SIMATIC S7-400
Brochures
For brochures serving as selectionguides for SIMATIC products refer to:
http://www.siemens.com/simatic/printmaterial
6/2 Introduction
6/4 Central processing units
6/4 Standard CPUs
6/4 CPU 412
6/17 CPU 414
6/32 CPU 416
6/47 CPU 417
6/52 SIPLUS Standard CPUs
6/54 Fail-safe CPUs
6/54 CPU 414F
6/62 CPU 416F
6/75 Fault-tolerant CPUs
6/75 CPU 412H
6/75 CPU 414H
6/75 CPU 417H
6/84 Sync-module for couplingthe CPU 41xH
6/85 Y-Link for S7-400H
6/88 SIPLUS fault-tolerant CPUs
6/91 SIPLUS sync module for connectingthe CPU 41xH
6/92 SIPLUS Y-Link for S7-400H
6/93 Interface modules
6/93 IF-964 DP PROFIBUS module
6/94 SIPLUS IF-964 DP interface module
6/95 Digital modules
6/95 SM 421 digital input module
6/98 SM 422 digital output module
6/101 SIPLUS digital modules
6/103 Analog modules
6/103 SM 431 analog input module
6/112 SM 432 analog output module
6/114 SIPLUS analog modules
6/116 Function modules
6/116 FM 450-1 counter module
6/118 FM 451 positioning module
6/120 FM 452 cam controller
6/122 FM 453 positioning module6/124 FM 455 controller module
6/128 FM 458-1 DP application module
6/139 SIPLUS function modules
6/141 Communication
6/141 CP 440
6/142 CP 441-1, CP 441-2
6/144 Loadable drivers for CP 441-2 andCP 341
6/146 CP 443-5 Basic
6/148 CP 443-5 Extended
6/150 CP 443-1
6/153 CP 443-1 Advanced
Ch. 5 TIM 4R-IE for WAN and Ethernet
Ch. 5 TIM 4R-IE DNP3
6/158 SIPLUS communication
6/162 Connection methods
6/162 Front connectors
6/163 SIMATIC TOP connect for SIMATIC S7
6/172 Racks
6/172 Racks
6/174 Fan subassembly
6/175 Expansion devices
6/176 SIPLUS module racks
6/177 Interface modules
6/177 IM 460-0
6/178 IM 461-0
6/179 IM 460-1
6/180 IM 461-1
6/181 IM 460-3
6/182 IM 461-3
6/183 IM 463-2
6/184 SIPLUS interface modules
6/186 Power supplies
6/190 Accessories
6/190 Labeling sheets
6/191 Spare parts
6/192 Modules for SIMATIC S7-400F/FH
6/192 IM 153-1/153-2
6/196 SIPLUS IM 153-6/153-2
6/198 Isolation module
6/199 SIPLUS isolation module
6/200 Fail-safe input/output modules
Siemens AG 2011 Siemens AG 2011
-
8/14/2019 Simatic St70 Chap06 English 2011
2/200
SIMATIC S7-400Introduction
S7-400/S7-400H/S7-400F/FH
6/2 Siemens ST 70 2011
Overview
The S7-400 is the most powerful PLC in the family of SIMATICcontrollers. It enables successful automation solutions withTotally Integrated Automation (TIA). The S7-400 is an automationplatform for system solutions in production and process
engineering, and it is characterized primarily by its modularityand performance reserves.
S7-400
The power PLC for the mid to high-end performance ranges.
The solution for even the most demanding tasks.
With a comprehensive range of modules and performance-graded CPUs for optimal adaptation to the automation task.
Flexible in use through simple implementation of distributedstructures; user-friendly connections.
Optimal communication and networking options.
User-friendly handling and uncomplicated design without a
fan. Can be expanded without problems when the tasks increase.
Multicomputing: Simultaneous operation of several CPUs inone S7-400 central controller. Multicomputing distributes theoverall performance power of an S7-400. For example,complex tasks can be divided into technologies such asopen-loop control, computing or communication, andassigned to different CPUs. And every CPU can be assignedits own local I/O.
Modularity: The powerful backplane bus of the S7-400 and thecommunication interfaces that can be connected direct to theCPU enable high-performance operation of a host of commu-nication lines. This enables, for example, division into onecommunication path for HMI and programming tasks, one forhigh-performance and equidistant motion control compo-nents, and one for a "normal" I/O fieldbus. Additionally
required connections to MES/ERP systems or the Internet canalso be implemented.
Engineering and diagnostics: The S7-400 is configured andprogrammed extremely efficiently together with the SIMATICEngineering Tools particularly in the case of extensiveautomation solutions with a high engineering component. Forthis purpose, high-level languages such as SCL and graphicalengineering tools for sequential controls, state graphprograms and technology-oriented diagrams are available, forexample.
S7-400H
Fault-tolerant automation system with redundant design. For applications with high fail-safety requirements. Processes
with high restart costs, expensive downtimes, little super-vision, and few maintenance options.
Redundant central functions.
Increases availability of I/O: switched I/O configuration.
Also possible to use I/Os with standard availability: single-sided configuration.
Hot stand-by: automatic reaction-free switching to the standbyunit in the event of a fault.
Configuration with two separate or one divided central rack.
Connection of switched I/O via redundant PROFIBUS DP.
Siemens AG 2011 Siemens AG 2011
-
8/14/2019 Simatic St70 Chap06 English 2011
3/200
SIMATIC S7-400Introduction
S7-400/S7-400H/S7-400F/FH
6/3Siemens ST 70 2011
Overview(continued)
S7-400F/FH
Failsafe automation system for plants with increased safetyrequirements
Complies with safety requirements to SIL 3 in accordance withIEC 61508, AK6 in accordance with DIN V 19250 and Cat. 4 inaccordance with EN 954-1
If required, also fault tolerant through redundant design
Without additional wiring of the safety-related I/O:
Safety-relevant communication via PROFIBUS DP withPROFIsafe profile
Based on S7-400H and ET 200M with fail-safe modules
Standard modules for non-safety-related applications canalso be used in the automation system
Isolation module for joint use of fail-safe and standardmodules in safety mode in one ET 200M
Technical specifications
For brochures serving as selection guides for SIMATIC productsrefer to:
www.siemens.com/simatic/printmaterial
General technical specifications
Degree of protection IP20
Ambient temperature 0 to 60 C
Relative humidity 5 to 95%, no condensationAtmospheric pressure 1080 to 795 hPa (corresponds to
an altitude of 1000 m to 2000 m)
Electromagnetic compatibility
Interference immunity According to EN 61000-6-2
E mitted interference According to EN 61000-6-4
Mechanical load
Vibration, test according to /tested with
IEC 60068-2-6 (sine)
10 to 58 Hz; constant amplitude0.075 mm;58 to 500 Hz; constant acceler-ation 1 g; duration of oscillation: 10frequency sweeps per axis in eachdirection of the three mutuallyperpendicular axes
Shock, test according to / tested
with
IEC 60068-2-27
Type of shock: Half-sine;strength of the shock 10 g(peak value), duration 6 msdirection of shock: 100 shocks ineach of the 3 mutually perpen-dicular axes.
Siemens AG 2011 Siemens AG 2011
-
8/14/2019 Simatic St70 Chap06 English 2011
4/200
SIMATIC S7-400Central processing unitsStandard CPUsCPU 412
6/4 Siemens ST 70 2011
Overview
The low-cost starter solution for the medium performancerange
Can be used in small and medium-sized systems with require-ments of the medium performance range
Technical specifications
6ES7 412-1XJ05-0AB0 6ES7 412-2XJ05-0AB0 6ES7 412-2EK06-0AB0
Product type designation CPU 412-1 CPU 412-2 CPU 412-2 PN
Product version
Hardware product version 03 03 01
Firmware version V5.3 V5.3 V6.0
Associated programming package STEP7 V 5.3 SP2 or higher with HWupdate
STEP7 V 5.3 SP2 or higher with HWupdate
STEP7 V5.5 or higher/iMap V3.0 +iMap STEP7 Add-on V3.0 SP5 orhigher
Supply voltages
Rated value
24 V DC No; Power supply via systempower supply
No; Power supply via systempower supply
No; Power supply via systempower supply
Feeding of external backup voltage
to CPU
5 to 15 V DC 5 to 15 V DC 5 to 15 V DC
Current consumption
from backplane bus 5 V DC, max. 0.6 A 1.1 A 1.3 A
from interface 5 V DC, max. 90 mA 90 mA; At each DP interface 90 mA; At the DP interface
Power losses
Power loss, typ. 2.5 W 4.5 W 5.5 W
Power loss, max. 3 W 5 W 6.5 W
Backup battery
Battery operation not relevant not relevant not relevant
Backup current, typ. 125 A; (up to 40 C) 125 A; (up to 40 C) 125 A; (up to 40 C)
Backup current, max. 300 A 550 A 450 A
Memory
Work memory
integrated (for program) 144 Kibyte 256 Kibyte 0.5 Mbyte
integrated (for data) 144 Kibyte 256 Kibyte 0.5 Mbyte expandable No No No
Load memory
expandable FEPROM Yes; with Memory Card (FLASH) Yes; with Memory Card (FLASH) Yes; with Memory Card (FLASH)
expandable FEPROM, max. 64 Mbyte 64 Mbyte 64 Mbyte
integrated RAM, max. 512 Kibyte 512 Kibyte 512 Kibyte
expandable RAM Yes; with Memory Card (RAM) Yes; with Memory Card (RAM) Yes; with Memory Card (RAM)
expandable RAM, max. 64 Mbyte 64 Mbyte 64 Mbyte
Backup
present Yes Yes Yes
with battery Yes; All data Yes; All data Yes; All data
without battery No No No
Siemens AG 2011 Siemens AG 2011
-
8/14/2019 Simatic St70 Chap06 English 2011
5/200
SIMATIC S7-400Central processing units
Standard CPUsCPU 412
6/5Siemens ST 70 2011
Technical specifications(continued)
CPU-blocks
DB
N umber, max. 1 500; Number range: 1 to 16,000 3 000; Number range: 1 to 16,000 3 000; Number range: 1 to 16,000
Size, max. 64 Kibyte 64 Kibyte 64 Kibyte
FB
Number, max. 750; Number range: 0 to 7999 1 500; Number range: 0 to 7999 1 500; Number range: 0 to 7999
Size, max. 64 Kibyte 64 Kibyte 64 Kibyte
FC
Number, max. 750; Number range: 0 to 7999 1 500; Number range: 0 to 7999 1 500; Number range: 0 to 7999
Size, max. 64 Kibyte 64 Kibyte 64 Kibyte
OB
Size, max. 64 Kibyte 64 Kibyte 64 Kibyte
Nesting depth
per priority class 24 24 24
additional within an error OB 1 1 1
CPU processing times
for bit operations, min. 75 ns 75 ns 75 ns
for word operations, min. 75 ns 75 ns 75 ns
for fixed point arithmetic, min. 75 ns 75 ns 75 ns
for floating point arithmetic, min. 225 ns 225 ns 225 ns
Counters, timers and theirretentivity
S7 counter
Number 2 048 2 048 2 048
Retentivity
- adjustable Yes Yes Yes
- lower limit 0 0 0
- upper limit 2 047 2 047 2 047
- preset Z 0 to Z 7 Z 0 to Z 7 Z 0 to Z 7
Counting range
- lower limit 0 0 0
- upper limit 999 999 999
IEC counter
present Yes Yes Yes
Type SFB SFB SFB
Number Unlimited (limited only by workmemory)
Unlimited (limited only by workmemory)
Unlimited (limited only by workmemory)
S7 times
Number 2 048 2 048 2 048
Retentivity
- adjustable Yes Yes Yes
- lower limit 0 0 0
- upper limit 2 047 2 047 2 047
- preset No times retentive No times retentive No times retentive
Time range
- lower limit 10 ms 10 ms 10 ms
- upper limit 9 990 s 9 990 s 9 990 s
IEC timer
present Yes Yes Yes
Type SFB SFB SFB
Number Unlimited (limited only by workmemory)
Unlimited (limited only by workmemory)
Unlimited (limited only by workmemory)
6ES7 412-1XJ05-0AB0 6ES7 412-2XJ05-0AB0 6ES7 412-2EK06-0AB0
Siemens AG 2011 Siemens AG 2011
-
8/14/2019 Simatic St70 Chap06 English 2011
6/200
SIMATIC S7-400Central processing unitsStandard CPUsCPU 412
6/6 Siemens ST 70 2011
Technical specifications(continued)
Data areas and their retentivity
retentive data area, total Total working and load memory(with backup battery)
Total working and load memory(with backup battery)
Total working and load memory(with backup battery)
Flag
Number, max. 4 Kibyte; Size of bit memoryaddress area
4 Kibyte; Size of bit memoryaddress area
4 Kibyte; Size of bit memoryaddress area
Retentivity available Yes Yes Yes
Number of clock memories 8; (in 1 memory byte) 8; (in 1 memory byte) 8; (in 1 memory byte)
Data blocks
N umber, max. 1 500; Number range: 1 to 16,000 3 000; Number range: 1 to 16,000 3 000; Number range: 1 to 16,000
Size, max. 64 Kibyte 64 Kibyte 64 Kibyte
Local data
adjustable, max. 8 Kibyte 8 Kibyte 8 Kibyte
preset 4 Kibyte 4 Kibyte 4 Kibyte
Address area
I/O address area
overall 4 Kibyte 4 Kibyte 4 Kibyte
Outputs 4 Kibyte 4 Kibyte 4 Kibyte of which, distributed
- MPI/DP interface, inputs 2 Kibyte 2 Kibyte 2 Kibyte
- MPI/DP interface, outputs 2 Kibyte 2 Kibyte 2 Kibyte
- DP interface, inputs 4 Kibyte
- DP interface, outputs 4 Kibyte
- PN interface, inputs 4 Kibyte
- PN interface, outputs 4 Kibyte
Process image
Inputs, adjustable 4 Kibyte 4 Kibyte 4 Kibyte
Outputs, adjustable 4 Kibyte 4 Kibyte 4 Kibyte
Inputs, preset 128 byte 128 byte 128 kbyte
Outputs, preset 128 byte 128 byte 128 Kibyte
Consistent data, max. 244 byte 244 byte 244 byte
Access to consistent data inprocess image
Yes Yes Yes
Subprocess images
Number of subprocess images,max.
