Simple, accurate tenant sub-metering PowerLogic EM4800 multi-circuit energy meter.

18
Simple, accurate tenant sub- metering PowerLogic EM4800 multi-circuit energy meter

Transcript of Simple, accurate tenant sub-metering PowerLogic EM4800 multi-circuit energy meter.

Page 1: Simple, accurate tenant sub-metering PowerLogic EM4800 multi-circuit energy meter.

Simple, accurate tenant sub-metering

PowerLogic EM4800multi-circuit energy meter

Page 2: Simple, accurate tenant sub-metering PowerLogic EM4800 multi-circuit energy meter.

Schneider Electric 2- Power Monitoring – Feb 2011

The PowerLogic EM4800 series meters provide simple, reliable, revenue-grade electricity metering.

● High density multi-circuit meter: connections for 24 CTs

● Billing-grade accuracy: ANSI C12.20 Class 0.5 & IEC 62053-22 Class 0.5S

● Wide-range voltage-sensing inputs: 100 to 300 V ac● Direct connect to: 120/240 V, 120/208 V, 230/240 V, 220/380 V, 240/415 V, 277/480

V

● Low cost per meter point

● Flexible installation options: ideal for both new construction and retrofit projects

● Multiple communication options: Ethernet, modem, onboard web server

● Onboard memory with industry standard protocols – Modbus TCP, FTP – providing easy integration into monitoring software

● Rugged enclosure and maintenance-free design

PowerLogic EM4800

Optional Remote Display

Page 3: Simple, accurate tenant sub-metering PowerLogic EM4800 multi-circuit energy meter.

Schneider Electric 3- Power Monitoring – Feb 2011

Applications

Ideal for multi-tenant and departmental metering applications in commercial buildings:

●Office towers

●Condominiums

●Apartment buildings

●Shopping centers

●University dormitories and apartments

●Other multi-user environments

Page 4: Simple, accurate tenant sub-metering PowerLogic EM4800 multi-circuit energy meter.

Schneider Electric 4- Power Monitoring – Feb 2011

Benefits

●Establish “green” image and qualify for LEED ratings

●Bill tenants accurately for energy use●Encourage tenants to manage energy consumption ●Manage energy use to reduce operational costs and

offer more competitive lease rates

●Allocate costs to departments or processes to expose wasteful energy practices

●Identify the source of peak demand charges●Identify saving opportunities within your facilities●Verify utility charges using accurate meters

Page 5: Simple, accurate tenant sub-metering PowerLogic EM4800 multi-circuit energy meter.

Schneider Electric 5- Power Monitoring – Feb 2011

Measurement parameters

● Real energy, delivered and received (kWh)*

● Reactive energy, delivered and received (KVARh)*

● Apparent energy (kVAh)*

● Real power (kW)

● Reactive power (kVAR)

● Apparent power (kVA)

● Voltage* and current (per phase)

● Power factor

● Pulse counts*

* Measurements available for data logging

The PowerLogic EM4800 meter provides the information that building owners need to bill tenants, manage energy use and reduce their overall costs.

Page 6: Simple, accurate tenant sub-metering PowerLogic EM4800 multi-circuit energy meter.

Schneider Electric 6- Power Monitoring – Feb 2011

High accuracy, multi-tenant metering

● Use the EM4800 to meter every tenant, as well as shared-use loads, within a commercial building.

● A single EM4800 can meter 24 single phase circuits or 8 three-phase circuits.

The PowerLogic EM4800 provides highly accurate energy information so that building owners can bill tenants for their actual energy use.

Common Area

Tenant #1

Tenant #2

Tenant #3

Tenant #4

EM4800

HVAC

To Tenant Billing Software

PowerLogic EM4800:a highly-accurate multi-tenant energy meter, at an affordable price.

Page 7: Simple, accurate tenant sub-metering PowerLogic EM4800 multi-circuit energy meter.

Schneider Electric 7- Power Monitoring – Feb 2011

Installation options

Embedded applicationWall Mount application

PowerLogic EM4800 meters are ideal for both retrofit and new installations.

PowerLogic EM4800

● Flexible installation options allow the product to be effectively used in virtually any commercial building that requires highly accurate and cost effective energy metering

● The rugged enclosure allows the meter to be either wall mounted, or embedded within a power distribution panel

Page 8: Simple, accurate tenant sub-metering PowerLogic EM4800 multi-circuit energy meter.

