SION Vacuum Circuit-Breakers - w3.siemens.com.cn · integration in all customary medium-voltage ......

64

Transcript of SION Vacuum Circuit-Breakers - w3.siemens.com.cn · integration in all customary medium-voltage ......

Page 1: SION Vacuum Circuit-Breakers - w3.siemens.com.cn · integration in all customary medium-voltage ... transformers, capacitors, generators, filter circuits ... The operating mechanism
Page 2: SION Vacuum Circuit-Breakers - w3.siemens.com.cn · integration in all customary medium-voltage ... transformers, capacitors, generators, filter circuits ... The operating mechanism

SION Vacuum Circuit-Breakers

R-HG

11-1

72.ti

f

2 Siemens HG 11.02 · 2006

Page 3: SION Vacuum Circuit-Breakers - w3.siemens.com.cn · integration in all customary medium-voltage ... transformers, capacitors, generators, filter circuits ... The operating mechanism

2

1

3

4

3Siemens HG 11.02 · 2006

SION VacuumCircuit-Breakers

Medium-Voltage EquipmentCatalog HG 11.02 · 2006

© Siemens AG 2006

Contents Page

DescriptionGeneral

Construction and mode of operation, standards

Ambient conditions,current carrying capacity and dielectric strength

Product range overview and basic equipment

56

7

10

11

Equipment SelectionOrdering data and configuration example

Selection of basic types, standard circuit-breakers

Secondary equipment for standard circuit-breakers

Selection of basic types, slide-in modules

Secondary equipment for slide-in modules

Accessories and spare parts

1314

15

23

28

32

37

Technical DataElectrical data, dimensions and weights:

Voltage levels 7.2 kV, 12 kV, 17.5 kV

Voltage level 24 kV

Operating times, short-circuit protectionof motors, consumption data of releases

Circuit diagrams

41

42

56

59

60

AnnexInquiry form

Configuration instructions

Configuration aid

6162

63

SION Vacuum Circuit-Breakers Contents

Foldout page

Page 4: SION Vacuum Circuit-Breakers - w3.siemens.com.cn · integration in all customary medium-voltage ... transformers, capacitors, generators, filter circuits ... The operating mechanism

4 Siemens HG 11.02 · 2006

R-HG

11-1

73.ti

f

SION Vacuum Circuit-Breakers

Page 5: SION Vacuum Circuit-Breakers - w3.siemens.com.cn · integration in all customary medium-voltage ... transformers, capacitors, generators, filter circuits ... The operating mechanism

1

Siemens HG 11.02 · 2006 5

DescriptionContents

Industrial application: Refinery

Contents Page

Description

General

Construction and mode of operation:

Switching medium

Pole assemblies

Operating mechanism

Trip-free mechanism

Releases

Closing / Circuit-breaker tripping signal

Interlocking

Low-voltage interface

Slide-in module

Standards

Ambient conditions

Current carrying capacity

Dielectric strength

Product range overview and basic equipment

5

6

7

7

7

7

8

8

8

8

9

9

10

10

10

11

R-HG

11-1

74.ti

f

SION Vacuum Circuit-Breakers

Page 6: SION Vacuum Circuit-Breakers - w3.siemens.com.cn · integration in all customary medium-voltage ... transformers, capacitors, generators, filter circuits ... The operating mechanism

1

Siemens HG 11.02 · 20066

SION vacuum circuit-breaker from 7.2 to 24 kV – The Innovative

Our comprehensive range of standard circuit-breakers offersa wide selection for pole-center distances and widths acrossflats as well as various built-in accessories packages forvoltage levels from 7.2 to 24 kV. The drawout element,contact arms, contact systems and bushings enable easyintegration in all customary medium-voltage switchgeartypes. Identical dimensions and connection dimensionsacross several voltage levels reduce planning costs and thediversity of panel versions. High reliability and availabilityare just as much a matter of course as 10,000 maintenance-free operating cycles.

The slide-in module contains all components required forthe circuit-breaker compartment of a panel. It consists of thecircuit-breaker on a drawout element with contact arms,fitted in a cartridge with side and rear walls. The module isequipped with bushings, fixed contacts, shutters and theshutter mechanism. The surfaces of the side and rear wallsform the tested connection compartment.

SION vacuum circuit-breakers control all switchingduties in medium-voltage distribution systems and aresuitable for installation in all customary air-insulatedmedium-voltage switchgear types. They are applicablefor operation of e.g. overhead lines, cables, transformers,

capacitors, generators, filter circuits, motors andreactors. The comprehensive installation accessoriesenable easy integration in the panel and form –maximally equipped as a slide-in module – almost thecomplete circuit-breaker compartment.

SION standard circuit-breaker – the variableR-

HG11

-167

.eps

SION slide-in module – the complete

R-HG

11-1

68.e

ps

DescriptionGeneral

SION Vacuum Circuit-Breakers

Page 7: SION Vacuum Circuit-Breakers - w3.siemens.com.cn · integration in all customary medium-voltage ... transformers, capacitors, generators, filter circuits ... The operating mechanism

1

Siemens HG 11.02 · 2006 7

Switching medium

The vacuum switching technology of the vacuum interrup-ters, which has been proven for 30 years, serves as arc-quenching principle.

Pole assemblies

The pole assemblies consist of the vacuum interrupters andthe pole shells. The vacuum interrupters are air-insulatedand freely accessible. The pole assemblies are fixed on themounting plate of the operating mechanism and supportedby means of the pole shell. The vacuum interrupter (3) ismounted rigidly to the upper interrupter support. The lowerpart of the interrupter is guided in the lower interruptersupport, allowing axial movement. The pole shell (4) absorbsthe external forces resulting from switching operations andthe contact pressure.

Operating mechanism

The whole operating mechanism is mounted on its mount-ing plate, including the motor, releases, indicators andactuating devices.

Stored-energy operating mechanism

The operating mechanism is a stored-energy spring mechan-ism. The force is transmitted from the operating mechan-ism to the pole assemblies via operating levers. The closingspring can be charged either electrically or manually andlatches automatically in when charging is complete. Theclosing spring acts as the stored-energy mechanism.

To close the breaker, the closing spring can be unlatchedeither mechanically by means of the local “ON” pushbuttonor electrically by remote control. The closing spring chargesthe contact-pressure / opening springs as the breaker closes.The now discharged closing spring will be charged againautomatically by the mechanism motor.

The breaker is now capable of performing the OPEN – CLOSE– OPEN operating sequence that is required for an unsuc-cessful auto-reclosing operation. All stored-energy mecha-nisms perform the switching duties of synchronizing andrapid load transfer as well as auto-reclosing.

Trip-free mechanism

In the event of an opening command being given after aclosing operation has been initiated, the moving contactsreturn to the open position and remain there even if theclosing command is sustained. This means that the contactsof the vacuum circuit-breakers are momentarily in the closedposition.

The motors for charging the closing spring operate inshort-time duty. Therefore the voltage and power con-sumption might differ from the data of the rating plate.

�����������

�����������

�����������

��

1 Separating shellto the operatingmechanism

2 Upper connection

3 Interrupter

4 Pole shell

5 Lower connection

6 Bell-type insulator

Vacuum circuit-breaker3AE1217.5 kV / 25 kA /1250 A

Pole structure

Front view

1 Auxiliary switch

2 1st release

3 Terminal strip

4 Motor

5 Closing solenoid

6 Closing spring

7 Gear

Operating mechanismwithout cover

1 Cover of low-voltageinterface

2 Central control board

R-HG

11-1

70.e

ps

DescriptionConstruction and mode of operation

SION Vacuum Circuit-Breakers

Page 8: SION Vacuum Circuit-Breakers - w3.siemens.com.cn · integration in all customary medium-voltage ... transformers, capacitors, generators, filter circuits ... The operating mechanism

1

Siemens HG 11.02 · 20068

Releases

A release is a device which transfers commands from anexternal source, such as a control room, to the latchingmechanism of the circuit-breaker so that it can be opened orclosed. The releases are designed for short-time duty up to1 minute and are reset internally. The various types ofreleases available are described in detail below:

• The closing solenoid unlatches the charged closing springof the vacuum circuit-breaker, closing it by electrical means.

• Shunt releases are used for automatic tripping of vacuumcircuit-breakers by suitable protection relays and for delib-erate tripping by electrical means. They are intended forconnection to an external power supply (DC or AC voltage)but, in special cases, may also be connected to a voltagetransformer for manual operation.

• Current-transformer operated releases comprise astored-energy mechanism, an unlatching mechanism, andan electromagnetic system. They are used when there is noexternal source of auxiliary power (e.g. a battery). Trippingis effected by means of a protection relay (e.g. overcurrent-time protection) acting on the current-transformer operatedrelease.

• Undervoltage releases comprise a stored-energy mecha-nism, an unlatching mechanism and an electromagneticsystem which is permanently connected to the secondary orauxiliary voltage while the vacuum circuit-breaker is closed.If the voltage falls below a predetermined value, unlatchingof the release is enabled and the circuit-breaker is openedvia the stored-energy mechanism.

The maximum equipment are 2 freely selected releases. Forrelease combinations, refer to page 23 or page 32. For con-sumption data, refer to page 59.

Closing / Circuit-breaker tripping signal

In the standard version, the vacuum circuit-breakers can beremote-closed electrically. In addition, they can be mechani-cally closed locally by direct unlatching of the closing spring.

If constant CLOSE and OPEN commands are present at thevacuum circuit-breaker at the same time, the vacuum circuit-breaker will return to the open position after closing. It re-mains in this position until a new CLOSE command is given.In this manner, continual closing and opening (= “pumping”)is prevented.

The charging status of the closing spring in the vacuumcircuit-breaker can be interrogated electrically by means ofthe position switch.

The NO contact S6 makes brief contact while the circuit-breaker is opening, and this is often used to operate ahazard-warning system which, however, is only allowed torespond to automatic tripping of the circuit-breaker. There-fore, the signal from the NO contact must be interruptedwhen the circuit-breaker is being opened intentionally. Thisis accomplished under local control with the cut-out switchS7 that is connected in series with the NO contact.

For the corresponding circuit diagrams, refer to page 60.

Interlocking

Mechanical interlocking

At the interface of the mechanical interlocking of thevacuum circuit-breaker, sensors on the switchgear side cancheck the switch position and prevent the associated dis-connector from being closed while the vacuum circuit-breaker is closed. The system also prevents the vacuumcircuit-breaker from being closed while the associateddisconnector is in a faulty position.

Vacuum circuit-breakers mounted on drawout elements aremechanically interlocked, with the result that the handle forracking the drawout element can only be inserted in the“OPEN” position. The lock of the drawout element can onlybe released in the disconnected position by operating thepushing handles.

If the vacuum circuit-breaker on the drawout element is inan intermediate position (neither in the service nor in thedisconnected position), operation is not possible due to themechanical interlocking.

Electrical interlocking

The auxiliary and signaling contacts which show the switchposition of the vacuum circuit-breaker or the position of thedrawout element can be integrated in the switchgear inter-locking concept in order to exclude impermissible switchingsequences.

Low-voltage interface

The separate cover enables easy access to the low-voltageinterface. All possible customer-side control and signalingconnections are concentrated here.

DescriptionConstruction and mode of operation

SION Vacuum Circuit-Breakers

Page 9: SION Vacuum Circuit-Breakers - w3.siemens.com.cn · integration in all customary medium-voltage ... transformers, capacitors, generators, filter circuits ... The operating mechanism

1

Siemens HG 11.02 · 2006 9

Slide-in module

Besides the circuit-breaker installation equipment available forstandard circuit-breakers by means of the packages for thedrawout element, contact arms, fixed contacts and bushings,it is also possible to supply a complete slide-in module.

The slide-in module contains all necessary components forthe circuit-breaker compartment of a panel. It consists of thecircuit-breaker on a drawout element with contact arms,mounted in a cartridge with side and rear walls, equippedwith bushings, fixed contacts, shutters and shutter mecha-nism. The surfaces of the side and rear walls form the testedconnection compartment.

The vacuum circuit-breaker on the drawout element isracked into the cartridge with the associated handle by therotary movement of the spindle. The shutter mechanismis controlled by lateral gates, and the shutters are openedfor contacting. Signals for the service and disconnectedpositions are transmitted to the module connector at thelow-voltage interface of the vacuum circuit-breaker via theposition switches of the drawout element.

Slide-in module

1 Contact system

2 Fixed contact

3 Shutter

4 Bushing

5 Cartridge

R-HG

11-1

71.e

ps

6 Contact arm

7 Low-voltage interface

8 Vacuum circuit-breaker

9 Drawout element

DescriptionConstruction and mode of operation

Standards

The vacuum circuit-breakers conform to the followingstandards:

• IEC 60 694

• IEC 62 271-100

All SION vacuum circuit-breakers fulfil the enduranceclasses E2, M2 and C2 according to IEC 62 271-100.

The slide-in modules have been tested according to

• IEC 62 271-200 regarding

– Dielectric strength

– Temperature rise

– Switching capacity.

SION Vacuum Circuit-Breakers

Page 10: SION Vacuum Circuit-Breakers - w3.siemens.com.cn · integration in all customary medium-voltage ... transformers, capacitors, generators, filter circuits ... The operating mechanism

1

Siemens HG 11.02 · 200610

Ambient conditions

Condensation can occasionally occur under the ambientconditions shown opposite.

SION vacuum circuit-breakers are suitable for use in thefollowing climatic classes according to IEC 60 721, Part 3-3:

Climatic ambient conditions: Class 3K41)

Biological ambient conditions: Class 3B1

Mechanical ambient conditions: Class 3M2

Chemically-active substances: Class 3C22)

Mechanically-active substances: Class 3C23)

1) Low temperature limit: - 5 °C

2) Without icing and wind-driven precipitation

3) Restriction: Clean insulation parts

Current carrying capacity

The rated normal currents specified in the diagram havebeen defined according to IEC 62 271-100 for an ambienttemperature of + 40 °C and apply to open switchgear.

For enclosed switchgear the data of the switchgearmanufacturer applies.

At ambient temperatures below + 40 °C, higher normalcurrents can be carried (see diagram):

Characteristics curve 1 = Rated normal current 800 ACharacteristics curve 2 = Rated normal current 1250 ACharacteristics curve 3 = Rated normal current 2000 ACharacteristics curve 4 = Rated normal current 2500 ACharacteristics curve 5 = Rated normal current 3150 A

Dielectric strength

The dielectric strength of air insulation decreases withincreasing altitude due to low air density. According toIEC 60 694, the rated lightning impulse withstand voltagevalues specified in the chapter “Technical Data” apply to asite altitude of 1000 m above sea level. For an altitudeabove 1000 m, the insulation level must be correctedaccording to the opposite diagram.

The characteristic shown applies to the rated short-durationpower-frequency withstand voltage and the rated lightningimpulse withstand voltage.

To select the devices, the following applies:

U W U0 x Ka

U Rated withstand voltage under standard reference atmosphere

U0 Rated withstand voltage requested for the place of installation

Ka Altitude correction factor according to the opposite diagram

Example

For a requested rated lightning impulse withstand voltageof 75 kV at an altitude of 2500 m, an insulation level of90 kV under standard reference atmosphere is required asa minimum:

90 kV W 75 kV x 1.2

����

����

��� ������������ ������������

����

����

� ���

����������

����

��������

����

����

����

����

����

����

����

����� �� ����

��������������

����� ��

�!"�����

���������"

����

����������������

�#��

�#��

�#��

�#��

�#������ ���� �����

�#��

$���!�����

�!�����" ��

"�� �%�"� �

DescriptionAmbient conditions, current carrying capacity and dielectric strength

SION Vacuum Circuit-Breakers

Page 11: SION Vacuum Circuit-Breakers - w3.siemens.com.cn · integration in all customary medium-voltage ... transformers, capacitors, generators, filter circuits ... The operating mechanism

1

Siemens HG 11.02 · 2006 11

Product range overview

Pole center distance (in mm)

150 160 210 275

Width across flats (in mm)

Type kV kA A 205 275 310 205 275 310 205 275 310 310

3AE10 7.2 16 800/1250 � �� �� � � � � �� ��

20 800/1250 � �� �� � � � � �� ��

25 800/1250 � �� �� � � � � �� ��

25 2000 ��

31.5 800/1250 � �� �� � � � � �� ��

31.5 2000/2500 ��

40 1250/2000 ��

40 2500/3150 ��

3AE11 12 16 800/1250 � �� �� � � � � �� ��

20 800/1250 � �� �� � � � � �� ��

25 800/1250 � �� �� � � � � �� ��

25 2000/2500 ��

31.5 800/1250 � �� �� � � � � �� ��

31.5 2000/2500 ��

40 1250/2000 ��

40 2500/3150 ��

3AE12 17.5 12.5 800/1250 � �� �� � � � � �� ��

16 800/1250 � �� �� � � � � �� ��

25 800/1250 � �� �� � � � � �� ��

25 2000/2500 ��

31.5 800/1250 � �� �� � � � � �� ��

31.5 2000/2500 ��

40 1250/2000 ��

40 2500/3150 ��

3AE13 24 12.5 800/1250 ��

16 800/1250/2000 �� ��

20 800/1250 �� ��

20 2000/2500 �� ��

25 800/1250 �� ��

25 2000/2500 �� ��

� Standard circuit-breaker (fixed-mounted/drawout version with installation accessories) � Slide-in module

DescriptionProduct range overview and basic equipment

Rate

dvo

ltage

Rate

dsh

ort-

circ

uitb

reak

ing

curr

ent

Rate

dno

rmal

curr

ent

Features Standard Alternative Remarks

Operating mechanism Electrical operating mechanism – Also for manual operation

Closing Closing solenoid andelectrical manual closing

– –

1st release Shunt release Undervoltage release,c.t.-operated release

2nd release Without Shunt release,undervoltage release,c.t.-operated release

Varistor circuit For W 60 V DC – For limiting switchingovervoltages

Auxiliary switch 6 NO + 6 NC 12 NO + 12 NC –

Plug connection 27-pole terminal strip 24-pole plug,64-pole plug

12 NO + 12 NC not availablewith 24-pole plug

Anti-pumping Available – –

Circuit-breaker trippingsignal

Without Possible –

Operating cycle counter Available – –

Position switches 2 – –

Mechanical interlocking Available for slide-in module Mechanical interlocking for circuit-breaker Required for slide-in module

Installation accessories Fixed-mounted With drawout element, contact arms, contactsystem, with fixed contacts and bushings,complete slide-in module

Basic equipment

SION Vacuum Circuit-Breakers

Page 12: SION Vacuum Circuit-Breakers - w3.siemens.com.cn · integration in all customary medium-voltage ... transformers, capacitors, generators, filter circuits ... The operating mechanism

12 Siemens HG 11.02 · 2006

R-HG

11-1

75.ti

f

SION Vacuum Circuit-Breakers

Page 13: SION Vacuum Circuit-Breakers - w3.siemens.com.cn · integration in all customary medium-voltage ... transformers, capacitors, generators, filter circuits ... The operating mechanism

2

13Siemens HG 11.02 · 2006

Standard circuit-breaker

Slide-in module

Contents Page

Equipment Selection

Ordering data and configuration example

Selection of basic types, standard circuit-breakers:

Voltage level 7.2 kV

Voltage level 12 kV

Voltage level 17.5 kV

Voltage level 24 kV

Secondary equipment for standard circuit-breakers

Additional equipment for standard circuit-breakers

Selection of basic types, slide-in modules:

Voltage level 7.2 kV

Voltage level 12 kV

Voltage level 17.5 kV

Voltage level 24 kV

Secondary equipment for slide-in modules

Additional equipment for slide-in modules

Accessories and spare parts

13

14

15

17

20

22

23

27

28

29

30

31

32

36

37

Equipment SelectionContents

R-HG

11-1

76.e

psR-

HG11

-168

.eps

SION Vacuum Circuit-Breakers

Page 14: SION Vacuum Circuit-Breakers - w3.siemens.com.cn · integration in all customary medium-voltage ... transformers, capacitors, generators, filter circuits ... The operating mechanism

2

14 Siemens HG 11.02 · 2006

Order number structure

The vacuum circuit-breakers consist of a primary and asecondary part. The relevant data make up the 16-digitorder number. The primary part covers the main electricaldata of the circuit-breaker poles. The secondary part coversthe auxiliary devices which are necessary for operating andcontrolling the vacuum circuit-breaker.

Order codes

Individual equipment versions, identified with 9 or Z in the9th or 16th position, are explained more in detail by a 3-digitorder code. Several order codes can be added to the ordernumber in succession and in any sequence.

Special versions (�)

In case of special versions, “-Z” is added to the order num-ber and a descriptive order code follows. If several specialversions are required, the suffix “-Z” is listed only once.If a requested special version is not in the catalog and cantherefore not be ordered via order code, it has to be identi-fied with Y 9 9 after consultation. The agreement heretois made between your responsible sales partner and theorder processing department (PTD M C S) in our SwitchgearFactory in Berlin.

Configuration example

In order to simplify the selection of the correct order numberfor the requested circuit-breaker type, you will find a con-figuration example on each side of the chapter “EquipmentSelection”. For the selection of the secondary part, alwaysthe last example of the primary part was taken over andcontinued, so that at the end of the equipment selection(pages 27 and 36) a completely configured circuit-breakerresults as an example.

On the foldout page we offer a configuring aid.Here you can fill in the order number you have deter-mined for your circuit-breaker.

a: alphabetical n: numerical

Position: 1 2 3 4 5 6 7 – 8 9 10 11 12 – 13 14 15 16 Order codes

Order No.: 3 A E n n n n – n a a n n – n a a n – � � � �

Primary part1st position Superior group

Switching devices

2nd position Main groupCircuit-breaker

3rd position SubgroupCircuit-breaker type series

4th to 8th position Basic equipmentDesign and ratingsprimary part

Secondary part9th to 16th position Secondary equipment

Operating mechanism, releases, operatingvoltages and further auxiliary equipment

Order codesGroup of 3 after the Order No.Format: a n a

Special versions (�)Initiated with “-Z”Group of 3 after the Order No.Format: a n n

Equipment SelectionOrdering data and configuration example

Example for Order No.: 3 A E 1 0 8 3 – 2 � � � � – � � � �

Order codes:

SION Vacuum Circuit-Breakers

Page 15: SION Vacuum Circuit-Breakers - w3.siemens.com.cn · integration in all customary medium-voltage ... transformers, capacitors, generators, filter circuits ... The operating mechanism

2

15Siemens HG 11.02 · 2006

7.2 kV Position: 1 2 3 4 5 6 7 – 8 9 10 11 12 – 13 14 15 16 Order codes

50/60 Hz Order No.: 3 A E 1 � � � – � � � � � – � � � � – � � � �

Ur Up Ud Isc Ima Ir

kV kV kV kA kA mm mm A

7.2 60 20 16 40/42 210 310 800 3 A E 1 0 8 2 – 1310 1250 3 A E 1 0 8 2 – 2275 800 3 A E 1 0 7 2 – 1275 1250 3 A E 1 0 7 2 – 2205 800 3 A E 1 0 6 2 – 1205 1250 3 A E 1 0 6 2 – 2

160 310 800 3 A E 1 0 5 2 – 1310 1250 3 A E 1 0 5 2 – 2275 800 3 A E 1 0 4 2 – 1275 1250 3 A E 1 0 4 2 – 2205 800 3 A E 1 0 3 2 – 1205 1250 3 A E 1 0 3 2 – 2

150 310 800 3 A E 1 0 2 2 – 1310 1250 3 A E 1 0 2 2 – 2275 800 3 A E 1 0 1 2 – 1275 1250 3 A E 1 0 1 2 – 2205 800 3 A E 1 0 0 2 – 1205 1250 3 A E 1 0 0 2 – 2

7.2 60 20 20 50/52 210 310 800 3 A E 1 0 8 3 – 1310 1250 3 A E 1 0 8 3 – 2275 800 3 A E 1 0 7 3 – 1275 1250 3 A E 1 0 7 3 – 2205 800 3 A E 1 0 6 3 – 1205 1250 3 A E 1 0 6 3 – 2

160 310 800 3 A E 1 0 5 3 – 1310 1250 3 A E 1 0 5 3 – 2275 800 3 A E 1 0 4 3 – 1275 1250 3 A E 1 0 4 3 – 2205 800 3 A E 1 0 3 3 – 1205 1250 3 A E 1 0 3 3 – 2

150 310 800 3 A E 1 0 2 3 – 1310 1250 3 A E 1 0 2 3 – 2275 800 3 A E 1 0 1 3 – 1275 1250 3 A E 1 0 1 3 – 2205 800 3 A E 1 0 0 3 – 1205 1250 3 A E 1 0 0 3 – 2

Configuration example

SION vacuum circuit-breaker 3 A E 1

Rated voltage Ur = 7.2 kV, 50/60 Hz

Rated lightning impulse withstand voltage Up = 60 kV

Rated short-circuit breaking current Isc = 20 kA

Rated normal current Ir = 1250 A

Pole-center distance = 210 mm, width across flats = 310 mm 0 8 3 – 2

Example for Order No.: 3 A E 1 0 8 3 – 2 � � � � – � � � �

Order codes:

See

page

23

See

page

23

See

page

24

See

page

24

See

page

25

See

page

25

See

page

26

See

page

26

See

page

27

Rate

dvo

ltage

Rate

dlig

htni

ngim

puls

ew

ithst

and

volta

ge

Rate

dsh

ort-

dura

tion

pow

er-f

requ

ency

with

stan

dvo

ltage

Rate

dsh

ort-

circ

uit

brea

king

curr

ent

at36

%A

Cco

mpo

nent

Rate

dsh

ort-

circ

uit

mak

ing

curr

ent

(at5

0/60

Hz)

Pole

-cen

terd

ista

nce

Wid

thac

ross

flats

Rate

dno

rmal

curr

ent

Equipment SelectionSelection of basic types, standard circuit-breakers

SION Vacuum Circuit-Breakers

Page 16: SION Vacuum Circuit-Breakers - w3.siemens.com.cn · integration in all customary medium-voltage ... transformers, capacitors, generators, filter circuits ... The operating mechanism

2

16 Siemens HG 11.02 · 2006

7.2 kV Position: 1 2 3 4 5 6 7 – 8 9 10 11 12 – 13 14 15 16 Order codes

50/60 Hz Order No.: 3 A E 1 � � � – � � � � � – � � � � – � � � �

Ur Up Ud Isc Ima Ir

kV kV kV kA kA mm mm A

7.2 60 20 25 63/65 210 310 800 3 A E 1 0 8 4 – 1310 1250 3 A E 1 0 8 4 – 2310 2000 3 A E 1 0 8 4 – 4275 800 3 A E 1 0 7 4 – 1275 1250 3 A E 1 0 7 4 – 2205 800 3 A E 1 0 6 4 – 1205 1250 3 A E 1 0 6 4 – 2

160 310 800 3 A E 1 0 5 4 – 1310 1250 3 A E 1 0 5 4 – 2275 800 3 A E 1 0 4 4 – 1275 1250 3 A E 1 0 4 4 – 2205 800 3 A E 1 0 3 4 – 1205 1250 3 A E 1 0 3 4 – 2

150 310 800 3 A E 1 0 2 4 – 1310 1250 3 A E 1 0 2 4 – 2275 800 3 A E 1 0 1 4 – 1275 1250 3 A E 1 0 1 4 – 2205 800 3 A E 1 0 0 4 – 1205 1250 3 A E 1 0 0 4 – 2

7.2 60 20 31.5 80/82 210 310 800 3 A E 1 0 8 5 – 1310 1250 3 A E 1 0 8 5 – 2310 2000 3 A E 1 0 8 5 – 4310 2500 3 A E 1 0 8 5 – 6275 800 3 A E 1 0 7 5 – 1275 1250 3 A E 1 0 7 5 – 2205 800 3 A E 1 0 6 5 – 1205 1250 3 A E 1 0 6 5 – 2

160 310 800 3 A E 1 0 5 5 – 1310 1250 3 A E 1 0 5 5 – 2275 800 3 A E 1 0 4 5 – 1275 1250 3 A E 1 0 4 5 – 2205 800 3 A E 1 0 3 5 – 1205 1250 3 A E 1 0 3 5 – 2

150 310 800 3 A E 1 0 2 5 – 1310 1250 3 A E 1 0 2 5 – 2275 800 3 A E 1 0 1 5 – 1275 1250 3 A E 1 0 1 5 – 2205 800 3 A E 1 0 0 5 – 1205 1250 3 A E 1 0 0 5 – 2

7.2 60 20 40 100/104 210 310 1250 3 A E 1 0 8 6 – 2310 2000 3 A E 1 0 8 6 – 4310 2500 3 A E 1 0 8 6 – 6310 3150 3 A E 1 0 8 6 – 7

Configuration example

SION vacuum circuit-breaker 3 A E 1

Rated voltage Ur = 7.2 kV, 50/60 Hz

Rated lightning impulse withstand voltage Up = 60 kV

Rated short-circuit breaking current Isc = 40 kA

Rated normal current Ir = 2000 A

Pole-center distance = 210 mm, width across flats = 310 mm 0 8 6 – 4

Example for Order No.: 3 A E 1 0 8 6 – 4 � � � � – � � � �

Order codes:

Equipment SelectionSelection of basic types, standard circuit-breakers

See

page

23

See

page

23

See

page

24

See

page

24

See

page

25

See

page

25

See

page

26

See

page

26

See

page

27

SION Vacuum Circuit-Breakers

Rate

dvo

ltage

Rate

dlig

htni

ngim

puls

ew

ithst

and

volta

ge

Rate

dsh

ort-

dura

tion

pow

er-f

requ

ency

with

stan

dvo

ltage

Rate

dsh

ort-

circ

uit

brea

king

curr

ent

at36

%A

Cco

mpo

nent

Rate

dsh

ort-

circ

uit

mak

ing

curr

ent

(at5

0/60

Hz)

Pole

-cen

terd

ista

nce

Wid

thac

ross

flats

Rate

dno

rmal

curr

ent

Page 17: SION Vacuum Circuit-Breakers - w3.siemens.com.cn · integration in all customary medium-voltage ... transformers, capacitors, generators, filter circuits ... The operating mechanism

2

17Siemens HG 11.02 · 2006

12 kV Position: 1 2 3 4 5 6 7 – 8 9 10 11 12 – 13 14 15 16 Order codes

50/60 Hz Order No.: 3 A E 1 � � � – � � � � � – � � � � – � � � �

Ur Up Ud Isc Ima Ir

kV kV kV kA kA mm mm A

12 75 28 16 40/42 210 310 800 3 A E 1 1 8 2 – 1310 1250 3 A E 1 1 8 2 – 2275 800 3 A E 1 1 7 2 – 1275 1250 3 A E 1 1 7 2 – 2205 800 3 A E 1 1 6 2 – 1205 1250 3 A E 1 1 6 2 – 2

160 310 800 3 A E 1 1 5 2 – 1310 1250 3 A E 1 1 5 2 – 2275 800 3 A E 1 1 4 2 – 1275 1250 3 A E 1 1 4 2 – 2205 800 3 A E 1 1 3 2 – 1205 1250 3 A E 1 1 3 2 – 2

150 310 800 3 A E 1 1 2 2 – 1310 1250 3 A E 1 1 2 2 – 2275 800 3 A E 1 1 1 2 – 1275 1250 3 A E 1 1 1 2 – 2205 800 3 A E 1 1 0 2 – 1205 1250 3 A E 1 1 0 2 – 2

12 75 28 20 50/52 210 310 800 3 A E 1 1 8 3 – 1310 1250 3 A E 1 1 8 3 – 2275 800 3 A E 1 1 7 3 – 1275 1250 3 A E 1 1 7 3 – 2205 800 3 A E 1 1 6 3 – 1205 1250 3 A E 1 1 6 3 – 2

160 310 800 3 A E 1 1 5 3 – 1310 1250 3 A E 1 1 5 3 – 2275 800 3 A E 1 1 4 3 – 1275 1250 3 A E 1 1 4 3 – 2205 800 3 A E 1 1 3 3 – 1205 1250 3 A E 1 1 3 3 – 2

150 310 800 3 A E 1 1 2 3 – 1310 1250 3 A E 1 1 2 3 – 2275 800 3 A E 1 1 1 3 – 1275 1250 3 A E 1 1 1 3 – 2205 800 3 A E 1 1 0 3 – 1205 1250 3 A E 1 1 0 3 – 2

Special version (available for all 12 kV standard circuit-breakers)

Ud = 42 kV – Z E 1 3

Configuration example

SION vacuum circuit-breaker 3 A E 1

Rated voltage Ur = 12 kV, 50/60 Hz

Rated lightning impulse withstand voltage Up = 75 kV

Rated short-circuit breaking current Isc = 16 kA

Rated normal current Ir = 800 A

Pole-center distance = 160 mm, width across flats = 275 mm 1 4 2 – 1

Rated short-duration power-frequency withstand voltage Ud = 42 kV – Z E 1 3

Example for Order No.: 3 A E 1 1 4 2 – 1 � � � � – � � � � – Z

Order codes: E 1 3

Equipment SelectionSelection of basic types, standard circuit-breakers

See

page

23

See

page

23

See

page

24

See

page

24

See

page

25

See

page

25

See

page

26

See

page

26

See

page

27

SION Vacuum Circuit-Breakers

Rate

dvo

ltage

Rate

dlig

htni

ngim

puls

ew

ithst

and

volta

ge

Rate

dsh

ort-

dura

tion

pow

er-f

requ

ency

with

stan

dvo

ltage

Rate

dsh

ort-

circ

uit

brea

king

curr

ent

at36

%A

Cco

mpo

nent

Rate

dsh

ort-

circ

uit

mak

ing

curr

ent

(at5

0/60

Hz)

Pole

-cen

terd

ista

nce

Wid

thac

ross

flats

Rate

dno

rmal

curr

ent

Page 18: SION Vacuum Circuit-Breakers - w3.siemens.com.cn · integration in all customary medium-voltage ... transformers, capacitors, generators, filter circuits ... The operating mechanism

2

18 Siemens HG 11.02 · 2006

12 kV Position: 1 2 3 4 5 6 7 – 8 9 10 11 12 – 13 14 15 16 Order codes

50/60 Hz Order No.: 3 A E 1 � � � – � � � � � – � � � � – � � � �

Ur Up Ud Isc Ima Ir

kV kV kV kA kA mm mm A

12 75 28 25 63/65 210 310 800 3 A E 1 1 8 4 – 1310 1250 3 A E 1 1 8 4 – 2310 2000 3 A E 1 1 8 4 – 4310 2500 3 A E 1 1 8 4 – 6275 800 3 A E 1 1 7 4 – 1275 1250 3 A E 1 1 7 4 – 2205 800 3 A E 1 1 6 4 – 1205 1250 3 A E 1 1 6 4 – 2

160 310 800 3 A E 1 1 5 4 – 1310 1250 3 A E 1 1 5 4 – 2275 800 3 A E 1 1 4 4 – 1275 1250 3 A E 1 1 4 4 – 2205 800 3 A E 1 1 3 4 – 1205 1250 3 A E 1 1 3 4 – 2

150 310 800 3 A E 1 1 2 4 – 1310 1250 3 A E 1 1 2 4 – 2275 800 3 A E 1 1 1 4 – 1275 1250 3 A E 1 1 1 4 – 2205 800 3 A E 1 1 0 4 – 1205 1250 3 A E 1 1 0 4 – 2

12 75 28 31.5 80/82 210 310 800 3 A E 1 1 8 5 – 1310 1250 3 A E 1 1 8 5 – 2310 2000 3 A E 1 1 8 5 – 4310 2500 3 A E 1 1 8 5 – 6275 800 3 A E 1 1 7 5 – 1275 1250 3 A E 1 1 7 5 – 2205 800 3 A E 1 1 6 5 – 1205 1250 3 A E 1 1 6 5 – 2

160 310 800 3 A E 1 1 5 5 – 1310 1250 3 A E 1 1 5 5 – 2275 800 3 A E 1 1 4 5 – 1275 1250 3 A E 1 1 4 5 – 2205 800 3 A E 1 1 3 5 – 1205 1250 3 A E 1 1 3 5 – 2

150 310 800 3 A E 1 1 2 5 – 1310 1250 3 A E 1 1 2 5 – 2275 800 3 A E 1 1 1 5 – 1275 1250 3 A E 1 1 1 5 – 2205 800 3 A E 1 1 0 5 – 1205 1250 3 A E 1 1 0 5 – 2

Special version (available for all 12 kV standard circuit-breakers)

Ud = 42 kV – Z E 1 3

Configuration example

SION vacuum circuit-breaker 3 A E 1

Rated voltage Ur = 12 kV, 50/60 Hz

Rated lightning impulse withstand voltage Up = 75 kV

Rated short-circuit breaking current Isc = 31.5 kA

Rated normal current Ir = 1250 A

Pole-center distance = 150 mm, width across flats = 205 mm 1 0 5 – 2

Example for Order No.: 3 A E 1 1 0 5 – 2 � � � � – � � � �

Order codes:

Equipment SelectionSelection of basic types, standard circuit-breakers

See

page

23

See

page

23

See

page

24

See

page

24

See

page

25

See

page

25

See

page

26

See

page

26

See

page

27

SION Vacuum Circuit-Breakers

Rate

dvo

ltage

Rate

dlig

htni

ngim

puls

ew

ithst

and

volta

ge

Rate

dsh

ort-

dura

tion

pow

er-f

requ

ency

with

stan

dvo

ltage

Rate

dsh

ort-

circ

uit

brea

king

curr

ent

at36

%A

Cco

mpo

nent

Rate

dsh

ort-

circ

uit

mak

ing

curr

ent

(at5

0/60

Hz)

Pole

-cen

terd

ista

nce

Wid

thac

ross

flats

Rate

dno

rmal

curr

ent

Page 19: SION Vacuum Circuit-Breakers - w3.siemens.com.cn · integration in all customary medium-voltage ... transformers, capacitors, generators, filter circuits ... The operating mechanism

2

19Siemens HG 11.02 · 2006

12 kV Position: 1 2 3 4 5 6 7 – 8 9 10 11 12 – 13 14 15 16 Order codes

50/60 Hz Order No.: 3 A E 1 � � � – � � � � � – � � � � – � � � �

Ur Up Ud Isc Ima Ir

kV kV kV kA kA mm mm A

12 75 28 40 100/104 210 310 1250 3 A E 1 1 8 6 – 2310 2000 3 A E 1 1 8 6 – 4310 2500 3 A E 1 1 8 6 – 6310 3150 3 A E 1 1 8 6 – 7

Special version (available for all 12 kV standard circuit-breakers)

Ud = 42 kV – Z E 1 3

Circuit-breaker for installation in NXAIR12 75 28 31.5 80/82 210 275 1250 3 A E 1 5 7 5 – 2

275 2500 3 A E 1 5 7 5 – 6160 275 1250 3 A E 1 5 4 5 – 2

12 75 28 40 100/104 210 275 1250 3 A E 1 5 7 6 – 2275 2000 3 A E 1 5 7 6 – 4275 2500 3 A E 1 5 7 6 – 6275 3150 3 A E 1 5 7 6 – 7

Special version (available for all 12 kV standard circuit-breakers)

Ud = 42 kV – Z E 1 3

Configuration example

SION vacuum circuit-breaker 3 A E 1

Rated voltage Ur = 12 kV, 50/60 Hz

Rated lightning impulse withstand voltage Up = 75 kV

Rated short-circuit breaking current Isc = 40 kA

Rated normal current Ir = 1250 A

Pole-center distance = 210 mm, width across flats = 310 mm 1 8 6 – 2

Example for Order No.: 3 A E 1 1 8 6 – 2 � � � � – � � � �

Order codes:

Equipment SelectionSelection of basic types, standard circuit-breakers

See

page

23

See

page

23

See

page

24

See

page

24

See

page

25

See

page

25

See

page

26

See

page

26

See

page

27

SION Vacuum Circuit-Breakers

Rate

dvo

ltage

Rate

dlig

htni

ngim

puls

ew

ithst

and

volta

ge

Rate

dsh

ort-

dura

tion

pow

er-f

requ

ency

with

stan

dvo

ltage

Rate

dsh

ort-

circ

uit

brea

king

curr

ent

at36

%A

Cco

mpo

nent

Rate

dsh

ort-

circ

uit

mak

ing

curr

ent

(at5

0/60

Hz)

Pole

-cen

terd

ista

nce

Wid

thac

ross

flats

Rate

dno

rmal

curr

ent

Page 20: SION Vacuum Circuit-Breakers - w3.siemens.com.cn · integration in all customary medium-voltage ... transformers, capacitors, generators, filter circuits ... The operating mechanism

2

20 Siemens HG 11.02 · 2006

17.5 kV Position: 1 2 3 4 5 6 7 – 8 9 10 11 12 – 13 14 15 16 Order codes

50/60 Hz Order No.: 3 A E 1 � � � – � � � � � – � � � � – � � � �

Ur Up Ud Isc Ima Ir

kV kV kV kA kA mm mm A

17.5 95 38 12.5 31/33 210 310 800 3 A E 1 2 8 1 – 1310 1250 3 A E 1 2 8 1 – 2275 800 3 A E 1 2 7 1 – 1275 1250 3 A E 1 2 7 1 – 2205 800 3 A E 1 2 6 1 – 1205 1250 3 A E 1 2 6 1 – 2

160 310 800 3 A E 1 2 5 1 – 1310 1250 3 A E 1 2 5 1 – 2275 800 3 A E 1 2 4 1 – 1275 1250 3 A E 1 2 4 1 – 2205 800 3 A E 1 2 3 1 – 1205 1250 3 A E 1 2 3 1 – 2

150 310 800 3 A E 1 2 2 1 – 1310 1250 3 A E 1 2 2 1 – 2275 800 3 A E 1 2 1 1 – 1275 1250 3 A E 1 2 1 1 – 2205 800 3 A E 1 2 0 1 – 1205 1250 3 A E 1 2 0 1 – 2

17.5 95 38 16 40/42 210 310 800 3 A E 1 2 8 2 – 1310 1250 3 A E 1 2 8 2 – 2275 800 3 A E 1 2 7 2 – 1275 1250 3 A E 1 2 7 2 – 2205 800 3 A E 1 2 6 2 – 1205 1250 3 A E 1 2 6 2 – 2

160 310 800 3 A E 1 2 5 2 – 1310 1250 3 A E 1 2 5 2 – 2275 800 3 A E 1 2 4 2 – 1275 1250 3 A E 1 2 4 2 – 2205 800 3 A E 1 2 3 2 – 1205 1250 3 A E 1 2 3 2 – 2

150 310 800 3 A E 1 2 2 2 – 1310 1250 3 A E 1 2 2 2 – 2275 800 3 A E 1 2 1 2 – 1275 1250 3 A E 1 2 1 2 – 2205 800 3 A E 1 2 0 2 – 1205 1250 3 A E 1 2 0 2 – 2

17.5 95 38 25 63/65 210 310 800 3 A E 1 2 8 4 – 1310 1250 3 A E 1 2 8 4 – 2310 2000 3 A E 1 2 8 4 – 4310 2500 3 A E 1 2 8 4 – 6

Configuration example

SION vacuum circuit-breaker 3 A E 1

Rated voltage Ur = 17.5 kV, 50/60 Hz

Rated lightning impulse withstand voltage Up = 95 kV

Rated short-circuit breaking current Isc = 16 kA

Rated normal current Ir = 1250 A

Pole-center distance = 210 mm, width across flats = 275 mm 2 7 2 – 2

Example for Order No.: 3 A E 1 2 7 2 – 2 � � � � – � � � �

Order codes:

Equipment SelectionSelection of basic types, standard circuit-breakers

See

page

23

See

page

23

See

page

24

See

page

24

See

page

25

See

page

25

See

page

26

See

page

26

See

page

27

SION Vacuum Circuit-Breakers

Rate

dvo

ltage

Rate

dlig

htni

ngim

puls

ew

ithst

and

volta

ge

Rate

dsh

ort-

dura

tion

pow

er-f

requ

ency

with

stan

dvo

ltage

Rate

dsh

ort-

circ

uit

brea

king

curr

ent

at36

%A

Cco

mpo

nent

Rate

dsh

ort-

circ

uit

mak

ing

curr

ent

(at5

0/60

Hz)

Pole

-cen

terd

ista

nce

Wid

thac

ross

flats

Rate

dno

rmal

curr

ent

Page 21: SION Vacuum Circuit-Breakers - w3.siemens.com.cn · integration in all customary medium-voltage ... transformers, capacitors, generators, filter circuits ... The operating mechanism

2

21Siemens HG 11.02 · 2006

17.5 kV Position: 1 2 3 4 5 6 7 – 8 9 10 11 12 – 13 14 15 16 Order codes

50/60 Hz Order No.: 3 A E 1 � � � – � � � � � – � � � � – � � � �

Ur Up Ud Isc Ima Ir

kV kV kV kA kA mm mm A

17.5 95 38 25 63/65 210 275 800 3 A E 1 2 7 4 – 1275 1250 3 A E 1 2 7 4 – 2205 800 3 A E 1 2 6 4 – 1205 1250 3 A E 1 2 6 4 – 2

160 310 800 3 A E 1 2 5 4 – 1310 1250 3 A E 1 2 5 4 – 2275 800 3 A E 1 2 4 4 – 1275 1250 3 A E 1 2 4 4 – 2205 800 3 A E 1 2 3 4 – 1205 1250 3 A E 1 2 3 4 – 2

150 310 800 3 A E 1 2 2 4 – 1310 1250 3 A E 1 2 2 4 – 2275 800 3 A E 1 2 1 4 – 1275 1250 3 A E 1 2 1 4 – 2205 800 3 A E 1 2 0 4 – 1205 1250 3 A E 1 2 0 4 – 2

17.5 95 38 31.5 80/82 210 310 800 3 A E 1 2 8 5 – 1310 1250 3 A E 1 2 8 5 – 2310 2000 3 A E 1 2 8 5 – 4310 2500 3 A E 1 2 8 5 – 6275 800 3 A E 1 2 7 5 – 1275 1250 3 A E 1 2 7 5 – 2205 800 3 A E 1 2 6 5 – 1205 1250 3 A E 1 2 6 5 – 2

160 310 800 3 A E 1 2 5 5 – 1310 1250 3 A E 1 2 5 5 – 2275 800 3 A E 1 2 4 5 – 1275 1250 3 A E 1 2 4 5 – 2205 800 3 A E 1 2 3 5 – 1205 1250 3 A E 1 2 3 5 – 2

150 310 800 3 A E 1 2 2 5 – 1310 1250 3 A E 1 2 2 5 – 2275 800 3 A E 1 2 1 5 – 1275 1250 3 A E 1 2 1 5 – 2205 800 3 A E 1 2 0 5 – 1205 1250 3 A E 1 2 0 5 – 2

17.5 95 38 40 100/104 210 310 1250 3 A E 1 2 8 6 – 2310 2000 3 A E 1 2 8 6 – 4310 2500 3 A E 1 2 8 6 – 6310 3150 3 A E 1 2 8 6 – 7

Configuration example

SION vacuum circuit-breaker 3 A E 1

Rated voltage Ur = 17.5 kV, 50/60 Hz

Rated lightning impulse withstand voltage Up = 95 kV

Rated short-circuit breaking current Isc = 31.5 kA

Rated normal current Ir = 2500 A

Pole-center distance = 210 mm, width across flats = 310 mm 2 8 5 – 6

Example for Order No.: 3 A E 1 2 8 5 – 6 � � � � – � � � �

Order codes:

Equipment SelectionSelection of basic types, standard circuit-breakers

See

page

23

See

page

23

See

page

24

See

page

24

See

page

25

See

page

25

See

page

26

See

page

26

See

page

27

SION Vacuum Circuit-Breakers

Rate

dvo

ltage

Rate

dlig

htni

ngim

puls

ew

ithst

and

volta

ge

Rate

dsh

ort-

dura

tion

pow

er-f

requ

ency

with

stan

dvo

ltage

Rate

dsh

ort-

circ

uit

brea

king

curr

ent

at36

%A

Cco

mpo

nent

Rate

dsh

ort-

circ

uit

mak

ing

curr

ent

(at5

0/60

Hz)

Pole

-cen

terd

ista

nce

Wid

thac

ross

flats

Rate

dno

rmal

curr

ent

Page 22: SION Vacuum Circuit-Breakers - w3.siemens.com.cn · integration in all customary medium-voltage ... transformers, capacitors, generators, filter circuits ... The operating mechanism

2

22 Siemens HG 11.02 · 2006

24 kV Position: 1 2 3 4 5 6 7 – 8 9 10 11 12 – 13 14 15 16 Order codes

50/60 Hz Order No.: 3 A E 1 � � � – � � � � � – � � � � – � � � �

Ur Up Ud Isc Ima Ir

kV kV kV kA kA mm mm A

24 125 50 12.5 31/33 210 310 800 3 A E 1 3 2 1 – 1310 1250 3 A E 1 3 2 1 – 2

24 125 50 16 40/42 210 310 800 3 A E 1 3 2 2 – 1310 1250 3 A E 1 3 2 2 – 2310 2000 3 A E 1 3 2 2 – 4

275 310 800 3 A E 1 3 5 2 – 1310 1250 3 A E 1 3 5 2 – 2310 2000 3 A E 1 3 5 2 – 4

24 125 50 20 50/52 210 310 800 3 A E 1 3 2 3 – 1310 1250 3 A E 1 3 2 3 – 2310 2000 3 A E 1 3 2 3 – 4310 2500 3 A E 1 3 2 3 – 6

275 310 800 3 A E 1 3 5 3 – 1310 1250 3 A E 1 3 5 3 – 2310 2000 3 A E 1 3 5 3 – 4310 2500 3 A E 1 3 5 3 – 6

24 125 50 25 63/65 210 310 800 3 A E 1 3 2 4 – 1310 1250 3 A E 1 3 2 4 – 2310 2000 3 A E 1 3 2 4 – 4310 2500 3 A E 1 3 2 4 – 6

275 310 800 3 A E 1 3 5 4 – 1310 1250 3 A E 1 3 5 4 – 2310 2000 3 A E 1 3 5 4 – 4310 2500 3 A E 1 3 5 4 – 6

Special version (available for all 24 kV standard circuit-breakers)

Ud = 55 kV – Z E 5 5

Circuit-breaker for installation in NXAIR24 125 50 25 63/65 210 320 1250 3 A E 1 7 2 4 – 2

275 320 2500 3 A E 1 7 5 4 – 6Special version (available for all 24 kV standard circuit-breakers)

Ud = 55 kV – Z E 5 5

Configuration example

SION vacuum circuit-breaker 3 A E 1

Rated voltage Ur = 24 kV, 50/60 Hz

Rated lightning impulse withstand voltage Up = 125 kV

Rated short-circuit breaking current Isc = 25 kA

Rated normal current Ir = 2000 A

Pole-center distance = 275 mm, width across flats = 310 mm 3 5 4 – 4

Example for Order No.: 3 A E 1 3 5 4 – 4 � � � � – � � � �

Order codes:

Equipment SelectionSelection of basic types, standard circuit-breakers

See

page

23

See

page

23

See

page

24

See

page

24

See

page

25

See

page

25

See

page

26

See

page

26

See

page

27

SION Vacuum Circuit-Breakers

Rate

dvo

ltage

Rate

dlig

htni

ngim

puls

ew

ithst

and

volta

ge

Rate

dsh

ort-

dura

tion

pow

er-f

requ

ency

with

stan

dvo

ltage

Rate

dsh

ort-

circ

uit

brea

king

curr

ent

at36

%A

Cco

mpo

nent

Rate

dsh

ort-

circ

uit

mak

ing

curr

ent

(at5

0/60

Hz)

Pole

-cen

terd

ista

nce

Wid

thac

ross

flats

Rate

dno

rmal

curr

ent

Page 23: SION Vacuum Circuit-Breakers - w3.siemens.com.cn · integration in all customary medium-voltage ... transformers, capacitors, generators, filter circuits ... The operating mechanism

2

23Siemens HG 11.02 · 2006

9th position Position: 1 2 3 4 5 6 7 – 8 9 10 11 12 – 13 14 15 16 Order codes

Release combination Order No.: 3 A E 1 � � � – � � � � � – � � � � – � � � �

� A� � B� � C� � G� � H� � F

� E� � N� � P� � Q

� J� L

� M

10th positionOperating voltage of the closing solenoid

24 V DC B48 V DC C60 V DC D

110 V DC E220 V DC F100 V AC 50/60 Hz 1) H110 V AC 50/60 Hz 1) J230 V AC 50/60 Hz 1) K

30 V DC M32 V DC N

120 V DC P125 V DC Q127 V DC R240 V DC S120 V AC 50/60 Hz 1) U125 V AC 50/60 Hz 1) V240 V AC 50/60 Hz 1) W

1) The AC frequency 50 or 60 Hz is selected at the 16th position of theorder number together with the language (see page 26)

Configuration example

SION vacuum circuit-breaker 3 A E 1

(Ur = 24 kV, 50/60 Hz, Up = 125 kV, Isc = 25 kA, Ir = 2000 A,

Pole-center distance = 275 mm, width across flats = 310 mm) 3 5 4 – 4

1st shunt release A

Operating voltage of the closing solenoid 48 V DC C

Example for Order No.: 3 A E 1 3 5 4 – 4 A C � � – � � � �

Order codes:

1stsh

untr

elea

se

2nd

shun

trel

ease

Und

ervo

ltage

rele

ase

C.t

.-ope

rate

dre

leas

e0.

