Two mainstream technologies are available – infra-red absorption and
catalytic types. Other types are available and in development; e.g.
metal oxide semiconductor sensors. Detection methods from the field
of analyzers may cross over to meet gas detection needs.
Point detectors are calibrated against the lower explosive limit (LEL) of
a certain gas, frequently methane. The lower explosive limit for
methane mixed in air is achieved at a 5% concentration. Typical alarm
settings are 20% LEL and 60% LEL. Confusion can arise as these levels
are traditionally labelled low gas and high gas, whereas control
instrument engineers would use the term high alarm and high-high
alarm.
Open path gas detectors are calibrated in LEL metres (LELm). This
setting has evolved as an analogue with the LEL range used in point
detectors.
Infra-red Absorption Combustible Gas Detection
The technology uses the absorption characteristics of the hydrocarbon
molecules to infra-red light. The more hydrocarbon molecules are
present, the higher the absorption of infra-red radiation. More than one
type of hydrocarbon gas may be detected.
This technology is more expensive than catalytic detection, but it is
used for many applications as it doesn’t need field calibration and
proof test intervals are considerably better (longer) than for catalytic
types. Speed of response is quicker than for catalytic types. The
measured value doesn’t drift unlike catalytic detectors. And unlike
catalytic types, the detector doesn’t need oxygen for operation,
Point infra-red gas detectors
Monitoring and Controlling of Smoke emission and Gas Leakage using PLC
23
Point detectors record the gas concentration at the detector location.
They need to be placed where a release of gas is considered possible.
They can be placed remotely and connected to the sampling location
by tubes, with air sucked across the detecting chamber. Consideration
needs to be given to the extra detection time added by the transit time
down the tube.
Example uses: Detection in confined spaces, specific locations, air
inlets etc.
Open path infra-red gas detectors
Open path gas detectors have a separate transmitter and receiver.
Manufacturers quote up to 200m range, but in practice smaller
distances are used, due to climatic and practical mounting
arrangements.
Detectors should be mounted rigidly to avoid misalignment between
the transmitter and receiver, both statically and due to vibrations.
Current devices will detect more than one hydrocarbon gas. New
devices are in development that are tuned to a particular gas. Different
versions of these can also detect H2S.
Example uses: Migration detection, pipe rack monitoring.
Catalytic Gas Detectors
Catalytic detectors rely upon burning gas in a sintered chamber. For
this reason they are only available as a point detector or as part of a
multi-point aspirating system.
Various technologies are available – chemical cell and semiconductor
point detectors; open path (Laser) gas detection is in development.
Monitoring and Controlling of Smoke emission and Gas Leakage using PLC
24
Many different types of gas can be detected. Cross-sensitivity to
different gases other than those being looked for needs to be given
careful attention.
Response times of detecting and testing frequencies need careful
attention.
Chemical cell types require sensor replacement at intervals
determined by the environment. Semiconductor cells are also affected
by their environment and may need to be ‘kept awake’ by exposure to
the detected gas. New products are in development that are less
susceptible to these limitations.
Infra-red single gas open path detectors are at an advanced stage of
development. These offer the important advantages of fast response
and high reliability.
Example uses: H2S from sour oil wells or processing plant; carbon
monoxide from burning products and Co2 (Carbon Dioxide) build up
Calibration
The most common failure in catalytic sensors is performance
degradation caused by exposure to certain poisons’. It is therefore
essential that any gas monitoring system should not only be calibrated
at the time of installation, but also checked regularly and re-calibrated
as necessary. Checks must be made using an accurately calibrated
standard gas mixture so that the zero and ‘span’ levels can be set
correctly on the controller.
Codes of practice such as EN50073:1999 can provide some guidance
about the calibration checking frequency and the alarm level settings.
Typically, checks should initially be made at weekly intervals but the
periods can be extended as operational experience is gained. Where
two alarm levels are required, these are normally set at 20-25% LEL for
the lower level and 50-55% LEL for the upper level.
Monitoring and Controlling of Smoke emission and Gas Leakage using PLC
25
Today, there are a number of ‘one-man’ calibration systems available
which allow the calibration procedures to be carried out at the sensor
itself. This considerably reduces the time and cost of maintenance,
particularly where the sensors are in difficult to get to locations, such
as an off-shore oil or gas platform. Alternatively, there are now some
sensors available which are designed to intrinsically safe standards,
and with these it is possible to calibrate the sensors at a convenient
place away from the site (in a maintenance depot for instance).
