Smart Grid Control Primer
AnuragKSrivastavaWashingtonStateUniversity
![Page 2: Smart Grid Control Primer - CREDC · switch status) o RTU, PDC ... or external factors. Momentarily • No formal metrics outage ignored. • SAIDI, SAIFI, MAIFI, etc ... - PowerWorld](https://reader033.fdocuments.in/reader033/viewer/2022050717/5ebba690cd8cb43a486d38a9/html5/thumbnails/2.jpg)
cred-c.org|2
Smart Grid Goals § PowerSystemOperaFonal
Paradigm(reliability,economics,resiliency,sustainability)
§ Sense
§ Communicate
§ Compute
§ Visualize
§ Control
§ Advancementinphysicalsystem,informaFonnetwork,
control,humanaspects
Sense
Commun
icate ComputeandsendControl
Signal
![Page 3: Smart Grid Control Primer - CREDC · switch status) o RTU, PDC ... or external factors. Momentarily • No formal metrics outage ignored. • SAIDI, SAIFI, MAIFI, etc ... - PowerWorld](https://reader033.fdocuments.in/reader033/viewer/2022050717/5ebba690cd8cb43a486d38a9/html5/thumbnails/3.jpg)
cred-c.org|3
ControlObjec-veandMul--scaleDynamicsinPowerSystem
![Page 4: Smart Grid Control Primer - CREDC · switch status) o RTU, PDC ... or external factors. Momentarily • No formal metrics outage ignored. • SAIDI, SAIFI, MAIFI, etc ... - PowerWorld](https://reader033.fdocuments.in/reader033/viewer/2022050717/5ebba690cd8cb43a486d38a9/html5/thumbnails/4.jpg)
cred-c.org|4
Centralized Control
Credit: PSERC report
Local/ Decentralized
Control
![Page 5: Smart Grid Control Primer - CREDC · switch status) o RTU, PDC ... or external factors. Momentarily • No formal metrics outage ignored. • SAIDI, SAIFI, MAIFI, etc ... - PowerWorld](https://reader033.fdocuments.in/reader033/viewer/2022050717/5ebba690cd8cb43a486d38a9/html5/thumbnails/5.jpg)
cred-c.org|5
Smart Grid Control n Voltage, frequency and
power control n Provide operators with
up-to-date information on the condition of the power systems
n critical quantities are measured
n voltages, currents, power flows, and the state of circuit breakers and switches
n frequency, generator outputs, and transformer tap positions
n the measurements are sent to the control center
n via the telemetry system
![Page 6: Smart Grid Control Primer - CREDC · switch status) o RTU, PDC ... or external factors. Momentarily • No formal metrics outage ignored. • SAIDI, SAIFI, MAIFI, etc ... - PowerWorld](https://reader033.fdocuments.in/reader033/viewer/2022050717/5ebba690cd8cb43a486d38a9/html5/thumbnails/6.jpg)
cred-c.org|6
PrevenFveMechanism• ForecasFngandplanning(shortterm,longterm)• Securityanalysisagainstprobablefailures• HumanOperator
CorrecFveMechanism• ProtecFon• Frequency/Voltage/StabilityControl• RemedialAcFonSchemes/SpecialProtecFonScheme• WideAreaControl• SystemrestoraFon• HumanOperator
Preventive and Corrective Control Mechanism
![Page 7: Smart Grid Control Primer - CREDC · switch status) o RTU, PDC ... or external factors. Momentarily • No formal metrics outage ignored. • SAIDI, SAIFI, MAIFI, etc ... - PowerWorld](https://reader033.fdocuments.in/reader033/viewer/2022050717/5ebba690cd8cb43a486d38a9/html5/thumbnails/7.jpg)
cred-c.org|7
Distributed,CoordinatedandHierarchal
Fast
Scalable
Sub-OpFmal
Fault-tolerant
SupportsBigdata
SupportsIoT
Centralized
Slow
NotScalable
OpFmal
Pronetofailures
Local
Fast
Non-opFmal
Hardcoded
Mayfailforunexpected
Exis-ngMonitoringandControl EvolvingMonitoring andControl
Existing and Evolving Smart Grid Control