5A

C.t

.-ope

rate

dre

leas

e1.

0A

C.t

.-ope

rate

dre

leas

ew

ithtr

ippi

ngpu

lse

W0.

1W

s(2

0O

)

Standard voltages Special voltages

SION Vacuum Circuit-Breakers Equipment SelectionSecondary equipment for standard circuit-breakers

See

page

24

See

page

24

See

page

25

See

page

25

See

page

26

See

page

26

See

page

27

Page 24: SION Vacuum Circuit-Breakers - w3.siemens.com.cn · integration in all customary medium-voltage ... transformers, capacitors, generators, filter circuits ... The operating mechanism

2

24 Siemens HG 11.02 · 2006

Equipment SelectionSecondary equipment for standard circuit-breakers

Example for Order No.: 3 A E 1 3 5 4 – 4 A C 9 0 – � � � �

Order codes: L 1 B

11th position Position: 1 2 3 4 5 6 7 – 8 9 10 11 12 – 13 14 15 16 Order codes

Operating voltage of the 1st release Order No.: 3 A E 1 � � � – � � � � � – � � � � – � � � �

C.t.-operated release 024 V DC 148 V DC 260 V DC 3

110 V DC 4220 V DC 5100 V AC 50/60 Hz 1) 6110 V AC 50/60 Hz 1) 7230 V AC 50/60 Hz 1) 8

30 V DC 9 With order code L 1 A32 V DC 9 With order code L 1 B

120 V DC 9 With order code L 1 C125 V DC 9 With order code L 1 D127 V DC 9 With order code L 1 E240 V DC 9 With order code L 1 F120 V AC 50/60 Hz 1) 9 With order code L 1 K125 V AC 50/60 Hz 1) 9 With order code L 1 L240 V AC 50/60 Hz 1) 9 With order code L 1 M

12th positionOperating voltage of the 2nd release

Without, or c.t.-operated release 024 V DC 148 V DC 260 V DC 3

110 V DC 4220 V DC 5100 V AC 50/60 Hz 1) 6110 V AC 50/60 Hz 1) 7230 V AC 50/60 Hz 1) 8

30 V DC 9 With order code M 1 A32 V DC 9 With order code M 1 B

120 V DC 9 With order code M 1 C125 V DC 9 With order code M 1 D127 V DC 9 With order code M 1 E240 V DC 9 With order code M 1 F120 V AC 50/60 Hz 1) 9 With order code M 1 K125 V AC 50/60 Hz 1) 9 With order code M 1 L240 V AC 50/60 Hz 1) 9 With order code M 1 M

1) The AC frequency 50 or 60 Hz is selected at the 16th position of theorder number together with the language (see page 26)

Configuration example

SION vacuum circuit-breaker 3 A E 1

(Ur = 24 kV, 50/60 Hz, Up = 125 kV, Isc = 25 kA, Ir = 2000 A,

Pole-center distance = 275 mm, width across flats = 310 mm) 3 5 4 – 4 A C

Operating voltage of the 1st release 32 V DC 9 L 1 B

Without 2nd release 0

Standard voltages Special voltages

Standard voltages Special voltages

See

page

25

See

page

25

See

page

26

See

page

26

See

page

27

SION Vacuum Circuit-Breakers

Page 25: SION Vacuum Circuit-Breakers - w3.siemens.com.cn · integration in all customary medium-voltage ... transformers, capacitors, generators, filter circuits ... The operating mechanism

2

25Siemens HG 11.02 · 2006

13th position Position: 1 2 3 4 5 6 7 – 8 9 10 11 12 – 13 14 15 16 Order codes

Circuit-breaker installation accessories Order No.: 3 A E 1 � � � – � � � � � – � � � � – � � � �

Options

Without circuit-breaker installation accessories,fixed-mounted circuit-breaker 0With drawout element 1With drawout element, contact arms and contact system 2With drawout element, contact arms and contact system,fixed contacts and bushings 3

14th positionOperating voltage of the motor operating mechanism

24 V DC B48 V DC C60 V DC D

110 V DC E220 V DC F100 V AC 50/60 Hz 1) H110 V AC 50/60 Hz 1) J230 V AC 50/60 Hz 1) K

30 V DC M32 V DC N

120 V DC P125 V DC Q127 V DC R240 V DC S120 V AC 50/60 Hz 1) U125 V AC 50/60 Hz 1) V240 V AC 50/60 Hz 1) W

1) The AC frequency 50 or 60 Hz is selected at the 16th position of theorder number together with the language (see page 26)

Configuration example

SION vacuum circuit-breaker 3 A E 1

(Ur = 24 kV, 50/60 Hz, Up = 125 kV, Isc = 25 kA, Ir = 2000 A,

Pole-center distance = 275 mm, width across flats = 310 mm) 3 5 4 – 4 A C 9 0 –

Fixed-mounted circuit-breaker 0

Operating voltage of the motor operating mechanism 230 V AC K

Example for Order No.: 3 A E 1 3 5 4 – 4 A C 9 0 – 0 K � �

Order codes: L 1 B

Standard voltages Special voltages

Equipment SelectionSecondary equipment for standard circuit-breakers

See

page

26

See

page

26

See

page

27

SION Vacuum Circuit-Breakers

Page 26: SION Vacuum Circuit-Breakers - w3.siemens.com.cn · integration in all customary medium-voltage ... transformers, capacitors, generators, filter circuits ... The operating mechanism

2

26 Siemens HG 11.02 · 2006

15th position Position: 1 2 3 4 5 6 7 – 8 9 10 11 12 – 13 14 15 16 Order codes

Interlocking, auxiliary switch, circuit-breaker Order No.: 3 A E 1 � � � – � � � � � – � � � � – � � � �

tripping signal and control cable connection

� � � B� � D� � � F� � H

� � � K� � M� � � R� � Q

� � � � A� � � C� � � � E� � � G� � � � J� � � L� � � � N� � � P

Special versions

Auxiliary switch contacts 12 NO + 12 NC and pinsof the 64-pole plug connector gold-plated – Z A 2 1Key-interlocking (RONIS-lock at the vacuum circuit-breaker)Only for circuit-breakers without mechanical interlocking – Z J 6 0

16th positionAC frequency of operating voltagesLanguages of operating instructions and rating plate

German 50 Hz or DC 060 Hz 1

English 50 Hz or DC 260 Hz 3

French 50 Hz or DC 460 Hz 5

Spanish 50 Hz or DC 660 Hz 7

Other languages on request

Configuration example

SION vacuum circuit-breaker 3 A E 1

(Ur = 24 kV, 50/60 Hz, Up = 125 kV, Isc = 25 kA, Ir = 2000 A,

Pole-center distance = 275 mm, width across flats = 310 mm) 3 5 4 – 4 A C 9 0 – 0 K

With mechanical interlocking, circuit-breaker tripping signal,

auxiliary switch 12 NO + 12 NC and 64-pole plug N

Frequency of the operating voltage 50 Hz or DC, operating instructions and rating plate in German 0

Mec

hani

cal

inte

rlock

ing

6N

O+

6N

C

12N

O+

12N

C

Circ

uit-

brea

ker

trip

ping

sign

al

27-p

ole

term

inal

strip

24-p

ole

plug

64-p

ole

plug

Auxiliary switch Control cable connection

Language Frequency

Example for Order No.: 3 A E 1 3 5 4 – 4 A C 9 0 – 0 K N 0

Order codes: L 1 B

Equipment SelectionSecondary equipment for standard circuit-breakers

See

page

27

SION Vacuum Circuit-Breakers

Page 27: SION Vacuum Circuit-Breakers - w3.siemens.com.cn · integration in all customary medium-voltage ... transformers, capacitors, generators, filter circuits ... The operating mechanism

2

27Siemens HG 11.02 · 2006

Additional equipment Position: 1 2 3 4 5 6 7 – 8 9 10 11 12 – 13 14 15 16 Order codes

Order No.: 3 A E 1 � � � – � � � � � – � � � � – � � � �

Options

Wiring cables, halogen-free and flame-retardant – Z A 1 0Condensation protection, heating for 230 V AC, 50 W – Z A 3 0Silicone-free design – Z A 3 1For circuit-breaker operation at ambient air temperatures down to -25° C – Z A 4 0Electrical closing lock-out – Z A 4 7Additional rating plate, loose delivery – Z B 0 0Separating shell towards contact arm side (standard version) – Z D 9 0Separating shell towards contact arm side (short version) – Z D 9 1Routine test certificate (enclosed with delivery) – Z F 2 0Routine test certificate (with stamp and signature) – Z F 2 1Routine test certificate (to orderer) – Z F 2 3Hand crank (for manual charging of the closing spring) – Z F 3 0Handle for drawout element (for racking the circuit-breaker on thedrawout element)

– Z F 3 2

Indication of disconnected position of the circuit-breaker(circuit-breaker with drawout element)

– Z J 6 1

Configuration exampleSION vacuum circuit-breaker 3 A E 1(Ur = 24 kV, 50/60 Hz, Up = 125 kV, Isc = 25 kA, Ir = 2000 A,Pole-center distance = 275 mm, width across flats = 310 mm) 3 5 4 – 41st shunt release AOperating voltage of the closing solenoid 48 V DC C

Operating voltage of the 1st release 32 V DC 9 With order code L 1 B

Without 2nd release 0 –

Fixed-mounted circuit-breaker 0

Operating voltage of the motor operating mechanism 230 V AC K

With mechanical interlocking, circuit-breaker tripping signal, auxiliary switch 12 NO + 12 NC and 64-pole plug N

Frequency of the operating voltage 50 Hz or DC, operating instructions and rating plate in German 0

Hand crank – Z F 3 0

Example for Order No.: 3 A E 1 3 5 4 – 4 A C 9 0 – 0 K N 0 – Z

Order codes: L 1 B + F 3 0

Equipment SelectionAdditional equipment for standard circuit-breakers

SION Vacuum Circuit-Breakers

Page 28: SION Vacuum Circuit-Breakers - w3.siemens.com.cn · integration in all customary medium-voltage ... transformers, capacitors, generators, filter circuits ... The operating mechanism

2

28 Siemens HG 11.02 · 2006

7.2 kV Position: 1 2 3 4 5 6 7 – 8 9 10 11 12 – 13 14 15 16 Order codes

50/60 Hz Order No.: 3 A E 1 � � � – � � � � � – � � � � – � � � �

Ur Up Ud Isc Ima Ir

kV kV kV kA kA mm mm A

7.2 60 20 16 40/42 210 310 800 3 A E 1 0 8 2 – 1310 1250 3 A E 1 0 8 2 – 2275 800 3 A E 1 0 7 2 – 1275 1250 3 A E 1 0 7 2 – 2

150 310 800 3 A E 1 0 2 2 – 1310 1250 3 A E 1 0 2 2 – 2275 800 3 A E 1 0 1 2 – 1275 1250 3 A E 1 0 1 2 – 2

7.2 60 20 20 50/52 210 310 800 3 A E 1 0 8 3 – 1310 1250 3 A E 1 0 8 3 – 2275 800 3 A E 1 0 7 3 – 1275 1250 3 A E 1 0 7 3 – 2

150 310 800 3 A E 1 0 2 3 – 1310 1250 3 A E 1 0 2 3 – 2275 800 3 A E 1 0 1 3 – 1275 1250 3 A E 1 0 1 3 – 2

7.2 60 20 25 63/65 210 310 800 3 A E 1 0 8 4 – 1310 1250 3 A E 1 0 8 4 – 2310 2000 3 A E 1 0 8 4 – 4275 800 3 A E 1 0 7 4 – 1275 1250 3 A E 1 0 7 4 – 2

150 310 800 3 A E 1 0 2 4 – 1310 1250 3 A E 1 0 2 4 – 2275 800 3 A E 1 0 1 4 – 1275 1250 3 A E 1 0 1 4 – 2

7.2 60 20 31.5 80/82 210 310 800 3 A E 1 0 8 5 – 1310 1250 3 A E 1 0 8 5 – 2310 2000 3 A E 1 0 8 5 – 4310 2500 3 A E 1 0 8 5 – 6275 800 3 A E 1 0 7 5 – 1275 1250 3 A E 1 0 7 5 – 2

150 310 800 3 A E 1 0 2 5 – 1310 1250 3 A E 1 0 2 5 – 2275 800 3 A E 1 0 1 5 – 1275 1250 3 A E 1 0 1 5 – 2

7.2 60 20 40 100/104 210 310 1250 3 A E 1 0 8 6 – 2310 2000 3 A E 1 0 8 6 – 4310 2500 3 A E 1 0 8 6 – 6310 3150 3 A E 1 0 8 6 – 7

Configuration example

SION vacuum circuit-breaker 3 A E 1

Rated voltage Ur = 7.2 kV, 50/60 Hz

Rated lightning impulse withstand voltage Up = 60 kV

Rated short-circuit breaking current Isc = 20 kA

Rated normal current Ir = 1250 A

Pole-center distance = 210 mm, width across flats = 310 mm 0 8 3 – 2

Example for Order No.: 3 A E 1 0 8 3 – 2 � � � � – � � � �

Order codes:

Equipment SelectionSelection of basic types, slide-in modules

See

page

32

See

page

32

See

page

33

See

page

33

See

page

34

See

page

34

See

page

35

See

page

35

See

page

36

SION Vacuum Circuit-Breakers

Rate

dvo

ltage

Rate

dlig

htni

ngim

puls

ew

ithst

and

volta

ge

Rate

dsh

ort-

dura

tion

pow

er-f

requ

ency

with

stan

dvo

ltage

Rate

dsh

ort-

circ

uit

brea

king

curr

ent

at36

%A

Cco

mpo

nent

Rate

dsh

ort-

circ

uit

mak

ing

curr

ent

(at5

0/60

Hz)

Pole

-cen

terd

ista

nce

Wid

thac

ross

flats

Rate

dno

rmal

curr

ent

Page 29: SION Vacuum Circuit-Breakers - w3.siemens.com.cn · integration in all customary medium-voltage ... transformers, capacitors, generators, filter circuits ... The operating mechanism

2

29Siemens HG 11.02 · 2006

12 kV Position: 1 2 3 4 5 6 7 – 8 9 10 11 12 – 13 14 15 16 Order codes

50/60 Hz Order No.: 3 A E 1 � � � – � � � � � – � � � � – � � � �

Ur Up Ud Isc Ima Ir

kV kV kV kA kA mm mm A

12 75 28 16 40/42 210 310 800 3 A E 1 1 8 2 – 1310 1250 3 A E 1 1 8 2 – 2275 800 3 A E 1 1 7 2 – 1275 1250 3 A E 1 1 7 2 – 2

150 310 800 3 A E 1 1 2 2 – 1310 1250 3 A E 1 1 2 2 – 2275 800 3 A E 1 1 1 2 – 1275 1250 3 A E 1 1 1 2 – 2

12 75 28 20 50/52 210 310 800 3 A E 1 1 8 3 – 1310 1250 3 A E 1 1 8 3 – 2275 800 3 A E 1 1 7 3 – 1275 1250 3 A E 1 1 7 3 – 2

150 310 800 3 A E 1 1 2 3 – 1310 1250 3 A E 1 1 2 3 – 2275 800 3 A E 1 1 1 3 – 1275 1250 3 A E 1 1 1 3 – 2

12 75 28 25 63/65 210 310 800 3 A E 1 1 8 4 – 1310 1250 3 A E 1 1 8 4 – 2310 2000 3 A E 1 1 8 4 – 4310 2500 3 A E 1 1 8 4 – 6275 800 3 A E 1 1 7 4 – 1275 1250 3 A E 1 1 7 4 – 2

150 310 800 3 A E 1 1 2 4 – 1310 1250 3 A E 1 1 2 4 – 2275 800 3 A E 1 1 1 4 – 1275 1250 3 A E 1 1 1 4 – 2

12 75 28 31.5 80/82 210 310 800 3 A E 1 1 8 5 – 1310 1250 3 A E 1 1 8 5 – 2310 2000 3 A E 1 1 8 5 – 4310 2500 3 A E 1 1 8 5 – 6275 800 3 A E 1 1 7 5 – 1275 1250 3 A E 1 1 7 5 – 2

150 310 800 3 A E 1 1 2 5 – 1310 1250 3 A E 1 1 2 5 – 2275 800 3 A E 1 1 1 5 – 1275 1250 3 A E 1 1 1 5 – 2

12 75 28 40 100/104 210 310 1250 3 A E 1 1 8 6 – 2310 2000 3 A E 1 1 8 6 – 4310 2500 3 A E 1 1 8 6 – 6310 3150 3 A E 1 1 8 6 – 7

Special version (available for all 12 kV slide-in modules)

Ud = 42 kV – Z E 1 3

Configuration example

SION vacuum circuit-breaker 3 A E 1

Rated voltage Ur = 12 kV, 50/60 Hz

Rated lightning impulse withstand voltage Up = 75 kV

Rated short-circuit breaking current Isc = 25 kA

Rated normal current Ir = 800 A

Pole-center distance = 150 mm, width across flats = 275 mm 1 1 4 – 1

Rated short-duration power-frequency withstand voltage Ud = 42 kV – Z E 1 3

Example for Order No.: 3 A E 1 1 1 4 – 1 � � � � – � � � � – Z

Order codes: E 1 3

Equipment SelectionSelection of basic types, slide-in modules

See

page

32

See

page

32

See

page

33

See

page

33

See

page

34

See

page

34

See

page

35

See

page

35

See

page

36

SION Vacuum Circuit-Breakers

Rate

dvo

ltage

Rate

dlig

htni

ngim

puls

ew

ithst

and

volta

ge

Rate

dsh

ort-

dura

tion

pow

er-f

requ

ency

with

stan

dvo

ltage

Rate

dsh

ort-

circ

uit

brea

king

curr

ent

at36

%A

Cco

mpo

nent

Rate

dsh

ort-

circ

uit

mak

ing

curr

ent

(at5

0/60

Hz)

Pole

-cen

terd

ista

nce

Wid

thac

ross

flats

Rate

dno

rmal

curr

ent

Page 30: SION Vacuum Circuit-Breakers - w3.siemens.com.cn · integration in all customary medium-voltage ... transformers, capacitors, generators, filter circuits ... The operating mechanism

2

30 Siemens HG 11.02 · 2006

17.5 kV Position: 1 2 3 4 5 6 7 – 8 9 10 11 12 – 13 14 15 16 Order codes

50/60 Hz Order No.: 3 A E 1 � � � – � � � � � – � � � � – � � � �

Ur Up Ud Isc Ima Ir

kV kV kV kA kA mm mm A

17.5 95 38 12.5 31/33 210 310 800 3 A E 1 2 8 1 – 1310 1250 3 A E 1 2 8 1 – 2275 800 3 A E 1 2 7 1 – 1275 1250 3 A E 1 2 7 1 – 2

150 310 800 3 A E 1 2 2 1 – 1310 1250 3 A E 1 2 2 1 – 2275 800 3 A E 1 2 1 1 – 1275 1250 3 A E 1 2 1 1 – 2

17.5 95 38 16 40/42 210 310 800 3 A E 1 2 8 2 – 1310 1250 3 A E 1 2 8 2 – 2275 800 3 A E 1 2 7 2 – 1275 1250 3 A E 1 2 7 2 – 2

150 310 800 3 A E 1 2 2 2 – 1310 1250 3 A E 1 2 2 2 – 2275 800 3 A E 1 2 1 2 – 1275 1250 3 A E 1 2 1 2 – 2

17.5 95 38 25 63/65 210 310 800 3 A E 1 2 8 4 – 1310 1250 3 A E 1 2 8 4 – 2310 2000 3 A E 1 2 8 4 – 4310 2500 3 A E 1 2 8 4 – 6275 800 3 A E 1 2 7 4 – 1275 1250 3 A E 1 2 7 4 – 2

150 310 800 3 A E 1 2 2 4 – 1310 1250 3 A E 1 2 2 4 – 2275 800 3 A E 1 2 1 4 – 1275 1250 3 A E 1 2 1 4 – 2

17.5 95 38 31.5 80/82 210 310 800 3 A E 1 2 8 5 – 1310 1250 3 A E 1 2 8 5 – 2310 2000 3 A E 1 2 8 5 – 4310 2500 3 A E 1 2 8 5 – 6275 800 3 A E 1 2 7 5 – 1275 1250 3 A E 1 2 7 5 – 2

150 310 800 3 A E 1 2 2 5 – 1310 1250 3 A E 1 2 2 5 – 2275 800 3 A E 1 2 1 5 – 1275 1250 3 A E 1 2 1 5 – 2

17.5 95 38 40 100/104 210 310 1250 3 A E 1 2 8 6 – 2310 2000 3 A E 1 2 8 6 – 4310 2500 3 A E 1 2 8 6 – 6310 3150 3 A E 1 2 8 6 – 7

Configuration example

SION vacuum circuit-breaker 3 A E 1

Rated voltage Ur = 17.5 kV, 50/60 Hz

Rated lightning impulse withstand voltage Up = 95 kV

Rated short-circuit breaking current Isc = 16 kA

Rated normal current Ir = 1250 A

Pole-center distance = 210 mm, width across flats = 275 mm 2 7 2 – 2

Example for Order No.: 3 A E 1 2 7 2 – 2 � � � � – � � � �

Order codes:

Equipment SelectionSelection of basic types, slide-in modules

See

page

32

See

page

32

See

page

33

See

page

33

See

page

34

See

page

34

See

page

35

See

page

35

See

page

36

SION Vacuum Circuit-Breakers

Rate

dvo

ltage

Rate

dlig

htni

ngim

puls

ew

ithst

and

volta

ge

Rate

dsh

ort-

dura

tion

pow

er-f

requ

ency

with

stan

dvo

ltage

Rate

dsh

ort-

circ

uit

brea

king

curr

ent

at36

%A

Cco

mpo

nent

Rate

dsh

ort-

circ

uit

mak

ing

curr

ent

(at5

0/60

Hz)

Pole

-cen

terd

ista

nce

Wid

thac

ross

flats

Rate

dno

rmal

curr

ent

Page 31: SION Vacuum Circuit-Breakers - w3.siemens.com.cn · integration in all customary medium-voltage ... transformers, capacitors, generators, filter circuits ... The operating mechanism

