Command Type NumbersA
12.2004 Edition
Technology Package CamAlarms
Diagnostics Manual
SIMOTION
6AU1900-1AD32-0BA0
-2� Siemens AG, 2004. All rights reserved
Technology Package CamAlarms, 12.2004 Edition
!Danger
indicates that death or serious injury will result if proper precautions are not taken.
!Warning
indicates that death or serious injury may result if proper precautions are not taken.
!Caution
with a safety alert symbol, indicates that minor injury may result if proper precautions are not taken.
Caution
without a safety alert symbol, indicates that property damage may result if proper precautions are nottaken.
Notice
indicates that an unintended result or situation can occur if the corresponding information is not taken intoaccount.
If more than one level of danger exists, the warning notice for the highest level of danger is used. A warn-ing notice accompanied by a safety alert symbol indicating a risk of bodily injury can also indicate a risk ofproperty damage.
Qualified personnelThe device/system may only be set up and operated in conjunction with this documentation. Only quali-fied personnel should be allowed to commission and operate the device/system. Qualified persons aredefined as persons who are authorized to commission, ground, and tag equipment, systems, and circuitsin accordance with established safety standards.
Correct usageNote the following:
!Warning
The device may only be used for the applications described in the catalog or the technical description,and only in combination with the equipment, components, and devices of other manufacturers that havebeen approved or recommended by Siemens.
This product can only function correctly and safely if it is transported, stored, set up, and installedcorrectly, and operated and maintained as recommended.
TrademarksAll names identified by � are registered trademarks of Siemens AG. Other names in this publication maybe trademarks whose use by third parties for their own purposes could violate the rights of the owner.
Safety notesThis manual contains notices that you must observe in order to ensure your personal safety, as well as toprevent damage to property. The notices referring to your personal safety are highlighted by a safety alertsymbol; notices referring to property damage alone have no safety alert symbol. These notices are shownbelow in order of decreasing danger:
We have checked the contents of this manual for agreement with thehardware and software described. Since discrepancies cannot be precludedentirely, we cannot guarantee full agreement. However, the informationcontained in this document is reviewed regularly and any necessarycorrections included in subsequent editions.
Disclaimer of LiabilityCopyright Siemens AG, 2004. All rights reserved
The reproduction, transmission, or use of this document or its contents is notpermitted without express written authority. Offenders will be liable fordamages. All rights, including rights created by patent grant or registration ofa utility model or design, are reserved.
Siemens AGAutomation & DrivesMotion Control SystemsP.O. Box 3180, D–91050 ErlangenFederal Republic of Germany
� Siemens AG, 2004.Subject to change without prior notice.
Siemens Aktiengesellschaft Technology Package Cam Alarms
Preface-3� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
Preface
This document is part of the SIMOTION Diagnostics Documentation Packagewith
Order no.: 6AU1900-1AD32-0BA0 12.2004 Edition
Information modules in this documentation
This diagnostics manual consists of 2 parts and provides an overview of thealarms of the technology packages Cam and Cam_ext. It serves as a supple-ment and reference work for the SIMOTION functional descriptions.
The Cam technology package is part of the Cam_ext technology package.
The alarm numbers are assigned to the respective technology object and listed innumerical order below.
The Cam technology object contains the following technology objects:
� Drive axis (driveAxis)
� Output cam (camType)
� Cam track (camTrackType)
� Measuring input (measuringInputType)
� External encoder (externalEncoderType)
� Positioning axis (posAxis)
� Following axis (followingAxis)
� Following object (followingObjectType)
� Cam
The Cam_ext technology object contains the following technology objects:
� Addition object (AdditionObjectType)
� Fixed gear (FixedGearType)
� Formula object (FormulaObjectType)
� Controller object (ControllerObjectType)
� Sensor (SensorType)
The command type numbers of the individual system functions are listed in Ap-pendix A.
Preface
Preface-4� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
Scope
This reference list is valid for SIMOTION Kernel Version 3.2.
Local response
With the settable local response, the user defines how the technology object is torespond in the event of an alarm and how further commands for the technologyobject are to be processed.
The programmable local responses can be parameterized by the user for eachalarm. Local responses are described at the beginning of each chapter on the re-spective technology object and listed in ascending priority.
Only one response can be in progress at any given time. This is the response withthe highest priority of all the alarms pending at that particular point in time. When aresponse occurs, the command decoder is stopped. Any programmed commandissued subsequently is rejected.
Command processing can be continued as soon as the alarm has been acknowl-edged. If an alarm requires a Power ON due to its global error response, it cannotbe acknowledged. Please refer to the functional description for Motion Control Ba-sic Functions.
References for technology objects
The functions for driveAxis and posAxis and for externalEncoder are describedin the functional description Motion Control Technology Object Axis Electric/hydraulic External Encoders.
The configuration and functions of the camType, camTrackType and measuringInput technology objects are described in the functional description Motion Control Technology Objects, Output Cam and Measuring Input.
The configuration and functions of the followingObjectType and cam technologyobjects are described in the functional description Motion Control, SynchronousOperation.
The configuration and functions of the FixedGearType, FormulaObjectType,ControllerObjectType, SensorType and AdditionObjectType technology ob-jects are described in the functional description Motion Control Advanced Technol-ogy Objects.
Preface
Preface-5� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
SIMOTION documentation
An overview of the SIMOTION documentation is provided in a separate list of ref-erences.
The list of references list is supplied on the “SIMOTION SCOUT” CD. In printed documentation, the list of references is supplied with every documenta-tion package.
The Bibliography can be ordered separately using the following order number:
Order no.: 6AU1900-1AA32-0BA0 12.2004 Edition
SIMOTION documentation consists of 10 documentation packages contain-ing approximately 50 SIMOTION documents and documents for other products(e.g., SINAMICS).
The following documentation packages are available for SIMOTION V3.2:
� How to Use the SIMOTION Engineering System
� SIMOTION System and Function Descriptions
� SIMOTION Diagnostics
� SIMOTION Programming
� SIMOTION Programming – Reference Lists
� SIMOTION C230
� SIMOTION P350
� SIMOTION D4xx
� SIMOTION Supplementary Documentation
� SIMOTION Function Library
Hotline and Internet addresses
If you have any questions, please contact our hotline (worldwide):
A&D Technical Supports Phone: +49 (180) 50 50 222Fax: +49 (180) 50 50 223E-mail: [email protected]
If you have any questions, suggestions, or corrections regarding the documenta-tion, please send them to the following fax number or e-mail address:
Fax: +49 (9131) 98 2176E-mail: [email protected]
Preface
Preface-6� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
Siemens Internet address
The latest information about SIMOTION products can be found on the Internet un-der:
� General informationhttp://www.siemens.de/simotion (German)http://www.siemens.com/simotion (international)
� Products supporthttp://www4.ad.siemens.de/view/cs/de/10805436
Additional support
We offer courses to help you get started with SIMOTION.
Please contact your regional training center or our main training center at D-90027Nuremberg, phone +49 (911) 895 3202.
Contents-7� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
Contents
Technology Package Cam Part I-35. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Technology Package Cam_ext Part II-571. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1 driveAxis 1-37
Possible local responses 1-37. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
20001 Internal error (Parameter1: /1/%d, Parameter2: /2/%d, Parameter3:/3/%d, Parameter4: /4/%d) 1-38. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
20002 Insufficient memory (Parameter1: /1/%d, Parameter2: /2/%d,Parameter3: /3/%d, Parameter4: /4/%d) 1-39. . . . . . . . . . . . . . . . . . . . . . . . . . . .
20003 No object configuration (Parameter1: /1/%d, Parameter2: /2/%d,Parameter3: /3/%d, Parameter4: /4/%d) 1-40. . . . . . . . . . . . . . . . . . . . . . . . . . . .
20004 At the logical address: /1/%d (bit number, if required: /2/%d) a driver(type: /3/%d) could be requested (error number: /4/%d) 1-41. . . . . . . . . . . . . . .
20005 Device type: /3/%d, log. address: /1/%d faulty. (Bit: /2/%d,reason: 0x/4/%Xh) 1-42. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
20006 Error in configuration(category: /1/%d, error number: /2/%d) 1-45. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
20007 Interconnection error (category: /1/%d, context: /2/%d,context parameter1: /3/%d, context parameter2: /4/%d) 1-52. . . . . . . . . . . . . .
20008 Cannot assign USER_DEFAULT to system variables 1-54. . . . . . . . . . . . . . . . .
20009 The permissible deviation between encoders (/1/%d) and (/2/%d)has been exceeded 1-54. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
20010 A restart is necessary to activate the configuration data 1-55. . . . . . . . . . . . . .
20011 Error when activating the configuration (category: /1/%d,error number: /2/%d) 1-56. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
20012 Restart not executed (reason: /1/%d) 1-63. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
20014 At the logical address: /1/%d (optional log. address:/2/%d and bit no.: /3/%d of the enable output), a driver(type: /4/%d) could not be requested 1-64. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30001 Illegal parameter (parameter index according to standard sequencein the system functions: /1/%d, command type: /4/%X) 1-65. . . . . . . . . . . . . . .
30002 Command aborted (reason: /1/%d, command type: /4/%X) 1-66. . . . . . . . . . . .
30003 Command aborted due to full command buffer(command type: /4/%X) 1-68. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30004 Unknown command (command type: /4/%X) 1-69. . . . . . . . . . . . . . . . . . . . . . . .
30005 Ambiguous commandId (number of commands with specified ID:/1/%d, command type: /4/%X) 1-70. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Contents
Contents-8� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
30006 Cannot execute command due to current object state(command type: /4/%X) 1-71. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30007 The error cannot be reset due to its configuration 1-72. . . . . . . . . . . . . . . . . . . .
30008 A connection to a technology object required for this operationdoes not exist (command type: /4/%X) 1-73. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30009 Command rejected due to suspension of command decodingon addressed technology object (command type: /4/%X) 1-74. . . . . . . . . . . . . .
30010 Command not available (command type: /4/%X) 1-75. . . . . . . . . . . . . . . . . . . . .
30011 Parameter unavailable (parameter index according tostandard sequence in the system functions: /1/%d,command type: /4/%X) 1-76. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30012 Command cannot be started synchronously (command type: /4/%X) 1-77. . .
30013 Synchronous start of the command using IMMEDIATELYmergeMode (command type: /4/%X) 1-78. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30014 Coordinate system not offset due to the internal traversingrange limit being exceeded (Parameter1: /1/% /1/%d,command type: /2/%X) 1-79. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30015 A technology required for this command was not configured(technology: /1/%d, command type: /4/%X) 1-80. . . . . . . . . . . . . . . . . . . . . . . . .
40001 Illegal state change on axis 1-81. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
40002 Programmed velocity is limited 1-82. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
40003 Programmed acceleration (type: /1/%d) is limited 1-83. . . . . . . . . . . . . . . . . . . .
40004 Programmed jerk (type: /1/%d) is limited 1-84. . . . . . . . . . . . . . . . . . . . . . . . . . . .
40005 Enable signal(s) missing (Parameter1: /1/%X) and/orincorrect mode (Parameter2: /2/%d) 1-85. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
40006 Programmed velocity is zero 1-86. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
40007 Programmed acceleration (type: /1/%d) is zero 1-86. . . . . . . . . . . . . . . . . . . . . .
40008 Programmed jerk (type: /1/%d) is zero 1-87. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
40009 Velocity limit is zero 1-87. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
40010 Acceleration limit (type: /1/%d) is zero 1-88. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
40011 Programmed jerk limit (type: /1/%d) is zero 1-88. . . . . . . . . . . . . . . . . . . . . . . . .
40012 Dynamic restrictions (type: /1/%d) violated 1-89. . . . . . . . . . . . . . . . . . . . . . . . . .
40013 Programmed stop time restricted by acceleration limits 1-90. . . . . . . . . . . . . . .
40014 Command not possible on virtual axis (command type: /4/%X) 1-91. . . . . . . . .
40015 Error in accessing specified cam 1-91. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
40016 The specified cam has not been interpolated 1-92. . . . . . . . . . . . . . . . . . . . . . . .
40017 Cam start point outside definition range 1-92. . . . . . . . . . . . . . . . . . . . . . . . . . . .
40018 Dynamic response of motion profiles (type: /1/%d)violated (reason: /2/%d) 1-93. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
40019 Error while accessing the motion interface 1-94. . . . . . . . . . . . . . . . . . . . . . . . . .
40020 Dynamic response of the setpoints on the motion interface(type: /1/%d) violated (reason: /2/%d) 1-95. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Contents
Contents-9� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
40021 StopEmergency command abort due to a pendingstop response of the same or higher priority 1-96. . . . . . . . . . . . . . . . . . . . . . . . . .
40022 Programmed pressure limiting is limited 1-97. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
40023 Programmed increase in pressure limiting limited 1-98. . . . . . . . . . . . . . . . . . . . .
40024 Programmed increase in pressure limiting is zero 1-98. . . . . . . . . . . . . . . . . . . . .
40025 Maximum increase in pressure limiting is zero 1-99. . . . . . . . . . . . . . . . . . . . . . . .
40026 Dynamic response of pressure/pressure limiting profiles(type: /1/%d) violated (reason: /2/%d) 1-100. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
50001 Drive failure 1-101. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
50002 Limiting frequency of measuring system exceeded 1-101. . . . . . . . . . . . . . . . . . .
50003 Speed acceleration setpoint limitation active 1-102. . . . . . . . . . . . . . . . . . . . . . . .
50005 Speed setpoint monitoring active (Parameter1: /1/%d) 1-103. . . . . . . . . . . . . . . .
50006 Zero mark monitoring 1-104. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
50007 Hardware limit switch (Parameter1: /1/%d, Parameter2: /2/%d) 1-105. . . . . . . .
50008 Timeout waiting for standstill signal 1-106. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
50009 Limit switch active: (Parameter1: /1/%d) only one traversingdirection possible 1-106. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
50010 Error while reading or writing data set (category: /1/%d,error number: /2/%d) 1-107. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
50011 Limit range of the incremental actual value exceeded(Parameter1: /1/%d) 1-115. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
50012 Drive does not support the selected function (Parameter1: /1/%d) 1-116. . . . . .
50013 Overshoot/undershoot of permissible range limits(logical address: /1/%d, reason: /2/%d) 1-117. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
50014 Permissible system deviation of pressure controller exceeded 1-118. . . . . . . . .
50015 Level overflow of IPO not detected 1-118. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
50016 Backstop limitation active 1-119. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
50017 Manipulated variable monitoring active at Q/F output(Parameter1: /1/%d) 1-120. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
50101 Reference model monitoring window exceeded 1-121. . . . . . . . . . . . . . . . . . . . . .
50109 Starting force window monitoring error 1-121. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
50110 Full-scale force monitoring error 1-122. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
50111 Pressure controller is operating at the limit 1-122. . . . . . . . . . . . . . . . . . . . . . . . . .
2 outputCamType 2-123. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Possible local responses 2-123. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
20001 Internal error (Parameter1: /1/%d, Parameter2: /2/%d,Parameter3: /3/%d, Parameter4: /4/%d) 2-123. . . . . . . . . . . . . . . . . . . . . . . . . . . .
20002 Insufficient memory (Parameter1: /1/%d, Parameter2: /2/%d,Parameter3: /3/%d, Parameter4: /4/%d) 2-124. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Contents
Contents-10� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
20003 No object configuration (Parameter1: /1/%d, Parameter2: /2/%d,Parameter3: /3/%d, Parameter4: /4/%d) 2-125. . . . . . . . . . . . . . . . . . . . . . . . . . . .
20004 At the logical address: /1/%d (bit number, if required: /2/%d) a driver(type: /3/%d) could be requested (error number: /4/%d) 2-126. . . . . . . . . . . . . . .
20005 Device type: /3/%d, log. address: /1/%d faulty. (Bit: /2/%d,reason: 0x/4/%Xh) 2-127. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
20006 Error in configuration (category: /1/%d, error number: /2/%d) 2-130. . . . . . . . . .
20007 Interconnection error (category: /1/%d, context: /2/%d,context parameter1: /3/%d, context parameter2: /4/%d) 2-131. . . . . . . . . . . . . .
20008 Cannot assign USER_DEFAULT to system variables 2-133. . . . . . . . . . . . . . . . .
20009 Reserved error 2-133. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
20010 A restart is necessary to activate the configuration data 2-134. . . . . . . . . . . . . .
20011 Error when activating the configuration (category: /1/%d,error number: /2/%d) 2-135. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
20012 Restart not executed (reason: /1/%d) 2-136. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
20014 At the logical address: /1/%d (optional log. address:/2/%d and bit no.: /3/%d of the enable output),a driver (type: /4/%d) could not be requested 2-137. . . . . . . . . . . . . . . . . . . . . . . .
30001 Illegal parameter (parameter index according to standard sequencein the system functions: /1/%d, command type: /4/%X) 2-138. . . . . . . . . . . . . . .
30002 Command aborted (reason: /1/%d, command type: /4/%X) 2-139. . . . . . . . . . . .
30003 Command aborted due to full command buffer(command type: /4/%X) 2-140. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30004 Unknown command (command type: /4/%X) 2-141. . . . . . . . . . . . . . . . . . . . . . . .
30005 Ambiguous commandId (number of commands with specified ID:/1/%d, command type: /4/%X) 2-142. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30006 Cannot execute command due to current object state(command type: /4/%X) 2-143. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30007 The error cannot be reset due to its configuration 2-143. . . . . . . . . . . . . . . . . . . .
30008 A connection to a technology object required for this operationdoes not exist (command type: /4/%X) 2-144. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30009 Command rejected due to suspension of command decodingon addressed technology object (command type: /4/%X) 2-145. . . . . . . . . . . . . .
30010 Command not available (command type: /4/%X) 2-145. . . . . . . . . . . . . . . . . . . . .
30011 Parameter unavailable (parameter index according tostandard sequence in the system functions: /1/%d,command type: /4/%X) 2-146. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30012 Command cannot be started synchronously(command type: /4/%X) 2-147. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30013 Synchronous start of the command using IMMEDIATELYmergeMode (command type: /4/%X) 2-148. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30015 A technology required for this command was not configured(technology: /1/%d, command type: /4/%X) 2-149. . . . . . . . . . . . . . . . . . . . . . . . .
Contents
Contents-11� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
40001 Error in output cam limitation (output cam position: /1/%d) 2-150. . . . . . . . . . . .
40003 Illegal range specification in parameters (parameter: /1/%d) 2-151. . . . . . . . . . .
3 camTrackType 3-153. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Possible local responses 3-153. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
20001 Internal error (Parameter1: /1/%d, Parameter2: /2/%d,Parameter3: /3/%d, Parameter4: /4/%d) 3-153. . . . . . . . . . . . . . . . . . . . . . . . . . . .
20002 Insufficient memory (Parameter1: /1/%d, Parameter2: /2/%d,Parameter3: /3/%d, Parameter4: /4/%d) 3-154. . . . . . . . . . . . . . . . . . . . . . . . . . . .
20003 No object configuration (Parameter1: /1/%d, Parameter2: /2/%d,Parameter3: /3/%d, Parameter4: /4/%d) 3-155. . . . . . . . . . . . . . . . . . . . . . . . . . . .
20004 At the logical address: /1/%d (bit number, if required: /2/%d) a driver(type: /3/%d) could be requested (error number: /4/%d) 3-156. . . . . . . . . . . . . . .
20005 Device type: /3/%d, log. address: /1/%d faulty. (Bit: /2/%d,reason: 0x/4/%Xh) 3-157. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
20006 Error in configuration (category: /1/%d, error number: /2/%d) 3-160. . . . . . . . . .
20007 Interconnection error (category: /1/%d, context: /2/%d,context parameter1: /3/%d, context parameter2: /4/%d) 3-161. . . . . . . . . . . . . .
20008 Cannot assign USER_DEFAULT to system variables 3-163. . . . . . . . . . . . . . . . .
20009 Reserved error 3-163. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
20010 A restart is necessary to activate the configuration data 3-164. . . . . . . . . . . . . .
20011 Error when activating the configuration (category: /1/%d,error number: /2/%d) 3-165. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
20012 Restart not executed (reason: /1/%d) 3-166. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
20014 At the logical address: /1/%d (optional log. address: /2/%d andbit no.: /3/%d of the enable output), a driver (type: /4/%d)could not be requested 3-167. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30001 Illegal parameter (parameter index according to standard sequencein the system functions: /1/%d, command type: /4/%X) 3-168. . . . . . . . . . . . . . .
30002 Command aborted (reason: /1/%d, command type: /4/%X) 3-169. . . . . . . . . . . .
30003 Command aborted due to full command buffer(command type: /4/%X) 3-170. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30004 Unknown command (command type: /4/%X) 3-171. . . . . . . . . . . . . . . . . . . . . . . .
30005 Ambiguous commandId (number of commands with specified ID:/1/%d, command type: /4/%X) 3-172. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30006 Cannot execute command due to current object state(command type: /4/%X) 3-173. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30007 The error cannot be reset due to its configuration 3-173. . . . . . . . . . . . . . . . . . . .
30008 A connection to a technology object required for this operationdoes not exist (command type: /4/%X) 3-174. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Contents
Contents-12� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
30009 Command rejected due to suspension of command decodingon addressed technology object (command type: /4/%X) 3-175. . . . . . . . . . . . . .
30010 Command not available (command type: /4/%X) 3-175. . . . . . . . . . . . . . . . . . . . .
30011 Parameter unavailable (parameter index according tostandard sequence in the system functions: /1/%d,command type: /4/%X) 3-176. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30012 Command cannot be started synchronously(command type: /4/%X) 3-177. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30013 Synchronous start of the command using IMMEDIATELYmergeMode (command type: /4/%X) 3-178. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30015 A technology required for this command was not configured(technology: /1/%d, command type: /4/%X) 3-179. . . . . . . . . . . . . . . . . . . . . . . . .
40003 Illegal range specification in parameters (parameter: /1/%d) 3-180. . . . . . . . . . .
4 measuringInputType 4-181. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Possible local responses 4-181. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
20001 Internal error (Parameter1: /1/%d, Parameter2: /2/%d,Parameter3: /3/%d, Parameter4: /4/%d) 4-181. . . . . . . . . . . . . . . . . . . . . . . . . . . .
20002 Insufficient memory (Parameter1: /1/%d, Parameter2: /2/%d,Parameter3: /3/%d, Parameter4: /4/%d) 4-182. . . . . . . . . . . . . . . . . . . . . . . . . . . .
20003 No object configuration (Parameter1: /1/%d, Parameter2: /2/%d,Parameter3: /3/%d, Parameter4: /4/%d) 4-183. . . . . . . . . . . . . . . . . . . . . . . . . . . .
20004 At the logical address: /1/%d (bit number, if required: /2/%d)a driver (type: /3/%d) could be requested (error number: /4/%d) 4-184. . . . . . .
20005 Device type: /3/%d, log. address: /1/%d faulty. (Bit: /2/%d,reason: 0x/4/%Xh) 4-185. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
20006 Error in configuration (category: /1/%d, error number: /2/%d) 4-188. . . . . . . . . .
20007 Interconnection error (category: /1/%d, context: /2/%d,context parameter1: /3/%d, context parameter2: /4/%d) 4-189. . . . . . . . . . . . . .
20008 Cannot assign USER_DEFAULT to system variables 4-191. . . . . . . . . . . . . . . . .
20009 Reserved error 4-191. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
20010 A restart is necessary to activate the configuration data 4-192. . . . . . . . . . . . . .
20011 Error when activating the configuration (category: /1/%d,error number: /2/%d) 4-193. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
20012 Restart not executed (reason: /1/%d) 4-194. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
20014 At the logical address: /1/%d (optional log. address: /2/%dand bit no.: /3/%d of the enable output), a driver (type: /4/%d)could not be requested 4-195. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30001 Illegal parameter (parameter index according to standardsequence in the system functions: /1/%d, command type: /4/%X) 4-196. . . . . .
30002 Command aborted (reason: /1/%d, command type: /4/%X) 4-197. . . . . . . . . . . .
30003 Command aborted due to full command buffer(command type: /4/%X) 4-198. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30004 Unknown command (command type: /4/%X) 4-199. . . . . . . . . . . . . . . . . . . . . . . .
Contents
Contents-13� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
30005 Ambiguous commandId (number of commands with specified ID:/1/%d, command type: /4/%X) 4-200. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30006 Cannot execute command due to current object state(command type: /4/%X) 4-201. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30007 The error cannot be reset due to its configuration 4-201. . . . . . . . . . . . . . . . . . . .
30008 A connection to a technology object required for this operationdoes not exist (command type: /4/%X) 4-202. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30009 Command rejected due to suspension of command decodingon addressed technology object (command type: /4/%X) 4-203. . . . . . . . . . . . . .
30010 Command not available (command type: /4/%X) 4-203. . . . . . . . . . . . . . . . . . . . .
30011 Parameter unavailable (parameter index according tostandard sequence in the system functions: /1/%d,command type: /4/%X) 4-204. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30012 Command cannot be started synchronously(command type: /4/%X) 4-205. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30013 Synchronous start of the command using IMMEDIATELYmergeMode (command type: /4/%X) 4-206. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30015 A technology required for this command was not configured(technology: /1/%d, command type: /4/%X) 4-207. . . . . . . . . . . . . . . . . . . . . . . . .
40001 Measurement not possible on virtual axis 4-207. . . . . . . . . . . . . . . . . . . . . . . . . . .
40002 Measurement task not possible during homing of assigned axis 4-208. . . . . . . .
40003 Measuring input not switched within validity range ofmeasurement task 4-208. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
40004 Validity range of measurement task not recognized 4-209. . . . . . . . . . . . . . . . . .
40005 Simultaneous access of several measuring inputs toone encoder is not possible 4-209. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
40006 Configuration of measurement inputs in an externaldevice not correct 4-210. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
40007 Measurement task was aborted by external device 4-210. . . . . . . . . . . . . . . . . . .
40008 Measurement task has been aborted due to a drive or encoder error 4-211. . .
5 externalEncoderType 5-213. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Possible local responses 5-213. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
20001 Internal error (Parameter1: /1/%d, Parameter2: /2/%d,Parameter3: /3/%d, Parameter4: /4/%d) 5-214. . . . . . . . . . . . . . . . . . . . . . . . . . . .
20002 Insufficient memory (Parameter1: /1/%d, Parameter2: /2/%d,Parameter3: /3/%d, Parameter4: /4/%d) 5-215. . . . . . . . . . . . . . . . . . . . . . . . . . . .
20003 No object configuration (Parameter1: /1/%d, Parameter2: /2/%d,Parameter3: /3/%d, Parameter4: /4/%d) 5-216. . . . . . . . . . . . . . . . . . . . . . . . . . . .
20004 At the logical address: /1/%d (bit number, if required: /2/%d)a driver (type: /3/%d) could be requested (error number: /4/%d) 5-217. . . . . . .
20005 Device type: /3/%d, log. address: /1/%d faulty. (Bit: /2/%d,reason: 0x/4/%Xh) 5-218. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Contents
Contents-14� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
20006 Error in configuration (category: /1/%d, error number: /2/%d) 5-221. . . . . . . . . .
20007 Interconnection error (category: /1/%d, context: /2/%d,context parameter1: /3/%d, context parameter2: /4/%d) 5-228. . . . . . . . . . . . . .
20008 Cannot assign USER_DEFAULT to system variables 5-230. . . . . . . . . . . . . . . . .
20009 Reserved error 5-230. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
20010 A restart is necessary to activate the configuration data 5-231. . . . . . . . . . . . . .
20011 Error when activating the configuration (category: /1/%d,error number: /2/%d) 5-232. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
20012 Restart not executed (reason: /1/%d) 5-239. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
20014 At the logical address: /1/%d (optional log. address: /2/%d and bit no.:/3/%d of the enable output), a driver (type: /4/%d)could not be requested 5-240. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30001 Illegal parameter (parameter index according to standardsequence in the system functions: /1/%d, command type: /4/%X) 5-241. . . . . .
30002 Command aborted (reason: /1/%d, command type: /4/%X) 5-242. . . . . . . . . . . .
30003 Command aborted due to full command buffer(command type: /4/%X) 5-243. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30004 Unknown command (command type: /4/%X) 5-244. . . . . . . . . . . . . . . . . . . . . . . .
30005 Ambiguous commandId (number of commands with specified ID:/1/%d, command type: /4/%X) 5-245. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30006 Cannot execute command due to current object state(command type: /4/%X) 5-246. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30007 The error cannot be reset due to its configuration 5-246. . . . . . . . . . . . . . . . . . . .
30008 A connection to a technology object required for thisoperation does not exist (command type: /4/%X) 5-247. . . . . . . . . . . . . . . . . . . .
30009 Command rejected due to suspension of command decodingon addressed technology object (command type: /4/%X) 5-248. . . . . . . . . . . . . .
30010 Command not available (command type: /4/%X) 5-249. . . . . . . . . . . . . . . . . . . . .
30011 Parameter unavailable (parameter index according tostandard sequence in the system functions: /1/%d,command type: /4/%X) 5-250. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30012 Command cannot be started synchronously(command type: /4/%X) 5-251. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30013 Synchronous start of the command using IMMEDIATELYmergeMode (command type: /4/%X) 5-252. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30014 Coordinate system not offset due to the internal traversing rangelimit being exceeded (Parameter1: /1/% /1/%d,command type: /2/%X) 5-253. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30015 A technology required for this command was not configured(technology: /1/%d, command type: /4/%X) 5-254. . . . . . . . . . . . . . . . . . . . . . . . .
40005 Enable signal(s) missing (Parameter1: /1/%X) and/orincorrect mode (Parameter2: /2/%d) 5-255. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
40102 Encoder zero mark not found during homing 5-256. . . . . . . . . . . . . . . . . . . . . . . .
Contents
Contents-15� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
40103 Error in homing configuration data (Parameter1: /1/%d) 5-257. . . . . . . . . . . . . . .
40110 Error triggered on slave during synchronous operation(error number: /1/%d) 5-258. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
40124 Offset cannot be compensated. 5-258. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
40125 Setpoint output delay deactivated in the master 5-259. . . . . . . . . . . . . . . . . . . . .
40301 Connection with slave failed (assignment: /1/%d) 5-260. . . . . . . . . . . . . . . . . . . .
40302 Sign-of-life monitoring for the slave in distributed synchronous operation is deactivated 5-261. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
40303 Local and slave interpolation cycle clock are different 5-261. . . . . . . . . . . . . . . . .
40304 Offset cannot be determined 5-262. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
50001 Drive failure 5-262. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
50002 Limiting frequency of measuring system exceeded 5-263. . . . . . . . . . . . . . . . . . .
50003 Speed acceleration setpoint limitation active 5-263. . . . . . . . . . . . . . . . . . . . . . . .
50005 Speed setpoint monitoring active (Parameter1: /1/%d) 5-264. . . . . . . . . . . . . . . .
50006 Zero mark monitoring 5-264. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
50007 Hardware limit switch (Parameter1: /1/%d, Parameter2: /2/%d) 5-265. . . . . . . .
50008 Timeout waiting for standstill signal 5-265. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
50009 Limit switch active: (Parameter1: /1/%d) only one traversingdirection possible 5-266. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
50010 Error while reading or writing data set (category: /1/%d,error number: /2/%d) 5-267. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
50011 Limit range of the incremental actual value exceeded(Parameter1: /1/%d) 5-274. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
50012 Drive does not support the selected function (Parameter1: /1/%d) 5-274. . . . . .
50013 Overshoot/undershoot of permissible range limits(logical address: /1/%d, reason: /2/%d) 5-275. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
50014 Permissible system deviation of pressure controller exceeded 5-275. . . . . . . . .
50015 Level overflow of IPO not detected 5-276. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
50016 Backstop limitation active 5-276. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
50017 Manipulated variable monitoring active at Q/F output(Parameter1: /1/%d) 5-277. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
50101 Reference model monitoring window exceeded 5-277. . . . . . . . . . . . . . . . . . . . . .
50102 Dynamic following error monitoring window exceeded 5-278. . . . . . . . . . . . . . . .
50103 Warning limits of dynamic following error monitoring reached 5-278. . . . . . . . . .
50106 Positioning monitoring error 5-279. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
50107 Standstill monitoring error 5-279. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
50108 Clamping monitoring error 5-280. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
50109 Starting force window monitoring error 5-280. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
50110 Full-scale force monitoring error 5-281. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Contents
Contents-16� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
50111 Pressure controller is operating at the limit 5-281. . . . . . . . . . . . . . . . . . . . . . . . . .
6 posAxis 6-283. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Possible local responses 6-283. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
20001 Internal error (Parameter1: /1/%d, Parameter2: /2/%d,Parameter3: /3/%d, Parameter4: /4/%d) 6-284. . . . . . . . . . . . . . . . . . . . . . . . . . . .
20002 Insufficient memory (Parameter1: /1/%d, Parameter2: /2/%d,Parameter3: /3/%d, Parameter4: /4/%d) 6-285. . . . . . . . . . . . . . . . . . . . . . . . . . . .
20003 No object configuration (Parameter1: /1/%d, Parameter2: /2/%d,Parameter3: /3/%d, Parameter4: /4/%d) 6-286. . . . . . . . . . . . . . . . . . . . . . . . . . . .
20004 At the logical address: /1/%d (bit number, if required: /2/%d)a driver (type: /3/%d) could be requested (error number: /4/%d) 6-287. . . . . . .
20005 Device type: /3/%d, log. address: /1/%d faulty. (Bit: /2/%d,reason: 0x/4/%Xh) 6-288. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
20006 Error in configuration (category: /1/%d, error number: /2/%d) 6-291. . . . . . . . . .
20007 Interconnection error (category: /1/%d, context: /2/%d,context parameter1: /3/%d, context parameter2: /4/%d) 6-298. . . . . . . . . . . . . .
20008 Cannot assign USER_DEFAULT to system variables 6-300. . . . . . . . . . . . . . . . .
20009 The permissible deviation between encoders (/1/%d) and (/2/%d)has been exceeded 6-300. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
20010 A restart is necessary to activate the configuration data 6-301. . . . . . . . . . . . . .
20011 Error when activating the configuration (category: /1/%d,error number: /2/%d) 6-302. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
20012 Restart not executed (reason: /1/%d) 6-309. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
20014 At the logical address: /1/%d (optional log. address: /2/%d andbit no.: /3/%d of the enable output), a driver (type: /4/%d)could not be requested 6-310. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30001 Illegal parameter (parameter index according to standard sequencein the system functions: /1/%d, command type: /4/%X) 6-311. . . . . . . . . . . . . . .
30002 Command aborted (reason: /1/%d, command type: /4/%X) 6-312. . . . . . . . . . . .
30003 Command aborted due to full command buffer(command type: /4/%X) 6-314. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30004 Unknown command (command type: /4/%X) 6-315. . . . . . . . . . . . . . . . . . . . . . . .
30005 Ambiguous commandId (number of commands with specified ID:/1/%d, command type: /4/%X) 6-316. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30006 Cannot execute command due to current object state(command type: /4/%X) 6-317. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30007 The error cannot be reset due to its configuration 6-318. . . . . . . . . . . . . . . . . . . .
30008 A connection to a technology object required for this operationdoes not exist (command type: /4/%X) 6-319. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Contents
Contents-17� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
30009 Command rejected due to suspension of command decodingon addressed technology object (command type: /4/%X) 6-320. . . . . . . . . . . . . .
30010 Command not available (command type: /4/%X) 6-321. . . . . . . . . . . . . . . . . . . . .
30011 Parameter unavailable (parameter index according tostandard sequence in the system functions: /1/%d,command type: /4/%X) 6-322. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30012 Command cannot be started synchronously(command type: /4/%X) 6-323. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30013 Synchronous start of the command using IMMEDIATELYmergeMode (command type: /4/%X) 6-324. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30014 Coordinate system not offset due to the internal traversingrange limit being exceeded (Parameter1: /1/% /1/%d,command type: /2/%X) 6-325. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30015 A technology required for this command was not configured(technology: /1/%d, command type: /4/%X) 6-326. . . . . . . . . . . . . . . . . . . . . . . . .
40001 Illegal state change on axis 6-327. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
40002 Programmed velocity is limited 6-328. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
40003 Programmed acceleration (type: /1/%d) is limited 6-329. . . . . . . . . . . . . . . . . . . .
40004 Programmed jerk (type: /1/%d) is limited 6-330. . . . . . . . . . . . . . . . . . . . . . . . . . . .
40005 Enable signal(s) missing (Parameter1: /1/%X) and/orincorrect mode (Parameter2: /2/%d) 6-331. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
40006 Programmed velocity is zero 6-332. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
40007 Programmed acceleration (type: /1/%d) is zero 6-332. . . . . . . . . . . . . . . . . . . . . .
40008 Programmed jerk (type: /1/%d) is zero 6-333. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
40009 Velocity limit is zero 6-333. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
40010 Acceleration limit (type: /1/%d) is zero 6-334. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
40011 Programmed jerk limit (type: /1/%d) is zero 6-334. . . . . . . . . . . . . . . . . . . . . . . . .
40012 Dynamic restrictions (type: /1/%d) violated 6-335. . . . . . . . . . . . . . . . . . . . . . . . . .
40013 Programmed stop time restricted by acceleration limits 6-336. . . . . . . . . . . . . . .
40014 Command not possible on virtual axis (command type: /4/%X) 6-337. . . . . . . . .
40015 Error in accessing specified cam 6-337. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
40016 The specified cam has not been interpolated 6-338. . . . . . . . . . . . . . . . . . . . . . . .
40017 Cam start point outside definition range 6-338. . . . . . . . . . . . . . . . . . . . . . . . . . . .
40018 Dynamic response of motion profiles (type: /1/%d) violated(reason: /2/%d) 6-339. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
40019 Error while accessing the motion interface 6-340. . . . . . . . . . . . . . . . . . . . . . . . . .
40020 Dynamic response of the setpoints on the motion interface(type: /1/%d) violated (reason: /2/%d) 6-341. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
40021 StopEmergency command abort due to a pending stop responseof the same or higher priority 6-342. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
40022 Programmed pressure limiting is limited 6-343. . . . . . . . . . . . . . . . . . . . . . . . . . . .
40023 Programmed increase in pressure limiting limited 6-343. . . . . . . . . . . . . . . . . . . .
40024 Programmed increase in pressure limiting is zero 6-344. . . . . . . . . . . . . . . . . . . .
Contents
Contents-18� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
40025 Maximum increase in pressure limiting is zero 6-344. . . . . . . . . . . . . . . . . . . . . . .
40026 Dynamic response of pressure/pressure limiting profiles(type: /1/%d) violated (reason: /2/%d) 6-345. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
40101 Homing output cam not found 6-346. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
40102 Encoder zero mark not found during homing 6-347. . . . . . . . . . . . . . . . . . . . . . . .
40103 Error in homing configuration data (Parameter1: /1/%d) 6-348. . . . . . . . . . . . . . .
40104 Error in software limit switch specification (Parameter1: /1/%d) 6-349. . . . . . . .
40105 Position limited to software limit switch (Parameter1: /1/%d) 6-350. . . . . . . . . . .
40106 Software limit switch (Parameter1: /1/%d) approached 6-350. . . . . . . . . . . . . . .
40107 Software limit switch (Parameter1: /1/%d) is crossed 6-351. . . . . . . . . . . . . . . . .
40108 Axis is not homed 6-351. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
40109 Error on synchronizing two encoders (reason: /1/%d) 6-352. . . . . . . . . . . . . . . . .
40110 Error triggered on slave during synchronous operation(error number: /1/%d) 6-353. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
40111 Internal traversing range limit (Parameter1: /1/%d) approached 6-353. . . . . . . .
40112 Internal traversing range limit (Parameter1: /1/%d) is crossed 6-354. . . . . . . . .
40120 Programmed pressure is limited 6-354. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
40121 Programmed pressure rise is limited 6-355. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
40122 Programmed pressure rise is zero 6-355. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
40123 Maximum pressure rise is zero 6-356. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
40124 Offset cannot be compensated. 6-356. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
40125 Setpoint output delay deactivated in the master 6-357. . . . . . . . . . . . . . . . . . . . .
40301 Connection with slave failed (assignment: /1/%d) 6-358. . . . . . . . . . . . . . . . . . . .
40302 Sign-of-life monitoring for the slave in distributed synchronous operation is deactivated 6-359. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
40303 Local and slave interpolation cycle clock are different 6-360. . . . . . . . . . . . . . . . .
40304 Offset cannot be determined 6-361. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
50001 Drive failure 6-362. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
50002 Limiting frequency of measuring system exceeded 6-362. . . . . . . . . . . . . . . . . . .
50003 Speed acceleration setpoint limitation active 6-363. . . . . . . . . . . . . . . . . . . . . . . .
50005 Speed setpoint monitoring active (Parameter1: /1/%d) 6-364. . . . . . . . . . . . . . . .
50006 Zero mark monitoring 6-365. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
50007 Hardware limit switch (Parameter1: /1/%d, Parameter2: /2/%d) 6-366. . . . . . . .
50008 Timeout waiting for standstill signal 6-367. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
50009 Limit switch active: (Parameter1: /1/%d) only one traversingdirection possible 6-367. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Contents
Contents-19� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
50010 Error while reading or writing data set(category: /1/%d, error number: /2/%d) 6-368. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
50011 Limit range of the incremental actual value exceeded(Parameter1: /1/%d) 6-375. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
50012 Drive does not support the selected function(Parameter1: /1/%d) 6-376. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
50013 Overshoot/undershoot of permissible range limits(logical address: /1/%d, reason: /2/%d) 6-377. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
50014 Permissible system deviation of pressure controller exceeded 6-378. . . . . . . . .
50015 Level overflow of IPO not detected 6-378. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
50016 Backstop limitation active 6-379. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
50017 Manipulated variable monitoring active at Q/F output(Parameter1: /1/%d) 6-380. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
50101 Reference model monitoring window exceeded 6-381. . . . . . . . . . . . . . . . . . . . . .
50102 Dynamic following error monitoring window exceeded 6-382. . . . . . . . . . . . . . . .
50103 Warning limits of dynamic following error monitoring reached 6-383. . . . . . . . . .
50106 Positioning monitoring error 6-384. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
50107 Standstill monitoring error 6-384. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
50108 Clamping monitoring error 6-385. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
50109 Starting force window monitoring error 6-385. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
50110 Full-scale force monitoring error 6-386. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
50111 Pressure controller is operating at the limit 6-386. . . . . . . . . . . . . . . . . . . . . . . . . .
7 followingAxis 7-387. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Possible local responses 7-387. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
20001 Internal error (Parameter1: /1/%d, Parameter2: /2/%d,Parameter3: /3/%d, Parameter4: /4/%d) 7-388. . . . . . . . . . . . . . . . . . . . . . . . . . . .
20002 Insufficient memory (Parameter1: /1/%d, Parameter2: /2/%d, Parameter3: /3/%d, Parameter4: /4/%d) 7-389. . . . . . . . . . . . . . . . . . . . . . . . . . . .
20003 No object configuration (Parameter1: /1/%d, Parameter2: /2/%d, Parameter3: /3/%d, Parameter4: /4/%d) 7-390. . . . . . . . . . . . . . . . . . . . . . . . . . . .
20004 At the logical address: /1/%d (bit number, if required: /2/%d) a driver (type: /3/%d) could be requested (error number: /4/%d) 7-391. . . . . . . . . . . . . . .
20005 Device type: /3/%d, log. address: /1/%d faulty. (Bit: /2/%d,reason: 0x/4/%Xh) 7-392. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
20006 Error in configuration (category: /1/%d, error number: /2/%d) 7-395. . . . . . . . . .
20007 Interconnection error (category: /1/%d, context: /2/%d,context parameter1: /3/%d, context parameter2: /4/%d) 7-402. . . . . . . . . . . . . .
20008 Cannot assign USER_DEFAULT to system variables 7-404. . . . . . . . . . . . . . . . .
Contents
Contents-20� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
20009 The permissible deviation between encoders (/1/%d) and (/2/%d)has been exceeded 7-404. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
20010 A restart is necessary to activate the configuration data 7-405. . . . . . . . . . . . . .
20011 Error when activating the configuration (category: /1/%d, error number: /2/%d) 7-406. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
20012 Restart not executed (reason: /1/%d) 7-414. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
20014 At the logical address: /1/%d (optional log. address:/2/%d and bit no.: /3/%d of the enable output), a driver(type: /4/%d) could not be requested 7-415. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30001 Illegal parameter (parameter index according to standard sequencein the system functions: /1/%d, command type: /4/%X) 7-416. . . . . . . . . . . . . . .
30002 Command aborted (reason: /1/%d, command type: /4/%X) 7-417. . . . . . . . . . . .
30003 Command aborted due to full command buffer(command type: /4/%X) 7-418. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30004 Unknown command (command type: /4/%X) 7-419. . . . . . . . . . . . . . . . . . . . . . . .
30005 Ambiguous commandId (number of commands with specified ID:/1/%d, command type: /4/%X) 7-420. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30006 Cannot execute command due to current object state(command type: /4/%X) 7-421. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30007 The error cannot be reset due to its configuration 7-422. . . . . . . . . . . . . . . . . . . .
30008 A connection to a technology object required for this operationdoes not exist (command type: /4/%X) 7-423. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30009 Command rejected due to suspension of command decodingon addressed technology object (command type: /4/%X) 7-424. . . . . . . . . . . . . .
30010 Command not available (command type: /4/%X) 7-425. . . . . . . . . . . . . . . . . . . . .
30011 Parameter unavailable (parameter index according tostandard sequence in the system functions: /1/%d,command type: /4/%X) 7-426. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30012 Command cannot be started synchronously(command type: /4/%X) 7-427. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30013 Synchronous start of the command using IMMEDIATELYmergeMode (command type: /4/%X) 7-428. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30014 Coordinate system not offset due to the internal traversing rangelimit being exceeded (Parameter1: /1/% /1/%d,command type: /2/%X) 7-429. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30015 A technology required for this command was not configured(technology: /1/%d, command type: /4/%X) 7-430. . . . . . . . . . . . . . . . . . . . . . . . .
40001 Illegal state change on axis 7-431. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
40002 Programmed velocity is limited 7-432. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
40003 Programmed acceleration (type: /1/%d) is limited 7-433. . . . . . . . . . . . . . . . . . . .
40004 Programmed jerk (type: /1/%d) is limited 7-434. . . . . . . . . . . . . . . . . . . . . . . . . . . .
40005 Enable signal(s) missing (Parameter1: /1/%X) and/orincorrect mode (Parameter2: /2/%d) 7-435. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Contents
Contents-21� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
40006 Programmed velocity is zero 7-436. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
40007 Programmed acceleration (type: /1/%d) is zero 7-436. . . . . . . . . . . . . . . . . . . . . .
40008 Programmed jerk (type: /1/%d) is zero 7-437. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
40009 Velocity limit is zero 7-437. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
40010 Acceleration limit (type: /1/%d) is zero 7-438. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
40011 Programmed jerk limit (type: /1/%d) is zero 7-438. . . . . . . . . . . . . . . . . . . . . . . . .
40012 Dynamic restrictions (type: /1/%d) violated 7-439. . . . . . . . . . . . . . . . . . . . . . . . . .
40013 Programmed stop time restricted by acceleration limits 7-440. . . . . . . . . . . . . . .
40014 Command not possible on virtual axis (command type: /4/%X) 7-441. . . . . . . . .
40015 Error in accessing specified cam 7-441. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
40016 The specified cam has not been interpolated 7-442. . . . . . . . . . . . . . . . . . . . . . . .
40017 Cam start point outside definition range 7-442. . . . . . . . . . . . . . . . . . . . . . . . . . . .
40018 Dynamic response of motion profiles (type: /1/%d) violated(reason: /2/%d) 7-443. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
40019 Error while accessing the motion interface 7-444. . . . . . . . . . . . . . . . . . . . . . . . . .
40020 Dynamic response of the setpoints on the motion interface(type: /1/%d) violated (reason: /2/%d) 7-445. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
40021 StopEmergency command abort due to a pending stop responseof the same or higher priority 7-446. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
40022 Programmed pressure limiting is limited 7-447. . . . . . . . . . . . . . . . . . . . . . . . . . . .
40023 Programmed increase in pressure limiting limited 7-447. . . . . . . . . . . . . . . . . . . .
40024 Programmed increase in pressure limiting is zero 7-448. . . . . . . . . . . . . . . . . . . .
40025 Maximum increase in pressure limiting is zero 7-448. . . . . . . . . . . . . . . . . . . . . . .
40026 Dynamic response of pressure/pressure limiting profiles(type: /1/%d) violated (reason: /2/%d) 7-449. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
40101 Homing output cam not found 7-450. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
40102 Encoder zero mark not found during homing 7-451. . . . . . . . . . . . . . . . . . . . . . . .
40103 Error in homing configuration data (Parameter1: /1/%d) 7-452. . . . . . . . . . . . . . .
40104 Error in software limit switch specification (Parameter1: /1/%d) 7-453. . . . . . . .
40105 Position limited to software limit switch (Parameter1: /1/%d) 7-454. . . . . . . . . . .
40106 Software limit switch (Parameter1: /1/%d) approached 7-454. . . . . . . . . . . . . . .
40107 Software limit switch (Parameter1: /1/%d) is crossed 7-455. . . . . . . . . . . . . . . . .
40108 Axis is not homed 7-455. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
40109 Error on synchronizing two encoders (reason: /1/%d) 7-456. . . . . . . . . . . . . . . . .
40110 Error triggered on slave during synchronous operation(error number: /1/%d) 7-457. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
40111 Internal traversing range limit (Parameter1: /1/%d) approached 7-457. . . . . . . .
Contents
Contents-22� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
40112 Internal traversing range limit (Parameter1: /1/%d) is crossed 7-458. . . . . . . . .
40120 Programmed pressure is limited 7-458. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
40121 Programmed pressure rise is limited 7-459. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
40122 Programmed pressure rise is zero 7-459. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
40123 Maximum pressure rise is zero 7-460. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
40124 Offset cannot be compensated. 7-460. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
40125 Setpoint output delay deactivated in the master 7-461. . . . . . . . . . . . . . . . . . . . .
40201 Synchronous operation tolerance exceeded on gearing axis(active monitoring system: /1/%d) 7-462. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
40202 Dynamic response of synchronous operation setpoints(type: /1/%d) violated (reason: /2/%d) 7-463. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
40301 Connection with slave failed (assignment: /1/%d) 7-464. . . . . . . . . . . . . . . . . . . .
40302 Sign-of-life monitoring for the slave in distributedsynchronous operation is deactivated 7-465. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
40303 Local and slave interpolation cycle clock are different 7-466. . . . . . . . . . . . . . . . .
40304 Offset cannot be determined 7-467. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
50001 Drive failure 7-467. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
50002 Limiting frequency of measuring system exceeded 7-468. . . . . . . . . . . . . . . . . . .
50003 Speed acceleration setpoint limitation active 7-469. . . . . . . . . . . . . . . . . . . . . . . .
50005 Speed setpoint monitoring active (Parameter1: /1/%d) 7-470. . . . . . . . . . . . . . . .
50006 Zero mark monitoring 7-471. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
50007 Hardware limit switch (Parameter1: /1/%d, Parameter2: /2/%d) 7-472. . . . . . . .
50008 Timeout waiting for standstill signal 7-473. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
50009 Limit switch active: (Parameter1: /1/%d) only one traversingdirection possible 7-473. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
50010 Error while reading or writing data set(category: /1/%d, error number: /2/%d) 7-474. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
50011 Limit range of the incremental actual value exceeded(Parameter1: /1/%d) 7-481. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
50012 Drive does not support the selected function (Parameter1: /1/%d) 7-482. . . . . .
50013 Overshoot/undershoot of permissible range limits(logical address: /1/%d, reason: /2/%d) 7-483. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
50014 Permissible system deviation of pressure controller exceeded 7-484. . . . . . . . .
50015 Level overflow of IPO not detected 7-484. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
50016 Backstop limitation active 7-485. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
50017 Manipulated variable monitoring active at Q/F output(Parameter1: /1/%d) 7-486. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
50101 Reference model monitoring window exceeded 7-487. . . . . . . . . . . . . . . . . . . . . .
Contents
Contents-23� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
50102 Dynamic following error monitoring window exceeded 7-488. . . . . . . . . . . . . . . .
50103 Warning limits of dynamic following error monitoring reached 7-489. . . . . . . . . .
50106 Positioning monitoring error 7-490. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
50107 Standstill monitoring error 7-490. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
50108 Clamping monitoring error 7-491. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
50109 Starting force window monitoring error 7-491. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
50110 Full-scale force monitoring error 7-492. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
50111 Pressure controller is operating at the limit 7-492. . . . . . . . . . . . . . . . . . . . . . . . . .
8 followingObjectType 8-493. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Possible local responses 8-493. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
20001 Internal error (Parameter1: /1/%d, Parameter2: /2/%d,Parameter3: /3/%d, Parameter4: /4/%d) 8-493. . . . . . . . . . . . . . . . . . . . . . . . . . . .
20002 Insufficient memory (Parameter1: /1/%d, Parameter2: /2/%d,Parameter3: /3/%d, Parameter4: /4/%d) 8-494. . . . . . . . . . . . . . . . . . . . . . . . . . . .
20003 No object configuration (Parameter1: /1/%d, Parameter2: /2/%d,Parameter3: /3/%d, Parameter4: /4/%d) 8-495. . . . . . . . . . . . . . . . . . . . . . . . . . . .
20004 At the logical address: /1/%d (bit number, if required: /2/%d) a driver(type: /3/%d) could be requested (error number: /4/%d) 8-496. . . . . . . . . . . . . . .
20005 Device type: /3/%d, log. address: /1/%d faulty. (Bit: /2/%d,reason: 0x/4/%Xh) 8-497. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
20006 Error in configuration (category: /1/%d, error number: /2/%d) 8-500. . . . . . . . . .
20007 Interconnection error (category: /1/%d, context: /2/%d,context parameter1: /3/%d, context parameter2: /4/%d) 8-501. . . . . . . . . . . . . .
20008 Cannot assign USER_DEFAULT to system variables 8-503. . . . . . . . . . . . . . . . .
20009 Reserved error 8-503. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
20010 A restart is necessary to activate the configuration data 8-504. . . . . . . . . . . . . .
20011 Error when activating the configuration (category: /1/%d,error number: /2/%d) 8-505. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
20012 Restart not executed (reason: /1/%d) 8-506. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
20014 At the logical address: /1/%d (optional log. address: /2/%dand bit no.: /3/%d of the enable output), a driver (type: /4/%d)could not be requested 8-507. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30001 Illegal parameter (parameter index according to standard sequencein the system functions: /1/%d, command type: /4/%X) 8-508. . . . . . . . . . . . . . .
30002 Command aborted (reason: /1/%d, command type: /4/%X) 8-509. . . . . . . . . . . .
30003 Command aborted due to full command buffer(command type: /4/%X) 8-510. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30004 Unknown command (command type: /4/%X) 8-511. . . . . . . . . . . . . . . . . . . . . . . .
Contents
Contents-24� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
30005 Ambiguous commandId (number of commands with specified ID:/1/%d, command type: /4/%X) 8-512. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30006 Cannot execute command due to current object state(command type: /4/%X) 8-513. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30007 The error cannot be reset due to its configuration 8-513. . . . . . . . . . . . . . . . . . . .
30008 A connection to a technology object required for this operationdoes not exist (command type: /4/%X) 8-514. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30009 Command rejected due to suspension of command decodingon addressed technology object (command type: /4/%X) 8-515. . . . . . . . . . . . . .
30010 Command not available (command type: /4/%X) 8-515. . . . . . . . . . . . . . . . . . . . .
30011 Parameter unavailable (parameter index according tostandard sequence in the system functions: /1/%d,command type: /4/%X) 8-516. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30012 Command cannot be started synchronously(command type: /4/%X) 8-517. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30013 Synchronous start of the command using IMMEDIATELYmergeMode (command type: /4/%X) 8-518. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30015 A technology required for this command was not configured(technology: /1/%d, command type: /4/%X) 8-519. . . . . . . . . . . . . . . . . . . . . . . . .
40002 Programmed velocity is limited 8-519. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
40003 Programmed acceleration (type: /1/%d) is limited 8-520. . . . . . . . . . . . . . . . . . . .
40004 Programmed jerk (type: /1/%d) is limited 8-520. . . . . . . . . . . . . . . . . . . . . . . . . . . .
40006 Programmed velocity is zero 8-521. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
40007 Programmed acceleration (type: /1/%d) is zero 8-521. . . . . . . . . . . . . . . . . . . . . .
40008 Programmed jerk (type: /1/%d) is zero 8-522. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
40009 Velocity limit is zero 8-522. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
40010 Acceleration limit (type: /1/%d) is zero 8-523. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
40011 Programmed jerk limit (type: /1/%d) is zero 8-523. . . . . . . . . . . . . . . . . . . . . . . . .
40012 Dynamic restrictions (type: /1/%d) violated 8-524. . . . . . . . . . . . . . . . . . . . . . . . . .
50001 Error in accessing specified cam 8-525. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
50002 The specified cam has not been interpolated 8-525. . . . . . . . . . . . . . . . . . . . . . . .
50003 Cam start point outside definition range 8-526. . . . . . . . . . . . . . . . . . . . . . . . . . . .
50004 Error while changing cam 8-526. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
50005 Deactivation of synchronous operation aborted 8-527. . . . . . . . . . . . . . . . . . . . . .
50006 Synchronous operation activated/deactivated directly 8-527. . . . . . . . . . . . . . . .
50007 Error when activating/deactivating synchronous operation 8-528. . . . . . . . . . . . .
50008 Long-term stability cannot be maintained for the gearing 8-528. . . . . . . . . . . . . .
50009 Changing the dynamic behavior of the master results in adynamic response violation during synchronization anddesynchronization 8-529. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
50101 The programmed master is not configured 8-529. . . . . . . . . . . . . . . . . . . . . . . . . .
50102 Master is not assigned or configured or is defective(reason: /1/%d) 8-530. . . .
Contents
Contents-25� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
50103 Master and slave values can only be read out if a synchronousoperation relationship is active 8-531. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
50104 Master and slave values cannot be read out during synchronizationand desynchronization 8-531. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
50105 No master value can be defined for a specified slave value 8-532. . . . . . . . . . .
50106 No slave value can be defined for a specified master value 8-532. . . . . . . . . . .
50107 Specified synchronization path or desynchronization path is lessthan or equal to zero 8-533. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
50108 Synchronization position is ’AT_THE_END_OF_CAM_CYCLE’but camming is not active. 8-533. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
50109 Synchronization position is AT_THE_END_OF_CAM_CYCLEbut the master mode is not RELATIVE 8-534. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
50110 An absolute position synchronous operation cannot be calledfollowing a velocity synchronous operation 8-534. . . . . . . . . . . . . . . . . . . . . . . . . .
50201 Connection with master failed (assignment: /1/%d) 8-535. . . . . . . . . . . . . . . . . . .
50202 Sign-of-life monitoring for the master in distributed synchronousoperation is deactivated 8-536. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
50203 Local and master interpolation cycle clock are different 8-536. . . . . . . . . . . . . . .
50204 Connection in startup phase 8-537. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
50205 Offset cannot be determined 8-538. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
50206 Loss of synchronization with master on assigned controller indistributed synchronous operation 8-538. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
50207 Master setpoint is outside the permissible range (reason: /1/%d) 8-539. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9 camType 9-541. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Possible local responses 9-541. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
20001 Internal error (Parameter1: /1/%d, Parameter2: /2/%d, Parameter3:/3/%d, Parameter4: /4/%d) 9-541. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
20002 Insufficient memory (Parameter1: /1/%d, Parameter2: /2/%d, Parameter3: /3/%d, Parameter4: /4/%d) 9-542. . . . . . . . . . . . . . . . . . . . . . . . . . . .
20003 No object configuration (Parameter1: /1/%d, Parameter2: /2/%d, Parameter3: /3/%d, Parameter4: /4/%d) 9-543. . . . . . . . . . . . . . . . . . . . . . . . . . . .
20004 At the logical address: /1/%d (bit number, if required: /2/%d)a driver (type: /3/%d) could be requested (error number: /4/%d) 9-544. . . . . . .
20005 Device type: /3/%d, log. address: /1/%d faulty. (Bit: /2/%d,reason: 0x/4/%Xh) 9-545. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
20006 Error in configuration (category: /1/%d, error number: /2/%d) 9-548. . . . . . . . . .
20007 Interconnection error (category: /1/%d, context: /2/%d, context parameter1: /3/%d, context parameter2: /4/%d) 9-549. . . . . . . . . . . . . . . . . . . . .
Contents
Contents-26� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
20008 Cannot assign USER_DEFAULT to system variables 9-551. . . . . . . . . . . . . . . . .
20009 Reserved error 9-551. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
20010 A restart is necessary to activate the configuration data 9-552. . . . . . . . . . . . . .
20011 Error when activating the configuration (category: /1/%d, error number: /2/%d) 9-553. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
20012 Restart not executed (reason: /1/%d) 9-554. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
20014 At the logical address: /1/%d (optional log. address: /2/%dand bit no.: /3/%d of the enable output), a driver (type: /4/%d)could not be requested 9-555. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30001 Illegal parameter (parameter index according to standard sequencein the system functions: /1/%d, command type: /4/%X) 9-556. . . . . . . . . . . . . . .
30002 Command aborted (reason: /1/%d, command type: /4/%X) 9-557. . . . . . . . . . . .
30003 Command aborted due to full command buffer(command type: /4/%X) 9-558. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30004 Unknown command (command type: /4/%X) 9-559. . . . . . . . . . . . . . . . . . . . . . . .
30005 Ambiguous commandId (number of commands with specified ID:/1/%d, command type: /4/%X) 9-560. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30006 Cannot execute command due to current object state(command type: /4/%X) 9-561. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30007 The error cannot be reset due to its configuration 9-561. . . . . . . . . . . . . . . . . . . .
30008 A connection to a technology object required for this operationdoes not exist (command type: /4/%X) 9-562. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30009 Command rejected due to suspension of command decodingon addressed technology object (command type: /4/%X) 9-562. . . . . . . . . . . . . .
30010 Command not available (command type: /4/%X) 9-563. . . . . . . . . . . . . . . . . . . . .
30011 Parameter unavailable (parameter index according to standardsequence in the system functions: /1/%d, command type: /4/%X) 9-563. . . . . .
30012 Command cannot be started synchronously(command type: /4/%X) 9-564. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30013 Synchronous start of the command using IMMEDIATELYmergeMode (command type: /4/%X) 9-565. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30015 A technology required for this command was not configured (technology: /1/%d, command type: /4/%X) 9-566. . . . . . . . . . . . . . . . . . . . . . . . .
40001 Write access to function denied (command type: /4/%X) 9-566. . . . . . . . . . . . . .
40002 Read access to function denied (command type: /4/%X) 9-567. . . . . . . . . . . . . .
40003 Illegal range specification in the parameters(command type: /4/%X) 9-567. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
40004 Segment with length zero will not be inserted in the function(start and end point = /1/%lf) 9-568. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
40005 The point (/1/%lf) is not within the definition range (/2/%lf, /3/%lf)of the function (representation: /4/%d). 9-568. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Contents
Contents-27� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
40006 The point (/1/%lf) is not within the value range (/2/%lf, /3/%lf)of the function (representation: /4/%d). 9-569. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
40007 Access to interpolated function denied (command type: /4/%X). 9-569. . . . . . . .
40008 Required property violated during interpolation 9-570. . . . . . . . . . . . . . . . . . . . . . .
10 AdditionObjectType 10-573. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Possible local responses 10-573. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
20001 Internal error (Parameter1: /1/%d, Parameter2: /2/%d, Parameter3:/3/%d, Parameter4: /4/%d) 10-573. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
20002 Insufficient memory (Parameter1: /1/%d, Parameter2: /2/%d, Parameter3: /3/%d, Parameter4: /4/%d) 10-574. . . . . . . . . . . . . . . . . . . . . . . . . . . .
20003 No object configuration (Parameter1: /1/%d, Parameter2: /2/%d, Parameter3: /3/%d, Parameter4: /4/%d) 10-575. . . . . . . . . . . . . . . . . . . . . . . . . . . .
20004 At the logical address: /1/%d (bit number, if required: /2/%d)a driver (type: /3/%d) could be requested (error number: /4/%d) 10-576. . . . . . .
20005 Device type: /3/%d, log. address: /1/%d faulty. (Bit: /2/%d,reason: 0x/4/%Xh) 10-577. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
20006 Error in configuration (category: /1/%d, error number: /2/%d) 10-580. . . . . . . . . .
20007 Interconnection error (category: /1/%d, context: /2/%d, context parameter1: /3/%d, context parameter2: /4/%d) 10-581. . . . . . . . . . . . . . . . . . . . .
20008 Cannot assign USER_DEFAULT to system variables 10-583. . . . . . . . . . . . . . . . .
20009 Reserved error 10-583. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
20010 A restart is necessary to activate the configuration data 10-584. . . . . . . . . . . . . .
20011 Error when activating the configuration (category: /1/%d, error number: /2/%d) 10-585. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
20012 Restart not executed (reason: /1/%d) 10-586. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
20014 At the logical address: /1/%d (optional log. address: /2/%d andbit no.: /3/%d of the enable output), a driver (type: /4/%d)could not be requested 10-587. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30001 Illegal parameter (parameter index according to standard sequencein the system functions: /1/%d, command type: /4/%X) 10-588. . . . . . . . . . . . . . .
30002 Command aborted (reason: /1/%d, command type: /4/%X) 10-589. . . . . . . . . . . .
30003 Command aborted due to full command buffer(command type: /4/%X) 10-590. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30004 Unknown command (command type: /4/%X) 10-591. . . . . . . . . . . . . . . . . . . . . . . .
30005 Ambiguous commandId (number of commands with specified ID:/1/%d, command type: /4/%X) 10-592. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30006 Cannot execute command due to current object state(command type: /4/%X) 10-593. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Contents
Contents-28� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
30007 The error cannot be reset due to its configuration 10-593. . . . . . . . . . . . . . . . . . . .
30008 A connection to a technology object required for this operationdoes not exist (command type: /4/%X) 10-594. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30009 Command rejected due to suspension of command decodingon addressed technology object (command type: /4/%X) 10-594. . . . . . . . . . . . . .
30010 Command not available (command type: /4/%X) 10-595. . . . . . . . . . . . . . . . . . . . .
30011 Parameter unavailable (parameter index according tostandard sequence in the system functions: /1/%d,command type: /4/%X) 10-595. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30012 Command cannot be started synchronously(command type: /4/%X) 10-596. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30013 Synchronous start of the command using IMMEDIATELYmergeMode (command type: /4/%X) 10-597. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30015 A technology required for this command was not configured (technology: /1/%d, command type: /4/%X) 10-598. . . . . . . . . . . . . . . . . . . . . . . . .
40001 Interface could not be activated (interface: 0x/1/%Xh) 10-599. . . . . . . . . . . . . . . .
40002 Modulo configuration is not taken over from the interconnectedoutput vector 10-600. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11 FixedGearType 11-601. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Possible local responses 11-601. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
20001 Internal error (Parameter1: /1/%d, Parameter2: /2/%d, Parameter3:/3/%d, Parameter4: /4/%d) 11-601. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
20002 Insufficient memory (Parameter1: /1/%d, Parameter2: /2/%d,Parameter3: /3/%d, Parameter4: /4/%d) 11-602. . . . . . . . . . . . . . . . . . . . . . . . . . . .
20003 No object configuration (Parameter1: /1/%d, Parameter2: /2/%d,Parameter3: /3/%d, Parameter4: /4/%d) 11-603. . . . . . . . . . . . . . . . . . . . . . . . . . . .
20004 At the logical address: /1/%d (bit number, if required: /2/%d) adriver (type: /3/%d) could be requested (error number: /4/%d) 11-604. . . . . . . . .
20005 Device type: /3/%d, log. address: /1/%d faulty. (Bit: /2/%d,reason: 0x/4/%Xh) 11-605. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
20006 Error in configuration (category: /1/%d, error number: /2/%d) 11-608. . . . . . . . . .
20007 Interconnection error (category: /1/%d, context: /2/%d,context parameter1: /3/%d, context parameter2: /4/%d) 11-609. . . . . . . . . . . . . .
20008 Cannot assign USER_DEFAULT to system variables 11-611. . . . . . . . . . . . . . . . .
20009 Reserved error 11-611. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
20010 A restart is necessary to activate the configuration data 11-612. . . . . . . . . . . . . .
20011 Error when activating the configuration (category: /1/%d,error number: /2/%d) 11-613. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
20012 Restart not executed (reason: /1/%d) 11-614. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Contents
Contents-29� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
20014 At the logical address: /1/%d (optional log. address: /2/%d and bit no.:/3/%d of the enable output), a driver (type: /4/%d)could not be requested 11-615. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30001 Illegal parameter (parameter index according to standard sequencein the system functions: /1/%d, command type: /4/%X) 11-616. . . . . . . . . . . . . . .
30002 Command aborted (reason: /1/%d, command type: /4/%X) 11-617. . . . . . . . . . . .
30003 Command aborted due to full command buffer(command type: /4/%X) 11-618. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30004 Unknown command (command type: /4/%X) 11-619. . . . . . . . . . . . . . . . . . . . . . . .
30005 Ambiguous commandId (number of commands withspecified ID: /1/%d, command type: /4/%X) 11-620. . . . . . . . . . . . . . . . . . . . . . . . .
30006 Cannot execute command due to current object state(command type: /4/%X) 11-621. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30007 The error cannot be reset due to its configuration 11-621. . . . . . . . . . . . . . . . . . . .
30008 A connection to a technology object required for this operationdoes not exist (command type: /4/%X) 11-622. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30009 Command rejected due to suspension of command decodingon addressed technology object (command type: /4/%X) 11-623. . . . . . . . . . . . . .
30010 Command not available (command type: /4/%X) 11-623. . . . . . . . . . . . . . . . . . . . .
30011 Parameter unavailable (parameter index according tostandard sequence in the system functions: /1/%d,command type: /4/%X) 11-624. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30012 Command cannot be started synchronously(command type: /4/%X) 11-625. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30013 Synchronous start of the command using IMMEDIATELYmergeMode (command type: /4/%X) 11-626. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30015 A technology required for this command was not configured(technology: /1/%d, command type: /4/%X) 11-627. . . . . . . . . . . . . . . . . . . . . . . . .
40001 Interface could not be activated (interface: 0x/1/%Xh) 11-628. . . . . . . . . . . . . . . .
40002 Modulo configuration is not taken over from the interconnectedoutput vector 11-629. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
50008 Long-term stability cannot be maintained for the gearing 11-629. . . . . . . . . . . . . .
50101 The programmed master is not configured 11-630. . . . . . . . . . . . . . . . . . . . . . . . . .
50102 Master is not assigned or configured or is defective (reason: /1/%d) 11-630. . . .
12 FormulaObjectType 12-631. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Possible local responses 12-631. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
20001 Internal error (Parameter1: /1/%d, Parameter2: /2/%d,Parameter3: /3/%d, Parameter4: /4/%d) 12-631. . . . . . . . . . . . . . . . . . . . . . . . . . . .
20002 Insufficient memory (Parameter1: /1/%d, Parameter2: /2/%d,Parameter3: /3/%d, Parameter4: /4/%d) 12-632. . . . . . . . . . . . . . . . . . . . . . . . . . . .
20003 No object configuration (Parameter1: /1/%d, Parameter2: /2/%d,Parameter3: /3/%d, Parameter4: /4/%d) 12-633. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Contents
Contents-30� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
20004 At the logical address: /1/%d (bit number, if required: /2/%d)a driver (type: /3/%d) could be requested (error number: /4/%d) 12-634. . . . . . .
20005 Device type: /3/%d, log. address: /1/%d faulty. (Bit: /2/%d,reason: 0x/4/%Xh) 12-635. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
20006 Error in configuration (category: /1/%d, error number: /2/%d) 12-638. . . . . . . . . .
20007 Interconnection error (category: /1/%d, context: /2/%d,context parameter1: /3/%d, context parameter2: /4/%d) 12-639. . . . . . . . . . . . . .
20008 Cannot assign USER_DEFAULT to system variables 12-641. . . . . . . . . . . . . . . . .
20009 Reserved error 12-641. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
20010 A restart is necessary to activate the configuration data 12-642. . . . . . . . . . . . . .
20011 Error when activating the configuration (category: /1/%d,error number: /2/%d) 12-643. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
20012 Restart not executed (reason: /1/%d) 12-644. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
20014 At the logical address: /1/%d (optional log. address: /2/%dand bit no.: /3/%d of the enable output), a driver (type: /4/%d)could not be requested 12-645. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30001 Illegal parameter (parameter index according to standard sequencein the system functions: /1/%d, command type: /4/%X) 12-646. . . . . . . . . . . . . . .
30002 Command aborted (reason: /1/%d, command type: /4/%X) 12-647. . . . . . . . . . . .
30003 Command aborted due to full command buffer(command type: /4/%X) 12-648. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30004 Unknown command (command type: /4/%X) 12-649. . . . . . . . . . . . . . . . . . . . . . . .
30005 Ambiguous commandId (number of commands with specified ID:/1/%d, command type: /4/%X) 12-650. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30006 Cannot execute command due to current object state(command type: /4/%X) 12-651. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30007 The error cannot be reset due to its configuration 12-651. . . . . . . . . . . . . . . . . . . .
30008 A connection to a technology object required for this operationdoes not exist (command type: /4/%X) 12-652. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30009 Command rejected due to suspension of command decodingon addressed technology object (command type: /4/%X) 12-652. . . . . . . . . . . . . .
30010 Command not available (command type: /4/%X) 12-653. . . . . . . . . . . . . . . . . . . . .
30011 Parameter unavailable (parameter index according tostandard sequence in the system functions: /1/%d,command type: /4/%X) 12-653. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30012 Command cannot be started synchronously(command type: /4/%X) 12-654. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30013 Synchronous start of the command using IMMEDIATELYmergeMode (command type: /4/%X) 12-655. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30015 A technology required for this command was not configured(technology: /1/%d, command type: /4/%X) 12-656. . . . . . . . . . . . . . . . . . . . . . . . .
40001 Interface could not be activated (interface: 0x/1/%Xh) 12-657. . . . . . . . . . . . . . . .
Contents
Contents-31� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
40301 Error when translating a formula expression(formula number: /1/%d, reason: /2/%d) 12-658. . . . . . . . . . . . . . . . . . . . . . . . . . . .
40302 Warning when translating a formula expression(formula number: /1/%d, reason: /2/%d) 12-659. . . . . . . . . . . . . . . . . . . . . . . . . . . .
40303 Division by ’0’ when calculating a formula expression(formula number: /1/%d) 12-659. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
40304 Overflow when calculating a formula expression(formula number: /1/%d) 12-660. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
40305 Underflow when calculating a formula expression(formula number: /1/%d) 12-660. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
40306 Function result when calculating a formula expression(formula number: /1/%d) 12-661. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
40307 Invalid formula number specified (formula number: /1/%d,reason: /2/%d) 12-662. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
13 ControllerObjectType 13-663. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Possible local responses 13-663. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
20001 Internal error (Parameter1: /1/%d, Parameter2: /2/%d,Parameter3: /3/%d, Parameter4: /4/%d) 13-663. . . . . . . . . . . . . . . . . . . . . . . . . . . .
20002 Insufficient memory (Parameter1: /1/%d, Parameter2: /2/%d, Parameter3: /3/%d, Parameter4: /4/%d) 13-664. . . . . . . . . . . . . . . . . . . . . . . . . . . .
20003 No object configuration (Parameter1: /1/%d, Parameter2: /2/%d, Parameter3: /3/%d, Parameter4: /4/%d) 13-665. . . . . . . . . . . . . . . . . . . . . . . . . . . .
20004 At the logical address: /1/%d (bit number, if required: /2/%d) a driver (type: /3/%d) could be requested (error number: /4/%d) 13-666. . . . . . . . . . . . . . .
20005 Device type: /3/%d, log. address: /1/%d faulty.(Bit: /2/%d, reason: 0x/4/%Xh) 13-667. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
20006 Error in configuration (category: /1/%d, error number: /2/%d) 13-670. . . . . . . . . .
20007 Interconnection error (category: /1/%d, context: /2/%d, context Parameter1: /3/%d, context Parameter2: /4/%d) 13-671. . . . . . . . . . . . . . . . . . . . .
20008 Cannot assign USER_DEFAULT to system variables 13-673. . . . . . . . . . . . . . . . .
20009 Reserved error 13-673. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
20010 A restart is necessary to activate the configuration data 13-674. . . . . . . . . . . . . .
20011 Error when activating the configuration (category: /1/%d, error number: /2/%d) 13-675. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
20012 Restart not executed (reason: /1/%d) 13-677. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
20014 At the logical address: /1/%d (optional log. address: /2/%dand bit no.: /3/%d of the enable output), a driver (type: /4/%d)could not be requested 13-678. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30001 Illegal parameter (parameter index according to standard sequencein the system functions: /1/%d, command type: /4/%X) 13-679. . . . . . . . . . . . . . .
30002 Command aborted (reason: /1/%d, command type: /4/%X) 13-680. . . . . . . . . . . .
Contents
Contents-32� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
30003 Command aborted due to full command buffer(command type: /4/%X) 13-681. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30004 Unknown command (command type: /4/%X) 13-682. . . . . . . . . . . . . . . . . . . . . . . .
30005 Ambiguous commandId (number of commandswith specified ID: /1/%d, command type: /4/%X) 13-683. . . . . . . . . . . . . . . . . . . . .
30006 Cannot execute command due to current object state(command type: /4/%X) 13-684. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30007 The error cannot be reset due to its configuration 13-684. . . . . . . . . . . . . . . . . . . .
30008 A connection to a technology object required for this operationdoes not exist (command type: /4/%X) 13-685. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30009 Command rejected due to suspension of command decodingon addressed technology object (command type: /4/%X) 13-685. . . . . . . . . . . . . .
30010 Command not available (command type: /4/%X) 13-686. . . . . . . . . . . . . . . . . . . . .
30011 Parameter unavailable (parameter index according tostandard sequence in the system functions: /1/%d,command type: /4/%X) 13-686. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30012 Command cannot be started synchronously(command type: /4/%X) 13-687. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30013 Synchronous start of the command using IMMEDIATELYmergeMode (command type: /4/%X) 13-688. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30015 A technology required for this command was not configured (technology: /1/%d, command type: /4/%X) 13-689. . . . . . . . . . . . . . . . . . . . . . . . .
40001 Actual value in violation of upper limit 13-689. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
40002 Actual value in violation of lower limit 13-690. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
40003 Setpoint in violation of upper limit 13-690. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
40004 Setpoint in violation of lower limit 13-691. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
40005 Feedforward control variable in violation of upper limit 13-691. . . . . . . . . . . . . . . .
40006 Feedforward variable in violation of lower limit 13-692. . . . . . . . . . . . . . . . . . . . . . .
40007 Permissible system deviation exceeded 13-692. . . . . . . . . . . . . . . . . . . . . . . . . . . .
14 SensorType 14-693. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Possible local responses 14-693. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
20001 Internal error (Parameter1: /1/%d, Parameter2: /2/%d,Parameter3: /3/%d, Parameter4: /4/%d) 14-693. . . . . . . . . . . . . . . . . . . . . . . . . . . .
20002 Insufficient memory (Parameter1: /1/%d, Parameter2: /2/%d,Parameter3: /3/%d, Parameter4: /4/%d) 14-694. . . . . . . . . . . . . . . . . . . . . . . . . . . .
20003 No object configuration (Parameter1: /1/%d, Parameter2: /2/%d,Parameter3: /3/%d, Parameter4: /4/%d) 14-695. . . . . . . . . . . . . . . . . . . . . . . . . . . .
20004 At the logical address: /1/%d (bit number, if required: /2/%d)a driver (type: /3/%d) could be requested(error number: /4/%d) 14-696. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
20005 Device type: /3/%d, log. address: /1/%d faulty. (Bit: /2/%d,reason: 0x/4/%Xh) 14-697. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
20006 Error in configuration (category: /1/%d, error number: /2/%d) 14-700. . . . . . . . . .
Contents
Contents-33� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
20007 Interconnection error (category: /1/%d, context: /2/%d,context parameter1: /3/%d, context parameter2: /4/%d) 14-701. . . . . . . . . . . . . .
20008 Cannot assign USER_DEFAULT to system variables 14-703. . . . . . . . . . . . . . . . .
20009 Reserved error 14-703. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
20010 A restart is necessary to activate the configuration data 14-704. . . . . . . . . . . . . .
20011 Error when activating the configuration (category: /1/%d,error number: /2/%d) 14-705. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
20012 Restart not executed (reason: /1/%d) 14-706. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
20014 At the logical address: /1/%d (optional log. address: /2/%d andbit no.: /3/%d of the enable output), a driver (type: /4/%d) couldnot be requested 14-707. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30001 Illegal parameter (parameter index according to standard sequencein the system functions: /1/%d, command type: /4/%X) 14-708. . . . . . . . . . . . . . .
30002 Command aborted (reason: /1/%d, command type: /4/%X) 14-709. . . . . . . . . . . .
30003 Command aborted due to full command buffer(command type: /4/%X) 14-710. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30004 Unknown command (command type: /4/%X) 14-711. . . . . . . . . . . . . . . . . . . . . . . .
30005 Ambiguous commandId (number of commands with specified ID:/1/%d, command type: /4/%X) 14-712. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30006 Cannot execute command due to current object state(command type: /4/%X) 14-713. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30007 The error cannot be reset due to its configuration 14-713. . . . . . . . . . . . . . . . . . . .
30008 A connection to a technology object required for this operationdoes not exist (command type: /4/%X) 14-714. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30009 Command rejected due to suspension of command decodingon addressed technology object (command type: /4/%X) 14-714. . . . . . . . . . . . . .
30010 Command not available (command type: /4/%X) 14-715. . . . . . . . . . . . . . . . . . . . .
30011 Parameter unavailable (parameter index according to standardsequence in the system functions: /1/%d, command type: /4/%X) 14-715. . . . . .
30012 Command cannot be started synchronously(command type: /4/%X) 14-716. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30013 Synchronous start of the command using IMMEDIATELYmergeMode (command type: /4/%X) 14-717. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30015 A technology required for this command was not configured(technology: /1/%d, command type: /4/%X) 14-718. . . . . . . . . . . . . . . . . . . . . . . . .
50013 Overshoot/undershoot of permissible range limits(logical address: /1/%d, reason: /2/%d) 14-719. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A Command Type Numbers of the Individual Commands A-721. . . . . . . . . . . . . . . . . . . .
Contents
Contents-34� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
Part ITechnology Package CamAlarms
driveAxis 1
outputCamType 2
camTrackType 3
measuringInputType 4
externalEncoderType 5
posAxis 6
followingAxis 7
followingObjectType 8
camType 9
1-36� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
1-37� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
driveAxis
Possible local responses
NONENo response
DECODE_STOPAbort command processing
END_OF_MOTION_STOPStop once the active motions are complete
MOTION_STOPStop motion with programmed values
MOTION_EMERGENCY_STOPStop motion with maximum limit values
MOTION_EMERGENCY_ABORTStop motion with maximum limit values and abort active commands
FEEDBACK_EMERGENCY_STOPStop motion following emergency stop ramp and abort all active commands
OPEN_POSITION_CONTROLStop motion with speed setpoint 0 and abort all active commands
RELEASE_DISABLEStop motion with controller disable and abort all active commands
1
driveAxis
1-38� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
20001 Internal error (Parameter1: /1/%d, Parameter2: /2/%d, Parameter3: /3/%d,Parameter4: /4/%d)
CauseThis alarm indicates internal error states providing information about the cause andlocation of the error in association with the related error number.
Meaning of alarm parameters
Parameter1: Error source
Parameter2 to 4: Error number
RemedyA detailed description of the system error alarm is not provided. Should a systemerror of this type occur, note the alarm number, the alarm text, and the internalsystem error number specified in the alarm and contact: SIEMENS AG A&D MC, Hotline.
Acknowledgment / responsePower On / STOP
Default setting for local responseRELEASE_DISABLE
Programmable local responsesRELEASE_DISABLE
driveAxis
1-39� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
20002 Insufficient memory (Parameter1: /1/%d, Parameter2: /2/%d, Parameter3:/3/%d, Parameter4: /4/%d)
CauseThe memory required by the system is no longer available. This alarm can occurboth during power up and after program calls.
Meaning of alarm parameters
Parameter1: Area in which the error occurred.
1–Command decoding
2–Interpolator
3–Controller
4–Manipulated variable output
5–Encoder system
6–Technology package
Parameters 2 to 4 are area-specific. They are not fully utilized by all areas.
Command decoding area:
Parameter2 and Parameter4 refer to the command in which the error occurred.
