Simovert Maintanance Manual

download Simovert Maintanance Manual

of 152

Transcript of Simovert Maintanance Manual

  • 8/18/2019 Simovert Maintanance Manual

    1/152

    SIMOVERT MVMedium-Voltage Drive Converters

    Maintenance Instructions Edition 07.2001

    with HV-IGBT technology

    Order No. 6SE8001-0CJ76

  • 8/18/2019 Simovert Maintanance Manual

    2/152

    Order No.: 6SE8001-0CJ76Ordering: A&D LD S1Printed in the Federal Republic of Germany

    The reproduction, transmission or use of this document or its contents isnot permitted without express written authority.Offenders will be liable for damages. All rights, including rights created bypatent grant or registration or a utility model or design, are reserved.

    Exclusion of liabilityWe have checked the contents of this Document to ensure that theycoincide with the described hardware and software. However, deviationscannot be completely ruled-out, so we cannot guarantee completeconformance. However, the information in this document is regularlychecked and the necessary corrections included in subsequent editions.We are thankful for any recommendations or suggestions.

    ! Siem ens AG 2001 All rights reserved W e reserve t he right to m ake technical changes

  • 8/18/2019 Simovert Maintanance Manual

    3/152

  • 8/18/2019 Simovert Maintanance Manual

    4/152

    Contents Edition 07.2001

    Siemens AG 6SE8001-0CJ76

    4   SIMOVERT MV Maintenance Instructions

    3.5.2 Filling the system ................................................................................36

    4 Replacing modules ...........................................................................37

    5 Fault and alarm messages ...............................................................39

    Note

    Hotline (Technical Support)Telefon 0180 5050222Fax 0180 5050223

    Note

    The information in this Manual does not purport to cover all details or variations inequipment, nor to provide for every possible contingency to be met in connectionwith installation, operation or maintenance.

    Should further information be desired or should particular problems arise which arenot covered sufficiently for the purchaser's purposes, please contact your localSiemens office.

    Further, the contents of this Manual shall neither become a part of nor modify anyprior or existing agreement, commitment or relationship. The sales contract

    contains the entire obligation of Siemens. The warranty contained in the contractbetween the parties is the sole warranty of Siemens. Any statements containedherein do not create new warranties nor modify the existing warranty

  • 8/18/2019 Simovert Maintanance Manual

    5/152

    Edition 07.2001 Definitions, warning information  

    Siemens AG 6SE8001-0CJ76

    SIMOVERT MV Maintenance Instructions   5

    Definitions, warning information

    Qualified personnel

    For the purpose of this Instruction Manual and product labels, a "Qualified person"is someone who is familiar with the installation, mounting, start-up and operation ofthe equipment and the hazards involved.He or she must have the following qualifications:

    •   Trained and authorised to energise, de-energise, clear, ground and tag circuitsand equipment in accordance with established safety procedures.

    •   Trained in the proper care and use of protective equipment in accordance withestablished safety procedures.

    •   Trained in rendering first aid.

    Safety related information and instructions

    This Manual contains information and instructions which you must observe for yourown personal safety and also to prevent material damage. The information andinstructions for your personal safety are identified by a warning triangle.Information and instructions on general material damage do not have a warningtriangle. Depending on the degree of danger, they are indicated as follows:

    DANGER

    means that death, grievous injury or extensive damage to property will occur if theappropriate precautions are not taken.

    WARNING

    means that death, grievous injury or extensive damage to property may  occur if theappropriate precautions are not taken.

    CAUTION

    with warning triangle, means that minor personal injury may occur if theappropriate precautions are not taken.

    CAUTION

    without warning triangle, means that damage to property may occur if theappropriate precautions are not taken.

    NOTICE

    means that an undesirable situation or condition can occur if the appropriateinformation/instruction is not observed.

    NOTE

    highlights an important item of information about the product or a section of theinstructions which requires careful attention.

  • 8/18/2019 Simovert Maintanance Manual

    6/152

    Definitions, warning information Edition 07.2001

    Siemens AG 6SE8001-0CJ76

    6   SIMOVERT MV Maintenance Instructions

    Correct operation and use

    Please observe the following:

    WARNING

    Electrical equipment contains components which are at dangerous voltage levels.

    If these instructions are not strictly adhered to, this can result in severe bodily injuryand material damage.

    Only appropriately qualified personnel may work on this equipment or in its vicinity.

    This personnel must be completely knowledgeable about all the warnings andservice measures according to this Instruction Manual.

    The successful and safe operation of this equipment is dependent on properhandling, installation, operation and maintenance.

    Domestic safety guidelines and regulations must be carefully observed.

  • 8/18/2019 Simovert Maintanance Manual

    7/152

    Edition 07.2001 Electrostatically sensitive devices (ESD)

    Siemens AG 6SE8001-0CJ76

    SIMOVERT MV Maintenance Instructions   7

    Electrostatically sensitive devices (ESD)

    Caution

    Electronic modules contain electrostatically sensitive devices that can easily bedestroyed if they are incorrectly handled. However, if your work does involve thehandling of such devices, please observe the following information:

    •   Electronics modules should not be touched unless work has to be carried-outon them.

    •   If it is essential for you to touch an electronic module, make sure that yourbody is electrostatically discharged beforehand.

    •   Modules may not be allowed to come into contact with electrically insulatingmaterials such as plastic foil, insulating table tops or clothing made of syntheticfibers.

    •   Modules may only be placed on electrically conducting surfaces.

    •   Modules and electronic components should always be packed in electricallyconducting containers (such as metallized plastic boxes or metal canisters)before being stored or shipped.

    •   If packing containers are used which are not conductive, modules and boardsmust first be wrapped in a conducting material. Examples of such materialsinclude electrically conducting foam rubber or household aluminum foil.

    For easy reference, the protective measures necessary when handling electrostaticsensitive devices are illustrated in the sketches below:

    −   a = Conductive flooring   −   d = Anti-static overall

    −   b = Anti-static table   −   e = Anti-static chain

    −   c = Anti-static footwear   −   f = Grounding connections of cabinets

    StehplatzSitzplatz Steh- / Sitzplatz

    a

    b

    e

    d

    c

    d

    ac

    db

    c a

    e

    f   f   f f f

    Note

    The HV-IGBTs (Insulated Gate Bipolar Transistors) which are used are deviceswhich can be destroyed by electrostatic discharge. The devices can be very easilydestroyed if they are incorrectly handled. All of the measures specified above mustbe applied to the HV-IGBTs to avoid the drive converter being damaged, and toensure that it still continues to function perfectly.Further, the gate- and emitter connections of HV-IGBTs must always be short-circuited before the devices are transported.

  • 8/18/2019 Simovert Maintanance Manual

    8/152

    Safety and application instructions and information for drive converters Edition 07.2001

    Siemens AG 6SE8001-0CJ76

    8   SIMOVERT MV Maintenance Instructions

    Safety and application instructions andinformation for drive converters

    Safety and application information for drive converters(according to: The Low-Voltage Directive 73/23/EC)

    SIMOVERT MV drive converters are medium-voltage drive converters. However,they use components which are subject to the Directives for low-voltage devicesand equipment. These include auxiliaries as well as open-loop and closed-loopcontrol components.

    1. General information

    During operation, in accordance with their degree of protection, drive converterscan have parts and components which are live (under voltage), bare and which aremoving or rotating; they can also have hot surfaces.

    There is a potential danger of severe personnel injury or significant material

    damage if the required covers are inadmissibly removed, if the equipment isincorrectly used or it has been incorrectly installed or controlled.

    Please refer to the documentation for additional information.

    Only  suitably qualified, trained personnel may be used to transport, install andcommission as well as service/maintain the equipment (observe IEC 364 andCENELEC HD 384 or DIN VDE 0100 and IEC Report 664 or DIN VDE 0110 andthe domestic accident prevention regulations).

    Qualified, trained personnel in the sense of this basic safety information arepersonnel who are knowledgeable about the installation, mounting, commissioningand operation of the product and are suitably qualified for the activities which theycarry-out.

    2. Correct use

    Drive converters are components which are designed to be installed in electricalplants or machines.

    When they are installed in machines, it is not permissible to commission the driveconverter (i.e. go into correct operation), until it has been clearly identified that themachine is in full compliance with the regulations specified in EC Directive89/392/EC (Machinery Directive); EN 60204 must be observed.

    Commissioning (i.e. go into correct operation) is only permitted if the EMC Directiveis maintained (89/336/EC).

    The drive converters fulfill the requirements of the Low-Voltage Directive 73/23/EC.The harmonized Standards, series EN 50178/DIN VDE 0160 in conjunction withEN 60439-1/DIN VDE 0660 Part 500 and EN 60146/DIN VDE 0558 are applied forthe drive converter.

    The technical data as well as the data on the supply/connection conditions shouldbe taken from the rating plate and the documentation. It is important that this datais carefully maintained.

    3. Transport, storage

    The information/instructions for transport, storage and correct handling of the driveconverter must be carefully observed.

    Climatic conditions must be maintained in compliance with EN 50178.

    4. Mounting

    The drive converters must be installed and cooled corresponding to thespecifications in the associated documentation.

    The drive converters must be protected against inadmissible stressing. Especiallyduring transport and handling, it is not permissible that components are bent and/orinsulating/isolating clearances changed. Electronic components and contactsshould not be touched.

  • 8/18/2019 Simovert Maintanance Manual

    9/152

    Edition 07.2001 Safety and application information for drive converters 

    Siemens AG 6SE8001-0CJ76

    SIMOVERT MV Maintenance Instructions   9

    Drive converters contain components which can be destroyed by electrostaticdischarge if they are incorrectly handled. It is not permissible that electricalcomponents are mechanically damaged or destroyed (under certain circumstancesthis can represent a health hazard!).

    5. Electrical connectionWhen working with drive converters which are powered-up (under voltage), therelevant domestic accident prevention regulations for the particular country mustbe carefully observed (e.g. VBG 4).

