Company Name Auditor Date Of Audit Trinity College Dublin Premises 29 September 2008 Bronagh Page SMART Access Assessment House 17/18/19 Botany Bay - Zone 2 Works and adjustments further considered for inclusion in longer term development planning or refurbishments. Adjustments to be incorporated into an existing maintenance or development works programmes in the medium term to long term. Adjustments required as a high priority to remove or avoid barriers to access for disabled people. Priority 3 Priority 2 Priority 1

Transcript of SMART Access Assessment - Trinity College, Dublin audits pdfs for each... · 7/65 SMART Access...

Page 1: SMART Access Assessment - Trinity College, Dublin audits pdfs for each... · 7/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2 The ease with which mobility impaired

Company Name

AuditorDate Of Audit

Trinity College DublinPremises

29 September 2008Bronagh Page

SMART Access Assessment

House 17/18/19 Botany Bay - Zone 2

Works and adjustments further considered for inclusion in longer term development planning or refurbishments.

Adjustments to be incorporated into an existing maintenance or development works programmes in the medium term to long term.

Adjustments required as a high priority to remove or avoid barriers to access for disabled people.

Priority 3Priority 2Priority 1

Page 2: SMART Access Assessment - Trinity College, Dublin audits pdfs for each... · 7/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2 The ease with which mobility impaired

ForewordThis access audit identifies a range of barriers that potentially restrict access for disabled people in the external and internal built environments.

For the purposes of the access assessment the environment’s features have been broken down into its constituent features. Each feature is assessed for conformity against certain access criteria. These criteria are derived from the following range of Best Practice sources, guidelines, standards, publications and legislation:

•Disability Act 2005 and related Sectoral Plans - Ref 1•Standards Institute BS8300:2001 and BS5588 - Ref 2•Regulations 2000, Technical Guidance Document M - Access for People with Disabilities

(Department of the Environment, Heritage and Local Government) - Ref 3•for Everyone - Access and use for all citizens (National Disability Authority) - Ref 4•to the Historic Environment - Meeting the needs of Disabled People (Lisa Foster) - Ref 5•Management Guidelines (Irish Government Publications 2003) - Ref 6•Auditing of the Built Environment guidelines (National Disability Authority) - Ref 7•Mobility - A Guide to Best Practice on Access to Pedestrian and Transport Infrastructure

(Department of Transport United Kingdom) - Ref 8•on the use of Tactile Paving Surfaces: UK Department for Transport - Ref 9

Where a site feature does not conform to this guidance, an explanation as to the potential restriction on access is provided, together with a suggested action and the priority in which such actions should be undertaken.

The Disability Act 2005 and the National Disability Authority’s initiatives build on relationships and practices which currently exist among councils, city planners, building professionals and community groups to make services in Ireland more accessible to people with disabilities.

In addition to people who use wheelchairs or have restricted mobility, there are many people affected by some degree of hearing loss, learning disability, facial disfigurement, visual impairment, mental illness or conditions such as arthritis or incontinence. This access assessment considers the needs of all potential users from a universal access perspective.

The audit is an organisation’s first step in identifying physical barriers that people with disabilities may encounter when engaging with the community, public services and facilities.

It is equally important to implement effective staff equality training and to implement good inclusive management strategies that ensure equal access for all.

Page 3: SMART Access Assessment - Trinity College, Dublin audits pdfs for each... · 7/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2 The ease with which mobility impaired

Configure Limited provides consultancy, project management and equipment to help make buildings accessible for all.

For further information contact us on 01 708 9198 or e-mail [email protected]

Configure Limited, First Floor, 32 Upper Kevin Street, Dublin 8www.configure.ie

Page 4: SMART Access Assessment - Trinity College, Dublin audits pdfs for each... · 7/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2 The ease with which mobility impaired

Introduction and General Information

This Audit Report is one of a series of measures that Trinity College Dublin is taking as part of its development program to identify, remove and prevent barriers to people with disabilities.

BackgroundTrinity College Dublin has engaged Configure Ltd to conduct Access Audits for the various campus buildings and facilities at the College. This Access Assessment identifies a range of barriers that potentially restrict access for people with disabilities in Trinity College. An Access Plan is included at the end of the assessment, bringing together issues of a similar priority and providing an indication as to the likely cost estimates of adjustments. The Assessment highlights issues in the physical environment. A scope of works of the physical environment is included. Responsibilities including the Equal Status Acts and the Disability Act 2005 are crucial to the vision of a College that improves accessibility and mobility for its students and staff. Through this Access Audit and Access Plan Trinity College may look to the future of the institution with a commitment to creating an accessible environment for all.

Accessibility initiatives already exist in Trinity College:- Trinity College has committed to a Code of Practice applying to the Employment of People with Disabilities.- Trinity College has an established policy of equal opportunity in education. - Trinity College has adopted a Universal Design Policy in recognition of the principles of Universal Access.

Configure provides advice, equipment and staff training to assist service providers in removing barriers which turn impairment into disability. We work with service providers from all sectors and are happy to offer advice and guidance on any access issue.

Building Rating for Disabled Access. This rating system serves as a summary designation for College's internal building management and planning

Rating ExplanationA Fully compliant with BS8300:2001 and other best practice guidelinesB Partially compliant, some changes required. Ground floor accessibleC Partially compliant, some changes required. Ground floor inaccessibleD Partially compliant, changes required include structural civil worksE Not compliant, major civil works required

Page 5: SMART Access Assessment - Trinity College, Dublin audits pdfs for each... · 7/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2 The ease with which mobility impaired

House 17/18/19 - Zone 2Botany BayTrinity College Dublin.

Building TypeThese buildings are rated C

Building DescriptionThe building comprises 4 storeys above ground, referred to as Ground, First, Second and Third Floor.Currently the buildings are inaccessible on the ground floor, due to steps at the main front entrance of the buildings. The upper floors are served by a main central staircase and are therefore inaccessible to wheelchair users also. The buildings comprise of two bed apartments which include a kitchen facility and Bathroom.

Uses of the BuildingThe buildings are occupied by: 1. Residents only

Building Opening Times:Monday to Fridays: 24 hours (key access only) Saturday and Sundays: 24 hours (key access only)

Facilities offered are: Apartments which consist of:BedroomsKitchenBathroomLiving room

Page 6: SMART Access Assessment - Trinity College, Dublin audits pdfs for each... · 7/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2 The ease with which mobility impaired

6/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2

Given that you do not provide general parking facilities for employees, students or visitors, you are not obliged to provide accessible parking. Ensure that your staff members know about local parking arrangements.

1.1

Accessible Parking Provision1.0

Page 7: SMART Access Assessment - Trinity College, Dublin audits pdfs for each... · 7/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2 The ease with which mobility impaired

7/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2

The ease with which mobility impaired people can approach the premises has an impact on their ability to access the services provided within the premises. Accordingly, the condition and layout of the access route to the premises is considered below. It is understood that you are responsible for the upkeep and maintenance of the access route to the premises.

2.1

Access Routes to the Premises2.0

PriorityActionAccess CommentConformsFeatureNo Action Required.YesIs the access route from the car

park to the entrance to the premises a minimum of 1200mm wide?

2.2

No Action Required.YesIs the access route surface free from holes or cavities more than 18 mm deep?

2.3

No Action Required.YesIs the difference in level between adjacent paving slabs or access covers less than 5 mm?

2.4

No Action Required.YesAre surface joints or cracks in the pavement no wider than 10mm and no deeper than 5mm?

2.5

No Action Required.YesAre slots in drain gratings no more than 13mm wide and set at right angles to the line of pedestrian movement?

2.6

No Action Required.YesIs the access route clear of abrupt changes in level with cross falls or cambers being less than 1:50?

2.7

Page 8: SMART Access Assessment - Trinity College, Dublin audits pdfs for each... · 7/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2 The ease with which mobility impaired

8/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2

PriorityActionAccess CommentConformsFeatureRemove or relocate moveable items to a position outside the main pedestrian thoroughfare. Highlight fixed security items such as bollards using high contrast marking.