Parameter2: Command return value
Parameter4: Command type
Remedy
� Reduce the size of the ST code.
� Reduce the number of technology objects.
� Reduce the number of interpolation points for cams, if present.
Acknowledgment / responsePower On / STOP
Default setting for local responseFEEDBACK_EMERGENCY_STOP
Programmable local responsesFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
driveAxis
1-40� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
20003 No object configuration (Parameter1: /1/%d, Parameter2: /2/%d, Parameter3:/3/%d, Parameter4: /4/%d)
CauseError in system configuration. The configuration data for a software tool could notbe found.
Meaning of alarm parameters
Parameter1: Area in which the error occurred.
1–Command decoding
2–Interpolator
3–Controller
4–Manipulated variable output
5–Encoder system
Parameters 2 to 4 are area-specific. They are not fully utilized by all areas.
Command decoding area:
Parameter2 and Parameter4 refer to the command in which the error occurred.
Parameter2: Command return value
Parameter4: Command type
RemedyCheck the accuracy of the configuration data in your project. When commands arecalled on technology objects, the technology objects must be configured.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
driveAxis
1-41� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
20004 At the logical address: /1/%d (bit number, if required: /2/%d) a driver (type:/3/%d) could be requested (error number: /4/%d)
CauseThe driver of a physical device or the device itself is not available.
Meaning of alarm parameters
Logical address:
This is the address configured on the technology object.
Bit number:
For bit driver only; bit number
Type:
1–Actuator driver
2–Encoder driver
3–BitRead driver
4–BitWrite driver
5–ByteRead driver
6–ByteWrite driver
7–WordRead driver
8–WordWrite driver
9–DWordRead driver
10–DWordWrite driver
Error number: Specification of error
1000 = “General driver configuration error”
Remedy
� Connect a suitable device.
� Check the device (function, connections, terminals).
� Check the topological configuration in HWConfig.
� Compare configuration of HWConfig and technology object.
� Contact the hotline.
Acknowledgment / responsePower On / START TechnologicalFaultTask
Default setting for local responseRELEASE_DISABLE
Programmable local responsesRELEASE_DISABLE
driveAxis
1-42� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
20005 Device type: /3/%d, log. address: /1/%d faulty. (Bit: /2/%d, reason: 0x/4/%Xh)
CauseThe driver of a physical device or the device itself has failed or is faulty. When thisalarm occurs, the error cause must be evaluated in the external device (drive orencoder).
Meaning of alarm parameters
Type:
1–Actuator driver
2–Encoder driver
3–BitRead driver
4–BitWrite driver
5–ByteRead driver
6–ByteWrite driver
7–WordRead driver
8–WordWrite driver
9–DWordRead driver
10–DWordWrite driver
Logical address:This is the address configured on the technology object.
Bit number:For bit driver type = 3 or 4 only; bit number
Reason:0–Not defined (e.g., for binary I/O)
� Type = 1
0x0001h: Fault message from drive (note: On PROFIBUS drives, whichsupport acyclic communication in accordance with PROFIdrive V3,the error number/numbers of the drives is/are displayed in thediagnostic buffer, e.g., on Masterdrives MC).
0x0002h: DP: Drive signal “control requested” failed
0x0004h: DP: Drive switched off itself
0x0008h: Slot for drive data is not available in the project
0x0010h: Actuator driver does not have a connection to the drive data
0x0020h: Actuator driver was not initialized during power up
0x0080h: DP: Difference between configuration data and drive parameters
0x4000h: DP: Drive on bus failed (station failure)
0x8000h: Sign of life of drive faulty or failed
driveAxis
1-43� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
� Type = 2
0x0000h: The number of permissible changes in the actual value of the maximum velocity of the absolute-value encoder has beenexceeded
0x0001h: Fault message from encoder (note: The error number/numbers is/are displayed in the diagnostic buffer)
0x0002h: General hardware error of encoder
0x0004h: Encoder contaminated
0x0008h: Slot for encoder data is not available in the project
0x0010h: Encoder driver does not have a connection to the encoder data
0x0020h: Encoder driver was not initialized during power up
0x0040h: Error when reading the absolute value of the encoder
0x0080h: DP: Difference between the configuration data and the encoder parameters
0x0100h: Zero mark monitoring of encoder
0x4000h: DP: Encoder on bus failed (station failure)
0x8000h: DP: Sign of life of encoder has malfunctioned or failed. (Note: For an encoder whose data are transferred in a drive message together with actuator data, the actuator sign of life applies for the encoder, e.g., a standard message 3 in accordance with PROFIdrive).
� Type = 3 to 10
0x0000h: Additional information, not assigned
Note:Codings for the reason of the failure can also occur in combination. Theindividual codings are then added to form a coding sum, which is displayed(e.g., 0x0005 = 0x0001 + 0x0004). A reason for failure marked as DP can only be present on PROFIBUS devices.
driveAxis
1-44� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
RemedyCheck the device with respect to function and connections (reason 0x0001,0x0002, 0x0004, 0x4000, 0x8000).
� Check the topological configuration in HW Config (with reason 0x0008).
� For PROFIBUS drives or encoders, compare the configuration of HWConfig, thetechnology object, and the drive parameter assignment.For:
Reason 0x0040:
– Compare the encoder type in the drive or encoder parameter P979 with theconfiguration data of the technology object.
Reason 0x0080:
– Compare the message frame type in the drive or encoder parameter P922with HW Config and the configuration data of the technology object.
– Compare the encoder type, resolution, multiplier and, with absoluteencoders, the data length in the drive or encoder parameter P979 with theconfiguration data of the technology object.
– Compare the parameterization named in reason 0x8000 (reason 0x8000 canoccur as secondary fault).
Reason 0x8000:
– Compare the cycle clock parameters of HW Config (PROFIBUS line, SlaveOM for drive or encoder) and the execution system. Tmapc and servo mustbe parameterized with the same cycle clock period!
� System fault, contact the hotline (reason 0x0008, 0x0010, 0x0020).
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseRELEASE_DISABLE
Programmable local responsesRELEASE_DISABLE
driveAxis
1-45� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
20006 Error in configuration (category: /1/%d, error number: /2/%d)
CauseThis alarm indicates error states caused by a faulty or inconsistent configuration.The technology objects perform a plausibility check on the configuration. Errors areidentified by the error codes below.
Meaning of alarm parameters
Category: Area in which the error occurred.
1–Command decoding
2–Interpolator
3–Controller
4–Manipulated variable output
5–Encoder system
6–Technology object
Error number: Specification of error
500 = “TO in illegal status for configuration”
501 = “More configuration data expected than received”
502 = “Invalid data in configuration”
503 = “Version conflict in configuration”
1000 = “General configuration error”
2000 = “Error in actuator system configuration”
2001 = “Outside of limits of manipulated variable”
2003 = “Error in load gear ratios”
2004 = “Error in maximum velocity”
2005 = “Maximum velocity greater than maximum attainable velocity”
2006 = “Drive not suitable for torque-controlled or torque-limited operation”
2007 = “Linear stepper motor not implemented”
2008 = “Right-aligned format for direct output not implemented”
2009 = “Illegal value in resolution for direct output”
2010 = “Missing configuration data for actuator system”
2011 = “Missing configuration data for additional actuator system”
2012 = “The backstop range (min to max) does not contain a zero point”
2014 = “Drive or message frame not suitable for torque superimposition”
2015 = “Gear ratios less than or equal to 0”
2016 = “Resolution for stepper motor is 0”
2017 = “Illegal value for the configuration data maxSpeed”
2018 = “Illegal value for the configuration data maxVelocity”
2019 = “Limits of a configuration data exceeded”
2020 = “Limits for the max. acceleration exceeded”
2021 = “Illegal values for dead-zone compensation”
2022 = “Illegal values for sliding-friction compensation”
driveAxis
1-46� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
2023 = “Illegal values for backstop range”
2024 = “Error in sliding-friction compensation parameter”
3000 = “Error in encoder system”
3001 = “Error in encoder system”
3002 = “Invalid axis type selected”
3003 = “Leadscrew pitch is 0”
3004 = “Modulo axis selected with modulo value less than or equal to 0”
3005 = “Illegal specification(s) in the encoder data (incremental / absolute, etc.)”
3006 = “Illegal number of encoders selected”
3007 = “Illegal incremental encoder number”
3008 = “Illegal data combination for homing with incremental encoder”
3009 = “Illegal encoder number”
3010 = “Illegal data on SSI encoder”
3011 = “Illegal encoder number”
3012 = “Illegal encoder number”
3013 = “Illegal measuring gear data, DRIVE assembly type (e.g., factor = 0)”
3014 = “Illegal encoder number”
3015 = “Illegal measuring gear data, LOAD assembly type (e.g., factor = 0)”
3016 = “Illegal data set number (e.g., factor = 0)”
3017 = “Encoder data sequence and number of encoders do not match”
3018 = “Error in encoder system”
3019 = “Illegal encoder number”
3020 = “Illegal encoder system / actuator system simulation selected”.
3021 = “Illegal encoder number or incorrect number of data sets”
3022 = “Illegal encoder number or incorrect number of data sets”
3023 = “Illegal data for ratio of external attachment (e.g., factor = 0)”
3024 = “Path/rotation of external attachment = 0”
3025 = “Illegal value for monitoring of actual velocity”
3026 = “Illegal encoder number in SSI encoder configuration”
3027 = “Illegal message format in SSI encoder configuration”
3028 = “Illegal baud rate in SSI encoder configuration”
3029 = “Illegal SSI state in SSI encoder configuration”
3030 = “Illegal encoder number in data set”
3031 = “Encoder number in data set not configured”
3032 = “Illegal numerator factor in data set”
3033 = “Illegal denominator factor in data set”
3034 = “Illegal data set number”
3035 = “Data set number not configured”
3036 = “Encoder not configured”
3037 = “Homing of ENDAT encoder with zero mark not possible”
3038 = “Homing of CAM negative edge onboard not possible”
3039 = “On-the-fly homing of ENDAT encoder with zero mark not possible”
driveAxis
1-47� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
3040 = “On-the-fly homing of CAM negative edge onboard not possible”
3041 = “Factors for adjusting encoder data to the mechanics are outside the permissible range of values”.
3042 = “Illegal data combination for homing wit external encoder”.
3043 = “The incremental position of the encoder is outside the permissible range of values”.
3044 = “The incremental position of the encoder is outside the permissible range of values”.
3045 = “Illegal value for resolution of linear measuring system”
3046 = “Illegal value for filter of actual-velocity encoder”
3047 = “Illegal value for smoothing of actual-value encoder”
3048 = “Illegal value for smoothing of actual-value encoder with actual-valuecoupling”
3049 = “Illegal DSC encoder selection”
3050 = “Configuration of encoder system not completed correctly”
3051 = “Error in configuration of the sensor data or the stepper motor”
3052 = “Actual-value type (position, interval, velocity) not implemented”
3053 = “Only homing with CAM possible for stepper motor”
3054 = “Only on-the-fly homing with CAM possible for stepper motor”
3055 = “Stepper motor only possible with a real axis”
3056 = “Only one encoder permissible with stepper motor”
3057 = “DSC encoder is not a DP encoder”
3058 = “Illegal message frame of the DSC encoder”
3059 = “Modulo value too small”
3060 = “Configuration differential measurement position faulty”.
3061 = “Illegal data in range configuration of the differential measurement position”.
4000 = “Error in controller”4001 = “Negative acceleration specified”4002 = “Unknown ’FipoType’ requested”4003 = “Error in runtime system, ratio of controller cycle clock to interpolator
cycle clock incorrect”.4004 = “Requested filter arrangement not possible”4005 = “Reserve for later use”4006 = “Maximum limit is lower than minimum”4007 = “Reserve for later use”4008 = “Error in configuration data for controller”4009 = “Reserve for later use”4010 = “Reserve for later use”4011 = “Reserve for later use”4012 = “Reserve for later use”4013 = “Requested controller type is not available”4014 = “Error in controller factors”4015 = “Feedforward control activated, kpc < 0 or kpc > 150”
driveAxis
1-48� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
4016 = “Reserve for later use”
4017 = “Reserve for later use”
4018 = “Reserve for later use”
4019 = “Reserve for later use”
4020 = “Reserve for later use”
4021 = “Reserve for later use”
4022 = “Reserve for later use”
4023 = “Feedforward control activated, kpc <= 0”
4024 = “Model reference monitoring: Error in value of tolerance window”
4025 = “Error in limit value for standstill signal”
4026 = “Error in parameter for positioning monitoring”
4027 = “Reference model and dynamic following error monitoring activated, not possible at the same time”.
4028 = “Sampling time parameter calculated incorrectly”
4029 = “Too many data sets requested”
4030 = “Error in runtime system, ratio of controller cycle clock to interpolator cycle clock incorrect”.
4031 = “Error in time constant for emergency stop ramp generator (positionTimeConstant)”.
4032 = “Feedforward control active, but fine interpolator type is DIRECT”
4033 = “Default data set outside limits”
4034 = “Maximum number of data sets not possible”
4035 = “Unknown data set alternating mode”
4036 = “Following error monitoring not activated/deactivated in all data sets”.
4037 = “Model reference monitoring not activated/deactivated in all data sets”.
4038 = “Different controller type in data sets”
4039 = “Feedforward control activated/deactivated in data sets”
4040 = “Time constant is 0”
4041 = “Error in dynamic adaptation parameter”
4042 = “System variable initialization could not be read”
4043 = “Driver simulation not implemented”
4044 = “Connection for stepper motors not implemented”
4045 = “Maximum velocity cannot be reached, maximum drive speed or a normalization factor incorrect”.
4046 = “DSC requires motor encoder data to be specified”
4047 = “Drive or message frame type not suitable for DSC”
4048 = “Error in clamping monitoring parameter. ’No identifier’ is not permitted for the fixed end stop identifier”
4049 = “Without sensor, monitoring of the actual velocity by ’DynamicControl’ not possible”.
4050 = “Inconsistent PROFIBUS parameterization; the sum of Ti and To is greater than one DP clock cycle”
driveAxis
1-49� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
4051 = “Error in manipulated variable limit parameter of force/pressure controller”
4052 = “Error in starting force/pressure monitoring parameter”
4053 = “Error in full-scale force/pressure monitoring parameter”
4054 = “Starting force/pressure monitoring tolerance less than tolerance of full-scale pressure monitoring”
4055 = “Error in force/pressure system deviation monitoring parameter”
4056 = “Different activation/deactivation of the control difference monitoring of the force/pressure controller not permitted in data sets”
4057 = “Different manipulated variable inversion of the force/pressure controller not permitted in data sets”
4058 = “Different force/pressure sensor types not permitted in data sets”
4059 = “Different activation/deactivation of the anti windup not permitted in data sets”
4060 = “Kd factor of the PID_ACTUAL controller is greater than 1”
4061 = “Time constant of the process model T1 <= T2”
4062 = “Illegal actuator type selection”
4063 = “Error in sliding friction compensation parameter”
4064 = “Error in offset application parameter”
4065 = “Feedforward control for force/pressure control not implemented”
4066 = “Error in standstill monitoring parameter”
4067 = “Following error monitoring: minVelocity must not be greater than or equal to maxVelocity”
4068 = “velocityTimeConstant when using a dead-time element for feedforward balancing too great”
4069 = “The system-related dead times are less than 0 after the calculation of additionalTime”
4070 = “Controller types not equal to DIRECT require the configuration of an encoder”
4071 = “Illegal values for delayTimeToActivate of the standstill signal”
4072 = “The IO device for the positive HW limit switch is not available”
4073 = “The IO device for the negative HW limit switch is not available”
4074 = “Limits of a controller parameter exceeded”
4075 = “Limit for emergency-stop-ramp brake delay exceeded”
4076 = “Limit for a substitute time constant exceeded”
4077 = “Limit for velocityTimeConstant exceeded”
4078 = “Error in value for configuration of QFDynamicData”
4079 = “Error in value for model reference monitoring”
4080 = “Error in following error monitoring parameter”
4081 = “Error in clamping monitoring parameter”
4082 = “Error in value for configuration of DynamicData”
driveAxis
1-50� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
4083 = “Error in value for configuration of PV controller”
4084 = “Incomplete configuration data for controller”
4085 = “Error in value for configuration of SystemDeadTimeData”
4086 = “Pressure control only possible with closed speed controller”
4087 = “DSC and compensation of valve characteristic not possible”
4088 = “DSC not possible on hydraulic axes”
4089 = “Time constant of dynamic compensation T1 <= T2”
4090 = “Incorrect value for correction of system dead time”
5000 = “Encoder data sequence and number of encoders do not match”
5001 = “Illegal number of additional sensors selected”
5002 = “Illegal additional sensor type selected”
5003 = “Illegal data in configuration of driver data for additional sensor”
5004 = “Illegal data in configuration of conversion data for additional sensor”
5006 = “Illegal data in configuration of range for additional sensor”
5007 = “Illegal data in configuration of filter time for additional sensor”
5008 = “Configuration of additional sensor not completed correctly”
5009 = “Illegal number for additional sensor in data set”
5010 = “Illegal data in configuration of differential pressure measurement”
5011 = “Error sensor A differential pressure measurement”
5012 = “Error sensor B differential pressure measurement”
5013 = “Illegal data in configuration of extrapolation”
5014 = “Illegal data in configuration of execution task for sensor TO”
5015 = “Illegal data in configuration of substitute value strategy for sensor TOtechnological alarm”
5020 = “Illegal data in configuration of driver data for analog sensor”
5021 = “Illegal data in configuration of position filter for analog sensor”
5022 = “Illegal data in configuration of conversion data for analog sensor”
5023 = “Illegal data in configuration of measurement input for analog sensor”
5030 = “Illegal data in configuration of conversion data for interval counter”
6000 = “In the configuration data, the monitoring of the positioning path isconfigured up to the reference-point switch, and the maximum pathto be traveled in the process is configured as zero”
6001 = “Error in configuration data numberOfMaxBufferedCommandId”
6002 = “Error in configuration data numberOfQueueCommands”
6003 = “Error in configuration data numberOfImmediateCommands”
6004 = “Configuration of behaviourAtTheEndOfProfile not implemented”
driveAxis
1-51� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
6005 = “Illegal value for the configuration data maximum acceleration”
6006 = “Illegal value for the configuration data maximum jerk”
6007 = “Illegal value for the configuration data maximum force/pressure setpoint”
6008 = “Illegal value for the configuration data maximum force/pressure setpoint
rate of rise”
6009 = “Illegal value for the configuration data synchronous operation tolerance on the setpoint side”
6010 = “Illegal value for the configuration data synchronous operation tolerance on the actual-value side”
6011 = “Illegal value for the configuration data enable synchronous operationtolerance on the setpoint side”
6012 = “Illegal value for the configuration data enable synchronous operationtolerance on the actual-value side”
6013 = “Illegal value for the configuration data tolerance window end-of-profiledetection”
6014 = “Illegal value for the configuration data extrapolation time actual values”
6015 = “Illegal value for the configuration data tolerance window actual-value coupling”
6016 = “Illegal value for the configuration data touchdown tolerance position limit”
6017 = “Illegal value for the configuration data handling mode position limit”
7000 = “Illegal data in configuration of a process model”
7001 = “Illegal data in configuration of the functional component >drive model<of a process model”
7002 = “Illegal data in configuration of the functional component >delay< ofa process model”
7003 = “Illegal data in configuration of the functional component >shut down drive<of a process model”
7004 = “Illegal data in configuration of the functional component >encoder< of aprocess model”
7005 = “Illegal data in configuration of the functional component >switch< of aprocess model”
RemedyChange the configuration data.
Acknowledgment / responsePower On / START TechnologicalFaultTask
Default setting for local responseRELEASE_DISABLE
Programmable local responsesFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
driveAxis
1-52� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
20007 Interconnection error (category: /1/%d, context: /2/%d, context parameter1:/3/%d, context parameter2: /4/%d)
CauseThis alarm indicates errors in the interconnection of technology objects. When theinterconnection is established, the technology object verifies it on the basis of theinterface properties. Errors are classified by category.
Meaning of alarm parameters
Category:
1 – TO compatibility errorAn interconnection is to be established with a technology object that has beenconfigured with another reference system (e.g., output cam with rotaryreference system and linear axis).
2 – Exclusive interfaceMultiple interconnections are to be established for an interface intended forexclusive interconnection.
3 – Interconnection requirementThe technology object is waiting for an interconnection required for thesequence.
4 – Interface initialization errorErrors result from extended initialization sequences at interfaces andparameter exchange between interconnected interfaces.
5 – Interface not available on technology objectAn interface specified in the interconnection is not available on the technologyobject.
6 – CircularityThe interconnection on the technology object leads to circular communicationwithin the technology object (e.g., circular master/slave interconnection ofgearing axes, whereby a gearing axis used as a master is in turn the slave ofanother master, which is assigned the master setpoints generated on thisgearing axis directly or via additional interconnections).
7 – Sequence-level compatibility errorAn interconnection is to be established with a technology object that isexecuted in another interpolator level (e.g., output cam with IPO and axis withIPO_2).
8 – Distribution initializationWhen interconnecting technology objects that are distributed among differentdevices, an error occurred during initialization of the communication interface.
9 – Illegal TO statusThe technology object cannot be interconnected in the current state.
Context:
The context provides additional information about the error category for the TOinterconnection. Additional parameters can be provided for the error descriptionon a context-specific basis. Context and context parameter are output as aninteger value.
driveAxis
1-53� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
Remedy
1 – Technology object compatibility error:Correct the configuration of the reference system of the technology objects tobe interconnected.
2 – Exclusive interface:Correct the configuration of the interconnected technology object.
3 – Interconnection request:Add the missing interconnection to your technology object.
4 – Error during interface initialization: Contact the hotline.
5 – Interface not available on technology object: Contact the hotline.
6 – Circularity:Remove unnecessary interconnections.
7 – Execution level compatibility error: Correct the configuration of the interpolator task level of the technology objectsto be interconnected.
8 – Distribution initialization:Check the hardware configuration. Ensure that the distributed interactingdevices are linked in the bus configuration. In addition, the address areas thatare used by the devices for communication must be set up. The address areasare automatically set up when the project is compiled; only afterwards is thevalid hardware configuration available for downloading.
9 – Illegal TO status:Correct the configuration of the technology object, correct execution errors.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseRELEASE_DISABLE
Programmable local responsesFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
driveAxis
1-54� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
20008 Cannot assign USER_DEFAULT to system variables
CauseIt is not appropriate to assign USER_DEFAULT to a UserDefault system variable,because the variable references itself in this case.This prevents generation of a useful value during reading out. When this erroroccurs, the new Enum value is not assigned. The variable retains the old value.
RemedyUSER_DEFAULT is designed for use in technology commands.Avoid assigning it to system variables.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONE
20009 The permissible deviation between encoders (/1/%d) and (/2/%d) has beenexceeded
CauseThe permissible deviation between two encoders (slip monitoring) has beenexceeded.
Remedy1. Check the mechanical configuration.2. Check the dimensioning of the dynamic limit values (acceleration, jerk).
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
driveAxis
1-55� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
20010 A restart is necessary to activate the configuration data
CauseThe configuration cannot be set to active, since data have been modified in such away that does not permit it. The technology object must be restarted to activate thedata.
Remedy
� Execute the technology object reset command, and set the activateRestartparameter to ACTIVATE_RESTART.
� Set the restartActivation system variable to ACTIVATE_RESTART.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
driveAxis
1-56� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
20011 Error when activating the configuration (category: /1/%d, error number:/2/%d)
CauseThis note indicates error conditions when activating the configuration. The errorconditions can be traced back to an incorrect or inconsistent configuration. Thetechnology objects perform a plausibility check on the configuration. Errors areidentified by the error codes below.If this information appears, the configuration will not be activated.
Meaning of alarm parameters
Category: Area in which the error occurred.
1–Command decoding
2–Interpolator
3–Controller
4–Manipulated variable output
5–Encoder system
6–Technology object
Error number: Specification of error
1000 = “General configuration error”
2000 = “Error in actuator system configuration”
2001 = “Outside of limits of manipulated variable”
2003 = “Error in load gear ratios”
2004 = “Error in maximum velocity”
2005 = “Maximum velocity greater than maximum attainable velocity”.
2006 = “Drive not suitable for torque-controlled or torque-limited operation”
2007 = “Linear stepper motor not implemented”
2008 = “Right-aligned format for direct output not implemented“
2009 = “Illegal value in resolution for direct output”
2010 = ”Missing configuration data for actuator system”
2011 = “Missing configuration data for additional actuator system”
2012 = “The backstop range (min to max) does not contain a zero point”
2014 = “Drive or message frame not suitable for torque superimposition”
2015 = “Gear ratios less than or equal to 0”
2016 = “Resolution for stepper motor is 0”
2017 = “Illegal value for the configuration data maxSpeed”
2018 = “Illegal value for the configuration data maxVelocity”
2019 = “Limits of a configuration data exceeded”
2020 = “Limits for the max. acceleration exceeded”
2021 = “Illegal values for dead-zone compensation”
2022 = “Illegal values for sliding-friction compensation”
2023 = “Illegal values for backstop range”
2024 = “Error in sliding-friction compensation parameter”
driveAxis
1-57� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
3000 = “Error in encoder system”
3001 = “Error in encoder system”
3002 = “Invalid axis type selected”
3003 = “Leadscrew pitch is 0”
3004 = “Modulo axis selected with modulo value less than or equal to 0”
3005 = “Illegal specification(s) in the encoder data (incremental / absolute, etc.)”
3006 = “Illegal number of encoders selected”
3007 = “Illegal incremental encoder number”
3008 = “Illegal data combination for homing with incremental encoder”
3009 = “Illegal encoder number”
3010 = “Illegal data on SSI encoder”
3011 = “Illegal encoder number”
3012 = “Illegal encoder number”
3013 = “Illegal measuring gear data, DRIVE assembly type (e.g., factor = 0)”
3014 = “Illegal encoder number”
3015 = “Illegal measuring gear data, LOAD assembly type (e.g., factor = 0)”
3016 = “Illegal data set number (e.g., factor = 0)”
3017 = “Encoder data sequence and number of encoders do not match”
3018 = “Error in encoder system”
3019 = “Illegal encoder number”
3020 = “Illegal encoder system / actuator system simulation selected”.
3021 = “Illegal encoder number or incorrect number of data sets”
3022 = “Illegal encoder number or incorrect number of data sets”
3023 = “Illegal data for ratio of external attachment (e.g., factor = 0)”
3024 = “Path/rotation of external attachment = 0”
3025 = “Illegal value for monitoring of actual velocity”
3026 = “Illegal encoder number in SSI encoder configuration”
3027 = “Illegal message format in SSI encoder configuration”
3028 = “Illegal baud rate in SSI encoder configuration”
3029 = “Illegal SSI state in SSI encoder configuration”
3030 = “Illegal encoder number in data set”
3031 = “Encoder number in data set not configured”
3032 = “Illegal numerator factor in data set”
3033 = “Illegal denominator factor in data set”
3034 = “Illegal data set number”
3035 = “Data set number not configured”
3036 = “Encoder not configured”
3037 = “Homing of ENDAT encoder with zero mark not possible”
3038 = “Homing of CAM negative edge onboard not possible”
3039 = “On-the-fly homing of ENDAT encoder with zero mark not possible”
3040 = “On-the-fly homing of CAM negative edge onboard not possible”
driveAxis
1-58� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
3041 = “Factors for adjusting encoder data to the mechanics are outside thepermissible range of values”
3042 = “Illegal data combination for homing with external encoder”
3043 = “The incremental position of the encoder is outside the permissible range of values”
3044 = “The incremental position of the encoder is outside the permissible range of values”
3045 = “Illegal value for resolution of linear measuring system”
3046 = “Illegal value for filter of actual-velocity encoder”
3047 = “Illegal value for smoothing of actual-value encoder”
3048 = “Illegal value for smoothing of actual-value encoder with actual-valuecoupling”
3049 = “Illegal DSC encoder selection”
3050 = “Configuration of encoder system not completed correctly”
3051 = “Error in configuration of the sensor data or the stepper motor”
3052 = “Actual-value type (position, interval, velocity) not implemented”
3053 = “Only homing with CAM possible for stepper motor”
3054 = “Only on-the-fly homing with CAM possible for stepper motor”
3055 = “Stepper motor only possible with a real axis”
3056 = “Only one encoder permissible with stepper motor”
3057 = “DSC encoder is not a DP encoder”
3058 = “Illegal message frame of the DSC encoder”
3059 = “Modulo value too small”
3060 = “Configuration differential measurement position faulty”
3061 = “Illegal data in range configuration of the differential measurement position”
4000 = “Error in controller”
4001 = “Negative acceleration specified”
4002 = “Unknown ’FipoType’ requested”
4003 = “Error in runtime system, ratio of controller cycle clock to interpolator cycle clock incorrect”
4004 = “Requested filter arrangement not possible”
4005 = “Reserve for later use”
4006 = “Maximum limit is lower than minimum”
4007 = “Reserve for later use”
4008 = “Error in configuration data for controller”
4009 = “Reserve for later use”
4010 = “Reserve for later use”
4011 = “Reserve for later use”
4012 = “Reserve for later use”
4013 = “Requested controller type is not available”
4014 = “Error in controller factors”
4015 = “Feedforward control activated, kpc < 0 or kpc > 150”
4016 = “Reserve for later use”
4017 = “Reserve for later use”
driveAxis
1-59� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
4018 = “Reserve for later use”
4019 = “Reserve for later use”
4020 = “Reserve for later use”
4021 = “Reserve for later use”
4022 = “Reserve for later use”
4023 = “Feedforward control activated, kpc <= 0”
4024 = “Model reference monitoring: Error in value of tolerance window”
4025 = “Error in limit value for standstill signal”
4026 = “Error in parameter for positioning monitoring”
4027 = “Reference model and dynamic following error monitoring activated, not possible at the same time”
4028 = “Sampling time parameter calculated incorrectly”
4029 = “Too many data sets requested”
4030 = “Error in runtime system, ratio of controller cycle clock to interpolator cycle clock incorrect”
4031 = “Error in time constant for emergency stop ramp generator (positionTimeConstant)”
4032 = “Feedforward control active, but fine interpolator type is DIRECT”
4033 = “Default data set outside limits”
4034 = “Maximum number of data sets not possible”
4035 = “Unknown data set alternating mode”
4036 = “Following error monitoring not activated/deactivated in all data sets”.
4037 = “Model reference monitoring not activated/deactivated in all data sets”.
4038 = “Different controller type in data sets”
4039 = “Feedforward control activated/deactivated in data sets”
4040 = “Time constant is 0”
4041 = “Error in dynamic adaptation parameter”
4042 = “System variable initialization could not be read”
4043 = “Driver simulation not implemented”
4044 = “Connection for stepper motors not implemented”
4045 = “Maximum velocity cannot be reached, maximum drive speed or a normalization factor incorrect”
4046 = “DSC requires motor encoder data to be specified”
4047 = “Drive or message frame type not suitable for DSC”
4048 = “Error in clamping monitoring parameter”. ’No identifier’ is not permitted for the fixed end stop identifier
4049 = “Without sensor, monitoring of the actual velocity by ’DynamicControl’ not possible”
4050 = “Inconsistent PROFIBUS parameterization; the sum of Ti and To is greater than one DP clock cycle”
4051 = “Error in manipulated variable limit parameter of force/pressure controller”
4052 = “Error in starting force/pressure monitoring parameter”
4053 = “Error in full-scale force/pressure monitoring parameter”
driveAxis
1-60� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
4054 = “Starting force/pressure monitoring tolerance less than tolerance of full-scale pressure monitoring”
4055 = “Error in force/pressure system deviation monitoring parameter”
4056 = “Different activation/deactivation of the control difference monitoring of the force/pressure controller not permitted in data sets”
4057 = “Different manipulated variable inversion of the force/pressure controller not permitted in data sets”
4058 = “Different force/pressure sensor types not permitted in data sets”
4059 = “Different activation/deactivation of the anti windup not permitted in data sets”
4060 = “Kd factor of the PID_ACTUAL controller is greater than 1”
4061 = “Time constant of the process model T1 <= T2”
4062 = “Illegal actuator type selection”
4063 = “Error in sliding friction compensation parameter”
4064 = “Error in offset application parameter”
4065 = “Feedforward control for force/pressure control not implemented”
4066 = “Error in standstill monitoring parameter”
4067 = “Following error monitoring: minVelocity must not be greater than or equal to maxVelocity”
4068 = “velocityTimeConstant when using a dead-time element for feedforward balancing too great”
4069 = “The system-related dead times are less than 0 after the calculation of additionalTime”
4070 = “Controller types not equal to DIRECT require the configuration of an encoder”
4071 = “Illegal values for delayTimeToActivate of the standstill signal”
4072 = “The IO device for the positive HW limit switch is not available”
4073 = “The IO device for the negative HW limit switch is not available”
4074 = “Limits of a controller parameter exceeded”
4075 = “Limit for emergency-stop-ramp brake delay exceeded”
4076 = “Limit for a substitute time constant exceeded”
4077 = “Limit for velocityTimeConstant exceeded”
4078 = “Error in value for configuration of QFDynamicData”
4079 = “Error in value for model reference monitoring”
4080 = “Error in following error monitoring parameter”
4081 = “Error in clamping monitoring parameter”
4082 = “Error in value for configuration of DynamicData”
4083 = “Error in value for configuration of PV controller”
4084 = “Incomplete configuration data for controller”
4085 = “Error in value for configuration of SystemDeadTimeData”
4086 = “Pressure control only possible with closed speed controller”
driveAxis
1-61� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
4087 = “DSC and compensation of valve characteristic not possible”
4088 = “DSC not possible on hydraulic axes”
4089 = “Time constant of dynamic compensation T1 <= T2”
4090 = “Incorrect value for correction of system dead time”
5000 = “Encoder data sequence and number of encoders do not match”
5001 = “Illegal number of additional sensors selected”
5002 = “Illegal additional sensor type selected”
5003 = “Illegal data in configuration of driver data for additional sensor”
5004 = “Illegal data in configuration of conversion data for additional sensor”
5006 = “Illegal data in configuration of range for additional sensor”
5007 = “Illegal data in configuration of filter time for additional sensor”
5008 = “Configuration of additional sensor not completed correctly”
5009 = “Illegal number for additional sensor in data set”
5010 = “Illegal data in configuration of differential pressure measurement”
5011 = “Error sensor A differential pressure measurement”
5012 = “Error sensor B differential pressure measurement”
5013 = “Illegal data in configuration of extrapolation”
5014 = “Illegal data in configuration of execution task for sensor TO”
5015 = “Illegal data in configuration of substitute value strategy for sensor TO technological alarm”
5020 = “Illegal data in configuration of driver data for analog sensor”
5021 = “Illegal data in configuration of position filter for analog sensor”
5022 = “Illegal data in configuration of conversion data for analog sensor”
5023 = “Illegal data in configuration of measurement input for analog sensor”
5030 = “Illegal data in configuration of conversion data for interval counter”
6000 = “In the configuration data, the monitoring of the positioning path isconfigured up to the reference-point switch, and the maximum path to be traveled in the process is configured as zero”
6001 = “Error in configuration data numberOfMaxBufferedCommandId”
6002 = “Error in configuration data numberOfQueueCommands”
6003 = “Error in configuration data numberOfImmediateCommands”
6004 = “Configuration of behaviourAtTheEndOfProfile not implemented”
6005 = “Illegal value for the configuration data maximum acceleration”
6006 = “Illegal value for the configuration data maximum jerk”
6007 = “Illegal value for the configuration data maximum force/pressure setpoint”
driveAxis
1-62� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
6008 = “Illegal value for the configuration data maximum force/pressure setpointrate of rise”
6009 = “Illegal value for the configuration data synchronous operation tolerance on the setpoint side”
6010 = “Illegal value for the configuration data synchronous operation tolerance on the actual-value side”
6011 = “Illegal value for the configuration data enable synchronous operationtolerance on the setpoint side”
6012 = “Illegal value for the configuration data enable synchronous operationtolerance on the actual-value side”
6013 = “Illegal value for the configuration data tolerance window end-of-profile detection”
6014 = “Illegal value for the configuration data extrapolation time actual values”
6015 = “Illegal value for the configuration data tolerance window actual-value coupling”
6016 = “Illegal value for the configuration data touchdown tolerance position limit”
6017 = “Illegal value for the configuration data handling mode position limit”
7000 = “Illegal data in configuration of a process model”
7001 = “Illegal data in configuration of the functional component >drive model<of a process model”
7002 = “Illegal data in configuration of the functional component >delay< of aprocess model”
7003 = “Illegal data in configuration of the functional component >shut down drive<of a process model”
7004 = “Illegal data in configuration of the functional component >encoder< of aprocess model”
7005 = “Illegal data in configuration of the functional component >switch< of aprocess model”
RemedyChange the configuration data.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
driveAxis
1-63� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
20012 Restart not executed (reason: /1/%d)
CauseTechnology object could not be restarted.
Meaning of alarm parameters
Reason:
1–The technology object configuration does not allow a restart with the restartsystem variable. You can initiate the restart using the reset command.
2–The technology object is not ready to be restarted.
3–A configured condition for restarting the technology object is not met (e.g.,technology object must be disabled).
4–Restart has not been executed or executed with the last programmedconfiguration of the technology object.
Remedy
� Work around the cause stated in the Reason parameter, or reload the project.
� Use the device diagnostics to establish whether technological alarms werereported and, if necessary, remedy the cause of the alarm.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
driveAxis
1-64� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
20014 At the logical address: /1/%d (optional log. address: /2/%d and bit no.: /3/%dof the enable output), a driver (type: /4/%d) could not be requested
CauseThe driver of a physical device is not available or is being used by another TO.
Meaning of alarm parameters
Logical address:
This is the address of the actuator driver configured on the technology object.
Logical address and bit number:
This specifies the address and bit number of the output enable bit.
Type:
1–Actuator driver
2–Encoder driver
3–BitRead driver
4–BitWrite driver
5–ByteRead driver
6–ByteWrite driver
7–WordRead driver
8–WordWrite driver
9–DWordRead driver
10–DWordWrite driver
Remedy
� Check that the logical device was available at the time of the request or whetherit was being used by another technology object.
� Connect a suitable device.
� Check the device (function, connections, terminals).
� Check the topological configuration in HWConfig.
� Compare configuration of HWConfig and technology object.
� Contact the hotline.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseRELEASE_DISABLE
Programmable local responsesRELEASE_DISABLE
driveAxis
1-65� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
30001 Illegal parameter (parameter index according to standard sequence in thesystem functions: /1/%d, command type: /4/%X)
CauseIllegal system function parameter, the command is aborted. The parameters indicate the position of the illegal system function parameteraccording to the standard sequence in the system functions and the command typeof an incorrectly entered parameter.
Meaning of alarm parameters
Parameter index:
Index of the first system function parameter that triggered this error (listedaccording to the standard sequence in the system functions).
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyChange the parameters.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
driveAxis
1-66� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
30002 Command aborted (reason: /1/%d, command type: /4/%X)
CauseExecution of the command was aborted before or during processing.This condition can arise as a result of loading a new command, resetting thecommand buffer, or an error state.
Meaning of alarm parameters
Reason:
1–Command buffer reset
2–Abort by another command
3–Aborted by a stop
4–Aborted by a higher-order stop
5–Abort by a pending error response
6–Aborted due to ambiguous commandId
7–Delayed acknowledgment
8–No actual value for axis (e.g., encoder or data bus not ready)
9–Aborted due to abnormal termination of a dependent command
10–Aborted due to active synchronous operation
11–Aborted due to active superimposed motion
12–Aborted due to active speed-controlled controller mode
13–Aborted due to active position-controlled controller mode
14–Aborted due to active motion to fixed end stop
15–Axis is not in pressure-limiting operation
16–Aborted due to active pressure-controlled operation
17–Aborted due to inactive pressure-controlled operation
18–Superimposed command is not permitted
19–Aborted due to error during cam access
20–Slave is not ready for operation
21–Error in slave synchronization
22–Aborted by command on slave
23–Aborted by stop on slave
24–Aborted by an active error response on the slave
25–No actual value for slave (e.g., encoder or data bus not ready)
26–Aborted by reset on slave
27–Master values are not valid
28–Active command in recursive TO interconnection
29–Aborted due to error during synchronization
30–Axis is in pressure-limiting operation
31–Maximum number of active commands exceeded
32–Aborted due to active correction command
33–Action only permissible in standstill
Command type:
Outputs the aborted command type. The command type is output as ahexadecimal integer value.
driveAxis
1-67� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
RemedyReset command via program.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
driveAxis
1-68� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
30003 Command aborted due to full command buffer (command type: /4/%X)
CauseThe command is not entered in the command buffer as the buffer is already full.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
Remedy
� Check the program flow.
� Typical cause: The ’nextCommand’ parameter is passed with the valueIMMEDIATELY. You need to synchronize the command sequence manually oruse another value for ’nextCommand’.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
driveAxis
1-69� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
30004 Unknown command (command type: /4/%X)
CauseThe active software tool does not support this command.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyCheck the versions of the engineering system and the runtime software.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
driveAxis
1-70� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
30005 Ambiguous commandId (number of commands with specified ID: /1/%d,command type: /4/%X)
CauseThe specified commandID refers to several commands.The specified action is performed for the command matching the specifiedcommandID that has been in the interpolator for the longest time. If nocorresponding command is found in the interpolator, the action refers to the nextcommand loaded in the interpolator.
Meaning of alarm parameters
Number of commands with specified ID:
Number of commands referenced by the specified commandId.
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyUse different commandIds for commands that are active simultaneously.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
driveAxis
1-71� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
30006 Cannot execute command due to current object state (command type: /4/%X)
CauseThe object is in the stop, error, or reset state and the command is not possible inthis object state.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
Remedy
� Check the object status.
� Check the permissible sequence of commands.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
driveAxis
1-72� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
30007 The error cannot be reset due to its configuration
CauseThe alarm cannot be acknowledged at the present time or by the selected means.
Remedy
� Check the configured acknowledgment procedure.
� If necessary, change the acknowledgment procedure for the alarm.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
driveAxis
1-73� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
30008 A connection to a technology object required for this operation does notexist (command type: /4/%X)
CauseThe object connection required for this operation has not been configured.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyCheck the project configuration, or change the object connection in the command.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
driveAxis
1-74� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
30009 Command rejected due to suspension of command decoding on addressedtechnology object (command type: /4/%X)
CauseCommand was rejected due to suspension of command decoding on theaddressed technology object.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
Remedy
� Check why the command was rejected.
� If necessary, acknowledge any active errors once you have corrected the causeof the error.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
driveAxis
1-75� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
30010 Command not available (command type: /4/%X)
CauseThe command is not available in this version of the runtime software.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyCheck the version of the runtime software.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
driveAxis
1-76� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
30011 Parameter unavailable (parameter index according to standard sequence inthe system functions: /1/%d, command type: /4/%X)
CauseThe parameter is not available in this version of the runtime software, thecommand is therefore rejected. The parameters indicate the position according tothe standard sequence in the system functions and the command type of anincorrectly entered parameter.
Meaning of alarm parameters
Parameter index:
Index of the command parameter triggering this error according to the standardsequence in the system functions.
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyCheck the version of the runtime software.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
driveAxis
1-77� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
30012 Command cannot be started synchronously (command type: /4/%X)
CauseThe command cannot be used during a BEGIN_SYNC, END_SYNC sequencebecause it is a reset command or a command that has only one return value in theuser program.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyDo not use this command type during a BEGIN_SYNC, END_SYNC sequence.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
driveAxis
1-78� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
30013 Synchronous start of the command using IMMEDIATELY mergeMode(command type: /4/%X)
CauseWith synchronous command start, only merge modes that immediately override thecurrent command (IMMEDIATELY) and superimpose the current command(SUPERIMPOSED_MOTION_MERGE) can be used. If an illegal merge mode isprogrammed (e.g., SEQUENTIAL or NEXT_MOTION), the system automaticallychanges the merge mode to IMMEDIATELY and outputs this warning.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyProgram the command, which is to be started synchronously to immediatelyoverride the current command. To do this, enter the value IMMEDIATELY in the’mergeMode’ command parameter.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
driveAxis
1-79� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
30014 Coordinate system not offset due to the internal traversing range limit beingexceeded (Parameter1: /1/% /1/%d, command type: /2/%X)
CauseThe programmed coordinate system offset causes the internal traversing rangelimit to be exceeded. The coordinate system is not shifted.
Meaning of alarm parameters
Parameter1:
= 0 negative internal traversing range limit
= 1 positive internal traversing range limit
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyCheck the programming for the coordinate system offset.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
driveAxis
1-80� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
30015 A technology required for this command was not configured (technology:/1/%d, command type: /4/%X)
CauseThe command cannot be selected in this technology object configuration.
Meaning of alarm parameters
Technology:
= 1 Axis with force/pressure control without flow/force specification= 2 Axis with force/pressure control and flow/force specification= 3 Axis without flow/force specification= 4 Axis with flow/force specification= 5 Axis with force specification= 6 Axis with pressure setpoint specification= 7 Axis with pressure limiting= 8 Axis with speed limiting parallel to force/pressure control= 9 Axis with flow specification
Command type:Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyActivate the technology needed for the command.
Technology:= 1 Select the mode setting REAL_AXIS_WITH_PRESSURE_CONTROL in theTypeOfAxis configuration data= 2 Select the mode settingREAL_QP_AXIS_WITH_CLOSED_LOOP_FORCE_CONTROL in theTypeOfAxis configuration data= 3 Select the mode setting VIRTUAL_AXIS, REAL_AXIS orREAL_AXIS_WITH_FORCE_CONTROL in the TypeOfAxis configuration data= 4 Select the mode setting EAL_QPAXIS,REAL_QP_AXIS_WITH_OPEN_LOOP_FORCE_CONTROL orREAL_QP_AXIS_WITH_CLOSED_LOOP_FORCE_CONTROL in theTypeOfAxis configuration data= 5 Select the mode settingREAL_QP_AXIS_WITH_OPEN_LOOP_FORCE_CONTROL in the TypeOfAxisconfiguration data= 6 Select the mode setting REAL_AXIS_WITH_PRESSURE_CONTROL orREAL_QP_AXIS_WITH_CLOSED_LOOP_FORCE_CONTROL in theTypeOfAxis configuration data= 7 Select the mode setting REAL_AXIS_WITH_PRESSURE_CONTROL,REAL_QP_AXIS_WITH_OPEN_LOOP_FORCE_CONTROL orREAL_QP_AXIS_WITH_CLOSED_LOOP_FORCE_CONTROL in theTypeOfAxis configuration data= 8 Select the mode settingREAL_QP_AXIS_WITH_CLOSED_LOOP_FORCE_CONTROL in theTypeOfAxis configuration data= 9 Select a mode setting with flow specification in the TypeOfAxis configurationdata
driveAxis
1-81� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
40001 Illegal state change on axis
CauseCommand for change of axis state could not be performed, because:1. The operating status phase is not complete.2. The operational transition is not possible.
RemedyFor 1.: Repeat command.For 2.: A reset must be performed first
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
driveAxis
1-82� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
40002 Programmed velocity is limited
Cause1. The system is limiting the programmed velocity to the maximum permissibleparameter.2. For a virtual axis, the velocity is limited to a value that reliably identifies thedirection, that is, the velocity of the axis must not exceed that at which, dependingon the IPO task, at least one measured value can be detected in the range ofone-half modulo length.
RemedyNot necessary, for information only.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
driveAxis
1-83� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
40003 Programmed acceleration (type: /1/%d) is limited
CauseThe system is limiting the programmed acceleration to the maximum limit.
Meaning of alarm parameters
Type:
0 – positive acceleration
1 – negative acceleration/deceleration
RemedyNot necessary, for information only.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
driveAxis
1-84� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
40004 Programmed jerk (type: /1/%d) is limited
CauseThe system is limiting the programmed jerk to the maximum limit.
Meaning of alarm parameters
Type:
0 – Increase in positive acceleration
1 – Reduction in positive acceleration
2 – Increase in negative acceleration/deceleration
3 – Reduction in negative acceleration/deceleration
RemedyNot necessary, for information only.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
driveAxis
1-85� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
40005 Enable signal(s) missing (Parameter1: /1/%X) and/or incorrect mode(Parameter2: /2/%d)
CauseThe enables are missing and/or follow-up mode is active on the axis are missing when a command is pending.
Meaning of alarm parameters
Parameter1:
Bit 1 = 0: POWER enable signal is available1: POWER enable signal is missing
Bit 2 = 0: DRIVE enable signal is available1: DRIVE enable signal is missing
Bit 3 = 0: Position controller enable signal is available1: Position controller enable signal is missing
Bit 4 = 0: Force/pressure controller enable signal is available1: Force/pressure controller enable signal is missing
Parameter2:
0 – Follow-up mode deselected
1 – Follow-up mode selected
RemedyActivate the enable signals before issuing a motion command.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseFEEDBACK_EMERGENCY_STOP
Programmable local responsesFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
driveAxis
1-86� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
40006 Programmed velocity is zero
CauseThe programmed velocity is zero. The specified motion cannot be executed.
RemedyProgram a value not equal to zero. If USER_DEFAULT is referenced, a value notequal to zero must be programmed in the assigned system variable.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseFEEDBACK_EMERGENCY_STOP
Programmable local responsesFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
40007 Programmed acceleration (type: /1/%d) is zero
CauseThe programmed acceleration is zero. The specified motion cannot be executed.
Meaning of alarm parameters
Type:
0 – positive acceleration
1 – negative acceleration/deceleration
RemedyProgram a value not equal to zero. If USER_DEFAULT is referenced, a value notequal to zero must be programmed in the assigned system variable.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseFEEDBACK_EMERGENCY_STOP
Programmable local responsesFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
driveAxis
1-87� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
40008 Programmed jerk (type: /1/%d) is zero
CauseThe programmed jerk is zero. The specified motion cannot be executed.
Meaning of alarm parameters
Type:
0 – Increase in positive acceleration
1 – Reduction in positive acceleration
2 – Increase in negative acceleration/deceleration
3 – Reduction in negative acceleration/deceleration
RemedyProgram a value not equal to zero. If USER_DEFAULT is referenced, a value notequal to zero must be programmed in the assigned system variable.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseFEEDBACK_EMERGENCY_STOP
Programmable local responsesFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
40009 Velocity limit is zero
CauseThe programmed velocity is zero. The specified motion cannot be executed.
RemedyProgram a value not equal to zero in the dynamic limit values.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseFEEDBACK_EMERGENCY_STOP
Programmable local responsesFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
driveAxis
1-88� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
40010 Acceleration limit (type: /1/%d) is zero
CauseThe programmed acceleration limit is zero. The specified motion cannot beexecuted.
Meaning of alarm parameters
Type:
0 – positive acceleration
1 – negative acceleration/deceleration
RemedyProgram a value not equal to zero.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseFEEDBACK_EMERGENCY_STOP
Programmable local responsesFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
40011 Programmed jerk limit (type: /1/%d) is zero
CauseThe programmed jerk is zero. The specified motion cannot be executed.
Meaning of alarm parameters
Type:
0 – Increase in positive acceleration
1 – Reduction in positive acceleration
2 – Increase in negative acceleration/deceleration
3 – Reduction in negative acceleration/deceleration
RemedyProgram a value not equal to zero.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseFEEDBACK_EMERGENCY_STOP
Programmable local responsesFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
driveAxis
1-89� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
40012 Dynamic restrictions (type: /1/%d) violated
CauseThe specified dynamic restrictions have been violated. This can occur due to:
� Programming of new jerk-controlled motions with extremely divergent dynamicparameters, which would lead to an additional reversing motion, reducing thecurrent acceleration.
� Programming of superimposed motions exceeding the resulting dynamicparameters, which would lead to overshoot or to a reversing motion whenrestricted to the maximum velocity or when entering final velocity.
One or more physical variables (velocity, acceleration, jerk) may be affected. The violations have only a temporary effect.
Meaning of alarm parameters
Type:
0 – The jerk is changed; the jerk limit is exceeded.
1 – The jerk limit is disabled during jerk-controlled motion.
2 – The acceleration is changed; the acceleration limit is exceeded.
3 – The acceleration is changed, and the jerk limit is disabled. The accelerationlimit is exceeded.
Remedy
� For new motion: Increase the dynamic response parameters.
� For superimposed motion: Allow for the current (resulting) limitations whenprogramming the dynamic response parameters.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
driveAxis
1-90� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
40013 Programmed stop time restricted by acceleration limits
CauseThe specified stop time cannot be achieved. It is violated due to the maximumacceleration limits. Deceleration is performed with the maximum values.
Remedy
� Increase the programmed time.
� Check the maximum acceleration and the active programmed limits.
� Increase the limits if necessary.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
driveAxis
1-91� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
40014 Command not possible on virtual axis (command type: /4/%X)
CauseThe command is not supported by virtual axes.
RemedyUse a real axis.
Acknowledgment / responseReset fault memory / NONE
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
40015 Error in accessing specified cam
CauseThe specified cam does not exist or is not connected with synchronous operation,or the cam is already active.
Remedy
� Check the programmed cam.
� Check the synchronous operation connection with the cam.
� Check the program sequence.
Acknowledgment / responseReset fault memory / NONE
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
driveAxis
1-92� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
40016 The specified cam has not been interpolated
CauseThe system only accepts verified and interpolated cams for this operation. Thespecified cam has not yet been interpolated.
RemedyCheck whether the specified cam has been interpolated.
Acknowledgment / responseReset fault memory / NONE
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
40017 Cam start point outside definition range
CauseThe addressed cam start point is outside the definition range of the cam.
Remedy
� Check the definition range of the cam.
� Check the cam start point.
Acknowledgment / responseReset fault memory / NONE
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
driveAxis
1-93� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
40018 Dynamic response of motion profiles (type: /1/%d) violated (reason: /2/%d)
CauseThe specified dynamic response cannot be achieved.
Meaning of alarm parameters
Type:
1 – Velocity-time profile
2 – Position-time profile
3 – Velocity-position profile
4 – Velocity-interface position profile
5 – Velocity-time limit profile
6 – Velocity-position limit profile
7 – Velocity-interface position limit profile
Reason:
0 – The velocity resulting form the profile has been limited to the programmedvalue.
1 – The acceleration/deceleration resulting from the profile has been limited to theprogrammed value.
Remedy
� For superimposed motion: Allow for the current (resulting) limitations when programming the dynamicresponse parameters.
� Increase the dynamic response parameters.
Acknowledgment / responseReset fault memory / NONE
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
driveAxis
1-94� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
40019 Error while accessing the motion interface
CauseThe specified reference object for the motion interface does not exist or is notconnected to the axis.
Remedy
� Check the programmed input interconnection.
� Check the program sequence.
Acknowledgment / responseReset fault memory / NONE
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
driveAxis
1-95� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
40020 Dynamic response of the setpoints on the motion interface (type: /1/%d)violated (reason: /2/%d)
CauseThe specified dynamic response cannot be achieved.
Meaning of alarm parameters
Type:
1 – Velocity-based setpoints
2 – Position-based setpoints
Reason:
0 – The velocity resulting form the interface has been limited to the programmedvalue.
1 – The acceleration/deceleration resulting from the interface has been limited tothe programmed value.
Remedy
� For superimposed motion: Allow for the current (resulting) limitations when programming the dynamicresponse parameters.
� Increase the dynamic response parameters.
Acknowledgment / responseReset fault memory / NONE
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
driveAxis
1-96� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
40021 StopEmergency command abort due to a pending stop response of the sameor higher priority
CauseThe StopEmergency command on the axis was aborted when called or while activedue to a stop response of the same or higher priority, resulting from anerror.The alarm is generated as an additional aid for emergency stop strategies, and canfor example ensure a safe program sequence by changing the stop response.
Remedy
Acknowledgment / responseReset fault memory / NONE
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
driveAxis
1-97� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
40022 Programmed pressure limiting is limited
CauseThe system is limiting the pressure limiting value to the maximum limit.
RemedyNot necessary, for information only.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
driveAxis
1-98� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
40023 Programmed increase in pressure limiting limited
CauseThe system is limiting the pressure limiting increase to the maximum limit.
RemedyNot necessary, for information only.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
40024 Programmed increase in pressure limiting is zero
CauseThe programmed increase in pressure limiting limit is zero. The specified pressurelimiting characteristic cannot be calculated.
RemedyProgram a value not equal to zero. If USER_DEFAULT is referenced, a value notequal to zero must be programmed in the assigned system variable.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseMOTION_EMERGENCY_ABORT
Programmable local responsesMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
driveAxis
1-99� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
40025 Maximum increase in pressure limiting is zero
CauseThe limit value for the pressure limiting increase is zero. The specified pressurelimiting characteristic cannot be calculated.
RemedyProgram a value not equal to zero in the dynamic limit values.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseMOTION_EMERGENCY_ABORT
Programmable local responsesMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
driveAxis
1-100� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
40026 Dynamic response of pressure/pressure limiting profiles (type: /1/%d)violated (reason: /2/%d)
CauseThe specified dynamic response cannot be achieved.
Meaning of alarm parameters
Type:
1 – Pressure-time limit profile
2 – Pressure-position limit profile
3 – Pressure-interface position limit profile
4 – Pressure-time profile
5 – Pressure-position profile
6 – Pressure-interface position profile
Reason:
0 – The pressure/pressure limiting value resulting from the profile has been limitedto the maximum pressure/pressure limiting value.
1 – The pressure/pressure limiting increase value resulting from the profile hasbeen limited to the maximum pressure/pressure limiting increase value.
Remedy
� Increase the dynamic response parameters.
Acknowledgment / responseReset fault memory / NONE
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
driveAxis
1-101� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
50001 Drive failure
CauseDrive fault.
RemedyCheck the configuration of the drive system, the cabling, and the power supply.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseRELEASE_DISABLE
Programmable local responsesRELEASE_DISABLE
50002 Limiting frequency of measuring system exceeded
CauseThe limiting frequency of the encoder has been exceeded.
Remedy
� Check the encoder connection.
� Check the maximum velocity limits in the configuration data.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
driveAxis
1-102� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
50003 Speed acceleration setpoint limitation active
CauseThe speed acceleration setpoint is limited.
Remedy
� Check the mechanical configuration.
� Check the encoder connection.
� Check the configuration of the speed setpoint interface.
� Check the maximum permissible acceleration rates in the configuration data.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
driveAxis
1-103� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
50005 Speed setpoint monitoring active (Parameter1: /1/%d)
CauseThe speed setpoint is limited.
Remedy
� Check the mechanical configuration.
� Check the encoder connection.
� Check the configuration of the speed setpoint interface.
� Check the maximum permissible velocities in the configuration data.
Parameter 1: Specification of limitation1–Limitation of the velocity-related definition range (on hydraulic axes beforethe cam) reached.2–Limitation of the value range (hydraulic axes only) reached.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
driveAxis
1-104� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
50006 Zero mark monitoring
CauseThe zero mark monitoring system has responded.
Remedy
� Check the mechanical configuration and the encoder configuration.
� Check the encoder error messages.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseOPEN_POSITION_CONTROL
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
driveAxis
1-105� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
50007 Hardware limit switch (Parameter1: /1/%d, Parameter2: /2/%d)
CauseHardware limit switch has been violated.
Meaning of alarm parameters
Parameter1:
1: Limit switch reached
2: Polarity reversal on limit switch (can only be deleted by reconfiguring thetechnology object or Power On)
3: Illegal retraction direction
4: Both limit switches are active
Parameter2:
0: Not relevant
1: Limit switch in positive traversing direction
2: Limit switch in negative traversing direction
Remedy
� Check the mechanical configuration.
� Check the limit switches.
� If an error has occurred in the program, change the program or use the softwarelimit switches.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseRELEASE_DISABLE
Programmable local responsesFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
driveAxis
1-106� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
50008 Timeout waiting for standstill signal
CauseTimeout occurred while waiting for standstill signal.
Remedy
� Check the configuration of ’Axis.TypeOfAxis.StandStillSignal’.
� Check that the control loop is operating correctly.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseRELEASE_DISABLE
Programmable local responsesOPEN_POSITION_CONTROLRELEASE_DISABLE
50009 Limit switch active: (Parameter1: /1/%d) only one traversing directionpossible
CauseA positive (Parameter1 = 1) or negative (Parameter1 = 2) hardware limit switch isactive or has been crossed. Motion is possible in the positive or negative traversing direction only.
Remedy
� Check the mechanical configuration.
� Check the limit switches.
� If an error has occurred in the program, change the program or use the softwarelimit switches.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONE
driveAxis
1-107� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
50010 Error while reading or writing data set (category: /1/%d, error number: /2/%d)
CauseAn error occurred while reading or writing.
Meaning of alarm parameters
Category: Area in which the error occurred.
1–Command decoding
2–Interpolator
3–Controller
4–Manipulated variable output
5–Encoder system
Error number: Specification of error
1000 = “General configuration error”
2000 = “Error in actuator system configuration”
2001 = “Outside of limits of manipulated variable”
2003 = “Error in load gear ratios”
2004 = “Error in maximum velocity”
2005 = “Maximum velocity greater than maximum attainable velocity”
2006 = “Drive not suitable for torque-controlled or torque-limited operation”
2007 = “Linear stepper motor not implemented”
2008 = “Right-aligned format for direct output not implemented”
2009 = “Illegal value in resolution for direct output”
2010 = “Missing configuration data for actuator system”
2011 = “Missing configuration data for additional actuator system”
2012 = “The backstop range (min to max) does not contain a zero point”
2014 = “Drive or message frame not suitable for torque superimposition”
2015 = “Gear ratios less than or equal to 0”
2016 = “Resolution for stepper motor is 0”
2017 = “Illegal value for the configuration data maxSpeed”
2018 = “Illegal value for the configuration data maxVelocity”
2019 = “Limits of a configuration data exceeded”
2020 = “Limits for the max. acceleration exceeded”
2021 = “Illegal values for dead-zone compensation”
2022 = “Illegal values for sliding-friction compensation”
2023 = “Illegal values for backstop range”
2024 = “Error in sliding-friction compensation parameter”
3000 = “Error in encoder system”
3001 = “Error in encoder system”
3002 = “Invalid axis type selected”
3003 = “Leadscrew pitch is 0”
3004 = “Modulo axis selected with modulo value less than or equal to 0”
driveAxis
1-108� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
3005 = “Illegal specification(s) in the encoder data (incremental / absolute, etc.)”
3006 = “Illegal number of encoders selected”
3007 = “Illegal incremental encoder number”
3008 = “Illegal data combination for homing with incremental encoder”.
3009 = “Illegal encoder number”
3010 = “Illegal data on SSI encoder”
3011 = “Illegal encoder number”
3012 = “Illegal encoder number”
3013 = “Illegal measuring gear data, DRIVE assembly type (e.g., factor = 0)”
3014 = “Illegal encoder number”
3015 = “Illegal measuring gear data, LOAD assembly type (e.g., factor = 0)”
3016 = “Illegal data set number (e.g., factor = 0)”
3017 = “Encoder data sequence and number of encoders do not match”
3018 = “Error in encoder system”
3019 = “Illegal encoder number”
3020 = “Illegal encoder system / actuator system simulation selected”.
3021 = “Illegal encoder number or incorrect number of data sets”
3022 = “Illegal encoder number or incorrect number of data sets”
3023 = “Illegal data for ratio of external attachment (e.g., factor = 0)”
3024 = “Path/rotation of external attachment = 0”
3025 = “Illegal value for monitoring of actual velocity”
3026 = “Illegal encoder number in SSI encoder configuration”
3027 = “Illegal message format in SSI encoder configuration”
3028 = “Illegal baud rate in SSI encoder configuration”
3029 = “Illegal SSI state in SSI encoder configuration”
3030 = “Illegal encoder number in data set”
3031 = “Encoder number in data set not configured”
3032 = “Illegal numerator factor in data set”
3033 = “Illegal denominator factor in data set”
3034 = “Illegal data set number”
3035 = “Data set number not configured”
3036 = “Encoder not configured”
3037 = “Homing of ENDAT encoder with zero mark not possible”
3038 = “Homing of CAM negative edge onboard not possible”
3039 = “On-the-fly homing of ENDAT encoder with zero mark not possible”
3040 = “On-the-fly homing of CAM negative edge onboard not possible”
3041 = “Factors for adjusting encoder data to the mechanics are outside the permissible range of values”
3042 = “Illegal data combination for homing with external encoder”
3043 = “The incremental position of the encoder is outside the permissible range of values”.
driveAxis
1-109� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
3044 = “The incremental position of the encoder is outside the permissible range of values”
3045 = “Illegal value for resolution of linear measuring system”3046 = “Illegal value for filter of actual-velocity encoder”3047 = “Illegal value for smoothing of actual-value encoder”3048 = “Illegal value for smoothing of actual-value encoder with actual-value
coupling”3049 = “Illegal DSC encoder selection”3050 = “Configuration of encoder system not completed correctly”3051 = “Error in configuration of the sensor data or the stepper motor”3052 = “Actual-value type (position, interval, velocity) not implemented”3053 = “Only homing with CAM possible for stepper motor”3054 = “Only on-the-fly homing with CAM possible for stepper motor”3055 = “Stepper motor only possible with a real axis”3056 = “Only one encoder permissible with stepper motor”3057 = “DSC encoder is not a DP encoder”3058 = “Illegal message frame of the DSC encoder”3059 = “Modulo value too small”3060 = “Configuration differential measurement position faulty”3061 = “Illegal data in range configuration of the differential measurement position”4000 = “Error in controller”4001 = “Negative acceleration specified”4002 = “Unknown ’FipoType’ requested”4003 = “Error in runtime system, ratio of controller cycle clock to interpolator
cycle clock incorrect”4004 = “Requested filter arrangement not possible”4005 = “Reserve for later use”4006 = “Maximum limit is lower than minimum”4007 = “Reserve for later use”4008 = “Error in configuration data for controller”4009 = “Reserve for later use”4010 = “Reserve for later use”4011 = “Reserve for later use”4012 = “Reserve for later use”4013 = “Requested controller type is not available”4014 = “Error in controller factors”4015 = “Feedforward control activated, kpc < 0 or kpc > 150”4016 = “Reserve for later use”4017 = “Reserve for later use”4018 = “Reserve for later use”4019 = “Reserve for later use”4020 = “Reserve for later use”4021 = “Reserve for later use”4022 = “Reserve for later use”
driveAxis
1-110� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
4023 = “Feedforward control activated, kpc <= 0”
4024 = “Model reference monitoring: Error in value of tolerance window”
4025 = “Error in limit value for standstill signal”
4026 = “Error in parameter for positioning monitoring”
4027 = “Reference model and dynamic following error monitoring activated, not possible at the same time”
4028 = “Sampling time parameter calculated incorrectly”
4029 = “Too many data sets requested”
4030 = “Error in runtime system, ratio of controller cycle clock to interpolator cycle clock incorrect”
4031 = “Error in time constant for emergency stop ramp generator (positionTimeConstant)”
4032 = “Feedforward control active, but fine interpolator type is DIRECT”
4033 = “Default data set outside limits”
4034 = “Maximum number of data sets not possible”
4035 = “Unknown data set alternating mode”
4036 = “Following error monitoring not activated/deactivated in all data sets”.
4037 = “Model reference monitoring not activated/deactivated in all data sets”.
4038 = “Different controller type in data sets”
4039 = “Feedforward control activated/deactivated in data sets”
4040 = “Time constant is 0”
4041 = “Error in dynamic adaptation parameter”
4042 = “System variable initialization could not be read”
4043 = “Driver simulation not implemented”
4044 = “Connection for stepper motors not implemented”
4045 = “Maximum velocity cannot be reached, maximum drive speed or a normalization factor incorrect”
4046 = “DSC requires motor encoder data to be specified”
4047 = “Drive or message frame type not suitable for DSC”
4048 = “Error in clamping monitoring parameter’No identifier’ is not permitted for the fixed end stop identifier”
4049 = “Without sensor, monitoring of the actual velocity by ’DynamicControl’ not possible”
4050 = “Inconsistent PROFIBUS parameterization; the sum of Ti and To is greater than one DP clock cycle”
4051 = “Error in manipulated variable limit parameter of force/pressure controller”
4052 = “Error in starting force/pressure monitoring parameter”
4053 = “Error in full-scale force/pressure monitoring parameter”
4054 = “Starting force/pressure monitoring tolerance less than tolerance of full-scale pressure monitoring”
4055 = “Error in force/pressure system deviation monitoring parameter”
driveAxis
1-111� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
4056 = “Different activation/deactivation of the control difference monitoring of the force/pressure controller not permitted in data sets”
4057 = “Different manipulated variable inversion of the force/pressure controller not permitted in data sets”
4058 = “Different force/pressure sensor types not permitted in data sets”
4059 = “Different activation/deactivation of the anti windup not permitted in data sets”
4060 = “Kd factor of the PID_ACTUAL controller is greater than 1”
4061 = “Time constant of the process model T1 <= T2”
4062 = “Illegal actuator type selection”
4063 = “Error in sliding friction compensation parameter”
4064 = “Error in offset application parameter”
4065 = “Feedforward control for force/pressure control not implemented”
4066 = “Error in standstill monitoring parameter”
4067 = “Following error monitoring: minVelocity must not be greater than or equal to maxVelocity”
4068 = “velocityTimeConstant when using a dead-time element for feedforward balancing too great”
4069 = “The system-related dead times are less than 0 after the calculation of additionalTime”
4070 = “Controller types not equal to DIRECT require the configuration of an encoder”
4071 = “Illegal values for delayTimeToActivate of the standstill signal”
4072 = “The IO device for the positive HW limit switch is not available”
4073 = “The IO device for the negative HW limit switch is not available”
4074 = “Limits of a controller parameter exceeded”
4075 = “Limit for emergency-stop-ramp brake delay exceeded”
4076 = “Limit for a substitute time constant exceeded”
4077 = “Limit for velocityTimeConstant exceeded”
4078 = “Error in value for configuration of QFDynamicData”
4079 = “Error in value for model reference monitoring”
4080 = “Error in following error monitoring parameter”
4081 = “Error in clamping monitoring parameter”
4082 = “Error in value for configuration of DynamicData”
4083 = “Error in value for configuration of PV controller”
4084 = “Incomplete configuration data for controller”
4085 = “Error in value for configuration of SystemDeadTimeData”
4086 = “Pressure control only possible with closed speed controller”
4087 = “DSC and compensation of valve characteristic not possible”
4088 = “DSC not possible on hydraulic axes”
4089 = “Time constant of dynamic compensation T1 <= T2”
driveAxis
1-112� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
4090 = “Incorrect value for correction of system dead time”
5000 = “Encoder data sequence and number of encoders do not match”
5001 = “Illegal number of additional sensors selected”
5002 = “Illegal additional sensor type selected”
5003 = “Illegal data in configuration of driver data for additional sensor”
5004 = “Illegal data in configuration of conversion data for additional sensor”
5006 = “Illegal data in configuration of range for additional sensor”
5007 = “Illegal data in configuration of filter time for additional sensor”
5008 = “Configuration of additional sensor not completed correctly”
5009 = “Illegal number for additional sensor in data set”
5010 = “Illegal data in configuration of differential pressure measurement”
5011 = “Error sensor A differential pressure measurement”
5012 = “Error sensor B differential pressure measurement”
5013 = “Illegal data in configuration of extrapolation”
5014 = “Illegal data in configuration of execution task for sensor TO”
5015 = “Illegal data in configuration of substitute value strategy for sensor TO technological alarm”
5020 = “Illegal data in configuration of driver data for analog sensor”
5021 = “Illegal data in configuration of position filter for analog sensor”
5022 = “Illegal data in configuration of conversion data for analog sensor”
5023 = “Illegal data in configuration of measurement input for analog sensor”
5030 = “Illegal data in configuration of conversion data for interval counter”
6000 = “In the configuration data, the monitoring of the positioning path isconfigured up to the reference-point switch, and the maximum path to be traveled in the process is configured as zero”
6001 = “Error in configuration data numberOfMaxBufferedCommandId”
6002 = “Error in configuration data numberOfQueueCommands”
6003 = “Error in configuration data numberOfImmediateCommands”
6004 = “Configuration of behaviourAtTheEndOfProfile not implemented”
6005 = “Illegal value for the configuration data maximum acceleration”
6006 = “Illegal value for the configuration data maximum jerk”
6007 = “Illegal value for the configuration data maximum force/pressure setpoint”
6008 = “Illegal value for the configuration data maximum force/pressure setpointrate of rise”
driveAxis
1-113� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
6009 = “Illegal value for the configuration data synchronous operation tolerance on the setpoint side”
6010 = “Illegal value for the configuration data synchronous operation tolerance on the actual-value side”
6011 = “Illegal value for the configuration data enable synchronous operationtolerance on the setpoint side”
6012 = “Illegal value for the configuration data enable synchronous operationtolerance on the actual-value side”
6013 = “Illegal value for the configuration data tolerance window end-of-profile detection”
6014 = “Illegal value for the configuration data extrapolation time actual values”
6015 = “Illegal value for the configuration data tolerance window actual-valuecoupling”
6016 = “Illegal value for the configuration data touchdown tolerance position limit”
6017 = “Illegal value for the configuration data handling mode position limit”
7000 = “Illegal data in configuration of a process model”
7001 = “Illegal data in configuration of the functional component >drive model< of a process model”
7002 = “Illegal data in configuration of the functional component >delay< of a process model”
7003 = “Illegal data in configuration of the functional component >shut down drive< of a process model”
7004 = “Illegal data in configuration of the functional component >encoder< of a process model”
7005 = “Illegal data in configuration of the functional component >switch< of a process model”
8000 = “General error when reading or writing data set”
8001 = “The selected data set number is not available”
8002 = “Cannot write the active data set”
8003 = “Changing the controller structure (by writing a data set) is not possible”
driveAxis
1-114� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
Remedy
Change data record parameter.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
driveAxis
1-115� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
50011 Limit range of the incremental actual value exceeded (Parameter1: /1/%d)
CauseThe limit range of the incremental actual value has been exceeded.
Meaning of alarm parameters
Parameter1:
1: Range exceeded in positive direction
2: Range exceeded in negative direction
4: The modified actual position is greater than the modulo length in one positioncontrol cycle clock.
Remedy
Check and adjust the configuration data used for adjusting the actual value to themechanics.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseRELEASE_DISABLE
Programmable local responsesRELEASE_DISABLE
driveAxis
1-116� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
50012 Drive does not support the selected function (Parameter1: /1/%d)
CauseError in selected function.
Meaning of alarm parameters
Parameter1:
1: The travel to home position function cannot be performed.
Remedy
Check and adjust the configuration data and the drive settings.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseRELEASE_DISABLE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
driveAxis
1-117� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
50013 Overshoot/undershoot of permissible range limits (logical address: /1/%d,reason: /2/%d)
CauseRange violation for additional sensor.
Meaning of alarm parameters
Logical address: Address configured on the technology object.
Reason:
1: Value greater than maximum permissible value.
2: Value smaller than minimum permissible value.
3: Positive overflow of sensor range.
4: Negative overflow of sensor range.
5: Error in accessing hardware address.
Remedy
� Check and adjust the configuration data.
� Check the sensor connection.
� Check the wiring.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseRELEASE_DISABLE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
driveAxis
1-118� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
50014 Permissible system deviation of pressure controller exceeded
CausePermissible system deviation of pressure controller exceeded.
RemedyCheck for correct functioning of the pressure control loop.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseRELEASE_DISABLE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
50015 Level overflow of IPO not detected
CauseThe system could not intercept a level overflow.
RemedyPlease contact Siemens Support with the error number indicated above.
Acknowledgment / responsePower On / STOP
Default setting for local responseRELEASE_DISABLE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
driveAxis
1-119� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
50016 Backstop limitation active
CauseThe speed setpoint is limited by the backstop.
Remedy
� Check the mechanical configuration.
� Check the encoder connection.
� Check the configuration of the speed setpoint interface.
� Check the maximum permissible backstop values in the configuration data.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
driveAxis
1-120� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
50017 Manipulated variable monitoring active at Q/F output (Parameter1: /1/%d)
CauseThe manipulated variable is limited.
Remedy
� Check the configuration of the valve characteristic.
� Check the maximum permissible velocity or the maximum permissible force/pressure setpoint in the configuration data.
� Check the encoder connection.
� Check the configuration of the setpoint interface.
Parameter 1: Specification of limiting1–Monitoring active at Q output.2–Monitoring active at F output.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
driveAxis
1-121� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
50101 Reference model monitoring window exceeded
CauseThe dynamic demands on the control loop are too high.
Remedy
� Check the encoder count direction.
� Check the control loop parameter assignment.
� Change the parameter assignment for following error monitoring.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseRELEASE_DISABLE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
50109 Starting force window monitoring error
CauseThe axis could not reach the starting force window in the specified time.
Remedy
� Check the control loop parameter assignment.
� Check the parameter assignment for monitoring.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseFEEDBACK_EMERGENCY_STOP
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
driveAxis
1-122� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
50110 Full-scale force monitoring error
CauseThe axis has left the full-scale force window or could not reach the window in thespecified time.
Remedy
� Check that the control loop is operating correctly.
� Check the parameter assignment for monitoring.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseFEEDBACK_EMERGENCY_STOP
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
50111 Pressure controller is operating at the limit
CauseThe manipulated variable required by the force controller cannot be implementedand is limited.
Remedy
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
2-123� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
outputCamType
Possible local responses
NONENo response
DECODE_STOPAbort command processing
OUTPUT_CAM_DISABLEStop and abort all commands
20001 Internal error (Parameter1: /1/%d, Parameter2: /2/%d, Parameter3: /3/%d,Parameter4: /4/%d)
CauseThis alarm indicates internal error states providing information about the cause andlocation of the error in association with the related error number.
Meaning of alarm parameters
Parameter1: Error source
Parameter2 to 4: Error number
RemedyA detailed description of the system error alarm is not provided. Should a systemerror of this type occur, note the alarm number, the alarm text, and the internalsystem error number specified in the alarm and contact: SIEMENS AG A&D MC, Hotline.
Acknowledgment / responsePower On / STOP
Default setting for local responseOUTPUT_CAM_DISABLE
Programmable local responsesOUTPUT_CAM_DISABLE
2
outputCamType
2-124� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
20002 Insufficient memory (Parameter1: /1/%d, Parameter2: /2/%d, Parameter3:/3/%d, Parameter4: /4/%d)
CauseThe memory required by the system is no longer available. This alarm can occurboth during power up and after program calls.
Meaning of alarm parameters
Parameter1: Area in which the error occurred.
1–Command decoding
2–Interpolator
3–Controller
4–Manipulated variable output
5–Encoder system
6–Technology package
Parameters 2 to 4 are area-specific. They are not fully utilized by all areas.
Command decoding area:
Parameter2 and Parameter4 refer to the command in which the error occurred.
Parameter2: Command return value
Parameter4: Command type
Remedy
� Reduce the size of the ST code.
� Reduce the number of technology objects.
� Reduce the number of interpolation points for cams, if present.
Acknowledgment / responsePower On / STOP
Default setting for local responseOUTPUT_CAM_DISABLE
Programmable local responsesOUTPUT_CAM_DISABLE
outputCamType
2-125� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
20003 No object configuration (Parameter1: /1/%d, Parameter2: /2/%d, Parameter3:/3/%d, Parameter4: /4/%d)
CauseError in system configuration. The configuration data for a software tool could notbe found.
Meaning of alarm parameters
Parameter1: Area in which the error occurred.
1–Command decoding
2–Interpolator
3–Controller
4–Manipulated variable output
5–Encoder system
Parameters 2 to 4 are area-specific. They are not fully utilized by all areas.
Command decoding area:
Parameter2 and Parameter4 refer to the command in which the error occurred.
Parameter2: Command return value
Parameter4: Command type
RemedyCheck the accuracy of the configuration data in your project. When commands arecalled on technology objects, the technology objects must be configured.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPOUTPUT_CAM_DISABLE
outputCamType
2-126� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
20004 At the logical address: /1/%d (bit number, if required: /2/%d) a driver (type:/3/%d) could be requested (error number: /4/%d)
CauseThe driver of a physical device or the device itself is not available.
Meaning of alarm parameters
Logical address:
This is the address configured on the technology object.
Bit number:
For bit driver only; bit number
Type:
1–Actuator driver
2–Encoder driver
3–BitRead driver
4–BitWrite driver
5–ByteRead driver
6–ByteWrite driver
7–WordRead driver
8–WordWrite driver
9–DWordRead driver
10–DWordWrite driver
Error number: Specification of error
Not relevant
Remedy
� Connect a suitable device.
� Check the device (function, connections, terminals).
� Check the topological configuration in HWConfig.
� Compare configuration of HWConfig and technology object.
� Contact the hotline.
Acknowledgment / responsePower On / START TechnologicalFaultTask
Default setting for local responseOUTPUT_CAM_DISABLE
Programmable local responsesOUTPUT_CAM_DISABLE
outputCamType
2-127� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
20005 Device type: /3/%d, log. address: /1/%d faulty. (Bit: /2/%d, reason: 0x/4/%Xh)
CauseThe driver of a physical device or the device itself has failed or is faulty. When thisalarm occurs, the error cause must be evaluated in the external device (drive orencoder).
Meaning of alarm parameters
Type:
1–Actuator driver
2–Encoder driver
3–BitRead driver
4–BitWrite driver
5–ByteRead driver
6–ByteWrite driver
7–WordRead driver
8–WordWrite driver
9–DWordRead driver
10–DWordWrite driver
Logical address:This is the address configured on the technology object.
Bit number:For bit driver type = 3 or 4 only; bit number
Reason:0–Not defined (e.g., for binary I/O)
� Type = 1
0x0001h: Fault message from drive (note: On PROFIBUS drives, whichsupport acyclic communication in accordance with PROFIdrive V3,the error number/numbers of the drives is/are displayed in thediagnostic buffer, e.g., on Masterdrives MC).
0x0002h: DP: Drive signal “control requested” failed
0x0004h: DP: Drive switched off itself
0x0008h: Slot for drive data is not available in the project
0x0010h: Actuator driver does not have a connection to the drive data
0x0020h: Actuator driver was not initialized during power up
0x0080h: DP: Difference between configuration data and drive parameters
0x4000h: DP: Drive on bus failed (station failure)
0x8000h: Sign of life of drive faulty or failed
outputCamType
2-128� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
� Type = 2
0x0000h: The number of permissible changes in the actual value of the maximum velocity of the absolute-value encoder has beenexceeded
0x0001h: Fault message from encoder (note: The error number/numbers is/are displayed in the diagnosticbuffer)
0x0002h: General hardware error of encoder
0x0004h: Encoder contaminated
0x0008h: Slot for encoder data is not available in the project
0x0010h: Encoder driver does not have a connection to the encoder data
0x0020h: Encoder driver was not initialized during power up
0x0040h: Error when reading the absolute value of the encoder
0x0080h: DP: Difference between the configuration data and the encoder parameters
0x0100h: Zero mark monitoring of encoder
0x4000h: DP: Encoder on bus failed (station failure)
0x8000h: DP: Sign of life of encoder has malfunctioned or failed. (Note: For an encoder whose data are transferred in a drive message together with actuator data, the actuator sign of life applies for the encoder, e.g., a standard message 3 in accordance with PROFIdrive).
� Type = 3 to 10
0x0000h: Additional information, not assigned
Note:Codings for the reason of the failure can also occur in combination. Theindividual codings are then added to form a coding sum, which is displayed(e.g., 0x0005 = 0x0001 + 0x0004). A reason for failure marked as DP can only be present on PROFIBUS devices.
RemedyCheck the device with respect to function and connections (reason 0x0001,0x0002, 0x0004, 0x4000, 0x8000).
� Check the topological configuration in HW Config (with reason 0x0008).
� For PROFIBUS drives or encoders, compare the configuration of HWConfig, thetechnology object, and the drive parameter assignment.For:
Reason 0x0040:
– Compare the encoder type in the drive or encoder parameter P979 with theconfiguration data of the technology object.
outputCamType
2-129� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
Reason 0x0080:
– Compare the message frame type in the drive or encoder parameter P922with HW Config and the configuration data of the technology object.
– Compare the encoder type, resolution, multiplier and, with absoluteencoders, the data length in the drive or encoder parameter P979 with theconfiguration data of the technology object.
– Compare the parameterization named in reason 0x8000 (reason 0x8000 canoccur as secondary fault).
Reason 0x8000:
– Compare the cycle clock parameters of HW Config (PROFIBUS line, SlaveOM for drive or encoder) and the execution system. Tmapc and servo mustbe parameterized with the same cycle clock period!
� System fault, contact the hotline (reason 0x0008, 0x0010, 0x0020).