    The drive converters must be electrically installed in full compliance with therelevant regulations (e.g. cable cross-sections, fuses and protective devices,protective conductor connection). More detailed information and instructions areprovided in the documentation.

    Information for EMC correct installation - such as shielding, grounding,arrangement and location of filters and routing cables - is provided in the driveconverter documentation. These instructions should always be observed, also fordrive converters with CE label. The manufacturer of the plant or machine is

    responsible in ensuring that the limit values, specified by the EMC legislation, aremaintained.

    6. Operation

    Plants and systems, in which the drive converters are installed, must, if required,be provided with additional monitoring and protective devices in accordance withthe valid safety regulations, e.g. legislation regarding equipment, accidentprevention regulations etc.

    After the drive converter has been disconnected and isolated from the supply, it isnot permissible that conductive equipment components and power connections areimmediately touched due to capacitors which are possibly charged. In this case,the appropriate labels on the drive converter must be carefully observed.

    All of the covers and doors must be kept closed during operation.

    7. Service and maintenance

    The manufacturer documentation must be observed.

    These safety instructions and information must be kept in a safe place!

  • 8/18/2019 Simovert Maintanance Manual

    10/152

    1 Regular (preventive) service/maintenance Edition 07.2001

    Siemens AG 6SE8001-0CJ76

    10   SIMOVERT MV Maintenance Instructions

    1 Regular (preventive) service/maintenance

    Warning

    Voltages of over 1000 Volt (medium voltage!) can be present when this driveconverter is operational. This can result in death or severe bodily injury. This is thereason that extreme care must be taken when working on or with the driveconverter. Please carefully observe the following warning information/instructions:

    Before starting any work on the drive converter, the following five safety rules,according to DIN VDE 0100, must be carefully maintained:

    Five safety rules

    Before starting any work:

    1. Disconnect from the supply

    2. Secure against re-closure

    3. Check that the equipment really isin a no-voltage condition

    4. Ground and short-circuit

    5. Cover or partition-off adjacentparts and components which

    are under voltage (live)

    Regulation label according to DIN 40 008

    Only qualified personnel may work on or with the drive converter or parts of it.All work carried-out on the drive converter and its installation must be carried-out infull compliance with the domestic electrical regulations (in Germany: VBG4) andthe local regulations in accordance with the appropriate specifications. This alsomeans that the drive converter cabinet must be correctly grounded (studs) and itmust ensured that no freely accessible part of the equipment is at line supply

    potential or at any other hazardous voltage potential.

  • 8/18/2019 Simovert Maintanance Manual

    11/152

  • 8/18/2019 Simovert Maintanance Manual

    12/152

    1 Regular (preventive) service/maintenance Edition 07.2001

    Siemens AG 6SE8001-0CJ76

    12   SIMOVERT MV Maintenance Instructions

    5. When carrying-out work on or in the control cabinet it must be observed thatthere is no central breaker for the auxiliary power supply (400 V / 230 V). Evenif all of the motor protection circuit-breakers and m.c.b.s are opened, voltage isstill present at its inputs. The equipment can only be safely shutdown if theupstream auxiliary power supply on the plant side can be powered-down.

    Ball pins

    Fig. 1-1 Spherical studs to ground the power circuit

    Caution

    The electronic modules contain components which can be destroyed byelectrostatic discharge. These components can be easily destroyed if they areincorrectly handled.When carrying-out any work, it is important that the ESDS protective measures aremaintained. If this is not observed, there is a danger that the components could beelectrically destroyed which would have a negative impact on the functioning of thedrive converter.

  • 8/18/2019 Simovert Maintanance Manual

    13/152

    Edition 07.2001 1 Regular (preventive) service/maintenance  

    Siemens AG 6SE8001-0CJ76

    SIMOVERT MV Maintenance Instructions   13

    1.1 Maintenance

    Maintenance includes measures and activities which are used to maintain and re-establish the reference status of the drive converter. These include:

    ♦   Inspection

    ♦   Maintenance

    ♦   Repair

    These instructions provide, in addition to information and instructions oninspection and  maintenance, also detailed information and instructions ontroubleshooting (refer to Section 3) and on replacing components (refer to Section4) of the drive converter (repair).

    Please contact the drive converter supplier for troubleshooting support.

    1.1.1 InspectionInspection is used to identify and evaluate the actual drive converter status. Thisessentially involves visual checks. Inspection work should be carried-out accordingto an appropriate schedule. The maintenance and inspection list (Section 1.2.1)can be used as basis for a regular inspection of the drive converter.

    1.1.2 Maintenance

    Maintenance is used to ensure that the drive converter is kept in its referencestate. Accumulated dirt must be regularly removed and worn parts replaced.

    Maintenance work should be carried-out according to an appropriate schedule. Themaintenance and inspection list (Section 1.2.1) can be used as basis for a regulardrive converter maintenance schedule.

  • 8/18/2019 Simovert Maintanance Manual

    14/152

    1 Regular (preventive) service/maintenance Edition 07.2001

    Siemens AG 6SE8001-0CJ76

    14   SIMOVERT MV Maintenance Instructions

    1.2 Power section

    1.2.1 Maintenance and inspection list

    Visual checks (≤≤≤≤ ½ year)

    Test / measured quantity,tools

    Comments

    Resources:2 technicians / 6 man hours

    Tools:− mirror

    − flashlight

    We recommend that the following visual checksare made on an annual basis. Checks must bemade for accumulated dirt, dependent on theapplication conditions, and removed more

    frequently (≤ ½ year).

    Accumulated dirt (every ½ year)

    Test / measured quantity,tools

    Comments

    −   Insulating clearances   Slight, dry and non-conductive dirt is permissible.Accumulated dirt, which has occurred due to dustin conjunction with a high air humidity, must beremoved. It is especially important that thesurfaces of the semiconductors, the insulatingstuds and fabric-base laminate of the low-inductance busbar assemblies are clean and dry.

    −   Removing accumulateddirt

    A dry, clean cloth must be used to wipe down allof the surfaces in the cabinet. In this case, care

    must be taken that the dirt is not simplydistributed, but is actually removed by continuallychanging the surface of the cloth which is beingused. Cleaning cloths must be manufactured outof a non-fleece material.

    Cloths dipped in ethyl alcohol (it is notpermissible that the cloth becomes saturated)can be used to remove higher levels of dirt. Alsohere, the cloth must be frequently changed sothat the accumulated dirt is not simply distributed.

    A brush and vacuum cleaner can be used toclean inaccessible locations using drycompressed air (max. 1 bar).

    NOTE

    Under no circumstances may fiber-optic cableand fiber-optic cable bundles be cleaned usingmoist cloths or similar. If there is a significantamount of dust, this must be removed using adry, non-fleecing cloth.

    −   Air filter elements(optional)

    Air filters are checked in the cabinet doors for dirtaccumulation. Clean or replace the filter elementsif the airflow is restricted (refer to the Section“Replacing the filter elements”.

  • 8/18/2019 Simovert Maintanance Manual

    15/152

    Edition 07.2001 1 Regular (preventive) service/maintenance  

    Siemens AG 6SE8001-0CJ76

    SIMOVERT MV Maintenance Instructions   15

    Connectors / fiber-optic cable connections

    Test / measured quantity,tools

    Comments

    The contacts are visibly checked to ensure thatthey are firmly seated and are free of anycorrosion.

    The fiber-optic cables for the gating modulesmust be inserted in the connectors up to thewhite mark.

    Checking the screw connections (annually)

    Test / measured quantity,tools

    Comments

    Resources:2 technicians / 8 man hoursTools: 1 set of torque

    wrenches, 1.8 Nmup to > 50 Nm

    Scope: Connections,electr. connections

    Loose connections must be tightened-up with thefollowing tightening torques.The final position of the screw connection shouldbe marked using a waterproof marker.

    Main circuit:

    Thread M4 M6 M8 M10 M12

    Torque 1.8 Nm 6 Nm 13 Nm 25 Nm 50 Nm

    HV-IGBT and neutral point diode connections:

    Thread M4 M8

    Torque 1.8 Nm 10 Nm

    Capacitor connections:

    Thread M8 M16

    Torque 4.5 Nm 25 Nm

  • 8/18/2019 Simovert Maintanance Manual

    16/152

    1 Regular (preventive) service/maintenance Edition 07.2001

    Siemens AG 6SE8001-0CJ76

    16   SIMOVERT MV Maintenance Instructions

    Checking the tension (every 3 years)

    Test / measured quantity,tools

    Comments

    Resources:2 technicians / 4 man hours

    Tool: Open-end wrench

    In order to secure the required function ofthyristors and diodes, the contact pressure ofsemiconductor components must be checked.

    −   Line supply diodes-V1 ... -V3

    The necessary contact pressure of 18 kN (+20 %

     /  −0 %) for the line supply diodes, which aretensioned on the heatsink using tensioning caps,is guaranteed, if the disk at the center of theclamping cap (below the nut) can be rotated.

    Replacing the fans (every 3 years) (only for air-cooling)

    Test / measured quantity,tools

    Comments

    Resources:

    2 technicians / 1.5 man hoursper fan

    Tool:   − set of wrenches

    − screwdriver

    Fans are replaced after approx. 30 000 h

    (refer to Section 1.4 “Replacing the fans”

  • 8/18/2019 Simovert Maintanance Manual

    17/152

  • 8/18/2019 Simovert Maintanance Manual

    18/152

    1 Regular (preventive) service/maintenance Edition 07.2001

    Siemens AG 6SE8001-0CJ76

    18   SIMOVERT MV Maintenance Instructions

    Replacing filter elements (options)

    For drive converters with filter elements, the level of accumulated dirt must bechecked. This should be checked at the beginning of every month to identify howquickly dirt accumulates. The filter elements should be replaced at the appropriate

    intervals.Order No. 6SY8101-0AA45 (460 mm x 1950 mm),

    6SY8101-0AA46 (360 mm x 460 mm)

    Tools required

    ♦   Screwdriver, Size 1

    Removal

    1. Release 2 or 3 M6 screws at the outer side of the door.

    2. Swing-out the filter element assembly.

    3. Remove the filter element.

    Installation

    4. Insert a new filter element and press against the Velcro strip located at the top.

    5. Close the filter assembly.

    6. Tighten the M6 screws.

  • 8/18/2019 Simovert Maintanance Manual

    19/152

    Edition 07.2001 1 Regular (preventive) service/maintenance  

    Siemens AG 6SE8001-0CJ76

    SIMOVERT MV Maintenance Instructions   19

    1.4 Air-cooled drive converters

    1.4.1 Replacing the fans

    The fans must be replaced after 30 000 operating hours. The fans should bereplaced in plenty of time in order to maintain the availability of the drive converter.

