Siemens Canada Limited Industrial Control Product Catalog 2019 1/1 1 MOTOR STARTER PROTECTORS contents Section Overview 1/2 - 1/3 Motor Starter Protectors 3RV20 MSP, Class 10/20 1/4 - 1/5 Circuit Breakers 3RV27, 3RV28 Circuit Breaker UL 489 1/6 Accessories Auxiliary Switches 1/7 Auxiliary Releases 1/7 Busbars 1/8 Mounting Accessories 1/9 - 1/12 Rotary Operating Mechanisms 1/13 Enclosures & Front Plates 1/13 3RV29 Infeed System 1/14 - 1/17 General Data for Motor Starter Protectors Manual Motor Starter Ratings 1/18 Group Installation Ratings 1/19 Combination Motor Controller Ratings 1/20 3RV27 and 3RV28 Circuit Breaker Ratings 1/21 Export Application Ratings 1/22 - 1/23 Rules for Mounting 1/24 Technical Data 1/25 - 1/28 Overview of MSP Functions & Applications 1/29 Application as a Combination Motor Controller 1/30 Application in DC Switching 1/31 Design 1/31 Characteristics 1/32 Circuit Diagrams 1/32 Dimensions 1/33 - 1/34 General Data for Accessories Mountable Accessories Overview 1/35 - 1/36 Circuit Diagrams 1/37 - 1/35 Dimensions 1/38 Busbar Accessories Overview 1/39 Dimensions 1/40 - 1/41 Operating Mechanisms Overview 1/42 Circuit Diagrams 1/43 Dimensions 1/43 - 1/44 Enclosures & Front Plates Overview 1/45 Dimensions 1/46 Spring Terminal Infeed System Design 1/47 Technical Data 1/47 Dimensions 1/48 1 Motor Starter Protectors Industrial Controls Product Catalog 2019 Section

Transcript of SIIS Motor Starter Protectors 1 - Siemensd...Manual Motor Starter Ratings 1/18 Group Installation...

  • SIRIUS

    Siemens Canada Limited Industrial Control Product Catalog 2019 1/1

    1M

    OTO

    R STARTER

    PROTECTO

    RS

    Siemens / Industrial Controls Previous folio: IC10 1/1

    contentsSection Overview 1/2 - 1/3

    Motor Starter Protectors3RV20 MSP, Class 10/20 1/4 - 1/5

    Circuit Breakers3RV27, 3RV28 Circuit Breaker UL 489 1/6

    AccessoriesAuxiliary Switches 1/7Auxiliary Releases 1/7Busbars 1/8Mounting Accessories 1/9 - 1/12Rotary Operating Mechanisms 1/13Enclosures & Front Plates 1/133RV29 Infeed System 1/14 - 1/17

    General Data for Motor Starter ProtectorsManual Motor Starter Ratings 1/18Group Installation Ratings 1/19Combination Motor Controller Ratings 1/203RV27 and 3RV28 Circuit Breaker Ratings 1/21Export Application Ratings 1/22 - 1/23Rules for Mounting 1/24Technical Data 1/25 - 1/28Overview of MSP Functions & Applications 1/29Application as a Combination Motor Controller 1/30Application in DC Switching 1/31Design 1/31Characteristics 1/32Circuit Diagrams 1/32Dimensions 1/33 - 1/34

    General Data for AccessoriesMountable Accessories Overview 1/35 - 1/36 Circuit Diagrams 1/37 - 1/35 Dimensions 1/38Busbar Accessories Overview 1/39 Dimensions 1/40 - 1/41Operating Mechanisms Overview 1/42 Circuit Diagrams 1/43 Dimensions 1/43 - 1/44Enclosures & Front Plates Overview 1/45 Dimensions 1/46Spring Terminal Infeed System Design 1/47 Technical Data 1/47 Dimensions 1/48

    1Motor Starter Protectors Industrial Controls Product Catalog 2019 Section

  • SIRIUS

    Siemens Canada Limited Industrial Control Product Catalog 20191/2

    1M

    OTO

    R ST

    ART

    ER

    PRO

    TECT

    ORS

    IEC Power Control

    Motor Starter Protectors

    Product Category IEC

    c o n t e n t s

    SIRIUS 3RV motor starter protectors up to 100 A

    Size S00, S0

    For motor protectionCLASS 10Selection and ordering data

    Size Rated Current PageS00 up to 16 A 1/4 S0 up to 40 A 1/4S2 up to 65 A 1/5S3 up to 100 A 1/5

