SM-E256S 0611
Automatic Energy-saving Function
Side-by-side installation
Versatile Functions
Global Performance
Network Compatibility
Micro Surge Voltage suppressfunction
Environment-friendly Inverter
Integrated EMC Filter
Safety Stop Function
Improved Trip Avoidance Function
Non-stop operation at IPF
Model Configuration Model Name IndicationCONTENTS
1-23456
7-910
11-121314
15-16
FeaturesStandard SpecificationsDimensionsOperation and ProgrammingOperation / Terminal FunctionsFunction ListProtective FunctionsConnecting DiagramWiring and AccessoriesTorque characteristics/Derating CurvesFor Correct Operation
X200-004 H F E F 2
RoHS compliance for all models.
Integrated EMC filter savescost and space.(European version only)
Single-phase input: EN61800-3 cat.C1Three-phase input : EN61800-3 cat.C2
Shuts down the inverter outputs by hardware, bypassing the CPU,to achieve a reliable safe stop function.EN954-1:1997,category3,EN60204-1:1997category0
Over current and over voltage trip suppression function is incorporated.This function reducesnuisance invertertripping.The X200 deceleratesand stops the motorusing regenerativeenergy from the motoron AC power loss.
The X200 delivers �real-time� energy-savingoperation for your fan andpump applications. Thisfunction insures thatmotor operates atminimum current inresponse to the tor�uere�uired by the load.
Inverters can be installed with no space betweenthem to save space in the panel.
� True analog monitor output (10-bit, 0-10 VDC)� �ow load detection� External thermistor terminal (PTC)� Cooling-fan on/off� Instantaneous power failure recovery� Second motor setting� 3-wire control� Analog input selection� Second acceleration/deceleration setting� �ogging� Auto-carrier fre�uency reduction� Unattended start protection (USP)� Analog input wire-brea� detection
� Conformity to global standards CE, U�, c-U� and c-Tic� approvals
�CE�
ISO 14001EC97�1095
Motor terminal voltage
E=650V, cable=100m
ISO 9001��A-1153
�U�, c-U�� �c-T ic��
Hitachi original PWM control method limits motor terminalvoltage to less than twice the inverter DC bus voltage - lowerthan Hitachi motor maximum insulation voltage (1250V).(During regeneration, the motor terminal voltage may exceed the maximuminsulation voltage(1250V))
A serial RS-485 Modbus/RTU port is standard.
Allows for smooth restart when an IPF(Instantaneous Power Failure) occurs. This isespecially useful in fan and pump applications.
Applicable MotorkW (HP)
1-/3-phase 200V class 3-phase 400V class
0.2(1/4)
0.4(1/2)
0.55(3/4)
0.75(1)
1.1(1.5)
1.5(2)
2.2(3)
3.0(4)
3.7(5)
4.0(5)
5.5(7.5)
7.5(10)
Hitachi variable fre�uencydrives (inverters) in thisbrochure are produced at thefactory registered under theISO 14001 standard forenvironmental manegementsystem and the ISO 9001standard for inverter �ualitymanagement system.
1
6 9
10
11
7
8
2
3
4
5
US version European version Japanese version US version European version Japanese version
Series Name
Applicable Motor
2 : Version
U : US versionE : European versionR : Japanese version
F : With keypad
Power SourceN : 1 or 3-phase 200V classS : 1-phase 200V classL : 3-phase 200V classH : 3-phase 400V class
F : Integrated EMC filter(European version)
Capacity002: 0.2kW(1/4HP)
075: 7.5kW(10HP)
X200-002SFEF2
X200-004SFEF2
X200-005SFEF2
X200-007SFEF2
X200-011SFEF2
X200-015SFEF2
X200-022SFEF2
X200-002LFRF2
X200-004LFRF2
X200-007LFRF2
X200-015LFRF2
X200-022LFRF2
X200-037LFRF2
X200-055LFRF2
X200-075LFRF2
X200-004HFU2
X200-007HFU2
X200-015HFU2
X200-022HFU2
X200-040HFU2
X200-055HFU2
X200-075HFU2
X200-004HFEF2
X200-007HFEF2
X200-015HFEF2
X200-022HFEF2
X200-030HFEF2
X200-040HFEF2
X200-055HFEF2
X200-075HFEF2
X200-004HFRF2
X200-007HFRF2
X200-015HFRF2
X200-022HFRF2
X200-037HFRF2
X200-055HFRF2
X200-075HFRF2
X200-002NFU2
X200-004NFU2
X200-007NFU2
X200-015NFU2
X200-022NFU2
X200-037LFU2
X200-055LFU2
X200-075LFU2
21
102030405060708090
100
00 10 20 30 40 50 60 70 80 90 100
Damper controlDamper control
EnergySavingEnergySaving
InvertercontrolInvertercontrol
76%76%
91%91%
61%61%
22%22%
Flow (%)
* Side-by-side installation has derating for carrier frequencyand output current required
no spacebetween
Req
uire
d po
wer
(%)
Simple, Trip-less and Eco-friendly Compact Inverter!Simple, Trip-less and Eco-friendly Compact Inverter!
Conducted emission data(Example of X200-007SFEF2)
Frequency[Hz]
Leve
l[dB
V]
0102030405060708090
100110120
150k 200k 500k 1M 2M 5M 10M 20M 30M
No filter
1,250V
Integrated EMC filter
OC trip Motorcurrent
Motorrotation
startstart
Mains
Motor current
Motor rotation
Automatic Energy-saving Function
Side-by-side installation
Versatile Functions
Global Performance
Network Compatibility
Micro Surge Voltage suppressfunction
Environment-friendly Inverter
Integrated EMC Filter
Safety Stop Function
Improved Trip Avoidance Function
Non-stop operation at IPF
Model Configuration Model Name IndicationCONTENTS
1-23456
7-910
11-121314
15-16
FeaturesStandard SpecificationsDimensionsOperation and ProgrammingOperation / Terminal FunctionsFunction ListProtective FunctionsConnecting DiagramWiring and AccessoriesTorque characteristics/Derating CurvesFor Correct Operation
X200-004 H F E F 2
RoHS compliance for all models.
Integrated EMC filter savescost and space.(European version only)
Single-phase input: EN61800-3 cat.C1Three-phase input : EN61800-3 cat.C2
Shuts down the inverter outputs by hardware, bypassing the CPU,to achieve a reliable safe stop function.EN954-1:1997,category3,EN60204-1:1997category0
Over current and over voltage trip suppression function is incorporated.This function reducesnuisance invertertripping.The X200 deceleratesand stops the motorusing regenerativeenergy from the motoron AC power loss.
The X200 delivers �real-time� energy-savingoperation for your fan andpump applications. Thisfunction insures thatmotor operates atminimum current inresponse to the tor�uere�uired by the load.
Inverters can be installed with no space betweenthem to save space in the panel.
� True analog monitor output (10-bit, 0-10 VDC)� �ow load detection� External thermistor terminal (PTC)� Cooling-fan on/off� Instantaneous power failure recovery� Second motor setting� 3-wire control� Analog input selection� Second acceleration/deceleration setting� �ogging� Auto-carrier fre�uency reduction� Unattended start protection (USP)� Analog input wire-brea� detection
� Conformity to global standards CE, U�, c-U� and c-Tic� approvals
�CE�
ISO 14001EC97�1095
Motor terminal voltage
E=650V, cable=100m
ISO 9001��A-1153
�U�, c-U�� �c-T ic��
Hitachi original PWM control method limits motor terminalvoltage to less than twice the inverter DC bus voltage - lowerthan Hitachi motor maximum insulation voltage (1250V).(During regeneration, the motor terminal voltage may exceed the maximuminsulation voltage(1250V))
A serial RS-485 Modbus/RTU port is standard.
Allows for smooth restart when an IPF(Instantaneous Power Failure) occurs. This isespecially useful in fan and pump applications.
Applicable MotorkW (HP)
1-/3-phase 200V class 3-phase 400V class
0.2(1/4)
0.4(1/2)
0.55(3/4)
0.75(1)
1.1(1.5)
1.5(2)
2.2(3)
3.0(4)
3.7(5)
4.0(5)
5.5(7.5)
7.5(10)
Hitachi variable fre�uencydrives (inverters) in thisbrochure are produced at thefactory registered under theISO 14001 standard forenvironmental manegementsystem and the ISO 9001standard for inverter �ualitymanagement system.