As far as possible, items of street furniture should be located outside the boundaries of the main pedestrian thoroughfare. Items to enhance security or limit access such as bollards should be easy to distinguish from the background. Chain link and low height fencing at the side of a footpath can be a dangerous trip hazard for sight impaired pedestrians and preferable should be replaced with a suitable balustrade or railing at least 900mm high. Any moveable items such as A-frame signboards or litter bins should be placed outside the main pedestrian route.

The following trip and collision hazards were identified on the access route:

• Low height bollards (lower than 800mm)Bicycles

NoIs the access route free from any trip or collision hazards for visually impaired or blind pedestrians?

2.8

No Action Required.YesIs the route free from windows and doors that could open out into the path of sight impaired pedestrians?

2.9

No Action Required.YesIs the access route clear of obstacles mounted more than 300mm above the floor and jutting out into the access route by more than 100mm?

2.10

Page 9: SMART Access Assessment - Trinity College, Dublin audits pdfs for each... · 7/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2 The ease with which mobility impaired

9/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2

View of the access route from the building entrance

In general the access route has a good surface finish.

Bicycles parked along the access route can become a trip hazard for people with

impaired visibility.

Low height bollards seen here at thend of the step can become a trip hazard for people

with impaired visibility

Page 10: SMART Access Assessment - Trinity College, Dublin audits pdfs for each... · 7/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2 The ease with which mobility impaired

10/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2

The following locations in the access route to the building were identified as having external steps:

1. Main Entrance Steps

3.1

External Steps3.0

PriorityActionAccess CommentConformsFeatureNo Action Required.YesIs the vertical height of each

individual step between 150mm to 170mm (exceptionally 100mm to 180mm)?

3.2

No Action Required.YesIs the flat tread of each step between 250mm to 300mm deep?

3.3

No Action Required.YesDoes the overlap or lip on the front edge of any step protrude less than 25mm?

3.4

No Action Required.YesDo steps have a minimum unobstructed width of 1000mm?

3.5

No Action Required.YesAre the vertical risers of each step solid and not open?

3.6

No Action Required.YesIs the flat tread of each step slip resistant?

3.7

No Action Required.YesDoes each continuous flight of steps between landings contain less than 12 individual steps?

3.8

Page 11: SMART Access Assessment - Trinity College, Dublin audits pdfs for each... · 7/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2 The ease with which mobility impaired

11/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2

PriorityActionAccess CommentConformsFeatureInstall corduroy hazard warning surfaces in the identified location.

Tactile warning surfaces provide an important indication to people with a visual impairment of the location of changes in level associated with steps and stairs.

Main Entrance Steps: The top and bottom landings do not incorporate a corduroy hazard warning surface.

NoDo the top and bottom landings of the flight of steps incorporate a corduroy hazard warning surface?

3.9

Install colour contrasting step nosing in the identified location.

Each step nosing should contrast in colour and luminance with the step tread and riser so that visually impaired people can distinguish the edge of the step whether ascending or descending.

The following steps lack contrasting step nosing:

Main Entrance Steps: 5 steps require contrasting step nosing.

NoAre contrasting step nosings incorporated on the front face as well as the top of each step?

3.10

Improve the lighting in the identified location.

Providing an even level of lighting helps people to negotiate steps without having to walk in their own shadow. The illuminance at tread level should be at least 100 lux.

Main Entrance Steps: There is insufficient or poorly configured lighting over the steps at this location.

NoIs lighting even, sufficiently bright and oriented so as to avoid people negotiating the steps in their own shadow?

3.11

Page 12: SMART Access Assessment - Trinity College, Dublin audits pdfs for each... · 7/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2 The ease with which mobility impaired

12/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2

PriorityActionAccess CommentConformsFeatureProvide dual handrails which conform with BS8300 for the identified external steps locations.

Where feasible, handrails should be provided on both sides of external steps to provide uninterrupted support and directional guidance for people with mobility and/or visual impairments.

It was noted that there is inadequate handrail provision for the steps at the following locations:

Main Entrance Steps: Left hand sideMain Entrance Steps: Right hand side

NoLooking from the bottom of the steps is there a handrail to the left and right hand side?

3.12

No Action RequiredYesIs there a minimum clear width between handrails of 1000mm?

3.13

Main Entrance Steps: House 19 Main Entrance Steps: The top and bottom landings do not incorporate a corduroy

hazard warning surface

Main Entrance Steps: Example of low height bollards at the bottom of the steps at house

17

Page 13: SMART Access Assessment - Trinity College, Dublin audits pdfs for each... · 7/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2 The ease with which mobility impaired

13/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2

Main Entrance Steps: There is inadequate handrail provision for the steps

Page 14: SMART Access Assessment - Trinity College, Dublin audits pdfs for each... · 7/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2 The ease with which mobility impaired

14/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2

The following entrances were identified at the premises:

• Front Entrance Door

4.1

Building Entrances and Entrance Doors4.0

PriorityActionAccess CommentConformsFeatureProvide additional signage to clearly indicate the location of the identified entrance.

Clear signage identifying the location of the entrance from the access route is essential. Colour contrasting signage with a minimum character size of 150mm is recommended. The presence and location of the following entrances are not adequately indicated by appropriate signage:

• Front Entrance Door

NoIs the entrance clearly indicated by appropriate signage?

4.2

Provide additional lighting in the identified location.

Entrances should be well lit to ensure they can be easily identified and approached.

• Front Entrance Door: This entrance does not have adequate lighting.

NoIs an adequate and even level of lighting provided at the entrance?

4.3

No Action Required.YesIs the entrance easy to identify and clearly distinguishable from the rest of the building by provision of colour contrasting doors, frames or ground surfaces?

4.4

Page 15: SMART Access Assessment - Trinity College, Dublin audits pdfs for each... · 7/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2 The ease with which mobility impaired

15/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2

PriorityActionAccess CommentConformsFeatureConsider upgrading doors to power operation or incorporating a low energy pneumatic opener for self closing doors.

Power operated entrance doors, although not essential, are of benefit to a wide range of people. It was observed that the doors at the following entrances are not power operated:

• Front Entrance Door

NoAre the doors at the entrance power operated?

4.5

No Action Required.YesIs the maximum force exerted by the door self-closing device no more than 20 Newtons?

4.6

No Action Required.YesIs the door handle set at a height between 900-1100mm?

4.7

No Action Required.YesIs the door handle D- or U-shaped with a minimum clearance between the handle and door of 45mm?

4.8

No Action Required.YesDoes the door handle contrast in colour and luminance with the door surface?

4.9

No Action Required.YesAre the existing door vision panels correctly configured?

4.10

No Action Required.YesIs an unobstructed passage width of at least 800mm available in the doorway when the door is fully open?

4.11

Page 16: SMART Access Assessment - Trinity College, Dublin audits pdfs for each... · 7/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2 The ease with which mobility impaired

16/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2

PriorityActionAccess CommentConformsFeatureProvide a portable ramp or build a permanent solution

It was observed that there are flight of steps, individual steps or a threshold step with a height exceeding 13mm at the following entrances:

• Front Entrance Door

NoIs level access provided at the entrance such that users are not required to navigate unavoidable flights of steps, individual steps or threshold lips more than 13mm high?

4.12

Provide a portable ramp or built solution to overcome entrance and threshold steps and lips.

In suitable location where the change in level is not too severe, a portable ramp should be made available for wheelchair users.

• Front Entrance Door

NoIs a portable ramp available for deployment to assist wheelchair users overcome steps at the entrance?

4.13

Replace or secure the weather mat.

The surface of the weather mat or matting provided inside and outside the entrance doorway should be level with flush joints between flooring materials. Surface laid mats which are not firmly fixed to the floor along all four edges are a trip hazard for sight and mobility impaired users.