Because they are intrinsically safe, it is allowed to freely exchange
them with the sensors needing replacement on site, without first
shutting down the system for safety.
Maintenance can therefore be carried out on a ‘hot’ system and is very
much faster and cheaper than early, conventional systems.
1.3.4 Location of Sensors
‘How many detectors do I need?’ and ‘where should I locate them?’ are
two of the most often asked questions about gas detection systems,
and probably two of the most difficult to answer. Unlike other types of
safety related detectors, such as smoke detectors, the location and
quantity of detectors required in different applications is not clearly
defined.
The placement of detectors should be determined following the advice
of experts having specialist knowledge of gas dispersion, experts
having knowledge of the process plant system and equipment
involved, safety and engineering personnel. The agreement reached
on the location of detectors should also be recorded.
Detectors should be mounted where the gas is most likely to be
present. Locations requiring the most protection in an industrial plant
would be around gas boilers, compressors, pressurized storage tanks,
cylinders or pipelines. Areas where leaks are most likely to occur are
valves, gauges, flanges, T-joints, filling or draining connections etc.
Monitoring and Controlling of Smoke emission and Gas Leakage using PLC
26
There are a number of simple and quite often obvious considerations
that help to determine detector location:
To detect gases that are lighter than air (e.g. Methane and Ammonia),
detectors should be mounted at high level and preferably use a
collecting cone. To detect heavier than air gases (e.g. Butane and
Sulfur Dioxide), detectors should be mounted at a low level. Consider
how escaping gas may behave due to natural or forced air currents.
Mount detectors in ventilation ducts if appropriate. When locating
detectors consider the possible damage caused by natural events e.g.
rain or flooding. For detectors mounted outdoors it is preferable to use
the weather protection assembly. Use a detector sunshade if locating a
detector in a hot climate and in direct sun. Consider the process
conditions. Butane and Ammonia, for instance are normally heavier
than air, but if released from a process line that is at an elevated
temperature and/or under pressure, the gas may rise rather than fall.
Detectors should be positioned a little way back from high pressure
parts to allow gas clouds to form. Otherwise any leak of gas is likely to
pass by in a high speed jet and not be detected. Consider ease of
access for functional testing and servicing. Detectors should be
installed at the designated location with the detector pointing
downwards. This ensures that dust or water will not collect on the front
of the sensor and stop the gas entering the detector. When siting open
path infrared devices it is important to ensure that there is no
permanent obscuration or blocking of the IR beam. Short term
blockage from vehicles, site personnel, birds etc can be
accommodated. Ensure the structures that open path devices are
mounted to are sturdy and not susceptible to vibration.
1.4Control Systems and mitigation
Mitigating actions
Monitoring and Controlling of Smoke emission and Gas Leakage using PLC
27
Actions may range from alerting a control room operator, release of
extinguishants to a complete plant shut down to sounding an
evacuation alarm. The control room operator may be part of the
control loop perhaps by being required to decide whether to initiate a
general alarm or plant shut-down.the ozone depleting effects of Halon
1301 and its almost complete ban has led to a review of the general
use of automatically released exinguishants and an increase in
emphasis on early warning of fire and manual interventions. This
emphasis is, however, company and country specific.
Start water fire pumps
Frequently fire pumps are started as a precautionary measurement
detection of fire or on a manually initiated fire indication. Fire pumps
can normally or stopped locally to the fire pump. Fire pump control
logic- sequencing is sometimes performed by a fire and gas system. It
can also be implemented in dedicated fire pump controllers supplied
by a fire pump supplier.
A manual start fire pump push-button should be provided in the control
room wired directly to the fire pump control panel.
Initiate Plant Alarms
Plant alarms can be automatic or manual and can be wired directly the
fire and the gas system or form part of a general, high integrity public
address system.
Consideration should be given to an alarm hierarchy and local zoning.
For example is it necessary to evacuate a complete site based local
alarm in an instrument room? visual repeats of audible alarms may be
needed in noisy areas. Some jurisdictions require all audible alarms to
be accompanied by a visual indication such as an integrated flashing.