1
6 9
10
11
7
8
2
3
4
5
US version European version Japanese version US version European version Japanese version
Series Name
Applicable Motor
2 : Version
U : US versionE : European versionR : Japanese version
F : With keypad
Power SourceN : 1 or 3-phase 200V classS : 1-phase 200V classL : 3-phase 200V classH : 3-phase 400V class
F : Integrated EMC filter(European version)
Capacity002: 0.2kW(1/4HP)
075: 7.5kW(10HP)
X200-002SFEF2
X200-004SFEF2
X200-005SFEF2
X200-007SFEF2
X200-011SFEF2
X200-015SFEF2
X200-022SFEF2
X200-002LFRF2
X200-004LFRF2
X200-007LFRF2
X200-015LFRF2
X200-022LFRF2
X200-037LFRF2
X200-055LFRF2
X200-075LFRF2
X200-004HFU2
X200-007HFU2
X200-015HFU2
X200-022HFU2
X200-040HFU2
X200-055HFU2
X200-075HFU2
X200-004HFEF2
X200-007HFEF2
X200-015HFEF2
X200-022HFEF2
X200-030HFEF2
X200-040HFEF2
X200-055HFEF2
X200-075HFEF2
X200-004HFRF2
X200-007HFRF2
X200-015HFRF2
X200-022HFRF2
X200-037HFRF2
X200-055HFRF2
X200-075HFRF2
X200-002NFU2
X200-004NFU2
X200-007NFU2
X200-015NFU2
X200-022NFU2
X200-037LFU2
X200-055LFU2
X200-075LFU2
21
102030405060708090
100
00 10 20 30 40 50 60 70 80 90 100
Damper controlDamper control
EnergySavingEnergySaving
InvertercontrolInvertercontrol
76%76%
91%91%
61%61%
22%22%
Flow (%)
* Side-by-side installation has derating for carrier frequencyand output current required
no spacebetween
Req
uire
d po
wer
(%)
Simple, Trip-less and Eco-friendly Compact Inverter!Simple, Trip-less and Eco-friendly Compact Inverter!
Conducted emission data(Example of X200-007SFEF2)
Frequency[Hz]
Leve
l[dB
V]
0102030405060708090
100110120
150k 200k 500k 1M 2M 5M 10M 20M 30M
No filter
1,250V
Integrated EMC filter
OC trip Motorcurrent
Motorrotation
startstart
Mains
Motor current
Motor rotation
1-/3-phase 200V class
Standard Specifications
3
General Specifications
3-phase 400V class
002SFEF2002NFU2002LFRF2
0.2(1/4)0.50.51.4
004SFEF2004NFU2004LFRF2
0.4(1/2)1.01.02.6
005SFEF2--
0.55(3/4)1.11.23.0
007SFEF2007NFU2007LFRF2
0.75(1)1.51.64.0
011SFEF2--
1.1(1.5)1.92.05.0
015SFEF2015NFU2015LFRF2
1.5 (2)2.82.97.1
022SFEF2022NFU2022LFRF2
2.2(3)3.94.1
10.0
-037LFU2
037LFRF23.7(5)
6.36.6
15.9
-55LFU2
055LFRF25.5(7.5)
9.69.924.0
-075LFU2
075LFRF27.5(10)
12.713.332.0
150% for 60 sec.3-phase (3-wire) 200 to 240V (corresponding to input voltage)
SFEF: 1-phase 200 to 240V+10%, -15%, 50/60Hz ±5% NFU: 1-/3-phase 200 to 240V+10%, -15%, 50/60Hz ±5% LFU/LFRF: 3-phase 200 to 240V+10%, -15%, 50/60Hz ±5%
Self-cooling Force ventilation
0.80.80.8
3.11.8
5.83.4
6.7-
9.05.2
11.2-
16.09.3
22.513.0
-20.0
-30.0
-40.0
-SFEF2-NFU2/LFU2-LFRF2
1.00.90.9
1.5--
1.51.51.1
2.4--
2.42.32.2
2.52.42.4
-2.32.4
-4.24.2
-4.24.2
Rated input voltage (V)
Rated input current (A)
European VersionUS VersionJP Version
Model X200-
Output Ratings
Input Rating
Enclosure *4Cooling method
Applicable motor size, 4-pole kW(HP) *1
Rated capacity
Rated output current (A) *2Overload capacity(output current)Rated output voltage (V)
230V240V
SFEF2NFU2/LFUF2/LFRF2
Weight (kg)
Zero phase Reactor
-SFEF2-NFU2/LFU2/LFRF2-LFRF2
Integrated EMC filter
Model X200-004HFEF2004HFU2
004HFRF20.4(1/2)
1.01.21.5
007HFEF2007HFU2
007HFRF20.75(1)
1.72.02.5
015HFEF2015HFU2
015HFRF21.5 (2)
2.63.13.8
022HFEF2022HFU2
022HFRF22.2(3)
3.84.55.5
030HFEF2--
3(4)5.46.47.8
040HFEF2040HFU2
037HFRF24(5)5.97.18.6
055HFEF2055HFU2
055HFRF25.5(7.5)
9.010.813.0
075HFEF2075HFU2
075HFRF27.5(10)
11.113.316.0
150% for 60 sec.3-phase (3-wire) 380 to 480V (corresponding to input voltage)
3-phase 380 to 480V +10%, -15%, 50/60Hz±5%
IP20Self-cooling Force ventilation
1.51.41.5
2.0 3.3 5.0 7.0 10.0 11.0 16.5 20.0
Output Ratings
Input Rating
Enclosure *4Cooling method
Applicable motor size, 4-pole kW(HP) *1
Rated capacity
Rated output current (A) *2Overload capacity(output current)Rated output voltage (V)
European VersionUS VersionJP Version
2.32.22.3
2.42.32.4
2.42.32.4
2.4-
2.4
2.42.32.4
4.24.24.2
4.24.24.2
Rated input voltage (V)Rated input current (A)
400V480V
-HFEF2-HFU2-HFRF2
Weight (kg)
Zero phase ReactorIntegrated EMC filter
Item General SpecificationsLine-to-line sine wave pulse-width modulation (PWM) control0.5 to 400HzDigital command :±0.01%, Analog command ± 0.4% (25 ± 10˚C)Digital: 0.1Hz, Analog: (max frequency)/1000V/f control,V/f variable (constant torque, reduced torque)0.01 to 3000 sec. (linear, sigmoid), two-stage accel./decel.100%/6Hz2.0 to 12kHzOver-current, over-voltage, under-voltage, overload, overheat, ground fault at power-on, input over-voltage, external trip, EEPROM error, CPU error, USP error, Termister error, Driver error, Safety stop10kohm input impedance, sink/source logic selectableFW(Forward), RV(Reverse), CF1-CF4(Multispeed command), JG(Jogging), DB(External DC braking), SET(Second motor constants setting), 2CH(Second accel./decel.), FRS(Free-run stop), EXT(External trip), USP(Unattended start protection), SFT(Software lock), AT(Analog input selection), RS(Reset), PTC(Thermistor input) *8, STA(3-wire start), STP(3-wire stop), F/R(3-wire fwd./rev.), PID(PID On/Off), PIDC(PID reset), UP/DWN(Remote-controlled accel./decel.) , UDC(Remote-controlled data clearing), OPE(Operator control), ADD(ADD frequency enable), F-TM(force terminal mode), RDY(quick start enable),S-ST(Special-Set 2nd Motor Data),EMR(Safety stop), NO(Not selected)27V DC 50mA max open collector output, 1 terminals 1c output 250V AC/30V DC 2.5A relay (AL0, AL1, AL2 terminals)RUN(run signal), FA1(Frequency arrival type 1 - constant speed), FA2(Frequency arrival type 2 - over-frequency), OL(overload advance notice signal), OD(Output deviation for PID control), AL(alarm signal), DC(Wire brake detect on analog input), FBV(PID Second Stage Output), NDC(ModBus Network Detection Signal), LOG(Logic Output Function), ODC(Option Card Detection Signal), LOC(Low load)0 to 10V DCAnalog Frequency monitor, analog current monitor4-digits 7 segment LEDsParameter setting, output frequency, output current, scaled value of output frequency, trip history, I/O terminal condition, output voltage. Rotation direction, PID Feedback, RON time, Power-on time.Power, Alarm, Run, Prg, Hz and A Potentiometer, RUN, STOP/RESET, UP, DOWN, FUN and STR keysUp and Down keys / Value settings or analog setting via potentiometer on operator keypad0 to 10 V DC, 4 to 20 mARS485 interface (Modbus RTU)Run key / Stop key (change FW/RV by function command)FW Run/Stop (NO contact), RV set by terminal assignment (NC/NO), 3-wire input availableRS485 interface (Modbus RTU)-10 to 50˚C(carrier derating required for aambient temperature higher than 40°C), no freezing-20 to 65˚C20 to 90% RH5.9mm/s2 (0.6G) 10 to 55HzAltitude 1,000 m or less, indoors (no corrosive gasses or dust)AVR (Automatic Voltage Regulation), V/f characteristic selection, accel./decel. curve selection, frequency upper/lower limit, 16 stage multispeed, PID control, frequency jump, external frequency input bias start/end, jogging, cooling fan On/Off, trip history etc.
Remote operator with copy function (WOP), input/output reactors, DC reactors, radio noise filters, braking resistors, braking units, LCR filter, communication cables (ICS-1, 3)
Control
Input terminal
Output signal
Operator
Operation
Environment
Other functions
Coating colorOptions
Control methodOutput frequency range *5Frequency accuracy *6Frequency setting resolutionVoltage/Frequency CharacteristicAcceleration/deceleration timeStarting torque *7Carrier frequency range
Protective functions
Specification
Functions
Intelligent output terminal
Analog output terminal
Display
Status LED Interface
Frequency setting
FW/RV Run
Operating temperatureStorage temperatureHumidityVibrationLocation
Operator keypadExternal signalSerial portOperator KeypadExternal signalSerial port
Function
SpecificationFunctionSpecification
Function
Note 1: The applicable motor refers to Hitachi standard 3-phase motor (4-pole). When using other motors, care must be taken to prevent the rated motor current (50/60 Hz) from exceeding the rated output current of the inverter.
Note 2: The output voltage decreases as the main supply voltage decreases (except when using the AVR function). In any case, the output voltage cannot exceed the input power supply voltage.