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseOUTPUT_CAM_DISABLE
Programmable local responsesOUTPUT_CAM_DISABLE
outputCamType
2-130� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
20006 Error in configuration (category: /1/%d, error number: /2/%d)
CauseThis alarm indicates error states caused by a faulty or inconsistent configuration.The technology objects perform a plausibility check on the configuration. Errors areidentified by the error codes below.
Meaning of alarm parameters
Category: Area in which the error occurred.
1–Command decoding
2–Interpolator
3–Controller
4–Manipulated variable output
5–Encoder system
6–Technology object
Error number: Specification of error
500 = “TO in illegal status for configuration”.
501 = “More configuration data expected than received”
502 = “Invalid data in configuration”
503 = “Version conflict in configuration”
1001 = “Fast and normal output cams cannot be connected to the same output”
1002 = “Interconnection of output cams with a technology object that does not havea measuring system is not permissible when taskLevel:= SERVO’ and ’posvaluetype:=ACTUAL’ is selected”
1003 = “Task level is not configured for the output cam calculation”
1004 = “Type of position value (RATED, ACTUAL) is not configured”
1005 = “Error in configuration of output cam signal output”
1006 = “Error in configuration of IPO/servo cycle clock ratio”
1007 = “Interconnection of output cam with ’posvaluetype:=RATED’ and an axiswith a faster TaskLevel results in accuracy problems and is therefore notpermissible”
RemedyChange the configuration data.
Acknowledgment / responsePower On / START TechnologicalFaultTask
Default setting for local responseOUTPUT_CAM_DISABLE
Programmable local responsesOUTPUT_CAM_DISABLE
outputCamType
2-131� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
20007 Interconnection error (category: /1/%d, context: /2/%d, context parameter1:/3/%d, context parameter2: /4/%d)
CauseThis alarm indicates errors in the interconnection of technology objects. When theinterconnection is established, the technology object verifies it on the basis of theinterface properties. Errors are classified by category.
Meaning of alarm parameters
Category:
1 – TO compatibility errorAn interconnection is to be established with a technology object that has beenconfigured with another reference system (e.g., output cam with rotaryreference system and linear axis).
2 – Exclusive interfaceMultiple interconnections are to be established for an interface intended forexclusive interconnection.
3 – Interconnection requirementThe technology object is waiting for an interconnection required for thesequence.
4 – Interface initialization errorErrors result from extended initialization sequences at interfaces andparameter exchange between interconnected interfaces.
5 – Interface not available on technology objectAn interface specified in the interconnection is not available on the technologyobject.
6 – CircularityThe interconnection on the technology object leads to circular communicationwithin the technology object (e.g., circular master/slave interconnection ofgearing axes, whereby a gearing axis used as a master is in turn the slave ofanother master, which is assigned the master setpoints generated on thisgearing axis directly or via additional interconnections).
7 – Sequence-level compatibility errorAn interconnection is to be established with a technology object that isexecuted in another interpolator level (e.g., output cam with IPO and axis withIPO_2).
8 – Distribution initializationWhen interconnecting technology objects that are distributed among differentdevices, an error occurred during initialization of the communication interface.
9 – Illegal TO statusThe technology object cannot be interconnected in the current state.
Context:
The context provides additional information about the error category for the TOinterconnection. Additional parameters can be provided for the error descriptionon a context-specific basis. Context and context parameter are output as aninteger value.
outputCamType
2-132� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
Remedy
1 – Technology object compatibility error Correct the configuration of the reference system of the technology objects tobe interconnected.
2 – Exclusive interface Correct the configuration of the interconnected technology object.
3 – Interconnection request Add the missing interconnection to your technology object.
4 – Error during interface initialization: Contact the hotline.
5 – Interface not available on technology object: Contact the hotline.
6 – Circularity:Remove unnecessary interconnections.
7 – Execution level compatibility error: Correct the configuration of the interpolator task level of the technology objectsto be interconnected.
8 – Distribution initializationCheck the hardware configuration. Ensure that the distributed interactingdevices are linked in the bus configuration. In addition, the address areas thatare used by the devices for communication must be set up. The address areasare automatically set up when the project is compiled; only afterwards is thevalid hardware configuration available for downloading.
9 – Illegal TO statusCorrect the configuration of the technology object, correct execution errors.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseOUTPUT_CAM_DISABLE
Programmable local responsesOUTPUT_CAM_DISABLE
outputCamType
2-133� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
20008 Cannot assign USER_DEFAULT to system variables
CauseIt is not appropriate to assign USER_DEFAULT to a UserDefault system variable,because the variable references itself in this case.This prevents generation of a useful value during reading out. When this erroroccurs, the new Enum value is not assigned. The variable retains the old value.
RemedyUSER_DEFAULT is designed for use in technology commands.Avoid assigning it to system variables.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONE
20009 Reserved error
CauseThis error is not currently in use.
RemedyNot necessary, for information only.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseOUTPUT_CAM_DISABLE
Programmable local responsesOUTPUT_CAM_DISABLE
outputCamType
2-134� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
20010 A restart is necessary to activate the configuration data
CauseThe configuration cannot be set to active, since data have been modified in such away that does not permit it. The technology object must be restarted to activate thedata.
Remedy
� Execute the technology object reset command, and set the activateRestartparameter to ACTIVATE_RESTART.
� Set the restartActivation system variable to ACTIVATE_RESTART.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPOUTPUT_CAM_DISABLE
outputCamType
2-135� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
20011 Error when activating the configuration (category: /1/%d, error number:/2/%d)
CauseThis note indicates error conditions when activating the configuration. The errorconditions can be traced back to an incorrect or inconsistent configuration. Thetechnology objects perform a plausibility check on the configuration. Errors areidentified by the error codes below.If this information appears, the configuration will not be activated.
Meaning of alarm parameters
Category: Area in which the error occurred.
1–Command decoding
2–Interpolator
3–Controller
4–Manipulated variable output
5–Encoder system
6–Technology object
Error number: Specification of error
1001 = “Fast and normal output cams cannot be connected to the same output”
1002 = “Interconnection of output cams with a technology object that does not havea measuring system is not permissible when taskLevel:= SERVO’ and ’posvaluetype:=ACTUAL’ is selected”
1003 = “Task level is not configured for the output cam calculation”
1004 = “Type of position value (RATED, ACTUAL) is not configured”
1005 = “Error in configuration of output cam signal output”
1006 = “Error in configuration of IPO/servo cycle clock ratio”
1007 = “Interconnection of output cam with ’posvaluetype:=RATED’ and an axiswith a faster TaskLevel results in accuracy problems and is therefore notpermissible”
RemedyChange the configuration data.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPOUTPUT_CAM_DISABLE
outputCamType
2-136� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
20012 Restart not executed (reason: /1/%d)
CauseTechnology object could not be restarted.
Meaning of alarm parameters
Reason:
1 – The technology object configuration does not allow a restart with the restartsystem variable. You can initiate the restart using the reset command.
2 – The technology object is not ready to be restarted.
3 – A configured condition for restarting the technology object is not met (e.g.,technology object must be disabled).
4 – Restart has not been executed or executed with the last programmedconfiguration of the technology object.
Remedy
� Work around the cause stated in the Reason parameter, or reload the project.
� Use the device diagnostics to establish whether technological alarms werereported and, if necessary, remedy the cause of the alarm.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPOUTPUT_CAM_DISABLE
outputCamType
2-137� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
20014 At the logical address: /1/%d (optional log. address: /2/%d and bit no.: /3/%dof the enable output), a driver (type: /4/%d) could not be requested
CauseThe driver of a physical device is not available or is being used by another TO.
Meaning of alarm parameters
Logical address:
This is the address of the actuator driver configured on the technology object.
Logical address and bit number:
This specifies the address and bit number of the output enable bit
Type:
1–Actuator driver
2–Encoder driver
3–BitRead driver
4–BitWrite driver
5–ByteRead driver
6–ByteWrite driver
7–WordRead driver
8–WordWrite driver
9–DWordRead driver
10–DWordWrite driver
Remedy
� Check that the logical device was available at the time of the request or whetherit was being used by another technology object.
� Connect a suitable device.
� Check the device (function, connections, terminals).
� Check the topological configuration in HWConfig.
� Compare configuration of HWConfig and technology object.
� Contact the hotline.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseOUTPUT_CAM_DISABLE
Programmable local responsesOUTPUT_CAM_DISABLE
outputCamType
2-138� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
30001 Illegal parameter (parameter index according to standard sequence in thesystem functions: /1/%d, command type: /4/%X)
CauseIllegal system function parameter, the command is aborted. The parameters indicate the position of the illegal system function parameteraccording to the standard sequence in the system functions and the command typeof an incorrectly entered parameter.
Meaning of alarm parameters
Parameter index:
Index of the first system function parameter that triggered this error (listedaccording to the standard sequence in the system functions).
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyChange the parameters.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPOUTPUT_CAM_DISABLE
outputCamType
2-139� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
30002 Command aborted (reason: /1/%d, command type: /4/%X)
CauseExecution of the command was aborted before or during processing.This condition can arise as a result of loading a new command, resetting thecommand buffer, or an error state.
Meaning of alarm parameters
Reason:
1–Command buffer reset
2–Abort by another command
3–Aborted by a stop
4–Aborted by a higher-order stop
5–Abort by a pending error response
6–Aborted due to ambiguous commandId
7–Delayed acknowledgment
8–No actual value for axis (e.g., encoder or data bus not ready)
9–Aborted due to abnormal termination of a dependent command
10–Aborted due to active synchronous operation
11–Aborted due to active superimposed motion
12–Aborted due to active speed-controlled controller mode
13–Aborted due to active position-controlled controller mode
14–Aborted due to active motion to fixed end stop
15–Axis is not in pressure-limiting operation
16–Aborted due to active pressure-controlled operation
17–Aborted due to inactive pressure-controlled operation
18–Superimposed command is not permitted
19–Aborted due to error during cam access
20–Slave is not ready for operation
21–Error in slave synchronization
22–Aborted by command on slave
23–Aborted by stop on slave
24–Aborted by an active error response on the slave
25–No actual value for slave (e.g., encoder or data bus not ready)
26–Aborted by reset on slave
27–Master values are not valid
28–Active command in recursive TO interconnection
29–Aborted due to error during synchronization
30–Axis is in pressure-limiting operation
31–Maximum number of active commands exceeded
32–Aborted due to active correction command
33–Action only permissible in standstill
Command type:
Outputs the aborted command type. The command type is output as ahexadecimal integer value.
outputCamType
2-140� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
RemedyReset command via program.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPOUTPUT_CAM_DISABLE
30003 Command aborted due to full command buffer (command type: /4/%X)
CauseThe command is not entered in the command buffer as the buffer is already full.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
Remedy
� Check the program flow.
� Typical cause: The ’nextCommand’ parameter is passed with the valueIMMEDIATELY. You need to synchronize the command sequence manually oruse another value for ’nextCommand’.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPOUTPUT_CAM_DISABLE
outputCamType
2-141� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
30004 Unknown command (command type: /4/%X)
CauseThe active software tool does not support this command.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyCheck the versions of the engineering system and the runtime software.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPOUTPUT_CAM_DISABLE
outputCamType
2-142� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
30005 Ambiguous commandId (number of commands with specified ID: /1/%d,command type: /4/%X)
CauseThe specified commandID refers to several commands.The specified action is performed for the command matching the specifiedcommandID that has been in the interpolator for the longest time. If nocorresponding command is found in the interpolator, the action refers to the nextcommand loaded in the interpolator.
Meaning of alarm parameters
Number of commands with specified ID:
Number of commands referenced by the specified commandId.
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyUse different commandIds for commands that are active simultaneously.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPOUTPUT_CAM_DISABLE
outputCamType
2-143� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
30006 Cannot execute command due to current object state (command type: /4/%X)
CauseThe object is in the stop, error, or reset state and the command is not possible inthis object state.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
Remedy
� Check the object status.
� Check the permissible sequence of commands.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPOUTPUT_CAM_DISABLE
30007 The error cannot be reset due to its configuration
CauseThe alarm cannot be acknowledged at the present time or by the selected means.
Remedy
� Check the configured acknowledgment procedure.
� If necessary, change the acknowledgment procedure for the alarm.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPOUTPUT_CAM_DISABLE
outputCamType
2-144� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
30008 A connection to a technology object required for this operation does notexist (command type: /4/%X)
CauseThe object connection required for this operation has not been configured.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyCheck the project configuration, or change the object connection in the command.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPOUTPUT_CAM_DISABLE
outputCamType
2-145� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
30009 Command rejected due to suspension of command decoding on addressedtechnology object (command type: /4/%X)
CauseCommand was rejected due to suspension of command decoding on theaddressed technology object.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
Remedy
� Check why the command was rejected.
� If necessary, acknowledge any active errors once you have corrected the causeof the error.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPOUTPUT_CAM_DISABLE
30010 Command not available (command type: /4/%X)
CauseThe command is not available in this version of the runtime software.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyCheck the version of the runtime software.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPOUTPUT_CAM_DISABLE
outputCamType
2-146� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
30011 Parameter unavailable (parameter index according to standard sequence inthe system functions: /1/%d, command type: /4/%X)
CauseThe parameter is not available in this version of the runtime software, thecommand is therefore rejected. The parameters indicate the position according tothe standard sequence in the system functions and the command type of anincorrectly entered parameter.
Meaning of alarm parameters
Parameter index:
Index of the command parameter triggering this error according to the standardsequence in the system functions.
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyCheck the version of the runtime software.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPOUTPUT_CAM_DISABLE
outputCamType
2-147� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
30012 Command cannot be started synchronously (command type: /4/%X)
CauseThe command cannot be used during a BEGIN_SYNC, END_SYNC sequencebecause it is a reset command or a command that has only one return value in theuser program.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyDo not use this command type during a BEGIN_SYNC, END_SYNC sequence.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPOUTPUT_CAM_DISABLE
outputCamType
2-148� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
30013 Synchronous start of the command using IMMEDIATELY mergeMode(command type: /4/%X)
CauseWith synchronous command start, only merge modes that immediately override thecurrent command (IMMEDIATELY) and superimpose the current command(SUPERIMPOSED_MOTION_MERGE) can be used. If an illegal merge mode isprogrammed (e.g., SEQUENTIAL or NEXT_MOTION), the system automaticallychanges the merge mode to IMMEDIATELY and outputs this warning.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyProgram the command, which is to be started synchronously to immediatelyoverride the current command. To do this, enter the value IMMEDIATELY in the’mergeMode’ command parameter.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPOUTPUT_CAM_DISABLE
outputCamType
2-149� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
30015 A technology required for this command was not configured (technology:/1/%d, command type: /4/%X)
CauseThe command cannot be selected in this technology object configuration.
Meaning of alarm parameters
Technology:
Not relevant
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyActivate the technology needed for the command.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPOUTPUT_CAM_DISABLE
outputCamType
2-150� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
40001 Error in output cam limitation (output cam position: /1/%d)
CauseAt least one output cam position is invalid.The output cam has moved beyond the limits of the operating range.
Meaning of alarm parameters
Parameters:
3 – switchOnPosition
5 – switchOffPosition
15 – inverted
RemedyCheck the assigned actuation or delay time (depending on the traversing directionof the axis): If it is too long, it must be reduced.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseOUTPUT_CAM_DISABLE
Programmable local responsesNONEDECODE_STOPOUTPUT_CAM_DISABLE
outputCamType
2-151� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
40003 Illegal range specification in parameters (parameter: /1/%d)
CauseIllegal value has been entered for a parameter.
Meaning of alarm parameters
Parameters:
3 – switchOnPosition
5 – switchOffPosition
12 – noSwitchingRange
Remedy
Parameters 3, 5:Only switch positions within the operating range are permissible.
Parameter 12:The maximum permissible switching hysteresis amounts to one-fourth of theoperating range.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPOUTPUT_CAM_DISABLE
outputCamType
2-152� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
3-153� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
camTrackType
Possible local responses
NONENo response
DECODE_STOPAbort command processing
CAMTRACK_DISABLEStop and abort all commands
20001 Internal error (Parameter1: /1/%d, Parameter2: /2/%d, Parameter3: /3/%d,Parameter4: /4/%d)
CauseThis alarm indicates internal error states providing information about the cause andlocation of the error in association with the related error number.
Meaning of alarm parameters
Parameter1: Error source
Parameter2 to 4: Error number
RemedyA detailed description of the system error alarm is not provided. Should a systemerror of this type occur, note the alarm number, the alarm text, and the internalsystem error number specified in the alarm and contact: SIEMENS AG A&D MC, Hotline.
Acknowledgment / responsePower On / STOP
Default setting for local responseCAMTRACK_DISABLE
Programmable local responsesCAMTRACK_DISABLE
3
camTrackType
3-154� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
20002 Insufficient memory (Parameter1: /1/%d, Parameter2: /2/%d, Parameter3:/3/%d, Parameter4: /4/%d)
CauseThe memory required by the system is no longer available. This alarm can occurboth during power up and after program calls.
Meaning of alarm parameters
Parameter1: Area in which the error occurred.
1–Command decoding
2–Interpolator
3–Controller
4–Manipulated variable output
5–Encoder system
6–Technology package
Parameters 2 to 4 are area-specific. They are not fully utilized by all areas.
Command decoding area:
Parameter2 and Parameter4 refer to the command in which the error occurred.
Parameter2: Command return value
Parameter4: Command type
Remedy
� Reduce the size of the ST code.
� Reduce the number of technology objects.
� Reduce the number of interpolation points for cams, if present.
Acknowledgment / responsePower On / STOP
Default setting for local responseCAMTRACK_DISABLE
Programmable local responsesCAMTRACK_DISABLE
camTrackType
3-155� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
20003 No object configuration (Parameter1: /1/%d, Parameter2: /2/%d, Parameter3:/3/%d, Parameter4: /4/%d)
CauseError in system configuration. The configuration data for a software tool could notbe found.
Meaning of alarm parameters
Parameter1: Area in which the error occurred.
1–Command decoding
2–Interpolator
3–Controller
4–Manipulated variable output
5–Encoder system
Parameters 2 to 4 are area-specific. They are not fully utilized by all areas.
Command decoding area:
Parameter2 and Parameter4 refer to the command in which the error occurred.
Parameter2: Command return value
Parameter4: Command type
RemedyCheck the accuracy of the configuration data in your project. When commands arecalled on technology objects, the technology objects must be configured.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPCAMTRACK_DISABLE
camTrackType
3-156� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
20004 At the logical address: /1/%d (bit number, if required: /2/%d) a driver (type:/3/%d) could be requested (error number: /4/%d)
CauseThe driver of a physical device or the device itself is not available.
Meaning of alarm parameters
Logical address:
This is the address configured on the technology object.
Bit number:
For bit driver only; bit number
Type:
1–Actuator driver
2–Encoder driver
3–BitRead driver
4–BitWrite driver
5–ByteRead driver
6–ByteWrite driver
7–WordRead driver
8–WordWrite driver
9–DWordRead driver
10–DWordWrite driver
Error number: Specification of error
Not relevant
Remedy
� Connect a suitable device.
� Check the device (function, connections, terminals).
� Check the topological configuration in HWConfig.
� Compare configuration of HWConfig and technology object.
� Contact the hotline.
Acknowledgment / responsePower On / START TechnologicalFaultTask
Default setting for local responseCAMTRACK_DISABLE
Programmable local responsesCAMTRACK_DISABLE
camTrackType
3-157� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
20005 Device type: /3/%d, log. address: /1/%d faulty. (Bit: /2/%d, reason: 0x/4/%Xh)
CauseThe driver of a physical device or the device itself has failed or is faulty. When thisalarm occurs, the error cause must be evaluated in the external device (drive orencoder).
Meaning of alarm parameters
Type:
1–Actuator driver
2–Encoder driver
3–BitRead driver
4–BitWrite driver
5–ByteRead driver
6–ByteWrite driver
7–WordRead driver
8–WordWrite driver
9–DWordRead driver
10–DWordWrite driver
Logical address:This is the address configured on the technology object.
Bit number:For bit driver type = 3 or 4 only; bit number
Reason:0–Not defined (e.g., for binary I/O)
� Type = 1
0x0001h: Fault message from drive (note: On PROFIBUS drives,which support acyclic communication in accordance withPROFIdrive V3, the error number/numbers of the drives is/aredisplayed in the diagnostic buffer, e.g., on Masterdrives MC).
0x0002h: DP: Drive signal “control requested” failed
0x0004h: DP: Drive switched off itself
0x0008h: Slot for drive data is not available in the project
0x0010h: Actuator driver does not have a connection to the drive data
0x0020h: Actuator driver was not initialized during power up
0x0080h: DP: Difference between configuration data and drive parameters
0x4000h: DP: Drive on bus failed (station failure)
0x8000h: Sign of life of drive faulty or failed
camTrackType
3-158� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
� Type = 2
0x0000h: The number of permissible changes in the actual value of the maximum velocity of the absolute-value encoder has beenexceeded
0x0001h: Fault message from encoder (note: The error number/numbers is/are displayed in the diagnosticbuffer)
0x0002h: General hardware error of encoder
0x0004h: Encoder contaminated
0x0008h: Slot for encoder data is not available in the project
0x0010h: Encoder driver does not have a connection to the encoder data
0x0020h: Encoder driver was not initialized during power up
0x0040h: Error when reading the absolute value of the encoder
0x0080h: DP: Difference between the configuration data and the encoder parameters
0x0100h: Zero mark monitoring of encoder
0x4000h: DP: Encoder on bus failed (station failure)
0x8000h: DP: Sign of life of encoder has malfunctioned or failed. (Note: For an encoder whose data are transferred in a drive message together with actuator data, the actuator sign of life applies for the encoder, e.g., a standard message 3 in accordance with PROFIdrive).
� Type = 3 to 10
0x0000h: Additional information, not assigned
Note:Codings for the reason of the failure can also occur in combination. Theindividual codings are then added to form a coding sum, which is displayed(e.g., 0x0005 = 0x0001 + 0x0004). A reason for failure marked as DP can onlybe present on PROFIBUS devices.
RemedyCheck the device with respect to function and connections (reason 0x0001,0x0002, 0x0004, 0x4000, 0x8000).
� Check the topological configuration in HW Config (with reason 0x0008).
� For PROFIBUS drives or encoders, compare the configuration of HWConfig, thetechnology object, and the drive parameter assignment.For:
Reason 0x0040:
– Compare the encoder type in the drive or encoder parameter P979 with theconfiguration data of the technology object.
camTrackType
3-159� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
Reason 0x0080:
– Compare the message frame type in the drive or encoder parameter P922with HW Config and the configuration data of the technology object.
– Compare the encoder type, resolution, multiplier and, with absoluteencoders, the data length in the drive or encoder parameter P979 with theconfiguration data of the technology object.
– Compare the parameterization named in reason 0x8000 (reason 0x8000 canoccur as secondary fault).
Reason 0x8000:
– Compare the cycle clock parameters of HW Config (PROFIBUS line, SlaveOM for drive or encoder) and the execution system. Tmapc and servo mustbe parameterized with the same cycle clock period!
� System fault, contact the hotline (reason 0x0008, 0x0010, 0x0020).
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseCAMTRACK_DISABLE
Programmable local responsesCAMTRACK_DISABLE
camTrackType
3-160� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
20006 Error in configuration (category: /1/%d, error number: /2/%d)
CauseThis alarm indicates error states caused by a faulty or inconsistent configuration.The technology objects perform a plausibility check on the configuration. Errors areidentified by the error codes below.
Meaning of alarm parameters
Category: Area in which the error occurred.
1–Command decoding
2–Interpolator
3–Controller
4–Manipulated variable output
5–Encoder system
6–Technology object
Error number: Specification of error
500 = “TO in illegal status for configuration”.
501 = “More configuration data expected than received”.
502 = “Invalid data in configuration”.
503 = “Version conflict in configuration”.
1001 = “Fast and normal output cams cannot be connected to the same output”
1002 = “Interconnection of output cams with a technology object that does not havea measuring system is not permissible when taskLevel:= SERVO’ and ’positionReference:=ACTUAL_VALUE’ isselected”
1003 = “Task level is not configured for the output cam calculation”
1004 = “Type of position value (COMMAND_VALUE, ACTUAL_VALUE) not configured”
1005 = “Error in configuration of output cam signal output”
1006 = “Error in configuration of IPO/servo cycle clock ratio”
1007 = “Interconnection of output cams with ’positionReference:=COMMAND_VALUE’ and an axis with a faster TaskLevel results in accuracy problems and is therefore not permissible”
RemedyChange the configuration data.
Acknowledgment / responsePower On / START TechnologicalFaultTask
Default setting for local responseCAMTRACK_DISABLE
Programmable local responsesCAMTRACK_DISABLE
camTrackType
3-161� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
20007 Interconnection error (category: /1/%d, context: /2/%d, context parameter1:/3/%d, context parameter2: /4/%d)
CauseThis alarm indicates errors in the interconnection of technology objects. When theinterconnection is established, the technology object verifies it on the basis of theinterface properties. Errors are classified by category.
Meaning of alarm parameters
Category:
1 – TO compatibility error:An interconnection is to be established with a technology object that has beenconfigured with another reference system (e.g., output cam with rotaryreference system and linear axis).
2 – Exclusive interface:Multiple interconnections are to be established for an interface intended forexclusive interconnection.
3 – Interconnection requirement:The technology object is waiting for an interconnection required for thesequence.
4 – Interface initialization error:Errors result from extended initialization sequences at interfaces andparameter exchange between interconnected interfaces.
5 – Interface not available on technology object:An interface specified in the interconnection is not available on the technologyobject.
6 – Circularity:The interconnection on the technology object leads to circular communicationwithin the technology object (e.g., circular master/slave interconnection ofgearing axes, whereby a gearing axis used as a master is in turn the slave ofanother master, which is assigned the master setpoints generated on thisgearing axis directly or via additional interconnections).
7 – Sequence-level compatibility error:An interconnection is to be established with a technology object that isexecuted in another interpolator level (e.g., output cam with IPO and axis withIPO_2).
8 – Distribution initialization:When interconnecting technology objects that are distributed among differentdevices, an error occurred during initialization of the communication interface.
9 – Illegal TO status:The technology object cannot be interconnected in the current state.
Context:
The context provides additional information about the error category for the TOinterconnection. Additional parameters can be provided for the error descriptionon a context-specific basis. Context and context parameter are output as aninteger value.
camTrackType
3-162� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
Remedy
1 – Technology object compatibility error: Correct the configuration of the reference system of the technology objects tobe interconnected.
2 – Exclusive interface: Correct the configuration of the interconnected technology object.
3 – Interconnection request: Add the missing interconnection to your technology object.
4 – Error during interface initialization: Contact the hotline.
5 – Interface not available on technology object: Contact the hotline.
6 – Circularity:Remove unnecessary interconnections.
7 – Execution level compatibility error: Correct the configuration of the interpolator task level of the technology objectsto be interconnected.
8 – Distribution initialization:Check the hardware configuration. Ensure that the distributed interactingdevices are linked in the bus configuration. In addition, the address areas thatare used by the devices for communication must be set up. The address areasare automatically set up when the project is compiled; only afterwards is thevalid hardware configuration available for downloading.
9 – Illegal TO status:Correct the configuration of the technology object, correct execution errors.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseCAMTRACK_DISABLE
Programmable local responsesCAMTRACK_DISABLE
camTrackType
3-163� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
20008 Cannot assign USER_DEFAULT to system variables
CauseIt is not appropriate to assign USER_DEFAULT to a UserDefault system variable,because the variable references itself in this case.This prevents generation of a useful value during reading out. When this erroroccurs, the new Enum value is not assigned. The variable retains the old value.
RemedyUSER_DEFAULT is designed for use in technology commands.Avoid assigning it to system variables.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONE
20009 Reserved error
CauseThis error is not currently in use.
RemedyNot necessary, for information only.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseCAMTRACK_DISABLE
Programmable local responsesCAMTRACK_DISABLE
camTrackType
3-164� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
20010 A restart is necessary to activate the configuration data
CauseThe configuration cannot be set to active, since data have been modified in such away that does not permit it. The technology object must be restarted to activate thedata.
Remedy
� Execute the technology object reset command, and set the activateRestartparameter to ACTIVATE_RESTART.
� Set the restartActivation system variable to ACTIVATE_RESTART.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPCAMTRACK_DISABLE
camTrackType
3-165� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
20011 Error when activating the configuration (category: /1/%d, error number:/2/%d)
CauseThis note indicates error conditions when activating the configuration. The errorconditions can be traced back to an incorrect or inconsistent configuration. Thetechnology objects perform a plausibility check on the configuration. Errors areidentified by the error codes below.If this information appears, the configuration will not be activated.
Meaning of alarm parameters
Category: Area in which the error occurred.
1–Command decoding
2–Interpolator
3–Controller
4–Manipulated variable output
5–Encoder system
6–Technology object
Error number: Specification of error
1001 = “Fast and normal output cams cannot be connected to the same output”
1002 = “Interconnection of output cams with a technology object that does not havea measuring system is not permissible when taskLevel:= SERVO’ and ’positionReference:=ACTUAL_VALUE’ isselected”
1003 = “Task level is not configured for the output cam calculation”
1004 = “Type of position value (COMMAND_VALUE, ACTUAL_VALUE) not configured”
1005 = “Error in configuration of output cam signal output”
1006 = “Error in configuration of IPO/servo cycle clock ratio”
1007 = “Interconnection of output cams with ’positionReference:=COMMAND_VALUE’ and an axis with a faster TaskLevel results in accuracy problems and is therefore not permissible”
RemedyChange the configuration data.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPCAMTRACK_DISABLE
camTrackType
3-166� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
20012 Restart not executed (reason: /1/%d)
CauseTechnology object could not be restarted.
Meaning of alarm parameters
Reason:
1 – The technology object configuration does not allow a restart with the restartsystem variable. You can initiate the restart using the reset command.
2 – The technology object is not ready to be restarted.
3 – A configured condition for restarting the technology object is not met (e.g.,technology object must be disabled).
4 – Restart has not been executed or executed with the last programmedconfiguration of the technology object.
Remedy
� Work around the cause stated in the Reason parameter, or reload the project.
� Use the device diagnostics to establish whether technological alarms werereported and, if necessary, remedy the cause of the alarm.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPCAMTRACK_DISABLE
camTrackType
3-167� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
20014 At the logical address: /1/%d (optional log. address: /2/%d and bit no.: /3/%dof the enable output), a driver (type: /4/%d) could not be requested
CauseThe driver of a physical device is not available or is being used by another TO.
Meaning of alarm parameters
Logical address:
This is the address of the actuator driver configured on the technology object.
Logical address and bit number:
This specifies the address and bit number of the output enable bit
Type:
1–Actuator driver
2–Encoder driver
3–BitRead driver
4–BitWrite driver
5–ByteRead driver
6–ByteWrite driver
7–WordRead driver
8–WordWrite driver
9–DWordRead driver
10–DWordWrite driver
Remedy
� Check that the logical device was available at the time of the request or whetherit was being used by another technology object.
� Connect a suitable device.
� Check the device (function, connections, terminals).
� Check the topological configuration in HWConfig.
� Compare configuration of HWConfig and technology object.
� Contact the hotline.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseCAMTRACK_DISABLE
Programmable local responsesCAMTRACK_DISABLE
camTrackType
3-168� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
30001 Illegal parameter (parameter index according to standard sequence in thesystem functions: /1/%d, command type: /4/%X)
CauseIllegal system function parameter, the command is aborted. The parameters indicate the position of the illegal system function parameteraccording to the standard sequence in the system functions and the command typeof an incorrectly entered parameter.
Meaning of alarm parameters
Parameter index:
Index of the first system function parameter that triggered this error (listedaccording to the standard sequence in the system functions).
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyChange the parameters.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPCAMTRACK_DISABLE
camTrackType
3-169� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
30002 Command aborted (reason: /1/%d, command type: /4/%X)
CauseExecution of the command was aborted before or during processing.This condition can arise as a result of loading a new command, resetting thecommand buffer, or an error state.
Meaning of alarm parameters
Reason:
1–Command buffer reset
2–Abort by another command
3–Aborted by a stop
4–Aborted by a higher-order stop
5–Abort by a pending error response
6–Aborted due to ambiguous commandId
7–Delayed acknowledgment
8–No actual value for axis (e.g., encoder or data bus not ready)
9–Aborted due to abnormal termination of a dependent command
10–Aborted due to active synchronous operation
11–Aborted due to active superimposed motion
12–Aborted due to active speed-controlled controller mode
13–Aborted due to active position-controlled controller mode
14–Aborted due to active motion to fixed end stop
15–Axis is not in pressure-limiting operation
16–Aborted due to active pressure-controlled operation
17–Aborted due to inactive pressure-controlled operation
18–Superimposed command is not permitted
19–Aborted due to error during cam access
20–Slave is not ready for operation
21–Error in slave synchronization
22–Aborted by command on slave
23–Aborted by stop on slave
24–Aborted by an active error response on the slave
25–No actual value for slave (e.g., encoder or data bus not ready)
26–Aborted by reset on slave
27–Master values are not valid
28–Active command in recursive TO interconnection
29–Aborted due to error during synchronization
30–Axis is in pressure-limiting operation
31–Maximum number of active commands exceeded
32–Aborted due to active correction command
33–Action only permissible in standstill
Command type:
Outputs the aborted command type. The command type is output as ahexadecimal integer value.
camTrackType
3-170� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
RemedyReset command via program.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPCAMTRACK_DISABLE
30003 Command aborted due to full command buffer (command type: /4/%X)
CauseThe command is not entered in the command buffer as the buffer is already full.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
Remedy
� Check the program flow.
� Typical cause: The ’nextCommand’ parameter is passed with the valueIMMEDIATELY. You need to synchronize the command sequence manually oruse another value for ’nextCommand’.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPCAMTRACK_DISABLE
camTrackType
3-171� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
30004 Unknown command (command type: /4/%X)
CauseThe active software tool does not support this command.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyCheck the versions of the engineering system and the runtime software.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPCAMTRACK_DISABLE
camTrackType
3-172� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
30005 Ambiguous commandId (number of commands with specified ID: /1/%d,command type: /4/%X)
CauseThe specified commandID refers to several commands.The specified action is performed for the command matching the specifiedcommandID that has been in the interpolator for the longest time. If nocorresponding command is found in the interpolator, the action refers to the nextcommand loaded in the interpolator.
Meaning of alarm parameters
Number of commands with specified ID:
Number of commands referenced by the specified commandId.
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyUse different commandIds for commands that are active simultaneously.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPCAMTRACK_DISABLE
camTrackType
3-173� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
30006 Cannot execute command due to current object state (command type: /4/%X)
CauseThe object is in the stop, error, or reset state and the command is not possible inthis object state.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
Remedy
� Check the object status.
� Check the permissible sequence of commands.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPCAMTRACK_DISABLE
30007 The error cannot be reset due to its configuration
CauseThe alarm cannot be acknowledged at the present time or by the selected means.
Remedy
� Check the configured acknowledgment procedure.
� If necessary, change the acknowledgment procedure for the alarm.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPCAMTRACK_DISABLE
camTrackType
3-174� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
30008 A connection to a technology object required for this operation does notexist (command type: /4/%X)
CauseThe object connection required for this operation has not been configured.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyCheck the project configuration, or change the object connection in the command.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPCAMTRACK_DISABLE
camTrackType
3-175� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
30009 Command rejected due to suspension of command decoding on addressedtechnology object (command type: /4/%X)
CauseCommand was rejected due to suspension of command decoding on theaddressed technology object.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
Remedy
� Check why the command was rejected.
� If necessary, acknowledge any active errors once you have corrected the causeof the error.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPCAMTRACK_DISABLE
30010 Command not available (command type: /4/%X)
CauseThe command is not available in this version of the runtime software.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyCheck the version of the runtime software.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPCAMTRACK_DISABLE
camTrackType
3-176� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
30011 Parameter unavailable (parameter index according to standard sequence inthe system functions: /1/%d, command type: /4/%X)
CauseThe parameter is not available in this version of the runtime software, thecommand is therefore rejected. The parameters indicate the position according tothe standard sequence in the system functions and the command type of anincorrectly entered parameter.
Meaning of alarm parameters
Parameter index:
Index of the command parameter triggering this error according to the standardsequence in the system functions.
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyCheck the version of the runtime software.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPCAMTRACK_DISABLE
camTrackType
3-177� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
30012 Command cannot be started synchronously (command type: /4/%X)
CauseThe command cannot be used during a BEGIN_SYNC, END_SYNC sequencebecause it is a reset command or a command that has only one return value in theuser program.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyDo not use this command type during a BEGIN_SYNC, END_SYNC sequence.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPCAMTRACK_DISABLE
camTrackType
3-178� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
30013 Synchronous start of the command using IMMEDIATELY mergeMode(command type: /4/%X)
CauseWith synchronous command start, only merge modes that immediately override thecurrent command (IMMEDIATELY) and superimpose the current command(SUPERIMPOSED_MOTION_MERGE) can be used. If an illegal merge mode isprogrammed (e.g., SEQUENTIAL or NEXT_MOTION), the system automaticallychanges the merge mode to IMMEDIATELY and outputs this warning.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyProgram the command, which is to be started synchronously to immediatelyoverride the current command. To do this, enter the value IMMEDIATELY in the’mergeMode’ command parameter.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPCAMTRACK_DISABLE
camTrackType
3-179� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
30015 A technology required for this command was not configured (technology:/1/%d, command type: /4/%X)
CauseThe command cannot be selected in this technology object configuration.
Meaning of alarm parameters
Technology:
Not relevant
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyActivate the technology needed for the command.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPCAMTRACK_DISABLE
camTrackType
3-180� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
40003 Illegal range specification in parameters (parameter: /1/%d)
CauseIllegal value has been entered for a parameter.
Meaning of alarm parameters
Parameters:
3 – startPosition
5 – endPosition
12 – hysteresisRange
Remedy
Parameters 3, 5:Only switch positions within the operating range are permissible.
Parameter 12:The maximum permissible switching hysteresis amounts to one-fourth of theoperating range.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPCAMTRACK_DISABLE
4-181� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
measuringInputType
Possible local responses
NONENo response
DECODE_STOPAbort command processing
MEASURING_INPUT_DISABLEStop and abort all commands
20001 Internal error (Parameter1: /1/%d, Parameter2: /2/%d, Parameter3: /3/%d,Parameter4: /4/%d)
CauseThis alarm indicates internal error states providing information about the cause andlocation of the error in association with the related error number.
Meaning of alarm parameters
Parameter1: Error source
Parameter2 to 4: Error number
RemedyA detailed description of the system error alarm is not provided. Should a systemerror of this type occur, note the alarm number, the alarm text, and the internalsystem error number specified in the alarm and contact: SIEMENS AG A&D MC, Hotline.
Acknowledgment / responsePower On / STOP
Default setting for local responseMEASURING_INPUT_DISABLE
Programmable local responsesMEASURING_INPUT_DISABLE
4
measuringInputType
4-182� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
20002 Insufficient memory (Parameter1: /1/%d, Parameter2: /2/%d, Parameter3:/3/%d, Parameter4: /4/%d)
CauseThe memory required by the system is no longer available. This alarm can occurboth during power up and after program calls.
Meaning of alarm parameters
Parameter1: Area in which the error occurred.
1–Command decoding
2–Interpolator
3–Controller
4–Manipulated variable output
5–Encoder system
6–Technology package
Parameters 2 to 4 are area-specific. They are not fully utilized by all areas.
Command decoding area
Parameter2 and Parameter4 refer to the command in which the error occurred.
Parameter2: Command return value
Parameter4: Command type
Remedy
� Reduce the size of the ST code.
� Reduce the number of technology objects.
� Reduce the number of interpolation points for cams, if present.
Acknowledgment / responsePower On / STOP
Default setting for local responseMEASURING_INPUT_DISABLE
Programmable local responsesMEASURING_INPUT_DISABLE
measuringInputType
4-183� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
20003 No object configuration (Parameter1: /1/%d, Parameter2: /2/%d, Parameter3:/3/%d, Parameter4: /4/%d)
CauseError in system configuration. The configuration data for a software tool could notbe found.
Meaning of alarm parameters
Parameter1: Area in which the error occurred.
1–Command decoding
2–Interpolator
3–Controller
4–Manipulated variable output
5–Encoder system
Parameters 2 to 4 are area-specific. They are not fully utilized by all areas.
Command decoding area
Parameter2 and Parameter4 refer to the command in which the error occurred.
Parameter2: Command return value
Parameter4: Command type
RemedyCheck the accuracy of the configuration data in your project. When commands arecalled on technology objects, the technology objects must be configured.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPMEASURING_INPUT_DISABLE
measuringInputType
4-184� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
20004 At the logical address: /1/%d (bit number, if required: /2/%d) a driver (type:/3/%d) could be requested (error number: /4/%d)
CauseThe driver of a physical device or the device itself is not available.
Meaning of alarm parameters
Logical address:
This is the address configured on the technology object.
Bit number:
For bit driver only; bit number
Type:
1–Actuator driver
2–Encoder driver
3–BitRead driver
4–BitWrite driver
5–ByteRead driver
6–ByteWrite driver
7–WordRead driver
8–WordWrite driver
9–DWordRead driver
10–DWordWrite driver
Error number: Specification of error
Not relevant
Remedy
� Connect a suitable device.
� Check the device (function, connections, terminals).
� Check the topological configuration in HWConfig.
� Compare configuration of HWConfig and technology object.
� Contact the hotline.
Acknowledgment / responsePower On / START TechnologicalFaultTask
Default setting for local responseMEASURING_INPUT_DISABLE
Programmable local responsesMEASURING_INPUT_DISABLE
measuringInputType
4-185� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
20005 Device type: /3/%d, log. address: /1/%d faulty. (Bit: /2/%d, reason: 0x/4/%Xh)
CauseThe driver of a physical device or the device itself has failed or is faulty. When thisalarm occurs, the error cause must be evaluated in the external device (drive orencoder).
Meaning of alarm parameters
Type:
1–Actuator driver
2–Encoder driver
3–BitRead driver
4–BitWrite driver
5–ByteRead driver
6–ByteWrite driver
7–WordRead driver
8–WordWrite driver
9–DWordRead driver
10–DWordWrite driver
Logical address:This is the address configured on the technology object.
Bit number:For bit driver type = 3 or 4 only; bit number
Reason:0–Not defined (e.g., for binary I/O)
� Type = 1
0x0001h: Fault message from drive (note: On PROFIBUS drives, whichsupport acyclic communication in accordance with PROFIdrive V3,the error number/numbers of the drives is/are displayed in thediagnostic buffer, e.g., on Masterdrives MC).
0x0002h: DP: Drive signal “control requested” failed
0x0004h: DP: Drive switched off itself
0x0008h: Slot for drive data is not available in the project
0x0010h: Actuator driver does not have a connection to the drive data
0x0020h: Actuator driver was not initialized during power up
0x0080h: DP: Difference between configuration data and drive parameters
0x4000h: DP: Drive on bus failed (station failure)
0x8000h: Sign of life of drive faulty or failed
measuringInputType
4-186� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
� Type = 2
0x0000h: The number of permissible changes in the actual value of the maximum velocity of the absolute-value encoder has beenexceeded
0x0001h: Fault message from encoder (note: The error number/numbersis/are displayed in the diagnostic buffer)
0x0002h: General hardware error of encoder
0x0004h: Encoder contaminated
0x0008h: Slot for encoder data is not available in the project
0x0010h: Encoder driver does not have a connection to the encoder data
0x0020h: Encoder driver was not initialized during power up
0x0040h: Error when reading the absolute value of the encoder
0x0080h: DP: Difference between the configuration data and the encoder parameters
0x0100h: Zero mark monitoring of encoder
0x4000h: DP: Encoder on bus failed (station failure)
0x8000h: DP: Sign of life of encoder has malfunctioned or failed. (Note: For an encoder whose data are transferred in a drive message together with actuator data, the actuator sign of lifeapplies for the encoder, e.g., a standard message 3 in accordancewith PROFIdrive).
� Type = 3 to 10
0x0000h: Additional information, not assigned
Note:Codings for the reason of the failure can also occur in combination. Theindividual codings are then added to form a coding sum, which is displayed(e.g., 0x0005 = 0x0001 + 0x0004). A reason for failure marked as DP can only be present on PROFIBUS devices.
RemedyCheck the device with respect to function and connections (reason 0x0001,0x0002, 0x0004, 0x4000, 0x8000).
� Check the topological configuration in HW Config (with reason 0x0008).
� For PROFIBUS drives or encoders, compare the configuration of HWConfig, thetechnology object, and the drive parameter assignment.For:
Reason 0x0040:
– Compare the encoder type in the drive or encoder parameter P979 with theconfiguration data of the technology object.
measuringInputType
4-187� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
Reason 0x0080:
– Compare the message frame type in the drive or encoder parameter P922with HW Config and the configuration data of the technology object.
– Compare the encoder type, resolution, multiplier and, with absoluteencoders, the data length in the drive or encoder parameter P979 with theconfiguration data of the technology object.
– Compare the parameterization named in reason 0x8000 (reason 0x8000 canoccur as secondary fault).
Reason 0x8000:
– Compare the cycle clock parameters of HW Config (PROFIBUS line, SlaveOM for drive or encoder) and the execution system. Tmapc and servo mustbe parameterized with the same cycle clock period!
� System fault, contact the hotline (reason 0x0008, 0x0010, 0x0020).
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseMEASURING_INPUT_DISABLE
Programmable local responsesMEASURING_INPUT_DISABLE
measuringInputType
4-188� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
20006 Error in configuration (category: /1/%d, error number: /2/%d)
CauseThis alarm indicates error states caused by a faulty or inconsistent configuration.The technology objects perform a plausibility check on the configuration. Errors areidentified by the error codes below.
Meaning of alarm parameters
Category: Area in which the error occurred.
1–Command decoding
2–Interpolator
3–Controller
4–Manipulated variable output
5–Encoder system
6–Technology object
Error number: Specification of error
500 = “TO in illegal status for configuration.”
501 = “More configuration data expected than received.”
502 = “Invalid data in configuration.”
503 = “Version conflict in configuration.”
1001 = “Illegal measuring input number”
1002 = “Illegal sensor system number”
1003 = “Illegal logical address of the measuring-input input”
RemedyChange the configuration data.
Acknowledgment / responsePower On / START TechnologicalFaultTask
Default setting for local responseMEASURING_INPUT_DISABLE
Programmable local responsesMEASURING_INPUT_DISABLE
measuringInputType
4-189� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
20007 Interconnection error (category: /1/%d, context: /2/%d, context parameter1:/3/%d, context parameter2: /4/%d)
CauseThis alarm indicates errors in the interconnection of technology objects. When theinterconnection is established, the technology object verifies it on the basis of theinterface properties. Errors are classified by category.
Meaning of alarm parameters
Category:
1 – TO compatibility errorAn interconnection is to be established with a technology object that has beenconfigured with another reference system (e.g., output cam with rotaryreference system and linear axis).
2 – Exclusive interfaceMultiple interconnections are to be established for an interface intended forexclusive interconnection.
3 – Interconnection requirementThe technology object is waiting for an interconnection required for thesequence.
4 – Interface initialization errorErrors result from extended initialization sequences at interfaces andparameter exchange between interconnected interfaces.
5 – Interface not available on technology objectAn interface specified in the interconnection is not available on the technologyobject.
6 – CircularityThe interconnection on the technology object leads to circular communicationwithin the technology object (e.g., circular master/slave interconnection ofgearing axes, whereby a gearing axis used as a master is in turn the slave ofanother master, which is assigned the master setpoints generated on thisgearing axis directly or via additional interconnections).
7 – Sequence-level compatibility errorAn interconnection is to be established with a technology object that isexecuted in another interpolator level (e.g., output cam with IPO and axis withIPO_2).
8 – Distribution initializationWhen interconnecting technology objects that are distributed among differentdevices, an error occurred during initialization of the communication interface.
9 – Illegal TO statusThe technology object cannot be interconnected in the current state.
Context:
The context provides additional information about the error category for the TOinterconnection. Additional parameters can be provided for the error descriptionon a context-specific basis. Context and context parameter are output as aninteger value.
measuringInputType
4-190� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
Remedy
1 – Technology object compatibility error: Correct the configuration of the reference system of the technology objects tobe interconnected.
2 – Exclusive interface: Correct the configuration of the interconnected technology object.
3 – Interconnection request: Add the missing interconnection to your technology object.
4 – Error during interface initialization: Contact the hotline.
5 – Interface not available on technology object: Contact the hotline.
6 – Circularity:Remove unnecessary interconnections.
7 – Execution level compatibility error: Correct the configuration of the interpolator task level of the technology objectsto be interconnected.
8 – Distribution initialization:Check the hardware configuration. Ensure that the distributed interactingdevices are linked in the bus configuration. In addition, the address areas thatare used by the devices for communication must be set up. The address areasare automatically set up when the project is compiled; only afterwards is thevalid hardware configuration available for downloading.
9 – Illegal TO status:Correct the configuration of the technology object, correct execution errors.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseMEASURING_INPUT_DISABLE
Programmable local responsesMEASURING_INPUT_DISABLE
measuringInputType
4-191� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
20008 Cannot assign USER_DEFAULT to system variables
CauseIt is not appropriate to assign USER_DEFAULT to a UserDefault system variable,because the variable references itself in this case.This prevents generation of a useful value during reading out. When this erroroccurs, the new Enum value is not assigned. The variable retains the old value.
RemedyUSER_DEFAULT is designed for use in technology commands.Avoid assigning it to system variables.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONE
20009 Reserved error
CauseThis error is not currently in use.
RemedyNot necessary, for information only.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseMEASURING_INPUT_DISABLE
Programmable local responsesMEASURING_INPUT_DISABLE
measuringInputType
4-192� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
20010 A restart is necessary to activate the configuration data
CauseThe configuration cannot be set to active, since data have been modified in such away that does not permit it. The technology object must be restarted to activate thedata.
Remedy
� Execute the technology object reset command, and set the activateRestartparameter to ACTIVATE_RESTART.
� Set the restartActivation system variable to ACTIVATE_RESTART.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPMEASURING_INPUT_DISABLE
measuringInputType
4-193� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
20011 Error when activating the configuration (category: /1/%d, error number:/2/%d)
CauseThis note indicates error conditions when activating the configuration. The errorconditions can be traced back to an incorrect or inconsistent configuration. Thetechnology objects perform a plausibility check on the configuration. Errors areidentified by the error codes below.If this information appears, the configuration will not be activated.
Meaning of alarm parameters
Category: Area in which the error occurred.
1–Command decoding
2–Interpolator
3–Controller
4–Manipulated variable output
5–Encoder system
6–Technology object
Error number: Specification of error
1001 = “Illegal measuring input number”
1002 = “Illegal sensor system number”
1003 = “Illegal logical address of the measuring-input input”
RemedyChange the configuration data.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPMEASURING_INPUT_DISABLE
measuringInputType
4-194� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
20012 Restart not executed (reason: /1/%d)
CauseTechnology object could not be restarted.
Meaning of alarm parameters
Reason:
1–The technology object configuration does not allow a restart with the restartsystem variable. You can initiate the restart using the reset command.
2–The technology object is not ready to be restarted.
3–A configured condition for restarting the technology object is not met (e.g.,technology object must be disabled).
4–Restart has not been executed or executed with the last programmedconfiguration of the technology object.
Remedy
� Work around the cause stated in the Reason parameter, or reload the project.
� Use the device diagnostics to establish whether technological alarms werereported and, if necessary, remedy the cause of the alarm.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPMEASURING_INPUT_DISABLE
measuringInputType
4-195� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
20014 At the logical address: /1/%d (optional log. address: /2/%d and bit no.: /3/%dof the enable output), a driver (type: /4/%d) could not be requested
CauseThe driver of a physical device is not available or is being used by another TO.
Meaning of alarm parameters
Logical address:
This is the address of the actuator driver configured on the technology object.
Logical address and bit number:
This specifies the address and bit number of the output enable bit
Type:
1–Actuator driver
2–Encoder driver
3–BitRead driver
4–BitWrite driver
5–ByteRead driver
6–ByteWrite driver
7–WordRead driver
8–WordWrite driver
9–DWordRead driver
10–DWordWrite driver
Remedy
� Check that the logical device was available at the time of the request or whetherit was being used by another technology object.
� Connect a suitable device.
� Check the device (function, connections, terminals).
� Check the topological configuration in HWConfig.
� Compare configuration of HWConfig and technology object.
� Contact the hotline.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseMEASURING_INPUT_DISABLE
Programmable local responsesMEASURING_INPUT_DISABLE
measuringInputType
4-196� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
30001 Illegal parameter (parameter index according to standard sequence in thesystem functions: /1/%d, command type: /4/%X)
CauseIllegal system function parameter, the command is aborted. The parameters indicate the position of the illegal system function parameteraccording to the standard sequence in the system functions and the command typeof an incorrectly entered parameter.
Meaning of alarm parameters
Parameter index:
Index of the first system function parameter that triggered this error (listedaccording to the standard sequence in the system functions).
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyChange the parameters.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPMEASURING_INPUT_DISABLE
measuringInputType
4-197� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
30002 Command aborted (reason: /1/%d, command type: /4/%X)
CauseExecution of the command was aborted before or during processing.This condition can arise as a result of loading a new command, resetting thecommand buffer, or an error state.
Meaning of alarm parameters
Reason:
1–Command buffer reset
2–Abort by another command
3–Aborted by a stop
4–Aborted by a higher-order stop
5–Abort by a pending error response
6–Aborted due to ambiguous commandId
7–Delayed acknowledgment
8–No actual value for axis (e.g., encoder or data bus not ready)
9–Aborted due to abnormal termination of a dependent command
10–Aborted due to active synchronous operation
11–Aborted due to active superimposed motion
12–Aborted due to active speed-controlled controller mode
13–Aborted due to active position-controlled controller mode
14–Aborted due to active motion to fixed end stop
15–Axis is not in pressure-limiting operation
16–Aborted due to active pressure-controlled operation
17–Aborted due to inactive pressure-controlled operation
18–Superimposed command is not permitted
19–Aborted due to error during cam access
20–Slave is not ready for operation
21–Error in slave synchronization
22–Aborted by command on slave
23–Aborted by stop on slave
24–Aborted by an active error response on the slave
25–No actual value for slave (e.g., encoder or data bus not ready)
26–Aborted by reset on slave
27–Master values are not valid
28–Active command in recursive TO interconnection
29–Aborted due to error during synchronization
30–Axis is in pressure-limiting operation
31–Maximum number of active commands exceeded
32–Aborted due to active correction command
33–Action only permissible in standstill
Command type:
Outputs the aborted command type. The command type is output as ahexadecimal integer value.
measuringInputType
4-198� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
RemedyReset command via program.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPMEASURING_INPUT_DISABLE
30003 Command aborted due to full command buffer (command type: /4/%X)
CauseThe command is not entered in the command buffer as the buffer is already full.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
Remedy
� Check the program flow.
� Typical cause: The ’nextCommand’ parameter is passed with the valueIMMEDIATELY. You need to synchronize the command sequence manually oruse another value for ’nextCommand’.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPMEASURING_INPUT_DISABLE
measuringInputType
4-199� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
30004 Unknown command (command type: /4/%X)
CauseThe active software tool does not support this command.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyCheck the versions of the engineering system and the runtime software.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPMEASURING_INPUT_DISABLE
measuringInputType
4-200� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
30005 Ambiguous commandId (number of commands with specified ID: /1/%d,command type: /4/%X)
CauseThe specified commandID refers to several commands.The specified action is performed for the command matching the specifiedcommandID that has been in the interpolator for the longest time. If nocorresponding command is found in the interpolator, the action refers to the nextcommand loaded in the interpolator.
Meaning of alarm parameters
Number of commands with specified ID:
Number of commands referenced by the specified commandId.
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyUse different commandIds for commands that are active simultaneously.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPMEASURING_INPUT_DISABLE
measuringInputType
4-201� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
30006 Cannot execute command due to current object state (command type: /4/%X)
CauseThe object is in the stop, error, or reset state and the command is not possible inthis object state.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
Remedy
� Check the object status.
� Check the permissible sequence of commands.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPMEASURING_INPUT_DISABLE
30007 The error cannot be reset due to its configuration
CauseThe alarm cannot be acknowledged at the present time or by the selected means.
Remedy
� Check the configured acknowledgment procedure.
� If necessary, change the acknowledgment procedure for the alarm.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPMEASURING_INPUT_DISABLE
measuringInputType
4-202� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
30008 A connection to a technology object required for this operation does notexist (command type: /4/%X)
CauseThe object connection required for this operation has not been configured.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyCheck the project configuration, or change the object connection in the command.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPMEASURING_INPUT_DISABLE
measuringInputType
4-203� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
30009 Command rejected due to suspension of command decoding on addressedtechnology object (command type: /4/%X)
CauseCommand was rejected due to suspension of command decoding on theaddressed technology object.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
Remedy
� Check why the command was rejected.
� If necessary, acknowledge any active errors once you have corrected the causeof the error.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPMEASURING_INPUT_DISABLE
30010 Command not available (command type: /4/%X)
CauseThe command is not available in this version of the runtime software.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyCheck the version of the runtime software.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPMEASURING_INPUT_DISABLE
measuringInputType
4-204� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
30011 Parameter unavailable (parameter index according to standard sequence inthe system functions: /1/%d, command type: /4/%X)
CauseThe parameter is not available in this version of the runtime software, thecommand is therefore rejected. The parameters indicate the position according tothe standard sequence in the system functions and the command type of anincorrectly entered parameter.
Meaning of alarm parameters
Parameter index:
Index of the command parameter triggering this error according to the standardsequence in the system functions.
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyCheck the version of the runtime software.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPMEASURING_INPUT_DISABLE
measuringInputType
4-205� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
30012 Command cannot be started synchronously (command type: /4/%X)
CauseThe command cannot be used during a BEGIN_SYNC, END_SYNC sequencebecause it is a reset command or a command that has only one return value in theuser program.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyDo not use this command type during a BEGIN_SYNC, END_SYNC sequence.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPMEASURING_INPUT_DISABLE
measuringInputType
4-206� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
30013 Synchronous start of the command using IMMEDIATELY mergeMode(command type: /4/%X)
CauseWith synchronous command start, only merge modes that immediately override thecurrent command (IMMEDIATELY) and superimpose the current command(SUPERIMPOSED_MOTION_MERGE) can be used. If an illegal merge mode isprogrammed (e.g., SEQUENTIAL or NEXT_MOTION), the system automaticallychanges the merge mode to IMMEDIATELY and outputs this warning.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyProgram the command, which is to be started synchronously to immediatelyoverride the current command. To do this, enter the value IMMEDIATELY in the’mergeMode’ command parameter.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPMEASURING_INPUT_DISABLE
measuringInputType
4-207� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
30015 A technology required for this command was not configured (technology:/1/%d, command type: /4/%X)
CauseThe command cannot be selected in this technology object configuration.
Meaning of alarm parameters
Technology:
Not relevant
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyActivate the technology needed for the command.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPMEASURING_INPUT_DISABLE
40001 Measurement not possible on virtual axis
CauseMeasurement is not supported by virtual axes.
RemedyUse a real axis.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPMEASURING_INPUT_DISABLE
measuringInputType
4-208� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
40002 Measurement task not possible during homing of assigned axis
CauseNo measurement tasks are executed while the axis assigned to the measuringinput is being homed.
RemedyFinish the homing procedure before the measurement.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPMEASURING_INPUT_DISABLE
40003 Measuring input not switched within validity range of measurement task
CauseMeasuring input deflection did not occur before the measuring input left the validityrange of the measurement task.
Remedy
� Check the validity range.
� Check the measuring input.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPMEASURING_INPUT_DISABLE
measuringInputType
4-209� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
40004 Validity range of measurement task not recognized
CauseThe validity range of the measurement task has been skipped.
Remedy
� Increase the validity range.
� Adjust the ratio between the validity range and the axis velocity.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPMEASURING_INPUT_DISABLE
40005 Simultaneous access of several measuring inputs to one encoder is notpossible
CauseSimultaneous access of several measuring inputs to one encoder is not supportedby the hardware.
RemedyDo not access one encoder simultaneously with several measuring inputs.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPMEASURING_INPUT_DISABLE
measuringInputType
4-210� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
40006 Configuration of measurement inputs in an external device not correct
CauseThe configuration of the measurement inputs in an external device is not correct.
RemedyCheck the configuration of the external device that is to be used for measurement.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseMEASURING_INPUT_DISABLE
Programmable local responsesMEASURING_INPUT_DISABLE
40007 Measurement task was aborted by external device
CauseAn external device has aborted an active measurement task.
RemedyCheck the external device that is to be used for measurement.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPMEASURING_INPUT_DISABLE
measuringInputType
4-211� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
40008 Measurement task has been aborted due to a drive or encoder error
CauseThe measurement task has been aborted due to an encoder or drive error.
RemedyCheck to determine whether there is an encoder error or the drive is not ready tooperate.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPMEASURING_INPUT_DISABLE
measuringInputType
4-212� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
5-213� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
externalEncoderType
Possible local responses
NONENo response
DECODE_STOPAbort command processing
SIMULATION_STOPSimulation stop
SIMULATION_ABORTAbort the active simulation command
ENCODER_DISABLEStop and abort all commands
5
externalEncoderType
5-214� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
20001 Internal error (Parameter1: /1/%d, Parameter2: /2/%d, Parameter3: /3/%d,Parameter4: /4/%d)
CauseThis alarm indicates internal error states providing information about the cause andlocation of the error in association with the related error number.
Meaning of alarm parameters
Parameter1: Error source
Parameter2 to 4: Error number
RemedyA detailed description of the system error alarm is not provided. Should a systemerror of this type occur, note the alarm number, the alarm text, and the internalsystem error number specified in the alarm and contact: SIEMENS AG A&D MC, Hotline.
Acknowledgment / responsePower On / STOP
Default setting for local responseENCODER_DISABLE
Programmable local responsesENCODER_DISABLE
externalEncoderType
5-215� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
20002 Insufficient memory (Parameter1: /1/%d, Parameter2: /2/%d, Parameter3:/3/%d, Parameter4: /4/%d)
CauseThe memory required by the system is no longer available. This alarm can occurboth during power up and after program calls.
Meaning of alarm parameters
Parameter1: Area in which the error occurred.
1–Command decoding
2–Interpolator
3–Controller
4–Manipulated variable output
5–Encoder system
6–Technology package
Parameters 2 to 4 are area-specific. They are not fully utilized by all areas.
Command decoding area:
Parameter2 and Parameter4 refer to the command in which the error occurred.
Parameter2: Command return value
Parameter4: Command type
Remedy
� Reduce the size of the ST code.
� Reduce the number of technology objects.
� Reduce the number of interpolation points for cams, if present.
Acknowledgment / responsePower On / STOP
Default setting for local responseENCODER_DISABLE
Programmable local responsesENCODER_DISABLE
externalEncoderType
5-216� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
20003 No object configuration (Parameter1: /1/%d, Parameter2: /2/%d, Parameter3:/3/%d, Parameter4: /4/%d)
CauseError in system configuration. The configuration data for a software tool could notbe found.
Meaning of alarm parameters
Parameter1: Area in which the error occurred.
1–Command decoding
2–Interpolator
3–Controller
4–Manipulated variable output
5–Encoder system
Parameters 2 to 4 are area-specific. They are not fully utilized by all areas.
Command decoding area:
Parameter2 and Parameter4 refer to the command in which the error occurred.
Parameter2: Command return value
Parameter4: Command type
RemedyCheck the accuracy of the configuration data in your project. When commands arecalled on technology objects, the technology objects must be configured.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPSIMULATION_STOPSIMULATION_ABORTENCODER_DISABLE
externalEncoderType
5-217� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
20004 At the logical address: /1/%d (bit number, if required: /2/%d) a driver (type:/3/%d) could be requested (error number: /4/%d)
CauseThe driver of a physical device or the device itself is not available.
Meaning of alarm parameters
Logical address:
This is the address configured on the technology object.
Bit number:
For bit driver only; bit number
Type:
1–Actuator driver
2–Encoder driver
3–BitRead driver
4–BitWrite driver
5–ByteRead driver
6–ByteWrite driver
7–WordRead driver
8–WordWrite driver
9–DWordRead driver
10–DWordWrite driver
Error number: Specification of error
1000 = “General driver configuration error”
Remedy
� Connect a suitable device.
� Check the device (function, connections, terminals).
� Check the topological configuration in HWConfig.
� Compare configuration of HWConfig and technology object.
� Contact the hotline.
Acknowledgment / responsePower On / START TechnologicalFaultTask
Default setting for local responseENCODER_DISABLE
Programmable local responsesENCODER_DISABLE
externalEncoderType
5-218� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
20005 Device type: /3/%d, log. address: /1/%d faulty. (Bit: /2/%d, reason: 0x/4/%Xh)
CauseThe driver of a physical device or the device itself has failed or is faulty. When thisalarm occurs, the error cause must be evaluated in the external device (drive orencoder).
Meaning of alarm parameters
Type:
1–Actuator driver
2–Encoder driver
3–BitRead driver
4–BitWrite driver
5–ByteRead driver
6–ByteWrite driver
7–WordRead driver
8–WordWrite driver
9–DWordRead driver
10–DWordWrite driver
Logical address:This is the address configured on the technology object.
Bit number:For bit driver type = 3 or 4 only; bit number
Reason:0–Not defined (e.g., for binary I/O)
� Type = 1
0x0001h: Fault message from drive (note: On PROFIBUS drives, whichsupport acyclic communication in accordance with PROFIdrive V3, the error number/numbers of the drives is/are displayed in thediagnostic buffer, e.g., on Masterdrives MC).
0x0002h: DP: Drive signal “control requested” failed
0x0004h: DP: Drive switched off itself
0x0008h: Slot for drive data is not available in the project
0x0010h: Actuator driver does not have a connection to the drive data
0x0020h: Actuator driver was not initialized during power up
0x0080h: DP: Difference between configuration data and drive parameters
0x4000h: DP: Drive on bus failed (station failure)
0x8000h: Sign of life of drive faulty or failed
externalEncoderType
5-219� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
� Type = 2
0x0000h: The number of permissible changes in the actual value of the maximum velocity of the absolute-value encoder has beenexceeded
0x0001h: Fault message from encoder (note: The error number/numbersis/are displayed in the diagnostic buffer)
0x0002h: General hardware error of encoder
0x0004h: Encoder contaminated
0x0008h: Slot for encoder data is not available in the project
0x0010h: Encoder driver does not have a connection to the encoder data
0x0020h: Encoder driver was not initialized during power up
0x0040h: Error when reading the absolute value of the encoder
0x0080h: DP: Difference between the configuration data and the encoder parameters
0x0100h: Zero mark monitoring of encoder
0x4000h: DP: Encoder on bus failed (station failure)
0x8000h: DP: Sign of life of encoder has malfunctioned or failed. (Note: For an encoder whose data are transferred in a drive message together with actuator data, the actuator sign of lifeapplies for the encoder, e.g., a standard message 3 in accordancewith PROFIdrive).
� Type = 3 to 10
0x0000h: Additional information, not assigned
Note:Codings for the reason of the failure can also occur in combination. Theindividual codings are then added to form a coding sum, which is displayed(e.g., 0x0005 = 0x0001 + 0x0004). A reason for failure marked as DP can onlybe present on PROFIBUS devices.
RemedyCheck the device with respect to function and connections (reason 0x0001,0x0002, 0x0004, 0x4000, 0x8000).
� Check the topological configuration in HW Config (with reason 0x0008).
� For PROFIBUS drives or encoders, compare the configuration of HWConfig, thetechnology object, and the drive parameter assignment.For:
Reason 0x0040:
– Compare the encoder type in the drive or encoder parameter P979 with theconfiguration data of the technology object.
externalEncoderType
5-220� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
Reason 0x0080:
– Compare the message frame type in the drive or encoder parameter P922with HW Config and the configuration data of the technology object.
– Compare the encoder type, resolution, multiplier and, with absoluteencoders, the data length in the drive or encoder parameter P979 with theconfiguration data of the technology object.
– Compare the parameterization named in reason 0x8000 (reason 0x8000 canoccur as secondary fault).
Reason 0x8000:
– Compare the cycle clock parameters of HW Config (PROFIBUS line, SlaveOM for drive or encoder) and the execution system. Tmapc and servo mustbe parameterized with the same cycle clock period!
� System fault, contact the hotline (reason 0x0008, 0x0010, 0x0020).
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseENCODER_DISABLE
Programmable local responsesENCODER_DISABLE
externalEncoderType
5-221� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
20006 Error in configuration (category: /1/%d, error number: /2/%d)
CauseThis alarm indicates error states caused by a faulty or inconsistent configuration.The technology objects perform a plausibility check on the configuration. Errors areidentified by the error codes below.
Meaning of alarm parameters
Category: Area in which the error occurred.
1–Command decoding
2–Interpolator
3–Controller
4–Manipulated variable output
5–Encoder system
6–Technology object
Error number: Specification of error
500 = “TO in illegal status for configuration”
501 = “More configuration data expected than received”
502 = “Invalid data in configuration”
503 = “Version conflict in configuration”
1000 = “General configuration error”
2000 = “Error in actuator system configuration”
2001 = “Outside of limits of manipulated variable”
2003 = “Error in load gear ratios”
2004 = “Error in maximum velocity”
2005 = “Maximum velocity greater than maximum attainable velocity”
2006 = “Drive not suitable for torque-controlled or torque-limited operation”
2007 = “Linear stepper motor not implemented”
2008 = “Right-aligned format for direct output not implemented”
2009 = “Illegal value in resolution for direct output”
2010 = “Missing configuration data for actuator system”
2011 = “Missing configuration data for additional actuator system”
2012 = “The backstop range (min to max) does not contain a zero point”
2014 = “Drive or message frame not suitable for torque superimposition”
2015 = “Gear ratios less than or equal to 0”
2016 = “Resolution for stepper motor is 0”
2017 = “Illegal value for the configuration data maxSpeed”
2018 = “Illegal value for the configuration data maxVelocity”
2019 = “Limits of a configuration data exceeded”
2020 = “Limits for the max. acceleration exceeded”
2021 = “Illegal values for dead-zone compensation”
2022 = “Illegal values for sliding-friction compensation”
externalEncoderType
5-222� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
2023 = “Illegal values for backstop range”
2024 = “Error in sliding-friction compensation parameter”
3000 = “Error in encoder system”
3001 = “Error in encoder system”
3002 = “Invalid axis type selected”
3003 = “Leadscrew pitch is 0”
3004 = “Modulo axis selected with modulo value less than or equal to 0”
3005 = “Illegal specification(s) in the encoder data (incremental / absolute, etc.)”
3006 = “Illegal number of encoders selected”
3007 = “Illegal incremental encoder number”
3008 = “Illegal data combination for homing withincremental encoder”
3009 = “Illegal encoder number”
3010 = “Illegal data on SSI encoder”
3011 = “Illegal encoder number”
3012 = “Illegal encoder number”
3013 = “Illegal measuring gear data, DRIVE assembly type (e.g., factor = 0)”
3014 = “Illegal encoder number”
3015 = “Illegal measuring gear data, LOAD assembly type (e.g., factor = 0)”
3016 = “Illegal data set number (e.g., factor = 0)”
3017 = “Encoder data sequence and number of encoders do not match”
3018 = “Error in encoder system”
3019 = “Illegal encoder number”
3020 = “Illegal encoder system / actuator system simulation selected”
3021 = “Illegal encoder number or incorrect number of data sets”
3022 = “Illegal encoder number or incorrect number of data sets”
3023 = “Illegal data for ratio of external attachment (e.g., factor = 0)”
3024 = “Path/rotation of external attachment = 0”
3025 = “Illegal value for monitoring of actual velocity”
3026 = “Illegal encoder number in SSI encoder configuration”
3027 = “Illegal message format in SSI encoder configuration”
3028 = “Illegal baud rate in SSI encoder configuration”
3029 = “Illegal SSI state in SSI encoder configuration”
3030 = “Illegal encoder number in data set”
3031 = “Encoder number in data set not configured”
3032 = “Illegal numerator factor in data set”
3033 = “Illegal denominator factor in data set”
3034 = “Illegal data set number”
3035 = “Data set number not configured”
3036 = “Encoder not configured”
3037 = “Homing of ENDAT encoder with zero mark not possible”
3038 = “Homing of CAM negative edge onboard not possible”
3039 = “On-the-fly homing of ENDAT encoder with zero mark not possible”
externalEncoderType
5-223� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
3040 = “On-the-fly homing of CAM negative edge onboard not possible”
3041 = “Factors for adjusting encoder data to the mechanics are outside the permissible range of values”
3042 = “Illegal data combination for homing with external encoder”
3043 = “The incremental position of the encoder is outside the permissible range of values”
3044 = “The incremental position of the encoder is outside the permissible range of values”
3045 = “Illegal value for resolution of linear measuring system”
3046 = “Illegal value for filter of actual-velocity encoder”
3047 = “Illegal value for smoothing of actual-value encoder”
3048 = “Illegal value for smoothing of actual-value encoder with actual-valuecoupling”
3049 = “Illegal DSC encoder selection”
3050 = “Configuration of encoder system not completed correctly”
3051 = “Error in configuration of the sensor data or the stepper motor”
3052 = “Actual-value type (position, interval, velocity) not implemented”
3053 = “Only homing with CAM possible for stepper motor”
3054 = “Only on-the-fly homing with CAM possible for stepper motor”
3055 = “Stepper motor only possible with a real axis”
3056 = “Only one encoder permissible with stepper motor”
3057 = “DSC encoder is not a DP encoder”
3058 = “Illegal message frame of the DSC encoder”
3059 = “Modulo value too small”
3060 = “Configuration differential measurement position faulty”
3061 = “Illegal data in range configuration of the differential measurement position”
4000 = “Error in controller”
4001 = “Negative acceleration specified”
4002 = “Unknown ’FipoType’ requested”
4003 = “Error in runtime system, ratio of controller cycle clock to interpolator cycle clock incorrect”
4004 = “Requested filter arrangement not possible”
4005 = “Reserve for later use”
4006 = “Maximum limit is lower than minimum”
4007 = “Reserve for later use”
4008 = “Error in configuration data for controller”
4009 = “Reserve for later use”
4010 = “Reserve for later use”
4011 = “Reserve for later use”
4012 = “Reserve for later use”
4013 = “Requested controller type is not available”
4014 = “Error in controller factors”
4015 = “Feedforward control activated, kpc < 0 or kpc > 150”
externalEncoderType
5-224� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
4016 = “Reserve for later use”
4017 = “Reserve for later use”
4018 = “Reserve for later use”
4019 = “Reserve for later use”
4020 = “Reserve for later use”
4021 = “Reserve for later use”
4022 = “Reserve for later use”
4023 = “Feedforward control activated, kpc <= 0”
4024 = “Model reference monitoring: Error in value of tolerance window”
4025 = “Error in limit value for standstill signal”
4026 = “Error in parameter for positioning monitoring”
4027 = “Reference model and dynamic following error monitoring activated, not possible at the same time”
4028 = “Sampling time parameter calculated incorrectly”
4029 = “Too many data sets requested”
4030 = “Error in runtime system, ratio of controller cycle clock to interpolator cycle clock incorrect”
4031 = “Error in time constant for emergency stop ramp generator (positionTimeConstant)”
4032 = “Feedforward control active, but fine interpolator type is DIRECT”
4033 = “Default data set outside limits”
4034 = “Maximum number of data sets not possible”
4035 = “Unknown data set alternating mode”
4036 = “Following error monitoring not activated/deactivated in all data sets”
4037 = “Model reference monitoring not activated/deactivated in all data sets”
4038 = “Different controller type in data sets”
4039 = “Feedforward control activated/deactivated in data sets”
4040 = “Time constant is 0”
4041 = “Error in dynamic adaptation parameter”
4042 = “System variable initialization could not be read”
4043 = “Driver simulation not implemented”
4044 = “Connection for stepper motors not implemented”
4045 = “Maximum velocity cannot be reached, maximum drive speed or a normalization factor incorrect”
4046 = “DSC requires motor encoder data to be specified”
4047 = “Drive or message frame type not suitable for DSC”
4048 = “Error in clamping monitoring parameter. ’No identifier’ is not permitted for the fixed end stop identifier.
4049 = “Without sensor, monitoring of the actual velocity by ’DynamicControl’ not possible”
4050 = “Inconsistent PROFIBUS parameterization; the sum of Ti and To is greater than one DP clock cycle”
4051 = “Error in manipulated variable limit parameter of force/pressure controller”
externalEncoderType
5-225� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
4052 = “Error in starting force/pressure monitoring parameter”
4053 = “Error in full-scale force/pressure monitoring parameter”
4054 = “Starting force/pressure monitoring tolerance less than tolerance of full-scale pressure monitoring”
4055 = “Error in force/pressure system deviation monitoring parameter”
4056 = “Different activation/deactivation of the control difference monitoring of theforce/pressure controller not permitted in data sets”
4057 = “Different manipulated variable inversion of the force/pressure controller not permitted in data sets”
4058 = “Different force/pressure sensor types not permitted in data sets”
4059 = “Different activation/deactivation of the anti windup not permitted in data sets”
4060 = “Kd factor of the PID_ACTUAL controller is greater than 1”
4061 = “Time constant of the process model T1 <= T2”
4062 = “Illegal actuator type selection”
4063 = “Error in sliding friction compensation parameter”
4064 = “Error in offset application parameter”
4065 = “Feedforward control for force/pressure control not implemented”
4066 = “Error in standstill monitoring parameter”
4067 = “Following error monitoring: minVelocity must not be greater than or equal to maxVelocity”
4068 = “velocityTimeConstant when using a dead-time element for feedforward balancing too great”
4069 = “The system-related dead times are less than 0 after the calculation of additionalTime”
4070 = “Controller types not equal to DIRECT require the configuration of an encoder”
4071 = “Illegal values for delayTimeToActivate of the standstill signal”
4072 = “The IO device for the positive HW limit switch is not available”
4073 = “The IO device for the negative HW limit switch is not available”
4074 = “Limits of a controller parameter exceeded”
4075 = “Limit for emergency-stop-ramp brake delay exceeded”
4076 = “Limit for a substitute time constant exceeded”
4077 = “Limit for velocityTimeConstant exceeded”
4078 = “Error in value for configuration of QFDynamicData”
4079 = “Error in value for model reference monitoring”
4080 = “Error in following error monitoring parameter”
4081 = “Error in clamping monitoring parameter”
4082 = “Error in value for configuration of DynamicData”
4083 = “Error in value for configuration of PV controller”
4084 = “Incomplete configuration data for controller”
externalEncoderType
5-226� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
4085 = “Error in value for configuration of SystemDeadTimeData”
4086 = “Pressure control only possible with closed speed controller”
4087 = “DSC and compensation of valve characteristic not possible”
4088 = “DSC not possible on hydraulic axes”
4089 = “Time constant of dynamic compensation T1 <= T2”
4090 = “Incorrect value for correction of system dead time”
5000 = “Encoder data sequence and number of encoders do not match”
5001 = “Illegal number of additional sensors selected”
5002 = “Illegal additional sensor type selected”
5003 = “Illegal data in configuration of driver data for additional sensor”
5004 = “Illegal data in configuration of conversion data for additional sensor”
5006 = “Illegal data in configuration of range for additional sensor”
5007 = “Illegal data in configuration of filter time for additional sensor”
5008 = “Configuration of additional sensor not completed correctly”
5009 = “Illegal number for additional sensor in data set”
5010 = “Illegal data in configuration of differential pressure measurement”
5011 = “Error sensor A differential pressure measurement”
5012 = “Error sensor B differential pressure measurement”
5013 = “Illegal data in configuration of extrapolation”
5014 = “Illegal data in configuration of execution task for sensor TO”
5015 = “Illegal data in configuration of substitute value strategy for sensor TO technological alarm”
5020 = “Illegal data in configuration of driver data for analog sensor”
5021 = “Illegal data in configuration of position filter for analog sensor”
5022 = “Illegal data in configuration of conversion data for analog sensor”
5023 = “Illegal data in configuration of measurement input for analog sensor”
5030 = “Illegal data in configuration of conversion data for interval counter”
6000 = “In the configuration data, the monitoring of the positioning path isconfigured up to the reference-point switch, and the maximum path to be traveled in the process is configured as zero”
6001 = “Error in configuration data numberOfMaxBufferedCommandId”
6002 = “Error in configuration data numberOfQueueCommands”
6003 = “Error in configuration data numberOfImmediateCommands”
6004 = “Configuration of behaviourAtTheEndOfProfile not implemented”
6005 = “Illegal value for the configuration data maximum acceleration”
externalEncoderType
5-227� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
6006 = “Illegal value for the configuration data maximum jerk”
6007 = “Illegal value for the configuration data maximum force/pressure setpoint”
6008 = “Illegal value for the configuration data maximum force/pressure setpointrate of rise”
6009 = “Illegal value for the configuration data synchronous operation tolerance on the setpoint side”
6010 = “Illegal value for the configuration data synchronous operation tolerance on the actual-value side”
6011 = “Illegal value for the configuration data enable synchronous operation tolerance on the setpoint side”
6012 = “Illegal value for the configuration data enable synchronous operationtolerance on the actual-value side”
6013 = “Illegal value for the configuration data tolerance window end-of-profile detection”
6014 = “Illegal value for the configuration data extrapolation time actual values”
6015 = “Illegal value for the configuration data tolerance window actual-valuecoupling”
6016 = “Illegal value for the configuration data touchdown tolerance position limit”
6017 = “Illegal value for the configuration data handling mode position limit”
7000 = “Illegal data in configuration of a process model”
7001 = “Illegal data in configuration of the functional component >drive model< of a process model”
7002 = “Illegal data in configuration of the functional component >delay< of a process model”
7003 = “Illegal data in configuration of the functional component >shut down drive< of a process model”
7004 = “Illegal data in configuration of the functional component >encoder< of a process model”
7005 = “Illegal data in configuration of the functional component >switch< of a process model”
RemedyChange the configuration data.
Acknowledgment / responsePower On / START TechnologicalFaultTask
Default setting for local responseENCODER_DISABLE
Programmable local responsesENCODER_DISABLE
externalEncoderType
5-228� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
20007 Interconnection error (category: /1/%d, context: /2/%d, context parameter1:/3/%d, context parameter2: /4/%d)
CauseThis alarm indicates errors in the interconnection of technology objects. When theinterconnection is established, the technology object verifies it on the basis of theinterface properties. Errors are classified by category.
Meaning of alarm parameters
Category:
1 – TO compatibility errorAn interconnection is to be established with a technology object that has beenconfigured with another reference system (e.g., output cam with rotaryreference system and linear axis).
2 – Exclusive interfaceMultiple interconnections are to be established for an interface intended forexclusive interconnection.
3 – Interconnection requirementThe technology object is waiting for an interconnection required for thesequence.
4 – Interface initialization errorErrors result from extended initialization sequences at interfaces andparameter exchange between interconnected interfaces.
5 – Interface not available on technology objectAn interface specified in the interconnection is not available on the technologyobject.
6 – CircularityThe interconnection on the technology object leads to circular communicationwithin the technology object (e.g., circular master/slave interconnection ofgearing axes, whereby a gearing axis used as a master is in turn the slave ofanother master, which is assigned the master setpoints generated on thisgearing axis directly or via additional interconnections).
7 – Sequence-level compatibility errorAn interconnection is to be established with a technology object that isexecuted in another interpolator level (e.g., output cam with IPO and axis withIPO_2).
8 – Distribution initializationWhen interconnecting technology objects that are distributed among differentdevices, an error occurred during initialization of the communication interface.
9 – Illegal TO statusThe technology object cannot be interconnected in the current state.
Context:
The context provides additional information about the error category for the TOinterconnection. Additional parameters can be provided for the error descriptionon a context-specific basis. Context and context parameter are output as aninteger value.
externalEncoderType
5-229� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
Remedy
1 – Technology object compatibility error:Correct the configuration of the reference system of the technology objects tobe interconnected.
2 – Exclusive interface: Correct the configuration of the interconnected technology object.
3 – Interconnection request: Add the missing interconnection to your technology object.
4 – Error during interface initialization: Contact the hotline.
5 – Interface not available on technology object: Contact the hotline.
6 – Circularity:Remove unnecessary interconnections.
7 – Execution level compatibility error: Correct the configuration of the interpolator task level of the technology objectsto be interconnected.
8 – Distribution initialization:Check the hardware configuration. Ensure that the distributed interactingdevices are linked in the bus configuration. In addition, the address areas thatare used by the devices for communication must be set up. The address areasare automatically set up when the project is compiled; only afterwards is thevalid hardware configuration available for downloading.
9 – Illegal TO status:Correct the configuration of the technology object, correct execution errors.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseENCODER_DISABLE
Programmable local responsesENCODER_DISABLE
externalEncoderType
5-230� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
20008 Cannot assign USER_DEFAULT to system variables
CauseIt is not appropriate to assign USER_DEFAULT to a UserDefault system variable,because the variable references itself in this case.This prevents generation of a useful value during reading out. When this erroroccurs, the new Enum value is not assigned. The variable retains the old value.