Monitoring and Controlling of Smoke emission and Gas Leakage using PLC
28
beacon(srobe) . Colours of visual indications need to be established at
an early stage to ensure that they don’t clash with other indicators .
The chopice of colours affects the distance covered by a device of
given power.
Fig 5: Horn & Beacon
For audible alarms, consideration needs to be given to how many
different sounds are required and how many sounds the plant
personnel can distinguish. Voice messages offer greater flexibility in
conveying messages, but may not be so effective in multilingual
projects or comprehensible to off-site personnel.
If alarm signaling is via another system, it needs to be established
which system has control over facilities such as system resetting,
inhibiting and silencing.
Choice of interface could be hard wired, secure serial or a combination
using remote I/O (inputs and outputs) co-located at the alarm signaling
system.
Audible and visual alarms can be initiated in the following ways:
Monitoring and Controlling of Smoke emission and Gas Leakage using PLC
29
Automatically on detection of fire, perhaps requiring more than one fire
detector to operate(voting) automatically on detection of gas, perhaps
voted automatically after a delay to allow for manual intervention
manually by the control room operator manually by manual call point
in the field other combinations of the above
1.4.1Fire alarm control panel
A Siemens MXL fire alarm control panel (top) and graphic annunciator.
Monitoring and Controlling of Smoke emission and Gas Leakage using PLC
30
A Fire Alarm Control Panel (FACP), or Fire Alarm Control
Unit (FACU), is the controlling component of a Fire Alarm System. The
panel receives information from environmental sensors designed to
detect changes associated with fire, monitors their operational
integrity and provides for automatic control of equipment, and
transmission of information necessary to prepare the facility for fire
based on a predetermined sequence. The panel may also supply
electrical energy to operate any associated sensor, control,
transmitter, or relay. There are four basic types of panels: coded
panels, conventional panels, addressable panels, and multiplex
systems.
Conventional Fire Alarm Control Panels
Conventional panels have been around ever since electronics became
small enough to make them viable. conventional panels are used less
frequently in large buildings than in the past, but are not uncommon
on smaller projects such as small schools, stores, restaurants, and
apartments.
A conventional Fire Alarm Control Panel employs one or more circuits,
connected to sensors (initiating devices) wired in parallel. These
sensors are devised to dramatically decrease the circuit resistance
when the environmental influence on any sensor exceeds a
predetermined threshold. In a conventional fire alarm system, the
information density is limited to the number of such circuits used.
To facilitate location and control of fire within a building, the structure
is subdivided into definite areas or zones. Floors of a multistory
building are one type of zone boundary.
An Initiating Device Circuit connected to multiple devices within the
same "zone" of protection, effectively provides 2 bits of information
about the zone corollary to the state of the circuit; normal, or off
Monitoring and Controlling of Smoke emission and Gas Leakage using PLC
31
normal and alarm or quiescent. The state of each Initiating Device
Circuit within a zone displays at the Fire Alarm Control Panel using
visible indications called Annunciators.
These Annunciators may employ a graphical representation of the
Zone boundaries on a floor plan (Zone map) using textual descriptions,
illuminated icons, illuminated sections, or illuminated points on the
map corresponding to Initiating Circuits connected to the Fire Alarm
Control Panel.
For this reason, slang often inaccurately refers to initiating circuits of a
Fire Alarm Control Panel as Zones.
Larger systems and increasing demand for finer diagnostic detail
beyond broad area location and control functions expanded the control
by Zone strategy of conventional systems by providing multiple
initiating circuits within a common Zone, each exclusively connected to
a particular type of initiating device, or group of devices. This
arrangement forms a device type by Zone matrix whose information is
particularly suited to the Tabular Annunciator In multistory buildings
employing a Tabular Annunciator for Example; rows of indicators
define the floors horizontally in their stacked relationship and the type
of device installed on that floor displays as columns of indicators
vertically aligned through each floor. The intersection of the floor and
device indicators provides the combined information. The density of
information however remains a function of the number of circuits
employed.
Even larger systems and demands for finer diagnostic and location
detail led to the introduction of addressable fire alarm systems with
each addressable device providing specific information about its state
while sharing a common communication circuit. Annunciation and
location strategies for the most part remain relatively unchanged.