• Front Entrance Door: The weather mat should be secured or replaced because it constitutes a trip hazard.

NoDoes the weather matting at the entrance provide a level and even surface?

4.14

Page 17: SMART Access Assessment - Trinity College, Dublin audits pdfs for each... · 7/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2 The ease with which mobility impaired

17/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2

Front Entrance Door: Houses are not numbered with clear colour contrasting signs

Front Entrance Door: Door entry system is swipe card operated

Front Entrance Door: House number 18

Front Entrance Door: House 18 signage and lighting

Front Entrance Door: Intercom system in use Front Entrance Door: The weather mat should be secured or replaced because it

constitutes a trip hazard.

Page 18: SMART Access Assessment - Trinity College, Dublin audits pdfs for each... · 7/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2 The ease with which mobility impaired

18/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2

Front Entrance Door: Lighting for the entrance to the premises is inadequate

Front Entrance Door: House number signage is not adequate

Page 19: SMART Access Assessment - Trinity College, Dublin audits pdfs for each... · 7/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2 The ease with which mobility impaired

19/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2

The existing signage provision within the premises is examined below.5.1

Signage5.0

PriorityActionAccess CommentConformsFeatureNo Action Required.YesAre external signs clear of

overgrown vegetation?5.2

No Action Required.YesDo suspended and wall mounted signs provide a minimum headroom of at least 2300mm?

5.3

Reposition signage at eye level on the wall next to the latch side of doors.

In order to assist blind and sight impaired people to identify specific room locations, it is recommended that room identification signage should be positioned on the wall next to the door in case the door is left open or is opened when the sign is being read.

NoAre room identification signs located consistently both at eye level (1500mm) and on the wall immediately adjacent to the latch side of the door?

5.4

Where blind or visually impaired people are required to navigate a building independently, it is recommended that Braille and tactile way-finding information is provided

Where blind or visually impaired people are likely to navigate a building independently, it is recommended that Braille and tactile way-finding information should be provided.

NoIs Braille and embossed signage provided in conjunction with standard signage?

5.5

Page 20: SMART Access Assessment - Trinity College, Dublin audits pdfs for each... · 7/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2 The ease with which mobility impaired

20/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2

PriorityActionAccess CommentConformsFeatureImprove internal non-tactile signage.

Glare can be a major cause of discomfort in buildings and can be responsible for disorienting sight impaired visitors and rendering signage unreadable. The most common causes of glare are signboards with a glazed or high gloss finish which reflects natural or artificial lighting and internally illuminated signs. Apply matt finishes to signage and avoid placing suspended signs directly against a light source. Wherever possible, all artificial light sources should be concealed or shaded and the intrusion of sunlight at different times of the day should be forestalled by providing blinds at windows.

NoAre internal signs presented without a glass or reflective surface?

5.6

No Action Required.YesDo signs incorporate clear colour contrast between the lettering and the sign background?

5.7

Page 21: SMART Access Assessment - Trinity College, Dublin audits pdfs for each... · 7/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2 The ease with which mobility impaired

21/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2

Bathroom door signage Door signage is highly reflective Reposition signage at eye level on the wall next to the latch side of doors.

Page 22: SMART Access Assessment - Trinity College, Dublin audits pdfs for each... · 7/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2 The ease with which mobility impaired

22/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2

The following corridors were observed at the premises:

• Main Entrance Lobby• Dorm Entrance Corridor Generic• Living Room Generic• Bedroom Generic• Dorm Bedoom Corridor

6.1

Corridors6.0

PriorityActionAccess CommentConformsFeatureNo Action Required.YesDoes the corridor have an

unobstructed circulation width of 1200mm?(A reduction in width to 1000mm around a permanent obstruction is permissable for a short distance only)

6.2

Carry out building adjustments to improve circulation in the identified corridor locations.

It was observed that there is insufficient space for wheelchair users to manoeuvre within the following corridor locations:

• Dorm Entrance Corridor Generic• Bedroom Generic• Dorm Bedoom Corridor

NoIs there a clear radius of at least 1800mm in which to circulate (i.e. the turning circle) at the junctions of the corridor with other corridors?

6.3

Page 23: SMART Access Assessment - Trinity College, Dublin audits pdfs for each... · 7/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2 The ease with which mobility impaired

23/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2

PriorityActionAccess CommentConformsFeatureRelocate any obstructions and ensure that staff members are aware of the need to keep the corridors unobstructed.

Moveable or temporary obstructions such as promotional stands or racking are not always considered when thinking about access issues. If such items reduce the corridor width to less than 1200mm it can restrict people's ability to pass through the internal access routes and is a potential hazard for blind and sight impaired people.

The corridors in the following locations are not kept free of obstructions:• Main Entrance Lobby

NoIs the corridor kept free from obstructions?

6.4

Living Room Generic: Good circulation space

Dorm Bedoom Corridor: Carry out building adjustments to improve circulation in the

identified corridor locations.

Bedroom Generic: There is insufficient space for wheelchair users to manoeuvre

Page 24: SMART Access Assessment - Trinity College, Dublin audits pdfs for each... · 7/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2 The ease with which mobility impaired

24/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2

Bedroom Generic: Consider relocating furniture to allow for a wider access route

Main Entrance Lobby: Circulation space is adequate

Main Entrance Lobby: House 17 - The lobby is obstructed with furniture

Page 25: SMART Access Assessment - Trinity College, Dublin audits pdfs for each... · 7/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2 The ease with which mobility impaired

25/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2

Both the condition of internal surfaces and the materials from which they are constructed can have an impact on the ease with which people can navigate around the building. The internal surfaces of the premises are considered below.

7.1

Internal Surfaces7.0

PriorityActionAccess CommentConformsFeatureReplace the identified flooring with a more slip-resistant surface when next refurbishing. In the interim, provide hazard signs whenever the flooring is wet and ensure cleaning and maintenance operations are appropriate.

Internal flooring which is not slip-resistant can be a hazard to users during wet weather, after cleaning operations and in cases of accidental fluid spillage or other contamination. It is recommended that flooring materials with high slip potential characteristics should be replaced when next refurbishing. Hazard signs should be erected whenever the floor is wet and members of staff should be trained to deal promptly with any occurrence which compromises the safety of floor surfaces on internal access routes.

The floor surfaces in the following locations were identified as lacking in slip-resistance when wet:

Living Room

NoIs the flooring throughout the building slip-resistant even when wet?

7.2

No Action Required.YesAre access routes within the building clear of highly reflective finishes or glass walls and partitions?

7.3

No Action RequiredYesWhere fitted, do carpets give a firm surface to allow wheelchair passage without sinking in?

7.4

Page 26: SMART Access Assessment - Trinity College, Dublin audits pdfs for each... · 7/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2 The ease with which mobility impaired

26/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2

PriorityActionAccess CommentConformsFeatureNo Action Required.YesAre there flush joints between

different types, textures and/or colours of flooring?

7.5

Laminate flooring can be slippy when wet. Joints between surfaces are good

Page 27: SMART Access Assessment - Trinity College, Dublin audits pdfs for each... · 7/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2 The ease with which mobility impaired

27/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2

The following internal doors or generic door types have been identified within the premises:

1. Dorm Entrance Door Generic2. Living Room Door Generic3. Bedroom Door Generic4. WC Door Generic5. Internal Dorm Entrance Door Generic

8.1

Internal Doors8.0

PriorityActionAccess CommentConformsFeatureNo Action Required.YesIs the minimum unobstructed

width of the door opening at least 750mm?

8.2

If a minimum of 300mm unobstructed area cannot be created at the side of the leading edge of the door, it is recommended that an automatic door opener should be provided.

Where a door is located in a corner position or there is a wall or other obstruction at the side of the leading edge, wheelchair users are unable to reach the door handle to manipulate the door. It may be possible to rehang the door and present the door handle on the opposite side. If 300mm clear space cannot be created and the door is likely to be used frequently by wheelchair users, you should consider installing power operation in conjunction with proximity sensors.