    Standard tools required

    ♦   Screwdriver, Size 3

    ♦   Socket wrench with socket Size 13

    Removal

    1. Withdraw the 10-pin connector (front right).

    2. Release the 14 M8 screws (perforated panel, front and rear).

    3. Release the 4 M8 nuts (vibration damping mechanism).4. Lift-out the fan.

    Warning

    The fan is extremely heavy; weight, approx. 50 kg.We recommend that a crane is used if adequate space is available.

    Caution

    When removing the fan take care not to damage the thread of the vibrationdamping mechanism.

    Installation

    5. Install the new fan in the inverse sequence.

    Screw M8 M8 nut

    Torque 13 Nm 13 Nm

  • 8/18/2019 Simovert Maintanance Manual

    20/152

    1 Regular (preventive) service/maintenance Edition 07.2001

    Siemens AG 6SE8001-0CJ76

    20   SIMOVERT MV Maintenance Instructions

    1.5 Water-cooled drive converters

    1.5.1 Cooling system

    Warning

    De-ionized water can escape when carrying-out maintenance and repair work. W etherefore recommend that protective gloves and protective glasses are worn and ifnecessary an acid-proof apron used.

    If seals are removed, then these should be replaced before re-assembling.

    Main flow filter

    The filter insert (-B118) should be cleaned after the system has beencommissioned for the first time. The filter inserts should be cleaned every year andchecked for damage. To do this, close valves (-Y101 / -Y102 / -Y104), screw open

    the filter and remove the filter inserts. Blow-out the filter inserts using compressedair. Re-install in the inverse sequence

    lon exchanger

    The operating time of an ion exchanger cartridge is, under normal operatingconditions, a minimum of 1 year.

    When replacing the ion exchanger, the pair of ball-type valves -Y102 / -Y106 mustbe closed.

    Caution

    When unscrewing the filter, the de-ionized water, remaining in the piping system,empties.

    The complete cartridge can be removed after releasing the PVC-C pipe gland atthe ion exchanger. The manufacturer can re-generate the used resin cartridge.

    Note:

    For more detailed maintenance information / instructions refer to thedocumentation / Operating Instructions of the cooling system.

  • 8/18/2019 Simovert Maintanance Manual

    21/152

  • 8/18/2019 Simovert Maintanance Manual

    22/152

    2 Troubleshooting Edition 07.2001

    Siemens AG 6SE8001-0CJ76

    22   SIMOVERT MV Maintenance Instructions

    2.1 Signal lamps on the modules

    2.1.1 Signal lamps on the common power supply GSV

    There are several LEDs on the GSV module. They have the following significance:

    The green LED ( Va ) is lit, if voltage is present at all of the outputs

     / 55V 100kHz ( standard operation ).

    The red LEDs have the same designation as the appropriate output terminal ( X..)and indicate if the appropriate output has been shutdown due to an overcurrentcondition ( -LED is bright ).

    After a fault has occurred, the unit can only be powered-up again after the inputvoltage has been switched-out and switched-in again using F90 or Q90.

  • 8/18/2019 Simovert Maintanance Manual

    23/152

    Edition 07.2001 2 Troubleshooting  

    Siemens AG 6SE8001-0CJ76

    SIMOVERT MV Maintenance Instructions   23

    2.1.2 Signal lamps on the control subrack

    -A200

    -D01   -D03 -D04   -D05 -D06 -D07

    -G1

    BatteryX4 X3 X2

    X1

    -D02

    PM5 ITSP MM3 CS7 CS8

          F      A      U      L      T

          O      K

    Fig. 2-1 Control subrack

    Input voltage

    The input voltage is monitored for undervoltage and overvoltage.

    ♦   For an undervoltage condition (< 170 ...175 V), the green OK LED goes dark.The system automatically restarts after the input voltage has increased toapprox. 190 V.

    ♦   For overvoltage (> approx. 265 V), the red FAULT LED is bright.

    Output voltages

    All of the output voltages are monitored for an undervoltage condition (e.g. due tooverload/short-circuit).

    ♦   If the 5 V output voltage drops to < 4.7 ... 4.85 V for t > 100 to 200 µs, the redFAULT LED is bright. The system does not automatically restart; the line supplyvoltage must first be disconnected.

    ♦   If the ±15 V output voltage drops to < approx. 14 V or >  −14 V, the red FAULTLED is bright. The 5 V voltage remains and a system failure message is output.

  • 8/18/2019 Simovert Maintanance Manual

    24/152

  • 8/18/2019 Simovert Maintanance Manual

    25/152

    Edition 07.2001 2 Troubleshooting  

    Siemens AG 6SE8001-0CJ76

    SIMOVERT MV Maintenance Instructions   25

    2.2 Signal lamps at the control cabinet (option L50)

    There are four signal lamps at the upper front section of the control cabinet.

    Green lamp

    Continuous light:  The drive converter is ready to be powered-up, i.e. the circuit-breaker is open, there is no fault and no OFF2 or OFF3 present.

    Flashing light:  The drive converter is not ready to be powered-up, but

    −   OFF2 or OFF3 is present.

    −   The download or drive settings’ status is active or MLFB input is active.

    −   The crowbar thyristor recovery time is running.

    White lamp

    Continuous light:  The drive converter is operational, the circuit-breaker is closedand the inverter is enabled.

    Flashing light: 

    −   The DC link is pre-charged, the circuit-breaker is closed, the inverter pulses areinhibited.

    −   The drive converter is just going into operation, i.e. pre-charging is running andthe auxiliaries are powered-up.

    −   The drive converter has just been powered-down (OFF2 and OFF3).

    −   Automatic restart is active.

    −   Test mode has been selected (pre-charging, circuit-breaker and chopper).

    Yellow lamp

    Continuous light:  An alarm (fault Class 5) is present.

    Red lamp

    Flashing light:  A fault is present.

  • 8/18/2019 Simovert Maintanance Manual

    26/152

    3 Replacing components Edition 07.2001

    Siemens AG 6SE8001-0CJ76

    26   SIMOVERT MV Maintenance Instructions

    3 Replacing components

    Warning

    When operational, over 1000 Volt (medium voltage!) can be present at this driveconverter. This can result in death or severe bodily injury. Extreme care must betaken when working on the equipment.

    It is imperative that the warning information and instructions in Section 1 arecarefully observed!

    CautionThe electronic modules contain components which can be destroyed byelectrostatic discharge. These components can be easily destroyed if they areincorrectly handled.When carrying-out any work, it is important that the ESDS protective measures aremaintained. If this is not observed, there is a danger that the components could beelectrically destroyed which would have a negative impact on the functioning of thedrive converter.

    Note

    The HV-IGBTs used (Insulated Gate Bipolar Transistor) are also components

    which can be destroyed by electrostatic discharge. These components can beeasily destroyed when incorrectly handled. All of the information and instructionsabove should also be observed for the HV-IGBTs in order to avoid damaging thedrive converter and to ensure that it continues to function correctly.Furthermore, before transporting the equipment, the gate and emitter connectionsof the HV-IGBTs must always be short-circuited.

    Warning

    When working on the drive converter it should be observed that the minimumbending radii for water hoses of r = 80 mm should not be fallen below.

    Caution

    When working on the drive converter it should be ensured that the minimumbending radii for fiber-optic cables of r = 30 mm is not fallen below.Fiber-optic cables are sensitive to pressure which means that they must becarefully handled.The fiber-optic cables can be destroyed if this information is not carefully observed.

  • 8/18/2019 Simovert Maintanance Manual

    27/152

  • 8/18/2019 Simovert Maintanance Manual

    28/152

  • 8/18/2019 Simovert Maintanance Manual

    29/152

    Edition 07.2001 3 Replacing components  

    Siemens AG 6SE8001-0CJ76

    SIMOVERT MV Maintenance Instructions   29

    Fig. 3-2 Installing the line supply diode modules

  • 8/18/2019 Simovert Maintanance Manual

    30/152

  • 8/18/2019 Simovert Maintanance Manual

    31/152

  • 8/18/2019 Simovert Maintanance Manual

    32/152

  • 8/18/2019 Simovert Maintanance Manual

    33/152

    Edition 07.2001 3 Replacing components  

    Siemens AG 6SE8001-0CJ76

    SIMOVERT MV Maintenance Instructions   33

    3.3 Replacing the electronic shunt AVT2

    Standard tools required

    ♦   Screwdriver, Size 1♦   Open-ended wrench SW19

    ♦   Torque wrench

            2        0

            1        1        0

    X6

          X     1

          X     2      (      I      )

          X     3      (      U      )

          X     5   +−

          X     4

    Rating plate

    X1: Power supply connectionX2: Output, current actual value via fiber-optic cable

    X3: Output, voltage actual value via fiber-optic cableX4: Connection, busbar (+)X5: Connection, busbar (-)X6: UHF connector for voltage input

    Fig. 3-4 Electronic shunt AVT2

  • 8/18/2019 Simovert Maintanance Manual

    34/152

  • 8/18/2019 Simovert Maintanance Manual

    35/152

    Edition 07.2001 3 Replacing components  

    Siemens AG 6SE8001-0CJ76

    SIMOVERT MV Maintenance Instructions   35

    3.4 Fiber-optic cable connection

    3.4.1 Thyristor gating

    The fiber-optic cables are provided with a colored ring so that the correct locationcan be checked. The colored ring must be flush with the union nut at the lighttransmitter and light receiver modules.