Note 3: The braking torque via capacitive feedback is the average deceleration torque at the shortest deceleration (stopping from 50/60 Hz as indicated). It is not continuous regenerative braking torque. The average decel torque varies with motor loss. This value decreases when operating beyond 50 Hz. If a large regenerative torque is required, the optional regenerative braking resistor should be used.
Note 4: The protection method conforms to JEM 1030.Note 5: To operate the motor beyond 50/60 Hz, consult the motor manufacturer
for the maximum allowable rotation speed. Note 6: The output frequency may exceed the maximum frequency setting
(A004 or A204) for automatic stabilization control. Note 7: At the rated voltage when using a Hitachi standard 3-phase, 4pole
motor.Note 8: Only terminal 5 is assignable the PTC (thermistor) function.
Blue
EN61800-3 category C1 filter
IP20
-
EN61800-3 category C2 filter
Built-in
Built-in
--HFEF2-HFU2/HFRF2-HFRF2
Specification
Dimensions
4
143(
5.63
)15
5(6.
10)
80(3.15)67(2.64)
5(0.20)
5(0.20)
6(0.
24)
4.4(
0.17
)93
(3.6
6)
13(0
.51)
2.6(
0.10
)
Wall
143(
5.63
)15
5(6.
10)
80(3.15)67(2.64)
5(0.20)
5(0.20)
6(0.
24)
4.4(
0.17
)10
7(4.
21)
27(1
.06)
2.6(
0.10
)
Wall
176(
6.93
)18
9(7.
44)
110(4.33)98(3.86)
5(0.20)
5(0.20)
6(0.
24)
4.4
(0.1
7)12
8(5.
04)
28(1
.10)
2.6(
0.10
)
176(
6.93
)18
9(7.
44)
5(0.20)
5(0.20)
6(0.
24)
4.4
(0.1
7)15
5(6.
10)
55(2
.17)
6(0.
24)
Wall
WallWall
WallWall
98(3.86)
Wall
110(4.33)
Air Intake
011SFEF2,007HFEF2,HFU2:without FAN
Exhaust
● X200-002SFEF2, NFU2, LFRF2
● X200-005SFEF2 ● X200-007SFEF2,NFU2● X200-004HFEF2,HFU2, HFRF2
● X200-055~075LFU2,LFRF2 ● X200-055~075HFEF2,HFU2,HFRF2● X200-011SFEF2 ● X200-015~022SFEF2, NFU2● X200-037LFU2 ● X200-007~040HFEF2, HFU2● X200-015~037LFRF2 ● X200-007~037HFRF2
● X200-004SFEF2, NFU2, LFRF2
180(7.09)164(6.46)
235(
9.25
)25
0(9.
84)
2-φ6(0.24)
4.4(
0.17
)
165(
6.50
)
6(0.24)
143(
5.63
)
155(
6.10
)
80(3.15)67(2.64)
5(0.20)
5(0.20)
6(0.
24)
4.4
(0.1
7)13
0(5.
12)
50(1
.97)
2.6(
0.10
)
● X200-007LFRF2
[Unit: mm(inch)]Inches for reference only
Operation and Programming
5
(1) or the value previously monitored is displayed.
(1) or the value previously monitored is displayed.
(1) or the value previously monitored is displayed.
(2)The motor runs at the frequency set by the potentiometer. (3)The motor stops.
(2)Function code appears. (3) appears.
(5) appears. (6)Preset value is displayed. (7)Newly set value is displayed.(8)Returns to and the setting is complete.
(4) or the code number set in the end of last setting is displayed.
Poweron
Power on
Power on
Press until appears.
Pressto set desired value.
Press until appears.
Press key.
Press key. Press key.
Press keyto store the value.
*To run the motor, go back tomonitor mode or basic setting mode.*Pressing key for a while and back to
Press key to stop the motor.Press key and turn the potentiometer clockwise.
Press key. Press key.
(2)Function code appears. appears.(4)Output current value is displayed.
Press
until appears.
1. Setting the maximum output frequency
2. Running the motor(by potentiometer)
3. Monitoring output current value
(3)
(Output frequency monitor)
RS-485 communication/operator selection switch
Safety stop ON/Off switch
S7
S8
ON
OFF485
OPE
Operation / Terminal Functions
6
Hardware switches
Terminal DescriptionTerminal Symbol
Jumper
Jumper
L1 / N
+1+-U/T1 V/T2W/T3
Jumper
L1 L2 L3/N
SFEF2
NFU2,LFU2,LFRF2
Jumper
+1+-U/T1 V/T2W/T3
Jumper
L1 / N
Jumper
L1 L2 L3/N
SFEF2
NFU2,LFU2
Jumper
R/L1 S/L2 T/L3HFEF2,HFU2,HFRF2
• X200- 002~004SFEF2, 002~004NFU2, 002~007LFRF2
• X200- 005~022SFEF2, 007~022NFU2, 037LFU2 004~040HFEF2, 004~040HFU2 055~075LFU2, 055~075HFU2 055~075HFEF2, 015~075LFRF2, 004~075HFRF2
Screw Diameter and Terminal Width
Terminal arrangement
Control circuit terminalsTerminal arrangement
AM H O OI L 5 4 3 2 1 L PCS P24 CM2 11
Short bar:default position (Source logic)
AL0AL1AL2
Note 1:The standard keypad OPE (OPE-SRmini) can be used either the switch is set to 485 or OPE.Note 2:Input terminal selection (EMR) cannot be chosen from an operaator. If the slide switch SW8 is turned ON, it
divides automatically and is attached.
Terminal function
+ - + -
Assign [AT] for input terminal to selecting frequency source from voltage or current.
(1kΩ-2kΩ) DC0-10VInput inpedance 10kΩ
DC4-20mAInput inpedance 250Ω
VR
H O OI L H O OI L H O OI L
SW7
SW8
RS-485 communication/key pad selection switch
Safety stop ON/OFF
Switch symbol Switch Name Switch Name DescriptionSelect communication connector distination. *1
485OPE [default]
RS-485 communicaiton via Modbus protocolKeypad (option)
Select frequency and run command input source. The SW8 is for the Safety signal input. If you turn this DIP switch ON, the inverter is ready to receive Safety signal from the dedicated terminal #3. Inverter shuts off the output by means of pure hardware when a signal is given to the terminal. Each signals related to this Safety input must be in accordance with the norm. Additionally, the logic input terminal assign will be changed automatically if the SW8 is made ON.
L1,L2,N/L3U/T1,V/T2,W/T3
+1,++ -
Main power supply input terminalsInverter output terminals
DC reactor connection terminalsExternal braking unit connection terminals
Ground connection terminal
Terminal Symbol Terminal Name
Model Screw diameter (mm)002 - 004NFU2/SFEF2002-007LFRF2007- 022NFU2, 037LFU2005 - 022SFEF2015-037LFRF2004- 040HFU2/HFEF2004-037HFRF2055- 075LFU2/LFRF2/HFU2/HFEF2/HFRF2
M3.5
M4
M5
Terminal width W (mm)
7.1
9.2
12
-
Terminal name Description Ranges and Notes
Input/monitor signals
AML
P24PCS
54321
Freqencysetting
Output signals
11
CM2
Relay output
AL2
AL1
AL0
H
O
OI
L
+10V analog reference
Analog input, voltage
Analog input, current
Common for inputs
Intelligent (programable) output terminals, selection from:RUN(run signal), FA1(Frequency arrival type 1 -constant speed), FA2(Frequency arrival type 2 -over-frequency), OL(overload advance notice signal), OD(Output deviation for PID control), AL(alarm signal), DC(Wire brake detect on analog input), FBV(Feedback voltage comparison), NDc(Network Disconnection), LOG(Logic operation result), ODC(Option Card Detection signal), LOC(Low Load Detection).
Open collector outputL level at operation (ON)27V DC, 50mA max.
Common for intelligent output terminals
10V DC, 10mA max
0 to 10V DC, input impedance10kohm
4 to 20mA DC,input impedance 250ohm
-
Voltage analog outputCommon for inputs+24V for logic inputsIntelligent input common
0 to10V DC, 1mA max.-
24V DC, 30mA (do not short to terminal L)-
Intelligent (programable) input terminals, selection from:FW(Forward), RV(Reverse), CF1-CF4(Multispeed command), JG(Jogging), DB(External DC braking), SET(Second motor constants setting), 2CH(Second accel./decel.), FRS(Free-run stop), EXT(External trip), USP(Unattended start protection), SFT(Software lock), AT(Analog input selection), RS(Reset), PTC(Thermistor input), STA(3-wire start), STP(3-wire stop), F/R(3-wire fwd./rev.), PID(PID On/Off), PIDC(PID reset), UP/DWN(Remote-controlled accel./decel.), UDC(Remote-controlled data clearing), OPE(Operator control), ADD(Frequency setpoint), F-TM(Force terminal enable), RDY(Quick start enable), S-ST(Special-Set 2nd Motor Data), EMR(Safety stop) or NO(Not selected).
-
SWP24
1-5
Operated by closing switch.(Input logic is selectable)
AC250V 2.5A (Resistive load) 0.2A (cos =0.4)DC30V 3.0A (Resistive load) 0.7A (cos =0.4)(minimum) AC100V 10mA DC 5V 100mA
AL2 AL1 AL0
Relay contact (alarm output)terminals (programable,function is selectable same asintelligent output terminals).