• Internal Dorm Entrance Door Generic

NoIs at least 300mm of unobstructed space available at the side of the leading edge of the door for wheelchair users to manoeuvre and operate the door handle?

8.3

Page 28: SMART Access Assessment - Trinity College, Dublin audits pdfs for each... · 7/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2 The ease with which mobility impaired

28/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2

PriorityActionAccess CommentConformsFeatureReplace doors or install correctly positioned visibility panels within the existing doors at the identified locations.

To enable people to see and be seen through internal doors in constant use, a glazed vision panel between 500mm and 1500mm from the floor, or two panels, one from 500mm to 800mm and a second 1150mm to 1500mm from the floor should be provided.

The following internal doors either lack visibility panels or the existing panels do not conform with the recommended configuration:• Internal Dorm Entrance Door Generic• Dorm Entrance Door Generic

NoAre clear visibility panels incorporated in doors which are in constant use?

8.4

No Action Required.YesIs the door handle located between 900mm and 1100mm from the floor and 50mm in from the leading edge of the door?

8.5

No Action Required.YesIs the door handle U shaped with a gap in excess of 45mm between the grip area of the handle and the door panel to which it is attached and does it contrast in colour to the door panel?

8.6

No Action Required.YesIs the maximum closing force of the leading edge of the door less than 20 Newtons? (A simple test is whether the door can be opened or closed using only one little finger)

8.7

Page 29: SMART Access Assessment - Trinity College, Dublin audits pdfs for each... · 7/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2 The ease with which mobility impaired

29/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2

PriorityActionAccess CommentConformsFeatureNo Action Required.YesIs the door entry security system

positioned with its uppermost point between 750mm and 1050mm?

8.8

No Action Required.YesCan the operating device for the door security entry system be operated without the user requiring good manual dexterity, the use of two hands or the strength to hold down pressure on the keys?

8.9

Living Room Door Generic: Incorporates wired glass vision panel

WC Door Generic: View from corridor Bedroom Door Generic: Good door width and incorporates self closing device

Page 30: SMART Access Assessment - Trinity College, Dublin audits pdfs for each... · 7/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2 The ease with which mobility impaired

30/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2

Dorm Entrance Door Generic: Contrasts visually with its surroundings

Internal Dorm Entrance Door Generic: Vision panels should be incorporated on doors in

constant use.

Page 31: SMART Access Assessment - Trinity College, Dublin audits pdfs for each... · 7/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2 The ease with which mobility impaired

31/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2

The following locations were identified as having steps:

1. Main Central Staircase

9.1

Internal Steps9.0

PriorityActionAccess CommentConformsFeatureNo Action Required.YesIs the vertical height of each

individual step between 150mm to 170mm (exceptionally 100mm to 180mm)?

9.2

No Action Required.YesIs the flat tread of each step between 250mm to 300mm deep?

9.3

No Action Required.YesDoes the overlap or lip on the front edge of any step protrude less than 25mm?

9.4

No Action Required.YesDo steps have a minimum unobstructed width of 1000mm?

9.5

No Action Required.YesAre the vertical risers of each step solid and not open?

9.6

No Action Required.YesIs the flat tread of each step slip resistant?

9.7

No Action Required.YesDoes each continuous flight of steps between landings contain less than 16 individual steps?

9.8

Page 32: SMART Access Assessment - Trinity College, Dublin audits pdfs for each... · 7/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2 The ease with which mobility impaired

32/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2

PriorityActionAccess CommentConformsFeatureInstall corduroy hazard warning surfaces in the identified location.

Tactile warning surfaces provide an important indication to people with a visual impairment of the location of changes in level associated with steps and stairs.

Main Central Staircase: The top and bottom landings for this staircase do not incorporate a corduroy hazard warning surface.

NoDo the top and bottom landings of the flight of steps incorporate a corduroy hazard warning surface?

9.9

Install colour contrasting nosings for the steps in the identified location.

Ensuring that step nosings incorporate clear colour contrast provides significantly improved access for visually impaired people.

Main Central Staircase: 60 steps require contrasting nosing

NoAre contrasting step nosings incorporated on the front face as well as the top of each step?

9.10

No Action Required.YesIs lighting over the steps sufficiently bright and oriented so that people do not have to walk in their own shadow?

9.11

Provide dual handrails for the identified stairway location.

Where feasible, handrails should be provided on both sides of internal steps and staircases to provide uninterrupted support and directional guidance for people with mobility and/or visual impairments.

It was noted that there is inadequate handrail provision for the steps at the following locations:

Main Central Staircase: Left hand side

NoLooking from the bottom of the steps is there a handrail to the left and right hand side?

9.12

Page 33: SMART Access Assessment - Trinity College, Dublin audits pdfs for each... · 7/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2 The ease with which mobility impaired

33/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2

PriorityActionAccess CommentConformsFeatureNo Action Required.YesIs the handrail provided between

900mm and 1000mm above the surface of the steps?

9.13

No Action Required.YesIs the height of the handrail above the steps consistent throughout its entire length?

9.14

No Action Required.YesIs the handrail sufficiently well secured to provide adequate support?

9.15

No Action Required.YesDo the handrail support brackets provide continuous hand contact with the rail and/or is the rail clear of other obstructions?

9.16

No Action Required.YesIs the handrail continuous, leaving no gaps at any point and extending across landings?

9.17

Replace or extend handrail in the identified location.

Some people with a visual impairment use handrails to assist in locating the top and bottom of the steps. Other people require a handrail to steady themselves before negotiating the change in level. Ensuring that handrails extend beyond the top and bottom of the steps and that the end of the handrail can be easily determined enhances these functions.

Main Central Staircase: The right handrail does not extend at least 300mm beyond the top and/or bottom of the steps and/or it does not return to the wall or the floor.

NoDoes the handrail extend at least 300mm beyond the top and bottom of the steps and return the end of the handrail to the wall or the floor?

9.18

Page 34: SMART Access Assessment - Trinity College, Dublin audits pdfs for each... · 7/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2 The ease with which mobility impaired

34/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2

PriorityActionAccess CommentConformsFeatureInstall tactile warning marks in the identified location.

Tactile warning marks at the top and bottom of a handrail assist people with a visual impairment to identify the approaching change in gradient.

Main Central Staircase: The right handrail does not incorporate tactile warning marks.

NoDoes the handrail contain tactile warning marks to indicate the top and bottom of the steps?

9.19

No Action Required.YesIs the handrail easy to grip and not cold to the touch?

9.20

Replace the handrail in the identified location.

Handrails with the correct diameter will be accessible to the broadest number of people.

Main Central Staircase: The right handrail is not of the recommended diameter.

NoIs the handrail between 45mm to 50mm in diameter?

9.21

Improve the colour contrasts in the identified location.

Providing colour contrast between handrails and their surroundings assists visually impaired people to locate and use the handrails.

Main Central Staircase: The right handrail is not contrasting in tone and colour.

NoIs the handrail contrasting in tone and colour to its surroundings?

9.22

No Action Required.YesIs the maximum intrusion of the handrail into the stairway less than 100mm with a clearance of 50-60mm provided between the rail and any adjacent wall surface?

9.23

Page 35: SMART Access Assessment - Trinity College, Dublin audits pdfs for each... · 7/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2 The ease with which mobility impaired

35/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2

Main Central Staircase: View from entrance lobby

Main Central Staircase: 60 steps require colour contrasting nosing

Main Central Staircase: Handrails should be extended across landings

Main Central Staircase: The right handrail is not contrasting in tone and colour

Main Central Staircase: Newl posts interrupt the continuity of handrails.