    Fiber-optic cable

    Shielding cover

    PC board

    White colored ring17.5

    X

    Device lens

    Light transmitter or receiver module

    Fig. 3-5 Fiber-optic cable connection

    Note

    In order to guarantee long-term, disturbance-free drive converter operation, it isessential that the fiber-optic cables are carefully inserted and screwed into place.In order to achieve minimum launch-in and launch-out damping effects for thefiber-optic cable connections, they have a white colored ring.

    Thus, when connecting the fiber-optic cables, it should be ensured that this whitecolored ring is flush with the union nut at the light transmitter and receiver modules.

    3.4.2 UEL module

    Check that the connector is firmly seated and has correctly snapped into place.

  • 8/18/2019 Simovert Maintanance Manual

    36/152

    3 Replacing components Edition 07.2001

    Siemens AG 6SE8001-0CJ76

    36   SIMOVERT MV Maintenance Instructions

    3.5 Cooling water

    When operational, the conductivity of the cooling water in the drive converter isautomatically kept at the required value using the ion exchanger in the coolingsystem. If the drive converter cooling water was drained, e.g. due to repair work,then only de-ionized water must be used to re-fill it (data, refer to the Descriptionof SIMOVERT MV).

    The de-ionized water is filled through the cooling system.

    A vent valve is provided at each vertical group pipe to vent the water circuit in thedrive converter.

    Caution

    When venting the drive converter it is not permissible that water sprays or dropsonto the drive converter components. Before the drive converter is powered-up, itmust be completely dry.A hose (8 mm diameter) must be screwed onto the vent valve (a connection is

    provided on the valve) to vent air from the system. Use a container to catch anywater.

    Refer to the Commissioning Instructions for the measures which are required to re-commission the drive converter (purge and vent reduce the conductivitycoefficient).

    If the drive converter was accidentally filled with normal raw water, then the driveconverter may not be powered-up. Drain the water and remove any residual rawwater from all of the pipes and heatsinks by blowing nitrogen through the completesystem.

    3.5.1 Draining the system

    De-ionized water circuit

    Warning

    Please observe the safety information and instructions before draining the system(protect eyes, hands and body)! The system may only be emptied with the pumpsstationary and the voltages disconnected.

    The de-ionized water circuit is emptied using the two drain valves in the coolingsystem. These are located at the lowest position in both the intake and return. Aftera suitable hose or similar is connected to the valve, the valve must be slowlyopened so that the pressure can slowly and continually decrease. All of the ballvalves in the de-ionized water circuit must be open. The vent valve at theequalization reservoir must be open. After a short time, the vents in the pipes mustbe opened. After the system has been emptied, all of the connections and ventsmust be correctly closed again.

    Raw water circuit

    Refer to the documentation / Operating Instructions, for the cooling system

    3.5.2 Filling the system

    Refer to the Commissioning Instructions and documentation / OperatingInstructions, cooling system.

  • 8/18/2019 Simovert Maintanance Manual

    37/152

  • 8/18/2019 Simovert Maintanance Manual

    38/152

    4 Replacing modules Edition 07.2001

    Siemens AG 6SE8001-0CJ76

    38   SIMOVERT MV Maintenance Instructions

    30.Re-check the correct location of the modules which have been inserted.

    Replacing the PM5 processor module

    The PM5 processor module (-A200-D01) contains a memory card. This must beremoved from the module which is to be replaced. The memory card should be re-inserted after the replacement module has been inserted.

    Replacing the interface module SS52 –X2 on the CS7 – module A200 – D05

    If the module is replaced, the appropriate firmware must be downloaded into thenew module. Refer to the Commissioning Instructions, Section 5 for downloadingthe firmware.

    Replacing the door – OP7 operator panelIf the OP7 is replaced, the appropriate firmware must be downloaded into the newOP7. Refer to the Commissioning Instructions, Section 5 for downloading thefirmware.

  • 8/18/2019 Simovert Maintanance Manual

    39/152

    Edition 07.2001 5 Fault and alarm messages  

    Siemens AG 6SE8001-0CJ76

    SIMOVERT MV Maintenance Instructions   39

    5 Fault and alarm messages

    All of the SIMOVERT MV drive converter fault messages, from software version 50,are described on the following pages.

    A page is reserved for each message, which is structured as follows:

    No.   Message number 

    Message:   Location message text 

    Description:   Brief explanation of the message text 

    Caution 

    Warning information if it involves the power section and a high voltage may be present. There is also a 400V auxiliary voltage in the control section which requires special care.

    Before starting any work, please observe the five safety rules listed in Section 1.

    Causes: Remedy:

    Possible first cause. Measures for the first cause.

    Possible second cause. Measures for the second cause.

    Possible third cause. Measures for the third cause.

    etc. etc.

  • 8/18/2019 Simovert Maintanance Manual

    40/152

    5 Fault and alarm messages Edition 07.2001

    Siemens AG 6SE8001-0CJ76

    40   SIMOVERT MV Maintenance Instructions

    No. 001

    Message: Circuit-breaker not ready

    Description: The "Circuit-breaker ready to close-up" checkback signalmissing or is not detected.

    Caution

    When operational, over 1000 Volt (medium voltage!) can be present at this driveconverter. This can result in death or severe bodily injury. Extreme care must betaken when working on the equipment.

    It is imperative that the warning information and instructions in Section 1 arecarefully observed!

    Causes: Remedy:

    Circuit-breaker withdrawn. Check the circuit-breaker.

    Interrupted cable.

    Poor contact.

    Defective signal generation in thecircuit breaker

    Check the signal flow according to the circuit diagram.

    Power supply –G120 failed, motorcircuit-breaker –F120 tripped,

    Check the cables and devices.

    Check the voltages.

    P390, bit 0 is not correctlyparameterized

    24V must be present at terminal module –A252 for thefactory setting of P390, if the circuit-breaker is ready.

    The signal level can be read at parameter r396 (bit 0):Circuit-breaker not ready. --> 1)

    Check parameter P390 (bit 0) as to whether the signal isinverted.

    Defective input module or terminalmodule –A252.

    Replace the input module or terminal module –A252.

  • 8/18/2019 Simovert Maintanance Manual

    41/152

  • 8/18/2019 Simovert Maintanance Manual

    42/152

    5 Fault and alarm messages Edition 07.2001

    Siemens AG 6SE8001-0CJ76

    42   SIMOVERT MV Maintenance Instructions

    No. 003

    Message: Circuit-breaker ON checkback signal missing

    Description: The “Circuit-breaker on” checkback signal missing or is notdetected.

    Caution

    When operational, over 1000 Volt (medium voltage!) can be present at this driveconverter. This can result in death or severe bodily injury. Extreme care must betaken when working on the equipment.

    It is imperative that the warning information/instructions in Section 1 arecarefully observed!

    Causes: Remedy:

    Interrupted cable.

    Poor contact.

    Defective signal generation in thecircuit-breaker.

    Check the signal flow according to the circuit diagram.

    P390, bit 1 is not correctlyparameterized

    24V must be available at terminal module –A253 for thefactory setting of P390, if the circuit-breaker is closed.

    The signal level can be read at parameter r396 (bit 1):

    Circuit-breaker checkback signal CLOSED. --> 1)

    Check parameter P390 (bit 1) as to whether the signal isinverted.

    Defective input module or terminalmodule –A252.

    Replace the input module or terminal module –A252.

  • 8/18/2019 Simovert Maintanance Manual

    43/152

  • 8/18/2019 Simovert Maintanance Manual

    44/152

    5 Fault and alarm messages Edition 07.2001

    Siemens AG 6SE8001-0CJ76

    44   SIMOVERT MV Maintenance Instructions

    No. 005

    Message: Circuit-breaker opening time > max

    Description: The “Circuit-breaker open” checkback signal is missing or isreceived too late. The time between the "Open circuit-breaker"command up to when the "Circuit-breaker open" checkbacksignal is received, is monitored. This fault message isdisplayed if this time is exceeded (more than 100ms). Also referto r399.

    Causes: Remedy:

    Circuit-breaker opens too slow. The circuit-breaker may not require longer than 100ms toopen.  For safety-related trips, the drive convertercould be damaged if the tripping time of the circuit-breaker is too long!

    -If the control of the off coil and the undervoltage trip arenot directly realized via the drive converter, but using oneor several coupling relays, then the coupling relays mustbe removed from the control circuit, as they extend thetripping time.

    Interrupted cable.

    Poor contact.

    Defective signal generation in thecircuit-breaker.

    Check the signal flow according to the circuit diagram.

    Power supply –G120 failed, motorcircuit-breaker –F120 tripped.

    Check the cables and devices.Check the voltages.

    P390, bit 2 is not correctlyparameterized

    24V must be available at terminal module –A253 for thefactory setting of P390, if the circuit-breaker is open.

    The signal level can be read at parameter r396 (bit 2):Circuit-breaker OPEN. --> 1)

    Check parameter P390 (bit 2) as to whether the signal isinverted.

    Defective input module or terminalmodule –A253.

    Replace the input module or terminal module –A253.

  • 8/18/2019 Simovert Maintanance Manual

    45/152

    Edition 07.2001 5 Fault and alarm messages  

    Siemens AG 6SE8001-0CJ76

    SIMOVERT MV Maintenance Instructions   45

    No. 017

    Message: Control cabinet power supply failure

    Description: The checkback signal of an auxiliary contact from at least oneprotective circuit-breaker is missing or is not detected.

    Causes: Remedy:

    The monitoring circuit at digital inputA263 : 5 has responded. It includesthe monitoring contacts from thepower supplies and their protectivecircuit-breaker.