RemedyUSER_DEFAULT is designed for use in technology commands.Avoid assigning it to system variables.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONE
20009 Reserved error
CauseThis error is not currently in use.
RemedyNot necessary, for information only.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseENCODER_DISABLE
Programmable local responsesENCODER_DISABLE
externalEncoderType
5-231� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
20010 A restart is necessary to activate the configuration data
CauseThe configuration cannot be set to active, since data have been modified in such away that does not permit it. The technology object must be restarted to activate thedata.
Remedy
� Execute the technology object reset command, and set the activateRestartparameter to ACTIVATE_RESTART.
� Set the restartActivation system variable to ACTIVATE_RESTART.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPSIMULATION_STOPSIMULATION_ABORTENCODER_DISABLE
externalEncoderType
5-232� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
20011 Error when activating the configuration (category: /1/%d, error number:/2/%d)
CauseThis note indicates error conditions when activating the configuration. The errorconditions can be traced back to an incorrect or inconsistent configuration. Thetechnology objects perform a plausibility check on the configuration. Errors areidentified by the error codes below.If this information appears, the configuration will not be activated.
Meaning of alarm parameters
Category: Area in which the error occurred.
1–Command decoding
2–Interpolator
3–Controller
4–Manipulated variable output
5–Encoder system
6–Technology object
Error number: Specification of error
1000 = “General configuration error”
2000 = “Error in actuator system configuration”
2001 = “Outside of limits of manipulated variable”
2003 = “Error in load gear ratios”
2004 = “Error in maximum velocity”
2005 = “Maximum velocity greater than maximum attainable velocity”
2006 = “Drive not suitable for torque-controlled or torque-limited operation”
2007 = “Linear stepper motor not implemented”
2008 = “Right-aligned format for direct output not implemented”
2009 = “Illegal value in resolution for direct output”
2010 = “Missing configuration data for actuator system”
2011 = “Missing configuration data for additional actuator system”
externalEncoderType
5-233� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
2012 = “The backstop range (min to max) does not contain a zero point”
2014 = “Drive or message frame not suitable for torque superimposition”
2015 = “Gear ratios less than or equal to 0”
2016 = “Resolution for stepper motor is 0”
2017 = “Illegal value for the configuration data maxSpeed”
2018 = “Illegal value for the configuration data maxVelocity”
2019 = “Limits of a configuration data exceeded”
2020 = “Limits for the max. acceleration exceeded”
2021 = “Illegal values for dead-zone compensation”
2022 = “Illegal values for sliding-friction compensation”
2023 = “Illegal values for backstop range”
2024 = “Error in sliding-friction compensation parameter”
3000 = “Error in encoder system”
3001 = “Error in encoder system”
3002 = “Invalid axis type selected”
3003 = “Leadscrew pitch is 0”
3004 = “Modulo axis selected with modulo value less than or equal to 0”
3005 = “Illegal specification(s) in the encoder data (incremental / absolute, etc.)”
3006 = “Illegal number of encoders selected”
3007 = “Illegal incremental encoder number”
3008 = “Illegal data combination for homing with incremental encoder”
3009 = “Illegal encoder number”
3010 = “Illegal data on SSI encoder”
3011 = “Illegal encoder number”
3012 = “Illegal encoder number”
3013 = “Illegal measuring gear data, DRIVE assembly type (e.g., factor = 0)”
3014 = “Illegal encoder number”
3015 = “Illegal measuring gear data, LOAD assembly type (e.g., factor = 0)”
3016 = “Illegal data set number (e.g., factor = 0)”
3017 = “Encoder data sequence and number of encoders do not match”
3018 = “Error in encoder system”
3019 = “Illegal encoder number”
3020 = “Illegal encoder system / actuator system simulation selected”
3021 = “Illegal encoder number or incorrect number of data sets”
3022 = “Illegal encoder number or incorrect number of data sets”
3023 = “Illegal data for ratio of external attachment (e.g., factor = 0)”
3024 = “Path/rotation of external attachment = 0”
3025 = “Illegal value for monitoring of actual velocity”
3026 = “Illegal encoder number in SSI encoder configuration”
3027 = “Illegal message format in SSI encoder configuration”
3028 = “Illegal baud rate in SSI encoder configuration”
externalEncoderType
5-234� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
3029 = “Illegal SSI state in SSI encoder configuration”
3030 = “Illegal encoder number in data set”
3031 = “Encoder number in data set not configured”
3032 = “Illegal numerator factor in data set”
3033 = “Illegal denominator factor in data set”
3034 = “Illegal data set number”
3035 = “Data set number not configured”
3036 = “Encoder not configured”
3037 = “Homing of ENDAT encoder with zero mark not possible”
3038 = “Homing of CAM negative edge onboard not possible”
3039 = “On-the-fly homing of ENDAT encoder with zero mark not possible”
3040 = “On-the-fly homing of CAM negative edge onboard not possible”
3041 = “Factors for adjusting encoder data to the mechanics are outside the permissible range of values”
3042 = “Illegal data combination for homing with external encoder”
3043 = “The incremental position of the encoder is outside the permissible range of values”
3044 = “The incremental position of the encoder is outside the permissible range of values”
3045 = “Illegal value for resolution of linear measuring system”
3046 = “Illegal value for filter of actual-velocity encoder”
3047 = “Illegal value for smoothing of actual-value encoder”
3048 = “Illegal value for smoothing of actual-value encoder with actual-valuecoupling”
3049 = “Illegal DSC encoder selection”
3050 = “Configuration of encoder system not completed correctly”
3051 = “Error in configuration of the sensor data or the stepper motor”
3052 = “Actual-value type (position, interval, velocity) not implemented”
3053 = “Only homing with CAM possible for stepper motor”
3054 = “Only on-the-fly homing with CAM possible for stepper motor”
3055 = “Stepper motor only possible with a real axis”
3056 = “Only one encoder permissible with stepper motor”
3057 = “DSC encoder is not a DP encoder”
3058 = “Illegal message frame of the DSC encoder”
3059 = “Modulo value too small”
3060 = “Configuration differential measurement position faulty”
3061 = “Illegal data in range configuration of the differential measurement position”
4000 = “Error in controller”
4001 = “Negative acceleration specified”
4002 = “Unknown ’FipoType’ requested”
4003 = “Error in runtime system, ratio of controller cycle clock to interpolator cycle clock incorrect”
4004 = “Requested filter arrangement not possible”
externalEncoderType
5-235� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
4005 = “Reserve for later use”
4006 = “Maximum limit is lower than minimum”
4007 = “Reserve for later use”
4008 = “Error in configuration data for controller”
4009 = “Reserve for later use”
4010 = “Reserve for later use”
4011 = “Reserve for later use”
4012 = “Reserve for later use”
4013 = “Requested controller type is not available”
4014 = “Error in controller factors”
4015 = “Feedforward control activated, kpc < 0 or kpc > 150”
4016 = “Reserve for later use”
4017 = “Reserve for later use”
4018 = “Reserve for later use”
4019 = “Reserve for later use”
4020 = “Reserve for later use”
4021 = “Reserve for later use”
4022 = “Reserve for later use”
4023 = “Feedforward control activated, kpc <= 0”
4024 = “Model reference monitoring: Error in value of tolerance window”
4025 = “Error in limit value for standstill signal”
4026 = “Error in parameter for positioning monitoring”
4027 = “Reference model and dynamic following error monitoring activated, not possible at the same time”
4028 = “Sampling time parameter calculated incorrectly”
4029 = “Too many data sets requested”
4030 = “Error in runtime system, ratio of controller cycle clock to interpolator cycle clock incorrect”
4031 = “Error in time constant for emergency stop ramp generator (positionTimeConstant)”
4032 = “Feedforward control active, but fine interpolator type is DIRECT”
4033 = “Default data set outside limits”
4034 = “Maximum number of data sets not possible”
4035 = “Unknown data set alternating mode”
4036 = “Following error monitoring not activated/deactivated in all data sets”
4037 = “Model reference monitoring not activated/deactivated in all data sets”
4038 = “Different controller type in data sets”
4039 = “Feedforward control activated/deactivated in data sets”
4040 = “Time constant is 0”
4041 = “Error in dynamic adaptation parameter”
4042 = “System variable initialization could not be read”
4043 = “Driver simulation not implemented”
4044 = “Connection for stepper motors not implemented”
externalEncoderType
5-236� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
4045 = “Maximum velocity cannot be reached, maximum drive speed or a normalization factor incorrect”
4046 = “DSC requires motor encoder data to be specified”
4047 = “Drive or message frame type not suitable for DSC”
4048 = “Error in clamping monitoring parameter” ’No identifier’ is not permitted for the fixed end stop identifier.
4049 = “Without sensor, monitoring of the actual velocity by ’DynamicControl’ not possible”
4050 = “Inconsistent PROFIBUS parameterization; the sum of Ti and To is greater than one DP clock cycle”
4051 = “Error in manipulated variable limit parameter of force/pressure controller”
4052 = “Error in starting force/pressure monitoring parameter”
4053 = “Error in full-scale force/pressure monitoring parameter”
4054 = “Starting force/pressure monitoring tolerance less than tolerance of full-scale pressure monitoring”
4055 = “Error in force/pressure system deviation monitoring parameter”
4056 = “Different activation/deactivation of the control difference monitoring of the force/pressure controller not permitted in data sets”
4057 = “Different manipulated variable inversion of the force/pressure controller not permitted in data sets”
4058 = “Different force/pressure sensor types not permitted in data sets”
4059 = “Different activation/deactivation of the anti windup not permitted in datasets”
4060 = “Kd factor of the PID_ACTUAL controller is greater than 1”
4061 = “Time constant of the process model T1 <= T2”
4062 = “Illegal actuator type selection”
4063 = “Error in sliding friction compensation parameter”
4064 = “Error in offset application parameter”
4065 = “Feedforward control for force/pressure control not implemented”
4066 = “Error in standstill monitoring parameter”
4067 = “Following error monitoring: minVelocity must not be greater than or equal to maxVelocity”
4068 = “velocityTimeConstant when using a dead-time element for feedforward balancing too great”
4069 = “The system-related dead times are less than 0 after the calculation of additionalTime”
4070 = “Controller types not equal to DIRECT require the configuration of an encoder”
4071 = “Illegal values for delayTimeToActivate of the standstill signal”
4072 = “The IO device for the positive HW limit switch is not available”
4073 = “The IO device for the negative HW limit switch is not available”
4074 = “Limits of a controller parameter exceeded”
externalEncoderType
5-237� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
4075 = “Limit for emergency-stop-ramp brake delay exceeded”
4076 = “Limit for a substitute time constant exceeded”
4077 = “Limit for velocityTimeConstant exceeded”
4078 = “Error in value for configuration of QFDynamicData”
4079 = “Error in value for model reference monitoring”
4080 = “Error in following error monitoring parameter”
4081 = “Error in clamping monitoring parameter”
4082 = “Error in value for configuration of DynamicData”
4083 = “Error in value for configuration of PV controller”
4084 = “Incomplete configuration data for controller”
4085 = “Error in value for configuration of SystemDeadTimeData”
4086 = “Pressure control only possible with closed speed controller”
4087 = “DSC and compensation of valve characteristic not possible”
4088 = “DSC not possible on hydraulic axes”
4089 = “Time constant of dynamic compensation T1 <= T2”
4090 = “Incorrect value for correction of system dead time”
5000 = “Encoder data sequence and number of encoders do not match”
5001 = “Illegal number of additional sensors selected”
5002 = “Illegal additional sensor type selected”
5003 = “Illegal data in configuration of driver data for additional sensor”
5004 = “Illegal data in configuration of conversion data for additional sensor”
5006 = “Illegal data in configuration of range for additional sensor”
5007 = “Illegal data in configuration of filter time for additional sensor”
5008 = “Configuration of additional sensor not completed correctly”
5009 = “Illegal number for additional sensor in data set”
5010 = “Illegal data in configuration of differential pressure measurement”
5011 = “Error sensor A differential pressure measurement”
5012 = “Error sensor B differential pressure measurement”
5013 = “Illegal data in configuration of extrapolation”
5014 = “Illegal data in configuration of execution task for sensor TO”
5015 = “Illegal data in configuration of substitute value strategy for sensor TO technological alarm”
5020 = “Illegal data in configuration of driver data for analog sensor”
5021 = “Illegal data in configuration of position filter for analog sensor”
5022 = “Illegal data in configuration of conversion data for analog sensor”
5023 = “Illegal data in configuration of measurement input for analog sensor”
externalEncoderType
5-238� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
5030 = “Illegal data in configuration of conversion data for interval counter”
6000 = “In the configuration data, the monitoring of the positioning path isconfigured up to the reference-point switch, and the maximum path to betraveled in the process is configured as zero”
6001 = “Error in configuration data numberOfMaxBufferedCommandId”
6002 = “Error in configuration data numberOfQueueCommands”
6003 = “Error in configuration data numberOfImmediateCommands”
6004 = “Configuration of behaviourAtTheEndOfProfile not implemented”
6005 = “Illegal value for the configuration data maximum acceleration”
6006 = “Illegal value for the configuration data maximum jerk”
6007 = “Illegal value for the configuration data maximum force/pressure setpoint”
6008 = “Illegal value for the configuration data maximum force/pressure setpointrate of rise”
6009 = “Illegal value for the configuration data synchronous operation tolerance on the setpoint side”
6010 = “Illegal value for the configuration data synchronous operation tolerance on the actual-value side”
6011 = “Illegal value for the configuration data enable synchronous operationtolerance on the setpoint side”
6012 = “Illegal value for the configuration data enable synchronous operationtolerance on the actual-value side”
6013 = “Illegal value for the configuration data tolerance window end-of-profile detection”
6014 = “Illegal value for the configuration data extrapolation time actual values”
6015 = “Illegal value for the configuration data tolerance window actual-valuecoupling”
6016 = “Illegal value for the configuration data touchdown tolerance position limit”
6017 = “Illegal value for the configuration data handling mode position limit”
7000 = “Illegal data in configuration of a process model”
7001 = “Illegal data in configuration of the functional component >drive model< of aprocess model”
7002 = “Illegal data in configuration of thefunctional component >delay< of a process model”
7003 = “Illegal data in configuration of thefunctional component >shut down drive< of a process model”
7004 = “Illegal data in configuration of the functional component >encoder< of a process model”
7005 = “Illegal data in configuration of the functional component >switch< of a process model”
RemedyChange the configuration data.
externalEncoderType
5-239� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPSIMULATION_STOPSIMULATION_ABORTENCODER_DISABLE
20012 Restart not executed (reason: /1/%d)
CauseTechnology object could not be restarted.
Meaning of alarm parameters
Reason:
1 – The technology object configuration does not allow a restart with the restartsystem variable. You can initiate the restart using the reset command.
2 – The technology object is not ready to be restarted.
3 – A configured condition for restarting the technology object is not met (e.g.,technology object must be disabled).
4 – Restart has not been executed or executed with the last programmedconfiguration of the technology object.
Remedy
� Work around the cause stated in the Reason parameter, or reload the project.
� Use the device diagnostics to establish whether technological alarms werereported and, if necessary, remedy the cause of the alarm.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPSIMULATION_STOPSIMULATION_ABORTENCODER_DISABLE
externalEncoderType
5-240� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
20014 At the logical address: /1/%d (optional log. address: /2/%d and bit no.: /3/%dof the enable output), a driver (type: /4/%d) could not be requested
CauseThe driver of a physical device is not available or is being used by another TO.
Meaning of alarm parameters
Logical address:
This is the address of the actuator driver configured on the technology object.
Logical address and bit number:
This specifies the address and bit number of the output enable bit
Type:
1–Actuator driver
2–Encoder driver
3–BitRead driver
4–BitWrite driver
5–ByteRead driver
6–ByteWrite driver
7–WordRead driver
8–WordWrite driver
9–DWordRead driver
10–DWordWrite driver
Remedy
� Check that the logical device was available at the time of the request or whetherit was being used by another technology object.
� Connect a suitable device.
� Check the device (function, connections, terminals).
� Check the topological configuration in HWConfig.
� Compare configuration of HWConfig and technology object.
� Contact the hotline.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseENCODER_DISABLE
Programmable local responsesENCODER_DISABLE
externalEncoderType
5-241� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
30001 Illegal parameter (parameter index according to standard sequence in thesystem functions: /1/%d, command type: /4/%X)
CauseIllegal system function parameter, the command is aborted. The parameters indicate the position of the illegal system function parameteraccording to the standard sequence in the system functions and the command typeof an incorrectly entered parameter.
Meaning of alarm parameters
Parameter index:
Index of the first system function parameter that triggered this error (listedaccording to the standard sequence in the system functions).
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyChange the parameters.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPSIMULATION_STOPSIMULATION_ABORTENCODER_DISABLE
externalEncoderType
5-242� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
30002 Command aborted (reason: /1/%d, command type: /4/%X)
CauseExecution of the command was aborted before or during processing.This condition can arise as a result of loading a new command, resetting thecommand buffer, or an error state.
Meaning of alarm parameters
Reason:
1–Command buffer reset
2–Abort by another command
3–Aborted by a stop
4–Aborted by a higher-order stop
5–Abort by a pending error response
6–Aborted due to ambiguous commandId
7–Delayed acknowledgment
8–No actual value for axis (e.g., encoder or data bus not ready)
9–Aborted due to abnormal termination of a dependent command
10–Aborted due to active synchronous operation
11–Aborted due to active superimposed motion
12–Aborted due to active speed-controlled controller mode
13–Aborted due to active position-controlled controller mode
14–Aborted due to active motion to fixed end stop
15–Axis is not in pressure-limiting operation
16–Aborted due to active pressure-controlled operation
17–Aborted due to inactive pressure-controlled operation
18–Superimposed command is not permitted
19–Aborted due to error during cam access
20–Slave is not ready for operation
21–Error in slave synchronization
22–Aborted by command on slave
23–Aborted by stop on slave
24–Aborted by an active error response on the slave
25–No actual value for slave (e.g., encoder or data bus not ready)
26–Aborted by reset on slave
27–Master values are not valid
28–Active command in recursive TO interconnection
29–Aborted due to error during synchronization
30–Axis is in pressure-limiting operation
31–Maximum number of active commands exceeded
32–Aborted due to active correction command
33–Action only permissible in standstill
Command type:
Outputs the aborted command type. The command type is output as ahexadecimal integer value.
externalEncoderType
5-243� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
RemedyReset command via program.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPSIMULATION_STOPSIMULATION_ABORTENCODER_DISABLE
30003 Command aborted due to full command buffer (command type: /4/%X)
CauseThe command is not entered in the command buffer as the buffer is already full.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
Remedy
� Check the program flow.
� Typical cause: The ’nextCommand’ parameter is passed with the valueIMMEDIATELY. You need to synchronize the command sequence manually oruse another value for ’nextCommand’.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPSIMULATION_STOPSIMULATION_ABORTENCODER_DISABLE
externalEncoderType
5-244� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
30004 Unknown command (command type: /4/%X)
CauseThe active software tool does not support this command.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyCheck the versions of the engineering system and the runtime software.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPSIMULATION_STOPSIMULATION_ABORTENCODER_DISABLE
externalEncoderType
5-245� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
30005 Ambiguous commandId (number of commands with specified ID: /1/%d,command type: /4/%X)
CauseThe specified commandID refers to several commands.The specified action is performed for the command matching the specifiedcommandID that has been in the interpolator for the longest time. If nocorresponding command is found in the interpolator, the action refers to the nextcommand loaded in the interpolator.
Meaning of alarm parameters
Number of commands with specified ID:
Number of commands referenced by the specified commandId.
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyUse different commandIds for commands that are active simultaneously.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPSIMULATION_STOPSIMULATION_ABORTENCODER_DISABLE
externalEncoderType
5-246� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
30006 Cannot execute command due to current object state (command type: /4/%X)
CauseThe object is in the stop, error, or reset state and the command is not possible inthis object state.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
Remedy
� Check the object status.
� Check the permissible sequence of commands.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPSIMULATION_STOPSIMULATION_ABORTENCODER_DISABLE
30007 The error cannot be reset due to its configuration
CauseThe alarm cannot be acknowledged at the present time or by the selected means.
Remedy
� Check the configured acknowledgment procedure.
� If necessary, change the acknowledgment procedure for the alarm.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPSIMULATION_STOPSIMULATION_ABORTENCODER_DISABLE
externalEncoderType
5-247� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
30008 A connection to a technology object required for this operation does notexist (command type: /4/%X)
CauseThe object connection required for this operation has not been configured.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyCheck the project configuration, or change the object connection in the command.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPSIMULATION_STOPSIMULATION_ABORTENCODER_DISABLE
externalEncoderType
5-248� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
30009 Command rejected due to suspension of command decoding on addressedtechnology object (command type: /4/%X)
CauseCommand was rejected due to suspension of command decoding on theaddressed technology object.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
Remedy
� Check why the command was rejected.
� If necessary, acknowledge any active errors once you have corrected the causeof the error.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPSIMULATION_STOPSIMULATION_ABORTENCODER_DISABLE
externalEncoderType
5-249� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
30010 Command not available (command type: /4/%X)
CauseThe command is not available in this version of the runtime software.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyCheck the version of the runtime software.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPSIMULATION_STOPSIMULATION_ABORTENCODER_DISABLE
externalEncoderType
5-250� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
30011 Parameter unavailable (parameter index according to standard sequence inthe system functions: /1/%d, command type: /4/%X)
CauseThe parameter is not available in this version of the runtime software, thecommand is therefore rejected. The parameters indicate the position according tothe standard sequence in the system functions and the command type of anincorrectly entered parameter.
Meaning of alarm parameters
Parameter index:
Index of the command parameter triggering this error according to the standardsequence in the system functions.
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyCheck the version of the runtime software.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPSIMULATION_STOPSIMULATION_ABORTENCODER_DISABLE
externalEncoderType
5-251� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
30012 Command cannot be started synchronously (command type: /4/%X)
CauseThe command cannot be used during a BEGIN_SYNC, END_SYNC sequencebecause it is a reset command or a command that has only one return value in theuser program.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyDo not use this command type during a BEGIN_SYNC, END_SYNC sequence.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPSIMULATION_STOPSIMULATION_ABORTENCODER_DISABLE
externalEncoderType
5-252� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
30013 Synchronous start of the command using IMMEDIATELY mergeMode(command type: /4/%X)
CauseWith synchronous command start, only merge modes that immediately override thecurrent command (IMMEDIATELY) and superimpose the current command(SUPERIMPOSED_MOTION_MERGE) can be used. If an illegal merge mode isprogrammed (e.g., SEQUENTIAL or NEXT_MOTION), the system automaticallychanges the merge mode to IMMEDIATELY and outputs this warning.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyProgram the command, which is to be started synchronously to immediatelyoverride the current command. To do this, enter the value IMMEDIATELY in the’mergeMode’ command parameter.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPSIMULATION_STOPSIMULATION_ABORTENCODER_DISABLE
externalEncoderType
5-253� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
30014 Coordinate system not offset due to the internal traversing range limit beingexceeded (Parameter1: /1/% /1/%d, command type: /2/%X)
CauseThe programmed coordinate system offset causes the internal traversing rangelimit to be exceeded. The coordinate system is not shifted.
Meaning of alarm parameters
Parameter1:
= 0 negative internal traversing range limit
= 1 positive internal traversing range limit
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyCheck the programming for the coordinate system offset.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPSIMULATION_STOPSIMULATION_ABORTENCODER_DISABLE
externalEncoderType
5-254� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
30015 A technology required for this command was not configured (technology:/1/%d, command type: /4/%X)
CauseThe command cannot be selected in this technology object configuration.
Meaning of alarm parameters
Technology:
= 1 Axis with force/pressure control without flow/force specification
= 2 Axis with force/pressure control and flow/force specification
= 3 Axis without flow/force specification
= 4 Axis with flow/force specification
= 5 Axis with force specification
= 6 Axis with pressure setpoint specification
= 7 Axis with pressure limiting
= 8 Axis with speed limiting parallel to force/pressure control
= 9 Axis with flow specification
Command type:Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyActivate the technology needed for the command.
Technology:
= 1 Select the mode setting REAL_AXIS_WITH_PRESSURE_CONTROL in theTypeOfAxis configuration data
= 2 Select the mode settingREAL_QP_AXIS_WITH_CLOSED_LOOP_FORCE_CONTROL in theTypeOfAxis configuration data
= 3 Select the mode setting VIRTUAL_AXIS, REAL_AXIS orREAL_AXIS_WITH_FORCE_CONTROL in the TypeOfAxis configuration data
= 4 Select the mode setting EAL_QPAXIS,REAL_QP_AXIS_WITH_OPEN_LOOP_FORCE_CONTROL orREAL_QP_AXIS_WITH_CLOSED_LOOP_FORCE_CONTROL in theTypeOfAxis configuration data
= 5 Select the mode settingREAL_QP_AXIS_WITH_OPEN_LOOP_FORCE_CONTROL in the TypeOfAxisconfiguration data
= 6 Select the mode setting REAL_AXIS_WITH_PRESSURE_CONTROL orREAL_QP_AXIS_WITH_CLOSED_LOOP_FORCE_CONTROL in theTypeOfAxis configuration data
= 7 Select the mode setting REAL_AXIS_WITH_PRESSURE_CONTROL,REAL_QP_AXIS_WITH_OPEN_LOOP_FORCE_CONTROL orREAL_QP_AXIS_WITH_CLOSED_LOOP_FORCE_CONTROL in theTypeOfAxis configuration data
= 8 Select the mode settingREAL_QP_AXIS_WITH_CLOSED_LOOP_FORCE_CONTROL in theTypeOfAxis configuration data
= 9 Select a mode setting with flow specification in the TypeOfAxis configurationdata
externalEncoderType
5-255� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPSIMULATION_STOPSIMULATION_ABORTENCODER_DISABLE
40005 Enable signal(s) missing (Parameter1: /1/%X) and/or incorrect mode(Parameter2: /2/%d)
CauseThe enables are missing and/or follow-up mode is active on the axis are missing when a command is pending.
Meaning of alarm parameters
Parameter1:
Bit 1 = 0: POWER enable signal is available1: POWER enable signal is missing
Bit 2 = 0: DRIVE enable signal is available1: DRIVE enable signal is missing
Bit 3 = 0: Position controller enable signal is available1: Position controller enable signal is missing
Bit 4 = 0: Force/pressure controller enable signal is available1: Force/pressure controller enable signal is missing
Parameter2:
0 – Follow-up mode deselected
1 – Follow-up mode selected
RemedyActivate the enable signals before issuing a motion command.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseENCODER_DISABLE
Programmable local responsesENCODER_DISABLE
externalEncoderType
5-256� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
40102 Encoder zero mark not found during homing
CauseThe encoder zero mark could not be found because:
� The difference between the reference output cam and the encoder zero mark isoutside the permissible range.
� Limit switch monitoring system has responded.
� The reference deceleration velocity is too high.
Remedy
� Check the permissible range.
� Check the hardware configuration.
� Reduce the deceleration velocity.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseENCODER_DISABLE
Programmable local responsesENCODER_DISABLE
externalEncoderType
5-257� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
40103 Error in homing configuration data (Parameter1: /1/%d)
CauseThe configured data of the external encoder and the selected parameters in thesynchronization command are inconsistent with one another.
Meaning of alarm parameters
Parameter1
1 – ENABLE_OFFSET_OF_ABSOLUTE_ENCODER has been selected in thesynchronization command but an incremental encoder is configured.
2 – PASSIVE_HOMING has been selected in the synchronization command, but anSSI encoder is configured.
4 – PASSIVE_HOMING or ENABLE_OFFSET_OF_ABSOLUTE_ENCODER hasbeen selected in the synchronization command, but NO_SENSOR has beenselected under encoderType in the configuration data for the encoder.
RemedyCheck the configuration data and the command parameters for homing
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseENCODER_DISABLE
Programmable local responsesENCODER_DISABLE
externalEncoderType
5-258� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
40110 Error triggered on slave during synchronous operation (error number: /1/%d)
CauseAn error was triggered on a slave during synchronous operation and reported tothe master.
Meaning of alarm parameters
Error number: Error reported by slave.
1–Synchronous operation setpoint tolerance exceeded.
2–Synchronous operation actual-value tolerance exceeded.
RemedyCheck the configuration data for synchronous operation monitoring on the slave,the programming (dynamic parameters, synchronous operation coupling), and thesystem variables.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseENCODER_DISABLE
Programmable local responsesENCODER_DISABLE
40124 Offset cannot be compensated
CauseThe determined cycle clock offset is greater than the maximum permissiblesetpoint output delay. The offset cannot be compensated completely in the master.
RemedyNot necessary, for information only.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPENCODER_DISABLE
externalEncoderType
5-259� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
40125 Setpoint output delay deactivated in the master
CauseThis leading value source operates without setpoint output delay on the masterside.The setpoint output delay on the master side has been activated on at least oneinterconnected following axis. The synchronous operation relationship between theleading value source and the following axis is not operating synchronously.
RemedyActivate the setpoint output delay for the master setpoint source in the master.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPENCODER_DISABLE
externalEncoderType
5-260� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
40301 Connection with slave failed (assignment: /1/%d)
CauseThe connection with an interconnected slave has failed. The slave is located on adistributed controller or has been assigned to a different execution level than themaster. Leading values of the master cannot be communicated to the slave for theduration of the connection failure. During the communication malfunction, asynchronous operation monitoring response on the slave cannot be communicatedto the master.
Meaning of alarm parameters
Assignment 1: The failed slave is located on an assigned controller.
Assignment 2: The failed slave has been assigned to a different execution levelthan the master.
Remedy
� Check that the assigned controller is activated, the slave is configured asdistributed, and communication is permitted by the operating mode of theassociated controller (assignment 1).
� Check the connection for mechanical damage, equivalence of configurednetwork topology, firm contact by the plug connector, and, if necessary, correctelectrical cable terminations (assignment 1).
� Check that the failed slave was not being reloaded at the time the error wasdetected (assignment 1 and 2).
� Check whether an overflow was diagnosed for the execution level of theassigned slave (assignment 2).
� Monitoring of the connection is set in the technology object configuration. Themaster and slave must have the same settings selected (assignment 1 and 2).
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEENCODER_DISABLE
externalEncoderType
5-261� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
40302 Sign-of-life monitoring for the slave in distributed synchronous operation isdeactivated
CauseSign-of-life monitoring for the slave connection on an assigned controller has beendeactivated. Monitoring is configured differently on the master and slave. As aresult, the connection is established without sign of life monitoring.
CauseUse identical configuration settings in the master and slave for sign-of-lifemonitoring of the connection
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEENCODER_DISABLE
40303 Local and slave interpolation cycle clock are different
CauseThe master and slave must have a common interpolation cycle clock for distributedsynchronous operation. However, when establishing the connection betweentechnology objects, different cycle clock settings were defined for interpolation.
RemedyUse identical cycle clock settings in the master and slave for interpolation.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEENCODER_DISABLE
externalEncoderType
5-262� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
40304 Offset cannot be determined
CauseThe offset for the slave cannot be determined. This can be caused by configuringthe PROFIBUS-DP without equidistance or a ratio of interpolator cycle clock toPROFIBUS-DP cycle clock greater than 64.
Remedy
� Select equidistant mode on the PROFIBUS-DP.
� Select a suitable IPO / DP cycle clock ratio setting
� Deactivate offset compensation on the technology objects involved. Deactivate compensation only if other remedies do not eliminate themalfunction. Deactivating the offset compensation limits the accuracy of motioncontrol.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEENCODER_DISABLE
50001 Drive failure
CauseDrive fault.
RemedyCheck the configuration of the drive system, the cabling, and the power supply.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseENCODER_DISABLE
Programmable local responsesENCODER_DISABLE
externalEncoderType
5-263� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
50002 Limiting frequency of measuring system exceeded
CauseThe limiting frequency of the encoder has been exceeded.
Remedy
� Check the encoder connection.
� Check the maximum velocity limits in the configuration data.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPSIMULATION_STOPSIMULATION_ABORTENCODER_DISABLE
50003 Speed acceleration setpoint limitation active
CauseThe speed acceleration setpoint is limited.
Remedy
� Check the mechanical configuration.
� Check the encoder connection.
� Check the configuration of the speed setpoint interface.
� Check the maximum permissible acceleration rates in the configuration data.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPSIMULATION_STOPSIMULATION_ABORTENCODER_DISABLE
externalEncoderType
5-264� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
50005 Speed setpoint monitoring active (Parameter1: /1/%d)
CauseThe speed setpoint is limited.
Remedy
� Check the mechanical configuration.
� Check the encoder connection.
� Check the configuration of the speed setpoint interface.
� Check the maximum permissible velocities in the configuration data.
Parameter 1: Specification of limitation1–Limitation of the velocity-related definition range (on hydraulic axes beforethe cam) reached.2–Limitation of the value range (hydraulic axes only) reached.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPSIMULATION_STOPSIMULATION_ABORTENCODER_DISABLE
50006 Zero mark monitoring
CauseThe zero mark monitoring system has responded.
Remedy
� Check the mechanical configuration and the encoder configuration.
� Check the encoder error messages.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseENCODER_DISABLE
Programmable local responsesNONEDECODE_STOPSIMULATION_STOPSIMULATION_ABORTENCODER_DISABLE
externalEncoderType
5-265� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
50007 Hardware limit switch (Parameter1: /1/%d, Parameter2: /2/%d)
CauseHardware limit switch has been violated.
Meaning of alarm parameters
Parameter1:
1: Limit switch reached
2: Polarity reversal on limit switch (can only be deleted by reconfiguring thetechnology object or Power On)
3: Illegal retraction direction
4: Both limit switches are active
Parameter2:
0: Not relevant
1: Limit switch in positive traversing direction
2: Limit switch in negative traversing direction
Remedy
� Check the mechanical configuration.
� Check the limit switches.
� If an error has occurred in the program, change the program or use the softwarelimit switches.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseENCODER_DISABLE
Programmable local responsesENCODER_DISABLE
50008 Timeout waiting for standstill signal
CauseTimeout occurred while waiting for standstill signal.
Remedy
� Check the configuration of ’Axis.TypeOfAxis.StandStillSignal’.
� Check that the control loop is operating correctly.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseENCODER_DISABLE
Programmable local responsesENCODER_DISABLE
externalEncoderType
5-266� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
50009 Limit switch active: (Parameter1: /1/%d) only one traversing directionpossible
CauseA positive (Parameter1 = 1) or negative (Parameter1 = 2) hardware limit switch isactive or has been crossed. Motion is possible in the positive or negative traversing direction only.
Remedy
� Check the mechanical configuration.
� Check the limit switches.
� If an error has occurred in the program, change the program or use the softwarelimit switches.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONE
externalEncoderType
5-267� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
50010 Error while reading or writing data set (category: /1/%d, error number: /2/%d)
CauseAn error occurred while reading or writing.
Meaning of alarm parameters
Category: Area in which the error occurred.
1–Command decoding
2–Interpolator
3–Controller
4–Manipulated variable output
5–Encoder system
Error number: Specification of error
1000 = “General configuration error”
2000 = “Error in actuator system configuration”
2001 = “Outside of limits of manipulated variable”
2003 = “Error in load gear ratios”
2004 = “Error in maximum velocity”
2005 = “Maximum velocity greater than maximum attainable velocity”
2006 = “Drive not suitable for torque-controlled or torque-limited operation”
2007 = “Linear stepper motor not implemented”
2008 = “Right-aligned format for direct output not implemented”
2009 = “Illegal value in resolution for direct output”
2010 = “Missing configuration data for actuator system”
2011 = “Missing configuration data for additional actuator system”
2012 = “The backstop range (min to max) does not contain a zero point”
2014 = “Drive or message frame not suitable for torque superimposition”
2015 = “Gear ratios less than or equal to 0”
2016 = “Resolution for stepper motor is 0”
2017 = “Illegal value for the configuration data maxSpeed”
2018 = “Illegal value for the configuration data maxVelocity”
2019 = “Limits of a configuration data exceeded”
2020 = “Limits for the max. acceleration exceeded”
2021 = “Illegal values for dead-zone compensation”
2022 = “Illegal values for sliding-friction compensation”
2023 = “Illegal values for backstop range”
2024 = “Error in sliding-friction compensation parameter”
3000 = “Error in encoder system”
3001 = “Error in encoder system”
3002 = “Invalid axis type selected”
3003 = “Leadscrew pitch is 0”
3004 = “Modulo axis selected with modulo value less than or equal to 0”
externalEncoderType
5-268� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
3005 = “Illegal specification(s) in the encoder data (incremental / absolute, etc.)”
3006 = “Illegal number of encoders selected”
3007 = “Illegal incremental encoder number”
3008 = “Illegal data combination for homing withincremental encoder”
3009 = “Illegal encoder number”
3010 = “Illegal data on SSI encoder”
3011 = “Illegal encoder number”
3012 = “Illegal encoder number”
3013 = “Illegal measuring gear data, DRIVE assembly type (e.g., factor = 0)”
3014 = “Illegal encoder number”
3015 = “Illegal measuring gear data, LOAD assembly type (e.g., factor = 0)”
3016 = “Illegal data set number (e.g., factor = 0)”
3017 = “Encoder data sequence and number of encoders do not match”
3018 = “Error in encoder system”
3019 = “Illegal encoder number”
3020 = “Illegal encoder system / actuator system simulation selected”
3021 = “Illegal encoder number or incorrect number of data sets“
3022 = “Illegal encoder number or incorrect number of data sets”
3023 = “Illegal data for ratio of external attachment (e.g., factor = 0)”
3024 = “Path/rotation of external attachment = 0”
3025 = “Illegal value for monitoring of actual velocity”
3026 = “Illegal encoder number in SSI encoder configuration”
3027 = “Illegal message format in SSI encoder configuration”
3028 = “Illegal baud rate in SSI encoder configuration”
3029 = “Illegal SSI state in SSI encoder configuration”
3030 = “Illegal encoder number in data set”
3031 = “Encoder number in data set not configured”
3032 = “Illegal numerator factor in data set”
3033 = “Illegal denominator factor in data set”
3034 = “Illegal data set number”
3035 = “Data set number not configured”
3036 = “Encoder not configured”
3037 = “Homing of ENDAT encoder with zero mark not possible”
3038 = “Homing of CAM negative edge onboard not possible”
3039 = “On-the-fly homing of ENDAT encoder with zero mark not possible”
3040 = “On-the-fly homing of CAM negative edge onboard not possible”
3041 = “Factors for adjusting encoder data to the mechanics are outside the permissible range of values”
3042 = “Illegal data combination for homing with external encoder”
3043 = “The incremental position of the encoder is outside the permissible range of values”
externalEncoderType
5-269� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
3044 = “The incremental position of the encoder is outside the permissible range of values”
3045 = “Illegal value for resolution of linear measuring system”3046 = “Illegal value for filter of actual-velocity encoder”3047 = “Illegal value for smoothing of actual-value encoder”3048 = “Illegal value for smoothing of actual-value encoder with actual-value
coupling”3049 = “Illegal DSC encoder selection”3050 = “Configuration of encoder system not completed correctly”3051 = “Error in configuration of the sensor data or the stepper motor”3052 = “Actual-value type (position, interval, velocity) not implemented”3053 = “Only homing with CAM possible for stepper motor”3054 = “Only on-the-fly homing with CAM possible for stepper motor”3055 = “Stepper motor only possible with a real axis”3056 = “Only one encoder permissible with stepper motor”3057 = “DSC encoder is not a DP encoder”3058 = “Illegal message frame of the DSC encoder”3059 = “Modulo value too small”3060 = “Configuration differential measurement position faulty”3061 = “Illegal data in range configuration of the differential measurement position”4000 = “Error in controller”4001 = “Negative acceleration specified”4002 = “Unknown ’FipoType’ requested”4003 = “Error in runtime system, ratio of controller cycle clock to interpolator
cycle clock incorrect”4004 = “Requested filter arrangement not possible”4005 = “Reserve for later use”4006 = “Maximum limit is lower than minimum”4007 = “Reserve for later use”4008 = “Error in configuration data for controller”4009 = “Reserve for later use”4010 = “Reserve for later use”4011 = “Reserve for later use”4012 = “Reserve for later use”4013 = “Requested controller type is not available”4014 = “Error in controller factors”4015 = “Feedforward control activated, kpc < 0 or kpc > 150”4016 = “Reserve for later use”4017 = “Reserve for later use”4018 = “Reserve for later use”4019 = “Reserve for later use”4020 = “Reserve for later use”4021 = “Reserve for later use”4022 = “Reserve for later use”
externalEncoderType
5-270� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
4023 = “Feedforward control activated, kpc <= 0”
4024 = “Model reference monitoring: Error in value of tolerance window”
4025 = “Error in limit value for standstill signal”
4026 = “Error in parameter for positioning monitoring”
4027 = “Reference model and dynamic following error monitoring activated, not possible at the same time”
4028 = “Sampling time parameter calculated incorrectly”
4029 = “Too many data sets requested”
4030 = “Error in runtime system, ratio of controller cycle clock to interpolator cycle clock incorrect”
4031 = “Error in time constant for emergency stop ramp generator (positionTimeConstant)”
4032 = “Feedforward control active, but fine interpolator type is DIRECT”
4033 = “Default data set outside limits”
4034 = “Maximum number of data sets not possible”
4035 = “Unknown data set alternating mode”
4036 = “Following error monitoring not activated/deactivated in all data sets”
4037 = “Model reference monitoring not activated/deactivated in all data sets”
4038 = “Different controller type in data sets”
4039 = “Feedforward control activated/deactivated in data sets”
4040 = “Time constant is 0”
4041 = “Error in dynamic adaptation parameter”
4042 = “System variable initialization could not be read”
4043 = “Driver simulation not implemented”
4044 = “Connection for stepper motors not implemented”
4045 = “Maximum velocity cannot be reached, maximum drive speed or a normalization factor incorrect”
4046 = “DSC requires motor encoder data to be specified”
4047 = “Drive or message frame type not suitable for DSC”
4048 = “Error in clamping monitoring parameter” ’No identifier’ is not permitted for the fixed end stop identifier.
4049 = “Without sensor, monitoring of the actual velocity by ’DynamicControl’ not possible”
4050 = “Inconsistent PROFIBUS parameterization; the sum of Ti and To is greater than one DP clock cycle”
4051 = “Error in manipulated variable limit parameter of force/pressure controller”
4052 = “Error in starting force/pressure monitoring parameter”
4053 = “Error in full-scale force/pressure monitoring parameter”
4054 = “Starting force/pressure monitoring tolerance less than tolerance of full-scale pressure monitoring”
4055 = “Error in force/pressure system deviation monitoring parameter”
externalEncoderType
5-271� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
4056 = “Different activation/deactivation of the control difference monitoring of the force/pressure controller not permitted in data sets”
4057 = “Different manipulated variable inversion of the force/pressure controller not permitted in data sets”
4058 = “Different force/pressure sensor types not permitted in data sets”
4059 = “Different activation/deactivation of the anti windup not permitted in data sets”
4060 = “Kd factor of the PID_ACTUAL controller is greater than 1”
4061 = “Time constant of the process model T1 <= T2”
4062 = “Illegal actuator type selection”
4063 = “Error in sliding friction compensation parameter”
4064 = “Error in offset application parameter”
4065 = “Feedforward control for force/pressure control not implemented”
4066 = “Error in standstill monitoring parameter”
4067 = “Following error monitoring: minVelocity must not be greater than or equal to maxVelocity”
4068 = “velocityTimeConstant when using a dead-time element for feedforward balancing too great”
4069 = “The system-related dead times are less than 0 after the calculation of additionalTime”
4070 = “Controller types not equal to DIRECT require the configuration of an encoder”
4071 = “Illegal values for delayTimeToActivate of the standstill signal”
4072 = “The IO device for the positive HW limit switch is not available”
4073 = “The IO device for the negative HW limit switch is not available”
4074 = “Limits of a controller parameter exceeded”
4075 = “Limit for emergency-stop-ramp brake delay exceeded”
4076 = “Limit for a substitute time constant exceeded”
4077 = “Limit for velocityTimeConstant exceeded”
4078 = “Error in value for configuration of QFDynamicData”
4079 = “Error in value for model reference monitoring”
4080 = “Error in following error monitoring parameter”
4081 = “Error in clamping monitoring parameter”
4082 = “Error in value for configuration of DynamicData”
4083 = “Error in value for configuration of PV controller”
4084 = “Incomplete configuration data for controller”
4085 = “Error in value for configuration of SystemDeadTimeData”
4086 = “Pressure control only possible with closed speed controller”
4087 = “DSC and compensation of valve characteristic not possible”
4088 = “DSC not possible on hydraulic axes”
4089 = “Time constant of dynamic compensation T1 <= T2”
externalEncoderType
5-272� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
4090 = “Incorrect value for correction of system dead time”
5000 = “Encoder data sequence and number of encoders do not match”
5001 = “Illegal number of additional sensors selected”
5002 = “Illegal additional sensor type selected”
5003 = “Illegal data in configuration of driver data for additional sensor”
5004 = “Illegal data in configuration of conversion data for additional sensor”
5006 = “Illegal data in configuration of range for additional sensor”
5007 = “Illegal data in configuration of filter time for additional sensor”
5008 = “Configuration of additional sensor not completed correctly”
5009 = “Illegal number for additional sensor in data set”
5010 = “Illegal data in configuration of differential pressure measurement”
5011 = “Error sensor A differential pressure measurement”
5012 = “Error sensor B differential pressure measurement”
5013 = “Illegal data in configuration of extrapolation”
5014 = “Illegal data in configuration of execution task for sensor TO”
5015 = “Illegal data in configuration of substitute value strategy for sensor TO technological alarm”
5020 = “Illegal data in configuration of driver data for analog sensor”
5021 = “Illegal data in configuration of position filter for analog sensor”
5022 = “Illegal data in configuration of conversion data for analog sensor”
5023 = “Illegal data in configuration of measurement input for analog sensor”
5030 = “Illegal data in configuration of conversion data for interval counter”
6000 = “In the configuration data, the monitoring of the positioning path isconfigured up to the reference-point switch, and the maximum path to be traveled in the process is configured as zero”
6001 = “Error in configuration data numberOfMaxBufferedCommandId”
6002 = “Error in configuration data numberOfQueueCommands”
6003 = “Error in configuration data numberOfImmediateCommands”
6004 = “Configuration of behaviourAtTheEndOfProfile not implemented”
6005 = “Illegal value for the configuration data maximum acceleration”
6006 = “Illegal value for the configuration data maximum jerk”
6007 = “Illegal value for the configuration data maximum force/pressure setpoint”
6008 = “Illegal value for the configuration data maximum force/pressure setpoint rate of rise”
externalEncoderType
5-273� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
6009 = “Illegal value for the configuration data synchronous operation tolerance on the setpoint side”
6010 = “Illegal value for the configuration data synchronous operation tolerance on the actual-value side”
6011 = “Illegal value for the configuration data enable synchronous operation tolerance on the setpoint side”
6012 = “Illegal value for the configuration data enable synchronous operationtolerance on the actual-value side”
6013 = “Illegal value for the configuration data tolerance window end-of-profile detection”
6014 = “Illegal value for the configuration data extrapolation time actual values”
6015 = “Illegal value for the configuration data tolerance window actual-valuecoupling”
6016 = “Illegal value for the configuration data touchdown tolerance position limit”
6017 = “Illegal value for the configuration data handling mode position limit”
7000 = “Illegal data in configuration of a process model”
7001 = “Illegal data in configuration of the functional component >drive model< of a process model”
7002 = “Illegal data in configuration of the functional component >delay< of a process model”
7003 = “Illegal data in configuration of the functional component >shut down drive< of a process model”
7004 = “Illegal data in configuration of the functional component >encoder< of a process model”
7005 = “Illegal data in configuration of the functional component >switch< of a process model”
8000 = “General error when reading or writing data set”
8001 = “The selected data set number is not available”
8002 = “Cannot write the active data set”
8003 = “Changing the controller structure (by writing a data set) is not possible”
Remedy
Change data record parameter.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPSIMULATION_STOPSIMULATION_ABORTENCODER_DISABLE
externalEncoderType
5-274� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
50011 Limit range of the incremental actual value exceeded (Parameter1: /1/%d)
CauseThe limit range of the incremental actual value has been exceeded.
Meaning of alarm parameters
Parameter1:
1: Range exceeded in positive direction
2: Range exceeded in negative direction
4: The modified actual position is greater than the modulo length in one positioncontrol cycle clock.
Remedy
Check and adjust the configuration data used for adjusting the actual value to themechanics.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseENCODER_DISABLE
Programmable local responsesENCODER_DISABLE
50012 Drive does not support the selected function (Parameter1: /1/%d)
CauseError in selected function.
Meaning of alarm parameters
Parameter1:
1: The travel to home position function cannot be performed.
Remedy
Check and adjust the configuration data and the drive settings.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseENCODER_DISABLE
Programmable local responsesNONEDECODE_STOPSIMULATION_STOPSIMULATION_ABORTENCODER_DISABLE
externalEncoderType
5-275� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
50013 Overshoot/undershoot of permissible range limits (logical address: /1/%d,reason: /2/%d)
CauseRange violation for additional sensor.
Meaning of alarm parameters
Logical address: Address configured on the technology object.
Reason:
1: Value greater than maximum permissible value.
2: Value smaller than minimum permissible value.
3: Positive overflow of sensor range.
4: Negative overflow of sensor range.
5: Error in accessing hardware address.
Remedy
� Check and adjust the configuration data.
� Check the sensor connection.
� Check the wiring.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseENCODER_DISABLE
Programmable local responsesNONEDECODE_STOPSIMULATION_STOPSIMULATION_ABORTENCODER_DISABLE
50014 Permissible system deviation of pressure controller exceeded
CausePermissible system deviation of pressure controller exceeded.
RemedyCheck for correct functioning of the pressure control loop.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseENCODER_DISABLE
Programmable local responsesENCODER_DISABLE
externalEncoderType
5-276� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
50015 Level overflow of IPO not detected
CauseThe system could not intercept a level overflow.
RemedyPlease contact Siemens Support with the error number indicated above.
Acknowledgment / responsePower On / STOP
Default setting for local responseENCODER_DISABLE
Programmable local responsesENCODER_DISABLE
50016 Backstop limitation active
CauseThe speed setpoint is limited by the backstop.
Remedy
� Check the mechanical configuration.
� Check the encoder connection.
� Check the configuration of the speed setpoint interface.
� Check the maximum permissible backstop values in the configuration data.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPSIMULATION_STOPSIMULATION_ABORTENCODER_DISABLE
externalEncoderType
5-277� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
50017 Manipulated variable monitoring active at Q/F output (Parameter1: /1/%d)
CauseThe manipulated variable is limited.
Remedy
� Check the configuration of the valve characteristic.
� Check the maximum permissible velocity or the maximum permissible force/pressure setpoint in the configuration data.
� Check the encoder connection.
� Check the configuration of the setpoint interface.
Parameter 1: Specification of limiting1–Monitoring active at Q output.2–Monitoring active at F output.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPSIMULATION_STOPSIMULATION_ABORTENCODER_DISABLE
50101 Reference model monitoring window exceeded
CauseThe dynamic demands on the control loop are too high.
Remedy
� Check the encoder count direction.
� Check the control loop parameter assignment.
� Change the parameter assignment for following error monitoring.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseENCODER_DISABLE
Programmable local responsesENCODER_DISABLE
externalEncoderType
5-278� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
50102 Dynamic following error monitoring window exceeded
CauseThe dynamic demands on the control loop are too high, or the control system isoverloaded.
Remedy
� Check the encoder count direction.
� Check the control loop parameter assignment.
� Change the parameter assignment for following error monitoring.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseENCODER_DISABLE
Programmable local responsesENCODER_DISABLE
50103 Warning limits of dynamic following error monitoring reached
CauseThe dynamic demands on the control loop are too high or the control system isoverloaded, the warning stage has been reached.
Remedy
� Check the encoder count direction.
� Check the control loop parameter assignment.
� Change the parameter assignment for following error monitoring.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseENCODER_DISABLE
Programmable local responsesENCODER_DISABLE
externalEncoderType
5-279� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
50106 Positioning monitoring error
CauseThe axis could not reach the positioning window in the specified time.
Remedy
� Check the control loop parameter assignment.
� Check the parameter assignment for positioning monitoring.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseENCODER_DISABLE
Programmable local responsesENCODER_DISABLE
50107 Standstill monitoring error
CauseThe axis has left the standstill window or could not reach the standstill window inthe specified time.
Remedy
� Check that the control loop is operating correctly.
� Check the parameter assignment for standstill monitoring.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseENCODER_DISABLE
Programmable local responsesENCODER_DISABLE
externalEncoderType
5-280� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
50108 Clamping monitoring error
CauseThe axis has exited the clamping tolerance window.
Remedy
� Check the mechanical end stop.
� Check that the control loop is operating correctly.
� Check the parameter assignment for clamping monitoring.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseENCODER_DISABLE
Programmable local responsesENCODER_DISABLE
50109 Starting force window monitoring error
CauseThe axis could not reach the starting force window in the specified time.
Remedy
� Check the control loop parameter assignment.
� Check the parameter assignment for monitoring.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseENCODER_DISABLE
Programmable local responsesENCODER_DISABLE
externalEncoderType
5-281� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
50110 Full-scale force monitoring error
CauseThe axis has left the full-scale force window or could not reach the window in thespecified time.
Remedy
� Check that the control loop is operating correctly.
� Check the parameter assignment for monitoring.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseENCODER_DISABLE
Programmable local responsesENCODER_DISABLE
50111 Pressure controller is operating at the limit
CauseThe manipulated variable required by the force controller cannot be implementedand is limited.
Remedy
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseENCODER_DISABLE
Programmable local responsesENCODER_DISABLE
externalEncoderType
5-282� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
6-283� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
posAxis
Possible local responses
NONENo response
DECODE_STOPAbort command processing
END_OF_MOTION_STOPStop once the active motions are complete.
MOTION_STOPStop motion with programmed values.
MOTION_EMERGENCY_STOPStop motion with maximum limit values.
MOTION_EMERGENCY_ABORTStop motion with maximum limit values and abort active commands.
FEEDBACK_EMERGENCY_STOPStop motion following emergency stop ramp and abort all active commands.
OPEN_POSITION_CONTROLStop motion with speed setpoint 0 and abort all active commands.
RELEASE_DISABLEStop motion with controller disable and abort all active commands.
6
posAxis
6-284� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
20001 Internal error (Parameter1: /1/%d, Parameter2: /2/%d, Parameter3: /3/%d,Parameter4: /4/%d)
CauseThis alarm indicates internal error states providing information about the cause andlocation of the error in association with the related error number.
Meaning of alarm parameters
Parameter1: Error source
Parameter2 to 4: Error number
RemedyA detailed description of the system error alarm is not provided. Should a systemerror of this type occur, note the alarm number, the alarm text, and the internalsystem error number specified in the alarm and contact: SIEMENS AG A&D MC, Hotline.
Acknowledgment / responsePower On / STOP
Default setting for local responseRELEASE_DISABLE
Programmable local responsesRELEASE_DISABLE
posAxis
6-285� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
20002 Insufficient memory (Parameter1: /1/%d, Parameter2: /2/%d, Parameter3:/3/%d, Parameter4: /4/%d)
CauseThe memory required by the system is no longer available. This alarm can occurboth during power up and after program calls.
Meaning of alarm parameters
Parameter1: Area in which the error occurred.
1–Command decoding
2–Interpolator
3–Controller
4–Manipulated variable output
5–Encoder system
6–Technology package
Parameters 2 to 4 are area-specific. They are not fully utilized by all areas.
Command decoding area
Parameter2 and Parameter4 refer to the command in which the error occurred.
Parameter2: Command return value
Parameter4: Command type
Remedy
� Reduce the size of the ST code.
� Reduce the number of technology objects.
� Reduce the number of interpolation points for cams, if present.
Acknowledgment / responsePower On / STOP
Default setting for local responseFEEDBACK_EMERGENCY_STOP
Programmable local responsesFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
posAxis
6-286� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
20003 No object configuration (Parameter1: /1/%d, Parameter2: /2/%d, Parameter3:/3/%d, Parameter4: /4/%d)
CauseError in system configuration. The configuration data for a software tool could notbe found.
Meaning of alarm parameters
Parameter1: Area in which the error occurred.
1–Command decoding
2–Interpolator
3–Controller
4–Manipulated variable output
5–Encoder system
Parameters 2 to 4 are area-specific. They are not fully utilized by all areas.
Command decoding area
Parameter2 and Parameter4 refer to the command in which the error occurred.
Parameter2: Command return value
Parameter4: Command type
RemedyCheck the accuracy of the configuration data in your project. When commands arecalled on technology objects, the technology objects must be configured.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
posAxis
6-287� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
20004 At the logical address: /1/%d (bit number, if required: /2/%d) a driver (type:/3/%d) could be requested (error number: /4/%d)
CauseThe driver of a physical device or the device itself is not available.
Meaning of alarm parameters
Logical address:
This is the address configured on the technology object.
Bit number:
For bit driver only; bit number
Type:
1–Actuator driver
2–Encoder driver
3–BitRead driver
4–BitWrite driver
5–ByteRead driver
6–ByteWrite driver
7–WordRead driver
8–WordWrite driver
9–DWordRead driver
10–DWordWrite driver
Error number: Specification of error
1000 = “General driver configuration error”
Remedy
� Connect a suitable device.
� Check the device (function, connections, terminals).
� Check the topological configuration in HWConfig.
� Compare configuration of HWConfig and technology object.
� Contact the hotline.
Acknowledgment / responsePower On / START TechnologicalFaultTask
Default setting for local responseRELEASE_DISABLE
Programmable local responsesRELEASE_DISABLE
posAxis
6-288� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
20005 Device type: /3/%d, log. address: /1/%d faulty. (Bit: /2/%d, reason: 0x/4/%Xh)
CauseThe driver of a physical device or the device itself has failed or is faulty. When thisalarm occurs, the error cause must be evaluated in the external device (drive orencoder).
Meaning of alarm parameters
Type:
1–Actuator driver
2–Encoder driver
3–BitRead driver
4–BitWrite driver
5–ByteRead driver
6–ByteWrite driver
7–WordRead driver
8–WordWrite driver
9–DWordRead driver
10–DWordWrite driver
Logical address:This is the address configured on the technology object.
Bit number:For bit driver type = 3 or 4 only; bit number
Reason:0–Not defined (e.g., for binary I/O)
� Type = 1
0x0001h: Fault message from drive (note: On PROFIBUS drives, whichsupport acyclic communication in accordance with PROFIdrive V3,the error number/numbers of the drives is/are displayed in thediagnostic buffer, e.g., on Masterdrives MC).
0x0002h: DP: Drive signal “control requested” failed
0x0004h: DP: Drive switched off itself
0x0008h: Slot for drive data is not available in the project
0x0010h: Actuator driver does not have a connection to the drive data
0x0020h: Actuator driver was not initialized during power up
0x0080h: DP: Difference between configuration data and drive parameters
0x4000h: DP: Drive on bus failed (station failure)
0x8000h: Sign of life of drive faulty or failed
posAxis
6-289� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
� Type = 2
0x0000h: The number of permissible changes in the actual value of the maximum velocity of the absolute-value encoder has beenexceeded
0x0001h: Fault message from encoder (note: The error number/numbers is/are displayed in the diagnostic buffer)
0x0002h: General hardware error of encoder
0x0004h: Encoder contaminated
0x0008h: Slot for encoder data is not available in the project
0x0010h: Encoder driver does not have a connection to the encoder data
0x0020h: Encoder driver was not initialized during power up
0x0040h: Error when reading the absolute value of the encoder
0x0080h: DP: Difference between the configuration data and the encoder parameters
0x0100h: Zero mark monitoring of encoder
0x4000h: DP: Encoder on bus failed (station failure)
0x8000h: DP: Sign of life of encoder has malfunctioned or failed. (Note: For an encoder whose data are transferred in a drive message together with actuator data, the actuator sign of life applies for the encoder, e.g., a standard message 3 in accordance with PROFIdrive).
� Type = 3 to 10
0x0000h: Additional information, not assigned
Note:Codings for the reason of the failure can also occur in combination. Theindividual codings are then added to form a coding sum, which is displayed(e.g., 0x0005 = 0x0001 + 0x0004). A reason for failure marked as DP can only be present on PROFIBUS devices.
RemedyCheck the device with respect to function and connections (reason 0x0001,0x0002, 0x0004, 0x4000, 0x8000).
� Check the topological configuration in HW Config (with reason 0x0008).
� For PROFIBUS drives or encoders, compare the configuration of HWConfig, thetechnology object, and the drive parameter assignment.For:
Reason 0x0040:
– Compare the encoder type in the drive or encoder parameter P979 with theconfiguration data of the technology object.
posAxis
6-290� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
Reason 0x0080:
– Compare the message frame type in the drive or encoder parameter P922with HW Config and the configuration data of the technology object.
– Compare the encoder type, resolution, multiplier and, with absoluteencoders, the data length in the drive or encoder parameter P979 with theconfiguration data of the technology object.
– Compare the parameterization named in reason 0x8000 (reason 0x8000 canoccur as secondary fault).
Reason 0x8000:
– Compare the cycle clock parameters of HW Config (PROFIBUS line, SlaveOM for drive or encoder) and the execution system. Tmapc and servo mustbe parameterized with the same cycle clock period!
� System fault, contact the hotline (reason 0x0008, 0x0010, 0x0020).
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseRELEASE_DISABLE
Programmable local responsesRELEASE_DISABLE
posAxis
6-291� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
20006 Error in configuration (category: /1/%d, error number: /2/%d)
CauseThis alarm indicates error states caused by a faulty or inconsistent configuration.The technology objects perform a plausibility check on the configuration. Errors areidentified by the error codes below.
Meaning of alarm parameters
Category: Area in which the error occurred.
1–Command decoding
2–Interpolator
3–Controller
4–Manipulated variable output
5–Encoder system
6–Technology object
Error number: Specification of error
500 = “TO in illegal status for configuration”
501 = “More configuration data expected than received”
502 = “Invalid data in configuration”
503 = “Version conflict in configuration”
1000 = “General configuration error”
2000 = “Error in actuator system configuration”
2001 = “Outside of limits of manipulated variable”
2003 = “Error in load gear ratios”
2004 = “Error in maximum velocity”
2005 = “Maximum velocity greater than maximum attainable velocity”
2006 = “Drive not suitable for torque-controlled or torque-limited operation”
2007 = “Linear stepper motor not implemented”
2008 = “Right-aligned format for direct output not implemented”
2009 = “Illegal value in resolution for direct output”
2010 = “Missing configuration data for actuator system”
2011 = “Missing configuration data for additional actuator system”
2012 = “The backstop range (min to max) does not contain a zero point”
2014 = “Drive or message frame not suitable for torque superimposition”
2015 = “Gear ratios less than or equal to 0”
2016 = “Resolution for stepper motor is 0”
2017 = “Illegal value for the configuration data maxSpeed”
2018 = “Illegal value for the configuration data maxVelocity”
2019 = “Limits of a configuration data exceeded”
2020 = “Limits for the max. acceleration exceeded”
2021 = “Illegal values for dead-zone compensation”
2022 = “Illegal values for sliding-friction compensation”
posAxis
6-292� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
2023 = “Illegal values for backstop range”
2024 = “Error in sliding-friction compensation parameter”
3000 = “Error in encoder system”
3001 = “Error in encoder system”
3002 = “Invalid axis type selected”
3003 = “Leadscrew pitch is 0”
3004 = “Modulo axis selected with modulo value less than or equal to 0”
3005 = “Illegal specification(s) in the encoder data (incremental / absolute, etc.)”
3006 = “Illegal number of encoders selected”
3007 = “Illegal incremental encoder number”
3008 = “Illegal data combination for homing with incremental encoder”
3009 = “Illegal encoder number”
3010 = “Illegal data on SSI encoder”
3011 = “Illegal encoder number”
3012 = “Illegal encoder number”
3013 = “Illegal measuring gear data, DRIVE assembly type (e.g., factor = 0)”
3014 = “Illegal encoder number”
3015 = “Illegal measuring gear data, LOAD assembly type (e.g., factor = 0)”
3016 = “Illegal data set number (e.g., factor = 0)”
3017 = “Encoder data sequence and number of encoders do not match”
3018 = “Error in encoder system”
3019 = “Illegal encoder number”
3020 = “Illegal encoder system / actuator system simulation selected”
3021 = “Illegal encoder number or incorrect number of data sets”
3022 = “Illegal encoder number or incorrect number of data sets”
3023 = “Illegal data for ratio of external attachment (e.g., factor = 0)”
3024 = “Path/rotation of external attachment = 0”
3025 = “Illegal value for monitoring of actual velocity”
3026 = “Illegal encoder number in SSI encoder configuration”
3027 = “Illegal message format in SSI encoder configuration”
3028 = “Illegal baud rate in SSI encoder configuration”
3029 = “Illegal SSI state in SSI encoder configuration”
3030 = “Illegal encoder number in data set”
3031 = “Encoder number in data set not configured”
3032 = “Illegal numerator factor in data set”
3033 = “Illegal denominator factor in data set”
3034 = “Illegal data set number”
3035 = “Data set number not configured”
3036 = “Encoder not configured”
3037 = “Homing of ENDAT encoder with zero mark not possible”
3038 = “Homing of CAM negative edge onboard not possible”
3039 = “On-the-fly homing of ENDAT encoder with zero mark not possible”
posAxis
6-293� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
3040 = “On-the-fly homing of CAM negative edge onboard not possible”
3041 = “Factors for adjusting encoder data to the mechanics are outside the permissible range of values”
3042 = “Illegal data combination for homing with external encoder”
3043 = “The incremental position of the encoder is outside the permissible range of values”
3044 = “The incremental position of the encoder is outside the permissible range of values”
3045 = “Illegal value for resolution of linear measuring system”
3046 = “Illegal value for filter of actual-velocity encoder”
3047 = “Illegal value for smoothing of actual-value encoder”
3048 = “Illegal value for smoothing of actual-value encoder with actual-valuecoupling”
3049 = “Illegal DSC encoder selection”
3050 = “Configuration of encoder system not completed correctly”
3051 = “Error in configuration of the sensor data or the stepper motor”
3052 = “Actual-value type (position, interval, velocity) not implemented”
3053 = “Only homing with CAM possible for stepper motor”
3054 = “Only on-the-fly homing with CAM possible for stepper motor”
3055 = “Stepper motor only possible with a real axis”
3056 = “Only one encoder permissible with stepper motor”
3057 = “DSC encoder is not a DP encoder”
3058 = “Illegal message frame of the DSC encoder”
3059 = “Modulo value too small”
3060 = “Configuration differential measurement position faulty”
3061 = “Illegal data in range configuration of the differential measurement position”
4000 = “Error in controller”
4001 = “Negative acceleration specified”
4002 = “Unknown ’FipoType’ requested”
4003 = “Error in runtime system, ratio of controller cycle clock to interpolator cycle clock incorrect”
4004 = “Requested filter arrangement not possible”
4005 = “Reserve for later use”
4006 = “Maximum limit is lower than minimum”
4007 = “Reserve for later use”
4008 = “Error in configuration data for controller”
4009 = “Reserve for later use”
4010 = “Reserve for later use”
4011 = “Reserve for later use”
4012 = “Reserve for later use”
4013 = “Requested controller type is not available”
4014 = “Error in controller factors”
4015 = “Feedforward control activated, kpc < 0 or kpc > 150”
posAxis
6-294� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
4016 = “Reserve for later use”
4017 = “Reserve for later use”
4018 = “Reserve for later use”
4019 = “Reserve for later use”
4020 = “Reserve for later use”
4021 = “Reserve for later use”
4022 = “Reserve for later use”
4023 = “Feedforward control activated, kpc <= 0”
4024 = “Model reference monitoring: Error in value of tolerance window”
4025 = “Error in limit value for standstill signal”
4026 = “Error in parameter for positioning monitoring”
4027 = “Reference model and dynamic following error monitoring activated, not possible at the same time”
4028 = “Sampling time parameter calculated incorrectly”
4029 = “Too many data sets requested”
4030 = “Error in runtime system, ratio of controller cycle clock to interpolator cycle clock incorrect”
4031 = “Error in time constant for emergency stop ramp generator (positionTimeConstant)”
4032 = “Feedforward control active, but fine interpolator type is DIRECT”
4033 = “Default data set outside limits”
4034 = “Maximum number of data sets not possible”
4035 = “Unknown data set alternating mode”
4036 = “Following error monitoring not activated/deactivated in all data sets”
4037 = “Model reference monitoring not activated/deactivated in all data sets”
4038 = “Different controller type in data sets”
4039 = “Feedforward control activated/deactivated in data sets”
4040 = “Time constant is 0”
4041 = “Error in dynamic adaptation parameter”
4042 = “System variable initialization could not be read”
4043 = “Driver simulation not implemented”
4044 = “Connection for stepper motors not implemented”
4045 = “Maximum velocity cannot be reached, maximum drive speed or a normalization factor incorrect”
4046 = “DSC requires motor encoder data to be specified”
4047 = “Drive or message frame type not suitable for DSC”
4048 = “Error in clamping monitoring parameter” ’No identifier’ is not permitted for the fixed end stop identifier.
4049 = “Without sensor, monitoring of the actual velocity by ’DynamicControl’ not possible”
4050 = “Inconsistent PROFIBUS parameterization; the sum of Ti and To is greater than one DP clock cycle”
4051 = “Error in manipulated variable limit parameter of force/pressure controller”
posAxis
6-295� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
4052 = “Error in starting force/pressure monitoring parameter”
4053 = “Error in full-scale force/pressure monitoring parameter”
4054 = “Starting force/pressure monitoring tolerance less than tolerance of full-scale pressure monitoring”
4055 = “Error in force/pressure system deviation monitoring parameter”
4056 = “Different activation/deactivation of the control difference monitoring of the force/pressure controller not permitted in data sets”
4057 = “Different manipulated variable inversion of the force/pressure controller not permitted in data sets”
4058 = “Different force/pressure sensor types not permitted in data sets”
4059 = “Different activation/deactivation of the anti windup not permitted in data sets”
4060 = “Kd factor of the PID_ACTUAL controller is greater than 1”
4061 = “Time constant of the process model T1 <= T2”
4062 = “Illegal actuator type selection”
4063 = “Error in sliding friction compensation parameter”
4064 = “Error in offset application parameter”
4065 = “Feedforward control for force/pressure control not implemented”
4066 = “Error in standstill monitoring parameter”
4067 = “Following error monitoring: minVelocity must not be greater than or equal to maxVelocity”
4068 = “velocityTimeConstant when using a dead-time element for feedforward balancing too great”
4069 = “The system-related dead times are less than 0 after the calculation of additionalTime”
4070 = “Controller types not equal to DIRECT require the configuration of an encoder”
4071 = “Illegal values for delayTimeToActivate of the standstill signal”
4072 = “The IO device for the positive HW limit switch is not available”
4073 = “The IO device for the negative HW limit switch is not available”
4074 = “Limits of a controller parameter exceeded”
4075 = “Limit for emergency-stop-ramp brake delay exceeded”
4076 = “Limit for a substitute time constant exceeded”
4077 = “Limit for velocityTimeConstant exceeded”
4078 = “Error in value for configuration of QFDynamicData”
4079 = “Error in value for model reference monitoring”
4080 = “Error in following error monitoring parameter”
4081 = “Error in clamping monitoring parameter”
4082 = “Error in value for configuration of DynamicData”
4083 = “Error in value for configuration of PV controller”
4084 = “Incomplete configuration data for controller”
posAxis
6-296� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
4085 = “Error in value for configuration of SystemDeadTimeData”
4086 = “Pressure control only possible with closed speed controller”
4087 = “DSC and compensation of valve characteristic not possible”
4088 = “DSC not possible on hydraulic axes”
4089 = “Time constant of dynamic compensation T1 <= T2”
4090 = “Incorrect value for correction of system dead time”
5000 = “Encoder data sequence and number of encoders do not match”
5001 = “Illegal number of additional sensors selected”
5002 = “Illegal additional sensor type selected”
5003 = “Illegal data in configuration of driver data for additional sensor”
5004 = “Illegal data in configuration of conversion data for additional sensor”
5006 = “Illegal data in configuration of range for additional sensor”
5007 = “Illegal data in configuration of filter time for additional sensor”
5008 = “Configuration of additional encoder not completed correctly”
5009 = “Illegal number for additional sensor in data set”
5010 = “Illegal data in configuration of differential pressure measurement”
5011 = “Error sensor A differential pressure measurement”
5012 = “Error sensor B differential pressure measurement”
5013 = “Illegal data in configuration of extrapolation”
5014 = “Illegal data in configuration of execution task for sensor TO”
5015 = “Illegal data in configuration of substitute value strategy for sensor TO technological alarm”
5020 = “Illegal data in configuration of driver data for analog sensor”
5021 = “Illegal data in configuration of position filter for analog sensor”
5022 = “Illegal data in configuration of conversion data for analog sensor”
5023 = “Illegal data in configuration of measurement input for analog sensor”
5030 = “Illegal data in configuration of conversion data for interval counter”
6000 = “In the configuration data, the monitoring of the positioning path isconfigured up to the reference-point switch, and the maximum path to be traveled in the process is configured as zero”
6001 = “Error in configuration data numberOfMaxBufferedCommandId”
6002 = “Error in configuration data numberOfQueueCommands”
6003 = “Error in configuration data numberOfImmediateCommands”
6004 = “Configuration of behaviourAtTheEndOfProfile not implemented”
6005 = “Illegal value for the configuration data maximum acceleration”
posAxis
6-297� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
6006 = “Illegal value for the configuration data maximum jerk”
6007 = “Illegal value for the configuration data maximum force/pressure setpoint”
6008 = “Illegal value for the configuration data maximum force/pressure setpointrate of rise”
6009 = “Illegal value for the configuration data synchronous operation tolerance on the setpoint side”
6010 = “Illegal value for the configuration data synchronous operation tolerance on the actual-value side”
6011 = “Illegal value for the configuration data enable synchronous operationtolerance on the setpoint side”
6012 = “Illegal value for the configuration data enable synchronous operationtolerance on the actual-value side”
6013 = “Illegal value for the configuration data tolerance window end-of-profile detection”
6014 = “Illegal value for the configuration data extrapolation time actual values”
6015 = “Illegal value for the configuration data tolerance window actual-valuecoupling”
6016 = “Illegal value for the configuration data touchdown tolerance position limit”
6017 = “Illegal value for the configuration data handling mode position limit”
7000 = “Illegal data in configuration of a process model”
7001 = “Illegal data in configuration of the functional component >drive model< of a process model”
7002 = “Illegal data in configuration of the functional component >delay< of a process model”
7003 = “Illegal data in configuration of the functional component >shut down drive< of a process model”
7004 = “Illegal data in configuration of the functional component >encoder< of a process model”
7005 = “Illegal data in configuration of the functional component >switch< of a process model”
RemedyChange the configuration data.
Acknowledgment / responsePower On / START TechnologicalFaultTask
Default setting for local responseRELEASE_DISABLE
Programmable local responsesFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
posAxis
6-298� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
20007 Interconnection error (category: /1/%d, context: /2/%d, context parameter1:/3/%d, context parameter2: /4/%d)
CauseThis alarm indicates errors in the interconnection of technology objects. When theinterconnection is established, the technology object verifies it on the basis of theinterface properties. Errors are classified by category.
Meaning of alarm parameters
Category:
1 – TO compatibility errorAn interconnection is to be established with a technology object that has beenconfigured with another reference system (e.g., output cam with rotaryreference system and linear axis).
2 – Exclusive interfaceMultiple interconnections are to be established for an interface intended forexclusive interconnection.
3 – Interconnection requirementThe technology object is waiting for an interconnection required for thesequence.
4 – Interface initialization errorErrors result from extended initialization sequences at interfaces andparameter exchange between interconnected interfaces.
5 – Interface not available on technology objectAn interface specified in the interconnection is not available on the technologyobject.
6 – CircularityThe interconnection on the technology object leads to circular communicationwithin the technology object (e.g., circular master/slave interconnection ofgearing axes, whereby a gearing axis used as a master is in turn the slave ofanother master, which is assigned the master setpoints generated on thisgearing axis directly or via additional interconnections).
7 – Execution level compatibility errorAn interconnection is to be established with a technology object that isexecuted in another interpolator level (e.g., output cam with IPO and axis withIPO_2).
8 – Distribution initializationWhen interconnecting technology objects that are distributed among differentdevices, an error occurred during initialization of the communication interface.
9 – Illegal TO statusThe technology object cannot be interconnected in the current state.
Context:
The context provides additional information about the error category for the TOinterconnection. Additional parameters can be provided for the error descriptionon a context-specific basis. Context and context parameter are output as aninteger value.
posAxis
6-299� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
Remedy
1 – Technology object compatibility error: Correct the configuration of the reference system of the technology objects tobe interconnected.
2 – Exclusive interface: Correct the configuration of the interconnected technology object.
3 – Interconnection request: Add the missing interconnection to your technology object.
4 – Error during interface initialization: Contact the hotline.
5 – Interface not available on technology object: Contact the hotline.
6 – Circularity:Remove unnecessary interconnections.
7 – Execution level compatibility error: Correct the configuration of the interpolator task level of the technology objectsto be interconnected.
8 – Distribution initialization:Check the hardware configuration. Ensure that the distributed interactingdevices are linked in the bus configuration. In addition, the address areas thatare used by the devices for communication must be set up. The address areasare automatically set up when the project is compiled; only afterwards is thevalid hardware configuration available for downloading.
9 – Illegal TO status:Correct the configuration of the technology object, correct execution errors.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseRELEASE_DISABLE
Programmable local responsesFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
posAxis
6-300� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
20008 Cannot assign USER_DEFAULT to system variables
CauseIt is not appropriate to assign USER_DEFAULT to a UserDefault system variable,because the variable references itself in this case.This prevents generation of a useful value during reading out. When this erroroccurs, the new Enum value is not assigned. The variable retains the old value.
RemedyUSER_DEFAULT is designed for use in technology commands.Avoid assigning it to system variables.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONE
20009 The permissible deviation between encoders (/1/%d) and (/2/%d) has beenexceeded
CauseThe permissible deviation between two encoders (slip monitoring) has beenexceeded.
Remedy1. Check the mechanical configuration.2. Check the dimensioning of the dynamic limit values (acceleration, jerk).
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
posAxis
6-301� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
20010 A restart is necessary to activate the configuration data
CauseThe configuration cannot be set to active, since data have been modified in such away that does not permit it. The technology object must be restarted to activate thedata.
Remedy
� Execute the technology object reset command, and set the activateRestartparameter to ACTIVATE_RESTART.
� Set the restartActivation system variable to ACTIVATE_RESTART.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
posAxis
6-302� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
20011 Error when activating the configuration (category: /1/%d, error number:/2/%d)
CauseThis note indicates error conditions when activating the configuration. The errorconditions can be traced back to an incorrect or inconsistent configuration. Thetechnology objects perform a plausibility check on the configuration. Errors areidentified by the error codes below.If this information appears, the configuration will not be activated.
Meaning of alarm parameters
Category: Area in which the error occurred.
1–Command decoding
2–Interpolator
3–Controller
4–Manipulated variable output
5–Encoder system
6–Technology object
Error number: Specification of error
1000 = “General configuration error”
2000 = “Error in actuator system configuration”
2001 = “Outside of limits of manipulated variable”
2003 = “Error in load gear ratios”
2004 = “Error in maximum velocity”
2005 = “Maximum velocity greater than maximum attainable velocity”
2006 = “Drive not suitable for torque-controlled or torque-limited operation”
2007 = “Linear stepper motor not implemented”
2008 = “Right-aligned format for direct output not implemented”
2009 = “Illegal value in resolution for direct output”
2010 = “Missing configuration data for actuator system”
2011 = “Missing configuration data for additional actuator system”
2012 = “The backstop range (min to max) does not contain a zero point”
2014 = “Drive or message frame not suitable for torque superimposition”
2015 = “Gear ratios less than or equal to 0”
2016 = “Resolution for stepper motor is 0”
2017 = “Illegal value for the configuration data maxSpeed”
2018 = “Illegal value for the configuration data maxVelocity”
2019 = “Limits of a configuration data exceeded”
2020 = “Limits for the max. acceleration exceeded”
2021 = “Illegal values for dead-zone compensation”
2022 = “Illegal values for sliding-friction compensation”
2023 = “Illegal values for backstop range”
2024 = “Error in sliding-friction compensation parameter”
posAxis
6-303� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
3000 = “Error in encoder system”
3001 = “Error in encoder system”
3002 = “Invalid axis type selected”
3003 = “Leadscrew pitch is 0”
3004 = “Modulo axis selected with modulo value less than or equal to 0”
3005 = “Illegal specification(s) in the encoder data (incremental / absolute, etc.)”
3006 = “Illegal number of encoders selected”
3007 = “Illegal incremental encoder number”
3008 = “Illegal data combination for homing with incremental encoder”
3009 = “Illegal encoder number”
3010 = “Illegal data on SSI encoder”
3011 = “Illegal encoder number”
3012 = “Illegal encoder number”
3013 = “Illegal measuring gear data, DRIVE assembly type (e.g., factor = 0)”
3014 = “Illegal encoder number”
3015 = “Illegal measuring gear data, LOAD assembly type (e.g., factor = 0)”
3016 = “Illegal data set number (e.g., factor = 0)”
3017 = “Encoder data sequence and number of encoders do not match”
3018 = “Error in encoder system”
3019 = “Illegal encoder number”
3020 = “Illegal encoder system / actuator system simulation selected”
3021 = “Illegal encoder number or incorrect number of data sets“
3022 = “Illegal encoder number or incorrect number of data sets”
3023 = “Illegal data for ratio of external attachment (e.g., factor = 0)”
3024 = “Path/rotation of external attachment = 0”
3025 = “Illegal value for monitoring of actual velocity”
3026 = “Illegal encoder number in SSI encoder configuration”
3027 = “Illegal message format in SSI encoder configuration”
3028 = “Illegal baud rate in SSI encoder configuration”
3029 = “Illegal SSI state in SSI encoder configuration”
3030 = “Illegal encoder number in data set”
3031 = “Encoder number in data set not configured”
3032 = “Illegal numerator factor in data set”
3033 = “Illegal denominator factor in data set”
3034 = “Illegal data set number”
3035 = “Data set number not configured”
3036 = “Encoder not configured”
3037 = “Homing of ENDAT encoder with zero mark not possible”
3038 = “Homing of CAM negative edge onboard not possible”
3039 = “On-the-fly homing of ENDAT encoder with zero mark not possible”
3040 = “On-the-fly homing of CAM negative edge onboard not possible”
posAxis
6-304� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
3041 = “Factors for adjusting encoder data to the mechanics are outside the permissible range of values”
3042 = “Illegal data combination for homing with external encoder”
3043 = “The incremental position of the encoder is outside the permissible range of values”
3044 = “The incremental position of the encoder is outside the permissible range of values”
3045 = “Illegal value for resolution of linear measuring system”
3046 = “Illegal value for filter of actual-velocity encoder”
3047 = “Illegal value for smoothing of actual-value encoder”
3048 = “Illegal value for smoothing of actual-value encoder with actual-valuecoupling”
3049 = “Illegal DSC encoder selection”
3050 = “Configuration of encoder system not completed correctly”
3051 = “Error in configuration of the sensor data or the stepper motor”
3052 = “Actual-value type (position, interval, velocity) not implemented”
3053 = “Only homing with CAM possible for stepper motor”
3054 = “Only on-the-fly homing with CAM possible for stepper motor”
3055 = “Stepper motor only possible with a real axis”
3056 = “Only one encoder permissible with stepper motor”
3057 = “DSC encoder is not a DP encoder”
3058 = “Illegal message frame of the DSC encoder”
3059 = “Modulo value too small”
3060 = “Configuration differential measurement position faulty”
3061 = “Illegal data in range configuration of the differential measurement position”
4000 = “Error in controller”
4001 = “Negative acceleration specified”
4002 = “Unknown ’FipoType’ requested”
4003 = “Error in runtime system, ratio of controller cycle clock to interpolator cycle clock incorrect”
4004 = “Requested filter arrangement not possible”
4005 = “Reserve for later use”
4006 = “Maximum limit is lower than minimum”
4007 = “Reserve for later use”
4008 = “Error in configuration data for controller”
4009 = “Reserve for later use”
4010 = “Reserve for later use”
4011 = “Reserve for later use”
4012 = “Reserve for later use”
4013 = “Requested controller type is not available”
4014 = “Error in controller factors”
4015 = “Feedforward control activated, kpc < 0 or kpc > 150”
4016 = “Reserve for later use”
4017 = “Reserve for later use”
posAxis
6-305� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
4018 = “Reserve for later use”
4019 = “Reserve for later use”
4020 = “Reserve for later use”
4021 = “Reserve for later use”
4022 = “Reserve for later use”
4023 = “Feedforward control activated, kpc <= 0”
4024 = “Model reference monitoring: Error in value of tolerance window”
4025 = “Error in limit value for standstill signal”
4026 = “Error in parameter for positioning monitoring”
4027 = “Reference model and dynamic following error monitoring activated, not possible at the same time”
4028 = “Sampling time parameter calculated incorrectly”
4029 = “Too many data sets requested”
4030 = “Error in runtime system, ratio of controller cycle clock to interpolator cycle clock incorrect”
4031 = “Error in time constant for emergency stop ramp generator (positionTimeConstant)”
4032 = “Feedforward control active, but fine interpolator type is DIRECT”
4033 = “Default data set outside limits”
4034 = “Maximum number of data sets not possible”
4035 = “Unknown data set alternating mode”
4036 = “Following error monitoring not activated/deactivated in all data sets”
4037 = “Model reference monitoring not activated/deactivated in all data sets”
4038 = “Different controller type in data sets”
4039 = “Feedforward control activated/deactivated in data sets”
4040 = “Time constant is 0”
4041 = “Error in dynamic adaptation parameter”
4042 = “System variable initialization could not be read”
4043 = “Driver simulation not implemented”
4044 = “Connection for stepper motors not implemented”
4045 = “Maximum velocity cannot be reached, maximum drive speed or anormalization factor incorrect”
4046 = “DSC requires motor encoder data to be specified”
4047 = “Drive or message frame type not suitable for DSC”
4048 = “Error in clamping monitoring parameter” ’No identifier’ is not permitted for the fixed end stop identifier.