Main Central Staircase: There is inadequate handrail provision for the steps at the left

hand side

Page 36: SMART Access Assessment - Trinity College, Dublin audits pdfs for each... · 7/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2 The ease with which mobility impaired

36/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2

Main Central Staircase: Balustrades are of recommended configuration

Page 37: SMART Access Assessment - Trinity College, Dublin audits pdfs for each... · 7/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2 The ease with which mobility impaired

37/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2

Where shared refreshment facilities are not provided for use by members of the general public, there is no general or anticipatory duty to make provision for disabled people, although it is recommended that specific adjustments to improve access for known disabled individuals and members of staff should be considered on their merits. The following shared refreshment facilities were identified:

• Kitchen Generic

10.1

Shared Refreshment Facilities10.0

PriorityActionAccess CommentConformsFeatureNo Action Required.YesIs there at least 1500×1500mm

of manoeuvring space available to enable wheelchair users and ambulant disabled users to gain access to work surfaces, storage facilities and seating areas?

10.2

No Action Required.YesIs there effective colour and luminance contrast between the walls, ceiling and floor to assist easy orientation by visually impaired users?

10.3

No Action Required.YesIs there good visual contrast between the background surfaces and the cupboard and storage units, work surfaces and items of equipment provided?

10.4

No Action RequiredYesDoes the level of illumination from natural and artificial sources provide an environment free from glare, reflections and shadows?

10.5

Page 38: SMART Access Assessment - Trinity College, Dublin audits pdfs for each... · 7/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2 The ease with which mobility impaired

38/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2

PriorityActionAccess CommentConformsFeatureNo Action Required.YesIs the floor surface slip resistant

even when wet?10.6

No Action RequiredYesAre work surfaces continous with smooth transitions so that users can slide rather than carry objects between key task areas?

10.7

No Action Required.YesIs the sink bowl no more than 150mm deep?

10.8

Provide a lever operated sink waste mechanism.

People with limited reach or dexterity are unable to conveniently operate traditional plug and chain devices to empty the sink of waste water.

• Kitchen Generic

NoIs the sink provided with a lever operated pop-up waste mechanism to empty waste water from the sink?

10.9

Provide automatic or lever operated water taps.

People with limited dexterity are unable to operate standard water taps which require users to grip and turn their wrist.

• Kitchen Generic

NoAre the existing water taps operated by lever action or automatic control?

10.10

Provide a swivel neck mixer tap at the side of the sink unit if wheelchair users regularly use the facility.

Wheelchair users and people with limited reach are unable to operate water taps located at the rear of the sink and will need to swivel the tap to fill kettles on the adjacent work surface.

• Kitchen Generic

NoIs there a swivel neck mixer tap fitted at the side of the sink bowl to be within easy reach of wheelchair users?

10.11

Page 39: SMART Access Assessment - Trinity College, Dublin audits pdfs for each... · 7/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2 The ease with which mobility impaired

39/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2

PriorityActionAccess CommentConformsFeatureProvide thermostatically controlled water

Particular care is needed for people who are insensitive to temperature. It is recommended that water heaters which do not incorporate thermostatic control or which do not provide a logical and clear indication of water temperature should be replaced.

• Kitchen Generic

NoIs a means provided for water temperature at the outlet to be limited below 41°C?

10.12

Install clear signage to notify users of the potential scalding hazard

A clearly displayed notice should be provided to warn users that water temperature at the outlet can exceed 41°C and lead to scalding.

• Kitchen Generic

NoAs the water temperature is not thermostatically controlled, is a notice clearly displayed to warn users of the danger of scalding?

10.13

No Action RequiredYesIs a cordless kettle provided for heating water for hot drinks?

10.14

No Action Required.YesAre cupboards and drawers provided with U-shaped handles which are easy to distinguish visually?

10.15

No Action Required.YesAre some cupboard and shelving storage areas available at a height appropriate for both wheelchair and ambulant users?

10.16

No Action Required.YesIs at least one shelf in any refrigerator or freezer provided at a height between 600-1200mm?

10.17

Page 40: SMART Access Assessment - Trinity College, Dublin audits pdfs for each... · 7/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2 The ease with which mobility impaired

40/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2

PriorityActionAccess CommentConformsFeatureNo Action RequiredYesIs the microwave oven mounted

so that the base of the oven is no higher than 850mm from the floor?

10.18

Relocate the microwave oven so that the controls can be seen and operated by wheelchair users.

The markings for the controls for a microwave oven should be clear and easy to understand. If the oven is to be used by wheelchair users, the display panels and controls should be located no higher than 1150mm from the floor.

• Kitchen Generic

NoAre the microwave oven controls positioned no higher than 1150mm from the floor?

10.19

Relocate the power sockets to a more accessible position.

Relocate any electrical controls to a location which is generally accessible.

• Kitchen Generic

NoAre any electrical power sockets or isolator switches that an independent user is required to operate located at a height between 900-1200mm and accessible without requiring users to stretch over a work surface or possess good manual dexterity?

10.20

Provide easy to read operating instructions.

It is recommended that equipment procured for a shared facility should be chosen on the basis that it is easy to use. Where necessary, accessible user instructions should be provided in an easy to read format.

• Kitchen Generic

NoAre any instructions for the use of items of equipment provided in a large easy-to-read typeface?

10.21

Page 41: SMART Access Assessment - Trinity College, Dublin audits pdfs for each... · 7/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2 The ease with which mobility impaired

41/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2

PriorityActionAccess CommentConformsFeatureRelocate the fire extinguisher to the recommended height in an unobstructed location between the hob and the main door

Where measures to tackle small fires have been provided, it is important that they are located in a position accessible to a wide range of users. The fire extinguisher / blanket in the following locations should be relocated to the recommended height in an unobstructed area.

• Kitchen Generic

NoIs the kitchen fire extinguisher / blanket located in an unobstructed position at a height between 900-1200mm?

10.22

No Action Required.YesHas a means been provided for wheelchair users and people of limited ambulancy to transport their cooked meal or drink to the seating area?

10.23

Provide auxiliiary aids as necessary.

Individual users may require the provision of specific items and auxiliary aids to be able to use the refreshment facilities independently.

• Kitchen Generic

NoAre auxiliary aids such as easy-grip cutlery and utensils and high-contrast glassware available?

10.24

No Action Required.YesIs there a variety of seating types available which is easy to rearrange to suit a range of different users?

10.25

Page 42: SMART Access Assessment - Trinity College, Dublin audits pdfs for each... · 7/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2 The ease with which mobility impaired

42/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2

Kitchen Generic: View from living room Kitchen Generic: People with limited dexterity are unable to operate standard

water taps which require users to grip and turn their wrist.

Kitchen Generic: Relocate the power sockets to a more accessible position.

Page 43: SMART Access Assessment - Trinity College, Dublin audits pdfs for each... · 7/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2 The ease with which mobility impaired

43/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2

Kitchen Generic: Relocate the microwave oven so that the controls can be seen and

operated by wheelchair users.

Kitchen Generic: A means has been provided for wheelchair users and people of limited ambulancy to transport their cooked

meal or drink to the seating area

Page 44: SMART Access Assessment - Trinity College, Dublin audits pdfs for each... · 7/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2 The ease with which mobility impaired

44/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2

Residential accommodation for disabled users was identified in the following locations:11.1

Accessible Bedrooms11.0

PriorityActionAccess CommentConformsFeatureProvide accommodation for mobility impaired

It is recommended that bedroom accommodation for disabled users should be located preferably on the entrance floor or floor level that is served by a lift.

NoIs the accommodation located on the entrance floor or on a floor level served by a lift?

11.2

Make necessary adjustments to remove physical constraints in the access routes from the residential accomodation to any communal facilities.

In order that people with disabilities are able to take full advantage of the communal facilities provided, any existing or proposed provision of bedroom accommodation should be located on an accessible route at least 1200mm wide which incorporates wheelchair accessible thresholds and measures to overcome steps and other obstructions.

NoIs the bedroom accomodation located on an accessible route to the building entrance, fire escape and any communal facilities such as common rooms, kitchen or laundry?

11.3

Provide a door with a minimum effective width of 800mm

The following door is below the recommended width of 800mm:

NoIs the clear opening width of the door not less than 800mm?