    Check and close the protective circuit-breaker.

    If required adjust or check the associated device.

    Check using the circuit diagram.

    P412 is incorrectly parameterizedPoor contact.

    Interrupted cable.

    The signal level can be read at parameter r413 (bit 1):

    All motor circuit-breakers closed --> 0,

    one motor circuit-breaker tripped --> 1).

    Check parameter P412 (bit 1) as to whether the signal isinverted. –P412 bit 1 must be inverted!

    Defective input module or terminalmodule –A263.

    Replace the input module or terminal module –A263.

  • 8/18/2019 Simovert Maintanance Manual

    46/152

    5 Fault and alarm messages Edition 07.2001

    Siemens AG 6SE8001-0CJ76

    46   SIMOVERT MV Maintenance Instructions

    No. 018

    Message: Drive converter insulation fault

    Description: The insulation monitoring –B190 has responded.

    Caution

    When operational, over 1000 Volt (medium voltage!) can be present at this driveconverter. This can result in death or severe bodily injury. Extreme care must betaken when working on the equipment.

    It is imperative that the warning information and instructions in Section 1 arecarefully observed! P412 is incorrectly parameterized.

    Causes: Remedy:

    The insulation measurement resultedin an inadmissible value.

    The insulation in the drive converterbetween the line and machine sides ismeasured. Poor contact.

    Interrupted cable.

    Check the setting and display of the insulation monitor(refer to the Commissioning Instructions).

    Check the power section, the pre-charging, with aninsulating measuring device, 2.5 kV DC.

    Caution: 

    The insulation monitoring –A190 / –B190 must be disconnected as otherwise it is also measured.

    P412 is incorrectly parameterized The signal level can be read at parameter r413 (bit 2):

    Insulation O.K. --> 0,

    Check parameter P412 (bit 2) as to whether the signal isinverted.

    Input module or terminal module – A264 defective.

    Replace the input module or terminal module –A264.

  • 8/18/2019 Simovert Maintanance Manual

    47/152

  • 8/18/2019 Simovert Maintanance Manual

    48/152

  • 8/18/2019 Simovert Maintanance Manual

    49/152

  • 8/18/2019 Simovert Maintanance Manual

    50/152

    5 Fault and alarm messages Edition 07.2001

    Siemens AG 6SE8001-0CJ76

    50   SIMOVERT MV Maintenance Instructions

    No. 022

    Message: Drive converter fault when pre-charging the DC link

    Description: When pre-charging, the DC link voltage must increase at adefined rate-of-rise. Message 022 is displayed if this value isnot reached.

    Caution

    When operational, over 1000 Volt (medium voltage!) can be present at this driveconverter. This can result in death or severe bodily injury. Extreme care must be

    taken when working on the equipment.It is imperative that the warning information and instructions in Section 1 arecarefully observed!

    Causes: Remedy:

    Motor circuit-breaker –Q140 tripped.

    Defective contactor –K140.

    Undervoltage condition of the 400Vauxiliary power supply.

    Defective Vd voltage sensing –U200,

    -R200, -R201.

    Interrupted cable.

    Defective pre-charging rectifier – A140.

    Defective pre-charging resistors – R140 .. –R145.

    Pre-charging transformer –T140, -T141 connected to the wrong tap.

    Defective/blown fuse F5 / F6 at thepre-charging rectifier A140.

    Check the DC link, pre-charging device and actual valuesensing according to the circuit diagram.

    Measure the voltages.

  • 8/18/2019 Simovert Maintanance Manual

    51/152

    Edition 07.2001 5 Fault and alarm messages  

    Siemens AG 6SE8001-0CJ76

    SIMOVERT MV Maintenance Instructions   51

    No. 023

    Message: Drive converter Fault when discharging the DC link

    Description: When discharging, the DC link voltage must decrease with adefined rate-of-rise. If this value is not reached, the signal isdisplayed. It is possible that the discharge device was notcontrolled. When used with a sinusoidal filter or IHV filter, athigh speeds, when powering-down the filter can energize themotor and the discharge operation can take a long time.

    Caution:

    A high DC link voltage can still be present.

    Caution

    When operational, over 1000 Volt (medium voltage!) can be present at this driveconverter. This can result in death or severe bodily injury. Extreme care must betaken when working on the equipment.

    It is imperative that the warning information and instructions in Section 1 arecarefully observed!

    Causes: Remedy:

    Defective discharge resistor –R180, -R181.

    Defective gating circuits –A181, -A182.

    Power supply of the dischargeequipment –F90 (-G90), -T182, -T183faulted

    Defective fiber-optic cable at – A300.U16, U17, U52, U53.

    Defective light transmitter on –A300.

    Faulted connecting cable –A300-X1 --D02-A2-X32.

    Check the discharge circuit according to the circuitdiagram.

    Check the power supply, fiber-optic cables and lighttransmitter.

    Kinked fiber-optic cables or weak transmitters can alsoresult in faults.

    Replace the appropriate components if defective.

  • 8/18/2019 Simovert Maintanance Manual

    52/152

    5 Fault and alarm messages Edition 07.2001

    Siemens AG 6SE8001-0CJ76

    52   SIMOVERT MV Maintenance Instructions

    No. 024

    Message: Control cabinet Safety circuit activated

    Description: The safety circuit has been interrupted.

    Causes: Remedy:

    Pushbutton –S10 in the controlcabinet door has been actuated.

    External trip (–X100.38 .39).

    Grounding breaker closed (-X100.42.43).

    Subrack –A200 failed.

    Localize the shutdown sources.

    Check according to the circuit diagram.

    Poor contact.

    Interrupted cable. Check according to the circuit diagram.

    P412 is incorrectly parameterized. The signal level can be read at parameter r413 (bit 0):

    Circuit closed --> 0,

    Check parameter P412 (bit 0) as to whether the signal isinverted.

    Defective input module or terminalmodule –A263.

    Replace the input module or terminal module –A263.

  • 8/18/2019 Simovert Maintanance Manual

    53/152

    Edition 07.2001 5 Fault and alarm messages  

    Siemens AG 6SE8001-0CJ76

    SIMOVERT MV Maintenance Instructions   53

    No. 025

    Message: Control cabinet Air discharge temperature > limit1

    Description: The air discharge temperature in the control cabinet is greaterthan the limit value in P422. The drive converter could betripped if the temperature continues to increase.

    Causes: Remedy:

    Incorrect limit value.   Check parameter P422. Factory setting: 55 °C, it is notpermissible that the value is set higher!

    Defective sensor. Check the temperature display in parameter r425.

    r425 must be greater than/equal to the measured ambient

    temperature.Check sensor –R883. If required, replace the sensor.

    Poor contact.

    Interrupted cable. Check according to the circuit diagram.

    The discharge equipment (crowbarthyristor) responds several times.

    Remove the cause for the frequent response of thedischarge equipment.

    Ambient temperature too high. Reduce the ambient temperature.

    Component in the control cabinet

    overheated.

    Check the devices in the control cabinet.

    Air cooling:

    Filter element in the cabinet doordirty.

    Replace the filter element.

    Water cooling:

    Air intake or discharge openingscovered.

    Ensure that air can freely enter through the cabinet doorand freely exit (top assembly).

    Especially for degree of protectionIP54: The discharge equipment(crowbar thyristor) responds several

    times.Internal cooling failed.

    Remove the cause for the frequent response of thedischarge equipment.

    Check the internal cooling (fan, heat exchanger in the

    power section, some of the air is also re-circulatedthrough openings in the control cabinet).

    Defective input module or terminalmodule –A262.

    Replace the input module or terminal module –A262.

  • 8/18/2019 Simovert Maintanance Manual

    54/152

    5 Fault and alarm messages Edition 07.2001

    Siemens AG 6SE8001-0CJ76

    54   SIMOVERT MV Maintenance Instructions

    No. 026

    Message: Control cabinet Air discharge temperature > limit2

    Description: The air discharge temperature in the control cabinet is greaterthan the limit value in P423. Also refer to message No. 25.

    Causes: Remedy:

    Incorrect limit value. Check parameter P423. Factory setting: 60 °C;

    this may not be set higher!

    Refer to message No. 25

  • 8/18/2019 Simovert Maintanance Manual

    55/152

  • 8/18/2019 Simovert Maintanance Manual

    56/152

    5 Fault and alarm messages Edition 07.2001

    Siemens AG 6SE8001-0CJ76

    56   SIMOVERT MV Maintenance Instructions

    No. 028

    Message: Drive converter Air discharge temperature > limit2

    Description: The air discharge temperature in the power section is greaterthan the limit value in P427. This message causes the driveconverter to trip.Also refer to message No. 27.

    Caution

    When operational, over 1000 Volt (medium voltage!) can be present at this drive

    converter. This can result in death or severe bodily injury. Extreme care must betaken when working on the equipment.

    It is imperative that the warning information and instructions in Section 1 arecarefully observed!

    Causes: Remedy:

    Incorrect limit value. Check parameter P427. The factory setting is 50 °C; thismay not be set higher!

    Refer to message No. 27.

  • 8/18/2019 Simovert Maintanance Manual

    57/152

    Edition 07.2001 5 Fault and alarm messages  

    Siemens AG 6SE8001-0CJ76

    SIMOVERT MV Maintenance Instructions   57

    No. 029

    Message: Drive converter Protective trip, optional fan

    Description: Fan failure for options, e.g. L08, L14, L15, M57.

    Caution

    When operational, over 1000 Volt (medium voltage!) can be present at this driveconverter. This can result in death or severe bodily injury. Extreme care must betaken when working on the equipment.

    It is imperative that the warning information and instructions in Section 1 are

    carefully observed!

    Causes: Remedy:

    P412 is incorrectly parameterized. The signal level can be read at parameter r413 (bit 3):

    No checkback signal --> 1,

    check parameter P412 (bit3) as to whether the signal isinverted.

    Option L08, output reactor   Check the fan for correct function using circuit diagram=.G1.