2

31Siemens HG 11.02 · 2006

24 kV Position: 1 2 3 4 5 6 7 – 8 9 10 11 12 – 13 14 15 16 Order codes

50/60 Hz Order No.: 3 A E 1 � � � – � � � � � – � � � � – � � � �

Ur Up Ud Isc Ima Ir

kV kV kV kA kA mm mm A

24 125 50 12.5 31/33 210 310 800 3 A E 1 3 2 1 – 1310 1250 3 A E 1 3 2 1 – 2

24 125 50 16 40/42 210 310 800 3 A E 1 3 2 2 – 1310 1250 3 A E 1 3 2 2 – 2310 2000 3 A E 1 3 2 2 – 4

275 310 800 3 A E 1 3 5 2 – 1310 1250 3 A E 1 3 5 2 – 2310 2000 3 A E 1 3 5 2 – 4

24 125 50 20 50/52 210 310 800 3 A E 1 3 2 3 – 1310 1250 3 A E 1 3 2 3 – 2310 2000 3 A E 1 3 2 3 – 4310 2500 3 A E 1 3 2 3 – 6

275 310 800 3 A E 1 3 5 3 – 1310 1250 3 A E 1 3 5 3 – 2310 2000 3 A E 1 3 5 3 – 4310 2500 3 A E 1 3 5 3 – 6

24 125 50 25 63/65 210 310 800 3 A E 1 3 2 4 – 1310 1250 3 A E 1 3 2 4 – 2310 2000 3 A E 1 3 2 4 – 4310 2500 3 A E 1 3 2 4 – 6

275 310 800 3 A E 1 3 5 4 – 1310 1250 3 A E 1 3 5 4 – 2310 2000 3 A E 1 3 5 4 – 4310 2500 3 A E 1 3 5 4 – 6

Configuration example

SION vacuum circuit-breaker 3 A E 1

Rated voltage Ur = 24 kV, 50/60 Hz

Rated lightning impulse withstand voltage Up = 125 kV

Rated short-circuit breaking current Isc = 25 kA

Rated normal current Ir = 2000 A

Pole-center distance = 275 mm, width across flats = 310 mm 3 5 4 – 4

Example for Order No.: 3 A E 1 3 5 4 – 4 � � � � – � � � �

Order codes:

Equipment SelectionSelection of basic types, slide-in modules

See

page

32

See

page

32

See

page

33

See

page

33

See

page

34

See

page

34

See

page

35

See

page

35

See

page

36

SION Vacuum Circuit-Breakers

Rate

dvo

ltage

Rate

dlig

htni

ngim

puls

ew

ithst

and

volta

ge

Rate

dsh

ort-

dura

tion

pow

er-f

requ

ency

with

stan

dvo

ltage

Rate

dsh

ort-

circ

uit

brea

king

curr

ent

at36

%A

Cco

mpo

nent

Rate

dsh

ort-

circ

uit

mak

ing

curr

ent

(at5

0/60

Hz)

Pole

-cen

terd

ista

nce

Wid

thac

ross

flats

Rate

dno

rmal

curr

ent

Page 32: SION Vacuum Circuit-Breakers - w3.siemens.com.cn · integration in all customary medium-voltage ... transformers, capacitors, generators, filter circuits ... The operating mechanism

2

32 Siemens HG 11.02 · 2006

9th position Position: 1 2 3 4 5 6 7 – 8 9 10 11 12 – 13 14 15 16 Order codes

Release combination Order No.: 3 A E 1 � � � – � � � � � – � � � � – � � � �

� A� � B� � C� � G� � H� � F

� E� � N� � P� � Q

� J� L

� M

10th positionOperating voltage of the closing solenoid

24 V DC B48 V DC C60 V DC D

110 V DC E220 V DC F100 V AC 50/60 Hz 1) H110 V AC 50/60 Hz 1) J230 V AC 50/60 Hz 1) K

30 V DC M32 V DC N

120 V DC P125 V DC Q127 V DC R240 V DC S120 V AC 50/60 Hz 1) U125 V AC 50/60 Hz 1) V240 V AC 50/60 Hz 1) W

1) The AC frequency 50 or 60 Hz is selected at the 16th position of theorder number together with the language (see page 35)

Configuration example

SION vacuum circuit-breaker 3 A E 1

(Ur = 24 kV, 50/60 Hz, Up = 125 kV, Isc = 25 kA, Ir = 2000 A,

Pole-center distance = 275 mm, width across flats = 310 mm) 3 5 4 – 4

1st shunt release A

Operating voltage of the closing solenoid 48 V DC C

Example for Order No.: 3 A E 1 3 5 4 – 4 A C � � – � � � �

Order codes:

Standard voltages Special voltages

Equipment SelectionSecondary equipment for slide-in modules

See

page

33

See

page

33

See

page

34

See

page

34

See

page

35

See

page

35

See

page

36

SION Vacuum Circuit-Breakers

1stsh

untr

elea

se

2nd

shun

trel

ease

Und

ervo

ltage

rele

ase

C.t

.-ope

rate

dre

leas

e0.

5A

C.t

.-ope

rate

dre

leas

e1.

0A

C.t

.-ope

rate

dre

leas

ew

ithtr

ippi

ngpu

lse

W0.

1W

s(2

0O

)

Page 33: SION Vacuum Circuit-Breakers - w3.siemens.com.cn · integration in all customary medium-voltage ... transformers, capacitors, generators, filter circuits ... The operating mechanism

2

33Siemens HG 11.02 · 2006

11th position Position: 1 2 3 4 5 6 7 – 8 9 10 11 12 – 13 14 15 16 Order codes

Operating voltage of the 1st release Order No.: 3 A E 1 � � � – � � � � � – � � � � – � � � �

C.t.-operated release 024 V DC 148 V DC 260 V DC 3

110 V DC 4220 V DC 5100 V AC 50/60 Hz 1) 6110 V AC 50/60 Hz 1) 7230 V AC 50/60 Hz 1) 8

30 V DC 9 With order code L 1 A32 V DC 9 With order code L 1 B

120 V DC 9 With order code L 1 C125 V DC 9 With order code L 1 D127 V DC 9 With order code L 1 E240 V DC 9 With order code L 1 F120 V AC 50/60 Hz 1) 9 With order code L 1 K125 V AC 50/60 Hz 1) 9 With order code L 1 L240 V AC 50/60 Hz 1) 9 With order code L 1 M

12th positionOperating voltage of the 2nd release

Without, or c.t.-operated release 024 V DC 148 V DC 260 V DC 3

110 V DC 4220 V DC 5100 V AC 50/60 Hz 1) 6110 V AC 50/60 Hz 1) 7230 V AC 50/60 Hz 1) 8

30 V DC 9 With order code M 1 A32 V DC 9 With order code M 1 B

120 V DC 9 With order code M 1 C125 V DC 9 With order code M 1 D127 V DC 9 With order code M 1 E240 V DC 9 With order code M 1 F120 V AC 50/60 Hz 1) 9 With order code M 1 K125 V AC 50/60 Hz 1) 9 With order code M 1 L240 V AC 50/60 Hz 1) 9 With order code M 1 M

1) The AC frequency 50 or 60 Hz is selected at the 16th position of theorder number together with the language (see page 35)

Configuration example

SION vacuum circuit-breaker 3 A E 1

(Ur = 24 kV, 50/60 Hz, Up = 125 kV, Isc = 25 kA, Ir = 2000 A,

Pole-center distance = 275 mm, width across flats = 310 mm) 3 5 4 – 4 A C

Operating voltage of the 1st release 32 V DC 9 L 1 B

Without 2nd release 0

Example for Order No.: 3 A E 1 3 5 4 – 4 A C 9 0 – � � � �

Order codes: L 1 B

Standard voltages Special voltages

Standard voltages Special voltagesSe

epa

ge34

See

page

34

See

page

35

See

page

35

See

page

36

SION Vacuum Circuit-Breakers Equipment SelectionSecondary equipment for slide-in modules

Page 34: SION Vacuum Circuit-Breakers - w3.siemens.com.cn · integration in all customary medium-voltage ... transformers, capacitors, generators, filter circuits ... The operating mechanism

2

34 Siemens HG 11.02 · 2006

13th position Position: 1 2 3 4 5 6 7 – 8 9 10 11 12 – 13 14 15 16 Order codes

Circuit-breaker installation accessories Order No.: 3 A E 1 � � � – � � � � � – � � � � – � � � �

On cartridge, with drawout element, contact arms, contact system,

fixed contacts, bushings and shutters 5On cartridge, with drawout element, contact arms, contact system,

fixed contacts, bushings, shutters and earthing switch

with short-circuit making capacity 6Drawings of the fully equipped slide-in-module.

Scope of supply includes fixed-mounted circuit-breaker 8

14th positionOperating voltage of the motor operating mechanism

24 V DC B48 V DC C60 V DC D

110 V DC E220 V DC F100 V AC 50/60 Hz 1) H110 V AC 50/60 Hz 1) J230 V AC 50/60 Hz 1) K

30 V DC M32 V DC N

120 V DC P125 V DC Q127 V DC R240 V DC S120 V AC 50/60 Hz 1) U125 V AC 50/60 Hz 1) V240 V AC 50/60 Hz 1) W

1) The AC frequency 50 or 60 Hz is selected at the 16th position of theorder number together with the language (see page 35)

Configuration example

SION vacuum circuit-breaker 3 A E 1

(Ur = 24 kV, 50/60 Hz, Up = 125 kV, Isc = 25 kA, Ir = 2000 A,

Pole-center distance = 275 mm, width across flats = 310 mm) 3 5 4 – 4 A C 9 0 –

Circuit-breaker on cartridge, with drawout element, contact arms,

contact system, fixed contacts, bushings and shutters 5

Operating voltage of the motor operating mechanism 240 V DC S

Standard voltages Special voltages

Example for Order No.: 3 A E 1 3 5 4 – 4 A C 9 0 – 5 S � �

Order codes: L 1 B

Equipment SelectionSecondary equipment for slide-in modules

See

page

35

See

page

35

See

page

36

Options

SION Vacuum Circuit-Breakers

Page 35: SION Vacuum Circuit-Breakers - w3.siemens.com.cn · integration in all customary medium-voltage ... transformers, capacitors, generators, filter circuits ... The operating mechanism

2

35Siemens HG 11.02 · 2006

16th positionAC frequency of operating voltagesLanguages of operating instructionsand rating plate

German 50 Hz or DC 060 Hz 1

English 50 Hz or DC 260 Hz 3

French 50 Hz or DC 460 Hz 5

Spanish 50 Hz or DC 660 Hz 7

Other languages on request

Configuration example

SION vacuum circuit-breaker 3 A E 1

(Ur = 24 kV, 50/60 Hz, Up = 125 kV, Isc = 25 kA, Ir = 2000 A,

Pole-center distance = 275 mm, width across flats = 310 mm) 3 5 4 – 4 A C 9 0 – 5 S

With mechanical interlocking, circuit-breaker tripping signal, auxiliary switch 12 NO + 12 NC and 64-pole plug N

Frequency of the operating voltage 50 Hz or DC, operating instruction and rating plate in Spanish 6

Auxiliary switch contacts 12 NO + 12 NC and plug pins gold-plated – Z A 2 1

Language Frequency

Example for Order No.: 3 A E 1 3 5 4 – 4 A C 9 0 – 5 S N 6 – Z

Order codes: L 1 B + A 2 1

Equipment SelectionSecondary equipment for slide-in modules

15th position Position: 1 2 3 4 5 6 7 – 8 9 10 11 12 – 13 14 15 16 Order codes

Interlocking, auxiliary switch, circuit-breaker Order No.: 3 A E 1 � � � – � � � � � – � � � � – � � � �

tripping signal and control cable connection

� � � � A� � � C� � � � J� � � L� � � � N� � � P

Special versions

Auxiliary switch contacts 12 NO + 12 NC and pins

of the 64-pole plug connector gold-plated – Z A 2 1

Mec

hani

cal

inte

rlock

ing

6N

O+

6N

C

12N

O+

12N

C

Circ

uit-

brea

ker

trip

ping

sign

al

27-p

ole

term

inal

strip

64-p

ole

plug

See

page

36

SION Vacuum Circuit-Breakers

Auxiliary switch Control cable connection

Page 36: SION Vacuum Circuit-Breakers - w3.siemens.com.cn · integration in all customary medium-voltage ... transformers, capacitors, generators, filter circuits ... The operating mechanism

2

36 Siemens HG 11.02 · 2006

Equipment SelectionAdditional equipment for slide-in modules

Additional equipment Position: 1 2 3 4 5 6 7 – 8 9 10 11 12 – 13 14 15 16 Order codes

Order No.: 3 A E 1 � � � – � � � � � – � � � � – � � � �

Options

Wiring cables, halogen-free and flame-retardant – Z A 1 0Condensation protection, heating for 230 V AC, 50 W – Z A 3 0Silicone-free design – Z A 3 1For circuit-breaker operation at ambient air temperatures down to -25° C – Z A 4 0Electrical closing lock-out – Z A 4 7Additional rating plate, loose delivery – Z B 0 0Routine test certificate (enclosed with delivery) – Z F 2 0Routine test certificate (with stamp and signature) – Z F 2 1Routine test certificate (to orderer) – Z F 2 3Hand crank (for manual charging of the closing spring) – Z F 3 0Handle for drawout element (for racking the circuit-breaker on thedrawout element)

– Z F 3 2

Handle for earthing switch (for operating the switch at the module) – Z F 3 4

Configuration exampleSION vacuum circuit-breaker 3 A E 1(Ur = 24 kV, 50/60 Hz, Up = 125 kV, Isc = 25 kA, Ir = 2000 A,Pole-center distance = 275 mm, width across flats = 310 mm) 3 5 4 – 41st shunt release AOperating voltage of the closing solenoid 48 V DC COperating voltage of the 1st release 32 V DC 9 With order code L 1 BWithout 2nd release 0 –

Circuit-breaker on cartridge, with drawout element, contact arms,

contact system, fixed contacts, bushings and shutters 5

Operating voltage of the motor operating mechanism 240 V DC S

With mechanical interlocking, circuit-breaker tripping signal, auxiliary switch 12 NO + 12 NC and 64-pole plug N

Frequency of the operating voltage 50 Hz or DC, operating instructions and rating plate in Spanish 6

Auxiliary switch contacts 12 NO + 12 NC and plug pins gold-plated – Z A 2 1

Wiring cables halogen-free and flame-retardant – Z A 1 0

Silicone-free design – Z A 3 1

Electrical closing lock-out – Z A 4 7

Example for Order No.: 3 A E 1 3 5 4 – 4 A C 9 0 – 5 S N 6 – Z

Order codes: L 1 B + A 2 1 + A 1 0 + A 3 1 + A 4 7

SION Vacuum Circuit-Breakers

Page 37: SION Vacuum Circuit-Breakers - w3.siemens.com.cn · integration in all customary medium-voltage ... transformers, capacitors, generators, filter circuits ... The operating mechanism

2

37Siemens HG 11.02 · 2006

Designation Remarks Operating voltage Order No.

Handles Hand crank for circuit-breaker 3AX15 30-2BLong hand crank for circuit-breaker 3AX14 30-2BHandle for drawout element 3AX14 30-2CHandle for earthing switch (for slide-in module) 3AX14 30-2D

Lubricant 180 g of Klüber-Isoflex Topas L32 3AX11 33-3H1 kg of Klüber-Isoflex Topas L32 3AX11 33-3E1 kg of Molykote grease 3AX11 33-2L

Operating solenoid Used as closing solenoid or 24 V DC 3AY15 10-5B1st shunt release 30/32 V DC 3AY15 10-5M

48 V DC 3AY15 10-5C60 V DC 3AY15 10-5D100/124 V DC 3AY15 10-5E125/144 V DC 3AY15 10-5N220/250 V DC 3AY15 10-5F100/125 V AC, 50/60 Hz 3AY15 10-5E230/240 V AC, 50/60 Hz 3AY15 10-5F

2nd shunt release 24/32 V DC 3AX11 01-2B48/60 V DC 3AX11 01-2C110/127 V DC 3AX11 01-2E220/240 V DC 3AX11 01-2F100/125 V AC, 50 Hz 3AX11 01-2G230/240 V AC, 50 Hz 3AX11 01-2J100/125 V AC, 60 Hz 3AX11 01-3G230/240 V AC, 60 Hz 3AX11 01-3J

Mounting parts For 2nd shunt release 3AX14 11-2ACurrent-transformeroperated release

For rated normal current 0.5 A 3AX11 02-2A

For rated normal current 1 A 3AX11 02-2BFor tripping pulse W 0.1 Ws, 20 O for protection relay 7SJ45 3AX11 04-2B

Mounting parts For current-transformer operated release 3AX14 11-2A

Retrofitting

When releases / solenoids are retrofitted, the order num-bers of the built-on parts must also be specified. For otheradditional equipment, the required mounting parts areincluded in the delivery.

Spare parts

When releases / solenoids are required as spare parts, theorder number and the type of construction of the asso-ciated standard circuit-breaker must also be specified.

Remark for orders

The order numbers are applicable to standard circuit-breakers of current manufacture. When mounting partsor spare parts are being ordered for an existing standardcircuit-breaker, always quote the type designation, serial No.,design code and the year of manufacture of the circuit-breaker to be sure to get the correct delivery.

Accessories for the plug connector

Included in the scope of supply of the basic equipment forstandard circuit-breakers:

For 24-pole plug connector

– Lower part of plug– Crimp sockets acc. to number of contacts– Upper part of plug with screwed contacts

(no crimp sockets required)

For 64-pole plug connector

– Lower part of plug– Upper part of plug– Crimp sockets according to number of contacts

Vacuum interrupters and other spare parts must only bereplaced by instructed personnel.

Equipment SelectionAccessories and spare parts

SION Vacuum Circuit-Breakers

Page 38: SION Vacuum Circuit-Breakers - w3.siemens.com.cn · integration in all customary medium-voltage ... transformers, capacitors, generators, filter circuits ... The operating mechanism

2

38 Siemens HG 11.02 · 2006

Designation Remarks Operating voltage Order No.

Undervoltage release 24 V DC 3AX11 03-2B30/32 V DC 3AX11 03-2L48 V DC 3AX11 03-2C60 V DC 3AX11 03-2D110 V DC 3AX11 03-2E120/127 V DC 3AX11 03-2N220 V DC 3AX11 03-2F240 V DC 3AX11 03-2P100 V AC, 50 Hz 3AX11 03-2G110/125 V AC, 50 Hz 3AX11 03-2H230 V AC, 50 Hz 3AX11 03-2J240 V AC, 50 Hz 3AX11 03-2M100 V AC, 60 Hz 3AX11 03-3G110/125 V AC, 60 Hz 3AX11 03-3H230 V AC, 60 Hz 3AX11 03-3J240 V AC, 60 Hz 3AX11 03-3M

Mounting parts For undervoltage release 3AX14 11-2ADrive motor 24/30/32 V DC 3AY17 11-2B

48 V DC 3AY17 11-2C60 V DC 3AY17 11-2D100/110/125 V DC/AC 3AY17 11-2E220 V DC/230 V AC 3AY17 11-2F

Auxiliary contactor 24 V DC SWB: 55656type 3RH11 22 for anti-pumping 30/32 V DC SWB: 55658

48 V DC SWB: 5565960 V DC SWB: 55660110 V DC SWB: 55661120/127 V DC SWB: 55662220 V DC SWB: 55663240/250 V AC SWB: 55665110 V AC, 50/60 Hz SWB: 55666120 V AC, 50/60 Hz SWB: 55667125 V AC, 50/60 Hz SWB: 55668230 V AC, 50/60 Hz SWB: 55669240 V AC, 50/60 Hz SWB: 55670

Position switch Type SE4 without installation accessories SWB: 46677Used for: Nos.

– Electrical anti-pumping (-S3) 1

– Electrical interlocking (-S12) 1

– Motor control (-S21, -S22) 2

– Closing spring charged (-S4) 1

– Circuit-breaker tripping signal (-S6, -S7) 2

– Electrical closing lock-out (-S5) 1

– Drawout element (-S1.0 to – S1.9) 10

Auxiliary switch (-S1) 6 NO + 6 NC 3SV92 73-2AA012 NO + 12 NC 3SV92 74-2AA0

Mechanical interlocking 3AX14 20-2AKey-operated interlocking 3AX14 37-2AModule connector State position indicator of drawout element 3AX14 60-2AAccessories for plug connector (for conductor cross-section 1.5 mm)

Crimp pins (for lower part of plug) 24-pole 3AX11 34-3A64-pole 3AX11 34-4B

Crimp sockets (for upper part of plug) 64-pole 3AX11 34-4C

Crimping pliers For notching the crimp pins and crimp sockets 3AX11 34-4DDisassembly tool 3AX11 34-4GPlug connector complete 24-pole 3AX11 34-7A

64-pole 3AX11 34-6A

Equipment SelectionAccessories and spare parts

SION Vacuum Circuit-Breakers

Page 39: SION Vacuum Circuit-Breakers - w3.siemens.com.cn · integration in all customary medium-voltage ... transformers, capacitors, generators, filter circuits ... The operating mechanism

2

39Siemens HG 11.02 · 2006

Designation Remarks Operating voltage Order No.

Electrical closing lock-out 24 V DC 3AX14 05-2B30/32 V DC 3AX14 05-2K48 V DC 3AX14 05-2C60 V DC 3AX14 05-2D110/127 V DC 3AX14 05-2E220/240 V DC 3AX14 05-2F100 V AC, 50/60 Hz 3AX14 05-2G110/125 V AC, 50/60 Hz 3AX14 05-2H220/240 V AC, 50/60 Hz 3AX14 05-2J

Mounting parts For electrical closing lock-out 3AX14 15-2ABushing 7.2 to 17.5 kV to 1250 A 3AX14 51-2A

7.2 to 17.5 kV to 3150 A 3AX14 51-2B24 kV to 2500 A 3AX14 51-2B

Separating shell towards Additional shielding for narrow mounting conditions

contact arm side, for standard Standard version, width across flats 310 mm 7.2 to 17.5 kV 3AX14 38-2Acircuit-breakers only Standard version, width across flats 275 mm 7.2 to 17.5 kV 3AX14 38-2C

Standard version, width across flats 205 mm 7.2 to 17.5 kV 3AX14 38-2DStandard version, width across flats 310 mm 24 kV 3AX14 38-2BShort version, width across flats 310 mm 24 kV 3AX14 38-3B

Gate for cartridge Short version 3AX14 52-2BContact system 7.2/12/24 kV, 800 to 1250 A 3AX14 42-2A

17.5 kV, 800 to 1250 A 3AX14 42-2B7.2/12/24 kV, to 3150 A 3AX14 42-2C17.5 kV, to 3150 A 3AX14 42-2D

����

����

���

Equipment SelectionAccessories and spare parts

Note:For any query regarding spare parts,subsequent deliveries, etc., the followingfour details are necessary:– Type designation– Serial No.– Design code– Year of manufacture

SION Vacuum Circuit-Breakers

Page 40: SION Vacuum Circuit-Breakers - w3.siemens.com.cn · integration in all customary medium-voltage ... transformers, capacitors, generators, filter circuits ... The operating mechanism

40 Siemens HG 11.02 · 2006

R-HG

11-1

77.ti

f

SION Vacuum Circuit-Breakers

Page 41: SION Vacuum Circuit-Breakers - w3.siemens.com.cn · integration in all customary medium-voltage ... transformers, capacitors, generators, filter circuits ... The operating mechanism

41Siemens HG 11.02 · 2006

3

SION vacuum circuit-breaker with drawout element,contact arms and contact system

SION vacuum circuit-breaker with drawout element,contact arms and contact system

Contents Page

Technical Data

Electrical data, dimensions and weights:

Voltage level 7.2 kV

Voltage level 12 kV

Voltage level 17.5 kV

Voltage level 24 kV

Dimension drawings:

Voltage levels 7.2 to 17.5 kV

Voltage level 24 kV

Operating times, short-circuit protectionof motors, consumption data of releases

Circuit diagrams

41

42

46

50

56

54

58

59

60

Technical DataContents

R-HG

11-1

78.e

psR-

HG11

-179

.eps

SION Vacuum Circuit-Breakers

Page 42: SION Vacuum Circuit-Breakers - w3.siemens.com.cn · integration in all customary medium-voltage ... transformers, capacitors, generators, filter circuits ... The operating mechanism

42 Siemens HG 11.02 · 2006

3

7.2 kV50/60 Hz

Ir tk Isc Ima Up Ud

A mm mm s kA % kA kA kV kV mV mm mm mm mm kg

3AE1 002-1 ... 800 205 150 � 3 16 36 17.9 40/42

60 20 2.1 129 140 105 75 80/ – 3M 44202010 001

1 K/–

3AE1 002-2 ... 1250 205 150 � 3 16 36 17.9 40/42

60 20 2.1 129 140 105 75 80/ – 3M 44202010 001

1 K/–

3AE1 003-1 ... 800 205 150 � 3 20 36 22.4 50/52

60 20 2.1 129 140 105 75 80/ – 3M 44202010 001

2 K/–

3AE1 003-2 ... 1250 205 150 � 3 20 36 22.4 50/52

60 20 2.1 129 140 105 75 80/ – 3M 44202010 001

2 K/–

3AE1 004-1 ... 800 205 150 � 3 25 36 28 63/65

60 20 2.1 129 140 105 75 80/ – 3M 44202010 001

3 K/–

3AE1 004-2 ... 1250 205 150 � 3 25 36 28 63/65

60 20 2.1 129 140 105 75 80/ – 3M 44202010 001

3 K/–

3AE1 005-1 ... 800 205 150 � 3 31.5 36 35.4 80/82

60 20 2.1 129 140 105 75 80/ – 3M 44202010 001

4 K/–

3AE1 005-2 ... 1250 205 150 � 3 31.5 36 35.4 80/82

60 20 2.1 129 140 105 75 80/ – 3M 44202010 001

4 K/–

3AE1 012-1 ... 800 275 150 � 3 16 36 17.9 40/42

60 20 2.1 129 140 105 75 80/120

3M 44202011 001

1 I/J

3AE1 012-2 ... 1250 275 150 � 3 16 36 17.9 40/42

60 20 2.1 129 140 105 75 80/120

3M 44202011 001

1 I/J

3AE1 013-1 ... 800 275 150 � 3 20 36 22.4 50/52

60 20 2.1 129 140 105 75 80/120

3M 44202011 001

2 I/J

3AE1 013-2 ... 1250 275 150 � 3 20 36 22.4 50/52

60 20 2.1 129 140 105 75 80/120

3M 44202011 001

2 I/J

3AE1 014-1 ... 800 275 150 � 3 25 36 28 63/65

60 20 2.1 129 140 105 75 80/120

3M 44202011 001

3 I/J

3AE1 014-2 ... 1250 275 150 � 3 25 36 28 63/65

60 20 2.1 129 140 105 75 80/120

3M 44202011 001

3 I/J

3AE1 015-1 ... 800 275 150 � 3 31.5 36 35.4 80/82

60 20 2.1 129 140 105 75 80/120

3M 44202011 001

4 I/J

3AE1 015-2 ... 1250 275 150 � 3 31.5 36 35.4 80/82

60 20 2.1 129 140 105 75 80/120

3M 44202011 001

4 I/J

3AE1 022-1 ... 800 310 150 � 3 16 36 17.9 40/42

60 20 2.1 129 140 100 75 80/120

3M 44202012 001

1 H/J

3AE1 022-2 ... 1250 310 150 � 3 16 36 17.9 40/42

60 20 2.1 129 140 100 75 80/120

3M 44202012 001

1 H/J

3AE1 023-1 ... 800 310 150 � 3 20 36 22.4 50/52

60 20 2.1 129 140 100 75 80/120

3M 44202012 001

2 H/J

3AE1 023-2 ... 1250 310 150 � 3 20 36 22.4 50/52

60 20 2.1 129 140 100 75 80/120

3M 44202012 001

2 H/J

3AE1 024-1 ... 800 310 150 � 3 25 36 28 63/65

60 20 2.1 129 140 100 75 80/120

3M 44202012 001

3 H/J

3AE1 024-2 ... 1250 310 150 � 3 25 36 28 63/65

60 20 2.1 129 140 100 75 80/120

3M 44202012 001

3 H/J

3AE1 025-1 ... 800 310 150 � 3 31.5 36 35.4 80/82

60 20 2.1 129 140 100 75 80/120

3M 44202012 001

4 H/J

3AE1 025-2 ... 1250 310 150 � 3 31.5 36 35.4 80/82

60 20 2.1 129 140 100 75 80/120

3M 44202012 001

4 H/J

� Standard acc. to IEC 62 271-100 Possible – Not available as slide-in module 1) The weight of the fixed-mounted circuit-breaker with draw-out element increases by the values specified in dimensiondrawing N

Ord

erN

o.