4049 = “Without sensor, monitoring of the actual velocity by ’DynamicControl’ not possible”
4050 = “Inconsistent PROFIBUS parameterization; the sum of Ti and To is greater than one DP clock cycle”
4051 = “Error in manipulated variable limit parameter of force/pressure controller”
4052 = “Error in starting force/pressure monitoring parameter”
4053 = “Error in full-scale force/pressure monitoring parameter”
posAxis
6-306� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
4054 = “Starting force/pressure monitoring tolerance less than tolerance of full-scale pressure monitoring”
4055 = “Error in force/pressure system deviation monitoring parameter”
4056 = “Different activation/deactivation of the control difference monitoring of theforce/pressure controller not permitted in data sets”
4057 = “Different manipulated variable inversion of the force/pressure controller not permitted in data sets”
4058 = “Different force/pressure sensor types not permitted in data sets”
4059 = “Different activation/deactivation of the anti windup not permitted in datasets”
4060 = “Kd factor of the PID_ACTUAL controller is greater than 1”
4061 = “Time constant of the process model T1 <= T2”
4062 = “Illegal actuator type selection”
4063 = “Error in sliding friction compensation parameter”
4064 = “Error in offset application parameter”
4065 = “Feedforward control for force/pressure control not implemented”
4066 = “Error in standstill monitoring parameter”
4067 = “Following error monitoring: minVelocity must not be greater than or equal to maxVelocity”
4068 = “velocityTimeConstant when using a dead-time element for feedforward balancing too great”
4069 = “The system-related dead times are less than 0 after the calculation of additionalTime”
4070 = “Controller types not equal to DIRECT require the configuration of an encoder”
4071 = “Illegal values for delayTimeToActivate of the standstill signal”
4072 = “The IO device for the positive HW limit switch is not available”
4073 = “The IO device for the negative HW limit switch is not available”
4074 = “Limits of a controller parameter exceeded”
4075 = “Limit for emergency-stop-ramp brake delay exceeded”
4076 = “Limit for a substitute time constant exceeded”
4077 = “Limit for velocityTimeConstant exceeded”
4078 = “Error in value for configuration of QFDynamicData”
4079 = “Error in value for model reference monitoring”
4080 = “Error in following error monitoring parameter”
4081 = “Error in clamping monitoring parameter”
4082 = “Error in value for configuration of DynamicData”
4083 = “Error in value for configuration of PV controller”
4084 = “Incomplete configuration data for controller”
4085 = “Error in value for configuration of SystemDeadTimeData”
4086 = “Pressure control only possible with closed speed controller”
posAxis
6-307� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
4087 = “DSC and compensation of valve characteristic not possible”
4088 = “DSC not possible on hydraulic axes”
4089 = “Time constant of dynamic compensation T1 <= T2”
4090 = “Incorrect value for correction of system dead time”
5000 = “Encoder data sequence and number of encoders do not match”
5001 = “Illegal number of additional sensors selected”
5002 = “Illegal additional sensor type selected”
5003 = “Illegal data in configuration of driver data for additional sensor”
5004 = “Illegal data in configuration of conversion data for additional sensor”
5006 = “Illegal data in configuration of range for additional sensor”
5007 = “Illegal data in configuration of filter time for additional sensor”
5008 = “Configuration of additional sensor not completed correctly”
5009 = “Illegal number for additional sensor in data set”
5010 = “Illegal data in configuration of differential pressure measurement”
5011 = “Error sensor A differential pressure measurement”
5012 = “Error sensor B differential pressure measurement”
5013 = “Illegal data in configuration of extrapolation”
5014 = “Illegal data in configuration of execution task for sensor TO”
5015 = “Illegal data in configuration of substitute value strategy for sensor TO technological alarm”
5020 = “Illegal data in configuration of driver data for analog sensor”
5021 = “Illegal data in configuration of position filter for analog sensor”
5022 = “Illegal data in configuration of conversion data for analog sensor”
5023 = “Illegal data in configuration of measurement input for analog sensor”
5030 = “Illegal data in configuration of conversion data for interval counter”
6000 = “In the configuration data, the monitoring of the positioning path isconfigured up to the reference-point switch, and the maximum path to be traveled in the process is configured as zero”
6001 = “Error in configuration data numberOfMaxBufferedCommandId”
6002 = “Error in configuration data numberOfQueueCommands”
6003 = “Error in configuration data numberOfImmediateCommands”
6004 = “Configuration of behaviourAtTheEndOfProfile not implemented”
6005 = “Illegal value for the configuration data maximum acceleration”
6006 = “Illegal value for the configuration data maximum jerk”
6007 = “Illegal value for the configuration data maximum force/pressure setpoint”
posAxis
6-308� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
6008 = “Illegal value for the configuration data maximum force/pressure setpoint rate of rise”
6009 = “Illegal value for the configuration data synchronous operation tolerance on the setpoint side”
6010 = “Illegal value for the configuration data synchronous operation tolerance on the actual-value side”
6011 = “Illegal value for the configuration data enable synchronous operationtolerance on the setpoint side”
6012 = “Illegal value for the configuration data enable synchronous operationtolerance on the actual-value side”
6013 = “Illegal value for the configuration data tolerance window end-of-profile detection”
6014 = “Illegal value for the configuration data extrapolation time actual values”
6015 = “Illegal value for the configuration data tolerance window actual-valuecoupling”
6016 = “Illegal value for the configuration data touchdown tolerance position limit”
6017 = “Illegal value for the configuration data handling mode position limit”
7000 = “Illegal data in configuration of a process model”
7001 = “Illegal data in configuration of the functional component >drive model< of a process model”
7002 = “Illegal data in configuration of the functional component >delay< of a process model”
7003 = “Illegal data in configuration of the functional component >shut down drive< of a process model”
7004 = “Illegal data in configuration of the functional component >encoder< of a process model”
7005 = “Illegal data in configuration of the functional component >switch< of a process model”
RemedyChange the configuration data.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
posAxis
6-309� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
20012 Restart not executed (reason: /1/%d)
CauseTechnology object could not be restarted.
Meaning of alarm parameters
Reason:
1 – The technology object configuration does not allow a restart with the restartsystem variable. You can initiate the restart using the reset command.
2 – The technology object is not ready to be restarted.
3 – A configured condition for restarting the technology object is not met (e.g.,technology object must be disabled).
4 – Restart has not been executed or executed with the last programmedconfiguration of the technology object.
Remedy
� Work around the cause stated in the Reason parameter, or reload the project.
� Use the device diagnostics to establish whether technological alarms werereported and, if necessary, remedy the cause of the alarm.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
posAxis
6-310� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
20014 At the logical address: /1/%d (optional log. address: /2/%d and bit no.: /3/%dof the enable output), a driver (type: /4/%d) could not be requested
CauseThe driver of a physical device is not available or is being used by another TO.
Meaning of alarm parameters
Logical address:
This is the address of the actuator driver configured on the technology object.
Logical address and bit number:
This specifies the address and bit number of the output enable bit
Type:
1–Actuator driver
2–Encoder driver
3–BitRead driver
4–BitWrite driver
5–ByteRead driver
6–ByteWrite driver
7–WordRead driver
8–WordWrite driver
9–DWordRead driver
10–DWordWrite driver
Remedy
� Check that the logical device was available at the time of the request or whetherit was being used by another technology object.
� Connect a suitable device.
� Check the device (function, connections, terminals).
� Check the topological configuration in HWConfig.
� Compare configuration of HWConfig and technology object.
� Contact the hotline.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseRELEASE_DISABLE
Programmable local responsesRELEASE_DISABLE
posAxis
6-311� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
30001 Illegal parameter (parameter index according to standard sequence in thesystem functions: /1/%d, command type: /4/%X)
CauseIllegal system function parameter, the command is aborted. The parameters indicate the position of the illegal system function parameteraccording to the standard sequence in the system functions and the command typeof an incorrectly entered parameter.
Meaning of alarm parameters
Parameter index:
Index of the first system function parameter that triggered this error (listedaccording to the standard sequence in the system functions).
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyChange the parameters.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
posAxis
6-312� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
30002 Command aborted (reason: /1/%d, command type: /4/%X)
CauseExecution of the command was aborted before or during processing.This condition can arise as a result of loading a new command, resetting thecommand buffer, or an error state.
Meaning of alarm parameters
Reason:
1–Command buffer reset
2–Abort by another command
3–Aborted by a stop
4–Aborted by a higher-order stop
5–Abort by a pending error response
6–Aborted due to ambiguous commandId
7–Delayed acknowledgment
8–No actual value for axis (e.g., encoder or data bus not ready)
9–Aborted due to abnormal termination of a dependent command
10–Aborted due to active synchronous operation
11–Aborted due to active superimposed motion
12–Aborted due to active speed-controlled controller mode
13–Aborted due to active position-controlled controller mode
14–Aborted due to active motion to fixed end stop
15–Axis is not in pressure-limiting operation
16–Aborted due to active pressure-controlled operation
17–Aborted due to inactive pressure-controlled operation
18–Superimposed command is not permitted
19–Aborted due to error during cam access
20–Slave is not ready for operation
21–Error in slave synchronization
22–Aborted by command on slave
23–Aborted by stop on slave
24–Aborted by an active error response on the slave
25–No actual value for slave (e.g., encoder or data bus not ready)
26–Aborted by reset on slave
27–Master values are not valid
28–Active command in recursive TO interconnection
29–Aborted due to error during synchronization
30–Axis is in pressure-limiting operation
31–Maximum number of active commands exceeded
32–Aborted due to active correction command
33–Action only permissible in standstill
Command type:
Outputs the aborted command type. The command type is output as ahexadecimal integer value.
posAxis
6-313� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
RemedyReset command via program.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
posAxis
6-314� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
30003 Command aborted due to full command buffer (command type: /4/%X)
CauseThe command is not entered in the command buffer as the buffer is already full.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
Remedy
� Check the program flow.
� Typical cause: The ’nextCommand’ parameter is passed with the valueIMMEDIATELY. You need to synchronize the command sequence manually oruse another value for ’nextCommand’.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
posAxis
6-315� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
30004 Unknown command (command type: /4/%X)
CauseThe active software tool does not support this command.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyCheck the versions of the engineering system and the runtime software.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
posAxis
6-316� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
30005 Ambiguous commandId (number of commands with specified ID: /1/%d,command type: /4/%X)
CauseThe specified commandID refers to several commands.The specified action is performed for the command matching the specifiedcommandID that has been in the interpolator for the longest time. If nocorresponding command is found in the interpolator, the action refers to the nextcommand loaded in the interpolator.
Meaning of alarm parameters
Number of commands with specified ID:
Number of commands referenced by the specified commandId.
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyUse different commandIds for commands that are active simultaneously.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
posAxis
6-317� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
30006 Cannot execute command due to current object state (command type: /4/%X)
CauseThe object is in the stop, error, or reset state and the command is not possible inthis object state.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
Remedy
� Check the object status.
� Check the permissible sequence of commands.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
posAxis
6-318� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
30007 The error cannot be reset due to its configuration
CauseThe alarm cannot be acknowledged at the present time or by the selected means.
Remedy
� Check the configured acknowledgment procedure.
� If necessary, change the acknowledgment procedure for the alarm.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
posAxis
6-319� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
30008 A connection to a technology object required for this operation does notexist (command type: /4/%X)
CauseThe object connection required for this operation has not been configured.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyCheck the project configuration, or change the object connection in the command.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
posAxis
6-320� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
30009 Command rejected due to suspension of command decoding on addressedtechnology object (command type: /4/%X)
CauseCommand was rejected due to suspension of command decoding on theaddressed technology object.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
Remedy
� Check why the command was rejected.
� If necessary, acknowledge any active errors once you have corrected the causeof the error.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
posAxis
6-321� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
30010 Command not available (command type: /4/%X)
CauseThe command is not available in this version of the runtime software.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyCheck the version of the runtime software.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
posAxis
6-322� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
30011 Parameter unavailable (parameter index according to standard sequence inthe system functions: /1/%d, command type: /4/%X)
CauseThe parameter is not available in this version of the runtime software, thecommand is therefore rejected. The parameters indicate the position according tothe standard sequence in the system functions and the command type of anincorrectly entered parameter.
Meaning of alarm parameters
Parameter index:
Index of the command parameter triggering this error according to the standardsequence in the system functions.
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyCheck the version of the runtime software.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
posAxis
6-323� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
30012 Command cannot be started synchronously (command type: /4/%X)
CauseThe command cannot be used during a BEGIN_SYNC, END_SYNC sequencebecause it is a reset command or a command that has only one return value in theuser program.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyDo not use this command type during a BEGIN_SYNC, END_SYNC sequence.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
posAxis
6-324� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
30013 Synchronous start of the command using IMMEDIATELY mergeMode(command type: /4/%X)
CauseWith synchronous command start, only merge modes that immediately override thecurrent command (IMMEDIATELY) and superimpose the current command(SUPERIMPOSED_MOTION_MERGE) can be used. If an illegal merge mode isprogrammed (e.g., SEQUENTIAL or NEXT_MOTION), the system automaticallychanges the merge mode to IMMEDIATELY and outputs this warning.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyProgram the command, which is to be started synchronously to immediatelyoverride the current command. To do this, enter the value IMMEDIATELY in the’mergeMode’ command parameter.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
posAxis
6-325� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
30014 Coordinate system not offset due to the internal traversing range limit beingexceeded (Parameter1: /1/% /1/%d, command type: /2/%X)
CauseThe programmed coordinate system offset causes the internal traversing rangelimit to be exceeded. The coordinate system is not shifted.
Meaning of alarm parameters
Parameter1:
= 0 negative internal traversing range limit
= 1 positive internal traversing range limit
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyCheck the programming for the coordinate system offset.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
posAxis
6-326� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
30015 A technology required for this command was not configured (technology:/1/%d, command type: /4/%X)
CauseThe command cannot be selected in this technology object configuration.
Meaning of alarm parametersTechnology:
= 1 Axis with force/pressure control without flow/force specification
= 2 Axis with force/pressure control and flow/force specification
= 3 Axis without flow/force specification
= 4 Axis with flow/force specification
= 5 Axis with force specification
= 6 Axis with pressure setpoint specification
= 7 Axis with pressure limiting
= 8 Axis with speed limiting parallel to force/pressure control
= 9 Axis with flow specification
Command type:Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyActivate the technology needed for the command.Technology:
= 1 Select the mode setting REAL_AXIS_WITH_PRESSURE_CONTROL in theTypeOfAxis configuration data
= 2 Select the mode settingREAL_QP_AXIS_WITH_CLOSED_LOOP_FORCE_CONTROL in theTypeOfAxis configuration data
= 3 Select the mode setting VIRTUAL_AXIS, REAL_AXIS orREAL_AXIS_WITH_FORCE_CONTROL in the TypeOfAxis configuration data
= 4 Select the mode setting EAL_QPAXIS,REAL_QP_AXIS_WITH_OPEN_LOOP_FORCE_CONTROL orREAL_QP_AXIS_WITH_CLOSED_LOOP_FORCE_CONTROL in theTypeOfAxis configuration data
= 5 Select the mode settingREAL_QP_AXIS_WITH_OPEN_LOOP_FORCE_CONTROL in the TypeOfAxisconfiguration data
= 6 Select the mode setting REAL_AXIS_WITH_PRESSURE_CONTROL orREAL_QP_AXIS_WITH_CLOSED_LOOP_FORCE_CONTROL in theTypeOfAxis configuration data
= 7 Select the mode setting REAL_AXIS_WITH_PRESSURE_CONTROL,REAL_QP_AXIS_WITH_OPEN_LOOP_FORCE_CONTROL orREAL_QP_AXIS_WITH_CLOSED_LOOP_FORCE_CONTROL in theTypeOfAxis configuration data
= 8 Select the mode settingREAL_QP_AXIS_WITH_CLOSED_LOOP_FORCE_CONTROL in theTypeOfAxis configuration data
= 9 Select a mode setting with flow specification in the TypeOfAxis configurationdata
posAxis
6-327� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
40001 Illegal state change on axis
CauseCommand for change of axis state could not be performed, because:1. The operating status phase is not complete.2. The operational transition is not possible.
RemedyFor 1.: Repeat command.For 2.: A reset must be performed first
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
posAxis
6-328� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
40002 Programmed velocity is limited
Cause1. The system is limiting the programmed velocity to the maximum permissibleparameter.2. For a virtual axis, the velocity is limited to a value that reliably identifies thedirection, that is, the velocity of the axis must not exceed that at which, dependingon the IPO task, at least one measured value can be detected in the range ofone-half modulo length.
RemedyNot necessary, for information only.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
posAxis
6-329� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
40003 Programmed acceleration (type: /1/%d) is limited
CauseThe system is limiting the programmed acceleration to the maximum limit.
Meaning of alarm parameters
Type:
0 – positive acceleration
1 – negative acceleration/deceleration
RemedyNot necessary, for information only.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
posAxis
6-330� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
40004 Programmed jerk (type: /1/%d) is limited
CauseThe system is limiting the programmed jerk to the maximum limit.
Meaning of alarm parameters
Type:
0 – Increase in positive acceleration
1 – Reduction in positive acceleration
2 – Increase in negative acceleration/deceleration
3 – Reduction in negative acceleration/deceleration
RemedyNot necessary, for information only.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
posAxis
6-331� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
40005 Enable signal(s) missing (Parameter1: /1/%X) and/or incorrect mode(Parameter2: /2/%d)
CauseThe enables are missing and/or follow-up mode is active on the axis are missing when a command is pending.
Meaning of alarm parameters
Parameter1:
Bit 1 = 0: POWER enable signal is available1: POWER enable signal is missing
Bit 2 = 0: DRIVE enable signal is available1: DRIVE enable signal is missing
Bit 3 = 0: Position controller enable signal is available1: Position controller enable signal is missing
Bit 4 = 0: Force/pressure controller enable signal is available1: Force/pressure controller enable signal is missing
Parameter2:
0 – Follow-up mode deselected
1 – Follow-up mode selected
RemedyActivate the enable signals before issuing a motion command.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseFEEDBACK_EMERGENCY_STOP
Programmable local responsesFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
posAxis
6-332� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
40006 Programmed velocity is zero
CauseThe programmed velocity is zero. The specified motion cannot be executed.
RemedyProgram a value not equal to zero. If USER_DEFAULT is referenced, a value notequal to zero must be programmed in the assigned system variable.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseFEEDBACK_EMERGENCY_STOP
Programmable local responsesFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
40007 Programmed acceleration (type: /1/%d) is zero
CauseThe programmed acceleration is zero. The specified motion cannot be executed.
Meaning of alarm parameters
Type:
0 – positive acceleration
1 – negative acceleration/deceleration
RemedyProgram a value not equal to zero. If USER_DEFAULT is referenced, a value notequal to zero must be programmed in the assigned system variable.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseFEEDBACK_EMERGENCY_STOP
Programmable local responsesFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
posAxis
6-333� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
40008 Programmed jerk (type: /1/%d) is zero
CauseThe programmed jerk is zero. The specified motion cannot be executed.
Meaning of alarm parameters
Type:
0 – Increase in positive acceleration
1 – Reduction in positive acceleration
2 – Increase in negative acceleration/deceleration
3 – Reduction in negative acceleration/deceleration
RemedyProgram a value not equal to zero. If USER_DEFAULT is referenced, a value notequal to zero must be programmed in the assigned system variable.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseFEEDBACK_EMERGENCY_STOP
Programmable local responsesFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
40009 Velocity limit is zero
CauseThe programmed velocity is zero. The specified motion cannot be executed.
RemedyProgram a value not equal to zero in the dynamic limit values.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseFEEDBACK_EMERGENCY_STOP
Programmable local responsesFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
posAxis
6-334� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
40010 Acceleration limit (type: /1/%d) is zero
CauseThe programmed acceleration limit is zero. The specified motion cannot beexecuted.
Meaning of alarm parameters
Type:
0 – positive acceleration
1 – negative acceleration/deceleration
RemedyProgram a value not equal to zero.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseFEEDBACK_EMERGENCY_STOP
Programmable local responsesFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
40011 Programmed jerk limit (type: /1/%d) is zero
CauseThe programmed jerk is zero. The specified motion cannot be executed.
Meaning of alarm parameters
Type:
0 – Increase in positive acceleration
1 – Reduction in positive acceleration
2 – Increase in negative acceleration/deceleration
3 – Reduction in negative acceleration/deceleration
RemedyProgram a value not equal to zero.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseFEEDBACK_EMERGENCY_STOP
Programmable local responsesFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
posAxis
6-335� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
40012 Dynamic restrictions (type: /1/%d) violated
CauseThe specified dynamic restrictions have been violated. This can occur due to:
� Programming of new jerk-controlled motions with extremely divergent dynamicparameters, which would lead to an additional reversing motion, reducing thecurrent acceleration.
� Programming of superimposed motions exceeding the resulting dynamicparameters, which would lead to overshoot or to a reversing motion whenrestricted to the maximum velocity or when entering final velocity.
One or more physical variables (velocity, acceleration, jerk) may be affected. The violations have only a temporary effect.
Meaning of alarm parameters
Type:
0 – The jerk is changed; the jerk limit is exceeded.
1 – The jerk limit is disabled during jerk-controlled motion.
2 – The acceleration is changed; the acceleration limit is exceeded.
3 – The acceleration is changed, and the jerk limit is disabled. The accelerationlimit is exceeded.
Remedy
� For new motion: Increase the dynamic response parameters.
� For superimposed motion: Allow for the current (resulting) limitations whenprogramming the dynamic response parameters.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
posAxis
6-336� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
40013 Programmed stop time restricted by acceleration limits
CauseThe specified stop time cannot be achieved. It is violated due to the maximumacceleration limits. Deceleration is performed with the maximum values.
Remedy
� Increase the programmed time.
� Check the maximum acceleration and the active programmed limits.
� Increase the limits if necessary.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
posAxis
6-337� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
40014 Command not possible on virtual axis (command type: /4/%X)
CauseThe command is not supported by virtual axes.
RemedyUse a real axis.
Acknowledgment / responseReset fault memory / NONE
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
40015 Error in accessing specified cam
CauseThe specified cam does not exist or is not connected with synchronous operation,or the cam is already active.
Remedy
� Check the programmed cam.
� Check the synchronous operation connection with the cam.
� Check the program sequence.
Acknowledgment / responseReset fault memory / NONE
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
posAxis
6-338� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
40016 The specified cam has not been interpolated
CauseThe system only accepts verified and interpolated cams for this operation. Thespecified cam has not yet been interpolated.
RemedyCheck whether the specified cam has been interpolated.
Acknowledgment / responseReset fault memory / NONE
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
40017 Cam start point outside definition range
CauseThe addressed cam start point is outside the definition range of the cam.
Remedy
� Check the definition range of the cam.
� Check the cam start point.
Acknowledgment / responseReset fault memory / NONE
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
posAxis
6-339� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
40018 Dynamic response of motion profiles (type: /1/%d) violated (reason: /2/%d)
CauseThe specified dynamic response cannot be achieved.
Meaning of alarm parameters
Type:
1 – Velocity-time profile
2 – Position-time profile
3 – Velocity-position profile
4 – Velocity-interface position profile
5 – Velocity-time limit profile
6 – Velocity-position limit profile
7 – Velocity-interface position limit profile
Reason:
0 – The velocity resulting form the profile has been limited to the programmedvalue.
1 – The acceleration/deceleration resulting from the profile has been limited to theprogrammed value.
Remedy
� For superimposed motion: Allow for the current (resulting) limitations when programming the dynamicresponse parameters.
� Increase the dynamic response parameters.
Acknowledgment / responseReset fault memory / NONE
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
posAxis
6-340� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
40019 Error while accessing the motion interface
CauseThe specified reference object for the motion interface does not exist or is notconnected to the axis.
Remedy
� Check the programmed input interconnection.
� Check the program sequence.
Acknowledgment / responseReset fault memory / NONE
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
posAxis
6-341� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
40020 Dynamic response of the setpoints on the motion interface (type: /1/%d)violated (reason: /2/%d)
CauseThe specified dynamic response cannot be achieved.
Meaning of alarm parameters
Type:
1 – Velocity-based setpoints
2 – Position-based setpoints
Reason:
0 – The velocity resulting form the interface has been limited to the programmedvalue.
1 – The acceleration/deceleration resulting from the interface has been limited tothe programmed value.
Remedy
� For superimposed motion: Allow for the current (resulting) limitations when programming the dynamicresponse parameters.
� Increase the dynamic response parameters.
Acknowledgment / responseReset fault memory / NONE
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
posAxis
6-342� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
40021 StopEmergency command abort due to a pending stop response of the sameor higher priority
CauseThe StopEmergency command on the axis was aborted when called or while activedue to a stop response of the same or higher priority, resulting from anerror.The alarm is generated as an additional aid for emergency stop strategies, and canfor example ensure a safe program sequence by changing the stop response.
Remedy
Acknowledgment / responseReset fault memory / NONE
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
posAxis
6-343� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
40022 Programmed pressure limiting is limited
CauseThe system is limiting the pressure limiting value to the maximum limit.
RemedyNot necessary, for information only.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
40023 Programmed increase in pressure limiting limited
CauseThe system is limiting the pressure limiting increase to the maximum limit.
RemedyNot necessary, for information only.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
posAxis
6-344� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
40024 Programmed increase in pressure limiting is zero
CauseThe programmed increase in pressure limiting limit is zero. The specified pressurelimiting characteristic cannot be calculated.
RemedyProgram a value not equal to zero. If USER_DEFAULT is referenced, a value notequal to zero must be programmed in the assigned system variable.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseMOTION_EMERGENCY_ABORT
Programmable local responsesMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
40025 Maximum increase in pressure limiting is zero
CauseThe limit value for the pressure limiting increase is zero. The specified pressurelimiting characteristic cannot be calculated.
RemedyProgram a value not equal to zero in the dynamic limit values.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseMOTION_EMERGENCY_ABORT
Programmable local responsesMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
posAxis
6-345� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
40026 Dynamic response of pressure/pressure limiting profiles (type: /1/%d)violated (reason: /2/%d)
CauseThe specified dynamic response cannot be achieved.
Meaning of alarm parameters
Type:
1 – Pressure-time limit profile
2 – Pressure-position limit profile
3 – Pressure-interface position limit profile
4 – Pressure-time profile
5 – Pressure-position profile
6 – Pressure-interface position profile
Reason:
0 – The pressure/pressure limiting value resulting from the profile has been limitedto the maximum pressure/pressure limiting value.
1 – The pressure/pressure limiting increase value resulting from the profile hasbeen limited to the maximum pressure/pressure limiting increase value.
Remedy
� Increase the dynamic response parameters.
Acknowledgment / responseReset fault memory / NONE
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
posAxis
6-346� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
40101 Homing output cam not found
CauseThe homing output cam has not been found because:
� It is outside the permissible range.
� Limit switch monitoring system has responded.
Remedy
� Check the permissible range for homing.
� Check the hardware configuration.
� Check the home position and, if the approach direction is incorrect, change thestart position of the axis for homing.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseMOTION_EMERGENCY_ABORT
Programmable local responsesMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
posAxis
6-347� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
40102 Encoder zero mark not found during homing
CauseThe encoder zero mark could not be found because:
� The difference between the reference output cam and the encoder zero mark isoutside the permissible range.
� Limit switch monitoring system has responded.
� The reference deceleration velocity is too high.
Remedy
� Check the permissible range.
� Check the hardware configuration.
� Reduce the deceleration velocity.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseFEEDBACK_EMERGENCY_STOP
Programmable local responsesFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
posAxis
6-348� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
40103 Error in homing configuration data (Parameter1: /1/%d)
CauseThe configured axis data and the selected parameters in the homing command areinconsistent with one another.
Meaning of alarm parameters
Parameter1
1 – ENABLE_OFFSET_OF_ABSOLUTE_ENCODER has been selected in thehoming command but an incremental encoder is configured.
2 – ACTIVE_HOMING or PASSIVE_HOMING has been selected in the homingcommand, but an SSI encoder is configured.
3 – ACTIVE_HOMING has been selected in the homing command, butNO_REFERENCE was configured under homingMode in the configurationdata for the encoder.
4 – ACTIVE_HOMING, PASSIVE_HOMING orENABLE_OFFSET_OF_ABSOLUTE_ENCODER has been selected in thehoming command, but NO_SENSOR was selected under encoderType in theconfiguration data for the encoder.
6 – The homing approach velocity is zero.
7 – The homing entry velocity is zero.
8 – The homing reduced velocity is zero.
RemedyCheck the configuration data and the command parameters for homing
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseFEEDBACK_EMERGENCY_STOP
Programmable local responsesFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
posAxis
6-349� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
40104 Error in software limit switch specification (Parameter1: /1/%d)
CauseThe software limit switches are programmed incorrectly.
Meaning of alarm parameters
Parameter1:
= 0: Negative switch is greater than positive switch when the axis is not amodulo axis.
= 1: Current set position is not in programmed range. The software limit switchwas deactivated.
RemedyReprogram the software limit switches.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseMOTION_EMERGENCY_STOP
Programmable local responsesMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
posAxis
6-350� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
40105 Position limited to software limit switch (Parameter1: /1/%d)
CauseThe programmed position has been limited to the software limit switch.
Meaning of alarm parameters
Parameter1:
= 0 negative switch
= 1 positive switch
RemedyCheck the program code for the motion.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseEND_OF_MOTION_STOP
Programmable local responsesEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
40106 Software limit switch (Parameter1: /1/%d) approached
CauseThe software limit switch has been approached during a motion sequence.
Meaning of alarm parameters
Parameter1:
= 0 negative switch
= 1 positive switch
RemedyCheck the program code for the motion.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseMOTION_EMERGENCY_ABORT
Programmable local responsesMOTION_EMERGENCY_ABORTRELEASE_DISABLE
posAxis
6-351� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
40107 Software limit switch (Parameter1: /1/%d) is crossed
CauseThe software limit switch has been crossed.
Meaning of alarm parameters
Parameter1:
= 0 negative switch
= 1 positive switch
RemedyCheck the program code for the motion.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseRELEASE_DISABLE
Programmable local responsesRELEASE_DISABLE
40108 Axis is not homed
CauseA command requiring a homed axis was passed to an axis that is not homed.
RemedyHome the axis.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseFEEDBACK_EMERGENCY_STOP
Programmable local responsesFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
posAxis
6-352� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
40109 Error on synchronizing two encoders (reason: /1/%d)
CauseAn attempt to synchronize two encoders has failed. Parameter 1 contains the exact error specification.
Meaning of alarm parameters
Reason:
= 0: The reference encoder is not configured or is defective.
= 1: The encoder to be synchronized is not configured or is defective.
= 2: Function not possible as only one encoder has been configured.
= 3: Illegal correction of the active encoder.
Remedy
� Check the command parameters.
� Configure the encoder.
� Remedy the fault on the encoder.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
posAxis
6-353� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
40110 Error triggered on slave during synchronous operation (error number: /1/%d)
CauseAn error was triggered on a slave during synchronous operation and reported tothe master.
Meaning of alarm parameters
Error number: Error reported by slave.
1–Synchronous operation setpoint tolerance exceeded.
2–Synchronous operation actual-value tolerance exceeded.
RemedyCheck the configuration data for synchronous operation monitoring on the slave,the programming (dynamic parameters, synchronous operation coupling), and thesystem variables.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseMOTION_EMERGENCY_ABORT
Programmable local responsesMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
40111 Internal traversing range limit (Parameter1: /1/%d) approached
CauseThe internal traversing range limit has been approached during a motion sequence.
Meaning of alarm parameters
Parameter1:
= 0 negative internal traversing range limit
= 1 positive internal traversing range limit
RemedyCheck the program code for the motion.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseMOTION_EMERGENCY_ABORT
Programmable local responsesMOTION_EMERGENCY_ABORTRELEASE_DISABLE
posAxis
6-354� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
40112 Internal traversing range limit (Parameter1: /1/%d) is crossed
CauseThe internal traversing range limit has been crossed.
Meaning of alarm parameters
Parameter1:
= 0 negative switch
= 1 positive switch
RemedyCheck the program code for the motion.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseRELEASE_DISABLE
Programmable local responsesRELEASE_DISABLE
40120 Programmed pressure is limited
CauseThe system is limiting the programmed pressure to the maximum permissiblepressure.
RemedyNot necessary, for information only.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
posAxis
6-355� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
40121 Programmed pressure rise is limited
CauseThe system is limiting the programmed pressure rise to the maximum permissiblepressure rise.
RemedyNot necessary, for information only.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
40122 Programmed pressure rise is zero
CauseThe programmed pressure rise is zero. The specified pressure characteristiccannot be calculated.
RemedyProgram a value not equal to zero. If USER_DEFAULT is referenced, a value notequal to zero must be programmed in the assigned system variable.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseMOTION_EMERGENCY_ABORT
Programmable local responsesMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
posAxis
6-356� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
40123 Maximum pressure rise is zero
CauseThe limit value for the pressure rise is zero. The specified pressure characteristiccannot be calculated.
RemedyProgram a value not equal to zero in the dynamic limit values.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseMOTION_EMERGENCY_ABORT
Programmable local responsesMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
40124 Offset cannot be compensated.
CauseThe determined cycle clock offset is greater than the maximum permissiblesetpoint output delay. The offset cannot be compensated completely in the master.
RemedyNot necessary, for information only.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
posAxis
6-357� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
40125 Setpoint output delay deactivated in the master
CauseThis leading value source operates without setpoint output delay on the masterside.The setpoint output delay on the master side has been activated on at least oneinterconnected following axis. The synchronous operation relationship between theleading value source and the following axis is not operating synchronously.
RemedyActivate the setpoint output delay for the master setpoint source in the master.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
posAxis
6-358� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
40301 Connection with slave failed (assignment: /1/%d)
CauseThe connection with an interconnected slave has failed. The slave is located on adistributed controller or has been assigned to a different execution level than themaster. Leading values of the master cannot be communicated to the slave for theduration of the connection failure. During the communication malfunction, asynchronous operation monitoring response on the slave cannot be communicatedto the master.
Meaning of alarm parameters
Assignment 1: The failed slave is located on an assigned controller.
Assignment 2: The failed slave has been assigned to a different execution levelthan the master.
Remedy
� Check that the assigned controller is activated, the slave is configured asdistributed, and communication is permitted by the operating mode of theassociated controller (assignment 1).
� Check the connection for mechanical damage, equivalence of configurednetwork topology, firm contact by the plug connector, and, if necessary, correctelectrical cable terminations (assignment 1).
� Check that the failed slave was not being reloaded at the time the error wasdetected (assignment 1 and 2).
� Check whether an overflow was diagnosed for the execution level of theassigned slave (assignment 2).
� Monitoring of the connection is set in the technology object configuration. Themaster and slave must have the same settings selected (assignment 1 and 2).
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
posAxis
6-359� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
40302 Sign-of-life monitoring for the slave in distributed synchronous operation isdeactivated
CauseSign-of-life monitoring for the slave connection on an assigned controller has beendeactivated. Monitoring is configured differently on the master and slave. As aresult, the connection is established without sign-of-life monitoring.
CauseUse identical configuration settings in the master and slave for sign-of-lifemonitoring of the connection
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
posAxis
6-360� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
40303 Local and slave interpolation cycle clock are different
CauseThe master and slave must have a common interpolation cycle clock for distributedsynchronous operation. However, when establishing the connection betweentechnology objects, different cycle clock settings were defined for interpolation.
RemedyUse identical cycle clock settings in the master and slave for interpolation.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
posAxis
6-361� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
40304 Offset cannot be determined
CauseThe offset for the slave cannot be determined. This can be caused by configuringthe PROFIBUS-DP without equidistance or a ratio of interpolator cycle clock toPROFIBUS-DP cycle clock greater than 64.
Remedy
� Select equidistant mode on the PROFIBUS-DP.
� Select a suitable IPO / DP cycle clock ratio setting
� Deactivate offset compensation on the technology objects involved. Deactivate compensation only if other remedies do not eliminate themalfunction. Deactivating the offset compensation limits the accuracy of motioncontrol.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
posAxis
6-362� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
50001 Drive failure
CauseDrive fault
RemedyCheck the configuration of the drive system, the cabling, and the power supply.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseRELEASE_DISABLE
Programmable local responsesRELEASE_DISABLE
50002 Limiting frequency of measuring system exceeded
CauseThe limiting frequency of the encoder has been exceeded.
Remedy
� Check the encoder connection.
� Check the maximum velocity limits in the configuration data.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
posAxis
6-363� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
50003 Speed acceleration setpoint limitation active
CauseThe speed acceleration setpoint is limited.
Remedy
� Check the mechanical configuration.
� Check the encoder connection.
� Check the configuration of the speed setpoint interface.
� Check the maximum permissible acceleration rates in the configuration data.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
posAxis
6-364� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
50005 Speed setpoint monitoring active (Parameter1: /1/%d)
CauseThe speed setpoint is limited.
Remedy
� Check the mechanical configuration.
� Check the encoder connection.
� Check the configuration of the speed setpoint interface.
� Check the maximum permissible velocities in the configuration data.
Parameter 1: Specification of limitation1–Limitation of the velocity-related definition range (on hydraulic axes beforethe cam) reached.2–Limitation of the value range (hydraulic axes only) reached.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
posAxis
6-365� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
50006 Zero mark monitoring
CauseThe zero mark monitoring system has responded.
Remedy
� Check the mechanical configuration and the encoder configuration.
� Check the encoder error messages.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseOPEN_POSITION_CONTROL
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
posAxis
6-366� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
50007 Hardware limit switch (Parameter1: /1/%d, Parameter2: /2/%d)
CauseHardware limit switch has been violated.
Meaning of alarm parameters
Parameter1:
1: Limit switch reached
2: Polarity reversal on limit switch (can only be deleted by reconfiguring thetechnology object or Power On)
3: Illegal retraction direction
4: Both limit switches are active
Parameter2:
0: Not relevant
1: Limit switch in positive traversing direction
2: Limit switch in negative traversing direction
Remedy
� Check the mechanical configuration.
� Check the limit switches.
� If an error has occurred in the program, change the program or use the softwarelimit switches.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseRELEASE_DISABLE
Programmable local responsesFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
posAxis
6-367� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
50008 Timeout waiting for standstill signal
CauseTimeout occurred while waiting for standstill signal.
Remedy
� Check the configuration of ’Axis.TypeOfAxis.StandStillSignal’.
� Check that the control loop is operating correctly.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseRELEASE_DISABLE
Programmable local responsesOPEN_POSITION_CONTROLRELEASE_DISABLE
50009 Limit switch active: (Parameter1: /1/%d) only one traversing directionpossible
CauseA positive (Parameter1 = 1) or negative (Parameter1 = 2) hardware limit switch isactive or has been crossed. Motion is possible in the positive or negative traversing direction only.
Remedy
� Check the mechanical configuration.
� Check the limit switches.
� If an error has occurred in the program, change the program or use the softwarelimit switches.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONE
posAxis
6-368� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
50010 Error while reading or writing data set (category: /1/%d, error number: /2/%d)
CauseAn error occurred while reading or writing.
Meaning of alarm parameters
Category: Area in which the error occurred.
1–Command decoding
2–Interpolator
3–Controller
4–Manipulated variable output
5–Encoder system
Error number: Specification of error
1000 = “General configuration error”
2000 = “Error in actuator system configuration”
2001 = “Outside of limits of manipulated variable”
2003 = “Error in load gear ratios”
2004 = “Error in maximum velocity”
2005 = “Maximum velocity greater than maximum attainable velocity”
2006 = “Drive not suitable for torque-controlled or torque-limited operation”
2007 = “Linear stepper motor not implemented”
2008 = “Right-aligned format for direct output not implemented”
2009 = “Illegal value in resolution for direct output”
2010 = “Missing configuration data for actuator system”
2011 = “Missing configuration data for additional actuator system”
2012 = “The backstop range (min to max) does not contain a zero point”
2014 = “Drive or message frame not suitable for torque superimposition”
2015 = “Gear ratios less than or equal to 0”
2016 = “Resolution for stepper motor is 0”
2017 = “Illegal value for the configuration data maxSpeed”
2018 = “Illegal value for the configuration data maxVelocity”
2019 = “Limits of a configuration data exceeded”
2020 = “Limits for the max. acceleration exceeded”
2021 = “Illegal values for dead-zone compensation”
2022 = “Illegal values for sliding-friction compensation”
2023 = “Illegal values for backstop range”
2024 = “Error in sliding-friction compensation parameter”
3000 = “Error in encoder system”
3001 = “Error in encoder system”
3002 = “Invalid axis type selected”
3003 = “Leadscrew pitch is 0”
3004 = “Modulo axis selected with modulo value less than or equal to 0”
posAxis
6-369� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
3005 = “Illegal specification(s) in the encoder data (incremental / absolute, etc.)”
3006 = “Illegal number of encoders selected”
3007 = “Illegal incremental encoder number”
3008 = “Illegal data combination for homing with incremental encoder”
3009 = “Illegal encoder number”
3010 = “Illegal data on SSI encoder”
3011 = “Illegal encoder number”
3012 = “Illegal encoder number”
3013 = “Illegal measuring gear data, DRIVE assembly type (e.g., factor = 0)”
3014 = “Illegal encoder number”
3015 = “Illegal measuring gear data, LOAD assembly type (e.g., factor = 0)”
3016 = “Illegal data set number (e.g., factor = 0)”
3017 = “Encoder data sequence and number of encoders do not match”
3018 = “Error in encoder system”
3019 = “Illegal encoder number”
3020 = “Illegal encoder system / actuator system simulation selected”
3021 = “Illegal encoder number or incorrect number of data sets”
3022 = “Illegal encoder number or incorrect number of data sets”
3023 = “Illegal data for ratio of external attachment (e.g., factor = 0)”
3024 = “Path/rotation of external attachment = 0”
3025 = “Illegal value for monitoring of actual velocity”
3026 = “Illegal encoder number in SSI encoder configuration”
3027 = “Illegal message format in SSI encoder configuration”
3028 = “Illegal baud rate in SSI encoder configuration”
3029 = “Illegal SSI state in SSI encoder configuration”
3030 = “Illegal encoder number in data set”
3031 = “Encoder number in data set not configured”
3032 = “Illegal numerator factor in data set”
3033 = “Illegal denominator factor in data set”
3034 = “Illegal data set number”
3035 = “Data set number not configured”
3036 = “Encoder not configured”
3037 = “Homing of ENDAT encoder with zero mark not possible”
3038 = “Homing of CAM negative edge onboard not possible”
3039 = “On-the-fly homing of ENDAT encoder with zero mark not possible”
3040 = “On-the-fly homing of CAM negative edge onboard not possible”
3041 = “Factors for adjusting encoder data to the mechanics are outside the permissible range of values”
3042 = “Illegal data combination for homing with external encoder”
posAxis
6-370� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
3043 = “The incremental position of the encoder is outside the permissible range of values”
3044 = “The incremental position of the encoder is outside the permissible range of values”
3045 = “Illegal value for resolution of linear measuring system”
3046 = “Illegal value for filter of actual-velocity encoder”
3047 = “Illegal value for smoothing of actual-value encoder”
3048 = “Illegal value for smoothing of actual-value encoder with actual-valuecoupling”
3049 = “Illegal DSC encoder selection”
3050 = “Configuration of encoder system not completed correctly”
3051 = “Error in configuration of the sensor data or the stepper motor”
3052 = “Actual-value type (position, interval, velocity) not implemented”
3053 = “Only homing with CAM possible for stepper motor”
3054 = “Only on-the-fly homing with CAM possible for stepper motor”
3055 = “Stepper motor only possible with a real axis”
3056 = “Only one encoder permissible with stepper motor”
3057 = “DSC encoder is not a DP encoder”
3058 = “Illegal message frame of the DSC encoder”
3059 = “Modulo value too small”
3060 = “Configuration differential measurement position faulty”
3061 = “Illegal data in range configuration of the differential measurement position”
4000 = “Error in controller”
4001 = “Negative acceleration specified”
4002 = “Unknown ’FipoType’ requested”
4003 = “Error in runtime system, ratio of controller cycle clock to interpolator cycle clock incorrect”
4004 = “Requested filter arrangement not possible”
4005 = “Reserve for later use”
4006 = “Maximum limit is lower than minimum”
4007 = “Reserve for later use”
4008 = “Error in configuration data for controller”
4009 = “Reserve for later use”
4010 = “Reserve for later use”
4011 = “Reserve for later use”
4012 = “Reserve for later use”
4013 = “Requested controller type is not available”
4014 = “Error in controller factors”
4015 = “Feedforward control activated, kpc < 0 or kpc > 150”
4016 = “Reserve for later use”
4017 = “Reserve for later use”
4018 = “Reserve for later use”
4019 = “Reserve for later use”
4020 = “Reserve for later use”
posAxis
6-371� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
4021 = “Reserve for later use”
4022 = “Reserve for later use”
4023 = “Feedforward control activated, kpc <= 0”
4024 = “Model reference monitoring: Error in value of tolerance window”
4025 = “Error in limit value for standstill signal”
4026 = “Error in parameter for positioning monitoring”
4027 = “Reference model and dynamic following error monitoring activated, not possible at the same time”
4028 = “Sampling time parameter calculated incorrectly”
4029 = “Too many data sets requested”
4030 = “Error in runtime system, ratio of controller cycle clock to interpolator cycle clock incorrect”
4031 = “Error in time constant for emergency stop ramp generator (positionTimeConstant)”
4032 = “Feedforward control active, but fine interpolator type is DIRECT”
4033 = “Default data set outside limits”
4034 = “Maximum number of data sets not possible”
4035 = “Unknown data set alternating mode”
4036 = “Following error monitoring not activated/deactivated in all data sets”
4037 = “Model reference monitoring not activated/deactivated in all data sets”
4038 = “Different controller type in data sets”
4039 = “Feedforward control activated/deactivated in data sets”
4040 = “Time constant is 0”
4041 = “Error in dynamic adaptation parameter”
4042 = “System variable initialization could not be read”
4043 = “Driver simulation not implemented”
4044 = “Connection for stepper motors not implemented”
4045 = “Maximum velocity cannot be reached, maximum drive speed or a normalization factor incorrect”
4046 = “DSC requires motor encoder data to be specified”
4047 = “Drive or message frame type not suitable for DSC”
4048 = “Error in clamping monitoring parameter” ’No identifier’ is not permitted for the fixed end stop identifier.
4049 = “Without sensor, monitoring of the actual velocity by ’DynamicControl’ not possible”
4050 = “Inconsistent PROFIBUS parameterization; the sum of Ti and To is greater than one DP clock cycle”
4051 = “Error in manipulated variable limit parameter of force/pressure controller”
4052 = “Error in starting force/pressure monitoring parameter”
4053 = “Error in full-scale force/pressure monitoring parameter”
4054 = “Starting force/pressure monitoring tolerance less than tolerance of full-scale pressure monitoring”
4055 = “Error in force/pressure system deviation monitoring parameter”
posAxis
6-372� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
4056 = “Different activation/deactivation of the control difference monitoring of theforce/pressure controller not permitted in data sets”
4057 = “Different manipulated variable inversion of the force/pressure controller not permitted in data sets”
4058 = “Different force/pressure sensor types not permitted in data sets”
4059 = “Different activation/deactivation of the anti windup not permitted in datasets”
4060 = “Kd factor of the PID_ACTUAL controller is greater than 1”
4061 = “Time constant of the process model T1 <= T2”
4062 = “Illegal actuator type selection”
4063 = “Error in sliding friction compensation parameter”
4064 = “Error in offset application parameter”
4065 = “Feedforward control for force/pressure control not implemented”
4066 = “Error in standstill monitoring parameter”
4067 = “Following error monitoring: minVelocity must not be greater than or equal to maxVelocity”
4068 = “velocityTimeConstant when using a dead-time element for feedforward balancing too great”
4069 = “The system-related dead times are less than 0 after the calculation of additionalTime”
4070 = “Controller types not equal to DIRECT require the configuration of an encoder”
4071 = “Illegal values for delayTimeToActivate of the standstill signal”
4072 = “The IO device for the positive HW limit switch is not available”
4073 = “The IO device for the negative HW limit switch is not available”
4074 = “Limits of a controller parameter exceeded”
4075 = “Limit for emergency-stop-ramp brake delay exceeded”
4076 = “Limit for a substitute time constant exceeded”
4077 = “Limit for velocityTimeConstant exceeded”
4078 = “Error in value for configuration of QFDynamicData”
4079 = “Error in value for model reference monitoring”
4080 = “Error in following error monitoring parameter”
4081 = “Error in clamping monitoring parameter”
4082 = “Error in value for configuration of DynamicData”
4083 = “Error in value for configuration of PV controller”
4084 = “Incomplete configuration data for controller”
4085 = “Error in value for configuration of SystemDeadTimeData”
4086 = “Pressure control only possible with closed speed controller”
4087 = “DSC and compensation of valve characteristic not possible”
4088 = “DSC not possible on hydraulic axes”
4089 = “Time constant of dynamic compensation T1 <= T2”
posAxis
6-373� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
4090 = “Incorrect value for correction of system dead time”
5000 = “Encoder data sequence and number of encoders do not match”
5001 = “Illegal number of additional sensors selected”
5002 = “Illegal additional sensor type selected”
5003 = “Illegal data in configuration of driver data for additional sensor”
5004 = “Illegal data in configuration of conversion data for additional sensor”
5006 = “Illegal data in configuration of range for additional sensor”
5007 = “Illegal data in configuration of filter time for additional sensor”
5008 = “Configuration of additional sensor not completed correctly”
5009 = “Illegal number for additional sensor in data set”
5010 = “Illegal data in configuration of differential pressure measurement”
5011 = “Error sensor A differential pressure measurement”
5012 = “Error sensor B differential pressure measurement”
5013 = “Illegal data in configuration of extrapolation”
5014 = “Illegal data in configuration of execution task for sensor TO”
5015 = “Illegal data in configuration of substitute value strategy for sensor TO technological alarm”
5020 = “Illegal data in configuration of driver data for analog sensor”
5021 = “Illegal data in configuration of position filter for analog sensor”
5022 = “Illegal data in configuration of conversion data for analog sensor”
5023 = “Illegal data in configuration of measurement input for analog sensor”
5030 = “Illegal data in configuration of conversion data for interval counter”
6000 = “In the configuration data, the monitoring of the positioning path isconfigured up to the reference-point switch, and the maximum path to be traveled in the process is configured as zero”
6001 = “Error in configuration data numberOfMaxBufferedCommandId”
6002 = “Error in configuration data numberOfQueueCommands”
6003 = “Error in configuration data numberOfImmediateCommands”
6004 = “Configuration of behaviourAtTheEndOfProfile not implemented”
6005 = “Illegal value for the configuration data maximum acceleration”
6006 = “Illegal value for the configuration data maximum jerk”
6007 = “Illegal value for the configuration data maximum force/pressure setpoint”
6008 = “Illegal value for the configuration data maximum force/pressure setpoint rate of rise”
posAxis
6-374� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
6009 = “Illegal value for the configuration data synchronous operation tolerance on the setpoint side”
6010 = “Illegal value for the configuration data synchronous operation tolerance on the actual-value side”
6011 = “Illegal value for the configuration data enable synchronous operationtolerance on the setpoint side”
6012 = “Illegal value for the configuration data enable synchronous operationtolerance on the actual-value side”
6013 = “Illegal value for the configuration data tolerance window end-of-profile detection”
6014 = “Illegal value for the configuration data extrapolation time actual values”
6015 = “Illegal value for the configuration data tolerance window actual-valuecoupling”
6016 = “Illegal value for the configuration data touchdown tolerance position limit”
6017 = “Illegal value for the configuration data handling mode position limit”
7000 = “Illegal data in configuration of a process model”
7001 = “Illegal data in configuration of the functional component >drive model< of a process model”
7002 = “Illegal data in configuration of the functional component >delay< of a process model”
7003 = “Illegal data in configuration of the functional component >shut down drive< of a process model”
7004 = “Illegal data in configuration of the functional component >encoder< of a process model”
7005 = “Illegal data in configuration of the functional component >switch< of a process model”
8000 = “General error when reading or writing data set”
8001 = “The selected data set number is not available”
8002 = “Cannot write the active data set”
8003 = “Changing the controller structure (by writing a data set) is not possible”
Remedy
Change data record parameter.
posAxis
6-375� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
50011 Limit range of the incremental actual value exceeded (Parameter1: /1/%d)
CauseThe limit range of the incremental actual value has been exceeded.
Meaning of alarm parameters
Parameter1:
1: Range exceeded in positive direction
2: Range exceeded in negative direction
4: The modified actual position is greater than the modulo length in one positioncontrol cycle clock.
Remedy
Check and adjust the configuration data used for adjusting the actual value to themechanics.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseRELEASE_DISABLE
Programmable local responsesRELEASE_DISABLE
posAxis
6-376� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
50012 Drive does not support the selected function (Parameter1: /1/%d)
CauseError in selected function.
Meaning of alarm parameters
Parameter1:
1: The travel to home position function cannot be performed.
Remedy
Check and adjust the configuration data and the drive settings.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseRELEASE_DISABLE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
posAxis
6-377� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
50013 Overshoot/undershoot of permissible range limits (logical address: /1/%d,reason: /2/%d)
CauseRange violation for additional sensor.
Meaning of alarm parameters
Logical address: Address configured on the technology object.
Reason:
1: Value greater than maximum permissible value.
2: Value smaller than minimum permissible value.
3: Positive overflow of sensor range.
4: Negative overflow of sensor range.
5: Error in accessing hardware address.
Remedy
� Check and adjust the configuration data.
� Check the sensor connection.
� Check the wiring.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseRELEASE_DISABLE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
posAxis
6-378� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
50014 Permissible system deviation of pressure controller exceeded
CausePermissible system deviation of pressure controller exceeded.
RemedyCheck for correct functioning of the pressure control loop.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseRELEASE_DISABLE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
50015 Level overflow of IPO not detected
CauseThe system could not intercept a level overflow.
RemedyPlease contact Siemens Support with the error number indicated above.
Acknowledgment / responsePower On / STOP
Default setting for local responseRELEASE_DISABLE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
posAxis
6-379� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
50016 Backstop limitation active
CauseThe speed setpoint is limited by the backstop.
Remedy
� Check the mechanical configuration.
� Check the encoder connection.
� Check the configuration of the speed setpoint interface.
� Check the maximum permissible backstop values in the configuration data.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
posAxis
6-380� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
50017 Manipulated variable monitoring active at Q/F output (Parameter1: /1/%d)
CauseThe manipulated variable is limited.
Remedy
� Check the configuration of the valve characteristic.
� Check the maximum permissible velocity or the maximum permissible force/pressure setpoint in the configuration data.
� Check the encoder connection.
� Check the configuration of the setpoint interface.
Parameter 1: Specification of limiting1–Monitoring active at Q output.2–Monitoring active at F output.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
posAxis
6-381� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
50101 Reference model monitoring window exceeded
CauseThe dynamic demands on the control loop are too high.
Remedy
� Check the encoder count direction.
� Check the control loop parameter assignment.
� Change the parameter assignment for following error monitoring.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseRELEASE_DISABLE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
posAxis
6-382� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
50102 Dynamic following error monitoring window exceeded
CauseThe dynamic demands on the control loop are too high, or the control system isoverloaded.
Remedy
� Check the encoder count direction.
� Check the control loop parameter assignment.
� Change the parameter assignment for following error monitoring.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseRELEASE_DISABLE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
posAxis
6-383� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
50103 Warning limits of dynamic following error monitoring reached
CauseThe dynamic demands on the control loop are too high or the control system isoverloaded, the warning stage has been reached.
Remedy
� Check the encoder count direction.
� Check the control loop parameter assignment.
� Change the parameter assignment for following error monitoring.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
posAxis
6-384� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
50106 Positioning monitoring error
CauseThe axis could not reach the positioning window in the specified time.
Remedy
� Check the control loop parameter assignment.
� Check the parameter assignment for positioning monitoring.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseRELEASE_DISABLE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
50107 Standstill monitoring error
CauseThe axis has left the standstill window or could not reach the standstill window inthe specified time.
Remedy
� Check that the control loop is operating correctly.
� Check the parameter assignment for standstill monitoring.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseRELEASE_DISABLE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
posAxis
6-385� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
50108 Clamping monitoring error
CauseThe axis has exited the clamping tolerance window.
Remedy
� Check the mechanical end stop.
� Check that the control loop is operating correctly.
� Check the parameter assignment for clamping monitoring.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseRELEASE_DISABLE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
50109 Starting force window monitoring error
CauseThe axis could not reach the starting force window in the specified time.
Remedy
� Check the control loop parameter assignment.
� Check the parameter assignment for monitoring.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseFEEDBACK_EMERGENCY_STOP
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
posAxis
6-386� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
50110 Full-scale force monitoring error
CauseThe axis has left the full-scale force window or could not reach the window in thespecified time.
Remedy
� Check that the control loop is operating correctly.
� Check the parameter assignment for monitoring.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseFEEDBACK_EMERGENCY_STOP
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
50111 Pressure controller is operating at the limit
CauseThe manipulated variable required by the force controller cannot be implementedand is limited.
Remedy
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
7-387� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
followingAxis
Possible local responses
NONENo response
DECODE_STOPAbort command processing.
END_OF_MOTION_STOPStop once the active motions are complete.
MOTION_STOPStop motion with programmed values.
MOTION_EMERGENCY_STOPStop motion with maximum limit values.
MOTION_EMERGENCY_ABORTStop motion with maximum limit values and abort active commands.
FEEDBACK_EMERGENCY_STOPStop motion following emergency stop ramp and abort all active commands.
OPEN_POSITION_CONTROLStop motion with speed setpoint 0 and abort all active commands.
RELEASE_DISABLEStop motion with controller disable and abort all active commands.
7
followingAxis
7-388� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
20001 Internal error (Parameter1: /1/%d, Parameter2: /2/%d, Parameter3: /3/%d,Parameter4: /4/%d)
CauseThis alarm indicates internal error states providing information about the cause andlocation of the error in association with the related error number.
Meaning of alarm parameters
Parameter1: Error source
Parameter2 to 4: Error number
RemedyA detailed description of the system error alarm is not provided. Should a systemerror of this type occur, note the alarm number, the alarm text, and the internalsystem error number specified in the alarm and contact: SIEMENS AG A&D MC, Hotline.
Acknowledgment / responsePower On / STOP
Default setting for local responseRELEASE_DISABLE
Programmable local responsesRELEASE_DISABLE
followingAxis
7-389� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
20002 Insufficient memory (Parameter1: /1/%d, Parameter2: /2/%d, Parameter3: /3/%d, Parameter4: /4/%d)
CauseThe memory required by the system is no longer available. This alarm can occurboth during power up and after program calls.
Meaning of alarm parameters
Parameter1: Area in which the error occurred.
1–Command decoding
2–Interpolator
3–Controller
4–Manipulated variable output
5–Encoder system
6–Technology package
Parameters 2 to 4 are area-specific. They are not fully utilized by all areas.
Command decoding area:
Parameter2 and Parameter4 refer to the command in which the error occurred.
Parameter2: Command return value
Parameter4: Command type
Remedy
� Reduce the size of the ST code.
� Reduce the number of technology objects.
� Reduce the number of interpolation points for cams, if present.
Acknowledgment / responsePower On / STOP
Default setting for local responseFEEDBACK_EMERGENCY_STOP
Programmable local responsesFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
followingAxis
7-390� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
20003 No object configuration (Parameter1: /1/%d, Parameter2: /2/%d, Parameter3: /3/%d, Parameter4: /4/%d)
CauseError in system configuration. The configuration data for a software tool could notbe found.
Meaning of alarm parameters
Parameter1: Area in which the error occurred.
1–Command decoding
2–Interpolator
3–Controller
4–Manipulated variable output
5–Encoder system
Parameters 2 to 4 are area-specific. They are not fully utilized by all areas.
Command decoding area:
Parameter2 and Parameter4 refer to the command in which the error occurred.
Parameter2: Command return value
Parameter4: Command type
RemedyCheck the accuracy of the configuration data in your project. When commands arecalled on technology objects, the technology objects must be configured.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
followingAxis
7-391� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
20004 At the logical address: /1/%d (bit number, if required: /2/%d) a driver (type: /3/%d) could be requested (error number: /4/%d)
CauseThe driver of a physical device or the device itself is not available.
Meaning of alarm parameters
Logical address:
This is the address configured on the technology object.
Bit number:
For bit driver only; bit number
Type:
1–Actuator driver
2–Encoder driver
3–BitRead driver
4–BitWrite driver
5–ByteRead driver
6–ByteWrite driver
7–WordRead driver
8–WordWrite driver
9–DWordRead driver
10–DWordWrite driver
Error number: Specification of error
1000 = “General driver configuration error”
Remedy
� Connect a suitable device.
� Check the device (function, connections, terminals).
� Check the topological configuration in HWConfig.
� Compare configuration of HWConfig and technology object.
� Contact the hotline.
Acknowledgment / responsePower On / START TechnologicalFaultTask
Default setting for local responseRELEASE_DISABLE
Programmable local responsesRELEASE_DISABLE
followingAxis
7-392� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
20005 Device type: /3/%d, log. address: /1/%d faulty. (Bit: /2/%d, reason: 0x/4/%Xh)
CauseThe driver of a physical device or the device itself has failed or is faulty. When thisalarm occurs, the error cause must be evaluated in the external device (drive orencoder).
Meaning of alarm parameters
Type:
1–Actuator driver
2–Encoder driver
3–BitRead driver
4–BitWrite driver
5–ByteRead driver
6–ByteWrite driver
7–WordRead driver
8–WordWrite driver
9–DWordRead driver
10–DWordWrite driver
Logical address:This is the address configured on the technology object.
Bit number:For bit driver type = 3 or 4 only; bit number
Reason:0–Not defined (e.g., for binary I/O)
� Type = 1
0x0001h: Fault message from drive (note: On PROFIBUS drives, whichsupport acyclic communication in accordance with PROFIdrive V3,the error number/numbers of the drives is/are displayed in the
diagnostic buffer, e.g., on Masterdrives MC).
0x0002h: DP: Drive signal “control requested” failed
0x0004h: DP: Drive switched off itself
0x0008h: Slot for drive data is not available in the project
0x0010h: Actuator driver does not have a connection to the drive data
0x0020h: Actuator driver was not initialized during power up
0x0080h: DP: Difference between configuration data and drive parameters
0x4000h: DP: Drive on bus failed (station failure)
0x8000h: Sign of life of drive faulty or failed
followingAxis
7-393� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
� Type = 2
0x0000h: The number of permissible changes in the actual value of the maximum velocity of the absolute-value encoder has been exceeded
0x0001h: Fault message from encoder (note: The error number/numbers is/are displayed in the diagnostic
buffer)
0x0002h: General hardware error of encoder
0x0004h: Encoder contaminated
0x0008h: Slot for encoder data is not available in the project
0x0010h: Encoder driver does not have a connection to the encoder data
0x0020h: Encoder driver was not initialized during power up
0x0040h: Error when reading the absolute value of the encoder
0x0080h: DP: Difference between the configuration data and the encoder parameters
0x0100h: Zero mark monitoring of encoder
0x4000h: DP: Encoder on bus failed (station failure)
0x8000h: DP: Sign of life of encoder has malfunctioned or failed. (Note: For an encoder whose data are transferred in a drive message together with actuator data, the actuator sign of life applies for the encoder, e.g., a standard message 3 in accordance with PROFIdrive).
� Type = 3 to 10
0x0000h: Additional information, not assigned
Note:Codings for the reason of the failure can also occur in combination. Theindividual codings are then added to form a coding sum, which is displayed(e.g., 0x0005 = 0x0001 + 0x0004). A reason for failure marked as DP can only be present on PROFIBUS devices.
RemedyCheck the device with respect to function and connections (reason 0x0001,0x0002, 0x0004, 0x4000, 0x8000).
� Check the topological configuration in HW Config (with reason 0x0008).
� For PROFIBUS drives or encoders, compare the configuration of HWConfig, thetechnology object, and the drive parameter assignment.For:
Reason 0x0040:
– Compare the encoder type in the drive or encoder parameter P979 with theconfiguration data of the technology object.
followingAxis
7-394� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
Reason 0x0080:
– Compare the message frame type in the drive or encoder parameter P922with HW Config and the configuration data of the technology object.
– Compare the encoder type, resolution, multiplier and, with absoluteencoders, the data length in the drive or encoder parameter P979 with theconfiguration data of the technology object.
– Compare the parameterization named in reason 0x8000 (reason 0x8000 canoccur as secondary fault).
Reason 0x8000:
– Compare the cycle clock parameters of HW Config (PROFIBUS line, SlaveOM for drive or encoder) and the execution system. Tmapc and servo mustbe parameterized with the same cycle clock period!
� System fault, contact the hotline (reason 0x0008, 0x0010, 0x0020).
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseRELEASE_DISABLE
Programmable local responsesRELEASE_DISABLE
followingAxis
7-395� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
20006 Error in configuration (category: /1/%d, error number: /2/%d)
CauseThis alarm indicates error states caused by a faulty or inconsistent configuration.The technology objects perform a plausibility check on the configuration. Errors areidentified by the error codes below.
Meaning of alarm parameters
Category: Area in which the error occurred.
1–Command decoding
2–Interpolator
3–Controller
4–Manipulated variable output
5–Encoder system
6–Technology object
Error number: Specification of error
500 = “TO in illegal status for configuration”
501 = “More configuration data expected than received”
502 = “Invalid data in configuration”
503 = “Version conflict in configuration”
1000 = “General configuration error”
2000 = “Error in actuator system configuration”
2001 = “Outside of limits of manipulated variable”
2003 = “Error in load gear ratios”
2004 = “Error in maximum velocity”
2005 = “Maximum velocity greater than maximum attainable velocity”
2006 = “Drive not suitable for torque-controlled or torque-limited operation”
2007 = “Linear stepper motor not implemented”
2008 = “Right-aligned format for direct output not implemented”
2009 = “Illegal value in resolution for direct output”
2010 = “Missing configuration data for actuator system”
2011 = “Missing configuration data for additional actuator system”
2012 = “The backstop range (min to max) does not contain a zero point”
2014 = “Drive or message frame not suitable for torque superimposition”
2015 = “Gear ratios less than or equal to 0”
2016 = “Resolution for stepper motor is 0”
2017 = “Illegal value for the configuration data maxSpeed”
2018 = “Illegal value for the configuration data maxVelocity”
2019 = “Limits of a configuration data exceeded”
2020 = “Limits for the max. acceleration exceeded”
2021 = “Illegal values for dead-zone compensation”
2022 = “Illegal values for sliding-friction compensation”
followingAxis
7-396� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
2023 = “Illegal values for backstop range”
2024 = “Error in sliding-friction compensation parameter”
3000 = “Error in encoder system”
3001 = “Error in encoder system”
3002 = “Invalid axis type selected”
3003 = “Leadscrew pitch is 0”
3004 = “Modulo axis selected with modulo value less than or equal to 0”
3005 = “Illegal specification(s) in the encoder data (incremental / absolute, etc.)”
3006 = “Illegal number of encoders selected”
3007 = “Illegal incremental encoder number”
3008 = “Illegal data combination for homing withincremental encoder”
3009 = “Illegal encoder number”
3010 = “Illegal data on SSI encoder”
3011 = “Illegal encoder number”
3012 = “Illegal encoder number”
3013 = “Illegal measuring gear data, DRIVE assembly type (e.g., factor = 0)”
3014 = “Illegal encoder number”
3015 = “Illegal measuring gear data, LOAD assembly type (e.g., factor = 0)”
3016 = “Illegal data set number (e.g., factor = 0)”
3017 = “Encoder data sequence and number of encoders do not match”
3018 = “Error in encoder system”
3019 = “Illegal encoder number”
3020 = “Illegal encoder system / actuator system simulation selected”
3021 = “Illegal encoder number or incorrect number of data sets”
3022 = “Illegal encoder number or incorrect number of data sets”
3023 = “Illegal data for ratio of external attachment (e.g., factor = 0)”
3024 = “Path/rotation of external attachment = 0”
3025 = “Illegal value for monitoring of actual velocity”
3026 = “Illegal encoder number in SSI encoder configuration”
3027 = “Illegal message format in SSI encoder configuration”
3028 = “Illegal baud rate in SSI encoder configuration”
3029 = “Illegal SSI state in SSI encoder configuration”
3030 = “Illegal encoder number in data set”
3031 = “Encoder number in data set not configured”
3032 = “Illegal numerator factor in data set”
3033 = “Illegal denominator factor in data set”
3034 = “Illegal data set number”
3035 = “Data set number not configured”
3036 = “Encoder not configured”
3037 = “Homing of ENDAT encoder with zero mark not possible”
3038 = “Homing of CAM negative edge onboard not possible”
3039 = “On-the-fly homing of ENDAT encoder with zero mark not possible”
followingAxis
7-397� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
3040 = “On-the-fly homing of CAM negative edge onboard not possible”
3041 = “Factors for adjusting encoder data to the mechanics are outside the permissible range of values”
3042 = “Illegal data combination for homing with external encoder”
3043 = “The incremental position of the encoder is outside the permissible range of values”
3044 = “The incremental position of the encoder is outside the permissible range of values”
3045 = “Illegal value for resolution of linear measuring system”
3046 = “Illegal value for filter of actual-velocity encoder”
3047 = “Illegal value for smoothing of actual-value encoder”
3048 = “Illegal value for smoothing of actual-value encoder with actual-value coupling”
3049 = “Illegal DSC encoder selection”
3050 = “Configuration of encoder system not completed correctly”
3051 = “Error in configuration of the sensor data or the stepper motor”
3052 = “Actual-value type (position, interval, velocity) not implemented”
3053 = “Only homing with CAM possible for stepper motor”
3054 = “Only on-the-fly homing with CAM possible for stepper motor”
3055 = “Stepper motor only possible with a real axis”
3056 = “Only one encoder permissible with stepper motor”
3057 = “DSC encoder is not a DP encoder”
3058 = “Illegal message frame of the DSC encoder”
3059 = “Modulo value too small”
3060 = “Configuration differential measurement position faulty”
3061 = “Illegal data in range configuration of the differential measurement position”
4000 = “Error in controller”
4001 = “Negative acceleration specified”
4002 = “Unknown ’FipoType’ requested”
4003 = “Error in runtime system, ratio of controller cycle clock to interpolator cycle clock incorrect”
4004 = “Requested filter arrangement not possible”
4005 = “Reserve for later use”
4006 = “Maximum limit is lower than minimum”
4007 = “Reserve for later use”
4008 = “Error in configuration data for controller”
4009 = “Reserve for later use”
4010 = “Reserve for later use”
4011 = “Reserve for later use”
4012 = “Reserve for later use”
4013 = “Requested controller type is not available”
4014 = “Error in controller factors”
4015 = “Feedforward control activated, kpc < 0 or kpc > 150”
followingAxis
7-398� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
4016 = “Reserve for later use”
4017 = “Reserve for later use”
4018 = “Reserve for later use”
4019 = “Reserve for later use”
4020 = “Reserve for later use”
4021 = “Reserve for later use”
4022 = “Reserve for later use”
4023 = “Feedforward control activated, kpc <= 0”
4024 = “Model reference monitoring: Error in value of tolerance window”
4025 = “Error in limit value for standstill signal”
4026 = “Error in parameter for positioning monitoring”
4027 = “Reference model and dynamic following error monitoring activated, not possible at the same time”
4028 = “Sampling time parameter calculated incorrectly”
4029 = “Too many data sets requested”
4030 = “Error in runtime system, ratio of controller cycle clock to interpolator cycle clock incorrect”
4031 = “Error in time constant for emergency stop ramp generator (positionTimeConstant)”
4032 = “Feedforward control active, but fine interpolator type is DIRECT”
4033 = “Default data set outside limits”
4034 = “Maximum number of data sets not possible”
4035 = “Unknown data set alternating mode”
4036 = “Following error monitoring not activated/deactivated in all data sets”
4037 = “Model reference monitoring not activated/deactivated in all data sets”
4038 = “Different controller type in data sets”
4039 = “Feedforward control activated/deactivated in data sets”
4040 = “Time constant is 0”
4041 = “Error in dynamic adaptation parameter”
4042 = “System variable initialization could not be read”
4043 = “Driver simulation not implemented”
4044 = “Connection for stepper motors not implemented”
4045 = “Maximum velocity cannot be reached, maximum drive speed or a normalization factor incorrect”
4046 = “DSC requires motor encoder data to be specified”
4047 = “Drive or message frame type not suitable for DSC”
4048 = “Error in clamping monitoring parameter” ’No identifier’ is not permitted for the fixed end stop identifier.
4049 = “Without sensor, monitoring of the actual velocity by ’DynamicControl’ not possible”
4050 = “Inconsistent PROFIBUS parameterization; the sum of Ti and To is greater than one DP clock cycle”
4051 = “Error in manipulated variable limit parameter of force/pressure controller”
followingAxis
7-399� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
4052 = “Error in starting force/pressure monitoring parameter”
4053 = “Error in full-scale force/pressure monitoring parameter”
4054 = “Starting force/pressure monitoring tolerance less than tolerance of full-scale pressure monitoring”
4055 = “Error in force/pressure system deviation monitoring parameter”
4056 = “Different activation/deactivation of the control difference monitoring of the force/pressure controller not permitted in data sets”
4057 = “Different manipulated variable inversion of the force/pressure controller not permitted in data sets”
4058 = “Different force/pressure sensor types not permitted in data sets”
4059 = “Different activation/deactivation of the anti windup not permitted in data sets”
4060 = “Kd factor of the PID_ACTUAL controller is greater than 1”
4061 = “Time constant of the process model T1 <= T2”
4062 = “Illegal actuator type selection”
4063 = “Error in sliding friction compensation parameter”
4064 = “Error in offset application parameter”
4065 = “Feedforward control for force/pressure control not implemented”
4066 = “Error in standstill monitoring parameter”
4067 = “Following error monitoring: minVelocity must not be greater than or equal to maxVelocity”
4068 = “velocityTimeConstant when using a dead-time element for feedforward balancing too great”
4069 = “The system-related dead times are less than 0 after the calculation of additionalTime”
4070 = “Controller types not equal to DIRECT require the configuration of an encoder”
4071 = “Illegal values for delayTimeToActivate of the standstill signal”
4072 = “The IO device for the positive HW limit switch is not available”
4073 = “The IO device for the negative HW limit switch is not available”
4074 = “Limits of a controller parameter exceeded”
4075 = “Limit for emergency-stop-ramp brake delay exceeded”
4076 = “Limit for a substitute time constant exceeded”
4077 = “Limit for velocityTimeConstant exceeded”
4078 = “Error in value for configuration of QFDynamicData”
4079 = “Error in value for model reference monitoring”
4080 = “Error in following error monitoring parameter”
4081 = “Error in clamping monitoring parameter”
4082 = “Error in value for configuration of DynamicData”
4083 = “Error in value for configuration of PV controller”
4084 = “Incomplete configuration data for controller”
followingAxis
7-400� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
4085 = “Error in value for configuration of SystemDeadTimeData”
4086 = “Pressure control only possible with closed speed controller”
4087 = “DSC and compensation of valve characteristic not possible”
4088 = “DSC not possible on hydraulic axes”
4089 = “Time constant of dynamic compensation T1 <= T2”
4090 = “Incorrect value for correction of system dead time”
5000 = “Encoder data sequence and number of encoders do not match”
5001 = “Illegal number of additional sensors selected”
5002 = “Illegal additional sensor type selected”
5003 = “Illegal data in configuration of driver data for additional sensor”
5004 = “Illegal data in configuration of conversion data for additional sensor”
5006 = “Illegal data in configuration of range for additional sensor”
5007 = “Illegal data in configuration of filter time for additional sensor”
5008 = “Configuration of additional sensor not completed correctly”
5009 = “Illegal number for additional sensor in data set”
5010 = “Illegal data in configuration of differential pressure measurement”
5011 = “Error sensor A differential pressure measurement”
5012 = “Error sensor B differential pressure measurement”
5013 = “Illegal data in configuration of extrapolation”
5014 = “Illegal data in configuration of execution task for sensor TO”
5015 = “Illegal data in configuration of substitute value strategy for sensor TO technological alarm”
5020 = “Illegal data in configuration of driver data for analog sensor”
5021 = “Illegal data in configuration of position filter for analog sensor”
5022 = “Illegal data in configuration of conversion data for analog sensor”
5023 = “Illegal data in configuration of measurement input for analog sensor”
5030 = “Illegal data in configuration of conversion data for interval counter”
6000 = “In the configuration data, the monitoring of the positioning path is configured up to the reference-point switch, and the maximum path to be traveled in the process is configured as zero”
6001 = “Error in configuration data numberOfMaxBufferedCommandId”
6002 = “Error in configuration data numberOfQueueCommands”
6003 = “Error in configuration data numberOfImmediateCommands”
6004 = “Configuration of behaviourAtTheEndOfProfile not implemented”
6005 = “Illegal value for the configuration data maximum acceleration”
followingAxis
7-401� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
6006 = “Illegal value for the configuration data maximum jerk”
6007 = “Illegal value for the configuration data maximum force/pressure setpoint”
6008 = “Illegal value for the configuration data maximum force/pressure setpoint rate of rise”
6009 = “Illegal value for the configuration data synchronous operation tolerance on the setpoint side”
6010 = “Illegal value for the configuration data synchronous operation tolerance on the actual-value side”
6011 = “Illegal value for the configuration data enable synchronous operation tolerance on the setpoint side”
6012 = “Illegal value for the configuration data enable synchronous operation tolerance on the actual-value side”
6013 = “Illegal value for the configuration data tolerance window end-of-profile detection”
6014 = “Illegal value for the configuration data extrapolation time actual values”
6015 = “Illegal value for the configuration data tolerance window actual-value coupling”
6016 = “Illegal value for the configuration data touchdown tolerance position limit”
6017 = “Illegal value for the configuration data handling mode position limit”
7000 = “Illegal data in configuration of a process model”
7001 = “Illegal data in configuration of the functional component >drive model< of a process model”
7002 = “Illegal data in configuration of the functional component >delay< of a process model”
7003 = “Illegal data in configuration of the functional component >shut down drive< of a process model”
7004 = “Illegal data in configuration of the functional component >encoder< of a process model”
7005 = “Illegal data in configuration of the functional component >switch< of a process model”
RemedyChange the configuration data.
Acknowledgment / responsePower On / START TechnologicalFaultTask
Default setting for local responseRELEASE_DISABLE
Programmable local responsesFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
followingAxis
7-402� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
20007 Interconnection error (category: /1/%d, context: /2/%d, context parameter1:/3/%d, context parameter2: /4/%d)
CauseThis alarm indicates errors in the interconnection of technology objects. When theinterconnection is established, the technology object verifies it on the basis of theinterface properties. Errors are classified by category.
Meaning of alarm parameters
Category:
1 – TO compatibility errorAn interconnection is to be established with a technology object that has beenconfigured with another reference system (e.g., output cam with rotaryreference system and linear axis).
2 – Exclusive interfaceMultiple interconnections are to be established for an interface intended forexclusive interconnection.
3 – Interconnection requirementThe technology object is waiting for an interconnection required for thesequence.
4 – Interface initialization errorErrors result from extended initialization sequences at interfaces andparameter exchange between interconnected interfaces.
5 – Interface not available on technology objectAn interface specified in the interconnection is not available on the technologyobject.
6 – CircularityThe interconnection on the technology object leads to circular communicationwithin the technology object (e.g., circular master/slave interconnection ofgearing axes, whereby a gearing axis used as a master is in turn the slave ofanother master, which is assigned the master setpoints generated on thisgearing axis directly or via additional interconnections).
7 – Execution level compatibility errorAn interconnection is to be established with a technology object that isexecuted in another interpolator level (e.g., output cam with IPO and axis withIPO_2).
8 – Distribution initializationWhen interconnecting technology objects that are distributed among differentdevices, an error occurred during initialization of the communication interface.
9 – Illegal TO statusThe technology object cannot be interconnected in the current state.
Context:
The context provides additional information about the error category for the TOinterconnection. Additional parameters can be provided for the error descriptionon a context-specific basis. Context and context parameter are output as aninteger value.
followingAxis
7-403� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
Remedy
1 – Technology object compatibility error: Correct the configuration of the reference system of the technology objects tobe interconnected.
2 – Exclusive interface: Correct the configuration of the interconnected technology object.
3 – Interconnection request: Add the missing interconnection to your technology object.
4 – Error during interface initialization: Contact the hotline.
5 – Interface not available on technology object: Contact the hotline.
6 – Circularity:Remove unnecessary interconnections.
7 – Execution level compatibility error: Correct the configuration of the interpolator task level of the technology objectsto be interconnected.
8 – Distribution initialization:Check the hardware configuration. Ensure that the distributed interactingdevices are linked in the bus configuration. In addition, the address areas thatare used by the devices for communication must be set up. The address areasare automatically set up when the project is compiled; only afterwards is thevalid hardware configuration available for downloading.
9 – Illegal TO status:Correct the configuration of the technology object, correct execution errors.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseRELEASE_DISABLE
Programmable local responsesFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
followingAxis
7-404� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
20008 Cannot assign USER_DEFAULT to system variables
CauseIt is not appropriate to assign USER_DEFAULT to a UserDefault system variable,because the variable references itself in this case.This prevents generation of a useful value during reading out. When this erroroccurs, the new Enum value is not assigned. The variable retains the old value.
RemedyUSER_DEFAULT is designed for use in technology commands.Avoid assigning it to system variables.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONE
20009 The permissible deviation between encoders (/1/%d) and (/2/%d) has beenexceeded
CauseThe permissible deviation between two encoders (slip monitoring) has beenexceeded.
Remedy1. Check the mechanical configuration.2. Check the dimensioning of the dynamic limit values (acceleration, jerk).
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
followingAxis
7-405� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
20010 A restart is necessary to activate the configuration data
CauseThe configuration cannot be set to active, since data have been modified in such away that does not permit it. The technology object must be restarted to activate thedata.
Remedy
� Execute the technology object reset command, and set the activateRestartparameter to ACTIVATE_RESTART.
� Set the restartActivation system variable to ACTIVATE_RESTART.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
followingAxis
7-406� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
20011 Error when activating the configuration (category: /1/%d, error number: /2/%d)
CauseThis note indicates error conditions when activating the configuration. The errorconditions can be traced back to an incorrect or inconsistent configuration. Thetechnology objects perform a plausibility check on the configuration. Errors areidentified by the error codes below.If this information appears, the configuration will not be activated.
Meaning of alarm parameters
Category: Area in which the error occurred.