    Maintain the maintenance intervals.

    Option L14, IHV filter   Check the fan for correct function using circuit diagram=.G3.

    Maintain the maintenance intervals.

    Option L15, sinusoidal EMC filter   Check the fan for correct function using circuit diagram=.G2.

    Maintain the maintenance intervals.

    Option M57, degree of protectionIP54

    Check the fan for correct function using circuit diagram=.D1.

    Maintain the maintenance intervals.Additional options Check the fan for correct function using circuit diagram.

    Maintain the maintenance intervals.

    Defective input module or terminalmodule –A264.

    Replace the input module or terminal module –A264.

  • 8/18/2019 Simovert Maintanance Manual

    58/152

    5 Fault and alarm messages Edition 07.2001

    Siemens AG 6SE8001-0CJ76

    58   SIMOVERT MV Maintenance Instructions

    No. 030

    Message: Crowbar thyristor Upper DC link halves, no checkback signal

    Description: The crowbar thyristor has been triggered by the control and thecommand checkback signal is not present.

    Caution

    When operational, over 1000 Volt (medium voltage!) can be present at this driveconverter. This can result in death or severe bodily injury. Extreme care must betaken when working on the equipment.

    It is imperative that the warning information and instructions in Section 1 arecarefully observed!

    Causes: Remedy:

    Defective fiber-optic cable connectionfrom the gating module –A181 to theUEL module –A300. Faultedconnecting cable –A300-X1 - -D02-A2-X32.

    Check the fiber-optic cable using a light source and, ifrequired, replace.

    -if required, replace A300.

    -if required, replace the connecting cable.

    Defective gating module –A181 ortransformer –T182.

    Check the modules using the circuit diagram.

    Replace the defective modules.

    Check the connectors and cables to ensure that they arefirmly seated.

  • 8/18/2019 Simovert Maintanance Manual

    59/152

    Edition 07.2001 5 Fault and alarm messages  

    Siemens AG 6SE8001-0CJ76

    SIMOVERT MV Maintenance Instructions   59

    No. 031

    Message: Crowbar thyristor Lower DC link halves no checkback signal

    Description: The crowbar thyristor has been triggered by the control and thecommand checkback signal is not present.

    Caution

    When operational, over 1000 Volt (medium voltage!) can be present at this driveconverter. This can result in death or severe bodily injury. Extreme care must betaken when working on the equipment.

    It is imperative that the warning information and instructions in Section 1 arecarefully observed!

    Caution: Remedy:

    Defective fiber-optic cable connectionfrom the gating module –A182 to theUEL module –A300. Faultedconnecting cable –A300-X1 - -D02-A2-X32.

    Check the fiber-optic cable using a light source and, ifrequired, replace.

    -if required, replace A300.

    -if required, replace the connecting cable.

    Defective gating module –A182 ortransformer –T183.

    Check the modules using the circuit diagram =.J1.

    Replace the defective modules.

    Check the connectors and cables to ensure that they arefirmly seated.

  • 8/18/2019 Simovert Maintanance Manual

    60/152

    5 Fault and alarm messages Edition 07.2001

    Siemens AG 6SE8001-0CJ76

    60   SIMOVERT MV Maintenance Instructions

    No. 034

    Message: Power-on logic 'Inverter inhibit' status transition missing

    Description: The change condition "Motor voltage = 0" or the changecondition "Discharge Unit On" is not fulfilled.This message signifies a problem which can only be solved byspecialists.In this case, the Hotline should be contacted:

    Europe and Africa time zone:

    !!!!   +49 (0)180 5050-222

    !!!!  +49 (0)180 5050-223

    """"   [email protected]

    North America time zone:

    !!!!   +1 (0)770 740-3505

    !!!!   +1 (0)770 740-3396

    """"   [email protected]

    Asia and Australia time zone:!!!!   +65 (0)740-7000

    !!!!   +65 (0)740-7001

    """"   [email protected]

  • 8/18/2019 Simovert Maintanance Manual

    61/152

    Edition 07.2001 5 Fault and alarm messages  

    Siemens AG 6SE8001-0CJ76

    SIMOVERT MV Maintenance Instructions   61

    No. 035

    Message: Power-on logic 'Circuit-breaker open' status transition

    missing

    Description: The change condition “Checkback signal circuit-breaker open”is not fulfilled.This message signifies a problem which can only be solved byspecialists.In this case, the Hotline should be contacted:

    Europe and Africa time zone:

    !!!!   +49 (0)180 5050-222

    !!!!   +49 (0)180 5050-223

    """"   [email protected]

    North America time zone:

    !!!!   +1 (0)770 740-3505

    !!!!   +1 (0)770 740-3396

    """"   [email protected]

    Asia and Australia time zone:

    !!!!   +65 (0)740-7000

    !!!!   +65 (0)740-7001

    """"   [email protected]

  • 8/18/2019 Simovert Maintanance Manual

    62/152

    5 Fault and alarm messages Edition 07.2001

    Siemens AG 6SE8001-0CJ76

    62   SIMOVERT MV Maintenance Instructions

    No. 036

    Message: Power-on logic 'Crowbar thyristor on' status transition

    missing.

    Description: The change condition “Checkback signal circuit-breaker open”is not fulfilled.This message signifies a problem which can only be solved byspecialists.In this case, the Hotline should be contacted:

    Europe and Africa time zone:

    !!!!   +49 (0)180 5050-222

    !!!!   +49 (0)180 5050-223

    """"   [email protected]

    North America time zone:

    !!!!   +1 (0)770 740-3505

    !!!!   +1 (0)770 740-3396

    """"   [email protected]

    Asia and Australia time zone:

    !!!!   +65 (0)740-7000

    !!!!   +65 (0)740-7001

    """"   [email protected]

  • 8/18/2019 Simovert Maintanance Manual

    63/152

    Edition 07.2001 5 Fault and alarm messages  

    Siemens AG 6SE8001-0CJ76

    SIMOVERT MV Maintenance Instructions   63

    No. 038

    Message: Power-on logic 'Pre-charge DC link' status transition missing

    Description: The change condition “85% rated voltage” reached is notfulfilled.This message signifies a problem which can only be solved byspecialists.In this case, the Hotline should be contacted:

    Europe and Africa time zone:

    !!!!   +49 (0)180 5050-222

    !!!!  +49 (0)180 5050-223

    """"   [email protected]

    North America time zone:

    !!!!   +1 (0)770 740-3505

    !!!!   +1 (0)770 740-3396

    """"   [email protected]

    Asia and Australia time zone:!!!!   +65 (0)740-7000

    !!!!   +65 (0)740-7001

    """"   [email protected]

  • 8/18/2019 Simovert Maintanance Manual

    64/152

  • 8/18/2019 Simovert Maintanance Manual

    65/152

    Edition 07.2001 5 Fault and alarm messages  

    Siemens AG 6SE8001-0CJ76

    SIMOVERT MV Maintenance Instructions   65

    No. 042

    Message: Power-on logic 'Off3' status transition missing

    Description: The change condition "Speed = 0" is not fulfilled.This message signifies a problem which can only be solved byspecialists.In this case, the Hotline should be contacted:

    Europe and Africa time zone:

    !!!!   +49 (0)180 5050-222

    !!!!   +49 (0)180 5050-223

    """"   [email protected]

    North America time zone:

    !!!!   +1 (0)770 740-3505

    !!!!   +1 (0)770 740-3396

    """"   [email protected]

    Asia and Australia time zone:

    !!!!   +65 (0)740-7000

    !!!!   +65 (0)740-7001

    """"   [email protected]

  • 8/18/2019 Simovert Maintanance Manual

    66/152

    5 Fault and alarm messages Edition 07.2001

    Siemens AG 6SE8001-0CJ76

    66   SIMOVERT MV Maintenance Instructions

    No. 043

    Message: Power-on logic 'Wait for power-on condition' status transition

    missing

    Description: The change conditions "Auxiliaries ready", "Circuit-breakerclosed", "Transformer inrush time not running" and "Coolingsystem on" are not fulfilled.This message signifies a problem which can only be solved byspecialists.In this case, the Hotline should be contacted:

    Europe and Africa time zone:

    !!!!   +49 (0)180 5050-222

    !!!!   +49 (0)180 5050-223

    """"   [email protected]

    North America time zone:

    !!!!   +1 (0)770 740-3505

    !!!!   +1 (0)770 740-3396

    """"   [email protected]

    Asia and Australia time zone:

    !!!!   +65 (0)740-7000

    !!!!   +65 (0)740-7001

    """"   [email protected]

  • 8/18/2019 Simovert Maintanance Manual

    67/152

    Edition 07.2001 5 Fault and alarm messages  

    Siemens AG 6SE8001-0CJ76

    SIMOVERT MV Maintenance Instructions   67

    No. 047

    Message: Fault, kinetic buffering

    Description: The kinetic buffering KIP was no longer able to maintain the DClink voltage and the drive converter was tripped (powered-down).The kinetic buffering function (KIP) must be enabled with P620= 1. During brief line supply faults, the KIP maintains the DClink voltage at a setpoint specified by P622. The drive slowlybrakes. If the line supply fault lasts for a longer period of time,the drive can be braked down to standstill. In this case, KIPshuts down with fault.

    If the automatic restart function WEA is also enabled, then thisattempts to power-up the drive again.If the WEA is not enabled, the drive remains in the "Fault"condition.

  • 8/18/2019 Simovert Maintanance Manual

    68/152

    5 Fault and alarm messages Edition 07.2001

    Siemens AG 6SE8001-0CJ76

    68   SIMOVERT MV Maintenance Instructions

    No. 048

    Message: Fault, automatic restart function

    Description: The automatic restart function was not able to power-up thedrive again after a line supply fault.

    Causes: Remedy:

    Delay time P836 too short, i.e. the linesupply fault is longer than the delaytime.

    Adapt P836 to the actual line supply conditions.

    P837 to P840 incorrect. Adapt P837 to P840 to the existing synchronizing voltage.