15 15 15
Digital channels
Inputs 32 768 32 768 32 768
Outputs 32 768 32 768 32 768
Inputs, of which central 32 768 32 768 32 768
Outputs, of which central 32 768 32 768 32 768
Analog channels
Inputs 2 048 2 048 2 048
Outputs 2 048 2 048 2 048
Inputs, of which central 2 048 2 048 2 048
Outputs, of which central 2 048 2 048 2 048
6ES7 412-1XJ05-0AB0 6ES7 412-2XJ05-0AB0 6ES7 412-2EK06-0AB0
Siemens AG 2011 Siemens AG 2011
-
8/14/2019 Simatic St70 Chap06 English 2011
7/200
SIMATIC S7-400Central processing units
Standard CPUsCPU 412
6/7Siemens ST 70 2011
Technical specifications(continued)
Hardware configuration
connectable OPs 31 31 47
Central devices, max. 1 1 1
Expansion devices, max. 21 21 21
Multicomputing Yes; 4 CPUs max. (with UR1 orUR2)
Yes; 4 CPUs max. (with UR1 orUR2)
Yes; 4 CPUs max. (with UR1 orUR2)
Interface modules
Number of connectable IMs (total),max.
6 6 6
Number of connectable IM 460s,max.
6 6 6
Number of connectable IM 463s,max.
4; IM 463-2 4; IM 463-2 4; IM 463-2
Number of DP masters
integrated 1 2 1
via IM 467 4 4 4
via CP 10; CP 443-5 Extended 10; CP 443-5 Extended 10; CP 443-5 Extended
Mixed mode IM + CP permitted No; IM 467 not suitable for use withCP 443-5 Ext. and CP443-1 EX4x,EX20, GX20 (in PNIO mode)
No; IM 467 not suitable for use withCP 443-5 Ext. and CP443-1 EX4x,EX20, GX20 (in PNIO mode)
No; IM 467 not suitable for use withCP 443-5 Ext. and CP443-1 EX4x,EX20, GX20 (in PNIO mode)
via interface module 0 0 0
Number of pluggable S5 modules(via adapter capsule in centraldevice), max.
6 6 6
Number of IO controllers
integrated 0 0 1
via CP 4; No mixed operation ofCP443-1 EX40 andCP443-1 EX 41/EX20/GX20,max. 4 in central controller
4; No mixed operation ofCP443-1 EX40 andCP443-1 EX 41/EX20/GX20,max. 4 in central controller
4; No mixed operation ofCP443-1 EX40 andCP443-1 EX 41/EX20/GX20,max. 4 in central controller
Number of operable FMs and CPs(recommended)
FM Limited by number of slots andnumber of connections
Limited by number of slots andnumber of connections
Limited by number of slots andnumber of connections
CP, point-to-point CP 440: Limited by number ofslots; CP 441: Limited by numberof slots and number of connections
CP 440: Limited by number ofslots; CP 441: Limited by numberof slots and number of connections
CP 440: Limited by number ofslots; CP 441: Limited by numberof slots and number of connections
PROFIBUS and Ethernet CPs 14; Of which 10 CPs max. or IMsas DP master, 4 PN controllermaximum
14; Of which 10 CPs max. or IMsas DP master, 4 PN controllermaximum
14; In total max. 10 CPs as DPmaster and PN controller, of whichup to 10 IMs or CPs as DP masterand up to 4 CPs as PN controller
Time
Clock
Hardware clock (real-time clock) Yes Yes Yes
battery-backed and synchronizable Yes Yes Yes
Resolution 1 ms 1 ms 1 ms
Runtime meter
Number 16 16 16
Clock synchronization
supported Yes Yes Yes to MPI, master Yes Yes Yes
to MPI, slave Yes Yes Yes
to DP, master Yes Yes Yes
to DP, slave Yes Yes Yes
in AS, master Yes Yes Yes
in AS, slave Yes Yes Yes
on Ethernet via NTP No; Via CP No; Via CP Yes; as client
to IF 964 DP No No
6ES7 412-1XJ05-0AB0 6ES7 412-2XJ05-0AB0 6ES7 412-2EK06-0AB0
Siemens AG 2011 Siemens AG 2011
-
8/14/2019 Simatic St70 Chap06 English 2011
8/200
SIMATIC S7-400Central processing unitsStandard CPUsCPU 412
6/8 Siemens ST 70 2011
Technical specifications(continued)
S7 message functions
Number of login stations formessage functions, max.
31; Max. 31 with alarm_S andalarm_D (OP's);
max. 8 with alarm_8 and alarm_P(e.g. WinCC)
31; Max. 31 with alarm_S andalarm_D (OP's);
max. 8 with alarm_8 and alarm_P(e.g. WinCC)
47; Max. 47 with Alarm_S/SQ andAlarm_D/DQ (OPs); max. 8 with
Alarm, Alarm_8, Alarm_8P, Notifyand Notify_8 (e.g. WinCC)
Symbol-related messages Yes Yes Yes
SCAN procedure Yes Yes Yes
Number of messages
overall, max. 512 512 512
Block related messages Yes Yes Yes
Process diagnostic messages Yes Yes Yes
Alarm 8-blocks Yes Yes Yes
Process control messages Yes Yes Yes
Test commissioning functions
Status/control
Status/control variable Yes; Up to 16 variable tables Yes; Up to 16 variable tables Yes; Up to 16 variable tables
Forcing Forcing Yes Yes Yes
Status block Yes; Up to 2 simultaneously Yes; Up to 2 simultaneously Yes; Up to 16 simultaneously
Single step Yes Yes Yes
Number of breakpoints 4 4 16
Diagnostic buffer
present Yes Yes Yes
Number of entries, max. 200 400 400
- adjustable Yes Yes Yes
- preset 120 120 120
Service data
can be read out Yes
Communication functions
PG/OP communication Yes Yes Yes
Data record routing Yes Yes Yes
Routing Yes; S7 routing Yes; S7 routing Yes; S7 routing
Global data communication
supported Yes Yes Yes
Size of GD packets, max. 54 byte 54 byte 54 byte
S7 basic communication
supported Yes Yes Yes
User data per job, max. 76 byte 76 byte 76 byte
S7 communication
supported Yes Yes Yes
as server Yes Yes Yes
as client Yes Yes Yes
User data per job, max. 64 Kibyte 64 Kibyte 64 Kibyte
S5-compatible communication supported Yes; Via FC AG_SEND and
AG_RECV, max. via 10 CP 443-1 or443-5
Yes; Via FC AG_SEND andAG_RECV, max. via 10 CP 443-1 or443-5
Yes; Via FC AG_SEND andAG_RECV, max. via 10 CP 443-1 or443-5
User data per job, max. 8 Kibyte 8 Kibyte 8 Kibyte
Standard communication (FMS)
supported Yes; Via CP and loadable FB Yes; Via CP and loadable FB Yes; Via CP and loadable FB
6ES7 412-1XJ05-0AB0 6ES7 412-2XJ05-0AB0 6ES7 412-2EK06-0AB0
Siemens AG 2011 Siemens AG 2011
-
8/14/2019 Simatic St70 Chap06 English 2011
9/200
SIMATIC S7-400Central processing units
Standard CPUsCPU 412
6/9Siemens ST 70 2011
Technical specifications(continued)
Web server
supported No No Yes
Number of HTTP clients 5
User-defined websites Yes
Open IE communication
TCP/IP Yes; Via integrated PROFINETinterface and loadable FBs
- Number of connections, max. 46
- Data length, max. 32 Kibyte
- Several passive connections perport, supported
Yes
ISO-on-TCP (RFC1006) Via CP 443-1 Adv. and loadable FB Via CP 443-1 and loadable FB Yes; Via integrated PROFINETinterface or CP 443-1 Adv. andloadable FBs
- Number of connections, max. 46
- Data length, max. 1452 bytes via CP 443-1 Adv. 1452 bytes via CP 443-1 Adv. 32 Kibyte; 1452 bytes via CP 443-1Adv.
UDP Yes; Via integrated PROFINETinterface and loadable FBs
- Number of connections, max. 46- Data length, max. 1 472 byte
Number of connections
overall 32 32 48
PROFINET CBA (at set setpointcommunication load)
Number of remote interconnectionpartners
32
Number of functions, master/slave 150
Total of all Master/Slaveconnections
4 500
Data length of all incomingconnections master/slave, max.
45 000 byte
Data length of all outgoingconnections master/slave, max.
45 000 byte
Number of device-internal andPROFIBUS interconnections
1 000
Data length of device-internal andPROFIBUS interconnections, max.
16 000 byte
Data length per connection, max. 2 000 byte
Remote interconnections withacyclic transmission
- Sampling frequency: Samplingtime, min.
200 ms; Depending on presetcommuncation load, number ofinterconnections and data lengthused
- Number of incominginterconnections
250
- Number of outgoinginterconnections
250
- Data length of all incominginterconnections, max.