11.4

Install an easy to operate lock mechanism.

The door lock for an accessible bedroom should be capable of single handed operation. The entry system should not require a steady hand or a strong twisting motion.

NoIs the door lock mechanism easy to operate for users with restricted manual dexterity?

11.5

Page 45: SMART Access Assessment - Trinity College, Dublin audits pdfs for each... · 7/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2 The ease with which mobility impaired

45/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2

PriorityActionAccess CommentConformsFeatureProvide a bed with firm edges on the outer rim at a height of 450mm

Wheelchair users have specific requirements in order to provide for easy transfer from a wheelchair. A bed with a height of 450mm from the floor which incorporates firm edges on the outer rim is preferred. To permit transfer from either side of the bed, it is recommended that the bed has two alternative positions.

NoDoes the bed provide a firm surface at a height between 450-540mm above the floor?

11.6

Rearrange the bed, furniture and fittings to provide an unobstructed area for wheelchair users to transfer to the bed.

Wheelchair users require a transfer zone at the side of the bed of at least 800mm.

NoIs 800mm of unobstructed transfer space provided on at least one side of the bed?

11.7

Install controls which operate the main room lighting from the bed.

The main room lighting controls cannot be operated from the bed

NoCan the main room lights be operated from the bed?

11.8

Relocate inaccessible controls.

Controls for appliances need to be easy to reach, simple to operate and consistent in design. The preferred height range is between 900-1200mm and switches and controls need to be 500mm from internal corners or other obstructions.

NoAre controls for heating, ventilation, curtains and electrical accessories reachable from a seated position and located between 900-1200mm in height?

11.9

Page 46: SMART Access Assessment - Trinity College, Dublin audits pdfs for each... · 7/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2 The ease with which mobility impaired

46/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2

PriorityActionAccess CommentConformsFeatureMaintain an unobstructed circulation width.

Wheelchair users require at least 800mm of circulation width within the room.

NoIs there an unobstructed route within the bedroom to all principal furniture and fittings of at least 800mm?

11.10

Ensure that desks and tables are accessible to wheelchair users.

Wheelchair users will be unable to access desk and table facilties provided within the room unless a suitable knee recess area is available undeneath the top surface.

NoIs there a desk or table with a suitable knee recess for wheelchair users at least 700mm high and 500mm deep?

11.11

Ensure that storage facilities can easily be accessed by wheelchair users and visually impaired users.

Storage unit handles should contrast visually with the background and should preferable be provided in a U-shape format for ease of operation. Wardrobe and cupboard facilities with a sliding door arrangement are recommended.

NoAre wardrobe and cupboad storage facilities provided with visually contrasting, easy to operate handles?

11.12

Provide en-suite shower and WC facilities

En-suite WC facilities should preferably be provided in conjuction with accessible bedroom accommodation.

NoAre accessible WC and shower facilities provided en-suite or at a nearby location?

11.13

Page 47: SMART Access Assessment - Trinity College, Dublin audits pdfs for each... · 7/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2 The ease with which mobility impaired

47/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2

In addition to any wheelchair accessible WC accommodation, it is recommended that standard single-sex toilet facilities should contain at least one WC cubicle suitable for use by ambulant disabled users. Equipment and fittings within the accommodation should be easy to access and operate. Single sex toilet accomodation was observed at the following locations:

• Bathroom Generic

12.1

Ambulant Disabled Toilets12.0

PriorityActionAccess CommentConformsFeatureCreate a cubicle for ambulant disabled users when next refurbishing.

Where sufficient space is available in WC accommodation, it is recommended that at least one WC cubicle suitable for use by ambulant disabled users should be provided.

• Bathroom Generic

NoDo any of the existing WC cubicles provide support for ambulant disabled users? [Such cubicles will typically contain internal support grabrails and provide a minimum internal cubicle width of 800mm]

12.2

Install easy to operate wash taps in the identified location.

Upgrade the wash taps to lever or automatic operation:

• Bathroom Generic

NoCan the wash basin taps be operated by lever control or automatic operation to assist people with restricted manual dexterity ?

12.3

Provide a means to control water temperature at the outlet.

It is important that water temperature at the tap outlet is thermostatically controlled.

• Bathroom Generic

NoIs there a means to ensure that water temperature at the tap outlet does not exceed 41°C?

12.4

Create an unobstructed manoeuvring area in front of wash basins.

People with restricted mobility require adequate space to manoeuvre in front of wash basins.

• Bathroom Generic

NoIs there an unobstructed manoeuvring space for ambulant disabled users of at least 800mm wide by 1100mm deep at the front of a hand wash basin?

12.5

Page 48: SMART Access Assessment - Trinity College, Dublin audits pdfs for each... · 7/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2 The ease with which mobility impaired

48/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2

PriorityActionAccess CommentConformsFeatureAdjust the configuration of the wash basin mirror.

It was observed that the configuration of the wash basin mirror does not conform with the recommended specification in the following locations:

• Bathroom Generic

NoIs the mirror fixed as closely as possible to the top of the wash basin and does it extend to at least 1600mm above the floor?

12.6

Install dual vertical grabrails for alt least one wash basin.

It is recommended that vertical grab rails should be installed to provide support for ambulant disabled users at one of wash basins.

• Bathroom Generic

NoAre 600mm vertical handrails provided on both sides of at least one wash basin?

12.7

Relocate the identified items to a more accessible position.

The operating height of the following items was observed to be located outside the recommended height range:

Bathroom Generic: Shaver Point

NoAre the operating heights of shaver points, automatic hand dryers, paper towel and soap dispensers set within the range of between 800-1000mm above floor level?

12.8

No Action Required.YesDoes the toilet accomodation generally offer effective colour contrast between the walls, ceiling and floor and are individual items easy to distinguish from their surroundings?

12.9

No Action Required.YesIs the floor surface slip-resistant even when wet?

12.10

Page 49: SMART Access Assessment - Trinity College, Dublin audits pdfs for each... · 7/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2 The ease with which mobility impaired

49/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2

Bathroom Generic: View from Door Bathroom Generic: Install dual vertical grabrails for the wash basin

Bathroom Generic: An unobstructed manoeuvring space for ambulant disabled users of at least 800mm wide by 1100mm

deep is required at the front of a hand wash basin

There were no toilet facilities in the public area observed during the audit. Accordingly, there is no obligation to provide toilet facilities that are accessible to mobility impaired people. If toilet facilities are added to the premises in the future, ensure that they are accessible to mobility impaired people.

13.1

Accessible Toilets13.0

No wheelchair accessible changing facilities were identified within the premises.14.1

Accessible Changing and Showers14.0

Page 50: SMART Access Assessment - Trinity College, Dublin audits pdfs for each... · 7/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2 The ease with which mobility impaired

50/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2

Current legislative documents and standards specify that it it the reponsibility of building managers or service providers to ensure that there are suitable procedures in place to evacuate everyone from a building in the case of a fire or other emergency. The existing fire and evacuation procedures are examined below.

15.1

Fire and Evacuation Procedures15.0

PriorityActionAccess CommentConformsFeatureNo Action Required.YesDo members of staff and

volunteers involved in the evacuation procedures for disabled people receive regular training based on written instructions from a competent person?

15.2

Page 51: SMART Access Assessment - Trinity College, Dublin audits pdfs for each... · 7/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2 The ease with which mobility impaired

51/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2

PriorityActionAccess CommentConformsFeatureProvide a personal escape plan for each building occupant who has an impaired ability to evacuate using the existing generic escape procedures.

While emergency procedures are usually generic, it is necessary to carry out a risk assessment for anyone who may have a problem escaping in an emergency and, as well as permanently disabled people, this may include children, pregnant women and people with a temporary impairment such as a broken leg. A mechanism to identify people at risk is required which normally operates by referral or pre-employment questionnaire. The risk assessment should be undertaken as soon as an impaired ability to evacuate is declared or there are reasonable grounds to suspect an impairment. An interview with the person at risk should establish which escape routes and strategies will be suitable for the individual and whether any special adjustments will be required. The personal emergency egress plan for the individual should be committed to a printed document which should be reviewed at regular intervals.