<Initial setting>Normal: AL0-AL1 closedTrip/Power OFF: AL0-AL2 closed
Function List
7
Monitoring and main profile parameters
A Group: Standard functions
: Allowed[ X: Not allowed ]Lo Hi
The parameter tables in this chapter have a column titled "Run Mode Edit." An Ex mark x means the parameter cannot be edited; a Check mark means the parameter can be edited. The table example to the right contains two adjacent marks "x ". These two marks (that can also be
"xx" or " ") correspond to low-access or high-access levels to Run Mode edits (note Lo and Hi in column heading).
: Allowed[ X: Not allowed ]
Function Code Name Range Default Unit Run mode edit
Monitor
Main Profile Parameters
F001F002F202F003F203F004
d001d002d003d004
d005
d006
d007d013d016d017d018d080d081d082d083d102d104
Output frequency monitorOutput current monitorRotation direction monitorProcess variable, PID feedback monitor
Intelligent input terminal status
Intelligent output terminal status
Scaled output frequency monitorOutput voltage monitorCumulative operation RUN time monitorCumulative power-on time monitorCooling fin temperature monitorTrip counterTrip monitor 1Trip monitor 2Trip monitor 3DC bus voltage monitorElectronic themal monitorOutput frequency settingAcceleration time (1) settingAcceleration time (2) settingDeceleration time (1) settingDeceleration time (2) settingKeypad Run key routing
----
-
-
-----------
HzA--
-
-
-Vhrhr˚C
events---V%
----
-
-
-----------
0.0/start freq. to 400.00.01 to 99.99/100.0 to 999.9/1000. to 3000.0.01 to 99.99/100.0 to 999.9/1000. to 3000.0.01 to 99.99/100.0 to 999.9/1000. to 3000.0.01 to 99.99/100.0 to 999.9/1000. to 3000.00(Forward)/01(Reverse)
0.010.010.010.010.000
Hzsecsecsecsec-
Expanded functions
A--b--C--H--P--
A Group: Standard functionsb Group: Fine-tuning functionsC Group: Intelligent terminal functionsH Group: Motor constants functionsP Group: Expansion Card Functions
5 4 3
ONOFF
2 1
AL
ONOFF
11
e.g. : 1,2 : ON 3,4,5 : OFFe.g. : 11 : ON AL : OFF
----
-
-
-----------
X
Basic setting
A001A201A002A202A003A203A004A204
Frequency source settingFrequency source setting, 2nd motorRun command source settingRun command source setting, 2nd motorBase frequency settingBase frequency setting, 2nd motorMaximum frequency settingMaximum frequency setting, 2nd motor
00(Keypad potentiometer)/01(Control terminal)/02(Function F001 setting)/03(RS485)/10(Calculation result)
01(Control terminal)/02(Run key on keypad)/03(RS485)
30 to maximum freq.30 to maximum freq.30 to 40030 to 400
0101010150.50.50.50.020.00.00.
100.018.
0.00.00.00.00.00.00.00.00.00.0
0.0
100.0000001.80.0
10.00.00000
100.100.100.0.50.00.
0.001
0000020260.60.60.60.020.00.00.
100.018.
0.00.05.0
10.015.020.030.040.050.060.0
0.0
100.0000001.80.0
10.00.00000
100.100.000.50.00.
0.001
0000020260.60.60.60.020.00.00.
100.018.
0.00.00.00.00.00.00.00.00.00.0
0.0
100.0000001.80.0
10.00.00000
100.100.100.0.50.00.
0.001
----HzHzHzHz-HzHz%%--HzHzHzHzHzHzHzHzHzHz
Hz
Hz---%%%%--%%-HzsecHzsec-
XXXXXXXXXXXXXXX
XXX
XX
XXXXXX
XXXXXXXX
XX
XX
Analog input setting
A005A011A012A013A014A015A016
[AT] selection[O]-[L] input active range start frequency[O]-[L] input active range end frequency[O]-[L] input active range start voltage[O]-[L] input active range end voltage[O]-[L] input start frequency enableExternal frequency filter time constant
02(O/VR)/03(OI/VR)/04(O)/05(OI)0.0 to maximum freq.0.0 to maximum freq.0 to 1000 to 10000(use set value)/01(use 0 Hz)1 to 17
Multi-speed and jogging
A020 A220 A021 A022 A023 A024 A025 A026 A027 A028 A029-A035A038A039A041A241A042A242A043A243A044A244A045A245A051A052A053A054A055A056
Multi-speed frequency setting (0)Multi-speed frequency (2nd), setting 2nd motorMulti-speed frequency setting (1)Multi-speed frequency setting (2)Multi-speed frequency setting (3)Multi-speed frequency setting (4)Multi-speed frequency setting (5)Multi-speed frequency setting (6)Multi-speed frequency setting (7)Multi-speed frequency setting (8)
Multi-speed frequency setting (9-15)
Jog frequency settingJog stop modeTorque boost selectTorque boost select 2nd motorManual torque boost valueManual torque boost value, 2nd motorManual torque boost frequency adjustmentManual torque boost frequency adjustment, 2nd motorV/f characteristic curve selectionV/f characteristic curve selection, 2nd motorV/f gain settingV/f gain setting, 2nd motorDC braking enableDC braking frequency settingDC braking wait timeDC braking force during decelerationDC braking time for decelerationDC braking / edge or level detection for [DB] input
0.00/start freq. to 9.9900(free-run stop)/01(deceleration and stop)/02 (DC braking)00(Manual)/01(Automatic)00(Manual)/01(Automatic)0.0 to 20.00.0 to 20.00.0 to 50.00.0 to 50.000(VC)/01(Reduced torque)/06 (Reduced torque 1)00(VC)/01(Reduced torque)/06 (Reduced torque 1)20 to 10020 to 10000(Disable)/01(Enable)/02(Frequency detection)0.0 to 60.00.0 to 5.00. to 100.0.0 to 60.000(Edge)/01(Level)
0.0/start freq. to maximum freq.
V/f Characteristic
DC braking
Run mode editFunction Code Name Range
Default
-EF(CE) -U(UL) -R(JP)Unit
Lo Hi
0.0 to 400.00.0 to 999.9F(Forward)/o(Stop)/r(Reverse)0.00 to 99.99/100.0 to 999.9/1000. to 9999.
0.00 to 99.99/100.0 to 999.9/1000. to 9999./1000 to 9999(10000 to 99999)0.0 to 600.00. to 9999./1000 to 9999/ 100 to 999 (10000 to 99900)0. to 9999./1000 to 99990.0 to 200.00. to 9999.
Displays trip event information
0.0 to 999.90.0 to 100.0
X
Function List
8
A Group: Standard functions
b Group: Fine-tuning functions
: Allowed[ X: Not allowed ]
: Allowed[ X: Not allowed ]
PID Control
PID Control
AVR function
Operation mode and acc./dec. function
External freq. tuning
Frequency caluculation
A061A261A062A262A063A064A065A066A067A068A071A072A073A074A075A076A077A078A081
A082
A085A086A092A292A093A293A094A294A095A295A096A296A097A098A101A102A103A104A105A141A142A143A145A146A151A152A153A154A155
Frequency upper limit settingFrequency upper limit setting, 2nd motorFrequency lower limit settingFrequency lower limit setting, 2nd motorJump (center) frequency setting 1Jump (hysteresis) frequency setting 1Jump (center) frequency setting 2Jump (hysteresis) frequency setting 2Jump (center) frequency setting 3Jump (hysteresis) frequency setting 3PID EnablePID EnablePID proportional gainPID integral time constantPID derivative time constantPV scale conversionPV source settingReverse PID actionPID output limitAVR function select
AVR voltage select
Operation mode selectionEnergy saving mode tuningAcceleration (2) time settingAcceleration (2) time setting, 2nd motorDeceleration (2) time settingDeceleration (2) time setting, 2nd motorSelect method to switch to Acc2/Dec2 profileSelect method to switch to Acc2/Dec2 profile, 2nd motorAcc1 to Acc2 frequency transition pointAcc1 to Acc2 frequency transition point, 2nd motorDec1 to Dec2 frequency transition pointDec1 to Dec2 frequency transition point, 2nd motorAcceleration curve selectionDeceleration curve selection[OI]-[L] input active range start frequency[OI]-[L] input active range end frequency[OI]-[L] input active range start current[OI]-[L] input active range end current[OI]-[L] input start frequency enableA input select for calculate functionB input select for calculate functionCalculation symbolADD frequencyADD direction selectPot. input active range start frequencyPot. input active range end frequencyPot. input active range start currentPot. input active range end currentPot.input start frequency enable
0.0/Freq. lower limit setting to maximum freq.0.0/Freq. lower limit setting (2nd) to maximum freq. (2nd)0.0/Start freq. to freq. upper limit setting0.0/Start freq. (2nd) to freq. upper limit setting (2nd)0.0 to 400.0.0 to 10.00.0 to 400.0.0 to 10.00.0 to 400.0.0 to 10.000(Disable)/01(Enable)0.2 to 5.00.0 to 150.00.00 to 100.00.01 to 99.9900([OI] terminal)/01([O] terminal)/02(RS485)/10(Calculation result)00(OFF)/01(ON)0.0 to 100.000(Enable)/01(Disable)/02(Enabled except during deceleration)200V class: 200/215/220/230/240400V class: 380/400/415/440/460/48000(Normal)/01(Energy-saver)0.0 to 100.00.01 to 99.99/100.0 to 999.9/1000. to 3000.0.01 to 99.99/100.0 to 999.9/1000. to 3000.0.01 to 99.99/100.0 to 999.9/1000. to 3000.0.01 to 99.99/100.0 to 999.9/1000. to 3000.00(2CH from input terminal)/01(transition freq.)00(2CH from input terminal)/01(transition freq.)0.0 to 400.00.0 to 400.00.0 to 400.00.0 to 400.000(Linear)/01(S-curve)00(Linear)/01(S-curve)0.0 to 400.00.0 to 400.00. to 100.0. to 100.00(Use setting value)/01(0Hz)00(Digital operator)/01(Keypad potentiometer)02(O input)/03(OI input)/04(RS485)00(A141+A142)/01(A141-A142)/02(A141*A142)0.0 to 400.000(Plus)/01(Minus)0.0 to 400.00.0 to 400.00.0 to 100.00.0 to 100.000(Use offect (A151 value))/01(Use 0Hz)
0.00.00.00.00.00.50.00.50.00.5001.01.0
0.001.0000000.000
200/400
0050.0
15.0015.0015.0015.00
00000.00.00.00.000000.00.00.