1–Command decoding
2–Interpolator
3–Controller
4–Manipulated variable output
5–Encoder system
6–Technology object
Error number: Specification of error
1000 = “General configuration error”
2000 = “Error in actuator system configuration”
2001 = “Outside of limits of manipulated variable”
2003 = “Error in load gear ratios”
2004 = “Error in maximum velocity”
2005 = “Maximum velocity greater than maximum attainable velocity”
2006 = “Drive not suitable for torque-controlled or torque-limited operation”
2007 = “Linear stepper motor not implemented”
2008 = “Right-aligned format for direct output not implemented”
2009 = “Illegal value in resolution for direct output”
2010 = “Missing configuration data for actuator system”
2011 = “Missing configuration data for additional actuator system”
2012 = “The backstop range (min to max) does not contain a zero point”
2014 = “Drive or message frame not suitable for torque superimposition”
2015 = “Gear ratios less than or equal to 0”
2016 = “Resolution for stepper motor is 0”
2017 = “Illegal value for the configuration data maxSpeed”
2018 = “Illegal value for the configuration data maxVelocity”
2019 = “Limits of a configuration data exceeded”
2020 = “Limits for the max. acceleration exceeded”
2021 = “Illegal values for dead-zone compensation”
2022 = “Illegal values for sliding-friction compensation”
2023 = “Illegal values for backstop range”
2024 = “Error in sliding-friction compensation parameter”
followingAxis
7-407� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
3000 = “Error in encoder system”
3001 = “Error in encoder system”
3002 = “Invalid axis type selected”
3003 = “Leadscrew pitch is 0”
3004 = “Modulo axis selected with modulo value less than or equal to 0”
3005 = “Illegal specification(s) in the encoder data (incremental / absolute, etc.)”
3006 = “Illegal number of encoders selected”
3007 = “Illegal incremental encoder number”
3008 = “Illegal data combination for homing with incremental encoder”
3009 = “Illegal encoder number”
3010 = “Illegal data on SSI encoder”
3011 = “Illegal encoder number”
3012 = “Illegal encoder number”
3013 = “Illegal measuring gear data, DRIVE assembly type (e.g., factor = 0)”
3014 = “Illegal encoder number”
3015 = “Illegal measuring gear data, LOAD assembly type (e.g., factor = 0)”
3016 = “Illegal data set number (e.g., factor = 0)”
3017 = “Encoder data sequence and number of encoders do not match”
3018 = “Error in encoder system”
3019 = “Illegal encoder number”
3020 = “Illegal encoder system / actuator system simulation selected”
3021 = “Illegal encoder number or incorrect number of data sets”
3022 = “Illegal encoder number or incorrect number of data sets”
3023 = “Illegal data for ratio of external attachment (e.g., factor = 0)”
3024 = “Path/rotation of external attachment = 0”
3025 = “Illegal value for monitoring of actual velocity”
3026 = “Illegal encoder number in SSI encoder configuration”
3027 = “Illegal message format in SSI encoder configuration”
3028 = “Illegal baud rate in SSI encoder configuration”
3029 = “Illegal SSI state in SSI encoder configuration”
3030 = “Illegal encoder number in data set”
3031 = “Encoder number in data set not configured”
3032 = “Illegal numerator factor in data set”
3033 = “Illegal denominator factor in data set”
3034 = “Illegal data set number”
3035 = “Data set number not configured”
3036 = “Encoder not configured”
3037 = “Homing of ENDAT encoder with zero mark not possible”
3038 = “Homing of CAM negative edge onboard not possible”
3039 = “On-the-fly homing of ENDAT encoder with zero mark not possible”
3040 = “On-the-fly homing of CAM negative edge onboard not possible”
followingAxis
7-408� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
3041 = “Factors for adjusting encoder data to the mechanics are outside the permissible range of values”
3042 = “Illegal data combination for homing with external encoder”3043 = “The incremental position of the encoder is outside the permissible
range of values”3044 = “The incremental position of the encoder is outside the permissible
range of values”3045 = “Illegal value for resolution of linear measuring system”3046 = “Illegal value for filter of actual-velocity encoder”3047 = “Illegal value for smoothing of actual-value encoder”3048 = “Illegal value for smoothing of actual-value encoder with actual-value
coupling”3049 = “Illegal DSC encoder selection”3050 = “Configuration of encoder system not completed correctly”3051 = “Error in configuration of the sensor data or the stepper motor”3052 = “Actual-value type (position, interval, velocity) not implemented”3053 = “Only homing with CAM possible for stepper motor”3054 = “Only on-the-fly homing with CAM possible for stepper motor”3055 = “Stepper motor only possible with a real axis”3056 = “Only one encoder permissible with stepper motor”3057 = “DSC encoder is not a DP encoder”3058 = “Illegal message frame of the DSC encoder”3059 = “Modulo value too small”3060 = “Configuration differential measurement position faulty”3061 = “Illegal data in range configuration of the differential measurement position”4000 = “Error in controller”4001 = “Negative acceleration specified”4002 = “Unknown ’FipoType’ requested”4003 = “Error in runtime system, ratio of controller cycle clock to interpolator
cycle clock incorrect”4004 = “Requested filter arrangement not possible”4005 = “Reserve for later use”4006 = “Maximum limit is lower than minimum”4007 = “Reserve for later use”4008 = “Error in configuration data for controller”4009 = “Reserve for later use”4010 = “Reserve for later use”4011 = “Reserve for later use”4012 = “Reserve for later use”4013 = “Requested controller type is not available”4014 = “Error in controller factors”4015 = “Feedforward control activated, kpc < 0 or kpc > 150”4016 = “Reserve for later use”4017 = “Reserve for later use”
followingAxis
7-409� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
4018 = “Reserve for later use”
4019 = “Reserve for later use”
4020 = “Reserve for later use”
4021 = “Reserve for later use”
4022 = “Reserve for later use”
4023 = “Feedforward control activated, kpc <= 0”
4024 = “Model reference monitoring: Error in value of tolerance window”
4025 = “Error in limit value for standstill signal”
4026 = “Error in parameter for positioning monitoring”
4027 = “Reference model and dynamic following error monitoring activated, not possible at the same time”
4028 = “Sampling time parameter calculated incorrectly”
4029 = “Too many data sets requested”
4030 = “Error in runtime system, ratio of controller cycle clock to interpolator cycle clock incorrect”
4031 = “Error in time constant for emergency stop ramp generator (positionTimeConstant)”
4032 = “Feedforward control active, but fine interpolator type is DIRECT”
4033 = “Default data set outside limits”
4034 = “Maximum number of data sets not possible”
4035 = “Unknown data set alternating mode”
4036 = “Following error monitoring not activated/deactivated in all data sets”
4037 = “Model reference monitoring not activated/deactivated in all data sets”
4038 = “Different controller type in data sets”
4039 = “Feedforward control activated/deactivated in data sets”
4040 = “Time constant is 0”
4041 = “Error in dynamic adaptation parameter”
4042 = “System variable initialization could not be read”
4043 = “Driver simulation not implemented”
4044 = “Connection for stepper motors not implemented”
4045 = “Maximum velocity cannot be reached, maximum drive speed or a normalization factor incorrect”
4046 = “DSC requires motor encoder data to be specified”
4047 = “Drive or message frame type not suitable for DSC”
4048 = “Error in clamping monitoring parameter. ’No identifier’ is not permitted for the fixed end stop identifier”
4049 = “Without sensor, monitoring of the actual velocity by ’DynamicControl’ not possible”
4050 = “Inconsistent PROFIBUS parameterization; the sum of Ti and To is greater than one DP clock cycle”
4051 = “Error in manipulated variable limit parameter of force/pressure controller”
4052 = “Error in starting force/pressure monitoring parameter”
followingAxis
7-410� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
4053 = “Error in full-scale force/pressure monitoring parameter”
4054 = “Starting force/pressure monitoring tolerance less than tolerance of full-scale pressure monitoring”
4055 = “Error in force/pressure system deviation monitoring parameter”
4056 = “Different activation/deactivation of the control difference monitoring of the force/pressure controller not permitted in data sets”
4057 = “Different manipulated variable inversion of the force/pressure controller not permitted in data sets”
4058 = “Different force/pressure sensor types not permitted in data sets”
4059 = “Different activation/deactivation of the anti windup not permitted in data sets”
4060 = “Kd factor of the PID_ACTUAL controller is greater than 1”
4061 = “Time constant of the process model T1 <= T2”
4062 = “Illegal actuator type selection”
4063 = “Error in sliding friction compensation parameter”
4064 = “Error in offset application parameter”
4065 = “Feedforward control for force/pressure control not implemented”
4066 = “Error in standstill monitoring parameter”
4067 = “Following error monitoring: minVelocity must not be greater than or equal to maxVelocity”
4068 = “velocityTimeConstant when using a dead-time element for feedforward balancing too great”
4069 = “The system-related dead times are less than 0 after the calculation of additionalTime”
4070 = “Controller types not equal to DIRECT require the configuration of an encoder”
4071 = “Illegal values for delayTimeToActivate of the standstill signal”
4072 = “The IO device for the positive HW limit switch is not available”
4073 = “The IO device for the negative HW limit switch is not available”
4074 = “Limits of a controller parameter exceeded”
4075 = “Limit for emergency-stop-ramp brake delay exceeded”
4076 = “Limit for a substitute time constant exceeded”
4077 = “Limit for velocityTimeConstant exceeded”
4078 = “Error in value for configuration of QFDynamicData”
4079 = “Error in value for model reference monitoring”
4080 = “Error in following error monitoring parameter”
4081 = “Error in clamping monitoring parameter”
4082 = “Error in value for configuration of DynamicData”
4083 = “Error in value for configuration of PV controller”
4084 = “Incomplete configuration data for controller”
4085 = “Error in value for configuration of SystemDeadTimeData”
followingAxis
7-411� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
4086 = “Pressure control only possible with closed speed controller”
4087 = “DSC and compensation of valve characteristic not possible”
4088 = “DSC not possible on hydraulic axes”
4089 = “Time constant of dynamic compensation T1 <= T2”
4090 = “Incorrect value for correction of system dead time”
5000 = “Encoder data sequence and number of encoders do not match”
5001 = “Illegal number of additional sensors selected”
5002 = “Illegal additional sensor type selected”
5003 = “Illegal data in configuration of driver data for additional sensor”
5004 = “Illegal data in configuration of conversion data for additional sensor”
5006 = “Illegal data in configuration of range for additional sensor”
5007 = “Illegal data in configuration of filter time for additional sensor”
5008 = “Configuration of additional sensor not completed correctly”
5009 = “Illegal number for additional sensor in data set”
5010 = “Illegal data in configuration of differential pressure measurement”
5011 = “Error sensor A differential pressure measurement”
5012 = “Error sensor B differential pressure measurement”
5013 = “Illegal data in configuration of extrapolation”
5014 = “Illegal data in configuration of execution task for sensor TO”
5015 = “Illegal data in configuration of substitute value strategy for sensor TO technological alarm”
5020 = “Illegal data in configuration of driver data for analog sensor”
5021 = “Illegal data in configuration of position filter for analog sensor”
5022 = “Illegal data in configuration of conversion data for analog sensor”
5023 = “Illegal data in configuration of measurement input for analog sensor”
5030 = “Illegal data in configuration of conversion data for interval counter”
6000 = “In the configuration data, the monitoring of the positioning path is configured up to the reference-point switch, and the maximum path to be traveled in the process is configured as zero”
6001 = “Error in configuration data numberOfMaxBufferedCommandId”
6002 = “Error in configuration data numberOfQueueCommands”
6003 = “Error in configuration data numberOfImmediateCommands”
6004 = “Configuration of behaviourAtTheEndOfProfile not implemented”
6005 = “Illegal value for the configuration data maximum acceleration”
6006 = “Illegal value for the configuration data maximum jerk”
followingAxis
7-412� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
6007 = “Illegal value for the configuration data maximum force/pressure setpoint”
6008 = “Illegal value for the configuration data maximum force/pressure setpoint rate of rise”
6009 = “Illegal value for the configuration data synchronous operation tolerance on the setpoint side”
6010 = “Illegal value for the configuration data synchronous operation tolerance on the actual-value side”
6011 = “Illegal value for the configuration data enable synchronous operation tolerance on the setpoint side”
6012 = “Illegal value for the configuration data enable synchronous operation tolerance on the actual-value side”
6013 = “Illegal value for the configuration data tolerance window end-of-profile detection”
6014 = “Illegal value for the configuration data extrapolation time actual values”
6015 = “Illegal value for the configuration data tolerance window actual-value coupling”
6016 = “Illegal value for the configuration data touchdown tolerance position limit”
6017 = “Illegal value for the configuration data handling mode position limit”
7000 = “Illegal data in configuration of a process model”
7001 = “Illegal data in configuration of the functional component >drive model< of aprocess model”
7002 = “Illegal data in configuration of the functional component >delay< of a process model”
7003 = “Illegal data in configuration of the functional component >shut down drive<of a process model”
7004 = “Illegal data in configuration of the functional component >encoder< of a process model”
7005 = “Illegal data in configuration of the functional component >switch< of a process model”
RemedyChange the configuration data.
followingAxis
7-413� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
followingAxis
7-414� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
20012 Restart not executed (reason: /1/%d)
CauseTechnology object could not be restarted.
Meaning of alarm parameters
Reason:
1 – The technology object configuration does not allow a restart with the restartsystem variable. You can initiate the restart using the reset command.
2 – The technology object is not ready to be restarted.
3 – A configured condition for restarting the technology object is not met (e.g.,technology object must be disabled).
4 – Restart has not been executed or executed with the last programmedconfiguration of the technology object.
Remedy
� Work around the cause stated in the Reason parameter, or reload the project.
� Use the device diagnostics to establish whether technological alarms werereported and, if necessary, remedy the cause of the alarm.
Acknowledgment / ResponseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
followingAxis
7-415� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
20014 At the logical address: /1/%d (optional log. address: /2/%d and bit no.: /3/%dof the enable output), a driver (type: /4/%d) could not be requested
CauseThe driver of a physical device is not available or is being used by another TO.
Meaning of alarm parameters
Logical address:
This is the address of the actuator driver configured on the technology object.
Logical address and bit number:
This specifies the address and bit number of the output enable bit
Type:
1–Actuator driver
2–Encoder driver
3–BitRead driver
4–BitWrite driver
5–ByteRead driver
6–ByteWrite driver
7–WordRead driver
8–WordWrite driver
9–DWordRead driver
10–DWordWrite driver
Remedy
� Check that the logical device was available at the time of the request or whetherit was being used by another technology object.
� Connect a suitable device.
� Check the device (function, connections, terminals).
� Check the topological configuration in HWConfig.
� Compare configuration of HWConfig and technology object.
� Contact the hotline.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseRELEASE_DISABLE
Programmable local responsesRELEASE_DISABLE
followingAxis
7-416� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
30001 Illegal parameter (parameter index according to standard sequence in thesystem functions: /1/%d, command type: /4/%X)
CauseIllegal system function parameter, the command is aborted. The parameters indicate the position of the illegal system function parameteraccording to the standard sequence in the system functions and the command typeof an incorrectly entered parameter.
Meaning of alarm parameters
Parameter index:
Index of the first system function parameter that triggered this error (listedaccording to the standard sequence in the system functions).
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyChange the parameters.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
followingAxis
7-417� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
30002 Command aborted (reason: /1/%d, command type: /4/%X)
CauseExecution of the command was aborted before or during processing.This condition can arise as a result of loading a new command, resetting thecommand buffer, or an error state.
Meaning of alarm parameters
Reason:
1–Command buffer reset
2–Abort by another command
3–Aborted by a stop
4–Aborted by a higher-order stop
5–Abort by a pending error response
6–Aborted due to ambiguous commandid
7–Delayed acknowledgment
8–No actual value for axis (e.g., encoder or data bus not ready)
9–Aborted due to abnormal termination of a dependent command
10–Aborted due to active synchronous operation
11–Aborted due to active superimposed motion
12–Aborted due to active speed-controlled controller mode
13–Aborted due to active position-controlled controller mode
14–Aborted due to active motion to fixed end stop
15–Axis is not in pressure-limiting operation
16–Aborted due to active pressure-controlled operation
17–Aborted due to inactive pressure-controlled operation
18–Superimposed command is not permitted
19–Aborted due to error during cam access
20–Slave is not ready for operation
21–Error in slave synchronization
22–Aborted by command on slave
23–Aborted by stop on slave
24–Aborted by an active error response on the slave
25–No actual value for slave (e.g., encoder or data bus not ready)
26–Aborted by reset on slave
27–Master values are not valid
28–Active command in recursive TO interconnection
29–Aborted due to error during synchronization
30–Axis is in pressure-limiting operation
31–Maximum number of active commands exceeded
32–Aborted due to active correction command
33–Action only permissible in standstill
Command type:
Outputs the aborted command type. The command type is output as ahexadecimal integer value.
followingAxis
7-418� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
RemedyReset command via program.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
30003 Command aborted due to full command buffer (command type: /4/%X)
CauseThe command is not entered in the command buffer as the buffer is already full.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
Remedy
� Check the program flow.
� Typical cause: The ’nextCommand’ parameter is passed with the valueIMMEDIATELY. You need to synchronize the command sequence manually oruse another value for ’nextCommand’.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
followingAxis
7-419� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
30004 Unknown command (command type: /4/%X)
CauseThe active software tool does not support this command.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyCheck the versions of the engineering system and the runtime software.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
followingAxis
7-420� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
30005 Ambiguous commandId (number of commands with specified ID: /1/%d,command type: /4/%X)
CauseThe specified commandID refers to several commands.The specified action is performed for the command matching the specifiedcommandID that has been in the interpolator for the longest time. If nocorresponding command is found in the interpolator, the action refers to the nextcommand loaded in the interpolator.
Meaning of alarm parameters
Number of commands with specified ID:
Number of commands referenced by the specified commandid.
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyUse different commandIds for commands that are active simultaneously.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
followingAxis
7-421� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
30006 Cannot execute command due to current object state (command type: /4/%X)
CauseThe object is in the stop, error, or reset state and the command is not possible inthis object state.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
Remedy
� Check the object status.
� Check the permissible sequence of commands.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
followingAxis
7-422� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
30007 The error cannot be reset due to its configuration
CauseThe alarm cannot be acknowledged at the present time or by the selected means.
Remedy
� Check the configured acknowledgment procedure.
� If necessary, change the acknowledgment procedure for the alarm.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
followingAxis
7-423� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
30008 A connection to a technology object required for this operation does notexist (command type: /4/%X)
CauseThe object connection required for this operation has not been configured.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyCheck the project configuration, or change the object connection in the command.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
followingAxis
7-424� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
30009 Command rejected due to suspension of command decoding on addressedtechnology object (command type: /4/%X)
CauseCommand was rejected due to suspension of command decoding on theaddressed technology object.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
Remedy
� Check why the command was rejected.
� If necessary, acknowledge any active errors once you have corrected the causeof the error.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
followingAxis
7-425� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
30010 Command not available (command type: /4/%X)
CauseThe command is not available in this version of the runtime software.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyCheck the version of the runtime software.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
followingAxis
7-426� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
30011 Parameter unavailable (parameter index according to standard sequence inthe system functions: /1/%d, command type: /4/%X)
CauseThe parameter is not available in this version of the runtime software, thecommand is therefore rejected. The parameters indicate the position according tothe standard sequence in the system functions and the command type of anincorrectly entered parameter.
Meaning of alarm parameters
Parameter index:
Index of the command parameter triggering this error according to the standardsequence in the system functions.
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyCheck the version of the runtime software.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
followingAxis
7-427� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
30012 Command cannot be started synchronously (command type: /4/%X)
CauseThe command cannot be used during a BEGIN_SYNC, END_SYNC sequencebecause it is a reset command or a command that has only one return value in theuser program.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyDo not use this command type during a BEGIN_SYNC, END_SYNC sequence.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
followingAxis
7-428� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
30013 Synchronous start of the command using IMMEDIATELY mergeMode(command type: /4/%X)
CauseWith synchronous command start, only merge modes that immediately override thecurrent command (IMMEDIATELY) and superimpose the current command(SUPERIMPOSED_MOTION_MERGE) can be used. If an illegal merge mode isprogrammed (e.g., SEQUENTIAL or NEXT_MOTION), the system automaticallychanges the merge mode to IMMEDIATELY and outputs this warning.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyProgram the command, which is to be started synchronously to immediatelyoverride the current command. To do this, enter the value IMMEDIATELY in the’mergeMode’ command parameter.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
followingAxis
7-429� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
30014 Coordinate system not offset due to the internal traversing range limit beingexceeded (Parameter1: /1/% /1/%d, command type: /2/%X)
CauseThe programmed coordinate system offset causes the internal traversing rangelimit to be exceeded. The coordinate system is not shifted.
Meaning of alarm parameters
Parameter1:
= 0 negative internal traversing range limit
= 1 positive internal traversing range limit
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyCheck the programming for the coordinate system offset.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
followingAxis
7-430� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
30015 A technology required for this command was not configured (technology: /1/%d, command type: /4/%X)
CauseThe command cannot be selected in this technology object configuration.
Meaning of alarm parameters
Technology:= 1 Axis with force/pressure control without flow/force specification
= 2 Axis with force/pressure control and flow/force specification
= 3 Axis without flow/force specification
= 4 Axis with flow/force specification
= 5 Axis with force specification
= 6 Axis with pressure setpoint specification
= 7 Axis with pressure limiting
= 8 Axis with speed limiting parallel to force/pressure control
= 9 Axis with flow specification
Command type:Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyActivate the technology needed for the command.Technology:
= 1 Select the mode setting REAL_AXIS_WITH_PRESSURE_CONTROL in theTypeOfAxis configuration data
= 2 Select the mode settingREAL_QP_AXIS_WITH_CLOSED_LOOP_FORCE_CONTROL in theTypeOfAxis configuration data
= 3 Select the mode setting VIRTUAL_AXIS, REAL_AXIS orREAL_AXIS_WITH_FORCE_CONTROL in the TypeOfAxis configuration data
= 4 Select the mode setting EAL_QPAXIS,REAL_QP_AXIS_WITH_OPEN_LOOP_FORCE_CONTROL orREAL_QP_AXIS_WITH_CLOSED_LOOP_FORCE_CONTROL in theTypeOfAxis configuration data
= 5 Select the mode settingREAL_QP_AXIS_WITH_OPEN_LOOP_FORCE_CONTROL in the TypeOfAxisconfiguration data
= 6 Select the mode setting REAL_AXIS_WITH_PRESSURE_CONTROL orREAL_QP_AXIS_WITH_CLOSED_LOOP_FORCE_CONTROL in theTypeOfAxis configuration data
= 7 Select the mode setting REAL_AXIS_WITH_PRESSURE_CONTROL,REAL_QP_AXIS_WITH_OPEN_LOOP_FORCE_CONTROL orREAL_QP_AXIS_WITH_CLOSED_LOOP_FORCE_CONTROL in theTypeOfAxis configuration data
= 8 Select the mode settingREAL_QP_AXIS_WITH_CLOSED_LOOP_FORCE_CONTROL in theTypeOfAxis configuration data
= 9 Select a mode setting with flow specification in the TypeOfAxis configurationdata
followingAxis
7-431� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
40001 Illegal state change on axis
CauseCommand for change of axis state could not be performed, because:1. The operating status phase is not complete.2. The operational transition is not possible.
RemedyFor 1.: Repeat command.For 2.: A reset must be performed first
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
followingAxis
7-432� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
40002 Programmed velocity is limited
Cause1. The system is limiting the programmed velocity to the maximum permissibleparameter.2. For a virtual axis, the velocity is limited to a value that reliably identifies thedirection, that is, the velocity of the axis must not exceed that at which, dependingon the IPO task, at least one measured value can be detected in the range ofone-half modulo length.
RemedyNot necessary, for information only.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
followingAxis
7-433� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
40003 Programmed acceleration (type: /1/%d) is limited
CauseThe system is limiting the programmed acceleration to the maximum limit.
Meaning of alarm parameters
Type:
0 – positive acceleration
1 – negative acceleration/deceleration
RemedyNot necessary, for information only.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
followingAxis
7-434� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
40004 Programmed jerk (type: /1/%d) is limited
CauseThe system is limiting the programmed jerk to the maximum limit.
Meaning of alarm parameters
Type:
0 – Increase in positive acceleration
1 – Reduction in positive acceleration
2 – Increase in negative acceleration/deceleration
3 – Reduction in negative acceleration/deceleration
RemedyNot necessary, for information only.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
followingAxis
7-435� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
40005 Enable signal(s) missing (Parameter1: /1/%X) and/or incorrect mode(Parameter2: /2/%d)
CauseThe enables are missing and/or follow-up mode is active on the axis are missing when a command is pending.
Meaning of alarm parameters
Parameter1:
Bit 1 = 0: POWER enable signal is available1: POWER enable signal is missing
Bit 2 = 0: DRIVE enable signal is available1: DRIVE enable signal is missing
Bit 3 = 0: Position controller enable signal is available1: Position controller enable signal is missing
Bit 4 = 0: Force/pressure controller enable signal is available1: Force/pressure controller enable signal is missing
Parameter2:
0 – Follow-up mode deselected
1 – Follow-up mode selected
RemedyActivate the enable signals before issuing a motion command.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseFEEDBACK_EMERGENCY_STOP
Programmable local responsesFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
followingAxis
7-436� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
40006 Programmed velocity is zero
CauseThe programmed velocity is zero. The specified motion cannot be executed.
RemedyProgram a value not equal to zero. If USER_DEFAULT is referenced, a value notequal to zero must be programmed in the assigned system variable.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseFEEDBACK_EMERGENCY_STOP
Programmable local responsesFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
40007 Programmed acceleration (type: /1/%d) is zero
CauseThe programmed acceleration is zero. The specified motion cannot be executed.
Meaning of alarm parameters
Type:
0 – positive acceleration
1 – negative acceleration/deceleration
RemedyProgram a value not equal to zero. If USER_DEFAULT is referenced, a value notequal to zero must be programmed in the assigned system variable.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseFEEDBACK_EMERGENCY_STOP
Programmable local responsesFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
followingAxis
7-437� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
40008 Programmed jerk (type: /1/%d) is zero
CauseThe programmed jerk is zero. The specified motion cannot be executed.
Meaning of alarm parameters
Type:
0 – Increase in positive acceleration
1 – Reduction in positive acceleration
2 – Increase in negative acceleration/deceleration
3 – Reduction in negative acceleration/deceleration
RemedyProgram a value not equal to zero. If USER_DEFAULT is referenced, a value notequal to zero must be programmed in the assigned system variable.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseFEEDBACK_EMERGENCY_STOP
Programmable local responsesFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
40009 Velocity limit is zero
CauseThe programmed velocity is zero. The specified motion cannot be executed.
RemedyProgram a value not equal to zero in the dynamic limit values.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseFEEDBACK_EMERGENCY_STOP
Programmable local responsesFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
followingAxis
7-438� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
40010 Acceleration limit (type: /1/%d) is zero
CauseThe programmed acceleration limit is zero. The specified motion cannot beexecuted.
Meaning of alarm parameters
Type:
0 – positive acceleration
1 – negative acceleration/deceleration
RemedyProgram a value not equal to zero.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseFEEDBACK_EMERGENCY_STOP
Programmable local responsesFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
40011 Programmed jerk limit (type: /1/%d) is zero
CauseThe programmed jerk is zero. The specified motion cannot be executed.
Meaning of alarm parameters
Type:
0 – Increase in positive acceleration
1 – Reduction in positive acceleration
2 – Increase in negative acceleration/deceleration
3 – Reduction in negative acceleration/deceleration
RemedyProgram a value not equal to zero.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseFEEDBACK_EMERGENCY_STOP
Programmable local responsesFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
followingAxis
7-439� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
40012 Dynamic restrictions (type: /1/%d) violated
CauseThe specified dynamic restrictions have been violated. This can occur due to:
� Programming of new jerk-controlled motions with extremely divergent dynamicparameters, which would lead to an additional reversing motion, reducing thecurrent acceleration.
� Programming of superimposed motions exceeding the resulting dynamicparameters, which would lead to overshoot or to a reversing motion whenrestricted to the maximum velocity or when entering final velocity.
One or more physical variables (velocity, acceleration, jerk) may be affected. The violations have only a temporary effect.
Meaning of alarm parameters
Type:
0 – The jerk is changed; the jerk limit is exceeded.
1 – The jerk limit is disabled during jerk-controlled motion.
2 – The acceleration is changed; the acceleration limit is exceeded.
3 – The acceleration is changed, and the jerk limit is disabled. The accelerationlimit is exceeded.
Remedy
� For new motion: Increase the dynamic response parameters.
� For superimposed motion: Allow for the current (resulting) limitations whenprogramming the dynamic response parameters.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
followingAxis
7-440� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
40013 Programmed stop time restricted by acceleration limits
CauseThe specified stop time cannot be achieved. It is violated due to the maximumacceleration limits. Deceleration is performed with the maximum values.
Remedy
� Increase the programmed time.
� Check the maximum acceleration and the active programmed limits.
� Increase the limits if necessary.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
followingAxis
7-441� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
40014 Command not possible on virtual axis (command type: /4/%X)
CauseThe command is not supported by virtual axes.
RemedyUse a real axis.
Acknowledgment / responseReset fault memory / NONE
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
40015 Error in accessing specified cam
CauseThe specified cam does not exist or is not connected with synchronous operation,or the cam is already active.
Remedy
� Check the programmed cam.
� Check the synchronous operation connection with the cam.
� Check the program sequence.
Acknowledgment / responseReset fault memory / NONE
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
followingAxis
7-442� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
40016 The specified cam has not been interpolated
CauseThe system only accepts verified and interpolated cams for this operation. Thespecified cam has not yet been interpolated.
RemedyCheck whether the specified cam has been interpolated.
Acknowledgment / responseReset fault memory / NONE
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
40017 Cam start point outside definition range
CauseThe addressed cam start point is outside the definition range of the cam.
Remedy
� Check the definition range of the cam.
� Check the cam start point.
Acknowledgment / responseReset fault memory / NONE
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
followingAxis
7-443� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
40018 Dynamic response of motion profiles (type: /1/%d) violated (reason: /2/%d)
CauseThe specified dynamic response cannot be achieved.
Meaning of alarm parameters
Type:
1 – Velocity-time profile
2 – Position-time profile
3 – Velocity-position profile
4 – Velocity-interface position profile
5 – Velocity-time limit profile
6 – Velocity–position limit profile
7 – Velocity-interface position limit profile
Reason:
0 – The velocity resulting form the profile has been limited to the programmedvalue.
1 – The acceleration/deceleration resulting from the profile has been limited to theprogrammed value.
Remedy
� For superimposed motion: Allow for the current (resulting) limitations when programming the dynamicresponse parameters.
� Increase the dynamic response parameters.
Acknowledgment / responseReset fault memory / NONE
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
followingAxis
7-444� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
40019 Error while accessing the motion interface
CauseThe specified reference object for the motion interface does not exist or is notconnected to the axis.
Remedy
� Check the programmed input interconnection.
� Check the program sequence.
Acknowledgment / responseReset fault memory / NONE
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
followingAxis
7-445� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
40020 Dynamic response of the setpoints on the motion interface (type: /1/%d)violated (reason: /2/%d)
CauseThe specified dynamic response cannot be achieved.
Meaning of alarm parameters
Type:
1 – Velocity-based setpoints
2 – Position-based setpoints
Reason:
0 – The velocity resulting form the interface has been limited to the programmedvalue.
1 – The acceleration/deceleration resulting from the interface has been limited tothe programmed value.
Remedy
� For superimposed motion: Allow for the current (resulting) limitations when programming the dynamicresponse parameters.
� Increase the dynamic response parameters.
Acknowledgment / responseReset fault memory / NONE
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
followingAxis
7-446� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
40021 StopEmergency command abort due to a pending stop response of the sameor higher priority
CauseThe StopEmergency command on the axis was aborted when called or while activedue to a stop response of the same or higher priority, resulting from an error.The alarm is generated as an additional aid for emergency stop strategies, andcan for example ensure a safe program sequence by changing the stop response.
Remedy
Acknowledgment / responseReset fault memory / NONE
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
followingAxis
7-447� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
40022 Programmed pressure limiting is limited
CauseThe system is limiting the pressure limiting value to the maximum limit.
RemedyNot necessary, for information only.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
40023 Programmed increase in pressure limiting limited
CauseThe system is limiting the pressure limiting increase to the maximum limit.
RemedyNot necessary, for information only.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
followingAxis
7-448� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
40024 Programmed increase in pressure limiting is zero
CauseThe programmed increase in pressure limiting limit is zero. The specified pressurelimiting characteristic cannot be calculated.
RemedyProgram a value not equal to zero. If USER_DEFAULT is referenced, a value notequal to zero must be programmed in the assigned system variable.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseMOTION_EMERGENCY_ABORT
Programmable local responsesMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
40025 Maximum increase in pressure limiting is zero
CauseThe limit value for the pressure limiting increase is zero. The specified pressurelimiting characteristic cannot be calculated.
RemedyProgram a value not equal to zero in the dynamic limit values.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseMOTION_EMERGENCY_ABORT
Programmable local responsesMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
followingAxis
7-449� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
40026 Dynamic response of pressure/pressure limiting profiles (type: /1/%d)violated (reason: /2/%d)
CauseThe specified dynamic response cannot be achieved.
Meaning of alarm parameters
Type:
1 – Pressure-time limit profile
2 – Pressure-position limit profile
3 – Pressure-interface position limit profile
4 – Pressure-time profile
5 – Pressure-position profile
6 – Pressure-interface position profile
Reason:
0 – The pressure/pressure limiting value resulting from the profile has been limitedto the maximum pressure/pressure limiting value.
1 – The pressure/pressure limiting increase value resulting from the profile hasbeen limited to the maximum pressure/pressure limiting increase value.
Remedy
� Increase the dynamic response parameters.
Acknowledgment / responseReset fault memory / NONE
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
followingAxis
7-450� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
40101 Homing output cam not found
CauseThe homing output cam has not been found because:
� It is outside the permissible range.
� Limit switch monitoring system has responded.
Remedy
� Check the permissible range for homing.
� Check the hardware configuration.
� Check the home position and, if the approach direction is incorrect, change thestart position of the axis for homing.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseMOTION_EMERGENCY_ABORT
Programmable local responsesMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
followingAxis
7-451� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
40102 Encoder zero mark not found during homing
CauseThe encoder zero mark could not be found because:
� The difference between the reference output cam and the encoder zero mark isoutside the permissible range.
� Limit switch monitoring system has responded.
� The reference deceleration velocity is too high.
Remedy
� Check the permissible range.
� Check the hardware configuration.
� Reduce the deceleration velocity.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseFEEDBACK_EMERGENCY_STOP
Programmable local responsesFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
followingAxis
7-452� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
40103 Error in homing configuration data (Parameter1: /1/%d)
CauseThe configured axis data and the selected parameters in the homing command areinconsistent with one another.
Meaning of alarm parameters
Parameter1
1 – ENABLE_OFFSET_OF_ABSOLUTE_ENCODER has been selected in thehoming command but an incremental encoder is configured.
2 – ACTIVE_HOMING or PASSIVE_HOMING has been selected in the homingcommand, but an SSI encoder is configured.
3 – ACTIVE_HOMING has been selected in the homing command, butNO_REFERENCE was configured under homingMode in the configurationdata for the encoder.
4 – ACTIVE_HOMING, PASSIVE_HOMING orENABLE_OFFSET_OF_ABSOLUTE_ENCODER has been selected in thehoming command, but NO_SENSOR was selected under encoderType in theconfiguration data for the encoder.
6 – The homing approach velocity is zero.
7 – The homing entry velocity is zero.
8 – The homing reduced velocity is zero.
RemedyCheck the configuration data and the command parameters for homing
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseFEEDBACK_EMERGENCY_STOP
Programmable local responsesFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
followingAxis
7-453� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
40104 Error in software limit switch specification (Parameter1: /1/%d)
CauseThe software limit switches are programmed incorrectly.
Meaning of alarm parameters
Parameter1:
= 0: Negative switch is greater than positive switch when the axis is not amodulo axis.
= 1: Current set position is not in programmed range. The software limit switchwas deactivated.
RemedyReprogram the software limit switches.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseMOTION_EMERGENCY_STOP
Programmable local responsesMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
followingAxis
7-454� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
40105 Position limited to software limit switch (Parameter1: /1/%d)
CauseThe programmed position has been limited to the software limit switch.
Meaning of alarm parameters
Parameter1:
= 0 negative switch
= 1 positive switch
RemedyCheck the program code for the motion.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseEND_OF_MOTION_STOP
Programmable local responsesEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
40106 Software limit switch (Parameter1: /1/%d) approached
CauseThe software limit switch has been approached during a motion sequence.
Meaning of alarm parameters
Parameter1:
= 0 negative switch
= 1 positive switch
RemedyCheck the program code for the motion.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseMOTION_EMERGENCY_ABORT
Programmable local responsesMOTION_EMERGENCY_ABORTRELEASE_DISABLE
followingAxis
7-455� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
40107 Software limit switch (Parameter1: /1/%d) is crossed
CauseThe software limit switch has been crossed.
Meaning of alarm parameters
Parameter1:
= 0 negative switch
= 1 positive switch
RemedyCheck the program code for the motion.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseRELEASE_DISABLE
Programmable local responsesRELEASE_DISABLE
40108 Axis is not homed
CauseA command requiring a homed axis was passed to an axis that is not homed.
RemedyHome the axis.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseFEEDBACK_EMERGENCY_STOP
Programmable local responsesFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
followingAxis
7-456� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
40109 Error on synchronizing two encoders (reason: /1/%d)
CauseAn attempt to synchronize two encoders has failed. Parameter 1 contains the exact error specification.
Meaning of alarm parameters
Reason:
= 0: The reference encoder is not configured or is defective.
= 1: The encoder to be synchronized is not configured or is defective.
= 2: Function not possible as only one encoder has been configured.
= 3: Illegal correction of the active encoder.
Remedy
� Check the command parameters.
� Configure the encoder.
� Remedy the fault on the encoder.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
followingAxis
7-457� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
40110 Error triggered on slave during synchronous operation (error number: /1/%d)
CauseAn error was triggered on a slave during synchronous operation and reported tothe master.
Meaning of alarm parameters
Error number: Error reported by slave.
1–Synchronous operation setpoint tolerance exceeded.
2–Synchronous operation actual-value tolerance exceeded.
RemedyCheck the configuration data for synchronous operation monitoring on the slave,the programming (dynamic parameters, synchronous operation coupling), and thesystem variables.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseMOTION_EMERGENCY_ABORT
Programmable local responsesMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
40111 Internal traversing range limit (Parameter1: /1/%d) approached
CauseThe internal traversing range limit has been approached during a motion sequence.
Meaning of alarm parameters
Parameter1:
= 0 negative internal traversing range limit
= 1 positive internal traversing range limit
RemedyCheck the program code for the motion.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseMOTION_EMERGENCY_ABORT
Programmable local responsesMOTION_EMERGENCY_ABORTRELEASE_DISABLE
followingAxis
7-458� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
40112 Internal traversing range limit (Parameter1: /1/%d) is crossed
CauseThe internal traversing range limit has been crossed.
Meaning of alarm parameters
Parameter1:
= 0 negative switch
= 1 positive switch
RemedyCheck the program code for the motion.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseRELEASE_DISABLE
Programmable local responsesRELEASE_DISABLE
40120 Programmed pressure is limited
CauseThe system is limiting the programmed pressure to the maximum permissiblepressure.
RemedyNot necessary, for information only.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
followingAxis
7-459� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
40121 Programmed pressure rise is limited
CauseThe system is limiting the programmed pressure rise to the maximum permissiblepressure rise.
RemedyNot necessary, for information only.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
40122 Programmed pressure rise is zero
CauseThe programmed pressure rise is zero. The specified pressure characteristiccannot be calculated.
RemedyProgram a value not equal to zero. If USER_DEFAULT is referenced, a value notequal to zero must be programmed in the assigned system variable.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseMOTION_EMERGENCY_ABORT
Programmable local responsesMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
followingAxis
7-460� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
40123 Maximum pressure rise is zero
CauseThe limit value for the pressure rise is zero. The specified pressure characteristiccannot be calculated.
RemedyProgram a value not equal to zero in the dynamic limit values.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseMOTION_EMERGENCY_ABORT
Programmable local responsesMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
40124 Offset cannot be compensated
CauseThe determined cycle clock offset is greater than the maximum permissiblesetpoint output delay. The offset cannot be compensated completely in the master.
RemedyNot necessary, for information only.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
followingAxis
7-461� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
40125 Setpoint output delay deactivated in the master
CauseThis leading value source operates without setpoint output delay on the masterside.The setpoint output delay on the master side has been activated on at least oneinterconnected following axis. The synchronous operation relationship between theleading value source and the following axis is not operating synchronously.
RemedyActivate the setpoint output delay for the master setpoint source in the master.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
followingAxis
7-462� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
40201 Synchronous operation tolerance exceeded on gearing axis (activemonitoring system: /1/%d)
CauseThe configured synchronous operation tolerance was exceededobserving the dynamic limit values.
Meaning of alarm parameters
Active monitoring:Indicates which synchronous operation monitoring system is active.
1–Setpoint monitoring
2–Actual-value monitoring
RemedyCheck the dynamic conditions for synchronous operation. This involves:
� checking the synchronous operation coupling, ratios, and cam mechanism
� checking the dynamic parameters for synchronization and desynchronization
� checking the configured units and the internal representation accuracy. Increasethe configured tolerance.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseMOTION_EMERGENCY_ABORT
Programmable local responsesNONEMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
followingAxis
7-463� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
40202 Dynamic response of synchronous operation setpoints (type: /1/%d) violated(reason: /2/%d)
CauseThe specified dynamic response cannot be achieved.
Meaning of alarm parameters
Type:
1 – Synchronous operation position
2 – Synchronous operation velocity
Reason:
0 – The resulting synchronous operation velocity setpoint has been reduced to thecurrent valid limit.
1 – The resulting synchronous operation acceleration setpoint has been reduced tothe current valid limit.
Remedy
� For superimposed motion: Allow for the current (resulting) limitations whenprogramming the dynamic response parameters.
� Increase the dynamic response parameters.
Acknowledgment / responseReset fault memory / NONE
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
followingAxis
7-464� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
40301 Connection with slave failed (assignment: /1/%d)
CauseThe connection with an interconnected slave has failed. The slave is located on adistributed controller or has been assigned to a different execution level than themaster. Leading values of the master cannot be communicated to the slave for theduration of the connection failure. During the communication malfunction, asynchronous operation monitoring response on the slave cannot be communicatedto the master.
Meaning of alarm parameters
Assignment 1: The failed slave is located on an assigned controller.
Assignment 2: The failed slave has been assigned to a different execution levelthan the master.
Remedy
� Check that the assigned controller is activated, the slave is configured asdistributed, and communication is permitted by the operating mode of theassociated controller (assignment 1).
� Check the connection for mechanical damage, equivalence of configurednetwork topology, firm contact by the plug connector, and, if necessary, correctelectrical cable terminations (assignment 1).
� Check that the failed slave was not being reloaded at the time the error wasdetected (assignment 1 and 2).
� Check whether an overflow was diagnosed for the execution level of theassigned slave (assignment 2).
� Monitoring of the connection is set in the technology object configuration. Themaster and slave must have the same settings selected (assignment 1 and 2).
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
followingAxis
7-465� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
40302 Sign-of-life monitoring for the slave in distributed synchronous operation isdeactivated
CauseSign-of-life monitoring for the slave connection on an assigned controller has beendeactivated. Monitoring is configured differently on the master and slave. As aresult, the connection is established without sign-of-life monitoring.
CauseUse identical configuration settings in the master and slave for sign-of-lifemonitoring of the connection
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
followingAxis
7-466� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
40303 Local and slave interpolation cycle clock are different
CauseThe master and slave must have a common interpolation cycle clock for distributedsynchronous operation. However, when establishing the connection betweentechnology objects, different cycle clock settings were defined for interpolation.
RemedyUse identical cycle clock settings in the master and slave for interpolation.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
followingAxis
7-467� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
40304 Offset cannot be determined
CauseThe offset for the slave cannot be determined. This can be caused by configuringthe PROFIBUS-DP without equidistance or a ratio of interpolator cycle clock toPROFIBUS-DP cycle clock greater than 64.
Remedy
� Select equidistant mode on the PROFIBUS-DP.
� Select a suitable IPO / DP cycle clock ratio setting.
� Deactivate offset compensation on the technology objects involved. Deactivate compensation only if other remedies do not eliminate themalfunction. Deactivating the offset compensation limits the accuracy of motioncontrol.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
50001 Drive failure
CauseDrive fault.
RemedyCheck the configuration of the drive system, the cabling, and the power supply.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseRELEASE_DISABLE
Programmable local responsesRELEASE_DISABLE
followingAxis
7-468� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
50002 Limiting frequency of measuring system exceeded
CauseThe limiting frequency of the encoder has been exceeded.
Remedy
� Check the encoder connection.
� Check the maximum velocity limits in the configuration data.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
followingAxis
7-469� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
50003 Speed acceleration setpoint limitation active
CauseThe speed acceleration setpoint is limited.
Remedy
� Check the mechanical configuration.
� Check the encoder connection.
� Check the configuration of the speed setpoint interface.
� Check the maximum permissible acceleration rates in the configuration data.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
followingAxis
7-470� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
50005 Speed setpoint monitoring active (Parameter1: /1/%d)
CauseThe speed setpoint is limited.
Remedy
� Check the mechanical configuration.
� Check the encoder connection.
� Check the configuration of the speed setpoint interface.
� Check the maximum permissible velocities in the configuration data.
Parameter 1: Specification of limitation1–Limitation of the velocity-related definition range (on hydraulic axes beforethe cam) reached.2–Limitation of the value range (hydraulic axes only) reached.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
followingAxis
7-471� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
50006 Zero mark monitoring
CauseThe zero mark monitoring system has responded.
Remedy
� Check the mechanical configuration and the encoder configuration.
� Check the encoder error messages.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseOPEN_POSITION_CONTROL
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
followingAxis
7-472� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
50007 Hardware limit switch (Parameter1: /1/%d, Parameter2: /2/%d)
CauseHardware limit switch has been violated.
Meaning of alarm parameters
Parameter1:
1: Limit switch reached
2: Polarity reversal on limit switch (can only be deleted by reconfiguring thetechnology object or Power On)
3: Illegal retraction direction
4: Both limit switches are active
Parameter2:
0: Not relevant
1: Limit switch in positive traversing direction
2: Limit switch in negative traversing direction
Remedy
� Check the mechanical configuration.
� Check the limit switches.
� If an error has occurred in the program, change the program or use the softwarelimit switches.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseRELEASE_DISABLE
Programmable local responsesFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
followingAxis
7-473� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
50008 Timeout waiting for standstill signal
CauseTimeout occurred while waiting for standstill signal.
Remedy
� Check the configuration of ’Axis.TypeOfAxis.StandStillSignal’.
� Check that the control loop is operating correctly.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseRELEASE_DISABLE
Programmable local responsesOPEN_POSITION_CONTROLRELEASE_DISABLE
50009 Limit switch active: (Parameter1: /1/%d) only one traversing directionpossible
CauseA positive (Parameter1 = 1) or negative (Parameter1 = 2) hardware limit switch isactive or has been crossed. Motion is possible in the positive or negative traversing direction only.
Remedy
� Check the mechanical configuration.
� Check the limit switches.
� If an error has occurred in the program, change the program or use the softwarelimit switches.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONE
followingAxis
7-474� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
50010 Error while reading or writing data set (category: /1/%d, error number: /2/%d)
CauseAn error occurred while reading or writing.
Meaning of alarm parameters
Category: Area in which the error occurred.
1–Command decoding
2–Interpolator
3–Controller
4–Manipulated variable output
5–Encoder system
Error number: Specification of error1000 = “General configuration error”2000 = “Error in actuator system configuration”2001 = “Outside of limits of manipulated variable”2003 = “Error in load gear ratios”2004 = “Error in maximum velocity”2005 = “Maximum velocity greater than maximum attainable velocity”2006 = “Drive not suitable for torque-controlled or torque-limited operation”2007 = “Linear stepper motor not implemented”2008 = “Right-aligned format for direct output not implemented”2009 = “Illegal value in resolution for direct output”2010 = “Missing configuration data for actuator system”2011 = “Missing configuration data for additional actuator system”2012 = “The backstop range (min to max) does not contain a zero point”2014 = “Drive or message frame not suitable for torque superimposition”2015 = “Gear ratios less than or equal to 0”2016 = “Resolution for stepper motor is 0”2017 = “Illegal value for the configuration data maxSpeed”2018 = “Illegal value for the configuration data maxVelocity”2019 = “Limits of a configuration data exceeded”2020 = “Limits for the max. acceleration exceeded”2021 = “Illegal values for dead-zone compensation”2022 = “Illegal values for sliding-friction compensation”2023 = “Illegal values for backstop range”2024 = “Error in sliding-friction compensation parameter”3000 = “Error in encoder system”3001 = “Error in encoder system”3002 = “Invalid axis type selected”3003 = “Leadscrew pitch is 0”3004 = “Modulo axis selected with modulo value less than or equal to 0”
followingAxis
7-475� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
3005 = “Illegal specification(s) in the encoder data (incremental / absolute, etc.)”
3006 = “Illegal number of encoders selected”
3007 = “Illegal incremental encoder number”
3008 = “Illegal data combination for homing with incremental encoder”
3009 = “Illegal encoder number”
3010 = “Illegal data on SSI encoder”
3011 = “Illegal encoder number”
3012 = “Illegal encoder number”
3013 = “Illegal measuring gear data, DRIVE assembly type (e.g., factor = 0)”
3014 = “Illegal encoder number”
3015 = “Illegal measuring gear data, LOAD assembly type (e.g., factor = 0)”
3016 = “Illegal data set number (e.g., factor = 0)”
3017 = “Encoder data sequence and number of encoders do not match”
3018 = “Error in encoder system”
3019 = “Illegal encoder number”
3020 = “Illegal encoder system / actuator system simulation selected”
3021 = “Illegal encoder number or incorrect number of data sets”
3022 = “Illegal encoder number or incorrect number of data sets”
3023 = “Illegal data for ratio of external attachment (e.g., factor = 0)”
3024 = “Path/rotation of external attachment = 0”
3025 = “Illegal value for monitoring of actual velocity”
3026 = “Illegal encoder number in SSI encoder configuration”
3027 = “Illegal message format in SSI encoder configuration”
3028 = “Illegal baud rate in SSI encoder configuration”
3029 = “Illegal SSI state in SSI encoder configuration”
3030 = “Illegal encoder number in data set”
3031 = “Encoder number in data set not configured”
3032 = “Illegal numerator factor in data set”
3033 = “Illegal denominator factor in data set”
3034 = “Illegal data set number”
3035 = “Data set number not configured”
3036 = “Encoder not configured”
3037 = “Homing of ENDAT encoder with zero mark not possible”
3038 = “Homing of CAM negative edge onboard not possible”
3039 = “On-the-fly homing of ENDAT encoder with zero mark not possible”
3040 = “On-the-fly homing of CAM negative edge onboard not possible”
3041 = “Factors for adjusting encoder data to the mechanics are outside the permissible range of values”
3042 = “Illegal data combination for homing with external encoder”
3043 = “The incremental position of the encoder is outside the permissible range of values”
followingAxis
7-476� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
3044 = “The incremental position of the encoder is outside the permissible range of values”
3045 = “Illegal value for resolution of linear measuring system”3046 = “Illegal value for filter of actual-velocity encoder”3047 = “Illegal value for smoothing of actual-value encoder”3048 = “Illegal value for smoothing of actual-value encoder with actual-value
coupling”3049 = “Illegal DSC encoder selection”3050 = “Configuration of encoder system not completed correctly”3051 = “Error in configuration of the sensor data or the stepper motor”3052 = “Actual-value type (position, interval, velocity) not implemented”3053 = “Only homing with CAM possible for stepper motor”3054 = “Only on-the-fly homing with CAM possible for stepper motor”3055 = “Stepper motor only possible with a real axis”3056 = “Only one encoder permissible with stepper motor”3057 = “DSC encoder is not a DP encoder”3058 = “Illegal message frame of the DSC encoder”3059 = “Modulo value too small”3060 = “Configuration differential measurement position faulty”3061 = “Illegal data in range configuration of the differential measurement position”4000 = “Error in controller”4001 = “Negative acceleration specified”4002 = “Unknown ’FipoType’ requested”4003 = “Error in runtime system, ratio of controller cycle clock to interpolator
cycle clock incorrect”4004 = “Requested filter arrangement not possible”4005 = “Reserve for later use”4006 = “Maximum limit is lower than minimum”4007 = “Reserve for later use”4008 = “Error in configuration data for controller”4009 = “Reserve for later use”4010 = “Reserve for later use”4011 = “Reserve for later use”4012 = “Reserve for later use”4013 = “Requested controller type is not available”4014 = “Error in controller factors”4015 = “Feedforward control activated, kpc < 0 or kpc > 150”4016 = “Reserve for later use”4017 = “Reserve for later use”4018 = “Reserve for later use”4019 = “Reserve for later use”4020 = “Reserve for later use”4021 = “Reserve for later use”4022 = “Reserve for later use”
followingAxis
7-477� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
4023 = “Feedforward control activated, kpc <= 0”
4024 = “Model reference monitoring: Error in value of tolerance window”
4025 = “Error in limit value for standstill signal”
4026 = “Error in parameter for positioning monitoring”
4027 = “Reference model and dynamic following error monitoring activated, not possible at the same time”
4028 = “Sampling time parameter calculated incorrectly”
4029 = “Too many data sets requested”
4030 = “Error in runtime system, ratio of controller cycle clock to interpolator cycle clock incorrect”
4031 = “Error in time constant for emergency stop ramp generator (positionTimeConstant)”
4032 = “Feedforward control active, but fine interpolator type is DIRECT”
4033 = “Default data set outside limits”
4034 = “Maximum number of data sets not possible”
4035 = “Unknown data set alternating mode”
4036 = “Following error monitoring not activated/deactivated in all data sets”
4037 = “Model reference monitoring not activated/deactivated in all data sets”
4038 = “Different controller type in data sets”
4039 = “Feedforward control activated/deactivated in data sets”
4040 = “Time constant is 0”
4041 = “Error in dynamic adaptation parameter”
4042 = “System variable initialization could not be read”
4043 = “Driver simulation not implemented”
4044 = “Connection for stepper motors not implemented”
4045 = “Maximum velocity cannot be reached, maximum drive speed or a normalization factor incorrect”
4046 = “DSC requires motor encoder data to be specified”
4047 = “Drive or message frame type not suitable for DSC”
4048 = “Error in clamping monitoring parameter” ’No identifier’ is not permitted for the fixed end stop identifier.
4049 = “Without sensor, monitoring of the actual velocity by ’DynamicControl’ not possible”
4050 = “Inconsistent PROFIBUS parameterization; the sum of Ti and To is greater than one DP clock cycle”
4051 = “Error in manipulated variable limit parameter of force/pressure controller”
4052 = “Error in starting force/pressure monitoring parameter”
4053 = “Error in full-scale force/pressure monitoring parameter”
4054 = “Starting force/pressure monitoring tolerance less than tolerance of full-scale pressure monitoring”
4055 = “Error in force/pressure system deviation monitoring parameter”
followingAxis
7-478� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
4056 = “Different activation/deactivation of the control difference monitoring of the force/pressure controller not permitted in data sets”
4057 = “Different manipulated variable inversion of the force/pressure controller not permitted in data sets”
4058 = “Different force/pressure sensor types not permitted in data sets”
4059 = “Different activation/deactivation of the anti windup not permitted in data sets”
4060 = “Kd factor of the PID_ACTUAL controller is greater than 1”
4061 = “Time constant of the process model T1 <= T2”
4062 = “Illegal actuator type selection”
4063 = “Error in sliding friction compensation parameter”
4064 = “Error in offset application parameter”
4065 = “Feedforward control for force/pressure control not implemented”
4066 = “Error in standstill monitoring parameter”
4067 = “Following error monitoring: minVelocity must not be greater than or equal to maxVelocity”
4068 = “velocityTimeConstant when using a dead-time element for feedforward balancing too great”
4069 = “The system-related dead times are less than 0 after the calculation of additionalTime”
4070 = “Controller types not equal to DIRECT require the configuration of an encoder”
4071 = “Illegal values for delayTimeToActivate of the standstill signal”
4072 = “The IO device for the positive HW limit switch is not available”
4073 = “The IO device for the negative HW limit switch is not available”
4074 = “Limits of a controller parameter exceeded”
4075 = “Limit for emergency-stop-ramp brake delay exceeded”
4076 = “Limit for a substitute time constant exceeded”
4077 = “Limit for velocityTimeConstant exceeded”
4078 = “Error in value for configuration of QFDynamicData”
4079 = “Error in value for model reference monitoring”
4080 = “Error in following error monitoring parameter”
4081 = “Error in clamping monitoring parameter”
4082 = “Error in value for configuration of DynamicData”
4083 = “Error in value for configuration of PV controller”
4084 = “Incomplete configuration data for controller”
4085 = “Error in value for configuration of SystemDeadTimeData”
4086 = “Pressure control only possible with closed speed controller”
4087 = “DSC and compensation of valve characteristic not possible”
4088 = “DSC not possible on hydraulic axes”
4089 = “Time constant of dynamic compensation T1 <= T2”
followingAxis
7-479� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
4090 = “Incorrect value for correction of system dead time”
5000 = “Encoder data sequence and number of encoders do not match”
5001 = “Illegal number of additional sensors selected”
5002 = “Illegal additional sensor type selected”
5003 = “Illegal data in configuration of driver data for additional sensor”
5004 = “Illegal data in configuration of conversion data for additional sensor”
5006 = “Illegal data in configuration of range for additional sensor”
5007 = “Illegal data in configuration of filter time for additional sensor”
5008 = “Configuration of additional encoder not completed correctly”
5009 = “Illegal number for additional sensor in data set”
5010 = “Illegal data in configuration of differential pressure measurement”
5011 = “Error sensor A differential pressure measurement”
5012 = “Error sensor B differential pressure measurement”
5013 = “Illegal data in configuration of extrapolation”
5014 = “Illegal data in configuration of execution task for sensor TO”
5015 = “Illegal data in configuration of substitute value strategy for sensor TO technological alarm”
5020 = “Illegal data in configuration of driver data for analog sensor”
5021 = “Illegal data in configuration of position filter for analog sensor”
5022 = “Illegal data in configuration of conversion data for analog sensor”
5023 = “Illegal data in configuration of measurement input for analog sensor”
5030 = “Illegal data in configuration of conversion data for interval counter”
6000 = “In the configuration data, the monitoring of the positioning path is configured up to the reference-point switch, and the maximum path to betraveled in the process is configured as zero”
6001 = “Error in configuration data numberOfMaxBufferedCommandId”
6002 = “Error in configuration data numberOfQueueCommands”
6003 = “Error in configuration data numberOfImmediateCommands”
6004 = “Configuration of behaviourAtTheEndOfProfile not implemented”
6005 = “Illegal value for the configuration data maximum acceleration”
6006 = “Illegal value for the configuration data maximum jerk”
6007 = “Illegal value for the configuration data maximum force/pressure setpoint”
6008 = “Illegal value for the configuration data maximum force/pressure setpoint rate of rise”
followingAxis
7-480� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
6009 = “Illegal value for the configuration data synchronous operation tolerance on the setpoint side”
6010 = “Illegal value for the configuration data synchronous operation tolerance on the actual-value side”
6011 = “Illegal value for the configuration data enable synchronous operation tolerance on the setpoint side”
6012 = “Illegal value for the configuration data enable synchronous operation tolerance on the actual-value side”
6013 = “Illegal value for the configuration data tolerance window end-of-profile detection”
6014 = “Illegal value for the configuration data extrapolation time actual values”
6015 = “Illegal value for the configuration data tolerance window actual-value coupling”
6016 = “Illegal value for the configuration data touchdown tolerance position limit”
6017 = “Illegal value for the configuration data handling mode position limit”
7000 = “Illegal data in configuration of a process model”
7001 = “Illegal data in configuration of the functional component >drive model< of aprocess model”
7002 = “Illegal data in configuration of the functional component >delay< of a process model”
7003 = “Illegal data in configuration of the functional component >shut down drive<of a process model”
7004 = “Illegal data in configuration of the functional component >encoder< of a process model”
7005 = “Illegal data in configuration of the functional component >switch< of a process model”
8000 = “General error when reading or writing data set”
8001 = “The selected data set number is not available”
8002 = “Cannot write the active data set”
8003 = “Changing the controller structure (by writing a data set) is not possible”
Remedy
Change data record parameter.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
followingAxis
7-481� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
50011 Limit range of the incremental actual value exceeded (Parameter1: /1/%d)
CauseThe limit range of the incremental actual value has been exceeded.
Meaning of alarm parameters
Parameter1:
1: Range exceeded in positive direction
2: Range exceeded in negative direction
4: The modified actual position is greater than the modulo length in one positioncontrol cycle clock.
Remedy
Check and adjust the configuration data used for adjusting the actual value to themechanics.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseRELEASE_DISABLE
Programmable local responsesRELEASE_DISABLE
followingAxis
7-482� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
50012 Drive does not support the selected function (Parameter1: /1/%d)
CauseError in selected function.
Meaning of alarm parameters
Parameter1:
1: The travel to home position function cannot be performed.
Remedy
Check and adjust the configuration data and the drive settings.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseRELEASE_DISABLE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
followingAxis
7-483� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
50013 Overshoot/undershoot of permissible range limits (logical address: /1/%d,reason: /2/%d)
CauseRange violation for additional sensor.
Meaning of alarm parameters
Logical address: Address configured on the technology object.
Reason:
1: Value greater than maximum permissible value.
2: Value smaller than minimum permissible value.
3: Positive overflow of sensor range.
4: Negative overflow of sensor range.
5: Error in accessing hardware address.
Remedy
� Check and adjust the configuration data.
� Check the sensor connection.
� Check the wiring.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseRELEASE_DISABLE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
followingAxis
7-484� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
50014 Permissible system deviation of pressure controller exceeded
CausePermissible system deviation of pressure controller exceeded.
RemedyCheck for correct functioning of the pressure control loop.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseRELEASE_DISABLE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
50015 Level overflow of IPO not detected
CauseThe system could not intercept a level overflow.
RemedyPlease contact Siemens Support with the error number indicated above.
Acknowledgment / responsePower On / STOP
Default setting for local responseRELEASE_DISABLE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
followingAxis
7-485� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
50016 Backstop limitation active
CauseThe speed setpoint is limited by the backstop.
Remedy
� Check the mechanical configuration.
� Check the encoder connection.
� Check the configuration of the speed setpoint interface.
� Check the maximum permissible backstop values in the configuration data.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
followingAxis
7-486� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
50017 Manipulated variable monitoring active at Q/F output (Parameter1: /1/%d)
CauseThe manipulated variable is limited.
Remedy
� Check the configuration of the valve characteristic.
� Check the maximum permissible velocity or the maximum permissible force/pressure setpoint in the configuration data.
� Check the encoder connection.
� Check the configuration of the setpoint interface.
Parameter 1: Specification of limiting1–Monitoring active at Q output.2–Monitoring active at F output.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
followingAxis
7-487� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
50101 Reference model monitoring window exceeded
CauseThe dynamic demands on the control loop are too high.
Remedy
� Check the encoder count direction.
� Check the control loop parameter assignment.
� Change the parameter assignment for following error monitoring.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseRELEASE_DISABLE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
followingAxis
7-488� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
50102 Dynamic following error monitoring window exceeded
CauseThe dynamic demands on the control loop are too high, or the control system isoverloaded.
Remedy
� Check the encoder count direction.
� Check the control loop parameter assignment.
� Change the parameter assignment for following error monitoring.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseRELEASE_DISABLE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
followingAxis
7-489� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
50103 Warning limits of dynamic following error monitoring reached
CauseThe dynamic demands on the control loop are too high or the control system isoverloaded, the warning stage has been reached.
Remedy
� Check the encoder count direction.
� Check the control loop parameter assignment.
� Change the parameter assignment for following error monitoring.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
followingAxis
7-490� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
50106 Positioning monitoring error
CauseThe axis could not reach the positioning window in the specified time.
Remedy
� Check the control loop parameter assignment.
� Check the parameter assignment for positioning monitoring.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseRELEASE_DISABLE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
50107 Standstill monitoring error
CauseThe axis has left the standstill window or could not reach the standstill window inthe specified time.
Remedy
� Check that the control loop is operating correctly.
� Check the parameter assignment for standstill monitoring.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseRELEASE_DISABLE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
followingAxis
7-491� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
50108 Clamping monitoring error
CauseThe axis has exited the clamping tolerance window.
Remedy
� Check the mechanical end stop.
� Check that the control loop is operating correctly.
� Check the parameter assignment for clamping monitoring.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseRELEASE_DISABLE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
50109 Starting force window monitoring error
CauseThe axis could not reach the starting force window in the specified time.
Remedy
� Check the control loop parameter assignment.
� Check the parameter assignment for monitoring.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseFEEDBACK_EMERGENCY_STOP
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
followingAxis
7-492� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
50110 Full-scale force monitoring error
CauseThe axis has left the full-scale force window or could not reach the window in thespecified time.
Remedy
� Check that the control loop is operating correctly.
� Check the parameter assignment for monitoring.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseFEEDBACK_EMERGENCY_STOP
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
50111 Pressure controller is operating at the limit
CauseThe manipulated variable required by the force controller cannot be implementedand is limited.
Remedy
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPEND_OF_MOTION_STOPMOTION_STOPMOTION_EMERGENCY_STOPMOTION_EMERGENCY_ABORTFEEDBACK_EMERGENCY_STOPOPEN_POSITION_CONTROLRELEASE_DISABLE
8-493� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
followingObjectType
Possible local responses
NONENo response
DECODE_STOPAbort command processing
FOLLOWING_OBJECT_DISABLEStop and abort all commands.
20001 Internal error (Parameter1: /1/%d, Parameter2: /2/%d, Parameter3: /3/%d,Parameter4: /4/%d)
CauseThis alarm indicates internal error states providing information about the cause andlocation of the error in association with the related error number.
Meaning of alarm parameters
Parameter1: Error source
Parameter2 to 4: Error number
RemedyA detailed description of the system error alarm is not provided. Should a systemerror of this type occur, note the alarm number, the alarm text, and the internalsystem error number specified in the alarm and contact: SIEMENS AG A&D MC, Hotline.
Acknowledgment / responsePower On / STOP
Default setting for local responseFOLLOWING_OBJECT_DISABLE
Programmable local responsesFOLLOWING_OBJECT_DISABLE
8
followingObjectType
8-494� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
20002 Insufficient memory (Parameter1: /1/%d, Parameter2: /2/%d, Parameter3:/3/%d, Parameter4: /4/%d)
CauseThe memory required by the system is no longer available. This alarm can occurboth during power up and after program calls.
Meaning of alarm parameters
Parameter1: Area in which the error occurred.
1–Command decoding
2–Interpolator
3–Controller
4–Manipulated variable output
5–Encoder system
6–Technology package
Parameters 2 to 4 are area-specific. They are not fully utilized by all areas.
Command decoding area:
Parameter2 and Parameter4 refer to the command in which the error occurred.
Parameter2: Command return value
Parameter4: Command type
Remedy
� Reduce the size of the ST code.
� Reduce the number of technology objects.
� Reduce the number of interpolation points for cams, if present.
Acknowledgment / responsePower On / STOP
Default setting for local responseFOLLOWING_OBJECT_DISABLE
Programmable local responsesFOLLOWING_OBJECT_DISABLE
followingObjectType
8-495� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
20003 No object configuration (Parameter1: /1/%d, Parameter2: /2/%d, Parameter3:/3/%d, Parameter4: /4/%d)
CauseError in system configuration. The configuration data for a software tool could notbe found.
Meaning of alarm parameters
Parameter1: Area in which the error occurred.
1–Command decoding
2–Interpolator
3–Controller
4–Manipulated variable output
5–Encoder system
Parameters 2 to 4 are area-specific. They are not fully utilized by all areas.
Command decoding area:
Parameter2 and Parameter4 refer to the command in which the error occurred.
Parameter2: Command return value
Parameter4: Command type
RemedyCheck the accuracy of the configuration data in your project. When commands arecalled on technology objects, the technology objects must be configured.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPFOLLOWING_OBJECT_DISABLE
followingObjectType
8-496� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
20004 At the logical address: /1/%d (bit number, if required: /2/%d) a driver (type:/3/%d) could be requested (error number: /4/%d)
CauseThe driver of a physical device or the device itself is not available.
Meaning of alarm parameters
Logical address:
This is the address configured on the technology object.
Bit number:
For bit driver only; bit number
Type:
1–Actuator driver
2–Encoder driver
3–BitRead driver
4–BitWrite driver
5–ByteRead driver
6–ByteWrite driver
7–WordRead driver
8–WordWrite driver
9–DWordRead driver
10–DWordWrite driver
Error number: Specification of error
Not relevant
Remedy
� Connect a suitable device.
� Check the device (function, connections, terminals).
� Check the topological configuration in HWConfig.
� Compare configuration of HWConfig and technology object.
� Contact the hotline.
Acknowledgment / responsePower On / START TechnologicalFaultTask
Default setting for local responseFOLLOWING_OBJECT_DISABLE
Programmable local responsesFOLLOWING_OBJECT_DISABLE
followingObjectType
8-497� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
20005 Device type: /3/%d, log. address: /1/%d faulty. (Bit: /2/%d, reason: 0x/4/%Xh)
CauseThe driver of a physical device or the device itself has failed or is faulty. When thisalarm occurs, the error cause must be evaluated in the external device (drive orencoder).
Meaning of alarm parameters
Type:
1–Actuator driver
2–Encoder driver
3–BitRead driver
4–BitWrite driver
5–ByteRead driver
6–ByteWrite driver
7–WordRead driver
8–WordWrite driver
9–DWordRead driver
10–DWordWrite driver
Logical address:This is the address configured on the technology object.
Bit number:For bit driver type = 3 or 4 only; bit number
Reason:0–Not defined (e.g., for binary I/O)
� Type = 1
0x0001h: Fault message from drive (note: On PROFIBUS drives, which support acyclic communication in accordance with PROFIdrive V3, the error number/numbers of the drives is/are displayed in thediagnostic buffer, e.g., on Masterdrives MC).
0x0002h: DP: Drive signal “control requested” failed
0x0004h: DP: Drive switched off itself
0x0008h: Slot for drive data is not available in the project
0x0010h: Actuator driver does not have a connection to the drive data
0x0020h: Actuator driver was not initialized during power up
0x0080h: DP: Difference between configuration data and drive parameters
0x4000h: DP: Drive on bus failed (station failure)
0x8000h: Sign of life of drive faulty or failed
followingObjectType
8-498� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
� Type = 2
0x0000h: The number of permissible changes in the actual value of the maximum velocity of the absolute-value encoder has beenexceeded.
0x0001h: Fault message from encoder (note: The error number/numbers is/are displayed in the diagnosticbuffer).
0x0002h: General hardware error of encoder
0x0004h: Encoder contaminated
0x0008h: Slot for encoder data is not available in the project
0x0010h: Encoder driver does not have a connection to the encoder data
0x0020h: Encoder driver was not initialized during power up
0x0040h: Error when reading the absolute value of the encoder
0x0080h: DP: Difference between the configuration data and the encoder parameters
0x0100h: Zero mark monitoring of encoder
0x4000h: DP: Encoder on bus failed (station failure)
0x8000h: DP: Sign of life of encoder has malfunctioned or failed. (Note: For an encoder whose data are transferred in a drive message together with actuator data, the actuator sign of life applies for the encoder, e.g., a standard message 3 in accordance with PROFIdrive).
� Type = 3 to 10
0x0000h: Additional information, not assigned
Note:Codings for the reason of the failure can also occur in combination. Theindividual codings are then added to form a coding sum, which is displayed(e.g., 0x0005 = 0x0001 + 0x0004). A reason for failure marked as DP can only be present on PROFIBUS devices.
RemedyCheck the device with respect to function and connections (reason 0x0001,0x0002, 0x0004, 0x4000, 0x8000).
� Check the topological configuration in HW Config (with reason 0x0008).
� For PROFIBUS drives or encoders, compare the configuration of HWConfig, thetechnology object, and the drive parameter assignment.For:
Reason 0x0040:
– Compare the encoder type in the drive or encoder parameter P979 with theconfiguration data of the technology object.
followingObjectType
8-499� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
Reason 0x0080:
– Compare the message frame type in the drive or encoder parameter P922with HW Config and the configuration data of the technology object.
– Compare the encoder type, resolution, multiplier and, with absoluteencoders, the data length in the drive or encoder parameter P979 with theconfiguration data of the technology object.
– Compare the parameterization named in reason 0x8000 (reason 0x8000 canoccur as secondary fault).
Reason 0x8000:
– Compare the cycle clock parameters of HW Config (PROFIBUS line, SlaveOM for drive or encoder) and the execution system. Tmapc and servo mustbe parameterized with the same cycle clock period!
� System fault, contact the hotline (reason 0x0008, 0x0010, 0x0020).
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseFOLLOWING_OBJECT_DISABLE
Programmable local responsesFOLLOWING_OBJECT_DISABLE
followingObjectType
8-500� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
20006 Error in configuration (category: /1/%d, error number: /2/%d)
CauseThis alarm indicates error states caused by a faulty or inconsistent configuration.The technology objects perform a plausibility check on the configuration. Errors areidentified by the error codes below.
Meaning of alarm parameters
Category: Area in which the error occurred.
1–Command decoding
2–Interpolator
3–Controller
4–Manipulated variable output
5–Encoder system
6–Technology object
Error number: Specification of error
500 = “TO in illegal status for configuration.”
501 = “More configuration data expected than received.”
502 = “Invalid data in configuration.”
503 = “Version conflict in configuration.”
1001 = “Error in configuration data numberOfMaxBufferedCommandId”
1002 = “Error in configuration data for maximum tolerated master setpoint change maximumOfMasterChange”
1003 = “Error in overdrive factor configuration data for synchronizationprocedures overDriveFactor”
1004 = “Configuration of approachLeadingValue not implemented”
RemedyChange the configuration data.
Acknowledgment / responsePower On / START TechnologicalFaultTask
Default setting for local responseFOLLOWING_OBJECT_DISABLE
Programmable local responsesFOLLOWING_OBJECT_DISABLE
followingObjectType
8-501� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
20007 Interconnection error (category: /1/%d, context: /2/%d, context parameter1:/3/%d, context parameter2: /4/%d)
CauseThis alarm indicates errors in the interconnection of technology objects. When theinterconnection is established, the technology object verifies it on the basis of theinterface properties. Errors are classified by category.
Meaning of alarm parameters
Category:
1 – TO compatibility error:An interconnection is to be established with a technology object that has beenconfigured with another reference system (e.g., output cam with rotaryreference system and linear axis).
2 – Exclusive interface:Multiple interconnections are to be established for an interface intended forexclusive interconnection.
3 – Interconnection requirement:The technology object is waiting for an interconnection required for thesequence.
4 – Interface initialization error:Errors result from extended initialization sequences at interfaces andparameter exchange between interconnected interfaces.
5 – Interface not available on technology object:An interface specified in the interconnection is not available on the technologyobject.
6 – Circularity:The interconnection on the technology object leads to circular communicationwithin the technology object (e.g., circular master/slave interconnection ofgearing axes, whereby a gearing axis used as a master is in turn the slave ofanother master, which is assigned the master setpoints generated on thisgearing axis directly or via additional interconnections).
7 – Sequence-level compatibility error:An interconnection is to be established with a technology object that isexecuted in another interpolator level (e.g., output cam with IPO and axis withIPO_2).
8 – Distribution initialization:When interconnecting technology objects that are distributed among differentdevices, an error occurred during initialization of the communication interface.
9 – Illegal TO status:The technology object cannot be interconnected in the current state.
Context:
The context provides additional information about the error category for the TOinterconnection. Additional parameters can be provided for the error descriptionon a context-specific basis. Context and context parameter are output as aninteger value.
followingObjectType
8-502� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
Remedy
1 – Technology object compatibility error Correct the configuration of the reference system of the technology objects tobe interconnected.
2 – Exclusive interface Correct the configuration of the interconnected technology object.
3 – Interconnection request Add the missing interconnection to your technology object.
4 – Error during interface initialization: Contact the hotline.
5 – Interface not available on technology object: Contact the hotline.
6 – Circularity:Remove unnecessary interconnections.
7 – Execution level compatibility error: Correct the configuration of the interpolator task level of the technology objectsto be interconnected.
8 – Distribution initializationCheck the hardware configuration. Ensure that the distributed interactingdevices are linked in the bus configuration. In addition, the address areas thatare used by the devices for communication must be set up. The address areasare automatically set up when the project is compiled; only afterwards is thevalid hardware configuration available for downloading.
9 – Illegal TO statusCorrect the configuration of the technology object, correct execution errors.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseFOLLOWING_OBJECT_DISABLE
Programmable local responsesFOLLOWING_OBJECT_DISABLE
followingObjectType
8-503� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
20008 Cannot assign USER_DEFAULT to system variables
CauseIt is not appropriate to assign USER_DEFAULT to a UserDefault system variable,because the variable references itself in this case.This prevents generation of a useful value during reading out. When this erroroccurs, the new Enum value is not assigned. The variable retains the old value.
RemedyUSER_DEFAULT is designed for use in technology commands.Avoid assigning it to system variables.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONE
20009 Reserved error
CauseThis error is not currently in use.
RemedyNot necessary, for information only.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseFOLLOWING_OBJECT_DISABLE
Programmable local responsesFOLLOWING_OBJECT_DISABLE
followingObjectType
8-504� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
20010 A restart is necessary to activate the configuration data
CauseThe configuration cannot be set to active, since data have been modified in such away that does not permit it. The technology object must be restarted to activate thedata.
Remedy
� Execute the technology object reset command, and set the activateRestartparameter to ACTIVATE_RESTART.
� Set the restartActivation system variable to ACTIVATE_RESTART.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPFOLLOWING_OBJECT_DISABLE
followingObjectType
8-505� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
20011 Error when activating the configuration (category: /1/%d, error number:/2/%d)
CauseThis note indicates error conditions when activating the configuration. The errorconditions can be traced back to an incorrect or inconsistent configuration. Thetechnology objects perform a plausibility check on the configuration. Errors areidentified by the error codes below.If this information appears, the configuration will not be activated.
Meaning of alarm parameters
Category: Area in which the error occurred.
1–Command decoding
2–Interpolator
3–Controller
4–Manipulated variable output
5–Encoder system
6–Technology object
Error number: Specification of error
1001 = “Error in configuration data numberOfMaxBufferedCommandId”
1002 = “Error in configuration data for maximum tolerated master setpoint change maximumOfMasterChange”
1003 = “Error in overdrive factor configuration data for synchronizationprocedures overDriveFactor”
1004 = “Configuration of approachLeadingValue not implemented”
RemedyChange the configuration data.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPFOLLOWING_OBJECT_DISABLE
followingObjectType
8-506� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
20012 Restart not executed (reason: /1/%d)
CauseTechnology object could not be restarted.
Meaning of alarm parameters
Reason:
1 – The technology object configuration does not allow a restart with the restartsystem variable. You can initiate the restart using the reset command.
2 – The technology object is not ready to be restarted.
3 – A configured condition for restarting the technology object is not met (e.g.,technology object must be disabled).
4 – Restart has not been executed or executed with the last programmedconfiguration of the technology object.
Remedy
� Work around the cause stated in the Reason parameter, or reload the project.
� Use the device diagnostics to establish whether technological alarms werereported and, if necessary, remedy the cause of the alarm.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPFOLLOWING_OBJECT_DISABLE
followingObjectType
8-507� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
20014 At the logical address: /1/%d (optional log. address: /2/%d and bit no.: /3/%dof the enable output), a driver (type: /4/%d) could not be requested
CauseThe driver of a physical device is not available or is being used by another TO.
Meaning of alarm parameters
Logical address:
This is the address of the actuator driver configured on the technology object.
Logical address and bit number:
This specifies the address and bit number of the output enable bit
Type:
1–Actuator driver
2–Encoder driver
3–BitRead driver
4–BitWrite driver
5–ByteRead driver
6–ByteWrite driver
7–WordRead driver
8–WordWrite driver
9–DWordRead driver
10–DWordWrite driver
Remedy
� Check that the logical device was available at the time of the request or whetherit was being used by another technology object.
� Connect a suitable device.
� Check the device (function, connections, terminals).
� Check the topological configuration in HWConfig.
� Compare configuration of HWConfig and technology object.
� Contact the hotline.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseFOLLOWING_OBJECT_DISABLE
Programmable local responsesFOLLOWING_OBJECT_DISABLE
followingObjectType
8-508� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
30001 Illegal parameter (parameter index according to standard sequence in thesystem functions: /1/%d, command type: /4/%X)
CauseIllegal system function parameter, the command is aborted. The parameters indicate the position of the illegal system function parameteraccording to the standard sequence in the system functions and the command typeof an incorrectly entered parameter.
Meaning of alarm parameters
Parameter index:
Index of the first system function parameter that triggered this error (listedaccording to the standard sequence in the system functions).
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyChange the parameters.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPFOLLOWING_OBJECT_DISABLE
followingObjectType
8-509� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
30002 Command aborted (reason: /1/%d, command type: /4/%X)
CauseExecution of the command was aborted before or during processing.This condition can arise as a result of loading a new command, resetting thecommand buffer, or an error state.
Meaning of alarm parameters
Reason:
1–Command buffer reset
2–Abort by another command
3–Aborted by a stop
4–Aborted by a higher-order stop
5–Abort by a pending error response
6–Aborted due to ambiguous commandId
7–Delayed acknowledgment
8–No actual value for axis (e.g., encoder or data bus not ready)
9–Aborted due to abnormal termination of a dependent command
10–Aborted due to active synchronous operation
11–Aborted due to active superimposed motion
12–Aborted due to active speed-controlled controller mode
13–Aborted due to active position-controlled controller mode
14–Aborted due to active motion to fixed end stop
15–Axis is not in pressure-limiting operation
16–Aborted due to active pressure-controlled operation
17–Aborted due to inactive pressure-controlled operation
18–Superimposed command is not permitted
19–Aborted due to error during cam access
20–Slave is not ready for operation
21–Error in slave synchronization
22–Aborted by command on slave
23–Aborted by stop on slave
24–Aborted by an active error response on the slave
25–No actual value for slave (e.g., encoder or data bus not ready)
26–Aborted by reset on slave
27–Master values are not valid
28–Active command in recursive TO interconnection
29–Aborted due to error during synchronization
30–Axis is in pressure-limiting operation
31–Maximum number of active commands exceeded
32–Aborted due to active correction command
33–Action only permissible in standstill
Command type:
Outputs the aborted command type. The command type is output as ahexadecimal integer value.
followingObjectType
8-510� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
RemedyReset command via program.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPFOLLOWING_OBJECT_DISABLE
30003 Command aborted due to full command buffer (command type: /4/%X)
CauseThe command is not entered in the command buffer as the buffer is already full.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
Remedy
� Check the program flow.
� Typical cause: The ’nextCommand’ parameter is passed with the valueIMMEDIATELY. You need to synchronize the command sequence manually oruse another value for ’nextCommand’.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPFOLLOWING_OBJECT_DISABLE
followingObjectType
8-511� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
30004 Unknown command (command type: /4/%X)
CauseThe active software tool does not support this command.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyCheck the versions of the engineering system and the runtime software.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPFOLLOWING_OBJECT_DISABLE
followingObjectType
8-512� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
30005 Ambiguous commandId (number of commands with specified ID: /1/%d,command type: /4/%X)
CauseThe specified commandID refers to several commands.The specified action is performed for the command matching the specifiedcommandID that has been in the interpolator for the longest time. If nocorresponding command is found in the interpolator, the action refers to the nextcommand loaded in the interpolator.
Meaning of alarm parameters
Number of commands with specified ID:
Number of commands referenced by the specified commandId.
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyUse different commandIds for commands that are active simultaneously.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPFOLLOWING_OBJECT_DISABLE
followingObjectType
8-513� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
30006 Cannot execute command due to current object state (command type: /4/%X)
CauseThe object is in the stop, error, or reset state and the command is not possible inthis object state.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
Remedy
� Check the object status.
� Check the permissible sequence of commands.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPFOLLOWING_OBJECT_DISABLE
30007 The error cannot be reset due to its configuration
CauseThe alarm cannot be acknowledged at the present time or by the selected means.
Remedy
� Check the configured acknowledgment procedure.
� If necessary, change the acknowledgment procedure for the alarm.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPFOLLOWING_OBJECT_DISABLE
followingObjectType
8-514� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
30008 A connection to a technology object required for this operation does notexist (command type: /4/%X)
CauseThe object connection required for this operation has not been configured.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyCheck the project configuration, or change the object connection in the command.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPFOLLOWING_OBJECT_DISABLE
followingObjectType
8-515� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
30009 Command rejected due to suspension of command decoding on addressedtechnology object (command type: /4/%X)
CauseCommand was rejected due to suspension of command decoding on theaddressed technology object.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
Remedy
� Check why the command was rejected.