8 000 byte
- Data length of all outgoinginterconnections, max.
8 000 byte
- Data length per connection, max. 2 000 byte
6ES7 412-1XJ05-0AB0 6ES7 412-2XJ05-0AB0 6ES7 412-2EK06-0AB0
Siemens AG 2011 Siemens AG 2011
-
8/14/2019 Simatic St70 Chap06 English 2011
10/200
SIMATIC S7-400Central processing unitsStandard CPUsCPU 412
6/10 Siemens ST 70 2011
Technical specifications(continued)
Remote interconnections withcyclic transmission
- Transmission frequency:
Transmission interval, min.
1 ms; Depending on preset
communication load, number ofinterconnections and data lengthused
- Number of incominginterconnections
300
- Number of outgoinginterconnections
300
- Data length of all incominginterconnections, max.
4 800 byte
- Data length of all outgoinginterconnections, max.
4 800 byte
- Data length per connection, max. 450 byte
HMI variables via PROFINET(acyclic)
- Number of stations that can log onfor HMI variables (PN OPC/iMap)
2x PN OPC/1x iMap
- HMI variable updating 500 ms
- Number of HMI variables 1 000- Data length of all HMI variables,
max.32 000 byte
PROFIBUS proxy functionality
- supported Yes; 32 PROFIBUS slaves max.connectable
- Data length per connection, max. 240 byte; Slave-dependent
1st interface
Type of interface Integrated Integrated Integrated
Physics RS 485 / PROFIBUS + MPI RS 485 / PROFIBUS + MPI RS 485 / PROFIBUS + MPI
Isolated Yes Yes Yes
Power supply to interface(15 to 30 V DC), max.
150 mA 150 mA 150 mA
Number of connection resources MPI: 32, DP: 16 MPI: 32, DP: 16 MPI: 32, DP: 16
Functionality MPI Yes Yes Yes
DP master Yes Yes Yes
DP slave Yes Yes Yes
MPI
Number of connections 32; if a diagnostic repeater is usedon the line, the number ofconnection resources on the line isreduced by 1
32; if a diagnostic repeater is usedon the line, the number ofconnection resources on the line isreduced by 1
32; if a diagnostic repeater is usedon the line, the number ofconnection resources on the line isreduced by 1
Services
- PG/OP communication Yes Yes Yes
- Routing Yes Yes Yes
- Global data communication Yes Yes Yes
- S7 basic communication Yes Yes Yes
- S7 communication Yes Yes Yes
- S7 communication, as client Yes Yes Yes
- S7 communication, as server Yes Yes Yes
Transmission rate, max. 12 Mbit/s 12 Mbit/s 12 Mbit/s
6ES7 412-1XJ05-0AB0 6ES7 412-2XJ05-0AB0 6ES7 412-2EK06-0AB0
Siemens AG 2011 Siemens AG 2011
-
8/14/2019 Simatic St70 Chap06 English 2011
11/200
SIMATIC S7-400Central processing units
Standard CPUsCPU 412
6/11Siemens ST 70 2011
Technical specifications(continued)
DP master
Number of connections, max. 16; if a diagnostic repeater is usedon the line, the number of
connection resources on the line isreduced by 1
16; if a diagnostic repeater is usedon the line, the number of
connection resources on the line isreduced by 1
16; if a diagnostic repeater is usedon the line, the number of
connection resources on the line isreduced by 1
Services
- PG/OP communication Yes Yes Yes
- Routing Yes Yes Yes
- Global data communication No No No
- S7 basic communication Yes Yes Yes
- S7 communication Yes Yes Yes
- S7 communication, as client Yes Yes Yes
- S7 communication, as server Yes Yes Yes
- Equidistance mode support Yes Yes Yes
- Isochronous mode Yes Yes Yes
- SYNC/FREEZE Yes Yes Yes
- Activation/deactivation of DPslaves
Yes Yes Yes
- Direct data exchange
(slave-to-slave communication)
Yes Yes Yes
- DPV1 Yes Yes Yes
Transmission rate, max. 12 Mbit/s 12 Mbit/s 12 Mbit/s
Number of DP slaves, max. 32 32 32
Address area
- Inputs, max. 2 Kibyte 2 Kibyte 2 Kibyte
- Outputs, max. 2 Kibyte 2 Kibyte 2 Kibyte
User data per DP slave
- User data per DP slave, max. 244 byte 244 byte 244 byte
- Inputs, max. 244 byte 244 byte 244 byte
- Outputs, max. 244 byte 244 byte 244 byte
- Slots, max. 244 244 244
- per slot, max. 128 byte 128 byte 128 byte
DP slave
Number of connections 16 16 16
Services- PG/OP communication Yes; with interface active Yes; with interface active Yes; with interface active
- S7 routing Yes; With interface active Yes; With interface active Yes; With interface active
- Global data communication No No No
- S7 basic communication No No No
- S7 communication Yes Yes Yes
- S7 communication, as client Yes Yes Yes
- S7 communication, as server Yes Yes Yes
- Direct data exchange(slave-to-slave communication)
No No No
- DPV1 No No No
GSD file http://support.automation.siemens.com/WW/view/en/113652
http://support.automation.siemens.com/WW/view/en/113652
http://support.automation.siemens.com/WW/view/en/113652
Transmission rate, max. 12 Mbit/s 12 Mbit/s 12 Mbit/s
Automatic baud rate search No No No
Transfer memory
- Inputs 244 byte 244 byte 244 byte- Outputs 244 byte 244 byte 244 byte
Address area, max. 32; Virtual slots 32; Virtual slots 32; Virtual slots
User data per address area, max. 32 byte 32 byte 32 byte
User data per address area, ofwhich consistent, max.
32 byte 32 byte 32 byte
6ES7 412-1XJ05-0AB0 6ES7 412-2XJ05-0AB0 6ES7 412-2EK06-0AB0
Siemens AG 2011 Siemens AG 2011
-
8/14/2019 Simatic St70 Chap06 English 2011
12/200
SIMATIC S7-400Central processing unitsStandard CPUsCPU 412
6/12 Siemens ST 70 2011
Technical specifications(continued)
2nd interface
Type of interface Integrated PROFINET
Physics RS 485 / PROFIBUS Ethernet RJ45
Isolated Yes Yes
Integrated switch Yes
Number of ports 2
Power supply to interface(15 to 30 V DC), max.
150 mA
Automatic detection of transmissionspeed
Yes; Autosensing
Autonegotiation Yes
Autocrossing Yes
Media redundancy
supported Yes
Switchover time on line break,typically
200 ms
Number of stations in the ring, max. 50
Change of IP address at runtime,supported
Yes; Assignment by higher-level IOcontroller or by the user programwith SFB104 "IP_CONF"
Number of connection resources 16 48
Functionality
DP master Yes No
DP slave Yes No
PROFINET IO controller Yes
PROFINET IO device Yes
PROFINET CBA Yes
Open IE communication Yes
Web server Yes
- Number of HTTP clients 5
Local Operating Network No
DP master
Number of connections, max. 16
Services
- PG/OP communication Yes
- Routing Yes
- Global data communication No
- S7 basic communication Yes
- S7 communication Yes
- S7 communication, as client Yes
- S7 communication, as server Yes
- Equidistance mode support Yes
- Isochronous mode Yes
- SYNC/FREEZE Yes
- Activation/deactivation ofDP slaves
Yes
- Direct data exchange(slave-to-slave communication)
Yes
- DPV1 Yes
Transmission rate, max. 12 Mbit/s
Number of DP slaves, max. 64
Address area
- Inputs, max. 4 Kibyte
- Outputs, max. 4 Kibyte
6ES7 412-1XJ05-0AB0 6ES7 412-2XJ05-0AB0 6ES7 412-2EK06-0AB0
Siemens AG 2011 Siemens AG 2011
-
8/14/2019 Simatic St70 Chap06 English 2011
13/200
SIMATIC S7-400Central processing units
Standard CPUsCPU 412
6/13Siemens ST 70 2011
Technical specifications(continued)
User data per DP slave
- User data per DP slave, max. 244 byte
- Inputs, max. 244 byte
- Outputs, max. 244 byte- Slots, max. 244
- per slot, max. 128 byte
DP slave
Number of connections 16
Services
- Routing Yes
- Programming Yes
GSD file http://support.automation.siemens.com/WW/view/en/113652
Transmission rate, max. 12 Mbit/s
Transfer memory
- Inputs 244 byte
- Outputs 244 byte
Address area, max. 32
User data per address area, max. 32 byte User data per address area, of
which consistent, max.32 byte
PROFINET IO controller
Services
- PG/OP communication Yes
- S7 routing Yes
- S7 communication Yes
- Isochronous mode Yes; Only with IRT and the HighPerformance option
- Open IE communication Yes
Transmission rate, min. 10 Mbit/s
Transmission rate, max. 100 Mbit/s
Number of connectable IO devices,max.
256
Max. number of connectable IO
devices for RT
256
- of which in line, max. 256
Number of IO devices with IRT andthe option "high flexibility"
256
- of which in line, max. 61
Number of IO devices with IRT andthe option "high performance", max.
64
- of which in line, max. 64
IRT, supported Yes
Shared device, supported Yes
Prioritized startup supported Yes
- Number of IO devices, max. 32
Activation/deactivation ofIO devices
Yes
- Number of IO devices that can besimultaneously activated/deacti-
vated, max.
8
IO devices changing duringoperation (partner ports),supported
Yes
- Max. number of IO devices pertool
8; 8 parallel calls of the SFC 12"D_ACT_DP" possible per line.Max. 32 IO devices changingduring operation (partner ports)are supported.
6ES7 412-1XJ05-0AB0 6ES7 412-2XJ05-0AB0 6ES7 412-2EK06-0AB0
Siemens AG 2011 Siemens AG 2011
-
8/14/2019 Simatic St70 Chap06 English 2011
14/200
SIMATIC S7-400Central processing unitsStandard CPUsCPU 412
6/14 Siemens ST 70 2011
Technical specifications(continued)
Device replacement without swapmedium
Yes
Send clock times 250 s, 500 s, 1 ms, 2 ms, 4 ms
additionally with IRT with highperformance: 250 s to 4 ms in125 s frame
Updating time 250 s to 512 ms; minimum valuedepends on preset communicationshare for PROFINET IO, on thenumber of IO devices and on theamount of configured user data,see PROFINET system description
Address area
- Inputs, max. 4 Kibyte
- Outputs, max. 4 Kibyte
User data per address area, max.
- User data consistency, max. 1 024 byte
PROFINET IO device
Services
- PG/OP communication Yes
- S7 routing Yes
- S7 communication Yes
- Isochronous mode No
- Open IE communication Yes
- IRT, supported Yes
- Prioritized startup supported Yes
- Shared device, supported Yes
- Number of IO controllers withshared device, max.
2
Transfer memory
- Inputs, max. 1 440 byte; Per IO controller withshared device
- Outputs, max. 1 440 byte; Per IO controller withshared device
Submodules
- Number, max. 64- User data per submodule, max. 1 024 byte
PROFINET CBA
acyclic transmission Yes
cyclic transmission Yes
Open IE communication
Open IE communication, supported Yes
Number of connections, max. 46
Local port numbers used at thesystem end
0, 20, 21, 25, 80, 102, 135, 161,34962, 34963, 34964, 65532,65533, 65534, 65535
Keep-alive function, supported Yes
Isochronous mode
Isochronous mode Yes; For PROFIBUS only Yes; For PROFIBUS only Yes; Via PROFIBUS DP orPROFINET interface
Number of DP masters withisochronous mode
1 2 1
User data per isochronous slave,max.