100.010102000.0000.00.00.0
100.01
0.00.00.00.00.00.50.00.50.00.5001.01.0
0.001.0000000.000
200/400
0050.0
15.0015.0015.0015.00
00000.00.00.00.000000.00.00.
100.010102000.0000.00.00.0
100.01
0.00.00.00.00.00.50.00.50.00.5001.01.00.001.0000000.002
200/400
0050.015.0015.0015.0015.00
00000.00.00.00.000000.00.00.
100.010102000.0000.00.00.0100.01
HzHzHzHzHzHzHzHzHzHz--
secsec---%-
V
-%
secsecsecsec--HzHzHzHz--HzHz%%----Hz-HzHz%%-
XXXXXXXXXXX
XXXXX
XXX
XXXXXXXXXXXXXXXX
XXXXXX
Run mode editFunction Code Name Range
Default
-EF(CE) -U(UL) -R(JP)Unit
Lo Hi
X
X
XXXXXXXX
Restart after instantaneous power
failure
b001
b002b003
b004
b005
b011
b012
b212
b013b213
Selection of automatic restart mode
Allowable under-voltage power failure timeRetry wait time before motor restartInstantaneous power failure / under-voltage trip alarm enableNumber of restarts on power failure / under-voltage trip eventsStart frequency to be used in case of frequency pull-in restart
Electronic thermal setting
Electronic thermal setting, 2nd motor
Electronic thermal characteristicElectronic thermal characteristic, 2nd motor
00(Alarm output)/01(Restart at 0Hz)/02(Resume after freq. matching)/03(Resume freq. matching then trip)0.3 to 25.00.3 to 100.0
00(Disable)/01(Enable)
00(Restart 16 times)/01(Always restart)
00(frequency at previous shutoff)/01(Max. Hz)/02(Set frequency)
0.2*Rated current to 1.0*Rated current
00(Reduced torque)/01(Constant torque)/02(Reduced torque 2)
00
1.01.0
00
00
00
0101
00
1.01.0
00
00
00
0101
-
secsec
-
-
-
A
A
--
X
XX
X
X
X
X
X
XX
Overload restriction
b021b221b022b222b023b223b028b228b029
b030
Overload restriction operation modeOverload restriction operation mode, 2nd motorOverload restriction settingOverload restriction setting, 2nd motorDeceleration rate at overload restrictionDeceleration rate at overload restriction, 2nd motorOverload restriction source selectionOverload restriction source selection, 2nd motorDeceleration rate of frequency pull-in restart
Current level of frequency pull-in restart
00(Disable)/01(Enable)/02(Enable for during acceleration)
0.2*Rated current to 1.5*Rated current
0.1 to 3000.0
00(b022/b222 setting level)/01([O]-[L] analog input)
0.1 to 3000.0
0.2*Rated current to 2.0*Rated current
0101
1.01.000000.5
0101
30.030.000000.5
--AA
secsec--
sec
A
XXXXXXXXX
X
Run mode editFunction Code Name Range
Default
-EF(CE) -U(UL) -R(JP)Unit
Lo Hi
Lock b031 Software lock mode selection
00([SFT] input blocks all edits)/01([SFT] input blocks edits except F001 and Multispeed parameters/02(No access to edits)/03(No access to edits except F001 and Multi-speed parameters)/10(High-level access,including b031)
01 01
00
1.01.0
00
00
00
00000101
1.01.000000.5
01 - X
XX
Automatic Energy Saving
X
X
X
Rated current
Rated current
1.5*Rated current
Rated current
Function List
9
C Group: Intelligent terminal functions : Allowed[ X: Not allowed ]
Note: C014: 01 for UL version.
Run mode editFunction Code Name Range
Default
-EF(CE) -U(UL) -R(JP)Unit
Lo
Intelligent input terminal
C001C201C002C202C003C203C004C204C005C205
Terminal [1] functionTerminal [1] function, 2nd motorTerminal [2] functionTerminal [2] function, 2nd motorTerminal [3] functionTerminal [3] function, 2nd motorTerminal [4] functionTerminal [4] function, 2nd motorTerminal [5] functionTerminal [5] function, 2nd motor
00(FW:Forward), 01(RV:Reverse), 02-05(CF1-CF4:Multispeed command), 06(JG:Jogging), 07(DB:External DC braking), 08(SET:Second motor constants setting), 09(2CH:Second accel./decel.), 11(FRS:Free-run stop), 12(EXT:External trip), 13(USP:Unattended start protection), 15(SFT:Software lock), 16(AT:Analog input selection), 18(RS:Reset), 19(PTC:Thermistor input), 20(STA:3-wire start), 21(STP:3-wire stop), 22(F/R:3-wire fwd./rev.), 23(PID:PID On/Off), 24(PIDC:PID reset), 27(UP:Remote-controlled accel.), 28(DWN:Remote-controlled decel.), 29(UDC:Remote-controlled data clearing), 31(OPE:Operator control), 50(ADD: Frequency setpoint), 51(F-TM: Force terminal enable), 52(RDY: Quick Start Enable), 53(S-ST: Special-Set (select) 2nd Motor Data), 64(EMR:Safety stop), 255(NO:Not selected)
00000101020203031818
00000101161613131818
-
-
-
-
-
XXXXXXXXXX
XXXXXXXXXX
Hi
C011- C015 Terminal [1] to [5] active state 00(NO)/01(NC) 00 00* - X X
C021 Terminal [11] function
00(RUN:run signal), 01(FA1:Frequency arrival type 1 - constant speed), 02(FA2:Frequency arrival type 2 - over-frequency), 03(OL:overload advance notice signal), 04(OD:Output deviation for PID control), 05(AL:alarm signal), 06(DC:Wire brake detect on analog input), 07(FBV: Feedback voltage comparison), 08(NDc: Network Disconnection), 09(LOG: Logic operation result), 10(ODC: Option Card Detection Signal), 43(LOC:Low load detection)
01 01 - X X
Intelligent input terminal
C026C028C031C036
C038
C039C041C241C042C043C044C052C053
Alarm relay function[AM] signal selectionTerminal [11] active stateAlarm relay active state
Output mode of low load detection signal
Low load detection levelOverload level settingOverload level setting, 2nd motorFrequency arrival setting for accelerationFrequency arrival setting for decelerationPID deviation level settingFeedback comparison upper levelFeedback comparison lower level
05000001
01
0.00.03.01000.0
05000001
01
0.00.03.01000.0
----
-
A
HzHz%%%
00(Output frequency)/01(Output current)00(NO)/01(NC)00(NO)/01(NC)00(Disabled)/01(During acceleration, deceleration and constant speed)/02(During constant speed only)0.0 to 2.0*Rated current
0.0*Rated current to 2.0*Rated current
0.0 to 400.00.0 to 400.00.0 to 100.00.0 to 100.00.0 to 100.0
XXXX
X
XXXXXXXX
X
XX
Serial communication
C070C071C072C074C075
C076
C077C078
SELECTION OF OPE/MODBUSCommunication speed selectionNode allocationCommunication parity selectionCommunication stop bit selection
Communication error mode
Communication error timeCommunication wait time
02(OPE or option)/03(485)04(4800bps)/05(9600bps)/06(19200bps)1. to 32.00(No parity)/01(Even parity)/02(Odd parity)1(1-bit)/2(2-bit)00(Trip)/01(Trip after deceleration stop)/02(Disable)/03(FRS)/04(Deceleration stop)0.00 to 99.990. to 1000.
02061.001
02
0.000.
02041.001
02
0.000.