Monitoring and Controlling of Smoke emission and Gas Leakage using PLC
32
Fig: 6 Wiring Diagram
A wiring diagram for a simple fire alarm system consisting of two input
loops (one closed, one open)
Releasing panels
Releasing panels are capable of usings solenoids to disperse fire-
fighting chemical agents such as halon or water from piping located
throughout a building. A releasing panel usually will have a manual
abort switch to abort an accidental release which could damage
property or equipment. Releasing capability can be part of both
addressable or conventional panels.
Addressable Fire Alarm Control Panels
Monitoring and Controlling of Smoke emission and Gas Leakage using PLC
33
Fig 7: Addressable FACP
A Simplex 4100U InfoALARM addressable fire alarm control panel: note
the voice-evacuation microphone built into it
Signaling Line Circuits
Addressable Fire Alarm Control Panels employ one or more Signaling
Line Circuits, slang - usually referred to as loops or SLC loops -
ranging between one and thirty. Depending on the protocol used, a
Signaling Line Circuit can monitor and control several hundred devices.
Some protocols permit any mix of detectors and input/output modules,
while other protocols have 50% of channel capacity restricted to
detectors/sensors and 50% restricted to input/output modules. Each
SLC polls the devices connected, which can number from a few devices
to several hundred, depending on the manufacturer. Large systems
may have multiple Signaling Line Circuits. [1] [2]
Each device on a SLC has its own address, and so the panel knows the
state of each individual device connected to it. Common addressable
input (initiating) devices include
Smoke detectors
Heat Detectors (Rate of Rise and Fixed Temperature)
Monitoring and Controlling of Smoke emission and Gas Leakage using PLC
34
Manual call points or manual pull stations
Notification appliances (Simplex systems with TrueAlert signals
only)
Responders
Fire sprinkler system inputs
Switches
Flow control
Pressure
Isolate
Standard switches
Addressable output devices are known as relays and include
(Warning System/Bell) Relays
Door Holder Relays
Auxiliary (Control Function) Relays
Relays are used to control a variety of functions such as
Switching fans on or off
Closing/opening doors
Activating fire suppression systems
Activating notification appliances
Shutting down industrial equipment
Recalling elevators to a safe exit floor
Activating another fire alarm panel or communicator
Mapping
Also known as "cause and effect" or "programming", mapping is
the process of activating outputs depending on which inputs
have been activated. Traditionally, when an input device is
activated, a certain output device (or relay) is activated. As time
has progressed, more and more advanced techniques have
become available, often with large variations in style between
different companies.
Monitoring and Controlling of Smoke emission and Gas Leakage using PLC
35
Zones
Zones are usually made by dividing a building, or area into
different sections. Then depending on the specific zone, a certain
amount and type of device is added to the zone to perform its
given job.
Groups
Groups contain multiple output devices such as relays. This
allows a single input, such as a smoke detector or MCP, to have
only one output programmed to a group, which then maps to
between two to many outputs or relays. This enables an installer
to simplify programming by having many inputs map to the
same outputs, and be able to change them all at once, and also
allows mapping to more outputs than the programming space for
a single detector/input allows.
Boolean logic
This is the part of a fire panel that has the largest variation
between different panels. It allows a panel to be programmed to
implement fairly complex inputs. For instance, a panel could be
programmed to notify the fire department only if more than one
device has activated. It can also be used for staged evacuation
procedures in conjunction with timers.
Networking
The principle of networking involves connecting several panels
together to form a system. Inputs on one panel may activate
outputs on another, for example, or the network may allow
monitoring of many systems. Networking is often used in
situations where one panel is not large enough, or in multiple-
building situations. These are often done with manufacturers'
"top of the line" control panels.
Monitoring and Controlling of Smoke emission and Gas Leakage using PLC
36
Although quasi-standards exist that allow panels from different
manufacturers to be networked with each other, they are not in
favor with a lot of companies. One of the most common protocols
used BAC net which is used for various type of industrial
networks.
More recently, some panels are being networked with
standard Ethernet, but this is not yet very common. Most
organizations choose to create their own proprietary protocol,
which has the added benefit of allowing them to do anything
they like, allowing the technology to progress further. However, a
bridging layer between the proprietary network and BACnet is
usually available]
Networking may be used to allow a number of different panels to
be monitored by one graphical monitoring system.
Monitoring
In nearly every state in the USA, the International Building
Code requires fire alarm and sprinkler systems to be monitored
by an approved supervising station.