244 byte 244 byte 244 byte
Equidistance Yes Yes Yes
Shortest clock pulse 1.5 ms; 0.5 ms without use of SFC126, 127
1.5 ms; 0.5 ms without use of SFC126, 127
1.5 ms; 0.5 ms without use of SFC126, 127
Max. cycle 32 ms 32 ms 32 ms
6ES7 412-1XJ05-0AB0 6ES7 412-2XJ05-0AB0 6ES7 412-2EK06-0AB0
Siemens AG 2011 Siemens AG 2011
-
8/14/2019 Simatic St70 Chap06 English 2011
15/200
SIMATIC S7-400Central processing units
Standard CPUsCPU 412
6/15Siemens ST 70 2011
Technical specifications(continued)
CiR - Configuration in RUN
CiR synchronization time, basic load 100 ms 100 ms 100 ms
CiR synchronization time, time perI/O slave
30 s; Time per I/O byte 200 s; Time per I/O byte 30 s; Time per I/O byte
Programming
Configuration software
STEP 7 Yes Yes Yes
Programming language
STEP 7 Yes Yes Yes
LAD Yes Yes Yes
FBD Yes Yes Yes
STL Yes Yes Yes
SCL Yes Yes Yes
CFC Yes Yes Yes
GRAPH Yes Yes Yes
HiGraph Yes Yes Yes
Nesting levels 7 7 7
Know-how protection User program protection/password
protectionYes Yes Yes
Block encryption Yes; With S7 block privacy
EMC
Emission of radio interference acc. toEN 55 011
Limit value class A, for use inindustrial areas
Yes Yes
Limit value class B, for use inresidential areas
No No
Dimensions
Required slots 1 1 1
Dimensions and weight
Dimensions
Width 25 mm 25 mm 25 mm Height 290 mm 290 mm 290 mm
Depth 219 mm 219 mm 219 mm
Weight
Weight, approx. 0.7 kg 0.7 kg 750 g
6ES7 412-1XJ05-0AB0 6ES7 412-2XJ05-0AB0 6ES7 412-2EK06-0AB0
Siemens AG 2011 Siemens AG 2011
-
8/14/2019 Simatic St70 Chap06 English 2011
16/200
SIMATIC S7-400Central processing unitsStandard CPUsCPU 412
6/16 Siemens ST 70 2011
Ordering data Order No. Order No.
D: Subject to export regulations AL: N and ECCN: 5D992
J: Subject to export regulations AL: N and ECCN: EAR99S
CPU 412-1 6ES7 412-1XJ05-0AB0
Work memory 288 KB, powersupply 24 V DC, MPI/PROFIBUSDP master interface, slot for
memory card, incl. slot numberlabels
CPU 412-2 6ES7 412-2XJ05-0AB0
Work memory 512 KB, powersupply 24 V DC, MPI/PROFIBUSDP master interface, slot formemory card, incl. slot numberlabels
CPU 412-2 PN 6ES7 412-2EK06-0AB0
Work memory 1 MB, powersupply 24 V DC, MPI/PROFIBUSDP master interface, PROFINETinterface, slot for memory card,incl. slot number labels
Memory card RAM
64 KB 6ES7 952-0AF00-0AA0
256 KB 6ES7 952-1AH00-0AA0
1 MB 6ES7 952-1AK00-0AA0
2 MB 6ES7 952-1AL00-0AA0
4 MB 6ES7 952-1AM00-0AA0
8 MB 6ES7 952-1AP00-0AA0
16 MB 6ES7 952-1AS00-0AA0
64 MB 6ES7 952-1AY00-0AA0
FEPROM memory card
64 KB 6ES7 952-0KF00-0AA0
256 KB 6ES7 952-0KH00-0AA0
1 MB 6ES7 952-1KK00-0AA0
2 MB 6ES7 952-1KL00-0AA04 MB 6ES7 952-1KM00-0AA0
8 MB 6ES7 952-1KP00-0AA0
16 MB 6ES7 952-1KS00-0AA0
32 MB 6ES7 952-1KT00-0AA0
64 MB 6ES7 952-1KY00-0AA0
MPI cable 6ES7 901-0BF00-0AA0
for connection of SIMATIC S7 andPG via MPI; 5 m in length
Slot number labels 6ES7 912-0AA00-0AA0
1 set (spare part)
Manual "SIMATIC S7-400programmable controller"
incl. instruction list
German 6ES7 498-8AA05-8AA0
English 6ES7 498-8AA05-8BA0
S7-400 operation list
German 6ES7 498-8AA05-8AN0
English 6ES7 498-8AA05-8BN0
Manual "Communication forSIMATIC S7-300/-400"
German 6ES7 398-8EA00-8AA0
English 6ES7 398-8EA00-8BA0
French 6ES7 398-8EA00-8CA0
Spanish 6ES7 398-8EA00-8DA0
Italian 6ES7 398-8EA00-8EA0
SIMATIC manual collection J 6ES7 998-8XC01-8YE0
Electronic manuals on DVD,multilingual: LOGO!, SIMADYN,SIMATIC bus components,SIMATIC C7,SIMATIC distributed I/O,SIMATIC HMI, SIMATIC Sensors,SIMATIC NET, SIMATIC PC BasedAutomation, SIMATIC PCS 7,SIMATIC PG/PC, SIMATIC S7,SIMATIC Software, SIMATIC TDC
SIMATIC manual collection
update service for 1 year
D 6ES7 998-8XC01-8YE2
Current "Manual Collection" DVDand the three subsequentupdates
Brochure "SIMATIC S7-400programmable controller -Design and application"
German 6ES7 498-8AA00-8AB0
English 6ES7 498-8AA00-8BB0
RS 485 bus connector with90 cable outlet
Max. transfer rate 12 Mbit/s
Without PG interface 6ES7 972-0BA12-0XA0
With PG interface 6ES7 972-0BB12-0XA0
RS 485 bus connector withangled cable outlet
Max. transfer rate 12 Mbit/s
Without PG interface 6ES7 972-0BA42-0XA0
With PG interface 6ES7 972-0BB42-0XA0
RS 485 bus connector with90 cable outlet forFast Connect system
Max. transfer rate 12 Mbit/s
Without PG interface
1 unit 6ES7 972-0BA52-0XA0
100 units 6ES7 972-0BA52-0XB0
With PG interface
1 unit 6ES7 972-0BB52-0XA0 100 units 6ES7 972-0BB52-0XB0
RS 485 bus connector withaxial cable outlet
For SIMATIC OP, for connection toPPI, MPI, PROFIBUS
6GK1 500-0EA02
PROFIBUS FastConnect buscable
Standard type with special designfor quick mounting, 2-core,shielded, sold by the meter, max.delivery unit 1000 m, minimumordering quantity 20 m
6XV1 830-0EH10
Siemens AG 2011 Siemens AG 2011
-
8/14/2019 Simatic St70 Chap06 English 2011
17/200
SIMATIC S7-400Central processing units
Standard CPUsCPU 414
6/17Siemens ST 70 2011
Overview
CPUs for high demands in the mid-level performance range
Applicable for plants with additional demands onprogramming scope and processing speed
Integrated PROFINET functions in CPU 414-3 PN/DP
Technical specifications6ES7 414-2XK05-0AB0 6ES7 414-3XM05-0AB0 6ES7 414-3EM06-0AB0
Product type designation CPU 414-2 CPU 414-3 CPU414-3 PN/DP
Product version
Hardware product version 03 03 01
Firmware version V5.3 V5.3 V6.0
associated programming package STEP7 V 5.3 SP2 or higher with HWupdate
STEP7 V 5.3 SP2 or higher with HWupdate
STEP7 V5.5 or higher/iMap V3.0 +iMap STEP7 Add-on V3.0 SP5 orhigher
Supply voltages
Rated value
24 V DC No; Power supply via systempower supply
No; Power supply via systempower supply
No; Power supply via systempower supply
Feeding of external backup voltageto CPU
5 to 15 V DC 5 to 15 V DC 5 to 15 V DC
Current consumption
from backplane bus 5 V DC, max. 1.1 A 1.3 A 1.5 A
from interface 5 V DC, max. 90 mA; At each DP interface 90 mA; At each DP interface 90 mA; At each DP interface
Power losses
Power loss, typ. 4.5 W 5.5 W 6.5 W
Power loss, max. 5 W 6 W 7.5 W
Backup battery
Battery operation not relevant not relevant not relevant
Backup current, typ. 125 A; (up to 40 C) 125 A 125 A; (up to 40 C)
Backup current, max. 550 A 550 A 450 A
Memory
Work memory
integrated (for program) 0.5 Mbyte 1.4 Mbyte 2 Mbyte integrated (for data) 0.5 Mbyte 1.4 Mbyte 2 Mbyte
expandable No No No
Load memory
expandable FEPROM Yes; with Memory Card (FLASH) Yes; with Memory Card (FLASH) Yes; with Memory Card (FLASH)
expandable FEPROM, max. 64 Mbyte 64 Mbyte 64 Mbyte
integrated RAM, max. 512 Kibyte 512 Kibyte 512 Kibyte
expandable RAM Yes; with Memory Card (RAM) Yes; with Memory Card (RAM) Yes; with Memory Card (RAM)
expandable RAM, max. 64 Mbyte 64 Mbyte 64 Mbyte
Backup
present Yes Yes Yes
with battery Yes; All data Yes; All data Yes; All data
without battery No No No
Siemens AG 2011 Siemens AG 2011
-
8/14/2019 Simatic St70 Chap06 English 2011
18/200
SIMATIC S7-400Central processing unitsStandard CPUsCPU 414
6/18 Siemens ST 70 2011
Technical specifications(continued)
CPU-blocks
DB
N umber, max. 6 000; Number range: 1 to 16,000 6 000; Number range: 1 to 16,000 6 000; Number range: 1 to 16,000
Size, max. 64 Kibyte 64 Kibyte 64 Kibyte
FB
Number, max. 3 000; Number range: 0 to 7999 3 000; Number range: 0 to 7999 3 000; Number range: 0 to 7999
Size, max. 64 Kibyte 64 Kibyte 64 Kibyte
FC
Number, max. 3 000; Number range: 0 to 7999 3 000; Number range: 0 to 7999 3 000; Number range: 0 to 7999
Size, max. 64 Kibyte 64 Kibyte 64 Kibyte
OB
Size, max. 64 Kibyte 64 Kibyte 64 Kibyte
Nesting depth
per priority class 24 24 24
additional within an error OB 1 1 1
CPU processing times
for bit operations, min. 45 ns 45 ns 45 ns
for word operations, min. 45 ns 45 ns 45 ns
for fixed point arithmetic, min. 45 ns 45 ns 45 ns
for floating point arithmetic, min. 135 ns 135 ns 135 ns
Counters, timers and theirretentivity
S7 counter
Number 2 048 2 048 2 048
Retentivity
- adjustable Yes Yes Yes
- lower limit 0 0 0
- upper limit 2 047 2 047 2 047
- preset Z 0 to Z 7 Z 0 to Z 7 Z 0 to Z 7
Counting range
- lower limit 0 0 0
- upper limit 999 999 999
IEC counter
Present Yes Yes Yes
Type SFB SFB SFB
Number Unlimited (limited only by workmemory)
Unlimited (limited only by workmemory)
Unlimited (limited only by workmemory)
S7 times
Number 2 048 2 048 2 048
Retentivity
- adjustable Yes Yes Yes
- lower limit 0 0 0
- upper limit 2 047 2 047 2 047
- preset No times retentive No times retentive No times retentive
Time range
- lower limit 10 ms 10 ms 10 ms
- upper limit 9 990 s 9 990 s 9 990 s
IEC timer
present Yes Yes Yes
Type SFB SFB SFB
Number Unlimited (limited only by workmemory)
Unlimited (limited only by workmemory)
Unlimited (limited only by workmemory)
6ES7 414-2XK05-0AB0 6ES7 414-3XM05-0AB0 6ES7 414-3EM06-0AB0
Siemens AG 2011 Siemens AG 2011
-
8/14/2019 Simatic St70 Chap06 English 2011
19/200
SIMATIC S7-400Central processing units
Standard CPUsCPU 414
6/19Siemens ST 70 2011
Technical specifications(continued)
Data areas and their retentivity
retentive data area, total Total working and load memory(with backup battery)
Total working and load memory(with backup battery)
Total working and load memory(with backup battery)
Flag
Number, max. 8 Kibyte; Size of bit memoryaddress area
8 Kibyte; Size of bit memoryaddress area
8 Kibyte; Size of bit memoryaddress area
Retentivity available Yes Yes Yes
Number of clock memories 8; (in 1 memory byte) 8; (in 1 memory byte) 8; (in 1 memory byte)
Data blocks
N umber, max. 6 000; Number range: 1 to 16,000 6 000; Number range: 1 to 16,000 6 000; Number range: 1 to 16,000
Size, max. 64 Kibyte 64 Kibyte 64 Kibyte
Local data
adjustable, max. 16 Kibyte 16 Kibyte 16 Kibyte
preset 8 Kibyte 8 Kibyte 8 Kibyte
Address area
I/O address area
overall 8 Kibyte 8 Kibyte 8 Kibyte
Outputs 8 Kibyte 8 Kibyte 8 Kibyte of which, distributed
- MPI/DP interface, inputs 2 Kibyte 2 Kibyte 2 Kibyte
- MPI/DP interface, outputs 2 Kibyte 2 Kibyte 2 Kibyte
- DP interface, inputs 6 Kibyte 6 Kibyte 6 Kibyte
- DP interface, outputs 6 Kibyte 6 Kibyte 6 Kibyte
- PN interface, inputs 8 Kibyte
- PN interface, outputs 8 Kibyte
Process image
Inputs, adjustable 8 Kibyte 8 Kibyte 8 Kibyte
Outputs, adjustable 8 Kibyte 8 Kibyte 8 Kibyte
Inputs, preset 256 byte 256 byte 256 byte
Outputs, preset 256 byte 256 byte 256 byte
consistent data, max. 244 byte 244 byte 244 byte
Access to consistent data inprocess image
Yes Yes Yes
Subprocess images
Number of subprocess images,max.