    Defective synchronizing voltage

    detection –A110.

    Measure the synchronizing voltage at input –A110.

    The measured value must be the same in all phases.Enter the measured value into P837.

    The following must be obtained: r846 = 1.0  ±  1%.

    Synchronizing voltage erroneous. The line frequency can be read-off at r845 and the linevoltage (referred to P837) at r846.

  • 8/18/2019 Simovert Maintanance Manual

    69/152

    Edition 07.2001 5 Fault and alarm messages  

    Siemens AG 6SE8001-0CJ76

    SIMOVERT MV Maintenance Instructions   69

    No. 049

    Message: External fault 1 from the remote control, terminal strip / bus

    Description: External fault 1 is present. The fault message can be connectedusing Biko technology.Factory setting:Parameter P231 -> 2011.Parameter H231 -> 2011.The cause of the message depends on the wiring.

    Causes: Remedy:

    An external monitoring device has

    responded.

    Check whether a monitoring device has responded.

    Check this according to the circuit diagram if the trip wasreceived via Profibus or the technology module. Checkthe monitoring devices connected to the communicationspartner or to the technology module.

    Interrupted cable.

    Poor contact.

    Trace the signal according to the circuit diagram.

    Profibus / control word 1 bit 15   Check the control word sent by the communicationspartner.

    Appropriate bits from the PZD word ofthe technology module

    Check the control word sent from the communicationsmodule.

  • 8/18/2019 Simovert Maintanance Manual

    70/152

  • 8/18/2019 Simovert Maintanance Manual

    71/152

    Edition 07.2001 5 Fault and alarm messages  

    Siemens AG 6SE8001-0CJ76

    SIMOVERT MV Maintenance Instructions   71

    No. 051

    Message: External alarm 1 from the remote control, terminal strip / bus

    Description: External alarm 1 is present. The fault message can beconnected using Biko technology.Factory setting:Parameter P243 -> 2011.Parameter H243 -> 2011.The cause of the message depends on the wiring.

    Causes: Remedy:

    An external monitoring device has

    responded.

    Check whether a monitoring device has responded.

    Check this according to the circuit diagram if the trip wasreceived via Profibus or the technology module. Checkthe monitoring devices connected to the communicationspartner or to the technology module.

    Interrupted cable.

    Poor contact.

    Trace the signal according to the circuit diagram.

    Profibus / control word 2 bit 12   Check the control word sent by the communicationspartner.

    Appropriate bits from the PZD word ofthe technology module

    Check the control word sent from the communicationsmodule.

  • 8/18/2019 Simovert Maintanance Manual

    72/152

    5 Fault and alarm messages Edition 07.2001

    Siemens AG 6SE8001-0CJ76

    72   SIMOVERT MV Maintenance Instructions

    No. 052

    Message: External alarm 2 from the remote control, terminal strip / bus

    Description: External alarm 2 is present. The fault message can beconnected using Biko technology.Factory setting:Parameter P244 -> 2011.Parameter H244 -> 2011.The cause of the message depends on the wiring.

    Causes: Remedy:

    An external monitoring device has

    responded.

    Check whether a monitoring device has responded.

    Check this according to the circuit diagram if the trip wasreceived via Profibus or the technology module. Checkthe monitoring devices connected to the communicationspartner or to the technology module.

    Interrupted cable.

    Poor contact.

    Trace the signal according to the circuit diagram.

    Profibus / control word 2 bit 13   Check the control word sent by the communicationspartner.

    Appropriate bits from the PZD word ofthe technology module

    Check the control word sent from the communicationsmodule.

  • 8/18/2019 Simovert Maintanance Manual

    73/152

    Edition 07.2001 5 Fault and alarm messages  

    Siemens AG 6SE8001-0CJ76

    SIMOVERT MV Maintenance Instructions   73

    No. 065

    Message: Cooling system Checkback signal ON missing

    Description: The “ON” checkback signal of the water cooling system ismissing or is not detected. This fault can only occur for water-cooled drive converters.

    Causes: Remedy:

    The cooling system did not power-upafter an ON command (ON commandvia terminal module –A234.1).

    Check the cables.

    Read-out the fault messages from the cooling systemcontrol.

    Cooling system power supply faulted. Check the cooling system.Read-out the fault messages of the cooling systemcontrol.

    Cooling system control faulted(the control is integrated in the coolingsystem).

    Read-out the fault messages of the cooling systemcontrol.

    Cable interrupted, poor contact at theterminal modules -A232, -A234 or inthe cooling system.

    Check the cables and terminal modules according to thecircuit diagram.

    Defective terminal module –A232. The signal level can be read at parameter r417 (bit 0):

    No checkback signal --> 1,

    check parameter P416 (bit 0) as to whether the signal isinverted.

  • 8/18/2019 Simovert Maintanance Manual

    74/152

    5 Fault and alarm messages Edition 07.2001

    Siemens AG 6SE8001-0CJ76

    74   SIMOVERT MV Maintenance Instructions

    No. 066

    Message: Cooling system Fault

    Description: The “FAULT” signal for the water cooling system is present.This fault can only occur for water-cooled drive converters.

    Causes: Remedy:

    The cooling system control hasdetected a fault. The control isintegrated in the cooling system.

    A text display is available in the cooling system controlwhere messages are output. The “fault signal” isgenerated from this control.

    P412 is incorrectly parameterized.

    Defective terminal module –A232.

    The signal level can be read at parameter r417 (bit 1):

    Fault --> 1,Check parameter P416 (bit 1) as to whether the signal isinverted.

  • 8/18/2019 Simovert Maintanance Manual

    75/152

    Edition 07.2001 5 Fault and alarm messages  

    Siemens AG 6SE8001-0CJ76

    SIMOVERT MV Maintenance Instructions   75

    No. 067

    Message: Cooling system is not ready to be powered-up

    Description: The “NOT READY” signal of the water cooling system ispresent. This fault can only occur for water-cooled driveconverters.

    Causes: Remedy:

    The water cooling system is notready.

    A text display is available in the cooling system controlwhere messages are output. The “ready signal” isgenerated from this control.

  • 8/18/2019 Simovert Maintanance Manual

    76/152

    5 Fault and alarm messages Edition 07.2001

    Siemens AG 6SE8001-0CJ76

    76   SIMOVERT MV Maintenance Instructions

    No. 069

    Message: Cooling system ALARM

    Description: The condition of the water cooling system has deteriorated.This alarm only occurs for water-cooled drive converters.

    Causes: Remedy:

    The cooling system control hasdetected a change. The control isintegrated in the cooling system.

    A text display is available in the cooling system controlwhere messages are output. The “alarm signal” isgenerated from this control.

  • 8/18/2019 Simovert Maintanance Manual

    77/152

    Edition 07.2001 5 Fault and alarm messages  

    Siemens AG 6SE8001-0CJ76

    SIMOVERT MV Maintenance Instructions   77

    No. 070

    Message: Drive converter Leak in the cooling circuit

    Description: The leakage water detection of the cooling system hasresponded. This fault can only occur for water-cooled driveconverters.

    Causes: Remedy:

    Leakage water in the cooling system. Identify where the leak is and repair it.

  • 8/18/2019 Simovert Maintanance Manual

    78/152

    5 Fault and alarm messages Edition 07.2001

    Siemens AG 6SE8001-0CJ76

    78   SIMOVERT MV Maintenance Instructions

    No. 074

    Message: Drive converter Air pressure < min

    Description: The differential pressure over the heatsink is less than the setminimum pressure. The differential pressure monitor hasresponded.

    Causes: Remedy:

    Motor circuit-breakers Q150, Q151,Q152, Q153 tripped.

    Check the motor circuit-breaker and its setting.

    Defective fan. Check the fan function and if required, replace the fan.

    Observe the maintenance intervals.Defective differential pressure sensor. Replace the sensor.

    Wiring interrupted. Check the screw terminals.

  • 8/18/2019 Simovert Maintanance Manual

    79/152

  • 8/18/2019 Simovert Maintanance Manual

    80/152

    5 Fault and alarm messages Edition 07.2001

    Siemens AG 6SE8001-0CJ76

    80   SIMOVERT MV Maintenance Instructions

    No. 076

    Message: Drive converter Emergency operation

    Description: At least one motor-protection circuit-breaker of the cooling fanhas failed.

    Causes: Remedy:

    Differential pressure sensor B81 hastripped.

    Check the fan function. Observe the maintenanceintervals.

    Motor circuit-breakers Q150, Q151,Q152, Q153 tripped.

    Check the motor circuit-breaker and their settings.

    P412 is incorrectly parameterized.

    Defective terminal module –A232.

    Check parameter P408 (bit 0) as to whether the signal isinverted.

    The signal level can be read at parameter r417 (bit 0):

    Fault --> 0

  • 8/18/2019 Simovert Maintanance Manual

    81/152

    Edition 07.2001 5 Fault and alarm messages  

    Siemens AG 6SE8001-0CJ76

    SIMOVERT MV Maintenance Instructions   81

    No. 080

    Message: Drive converter Fan operating hours > max

    Description: The permissible fan operating hours status has been reached.We recommend that the fan is replaced.

  • 8/18/2019 Simovert Maintanance Manual

    82/152

    5 Fault and alarm messages Edition 07.2001

    Siemens AG 6SE8001-0CJ76

    82   SIMOVERT MV Maintenance Instructions

    No. 081

    Message: Control cabinet Communications with the terminal strip

    faulted

    Description: The Profibus connection to ET200 is faulted.

    Causes: Remedy:

    Check the Profibus connection (bus cable) from theinterface module (SS52) to the terminal strip -A210(ET200).

    Check the initialization of the interface module (SS52).