Rat

edn

orm

alcu

rren

t

Wid

thac

ross

flat

s

Pole

-cen

ter

dis

tan

ce

Rate

dop

erat

ing

sequ

ence

:

O-3

min

-CO

-3m

in-C

O

O-0

.3s

-CO

-3m

in-C

O

O-0

.3s

-CO

-15

s-C

O

Rate

dsh

ort-

circ

uitd

urat

ion

Rate

dsh

ort-

circ

uitb

reak

ing

curr

ent

DC

com

pone

ntin

%of

the

rate

dsh

ort-

circ

uitb

reak

ing

curr

ent

Asy

mm

etric

albr

eaki

ngcu

rren

t

Rate

dsh

ort-

circ

uitm

akin

gcu

rren

t(a

t50/

60H

z)

Rate

dlig

htni

ngim

puls

ew

ithst

and

volta

ge

Rate

dsh

ort-

dura

tion

pow

er-f

requ

ency

with

stan

dvo

ltage

Vol

tage

drop

ΔUbe

twee

nco

nnec

tions

(acc

ordi

ngto

IEC

6069

4at

DC

100

A)

Min

imum

cree

page

dist

ance

,in

terr

upte

r

Min

imum

cree

page

dist

ance

,ph

ase-

to-e

arth

Min

imum

clea

ranc

e,ph

ase-

to-p

hase

Min

imum

clea

ranc

e,ph

ase-

to-e

arth

Wei

ght1

)

(fix

ed-m

ount

edci

rcui

t-br

eake

r/slid

e-in

mod

ule)

Det

aile

ddi

men

sion

draw

ing

(has

tobe

orde

red)

Ope

ratin

gcy

cle

diag

ram

No.

(see

page

45)

Cata

log

dim

ensi

ondr

awin

gs(s

eepa

ges

54/5

5)(f

ixed

-mou

nted

circ

uit-

brea

ker/s

lide-

inm

odul

e)

Technical DataElectrical data, dimensions and weights

SION Vacuum Circuit-Breakers

Page 43: SION Vacuum Circuit-Breakers - w3.siemens.com.cn · integration in all customary medium-voltage ... transformers, capacitors, generators, filter circuits ... The operating mechanism

43Siemens HG 11.02 · 2006

3

7.2 kV50/60 Hz

Ir tk Isc Ima Up Ud

A mm mm s kA % kA kA kV kV mV mm mm mm mm kg

3AE1 032-1 ... 800 205 160 � 3 16 36 17.9 40/42

60 20 2.1 129 140 115 75 80/ – 3M 44202016 001

1 G/–

3AE1 032-2 ... 1250 205 160 � 3 16 36 17.9 40/42

60 20 2.1 129 140 115 75 80/ – 3M 44202016 001

1 G/–

3AE1 033-1 ... 800 205 160 � 3 20 36 22.4 50/52

60 20 2.1 129 140 115 75 80/ – 3M 44202016 001

2 G/–

3AE1 033-2 ... 1250 205 160 � 3 20 36 22.4 50/52

60 20 2.1 129 140 115 75 80/ – 3M 44202016 001

2 G/–

3AE1 034-1 ... 800 205 160 � 3 25 36 28 63/65

60 20 2.1 129 140 115 75 80/ – 3M 44202016 001

3 G/–

3AE1 034-2 ... 1250 205 160 � 3 25 36 28 63/65

60 20 2.1 129 140 115 75 80/ – 3M 44202016 001

3 G/–

3AE1 035-1 ... 800 205 160 � 3 31.5 36 35.4 80/82

60 20 2.1 129 140 115 75 80/ – 3M 44202016 001

4 G/–

3AE1 035-2 ... 1250 205 160 � 3 31.5 36 35.4 80/82

60 20 2.1 129 140 115 75 80/ – 3M 44202016 001

4 G/–

3AE1 042-1 ... 800 275 160 � 3 16 36 17.9 40/42

60 20 2.1 129 140 115 75 80/ – 3M 44202017 001

1 F/–

3AE1 042-2 ... 1250 275 160 � 3 16 36 17.9 40/42

60 20 2.1 129 140 115 75 80/ – 3M 44202017 001

1 F/–

3AE1 043-1 ... 800 275 160 � 3 20 36 22.4 50/52

60 20 2.1 129 140 115 75 80/ – 3M 44202017 001

2 F/–

3AE1 043-2 ... 1250 275 160 � 3 20 36 22.4 50/52

60 20 2.1 129 140 115 75 80/ – 3M 44202017 001

2 F/–

3AE1 044-1 ... 800 275 160 � 3 25 36 28 63/65

60 20 2.1 129 140 115 75 80/ – 3M 44202017 001

3 F/–

3AE1 044-2 ... 1250 275 160 � 3 25 36 28 63/65

60 20 2.1 129 140 115 75 80/ – 3M 44202017 001

3 F/–

3AE1 045-1 ... 800 275 160 � 3 31.5 36 35.4 80/82

60 20 2.1 129 140 115 75 80/ – 3M 44202017 001

4 F/–

3AE1 045-2 ... 1250 275 160 � 3 31.5 36 35.4 80/82

60 20 2.1 129 140 115 75 80/ – 3M 44202017 001

4 F/–

3AE1 052-1 ... 800 310 160 � 3 16 36 17.9 40/42

60 20 2.1 129 140 110 75 80/ – 3M 44202018 001

1 E/–

3AE1 052-2 ... 1250 310 160 � 3 16 36 17.9 40/42

60 20 2.1 129 140 110 75 80/ – 3M 44202018 001

1 E/–

3AE1 053-1 ... 800 310 160 � 3 20 36 22.4 50/52

60 20 2.1 129 140 110 75 80/ – 3M 44202018 001

2 E/–

3AE1 053-2 ... 1250 310 160 � 3 20 36 22.4 50/52

60 20 2.1 129 140 110 75 80/ – 3M 44202018 001

2 E/–

3AE1 054-1 ... 800 310 160 � 3 25 36 28 63/65

60 20 2.1 129 140 110 75 80/ – 3M 44202018 001

3 E/–

3AE1 054-2 ... 1250 310 160 � 3 25 36 28 63/65

60 20 2.1 129 140 110 75 80/ – 3M 44202018 001

3 E/–

3AE1 055-1 ... 800 310 160 � 3 31.5 36 35.4 80/82

60 20 2.1 129 140 110 75 80/ – 3M 44202018 001

4 E/–

3AE1 055-2 ... 1250 310 160 � 3 31.5 36 35.4 80/82

60 20 2.1 129 140 110 75 80/ – 3M 44202018 001

4 E/–

3AE1 062-1 ... 800 205 210 � 3 16 36 17.9 40/42

60 20 2.1 129 140 165 75 90/ – 3M 44202022 001

1 D/–

3AE1 062-2 ... 1250 205 210 � 3 16 36 17.9 40/42

60 20 2.1 129 140 165 75 90/ – 3M 44202022 001

1 D/–

� Standard acc. to IEC 62 271-100 Possible – Not available as slide-in module 1) The weight of the fixed-mounted circuit-breaker with draw-out element increases by the values specified in dimensiondrawing N

Technical DataElectrical data, dimensions and weights

SION Vacuum Circuit-Breakers

Ord

erN

o.

Rat

edn

orm

alcu

rren

t

Wid

thac

ross

flat

s

Pole

-cen

ter

dis

tan

ce

Rate

dop

erat

ing

sequ

ence

:

O-3

min

-CO

-3m

in-C

O

O-0

.3s

-CO

-3m

in-C

O

O-0

.3s

-CO

-15

s-C

O

Rate

dsh

ort-

circ

uitd

urat

ion

Rate

dsh

ort-

circ

uitb

reak

ing

curr

ent

DC

com

pone

ntin

%of

the

rate

dsh

ort-

circ

uitb

reak

ing

curr

ent

Asy

mm

etric

albr

eaki

ngcu

rren

t

Rate

dsh

ort-

circ

uitm

akin

gcu

rren

t(a

t50/

60H

z)

Rate

dlig

htni

ngim

puls

ew

ithst

and

volta

ge

Rate

dsh

ort-

dura

tion

pow

er-f

requ

ency

with

stan

dvo

ltage

Vol

tage

drop

ΔUbe

twee

nco

nnec

tions

(acc

ordi

ngto

IEC

6069

4at

DC

100

A)

Min

imum

cree

page

dist

ance

,in

terr

upte

r

Min

imum

cree

page

dist

ance

,ph

ase-

to-e

arth

Min

imum

clea

ranc

e,ph

ase-

to-p

hase

Min

imum

clea

ranc

e,ph

ase-

to-e

arth

Wei

ght1

)

(fix

ed-m

ount

edci

rcui

t-br

eake

r/slid

e-in

mod

ule)

Det

aile

ddi

men

sion

draw

ing

(has

tobe

orde

red)

Ope

ratin

gcy

cle

diag

ram

No.

(see

page

45)

Cata

log

dim

ensi

ondr

awin

gs(s

eepa

ges

54/5

5)(f

ixed

-mou

nted

circ

uit-

brea

ker/s

lide-

inm

odul

e)

Page 44: SION Vacuum Circuit-Breakers - w3.siemens.com.cn · integration in all customary medium-voltage ... transformers, capacitors, generators, filter circuits ... The operating mechanism

44 Siemens HG 11.02 · 2006

3

7.2 kV50/60 Hz

Ir tk Isc Ima Up Ud

A mm mm s kA % kA kA kV kV mV mm mm mm mm kg

3AE1 063-1 ... 800 205 210 � 3 20 36 22.4 50/52

60 20 2.1 129 140 165 75 90/ – 3M 44202022 001

2 D/–

3AE1 063-2 ... 1250 205 210 � 3 20 36 22.4 50/52

60 20 2.1 129 140 165 75 90/ – 3M 44202022 001

2 D/–

3AE1 064-1 ... 800 205 210 � 3 25 36 28 63/65

60 20 2.1 129 140 165 75 90/ – 3M 44202022 001

3 D/–

3AE1 064-2 ... 1250 205 210 � 3 25 36 28 63/65

60 20 2.1 129 140 165 75 90/ – 3M 44202022 001

3 D/–

3AE1 065-1 ... 800 205 210 � 3 31.5 36 35.4 80/82

60 20 2.1 129 140 165 75 90/ – 3M 44202022 001

4 D/–

3AE1 065-2 ... 1250 205 210 � 3 31.5 36 35.4 80/82

60 20 2.1 129 140 165 75 90/ – 3M 44202022 001

4 D/–

3AE1 072-1 ... 800 275 210 � 3 16 36 17.9 40/42

60 20 2.1 129 140 165 75 90/130

3M 44202023 001

1 B/C

3AE1 072-2 ... 1250 275 210 � 3 16 36 17.9 40/42

60 20 2.1 129 140 165 75 90/130

3M 44202023 001

1 B/C

3AE1 073-1 ... 800 275 210 � 3 20 36 22.4 50/52

60 20 2.1 129 140 165 75 90/130

3M 44202023 001

2 B/C

3AE1 073-2 ... 1250 275 210 � 3 20 36 22.4 50/52

60 20 2.1 129 140 165 75 90/130

3M 44202023 001

2 B/C

3AE1 074-1 ... 800 275 210 � 3 25 36 28 63/65

60 20 2.1 129 140 165 75 90/130

3M 44202023 001

3 B/C

3AE1 074-2 ... 1250 275 210 � 3 25 36 28 63/65

60 20 2.1 129 140 165 75 90/130

3M 44202023 001

3 B/C

3AE1 075-1 ... 800 275 210 � 3 31.5 36 35.4 80/82

60 20 2.1 129 140 165 75 90/130

3M 44202023 001

4 B/C

3AE1 075-2 ... 1250 275 210 � 3 31.5 36 35.4 80/82

60 20 2.1 129 140 165 75 90/130

3M 44202023 001

4 B/C

3AE1 082-1 ... 800 310 210 � 3 16 36 17.9 40/42

60 20 2.1 129 140 160 75 90/130

3M 44202024 001

1 A/C

3AE1 082-2 ... 1250 310 210 � 3 16 36 17.9 40/42

60 20 2.1 129 140 160 75 90/130

3M 44202024 001

1 A/C

3AE1 083-1 ... 800 310 210 � 3 20 36 22.4 50/52

60 20 2.1 129 140 160 75 90/130

3M 44202024 001

2 A/C

3AE1 083-2 ... 1250 310 210 � 3 20 36 22.4 50/52

60 20 2.1 129 140 160 75 90/130

3M 44202024 001

2 A/C

3AE1 084-1 ... 800 310 210 � 3 25 36 28 63/65

60 20 2.1 129 140 160 75 90/130

3M 44202024 001

3 A/C

3AE1 084-2 ... 1250 310 210 � 3 25 36 28 63/65

60 20 2.1 129 140 160 75 90/130

3M 44202024 001

3 A/C

3AE1 084-4 ... 2000 310 210 � 3 25 36 28 63/65

60 20 1.5 129 265 130 130 110/150

3M 44202028 001

3 L/C

3AE1 085-1 ... 800 310 210 � 3 31.5 36 35.4 80/82

60 20 2.1 129 140 160 75 90/130

3M 44202024 001

4 A/C

3AE1 085-2 ... 1250 310 210 � 3 31.5 36 35.4 80/82

60 20 2.1 129 140 160 75 90/130

3M 44202024 001

4 A/C

3AE1 085-4 ... 2000 310 210 � 3 31.5 36 35.4 80/82

60 20 1.5 129 265 130 130 110/150

3M 44202028 001

4 L/C

3AE1 085-6 ... 2500 310 210 � 3 31.5 36 35.4 80/82

60 20 1.5 129 265 130 130 110/150

3M 44202028 001

4 L/C

� Standard acc. to IEC 62 271-100 Possible – Not available as slide-in module 1) The weight of the fixed-mounted circuit-breaker with draw-out element increases by the values specified in dimensiondrawing N

Technical DataElectrical data, dimensions and weights

SION Vacuum Circuit-Breakers

Ord

erN

o.

Rat

edn

orm

alcu

rren

t

Wid

thac

ross

flat

s

Pole

-cen

ter

dis

tan

ce

Rate

dop

erat

ing

sequ

ence

:

O-3

min

-CO

-3m

in-C

O

O-0

.3s

-CO

-3m

in-C

O

O-0

.3s

-CO

-15

s-C

O

Rate

dsh

ort-

circ

uitd

urat

ion

Rate

dsh

ort-

circ

uitb

reak

ing

curr

ent

DC

com

pone

ntin

%of

the

rate

dsh

ort-

circ

uitb

reak

ing

curr

ent

Asy

mm

etric

albr

eaki

ngcu

rren

t

Rate

dsh

ort-

circ

uitm

akin

gcu

rren

t(a

t50/

60H

z)

Rate

dlig

htni

ngim

puls

ew

ithst

and

volta

ge

Rate

dsh

ort-

dura

tion

pow

er-f

requ

ency

with

stan

dvo

ltage

Vol

tage

drop

ΔUbe

twee

nco

nnec

tions

(acc

ordi

ngto

IEC

6069

4at

DC

100

A)

Min

imum

cree

page

dist

ance

,in

terr

upte

r

Min

imum

cree

page

dist

ance

,ph

ase-

to-e

arth

Min

imum

clea

ranc

e,ph

ase-

to-p

hase

Min

imum

clea

ranc

e,ph

ase-

to-e

arth

Wei

ght1

)

(fix

ed-m

ount

edci

rcui

t-br

eake

r/slid

e-in

mod

ule)

Det

aile

ddi

men

sion

draw

ing

(has

tobe

orde

red)

Ope

ratin

gcy

cle

diag

ram

No.

(see

page

45)

Cata

log

dim

ensi

ondr

awin

gs(s

eepa

ges

54/5

5)(f

ixed

-mou

nted

circ

uit-

brea

ker/s

lide-

inm

odul

e)

Page 45: SION Vacuum Circuit-Breakers - w3.siemens.com.cn · integration in all customary medium-voltage ... transformers, capacitors, generators, filter circuits ... The operating mechanism

Operating cycle diagram

�����&������'�(���)���

������

����

����

����

���

���

���

��

��

��

��� � � � �� ��*� ���� ��

��

���

����

����+� �

��

�� �

45Siemens HG 11.02 · 2006

3

7.2 kV50/60 Hz

Ir tk Isc Ima Up Ud

A mm mm s kA % kA kA kV kV mV mm mm mm mm kg

3AE1 086-2 ... 1250 310 210 � 3 40 36 44.9 100/104

60 20 1.7 145 155 169 140 120/160

3M 44202070 001

5 M/C

3AE1 086-4 ... 2000 310 210 � 3 40 36 44.9 100/104

60 20 1.0 145 249 149 140 160/210

3M 44202071 001

5 M/C

3AE1 086-6 ... 2500 310 210 � 3 40 36 44.9 100/104

60 20 1.0 145 249 149 140 160/210

3M 44202071 001

5 M/C

3AE1 086-7 ... 3150 310 210 � 3 40 36 44.9 100/104

60 20 1.0 145 249 149 140 160/210

3M 44202071 001

5 M/C

� Standard acc. to IEC 62 271-100 Possible – Not available as slide-in module 1) The weight of the fixed-mounted circuit-breaker with draw-out element increases by the values specified in dimensiondrawing N

Technical DataElectrical data, dimensions and weights

Operating cycle diagram

�����&������'�(���)���

������

����

����

����

���

���

���

��

����� � � � �� ��*� ��

��

���

����

����

� ���

��

��

The permissible number of

electrical operating cycles

is shown as a function of

the breaking current

(r.m.s. value). All SION

vacuum circuit-breakers

fulfil the endurance classes

E2, M2 and C2 according

to IEC 62 271-100. The

curve shape beyond the

parameters defined in

IEC 62 271-100 is based on

average experience data.

The number of operating

cycles that can actually be

reached can be different

depending on the respec-

tive application.

SION Vacuum Circuit-Breakers

Ord

erN

o.

Rat

edn

orm

alcu

rren

t

Wid

thac

ross

flat

s

Pole

-cen

ter

dis

tan

ce

Rate

dop

erat

ing

sequ

ence

:

O-3

min

-CO

-3m

in-C

O

O-0

.3s

-CO

-3m

in-C

O

O-0

.3s

-CO

-15

s-C

O

Rate

dsh

ort-

circ

uitd

urat

ion

Rate

dsh

ort-

circ

uitb

reak

ing

curr

ent

DC

com

pone

ntin

%of

the

rate

dsh

ort-

circ

uitb

reak

ing

curr

ent

Asy

mm

etric

albr

eaki

ngcu

rren

t

Rate

dsh

ort-

circ

uitm

akin

gcu

rren

t(a

t50/

60H

z)

Rate

dlig

htni

ngim

puls

ew

ithst

and

volta

ge

Rate

dsh

ort-

dura

tion

pow

er-f

requ

ency

with

stan

dvo

ltage

Vol

tage

drop

ΔUbe

twee

nco

nnec

tions

(acc

ordi

ngto

IEC

6069

4at

DC

100

A)

Min

imum

cree

page

dist

ance

,in

terr

upte

r

Min

imum

cree

page

dist

ance

,ph

ase-

to-e

arth

Min

imum

clea

ranc

e,ph

ase-

to-p

hase

Min

imum

clea

ranc

e,ph

ase-

to-e

arth

Wei

ght1

)

(fix

ed-m

ount

edci

rcui

t-br

eake

r/slid

e-in

mod

ule)

Det

aile

ddi

men

sion

draw

ing

(has

tobe

orde

red)

Ope

ratin

gcy

cle

diag

ram

No.