----bit
-
secmsec
XXXXX
X
XX
Analog meter settingC081C082C086
0. to 200.0. to 200.0.0 to 10.0
[O] input span calibration[OI] input span calibration[AM] terminal offset tuning
100.100.0.0
100.100.0.0
%%V
00 (must not be changed)00(Clear last frequency)/01(Keep last frequency adjusted by UP/DWN)00(Cancel trip state at input signal ON transition)/ 01(Cancel trip state at signal OFF transition)/02(Cancel trip state at input signal ON transition)00(RUN)/01(FA1)/02(FA2)/03(OL)/04(OD)05(AL)/06(Dc)/07(FBV)/08(NDc)/10(ODc)/43(LOC)00(AND)/01(OR)/02(XOR)0.0 to 100.00.0 to 100.00.0 to 100.00.0 to 100.0
Others
C091C101
C102
C141C142C143C144C145C148C149
Reserved (for factory adjustment)Up/Down memory mode selection
Reset mode selection
Input A select for logic output 1Input A select for logic output 2Logic function selectON delay time, output terminal 11OFF delay time, output terminal 11ON delay time, relayOFF delay time, relay
0000
00
0001000.00.00.00.0
0000
00
0001000.00.00.00.0
00000101020203031818
00
01
05000001
01
0.00.03.01000.002041.001
02
0.000.
100.100.0.00000
00
0001000.00.00.00.0
--
-
---
secsecsecsec
X
X
XXXXXXX
XXX
Run mode editFunction Code Name Range
Default
-EF(CE) -U(UL) -R(JP)Unit
Lo Hi
Others
b050b051b052b053b054b055b056b080b082b083
b084
b085b086b087b088
b089
b091
b092
b130b131b133b134b140b150b151
Selection of the non stop operationNon stop operarion start voltage settingOV-LAD Stop level of non stop operation settingDeceleration time of non stop operation settingFrequency width of quick deceleration settingDC bus AVR P-gainDC bus AVR I-time[AM] terminal analog meter adjustmentStart frequency adjustmentCarrier frequency setting
Initialization mode (parameters or trip history)
Country code for initializationFrequency scaling conversion factorSTOP key enableRestart mode after FRS
Monitor display select for networked inverter
Stop mode selection
Cooling fan control (see note below)
Over-voltage LADSTOP enableOver-voltage LADSTOP levelDC bus AVR selectionThreshold voltage of DC bus AVR settingOver-current trip suppressionCarrier modeQuick start enable
00(Disabled)/01(Enabled stop)/02(Enabled restart)0.0 to 1000.00.0 to 1000.00.01 to 30000.0 to 10.00.2 to 5.00.0 to 150.00. to 255.0.5 to 9.92.0 to 12.000(Trip history clear)/01(Parameter initialization)/02(Trip history clear and parameter initialization)00(JP)/01(CE)/02(US)0.1 to 99.900(Enable)/01(Disable)00(Restart from 0Hz)/01(Restart with frequency detection)01(Output frequency)/02(Output current)/03(Rotation direction)/04(PV, PID feedback)/05(Input terminal status)/06(Output terminal status)/07(Scaled output frequency)00(Deceleration and stop)/01(Free-run stop)00(Always ON)/01(ON during RUN, OFF during STOP)/02(Temperature controlled)00(Disable)/01(Enable)330 to 395V/660 to 790V00(Disabled)/01(Enabled)330 to 395V/660 to 790V00(Disable)/01(Enable)00(Disable)/01(Enable)00(Disable)/01(Enable)
000.00.01.00.00.20.2
100.0.53.0
00
011.00000
01
00
00
00380/760
00380/760
010000
000.00.01.00.00.20.2
100.0.53.0
00
021.00000
01
00
00
00380/760
00380/760
010000
000.00.01.00.00.20.2
100.0.53.0
00
001.00000
01
00
00
00380/760
00380/760
010000
-VV
secHz-
sec-HzkHz
-
----
-
-
-
-V-V---
XXXXXXX
XX
X
X
XX
X
X
X
XXXX
XXXXXXX
X
X
X
X
X
Rated current
OC.Drive
OC.Decel
OC.Accel
Over.C
Over.L
Over.V
EEPROM
Under.V
CPU
EXTERNAL
USP
GND.Flt
OV.SRC
OH FIN
DRIV
EepBlank
TH
EMERGENCY
NET.ERR
Protective Functions
10
Name
Over current
Overload protection *1
Over voltage protection
EEPROM error *2,3
Under-voltage error
CPU error
External trip
USP *4
Ground fault *5
Input over-voltage
Inverter thermal trip
Thermistor
Communications error
Cause(s) Display on digital operator
The inverter output was short-circuited, or the motor shaft is locked or has a heavy load. These conditions cause excessive current for the inverter, so the inverter output is turned OFF.
When a motor overload is detected by the electronic thermal function, the inverter trips and turns OFF its output.
When the DC bus voltage exceeds a threshold, due to regenerative energy from the motor.
When the built-in EEPROM memory has problems due to noise or excessive temperature, the inverter trips and turns OFF its output to the motor. A decrease of internal DC bus voltage below a threshold results in a control circuit fault. This condition can also generate excessive motor heat or cause low torque. The inverter trips and turns OFF its output.A malfunction in the built-in CPU has occurred, so the inverter trips and turns OFF its output to the motor. A signal on an intelligent input terminal configured as EXT has occurred. The inverter trips and turns OFF the output to the motor. When the Unattended Start Protection (USP) is enabled, an error occurred when power is applied while a Run signal is present. The inverter trips and does not go into Run Mode until the error is cleared. The inverter is protected by the detection of ground faults between the inverter output and the motor during powerup tests. This feature protects the inverter, and does not protect humans. When the input voltage is higher than the specified value, it is detected 100 seconds after powerup and the inverter trips and turns OFF its output. When the inverter internal temperature is above the threshold, the thermal sensor in the inverter module detects the excessive temperature of the power devices and trips, turning the inverter output OFF.
When a thermistor is connected to terminals [PTC] and [CM1] and the inverter has sensed the temperature is too high, the inverter trips and turns OFF the output.
The inverter's watchdog timer for the communications network has timed out.
While at constant speedDuring decelerationDuring acceleration
Others
Display on remote operator/copy unit
Error Codes
Error codeOutput frequency
at trip pointMotor currentat trip point
Voltage betweenP(+) and N(-) at trip point
Cumulative inverterRUN time at trip point
Cumulative power-ontime at trip point
1 2 1 2 1 2 1 2 1 2
1 2
How to access the details about the present fault
Note 1: Reset operations acceptable 10 seconds after the trip. Note 2: If an EEPROM error (E08) occurs, be sure to confirm the parameter data values are still correct. Note 3: EEPROM error may occer at power-on after shutting down the power while copying data with remote operator or initializing data. Shut down the power after completing copy or initialization. Note 4: USP error occures at reseting trip after under-voltage error (E09) if USP is enabled. Reset once more to recover. Note 5: Ground fault error (E14) cannot be released with resetting. Shut the power and check wiring.
P Group: Expansion Card Functions
H Group: Motor constants functions
Note: The "P" Group parameters do not appear in the parameter list shown on the keypad display unless the expansion card is installed on the inverter.
Function List
Option Setting
Motor constants and gain
P044
P045
P046P047
P048
P049
H003H203H004H204H006H206
Network comm watchdog timer
Inverter action on network comm error
Polled I/O output instance numberPolled I/O input instance number
Inverter action on network idle mode
Network motor poles setting for RPM
0.00 to 99.9900(Trip (Error Code E70)) 01(Decelerate to stop and trip (Error Code E70))02(Hold last speed), 03(Free run stop), 04(Decelerate and stop)20/21/10070/71/10100(Trip (Error Code E70))01(Decelerate to stop and trip (Error Code E70))02(Hold last speed), 03(Free run stop), 04(Decelerate and stop)00 to 38
1.00
01
2171
01
0
1.00
01
2171
01
0
1.00
01
2171
01
0
sec.
-
--
-
-
Run mode edit
Run mode edit
Function Code
Function Code
Name
Name
Range
Range
Default
Default
-EF(CE)
-EF(CE)
-U(UL)
-U(UL)
-R(JP)
-R(JP)
Unit
Unit
Lo
Lo
Hi
Hi
X
X
XX
X
X
X
X
XX
X
X
: Allowed[ X: Not allowed ]
: Allowed[ X: Not allowed ]
Driver error
EEPROM not Initialized
An internal inverter error has occurred at the safety protection circuit between the CPU and main driver unit. Excessive electrical noise may be the cause. The inverter has turned OFF the IGBT module output.
Important data stored on the EEPROM are unexpected value.
Safety Stop Safety stop signal given.
Motor capacity, 1st motorMotor capacity, 2nd motorMotor poles setting, 1st motorMotor poles setting, 2nd motorMotor stabilization constant, 1st motorMotor stabilization constant, 2nd motor
0.2/0.4/0.55/0.75/1.1/1.5/2.2/3.0/4.0/5.5
2/4/6/8
0. to 255.
Factoryset44
100100
Factoryset44
100100
Factoryset44
100100
kWkW
polespoles
%%
XXXX
XXXX
Connecting Diagram
11
AL2
AL1
AL0
R(L1)
T/N(L3)
S(L2)
(T1) U
(T3) W
(T2) V
P24
4
5
3
2
1
PCS
L
AM
H
O
OI
L
DC24V
DC10V
11
CM2
(+1)PD
(+)P
(-)N
DC link choke
Motor
Intelligent relayoutput contacts
Intelligent outputterminal
Current input4mA~20mA
X200
Intelligent inputterminals
(5 terminals)Source type
DC 0~10V(8bit)
Terminal 1,2,3,4,5 H,O,OI 11
Common Sink logic : L
L CM2 Source logic : PCS
Note 1: Common terminals are depend on logic.