![Page 8: Smart Grid Control Primer - CREDC · switch status) o RTU, PDC ... or external factors. Momentarily • No formal metrics outage ignored. • SAIDI, SAIFI, MAIFI, etc ... - PowerWorld](https://reader033.fdocuments.in/reader033/viewer/2022050717/5ebba690cd8cb43a486d38a9/html5/thumbnails/8.jpg)
cred-c.org|8
Local Control: Generation Control Loop
![Page 9: Smart Grid Control Primer - CREDC · switch status) o RTU, PDC ... or external factors. Momentarily • No formal metrics outage ignored. • SAIDI, SAIFI, MAIFI, etc ... - PowerWorld](https://reader033.fdocuments.in/reader033/viewer/2022050717/5ebba690cd8cb43a486d38a9/html5/thumbnails/9.jpg)
cred-c.org|9
Local Control
Power System Operation
Automatic Control
Parameter: Voltage, frequency, power flow
Protection Droop Control AVR AGC RAS UFLS
![Page 10: Smart Grid Control Primer - CREDC · switch status) o RTU, PDC ... or external factors. Momentarily • No formal metrics outage ignored. • SAIDI, SAIFI, MAIFI, etc ... - PowerWorld](https://reader033.fdocuments.in/reader033/viewer/2022050717/5ebba690cd8cb43a486d38a9/html5/thumbnails/10.jpg)
cred-c.org|10
Centralized Control
![Page 11: Smart Grid Control Primer - CREDC · switch status) o RTU, PDC ... or external factors. Momentarily • No formal metrics outage ignored. • SAIDI, SAIFI, MAIFI, etc ... - PowerWorld](https://reader033.fdocuments.in/reader033/viewer/2022050717/5ebba690cd8cb43a486d38a9/html5/thumbnails/11.jpg)
cred-c.org|11
Power System Operation
Situational Awareness
Decision Support
Regulatory Framework: vertical vs market operation
Timeframe: Second, minutes, hours, day, months
Parameter: Voltage, frequency, power flow
Geographical: Area, reliability coordinator, Interconnection
Ownership: Investor owned, public owned, IPP, co-op
Asset: Gen, trans, dist
Centralized Control
![Page 12: Smart Grid Control Primer - CREDC · switch status) o RTU, PDC ... or external factors. Momentarily • No formal metrics outage ignored. • SAIDI, SAIFI, MAIFI, etc ... - PowerWorld](https://reader033.fdocuments.in/reader033/viewer/2022050717/5ebba690cd8cb43a486d38a9/html5/thumbnails/12.jpg)
cred-c.org|12
Power System Operation
Situational Awareness
• SCADA o Sensors (CT/PT, PMU,
switch status) o RTU, PDC merging units o Communication system o Data archival, historian
• State Estimation • Control Center Display,
organization • Visualization tool • Alarm, alerts
Centralized Control
![Page 13: Smart Grid Control Primer - CREDC · switch status) o RTU, PDC ... or external factors. Momentarily • No formal metrics outage ignored. • SAIDI, SAIFI, MAIFI, etc ... - PowerWorld](https://reader033.fdocuments.in/reader033/viewer/2022050717/5ebba690cd8cb43a486d38a9/html5/thumbnails/13.jpg)
cred-c.org|13
Power System Operation
Decision Support
• Real Time Operational
• Short Term Planning
• Long term Planning
• OPFo UnitCommitmento EconomicDispatcho Hydro-Thermal
Scheduling• SecurityAnalysis• LoadandpriceforecasFng• EnergyInterchange• Marketpoweranalysis
Timeframe: Second, minutes, hours, day, months
Centralized Control
![Page 14: Smart Grid Control Primer - CREDC · switch status) o RTU, PDC ... or external factors. Momentarily • No formal metrics outage ignored. • SAIDI, SAIFI, MAIFI, etc ... - PowerWorld](https://reader033.fdocuments.in/reader033/viewer/2022050717/5ebba690cd8cb43a486d38a9/html5/thumbnails/14.jpg)
cred-c.org|14
Operator Tasks
ManaginganenFty(electricity)thatis:• Invisible• Travelsinthespeedoflight• Dangerous/Fatal
• Ensuringthereliabledeliveryofelectricitytocustomers.