15 15 15
Digital channels
Inputs 65 536 65 536 65 536
Outputs 65 536 65 536 65 536
Inputs, of which central 65 536 65 536 65 536
Outputs, of which central 65 536 65 536 65 536
Analog channels
Inputs 4 096 4 096 4 096
Outputs 4 096 4 096 4 096
Inputs, of which central 4 096 4 096 4 096
Outputs, of which central 4 096 4 096 4 096
Hardware configuration
connectable OPs 31 31 63
Central devices, max. 1 1 1
Expansion devices, max. 21 21 21
Multicomputing Yes; 4 CPUs max. (with UR1 orUR2)
Yes; 4 CPUs max. (with UR1 orUR2)
Yes; 4 CPUs max. (with UR1 orUR2)
Interface modules
Number of connectable IMs (total),max.
6 6 6
Number of connectable IM 460s,max.
6 6 6
Number of connectable IM 463s,max.
4; IM 463-2 4; IM 463-2 4; IM 463-2
6ES7 414-2XK05-0AB0 6ES7 414-3XM05-0AB0 6ES7 414-3EM06-0AB0
Siemens AG 2011 Siemens AG 2011
-
8/14/2019 Simatic St70 Chap06 English 2011
20/200
SIMATIC S7-400Central processing unitsStandard CPUsCPU 414
6/20 Siemens ST 70 2011
Technical specifications(continued)
Number of DP masters
integrated 2 2 1
via IM 467 4 4 4
via CP 10; CP 443-5 Extended 10; CP 443-5 Extended 10; CP 443-5 Extended Mixed mode IM + CP permitted No; IM 467 not suitable for use with
CP 443-5 Ext. and CP443-1 EX4x,EX20, GX20 (in PNIO mode)
No; IM 467 not suitable for use withCP 443-5 Ext. and CP443-1 EX4x,EX20, GX20 (in PNIO mode)
No; IM 467 not suitable for use withCP 443-5 Ext. and CP443-1 EX4x,EX20, GX20 (in PNIO mode)
via interface module 0 1 1; IF 964-DP
Number of pluggable S5 modules(via adapter capsule in centraldevice), max.
6 6 6
Number of IO controllers
integrated 0 0 1
via CP 4; No mixed operation of CP443-1EX40 and CP443-1 EX 41/EX20/GX20, max. 4 in central controller
4; No mixed operation of CP443-1EX40 and CP443-1 EX 41/EX20/GX20, max. 4 in central controller
4; No mixed operation of CP443-1EX40 and CP443-1 EX 41/EX20/GX20, max. 4 in central controller
Number of operable FMs and CPs(recommended)
FM Limited by number of slots and
number of connections
Limited by number of slots and
number of connections
Limited by number of slots and
number of connections CP, point-to-point CP 440: limited by number of slots;
CP 441: limited by number ofconnections
CP 440: limited by number of slots;CP 441: limited by number ofconnections
CP 440: Limited by number ofslots; CP 441: Limited by numberof slots and number of connections
PROFIBUS and Ethernet CPs 14; Of which 10 CPs max. or IMsas DP master, 4 PN controllermaximum
14; Of which 10 CPs max. or IMsas DP master, 4 PN controllermaximum
14; In total max. 10 CPs as DPmaster and PN controller, of whichup to 10 IMs or CPs as DP masterand up to 4 CPs as PN controller
Time
Clock
Hardware clock (real-time clock) Yes Yes Yes
Battery-backed and synchronizable Yes Yes Yes
Resolution 1 ms 1 ms 1 ms
Runtime meter
Number 16 16 16
Clock synchronization supported Yes Yes Yes
to MPI, master Yes Yes Yes
to MPI, slave Yes Yes Yes
to DP, master Yes Yes Yes
to DP, slave Yes Yes Yes
in AS, master Yes Yes Yes
in AS, slave Yes Yes Yes
on Ethernet via NTP No; via CP No; via CP Yes; as client
to IF 964 DP No Yes Yes
S7 message functions
Number of login stations formessage functions, max.
31; max. 31 with alarm_S andalarm_D (OP's); max. 8 withalarm_8 and alarm_P (e.g. WinCC)
31; max. 31 with alarm_S andalarm_D (OP's); max. 8 withalarm_8 and alarm_P (e.g. WinCC)
63; max. 63 with Alarm_S/SQ andAlarm_D/DQ (OPs); max. 8 withAlarm, Alarm_8, Alarm_8P, Notifyand Notify_8 (e.g. WinCC)
Symbol-related messages Yes Yes Yes
SCAN procedure Yes Yes Yes
Number of messages
overall, max. 512 512 512
Block related messages Yes Yes Yes
Process diagnostic messages Yes Yes Yes
Alarm 8-blocks Yes Yes Yes
Process control messages Yes Yes Yes
6ES7 414-2XK05-0AB0 6ES7 414-3XM05-0AB0 6ES7 414-3EM06-0AB0
Siemens AG 2011 Siemens AG 2011
-
8/14/2019 Simatic St70 Chap06 English 2011
21/200
SIMATIC S7-400Central processing units
Standard CPUsCPU 414
6/21Siemens ST 70 2011
Technical specifications(continued)
Test commissioning functions
Status/control
Status/control variable Yes; Up to 16 variable tables Yes; Up to 16 variable tables Yes; Up to 16 variable tables
Forcing
Forcing Yes Yes Yes
Status block Yes; Up to 2 simultaneously Yes; Up to 2 simultaneously Yes; Up to 16 simultaneously
Single step Yes Yes Yes
Number of breakpoints 4 4 16
Diagnostic buffer
present Yes Yes Yes
Number of entries, max. 400 3 200 3 200
- adjustable Yes Yes Yes
- preset 120 120 120
Service data
can be read out Yes
Communication functions
PG/OP communication Yes Yes Yes
Data record routing Yes Yes Yes
Routing Yes; S7 routing Yes; S7 routing Yes; S7 routing
Global data communication
supported Yes Yes Yes
Size of GD packets, max. 54 byte 54 byte 54 byte
S7 basic communication
supported Yes Yes Yes
User data per job, max. 76 byte 76 byte 76 byte
S7 communication
supported Yes Yes Yes
as server Yes Yes Yes
as client Yes Yes Yes
User data per job, max. 64 Kibyte 64 Kibyte 64 Kibyte
S5-compatible communication
supported Yes; Via FC AG_SEND andAG_RECV, max. via 10 CP 443-1 or443-5
Yes; Via FC AG_SEND andAG_RECV, max. via 10 CP 443-1 or443-5
Yes; Via FC AG_SEND andAG_RECV, max. via 10 CP 443-1 or443-5
User data per job, max. 8 Kibyte 8 Kibyte 8 Kibyte
Standard communication (FMS)
supported Yes; Via CP and loadable FB Yes; Via CP and loadable FB Yes; Via CP and loadable FB
Web server
supported No No Yes
Number of HTTP clients 5
User-defined websites Yes
Open IE communication
TCP/IP Yes; Via integrated PROFINETinterface and loadable FBs
- Number of connections, max. 62
- Data length, max. 32 Kibyte
- Several passive connections perport, supported
Yes
6ES7 414-2XK05-0AB0 6ES7 414-3XM05-0AB0 6ES7 414-3EM06-0AB0
Siemens AG 2011 Siemens AG 2011
-
8/14/2019 Simatic St70 Chap06 English 2011
22/200
SIMATIC S7-400Central processing unitsStandard CPUsCPU 414
6/22 Siemens ST 70 2011
Technical specifications(continued)
ISO-on-TCP (RFC1006) Via CP 443-1 and loadable FB Via CP 443-1 and loadable FB Yes; Via integrated PROFINETinterface or CP 443-1 Adv. andloadable FBs
- Number of connections, max. 62- Data length, max. 1452 bytes via CP 443-1 Adv. 1452 bytes via CP 443-1 Adv. 32 Kibyte; 1452 bytes via CP 443-1
Adv.
UDP Yes; Via integrated PROFINETinterface and loadable FBs
- Number of connections, max. 62
- Data length, max. 1 472 byte
Number of connections
overall 32 32 64
PROFINET CBA (at set setpointcommunication load)
Number of remote interconnectionpartners
32
Number of functions, master/slave 150
Total of all Master/Slave connec-tions
4 500
Data length of all incomingconnections master/slave, max.
45 000 byte
Data length of all outgoingconnections master/slave, max.
45 000 byte
Number of device-internal andPROFIBUS interconnections
1 000
Data length of device-internal andPROFIBUS interconnections, max.
16 000 byte
Data length per connection, max. 2 000 byte
Remote interconnections withacyclic transmission
- Sampling frequency: Samplingtime, min.
200 ms; Depending on presetcommuncation load, number ofinterconnections and data lengthused
- Number of incominginterconnections
250
- Number of outgoinginterconnections
250
- Data length of all incominginterconnections, max.
8 000 byte
- Data length of all outgoinginterconnections, max.
8 000 byte
- Data length per connection, max. 2 000 byte
Remote interconnections withcyclic transmission
- Transmission frequency:Transmission interval, min.