(see

belo

w)

Cata

log

dim

ensi

ondr

awin

gs(s

eepa

ges

54/5

5)(f

ixed

-mou

nted

circ

uit-

brea

ker/s

lide-

inm

odul

e)

Page 46: SION Vacuum Circuit-Breakers - w3.siemens.com.cn · integration in all customary medium-voltage ... transformers, capacitors, generators, filter circuits ... The operating mechanism

46 Siemens HG 11.02 · 2006

3

12 kV50/60 Hz

Ir tk Isc Ima Up Ud

A mm mm s kA % kA kA kV kV mV mm mm mm mm kg

3AE1 102-1 ... 800 205 150 � 3 16 36 17.9 40/42

75 28 2.1 129 140 105 75 80/ – 3M 44202010 001

1 K/–

3AE1 102-2 ... 1250 205 150 � 3 16 36 17.9 40/42

75 28 2.1 129 140 105 75 80/ – 3M 44202010 001

1 K/–

3AE1 103-1 ... 800 205 150 � 3 20 36 22.4 50/52

75 28 2.1 129 140 105 75 80/ – 3M 44202010 001

2 K/–

3AE1 103-2 ... 1250 205 150 � 3 20 36 22.4 50/52

75 28 2.1 129 140 105 75 80/ – 3M 44202010 001

2 K/–

3AE1 104-1 ... 800 205 150 � 3 25 36 28 63/65

75 28 2.1 129 140 105 75 80/ – 3M 44202010 001

3 K/–

3AE1 104-2 ... 1250 205 150 � 3 25 36 28 63/65

75 28 2.1 129 140 105 75 80/ – 3M 44202010 001

3 K/–

3AE1 105-1 ... 800 205 150 � 3 31.5 36 35.4 80/82

75 28 2.1 129 140 105 75 80/ – 3M 44202010 001

4 K/–

3AE1 105-2 ... 1250 205 150 � 3 31.5 36 35.4 80/82

75 28 2.1 129 140 105 75 80/ – 3M 44202010 001

4 K/–

3AE1 112-1 ... 800 275 150 � 3 16 36 17.9 40/42

75 28 2.1 129 140 105 75 80/120

3M 44202011 001

1 I/J

3AE1 112-2 ... 1250 275 150 � 3 16 36 17.9 40/42

75 28 2.1 129 140 105 75 80/120

3M 44202011 001

1 I/J

3AE1 113-1 ... 800 275 150 � 3 20 36 22.4 50/52

75 28 2.1 129 140 105 75 80/120

3M 44202011 001

2 I/J

3AE1 113-2 ... 1250 275 150 � 3 20 36 22.4 50/52

75 28 2.1 129 140 105 75 80/120

3M 44202011 001

2 I/J

3AE1 114-1 ... 800 275 150 � 3 25 36 28 63/65

75 28 2.1 129 140 105 75 80/120

3M 44202011 001

3 I/J

3AE1 114-2 ... 1250 275 150 � 3 25 36 28 63/65

75 28 2.1 129 140 105 75 80/120

3M 44202011 001

3 I/J

3AE1 115-1 ... 800 275 150 � 3 31.5 36 35.4 80/82

75 28 2.1 129 140 105 75 80/120

3M 44202011 001

4 I/J

3AE1 115-2 ... 1250 275 150 � 3 31.5 36 35.4 80/82

75 28 2.1 129 140 105 75 80/120

3M 44202011 001

4 I/J

3AE1 122-1 ... 800 310 150 � 3 16 36 17.9 40/42

75 28 2.1 129 140 100 75 80/120

3M 44202012 001

1 H/J

3AE1 122-2 ... 1250 310 150 � 3 16 36 17.9 40/42

75 28 2.1 129 140 100 75 80/120

3M 44202012 001

1 H/J

3AE1 123-1 ... 800 310 150 � 3 20 36 22.4 50/52

75 28 2.1 129 140 100 75 80/120

3M 44202012 001

2 H/J

3AE1 123-2 ... 1250 310 150 � 3 20 36 22.4 50/52

75 28 2.1 129 140 100 75 80/120

3M 44202012 001

2 H/J

3AE1 124-1 ... 800 310 150 � 3 25 36 28 63/65

75 28 2.1 129 140 100 75 80/120

3M 44202012 001

3 H/J

3AE1 124-2 ... 1250 310 150 � 3 25 36 28 63/65

75 28 2.1 129 140 100 75 80/120

3M 44202012 001

3 H/J

3AE1 125-1 ... 800 310 150 � 3 31.5 36 35.4 80/82

75 28 2.1 129 140 100 75 80/120

3M 44202012 001

4 H/J

3AE1 125-2 ... 1250 310 150 � 3 31.5 36 35.4 80/82

75 28 2.1 129 140 100 75 80/120

3M 44202012 001

4 H/J

3AE1 132-1 ... 800 205 160 � 3 16 36 17.9 40/42

75 28 2.1 129 140 115 75 80/ – 3M 44202016 001

1 G/–

3AE1 132-2 ... 1250 205 160 � 3 16 36 17.9 40/42

75 28 2.1 129 140 115 75 80/ – 3M 44202016 001

1 G/–

� Standard acc. to IEC 62 271-100 Possible – Not available as slide-in module 1) The weight of the fixed-mounted circuit-breaker with draw-out element increases by the values specified in dimensiondrawing N

Technical DataElectrical data, dimensions and weights

SION Vacuum Circuit-Breakers

Ord

erN

o.

Rat

edn

orm

alcu

rren

t

Wid

thac

ross

flat

s

Pole

-cen

ter

dis

tan

ce

Rate

dop

erat

ing

sequ

ence

:

O-3

min

-CO

-3m

in-C

O

O-0

.3s

-CO

-3m

in-C

O

O-0

.3s

-CO

-15

s-C

O

Rate

dsh

ort-

circ

uitd

urat

ion

Rate

dsh

ort-

circ

uitb

reak

ing

curr

ent

DC

com

pone

ntin

%of

the

rate

dsh

ort-

circ

uitb

reak

ing

curr

ent

Asy

mm

etric

albr

eaki

ngcu

rren

t

Rate

dsh

ort-

circ

uitm

akin

gcu

rren

t(a

t50/

60H

z)

Rate

dlig

htni

ngim

puls

ew

ithst

and

volta

ge

Rate

dsh

ort-

dura

tion

pow

er-f

requ

ency

with

stan

dvo

ltage

Vol

tage

drop

ΔUbe

twee

nco

nnec

tions

(acc

ordi

ngto

IEC

6069

4at

DC

100

A)

Min

imum

cree

page

dist

ance

,in

terr

upte

r

Min

imum

cree

page

dist

ance

,ph

ase-

to-e

arth

Min

imum

clea

ranc

e,ph

ase-

to-p

hase

Min

imum

clea

ranc

e,ph

ase-

to-e

arth

Wei

ght1

)

(fix

ed-m

ount

edci

rcui

t-br

eake

r/slid

e-in

mod

ule)

Det

aile

ddi

men

sion

draw

ing

(has

tobe

orde

red)

Ope

ratin

gcy

cle

diag

ram

No.

(see

page

49)

Cata

log

dim

ensi

ondr

awin

gs(s

eepa

ges

54/5

5)(f

ixed

-mou

nted

circ

uit-

brea

ker/s

lide-

inm

odul

e)

Page 47: SION Vacuum Circuit-Breakers - w3.siemens.com.cn · integration in all customary medium-voltage ... transformers, capacitors, generators, filter circuits ... The operating mechanism

47Siemens HG 11.02 · 2006

3

12 kV50/60 Hz

Ir tk Isc Ima Up Ud

A mm mm s kA % kA kA kV kV mV mm mm mm mm kg

3AE1 133-1 ... 800 205 160 � 3 20 36 22.4 50/52

75 28 2.1 129 140 115 75 80/ – 3M 44202016 001

2 G/–

3AE1 133-2 ... 1250 205 160 � 3 20 36 22.4 50/52

75 28 2.1 129 140 115 75 80/ – 3M 44202016 001

2 G/–

3AE1 134-1 ... 800 205 160 � 3 25 36 28 63/65

75 28 2.1 129 140 115 75 80/ – 3M 44202016 001

3 G/–

3AE1 134-2 ... 1250 205 160 � 3 25 36 28 63/65

75 28 2.1 129 140 115 75 80/ – 3M 44202016 001

3 G/–

3AE1 135-1 ... 800 205 160 � 3 31.5 36 35.4 80/82

75 28 2.1 129 140 115 75 80/ – 3M 44202016 001

4 G/–

3AE1 135-2 ... 1250 205 160 � 3 31.5 36 35.4 80/82

75 28 2.1 129 140 115 75 80/ – 3M 44202016 001

4 G/–

3AE1 142-1 ... 800 275 160 � 3 16 36 17.9 40/42

75 28 2.1 129 140 115 75 80/ – 3M 44202017 001

1 F/–

3AE1 142-2 ... 1250 275 160 � 3 16 36 17.9 40/42

75 28 2.1 129 140 115 75 80/ – 3M 44202017 001

1 F/–

3AE1 143-1 ... 800 275 160 � 3 20 36 22.4 50/52

75 28 2.1 129 140 115 75 80/ – 3M 44202017 001

2 F/–

3AE1 143-2 ... 1250 275 160 � 3 20 36 22.4 50/52

75 28 2.1 129 140 115 75 80/ – 3M 44202017 001

2 F/–

3AE1 144-1 ... 800 275 160 � 3 25 36 28 63/65

75 28 2.1 129 140 115 75 80/ – 3M 44202017 001

3 F/–

3AE1 144-2 ... 1250 275 160 � 3 25 36 28 63/65

75 28 2.1 129 140 115 75 80/ – 3M 44202017 001

3 F/–

3AE1 145-1 ... 800 275 160 � 3 31.5 36 35.4 80/82

75 28 2.1 129 140 115 75 80/ – 3M 44202017 001

4 F/–

3AE1 145-2 ... 1250 275 160 � 3 31.5 36 35.4 80/82

75 28 2.1 129 140 115 75 80/ – 3M 44202017 001

4 F/–

3AE1 152-1 ... 800 310 160 � 3 16 36 17.9 40/42

75 28 2.1 129 140 110 75 80/ – 3M 44202018 001

1 E/–

3AE1 152-2 ... 1250 310 160 � 3 16 36 17.9 40/42

75 28 2.1 129 140 110 75 80/ – 3M 44202018 001

1 E/–

3AE1 153-1 ... 800 310 160 � 3 20 36 22.4 50/52

75 28 2.1 129 140 110 75 80/ – 3M 44202018 001

2 E/–

3AE1 153-2 ... 1250 310 160 � 3 20 36 22.4 50/52

75 28 2.1 129 140 110 75 80/ – 3M 44202018 001

2 E/–

3AE1 154-1 ... 800 310 160 � 3 25 36 28 63/65

75 28 2.1 129 140 110 75 80/ – 3M 44202018 001

3 E/–

3AE1 154-2 ... 1250 310 160 � 3 25 36 28 63/65

75 28 2.1 129 140 110 75 80/ – 3M 44202018 001

3 E/–

3AE1 155-1 ... 800 310 160 � 3 31.5 36 35.4 80/82

75 28 2.1 129 140 110 75 80/ – 3M 44202018 001

4 E/–

3AE1 155-2 ... 1250 310 160 � 3 31.5 36 35.4 80/82

75 28 2.1 129 140 110 75 80/ – 3M 44202018 001

4 E/–

3AE1 162-1 ... 800 205 210 � 3 16 36 17.9 40/42

75 28 2.1 129 140 165 75 90/ – 3M 44202022 001

1 D/–

3AE1 162-2 ... 1250 205 210 � 3 16 36 17.9 40/42

75 28 2.1 129 140 165 75 90/ – 3M 44202022 001

1 D/–

3AE1 163-1 ... 800 205 210 � 3 20 36 22.4 50/52

75 28 2.1 129 140 165 75 90/ – 3M 44202022 001

2 D/–

3AE1 163-2 ... 1250 205 210 � 3 20 36 22.4 50/52

75 28 2.1 129 140 165 75 90/ – 3M 44202022 001

2 D/–

� Standard acc. to IEC 62 271-100 Possible – Not available as slide-in module 1) The weight of the fixed-mounted circuit-breaker with draw-out element increases by the values specified in dimensiondrawing N

Technical DataElectrical data, dimensions and weights

SION Vacuum Circuit-Breakers

Ord

erN

o.

Rat

edn

orm

alcu

rren

t

Wid

thac

ross

flat

s

Pole

-cen

ter

dis

tan

ce

Rate

dop

erat

ing

sequ

ence

:

O-3

min

-CO

-3m

in-C

O

O-0

.3s

-CO

-3m

in-C

O

O-0

.3s

-CO

-15

s-C

O

Rate

dsh

ort-

circ

uitd

urat

ion

Rate

dsh

ort-

circ

uitb

reak

ing

curr

ent

DC

com

pone

ntin

%of

the

rate

dsh

ort-

circ

uitb

reak

ing

curr

ent

Asy

mm

etric

albr

eaki

ngcu

rren

t

Rate

dsh

ort-

circ

uitm

akin

gcu

rren

t(a

t50/

60H

z)

Rate

dlig

htni

ngim

puls

ew

ithst

and

volta

ge

Rate

dsh

ort-

dura

tion

pow

er-f

requ

ency

with

stan

dvo

ltage

Vol

tage

drop

ΔUbe

twee

nco

nnec

tions

(acc

ordi

ngto

IEC

6069

4at

DC

100

A)

Min

imum

cree

page

dist

ance

,in

terr

upte

r

Min

imum

cree

page

dist

ance

,ph

ase-

to-e

arth

Min

imum

clea

ranc

e,ph

ase-

to-p

hase

Min

imum

clea

ranc

e,ph

ase-

to-e

arth

Wei

ght1

)

(fix

ed-m

ount

edci

rcui

t-br

eake

r/slid

e-in

mod

ule)

Det

aile

ddi

men

sion

draw

ing

(has

tobe

orde

red)

Ope

ratin

gcy

cle

diag

ram

No.

(see

page

49)

Cata

log

dim

ensi

ondr

awin

gs(s

eepa

ges

54/5

5)(f

ixed

-mou

nted

circ

uit-

brea

ker/s

lide-

inm

odul

e)

Page 48: SION Vacuum Circuit-Breakers - w3.siemens.com.cn · integration in all customary medium-voltage ... transformers, capacitors, generators, filter circuits ... The operating mechanism

48 Siemens HG 11.02 · 2006

3

12 kV50/60 Hz

Ir tk Isc Ima Up Ud

A mm mm s kA % kA kA kV kV mV mm mm mm mm kg

3AE1 164-1 ... 800 205 210 � 3 25 36 28 63/65

75 28 2.1 129 140 165 75 90/ – 3M 44202022 001

3 D/–

3AE1 164-2 ... 1250 205 210 � 3 25 36 28 63/65

75 28 2.1 129 140 165 75 90/ – 3M 44202022 001

3 D/–

3AE1 165-1 ... 800 205 210 � 3 31.5 36 35.4 80/82

75 28 2.1 129 140 165 75 90/ – 3M 44202022 001

4 D/–

3AE1 165-2 ... 1250 205 210 � 3 31.5 36 35.4 80/82

75 28 2.1 129 140 165 75 90/ – 3M 44202022 001

4 D/–

3AE1 172-1 ... 800 275 210 � 3 16 36 17.9 40/42

75 28 2.1 129 140 165 75 90/130

3M 44202023 001

1 B/C

3AE1 172-2 ... 1250 275 210 � 3 16 36 17.9 40/42

75 28 2.1 129 140 165 75 90/130

3M 44202023 001

1 B/C

3AE1 173-1 ... 800 275 210 � 3 20 36 22.4 50/52

75 28 2.1 129 140 165 75 90/130

3M 44202023 001

2 B/C

3AE1 173-2 ... 1250 275 210 � 3 20 36 22.4 50/52

75 28 2.1 129 140 165 75 90/130

3M 44202023 001

2 B/C

3AE1 174-1 ... 800 275 210 � 3 25 36 28 63/65

75 28 2.1 129 140 165 75 90/130

3M 44202023 001

3 B/C

3AE1 174-2 ... 1250 275 210 � 3 25 36 28 63/65

75 28 2.1 129 140 165 75 90/130

3M 44202023 001

3 B/C

3AE1 175-1 ... 800 275 210 � 3 31.5 36 35.4 80/82

75 28 2.1 129 140 165 75 90/130

3M 44202023 001

4 B/C

3AE1 175-2 ... 1250 275 210 � 3 31.5 36 35.4 80/82

75 28 2.1 129 140 165 75 90/130

3M 44202023 001

4 B/C

3AE1 182-1 ... 800 310 210 � 3 16 36 17.9 40/42

75 28 2.1 129 140 160 75 90/130

3M 44202024 001

1 A/C

3AE1 182-2 ... 1250 310 210 � 3 16 36 17.9 40/42

75 28 2.1 129 140 160 75 90/130

3M 44202024 001

1 A/C

3AE1 183-1 ... 800 310 210 � 3 20 36 22.4 50/52

75 28 2.1 129 140 160 75 90/130

3M 44202024 001

2 A/C

3AE1 183-2 ... 1250 310 210 � 3 20 36 22.4 50/52

75 28 2.1 129 140 160 75 90/130

3M 44202024 001

2 A/C

3AE1 184-1 ... 800 310 210 � 3 25 36 28 63/65

75 28 2.1 129 140 160 75 90/130

3M 44202024 001

3 A/C

3AE1 184-2 ... 1250 310 210 � 3 25 36 28 63/65

75 28 2.1 129 140 160 75 90/130

3M 44202024 001

3 A/C

3AE1 184-4 ... 2000 310 210 � 3 25 36 28 63/65

75 28 1.5 129 265 130 130 110/150

3M 44202028 001

3 L/C

3AE1 184-6 ... 2500 310 210 � 3 25 36 28 63/65

75 28 1.5 129 265 130 130 110/150

3M 44202028 001

3 L/C

3AE1 185-1 ... 800 310 210 � 3 31.5 36 35.4 80/82

75 28 2.1 129 140 160 75 90/130

3M 44202024 001

4 A/C

3AE1 185-2 ... 1250 310 210 � 3 31.5 36 35.4 80/82

75 28 2.1 129 140 160 75 90/130

3M 44202024 001

4 A/C

3AE1 185-4 ... 2000 310 210 � 3 31.5 36 35.4 80/82

75 28 1.5 129 265 130 130 110/150

3M 44202028 001

4 L/C

3AE1 185-6 ... 2500 310 210 � 3 31.5 36 35.4 80/82

75 28 1.5 129 265 130 130 110/150

3M 44202028 001

4 L/C

� Standard acc. to IEC 62 271-100 Possible – Not available as slide-in module 1) The weight of the fixed-mounted circuit-breaker with draw-out element increases by the values specified in dimensiondrawing N

Technical DataElectrical data, dimensions and weights

SION Vacuum Circuit-Breakers

Ord

erN

o.

Rat

edn

orm

alcu

rren

t

Wid

thac

ross

flat

s

Pole

-cen

ter

dis

tan

ce

Rate

dop

erat

ing

sequ

ence

:

O-3

min

-CO

-3m

in-C

O

O-0

.3s

-CO

-3m

in-C

O

O-0

.3s

-CO

-15

s-C

O

Rate

dsh

ort-

circ

uitd

urat

ion

Rate

dsh

ort-

circ

uitb

reak

ing

curr

ent

DC

com

pone

ntin

%of

the

rate

dsh

ort-

circ

uitb

reak

ing

curr

ent

Asy

mm

etric

albr

eaki

ngcu

rren

t

Rate

dsh

ort-

circ

uitm

akin

gcu

rren

t(a

t50/

60H

z)

Rate

dlig

htni

ngim

puls

ew

ithst

and

volta

ge

Rate

dsh

ort-

dura

tion

pow

er-f

requ

ency

with

stan

dvo

ltage

Vol

tage

drop

ΔUbe

twee

nco

nnec

tions

(acc

ordi

ngto

IEC

6069

4at

DC

100

A)

Min

imum

cree

page

dist

ance

,in

terr

upte

r

Min

imum

cree

page

dist

ance

,ph

ase-

to-e

arth

Min

imum

clea

ranc

e,ph

ase-

to-p

hase

Min

imum

clea

ranc

e,ph

ase-

to-e

arth

Wei

ght1

)

(fix

ed-m

ount

edci

rcui

t-br

eake

r/slid

e-in

mod

ule)

Det

aile

ddi

men

sion

draw

ing

(has

tobe

orde

red)

Ope

ratin

gcy

cle

diag

ram

No.

(see

page

49)

Cata

log

dim

ensi

ondr

awin

gs(s

eepa

ges

54/5

5)(f

ixed

-mou

nted

circ

uit-

brea

ker/s

lide-

inm

odul

e)

Page 49: SION Vacuum Circuit-Breakers - w3.siemens.com.cn · integration in all customary medium-voltage ... transformers, capacitors, generators, filter circuits ... The operating mechanism

49Siemens HG 11.02 · 2006

3

12 kV50/60 Hz

Ir tk Isc Ima Up Ud

A mm mm s kA % kA kA kV kV mV mm mm mm mm kg

3AE1 186-2 ... 1250 310 210 � 3 40 36 44.9 100/104

75 28 1.7 145 155 169 140 120/160

3M 44202070 001

5 M/C

3AE1 186-4 ... 2000 310 210 � 3 40 36 44.9 100/104

75 28 1.0 145 249 149 140 160/210

3M 44202071 001

5 M/C

3AE1 186-6 ... 2500 310 210 � 3 40 36 44.9 100/104

75 28 1.0 145 249 149 140 160/210

3M 44202071 001

5 M/C

3AE1 186-7 ... 3150 310 210 � 3 40 36 44.9 100/104

75 28 1.0 145 249 149 140 160/210

3M 44202071 001

5 M/C

3AE1 545-2 ... 1250 275 160 � 3 31.5 36 35.4 80/82

75 28 2.1 129 140 115 75 80/ – – 4 –/–

3AE1 575-2 ... 1250 275 210 � 3 31.5 36 35.4 80/82

75 28 2.1 129 140 160 75 90/ – – 4 –/–

3AE1 575-6 ... 2500 275 210 � 3 31.5 36 35.4 80/82

75 28 1.5 129 265 130 130 110/ – – 4 –/–

3AE1 576-2 ... 1250 275 210 � 3 40 36 44.9 100/104

75 28 1.7 145 155 169 140 120/ – – 5 –/–

3AE1 576-4 ... 2000 275 210 � 3 40 36 44.9 100/104

75 28 1.0 145 249 149 140 160/ – – 5 –/–

3AE1 576-6 ... 2500 310 210 � 3 40 36 44.9 100/104

75 28 1.0 145 249 149 140 160/ – – 5 –/–

3AE1 576-7 ... 3150 310 210 � 3 40 36 44.9 100/104

75 28 1.0 145 249 149 140 160/ – – 5 –/–

� Standard acc. to IEC 62 271-100 Possible – Not available as slide-in module 1) The weight of the fixed-mounted circuit-breaker with draw-out element increases by the values specified in dimensiondrawing N

Technical DataElectrical data, dimensions and weights

Operating cycle diagram Operating cycle diagram

�����&������'�(���)���

������

����

����

����

���

���

���

��

����� � � � �� ��*� ��

��

���

����

����

� ���

��

��

The permissible number of

electrical operating cycles

is shown as a function of

the breaking current

(r.m.s. value). All SION

vacuum circuit-breakers

fulfil the endurance classes

E2, M2 and C2 according

to IEC 62 271-100. The

curve shape beyond the

parameters defined in

IEC 62 271-100 is based on

average experience data.

The number of operating

cycles that can actually be

reached can be different

depending on the respec-

tive application.

�����&������'�(���)���

������

����

����

����

���

���

���

��

��

��

��� � � � �� ��*� ���� ��

��

���

����

����+� �

��

�� �

SION Vacuum Circuit-Breakers

Ord

erN

o.

Rat

edn

orm

alcu

rren

t

Wid

thac

ross

flat

s

Pole

-cen

ter

dis

tan

ce

Rate

dop

erat

ing

sequ

ence

:

O-3

min

-CO

-3m

in-C

O

O-0

.3s

-CO

-3m

in-C

O

O-0

.3s

-CO

-15

s-C

O

Rate

dsh

ort-

circ

uitd

urat

ion

Rate

dsh

ort-

circ

uitb

reak

ing

curr

ent

DC

com

pone

ntin

%of

the

rate

dsh

ort-

circ

uitb

reak

ing

curr

ent

Asy

mm

etric

albr

eaki

ngcu

rren

t

Rate

dsh

ort-

circ

uitm

akin

gcu

rren

t(a

t50/

60H

z)

Rate

dlig

htni

ngim

puls

ew

ithst

and

volta

ge

Rate

dsh

ort-

dura

tion

pow

er-f

requ

ency

with

stan

dvo

ltage

Vol

tage

drop

ΔUbe

twee

nco

nnec

tions

(acc

ordi

ngto

IEC

6069

4at

DC

100

A)

Min

imum

cree

page

dist

ance

,in

terr

upte

r

Min

imum

cree

page

dist

ance

,ph

ase-

to-e

arth

Min

imum

clea

ranc

e,ph

ase-

to-p

hase

Min

imum

clea

ranc

e,ph

ase-

to-e

arth

Wei

ght1

)

(fix

ed-m

ount

edci

rcui

t-br

eake

r/slid

e-in

mod

ule)

Det

aile

ddi

men

sion

draw

ing

(has

tobe

orde

red)

Ope

ratin

gcy

cle

diag

ram

No.