• Managethepowergridfromasetofcomputerconsoleswithinacontrolcenter.
• Interactoverthephonewithfieldcrews,generalpersonnel,substaFonpersonnel,andothersystemoperatorswithintheirownuFlityandwithneighboringuFliFes.
InterchangeOperator-monitoringinterchangeacFviFesbetweendifferentbalancingareas.BalancingOperator-adequatepowergeneraFonforexpectedpowerdemandTransmissionOperator-transmissionswitching,monitoringsystemlineloadingandvoltagecondiFons.ReliabilityCoordinator-stabilityandreliabilityofmulFpleareas,coordinaFngtaskswithmulFpleenFFes,andmaintainreliabilityoversuchareas.MarketOperators-separatedfromthereliability-oriented.Purchaseorsellcurrentandfutureenergyassetstomaximizeprofits.UnderstandNERCStandardsandconstraintsRenewableOperator
![Page 15: Smart Grid Control Primer - CREDC · switch status) o RTU, PDC ... or external factors. Momentarily • No formal metrics outage ignored. • SAIDI, SAIFI, MAIFI, etc ... - PowerWorld](https://reader033.fdocuments.in/reader033/viewer/2022050717/5ebba690cd8cb43a486d38a9/html5/thumbnails/15.jpg)
cred-c.org|15
Operator Tasks
• Reacttoalarms,i.e.invesFgatethecauseandvalidityofthealarmsandprovidecorrecFveacFons.
• ControlthestaFonandtransmissionsystemvoltagesandensurethevoltageiswithinthescheduleandspecificaFon.
• FacilitatesallscheduledprevenFvemaintenance.• Reacttoothernon-forecastedevents,i.e.carcollidingwithanelectricpolethateither
resultedindamagetothepoleandequipmentorthefiredepartment/policedepartmentorthecityrequesFngthatweremovefromservicethecables.
• Coordinatewithgeneratoroperatorswhentheunitsareeithercomingonlineorofflineorwhenthereisaneedtoadjusttheirloads.
• WorkwithengineeringwhenanexisFngequipmentorcableisapproachingitscapabilityorexceededitscapability.
• PrepareconFngencyplansforscheduleoutage,basicallyevaluateallthe“whatifscenarios”andprovidingcorrecFveacFonforeachscenario.
• Reviewimpactofproposedscheduleoutage.
![Page 16: Smart Grid Control Primer - CREDC · switch status) o RTU, PDC ... or external factors. Momentarily • No formal metrics outage ignored. • SAIDI, SAIFI, MAIFI, etc ... - PowerWorld](https://reader033.fdocuments.in/reader033/viewer/2022050717/5ebba690cd8cb43a486d38a9/html5/thumbnails/16.jpg)
cred-c.org|16
Evolving Control: Transactive Control • Transactive energy is a means of using economic signals or incentives to engage all the intelligent devices in the power grid from the consumer to the transmission system to get a more optimal allocation of resources and engage demand in ways we haven’t been able to before.
• Enabled with the communication concepts we get with the smart grid.