1 ms; Depending on presetcommunication load, number ofinterconnections and data lengthused
- Number of incominginterconnections
300
- Number of outgoinginterconnections
300
- Data length of all incominginterconnections, max.
4 800 byte
- Data length of all outgoinginterconnections, max.
4 800 byte
- Data length per connection, max. 450 byte
6ES7 414-2XK05-0AB0 6ES7 414-3XM05-0AB0 6ES7 414-3EM06-0AB0
Siemens AG 2011 Siemens AG 2011
-
8/14/2019 Simatic St70 Chap06 English 2011
23/200
SIMATIC S7-400Central processing units
Standard CPUsCPU 414
6/23Siemens ST 70 2011
Technical specifications(continued)
HMI variables via PROFINET(acyclic)
- Number of stations that can log on
for HMI variables (PN OPC/iMap)
2x PN OPC/1x iMap
- HMI variable updating 500 ms
- Number of HMI variables 1 000
- Data length of all HMI variables,max.
32 000 byte
PROFIBUS proxy functionality
- supported Yes; 32 PROFIBUS slaves max.connectable
- Data length per connection, max. 240 byte; Slave-dependent
1st interface
Type of interface Integrated Integrated Integrated
Physics RS 485 / PROFIBUS + MPI RS 485 / PROFIBUS + MPI RS 485 / PROFIBUS + MPI
Isolated Yes Yes Yes
Power supply to interface(15 to 30 V DC), max.
150 mA 150 mA 150 mA
Number of connection resources MPI: 32, DP: 16 MPI: 32, DP: 16 MPI: 32, DP: 16
Functionality
MPI Yes Yes Yes
DP master Yes Yes Yes
DP slave Yes Yes Yes
MPI
Number of connections 32; if a diagnostic repeater is usedon the line, the number ofconnection resources on the line isreduced by 1
32; if a diagnostic repeater is usedon the line, the number ofconnection resources on the line isreduced by 1
32; if a diagnostic repeater is usedon the line, the number ofconnection resources on the line isreduced by 1
Services
- PG/OP communication Yes Yes Yes
- Routing Yes Yes Yes
- Global data communication Yes Yes Yes
- S7 basic communication Yes Yes Yes
- S7 communication Yes Yes Yes- S7 communication, as client Yes Yes Yes
- S7 communication, as server Yes Yes Yes
Transmission rate, max. 12 Mbit/s 12 Mbit/s 12 Mbit/s
DP master
Number of connections, max. 16; if a diagnostic repeater is usedon the line, the number ofconnection resources on the line isreduced by 1
16; if a diagnostic repeater is usedon the line, the number ofconnection resources on the line isreduced by 1
16; if a diagnostic repeater is usedon the line, the number ofconnection resources on the line isreduced by 1
Services
- PG/OP communication Yes Yes Yes
- Routing Yes Yes Yes
- Global data communication No No No
- S7 basic communication Yes Yes Yes
- S7 communication Yes Yes Yes
- S7 communication, as client Yes Yes Yes- S7 communication, as server Yes Yes Yes
- Equidistance mode support Yes Yes Yes
- Isochronous mode Yes Yes Yes
- SYNC/FREEZE Yes Yes Yes
- Activation/deactivation of DPslaves
Yes Yes Yes
- Direct data exchange(slave-to-slave communication)
Yes Yes Yes
- DPV1 Yes Yes Yes
6ES7 414-2XK05-0AB0 6ES7 414-3XM05-0AB0 6ES7 414-3EM06-0AB0
Siemens AG 2011 Siemens AG 2011
-
8/14/2019 Simatic St70 Chap06 English 2011
24/200
SIMATIC S7-400Central processing unitsStandard CPUsCPU 414
6/24 Siemens ST 70 2011
Technical specifications(continued)
Transmission rate, max. 12 Mbit/s 12 Mbit/s 12 Mbit/s
Number of DP slaves, max. 32 32 32
Address area
- Inputs, max. 2 Kibyte 2 Kibyte 2 Kibyte- Outputs, max. 2 Kibyte 2 Kibyte 2 Kibyte
User data per DP slave
- User data per DP slave, max. 244 byte 244 byte 244 byte
- Inputs, max. 244 byte 244 byte 244 byte
- Outputs, max. 244 byte 244 byte 244 byte
- Slots, max. 244 244 244
- per slot, max. 128 byte 128 byte 128 byte
DP slave
Number of connections 16 16 16
Services
- PG/OP communication Yes; with interface active Yes; with interface active Yes; with interface active
- S7 routing Yes; With interface active Yes; With interface active Yes; With interface active
- Global data communication No No No
- S7 basic communication No No No
- S7 communication Yes Yes Yes- S7 communication, as client Yes Yes Yes
- S7 communication, as server Yes Yes Yes
- Direct data exchange(slave-to-slave communication)
No No No
- DPV1 No No No
GSD file http://support.automation.siemens.com/WW/view/en/113652
http://support.automation.siemens.com/WW/view/en/113652
http://support.automation.siemens.com/WW/view/en/113652
Transmission rate, max. 12 Mbit/s 12 Mbit/s 12 Mbit/s
Automatic baud rate search No No No
Transfer memory
- Inputs 244 byte 244 byte 244 byte
- Outputs 244 byte 244 byte 244 byte
Address area, max. 32; Virtual slots 32; Virtual slots 32; Virtual slots
User data per address area, max. 32 byte 32 byte 32 byte
User data per address area, of
which consistent, max.
32 byte 32 byte 32 byte
2nd interface
Type of interface Integrated Integrated PROFINET
Physics RS 485 / PROFIBUS RS 485 / PROFIBUS Ethernet RJ45
Isolated Yes Yes Yes
Integrated switch Yes
Number of ports 2
Power supply to interface(15 to 30 V DC), max.
150 mA 150 mA
Automatic detection of transmissionspeed
Yes; Autosensing
Autonegotiation Yes
Autocrossing Yes
Media redundancy
supported Yes
Switchover time on line break,typically
200 ms
Number of stations in the ring, max. 50
Change of IP address at runtime,supported
Yes; Assignment by higher-level IOcontroller or by the user programwith SFB104 "IP_CONF"
6ES7 414-2XK05-0AB0 6ES7 414-3XM05-0AB0 6ES7 414-3EM06-0AB0
Siemens AG 2011 Siemens AG 2011
-
8/14/2019 Simatic St70 Chap06 English 2011
25/200
SIMATIC S7-400Central processing units
Standard CPUsCPU 414
6/25Siemens ST 70 2011
Technical specifications(continued)
Number of connection resources 16 16 64
Functionality
DP master Yes Yes No
DP slave Yes Yes No
PROFINET IO controller Yes
PROFINET IO device Yes
PROFINET CBA Yes
Open IE communication Yes
Web server Yes
- Number of HTTP clients 5
Local Operating Network No
DP master
Number of connections, max. 16 16
Services
- PG/OP communication Yes Yes
- Routing Yes Yes
- Global data communication No No
- S7 basic communication Yes Yes
- S7 communication Yes Yes
- S7 communication, as client Yes Yes
- S7 communication, as server Yes Yes
- Equidistance mode support Yes Yes
- Isochronous mode Yes Yes
- SYNC/FREEZE Yes Yes
- Activation/deactivation of DPslaves
Yes Yes
- Direct data exchange(slave-to-slave communication)
Yes Yes
- DPV1 Yes Yes
Transmission rate, max. 12 Mbit/s 12 Mbit/s
Number of DP slaves, max. 96 96
Address area
- Inputs, max. 6 Kibyte 6 Kibyte
- Outputs, max. 6 Kibyte 6 Kibyte User data per DP slave
- User data per DP slave, max. 244 byte 244 byte
- Inputs, max. 244 byte 244 byte
- Outputs, max. 244 byte 244 byte
- Slots, max. 244 244
- per slot, max. 128 byte 128 byte
DP slave
Number of connections 16 16
Services
- Routing Yes Yes
- Programming Yes Yes
GSD file http://support.automation.siemens.com/WW/view/en/113652
http://support.automation.siemens.com/WW/view/en/113652
Transmission rate, max. 12 Mbit/s 12 Mbit/s
Transfer memory
- Inputs 244 byte 244 byte
- Outputs 244 byte 244 byte
Address area, max. 32 32
User data per address area, max. 32 byte 32 byte
User data per address area, ofwhich consistent, max.
32 byte 32 byte
6ES7 414-2XK05-0AB0 6ES7 414-3XM05-0AB0 6ES7 414-3EM06-0AB0
Siemens AG 2011 Siemens AG 2011
-
8/14/2019 Simatic St70 Chap06 English 2011
26/200
SIMATIC S7-400Central processing unitsStandard CPUsCPU 414
6/26 Siemens ST 70 2011
Technical specifications(continued)
PROFINET IO controller
Services
- PG/OP communication Yes
- S7 routing Yes- S7 communication Yes
- Isochronous mode Yes; only with IRT and the HighPerformance option
- Open IE communication Yes
Transmission rate, min. 10 Mbit/s
Transmission rate, max. 100 Mbit/s
Number of connectable IO devices,max.
256
Max. number of connectableIO devices for RT
256
- of which in line, max. 256
Number of IO devices with IRT andthe option "high flexibility"
256
- of which in line, max. 61
Number of IO devices with IRT and
the option "high performance", max.
64
- of which in line, max. 64
IRT, supported Yes
Shared device, supported Yes
Prioritized startup supported Yes
- Number of IO devices, max. 32
Activation/deactivation ofIO devices
Yes
- Number of IO devices that canbe simultaneously activated/deactivated, max.
8
IO devices changing duringoperation (partner ports),supported
Yes
- Max. number of IO devices pertool
8; 8 parallel calls of the SFC 12"D_ACT_DP" possible per line.Max. 32 IO devices changing
during operation (partner ports)are supported.
Device replacement without swapmedium
Yes
Send clock times 250 s, 500 s, 1 ms, 2 ms, 4 msadditionally with IRT with highperformance: 250 s to 4 ms in125 s frame
Updating time 250 s to 512 ms; minimum valuedepends on preset communicationshare for PROFINET IO, on thenumber of IO devices and on theamount of configured user data,see PROFINET system description
Address area
- Inputs, max. 8 Kibyte
- Outputs, max. 8 Kibyte
User data per address area, max.- User data consistency, max. 1 024 byte
6ES7 414-2XK05-0AB0 6ES7 414-3XM05-0AB0 6ES7 414-3EM06-0AB0
Siemens AG 2011 Siemens AG 2011
-
8/14/2019 Simatic St70 Chap06 English 2011
27/200
-
8/14/2019 Simatic St70 Chap06 English 2011
28/200
SIMATIC S7-400Central processing unitsStandard CPUsCPU 414
6/28 Siemens ST 70 2011
Technical specifications(continued)
DP master
Number of connections, max. 16 16
Services
- PG/OP communication Yes Yes- Routing Yes; S7 routing Yes; S7 routing
- Global data communication No No
- S7 basic communication No Yes
- S7 communication Yes Yes
- S7 communication, as client Yes Yes
- S7 communication, as server Yes Yes
- Equidistance mode support Yes Yes
- Isochronous mode Yes Yes
- SYNC/FREEZE Yes Yes
- Activation/deactivation of DPslaves
Yes Yes
- Direct data exchange(slave-to-slave communication)
Yes Yes
- DPV0 Yes Yes
- DPV1 Yes Yes
Transmission rate, max. 12 Mbit/s 12 Mbit/s
Transmission rate, min. 9.6 kbit/s 9.6 kbit/s
Number of DP slaves, max. 96 96
Address area
- Inputs, max. 6 Kibyte 6 Kibyte
- Outputs, max. 6 Kibyte 6 Kibyte
User data per DP slave
- User data per DP slave, max. 244 byte 244 byte
- Inputs, max. 244 byte 244 byte
- Outputs, max. 244 byte 244 byte
- Slots, max. 244 244
- per slot, max. 128 byte 128 byte
DP slave
Number of connections 16 16
Services
- PG/OP communication Yes Yes
- S7 routing Yes; With active interface Yes; With active interface
- Global data communication No No
- S7 basic communication No No
- S7 communication Yes Yes
- S7 communication, as client Yes Yes
- S7 communication, as server Yes Yes
- SYNC/FREEZE No No
- Direct data exchange(slave-to-slave communication)
No No
- DPV1 No No
- Status/control Yes; When interface active Yes; When interface active
GSD file http://support.automation.siemens.com/WW/view/en/113652
http://support.automation.siemens.com/WW/view/en/113652
Transmission rate, min. 9.6 kbit/s 9.6 kbit/s
Transmission rate, max. 12 Mbit/s 12 Mbit/s Automatic baud rate search No No
Transfer memory
- Inputs 244 byte 244 byte
- Outputs 244 byte 244 byte
Address areas, max. 32 32; Virtual slots
User data per address area, max. 32 byte 32 byte
User data per address area, ofwhich consistent, max.