A fire alarm system consists of a computer-based control
connected to a central station. The majority of fire alarm systems
installed in the USA are monitored by a UL listed or FM Global
approved supervising station.
These systems will generally have a top level map of the entire
site, with various building levels displayed. The user (most likely
a security guard) can progress through the different stages. From
top level site → building plan → floor plan → zone plan, or
however else the building's security system is organised.
A lot of these systems have touch screens, but most users tend
to prefer a mouse (and a normal monitor), as it is quite easy for a
touch screen to become misaligned and for mistakes to be made.
Monitoring and Controlling of Smoke emission and Gas Leakage using PLC
37
With the advent of the optical mouse, this is now a very viable
option.
System functions
Fig 8: System Functions
There are many functions on a fire alarm panel. Some of these are:
System reset
This resets the panel after an alarm condition. All initiating devices are
reset, and the panel is cleared of any alarm conditions. If an initiating
device is still in alarm after the system is reset, such as a smoke
detector continuing to sense smoke, or a manual pull station still in an
activated position, another alarm will be initiated. A system reset is
often required to clear supervisory conditions. A system reset does not
usually clear trouble conditions. Most trouble conditions will clear
automatically when conditions are returned to normal.
On UK and most US panels, a "Silence" or "Acknowledge" is usually
required before a "System Reset" can be performed.
Acknowledge
This function, also abbreviated to "ACK", is used to acknowledge an
abnormal situation such as an alarm, trouble or supervisory. The
Monitoring and Controlling of Smoke emission and Gas Leakage using PLC
38
acknowledge function tells the panel that building personnel or
emergency responders are aware of the alarm, trouble, or supervisory
condition. Acknowledging the alarm or trouble condition also normally
silences the panel's own sounder, but does not silence any Notification
Appliances.
Fig 9: Fire alarm panel, showing drill switch
Drill
Also known as "manual evacuation" or "evacuate". On panels that have
this function, the drill function activates the system's notification
appliances, often for purposes of conducting a fire drill. Using the drill
function, an alarm is normally not transmitted to the fire department or
monitoring center. However, building personnel often notify these
agencies in advance in case an alarm is inadvertently transmitted.
Walk test
Walk test allows the functional testing of the system's devices without
the assistance of additional people at the control panel itself. It is also
Monitoring and Controlling of Smoke emission and Gas Leakage using PLC
39
designed to allow initiating devices to be tested without setting off the
building's alarms. Most panels offer the option for a silent walk test (no
alarms activate) or an audible walk test (alarms activate for a brief
period when a device is initiated). A system trouble is typically
generated while the panel is in walk test mode. On European panels,
this is usually an engineer-only function and cannot be activated by a
user.
Signal silence
Also known as "alarm silence" or "audible silence". Depending on the
configuration of the alarm system, this function will either silence the
system's notification appliances completely, or will silence only the
audible alarm, with strobe lights continuing to flash. Audible silence
allows for easier communication amongst emergency responders while
responding to an alarm. This can also be used during construction as a
means of a preliminary test, before the final full test.
Lamp test
Also known as "flash test". This button is known to have become
obsolete, but is still used on many panels. This function is used to
check the condition of the LEDs themselves. A "Lamp Test" button is
required by code on multi-zone panels installed in Canada. Many
panels do a lamp test when the system is reset.
Alarm circuit supervision
Various forms of alarm circuit supervision have been used to indicate
trouble with an alarm circuit. Possible alarm circuit faults on a two wire
circuit include one of the conductors being shorted to ground, open
circuit (conductor continuity break), or a short circuit between the
conductors. Also the circuits could be tampered with by having an
external AC or DC voltage applied with various duty cycles or
waveforms. There are a number of US patents that address this issue
and some have been implemented in available system products. One
Monitoring and Controlling of Smoke emission and Gas Leakage using PLC
40
of the first to address this issue was Patent No. 3,588,890 "Resistance
Sensing Supervisory System" issued on June 28, 1971 and assigned to
General Motors Corporation. General Motors used this supervision on
all circuits installed in GM plants starting in 1970.[3] An improvement to
this basic "Resistance Sensing Supervisory System" can be obtained by
providing a pulsed or time dependent variable voltage applied to the
alarm circuit and is addressed in US patent numbers 4,030,095 [1] and
4,716,401 [2].
