sls-10

2
Server Load Simulator Model SLS-10 10 KW CFM-Trim Control for Delta-T Adjustment Standard 9U Rack Design Overtemperature Protection Convenient Handles for Sliding in and out of Server Racks Touch Safe Terminal Connections power test solutions The SLS-10 is designed for data cen- ter heat-load testing and server place- ment during the data center design and construction stage. In today’s high power data center environments, it is absolutely critical to design and test the facility HVAC cooling system prior to installation of the actual serv- ers themselves. The Avtron Server Load Simulator mimics the exact heat output of the actual server under load and has the same form factor and di- mensions as the servers themselves, whether they are conventional low power density servers (2-6 KW per rack) or the new high-density blade servers (up to 24 KW per rack). This real-world heat loading using actual Avtron Server Load Simulators is far more accurate and precise than using conventional HVAC software simula- tion (without any heat loading). Potential heating problems can be easily identified and corrected using the SLS-10 Server Load Simulator. The Avtron Server Load Simulator is rated for single phase 120, 208, 230, or 240 VAC input with a power output up to 10 KW total. The 10 KW total rating of the SLS-10 (in 240 VAC mode) is greater than most competi- tive units! This saves time and money when performing a data center server load simulation since fewer units are needed. The SLS-10 load simulator is 9U (15.75" [400]) high and designed to fit into an industry standard rack(s). Cold-side blanking panels (to prevent recirculation of hot air) are available as an option. The Avtron SLS-10 is self-cooled with two integral cooling systems (one per channel) which operate from a 120 VAC, single phase external power supply or from internal load power. The SLS-10 draws in cool air through it’s front side from the “Cold Aisle”. The hot air exhaust is then discharged through the rear of the unit into the “Hot Aisle”. The unit also features CFM “Trim-Control” to decrease the Delta-T across the unit. Legendary Avtron quality combined with simple operation and mainte- nance will provide years of trouble free service. Avtron’s extensive line of Load Bank and Industrial Resistor Products are solid performers used throughout the world. For total technical support or additional information, please contact Avtron at (216) 573-7600 or LBsales@ on.com. The Avtron Server Load Simulator Model SLS-10 is a self-contained, rack-mounted unit that simulates the actual heat loading of a computer server.

description

skripta

Transcript of sls-10

  • Server Load Simulator Model SLS-10 10 KW

    CFM-Trim Control for Delta-T Adjustment

    Standard 9U Rack Design

    Overtemperature Protection

    Convenient Handles for Sliding in and out of Server Racks

    Touch Safe Terminal Connections

    power test solutions

    The SLS-10 is designed for data cen-ter heat-load testing and server place-ment during the data center design and construction stage. In todays high power data center environments, it is absolutely critical to design and test the facility HVAC cooling system prior to installation of the actual serv-ers themselves. The Avtron Server Load Simulator mimics the exact heat output of the actual server under load and has the same form factor and di-mensions as the servers themselves, whether they are conventional low power density servers (2-6 KW per rack) or the new high-density blade servers (up to 24 KW per rack). This real-world heat loading using actual Avtron Server Load Simulators is far more accurate and precise than using conventional HVAC software simula-tion (without any heat loading). Potential heating problems can be

    easily identified and corrected using the SLS-10 Server Load Simulator.

    The Avtron Server Load Simulator is rated for single phase 120, 208, 230, or 240 VAC input with a power output up to 10 KW total. The 10 KW total rating of the SLS-10 (in 240 VAC mode) is greater than most competi-tive units! This saves time and money when performing a data center server load simulation since fewer units are needed. The SLS-10 load simulator is 9U (15.75" [400]) high and designed to fit into an industry standard rack(s). Cold-side blanking panels (to prevent recirculation of hot air) are available as an option.

    The Avtron SLS-10 is self-cooled with two integral cooling systems (one per channel) which operate from a 120 VAC, single phase external power

    supply or from internal load power. The SLS-10 draws in cool air through its front side from the Cold Aisle. The hot air exhaust is then discharged through the rear of the unit into the Hot Aisle. The unit also features CFM Trim-Control to decrease the Delta-T across the unit.

    Legendary Avtron quality combined with simple operation and mainte-nance will provide years of trouble free service.

    Avtrons extensive line of Load Bank and Industrial Resis tor Products are solid performers used throughout the world.

    For total technical support or additional information, please contact Avtron at (216) 573-7600 or [email protected].

    The Avtron Server Load Simulator Model SLS-10 is a self-contained, rack-mounted unit that simulates the actual heat loading of a computer server.

  • 19.00 [483.00]18.250 [464.00] 1.50 [38.00]

    15.75[400.00]

    6.375 [161.00]

    6.375 [161.00]

    0.125R [3] TYP 6 PLACES 1.62 [41.00] 23.50 [596.00] MAX

    ON

    0

    MASTER LOAD

    0

    STEP 1

    0

    STEP 2

    0

    STEP 3

    OVERTEMP

    CHANNEL A

    +200+0+CFM TRIM

    ON

    +CFM TRIM+0 +200

    OVERTEMP

    STEP 3

    0

    STEP 2

    0

    STEP 1

    0

    MASTER LOAD

    0

    1

    1

    1

    1 1

    1

    1

    1

    CHANNEL B 654321 1 2

    CHANNEL ATB1 TB2

    211 2 3 4 5 6

    TB3 CHANNEL B TB4 SLS-10

    RATING: 10KW @ 230V, 2 CHANNEL

    SCHEMATIC DWG: D50714

    SERVER LOAD SIMULATORMODEL/SYSTEM: SLS-10-D50687

    SCCR RATING: 5KA RMS SYMMETRICAL

    SERIAL NUMBER:

    SPECIFICATIONS:

    CHANNELS TOTAL: 2

    INPUTS per CHANNEL: 1

    RATINGS per CHANNEL (multiply x2 for TOTAL LOAD):

    STEP 120 VAC* 208 VAC* 230 VAC* 240 VAC*

    1 529 844 1035 1173

    2 1026 1706 2141 2382

    3 1030 1683 2117 2340

    1+2 1469 2545 3167 3528

    1+3 1469 2556 3170 3500

    2+3 1860 3420 4231 4669

    1+2+3 2202 4277 5288 5796

    *Measured Values Voltage changes at input accounts for non-adding steps.

    Server Load Simulator Model SLS-10

    6255 Halle Drive Cleveland, Ohio, U.S.A. 44125-4615 216.573.7600 FAX 216.573.5953 www.avtronloadbank.com [email protected] Bulletin 445 Rev. -

    OUTLINE DRAWING:

    LOAD VOLTAGE (VAC): 120, 208, 230, 240 (channels can operate with independent voltages i.e.; Channel 1 can have 120 V ap-plied and Channel 2 can have 240 V applied.)

    SAFETY FEATURES: Touch safe terminal connections, overtemperature protection, control circuit fusing, and automatic fan-run circuit for element cooling at shut-down.

    OPTIONS: Cold-side blanking panel 9U (15.75 [400]) high.

    All dimensions are in inches [millimeters]. Specifications subject to change without notice.

    Quality System Certified to ISO 9001