32 byte 32 byte
6ES7 414-2XK05-0AB0 6ES7 414-3XM05-0AB0 6ES7 414-3EM06-0AB0
Siemens AG 2011 Siemens AG 2011
-
8/14/2019 Simatic St70 Chap06 English 2011
29/200
SIMATIC S7-400Central processing units
Standard CPUsCPU 414
6/29Siemens ST 70 2011
Technical specifications(continued)
Isochronous mode
Isochronous mode Yes; For PROFIBUS only Yes; For PROFIBUS only Yes; Via PROFIBUS DP orPROFINET interface
Number of DP masters withisochronous mode
2 3 2
User data per isochronous slave,max.
244 byte 244 byte 244 byte
Equidistance Yes Yes Yes
Shortest clock pulse 1 ms; 0.5 ms without use ofSFC 126, 127
1 ms; 0.5 ms without use ofSFC 126, 127
1 ms; 0.5 ms without use ofSFC 126, 127
Max. cycle 32 ms 32 ms 32 ms
CiR - Configuration in RUN
CiR synchronization time, basic load 100 ms 100 ms 100 ms
CiR synchronization time, time perI/O slave
15 s; Time per I/O byte 15 s 15 s; Time per I/O byte
programming
Configuration software
STEP 7 Yes Yes Yes
Programming language
STEP 7 Yes Yes Yes
LAD Yes Yes Yes
FBD Yes Yes Yes
STL Yes Yes Yes
SCL Yes Yes Yes
CFC Yes Yes Yes
GRAPH Yes Yes Yes
HiGraph Yes Yes Yes
Nesting levels 7 7 7
Know-how protection
User program protection/passwordprotection
Yes Yes Yes
Block encryption Yes; With S7 block PrivacyEMC
Emission of radio interference acc. toEN 55 011
Limit value class A, for use inindustrial areas
Yes
Limit value class B, for use inresidential areas
No
Dimensions
Required slots 1 2 2
Dimensions and weight
Dimensions
Width 25 mm 50 mm 50 mm
Height 290 mm 290 mm 290 mm
Depth 219 mm 219 mm 219 mm
Weight Weight, approx. 0.7 kg 0.9 kg 900 g
6ES7 414-2XK05-0AB0 6ES7 414-3XM05-0AB0 6ES7 414-3EM06-0AB0
Siemens AG 2011 Siemens AG 2011
-
8/14/2019 Simatic St70 Chap06 English 2011
30/200
SIMATIC S7-400Central processing unitsStandard CPUsCPU 414
6/30 Siemens ST 70 2011
Ordering data Order No. Order No.
CPU 414-2 6ES7 414-2XK05-0AB0
Work memory 1 MB, powersupply 24 V DC, MPI/PROFIBUSDP master interface, slot for
memory card, incl. slot numberlabels
CPU 414-3 6ES7 414-3XM05-0AB0
Work memory 2.8 MB, powersupply 24 V DC, MPI/PROFIBUSDP master interface, PROFIBUSDP master interface, slot formemory card, module slots for1 IF module, incl. slot numberlabels
CPU 414-3 PN/DP 6ES7 414-3EM06-0AB0
Work memory 4 MB, powersupply 24 V DC, MPI/PROFIBUSDP master interface, PROFINETinterface, slot for memory card,module slot for 1 IF module, incl.slot number labels
Memory card RAM
64 KB 6ES7 952-0AF00-0AA0
256 KB 6ES7 952-1AH00-0AA0
1 MB 6ES7 952-1AK00-0AA0
2 MB 6ES7 952-1AL00-0AA0
4 MB 6ES7 952-1AM00-0AA0
8 MB 6ES7 952-1AP00-0AA0
16 MB 6ES7 952-1AS00-0AA0
64 MB 6ES7 952-1AY00-0AA0
FEPROM memory card
64 KB 6ES7 952-0KF00-0AA0
256 KB 6ES7 952-0KH00-0AA01 MB 6ES7 952-1KK00-0AA0
2 MB 6ES7 952-1KL00-0AA0
4 MB 6ES7 952-1KM00-0AA0
8 MB 6ES7 952-1KP00-0AA0
16 MB 6ES7 952-1KS00-0AA0
32 MB 6ES7 952-1KT00-0AA0
64 MB 6ES7 952-1KY00-0AA0
MPI cable 6ES7 901-0BF00-0AA0
for connection of SIMATIC S7 andPG via MPI; 5 m in length
IF 964-DP interface module 6ES7 964-2AA04-0AB0
To connect an additional DP line;for CPU 414-3, CPU 414-3 PN/DP,CPU 416-3, CPU 416-3 PN/DP,
CPU 417-4Slot number labels 6ES7 912-0AA00-0AA0
1 set (spare part)
Manual "SIMATIC S7-400programmable controller"
incl. instruction list
German 6ES7 498-8AA05-8AA0
English 6ES7 498-8AA05-8BA0
S7-400 operation list
German 6ES7 498-8AA05-8AN0
English 6ES7 498-8AA05-8BN0
Manual "Communication forSIMATIC S7-300/-400"
German 6ES7 398-8EA00-8AA0
English 6ES7 398-8EA00-8BA0
French 6ES7 398-8EA00-8CA0
Spanish 6ES7 398-8EA00-8DA0
Italian 6ES7 398-8EA00-8EA0
SIMATIC manual collection J 6ES7 998-8XC01-8YE0
Electronic manuals on DVD,multilingual: LOGO!, SIMADYN,SIMATIC bus components,SIMATIC C7,SIMATIC distributed I/O,SIMATIC HMI, SIMATIC Sensors,SIMATIC NET, SIMATIC PC BasedAutomation, SIMATIC PCS 7,SIMATIC PG/PC, SIMATIC S7,
SIMATIC Software, SIMATIC TDC
SIMATIC manual collectionupdate service for 1 year
D 6ES7 998-8XC01-8YE2
Current "Manual Collection" DVDand the three subsequentupdates
Brochure "SIMATIC S7-400programmable controller -Design and application"
German 6ES7 498-8AA00-8AB0
English 6ES7 498-8AA00-8BB0
D: Subject to export regulations AL: N and ECCN: 5D992
J: Subject to export regulations AL: N and ECCN: EAR99S
Siemens AG 2011 Siemens AG 2011
-
8/14/2019 Simatic St70 Chap06 English 2011
31/200
SIMATIC S7-400Central processing units
Standard CPUsCPU 414
6/31Siemens ST 70 2011
Ordering data Order No. Order No.
I: Subject to export regulations AL: N and ECCN: EAR99H
PROFIBUS bus components
RS 485 bus connector with90 cable outlet
Max. transfer rate 12 Mbit/s
Without PG interface 6ES7 972-0BA12-0XA0
With PG interface 6ES7 972-0BB12-0XA0
RS 485 bus connector withangled cable outlet
Max. transfer rate 12 Mbit/s
Without PG interface 6ES7 972-0BA42-0XA0
With PG interface 6ES7 972-0BB42-0XA0
RS 485 bus connector with90 cable outlet forFast Connect system
Max. transfer rate 12 Mbit/s
without PG interface
1 unit 6ES7 972-0BA52-0XA0
100 units 6ES7 972-0BA52-0XB0
with PG interface
1 unit 6ES7 972-0BB52-0XA0
100 units 6ES7 972-0BB52-0XB0
RS 485 bus connector withaxial cable outlet
For SIMATIC OP, for connection toPPI, MPI, PROFIBUS
6GK1 500-0EA02
PROFIBUS FastConnect buscable
Standard type with special design
for quick mounting, 2-core,shielded, sold by the meter, max.delivery unit 1000 m, minimumordering quantity 20 m
6XV1 830-0EH10
RS 485 repeater for PROFIBUS 6ES7 972-0AA02-0XA0
Transfer rate up to 12 Mbit/s;24 V DC; IP20 enclosure
PROFINET bus components
IE FC TP standard cable GP 2x2 6XV1 840-2AH10
4-core, shielded TP installationcable for connection to IE
FC Outlet RJ45/ IE FC RJ45 Plug;PROFINET-compatible; with ULapproval;
Sold by the meter
FO standard cable GP (50/125) 6XV1 873-2A
Standard cable, splittable, ULapproval, sold by the meter
SCALANCE X204-2 IndustrialEthernet switch
I 6GK5 204-2BB10-2AA3
Industrial Ethernet Switches withintegral SNMP access, webdiagnostics, copper cablediagnostics and PROFINETdiagnostics for configuring line,star and ring topologies; four10/100 Mbit/s RJ45 ports and twoFO ports
IE FC RJ45 plugs
RJ45 plug connector for IndustrialEthernet with a rugged metalenclosure and integratedinsulation displacement contactsfor connecting Industrial EthernetFC installation cables
IE FC RJ45 plug 180
180 cable outlet
1 unit 6GK1 901-1BB10-2AA0
10 units 6GK1 901-1BB10-2AB0
50 units 6GK1 901-1BB10-2AE0
PROFIBUS/PROFINET buscomponents
see Catalogs IK PI, CA 01
For establishing MPI/PROFIBUS/PROFINET communication
Siemens AG 2011 Siemens AG 2011
-
8/14/2019 Simatic St70 Chap06 English 2011
32/200
SIMATIC S7-400Central processing unitsStandard CPUsCPU 416
6/32 Siemens ST 70 2011
Overview
High-performance CPUs in the high-end performance range
Applicable for plants with high requirements in the high-endperformance range
Integrated PROFINET functions in CPU 416-3 PN/DP
Technical specifications6ES7 416-2XN05-0AB0 6ES7 416-3XR05-0AB0 6ES7 416-3ES06-0AB0
Product type designation CPU416-3 PN/DP
Product version
Hardware product version 01
Firmware version V5.0 V5.0 V6.0
Associated programming package STEP7 V 5.3 SP2 or higher withHW update
STEP7 V 5.3 SP2 or higher withHW update
STEP7 V5.5 or higher/iMap V3.0 +iMap STEP7 Add-on V3.0 SP5 orhigher
Supply voltages
Rated value
24 V DC No; Power supply via systempower supply
Feeding of external backup voltageto CPU
5 to 15 V DC 5 to 15 V DC 5 to 15 V DC
Current consumption
from backplane bus 5 V DC, max. 1.1 A 1.3 A 1.5 A
from interface 5 V DC, max. 90 mA; at each DP interface 90 mA; at each DP interface 90 mA; at each DP interface
Power losses
Power loss, typ. 4 W 4.5 W 6.5 W
Power loss, max. 7.5 W
Backup battery
Battery operation not relevant
Backup current, typ. 125 A; valid up to 40C 125 A; valid up to 40C 125 A; (up to 40 C)
Backup current, max. 550 A 550 A 450 A
Memory
Work memory
integrated (for program) 2.8 Mbyte 5.6 Mbyte 8 Mbyte integrated (for data) 2.8 Mbyte 5.6 Mbyte 8 Mbyte
expandable No No No
Load memory
expandable FEPROM Yes Yes Yes; with Memory Card (FLASH)
expandable FEPROM, max. 64 Mbyte 64 Mbyte 64 Mbyte
integrated RAM, max. 1 Mbyte 1 Mbyte 1 Mbyte
expandable RAM Yes Yes Yes; with Memory Card (RAM)
expandable RAM, max. 64 Mbyte 64 Mbyte 64 Mbyte
Backup
present Yes Yes Yes
with battery Yes Yes Yes; all data