NoHas each disabled student and member of staff been issued with a personal escape plan?

15.3

No Action Required.YesAre evacuation routes checked regularly for combustible materials, obstacles and locked doors?

15.4

No Action Required.YesAre escape routes and final exit points as accessible to sight and mobility impaired people and wheelchair users as the entry routes?

15.5

Page 52: SMART Access Assessment - Trinity College, Dublin audits pdfs for each... · 7/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2 The ease with which mobility impaired

52/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2

PriorityActionAccess CommentConformsFeatureNo Action Required.YesAre external routes from the fire

escapes to the assembly points free from hazards such as obstructions, unbound or slippery surface materials or poor lighting levels.

15.6

Consider providing an evacuation lift.

Unlike a normal passenger lift, an evacuation lift can continue to operate safely when there is a fire in the building. Providing an evacuation lift can be an expensive option but in high occupancy, multi-storey buildings the introduction of at least one evacuation lift with a protected power supply should be considered.

NoIs an evacuation lift with an independent power supply available to provide vertical escape from any upper or lower floor levels?

15.7

Provide carry chairs or chair sliders for stairwell refuge locations to assist in final evacuation of disabled building occupants.

Apart from refuge areas associated with an evacuation lift, an appropriate evacuation aid should be provided to assist the final removal from the refuge areas to the nearest exit point. Evacuation chairs and stair sliders are now available that can be operated safely by one person.

NoAre carry chairs provided in stairwells and at designated refuge areas where there is no alternative means to evacuate people unable to negotiate stairs?

15.8

Page 53: SMART Access Assessment - Trinity College, Dublin audits pdfs for each... · 7/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2 The ease with which mobility impaired

53/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2

PriorityActionAccess CommentConformsFeatureProvide flashing beacons or vibrating pagers in conjunction with the main audible alarm system.

In some buildings it is necessary to provide the same level of fire warning to a profoundly deaf person as for a person with normal hearing. Buildings which contain residential accommodation should have visual alarms throughout and tactile alarms (a small vibrating unit that goes under a pillow) in rooms of sleep. It can be very costly to retro-fit visual alarms in every area of as building but you should consider providing supplementary visual alarms in locations where a hearing impaired person is likely to be alone when the alarm sounds, for example, a library or an individual study or bedroom. Other situations where this may be relevant are in a sports changing room where people change in individual cubicles or in disabled toilets where a deaf person could be on their own behind a closed door. Providing profoundly deaf individuals with a specialist remote pager system which listens for activation of the main alarm sirens and then sets off a vibrating alert is an option which should be considered for members of staff and recognised individuals who are known to be unable to hear the audible alarm.

NoIs the fire alarm system supplemented by visual indicators or vibrating alert pagers to assist people who are unable to hear the audible alarm?

15.9

No Action Required.YesIs there a logical and consistent system of signage to indicate evacuation routes and fire doors throughout the premises?

15.10

Page 54: SMART Access Assessment - Trinity College, Dublin audits pdfs for each... · 7/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2 The ease with which mobility impaired

54/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2

Fire Extinguisher Break Glass Unit Fire Alarm Panel

Directional Emergency Exit Signs Fire Blanket and Fire Extinguisher Emergency Exit Plan

Page 55: SMART Access Assessment - Trinity College, Dublin audits pdfs for each... · 7/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2 The ease with which mobility impaired

55/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2

Smoke Detectors are fitted Fire Alarm

Page 56: SMART Access Assessment - Trinity College, Dublin audits pdfs for each... · 7/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2 The ease with which mobility impaired

56/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2

PremisesCompany Name

SMART Access Plan

Date Of Audit

Trinity College Dublin

Bronagh PageAuditor29 September 2008House 17/18/19 Botany Bay - Zone 2

Executive Summary

Page 57: SMART Access Assessment - Trinity College, Dublin audits pdfs for each... · 7/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2 The ease with which mobility impaired

57/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2

ForewordThis access audit identifies a range of barriers that potentially restrict access for disabled people in the external and internal built environments.

For the purposes of the access assessment the environment’s features have been broken down into its constituent features. Each feature is assessed for conformity against certain access criteria. These criteria are derived from the following range of Best Practice sources, guidelines, standards, publications and legislation:

•Disability Act 2005 and related Sectoral Plans - Ref 1•Standards Institute BS8300:2001 and BS5588 - Ref 2•Regulations 2000, Technical Guidance Document M - Access for People with Disabilities

(Department of the Environment, Heritage and Local Government) - Ref 3•for Everyone - Access and use for all citizens (National Disability Authority) - Ref 4•to the Historic Environment - Meeting the needs of Disabled People (Lisa Foster) - Ref 5•Management Guidelines (Irish Government Publications 2003) - Ref 6•Auditing of the Built Environment guidelines (National Disability Authority) - Ref 7•Mobility - A Guide to Best Practice on Access to Pedestrian and Transport Infrastructure

(Department of Transport United Kingdom) - Ref 8•on the use of Tactile Paving Surfaces: UK Department for Transport - Ref 9

Where a site feature does not conform to this guidance, an explanation as to the potential restriction on access is provided, together with a suggested action and the priority in which such actions should be undertaken.

The Disability Act 2005 and the National Disability Authority’s initiatives build on relationships and practices which currently exist among councils, city planners, building professionals and community groups to make services in Ireland more accessible to people with disabilities.

In addition to people who use wheelchairs or have restricted mobility, there are many people affected by some degree of hearing loss, learning disability, facial disfigurement, visual impairment, mental illness or conditions such as arthritis or incontinence. This access assessment considers the needs of all potential users from a universal access perspective.

The audit is an organisation’s first step in identifying physical barriers that people with disabilities may encounter when engaging with the community, public services and facilities.

It is equally important to implement effective staff equality training and to implement good inclusive management strategies that ensure equal access for all.

Page 58: SMART Access Assessment - Trinity College, Dublin audits pdfs for each... · 7/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2 The ease with which mobility impaired

58/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2

Configure Limited provides consultancy, project management and equipment to help make buildings accessible for all.

For further information contact us on 01 708 9198 or e-mail [email protected]

Configure Limited, First Floor, 32 Upper Kevin Street, Dublin 8www.configure.ie

Page 59: SMART Access Assessment - Trinity College, Dublin audits pdfs for each... · 7/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2 The ease with which mobility impaired

59/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2

Priority 1 AdjustmentsCostingActionFeature

External Steps3.0from €1900 per rail per flightProvide dual handrails which conform with

BS8300 for the identified external steps locations.

Provide dual handrails3.12

Building Entrances and Entrance Doors4.0from €180 eachProvide additional signage to clearly indicate

the location of the identified entrance.Entrance identification signage inadequate

4.2

€300 per light (estimate)Provide additional lighting in the identified location.

Lighting at the entrance.4.3

From €997Provide a portable ramp or build a permanent solution

Step or high threshold at Entrance4.12

From €997Provide a portable ramp or built solution to overcome entrance and threshold steps and lips.

Portable ramp for entrance steps and lips.

4.13

From €400Replace or secure the weather mat.Weather mat trip hazard4.14

Signage5.0Self help - Include in maintenance Plan.

Reposition signage at eye level on the wall next to the latch side of doors.

Consistently positioned room identification signage.

5.4

from €120 each signWhere blind or visually impaired people are required to navigate a building independently, it is recommended that Braille and tactile way-finding information is provided

Braille and tactile signage.5.5

Page 60: SMART Access Assessment - Trinity College, Dublin audits pdfs for each... · 7/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2 The ease with which mobility impaired

60/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2

CostingActionFeature

Maintenance PlanImprove internal non-tactile signage.Glass or reflective sign surfaces.5.6

Corridors6.0Self HelpRelocate any obstructions and ensure that staff

members are aware of the need to keep the corridors unobstructed.