![Page 17: Smart Grid Control Primer - CREDC · switch status) o RTU, PDC ... or external factors. Momentarily • No formal metrics outage ignored. • SAIDI, SAIFI, MAIFI, etc ... - PowerWorld](https://reader033.fdocuments.in/reader033/viewer/2022050717/5ebba690cd8cb43a486d38a9/html5/thumbnails/17.jpg)
cred-c.org|17
Transactive Control
• Respond to system operation moving from deterministic to stochastic model by fully engaging all resources at all levels
• Use local conditions and global information • Forecast as a feedback and function as incentive
![Page 18: Smart Grid Control Primer - CREDC · switch status) o RTU, PDC ... or external factors. Momentarily • No formal metrics outage ignored. • SAIDI, SAIFI, MAIFI, etc ... - PowerWorld](https://reader033.fdocuments.in/reader033/viewer/2022050717/5ebba690cd8cb43a486d38a9/html5/thumbnails/18.jpg)
cred-c.org|18
Transactive Control
![Page 19: Smart Grid Control Primer - CREDC · switch status) o RTU, PDC ... or external factors. Momentarily • No formal metrics outage ignored. • SAIDI, SAIFI, MAIFI, etc ... - PowerWorld](https://reader033.fdocuments.in/reader033/viewer/2022050717/5ebba690cd8cb43a486d38a9/html5/thumbnails/19.jpg)
cred-c.org|19
Transactive Control
� Transactive control is distributed way to respond to grid needs � Incentive signal can be from big wind farm, transmission
constraints, demand charges, imported energy � Feedback signal can befrom HVAC thermostat, storage PHEV
![Page 20: Smart Grid Control Primer - CREDC · switch status) o RTU, PDC ... or external factors. Momentarily • No formal metrics outage ignored. • SAIDI, SAIFI, MAIFI, etc ... - PowerWorld](https://reader033.fdocuments.in/reader033/viewer/2022050717/5ebba690cd8cb43a486d38a9/html5/thumbnails/20.jpg)
cred-c.org|20
Differences Between Reliability and Resiliency
Resiliency
• Measured in anticipation of some form of threat
• Assessed in extreme disturbance
Reliability
• Measure of operational consistency and performance in meeting connected customers load
• Priority of critical loads is considered
• No classification of load is reflected in measurement of reliability • Resiliency is an indication of
preparedness of a network to withstand or avert damage coming from outside the power system [like weather]
• Reliability accounts for sustainable power lost due to normal operational or equipment damages or external factors. Momentarily outage ignored. • No formal metrics
• SAIDI, SAIFI, MAIFI, etc
Resilient Control
![Page 21: Smart Grid Control Primer - CREDC · switch status) o RTU, PDC ... or external factors. Momentarily • No formal metrics outage ignored. • SAIDI, SAIFI, MAIFI, etc ... - PowerWorld](https://reader033.fdocuments.in/reader033/viewer/2022050717/5ebba690cd8cb43a486d38a9/html5/thumbnails/21.jpg)
cred-c.org|21
WeatherImpact- PowerWorldPowerSystemAnalysis- PowerWorld,PSLF
DynamicAnalysisTool- PSS/EControlSystemModeling- Hypersim
ProtecFonModelingTool- CAPE
CyberModelingTool- NS-3,DeterLabConFngencyModelingToolInterfacing
Designing Resilient Control
![Page 22: Smart Grid Control Primer - CREDC · switch status) o RTU, PDC ... or external factors. Momentarily • No formal metrics outage ignored. • SAIDI, SAIFI, MAIFI, etc ... - PowerWorld](https://reader033.fdocuments.in/reader033/viewer/2022050717/5ebba690cd8cb43a486d38a9/html5/thumbnails/22.jpg)
cred-c.org|22IEEESmartGridControlVision2030
![Page 23: Smart Grid Control Primer - CREDC · switch status) o RTU, PDC ... or external factors. Momentarily • No formal metrics outage ignored. • SAIDI, SAIFI, MAIFI, etc ... - PowerWorld](https://reader033.fdocuments.in/reader033/viewer/2022050717/5ebba690cd8cb43a486d38a9/html5/thumbnails/23.jpg)
cred-c.org|23
Future EMS and Control
Energy Management System
• Renewables...forecasFng&variabilitymanagement:StochasFcControl
• DemandResponse&EMSintegraFon• IntegraFonofEMSwithDMS• Growthofphasoranalysis&VisualizaFon• IntegraFngIEDdatamoreintelligently• UFlizingfastercommunicaFon• SynchronousFmeotherthanPMU• ResiliencyMetricandValueinControl• DecentralizedandCoordinated• FaultTolerant• Cyber–resilient,delayaware