Panel alerting
Many panels today have the capability of alerting building personnel of
a situation which can arise into a potentially serious problem. Fire
alarm panels indicate an abnormal condition via a solid or flashing LED.
Some panels also contain a small sounder, used in conjunction with the
visual alert. A number of indicators are shown below. Note that not all
fire alarm panels have all of these indicators.
Alarm
Also known as "Fire" or "General Alarm". This indicator is lit when an
alarm condition exists in the system, initiated by smoke
detectors, heat detectors, sprinkler flow switches, manual pull stations,
manual call points, or otherwise. Along with the indicator on the panel,
notification appliances, such as horns and strobes, are also activated,
signaling a need to evacuate to building occupants. In an alarm
condition, the fire alarm panel indicates where the alarm originated.
The alarm panel can be reset once the device which initiated the alarm
is reset, such as returning the handle of a manual pull station to its
normal position.
Audible silence
The Audible Silence indicator is used in conjunction with the "Alarm"
indicator. It indicates that the fire alarm panel is still in an alarm
condition, but that notification appliances have been silenced. While
Monitoring and Controlling of Smoke emission and Gas Leakage using PLC
41
the alarm is silenced, other functions in an alarm condition continue to
operate, such as emergency service for elevators, stairway
pressurization, and ventilation functions. A new alarm initiation while
the alarm is silenced will take the panel out of Audible Silence and
reactivate the notification appliances.
Report
Also known as "Brigade Called". This indicator is activated when
emergency responders have been automatically notified by the fire
alarm system. A variant of this LED known as "kissoff" activates when
the monitoring center replies back to the panel, indicating a successful
communication. Requirements vary depending on jurisdiction
regarding whether a direct connection to the fire department is
required, optional, or prohibited. If a connection to the fire department
is optional, or is prohibited, a fire alarm system is often connected to a
monitoring center at the building owner's discretion.
Drill
Also known as "Manual Evacuation" or "Evacuate". On panels
containing this function, the "Drill" indicator shows that the alarm
condition was activated from the fire alarm panel, often in order to
conduct a fire drill. When an alarm is initiated for a drill, the fire
department or monitoring company is usually not notified
automatically. However, building personnel preparing to conduct a fire
drill often will provide advance notice of a drill to the fire department
and monitoring center in case an alarm is unintentionally transmitted.
Pre alarm
This LED is often used in conjunction with a two-stage system, in which
the panel requires two devices to be activated (and/or a predetermined
time limit to run out after one device is activated) in order to go into
full alarm.[4] This is mostly used in areas where false alarms are a
common problem, or in large applications (such as hospitals) where
Monitoring and Controlling of Smoke emission and Gas Leakage using PLC
42
evacuating the entire building would not be efficient. The prealarm LED
is lit when one device has tripped. The prealarm LED may also be used
if an analog smoke detector registers low levels of smoke in the
detection chamber, but not enough to trigger a full alarm.[5] Depending
on the system's layout, the NAC's may or may not activate for
prealarm conditions. In a two-stage system, the NAC's are typically
coded to a special first-stage coding, or in some situations where a
loud alarm signal could be disruptive, chimes will activate. If there is a
voice evacuation system, it will usually instruct building occupants to
await further instructions while the alarm is being investigated.
Priority 2 alarm
Also known as "Security". This LED is common on top-of-the-line
intelligent panels. This LED can only activate if there is a secondary
device hooked into the "Priority 2 Alarm" terminals. This secondary
device could be a security system, building management system, or
another fire alarm control panel. Depending on how the panel is
programmed, the panel's alarms may or may not activate when a
condition like this is present.
Trouble
Also known as "Fault" or "Defect". When held steady or flashing, it
means that a trouble condition exists on the panel. Trouble conditions
are often activated by a contaminated smoke detector or an electrical
problem within the system. Trouble conditions are also activated by a
zone being disabled (disconnected from the system), a circuit being
disabled, low power on the backup battery, the disabling of a
notification appliance, the ground faults, or short or open circuits.