Schneider Electric 8- Power Monitoring – Feb 2011

Physical characteristics

Rugged enclosure for either wall mount or installation within a power distribution panel. Suitable for both indoor and enclosed outdoor applications.

LCD backlit display, with optional remote display

Standard Ethernet port and onboard modem enable fast and easy integration into existing networks

Two digital pulse inputs to accumulate information from WAGES meters

Voltage sense inputs allow a wide input range: 100 Vac to 300 Vac L-N

Connection points for 24 current transformers (CTs). Configure each EM4800 to match your needs: • 24 single CT meter points• 12 two CT meter points• 8 three CT meter points

Onboard memory collects up to two years of energy use data, while the clock ensures accurate time-stamping

Web server allows connection through your browser

Page 9: Simple, accurate tenant sub-metering PowerLogic EM4800 multi-circuit energy meter.

Schneider Electric 9- Power Monitoring – Feb 2011

Flexible configuration

PowerLogic EM4800 multi-circuit meters can be configured to match the power distribution panel that you are monitoring: configuration is user-selected andcan change as often as required.

Option 1: Configure as 24 single-phase, one-CT meters

Option 2: Configure as 12 single-phase, two-CT meters

Option 3: Configure as 8 three-phase, three-CT meters

Phase Meter Point

A 1

B 2

C 3

A 4

B 5

A 22

B 23

C 24

Phase Meter Point

A1

B

C2

A

B12

C

Phase Meter Point

A

1B

C

A

2B

C

A

8B

C

Each meter point can be assigned to a tenant or department

Page 10: Simple, accurate tenant sub-metering PowerLogic EM4800 multi-circuit energy meter.

Schneider Electric 10- Power Monitoring – Feb 2011

Low cost per meter point

A single PowerLogic EM4800 multi-circuit meter can replace up to 8 three-phase power meters, resulting in significant cost savings.

ABC

ABC

ABC

ABC

ABC

ABC

ABC

ABC

ABC

ABC

ABC

ABC

ABC

ABC

ABC

ABC

ABC

ABC

ABC

ABC

ABC

ABC

ABC

ABC

ABC

ABC

ABC

ABC

Power distribution panel #1 Power distribution panel #2

Select the loads to meter - even if they are in different power distribution panels. Note: the panels must share a common voltage reference

Example meter point: CTs installed adjacent to a 3-phase circuit breaker; 8 meter points shown in diagram.

Conduit for CT leads and voltage connections

EM4800

Page 11: Simple, accurate tenant sub-metering PowerLogic EM4800 multi-circuit energy meter.

Schneider Electric 11- Power Monitoring – Feb 2011

PowerLogic EM4800 series meter overviewThe meters are available in three models. Measured values, communication options, features and software support are consistent for all three models.

Select the model that you need for your specific project:

EM4833 - Uses 1/3 V output CTs

The best solution for retrofit projects● Solid core and split core CTs

available● Extra long leads supported – up to

100 m (325 feet)● Shorting blocks not required● Enclosure size:

33.5 cm x 30.5 cm x 5.5 cm

13.125 in x 12 in x 2.125 in

EM4880 - Uses 80 mA output CTs

Used for new installations● Solid core, 200 A primary CT

available ● Extra long leads supported – up

to 100 m (325 feet)● Shorting blocks recommended● Enclosure size:

33.5 cm x 30.5 cm x 5.5 cm

13.125 in x 12 in x 2.125 in

EM4805 - Uses 5 A output CTs

Used for retrofits and new installations● Industry standard CTs - available in a

wide range of sizes● Solid core and split core CTs available● Shorting blocks required● Enclosure size:

33.5 cm x 44 cm x 5.5 cm

13.125 in x 17 in x 2.125 in

EM4833 or EM4880

Lead lengths up to 100 m (325 feet) for 1/3 V and 80 mA CTs!

EM4800

Page 12: Simple, accurate tenant sub-metering PowerLogic EM4800 multi-circuit energy meter.

Schneider Electric 12- Power Monitoring – Feb 2011

Electrical Room #1

Electrical Room #2

Three-phase meter point with 80 mA or 1/3 V CTs. A total of 8 three phase meter points are shown.