(see

belo

w)

Cata

log

dim

ensi

ondr

awin

gs(s

eepa

ges

54)

(fix

ed-m

ount

edci

rcui

t-br

eake

r/slid

e-in

mod

ule)

Page 50: SION Vacuum Circuit-Breakers - w3.siemens.com.cn · integration in all customary medium-voltage ... transformers, capacitors, generators, filter circuits ... The operating mechanism

50 Siemens HG 11.02 · 2006

3

17.5 kV50/60 Hz

Ir tk Isc Ima Up Ud

A mm mm s kA % kA kA kV kV mV mm mm mm mm kg

3AE1 201-1 ... 800 205 150 � 3 12.5 36 14.9 31/33

95 38 2.1 129 275 237 150 80/ – 3M 44202013 001

1 K/–

3AE1 201-2 ... 1250 205 150 � 3 12.5 36 14.9 31/33

95 38 2.1 129 275 237 150 80/ – 3M 44202013 001

1 K/–

3AE1 202-1 ... 800 205 150 � 3 16 36 17.9 40/42

95 38 2.1 129 275 237 150 80/ – 3M 44202013 001

2 K/–

3AE1 202-2 ... 1250 205 150 � 3 16 36 17.9 40/42

95 38 2.1 129 275 237 150 80/ – 3M 44202013 001

2 K/–

3AE1 204-1 ... 800 205 150 � 3 25 36 28 63/65

95 38 2.1 129 275 237 150 80/ – 3M 44202013 001

3 K/–

3AE1 204-2 ... 1250 205 150 � 3 25 36 28 63/65

95 38 2.1 129 275 237 150 80/ – 3M 44202013 001

3 K/–

3AE1 205-1 ... 800 205 150 � 3 31.5 36 35.4 80/82

95 38 2.1 129 275 237 150 80/ – 3M 44202013 001

4 K/–

3AE1 205-2 ... 1250 205 150 � 3 31.5 36 35.4 80/82

95 38 2.1 129 275 237 150 80/ – 3M 44202013 001

4 K/–

3AE1 211-1 ... 800 275 150 � 3 12.5 36 14.9 31/33

95 38 2.1 129 275 214 150 80/120

3M 44202014 001

1 I/J

3AE1 211-2 ... 1250 275 150 � 3 12.5 36 14.9 31/33

95 38 2.1 129 275 214 150 80/120

3M 44202014 001

1 I/J

3AE1 212-1 ... 800 275 150 � 3 16 36 17.9 40/42

95 38 2.1 129 275 214 150 80/120

3M 44202014 001

2 I/J

3AE1 212-2 ... 1250 275 150 � 3 16 36 17.9 40/42

95 38 2.1 129 275 214 150 80/120

3M 44202014 001

2 I/J

3AE1 214-1 ... 800 275 150 � 3 25 36 28 63/65

95 38 2.1 129 275 214 150 80/120

3M 44202014 001

3 I/J

3AE1 214-2 ... 1250 275 150 � 3 25 36 28 63/65

95 38 2.1 129 275 214 150 80/120

3M 44202014 001

3 I/J

3AE1 215-1 ... 800 275 150 � 3 31.5 36 35.4 80/82

95 38 2.1 129 275 214 150 80/120

3M 44202014 001

4 I/J

3AE1 215-2 ... 1250 275 150 � 3 31.5 36 35.4 80/82

95 38 2.1 129 275 214 150 80/120

3M 44202014 001

4 I/J

3AE1 221-1 ... 800 310 150 � 3 12.5 36 14.9 31/33

95 38 2.1 129 275 190 150 80/120

3M 44202015 001

1 H/J

3AE1 221-2 ... 1250 310 150 � 3 12.5 36 14.9 31/33

95 38 2.1 129 275 190 150 80/120

3M 44202015 001

1 H/J

3AE1 222-1 ... 800 310 150 � 3 16 36 17.9 40/42

95 38 2.1 129 275 190 150 80/120

3M 44202015 001

2 H/J

3AE1 222-2 ... 1250 310 150 � 3 16 36 17.9 40/42

95 38 2.1 129 275 190 150 80/120

3M 44202015 001

2 H/J

3AE1 224-1 ... 800 310 150 � 3 25 36 28 63/65

95 38 2.1 129 275 190 150 80/120

3M 44202015 001

3 H/J

3AE1 224-2 ... 1250 310 150 � 3 25 36 28 63/65

95 38 2.1 129 275 190 150 80/120

3M 44202015 001

3 H/J

3AE1 225-1 ... 800 310 150 � 3 31.5 36 35.4 80/82

95 38 2.1 129 275 190 150 80/120

3M 44202015 001

4 H/J

3AE1 225-2 ... 1250 310 150 � 3 31.5 36 35.4 80/82

95 38 2.1 129 275 190 150 80/120

3M 44202015 001

4 H/J

3AE1 231-1 ... 800 205 160 � 3 12.5 36 14.9 31/33

95 38 2.1 129 275 247 150 80/ – 3M 44202019 001

1 G/–

3AE1 231-2 ... 1250 205 160 � 3 12.5 36 14.9 31/33

95 38 2.1 129 275 247 150 80/ – 3M 44202019 001

1 G/–

� Standard acc. to IEC 62 271-100 Possible – Not available as slide-in module 1) The weight of the fixed-mounted circuit-breaker with draw-out element increases by the values specified in dimensiondrawing N

Technical DataElectrical data, dimensions and weights

SION Vacuum Circuit-Breakers

Ord

erN

o.

Rat

edn

orm

alcu

rren

t

Wid

thac

ross

flat

s

Pole

-cen

ter

dis

tan

ce

Rate

dop

erat

ing

sequ

ence

:

O-3

min

-CO

-3m

in-C

O

O-0

.3s

-CO

-3m

in-C

O

O-0

.3s

-CO

-15

s-C

O

Rate

dsh

ort-

circ

uitd

urat

ion

Rate

dsh

ort-

circ

uitb

reak

ing

curr

ent

DC

com

pone

ntin

%of

the

rate

dsh

ort-

circ

uitb

reak

ing

curr

ent

Asy

mm

etric

albr

eaki

ngcu

rren

t

Rate

dsh

ort-

circ

uitm

akin

gcu

rren

t(a

t50/

60H

z)

Rate

dlig

htni

ngim

puls

ew

ithst

and

volta

ge

Rate

dsh

ort-

dura

tion

pow

er-f

requ

ency

with

stan

dvo

ltage

Vol

tage

drop

ΔUbe

twee

nco

nnec

tions

(acc

ordi

ngto

IEC

6069

4at

DC

100

A)

Min

imum

cree

page

dist

ance

,in

terr

upte

r

Min

imum

cree

page

dist

ance

,ph

ase-

to-e

arth

Min

imum

clea

ranc

e,ph

ase-

to-p

hase

Min

imum

clea

ranc

e,ph

ase-

to-e

arth

Wei

ght1

)

(fix

ed-m

ount

edci

rcui

t-br

eake

r/slid

e-in

mod

ule)

Det

aile

ddi

men

sion

draw

ing

(has

tobe

orde

red)

Ope

ratin

gcy

cle

diag

ram

No.

(see

page

53)

Cata

log

dim

ensi

ondr

awin

gs(s

eepa

ges

54/5

5)(f

ixed

-mou

nted

circ

uit-

brea

ker/s

lide-

inm

odul

e)

Page 51: SION Vacuum Circuit-Breakers - w3.siemens.com.cn · integration in all customary medium-voltage ... transformers, capacitors, generators, filter circuits ... The operating mechanism

51Siemens HG 11.02 · 2006

3

17.5 kV50/60 Hz

Ir tk Isc Ima Up Ud

A mm mm s kA % kA kA kV kV mV mm mm mm mm kg

3AE1 232-1 ... 800 205 160 � 3 16 36 17.9 40/42

95 38 2.1 129 275 247 150 80/ – 3M 44202019 001

2 G/–

3AE1 232-2 ... 1250 205 160 � 3 16 36 17.9 40/42

95 38 2.1 129 275 247 150 80/ – 3M 44202019 001

2 G/–

3AE1 234-1 ... 800 205 160 � 3 25 36 28 63/65

95 38 2.1 129 275 247 150 80/ – 3M 44202019 001

3 G/–

3AE1 234-2 ... 1250 205 160 � 3 25 36 28 63/65

95 38 2.1 129 275 247 150 80/ – 3M 44202019 001

3 G/–

3AE1 235-1 ... 800 205 160 � 3 31.5 36 35.4 80/82

95 38 2.1 129 275 247 150 80/ – 3M 44202019 001

4 G/–

3AE1 235-2 ... 1250 205 160 � 3 31.5 36 35.4 80/82

95 38 2.1 129 275 247 150 80/ – 3M 44202019 001

4 G/–

3AE1 241-1 ... 800 275 160 � 3 12.5 36 14.9 31/33

95 38 2.1 129 275 224 150 80/ – 3M 44202020 001

1 F/–

3AE1 241-2 ... 1250 275 160 � 3 12.5 36 14.9 31/33

95 38 2.1 129 275 224 150 80/ – 3M 44202020 001

1 F/–

3AE1 242-1 ... 800 275 160 � 3 16 36 17.9 40/42

95 38 2.1 129 275 224 150 80/ – 3M 44202020 001

2 F/–

3AE1 242-2 ... 1250 275 160 � 3 16 36 17.9 40/42

95 38 2.1 129 275 224 150 80/ – 3M 44202020 001

2 F/–

3AE1 244-1 ... 800 275 160 � 3 25 36 28 63/65

95 38 2.1 129 275 224 150 80/ – 3M 44202020 001

3 F/–

3AE1 244-2 ... 1250 275 160 � 3 25 36 28 63/65

95 38 2.1 129 275 224 150 80/ – 3M 44202020 001

3 F/–

3AE1 245-1 ... 800 275 160 � 3 31.5 36 35.4 80/82

95 38 2.1 129 275 224 150 80/ – 3M 44202020 001

4 F/–

3AE1 245-2 ... 1250 275 160 � 3 31.5 36 35.4 80/82

95 38 2.1 129 275 224 150 80/ – 3M 44202020 001

4 F/–

3AE1 251-1 ... 800 310 160 � 3 12.5 36 14.9 31/33

95 38 2.1 129 275 200 150 80/ – 3M 44202021 001

1 E/–

3AE1 251-2 ... 1250 310 160 � 3 12.5 36 14.9 31/33

95 38 2.1 129 275 200 150 80/ – 3M 44202021 001

1 E/–

3AE1 252-1 ... 800 310 160 � 3 16 36 17.9 40/42

95 38 2.1 129 275 200 150 80/ – 3M 44202021 001

2 E/–

3AE1 252-2 ... 1250 310 160 � 3 16 36 17.9 40/42

95 38 2.1 129 275 200 150 80/ – 3M 44202021 001

2 E/–

3AE1 254-1 ... 800 310 160 � 3 25 36 28 63/65

95 38 2.1 129 275 200 150 80/ – 3M 44202021 001

3 E/–

3AE1 254-2 ... 1250 310 160 � 3 25 36 28 63/65

95 38 2.1 129 275 200 150 80/ – 3M 44202021 001

3 E/–

3AE1 255-1 ... 800 310 160 � 3 31.5 36 35.4 80/82

95 38 2.1 129 275 200 150 80/ – 3M 44202021 001

4 E/–

3AE1 255-2 ... 1250 310 160 � 3 31.5 36 35.4 80/82

95 38 2.1 129 275 200 150 80/ – 3M 44202021 001

4 E/–

3AE1 261-1 ... 800 205 210 � 3 12.5 36 14.9 31/33

95 38 2.1 129 275 165 150 90/ – 3M 44202025 001

1 D/–

3AE1 261-2 ... 1250 205 210 � 3 12.5 36 14.9 31/33

95 38 2.1 129 275 165 150 90/ – 3M 44202025 001

1 D/–

3AE1 262-1 ... 800 205 210 � 3 16 36 17.9 40/42

95 38 2.1 129 275 165 150 90/ – 3M 44202025 001

2 D/–

3AE1 262-2 ... 1250 205 210 � 3 16 36 17.9 40/42

95 38 2.1 129 275 165 150 90/ – 3M 44202025 001

2 D/–

� Standard acc. to IEC 62 271-100 Possible – Not available as slide-in module 1) The weight of the fixed-mounted circuit-breaker with draw-out element increases by the values specified in dimensiondrawing N

Technical DataElectrical data, dimensions and weights

SION Vacuum Circuit-Breakers

Ord

erN

o.

Rat

edn

orm

alcu

rren

t

Wid

thac

ross

flat

s

Pole

-cen

ter

dis

tan

ce

Rate

dop

erat

ing

sequ

ence

:

O-3

min

-CO

-3m

in-C

O

O-0

.3s

-CO

-3m

in-C

O

O-0

.3s

-CO

-15

s-C

O

Rate

dsh

ort-

circ

uitd

urat

ion

Rate

dsh

ort-

circ

uitb

reak

ing

curr

ent

DC

com

pone

ntin

%of

the

rate

dsh

ort-

circ

uitb

reak

ing

curr

ent

Asy

mm

etric

albr

eaki

ngcu

rren

t

Rate

dsh

ort-

circ

uitm

akin

gcu

rren

t(a

t50/

60H

z)

Rate

dlig

htni

ngim

puls

ew

ithst

and

volta

ge

Rate

dsh

ort-

dura

tion

pow

er-f

requ

ency

with

stan

dvo

ltage

Vol

tage

drop

ΔUbe

twee

nco

nnec

tions

(acc

ordi

ngto

IEC

6069

4at

DC

100

A)

Min

imum

cree

page

dist

ance

,in

terr

upte

r

Min

imum

cree

page

dist

ance

,ph

ase-

to-e

arth

Min

imum

clea

ranc

e,ph

ase-

to-p

hase

Min

imum

clea

ranc

e,ph

ase-

to-e

arth

Wei

ght1

)

(fix

ed-m

ount

edci

rcui

t-br

eake

r/slid

e-in

mod

ule)

Det

aile

ddi

men

sion

draw

ing

(has

tobe

orde

red)

Ope

ratin

gcy

cle

diag

ram

No.

(see

page

53)

Cata

log

dim

ensi

ondr

awin

gs(s

eepa

ges

54/5

5)(f

ixed

-mou

nted

circ

uit-

brea

ker/s

lide-

inm

odul

e)

Page 52: SION Vacuum Circuit-Breakers - w3.siemens.com.cn · integration in all customary medium-voltage ... transformers, capacitors, generators, filter circuits ... The operating mechanism

52 Siemens HG 11.02 · 2006

3

17.5 kV50/60 Hz

Ir tk Isc Ima Up Ud

A mm mm s kA % kA kA kV kV mV mm mm mm mm kg

3AE1 264-1 ... 800 205 210 � 3 25 36 28 63/65

95 38 2.1 129 275 165 150 90/ – 3M 44202025 001

3 D/–

3AE1 264-2 ... 1250 205 210 � 3 25 36 28 63/65

95 38 2.1 129 275 165 150 90/ – 3M 44202025 001

3 D/–

3AE1 265-1 ... 800 205 210 � 3 31.5 36 35.4 80/82

95 38 2.1 129 275 165 150 90/ – 3M 44202025 001

4 D/–

3AE1 265-2 ... 1250 205 210 � 3 31.5 36 35.4 80/82

95 38 2.1 129 275 165 150 90/ – 3M 44202025 001

4 D/–

3AE1 271-1 ... 800 275 210 � 3 12.5 36 14.9 31/33

95 38 2.1 129 275 165 150 90/130

3M 44202026 001

1 B/C

3AE1 271-2 ... 1250 275 210 � 3 12.5 36 14.9 31/33

95 38 2.1 129 275 165 150 90/130

3M 44202026 001

1 B/C

3AE1 272-1 ... 800 275 210 � 3 16 36 17.9 40/42

95 38 2.1 129 275 165 150 90/130

3M 44202026 001

2 B/C

3AE1 272-2 ... 1250 275 210 � 3 16 36 17.9 40/42

95 38 2.1 129 275 165 150 90/130

3M 44202026 001

2 B/C

3AE1 274-1 ... 800 275 210 � 3 25 36 28 63/65

95 38 2.1 129 275 165 150 90/130

3M 44202026 001

3 B/C

3AE1 274-2 ... 1250 275 210 � 3 25 36 28 63/65

95 38 2.1 129 275 165 150 90/130

3M 44202026 001

3 B/C

3AE1 275-1 ... 800 275 210 � 3 31.5 36 35.4 80/82

95 38 2.1 129 275 165 150 90/130

3M 44202026 001

4 B/C

3AE1 275-2 ... 1250 275 210 � 3 31.5 36 35.4 80/82

95 38 2.1 129 275 165 150 90/130

3M 44202026 001

4 B/C

3AE1 281-1 ... 800 310 210 � 3 12.5 36 14.9 31/33

95 38 2.1 129 275 160 150 90/130

3M 44202027 001

1 A/C

3AE1 281-2 ... 1250 310 210 � 3 12.5 36 14.9 31/33

95 38 2.1 129 275 160 150 90/130

3M 44202027 001

1 A/C

3AE1 282-1 ... 800 310 210 � 3 16 36 17.9 40/42

95 38 2.1 129 275 160 150 90/130

3M 44202027 001

2 A/C

3AE1 282-2 ... 1250 310 210 � 3 16 36 17.9 40/42

95 38 2.1 129 275 160 150 90/130

3M 44202027 001

2 A/C

3AE1 284-1 ... 800 310 210 � 3 25 36 28 63/65

95 38 2.1 129 275 160 150 90/130

3M 44202027 001

3 A/C

3AE1 284-2 ... 1250 310 210 � 3 25 36 28 63/65

95 38 2.1 129 275 160 150 90/130

3M 44202027 001

3 A/C

3AE1 284-4 ... 2000 310 210 � 3 25 36 28 63/65

95 38 1.5 129 265 130 130 110/150

3M 44202029 001

3 L/C

3AE1 284-6 ... 2500 310 210 � 3 25 36 28 63/65

95 38 1.5 129 265 130 130 110/150

3M 44202029 001

3 L/C

3AE1 285-1 ... 800 310 210 � 3 31.5 36 35.4 80/82

95 38 2.1 129 275 160 150 90/130

3M 44202027 001

4 A/C

3AE1 285-2 ... 1250 310 210 � 3 31.5 36 35.4 80/82

95 38 2.1 129 275 160 150 90/130

3M 44202027 001

4 A/C

3AE1 285-4 ... 2000 310 210 � 3 31.5 36 35.4 80/82

95 38 1.5 129 265 130 130 110/150

3M 44202029 001

4 L/C

3AE1 285-6 ... 2500 310 210 � 3 31.5 36 35.4 80/82

95 38 1.5 129 265 130 130 110/150

3M 44202029 001

4 L/C

� Standard acc. to IEC 62 271-100 Possible – Not available as slide-in module 1) The weight of the fixed-mounted circuit-breaker with draw-out element increases by the values specified in dimensiondrawing N

Technical DataElectrical data, dimensions and weights

SION Vacuum Circuit-Breakers

Ord

erN

o.

Rat

edn

orm

alcu

rren

t

Wid

thac

ross

flat

s

Pole

-cen

ter

dis

tan

ce

Rate

dop

erat

ing

sequ

ence

:

O-3

min

-CO

-3m

in-C

O

O-0

.3s

-CO

-3m

in-C

O

O-0

.3s

-CO

-15

s-C

O

Rate

dsh

ort-

circ

uitd

urat

ion

Rate

dsh

ort-

circ

uitb

reak

ing

curr

ent

DC

com

pone

ntin

%of

the

rate

dsh

ort-

circ

uitb

reak

ing

curr

ent

Asy

mm

etric

albr

eaki

ngcu

rren

t

Rate

dsh

ort-

circ

uitm

akin

gcu

rren

t(a

t50/

60H

z)

Rate

dlig

htni

ngim

puls

ew

ithst

and

volta

ge

Rate

dsh

ort-

dura

tion

pow

er-f

requ

ency

with

stan

dvo

ltage

Vol

tage

drop

ΔUbe

twee

nco

nnec

tions

(acc

ordi

ngto

IEC

6069

4at

DC

100

A)

Min

imum

cree

page

dist

ance

,in

terr

upte

r

Min

imum

cree

page

dist

ance

,ph

ase-

to-e

arth

Min

imum

clea

ranc

e,ph

ase-

to-p

hase

Min

imum

clea

ranc

e,ph

ase-

to-e

arth

Wei

ght1

)

(fix

ed-m

ount

edci

rcui

t-br

eake

r/slid

e-in

mod

ule)

Det

aile

ddi

men

sion

draw

ing

(has

tobe

orde

red)

Ope

ratin

gcy

cle

diag

ram

No.

(see

page

53)

Cata

log

dim

ensi

ondr

awin

gs(s

eepa

ges

54/5

5)(f

ixed

-mou

nted

circ

uit-

brea

ker/s

lide-

inm

odul

e)

Page 53: SION Vacuum Circuit-Breakers - w3.siemens.com.cn · integration in all customary medium-voltage ... transformers, capacitors, generators, filter circuits ... The operating mechanism

53Siemens HG 11.02 · 2006

3

17.5 kV50/60 Hz

Ir tk Isc Ima Up Ud

A mm mm s kA % kA kA kV kV mV mm mm mm mm kg

3AE1 286-2 ... 1250 310 210 � 3 40 36 44.9 100/104

95 38 1.7 145 249 169 140 120/160

3M 44202070 001

5 M/C

3AE1 286-4 ... 2000 310 210 � 3 40 36 44.9 100/104

95 38 1.0 145 249 149 140 160/210

3M 44202071 001

5 M/C

3AE1 286-6 ... 2500 310 210 � 3 40 36 44.9 100/104

95 38 1.0 145 249 149 140 160/210

3M 44202071 001

5 M/C

3AE1 286-7 ... 3150 310 210 � 3 40 36 44.9 100/104

95 38 1.0 145 249 149 140 160/210

3M 44202071 001

5 M/C

� Standard acc. to IEC 62 271-100 Possible – Not available as slide-in module 1) The weight of the fixed-mounted circuit-breaker with draw-out element increases by the values specified in dimensiondrawing N

Technical DataElectrical data, dimensions and weights

Operating cycle diagram

�����

������

����

����

����

���

���

���

��

��

��

��� � � � �� ��*� ���� ��

��

���

����

����

�� �

��

&������'�(���)���

�� �

Operating cycle diagram

�����

������

����

����

����

���

���

���

��

��

��

��� � � � �� ��*� ������

��

���

����

����

� ��

&������'�(���)���

��

The permissible number of

electrical operating cycles

is shown as a function of

the breaking current

(r.m.s. value). All SION

vacuum circuit-breakers

fulfil the endurance classes

E2, M2 and C2 according

to IEC 62 271-100. The

curve shape beyond the

parameters defined in

IEC 62 271-100 is based on

average experience data.

The number of operating

cycles that can actually be

reached can be different

depending on the respec-

tive application.

SION Vacuum Circuit-Breakers

Ord

erN

o.

Rat

edn

orm

alcu

rren

t

Wid

thac

ross

flat

s

Pole

-cen

ter

dis

tan

ce

Rate

dop

erat

ing

sequ

ence

:

O-3

min

-CO

-3m

in-C

O

O-0

.3s

-CO

-3m

in-C

O

O-0

.3s

-CO

-15

s-C

O

Rate

dsh

ort-

circ

uitd

urat

ion

Rate

dsh

ort-

circ

uitb

reak

ing

curr

ent

DC

com

pone

ntin

%of

the

rate

dsh

ort-

circ

uitb

reak

ing

curr

ent

Asy

mm

etric

albr

eaki

ngcu

rren

t

Rate

dsh

ort-

circ

uitm

akin

gcu

rren

t(a

t50/

60H

z)

Rate

dlig

htni

ngim

puls

ew

ithst

and

volta

ge

Rate

dsh

ort-

dura

tion

pow

er-f

requ

ency

with

stan

dvo

ltage

Vol

tage

drop

ΔUbe

twee

nco

nnec

tions

(acc

ordi

ngto

IEC

6069

4at

DC

100

A)

Min

imum

cree

page

dist

ance

,in

terr

upte

r

Min

imum

cree

page

dist

ance

,ph

ase-

to-e

arth

Min

imum

clea

ranc

e,ph

ase-

to-p

hase

Min

imum

clea

ranc

e,ph

ase-

to-e

arth

Wei

ght1

)

(fix

ed-m

ount

edci

rcui

t-br

eake

r/slid

e-in

mod

ule)

Det

aile

ddi

men

sion

draw

ing

(has

tobe

orde

red)

Ope

ratin

gcy

cle

diag

ram

No.

(see

belo

w)

Cata

log

dim

ensi

ondr

awin

gs(s

eepa

ges

54/5

5)(f

ixed

-mou

nted

circ

uit-

brea

ker/s

lide-

inm

odul

e)

Page 54: SION Vacuum Circuit-Breakers - w3.siemens.com.cn · integration in all customary medium-voltage ... transformers, capacitors, generators, filter circuits ... The operating mechanism

54 Siemens HG 11.02 · 2006

3

Technical DataDimensions drawings for voltage levels 7.2 kV to 17.5 kV

������

��

���,�

���

���

"�#��

��� ������ ���

���,�

���,�

���

���,�

��������

���

Dimension drawing A

������

��

���,�

���

���

"�#��

��� ������ ���

���,�

���,�

���

�����������

Dimension drawing B

���-����.