Note 2: Please choose proper inverter input volotage rating.
10k 250
Frequency setting1k ~2k
Dynamic breaking umit (BRD)
P
P
N
RBRB
R1 AL1
AL2R2
Power source1-/3-phase 200~240V+10%, -15%
3-phase 380~480V+10%, -15%50/60Hz 5%
Short bar
Source type logic
Connecting Diagram
12
R(L1)
T/N(L3)
S(L2)
(T1) U
(T3) W
(T2) V
P24
PCS
4
5
3
2
1
L
AM
H
O
OI
L
DC24V
DC10V
11
CM2
(+1)PD
(+)P
(-)N
DC link choke
Motor
Intelligent relayoutput contacts
Intelligent outputterminal
Current input4mA~20mA
X200
Intelligent inputterminals
(5 terminals)Sink type
Short bar
DC 0~10V(8bit)
Terminal 1,2,3,4,5 H,O,OI 11
Common Sink logic : L L CM2 Source logic : PCS
Note 1: Common terminals are depend on logic.
Note 2: Please choose proper inverter input volotage rating.
10k 250
Frequency setting1k ~2k
Dynamic breaking umit (BRD)
P
P
N
RBRB
R1 AL1
AL2R2
Power source1-/3-phase 200~240V+10%, -15%
3-phase 380~480V+10%, -15%50/60Hz 5%
AL2
AL1
AL0
Sink type logic
13
Wiring and Accessories
L1 L2 L3
U(T1) V(T2) W(T3)
+1
+
-
IM
Power Supply
Fuse
Inverter
Motor
Note 1: Field wiring connection must be made by a UL and c-UL listed closed-loop terminal connector sized for the wire gauge involved. Connector must be fixed using the crimping tool specified by the connector manufacturer. Note 2: Be sure to use large wire gauges for power wiring if the distance exceeds 20m (66ft). Note 3: Use 0.75mm2 /18 AWG wire for the relay terminals (AL0, AL1 and AL2) signal wire.
Name Function
This is useful in suppressing harmonics induced on the power supplylines, or when the main power voltage imbalance exceeds 3% (and power source capacity is more than 500kVA), or to smooth out line fluctuations. It also improves the power factor.
Electrical noise interference may occur on nearby equipment such as a radio receiver. This magnetic choke filter helps reduce radiat-ed noise (can also be used on output).
Reduces the conducted noise on the power supply wiring generated by theinverter. Connect to the inverter input side.
This capacitor filter reduces radiated noise from the main power wires in the inverter input side.
Suppresses harmonics generated by the inverter.
This is useful for increasing the inverter's control torque for high duty-cycle (on-off) applications, and improving the decelerating capability.
Reduces radiated noise from wiring in the inverter output side.
Electrical noise interference may occur on nearby equipment such as a radio receiver. This magnetic choke filter helps reduce radiated noise (can also be used on input).
This reactor reduces the vibration in the motor caused by the inver-ter's switching waveforms, by smoothing the waveforms to approximate commercial power quality. It is also useful when wiring from the inverter to the motor is more than 10m in length, to reduce harmonics.
Sine wave shaping filter for the output side.
Input side AC reactor
Radio noise filter
EMC filter
Radio noise filter (Capacitor filter)
DC link choke
Braking resistor
Braking unit
Output side noise filter
Radio noise filter
AC reactor
LCR filter
Input Voltage
Applicable Motor
(kW(HP))Model
Wireing Power Lines
AWG mm2 Signal Lines
Fuse (Class J)
0.2(1/4)
0.4(1/2)
0.55(3/4)0.75(1)1.1(1.5)
1.5(2)
2.2(3)
3.7(5)5.5(7.5)7.5(10)0.4(1/2)0.75(1)1.5(2)2.2(3)3(4)3.7(5)4.0(5)5.5(7.5)7.5(10)
X200-002NFU2/SFEF2X200-002LFRF2X200-004NFU2/SFEF2X200-004LFRF2X200-005SFEF2X200-007NFU2/SFEF2/LFRF2X200-011SFEF2X200-015NFU2/SFEF2X200-015LFRF2X200-022NFU2/SFEF2X200-022LFRF2X200-037LFU2/LFRF2X200-055LFU2/LFRF2X200-075LFU2/LFRF2X200-004HFU2/HFEF2/HFRF2X200-007HFU2/HFEF2/HFRF2X200-015HFU2/HFEF2/HFRF2X200-022HFU2/HFEF2/HFRF2X200-030HFEF2X200-037HFRF2X200-040HFU2/HFEF2X200-055HFU2/HFEF2/HFRF2X200-075HFU2/HFEF2/HFRF2
141614161414101014101412108
161616141414141212
2.01.252.0
1.252.02.05.55.52.05.52.03.55.38.4
1.251.251.252.02.02.02.03.33.3
18 to 28 AWG0.14 to
0.75mm2
shelded wire
18 to 28 AWG0.14 to
0.75mm2
shelded wire
10101010101515202030303040503610101515152025
400V
200V
14
Torque characteristics/Derating Curves
150
130
95
80
554535
100
1 6 20 60 120
Out
put t
orqu
e (%
)
Base frequency = 60Hz Base frequency = 50Hz
100
130
150
7555
4535
90
1 5 16.7 50 120
Output frequency (Hz)Output frequency (Hz)
Out
put t
orqu
e (%
)
0.2~4kW
0.2~4kW
5.5, 7.5kW
Continuous performance
5.5, 7.5kW
Short time performanceShort time performance
Continuous performance
0.2~4kW
5.5, 7.5kW
0.2~4kW
5.5, 7.5kW
Torque characteristics
Carrier frequency(kHz)
% o
f rat
ed o
utpu
t cur
rent
100%
95%
90%
85%
80%
75%
70%4 6 10 122 8
200V class
Carrier frequency(kHz)
% o
f rat
ed o
utpu
t cur
rent
100%
95%
90%
85%
80%
75%
70% 4 6 10 122 8
037LFU2/LFRF2
Carrier frequency(kHz)
% o
f rat
ed o
utpu
t cur
rent
% o
f rat
ed o
utpu
t cur
rent
4 6 10 122 8
002~004、022SFEF2/NFU2/LFRF2,005SFEF2、055LFU2/LFRF2
60%
65%
70%
75%
80%
85%
90%
95%
100%
Carrier frequency(kHz)
% o
f rat
ed o
utpu
t cur
rent
4 6 10 122 8
055HFEF/HFU/HFRF
60%
65%
70%
75%
80%
85%
90%
95%
100%
Carrier frequency(kHz)4 6 10 122 8
002~022SFEF2/NFU2/LFRF2,055、075LFU2/LFRF2
75%
80%
85%
90%
95%
100%
037LFU2
400V class
075LFU2/LFRF2
055HFEF2/HFU2/HFRF2
% o
f rat
ed o
utpu
t cur
rent
Carrier frequency(kHz)4 6 10 122 8
004~030,055,075HFEF2/HFU2004~022,055,075HFRF2
75%
80%
85%
90%
95%
100%
040HFEF2/HFU2/037HFRF2
037LFU2/LFRF2
200V class 200V class
400V class 400V class
007SFEF2/NFU2/LFRF2,011SFEF2
004~015、075HFEF2/HFU2/HFRF2
022HFEF2/HFU2/HFRF2
040HFEF2/HFU2/037HFRF2
030HFEF2
002~022SFEF2/NFU2/LFRF2,055,075LFU2/LFRF2
075HFEF2/HFU2/HFRF2
030HFEF2
004~022HFEF2/HFU2/HFRF2
040HFEF2/HFU2/037HFRF2
015SFEF2/NFU2/LFRF2
Derating CurvesUse the following derating curves to help determine the optimal carrier frequency setting for your inverter and find the output current derating. Be sure to use the proper curve for your particular X200 inverter model number.
For Correct Operation
15
Application to Motors
The overspeed endurance of a general-purpose motor is 120% of the rated speed for 2 minutes (JIS C4,004). For operation at higher than 60Hz, it is required to examine the allowable torque of the motor, useful life of bearings, noise, vibration, etc. In this case, be sure to consult the motor manufacturer as the maximum allowable rpm differs depending on the motor capacity, etc.The torque characteristics of driving a general-purpose motor with an inverter differ from those of driving it using commercial power (starting torque decreases in particular). Carefully check the load torque characteristic of a connected machine and the driving torque characteristic of the motor.
Application to general-purpose motors
Operating frequency
Torque characteristics
The torque characteristics of driving a general-purpose motor with an inverter differ from those of driving it using commercial power Motor loss andtemperature increase
When run by an inverter, a general-purpose motor generates noise slightly greater than with commercial power.NoiseWhen run by an inverter at variable speeds, the motor may generate vibration, especially because of (a) unbalance of the rotor including a connected machine, or (b) resonance caused by the natural vibration frequency of a mechanical system. Particularly, be careful of (b) when operating at variable speeds a machine previously fitted with a constant speed motor. Vibration can be minimized by (1) avoiding resonance points using the frequency jump function of the inverter, (2) using a tire-shaped coupling, or (3) placing a rubber shock absorber beneath the motor base.
Vibration
Under continued, low-speed operation, oil lubrication can deteriorate in a power transmission mechanism with an oil-type gear box (gear motor) or reducer. Check with the motor manufacturer for the permissible range of continuous speed. To operate at more than 60Hz, confirm the machine , s ability to withstand the centrifugal force generated.