Conduit used to connect CT leads to EM4800 meter. All CT leads are up to 100 m (325 feet) in total length

Previously, building owners with dispersed loads would need to install energy meters throughout their facility – but the EM4800 provides a simpler solution:

80 mA and 1/3 V CTs support extra long lead lengths of up to 100 m (325 feet) – you can monitor loads throughout your facility with a single EM4800 meter!

EM4880 or EM4833 meter, installed outside of Electrical Room, allowing easy access

The EM4800 can even monitor panels on different floors within the building Note: the panels must share a common voltage reference

Installation example: EM4880 or EM4833

Commercial building floor plan

Page 13: Simple, accurate tenant sub-metering PowerLogic EM4800 multi-circuit energy meter.

Schneider Electric 13- Power Monitoring – Feb 2011

Flexible communications

The EM4800 comes standard with both an Ethernet port and a modem so that you can quickly connect to the meter over your existing communication network

Industry standard protocols ensure that you can easily integrate the energy data from the EM4800 into your tenant billing or energy management software

EM4800

Ethernet port

-Modbus TCP

-FTP

-HTTP (Webserver)

-SNTP (time sych)

Modem

-FTP

-SNTP (time sych)The EM4800 is fully supported in Schneider Electric software: ION Enterprise* and Remote Energy Monitoring (REM)

*Available: September, 2011

Page 14: Simple, accurate tenant sub-metering PowerLogic EM4800 multi-circuit energy meter.

Schneider Electric 14- Power Monitoring – Feb 2011

Pulse inputs for WAGES metering

Two digital pulse inputs accumulate readings from WAGES meters to give you a complete view of your overall energy use.

Water meter pulse

Gas meter pulse

Easily accumulate data from WAGES meters using the 2 digital pulse inputs. Pulse data is logged in onboard memory.

Water

Air

Gas

Electricity

Steam

EM4800

Page 15: Simple, accurate tenant sub-metering PowerLogic EM4800 multi-circuit energy meter.

Schneider Electric 15- Power Monitoring – Feb 2011

Onboard data logging

● User selected data logging interval time (from 5 to 60 minutes)

● Data is stored onboard in non-volatile memory, unaffected by power outage

● Capacity up to 2.4 years at 1 hour intervals or over 200 days at 15 minute intervals

Log file push

Two options to retrieve your logged data…..

Option 1: FTP File Push Option 2: Modbus log file reads

FTP ServerEthernet or

Modem

Modbus Master

Modbus TCP/IP

Data file read

EM4800 EM4800

Page 16: Simple, accurate tenant sub-metering PowerLogic EM4800 multi-circuit energy meter.

Schneider Electric 16- Power Monitoring – Feb 2011

Full support from ION Enterprise softwareAvailable: September, 2011

ION Enterprise server(Modbus Master)

Web Browser

EM4800Real time values

Diagnostic Information

Access the onboard web server to view both real-time values and valuable diagnostic information.

ION Enterprise

EM4800Real time values

Interval/logged values

Use PowerLogic ION Enterprise software to access both real-time values and onboard data logs.

PowerLogic EM4800 plus ION Enterprise:a powerful solution for energy management applications.

EM4800

You can quickly and easily integrate multiple PowerLogic EM4800 meters into your PowerLogic ION Enterprise power monitoring system. EM4800

EM4800

Modbus TCP

LAN (Ethernet TCP/IP)

Page 17: Simple, accurate tenant sub-metering PowerLogic EM4800 multi-circuit energy meter.

Schneider Electric 17- Power Monitoring – Feb 2011

InternetInternetFTP log file push

REMDatabase

Web Browser

REM

The PowerLogic EM4800 combined with the hosted Remote Energy Monitoring (REM) solution provides simple and cost effective access to your energy use information – from anywhere at anytime

FTPHosted Solution

Customer Building 1 Customer Building 2

FTP

Building 1 Building 2

Full support from Remote Energy Monitoring

… Additional Buildings

Page 18: Simple, accurate tenant sub-metering PowerLogic EM4800 multi-circuit energy meter.

Schneider Electric 18- Power Monitoring – Feb 2011

Contact Schneider Electric for more detailed information on this product, or other products, services and solutions.