Smoke Alarm Research at NIST Thomas G. Cleary Fire Research Division National Institute of Standards and Technology March 27, 2014

Transcript of Smoke Alarm Research at NIST - Vision 20/20• The rate of alarm decreased by a factor of between...

Page 1: Smoke Alarm Research at NIST - Vision 20/20• The rate of alarm decreased by a factor of between 2.5 to 4 as distance between the cooking source and alarm increased from 10 ft ...

Smoke Alarm Research at NIST

Thomas G. Cleary Fire Research Division

National Institute of Standards and Technology

March 27, 2014

Page 2: Smoke Alarm Research at NIST - Vision 20/20• The rate of alarm decreased by a factor of between 2.5 to 4 as distance between the cooking source and alarm increased from 10 ft ...

Outline

•  Kitchen fire and nuisance alarm experiments (CPSC funded)

•  New NIST kitchen pre-fire detection research •  Measurements for advanced detectors •  Codes and Standards

Page 3: Smoke Alarm Research at NIST - Vision 20/20• The rate of alarm decreased by a factor of between 2.5 to 4 as distance between the cooking source and alarm increased from 10 ft ...

Kitchen Fire and Nuisance Experiments

8.6 m

4.4 m

Page 4: Smoke Alarm Research at NIST - Vision 20/20• The rate of alarm decreased by a factor of between 2.5 to 4 as distance between the cooking source and alarm increased from 10 ft ...

Kitchen Fire and Nuisance Experiments

Page 5: Smoke Alarm Research at NIST - Vision 20/20• The rate of alarm decreased by a factor of between 2.5 to 4 as distance between the cooking source and alarm increased from 10 ft ...

Kitchen Fire and Nuisance Experiments

•  Alarms and Instrumentation –  Various commercially-available smoke alarms

–  Aerosol characterization instrumentation

–  Carbon monoxide, carbon dioxide and oxygen concentrations (5 ft for tenability for fire tests)

–  Temperatures (ceiling and 5 ft for tenability)

–  Smoke extinction (5 ft for egress)

–  Ceiling air flows during nuisance tests

Page 6: Smoke Alarm Research at NIST - Vision 20/20• The rate of alarm decreased by a factor of between 2.5 to 4 as distance between the cooking source and alarm increased from 10 ft ...

Cooking Experiments

•  Cooking scenarios consisted of: –  broiling a hamburger –  broiling frozen pizza –  frying a hamburger –  making a grilled-cheese sandwich in a no-stick frying pan –  stir-frying vegetables in a wok on the electric burner –  frying bacon –  toasting bread

•  Light, medium, and dark toast

–  toasting frozen bagels

Page 7: Smoke Alarm Research at NIST - Vision 20/20• The rate of alarm decreased by a factor of between 2.5 to 4 as distance between the cooking source and alarm increased from 10 ft ...

Cooking Activities Toasting

Page 8: Smoke Alarm Research at NIST - Vision 20/20• The rate of alarm decreased by a factor of between 2.5 to 4 as distance between the cooking source and alarm increased from 10 ft ...

Cooking Activities Frying

Page 9: Smoke Alarm Research at NIST - Vision 20/20• The rate of alarm decreased by a factor of between 2.5 to 4 as distance between the cooking source and alarm increased from 10 ft ...

Cooking Activities Frying

Page 10: Smoke Alarm Research at NIST - Vision 20/20• The rate of alarm decreased by a factor of between 2.5 to 4 as distance between the cooking source and alarm increased from 10 ft ...

Cooking Activities Broiling

Page 11: Smoke Alarm Research at NIST - Vision 20/20• The rate of alarm decreased by a factor of between 2.5 to 4 as distance between the cooking source and alarm increased from 10 ft ...

General trends

•  Propensity to alarm depended on alarm type and scenario.

•  The rate of alarm decreased by a factor of between 2.5 to 4 as distance between the cooking source and alarm increased from 10 ft to 20 ft.