� If necessary, acknowledge any active errors once you have corrected the causeof the error.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPFOLLOWING_OBJECT_DISABLE
30010 Command not available (command type: /4/%X)
CauseThe command is not available in this version of the runtime software.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyCheck the version of the runtime software.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPFOLLOWING_OBJECT_DISABLE
followingObjectType
8-516� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
30011 Parameter unavailable (parameter index according to standard sequence inthe system functions: /1/%d, command type: /4/%X)
CauseThe parameter is not available in this version of the runtime software, thecommand is therefore rejected. The parameters indicate the position according tothe standard sequence in the system functions and the command type of anincorrectly entered parameter.
Meaning of alarm parameters
Parameter index:
Index of the command parameter triggering this error according to the standardsequence in the system functions.
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyCheck the version of the runtime software.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPFOLLOWING_OBJECT_DISABLE
followingObjectType
8-517� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
30012 Command cannot be started synchronously (command type: /4/%X)
CauseThe command cannot be used during a BEGIN_SYNC, END_SYNC sequencebecause it is a reset command or a command that has only one return value in theuser program.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyDo not use this command type during a BEGIN_SYNC, END_SYNC sequence.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPFOLLOWING_OBJECT_DISABLE
followingObjectType
8-518� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
30013 Synchronous start of the command using IMMEDIATELY mergeMode(command type: /4/%X)
CauseWith synchronous command start, only merge modes that immediately override thecurrent command (IMMEDIATELY) and superimpose the current command(SUPERIMPOSED_MOTION_MERGE) can be used. If an illegal merge mode isprogrammed (e.g., SEQUENTIAL or NEXT_MOTION), the system automaticallychanges the merge mode to IMMEDIATELY and outputs this warning.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyProgram the command, which is to be started synchronously to immediatelyoverride the current command. To do this, enter the value IMMEDIATELY in the’mergeMode’ command parameter.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPFOLLOWING_OBJECT_DISABLE
followingObjectType
8-519� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
30015 A technology required for this command was not configured (technology:/1/%d, command type: /4/%X)
CauseThe command cannot be selected in this technology object configuration.
Meaning of alarm parameters
Technology:
Not relevant
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyActivate the technology needed for the command.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPFOLLOWING_OBJECT_DISABLE
40002 Programmed velocity is limited
Cause1. The system is limiting the programmed velocity to the maximum permissibleparameter.2. For a virtual axis, the velocity is limited to a value that reliably identifies thedirection, that is, the velocity of the axis must not exceed that at which, dependingon the IPO task, at least one measured value can be detected in the range ofone-half modulo length.
RemedyNot necessary, for information only.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPFOLLOWING_OBJECT_DISABLE
followingObjectType
8-520� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
40003 Programmed acceleration (type: /1/%d) is limited
CauseThe system is limiting the programmed acceleration to the maximum limit.
Meaning of alarm parameters
Type:
0 – positive acceleration
1 – negative acceleration/deceleration
RemedyNot necessary, for information only.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPFOLLOWING_OBJECT_DISABLE
40004 Programmed jerk (type: /1/%d) is limited
CauseThe system is limiting the programmed jerk to the maximum limit.
Meaning of alarm parameters
Type:
0 – Increase in positive acceleration
1 – Reduction in positive acceleration
2 – Increase in negative acceleration/deceleration
3 – Reduction in negative acceleration/deceleration
RemedyNot necessary, for information only.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPFOLLOWING_OBJECT_DISABLE
followingObjectType
8-521� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
40006 Programmed velocity is zero
CauseThe programmed velocity is zero. The specified motion cannot be executed.
RemedyProgram a value not equal to zero. If USER_DEFAULT is referenced, a value notequal to zero must be programmed in the assigned system variable.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseFOLLOWING_OBJECT_DISABLE
Programmable local responsesDECODE_STOPFOLLOWING_OBJECT_DISABLE
40007 Programmed acceleration (type: /1/%d) is zero
CauseThe programmed acceleration is zero. The specified motion cannot be executed.
Meaning of alarm parameters
Type:
0 – positive acceleration
1 – negative acceleration/deceleration
RemedyProgram a value not equal to zero. If USER_DEFAULT is referenced, a value notequal to zero must be programmed in the assigned system variable.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseFOLLOWING_OBJECT_DISABLE
Programmable local responsesDECODE_STOPFOLLOWING_OBJECT_DISABLE
followingObjectType
8-522� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
40008 Programmed jerk (type: /1/%d) is zero
CauseThe programmed jerk is zero. The specified motion cannot be executed.
Meaning of alarm parameters
Type:
0 – Increase in positive acceleration
1 – Reduction in positive acceleration
2 – Increase in negative acceleration/deceleration
3 – Reduction in negative acceleration/deceleration
RemedyProgram a value not equal to zero. If USER_DEFAULT is referenced, a value notequal to zero must be programmed in the assigned system variable.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseFOLLOWING_OBJECT_DISABLE
Programmable local responsesDECODE_STOPFOLLOWING_OBJECT_DISABLE
40009 Velocity limit is zero
CauseThe programmed velocity is zero. The specified motion cannot be executed.
RemedyProgram a value not equal to zero in the dynamic limit values.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseFOLLOWING_OBJECT_DISABLE
Programmable local responsesDECODE_STOPFOLLOWING_OBJECT_DISABLE
followingObjectType
8-523� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
40010 Acceleration limit (type: /1/%d) is zero
CauseThe programmed acceleration limit is zero. The specified motion cannot beexecuted.
Meaning of alarm parameters
Type:
0 – positive acceleration
1 – negative acceleration/deceleration
RemedyProgram a value not equal to zero.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseFOLLOWING_OBJECT_DISABLE
Programmable local responsesDECODE_STOPFOLLOWING_OBJECT_DISABLE
40011 Programmed jerk limit (type: /1/%d) is zero
CauseThe programmed jerk is zero. The specified motion cannot be executed.
Meaning of alarm parameters
Type:
0 – Increase in positive acceleration
1 – Reduction in positive acceleration
2 – Increase in negative acceleration/deceleration
3 – Reduction in negative acceleration/deceleration
RemedyProgram a value not equal to zero.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseFOLLOWING_OBJECT_DISABLE
Programmable local responsesDECODE_STOPFOLLOWING_OBJECT_DISABLE
followingObjectType
8-524� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
40012 Dynamic restrictions (type: /1/%d) violated
CauseThe specified dynamic restrictions have been violated. This can occur due to:
� The incompatibility between the dynamic values from the synchronousoperation and
� The programmed dynamic values for synchronization.
One or more physical variables (velocity, acceleration, jerk) may be affected. The violations have only a temporary effect.
Meaning of alarm parameters
Type:
0 – The jerk is changed; the jerk limit is exceeded.
1 – The jerk limit is disabled during jerk-controlled motion.
2 – The acceleration is changed; the acceleration limit is exceeded.
3 – The acceleration is changed, and the jerk limit is disabled. The accelerationlimit is exceeded.
4 – The programmed dynamic response values are adjusted to the target dynamicresponse values.
5 – If the current master setpoint dynamic response is retained, the programmeddynamic response values are exceeded during synchronization. These areadjusted in accordance with the target dynamic response values.
Remedy
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPFOLLOWING_OBJECT_DISABLE
followingObjectType
8-525� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
50001 Error in accessing specified cam
CauseThe specified cam:
� does not exist or
� is not connected with synchronous operation or
� is already active
Remedy
� Check the programmed cam.
� Check the synchronous operation connection with the cam.
� Check the program sequence.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseFOLLOWING_OBJECT_DISABLE
Programmable local responsesFOLLOWING_OBJECT_DISABLE
50002 The specified cam has not been interpolated
CauseThe system only accepts verified and interpolated cams for this operation. Thespecified cam has not yet been interpolated.
RemedyCheck whether the specified cam has been interpolated.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseFOLLOWING_OBJECT_DISABLE
Programmable local responsesFOLLOWING_OBJECT_DISABLE
followingObjectType
8-526� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
50003 Cam start point outside definition range
CauseThe addressed cam start point is outside the definition range of the cam.
Remedy
� Check the definition range of your cam.
� Check the cam start point.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPFOLLOWING_OBJECT_DISABLE
50004 Error while changing cam
CauseAn access conflict occurred while changing a cam.
RemedyCheck whether the cam object data was modified at the time of the error as a resultof programming or downloading.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseFOLLOWING_OBJECT_DISABLE
Programmable local responsesNONEDECODE_STOPFOLLOWING_OBJECT_DISABLE
followingObjectType
8-527� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
50005 Deactivation of synchronous operation aborted
CauseDeactivation of synchronous operation has been rejected as the current followingobject type (gear / cam gear) does not agree with the deactivation type.
RemedyChange the deactivation type.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPFOLLOWING_OBJECT_DISABLE
50006 Synchronous operation activated/deactivated directly
CauseSynchronous operation has been activated/deactivated directly regardless of thesynchronization conditions as the master and/or slave velocity was zero.
RemedyNot necessary, for information only.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPFOLLOWING_OBJECT_DISABLE
followingObjectType
8-528� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
50007 Error when activating/deactivating synchronous operation
CauseActivation/deactivation of synchronous operation led to a serious error. Possiblecauses are:
� During the synchronization operation, the master reversed direction and theselected synchronization/desynchronization strategy cannot tolerate thisreversal.
� Changes to master values result in an unattainable motion, e.g., by calling’setMaster’.
Remedy
� Check to determine whether the previously processed gearing command wascompletely executed.
� Check the master motion and change the synchronization strategy, if necessary.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseFOLLOWING_OBJECT_DISABLE
Programmable local responsesFOLLOWING_OBJECT_DISABLE
50008 Long-term stability cannot be maintained for the gearing
CauseThe programmed gear ratio of numerator and denominator cannot be kept stableover the long term.
Remedy
� Resynchronize in the event of inaccuracies.
� Reduce the gear ratio.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPFOLLOWING_OBJECT_DISABLE
followingObjectType
8-529� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
50009 Changing the dynamic behavior of the master results in a dynamic responseviolation during synchronization and desynchronization
CauseThe velocity change of the master exceeded the dynamic rate action specified inthe ’maximumOfMasterChange’ configuration data.
Remedy
� Check the master programming.
� Check the dynamic rate action.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPFOLLOWING_OBJECT_DISABLE
50101 The programmed master is not configured
CauseThe programmed master has not been configured as master for synchronousoperation.
Remedy
� Check the master configuration in synchronous operation.
� Check the programmed master.
� Add the appropriate master.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPFOLLOWING_OBJECT_DISABLE
followingObjectType
8-530� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
50102 Master is not assigned or configured or is defective (reason: /1/%d)
CauseA command on the following object cannot be executed because of an error in datacommunication with the master.
Meaning of alarm parameters
Reason 1: No master has been assigned to synchronous operation.
Reason 2: The master connection is not equidistant
(distributed synchronous operation).
Reason 3: Bus ramp-up (distributed synchronous operation).
Reason 4: Waiting for connection on bus (distributed synchronous operation).
Reason 5: Parameter exchange on bus (distributed synchronous operation).
Reason 6: Sign-of-life synchronization on bus (distributed synchronousoperation).
Reason 7: Reconfiguration on bus (distributed synchronous operation).
Reason 8: Offset determination (distributed synchronous operation).
Reason 9: Master setpoint not valid.
Remedy
� Create the missing master assignment (reason 1).
� Check the communication configuration.
� Synchronize your program sequence with the operating state of thecommunication system (e.g., via system variables).
� Check the enable at the master (reason 9).
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseFOLLOWING_OBJECT_DISABLE
Programmable local responsesFOLLOWING_OBJECT_DISABLE
followingObjectType
8-531� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
50103 Master and slave values can only be read out if a synchronous operationrelationship is active
CauseMaster and slave values can only be read out with the commands _getMasterValueand _getSlaveValue if a synchronous operation relationship is active.
RemedyUse the _getMasterValue and _getSlaveValue commands only for an activesynchronous operation relationship.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPFOLLOWING_OBJECT_DISABLE
50104 Master and slave values cannot be read out during synchronization anddesynchronization
CauseMaster and slave values can only be read out with commands _getMasterValueand _getSlaveValue after synchronization and desynchronization of the slave axisis complete.
RemedyDo not use the _getMasterValue and _getSlaveValue commands duringsynchronization and desynchronization.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPFOLLOWING_OBJECT_DISABLE
followingObjectType
8-532� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
50105 No master value can be defined for a specified slave value
CauseA master value cannot be defined for a specified slave value, as the slave value isoutside the permissible value range of the synchronous operation relationship.
RemedyTake account of the value range of the synchronous operation relationship whenspecifying slave values.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPFOLLOWING_OBJECT_DISABLE
50106 No slave value can be defined for a specified master value
CauseA slave value cannot be defined for a specified master value, as the master valueis outside the permissible definition range of the synchronous operationrelationship
RemedyTake account of the definition range of the synchronous operation relationshipwhen specifying master values.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPFOLLOWING_OBJECT_DISABLE
followingObjectType
8-533� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
50107 Specified synchronization path or desynchronization path is less than orequal to zero
CauseA synchronization length is required for the synchronization/desynchronizationwhen the parameter’syncProfileReference:=RELATE_SYNC_PROFILE_TO_LEADING_VALUE’ isspecified. This synchronization length must be greater than zero. It is defined byparameters ’syncLengthType’ and ’syncLength’.
RemedySpecify a synchronization length using the ’syncLengthType’ and ’syncLength’parameters.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPFOLLOWING_OBJECT_DISABLE
50108 Synchronization position is ’AT_THE_END_OF_CAM_CYCLE’ but camming isnot active.
CauseSynchronization mode AT_THE_END_OF_CAM_CYCLE is used to link a newcamming to an existing camming. If camming is not active when the command isissued, this alarm is output.
RemedyUse ’AT_THE_END_OF_CAM_CYCLE’ only if camming is already active.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPFOLLOWING_OBJECT_DISABLE
followingObjectType
8-534� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
50109 Synchronization position is AT_THE_END_OF_CAM_CYCLE but the mastermode is not RELATIVE
CauseSynchronization mode AT_THE_END_OF_CAM_CYCLE is used to link a newcamming to an existing camming. For this, RELATIVE must be specified for’masterMode’.
Remedy
� Enter RELATIVE in command parameter ’masterMode’.
� Enter a position for synchronization other than that inAT_THE_END_OF_CAM_CYCLE.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPFOLLOWING_OBJECT_DISABLE
50110 An absolute position synchronous operation cannot be called following avelocity synchronous operation
CauseAn absolute position synchronous operation (gear or cam synchronous operation)cannot be called following a velocity synchronous operation.
Remedy
� With relative position synchronous operation, switch out of “velocitysynchronous operation” mode in advance.
� On the following axis, apply an override switch out of speed-controlled mode inadvance.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPFOLLOWING_OBJECT_DISABLE
followingObjectType
8-535� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
50201 Connection with master failed (assignment: /1/%d)
CauseThe connection with an interconnected master has failed. The master is located ona distributed controller or has been assigned to a different execution level than theslave. The slave cannot be controlled without the leading value of the master.
Meaning of alarm parameters
Assignment 1: The failed master is located on an assigned controller.
Assignment 2: The failed master has been assigned to a different executionlevel than the master.
Remedy
� Check that the assigned controller is activated, the master is configured asdistributed, and communication is permitted by the operating mode of theassociated controller (assignment 1).
� Check the connection for mechanical damage, equivalence of configurednetwork topology, firm contact by the plug connector, and, if necessary, correctelectrical cable terminations (assignment 1).
� Check that the failed master was not being reloaded at the time the error wasdetected (assignment 1 and 2).
� Check whether an overflow was diagnosed for the execution level of theassigned master (assignment 2).
� Monitoring of the connection is set in the technology object configuration. Themaster and slave must have the same settings selected (assignment 1 and 2).
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseFOLLOWING_OBJECT_DISABLE
Programmable local responsesFOLLOWING_OBJECT_DISABLE
followingObjectType
8-536� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
50202 Sign-of-life monitoring for the master in distributed synchronous operation isdeactivated
CauseThe sign-of-life monitoring for the master connection on an assigned controller hasbeen deactivated. Monitoring is configured differently on the master and slave. Asa result, the connection is established without sign-of-life monitoring.
CauseUse identical configuration settings in the master and slave for sign-of-lifemonitoring of the connection
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPFOLLOWING_OBJECT_DISABLE
50203 Local and master interpolation cycle clock are different
CauseThe master and slave must have a common interpolation cycle clock for distributedsynchronous operation. However, when establishing the connection betweentechnology objects, different cycle clock settings were defined for interpolation.
RemedyUse identical cycle clock settings in the master and slave for interpolation.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseFOLLOWING_OBJECT_DISABLE
Programmable local responsesFOLLOWING_OBJECT_DISABLE
followingObjectType
8-537� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
50204 Connection in startup phase
CauseStartup of the connection between master and slave had not been completed whenthe motion command was called. At the end of startup, the offset between anytechnology objects communicating in a distributed synchronous operationrelationship is determined. This is necessary to enable offset-compensating motioncontrol to function correctly. The connection to the master is not ready until theoffset calculation has been successfully completed.
Remedy
� Check the connection for mechanical damage, equivalence of configurednetwork topology, firm contact by the plug connector, and, if necessary, correctelectrical cable terminations.
� Synchronize your program sequence with system variables for offsetdetermination on the technology object.
� Deactivate offset compensation on the technology objects involved. Deactivatecompensation only if other remedies do not eliminate the malfunction.Deactivating the offset compensation limits the accuracy of motion control.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseFOLLOWING_OBJECT_DISABLE
Programmable local responsesFOLLOWING_OBJECT_DISABLE
followingObjectType
8-538� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
50205 Offset cannot be determined
CauseThe offset for the master cannot be determined. This can be caused by configuringthe PROFIBUS-DP without equidistant operation or a ratio of interpolator cycleclock to PROFIBUS-DP cycle clock greater than 64.
Remedy
� Select equidistant mode on the PROFIBUS-DP.
� Select a suitable IPO / DP cycle clock ratio setting
� Deactivate offset compensation on the technology objects involved. Deactivatecompensation only if other remedies do not eliminate the malfunction.Deactivating the offset compensation limits the accuracy of motion control.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseFOLLOWING_OBJECT_DISABLE
Programmable local responsesFOLLOWING_OBJECT_DISABLE
50206 Loss of synchronization with master on assigned controller in distributedsynchronous operation
CauseThere is no equidistance between the local and distributed controller. The localsynchronization object and the assigned master thus have no common timereference system. When clock synchronism is lost, the parameters determined forthis connection are no longer valid and further operation is not permissible.
Remedy
� Ensure that the connection between the controllers is configured for equidistantmode.
� Check if the user program is affecting the synchronization or if it has beendeactivated.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseFOLLOWING_OBJECT_DISABLE
Programmable local responsesFOLLOWING_OBJECT_DISABLE
followingObjectType
8-539� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
50207 Master setpoint is outside the permissible range (reason: /1/%d)
CauseOne or more values in the master setpoint protocol received on the slave hasexceeded the permissible value range. The permissible value range is specifiedseparately for each device. When distributing synchronous operation functionalityacross different devices, a slave can receive lead values which it is incapable ofrepresenting internally.
Meaning of alarm parameters
Reason 1: The position master setpoint has exceeded the specified limit value.
Reason 2: The velocity master setpoint has exceeded the specified limit value.
Reason 3: The position and velocity master setpoints have exceeded thespecified limit values.
RemedyTake measures in the TO configuration and user program to ensure that it is notpossible to exceed the permissible value range. The error can be avoided by configuring the master as a cyclic technology object(modulo).
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseFOLLOWING_OBJECT_DISABLE
Programmable local responsesFOLLOWING_OBJECT_DISABLE
followingObjectType
8-540� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
9-541� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
camType
Possible local responses
NONENo response
DECODE_STOPAbort command processing
20001 Internal error (Parameter1: /1/%d, Parameter2: /2/%d, Parameter3: /3/%d,Parameter4: /4/%d)
CauseThis alarm indicates internal error states providing information about the cause andlocation of the error in association with the related error number.
Meaning of alarm parameters
Parameter1: Error source
Parameter2 to 4: Error number
RemedyA detailed description of the system error alarm is not provided. Should a systemerror of this type occur, note the alarm number, the alarm text, and the internalsystem error number specified in the alarm and contact: SIEMENS AG A&D MC, Hotline.
Acknowledgment / ResponsePower On / STOP
Default setting for local responseDECODE_STOP
Programmable local responsesDECODE_STOP
9
camType
9-542� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
20002 Insufficient memory (Parameter1: /1/%d, Parameter2: /2/%d, Parameter3: /3/%d, Parameter4: /4/%d)
CauseThe memory required by the system is no longer available. This alarm can occurboth during power up and after program calls.
Meaning of alarm parameters
Parameter1: Area in which the error occurred.
1–Command decoding
2–Interpolator
3–Controller
4–Manipulated variable output
5–Encoder system
6–Technology package
Parameters 2 to 4 are area-specific. They are not fully utilized by all areas.
Command decoding area:
Parameter2 and Parameter4 refer to the command in which the error occurred.
Parameter2: Command return value
Parameter4: Command type
Remedy
� Reduce the size of the ST code.
� Reduce the number of technology objects.
� Reduce the number of interpolation points for cams, if present.
Acknowledgment / ResponsePower On / STOP
Default setting for local responseDECODE_STOP
Programmable local responsesDECODE_STOP
camType
9-543� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
20003 No object configuration (Parameter1: /1/%d, Parameter2: /2/%d, Parameter3: /3/%d, Parameter4: /4/%d)
CauseError in system configuration. The configuration data for a software tool could notbe found.
Meaning of alarm parameters
Parameter1: Area in which the error occurred.
1–Command decoding
2–Interpolator
3–Controller
4–Manipulated variable output
5–Encoder system
Parameters 2 to 4 are area-specific. They are not fully utilized by all areas.
Command decoding area:
Parameter2 and Parameter4 refer to the command in which the error occurred.
Parameter2: Command return value
Parameter4: Command type
RemedyCheck the accuracy of the configuration data in your project. When commands arecalled on technology objects, the technology objects must be configured.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOP
camType
9-544� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
20004 At the logical address: /1/%d (bit number, if required: /2/%d) a driver (type: /3/%d) could be requested (error number: /4/%d)
CauseThe driver of a physical device or the device itself is not available.
Meaning of alarm parameters
Logical address:
This is the address configured on the technology object.
Bit number:
For bit driver only; bit number
Type:
1–Actuator driver
2–Encoder driver
3–BitRead driver
4–BitWrite driver
5–ByteRead driver
6–ByteWrite driver
7–WordRead driver
8–WordWrite driver
9–DWordRead driver
10–DWordWrite driver
Error number: Specification of error
Not relevant
Remedy
� Connect a suitable device.
� Check the device (function, connections, terminals).
� Check the topological configuration in HWConfig.
� Compare configuration of HWConfig and technology object.
� Contact the hotline.
Acknowledgment / responsePower On / START TechnologicalFaultTask
Default setting for local responseDECODE_STOP
Programmable local responsesDECODE_STOP
camType
9-545� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
20005 Device type: /3/%d, log. address: /1/%d faulty. (Bit: /2/%d, reason: 0x/4/%Xh)
CauseThe driver of a physical device or the device itself has failed or is faulty. When thisalarm occurs, the error cause must be evaluated in the external device (drive orencoder).
Meaning of alarm parameters
Type:
1–Actuator driver
2–Encoder driver
3–BitRead driver
4–BitWrite driver
5–ByteRead driver
6–ByteWrite driver
7–WordRead driver
8–WordWrite driver
9–DWordRead driver
10–DWordWrite driver
Logical address:This is the address configured on the technology object.
Bit number:For bit driver type = 3 or 4 only; bit number
Reason:0–Not defined (e.g., for binary I/O)
� Type = 1
0x0001h: Fault message from drive (note: On PROFIBUS drives, which support acyclic communication in accordance with PROFIdrive V3, the error number/numbers of the drives is/are displayed in the diagnostic buffer, e.g., on Masterdrives MC).
0x0002h: DP: Drive signal “control requested” failed
0x0004h: DP: Drive switched off itself
0x0008h: Slot for drive data is not available in the project
0x0010h: Actuator driver does not have a connection to the drive data
0x0020h: Actuator driver was not initialized during power up
0x0080h: DP: Difference between configuration data and drive parameters
0x4000h: DP: Drive on bus failed (station failure)
0x8000h: Sign of life of drive faulty or failed
camType
9-546� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
� Type = 2
0x0000h: The number of permissible changes in the actual value of the maximum velocity of the absolute-value encoder has been exceeded
0x0001h: Fault message from encoder (note: The error number/numbers is/are displayed in the diagnostic buffer)
0x0002h: General hardware error of encoder
0x0004h: Encoder contaminated
0x0008h: Slot for encoder data is not available in the project
0x0010h: Encoder driver does not have a connection to the encoder data
0x0020h: Encoder driver was not initialized during power up
0x0040h: Error when reading the absolute value of the encoder
0x0080h: DP: Difference between the configuration data and the encoder parameters
0x0100h: Zero mark monitoring of encoder
0x4000h: DP: Encoder on bus failed (station failure)
0x8000h: DP: Sign of life of encoder has malfunctioned or failed. (Note: For an encoder whose data are transferred in a drive message together with actuator data, the actuator sign of life applies for the encoder, e.g., a standard message 3 in accordance with PROFIdrive).
� Type = 3 to 10
0x0000h: Additional information, not assigned
Note:Codings for the reason of the failure can also occur in combination. Theindividual codings are then added to form a coding sum, which is displayed(e.g., 0x0005 = 0x0001 + 0x0004). A reason for failure marked as DP can only be present on PROFIBUS devices.
RemedyCheck the device with respect to function and connections (reason 0x0001,0x0002, 0x0004, 0x4000, 0x8000).
� Check the topological configuration in HW Config (with reason 0x0008).
� For PROFIBUS drives or encoders, compare the configuration of HWConfig, thetechnology object, and the drive parameter assignment.For:
Reason 0x0040:
– Compare the encoder type in the drive or encoder parameter P979 with theconfiguration data of the technology object.
camType
9-547� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
Reason 0x0080:
– Compare the message frame type in the drive or encoder parameter P922with HW Config and the configuration data of the technology object.
– Compare the encoder type, resolution, multiplier and, with absoluteencoders, the data length in the drive or encoder parameter P979 with theconfiguration data of the technology object.
– Compare the parameterization named in reason 0x8000 (reason 0x8000 canoccur as secondary fault).
Reason 0x8000:
– Compare the cycle clock parameters of HW Config (PROFIBUS line, SlaveOM for drive or encoder) and the execution system. Tmapc and servo mustbe parameterized with the same cycle clock period!
� System fault, contact the hotline (reason 0x0008, 0x0010, 0x0020).
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseDECODE_STOP
Programmable local responsesDECODE_STOP
camType
9-548� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
20006 Error in configuration (category: /1/%d, error number: /2/%d)
CauseThis alarm indicates error states caused by a faulty or inconsistent configuration.The technology objects perform a plausibility check on the configuration. Errors areidentified by the error codes below.
Meaning of alarm parameters
Category: Area in which the error occurred.
1–Command decoding
2–Interpolator
3–Controller
4–Manipulated variable output
5–Encoder system
6–Technology object
Error number: Specification of error
500 = “TO in illegal status for configuration”
501 = “More configuration data expected than received”
502 = “Invalid data in configuration”
503 = “Version conflict in configuration”
Not relevant
RemedyChange the configuration data.
Acknowledgment / responsePower On / START TechnologicalFaultTask
Default setting for local responseDECODE_STOP
Programmable local responsesDECODE_STOP
camType
9-549� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
20007 Interconnection error (category: /1/%d, context: /2/%d, context parameter1: /3/%d, context parameter2: /4/%d)
CauseThis alarm indicates errors in the interconnection of technology objects. When theinterconnection is established, the technology object verifies it on the basis of theinterface properties. Errors are classified by category.
Meaning of alarm parameters
Category:
1 – TO compatibility errorAn interconnection is to be established with a technology object that has beenconfigured with another reference system (e.g., output cam with rotaryreference system and linear axis).
2 – Exclusive interfaceMultiple interconnections are to be established for an interface intended forexclusive interconnection.
3 – Interconnection requirementThe technology object is waiting for an interconnection required for thesequence.
4 – Interface initialization errorErrors result from extended initialization sequences at interfaces andparameter exchange between interconnected interfaces.
5 – Interface not available on technology objectAn interface specified in the interconnection is not available on the technologyobject.
6 – CircularityThe interconnection on the technology object leads to circular communicationwithin the technology object (e.g., circular master/slave interconnection ofgearing axes, whereby a gearing axis used as a master is in turn the slave ofanother master, which is assigned the master setpoints generated on thisgearing axis directly or via additional interconnections).
7 – Sequence-level compatibility errorAn interconnection is to be established with a technology object that isexecuted in another interpolator level (e.g., output cam with IPO and axis withIPO_2).
8 – Distribution initializationWhen interconnecting technology objects that are distributed among differentdevices, an error occurred during initialization of the communication interface.
9 – Illegal TO statusThe technology object cannot be interconnected in the current state.
Context:
The context provides additional information about the error category for the TOinterconnection. Additional parameters can be provided for the error descriptionon a context-specific basis. Context and context parameter are output as aninteger value.
camType
9-550� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
Remedy
1 – Technology object compatibility error: Correct the configuration of the reference system of the technology objects tobe interconnected.
2 – Exclusive interface: Correct the configuration of the interconnected technology object.
3 – Interconnection request: Add the missing interconnection to your technology object.
4 – Error during interface initialization: Contact the hotline.
5 – Interface not available on technology object: Contact the hotline.
6 – Circularity:Remove unnecessary interconnections.
7 – Execution level compatibility error: Correct the configuration of the interpolator task level of the technology objectsto be interconnected.
8 – Distribution initialization:Check the hardware configuration. Ensure that the distributed interactingdevices are linked in the bus configuration. In addition, the address areas thatare used by the devices for communication must be set up. The address areasare automatically set up when the project is compiled; only afterwards is thevalid hardware configuration available for downloading.
9 – Illegal TO status:Correct the configuration of the technology object, correct execution errors.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseDECODE_STOP
Programmable local responsesDECODE_STOP
camType
9-551� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
20008 Cannot assign USER_DEFAULT to system variables
CauseIt is not appropriate to assign USER_DEFAULT to a UserDefault system variable,because the variable references itself in this case.This prevents generation of a useful value during reading out. When this erroroccurs, the new Enum value is not assigned. The variable retains the old value.
RemedyUSER_DEFAULT is designed for use in technology commands.Avoid assigning it to system variables.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONE
20009 Reserved error
CauseThis error is not currently in use.
RemedyNot necessary, for information only.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseDECODE_STOP
Programmable local responsesDECODE_STOP
camType
9-552� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
20010 A restart is necessary to activate the configuration data
CauseThe configuration cannot be set to active, since data have been modified in such away that does not permit it. The technology object must be restarted to activate thedata.
Remedy
� Execute the technology object reset command, and set the activateRestartparameter to ACTIVATE_RESTART.
� Set the restartActivation system variable to ACTIVATE_RESTART.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOP
camType
9-553� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
20011 Error when activating the configuration (category: /1/%d, error number: /2/%d)
CauseThis note indicates error conditions when activating the configuration. The errorconditions can be traced back to an incorrect or inconsistent configuration. Thetechnology objects perform a plausibility check on the configuration. Errors areidentified by the error codes below.If this information appears, the configuration will not be activated.
Meaning of alarm parameters
Category: Area in which the error occurred.
1–Command decoding
2–Interpolator
3–Controller
4–Manipulated variable output
5–Encoder system
6–Technology object
Error number: Specification of error
Not relevant
RemedyChange the configuration data.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOP
camType
9-554� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
20012 Restart not executed (reason: /1/%d)
CauseTechnology object could not be restarted.
Meaning of alarm parameters
Reason:
1 – The technology object configuration does not allow a restart with the restartsystem variable. You can initiate the restart using the reset command.
2 – The technology object is not ready to be restarted.
3 – A configured condition for restarting the technology object is not met (e.g.,technology object must be disabled).
4 – Restart has not been executed or executed with the last programmedconfiguration of the technology object.
Remedy
� Work around the cause stated in the Reason parameter, or reload the project.
� Use the device diagnostics to establish whether technological alarms werereported and, if necessary, remedy the cause of the alarm.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOP
camType
9-555� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
20014 At the logical address: /1/%d (optional log. address: /2/%d and bit no.: /3/%dof the enable output), a driver (type: /4/%d) could not be requested
CauseThe driver of a physical device is not available or is being used by another TO.
Meaning of alarm parameters
Logical address:
This is the address of the actuator driver configured on the technology object.
Logical address and bit number:
This specifies the address and bit number of the output enable bit
Type:
1–Actuator driver
2–Encoder driver
3–BitRead driver
4–BitWrite driver
5–ByteRead driver
6–ByteWrite driver
7–WordRead driver
8–WordWrite driver
9–DWordRead driver
10–DWordWrite driver
Remedy
� Check that the logical device was available at the time of the request or whetherit was being used by another technology object.
� Connect a suitable device.
� Check the device (function, connections, terminals).
� Check the topological configuration in HWConfig.
� Compare configuration of HWConfig and technology object.
� Contact the hotline.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseDECODE_STOP
Programmable local responsesDECODE_STOP
camType
9-556� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
30001 Illegal parameter (parameter index according to standard sequence in thesystem functions: /1/%d, command type: /4/%X)
CauseIllegal system function parameter, the command is aborted. The parameters indicate the position of the illegal system function parameteraccording to the standard sequence in the system functions and the command typeof an incorrectly entered parameter.
Meaning of alarm parameters
Parameter index:
Index of the first system function parameter that triggered this error (listedaccording to the standard sequence in the system functions).
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyChange the parameters.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOP
camType
9-557� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
30002 Command aborted (reason: /1/%d, command type: /4/%X)
CauseExecution of the command was aborted before or during processing.This condition can arise as a result of loading a new command, resetting thecommand buffer, or an error state.
Meaning of alarm parameters
Reason:
1–Command buffer reset
2–Abort by another command
3–Aborted by a stop
4–Aborted by a higher-order stop
5–Abort by a pending error response
6–Aborted due to ambiguous commandId
7–Delayed acknowledgment
8–No actual value for axis (e.g., encoder or data bus not ready)
9–Aborted due to abnormal termination of a dependent command
10–Aborted due to active synchronous operation
11–Aborted due to active superimposed motion
12–Aborted due to active speed-controlled controller mode
13–Aborted due to active position-controlled controller mode
14–Aborted due to active motion to fixed end stop
15–Axis is not in pressure-limiting operation
16–Aborted due to active pressure-controlled operation
17–Aborted due to inactive pressure-controlled operation
18–Superimposed command is not permitted
19–Aborted due to error during cam access
20–Slave is not ready for operation
21–Error in slave synchronization
22–Aborted by command on slave
23–Aborted by stop on slave
24–Aborted by an active error response on the slave
25–No actual value for slave (e.g., encoder or data bus not ready)
26–Aborted by reset on slave
27–Master values are not valid
28–Active command in recursive TO interconnection
29–Aborted due to error during synchronization
30–Axis is in pressure-limiting operation
31–Maximum number of active commands exceeded
32–Aborted due to active correction command
33–Action only permissible in standstill
Command type:
Outputs the aborted command type. The command type is output as ahexadecimal integer value.
camType
9-558� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
RemedyReset command via program.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOP
30003 Command aborted due to full command buffer (command type: /4/%X)
CauseThe command is not entered in the command buffer as the buffer is already full.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
Remedy
� Check the program flow.
� Typical cause: The ’nextCommand’ parameter is passed with the valueIMMEDIATELY. You need to synchronize the command sequence manually oruse another value for ’nextCommand’.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOP
camType
9-559� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
30004 Unknown command (command type: /4/%X)
CauseThe active software tool does not support this command.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyCheck the versions of the engineering system and the runtime software.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOP
camType
9-560� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
30005 Ambiguous commandId (number of commands with specified ID: /1/%d,command type: /4/%X)
CauseThe specified commandID refers to several commands.The specified action is performed for the command matching the specifiedcommandID that has been in the interpolator for the longest time. If nocorresponding command is found in the interpolator, the action refers to the nextcommand loaded in the interpolator.
Meaning of alarm parameters
Number of commands with specified ID:
Number of commands referenced by the specified commandId.
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyUse different commandIds for commands that are active simultaneously.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOP
camType
9-561� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
30006 Cannot execute command due to current object state (command type: /4/%X)
CauseThe object is in the stop, error, or reset state and the command is not possible inthis object state.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
Remedy
� Check the object status.
� Check the permissible sequence of commands.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOP
30007 The error cannot be reset due to its configuration
CauseThe alarm cannot be acknowledged at the present time or by the selected means.
Remedy
� Check the configured acknowledgment procedure.
� If necessary, change the acknowledgment procedure for the alarm.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOP
camType
9-562� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
30008 A connection to a technology object required for this operation does notexist (command type: /4/%X)
CauseThe object connection required for this operation has not been configured.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyCheck the project configuration, or change the object connection in the command.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOP
30009 Command rejected due to suspension of command decoding on addressedtechnology object (command type: /4/%X)
CauseCommand was rejected due to suspension of command decoding on theaddressed technology object.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
Remedy
� Check why the command was rejected.
� If necessary, acknowledge any active errors once you have corrected the causeof the error.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOP
camType
9-563� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
30010 Command not available (command type: /4/%X)
CauseThe command is not available in this version of the runtime software.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyCheck the version of the runtime software.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOP
30011 Parameter unavailable (parameter index according to standard sequence inthe system functions: /1/%d, command type: /4/%X)
CauseThe parameter is not available in this version of the runtime software, thecommand is therefore rejected. The parameters indicate the position according tothe standard sequence in the system functions and the command type of anincorrectly entered parameter.
Meaning of alarm parameters
Parameter index:
Index of the command parameter triggering this error according to the standardsequence in the system functions.
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyCheck the version of the runtime software.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOP
camType
9-564� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
30012 Command cannot be started synchronously (command type: /4/%X)
CauseThe command cannot be used during a BEGIN_SYNC, END_SYNC sequencebecause it is a reset command or a command that has only one return value in theuser program.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyDo not use this command type during a BEGIN_SYNC, END_SYNC sequence.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOP
camType
9-565� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
30013 Synchronous start of the command using IMMEDIATELY mergeMode(command type: /4/%X)
CauseWith synchronous command start, only merge modes that immediately override thecurrent command (IMMEDIATELY) and superimpose the current command(SUPERIMPOSED_MOTION_MERGE) can be used. If an illegal merge mode isprogrammed (e.g., SEQUENTIAL or NEXT_MOTION), the system automaticallychanges the merge mode to IMMEDIATELY and outputs this warning.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyProgram the command, which is to be started synchronously to immediatelyoverride the current command. To do this, enter the value IMMEDIATELY in the’mergeMode’ command parameter.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOP
camType
9-566� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
30015 A technology required for this command was not configured (technology: /1/%d, command type: /4/%X)
CauseThe command cannot be selected in this technology object configuration.
Meaning of alarm parameters
Technology:
Not relevant
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyActivate the technology needed for the command.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOP
40001 Write access to function denied (command type: /4/%X)
CauseThis error occurs if a read or write access is made to the function while thecommand is being executed.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as an integer value.
Remedy
� Avoid reading and writing data simultaneously.
� Check whether another technology object is accessing the function.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOP
camType
9-567� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
40002 Read access to function denied (command type: /4/%X)
CauseThis error occurs if write access to the function has been granted to an externaldata source while the command is being executed.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as an integer value.
RemedyAvoid reading and writing data simultaneously.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOP
40003 Illegal range specification in the parameters (command type: /4/%X)
CauseThe combination of several parameters is not permissible.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as an integer value.
RemedyChange the parameter.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOP
camType
9-568� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
40004 Segment with length zero will not be inserted in the function (start and endpoint = /1/%lf)
CauseThe start and end point for mapping the segment onto the master axis are identicalin the ’_addSegmentToCam’ command(’leadingRangeStartPoint:=leadingRangeEndPoint’).
Remedy
� Remove the segment from your function if it is not needed.
� Extend the segment in the direction of the master axis.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOP
40005 The point (/1/%lf) is not within the definition range (/2/%lf, /3/%lf) of thefunction (representation: /4/%d).
CauseA point has been selected that is outside the definition range of the function.
Meaning of alarm parameters
Definition range:
Precise definition of the axis range that can be accessed.
Representation:
1 – The parameters for this alarm are shown with scaling and shifting.
2 – The parameters for this alarm are shown without scaling and shifting.
RemedyTake account of the range limits when specifying points in the definition range.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOP
camType
9-569� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
40006 The point (/1/%lf) is not within the value range (/2/%lf, /3/%lf) of the function(representation: /4/%d).
CauseA point has been selected that is outside the value range of the function.
Meaning of alarm parameters
Value range:
Value range of function at the time of access.
Representation:
1 – The parameters for this alarm are shown with scaling and shifting
2 – The parameters for this alarm are shown without scaling and shifting
RemedyTake account of the range limits when specifying points in the value range.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOP
40007 Access to interpolated function denied (command type: /4/%X).
CauseThis error occurs in commands that cannot be applied to interpolated functions.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as an integer value.
RemedyReset the function before executing the command.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOP
camType
9-570� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
40008 Required property violated during interpolation
CauseThis message occurs when:
� Interpolation cannot allow a continuous progression in the value range becausethere is a continuous progression in the definition range and the difference inthe value range is outside the permissible segment adaptation limit.
� The end criterion was violated for the same reasons.
Remedy
� Move the interpolation limits.
� Check the shape of the cam.
� Change the criteria for interpolation of segments.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOP
Part IITechnology PackageCam_ext Alarms
AdditionObjectType 10
FixedGearType 11
FormulaObjectType 12
ControllerObjectType 13
SensorType 14
9-572� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
10-573� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
AdditionObjectType
Possible local responses
NONENo response
DISABLEStop TO execution
20001 Internal error (Parameter1: /1/%d, Parameter2: /2/%d, Parameter3: /3/%d,Parameter4: /4/%d)
CauseThis alarm indicates internal error states providing information about the cause andlocation of the error in association with the related error number.
Meaning of alarm parameters
Parameter1: Error source
Parameter2 to 4: Error number
RemedyA detailed description of the system error alarm is not provided. Should a systemerror of this type occur, note the alarm number, the alarm text, and the internalsystem error number specified in the alarm and contact: SIEMENS AG A&D MC, Hotline.
Acknowledgment / responsePower On / STOP
Default setting for local responseDISABLE
Programmable local responsesDISABLE
10
AdditionObjectType
10-574� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
20002 Insufficient memory (Parameter1: /1/%d, Parameter2: /2/%d, Parameter3: /3/%d, Parameter4: /4/%d)
CauseThe memory required by the system is no longer available. This alarm can occurboth during power up and after program calls.
Meaning of alarm parameters
Parameter1: Area in which the error occurred.
1–Command decoding
2–Interpolator
3–Controller
4–Manipulated variable output
5–Encoder system
6–Technology package
Parameters 2 to 4 are area-specific. They are not fully utilized by all areas.
Command decoding area:
Parameter2 and Parameter4 refer to the command in which the error occurred.
Parameter2: Command return value
Parameter4: Command type
Remedy
� Reduce the size of the ST code.
� Reduce the number of technology objects.
� Reduce the number of interpolation points for cams, if present.
Acknowledgment / responsePower On / STOP
Default setting for local responseDISABLE
Programmable local responsesDISABLE
AdditionObjectType
10-575� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
20003 No object configuration (Parameter1: /1/%d, Parameter2: /2/%d, Parameter3: /3/%d, Parameter4: /4/%d)
CauseError in system configuration. The configuration data for a software tool could notbe found.
Meaning of alarm parameters
Parameter1: Area in which the error occurred.
1–Command decoding
2–Interpolator
3–Controller
4–Manipulated variable output
5–Encoder system
Parameters 2 to 4 are area-specific. They are not fully utilized by all areas.
Command decoding area:
Parameter2 and Parameter4 refer to the command in which the error occurred.
Parameter2: Command return value
Parameter4: Command type
RemedyCheck the accuracy of the configuration data in your project. When commands arecalled on technology objects, the technology objects must be configured.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDISABLE
AdditionObjectType
10-576� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
20004 At the logical address: /1/%d (bit number, if required: /2/%d) a driver (type: /3/%d) could be requested (error number: /4/%d)
CauseThe driver of a physical device or the device itself is not available.
Meaning of alarm parameters
Logical address:
This is the address configured on the technology object.
Bit number:
For bit driver only; bit number
Type:
1–Actuator driver
2–Encoder driver
3–BitRead driver
4–BitWrite driver
5–ByteRead driver
6–ByteWrite driver
7–WordRead driver
8–WordWrite driver
9–DWordRead driver
10–DWordWrite driver
Error number: Specification of error
Remedy
� Connect a suitable device.
� Check the device (function, connections, terminals).
� Check the topological configuration in HWConfig.
� Compare configuration of HWConfig and technology object.
� Contact the hotline.
Acknowledgment / responsePower On / START TechnologicalFaultTask
Default setting for local responseDISABLE
Programmable local responsesDISABLE
AdditionObjectType
10-577� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
20005 Device type: /3/%d, log. address: /1/%d faulty. (Bit: /2/%d, reason: 0x/4/%Xh)
CauseThe driver of a physical device or the device itself has failed or is faulty. When thisalarm occurs, the error cause must be evaluated in the external device (drive orencoder).
Meaning of alarm parameters
Type:
1–Actuator driver
2–Encoder driver
3–BitRead driver
4–BitWrite driver
5–ByteRead driver
6–ByteWrite driver
7–WordRead driver
8–WordWrite driver
9–DWordRead driver
10–DWordWrite driver
Logical address:This is the address configured on the technology object.
Bit number:For bit driver type = 3 or 4 only; bit number
Reason:0–Not defined (e.g., for binary I/O)
� Type = 1
0x0001h: Fault message from drive (note: On ROFIBUS drives, which support acyclic communication in accordance with PROFIdrive V3,
the error number/numbers of the drives is/are displayed in the diagnostic buffer, e.g., on Masterdrives MC).
0x0002h: DP: Drive signal “control requested” failed
0x0004h: DP: Drive switched off itself
0x0008h: Slot for drive data is not available in the project
0x0010h: Actuator driver does not have a connection to the drive data
0x0020h: Actuator driver was not initialized during power up
0x0080h: DP: Difference between configuration data and drive parameters
0x4000h: DP: Drive on bus failed (station failure)
0x8000h: Sign of life of drive faulty or failed
AdditionObjectType
10-578� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
� Type = 2
0x0000h: The number of permissible changes in the actual value of the maximum velocity of the absolute-value encoder has been exceeded.
0x0001h: Fault message from encoder (note: The error number/numbers is/are displayed in the diagnostic buffer)
0x0002h: General hardware error of encoder
0x0004h: Encoder contaminated
0x0008h: Slot for encoder data is not available in the project
0x0010h: Encoder driver does not have a connection to the encoder data
0x0020h: Encoder driver was not initialized during power up
0x0040h: Error when reading the absolute value of the encoder
0x0080h: DP: Difference between the configuration data and the encoder parameters
0x0100h: Zero mark monitoring of encoder
0x4000h: DP: Encoder on bus failed (station failure)
0x8000h: DP: Sign of life of encoder has malfunctioned or failed. (Note: For an encoder whose data are transferred in a drive message together with actuator data, the actuator sign of life applies for the encoder, e.g., a standard message 3 in accordance with PROFIdrive).
� Type = 3 to 10
0x0000h: Additional information, not assigned
Note:Codings for the reason of the failure can also occur in combination. Theindividual codings are then added to form a coding sum, which is displayed(e.g., 0x0005 = 0x0001 + 0x0004). A reason for failure marked as DP can only be present on PROFIBUS devices.
RemedyCheck the device with respect to function and connections (reason 0x0001,0x0002, 0x0004, 0x4000, 0x8000).
� Check the topological configuration in HW Config (with reason 0x0008).
� For PROFIBUS drives or encoders, compare the configuration of HWConfig, thetechnology object, and the drive parameter assignment.For:
Reason 0x0040:
– Compare the encoder type in the drive or encoder parameter P979 with theconfiguration data of the technology object.
AdditionObjectType
10-579� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
Reason 0x0080:
– Compare the message frame type in the drive or encoder parameter P922with HW Config and the configuration data of the technology object.
– Compare the encoder type, resolution, multiplier and, with absoluteencoders, the data length in the drive or encoder parameter P979 with theconfiguration data of the technology object.
– Compare the parameterization named in reason 0x8000 (reason 0x8000 canoccur as secondary fault).
Reason 0x8000:
– Compare the cycle clock parameters of HW Config (PROFIBUS line, SlaveOM for drive or encoder) and the execution system. Tmapc and servo mustbe parameterized with the same cycle clock period!
� System fault, contact the hotline (reason 0x0008, 0x0010, 0x0020).
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseDISABLE
Programmable local responsesDISABLE
AdditionObjectType
10-580� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
20006 Error in configuration (category: /1/%d, error number: /2/%d)
CauseThis alarm indicates error states caused by a faulty or inconsistent configuration.The technology objects perform a plausibility check on the configuration. Errors areidentified by the error codes below.
Meaning of alarm parameters
Category: Area in which the error occurred.
1–Command decoding
2–Interpolator
3–Controller
4–Manipulated variable output
5–Encoder system
6–Technology object
Error number: Specification of error
500 = “TO in illegal status for configuration”
501 = “More configuration data expected than received”
502 = “Invalid data in configuration”
503 = “Version conflict in configuration”
RemedyChange the configuration data.
Acknowledgment / responsePower On / START TechnologicalFaultTask
Default setting for local responseDISABLE
Programmable local responsesDISABLE
AdditionObjectType
10-581� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
20007 Interconnection error (category: /1/%d, context: /2/%d, context parameter1: /3/%d, context parameter2: /4/%d)
CauseThis alarm indicates errors in the interconnection of technology objects. When theinterconnection is established, the technology object verifies it on the basis of theinterface properties. Errors are classified by category.
Meaning of alarm parameters
Category:
1 – TO compatibility errorAn interconnection is to be established with a technology object that has beenconfigured with another reference system (e.g., output cam with rotaryreference system and linear axis).
2 – Exclusive interfaceMultiple interconnections are to be established for an interface intended forexclusive interconnection.
3 – Interconnection requirementThe technology object is waiting for an interconnection required for thesequence.
4 – Interface initialization errorErrors result from extended initialization sequences at interfaces andparameter exchange between interconnected interfaces.
5 – Interface not available on technology objectAn interface specified in the interconnection is not available on the technologyobject.
6 – CircularityThe interconnection on the technology object leads to circular communicationwithin the technology object (e.g., circular master/slave interconnection ofgearing axes, whereby a gearing axis used as a master is in turn the slave ofanother master, which is assigned the master setpoints generated on thisgearing axis directly or via additional interconnections).
7 – Sequence-level compatibility errorAn interconnection is to be established with a technology object that isexecuted in another interpolator level (e.g., output cam with IPO and axis withIPO_2).
8 – Distribution initializationWhen interconnecting technology objects that are distributed among differentdevices, an error occurred during initialization of the communication interface.
9 – Illegal TO statusThe technology object cannot be interconnected in the current state.
Context:
The context provides additional information about the error category for the TOinterconnection. Additional parameters can be provided for the error descriptionon a context-specific basis. Context and context parameter are output as aninteger value.
AdditionObjectType
10-582� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
Remedy
1 – Technology object compatibility error: Correct the configuration of the reference system of the technology objects tobe interconnected.
2 – Exclusive interface: Correct the configuration of the interconnected technology object.
3 – Interconnection request Add the missing interconnection to your technology object.
4 – Error during interface initialization: Contact the hotline.
5 – Interface not available on technology object: Contact the hotline.
6 – Circularity:Remove unnecessary interconnections.
7 – Execution level compatibility error: Correct the configuration of the interpolator task level of the technology objectsto be interconnected.
8 – Distribution initialization:Check the hardware configuration. Ensure that the distributed interactingdevices are linked in the bus configuration. In addition, the address areas thatare used by the devices for communication must be set up. The address areasare automatically set up when the project is compiled; only afterwards is thevalid hardware configuration available for downloading.
9 – Illegal TO status:Correct the configuration of the technology object, correct execution errors.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseDISABLE
Programmable local responsesDISABLE
AdditionObjectType
10-583� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
20008 Cannot assign USER_DEFAULT to system variables
CauseIt is not appropriate to assign USER_DEFAULT to a UserDefault system variable,because the variable references itself in this case.This prevents generation of a useful value during reading out. When this erroroccurs, the new Enum value is not assigned. The variable retains the old value.
RemedyUSER_DEFAULT is designed for use in technology commands.Avoid assigning it to system variables.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONE
20009 Reserved error
CauseThis error is not currently in use.
RemedyNot necessary, for information only.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseDISABLE
Programmable local responsesDISABLE
AdditionObjectType
10-584� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
20010 A restart is necessary to activate the configuration data
CauseThe configuration cannot be set to active, since data have been modified in such away that does not permit it. The technology object must be restarted to activate thedata.
Remedy
� Execute the technology object reset command, and set the activateRestartparameter to ACTIVATE_RESTART.
� Set the restartActivation system variable to ACTIVATE_RESTART.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDISABLE
AdditionObjectType
10-585� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
20011 Error when activating the configuration (category: /1/%d, error number: /2/%d)
CauseThis note indicates error conditions when activating the configuration. The errorconditions can be traced back to an incorrect or inconsistent configuration. Thetechnology objects perform a plausibility check on the configuration. Errors areidentified by the error codes below.If this information appears, the configuration will not be activated.
Meaning of alarm parameters
Category: Area in which the error occurred.
1–Command decoding
2–Interpolator
3–Controller
4–Manipulated variable output
5–Encoder system
6–Technology object
Error number: Specification of error
RemedyChange the configuration data.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDISABLE
AdditionObjectType
10-586� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
20012 Restart not executed (reason: /1/%d)
CauseTechnology object could not be restarted.
Meaning of alarm parameters
Reason:
1 – The technology object configuration does not allow a restart with the restartsystem variable. You can initiate the restart using the reset command.
2 – The technology object is not ready to be restarted.
3 – A configured condition for restarting the technology object is not met (e.g.,technology object must be disabled).
4 – Restart has not been executed or executed with the last programmedconfiguration of the technology object.
Remedy
� Work around the cause stated in the Reason parameter, or reload the project.
� Use the device diagnostics to establish whether technological alarms werereported and, if necessary, remedy the cause of the alarm.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDISABLE
AdditionObjectType
10-587� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
20014 At the logical address: /1/%d (optional log. address: /2/%d and bit no.: /3/%dof the enable output), a driver (type: /4/%d) could not be requested
CauseThe driver of a physical device is not available or is being used by another TO.
Meaning of alarm parameters
Logical address:
This is the address of the actuator driver configured on the technology object.
Logical address and bit number:
This specifies the address and bit number of the output enable bit
Type:
1–Actuator driver
2–Encoder driver
3–BitRead driver
4–BitWrite driver
5–ByteRead driver
6–ByteWrite driver
7–WordRead driver
8–WordWrite driver
9–DWordRead driver
10–DWordWrite driver
Remedy
� Check that the logical device was available at the time of the request or whetherit was being used by another technology object.
� Connect a suitable device.
� Check the device (function, connections, terminals).
� Check the topological configuration in HWConfig.
� Compare configuration of HWConfig and technology object.
� Contact the hotline.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseDISABLE
Programmable local responsesDISABLE
AdditionObjectType
10-588� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
30001 Illegal parameter (parameter index according to standard sequence in thesystem functions: /1/%d, command type: /4/%X)
CauseIllegal system function parameter, the command is aborted. The parameters indicate the position of the illegal system function parameteraccording to the standard sequence in the system functions and the command typeof an incorrectly entered parameter.
Meaning of alarm parameters
Parameter index:
Index of the first system function parameter that triggered this error (listedaccording to the standard sequence in the system functions).
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyChange the parameters.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDISABLE
AdditionObjectType
10-589� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
30002 Command aborted (reason: /1/%d, command type: /4/%X)
CauseExecution of the command was aborted before or during processing.This condition can arise as a result of loading a new command, resetting thecommand buffer, or an error state.
Meaning of alarm parameters
Reason:
1–Command buffer reset
2–Abort by another command
3–Aborted by a stop
4–Aborted by a higher-order stop
5–Abort by a pending error response
6–Aborted due to ambiguous commandId
7–Delayed acknowledgment
8–No actual value for axis (e.g., encoder or data bus not ready)
9–Aborted due to abnormal termination of a dependent command
10–Aborted due to active synchronous operation
11–Aborted due to active superimposed motion
12–Aborted due to active speed-controlled controller mode
13–Aborted due to active position-controlled controller mode
14–Aborted due to active motion to fixed end stop
15–Axis is not in pressure-limiting operation
16–Aborted due to active pressure-controlled operation
17–Aborted due to inactive pressure-controlled operation
18–Superimposed command is not permitted
19–Aborted due to error during cam access
20–Slave is not ready for operation
21–Error in slave synchronization
22–Aborted by command on slave
23–Aborted by stop on slave
24–Aborted by an active error response on the slave
25–No actual value for slave (e.g., encoder or data bus not ready)
26–Aborted by reset on slave
27–Master values are not valid
28–Active command in recursive TO interconnection
29–Aborted due to error during synchronization
30–Axis is in pressure-limiting operation
31–Maximum number of active commands exceeded
32–Aborted due to active correction command
33–Action only permissible in standstill
Command type:
Outputs the aborted command type. The command type is output as ahexadecimal integer value.
AdditionObjectType
10-590� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
RemedyReset command via program.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDISABLE
30003 Command aborted due to full command buffer (command type: /4/%X)
CauseThe command is not entered in the command buffer as the buffer is already full.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
Remedy
� Check the program flow.
� Typical cause: The ’nextCommand’ parameter is passed with the valueIMMEDIATELY. You need to synchronize the command sequence manually oruse another value for ’nextCommand’.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDISABLE
AdditionObjectType
10-591� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
30004 Unknown command (command type: /4/%X)
CauseThe active software tool does not support this command.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyCheck the versions of the engineering system and the runtime software.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDISABLE
AdditionObjectType
10-592� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
30005 Ambiguous commandId (number of commands with specified ID: /1/%d,command type: /4/%X)
CauseThe specified commandID refers to several commands.The specified action is performed for the command matching the specifiedcommandID that has been in the interpolator for the longest time. If nocorresponding command is found in the interpolator, the action refers to the nextcommand loaded in the interpolator.
Meaning of alarm parameters
Number of commands with specified ID:
Number of commands referenced by the specified commandId.
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyUse different commandIds for commands that are active simultaneously.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDISABLE
AdditionObjectType
10-593� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
30006 Cannot execute command due to current object state (command type: /4/%X)
CauseThe object is in the stop, error, or reset state and the command is not possible inthis object state.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
Remedy
� Check the object status.
� Check the permissible sequence of commands.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDISABLE
30007 The error cannot be reset due to its configuration
CauseThe alarm cannot be acknowledged at the present time or by the selected means.
Remedy
� Check the configured acknowledgment procedure.
� If necessary, change the acknowledgment procedure for the alarm.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDISABLE
AdditionObjectType
10-594� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
30008 A connection to a technology object required for this operation does notexist (command type: /4/%X)
CauseThe object connection required for this operation has not been configured.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyCheck the project configuration, or change the object connection in the command.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDISABLE
30009 Command rejected due to suspension of command decoding on addressedtechnology object (command type: /4/%X)
CauseCommand was rejected due to suspension of command decoding on theaddressed technology object.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
Remedy
� Check why the command was rejected.
� If necessary, acknowledge any active errors once you have corrected the causeof the error.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDISABLE
AdditionObjectType
10-595� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
30010 Command not available (command type: /4/%X)
CauseThe command is not available in this version of the runtime software.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyCheck the version of the runtime software.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDISABLE
30011 Parameter unavailable (parameter index according to standard sequence inthe system functions: /1/%d, command type: /4/%X)
CauseThe parameter is not available in this version of the runtime software, thecommand is therefore rejected. The parameters indicate the position according tothe standard sequence in the system functions and the command type of anincorrectly entered parameter.
Meaning of alarm parameters
Parameter index:
Index of the command parameter triggering this error according to the standardsequence in the system functions.
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyCheck the version of the runtime software.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDISABLE
AdditionObjectType
10-596� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
30012 Command cannot be started synchronously (command type: /4/%X)
CauseThe command cannot be used during a BEGIN_SYNC, END_SYNC sequencebecause it is a reset command or a command that has only one return value in theuser program.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyDo not use this command type during a BEGIN_SYNC, END_SYNC sequence.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDISABLE
AdditionObjectType
10-597� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
30013 Synchronous start of the command using IMMEDIATELY mergeMode(command type: /4/%X)
CauseWith synchronous command start, only merge modes that immediately override thecurrent command (IMMEDIATELY) and superimpose the current command(SUPERIMPOSED_MOTION_MERGE) can be used. If an illegal merge mode isprogrammed (e.g., SEQUENTIAL or NEXT_MOTION), the system automaticallychanges the merge mode to IMMEDIATELY and outputs this warning.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyProgram the command, which is to be started synchronously to immediatelyoverride the current command. To do this, enter the value IMMEDIATELY in the’mergeMode’ command parameter.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDISABLE
AdditionObjectType
10-598� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
30015 A technology required for this command was not configured (technology: /1/%d, command type: /4/%X)
CauseThe command cannot be selected in this technology object configuration.
Meaning of alarm parameters
Technology:
Not relevant
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyActivate the technology needed for the command.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDISABLE
AdditionObjectType
10-599� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
40001 Interface could not be activated (interface: 0x/1/%Xh)
CauseThe interface could not be activated as a connection to this interface has not beenconfigured.
Meaning of alarm parameters
Interface:
0x0001h: MotionIn1
0x0002h: MotionIn2
0x0004h: MotionIn3
0x0008h: MotionIn4
0x0010h: MotionOut
Remedy
� Check the command for activating the interface.
� Interconnect the interface to be activated.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDISABLE
AdditionObjectType
10-600� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
40002 Modulo configuration is not taken over from the interconnected outputvector
CauseThe modulo configuration could not be taken over from the interconnected outputvector.
Possible causes:
Multiple interconnection of the output vector with different modulo configurationsof the interconnected TO.
Interconnection of the output vector with a TO without modulo configuration.
Remedy
� Check the modulo configuration of the TO interconnected to the output vector.
� Disable transfer of the modulo configuration from the interconnected outputvector to the configuration data.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDISABLE
11-601� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
FixedGearType
Possible local responses
NONENo response
DECODE_STOPAbort command processing
FIXED_GEAR_DISABLEStop and abort all commands.
20001 Internal error (Parameter1: /1/%d, Parameter2: /2/%d, Parameter3: /3/%d,Parameter4: /4/%d)
CauseThis alarm indicates internal error states providing information about the cause andlocation of the error in association with the related error number.
Meaning of alarm parameters
Parameter1: Error source
Parameter2 to 4: Error number
RemedyA detailed description of the system error alarm is not provided. Should a systemerror of this type occur, note the alarm number, the alarm text, and the internalsystem error number specified in the alarm and contact: SIEMENS AG A&D MC, Hotline.
Acknowledgment / responsePower On / STOP
Default setting for local responseFIXED_GEAR_DISABLE
Programmable local responsesFIXED_GEAR_DISABLE
11
FixedGearType
11-602� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
20002 Insufficient memory (Parameter1: /1/%d, Parameter2: /2/%d, Parameter3:/3/%d, Parameter4: /4/%d)
CauseThe memory required by the system is no longer available. This alarm can occurboth during power up and after program calls.
Meaning of alarm parameters
Parameter1: Area in which the error occurred.
1–Command decoding
2–Interpolator
3–Controller
4–Manipulated variable output
5–Encoder system
6–Technology package
Parameters 2 to 4 are area-specific. They are not fully utilized by all areas.
Command decoding area:
Parameter2 and Parameter4 refer to the command in which the error occurred.
Parameter2: Command return value
Parameter4: Command type
Remedy
� Reduce the size of the ST code.
� Reduce the number of technology objects.
� Reduce the number of interpolation points for cams, if present.
Acknowledgment / responsePower On / STOP
Default setting for local responseFIXED_GEAR_DISABLE
Programmable local responsesFIXED_GEAR_DISABLE
FixedGearType
11-603� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
20003 No object configuration (Parameter1: /1/%d, Parameter2: /2/%d, Parameter3:/3/%d, Parameter4: /4/%d)
CauseError in system configuration. The configuration data for a software tool could notbe found.
Meaning of alarm parameters
Parameter1: Area in which the error occurred.
1–Command decoding
2–Interpolator
3–Controller
4–Manipulated variable output
5–Encoder system
Parameters 2 to 4 are area-specific. They are not fully utilized by all areas.
Command decoding area:
Parameter2 and Parameter4 refer to the command in which the error occurred.
Parameter2: Command return value
Parameter4: Command type
RemedyCheck the accuracy of the configuration data in your project. When commands arecalled on technology objects, the technology objects must be configured.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPFIXED_GEAR_DISABLE
FixedGearType
11-604� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
20004 At the logical address: /1/%d (bit number, if required: /2/%d) a driver (type:/3/%d) could be requested (error number: /4/%d)
CauseThe driver of a physical device or the device itself is not available.
Meaning of alarm parameters
Logical address:
This is the address configured on the technology object.
Bit number:
For bit driver only; bit number
Type:
1–Actuator driver
2–Encoder driver
3–BitRead driver
4–BitWrite driver
5–ByteRead driver
6–ByteWrite driver
7–WordRead driver
8–WordWrite driver
9–DWordRead driver
10–DWordWrite driver
Error number: Specification of error
Remedy
� Connect a suitable device.
� Check the device (function, connections, terminals).
� Check the topological configuration in HWConfig.
� Compare configuration of HWConfig and technology object.
� Contact the hotline.
Acknowledgment / responsePower On / START TechnologicalFaultTask
Default setting for local responseFIXED_GEAR_DISABLE
Programmable local responsesFIXED_GEAR_DISABLE
FixedGearType
11-605� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
20005 Device type: /3/%d, log. address: /1/%d faulty. (Bit: /2/%d, reason: 0x/4/%Xh)
CauseThe driver of a physical device or the device itself has failed or is faulty. When thisalarm occurs, the error cause must be evaluated in the external device (drive orencoder).
Meaning of alarm parameters
Type:
1–Actuator driver
2–Encoder driver
3–BitRead driver
4–BitWrite driver
5–ByteRead driver
6–ByteWrite driver
7–WordRead driver
8–WordWrite driver
9–DWordRead driver
10–DWordWrite driver
Logical address:This is the address configured on the technology object.
Bit number:For bit driver type=3 or 4 only; bit number
Reason:0–Not defined (e.g., for binary I/O)
� Type = 1
0x0001h: Fault message from drive (note: On PROFIBUS drives, whichsupport acyclic communication in accordance with PROFIdrive V3,the error number/numbers of the drives is/are displayed in thediagnostic buffer, e.g., on Masterdrives MC).
0x0002h: DP: Drive signal “control requested” failed
0x0004h: DP: Drive switched off itself
0x0008h: Slot for drive data is not available in the project
0x0010h: Actuator driver does not have a connection to the drive data
0x0020h: Actuator driver was not initialized during power up
0x0080h: DP: Difference between configuration data and drive parameters
0x4000h: DP: Drive on bus failed (station failure)
0x8000h: Sign of life of drive faulty or failed
FixedGearType
11-606� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
� Type = 2
0x0000h: The number of permissible changes in the actual value of the maximum velocity of the absolute-value encoder has beenexceeded
0x0001h: Fault message from encoder (note: The error number/numbers is/are displayed in the diagnosticbuffer)
0x0002h: General hardware error of encoder
0x0004h: Encoder contaminated
0x0008h: Slot for encoder data is not available in the project
0x0010h: Encoder driver does not have a connection to the encoder data
0x0020h: Encoder driver was not initialized during power up
0x0040h: Error when reading the absolute value of the encoder
0x0080h: DP: Difference between the configuration data and the encoder parameters
0x0100h: Zero mark monitoring of encoder
0x4000h: DP: Encoder on bus failed (station failure)
0x8000h: DP: Sign of life of encoder has malfunctioned or failed. (Note: For an encoder whose data are transferred in a drive message together with actuator data, the actuator sign of lifeapplies for the encoder, e.g., a standard message 3 in accordancewith PROFIdrive).
� Type = 3 to 10
0x0000h: Additional information, not assigned
Note:Codings for the reason of the failure can also occur in combination. Theindividual codings are then added to form a coding sum, which is displayed(e.g., 0x0005 = 0x0001 + 0x0004). A reason for failure marked as DP can only be present on PROFIBUS devices.
RemedyCheck the device with respect to function and connections (reason 0x0001,0x0002, 0x0004, 0x4000, 0x8000).
� Check the topological configuration in HW Config (with reason 0x0008).
� For PROFIBUS drives or encoders, compare the configuration of HWConfig, thetechnology object, and the drive parameter assignment.For:
Reason 0x0040:
– Compare the encoder type in the drive or encoder parameter P979 with theconfiguration data of the technology object.
FixedGearType
11-607� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
Reason 0x0080:
– Compare the message frame type in the drive or encoder parameter P922with HW Config and the configuration data of the technology object.
– Compare the encoder type, resolution, multiplier and, with absoluteencoders, the data length in the drive or encoder parameter P979 with theconfiguration data of the technology object.
– Compare the parameterization named in reason 0x8000 (reason 0x8000 canoccur as secondary fault).
Reason 0x8000:
– Compare the cycle clock parameters of HW Config (PROFIBUS line, SlaveOM for drive or encoder) and the execution system. Tmapc and servo mustbe parameterized with the same cycle clock period!
� System fault, contact the hotline (reason 0x0008, 0x0010, 0x0020).
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseFIXED_GEAR_DISABLE
Programmable local responsesFIXED_GEAR_DISABLE
FixedGearType
11-608� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
20006 Error in configuration (category: /1/%d, error number: /2/%d)
CauseThis alarm indicates error states caused by a faulty or inconsistent configuration.The technology objects perform a plausibility check on the configuration. Errors areidentified by the error codes below.
Meaning of alarm parameters
Category: Area in which the error occurred.
1–Command decoding
2–Interpolator
3–Controller
4–Manipulated variable output
5–Encoder system
6–Technology object
Error number: Specification of error
500 = “TO in illegal status for configuration”
501 = “More configuration data expected than received”
502 = “Invalid data in configuration”
503 = “Version conflict in configuration”
RemedyChange the configuration data.
Acknowledgment / responsePower On / START TechnologicalFaultTask
Default setting for local responseFIXED_GEAR_DISABLE
Programmable local responsesFIXED_GEAR_DISABLE
FixedGearType
11-609� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
20007 Interconnection error (category: /1/%d, context: /2/%d, context parameter1:/3/%d, context parameter2: /4/%d)
CauseThis alarm indicates errors in the interconnection of technology objects. When theinterconnection is established, the technology object verifies it on the basis of theinterface properties. Errors are classified by category.
Meaning of alarm parameters
Category:
1 – TO compatibility errorAn interconnection is to be established with a technology object that has beenconfigured with another reference system (e.g., output cam with rotaryreference system and linear axis).
2 – Exclusive interfaceMultiple interconnections are to be established for an interface intended forexclusive interconnection.
3 – Interconnection requirementThe technology object is waiting for an interconnection required for thesequence.
4 – Interface initialization errorErrors result from extended initialization sequences at interfaces andparameter exchange between interconnected interfaces.
5 – Interface not available on technology objectAn interface specified in the interconnection is not available on the technologyobject.
6 – CircularityThe interconnection on the technology object leads to circular communicationwithin the technology object (e.g., circular master/slave interconnection ofgearing axes, whereby a gearing axis used as a master is in turn the slave ofanother master, which is assigned the master setpoints generated on thisgearing axis directly or via additional interconnections).
7 – Sequence-level compatibility errorAn interconnection is to be established with a technology object that isexecuted in another interpolator level (e.g., output cam with IPO and axis withIPO_2).
8 – Distribution initializationWhen interconnecting technology objects that are distributed among differentdevices, an error occurred during initialization of the communication interface.
9 – Illegal TO statusThe technology object cannot be interconnected in the current state.
Context:
The context provides additional information about the error category for the TOinterconnection. Additional parameters can be provided for the error descriptionon a context-specific basis. Context and context parameter are output as aninteger value.
FixedGearType
11-610� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
Remedy
1 – Technology object compatibility error: Correct the configuration of the reference system of the technology objects tobe interconnected.
2 – Exclusive interface: Correct the configuration of the interconnected technology object.
3 – Interconnection request: Add the missing interconnection to your technology object.
4 – Error during interface initialization: Contact the hotline.
5 – Interface not available on technology object: Contact the hotline.
6 – Circularity:Remove unnecessary interconnections.
7 – Execution level compatibility error: Correct the configuration of the interpolator task level of the technology objectsto be interconnected.
8 – Distribution initialization:Check the hardware configuration. Ensure that the distributed interactingdevices are linked in the bus configuration. In addition, the address areas thatare used by the devices for communication must be set up. The address areasare automatically set up when the project is compiled; only afterwards is thevalid hardware configuration available for downloading.
9 – Illegal TO status:Correct the configuration of the technology object, correct execution errors.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseFIXED_GEAR_DISABLE
Programmable local responsesFIXED_GEAR_DISABLE
FixedGearType
11-611� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
20008 Cannot assign USER_DEFAULT to system variables
CauseIt is not appropriate to assign USER_DEFAULT to a UserDefault system variable,because the variable references itself in this case.This prevents generation of a useful value during reading out. When this erroroccurs, the new Enum value is not assigned. The variable retains the old value.
RemedyUSER_DEFAULT is designed for use in technology commands.Avoid assigning it to system variables.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONE
20009 Reserved error
CauseThis error is not currently in use.
RemedyNot necessary, for information only.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseFIXED_GEAR_DISABLE
Programmable local responsesFIXED_GEAR_DISABLE
FixedGearType
11-612� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
20010 A restart is necessary to activate the configuration data
CauseThe configuration cannot be set to active, since data have been modified in such away that does not permit it. The technology object must be restarted to activate thedata.
Remedy
� Execute the technology object reset command, and set the activateRestartparameter to ACTIVATE_RESTART.
� Set the restartActivation system variable to ACTIVATE_RESTART.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPFIXED_GEAR_DISABLE
FixedGearType
11-613� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
20011 Error when activating the configuration (category: /1/%d, error number:/2/%d)
CauseThis note indicates error conditions when activating the configuration. The errorconditions can be traced back to an incorrect or inconsistent configuration. Thetechnology objects perform a plausibility check on the configuration. Errors areidentified by the error codes below.If this information appears, the configuration will not be activated.
Meaning of alarm parameters
Category: Area in which the error occurred.
1–Command decoding
2–Interpolator
3–Controller
4–Manipulated variable output
5–Encoder system
6–Technology object
Error number: Specification of error
RemedyChange the configuration data.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPFIXED_GEAR_DISABLE
FixedGearType
11-614� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
20012 Restart not executed (reason: /1/%d)
CauseTechnology object could not be restarted.
Meaning of alarm parameters
Reason:
1–The technology object configuration does not allow a restart with the restartsystem variable. You can initiate the restart using the reset command.
2–The technology object is not ready to be restarted.
3–A configured condition for restarting the technology object is not met (e.g.,technology object must be disabled).
4–Restart has not been executed or executed with the last programmedconfiguration of the technology object.
Remedy
� Work around the cause stated in the Reason parameter, or reload the project.
� Use the device diagnostics to establish whether technological alarms werereported and, if necessary, remedy the cause of the alarm.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPFIXED_GEAR_DISABLE
FixedGearType
11-615� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
20014 At the logical address: /1/%d (optional log. address: /2/%d and bit no.: /3/%dof the enable output), a driver (type: /4/%d) could not be requested
CauseThe driver of a physical device is not available or is being used by another TO.
Meaning of alarm parameters
Logical address:
This is the address of the actuator driver configured on the technology object.
Logical address and bit number:
This specifies the address and bit number of the output enable bit.
Type:
1–Actuator driver
2–Encoder driver
3–BitRead driver
4–BitWrite driver
5–ByteRead driver
6–ByteWrite driver
7–WordRead driver
8–WordWrite driver
9–DWordRead driver
10–DWordWrite driver
Remedy
� Check that the logical device was available at the time of the request or whetherit was being used by another technology object.
� Connect a suitable device.
� Check the device (function, connections, terminals).
� Check the topological configuration in HWConfig.
� Compare configuration of HWConfig and technology object.
� Contact the hotline.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseFIXED_GEAR_DISABLE
Programmable local responsesFIXED_GEAR_DISABLE
FixedGearType
11-616� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
30001 Illegal parameter (parameter index according to standard sequence in thesystem functions: /1/%d, command type: /4/%X)
CauseIllegal system function parameter, the command is aborted. The parameters indicate the position of the illegal system function parameteraccording to the standard sequence in the system functions and the command typeof an incorrectly entered parameter.
Meaning of alarm parameters
Parameter index:
Index of the first system function parameter that triggered this error (listedaccording to the standard sequence in the system functions).
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyChange the parameters.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPFIXED_GEAR_DISABLE
FixedGearType
11-617� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
30002 Command aborted (reason: /1/%d, command type: /4/%X)
CauseExecution of the command was aborted before or during processing.This condition can arise as a result of loading a new command, resetting thecommand buffer, or an error state.
Meaning of alarm parameters
Reason:
1–Command buffer reset
2–Abort by another command
3–Aborted by a stop
4–Aborted by a higher-order stop
5–Abort by a pending error response
6–Aborted due to ambiguous commandId
7–Delayed acknowledgment
8–No actual value for axis (e.g., encoder or data bus not ready)
9–Aborted due to abnormal termination of a dependent command
10–Aborted due to active synchronous operation
11–Aborted due to active superimposed motion
12–Aborted due to active speed-controlled controller mode
13–Aborted due to active position-controlled controller mode
14–Aborted due to active motion to fixed end stop
15–Axis is not in pressure-limiting operation
16–Aborted due to active pressure-controlled operation
17–Aborted due to inactive pressure-controlled operation
18–Superimposed command is not permitted
19–Aborted due to error during cam access
20–Slave is not ready for operation
21–Error in slave synchronization
22–Aborted by command on slave
23–Aborted by stop on slave
24–Aborted by an active error response on the slave
25–No actual value for slave (e.g., encoder or data bus not ready)
26–Aborted by reset on slave
27–Master values are not valid
28–Active command in recursive TO interconnection
29–Aborted due to error during synchronization
30-Axis is in pressure–limiting operation
31–Maximum number of active commands exceeded
32–Aborted due to active correction command
33–Action only permissible in standstill
Command type:
Outputs the aborted command type. The command type is output as ahexadecimal integer value.
FixedGearType
11-618� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
RemedyReset command via program.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPFIXED_GEAR_DISABLE
30003 Command aborted due to full command buffer (command type: /4/%X)
CauseThe command is not entered in the command buffer as the buffer is already full.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
Remedy
� Check the program flow.
� Typical cause: The ’nextCommand’ parameter is passed with the valueIMMEDIATELY. You need to synchronize the command sequence manually oruse another value for ’nextCommand’.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPFIXED_GEAR_DISABLE
FixedGearType
11-619� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
30004 Unknown command (command type: /4/%X)
CauseThe active software tool does not support this command.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyCheck the versions of the engineering system and the runtime software.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPFIXED_GEAR_DISABLE
FixedGearType
11-620� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
30005 Ambiguous commandId (number of commands with specified ID: /1/%d,command type: /4/%X)
CauseThe specified commandID refers to several commands.The specified action is performed for the command matching the specifiedcommandID that has been in the interpolator for the longest time. If nocorresponding command is found in the interpolator, the action refers to the nextcommand loaded in the interpolator.
Meaning of alarm parameters
Number of commands with specified ID:
Number of commands referenced by the specified commandId.
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyUse different commandIds for commands that are active simultaneously.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPFIXED_GEAR_DISABLE
FixedGearType
11-621� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
30006 Cannot execute command due to current object state (command type: /4/%X)
CauseThe object is in the stop, error, or reset state and the command is not possible inthis object state.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
Remedy
� Check the object status.
� Check the permissible sequence of commands.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPFIXED_GEAR_DISABLE
30007 The error cannot be reset due to its configuration
CauseThe alarm cannot be acknowledged at the present time or by the selected means.
Remedy
� Check the configured acknowledgment procedure.
� If necessary, change the acknowledgment procedure for the alarm.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPFIXED_GEAR_DISABLE
FixedGearType
11-622� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
30008 A connection to a technology object required for this operation does notexist (command type: /4/%X)
CauseThe object connection required for this operation has not been configured.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyCheck the project configuration, or change the object connection in the command.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPFIXED_GEAR_DISABLE
FixedGearType
11-623� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
30009 Command rejected due to suspension of command decoding on addressedtechnology object (command type: /4/%X)
CauseCommand was rejected due to suspension of command decoding on theaddressed technology object.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
Remedy
� Check why the command was rejected.
� If necessary, acknowledge any active errors once you have corrected the causeof the error.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPFIXED_GEAR_DISABLE
30010 Command not available (command type: /4/%X)
CauseThe command is not available in this version of the runtime software.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyCheck the version of the runtime software.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPFIXED_GEAR_DISABLE
FixedGearType
11-624� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
30011 Parameter unavailable (parameter index according to standard sequence inthe system functions: /1/%d, command type: /4/%X)
CauseThe parameter is not available in this version of the runtime software, thecommand is therefore rejected. The parameters indicate the position according tothe standard sequence in the system functions and the command type of anincorrectly entered parameter.
Meaning of alarm parameters
Parameter index:
Index of the command parameter triggering this error according to the standardsequence in the system functions.
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyCheck the version of the runtime software.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPFIXED_GEAR_DISABLE
FixedGearType
11-625� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
30012 Command cannot be started synchronously (command type: /4/%X)
CauseThe command cannot be used during a BEGIN_SYNC, END_SYNC sequencebecause it is a reset command or a command that has only one return value in theuser program.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyDo not use this command type during a BEGIN_SYNC, END_SYNC sequence.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPFIXED_GEAR_DISABLE
FixedGearType
11-626� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
30013 Synchronous start of the command using IMMEDIATELY mergeMode(command type: /4/%X)
CauseWith synchronous command start, only merge modes that immediately override thecurrent command (IMMEDIATELY) and superimpose the current command(SUPERIMPOSED_MOTION_MERGE) can be used. If an illegal merge mode isprogrammed (e.g., SEQUENTIAL or NEXT_MOTION), the system automaticallychanges the merge mode to IMMEDIATELY and outputs this warning.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyProgram the command, which is to be started synchronously to immediatelyoverride the current command. To do this, enter the value IMMEDIATELY in the’mergeMode’ command parameter.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPFIXED_GEAR_DISABLE
FixedGearType
11-627� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
30015 A technology required for this command was not configured (technology:/1/%d, command type: /4/%X)
CauseThe command cannot be selected in this technology object configuration.
Meaning of alarm parameters
Technology:
Not relevant
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyActivate the technology needed for the command.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPFIXED_GEAR_DISABLE
FixedGearType
11-628� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
40001 Interface could not be activated (interface: 0x/1/%Xh)
CauseThe interface could not be activated as a connection to this interface has not beenconfigured.
Meaning of alarm parameters
Interface:
0x0001h: MotionIn
0x0010h: MotionOut
Remedy
� Check the command for activating the interface.
� Interconnect the interface to be activated.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPFIXED_GEAR_DISABLE
FixedGearType
11-629� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
40002 Modulo configuration is not taken over from the interconnected outputvector
CauseThe modulo configuration could not be taken over from the interconnected outputvector.
Possible causes:
Multiple interconnection of the output vector with different modulo configurationsof the interconnected TO.
Interconnection of the output vector with a TO without modulo configuration.
Remedy
� Check the modulo configuration of the TO interconnected to the output vector.
� Disable transfer of the modulo configuration from the interconnected outputvector to the configuration data.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPFIXED_GEAR_DISABLE
50008 Long-term stability cannot be maintained for the gearing
CauseThe programmed gear ratio of numerator and denominator cannot be kept stableover the long term.
Remedy
� Resynchronize in the event of inaccuracies.
� Reduce the gear ratio.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPFIXED_GEAR_DISABLE
FixedGearType
11-630� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
50101 The programmed master is not configured
CauseThe programmed master has not been configured as master for synchronousoperation.