Usually the alarm panel's sounder will activate if a trouble condition
exists, though older systems would sometimes activate a bell or other
audible signal connected to the panel. In a trouble condition, the panel
displays the zone or devices causing the condition. Usually, the
Monitoring and Controlling of Smoke emission and Gas Leakage using PLC
43
"Trouble" indicator goes out automatically when the situation causing
the trouble condition is rectified, however in some systems (EST) the
panel must be reset to clear the trouble alarm. Some panels have
more specific indicators such as 'Trouble-PSU' which shows when the
panel itself is compromised and 'Trouble-Bell' ('Sounder fault' on UK
panels) which shows that the sounders are not functioning correctly.
On most panels, an acknowledge button is pressed to turn off the
panel's buzzer.
Supervisory
This signal indicates that a portion of the building's fire protection
system has been disabled (such as a fire sprinkler control valve being
closed and, consequently, a sprinkler tamper switch being activated),
or, less frequently, that a lower priority initiating device has been
triggered (such as a duct smoke detector). Depending on the system's
design, the supervisory point may be latching, meaning the panel must
be reset to clear the supervisory condition, or non-latching, meaning
the indicator automatically goes out when the condition has cleared.
However, some panels require a reset regardless of whether the
supervisory point is latching or non-latching.
AC power
Also known as "Normal". When this indicator is lit, power is being
provided to the system from the building's electrical system, and not
from the backup battery. When an AC power condition changes, the
Trouble indicator comes on and the AC power indicator goes off and
the screen alerts building personnel of a power failure. If the AC power
indicator is lit without any other indicators also lit, then the system is
in a normal condition. If no LEDs are lit, there is no power source
feeding the panel.
DC power
Monitoring and Controlling of Smoke emission and Gas Leakage using PLC
44
This is used to tell the operator that DC power (batteries) are being
charged or used. While using DC power, the system remains in a
trouble condition.
Highrate
This LED is on when there are unusual power-line conditions.
1.5Programmable Logic Controller (PLC)
Programmable logic control or PLC is the most commonly used
industrial automation technique in the world. It is universally
applied for factory automation, process control and
manufacturing systems. Programmable logic control originated
from the creation of computerized versions of relay control
systems used to control manufacturing and chemical process
systems. The programming is done using a special technique
called ladder logic, which allows sequences of logical actions to
be set up, inter-linked and timed. A standard task in logic
control is batch control and sequencing in a process system.
1.5.1 PLC Introduction
A PLC or Programmable Logic Controller is a user friendly,
microprocessor specialized computer that carries out control
functions of many types and levels of complexity. Its purpose is
to monitor crucial process parameters and adjust process
operations accordingly. It can be programmed, controlled and
operated by a person unskilled in operating computers.
Essentially, a PLC's operator draws the lines and devices of
ladder diagrams with a keyboard onto a display screen. The
resulting drawing is converted into computer machine language
and run as a user program.
PLC will operate any system that has output devices that go on
and off (Discrete, or Digital, outputs). It can also operate any
Monitoring and Controlling of Smoke emission and Gas Leakage using PLC
45
system with variable (analog) outputs. The Programmable Logic
Control can be operated on the input side by ON/OFF devices or
by variable (analog) input devices.
Control engineering has evolved over time. In the past humans
was the main method for controlling a system. More recently
electricity has been used for control and early electrical control
was based on relays. These relays allow power to be switched
on and off without a mechanical switch. It is common to use
relays to make simple logical control decisions. The
development of low cost computer has brought the most recent
revolution, the Programmable Logic Controller (PLC). The
advent of the PLC began in the 1970s, and has become the
most common choice for manufacturing controls.
Programmable Logic Controllers have been gaining popularity
on the factory floor and will probably remain predominant for
some time to come. Most of this is because of the advantages
they offer.
1.5.2 PLC Advantages and Disadvantages
Flexibility: One single Programmable Logic Controller can easily
run many machines.
Correcting Errors: In old days, with wired relay-type panels,
any program alterations required time for rewiring of panels and
devices. With PLC control any change in circuit design or
sequence is as simple as retyping the logic. Correcting errors in
PLC is extremely short and cost effective.
Space Efficient: Today's Programmable Logic Control memory
is getting bigger and bigger this means that we can generate
more and more contacts, coils, timers, sequencers, counters and
so on. We can have thousands of contact timers and counters in
Monitoring and Controlling of Smoke emission and Gas Leakage using PLC
46
a single PLC. Imagine what it would be like to have so many
things in one panel.