•  Inside the kitchen, the rate of alarm varied from 40 % to 84% depending on the alarm, while at the farthest two locations the rate varied between 4 % to 28 %.

Page 12: Smoke Alarm Research at NIST - Vision 20/20• The rate of alarm decreased by a factor of between 2.5 to 4 as distance between the cooking source and alarm increased from 10 ft ...

All Cooking Events Alarm activation frequency for equal fractions of range top,

oven and toasting activities

0

0.2

0.4

0.6

0.8

1

0 1 2 3 4 5 6 7

P1 I1 D1 D2 M1 M2

Ala

rm A

ctiv

atio

n Fr

eque

ncy

Distance from Cooking Source (m)

Page 13: Smoke Alarm Research at NIST - Vision 20/20• The rate of alarm decreased by a factor of between 2.5 to 4 as distance between the cooking source and alarm increased from 10 ft ...

Kitchen Fire Experiments

•  Two cabinet types –  Pressboard with solid oak doors –  Pressboard with thin plastic veneer

•  Two ignition scenario variations of an electric coil heating element ignition of roll of paper towels spreading flames to various combustibles –  Scenario 1 including a small coffee maker –  Scenario 2 including cooking oil soaked rag and

paper towels

Page 14: Smoke Alarm Research at NIST - Vision 20/20• The rate of alarm decreased by a factor of between 2.5 to 4 as distance between the cooking source and alarm increased from 10 ft ...

Kitchen Fire – Ignition Scenario 1

paper towels

5 foam plates

Coffee maker

bag of potato chips

coil burner

Page 15: Smoke Alarm Research at NIST - Vision 20/20• The rate of alarm decreased by a factor of between 2.5 to 4 as distance between the cooking source and alarm increased from 10 ft ...

Kitchen Fire – Ignition Scenario 2

paper towels

10 foam plates under paper towels

box of microwave popcorn

bag of potato chips

coil burner

bag of corn chips

oil-soaked dish rag plastic plate with oil-soaked paper towels

Page 16: Smoke Alarm Research at NIST - Vision 20/20• The rate of alarm decreased by a factor of between 2.5 to 4 as distance between the cooking source and alarm increased from 10 ft ...

Kitchen Fire HRR – Scenario 1A

Peak HRR

0

100

200

300

400

500

600

700

0 200 400 600 800 1000

HRR (kW)

Hea

t Rel

ease

Rat

e (k

W)

Time (s)

Page 17: Smoke Alarm Research at NIST - Vision 20/20• The rate of alarm decreased by a factor of between 2.5 to 4 as distance between the cooking source and alarm increased from 10 ft ...

Kitchen Fire – Scenario 2A

Peak HRR

0

50

100

150

200

0 200 400 600 800 1000

Hea

t Rel

ease

Rat

e (k

W)

Time (s)

Page 18: Smoke Alarm Research at NIST - Vision 20/20• The rate of alarm decreased by a factor of between 2.5 to 4 as distance between the cooking source and alarm increased from 10 ft ...

Kitchen Fire – Scenario 2B

Peak HRR

0

100

200

300

400

500

600

700

0 200 400 600 800 1000

HRR (kW)

Hea

t Rel

ease

Rat

e (k

W)

Time (s)

Page 19: Smoke Alarm Research at NIST - Vision 20/20• The rate of alarm decreased by a factor of between 2.5 to 4 as distance between the cooking source and alarm increased from 10 ft ...

Kitchen Fire – Scenario 1

Page 20: Smoke Alarm Research at NIST - Vision 20/20• The rate of alarm decreased by a factor of between 2.5 to 4 as distance between the cooking source and alarm increased from 10 ft ...

Kitchen Fire – Scenario 2

Page 21: Smoke Alarm Research at NIST - Vision 20/20• The rate of alarm decreased by a factor of between 2.5 to 4 as distance between the cooking source and alarm increased from 10 ft ...