Remedy
� Check the master configuration in synchronous operation.
� Check the programmed master.
� Add the appropriate master.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPFIXED_GEAR_DISABLE
50102 Master is not assigned or configured or is defective (reason: /1/%d)
CauseA command on the following object cannot be executed because of an error in datacommunication with the master.
Meaning of alarm parameters
Reason 1: No master has been assigned to synchronous operation.
Remedy
� Create the missing master assignment (reason 1).
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseFIXED_GEAR_DISABLE
Programmable local responsesFIXED_GEAR_DISABLE
12-631� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
FormulaObjectType
Possible local responses
NONENo response
DISABLEStop TO execution
STOP_SPECIFIC_FORMULAStop execution of a spec. formula
STOP_ALL_FORMULAStop execution of all formulas
20001 Internal error (Parameter1: /1/%d, Parameter2: /2/%d, Parameter3: /3/%d,Parameter4: /4/%d)
CauseThis alarm indicates internal error states providing information about the cause andlocation of the error in association with the related error number.
Meaning of alarm parameters
Parameter1: Error source
Parameter2 to 4: Error number
RemedyA detailed description of the system error alarm is not provided. Should a systemerror of this type occur, note the alarm number, the alarm text, and the internalsystem error number specified in the alarm and contact: SIEMENS AG A&D MC, Hotline.
Acknowledgment / responsePower On / STOP
Default setting for local responseDISABLE
Programmable local responsesDISABLE
12
FormulaObjectType
12-632� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
20002 Insufficient memory (Parameter1: /1/%d, Parameter2: /2/%d, Parameter3:/3/%d, Parameter4: /4/%d)
CauseThe memory required by the system is no longer available. This alarm can occurboth during power up and after program calls.
Meaning of alarm parameters
Parameter1: Area in which the error occurred.
1–Command decoding
2–Interpolator
3–Controller
4–Manipulated variable output
5–Encoder system
6–Technology package
Parameters 2 to 4 are area-specific. They are not fully utilized by all areas.
Command decoding area:
Parameter2 and Parameter4 refer to the command in which the error occurred.
Parameter2: Command return value
Parameter4: Command type
Remedy
� Reduce the size of the ST code.
� Reduce the number of technology objects.
� Reduce the number of interpolation points for cams, if present.
Acknowledgment / responsePower On / STOP
Default setting for local responseDISABLE
Programmable local responsesDISABLE
FormulaObjectType
12-633� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
20003 No object configuration (Parameter1: /1/%d, Parameter2: /2/%d, Parameter3:/3/%d, Parameter4: /4/%d)
CauseError in system configuration. The configuration data for a software tool could notbe found.
Meaning of alarm parameters
Parameter1: Area in which the error occurred.
1–Command decoding
2–Interpolator
3–Controller
4–Manipulated variable output
5–Encoder system
Parameters 2 to 4 are area-specific. They are not fully utilized by all areas.
Command decoding area:
Parameter2 and Parameter4 refer to the command in which the error occurred.
Parameter2: Command return value
Parameter4: Command type
RemedyCheck the accuracy of the configuration data in your project. When commands arecalled on technology objects, the technology objects must be configured.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDISABLE
FormulaObjectType
12-634� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
20004 At the logical address: /1/%d (bit number, if required: /2/%d) a driver (type:/3/%d) could be requested (error number: /4/%d)
CauseThe driver of a physical device or the device itself is not available.
Meaning of alarm parameters
Logical address:
This is the address configured on the technology object.
Bit number:
For bit driver only; bit number
Type:
1–Actuator driver
2–Encoder driver
3–BitRead driver
4–BitWrite driver
5–ByteRead driver
6–ByteWrite driver
7–WordRead driver
8–WordWrite driver
9–DWordRead driver
10–DWordWrite driver
Error number: Specification of error
Remedy
� Connect a suitable device.
� Check the device (function, connections, terminals).
� Check the topological configuration in HWConfig.
� Compare configuration of HWConfig and technology object.
� Contact the hotline.
Acknowledgment / responsePower On / START TechnologicalFaultTask
Default setting for local responseDISABLE
Programmable local responsesDISABLE
FormulaObjectType
12-635� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
20005 Device type: /3/%d, log. address: /1/%d faulty. (Bit: /2/%d, reason: 0x/4/%Xh)
CauseThe driver of a physical device or the device itself has failed or is faulty. When thisalarm occurs, the error cause must be evaluated in the external device (drive orencoder).
Meaning of alarm parameters
Type:
1–Actuator driver
2–Encoder driver
3–BitRead driver
4–BitWrite driver
5–ByteRead driver
6–ByteWrite driver
7–WordRead driver
8–WordWrite driver
9–DWordRead driver
10–DWordWrite driver
Logical address:This is the address configured on the technology object.
Bit number:For bit driver type = 3 or 4 only; bit number
Reason:0–Not defined (e.g., for binary I/O)
� Type = 1
0x0001h: Fault message from drive (note: On PROFIBUS drives, whichsupport acyclic communication in accordance with PROFIdrive V3,the error number/numbers of the drives is/are displayed in thediagnostic buffer, .g., on Masterdrives MC).
0x0002h: DP: Drive signal “control requested” failed
0x0004h: DP: Drive switched off itself
0x0008h: Slot for drive data is not available in the project
0x0010h: Actuator driver does not have a connection to the drive data
0x0020h: Actuator driver was not initialized during power up
0x0080h: DP: Difference between configuration data and drive parameters
0x4000h: DP: Drive on bus failed (station failure)
0x8000h: Sign of life of drive faulty or failed
FormulaObjectType
12-636� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
� Type = 2
0x0000h: The number of permissible changes in the actual value of the maximum velocity of the absolute-value encoder has beenexceeded.
0x0001h: Fault message from encoder (note: The error number/numbersis/are displayed in the diagnostic buffer).
0x0002h: General hardware error of encoder
0x0004h: Encoder contaminated
0x0008h: Slot for encoder data is not available in the project
0x0010h: Encoder driver does not have a connection to the encoder data
0x0020h: Encoder driver was not initialized during power up
0x0040h: Error when reading the absolute value of the encoder
0x0080h: DP: Difference between the configuration data and the encoderparameters
0x0100h: Zero mark monitoring of encoder
0x4000h: DP: Encoder on bus failed (station failure)
0x8000h: DP: Sign of life of encoder has malfunctioned or failed. (Note: For an encoder whose data are transferred in a drivemessage together with actuator data, the actuator sign of lifeapplies for the encoder, e.g., a standard message 3 in accordancewith PROFIdrive).
� Type = 3 to 10
0x0000h: Additional information, not assigned
Note:Codings for the reason of the failure can also occur in combination. Theindividual codings are then added to form a coding sum, which is displayed(e.g., 0x0005 = 0x0001 + 0x0004). A reason for failure marked as DP can only be present on PROFIBUS devices.
RemedyCheck the device with respect to function and connections (reason 0x0001,0x0002, 0x0004, 0x4000, 0x8000).
� Check the topological configuration in HW Config (with reason 0x0008).
� For PROFIBUS drives or encoders, compare the configuration of HWConfig, thetechnology object, and the drive parameter assignment.For:
Reason 0x0040:
– Compare the encoder type in the drive or encoder parameter P979 with theconfiguration data of the technology object.
FormulaObjectType
12-637� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
Reason 0x0080:
– Compare the message frame type in the drive or encoder parameter P922with HW Config and the configuration data of the technology object.
– Compare the encoder type, resolution, multiplier and, with absoluteencoders, the data length in the drive or encoder parameter P979 with theconfiguration data of the technology object.
– Compare the parameterization named in reason 0x8000 (reason 0x8000 canoccur as secondary fault).
Reason 0x8000:
– Compare the cycle clock parameters of HW Config (PROFIBUS line, SlaveOM for drive or encoder) and the execution system. Tmapc and servo mustbe parameterized with the same cycle clock period!
� System fault, contact the hotline (reason 0x0008, 0x0010, 0x0020).
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseDISABLE
Programmable local responsesDISABLE
FormulaObjectType
12-638� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
20006 Error in configuration (category: /1/%d, error number: /2/%d)
CauseThis alarm indicates error states caused by a faulty or inconsistent configuration.The technology objects perform a plausibility check on the configuration. Errors areidentified by the error codes below.
Meaning of alarm parameters
Category: Area in which the error occurred.
1–Command decoding
2–Interpolator
3–Controller
4–Manipulated variable output
5–Encoder system
6–Technology object
Error number: Specification of error
500 = “TO in illegal status for configuration”
501 = “More configuration data expected than received”
502 = “Invalid data in configuration”
503 = “Version conflict in configuration”
RemedyChange the configuration data.
Acknowledgment / responsePower On / START TechnologicalFaultTask
Default setting for local responseDISABLE
Programmable local responsesDISABLE
FormulaObjectType
12-639� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
20007 Interconnection error (category: /1/%d, context: /2/%d, context parameter1:/3/%d, context parameter2: /4/%d)
CauseThis alarm indicates errors in the interconnection of technology objects. When theinterconnection is established, the technology object verifies it on the basis of theinterface properties. Errors are classified by category.
Meaning of alarm parameters
Category:
1 – TO compatibility errorAn interconnection is to be established with a technology object that has beenconfigured with another reference system (e.g., output cam with rotaryreference system and linear axis).
2 – Exclusive interfaceMultiple interconnections are to be established for an interface intended forexclusive interconnection.
3 – Interconnection requirementThe technology object is waiting for an interconnection required for thesequence.
4 – Interface initialization errorErrors result from extended initialization sequences at interfaces andparameter exchange between interconnected interfaces.
5 – Interface not available on technology objectAn interface specified in the interconnection is not available on the technologyobject.
6 – CircularityThe interconnection on the technology object leads to circular communicationwithin the technology object (e.g., circular master/slave interconnection ofgearing axes, whereby a gearing axis used as a master is in turn the slave ofanother master, which is assigned the master setpoints generated on thisgearing axis directly or via additional interconnections).
7 – Sequence-level compatibility errorAn interconnection is to be established with a technology object that isexecuted in another interpolator level (e.g., output cam with IPO and axis withIPO_2).
8 – Distribution initializationWhen interconnecting technology objects that are distributed among differentdevices, an error occurred during initialization of the communication interface.
9 – Illegal TO statusThe technology object cannot be interconnected in the current state.
Context:
The context provides additional information about the error category for the TOinterconnection. Additional parameters can be provided for the error descriptionon a context-specific basis. Context and context parameter are output as aninteger value.
FormulaObjectType
12-640� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
Remedy
1 – Technology object compatibility error: Correct the configuration of the reference system of the technology objects tobe interconnected.
2 – Exclusive interface: Correct the configuration of the interconnected technology object.
3 – Interconnection request: Add the missing interconnection to your technology object.
4 – Error during interface initialization: Contact the hotline.
5 – Interface not available on technology object: Contact the hotline.
6 – Circularity:Remove unnecessary interconnections.
7 – Execution level compatibility error: Correct the configuration of the interpolator task level of the technology objectsto be interconnected.
8 – Distribution initialization:Check the hardware configuration. Ensure that the distributed interactingdevices are linked in the bus configuration. In addition, the address areas thatare used by the devices for communication must be set up. The address areasare automatically set up when the project is compiled; only afterwards is thevalid hardware configuration available for downloading.
9 – Illegal TO status:Correct the configuration of the technology object, correct execution errors.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseDISABLE
Programmable local responsesDISABLE
FormulaObjectType
12-641� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
20008 Cannot assign USER_DEFAULT to system variables
CauseIt is not appropriate to assign USER_DEFAULT to a UserDefault system variable,because the variable references itself in this case.This prevents generation of a useful value during reading out. When this erroroccurs, the new Enum value is not assigned. The variable retains the old value.
RemedyUSER_DEFAULT is designed for use in technology commands.Avoid assigning it to system variables.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONE
20009 Reserved error
CauseThis error is not currently in use.
RemedyNot necessary, for information only.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseDISABLE
Programmable local responsesDISABLE
FormulaObjectType
12-642� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
20010 A restart is necessary to activate the configuration data
CauseThe configuration cannot be set to active, since data have been modified in such away that does not permit it. The technology object must be restarted to activate thedata.
Remedy
� Execute the technology object reset command, and set the activateRestartparameter to ACTIVATE_RESTART.
� Set the restartActivation system variable to ACTIVATE_RESTART.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDISABLE
FormulaObjectType
12-643� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
20011 Error when activating the configuration (category: /1/%d, error number:/2/%d)
CauseThis note indicates error conditions when activating the configuration. The errorconditions can be traced back to an incorrect or inconsistent configuration. Thetechnology objects perform a plausibility check on the configuration. Errors areidentified by the error codes below.If this information appears, the configuration will not be activated.
Meaning of alarm parameters
Category: Area in which the error occurred.
1–Command decoding
2–Interpolator
3–Controller
4–Manipulated variable output
5–Encoder system
6–Technology object
Error number: Specification of error
RemedyChange the configuration data.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDISABLE
FormulaObjectType
12-644� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
20012 Restart not executed (reason: /1/%d)
CauseTechnology object could not be restarted.
Meaning of alarm parameters
Reason:
1–The technology object configuration does not allow a restart with the restartsystem variable. You can initiate the restart using the reset command.
2–The technology object is not ready to be restarted.
3–A configured condition for restarting the technology object is not met (e.g.,technology object must be disabled).
4–Restart has not been executed or executed with the last programmedconfiguration of the technology object.
Remedy
� Work around the cause stated in the Reason parameter, or reload the project.
� Use the device diagnostics to establish whether technological alarms werereported and, if necessary, remedy the cause of the alarm.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDISABLE
FormulaObjectType
12-645� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
20014 At the logical address: /1/%d (optional log. address: /2/%d and bit no.: /3/%dof the enable output), a driver (type: /4/%d) could not be requested
CauseThe driver of a physical device is not available or is being used by another TO.
Meaning of alarm parameters
Logical address:
This is the address of the actuator driver configured on the technology object.
Logical address and bit number:
This specifies the address and bit number of the output enable bit.
Type:
1–Actuator driver
2–Encoder driver
3–BitRead driver
4–BitWrite driver
5–ByteRead driver
6–ByteWrite driver
7–WordRead driver
8–WordWrite driver
9–DWordRead driver
10–DWordWrite driver
Remedy
� Check that the logical device was available at the time of the request or whetherit was being used by another technology object.
� Connect a suitable device.
� Check the device (function, connections, terminals).
� Check the topological configuration in HWConfig.
� Compare configuration of HWConfig and technology object.
� Contact the hotline.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseDISABLE
Programmable local responsesDISABLE
FormulaObjectType
12-646� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
30001 Illegal parameter (parameter index according to standard sequence in thesystem functions: /1/%d, command type: /4/%X)
CauseIllegal system function parameter, the command is aborted. The parameters indicate the position of the illegal system function parameteraccording to the standard sequence in the system functions and the command typeof an incorrectly entered parameter.
Meaning of alarm parameters
Parameter index:
Index of the first system function parameter that triggered this error (listedaccording to the standard sequence in the system functions).
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyChange the parameters.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDISABLE
FormulaObjectType
12-647� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
30002 Command aborted (reason: /1/%d, command type: /4/%X)
CauseExecution of the command was aborted before or during processing.This condition can arise as a result of loading a new command, resetting thecommand buffer, or an error state.
Meaning of alarm parameters
Reason:
1–Command buffer reset
2–Abort by another command
3–Aborted by a stop
4–Aborted by a higher-order stop
5–Abort by a pending error response
6–Aborted due to ambiguous commandId
7–Delayed acknowledgment
8–No actual value for axis (e.g., encoder or data bus not ready)
9–Aborted due to abnormal termination of a dependent command
10–Aborted due to active synchronous operation
11–Aborted due to active superimposed motion
12–Aborted due to active speed-controlled controller mode
13–Aborted due to active position-controlled controller mode
14–Aborted due to active motion to fixed end stop
15–Axis is not in pressure-limiting operation
16–Aborted due to active pressure-controlled operation
17–Aborted due to inactive pressure-controlled operation
18–Superimposed command is not permitted
19–Aborted due to error during cam access
20–Slave is not ready for operation
21–Error in slave synchronization
22–Aborted by command on slave
23–Aborted by stop on slave
24–Aborted by an active error response on the slave
25–No actual value for slave (e.g., encoder or data bus not ready)
26–Aborted by reset on slave
27–Master values are not valid
28–Active command in recursive TO interconnection
29–Aborted due to error during synchronization
30–Axis is in pressure-limiting operation
31–Maximum number of active commands exceeded
32–Aborted due to active correction command
33–Action only permissible in standstill
Command type:
Outputs the aborted command type. The command type is output as ahexadecimal integer value.
FormulaObjectType
12-648� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
RemedyReset command via program.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDISABLE
30003 Command aborted due to full command buffer (command type: /4/%X)
CauseThe command is not entered in the command buffer as the buffer is already full.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
Remedy
� Check the program flow.
� Typical cause: The ’nextCommand’ parameter is passed with the valueIMMEDIATELY. You need to synchronize the command sequence manually oruse another value for ’nextCommand’.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDISABLE
FormulaObjectType
12-649� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
30004 Unknown command (command type: /4/%X)
CauseThe active software tool does not support this command.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyCheck the versions of the engineering system and the runtime software.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDISABLE
FormulaObjectType
12-650� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
30005 Ambiguous commandId (number of commands with specified ID: /1/%d,command type: /4/%X)
CauseThe specified commandID refers to several commands.The specified action is performed for the command matching the specifiedcommandID that has been in the interpolator for the longest time. If nocorresponding command is found in the interpolator, the action refers to the nextcommand loaded in the interpolator.
Meaning of alarm parameters
Number of commands with specified ID:
Number of commands referenced by the specified commandId.
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyUse different commandIds for commands that are active simultaneously.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDISABLE
FormulaObjectType
12-651� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
30006 Cannot execute command due to current object state (command type: /4/%X)
CauseThe object is in the stop, error, or reset state and the command is not possible inthis object state.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
Remedy
� Check the object status.
� Check the permissible sequence of commands.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDISABLE
30007 The error cannot be reset due to its configuration
CauseThe alarm cannot be acknowledged at the present time or by the selected means.
Remedy
� Check the configured acknowledgment procedure.
� If necessary, change the acknowledgment procedure for the alarm.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDISABLE
FormulaObjectType
12-652� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
30008 A connection to a technology object required for this operation does notexist (command type: /4/%X)
CauseThe object connection required for this operation has not been configured.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyCheck the project configuration, or change the object connection in the command.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDISABLE
30009 Command rejected due to suspension of command decoding on addressedtechnology object (command type: /4/%X)
CauseCommand was rejected due to suspension of command decoding on theaddressed technology object.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
Remedy
� Check why the command was rejected.
� If necessary, acknowledge any active errors once you have corrected the causeof the error.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDISABLE
FormulaObjectType
12-653� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
30010 Command not available (command type: /4/%X)
CauseThe command is not available in this version of the runtime software.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyCheck the version of the runtime software.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDISABLE
30011 Parameter unavailable (parameter index according to standard sequence inthe system functions: /1/%d, command type: /4/%X)
CauseThe parameter is not available in this version of the runtime software, thecommand is therefore rejected. The parameters indicate the position according tothe standard sequence in the system functions and the command type of anincorrectly entered parameter.
Meaning of alarm parameters
Parameter index:
Index of the command parameter triggering this error according to the standardsequence in the system functions.
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyCheck the version of the runtime software.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDISABLE
FormulaObjectType
12-654� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
30012 Command cannot be started synchronously (command type: /4/%X)
CauseThe command cannot be used during a BEGIN_SYNC, END_SYNC sequencebecause it is a reset command or a command that has only one return value in theuser program.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyDo not use this command type during a BEGIN_SYNC, END_SYNC sequence.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDISABLE
FormulaObjectType
12-655� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
30013 Synchronous start of the command using IMMEDIATELY mergeMode(command type: /4/%X)
CauseWith synchronous command start, only merge modes that immediately override thecurrent command (IMMEDIATELY) and superimpose the current command(SUPERIMPOSED_MOTION_MERGE) can be used. If an illegal merge mode isprogrammed (e.g., SEQUENTIAL or NEXT_MOTION), the system automaticallychanges the merge mode to IMMEDIATELY and outputs this warning.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyProgram the command, which is to be started synchronously to immediatelyoverride the current command. To do this, enter the value IMMEDIATELY in the’mergeMode’ command parameter.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDISABLE
FormulaObjectType
12-656� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
30015 A technology required for this command was not configured (technology:/1/%d, command type: /4/%X)
CauseThe command cannot be selected in this technology object configuration.
Meaning of alarm parameters
Technology:
Not relevant
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyActivate the technology needed for the command.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDISABLE
FormulaObjectType
12-657� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
40001 Interface could not be activated (interface: 0x/1/%Xh)
CauseThe interface could not be activated as a connection to this interface has not beenconfigured.
Meaning of alarm parameters
Interface:
0x000001h: MotionIn1
0x000002h: MotionIn2
0x000004h: MotionIn3
0x000010h: DINTIn1
0x000020h: DINTIn2
0x000040h: DINTIn3
0x000080h: DINTIn4
0x000100h: LREALIn1
0x000200h: LREALIn2
0x000400h: LREALIn3
0x000800h: LREALIn4
0x001000h: MotionOut1
0x002000h: MotionOut2
0x004000h: MotionOut3
0x010000h: DINTOut1
0x020000h: DINTOut2
0x040000h: DINTOut3
0x080000h: DINTOut4
0x100000h: LREALOut1
0x200000h: LREALOut2
0x400000h: LREALOut3
0x800000h: LREALOut4
Remedy
� Check the command for activating the interface.
� Interconnect the interface to be activated.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDISABLESTOP_ALL_FORMULA
FormulaObjectType
12-658� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
40301 Error when translating a formula expression (formula number: /1/%d, reason:/2/%d)
CauseAn error occurred when translating a formula expression.
Meaning of alarm parametersFormula number:
Reason:
1: – Fatal PARSER error
2: – Fatal EXPRESSION error
3: – Character unknown
4: – Illegal value specified for data type
5: – Expression expected
6: – Variable identifier expected
7: – Type conflict in expression
8: – Variable cannot be accessed
9: – Return value expected
10: – Function argument expected
11: – Number of arguments when called does not tally with declaration
12: – Function parameter has no default value
13: – Constant value outside definition range
14: – Cannot be divided by “0”
15: – Function parameter already in call
16: – Type conflict in expression (conversion not possible)
17: – Type conflict in expression (operation incompatible with data type)
18: – Mixed use of function argument assignments and settingparameters not permitted
19: – Variable must be directly accessible input or output I/O
20: – Syntax error
21: – Construct not supported in this version
Remedy
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseDISABLE
Programmable local responsesNONEDISABLESTOP_ALL_FORMULA
FormulaObjectType
12-659� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
40302 Warning when translating a formula expression (formula number: /1/%d,reason: /2/%d)
CauseA warning occurred when translating a formula expression.
Meaning of alarm parameters
Formula number:
Number of formula, which triggered this error
Reason:
1: – Data type of comparison operation not specified
2: – Constant rounded to next value that can be displayed
3: – Data type conversion between signed and unsigned
Remedy
Acknowledgment / responseReset fault memory / NONE
Default setting for local responseNONE
Programmable local responsesNONEDISABLESTOP_ALL_FORMULA
40303 Division by ’0’ when calculating a formula expression (formula number:/1/%d)
CauseA division by ’0’ occurred when calculating a formula expression.
Meaning of alarm parameters
Formula number:
Number of formula, which triggered this error
RemedyCheck/change the associated formula expression.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseDISABLE
Programmable local responsesDISABLESTOP_SPECIFIC_FORMULASTOP_ALL_FORMULA
FormulaObjectType
12-660� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
40304 Overflow when calculating a formula expression (formula number: /1/%d)
CauseAn overflow occurred when calculating a formula expression.
Meaning of alarm parameters
Formula number:
Number of formula, which triggered this error
RemedyCheck/change the associated formula expression.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseDISABLE
Programmable local responsesDISABLESTOP_SPECIFIC_FORMULASTOP_ALL_FORMULA
40305 Underflow when calculating a formula expression (formula number: /1/%d)
CauseAn underflow occurred when calculating a formula expression.
Meaning of alarm parameters
Formula number:
Number of formula, which triggered this error
RemedyCheck/change the associated formula expression.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseDISABLE
Programmable local responsesDISABLESTOP_SPECIFIC_FORMULASTOP_ALL_FORMULA
FormulaObjectType
12-661� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
40306 Function result when calculating a formula expression (formula number:/1/%d)
CauseThe result of a calculation in the formula expression is not defined (e.g., root fromnegative number).
Meaning of alarm parameters
Formula number:Number of formula, which triggered this error
RemedyCheck/change the function arguments in the associated formula expression.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseDISABLE
Programmable local responsesDISABLESTOP_SPECIFIC_FORMULASTOP_ALL_FORMULA
FormulaObjectType
12-662� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
40307 Invalid formula number specified (formula number: /1/%d, reason: /2/%d)
CauseAn invalid formula number has been specified.
Meaning of alarm parameters
Formula number:
Number of formula, which triggered this error
Reason:
1: The formula number is outside the permissible range. Valid formula numbers are0 (predefined zero formula, which cannot be overwritten), 1 to 34 (formulas,which can be defined).
2: A formula with the specified number has already been assigned to an output andcan therefore not be redefined.
3: A formula with the specified number has not been defined.
Remedy
� Select a valid formula number.
� Before assigning a formula to an output, define a formula with the specifiednumber.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseDISABLE
Programmable local responsesNONEDISABLESTOP_ALL_FORMULA
13-663� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
ControllerObjectType
Possible local responses
NONENo response
DECODE_STOPAbort command processing
CONTROL_STOPStop controller
DISABLE_CONTROLLERDisable controller object
20001 Internal error (Parameter1: /1/%d, Parameter2: /2/%d, Parameter3: /3/%d,Parameter4: /4/%d)
CauseThis alarm indicates internal error states providing information about the cause andlocation of the error in association with the related error number.
Meaning of alarm parameters
Parameter1: Error source
Parameter2 to 4: Error number
RemedyA detailed description of the system error alarm is not provided. Should a systemerror of this type occur, note the alarm number, the alarm text, and the internalsystem error number specified in the alarm and contact: SIEMENS AG A&D MC, Hotline.
Acknowledgment / responsePower On / STOP
Default setting for local responseDISABLE_CONTROLLER
Programmable local responsesDISABLE_CONTROLLER
13
ControllerObjectType
13-664� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
20002 Insufficient memory (Parameter1: /1/%d, Parameter2: /2/%d, Parameter3: /3/%d, Parameter4: /4/%d)
CauseThe memory required by the system is no longer available. This alarm can occurboth during power up and after program calls.
Meaning of alarm parameters
Parameter1: Area in which the error occurred.
1–Command decoding
2–Config manager
3–Sequential control
4–Controller
5–Identification
6–Technology package
Parameters 2 to 4 are area-specific. They are not fully utilized by all areas.
Command decoding area:
Parameter2 and Parameter4 refer to the command in which the error occurred.
Parameter2: Command return value
Parameter4: Command type
Remedy
� Reduce the size of the ST code.
� Reduce the number of technology objects.
� Reduce the number of interpolation points for cams, if present.
Acknowledgment / responsePower On / STOP
Default setting for local responseDISABLE_CONTROLLER
Programmable local responsesDISABLE_CONTROLLER
ControllerObjectType
13-665� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
20003 No object configuration (Parameter1: /1/%d, Parameter2: /2/%d, Parameter3: /3/%d, Parameter4: /4/%d)
CauseError in system configuration. The configuration data for a software tool could notbe found.
Meaning of alarm parameters
Parameter1: Area in which the error occurred.
1–Command decoding
2–Config manager
3–Sequential control
4–Controller
5–Identification
6–Technology package
Parameters 2 to 4 are area-specific. They are not fully utilized by all areas.
Command decoding area:
Parameter2 and Parameter4 refer to the command in which the error occurred.
Parameter2: Command return value
Parameter4: Command type
RemedyCheck the accuracy of the configuration data in your project. When commands arecalled on technology objects, the technology objects must be configured.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONECONTROL_STOPDECODE_STOPDISABLE_CONTROLLER
ControllerObjectType
13-666� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
20004 At the logical address: /1/%d (bit number, if required: /2/%d) a driver (type: /3/%d) could be requested (error number: /4/%d)
CauseThe driver of a physical device or the device itself is not available.
Meaning of alarm parameters
Logical address:
This is the address configured on the technology object.
Bit number:
For bit driver only; bit number
Type:
1–Actuator driver
2–Encoder driver
3–BitRead driver
4–BitWrite driver
5–ByteRead driver
6–ByteWrite driver
7–WordRead driver
8–WordWrite driver
9–DWordRead driver
10–DWordWrite driver
Error number: Specification of error
Not relevant
Remedy
� Connect a suitable device.
� Check the device (function, connections, terminals).
� Check the topological configuration in HWConfig.
� Compare configuration of HWConfig and technology object.
� Contact the hotline.
Acknowledgment / responsePower On / START TechnologicalFaultTask
Default setting for local responseDISABLE_CONTROLLER
Programmable local responsesDISABLE_CONTROLLER
ControllerObjectType
13-667� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
20005 Device type: /3/%d, log. address: /1/%d faulty. (Bit: /2/%d, reason: 0x/4/%Xh)
CauseThe driver of a physical device or the device itself has failed or is faulty. When thisalarm occurs, the error cause must be evaluated in the external device (drive orencoder).
Meaning of alarm parameters
Type:
1–Actuator driver
2–Encoder driver
3–BitRead driver
4–BitWrite driver
5–ByteRead driver
6–ByteWrite driver
7–WordRead driver
8–WordWrite driver
9–DWordRead driver
10–DWordWrite driver
Logical address:This is the address configured on the technology object.
Bit number:For bit driver type = 3 or 4 only; bit number
Reason:0–Not defined (e.g., for binary I/O)
� Type = 1
0x0001h: Fault message from drive (note: On PROFIBUS drives, which support acyclic communication in accordance with PROFIdrive V3, the error number/numbers of the drives is/are displayed in the diagnostic buffer, e.g., on Masterdrives MC).
0x0002h: DP: Drive signal “control requested” failed
0x0004h: DP: Drive switched off itself
0x0008h: Slot for drive data is not available in the project
0x0010h: Actuator driver does not have a connection to the drive data
0x0020h: Actuator driver was not initialized during power up
0x0080h: DP: Difference between configuration data and drive parameters
0x4000h: DP: Drive on bus failed (station failure)
0x8000h: Sign of life of drive faulty or failed
ControllerObjectType
13-668� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
� Type = 2
0x0000h: The number of permissible changes in the actual value of the maximum velocity of the absolute-value encoder has been exceeded
0x0001h: Fault message from encoder (note: The error number/numbers is/are displayed in the diagnostic buffer)
0x0002h: General hardware error of encoder
0x0004h: Encoder contaminated
0x0008h: Slot for encoder data is not available in the project
0x0010h: Encoder driver does not have a connection to the encoder data
0x0020h: Encoder driver was not initialized during power up
0x0040h: Error when reading the absolute value of the encoder
0x0080h: DP: Difference between the configuration data and the encoder parameters
0x0100h: Zero mark monitoring of encoder
0x4000h: DP: Encoder on bus failed (station failure)
0x8000h: DP: Sign of life of encoder has malfunctioned or failed. (Note: For an encoder whose data are transferred in a drive message together with actuator data, the actuator sign of life applies for the encoder, e.g., a standard message 3 in accordance with PROFIdrive).
� Type = 3 to 10
0x0000h: Additional information, not assigned
Note:Codings for the reason of the failure can also occur in combination. Theindividual codings are then added to form a coding sum, which is displayed(e.g., 0x0005 = 0x0001 + 0x0004). A reason for failure marked as DP can only be present on PROFIBUS devices.
RemedyCheck the device with respect to function and connections (reason 0x0001,0x0002, 0x0004, 0x4000, 0x8000).
� Check the topological configuration in HW Config (with reason 0x0008).
� For PROFIBUS drives or encoders, compare the configuration of HWConfig, thetechnology object, and the drive parameter assignment.For:
Reason 0x0040:
– Compare the encoder type in the drive or encoder parameter P979 with theconfiguration data of the technology object.
ControllerObjectType
13-669� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
Reason 0x0080:
– Compare the message frame type in the drive or encoder parameter P922with HW Config and the configuration data of the technology object.
– Compare the encoder type, resolution, multiplier and, with absoluteencoders, the data length in the drive or encoder parameter P979 with theconfiguration data of the technology object.
– Compare the parameterization named in reason 0x8000 (reason 0x8000 canoccur as secondary fault).
Reason 0x8000:
– Compare the cycle clock parameters of HW Config (PROFIBUS line, SlaveOM for drive or encoder) and the execution system. Tmapc and servo mustbe parameterized with the same cycle clock period!
� System fault, contact the hotline (reason 0x0008, 0x0010, 0x0020).
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseDISABLE_CONTROLLER
Programmable local responsesDISABLE_CONTROLLER
ControllerObjectType
13-670� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
20006 Error in configuration (category: /1/%d, error number: /2/%d)
CauseThis alarm indicates error states caused by a faulty or inconsistent configuration.The technology objects perform a plausibility check on the configuration. Errors areidentified by the error codes below.
Meaning of alarm parameters
Category: Area in which the error occurred.
1–Command decoding
2–Config manager
3–Sequential control
4–Controller
5–Identification
6–Technology object
Error number: Specification of error
500 = “TO in illegal status for configuration”
501 = “More configuration data expected than received”
502 = “Invalid data in configuration”
503 = “Version conflict in configuration”
1000 = “General configuration error”
1001 = “Invalid controller type selected”
1002 = “Invalid execution level selected”
1003 = “Incomplete configuration data for controller TO”
1004 = “Error generating controller TO”
1005 = “Limit value for feedforward control factor exceeded”
1006 = “Proportional-action controller for this TO not implemented”
1007 = “Limit value for system deviation threshold exceeded”
1008 = “Limit value for system deviation monitoring exceeded”
1009 = “Limit value for integral-action feedback factor exceeded”
1010 = “Limit value for derivative-action actual-value factor exceeded”
1011 = “Limit value for rate-of-rise limit at output exceeded”
1012 = “Limit value for limiter minimum value exceeded”
1013 = “Limit value for limiter maximum value exceeded”
1014 = “Limiter minimum value greater than its maximum value”
RemedyChange the configuration data.
Acknowledgment / responsePower On / START TechnologicalFaultTask
Default setting for local responseDISABLE_CONTROLLER
Programmable local responsesDISABLE_CONTROLLER
ControllerObjectType
13-671� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
20007 Interconnection error (category: /1/%d, context: /2/%d, context Parameter1: /3/%d, context Parameter2: /4/%d)
CauseThis alarm indicates errors in the interconnection of technology objects. When theinterconnection is established, the technology object verifies it on the basis of theinterface properties. Errors are classified by category.
Meaning of alarm parameters
Category:
1 – TO compatibility errorAn interconnection is to be established with a technology object that has beenconfigured with another reference system (e.g., output cam with rotaryreference system and linear axis).
2 – Exclusive interfaceMultiple interconnections are to be established for an interface intended forexclusive interconnection.
3 – Interconnection requirementThe technology object is waiting for an interconnection required for thesequence.
4 – Interface initialization errorErrors result from extended initialization sequences at interfaces andparameter exchange between interconnected interfaces.
5 – Interface not available on technology objectAn interface specified in the interconnection is not available on the technologyobject.
6 – CircularityThe interconnection on the technology object leads to circular communicationwithin the technology object (e.g., circular master/slave interconnection ofgearing axes, whereby a gearing axis used as a master is in turn the slave ofanother master, which is assigned the master setpoints generated on thisgearing axis directly or via additional interconnections).
7 – Sequence-level compatibility errorAn interconnection is to be established with a technology object that isexecuted in another interpolator level (e.g., output cam with IPO and axis withIPO_2).
8 – Distribution initializationWhen interconnecting technology objects that are distributed among differentdevices, an error occurred during initialization of the communication interface.
9 – Illegal TO statusThe technology object cannot be interconnected in the current state.
Context:
The context provides additional information about the error category for the TOinterconnection. Additional parameters can be provided for the error descriptionon a context-specific basis. Context and context parameter are output as aninteger value.
ControllerObjectType
13-672� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
Remedy
1 – Technology object compatibility error: Correct the configuration of the reference system of the technology objects tobe interconnected.
2 – Exclusive interface: Correct the configuration of the interconnected technology object.
3 – Interconnection request: Add the missing interconnection to your technology object.
4 – Error during interface initialization: Contact the hotline.
5 – Interface not available on technology object: Contact the hotline.
6 – Circularity:Remove unnecessary interconnections.
7 – Execution level compatibility error: Correct the configuration of the interpolator task level of the technology objectsto be interconnected.
8 – Distribution initialization:Check the hardware configuration. Ensure that the distributed interactingdevices are linked in the bus configuration. In addition, the address areas thatare used by the devices for communication must be set up. The address areasare automatically set up when the project is compiled; only afterwards is thevalid hardware configuration available for downloading.
9 – Illegal TO status:Correct the configuration of the technology object, correct execution errors.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseDISABLE_CONTROLLER
Programmable local responsesDISABLE_CONTROLLER
ControllerObjectType
13-673� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
20008 Cannot assign USER_DEFAULT to system variables
CauseIt is not appropriate to assign USER_DEFAULT to a UserDefault system variable,because the variable references itself in this case.This prevents generation of a useful value during reading out. When this erroroccurs, the new Enum value is not assigned. The variable retains the old value.
RemedyUSER_DEFAULT is designed for use in technology commands.Avoid assigning it to system variables.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONE
20009 Reserved error
CauseThis error is not currently in use.
RemedyNot necessary, for information only.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseDISABLE_CONTROLLER
Programmable local responsesDISABLE_CONTROLLER
ControllerObjectType
13-674� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
20010 A restart is necessary to activate the configuration data
CauseThe configuration cannot be set to active, since data have been modified in such away that does not permit it. The technology object must be restarted to activate thedata.
Remedy
� Execute the technology object reset command, and set the activateRestartparameter to ACTIVATE_RESTART.
� Set the restartActivation system variable to ACTIVATE_RESTART.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONECONTROL_STOPDECODE_STOPDISABLE_CONTROLLER
ControllerObjectType
13-675� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
20011 Error when activating the configuration (category: /1/%d, error number: /2/%d)
CauseThis note indicates error conditions when activating the configuration. The errorconditions can be traced back to an incorrect or inconsistent configuration. Thetechnology objects perform a plausibility check on the configuration. Errors areidentified by the error codes below.If this information appears, the configuration will not be activated.
Meaning of alarm parameters
Category: Area in which the error occurred.
1–Command decoding
2–Config manager
3–Sequential control
4–Controller
5–Identification
6–Technology object
Error number: Specification of error
500 = “TO in illegal status for configuration”
501 = “More configuration data expected than received”
502 = “Invalid data in configuration”
503 = “Version conflict in configuration”
1000 = “General configuration error”
1001 = “Invalid controller type selected”
1002 = “Invalid execution level selected”
1003 = “Incomplete configuration data for controller TO”
1004 = “Error generating controller TO”
1005 = “Limit value for feedforward control factor exceeded”
1006 = “Proportional-action controller for this TO not implemented”
1007 = “Limit value for system deviation threshold exceeded”
1008 = “Limit value for system deviation monitoring exceeded”
1009 = “Limit value for integral-action feedback exceeded”
1010 = “Limit value for derivative-action actual-value factor exceeded”
1011 = “Limit value for rate-of-rise limit at output exceeded”
1012 = “Limit value for limiter minimum value exceeded”
1013 = “Limit value for limiter maximum value exceeded”
1014 = “Limiter minimum value greater than its maximum value”
ControllerObjectType
13-676� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
RemedyChange the configuration data.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONECONTROL_STOPDECODE_STOPDISABLE_CONTROLLER
ControllerObjectType
13-677� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
20012 Restart not executed (reason: /1/%d)
CauseTechnology object could not be restarted.
Meaning of alarm parameters
Reason:
1 – The technology object configuration does not allow a restart with the restartsystem variable. You can initiate the restart using the reset command.
2 – The technology object is not ready to be restarted.
3 – A configured condition for restarting the technology object is not met (e.g.,technology object must be disabled).
4 – Restart has not been executed or executed with the last programmedconfiguration of the technology object.
Remedy
� Work around the cause stated in the Reason parameter, or reload the project.
� Use the device diagnostics to establish whether technological alarms werereported and, if necessary, remedy the cause of the alarm.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONECONTROL_STOPDECODE_STOPDISABLE_CONTROLLER
ControllerObjectType
13-678� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
20014 At the logical address: /1/%d (optional log. address: /2/%d and bit no.: /3/%dof the enable output), a driver (type: /4/%d) could not be requested
CauseThe driver of a physical device is not available or is being used by another TO.
Meaning of alarm parameters
Logical address:
This is the address of the actuator driver configured on the technology object.
Logical address and bit number:
This specifies the address and bit number of the output enable bit
Type:
1–Actuator driver
2–Encoder driver
3–BitRead driver
4–BitWrite driver
5–ByteRead driver
6–ByteWrite driver
7–WordRead driver
8–WordWrite driver
9–DWordRead driver
10–DWordWrite driver
Remedy
� Check that the logical device was available at the time of the request or whetherit was being used by another technology object.
� Connect a suitable device.
� Check the device (function, connections, terminals).
� Check the topological configuration in HWConfig.
� Compare configuration of HWConfig and technology object.
� Contact the hotline.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseDISABLE_CONTROLLER
Programmable local responsesDISABLE_CONTROLLER
ControllerObjectType
13-679� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
30001 Illegal parameter (parameter index according to standard sequence in thesystem functions: /1/%d, command type: /4/%X)
CauseIllegal system function parameter, the command is aborted. The parameters indicate the position of the illegal system function parameteraccording to the standard sequence in the system functions and the command typeof an incorrectly entered parameter.
Meaning of alarm parameters
Parameter index:
Index of the first system function parameter that triggered this error (listedaccording to the standard sequence in the system functions).
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyChange the parameters.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOP
ControllerObjectType
13-680� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
30002 Command aborted (reason: /1/%d, command type: /4/%X)
CauseExecution of the command was aborted before or during processing.This condition can arise as a result of loading a new command, resetting thecommand buffer, or an error state.
Meaning of alarm parameters
Reason:
1–Command buffer reset
2–Abort by another command
3–Aborted by a stop
4–Aborted by a higher-order stop
5–Abort by a pending error response
6–Aborted due to ambiguous commandId
7–Delayed acknowledgment
8–No actual value for axis (e.g., encoder or data bus not ready)
9–Aborted due to abnormal termination of a dependent command
10–Aborted due to active synchronous operation
11–Aborted due to active superimposed motion
12–Aborted due to active speed-controlled controller mode
13–Aborted due to active position-controlled controller mode
14–Aborted due to active motion to fixed end stop
15–Axis is not in pressure-limiting operation
16–Aborted due to active pressure-controlled operation
17–Aborted due to inactive pressure-controlled operation
18–Superimposed command is not permitted
19–Aborted due to error during cam access
20–Slave is not ready for operation
21–Error in slave synchronization
22–Aborted by command on slave
23–Aborted by stop on slave
24–Aborted by an active error response on the slave
25–No actual value for slave (e.g., encoder or data bus not ready)
26–Aborted by reset on slave
27–Master values are not valid
28–Active command in recursive TO interconnection
29–Aborted due to error during synchronization
30–Axis is in pressure-limiting operation
31–Maximum number of active commands exceeded
32–Aborted due to active correction command
33–Action only permissible in standstill
Command type:
Outputs the aborted command type. The command type is output as ahexadecimal integer value.
ControllerObjectType
13-681� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
RemedyReset command via program.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOP
30003 Command aborted due to full command buffer (command type: /4/%X)
CauseThe command is not entered in the command buffer as the buffer is already full.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
Remedy
� Check the program flow.
� Typical cause: The ’nextCommand’ parameter is passed with the valueIMMEDIATELY. You need to synchronize the command sequence manually oruse another value for ’nextCommand’.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOP
ControllerObjectType
13-682� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
30004 Unknown command (command type: /4/%X)
CauseThe active software tool does not support this command.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyCheck the versions of the engineering system and the runtime software.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOP
ControllerObjectType
13-683� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
30005 Ambiguous commandId (number of commands with specified ID: /1/%d,command type: /4/%X)
CauseThe specified commandID refers to several commands.The specified action is performed for the command matching the specifiedcommandID that has been in the interpolator for the longest time. If nocorresponding command is found in the interpolator, the action refers to the nextcommand loaded in the interpolator.
Meaning of alarm parameters
Number of commands with specified ID:
Number of commands referenced by the specified commandId.
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyUse different commandIds for commands that are active simultaneously.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOP
ControllerObjectType
13-684� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
30006 Cannot execute command due to current object state (command type: /4/%X)
CauseThe object is in the stop, error, or reset state and the command is not possible inthis object state.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
Remedy
� Check the object status.
� Check the permissible sequence of commands.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOP
30007 The error cannot be reset due to its configuration
CauseThe alarm cannot be acknowledged at the present time or by the selected means.
Remedy
� Check the configured acknowledgment procedure.
� If necessary, change the acknowledgment procedure for the alarm.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOP
ControllerObjectType
13-685� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
30008 A connection to a technology object required for this operation does notexist (command type: /4/%X)
CauseThe object connection required for this operation has not been configured.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyCheck the project configuration, or change the object connection in the command.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOP
30009 Command rejected due to suspension of command decoding on addressedtechnology object (command type: /4/%X)
CauseCommand was rejected due to suspension of command decoding on theaddressed technology object.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
Remedy
� Check why the command was rejected.
� If necessary, acknowledge any active errors once you have corrected the causeof the error.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOP
ControllerObjectType
13-686� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
30010 Command not available (command type: /4/%X)
CauseThe command is not available in this version of the runtime software.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyCheck the version of the runtime software.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOP
30011 Parameter unavailable (parameter index according to standard sequence inthe system functions: /1/%d, command type: /4/%X)
CauseThe parameter is not available in this version of the runtime software, thecommand is therefore rejected. The parameters indicate the position according tothe standard sequence in the system functions and the command type of anincorrectly entered parameter.
Meaning of alarm parameters
Parameter index:
Index of the command parameter triggering this error according to the standardsequence in the system functions.
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyCheck the version of the runtime software.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOP
ControllerObjectType
13-687� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
30012 Command cannot be started synchronously (command type: /4/%X)
CauseThe command cannot be used during a BEGIN_SYNC, END_SYNC sequencebecause it is a reset command or a command that has only one return value in theuser program.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyDo not use this command type during a BEGIN_SYNC, END_SYNC sequence.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOP
ControllerObjectType
13-688� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
30013 Synchronous start of the command using IMMEDIATELY mergeMode(command type: /4/%X)
CauseWith synchronous command start, only merge modes that immediately override thecurrent command (IMMEDIATELY) and superimpose the current command(SUPERIMPOSED_MOTION_MERGE) can be used. If an illegal merge mode isprogrammed (e.g., SEQUENTIAL or NEXT_MOTION), the system automaticallychanges the merge mode to IMMEDIATELY and outputs this warning.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyProgram the command, which is to be started synchronously to immediatelyoverride the current command. To do this, enter the value IMMEDIATELY in the’mergeMode’ command parameter.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOP
ControllerObjectType
13-689� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
30015 A technology required for this command was not configured (technology: /1/%d, command type: /4/%X)
CauseThe command cannot be selected in this technology object configuration.
Meaning of alarm parameters
Technology:
Not relevant
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyActivate the technology needed for the command.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOP
40001 Actual value in violation of upper limit
CauseMeaning of alarm parameters
RemedyCheck program and sampling time
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseDISABLE_CONTROLLER
Programmable local responsesNONEDECODE_STOPCONTROL_STOPDISABLE_CONTROLLER
ControllerObjectType
13-690� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
40002 Actual value in violation of lower limit
CauseMeaning of alarm parameters
RemedyCheck program and sampling time
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseDISABLE_CONTROLLER
Programmable local responsesNONEDECODE_STOPCONTROL_STOPDISABLE_CONTROLLER
40003 Setpoint in violation of upper limit
CauseMeaning of alarm parameters
RemedyCheck program and sampling time
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseDISABLE_CONTROLLER
Programmable local responsesNONEDECODE_STOPCONTROL_STOPDISABLE_CONTROLLER
ControllerObjectType
13-691� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
40004 Setpoint in violation of lower limit
CauseMeaning of alarm parameters
RemedyCheck program and sampling time
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseDISABLE_CONTROLLER
Programmable local responsesNONEDECODE_STOPCONTROL_STOPDISABLE_CONTROLLER
40005 Feedforward control variable in violation of upper limit
CauseMeaning of alarm parameters
RemedyCheck program and sampling time
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseDISABLE_CONTROLLER
Programmable local responsesNONEDECODE_STOPCONTROL_STOPDISABLE_CONTROLLER
ControllerObjectType
13-692� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
40006 Feedforward variable in violation of lower limit
CauseMeaning of alarm parameters
RemedyCheck program and sampling time
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseDISABLE_CONTROLLER
Programmable local responsesNONEDECODE_STOPCONTROL_STOPDISABLE_CONTROLLER
40007 Permissible system deviation exceeded
CauseMeaning of alarm parameters
RemedyCheck program and sampling time
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseDISABLE_CONTROLLER
Programmable local responsesNONEDECODE_STOPCONTROL_STOPDISABLE_CONTROLLER
14-693� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
SensorType
Possible local responses
NONENo response
DECODE_STOPAbort command processing
CONFIGURED_OUTPUT_VALUESet configured output
20001 Internal error (Parameter1: /1/%d, Parameter2: /2/%d, Parameter3: /3/%d,Parameter4: /4/%d)
CauseThis alarm indicates internal error states providing information about the cause andlocation of the error in association with the related error number.
Meaning of alarm parameters
Parameter1: Error source
Parameter2 to 4: Error number
RemedyA detailed description of the system error alarm is not provided. Should a systemerror of this type occur, note the alarm number, the alarm text, and the internalsystem error number specified in the alarm and contact: SIEMENS AG A&D MC, Hotline.
Acknowledgment / responsePower On / STOP
Default setting for local responseDECODE_STOP
Programmable local responsesDECODE_STOP
14
SensorType
14-694� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
20002 Insufficient memory (Parameter1: /1/%d, Parameter2: /2/%d, Parameter3:/3/%d, Parameter4: /4/%d)
CauseThe memory required by the system is no longer available. This alarm can occurboth during power up and after program calls.
Meaning of alarm parameters
Parameter1: Area in which the error occurred.
1–Command decoding
2–Interpolator
3–Controller
4–Manipulated variable output
5–Encoder system
6–Technology package
Parameters 2 to 4 are area-specific. They are not fully utilized by all areas.
Command decoding area:
Parameter2 and Parameter4 refer to the command in which the error occurred.
Parameter2: Command return value
Parameter4: Command type
Remedy
� Reduce the size of the ST code.
� Reduce the number of technology objects.
� Reduce the number of interpolation points for cams, if present.
Acknowledgment / responsePower On / STOP
Default setting for local responseDECODE_STOP
Programmable local responsesDECODE_STOP
SensorType
14-695� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
20003 No object configuration (Parameter1: /1/%d, Parameter2: /2/%d, Parameter3:/3/%d, Parameter4: /4/%d)
CauseError in system configuration. The configuration data for a software tool could notbe found.
Meaning of alarm parameters
Parameter1: Area in which the error occurred.
1–Command decoding
2–Interpolator
3–Controller
4–Manipulated variable output
5–Encoder system
Parameters 2 to 4 are area-specific. They are not fully utilized by all areas.
Command decoding area
Parameter2 and Parameter4 refer to the command in which the error occurred.
Parameter2: Command return value
Parameter4: Command type
RemedyCheck the accuracy of the configuration data in your project. When commands arecalled on technology objects, the technology objects must be configured.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOP
SensorType
14-696� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
20004 At the logical address: /1/%d (bit number, if required: /2/%d) a driver (type:/3/%d) could be requested (error number: /4/%d)
CauseThe driver of a physical device or the device itself is not available.
Meaning of alarm parameters
Logical address:
This is the address configured on the technology object.
Bit number:
For bit driver only; bit number
Type:
1–Actuator driver
2–Encoder driver
3–BitRead driver
4–BitWrite driver
5–ByteRead driver
6–ByteWrite driver
7–WordRead driver
8–WordWrite driver
9–DWordRead driver
10–DWordWrite driver
Error number: Specification of error
Remedy
� Connect a suitable device.
� Check the device (function, connections, terminals).
� Check the topological configuration in HWConfig.
� Compare configuration of HWConfig and technology object.
� Contact the hotline.
Acknowledgment / responsePower On / START TechnologicalFaultTask
Default setting for local responseDECODE_STOP
Programmable local responsesDECODE_STOP
SensorType
14-697� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
20005 Device type: /3/%d, log. address: /1/%d faulty. (Bit: /2/%d, reason: 0x/4/%Xh)
CauseThe driver of a physical device or the device itself has failed or is faulty. When thisalarm occurs, the error cause must be evaluated in the external device (drive orencoder).
Meaning of alarm parameters
Type:
1–Actuator driver
2–Encoder driver
3–BitRead driver
4–BitWrite driver
5–ByteRead driver
6–ByteWrite driver
7–WordRead driver
8–WordWrite driver
9–DWordRead driver
10–DWordWrite driver
Logical address:This is the address configured on the technology object.
Bit number:For bit driver type = 3 or 4 only; bit number
Reason:0–Not defined (e.g., for binary I/O)
� Type = 1
0x0001h: Fault message from drive (note: On PROFIBUS drives, whichsupport acyclic communication in accordance with PROFIdrive V3,the error number/numbers of the drives is/are displayed in thediagnostic buffer, e.g., on Masterdrives MC).
0x0002h: DP: Drive signal “control requested” failed
0x0004h: DP: Drive switched off itself
0x0008h: Slot for drive data is not available in the project
0x0010h: Actuator driver does not have a connection to the drive data
0x0020h: Actuator driver was not initialized during power up
0x0080h: DP: Difference between configuration data and drive parameters
0x4000h: DP: Drive on bus failed (station failure)
0x8000h: Sign of life of drive faulty or failed
SensorType
14-698� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
� Type = 2
0x0000h: The number of permissible changes in the actual value of the maximum velocity of the absolute-value encoder has beenexceeded
0x0001h: Fault message from encoder (note: The error number/numbers is/are displayed in the diagnosticbuffer)
0x0002h: General hardware error of encoder
0x0004h: Encoder contaminated
0x0008h: Slot for encoder data is not available in the project
0x0010h: Encoder driver does not have a connection to the encoder data
0x0020h: Encoder driver was not initialized during power up
0x0040h: Error when reading the absolute value of the encoder
0x0080h: DP: Difference between the configuration data and the encoder parameters
0x0100h: Zero mark monitoring of encoder
0x4000h: DP: Encoder on bus failed (station failure)
0x8000h: DP: Sign of life of encoder has malfunctioned or failed. (Note: For an encoder whose data are transferred in a drive message together with actuator data, the actuator sign of lifeapplies for the encoder, e.g., a standard message 3 in accordancewith PROFIdrive).
� Type = 3 to 10
0x0000h: Additional information, not assigned
Note:Codings for the reason of the failure can also occur in combination. Theindividual codings are then added to form a coding sum, which is displayed(e.g., 0x0005 = 0x0001 + 0x0004). A reason for failure marked as DP can onlybe present on PROFIBUS devices.
RemedyCheck the device with respect to function and connections (reason 0x0001,0x0002, 0x0004, 0x4000, 0x8000).
� Check the topological configuration in HW Config (with reason 0x0008).
� For PROFIBUS drives or encoders, compare the configuration of HWConfig, thetechnology object, and the drive parameter assignment.For:
Reason 0x0040:
– Compare the encoder type in the drive or encoder parameter P979 with theconfiguration data of the technology object.
SensorType
14-699� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
Reason 0x0080:
– Compare the message frame type in the drive or encoder parameter P922with HW Config and the configuration data of the technology object.
– Compare the encoder type, resolution, multiplier and, with absoluteencoders, the data length in the drive or encoder parameter P979 with theconfiguration data of the technology object.
– Compare the parameterization named in reason 0x8000 (reason 0x8000 canoccur as secondary fault).
Reason 0x8000:
– Compare the cycle clock parameters of HW Config (PROFIBUS line, SlaveOM for drive or encoder) and the execution system. Tmapc and servo mustbe parameterized with the same cycle clock period!
� System fault, contact the hotline (reason 0x0008, 0x0010, 0x0020).
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseDECODE_STOP
Programmable local responsesDECODE_STOP
SensorType
14-700� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
20006 Error in configuration (category: /1/%d, error number: /2/%d)
CauseThis alarm indicates error states caused by a faulty or inconsistent configuration.The technology objects perform a plausibility check on the configuration. Errors areidentified by the error codes below.
Meaning of alarm parameters
Category: Area in which the error occurred.
1–Command decoding
2–Interpolator
3–Controller
4–Manipulated variable output
5–Encoder system
6–Technology object
Error number: Specification of error
500 = “TO in illegal status for configuration.”
501 = “More configuration data expected than received.”
502 = “Invalid data in configuration.”
503 = “Version conflict in configuration.”
RemedyChange the configuration data.
Acknowledgment / responsePower On / START TechnologicalFaultTask
Default setting for local responseDECODE_STOP
Programmable local responsesDECODE_STOP
SensorType
14-701� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
20007 Interconnection error (category: /1/%d, context: /2/%d, context parameter1:/3/%d, context parameter2: /4/%d)
CauseThis alarm indicates errors in the interconnection of technology objects. When theinterconnection is established, the technology object verifies it on the basis of theinterface properties. Errors are classified by category.
Meaning of alarm parameters
Category:
1 – TO compatibility errorAn interconnection is to be established with a technology object that has beenconfigured with another reference system (e.g., output cam with rotaryreference system and linear axis).
2 – Exclusive interfaceMultiple interconnections are to be established for an interface intended forexclusive interconnection.
3 – Interconnection requirementThe technology object is waiting for an interconnection required for thesequence.
4 – Interface initialization errorErrors result from extended initialization sequences at interfaces andparameter exchange between interconnected interfaces.
5 – Interface not available on technology objectAn interface specified in the interconnection is not available on the technologyobject.
6 – CircularityThe interconnection on the technology object leads to circular communicationwithin the technology object (e.g., circular master/slave interconnection ofgearing axes, whereby a gearing axis used as a master is in turn the slave ofanother master, which is assigned the master setpoints generated on thisgearing axis directly or via additional interconnections).
7 – Sequence-level compatibility errorAn interconnection is to be established with a technology object that isexecuted in another interpolator level (e.g., output cam with IPO and axis withIPO_2).
8 – Distribution initializationWhen interconnecting technology objects that are distributed among differentdevices, an error occurred during initialization of the communication interface.
9 – Illegal TO statusThe technology object cannot be interconnected in the current state.
Context:
The context provides additional information about the error category for the TOinterconnection. Additional parameters can be provided for the error descriptionon a context-specific basis. Context and context parameter are output as aninteger value.
SensorType
14-702� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
Remedy
1 – Technology object compatibility error: Correct the configuration of the reference system of the technology objects tobe interconnected.
2 – Exclusive interface: Correct the configuration of the interconnected technology object.
3 – Interconnection request: Add the missing interconnection to your technology object.
4 – Error during interface initialization: Contact the hotline.
5 – Interface not available on technology object: Contact the hotline.
6 – Circularity:Remove unnecessary interconnections.
7 – Execution level compatibility error: Correct the configuration of the interpolator task level of the technology objectsto be interconnected.
8 – Distribution initialization:Check the hardware configuration. Ensure that the distributed interactingdevices are linked in the bus configuration. In addition, the address areas thatare used by the devices for communication must be set up. The address areasare automatically set up when the project is compiled; only afterwards is thevalid hardware configuration available for downloading.
9 – Illegal TO status:Correct the configuration of the technology object, correct execution errors.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseDECODE_STOP
Programmable local responsesDECODE_STOP
SensorType
14-703� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
20008 Cannot assign USER_DEFAULT to system variables
CauseIt is not appropriate to assign USER_DEFAULT to a UserDefault system variable,because the variable references itself in this case.This prevents generation of a useful value during reading out. When this erroroccurs, the new Enum value is not assigned. The variable retains the old value.
RemedyUSER_DEFAULT is designed for use in technology commands.Avoid assigning it to system variables.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONE
20009 Reserved error
CauseThis error is not currently in use.
RemedyNot necessary, for information only.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseDECODE_STOP
Programmable local responsesDECODE_STOP
SensorType
14-704� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
20010 A restart is necessary to activate the configuration data
CauseThe configuration cannot be set to active, since data have been modified in such away that does not permit it. The technology object must be restarted to activate thedata.
Remedy
� Execute the technology object reset command, and set the activateRestartparameter to ACTIVATE_RESTART.
� Set the restartActivation system variable to ACTIVATE_RESTART.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOP
SensorType
14-705� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
20011 Error when activating the configuration (category: /1/%d, error number:/2/%d)
CauseThis note indicates error conditions when activating the configuration. The errorconditions can be traced back to an incorrect or inconsistent configuration. Thetechnology objects perform a plausibility check on the configuration. Errors areidentified by the error codes below.If this information appears, the configuration will not be activated.
Meaning of alarm parameters
Category: Area in which the error occurred.
1–Command decoding
2–Interpolator
3–Controller
4–Manipulated variable output
5–Encoder system
6–Technology object
Error number: Specification of error
RemedyChange the configuration data.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOP
SensorType
14-706� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
20012 Restart not executed (reason: /1/%d)
CauseTechnology object could not be restarted.
Meaning of alarm parameters
Reason:
1 – The technology object configuration does not allow a restart with the restartsystem variable. You can initiate the restart using the reset command.
2 – The technology object is not ready to be restarted.
3 – A configured condition for restarting the technology object is not met (e.g.,technology object must be disabled).
4 – Restart has not been executed or executed with the last programmedconfiguration of the technology object.
Remedy
� Work around the cause stated in the Reason parameter, or reload the project.
� Use the device diagnostics to establish whether technological alarms werereported and, if necessary, remedy the cause of the alarm.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOP
SensorType
14-707� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
20014 At the logical address: /1/%d (optional log. address: /2/%d and bit no.: /3/%dof the enable output), a driver (type: /4/%d) could not be requested
CauseThe driver of a physical device is not available or is being used by another TO.
Meaning of alarm parameters
Logical address:
This is the address of the actuator driver configured on the technology object.
Logical address and bit number:
This specifies the address and bit number of the output enable bit.
Type:
1–Actuator driver
2–Encoder driver
3–BitRead driver
4–BitWrite driver
5–ByteRead driver
6–ByteWrite driver
7–WordRead driver
8–WordWrite driver
9–DWordRead driver
10–DWordWrite driver
Remedy
� Check that the logical device was available at the time of the request or whetherit was being used by another technology object.
� Connect a suitable device.
� Check the device (function, connections, terminals).
� Check the topological configuration in HWConfig.
� Compare configuration of HWConfig and technology object.
� Contact the hotline.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseDECODE_STOP
Programmable local responsesDECODE_STOP
SensorType
14-708� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
30001 Illegal parameter (parameter index according to standard sequence in thesystem functions: /1/%d, command type: /4/%X)
CauseIllegal system function parameter, the command is aborted. The parameters indicate the position of the illegal system function parameteraccording to the standard sequence in the system functions and the command typeof an incorrectly entered parameter.
Meaning of alarm parameters
Parameter index:
Index of the first system function parameter that triggered this error (listedaccording to the standard sequence in the system functions).
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyChange the parameters.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOP
SensorType
14-709� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
30002 Command aborted (reason: /1/%d, command type: /4/%X)
CauseExecution of the command was aborted before or during processing.This condition can arise as a result of loading a new command, resetting thecommand buffer, or an error state.
Meaning of alarm parameters
Reason:
1–Command buffer reset
2–Abort by another command
3–Aborted by a stop
4–Aborted by a higher-order stop
5–Abort by a pending error response
6–Aborted due to ambiguous commandId
7–Delayed acknowledgment
8–No actual value for axis (e.g., encoder or data bus not ready)
9–Aborted due to abnormal termination of a dependent command
10–Aborted due to active synchronous operation
11–Aborted due to active superimposed motion
12–Aborted due to active speed-controlled controller mode
13–Aborted due to active position-controlled controller mode
14–Aborted due to active motion to fixed end stop
15–Axis is not in pressure-limiting operation
16–Aborted due to active pressure-controlled operation
17–Aborted due to inactive pressure-controlled operation
18–Superimposed command is not permitted
19–Aborted due to error during cam access
20–Slave is not ready for operation
21–Error in slave synchronization
22–Aborted by command on slave
23–Aborted by stop on slave
24–Aborted by an active error response on the slave
25–No actual value for slave (e.g., encoder or data bus not ready)
26–Aborted by reset on slave
27–Master values are not valid
28–Active command in recursive TO interconnection
29–Aborted due to error during synchronization
30–Axis is in pressure-limiting operation
31–Maximum number of active commands exceeded
32–Aborted due to active correction command
33–Action only permissible in standstill
Command type:
Outputs the aborted command type. The command type is output as ahexadecimal integer value.
SensorType
14-710� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
RemedyReset command via program.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOP
30003 Command aborted due to full command buffer (command type: /4/%X)
CauseThe command is not entered in the command buffer as the buffer is already full.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
Remedy
� Check the program flow.
� Typical cause: The ’nextCommand’ parameter is passed with the valueIMMEDIATELY. You need to synchronize the command sequence manually oruse another value for ’nextCommand’.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOP
SensorType
14-711� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
30004 Unknown command (command type: /4/%X)
CauseThe active software tool does not support this command.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyCheck the versions of the engineering system and the runtime software.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOP
SensorType
14-712� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
30005 Ambiguous commandId (number of commands with specified ID: /1/%d,command type: /4/%X)
CauseThe specified commandID refers to several commands.The specified action is performed for the command matching the specifiedcommandID that has been in the interpolator for the longest time. If nocorresponding command is found in the interpolator, the action refers to the nextcommand loaded in the interpolator.
Meaning of alarm parameters
Number of commands with specified ID:
Number of commands referenced by the specified commandId.
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyUse different commandIds for commands that are active simultaneously.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOP
SensorType
14-713� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
30006 Cannot execute command due to current object state (command type: /4/%X)
CauseThe object is in the stop, error, or reset state and the command is not possible inthis object state.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
Remedy
� Check the object status.
� Check the permissible sequence of commands.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOP
30007 The error cannot be reset due to its configuration
CauseThe alarm cannot be acknowledged at the present time or by the selected means.
Remedy
� Check the configured acknowledgment procedure.
� If necessary, change the acknowledgment procedure for the alarm.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOP
SensorType
14-714� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
30008 A connection to a technology object required for this operation does notexist (command type: /4/%X)
CauseThe object connection required for this operation has not been configured.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyCheck the project configuration, or change the object connection in the command.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOP
30009 Command rejected due to suspension of command decoding on addressedtechnology object (command type: /4/%X)
CauseCommand was rejected due to suspension of command decoding on theaddressed technology object.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
Remedy
� Check why the command was rejected.
� If necessary, acknowledge any active errors once you have corrected the causeof the error.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOP
SensorType
14-715� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
30010 Command not available (command type: /4/%X)
CauseThe command is not available in this version of the runtime software.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyCheck the version of the runtime software.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOP
30011 Parameter unavailable (parameter index according to standard sequence inthe system functions: /1/%d, command type: /4/%X)
CauseThe parameter is not available in this version of the runtime software, thecommand is therefore rejected. The parameters indicate the position according tothe standard sequence in the system functions and the command type of anincorrectly entered parameter.
Meaning of alarm parameters
Parameter index:
Index of the command parameter triggering this error according to the standardsequence in the system functions.
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyCheck the version of the runtime software.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOP
SensorType
14-716� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
30012 Command cannot be started synchronously (command type: /4/%X)
CauseThe command cannot be used during a BEGIN_SYNC, END_SYNC sequencebecause it is a reset command or a command that has only one return value in theuser program.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyDo not use this command type during a BEGIN_SYNC, END_SYNC sequence.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOP
SensorType
14-717� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
30013 Synchronous start of the command using IMMEDIATELY mergeMode(command type: /4/%X)
CauseWith synchronous command start, only merge modes that immediately override thecurrent command (IMMEDIATELY) and superimpose the current command(SUPERIMPOSED_MOTION_MERGE) can be used. If an illegal merge mode isprogrammed (e.g., SEQUENTIAL or NEXT_MOTION), the system automaticallychanges the merge mode to IMMEDIATELY and outputs this warning.
Meaning of alarm parameters
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyProgram the command, which is to be started synchronously to immediatelyoverride the current command. To do this, enter the value IMMEDIATELY in the’mergeMode’ command parameter.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOP
SensorType
14-718� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
30015 A technology required for this command was not configured (technology:/1/%d, command type: /4/%X)
CauseThe command cannot be selected in this technology object configuration.
Meaning of alarm parameters
Technology:
Not relevant
Command type:
Outputs the command type. The command type is output as a hexadecimalinteger value.
RemedyActivate the technology needed for the command.
Acknowledgment / responseReset fault memory / START TechnologicalFaultTask
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOP
SensorType
14-719� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
50013 Overshoot/undershoot of permissible range limits (logical address: /1/%d,reason: /2/%d)
CauseRange violation for additional sensor.
Meaning of alarm parameters
Logical address: Address configured on the technology object.
Reason:
1: Value greater than maximum permissible value.
2: Value smaller than minimum permissible value.
3: Positive overflow of sensor range.
4: Negative overflow of sensor range.
5: Error in accessing hardware address.
Remedy
� Check and adjust the configuration data.
� Check the sensor connection.
� Check the wiring.
Acknowledgment / responseReset fault memory / NONE
Default setting for local responseNONE
Programmable local responsesNONEDECODE_STOPCONFIGURED_OUTPUT_VALUE
SensorType
14-720� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
A-721� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
Command Type Numbers of the IndividualCommands
Command Decimal Hex
_MOVE 4097 1001
_ENABLEAXISSIMULATION 4103 1007
_DISABLEAXISSIMULATION 4104 1008
_GETSTATEOFAXISCOMMAND 4107 100B
_RESETMOTIONBUFFER 4108 100C
_GETSTATEOFMOTIONBUFFER 4109 100D
_SETAXISDATASETACTIVE 4112 1010
_GETMOTIONSTATEOFAXISCOMMAND 4115 1013
_REMOVEBUFFEREDAXISCOMMANDID 4117 1015
_DISABLETORQUELIMITING 4119 1017
_ENABLETORQUELIMITING 4120 1018
_RESETAXISCONFIGDATABUFFER 4124 101C
_GETAXISERRORNUMBERSTATE 4127 101F
_DISABLEFORCELIMITING 4129 1021
_STOPEMERGENCY 4132 1024
_STOP 4133 1025
_RUNVELOCITYBASEDMOTIONIN 4134 1026
_SETAXISSTW 4135 1027
_ENABLEAXISADDITIVETORQUE 4136 1028
_DISABLEAXISADDITIVETORQUE 4137 1029
_ENABLEAXISTORQUELIMITPOSITIVE 4138 102A
_DISABLEAXISTORQUELIMITPOSITIVE 4139 102B
_ENABLEAXISTORQUELIMITNEGATIVE 4140 102C
_DISABLEAXISTORQUELIMITNEGATIVE 4141 102D
_ENABLEQFAXIS 4143 102F
_RESETAXIS 4145 1031
_RESETAXISERROR 4146 1032
_ENABLEFORCELIMITINGVALUE 4147 1033
_BUFFERAXISCOMMANDID 4148 1034
A
Command Type Numbers of the Individual Commands
A-722� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
Command HexDecimal
_SETFORCECOMMANDVALUE 4149 1035
_SETFORCECONTROLDATASETPARAMETER 4150 1036
_GETFORCECONTROLDATASETPARAMETER 4151 1037
_ENABLEAXIS 4152 1038
_DISABLEAXIS 4153 1039
_DISABLEQFAXIS 4154 103A
_SETAXISDATASETPARAMETER 4155 103B
_GETAXISDATASETPARAMETER 4156 103C
_SETQFAXISDATASETPARAMETER 4157 103D
_GETQFAXISDATASETPARAMETER 4158 103E
_CONTINUE 4160 1040
_RUNTIMELOCKEDVELOCITYPROFILE 4177 1051
_SETQFAXISQCHARACTERISTICS 4178 1052
_SETQFAXISFCHARACTERISTICS 4179 1053
_RUNMOTIONINPOSITIONLOCKEDFORCEPROFILE 4181 1055
_RUNMOTIONINPOSITIONLOCKEDVELOCITYPROFILE 4182 1056
_ENABLEMOTIONINPOSITIONLOCKEDFORCELIMITINGPROFILE
4183 1057
_ENABLETIMELOCKEDFORCELIMITINGPROFILE 4184 1058
_RUNTIMELOCKEDFORCEPROFILE 4185 1059
_POS 4609 1201
_HOMING 4610 1202
_REDEFINEPOSITION 4611 1203
_SETANDGETENCODERVALUE 4612 1204
_ENABLEMONITORINGOFENCODERDIFFERENCE 4613 1205
_DISABLEMONITORINGOFENCODERDIFFERENCE 4614 1206
_GETAXISUSERPOSITION 4615 1207
_GETAXISINTERNALPOSITION 4616 1208
_DISABLEMOVINGTOENDSTOP 4619 120B
_ENABLEMOVINGTOENDSTOP 4620 120C
_GETPROGRAMMEDTARGETPOSITION 4622 120E
_ENABLEVELOCITYLIMITINGVALUE 4625 1211
_DISABLEVELOCITYLIMITING 4626 1212
_RUNPOSITIONBASEDMOTIONIN 4628 1214
_RUNTIMELOCKEDPOSITIONPROFILE 4689 1251
_RUNPOSITIONLOCKEDFORCEPROFILE 4693 1255
_RUNPOSITIONLOCKEDVELOCITYPROFILE 4694 1256
_ENABLEPOSITIONLOCKEDVELOCITYLIMITINGPROFILE 4695 1257
Command Type Numbers of the Individual Commands
A-723� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
Command HexDecimal
_ENABLETIMELOCKEDVELOCITYLIMITINGPROFILE 4697 1259
_ENABLEPOSITIONLOCKEDFORCELIMITINGPROFILE 4698 125A
_ENABLEFORCECONTROLBYCONDITION 4699 125B
_ENABLEFORCELIMITINGBYCONDITION 4700 125C
_ENABLEMOTIONINPOSITIONLOCKEDVELOCITYLIMITINGPROFILE
4701 125D
_ADDPOINTTOCAM 4868 1304
_INTERPOLATECAM 4869 1305
_SETCAMSCALE 4870 1306
_SETCAMOFFSET 4871 1307
_GETCAMFOLLOWINGVALUE 4872 1308
_GETCAMLEADINGVALUE 4873 1309
_ADDSEGMENTTOCAM 4874 130A
_ADDPOLYNOMIALSEGMENTTOCAM 4875 130B
_RESETCAMCONFIGDATABUFFER 4877 130D
_GETCAMERRORNUMBERSTATE 4878 130E
_RESETCAM 4880 1310
_RESETCAMERROR 4881 1311
_GETSTATEOFCAMCOMMAND 4882 1312
_BUFFERCAMCOMMANDID 4883 1313
_REMOVEBUFFEREDCAMCOMMANDID 4884 1314
_ENABLEMEASURINGINPUT 5123 1403
_DISABLEMEASURINGINPUT 5124 1404
_ENABLEMEASURINGINPUTSIMULATION 5125 1405
_DISABLEMEASURINGINPUTSIMULATION 5126 1406
_RESETMEASURINGINPUTCONFIGDATABUFFER 5128 1408
_GETMEASURINGINPUTERRORNUMBERSTATE 5129 1409
_RESETMEASURINGINPUT 5131 140B
_RESETMEASURINGINPUTERROR 5132 140C
_GETSTATEOFMEASURINGINPUTCOMMAND 5133 140D
_BUFFERMEASURINGINPUTCOMMANDID 5134 140E
_REMOVEBUFFEREDMEASURINGINPUTCOMMANDID 5135 140F
_ENABLEMEASURINGINPUTCYCLIC 5136 1410
_ENABLEOUTPUTCAM 5377 1501
_DISABLEOUTPUTCAM 5378 1502
_ENABLEOUTPUTCAMSIMULATION 5379 1503
_DISABLEOUTPUTCAMSIMULATION 5380 1504
_SETOUTPUTCAMSTATE 5381 1505
Command Type Numbers of the Individual Commands
A-724� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
Command HexDecimal
_SETOUTPUTCAMCOUNTER 5384 1508
_RESETOUTPUTCAMCONFIGDATABUFFER 5386 150A
_GETOUTPUTCAMERRORNUMBERSTATE 5387 150B
_RESETOUTPUTCAM 5389 150D
_RESETOUTPUTCAMERROR 5390 150E
_GETSTATEOFOUTPUTCAMCOMMAND 5391 150F
_BUFFEROUTPUTCAMCOMMANDID 5392 1510
_REMOVEBUFFEREDOUTPUTCAMCOMMANDID 5393 1511
_GETSLAVEVALUE 5635 1603
_GETMASTERVALUE 5636 1604
_GETSTATEOFFOLLOWINGOBJECTCOMMAND 5645 160D
_GETMOTIONSTATEOFFOLLOWINGOBJECTCOMMAND 5646 160E
_REMOVEBUFFEREDFOLLOWINGOBJECTCOMMANDID 5648 1610
_RESETFOLLOWINGOBJECTCONFIGDATABUFFER 5650 1612
_GETFOLLOWINGOBJECTERRORNUMBERSTATE 5651 1613
_SETMASTER 5652 1614
_ENABLEVELOCITYGEARING 5653 1615
_DISABLEVELOCITYGEARING 5654 1616
_DISABLEGEARING 5657 1619
_RESETFOLLOWINGOBJECTERROR 5659 161B
_RESETFOLLOWINGOBJECT 5660 161C
_BUFFERFOLLOWINGOBJECTCOMMANDID 5661 161D
_ENABLEFOLLOWINGOBJECTSIMULATION 5662 161E
_DISABLEFOLLOWINGOBJECTSIMULATION 5663 161F
_SETGEARINGOFFSET 5664 1620
_ENABLEGEARING 5665 1621
_ENABLECAMMING 5719 1657
_DISABLECAMMING 5720 1658
_SETCAMMINGOFFSET 5721 1659
_SETCAMMINGSCALE 5722 165A
_ENABLEEXTERNALENCODER 6147 1803
_DISABLEEXTERNALENCODER 6148 1804
_SYNCHRONIZEEXTERNALENCODER 6149 1805
_ENABLEEXTERNALENCODERSIMULATION 6150 1806
_DISABLEEXTERNALENCODERSIMULATION 6151 1807
_SETEXTERNALENCODERVALUE 6152 1808
_RESETEXTERNALENCODERCONFIGDATABUFFER 6154 180A
Command Type Numbers of the Individual Commands
A-725� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
Command HexDecimal
_GETEXTERNALENCODERERRORNUMBERSTATE 6155 180B
_GETSTATEOFEXTERNALENCODERCOMMAND 6156 180C
_REMOVEBUFFEREDEXTERNALENCODERCOMMANDID 6158 180E
_RESETEXTERNALENCODER 6159 180F
_RESETEXTERNALENCODERERROR 6160 1810
_BUFFEREXTERNALENCODERCOMMANDID 6161 1811
_REDEFINEEXTERNALENCODERPOSITION 6162 1812
_RESETCONTROLLEROBJECT 8961 2301
_RESETCONTROLLEROBJECTERROR 8962 2302
_RESETCONTROLLEROBJECTCONFIGDATABUFFER 8963 2303
_GETSTATEOFCONTROLLEROBJECTCOMMAND 8964 2304
_BUFFERCONTROLLEROBJECTCOMMANDID 8965 2305
_REMOVEBUFFEREDCONTROLLEROBJECTCOMMANDID 8966 2306
_GETCONTROLLEROBJECTERRORNUMBERSTATE 8967 2307
_ENABLECONTROLLEROBJECTIN 8968 2308
_DISABLECONTROLLEROBJECTIN 8969 2309
_CHANGEENABLEMODEOFCONTROLLEROBJECTIN 8970 230A
_ENABLECONTROLLEROBJECT 8971 230B
_DISABLECONTROLLEROBJECT 8972 230C
_SETCONTROLLEROBJECTPIDCONTROL 8973 230D
_RESETSENSOR 9473 2501
_RESETSENSORERROR 9474 2502
_RESETSENSORCONFIGDATABUFFER 9475 2503
_GETSTATEOFSENSORCOMMAND 9476 2504
_BUFFERSENSORCOMMANDID 9477 2505
_REMOVEBUFFEREDSENSORCOMMANDID 9478 2506
_GETSENSORERRORNUMBERSTATE 9479 2507
_ENABLESENSOR 9480 2508
_DISABLESENSOR 9481 2509
_RESETADDITIONOBJECT 9729 2601
_RESETADDITIONOBJECTERROR 9730 2602
_RESETADDITIONOBJECTCONFIGDATABUFFER 9731 2603
_ENABLEADDITIONOBJECTIN 9732 2604
_DISABLEADDITIONOBJECTIN 9733 2605
_GETADDITIONOBJECTERRORNUMBERSTATE 9734 2606
_GETSTATEOFADDITIONOBJECTCOMMAND 9735 2607
_BUFFERADDITIONOBJECTCOMMANDID 9736 2608
Command Type Numbers of the Individual Commands
A-726� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition
Command HexDecimal
_REMOVEBUFFEREDADDITIONOBJECTCOMMANDID 9737 2609
_CHANGEENABLEMODEOFADDITIONOBJECTIN 9738 260A
_RESETFIXEDGEAR 9985 2701
_RESETFIXEDGEARERROR 9986 2702
_RESETFIXEDGEARCONFIGDATABUFFER 9987 2703
_ENABLEFIXEDGEARMOTIONIN 9988 2704
_DISABLEFIXEDGEARMOTIONIN 9989 2705
_ENABLEFIXEDGEARING 9990 2706
_DISABLEFIXEDGEARING 9991 2707
_SETFIXEDGEARINGOFFSET 9992 2708
_SETFIXEDGEARMASTER 9993 2709
_GETSTATEOFFIXEDGEARCOMMAND 9994 270A
_BUFFERFIXEDGEARCOMMANDID 9995 270B
_REMOVEBUFFEREDFIXEDGEARCOMMANDID 9996 270C
_GETFIXEDGEARERRORNUMBERSTATE 9997 270D
_RESETFORMULAOBJECT 10241 2801
_RESETFORMULAOBJECTERROR 10242 2802
_RESETFORMULAOBJECTCONFIGDATABUFFER 10243 2803
_GETFORMULAOBJECTERRORNUMBERSTATE 10244 2804
_SETFORMULA 10245 2805
_ENABLEFORMULAOBJECTIN 10246 2806
_DISABLEFORMULAOBJECTIN 10247 2807
_CHANGEENABLEMODEOFFORMULAOBJECTIN 10248 2808
_SETFORMULAOBJECTOUTPUTVALUE 10249 2809
_ENABLEFORMULA 10250 280A
_DISABLEFORMULA 10251 280B
_CHANGEENABLEOFFORMULA 10252 280C
_DEFINEFORMULA 10253 280D
_GETSTATEOFFORMULAOBJECTCOMMAND 10254 280E
_BUFFERFORMULAOBJECTCOMMANDID 10255 280F
_REMOVEBUFFEREDFORMULAOBJECTCOMMANDID 10256 2810
_ENABLECAMTRACK 10497 2901
_DISABLECAMTRACK 10498 2902
_ENABLECAMTRACKSIMULATION 10499 2903
_DISABLECAMTRACKSIMULATION 10500 2904
_SETCAMTRACKSTATE 10501 2905
_GETCAMTRACKERRORNUMBERSTATE 10502 2906
Command Type Numbers of the Individual Commands
A-727� Siemens AG, 2004. All rights reservedTechnology Package Cam Alarms, 12.2004 Edition
Command HexDecimal
_RESETCAMTRACK 10503 2907
_RESETCAMTRACKERROR 10504 2908
_GETSTATEOFCAMTRACKCOMMAND 10505 2909
_BUFFERCAMTRACKCOMMANDID 10506 290A
_REMOVEBUFFEREDCAMTRACKCOMMANDID 10507 290B
_RESETCAMTRACKCONFIGDATABUFFER 10508 290C
Command Type Numbers of the Individual Commands
A-728� Siemens AG, 2004. All rights reserved
Technology Package Cam Alarms, 12.2004 Edition