Low Cost: Prices of Programmable Logic Controlers vary from
few hundreds to few thousands. This is nothing compared to the
prices of the contact and coils and timers that you would pay to
match the same things. Add to that the installation cost, the
shipping cost and so on.
Testing: A Programmable Logic Control program can be tested
and evaluated in a lab. The program can be tested, validated and
corrected saving very valuable time.
Visual observation: When running a PLC program a visual
operation can be seen on the screen. Hence troubleshooting a
circuit is really quick, easy and simple.
1.5.3 ALLEN BRADLEY PLC MICROLOGIX 1200 CONTROLLER.
AB PLC TYPES:
Allen Bradley PLCs, the standard by which other PLCs are measured.
From the very inception of the idea of the programmable logic
controller the Allen Bradley PLC's were there. Thirty years of history
and experience is involved in every Allen Bradley programmable logic
controller that you get, helping you to move forward, to exert powerful
and expert control of your devices. .
The Programmable logic controller was designed to provide you with
the control solutions that you need for your remote mechanics. The
Allen Bradley controllers offer some key ways to solve your problems
and to give you what you need.
Solving the challenges of manufacturing and lowering your costs is the
business of every business. Improving your output, increasing the
quality and the flexibility that you have is your secondary aim. Allen
Bradley programmable logic controllers are expert at those things.
Monitoring and Controlling of Smoke emission and Gas Leakage using PLC
47
They bring to your business a highly customizable integrated solution
to the control of your systems and devices. Your PLC will be up the
challenges that you face when you select the Allen Bradley
Programmable logic controller.
The Allen Bradley Programmable logic controllers help you in both time
and money saving, as well as offering you a faster start-up. Your new
fast start up time is a result of products that are pre-integrated--
designed to fit together like pieces of a well oiled puzzle. From the
beginning to the end of the operation, the maintenance will be far less
and the need for programming will be minimal.
Allen Bradley is a part of Rockwell Automation Integrated
Architecture and offers controllers that are suitable for drives, for
motion, and for process controlling. No matter what you need, if you
have to have high performance or value based in your programmable
logic controller system, you will find just the right controller with the
Allen Bradley programmable logic controllers.
The many different offerings from Allen Bradley-Rockwell Automation
Integration include the NetLinx, the Kinetix, and the Logix. All of these
will offer you maximum capabilities, easy use, reuse capacity of
program, flexibility in the communications system and fast easy use so
that you can spend less of your company's time and money on the
entire setup process.
Allen Bradley uses five different types of programmable logic
controllers. These different types of PLCs perform specialized
functions.
Pico Controllers are simple, as well as flexible and small, performing
logic, counting, time and clock operations..
MicroLogix PLCs are a cost-effective solution for micro-control that
will expand as needed.
Monitoring and Controlling of Smoke emission and Gas Leakage using PLC
48
SLC 500s are small, modular programmable controllers that are
chassis-based. It is often the choice for I/O and power supply functions.
PLC-5 is the most popular Allen Bradley PLC and can be found
worldwide, providing flexibility in networking, I/O and programming
and being suitable for a wide variety of applications. .
1758-RTU is a programmable logic controller designed for rugged and
harsh environments as a Remote Terminal Unit (RTU).
From conception to implementation, any Allen Bradley programmable
logic controller results in cost savings, increased productivity and
satisfied clients.
Monitoring and Controlling of Smoke emission and Gas Leakage using PLC
49
Monitoring and Controlling of Smoke emission and Gas Leakage using PLC
System Overview
The MicroLogix 1200/1762 system provides functionality between the MicroLogix
1000/1761 and MicroLogix 1500/1764 systems, using the proven MicroLogix and
SLC family architecture. The 6K-word memory provides for a maximum program
of 4K words and maximum data of 2K words with 100% data retention. An
optional
memory module provides program and data backup with program upload and
download capability. The optional real-time clock enables time scheduling of
control
activities. The flash upgradeable operating system lets you upgrade system
software
without replacing hardware.
Product Design
The MicroLogix 1200 controller and expansion I/O modules provide a modular,
rackless control system designed for ease of installation and maintenance. Each
MicroLogix 1200 controller includes a processor, built-in I/O, and power supply.
Expansion I/O modules install to the right of the controller. Cables built into the
I/O modules provide connection to the adjacent I/O module or controller.
Controllers and I/O modules can be mounted either on a panel or on a DIN-rail.