Kitchen Fire Observations

•  Ignition source and cabinet type affect fire growth rate

•  Small space tended to limit oxygen to fire •  Installed smoke alarms at any distance

provided safe egress times of greater than 90 s

Page 22: Smoke Alarm Research at NIST - Vision 20/20• The rate of alarm decreased by a factor of between 2.5 to 4 as distance between the cooking source and alarm increased from 10 ft ...

Current Research Kitchen Pre-fire Detection

Objectives

•  (1) To experimentally determine the levels of smoke produced and other signatures, and corresponding times before ignition of cooking fires that existing measurement technologies can utilize to sense pre-fire conditions.

•  (2) To provide the sensitivities and operating parameters for kitchen-deployable unattended cooking pre-fire detector that could interrupt power to offending appliances and/or alert consumers allowing intervention to prevent ignition of unattended cooking fires.

Page 23: Smoke Alarm Research at NIST - Vision 20/20• The rate of alarm decreased by a factor of between 2.5 to 4 as distance between the cooking source and alarm increased from 10 ft ...

Kitchen Pre-fire Detection Conducted in NIST Fire Detection Room

Page 24: Smoke Alarm Research at NIST - Vision 20/20• The rate of alarm decreased by a factor of between 2.5 to 4 as distance between the cooking source and alarm increased from 10 ft ...

Planned Experiments •  Unattended cooking scenarios will include:

–  heating vegetable oil

–  frying chicken or potatoes with oil

–  frying bacon

–  caramelizing sugar among others

•  Some heavy smoke-producing normal/attended cooking scenarios (e.g., broiling meat, and stir fry) will be included to differentiate cooking activities that most-likely will not ignite and spread fire.

Page 25: Smoke Alarm Research at NIST - Vision 20/20• The rate of alarm decreased by a factor of between 2.5 to 4 as distance between the cooking source and alarm increased from 10 ft ...

Measurements

•  Smoke concentrations (extinction, mass concentration, analog smoke alarm)

•  CO and CO2 •  Thermal (surface and ceiling air temperature With and without range hood running Examine boundary between nuisance alarm activation and pre-fire conditions.

Page 26: Smoke Alarm Research at NIST - Vision 20/20• The rate of alarm decreased by a factor of between 2.5 to 4 as distance between the cooking source and alarm increased from 10 ft ...

Advanced Detection Research

•  Examine sensors and advanced algorithms that may provide early fire detection and robust discrimination of non-fire nuisance conditions

•  Detailed measurements of smoke and nuisance aerosol concentrations, gas, thermal and other sensor outputs.

Page 27: Smoke Alarm Research at NIST - Vision 20/20• The rate of alarm decreased by a factor of between 2.5 to 4 as distance between the cooking source and alarm increased from 10 ft ...

Smoke InletSheath Air

Fixed AngleLight ScatteringDisks

Rotating Detector Stage

Transparent Tube

Beam BlockSupport Plate

Polarized Laser Beam

Smoke Outlet

Table

405nm, 638nm, 785nm, 980nm

405 nm, 635nm, or 850 nm

Advanced Detection Research Smoke Nephelometer, Aerosol Polarimeter

•  16 simultaneous scattering measurements user

configurable over 8 angles and 4 laser wavelengths

•  Polarimeter measurements on steady smoke sources for detailed smoke and nuisance source characterization

•  Propose and test discriminating algorithms for advanced smoke detection

Page 28: Smoke Alarm Research at NIST - Vision 20/20• The rate of alarm decreased by a factor of between 2.5 to 4 as distance between the cooking source and alarm increased from 10 ft ...

Codes and Standards

•  NIST experimental results and research being considered to define performance criteria for new UL 217/268 PU foam fire tests.

•  NIST experimental data on cooking aerosols being used to develop new UL 217/268 nuisance alarm tests

•  NFPA 72 household alarms (SIG HOU) has nuisance resistant alarm requirements (2019)

Page 29: Smoke Alarm Research at NIST - Vision 20/20• The rate of alarm decreased by a factor of between 2.5 to 4 as distance between the cooking source and alarm increased from 10 ft ...

Thank you for your attention