��

���

��,�

���-����. ������ ���

���,�

��

���

��,�

������

������������

Dimension drawing C

������

��

���,�

���

���

"�#��

��� ������ ���

���,�

���,�

���

�����������

Dimension drawing D

������

��

���,�

���

���

"�#��

��� ������ ���

���,�

���,�

���

���,�

�����������

Dimension drawing E

������

��

���,�

���

���

"�#��

��� ������ ���

���,�

���,�

���

�����������

Dimension drawing F

������

��

���,�

���

���

"�#��

��� ������ ���

���,�

���,�

���

�����������

Dimension drawing G

Width across flats mm Height mm

a b

310 905

275 850

1) for 40 kA

SION Vacuum Circuit-Breakers

Page 55: SION Vacuum Circuit-Breakers - w3.siemens.com.cn · integration in all customary medium-voltage ... transformers, capacitors, generators, filter circuits ... The operating mechanism

55Siemens HG 11.02 · 2006

3

Technical DataDimensions drawings for voltage levels 7.2 kV to 17.5 kV

������

��

���,�

���

���

"�#��

��� ������ ���

���,�

���,�

���

���,�

�����������

Dimension drawing H

������

��

���,�

���

���

"�#��

��� ������ ���

���,�

���,�

���

�����������

Dimension drawing I

������

��

���

��,�

���

��

������

������ ���

���,�

����

��,�

������������

Dimension drawing J

������

��

���,�

���

���

"�#��

��� ������ ���

���,�

���,�

���

��������

���

Dimension drawing K

������

��

���,�

���

���

"�#��

��� ������ ���

���,�

���,�

���

���

�����������

Dimension drawing L

������

��

���

���

���

"�#��

��� ��� ���

���,�

���

�����������

Dimension drawing M

Width across flats mm Height mm

a b

310 905

275 850

SION Vacuum Circuit-Breakers

���

"

���

��������

���

PCD a c d Weight

150 529 500 470 ca. 15 kg

160 529 500 470 ca. 15 kg

210 679 650 620 ca. 20 kg

Height of drawout element: 60

Dimension drawing N

PCD Pole-center distance

a Width of drawout element

c Total width across wheels

d Distance between wheels

Page 56: SION Vacuum Circuit-Breakers - w3.siemens.com.cn · integration in all customary medium-voltage ... transformers, capacitors, generators, filter circuits ... The operating mechanism

56 Siemens HG 11.02 · 2006

3

24 kV50/60 Hz

Ir tk Isc Ima Up Ud

A mm mm s kA % kA kA kV kV mV mm mm mm mm kg

3AE1 321-1 ... 800 310 210 � 3 12.5 36 14.9 31/33

125 50 2.6 200 350 200 210 120/160

3M 44202050 001

1 A/B

3AE1 321-2 ... 1250 310 210 � 3 12.5 36 14.9 31/33

125 50 2.6 200 350 200 210 120/160

3M 44202050 001

1 A/B

3AE1 322-1 ... 800 310 210 � 3 16 36 17.9 40/42

125 50 2.6 200 350 200 210 120/160

3M 44202050 001

2 A/B

3AE1 322-2 ... 1250 310 210 � 3 16 36 17.9 40/42

125 50 2.6 200 350 200 210 120/160

3M 44202050 001

2 A/B

3AE1 322-4 ... 2000 310 210 � 3 16 36 17.9 40/42

125 50 2.0 200 340 200 205 140/180

3M 44202051 001

2 A/B

3AE1 323-1 ... 800 310 210 � 3 20 36 22.4 50/52

125 50 2.6 200 350 200 210 120/160

3M 44202050 001

3 A/B

3AE1 323-2 ... 1250 310 210 � 3 20 36 22.4 50/52

125 50 2.6 200 350 200 210 120/160

3M 44202050 001

3 A/B

3AE1 323-4 ... 2000 310 210 � 3 20 36 22.4 50/52

125 50 2.0 200 340 200 205 140/180

3M 44202051 001

3 A/B

3AE1 323-6 ... 2500 310 210 � 3 20 36 22.4 50/52

125 50 2.0 200 340 200 205 140/180

3M 44202051 001

3 A/B

3AE1 324-1 ... 800 310 210 � 3 25 36 28 63/65

125 50 2.6 200 350 200 210 120/160

3M 44202050 001

4 A/B

3AE1 324-2 ... 1250 310 210 � 3 25 36 28 63/65

125 50 2.6 200 350 200 210 120/160

3M 44202050 001

4 A/B

3AE1 324-4 ... 2000 310 210 � 3 25 36 28 63/65

125 50 2.0 200 340 200 205 140/180

3M 44202051 001

4 A/B

3AE1 324-6 ... 2500 310 210 � 3 25 36 28 63/65

125 50 2.0 200 340 200 205 140/180

3M 44202051 001

4 A/B

3AE1 352-1 ... 800 310 275 � 3 16 36 17.9 40/42

125 50 2.6 200 350 265 210 130/180

3M 44202052 001

2 C/E

3AE1 352-2 ... 1250 310 275 � 3 16 36 17.9 40/42

125 50 2.6 200 350 265 210 130/180

3M 44202052 001

2 C/E

3AE1 352-4 ... 2000 310 275 � 3 16 36 17.9 40/42

125 50 2.0 200 340 265 205 150/200

3M 44202053 001

2 D/E

� Standard acc. to IEC 62 271-100 Possible – Not available as slide-in module 1) The weight of the fixed-mounted circuit-breaker with draw-out element increases by the values specified in dimensiondrawing F

Technical DataElectrical data, dimensions and weights

SION Vacuum Circuit-Breakers

Ord

erN

o.

Rat

edn

orm

alcu

rren

t

Wid

thac

ross

flat

s

Pole

-cen

ter

dis

tan

ce

Rate

dop

erat

ing

sequ

ence

:

O-3

min

-CO

-3m

in-C

O

O-0

.3s

-CO

-3m

in-C

O

O-0

.3s

-CO

-15

s-C

O

Rate

dsh

ort-

circ

uitd

urat

ion

Rate

dsh

ort-

circ

uitb

reak

ing

curr

ent

DC

com

pone

ntin

%of

the

rate

dsh

ort-

circ

uitb

reak

ing

curr

ent

Asy

mm

etric

albr

eaki

ngcu

rren

t

Rate

dsh

ort-

circ

uitm

akin

gcu

rren

t(a

t50/

60H

z)

Rate

dlig

htni

ngim

puls

ew

ithst

and

volta

ge

Rate

dsh

ort-

dura

tion

pow

er-f

requ

ency

with

stan

dvo

ltage

Vol

tage

drop

ΔUbe

twee

nco

nnec

tions

(acc

ordi

ngto

IEC

6069

4at

DC

100

A)

Min

imum

cree

page

dist

ance

,in

terr

upte

r

Min

imum

cree

page

dist

ance

,ph

ase-

to-e

arth

Min

imum

clea

ranc

e,ph

ase-

to-p

hase

Min

imum

clea

ranc

e,ph

ase-

to-e

arth

Wei

ght1

)

(fix

ed-m

ount

edci

rcui

t-br

eake

r/slid

e-in

mod

ule)

Det

aile

ddi

men

sion

draw

ing

(has

tobe

orde

red)

Ope

ratin

gcy

cle

diag

ram

No.

(see

page

57)

Cata

log

dim

ensi

ondr

awin

gs(s

eepa

ge58

)(f

ixed

-mou

nted

circ

uit-

brea

ker/s

lide-

inm

odul

e)

Page 57: SION Vacuum Circuit-Breakers - w3.siemens.com.cn · integration in all customary medium-voltage ... transformers, capacitors, generators, filter circuits ... The operating mechanism

57Siemens HG 11.02 · 2006

3

24 kV50/60 Hz

Ir tk Isc Ima Up Ud

A mm mm s kA % kA kA kV kV mV mm mm mm mm kg

3AE1 353-1 ... 800 310 275 � 3 20 36 22.4 50/52

125 50 2.6 200 350 265 210 130/180

3M 44202052 001

3 C/E

3AE1 353-2 ... 1250 310 275 � 3 20 36 22.4 50/52

125 50 2.6 200 350 265 210 130/180

3M 44202052 001

3 C/E

3AE1 353-4 ... 2000 310 275 � 3 20 36 22.4 50/52

125 50 2.0 200 340 265 205 150/200

3M 44202053 001

3 D/E

3AE1 353-6 ... 2500 310 275 � 3 20 36 22.4 50/52

125 50 2.0 200 340 265 205 150/200

3M 44202053 001

3 D/E

3AE1 354-1 ... 800 310 275 � 3 25 36 28 63/65

125 50 2.6 200 350 265 210 130/180

3M 44202052 001

4 C/E

3AE1 354-2 ... 1250 310 275 � 3 25 36 28 63/65

125 50 2.6 200 350 265 210 130/180

3M 44202052 001

4 C/E

3AE1 354-4 ... 2000 310 275 � 3 25 36 28 63/65

125 50 2.0 200 340 265 205 150/200

3M 44202053 001

4 D/E

3AE1 354-6 ... 2500 310 275 � 3 25 36 28 63/65

125 50 2.0 200 340 265 205 150/200

3M 44202053 001

4 D/E

3AE1 724-2 ... 1250 320 210 � 3 25 36 28 63/65

125 50 2.6 200 350 200 210 120/ – – 4 –/–

3AE1 754-6 ... 2500 320 275 � 3 25 36 28 63/65

125 50 2.0 200 340 200 205 150/ – – 4 –/–

� Standard acc. to IEC 62 271-100 Possible – Not available as slide-in module 1) The weight of the fixed-mounted circuit-breaker with draw-out element increases by the values specified in dimensiondrawing F

Technical DataElectrical data, dimensions and weights

Operating cycle diagram

�����

������

����

����

����

���

���

���

��

����� � � � �� ��*��� ��

��

����

����

� ��

&������'�(���)���

��

��

The permissible number of

electrical operating cycles

is shown as a function of

the breaking current

(r.m.s. value). All SION

vacuum circuit-breakers

fulfil the endurance classes

E2, M2 and C2 according

to IEC 62 271-100. The

curve shape beyond the

parameters defined in

IEC 62 271-100 is based on

average experience data.

The number of operating

cycles that can actually be

reached can be different

depending on the respec-

tive application.

Operating cycle diagram

�����

������

����

����

����

���

���

���

��

��

��

��� � � � �� �� ��*�����

���

����

����

� �

��

&������'�(���)���

��

SION Vacuum Circuit-Breakers

Ord

erN

o.

Rat

edn

orm

alcu

rren

t

Wid

thac

ross

flat

s

Pole

-cen

ter

dis

tan

ce

Rate

dop

erat

ing

sequ

ence

:

O-3

min

-CO

-3m

in-C

O

O-0

.3s

-CO

-3m

in-C

O

O-0

.3s

-CO

-15

s-C

O

Rate

dsh

ort-

circ

uitd

urat

ion

Rate

dsh

ort-

circ

uitb

reak

ing

curr

ent

DC

com

pone

ntin

%of

the

rate

dsh

ort-

circ

uitb

reak

ing

curr

ent

Asy

mm

etric

albr

eaki

ngcu

rren

t

Rate

dsh

ort-

circ

uitm

akin

gcu

rren

t(a

t50/

60H

z)

Rate

dlig

htni

ngim

puls

ew

ithst

and

volta

ge

Rate

dsh

ort-

dura

tion

pow

er-f

requ

ency

with

stan

dvo

ltage

Vol

tage

drop

ΔUbe

twee

nco

nnec

tions

(acc

ordi

ngto

IEC

6069

4at

DC

100

A)

Min

imum

cree

page

dist

ance

,in

terr

upte

r

Min

imum

cree

page

dist

ance

,ph

ase-

to-e

arth

Min

imum

clea

ranc

e,ph

ase-

to-p

hase

Min

imum

clea

ranc

e,ph

ase-

to-e

arth

Wei

ght1

)

(fix

ed-m

ount

edci

rcui

t-br

eake

r/slid

e-in

mod

ule)

Det

aile

ddi

men

sion

draw

ing

(has

tobe

orde

red)

Ope

ratin

gcy

cle

diag

ram

No.

(see

belo

w)

Cata

log

dim

ensi

ondr

awin

gs(s

eepa

ge58

)(f

ixed

-mou

nted

circ

uit-

brea

ker/s

lide-

inm

odul

e)

Page 58: SION Vacuum Circuit-Breakers - w3.siemens.com.cn · integration in all customary medium-voltage ... transformers, capacitors, generators, filter circuits ... The operating mechanism

58 Siemens HG 11.02 · 2006

3

��������

���

���

"�#��

��� ������ ���

���

���

���

���

�����������

Dimension drawing A

������

��

���,�

���

��,�

��� ������ ���

����,�

���

���

����

��,�

���

��,�

������

������������

Dimension drawing B

��������

���

���

"�#��

��� ������ ���

���

���

���

���

�����������

Dimension drawing C

������

��

���,�

���

��,�

��� ������ ���

����,�

���

���

����

��,�

���

��,�

������

������������

Dimension drawing E

��������

���

���

"�#��

��� ������ ���

���

���

���

���

�����������

Dimension drawing D

Technical DataDimensions drawings for voltage level 24 kV

SION Vacuum Circuit-Breakers

���

"

�����������

���

PCD a c d Weight

210 679 650 620 ca. 20 kg

275 879 850 820 ca. 25 kg

Dimension drawing F

Height of drawout element: 60

PCD Pole-center distance

a Width of drawout element

c Total width across wheels

d Distance between wheels

Page 59: SION Vacuum Circuit-Breakers - w3.siemens.com.cn · integration in all customary medium-voltage ... transformers, capacitors, generators, filter circuits ... The operating mechanism

59Siemens HG 11.02 · 2006

3

Operating times at rated voltage of the secondary circuit

Vacuum circuit-breaker equipment Operating time

Closing time – < 75 ms

Opening time 1st shunt release < 65 ms

2nd release < 50 ms

Arcing time – < 15 ms

Opening time 1st shunt release < 80 ms

2nd release < 65 ms

Dead time – 300 ms

CLOSE/OPEN contact time 1st shunt release < 75 ms

2nd release < 60 ms

Minimum command duration Closing solenoid 45 ms

1st shunt release 40 ms

2nd release 20 ms

Pulse time for circuit-breaker tripping signal 1st shunt release > 15 ms

2nd release > 10 ms

Charging time for electrical operation < 10 s

Synchronism error between the poles 2 ms

Short-circuit protection of motors (fuse protection of drive motors)

Ratedvoltage ofthe motor

Operating voltage Power consumptionof the motor

Smallest possible ratedcurrent1) of the m.c.b.(miniature circuit-breaker)with C-characteristic

V max. V min. V W (at DC) VA (at AC) A

DC 24 26 20 350 – 8

DC 48 53 41 350 – 6

DC 60 66 51 350 – 4

DC 110 121 93 350 – 2

DC 220 242 187 350 – 1.6

AC 110 121 93 – 400 2

AC 230 244 187 – 400 1.6

1) The current inrush in the drive motor can be neglected due to its very short presence

Consumption data of releases

Release Power consumption Tripping ranges

Operation at Tripping voltage Tripping voltage ortripping current

DCapprox. W

AC 50/60 Hzapprox. VA

at DC at AC 50/60 Hz

Closing solenoid 3AY15 10 140 140 85 to 110 % U 85 to 110 % U1st shunt release(without energy store) 3AY15 10

140 140 70 to 110 % U 85 to 110 % U

2nd shunt release(with energy store) 3AY11 01

70 50 70 to 110 % U 85 to 110 % U

Undervoltage release 3AY11 03 20 20 35 to 0 % U 35 to 0 % UCurrent-transformer operated release 3AX11 02(rated current 0.5 A or 1 A)

– 10 2) – 90 to 110 % Ia

Current-transformer operated release 3AX11 04(tripping pulse W 0.1 Ws)

– – – –

2) Consumption at pickup current (90 % of the rated current) and open armature

Technical DataOperating times, short-circuit protection of motors, consumption data of releases

SION Vacuum Circuit-Breakers

Page 60: SION Vacuum Circuit-Breakers - w3.siemens.com.cn · integration in all customary medium-voltage ... transformers, capacitors, generators, filter circuits ... The operating mechanism

60 Siemens HG 11.02 · 2006

3

���/�

��

�0���

��

���/�

��

�/���

��

���$���

��

���$�

1�

1�

��

��

��

��

�$���

���$�

�0���

��

���$����

�2�

��

3�

2� 4

���$����

��

��

�����������

��

��

��

���$�

��

��

��

��

��

��

��

��

��

��

��

��

��

��

��

��

��

��

��

��

�����������

Basic equipment

Motor Closing and anti- Signal 1st shunt Auxiliary switch 6 NO + 6 NCoperating pumping for motor “closing spring releasemecha- operating stored-energy charged“nism mechanism

���/�

��

�0���

��

���/�

��

�/���

��

���$���

��

���$�

1�

1�

��

��

��

�$����

���$�

��

1�

1�

�����������

��

��

���$�

��

�$�

1�

1�

1�

1�

�����������

��

��

��

���$�

��

��

��

��

��

��

��

��

��

��

��

��

��

��

��

��

��

��

��

��

��

��

��

��

��

��

��

��

��

��

��

��

���

���

���

���

���

���

���

���

���

���

���

���

�1�

�1� ��������

���

Additional equipment

Closing and anti-pumping Circuit-breaker Auxiliary switch 12 NO + 12 NCfor motor operating tripping signalstored-energy mechanism

1�

1�1�

1�

���$�

��

�0���

��

�����������

�0���

��

1�

1�1�

1�

�����������

�0���

��

1�

1�1�

1�

�����������

�0�3�

3�

1�

1�1�

1�

���$�

��

��� �

�����������

Additional equipment: Releases (for possible combinations see chapter 2 under “Secondary equipment“)

2nd shunt Current-transformer Low-energy current- Undervoltage releaserelease operated release transformer operated

0.5 A or 1 A release 0.1 Ws

LegendK1 Contactor (anti-pumping)

M1 Motor operating mechanism

R1 Resistance

S1 Auxiliary switch

S12 Mechanical interlocking

S21 Position switches

S22 (to de-energize the motor oper-

ating mechanism after charging)

S3 Position switch

(anti-pumping)

S4 Position switch

(for closing spring charged)

S5 Electrical closing lock-out

S6 Circuit-breaker tripping signal

S7 Cutout switch for

circuit-breaker tripping signal

X0 Plug connector

24-pole or 64-pole

X1 Terminal strip 25-pole

Y1 1st shunt release

Y2 2nd shunt release

Y4 Current-transformer

operated release

(rated current 0.5 A or 1 A)

Y 6 Current-transformer operated

release (tripping pulse W W 0.1 Ws)

Y7 Undervoltage release

Y9 Closing solenoid

Abbreviations:

NO Normally open

NC Normally closed

Technical DataCircuit diagrams

SION Vacuum Circuit-Breakers

Page 61: SION Vacuum Circuit-Breakers - w3.siemens.com.cn · integration in all customary medium-voltage ... transformers, capacitors, generators, filter circuits ... The operating mechanism

61Siemens HG 11.02 · 2006

4

Brandenburger Tor, Berlin, Germany

Contents Page

Annex

Inquiry form

Configuration instructions

Configuration aid

61

62

63

AnnexContents

R-HG

11-1

81.ti

fR-

HG11

-180

.eps

Foldout page

SION Vacuum Circuit-Breakers

Switchgear Factory in Berlin, Germany

Page 62: SION Vacuum Circuit-Breakers - w3.siemens.com.cn · integration in all customary medium-voltage ... transformers, capacitors, generators, filter circuits ... The operating mechanism

62 Siemens HG 11.02 · 2006

4

AnnexInquiry form

Inquiry concerning

� SION standardcircuit-breaker

� SION slide-in module

Please

� Submit an offer� Call us� Visit us

Your address

Company

Dept.

Name

Street

Postal code/city

Phone

Fax

E-mail

Siemens AG

Dept.

Name

Street

Postal code/city

Fax

Technical dataOther values

Rated voltage � 7.2 kV

� 24 kV

� 12 kV � 17.5 kV

� _ _ _ kV

Rated lightning impulse

withstand voltage

� 60 kV

� 125 kV

� 75 kV � 95 kV

� _ _ _ kV

Rated short-duration

power-frequency withstand voltage

� 20 kV

� 42 kV

� 28 kV

� 50 kV

� 38 kV

� 55 kV � _ _ _ kV

Rated short-circuit

breaking current

� 12.5 kA

� 25 kA

� 16 kA

� 31.5 kA

� 20 kA

� 40 kA � _ _ _ kA

Rated normal current � 800 A

� 2500 A

� 1250 A

� 3150 A

� 2000 A

� _ _ _ kA

Pole-center distance � 150 mm � 160 mm � 210 mm � 275 mm

Width across flats � 205 mm � 275 mm � 310 mm

Secondary equipment

For possible combinations see pages 23 to 26 or 32 to 35

Circuit-breaker equipment

(only for standard circuit-breaker)

� Fixed mounting � With drawout element

� Drawout element, contact arms

� Drawout element, contact arms, bushings

Motor operating mechanism � _ _ _ V DC � _ _ _ V AC, _ _ _ Hz

Closing solenoid � _ _ _ V DC � _ _ _ V AC, _ _ _ Hz

1st shunt release � _ _ _ V DC � _ _ _ V AC, _ _ _ Hz

2nd shunt release � _ _ _ V DC � _ _ _ V AC, _ _ _ Hz

Current-transformer operated release �

Undervoltage release � _ _ _ V DC � AC _ _ _ V, _ _ _ Hz

Auxiliary switch � 6 NO + 6 NC � 12 NO + 12 NC

Low-voltage connection � 27-pole

terminal strip

� 24-pole

plug

� 64-pole

plug

� Mechanical interlocking

� Circuit-breaker tripping signal

� Electrical closing lock-out

� Operating instructions � English � German � French � Spanish

Application and other requirements

� Please check off _ _ _ Please fill in

Please copy and return to your Siemens partneror you can use our prompted online configuratorunder www.siemens.com/SION

SION Vacuum Circuit-Breakers

Page 63: SION Vacuum Circuit-Breakers - w3.siemens.com.cn · integration in all customary medium-voltage ... transformers, capacitors, generators, filter circuits ... The operating mechanism

You prefer to configure your SION vacuum circuit-breaker on your own?Please follow the steps for configuration and enter the order number in the configuration aid.Alternatively you can also use our prompted online configurator under www.siemens.com/SION.

Instruction for configuration of the SION vacuum circuit-breaker

1st step: Definition of the primary part (see pages 15 to 22 and pages 28 to 31)

Please specify the following ratings: Possible options:

Rated voltage (Ur) Ur: 7.2 kV to 24 kV

Rated lightning impulse withstand voltage (Up) Up: 60 kV to 125 kV

Rated short-duration power-frequency withstand voltage (Ud) Ud: 20 kV to 55 kV

Rated short-circuit breaking current (Isc) Isc: 12.5 kA to 40 kA

Rated normal current (Ir) Ir: 800 A to 3150 A

Pole-centre distance 150 mm to 275 mm

Width across flats 205 mm to 310 mm

These ratings define the positions 5 to 8 of the order number

2nd step: Definition of the secondary equipment (see pages 23 to 26 and pages 32 to 35)

Please specify the following equipment features: Possible options:

Release combination(position 9)

Shunt release, current-transformer operated releaseand undervoltage release

Closing solenoid(position 10)

Operating voltages from 24 V DC to 240 V AC

Operating voltage of the releases(positions 11 / 12)

Operating voltages from 24 V DC to 240 V AC

Installation accessories(position 13)

Fixed mounting; with drawout element, contactarms, contact system; slide-in module

Motor operating mechanism(position 14)

Operating voltages from 24 V DC to 240 V AC

Number of auxiliary contacts(position 15)

6 NO + 6 NC, 12 NO + 12 NC

Design of the control cable connection(position 15)

27-pole terminal strip, 24-pole plug connector64-pole plug connector

Mechanical interlocking, circuit-breaker tripping signal(position 15)

With or without

Language of the documentation(position 16)

English, German, French, Spanish

Frequency of the operating voltage of thesecondary equipment at AC (position 16)

50 Hz/60 Hz

These equipment features define the positions 9 to 16 of the order number

3rd step: Do you have any further requirements concerning the equipment? (Please refer to pages 27 and 36)

Should you still need more options than the possible special equipment like halogen-free andflame-retardant or silicone-free version, condensate protection or an additional rating plate, etc.,please contact your responsible sales partner.

1 2 3 4 5 6 7 – 8 9 10 11 12 – 13 14 15 16

3 A E 1 � � � – � � � � � – � � � � – Z

3 A E 1 – –

+ + + +

+ + + +

3 A E 1 – –

+ + + +

+ + + +

3 A E 1 – –

+ + + +

+ + + +

3 A E 1 – –

+ + + +

+ + + +

3 A E 1 – –

+ + + +

+ + + +

3 A E 1 – –

+ + + +

+ + + +

3 A E 1 – –

+ + + +

+ + + +

3 A E 1 – –

+ + + +

+ + + +

3 A E 1 – –

+ + + +

+ + + +

See

page

23or

32

See

page

23or

32

See

page

24or

33

See

page

24or

33

See

page

25or

34

See

page

25or

34Se

epa

ge26

or35

See

page

26or

35

See

page

27or

36

See

page

15or

28

to page

22or

31

For configuration of yourSION vacuum circuit-breaker

63Siemens HG 11.02 · 2006

Page 64: SION Vacuum Circuit-Breakers - w3.siemens.com.cn · integration in all customary medium-voltage ... transformers, capacitors, generators, filter circuits ... The operating mechanism

For questions concerningPower Transmission and Distribution:You can contact our Customer SupportCenter 24 hours a day, 365 days a year.Tel.: +49 180/524 70 00Fax: +49 180/524 24 71(Calls charged: e.g. 12 Ct/min)E-mail: [email protected]/energy-support

Siemens AGPower Transmission and DistributionMedium Voltage DivisionNonnendammallee 10413623 BerlinGermany

www.siemens.com/SION

Subject to change without noticeOrder No. E50001-K1511-A021-A1-7600Printed in GermanyDispo 31601KG 12.06 7.0 60 En101983 6101/C6103

The information in this document contains general descriptions of the technical options available, which do not always have to be present in individual cases.The required features should therefore be specified in each individual case at the time of closing the contract.

If not stated otherwise on the individual pages of thiscatalog, we reserve the right to include modifications,especially regarding the stated values, dimensions and weights.Drawings are not binding. All product designations usedare trademarks or product names of Siemens AG or othersuppliers. If not stated otherwise, all dimensions in thiscatalog are given in mm.

Responsible for

Technical contents: General editing:Siemens AG, Dept. PTD M C PPM Siemens AG, Dept. PTD CC MBerlin Erlangen

R-HG

11-1

82.ti

f