without battery No No No
Siemens AG 2011 Siemens AG 2011
-
8/14/2019 Simatic St70 Chap06 English 2011
33/200
SIMATIC S7-400Central processing units
Standard CPUsCPU 416
6/33Siemens ST 70 2011
Technical specifications(continued)
CPU-blocks
DB
Number, max. 10 000; Number range: 1 to 16000 10 000; Number range: 1 to 16000 10 000; Number range: 1 to 16000
Size, max. 64 Kibyte 64 Kibyte 64 Kibyte
FB
Number, max. 5 000; Number range: 0 to 7999 5 000; Number range: 0 to 7999 5 000; Number range: 0 to 7999
Size, max. 64 Kibyte 64 Kibyte 64 Kibyte
FC
Number, max. 5 000; Number range: 0 to 7999 5 000; Number range: 0 to 7999 5 000; Number range: 0 to 7999
Size, max. 64 Kibyte 64 Kibyte 64 Kibyte
OB
Size, max. 64 Kibyte 64 Kibyte 64 Kibyte
Nesting depth
per priority class 24 24 24
additional within an error OB 2 2 2
CPU processing times
for bit operations, min. 30 ns 30 ns 30 ns
for word operations, min. 30 ns 30 ns 30 ns
for fixed point arithmetic, min. 30 ns 30 ns 30 ns
for floating point arithmetic, min. 90 ns 90 ns 90 ns
Counters, timers and theirretentivity
S7 counter
Number 2 048 2 048 2 048
Retentivity
- adjustable Yes Yes Yes
- lower limit 0 0 0
- upper limit 2 047 2 047 2 047
- preset Z 0 to Z 7 Z 0 to Z 7 Z 0 to Z 7
Counting range
- lower limit 0 0 0
- upper limit 999 999 999
IEC counter
present Yes Yes Yes
Type SFB SFB SFB
Number Unlimited (limited only by workmemory)
S7 times
Number 2 048 2 048 2 048
Retentivity
- adjustable Yes Yes Yes
- lower limit 0 0 0
- upper limit 2 047 2 047 2 047
- preset No times retentive No times retentive No times retentive
Time range
- lower limit 10 ms 10 ms 10 ms
- upper limit 9 990 s 9 990 s 9 990 s
IEC timer
Present Yes Yes Yes
Type SFB SFB SFB
Number Unlimited (limited only by workmemory)
6ES7 416-2XN05-0AB0 6ES7 416-3XR05-0AB0 6ES7 416-3ES06-0AB0
Siemens AG 2011 Siemens AG 2011
-
8/14/2019 Simatic St70 Chap06 English 2011
34/200
SIMATIC S7-400Central processing unitsStandard CPUsCPU 416
6/34 Siemens ST 70 2011
Technical specifications(continued)
Data areas and their retentivity
retentive data area, total Total working and load memory(with backup battery)
Total working and load memory(with backup battery)
Total working and load memory(with backup battery)
Flag
Number, max. 16 Kibyte 16 Kibyte 16 Kibyte; Size of bit memoryaddress area
Retentivity available Yes Yes Yes
Number of clock memories 8; (in 1 memory byte) 8; (in 1 memory byte) 8; (in 1 memory byte)
Data blocks
Number, max. 10 000; Number range: 1 to 16000 10 000; Number range: 1 to 16000 10 000; Number range: 1 to 16000
Size, max. 64 Kibyte 64 Kibyte 64 Kibyte
Local data
adjustable, max. 32 Kibyte 32 Kibyte 32 Kibyte
preset 16 Kibyte 16 Kibyte 16 Kibyte
Address area
I/O address area
overall 16 Kibyte 16 Kibyte 16 Kibyte
Outputs 16 Kibyte 16 Kibyte 16 Kibyte of which, distributed
- MPI/DP interface, inputs 2 Kibyte 2 Kibyte 2 Kibyte
- MPI/DP interface, outputs 2 Kibyte 2 Kibyte 2 Kibyte
- DP interface, inputs 8 Kibyte 8 Kibyte 8 Kibyte
- DP interface, outputs 8 Kibyte 8 Kibyte 8 Kibyte
- PN interface, inputs 8 Kibyte
- PN interface, outputs 8 Kibyte
Process image
Inputs, adjustable 16 Kibyte 16 Kibyte 16 Kibyte
Outputs, adjustable 16 Kibyte 16 Kibyte 16 Kibyte
Inputs, preset 512 byte 512 byte 512 byte
Outputs, preset 512 byte 512 byte 512 byte
Consistent data, max. 244 byte 244 byte 244 byte
Access to consistent data inprocess image
Yes Yes Yes
Subprocess images
Number of subprocess images,max.
15 15 15
Digital channels
Inputs 131 072 131 072 131 072
Outputs 131 072 131 072 131 072
Inputs, of which central 131 072 131 072 131 072
Outputs, of which central 131 072 131 072 131 072
Analog channels
Inputs 8 192 8 192 8 192
Outputs 8 192 8 192 8 192
Inputs, of which central 8 192 8 192 8 192
Outputs, of which central 8 192 8 192 8 192
6ES7 416-2XN05-0AB0 6ES7 416-3XR05-0AB0 6ES7 416-3ES06-0AB0
Siemens AG 2011 Siemens AG 2011
-
8/14/2019 Simatic St70 Chap06 English 2011
35/200
SIMATIC S7-400Central processing units
Standard CPUsCPU 416
6/35Siemens ST 70 2011
Technical specifications(continued)
Hardware configuration
connectable OPs 63 63 95
Central devices, max. 1 1 1
Expansion devices, max. 21 21 21
Multicomputing Yes; 4 CPUs max.(with UR1 or UR2)
Yes; 4 CPUs max.(with UR1 or UR2)
Yes; 4 CPUs max.(with UR1 or UR2)
Interface modules
Number of connectable IMs (total),max.
6 6 6
Number of connectable IMs 460,max.
6 6 6
Number of connectable IMs 463,max.
4; IM 463-2 4; IM 463-2 4; IM 463-2
Number of DP masters
integrated 2 2 1
via IM 467 4 4 4
via CP 10; CP 443-5 Extended 10; CP 443-5 Extended 10; CP 443-5 Extended
Mixed mode IM + CP permitted No; IM 467 cannot be used withCP 443-5 Ext.; IM 467 cannot beused with CP 443-1 EX40 inPN IO mode
No; IM 467 cannot be used withCP 443-5 Ext.; IM 467 cannot beused with CP 443-1 EX40 inPN IO mode
No; IM 467 not suitable for use withCP 443-5 Ext. and CP443-1 EX4x,EX20, GX20 (in PNIO mode)
via interface module 0 1 1; IF 964-DP
Number of pluggable S5 modules(via adapter capsule in centraldevice), max.
6 6 6
Number of IO controllers
integrated 1
via CP 4; Via CP 443-1 EX 41 in PN mode;max. 4 in central controller
4; Via CP 443-1 EX 41 in PN mode;max. 4 in central controller
4; No mixed operation of CP443-1EX40 and CP443-1 EX 41/EX20/GX20, max. 4 in central controller
Number of operable FMs and CPs(recommended)
FM Limited by number of slots andnumber of connections
Limited by number of slots andnumber of connections
Limited by number of slots ornumber of connections
CP, point-to-point Limited by number of slots andnumber of connections
Limited by number of slots andnumber of connections
CP 440: Limited by number ofslots; CP 441: Limited by numberof slots and number of connections
PROFIBUS and Ethernet CPs 14; Of which 10 CP or IM max. asDP master and PN controller
14; Of which 10 CP or IM max. asDP master and PN controller
14; In total max. 10 CPs as DPmaster and PN controller, of whichup to 10 IMs or CPs as DP masterand up to 4 CPs as PN controller
Time
Clock
Hardware clock (real-time clock) Yes Yes Yes
battery-backed and synchronizable Yes Yes Yes
Resolution 1 ms 1 ms 1 ms
Runtime meter
Number 8 8 16
Clock synchronization
supported Yes Yes Yes to MPI, master Yes Yes Yes
to MPI, slave Yes Yes Yes
to DP, master Yes Yes Yes
to DP, slave Yes Yes Yes
in AS, master Yes Yes Yes
in AS, slave Yes Yes Yes
on Ethernet via NTP Via CP Via CP Yes; as client
to IF 964 DP Yes Yes
6ES7 416-2XN05-0AB0 6ES7 416-3XR05-0AB0 6ES7 416-3ES06-0AB0
Siemens AG 2011 Siemens AG 2011
-
8/14/2019 Simatic St70 Chap06 English 2011
36/200
SIMATIC S7-400Central processing unitsStandard CPUsCPU 416
6/36 Siemens ST 70 2011
Technical specifications(continued)
S7 message functions
Number of login stations formessage functions, max.
63; Max. 63 with ALARM_S andALARM_D (OPs); max. 12 with
ALARM_8 and ALARM_P(e.g. WinCC)
63; Max. 63 with ALARM_S andALARM_D (OPs); max. 12 with
ALARM_8 and ALARM_P(e.g. WinCC)
95; Max. 95 with Alarm_S/SQ andAlarm_D/DQ (OPs); max. 8 with
Alarm, Alarm_8, Alarm_8P, Notifyand Notify_8 (e.g. WinCC)
Symbol-related messages Yes Yes Yes
SCAN procedure Yes
Number of messages
overall, max. 1 024 1 024 1 024
Block related messages Yes Yes Yes
Process diagnostic messages Yes
Alarm 8-blocks Yes Yes Yes
Process control messages Yes Yes Yes
Test commissioning functions
Status/control
Status/control variable Yes Yes Yes; Up to 16 variable tables
Forcing Forcing Yes Yes Yes
Status block Yes Yes Yes; Up to 16 simultaneously
Single step Yes Yes Yes
Number of breakpoints 4 4 16
Diagnostic buffer
present Yes Yes Yes
Number of entries, max. 3 200 3 200 3 200
- adjustable Yes Yes Yes
- preset 120 120 120
Service data
can be read out Yes
Communication functions
PG/OP communication Yes Yes Yes
Data record routing Yes
Routing Yes Yes Yes; S7 routing
Global data communication
supported Yes Yes Yes
Size of GD packets, max. 54 byte 54 byte 54 byte
S7 basic communication
supported Yes Yes Yes
User data per job, max. 76 byte 76 byte 76 byte
S7 communication
supported Yes Yes Yes
as server Yes
as client Yes
User data per job, max. 64 Kibyte 64 Kibyte 64 Kibyte
S5-compatible communication supported Yes; (via CP max. 10 and FC
AG_SEND and FC AG_RECV)Yes; (via CP max. 10 and FCAG_SEND and FC AG_RECV)
Yes