6.4

Internal Steps9.0from €1900 per rail per flightProvide dual handrails for the identified stairway

location.Provide dual handrails for internal steps9.12

€25 per handrail.Install tactile warning marks in the identified location.

Tactile marks on handrails.9.19

Shared Refreshment Facilities10.0Self help - Include in

maintenance planInstall clear signage to notify users of the potential scalding hazard

Water temperature warning notice10.13

Self HelpProvide easy to read operating instructions.Operating instructions10.21

Self HelpProvide auxiliiary aids as necessary.Auxiliary Aids10.24

Accessible Bedrooms11.0Configure engineers report

requiredEnsure that storage facilities can easily be accessed by wheelchair users and visually impaired users.

Storage facilities and door handles11.12

Fire and Evacuation Procedures15.0Self HelpProvide a personal escape plan for each

building occupant who has an impaired ability to evacuate using the existing generic escape procedures.

Personal Emergency Egress Plan (PEEP)

15.3

Page 61: SMART Access Assessment - Trinity College, Dublin audits pdfs for each... · 7/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2 The ease with which mobility impaired

61/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2

Priority 2 AdjustmentsCostingActionFeature

Access Routes to the Premises2.0Bollards €24 per markerRemove or relocate moveable items to a

position outside the main pedestrian thoroughfare. Highlight fixed security items such as bollards using high contrast marking.

Trip and collision hazards in main thoroughfare

2.8

External Steps3.0from €540 per staircase flight (Dimensions 1.2m

wide x 800 depth)

Install corduroy hazard warning surfaces in the identified location.

Corduroy hazard warning.3.9

€50 per metre fittedInstall colour contrasting step nosing in the identified location.

Colour contrasting step nosing.3.10

€300 per light (estimate)Improve the lighting in the identified location.Lighting over steps3.11

Internal Doors8.0from €400 per door - subject

to site surveyReplace doors or install correctly positioned visibility panels within the existing doors at the identified locations.

8.4

Internal Steps9.0€240 per locationInstall corduroy hazard warning surfaces in the

identified location.Corduroy hazard warning.9.9

from €50 per metreInstall colour contrasting nosings for the steps in the identified location.

Colour contrasting step nosings.9.10

Page 62: SMART Access Assessment - Trinity College, Dublin audits pdfs for each... · 7/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2 The ease with which mobility impaired

62/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2

CostingActionFeature

from €1900 per rail per flightReplace or extend handrail in the identified location.

Handrail extends 300mm beyond the end of the steps.

9.18

Shared Refreshment Facilities10.0Self help - Include in

maintenance planProvide automatic or lever operated water taps.Easy operation water taps10.10

Self HelpRelocate the microwave oven so that the controls can be seen and operated by wheelchair users.

Microwave operating controls10.19

Self help - Include in maintenance plan

Relocate the fire extinguisher to the recommended height in an unobstructed location between the hob and the main door

Siting of kitchen fire extinguisher / blanket

10.22

Accessible Bedrooms11.00Provide accommodation for mobility impairedLocation of accommodation11.2

Configure Engineers report required

Make necessary adjustments to remove physical constraints in the access routes from the residential accomodation to any communal facilities.

Proximity of bedroom to communal facilities

11.3

Configure Engineers report required

Provide a door with a minimum effective width of 800mm

Door opening width11.4

€400 per doorInstall an easy to operate lock mechanism.Door lock easy to operate11.5

Self helpProvide a bed with firm edges on the outer rim at a height of 450mm

Firm bed surface11.6

Self HelpRearrange the bed, furniture and fittings to provide an unobstructed area for wheelchair users to transfer to the bed.

Bed transfer space11.7

Self help - Include in maintenance plan

Install controls which operate the main room lighting from the bed.

Operate lights from bed11.8

Page 63: SMART Access Assessment - Trinity College, Dublin audits pdfs for each... · 7/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2 The ease with which mobility impaired

63/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2

CostingActionFeature

Self help - Include in maintenance plan

Relocate inaccessible controls.Accessible switches and controls11.9

Self helpMaintain an unobstructed circulation width.Circulation space11.10

Configure engineers report required

Ensure that desks and tables are accessible to wheelchair users.

Table/Desk knee recess11.11

Configure engineers report required

Provide en-suite shower and WC facilitiesWC / Shower11.13

Ambulant Disabled Toilets12.0Configure Engineers report

requiredProvide a means to control water temperature at the outlet.

Water temperature above 41°C.12.4

Configure Engineers report required

Create an unobstructed manoeuvring area in front of wash basins.

Wash basin manoeuvring space.12.5

€160 per Handrail unit fitted.Install dual vertical grabrails for alt least one wash basin.

Wash basin grabrails12.7

Self help - Include in maintenance plan

Relocate the identified items to a more accessible position.

Height of equipment12.8

Fire and Evacuation Procedures15.0approx €1200 per chair, inc

trainingor

approx €2000 per chair, inc training

Provide carry chairs or chair sliders for stairwell refuge locations to assist in final evacuation of disabled building occupants.

Carry chairs and life sliders15.8

From €740 per sounderor

From €4000

Provide flashing beacons or vibrating pagers in conjunction with the main audible alarm system.

Supplementary fire alert for hearing impaired people

15.9

Page 64: SMART Access Assessment - Trinity College, Dublin audits pdfs for each... · 7/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2 The ease with which mobility impaired

64/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2

Priority 3 AdjustmentsCostingActionFeature

Building Entrances and Entrance Doors4.0€1,500 per door leaf -

subject to surveyConsider upgrading doors to power operation or incorporating a low energy pneumatic opener for self closing doors.

Power operated doors4.5

Corridors6.0From €8000 - subject to site

surveyCarry out building adjustments to improve circulation in the identified corridor locations.

Corridor manoeuvring space6.3

Internal Surfaces7.0€30m2Replace the identified flooring with a more slip-

resistant surface when next refurbishing. In the interim, provide hazard signs whenever the flooring is wet and ensure cleaning and maintenance operations are appropriate.

Slip-resistance of floor surfaces.7.2

Internal Doors8.0Configure Engineers report

requiredIf a minimum of 300mm unobstructed area cannot be created at the side of the leading edge of the door, it is recommended that an automatic door opener should be provided.

Side clearance of doors8.3

Internal Steps9.0from €1900 per rail per flightReplace the handrail in the identified location.Handrail diameter.9.21

€320 per handrail per flight(estimate)

Improve the colour contrasts in the identified location.

Handrail colour contrasts.9.22

Page 65: SMART Access Assessment - Trinity College, Dublin audits pdfs for each... · 7/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2 The ease with which mobility impaired

65/65 SMART Access Assessment: House 17/18/19 Botany Bay - Zone 2

CostingActionFeature

Shared Refreshment Facilities10.0Self help - Include in

maintenance planProvide a lever operated sink waste mechanism.

Lever waste mechanism10.9

Self help - Include in maintenance plan

Provide a swivel neck mixer tap at the side of the sink unit if wheelchair users regularly use the facility.

Side located swivel neck tap10.11

Configure Engineers reportProvide thermostatically controlled waterWater supply limited below 41°C10.12

Self help - Include in maintenance plan

Relocate the power sockets to a more accessible position.

Power sockets10.20

Ambulant Disabled Toilets12.0Configure Engineers report

requiredCreate a cubicle for ambulant disabled users when next refurbishing.

WC cubicle for ambulant users12.2

Self help - Include in maintenance plan

Install easy to operate wash taps in the identified location.

Wash basin taps12.3

Self help - Include in maintenance plan

Adjust the configuration of the wash basin mirror.

Wash basin mirror12.6

Fire and Evacuation Procedures15.0Configures Engineers report

required Consider providing an evacuation lift.Evacuation Lift15.7