Power transmission mechanism
The allowable rotation range of continuous drive varies depending on the lubrication method or motor manufacturer.(Particularly in case of oil lubrication, pay attention to the low frequency range.)
Application to special motors
Gear motor
For use of a brake-equipped motor, be sure to connect the braking power supply from the primary side of the inverter.Brake-equipped motorThere are different kinds of pole-change motors (constant output characteristic type, constant torque characteristic type, etc.), with different rated current values. In motor selection, check the maximum allowable current for each motor of a different pole count. At the time of pole changing, be sure to stop the motor. Also see: Application to the 400V-class motor.
Pole-change motor
The rated current of a submersible motor is significantly larger than that of the general-purpose motor. In inverter selection, be sure to check the rated current of the motor.Submersible motor
Inverter drive is not suitable for a safety-enhanced explosion-proof type motor. The inverter should be used in combination with a pressure-proof explosion-proof type of motor.*Explosion-proof verification is not available for X200 Series.
Explosion-proof motor
In most cases, the synchronous (MS) motor and the high-speed (HFM) motor are designed and manufactured to meet the specifications suitable for a connected machine. As to proper inverter selection, consult the manufacturer.
Synchronous (MS) motorHigh-speed (HFM) motor
A single-phase motor is not suitable for variable-speed operation by an inverter drive. Therefore, use a three-phase motor.Single-phase motor
Application to the 400V-class motor
A system applying a voltage-type PWM inverter with IGBT may have surge voltage at the motor terminals resulting from the cable constants including the cable length and the cable laying method. Depending on the surge current magnification, the motor coil insulation may be degraded. In particular, when a 400V-class motor is used, a longer cable is used, and critical loss can occur, take the following countermeasures:(1) install the LCR filter between the inverter and the motor,(2) install the AC reactor between the inverter and the motor, or(3) enhance the insulation of the motor coil.
Notes on UseDrive
Run or stop of the inverter must be done with the keys on the operator panel or through the control circuit terminal. Do not operate by installing a electromagnetic contactor (MC) in the main circuit.Run/Stop
When the protective function is operating or the power supply stops, the motor enters the free run stop state. When an emergency stop is required or when the motor should be kept stopped, use of a mechanical brake should be considered.Emergency motor stop
A max. 400Hz can be selected on the X200 Series. However, a two-pole motor can attain up to approx. 24,000 rpm, which is extremely dangerous. Therefore, carefully make selection and settings by checking the mechanical strength of the motor and connected machines. Consult the motor manufacturer when it is necessary to drive a standard (general-purpose)motor above 60Hz. A full line of high-speed motors is available from Hitachi.
High-frequency run
About the load of a frequent repetition use
About the use in highlands beyond 1,000m above sea level
About frequent repetition use (crane, elevator, press, washing machine) , a power semiconductor (IGBT, a rectification diode, thyristor) in the inverter may come to remarkably have a short life by heat exhaustion.The life can be prolonged by lower a load electric current. Lengthen acceleration / deceleration time. Lower carrier frequency. or increasing capacity of the inverter.
When the standard inverter is used at a place beyond 1,000m above sea level because it cool heating element with air, please be careful as follows. But please inquire for the highlands more than 2,500m separately.1. Reduction of the inverter rating current
The density of air decreases by 1% whenever rising by 100m when the altitude exceeds 1000m. For example, in the case of 2,000m above sea level, it is {2,000(m) -Because it becomes 1,000(m)}/100(m) X {-1(%)} =-10(%), please use with 10(%) reduction (0.9* inverter rating electric current) of a rating current of the inverter.
2. Reduction of the breakdown voltageWhen using inverter at a place beyond 1,000m, the breakdown voltage decreases as follows. 1,000m or less:1.00/1,500m:0.95/2,000m:0.90/2,500m:0.85. But please do not perform the withstand pressure test as mention of the instruction manual.
Unbalance factor of voltage =
VRS-(VRS+VST+VTR)/3(VRS+VST+VTR)/3
Max. line voltage (min.) - Mean line voltageMean line voltage x100
= x100 = x100 =1.5(%)205-202
202
16
Installation location and operating environmentAvoid installation in areas of high temperature, excessive humidity, or where moisture can easily collect, as well as areas that are dusty, subject to corrosive gasses, mist of liquid for grinding, or salt. Install the inverter away from direct sunlight in a well-ventilated room that is free of vibration. The inverter can be operated in the ambient temperature range from -10 to 50˚C.(Carrier frequency and output current must be reduced in the range of 40 to 50˚C.)
In the following examples involving a general-purpose inverter, a large peak current flows on the main power supply side, and is able to destroy the converter module. Where such situations are foreseen or the connected equipment must be highly reliable, install an AC reactor between the power supply and the inverter. Also, where influence of indirect lightning strike is possible,install a lightning conductor.(A) The unbalance factor of the power supply is 3% or higher. (Note)(B) The power supply capacity is at least 10 times greater than the inverter capacity (the power supply capacity is 500 kVA or more).(C) Abrupt power supply changes are expected. Examples: (1) Several inverters are interconnected with a short bus. (2) A thyristor converter and an inverter are interconnected with a short bus. (3) An installed phase advance capacitor opens and closes.In cases (A), (B) and (C), it is recommended to install an AC reactor on the main power supply side.Note: Example calculation with VRS = 205V, VST = 201V, VTR = 200V VRS : R-S line voltage, VST : S-T line voltage, VTR : T-R line voltage
An inverter run by a private power generator may overheat the generator or suffer from a deformed output voltage waveform of the generator. Generally, the generator capacity should be five times that of the inverter (kVA) in a PWM control system, or six times greater in a PAM control system.
Main power supply
Installation of anAC reactor on the
input side
Using a private powergenerator
(1) Be sure to connect main power wires with R(L1), S(L2), and T(L3) terminals (input) and motor wires to U(T1), V(T2), and W(T3) terminals (output). (Incorrect connection will cause an immediate failure.)
(2) Be sure to provide a grounding connection with the ground terminal ( ).When an electromagnetic contactor is installed between the inverter and the motor, do not perform on-off switching during running operation.
When used with standard applicable output motors (standard three-phase squirrel-cage four-pole motors), the X200 Series does not need a thermal relay for motor protection due to the internal electronic protective circuit. A thermal relay, however, should be used:• during continuous running outside a range of 30 to 60 Hz.• for motors exceeding the range of electronic thermal adjustment (rated current). • when several motors are driven by the same inverter; install a thermal relay for each motor. • The RC value of the thermal relay should be more than 1.1 times the rated current of the motor. Where the wiring length is 10 m or more, the thermal relay tends to turn off readily. In this case, provide an AC reactor on the output side or use a current sensor.
Install a circuit breaker on the main power input side to protect inverter wiring and ensure personal safety. Choose an inverter-compatible circuit breaker. The conventional type may malfunction due to harmonics from the inverter. For more information, consult the circuit breaker manufacturer.
Notes on Peripheral Equipment Selection
Wiring connections
Wiring between
inverter andmotor
Installing a circuit breaker
The wiring distance between the inverter and the remote operator panel should be 20 meters or less. When this distance isexceeded, use CVD-E (current-voltage converter) or RCD-E (remote control device). Shielded cable should be used on thewiring. Beware of voltage drops on main circuit wires. (A large voltage drop reduces torque.)
IWiring distance
If the earth leakage relay (or earth leakage breaker) is used, it should have a sensitivity level of 15 mA or more (per inverter).Earth leakage relayDo not use a capacitor for power factor improvement between the inverter and the motor because the high-frequency components of the inverter output may overheat or damage the capacitor.Phase advance capacitor
Electromagnetic contactor
Thermal relay
High-frequency Noise and Leakage Current(1) High-frequency components are included in the input/output of the inverter main circuit, and they may cause interference in a transmitter, radio, or sensor if used near the inverter. The interference can be minimized by attaching noise filters (option) in the inverter circuitry.(2) The switching action of an inverter causes an increase in leakage current. Be sure to ground the inverter and the motor.
Lifetime of Primary PartsBecause a DC bus capacitor deteriorates as it undergoes internal chemical reaction, it should normally be replaced every five years. Be aware, however, that its life expectancy is considerably shorter when the inverter is subjected to such adverse factors as high temperatures or heavy loads exceeding the rated current of the inverter.The approximate lifetime of the capacitor is as shown in the figure at the right when it is used 12 hours daily (according to the " Instructions for Periodic Inspection of General-Purpose Inverter " (JEMA).)Also, such moving parts as a cooling fan should be replaced. Maintenance inspection and parts replacement must beperformed by only specified trained personnel.
50
40
30
2.5 5 10Capacltor lifetime(years)A
mbi
ent t
empe
ratu
re(˚
C)
Precaution for Correct Usage• Before use, be sure to read through the Instruction Manual to insure proper use of the inverter.• Note that the inverter requires electrical wiring; a trained specialist should carry out the wiring.• The inverter in this catalog is designed for general industrial applications. For special applications in fields such as aircraft, outer space, nuclear power, electrical power, transport vehicles, clinics, and underwater equipment, please consult with us in advance.• For application in a facility where human life is involved or serious losses may occur, make sure to provide safety devices to avoid a serious accident.• The inverter is intended for use with a three-phase AC motor. For use with a load other than this, please consult with us.
Information in this brochure is subject to change without notice.