  • 8/18/2019 Simovert Maintanance Manual

    83/152

    Edition 07.2001 5 Fault and alarm messages  

    Siemens AG 6SE8001-0CJ76

    SIMOVERT MV Maintenance Instructions   83

    No. 084

    Message: Software version OP7 is not compatible

    Description: The software in the OP7 is not compatible to the software ofmemory card A200-S01-X50 (various versions are mixed).If new software is downloaded into the OP7, this messageappears once, also with the correct software.Remedy in this case: This message deleted by displaying theOP7 software version on the OP7 (menu, start screen ->software version).

  • 8/18/2019 Simovert Maintanance Manual

    84/152

    5 Fault and alarm messages Edition 07.2001

    Siemens AG 6SE8001-0CJ76

    84   SIMOVERT MV Maintenance Instructions

    No. 085

    Message: Control cabinet Communications via Profibus faulted

    Description: Module A200-S07-X01 has detected erroneous data transfer.

    Causes: Remedy:

    All LEDs flash. Data transfer is o.k.

    Red LED dark. Power supply voltage faulted.

    Yellow LED dark. No data transfer.

    Green LED dark. Data is being transferred but no net (useful) dataavailable.

  • 8/18/2019 Simovert Maintanance Manual

    85/152

    Edition 07.2001 5 Fault and alarm messages  

    Siemens AG 6SE8001-0CJ76

    SIMOVERT MV Maintenance Instructions   85

    No. 088

    Message: Control cabinet Communications fault OP7

    Description: Data transfer with the OP7 operator device is faulted.

    Causes: Remedy:

    Defective A200-S06-X3 module. Replace the module.

    Defective cable or poor contact.   Check the cable. Ensure that OP7 and A200-S06-X3module are correctly located.

    Defective OP7. Replace the OP7.

  • 8/18/2019 Simovert Maintanance Manual

    86/152

    5 Fault and alarm messages Edition 07.2001

    Siemens AG 6SE8001-0CJ76

    86   SIMOVERT MV Maintenance Instructions

    No. 089

    Message: Control cabinet Analog input module –A212/1 over-controlled

    or under-controlled

    Description: The main setpoint lies outside the tolerance range.Technical data of the module: Refer to the CommissioningInstructions.

    Causes: Remedy:

    Incorrect parameterization. Check parameter P192.

    The signal which is present is either

    too high or too low - defective signalsource.

    Check the signals, check the signal source.

  • 8/18/2019 Simovert Maintanance Manual

    87/152

    Edition 07.2001 5 Fault and alarm messages  

    Siemens AG 6SE8001-0CJ76

    SIMOVERT MV Maintenance Instructions   87

    No. 090

    Message: Control cabinet Analog input module –A212/2 over-controlled

    or under-controlled

    Description: The supplementary setpoint lies outside the tolerance range.Technical data of the module: Refer to the CommissioningInstructions.

    Causes: Remedy:

    Incorrect parameterization. Check parameter P192.

    The signal which is present is either

    too high or too low - defective signalsource.

    Check the signals, check the signal source.

  • 8/18/2019 Simovert Maintanance Manual

    88/152

    5 Fault and alarm messages Edition 07.2001

    Siemens AG 6SE8001-0CJ76

    88   SIMOVERT MV Maintenance Instructions

    No. 091

    Message: Control cabinet Analog input module –A262/1 over-controlled

    or under-controlled

    Description: The PT100 input (air temperature, power section) lies outsidethe tolerance range.Technical data of the module: Refer to the CommissioningInstructions.

    Causes: Remedy:

    Incorrect parameterization Check parameter P192.

    Defective Pt100. Check PT100. The resistance must be 100 Ohm.

    Loose connection, wire breakage. Check the wiring connections and screw couplings.

  • 8/18/2019 Simovert Maintanance Manual

    89/152

    Edition 07.2001 5 Fault and alarm messages  

    Siemens AG 6SE8001-0CJ76

    SIMOVERT MV Maintenance Instructions   89

    No. 092

    Message: Control cabinet Analog input module –A262/2 over-controlled

    or under-controlled

    Description: The PT100 input (air temperature, control cabinet) lies outsidethe tolerance range.Technical data of the module: Refer to the CommissioningInstructions.

    Causes: Remedy:

    Incorrect parameterization Check parameter P192.

    Defective Pt100. Check PT100. The resistance must be 100 Ohm.

    Loose connection, wire breakage. Check the wiring connections and screw couplings.

  • 8/18/2019 Simovert Maintanance Manual

    90/152

    5 Fault and alarm messages Edition 07.2001

    Siemens AG 6SE8001-0CJ76

    90   SIMOVERT MV Maintenance Instructions

    No. 097

    Message: Motor I2t Load > limit 1

    Description: The motor temperature is higher than the alarm limit value. The

    motor temperature is estimated with an i2

    t calculation. Thedrive converter is powered-down (tripped) if the temperaturecontinues to increase.

    Causes: Remedy:

    Motor load too high. Reduce the load.

    Motor cooling faulted. Check the motor auxiliaries.

    Incorrect parameterization. Check parameters P640 – P643 (H640 – H643).

  • 8/18/2019 Simovert Maintanance Manual

    91/152

    Edition 07.2001 5 Fault and alarm messages  

    Siemens AG 6SE8001-0CJ76

    SIMOVERT MV Maintenance Instructions   91

    No. 098

    Message: Motor I2t Load > limit 2

    Description: The motor temperature is higher than the alarm limit value. The

    motor temperature is estimated with an i2

    t calculation. Thedrive converter is powered-down (tripped).

    Causes: Remedy:

    Motor load too high. Reduce the load.

    Motor cooling faulted. Check the motor auxiliaries.

    Incorrect parameterization. Check parameters P640 – P643 (H640 – H643).

  • 8/18/2019 Simovert Maintanance Manual

    92/152

    5 Fault and alarm messages Edition 07.2001

    Siemens AG 6SE8001-0CJ76

    92   SIMOVERT MV Maintenance Instructions

    No. 101

    Message: Motor Inadmissible operation at the motoring torque limit

    Description: The speed controller output is at the motoring torque limit forthe time entered in P337.

    Causes: Remedy:

    P337 is set too low. Adapt P337 to the actual load situation.

    Load too high, motor stalled. Reduce the load or remove the blockage.

  • 8/18/2019 Simovert Maintanance Manual

    93/152

    Edition 07.2001 5 Fault and alarm messages  

    Siemens AG 6SE8001-0CJ76

    SIMOVERT MV Maintenance Instructions   93

    No. 102

    Message: Motor Motor blocked

    Description: The limit value of the speed setpoint-actual value deviation, inP326, has been exceeded.

    Causes: Remedy:

    P326, P327, P328 incorrectly set. Set P326 using the actual following error, if requiredincrease the ramp-up time.

    Load too high, motor stalled. Reduce the load or remove the blockage.

    Ramp-up time too low, the motor hasstalled.

    Increase the run-up time (acceleration time).

  • 8/18/2019 Simovert Maintanance Manual

    94/152

  • 8/18/2019 Simovert Maintanance Manual

    95/152

    Edition 07.2001 5 Fault and alarm messages  

    Siemens AG 6SE8001-0CJ76

    SIMOVERT MV Maintenance Instructions   95

    No. 113

    Message: External auxiliaries No checkback signal

    Description: The “External auxiliaries on” checkback signal is eithermissing or is not detected.

    Causes: Remedy:

    The external auxiliaries have notpowered-up after the ON command(ON command via terminal module – A246.1).

    Check the cables.

    The signal level can be read at parameter d924 (bit 0):

    Check parameter H924 (bit 0) as to whether the signal isinverted.

    Power supply of the externalauxiliaries faulted.

    Check the auxiliaries.

    Checkback signal cable interrupted.

    Poor contact at the terminal modules –A242, -A246 or in the externalauxiliaries.

    Check the cables and terminal modules according to thecircuit diagram.

    P412 is incorrectly parameterized.

    Defective terminal module –A242.

    The signal level can be read at parameter d922 (bit 0):

    No checkback signal --> 1,

    check parameter H921 (bit 0) as to whether the signal isinverted.

  • 8/18/2019 Simovert Maintanance Manual

    96/152

  • 8/18/2019 Simovert Maintanance Manual

    97/152

  • 8/18/2019 Simovert Maintanance Manual

    98/152

    5 Fault and alarm messages Edition 07.2001

    Siemens AG 6SE8001-0CJ76

    98   SIMOVERT MV Maintenance Instructions

    No. 116

    Message: External auxiliaries Fault 2

    Description: The “Fault signal 2” message of the auxiliaries is present.

    Causes: Remedy:

    Auxiliaries faulted. Check the auxiliaries.

    P412 is incorrectly parameterized.

    Defective terminal module –A244.

    The signal level can be read at parameter d922 (bit 4):

    Fault signal is present --> 1,

    Check parameter H921 (bit 4) as to whether the signal isinverted.

  • 8/18/2019 Simovert Maintanance Manual

    99/152

  • 8/18/2019 Simovert Maintanance Manual

    100/152

    5 Fault and alarm messages Edition 07.2001

    Siemens AG 6SE8001-0CJ76

    100   SIMOVERT MV Maintenance Instructions

    No. 118

    Message: Motor Alarm 2

    Description: The motor monitoring has detected a deterioration of the motorcondition or its auxiliaries.

    Causes: Remedy:

    Power supply of the externalauxiliaries faulted.

    Check the auxiliaries.

    Checkback signal cable interrupted.

    Poor contact at the terminal modules

     –A243 or in the external auxiliaries.

    Check the cables and terminal modules according to thecircuit diagram.

    P412 is incorrectly parameterized.

    Defective terminal module –A243.

    The signal level can be read at parameter d921 (bit 2):

    Alarm is present --> 1,

    Check parameter H921 (bit 2) as to whether the signal isinverted.

  • 8/18/2019 Simovert Maintanance Manual

    101/152

    Edition 07.2001 5 Fault and alarm messages  

    Siemens AG 6SE8001-0CJ76

    SIMOVERT MV Maintenance Instructions   101

    No. 119

    Message: Motor Fault 1

    Description: The motor monitoring has detec