    For motor protectionCLASS 20Selection and ordering data

    Size Rated Current PageS2 up to 65 A 1/5S3 up to 100 A 1/5

    General data for SIRIUSmotor starter protectors PageTechnical data 1/18Overview 1/28Characteristics 1/32Circuit diagrams 1/32Dimension drawings 1/33

    Circuit Breakers 3RV27, 3RV28

    SIRIUS 3RV29infeed system

    3RV MSP auxiliaries and accessories

    Page

    Selection and ordering data 1/6

    Page

    Selection and ordering data 1/16-1/17

    Page

    Selection and ordering data 1/7-1/8

    Dimension drawings 1/34 Technical data 1/47Overview 1/14-1/15Dimension drawings 1/48

    Technical data 1/27 Overview 1/35 Circuit diagrams 1/37 Dimension drawings 1/38

  • SIRIUS

    Siemens Canada Limited Industrial Control Product Catalog 2019 1/3

    1M

    OTO

    R STARTER

    PROTECTO

    RSIEC Power Control

    Accessories

    Product Category IEC

    c o n t e n t s

    3RV busbar and accessories

    Accessories for motor starter protectors with Spring-Type terminals

    Mounting Accessories

    Page

    Selection and ordering data 1/8

    Page

    Selection and ordering data 1/7

    Page

    Selection and ordering data 1/9 -1/12

    Overview 1/39Technical data 1/40

    Technical data 1/28 Overview 1/36Technical data 1/38

    Rotary operating mechanisms Enclosures and front plates

    Page

    Selection and ordering data 1/13

    Page

    Selection and ordering data 1/13

    Technical data 1/28Overview 1/42Circuit diagrams 1/43Dimension drawings 1/43

    Overview 1/45Dimension drawings 1/46

  • SIRIUS

    Siemens Canada Limited Industrial Control Product Catalog 20191/4

    1M

    OTO

    R ST

    ART

    ER

    PRO

    TECT

    ORS

    Note: Select MSP by motor Full Load Amperes. Horsepower ratings are for reference only.

    1) Select motor starter protector by motor full load amps. Horsepower ratings for reference only.

    2) The motor starter protectors rated up to 32 A can be used as manual motor controllers or as Type E combination motor controllers. For use as a Type E combination motor control-ler, a Type E terminal is required. See accessories page 1/10.

    3) These products are NOT certified as Type E combi-nation motor controllers. They can only be used as manual motor controllers.

    4) 3RV2 MSPs can only be used with Innovations contac-tors and accessories

    5) Available only with •• = 10, or •• = 15, or •• = 20

    6) Available only with •• = 10, or •• = 15

    7) Available only with •• = 10, or •• = 20

    Illustration

    FLA Adjustment Range [A]

    Single-Phase HP Ratings

    Three-Phase HP Ratings1)

    Instant- aneous short circuit release [A]

    UL short-circuit breaking capacity @ 480V [kA]

    Size S00 2) 4)

    Order Number

    Size S0 2) 4)

    Order Number115V 230V 200V 230V 460V 575V

    0.11-0.160.14-0.20.18-0.250.22-0.32

    ————

    ————

    ————

    ————

    ————

    ————

    2.12.63.34.2

    65656565

    3RV2011-0AA●●3RV2011-0BA●●3RV2011-0CA●●3RV2011-0DA●●

    ————

    0.28-0.40.35-0.50.45-0.630.55-0.8

    ————

    ————

    ————

    ————

    ———½

    ———½

    5.26.58.2

    10

    65656565

    3RV2011-0EA●●3RV2011-0FA●●3RV2011-0GA●●3RV2011-0HA●●

    ——

    3RV2021-0GA●●3RV2021-0HA●●

    0.7-10.9-1.251.1-1.61.4-2

    ————

    ——1⁄101⁄6

    ————

    ——½½

    ½¾11

    ½¾11 ½

    13162126

    65656565

    3RV2011-0JA●●3RV2011-0KA●●3RV2011-1AA●●3RV2011-1BA●●

    3RV2021-0JA●●3RV2021-0KA●●3RV2021-1AA●●3RV2021-1BA●●

    1.8-2.52.2-3.22.8-43.5-5

    1⁄101⁄81⁄6¼

    ¼1⁄3½½

    ½¾11 ½

    ¾111 ½

    1 ½233

    2335

    33425265

    65656565

    3RV2011-1CA●●3RV2011-1DA●●3RV2011-1EA●●3RV2011-1FA●●

    3RV2021-1CA●●3RV2021-1DA●●3RV2021-1EA●●3RV2021-1FA●●

    4.5-6.35.5-8

    7-109-12.5

    ¼1⁄3½¾

    ¾11 ½2

    22233

    2335

    557 ½7 ½

    57 ½1010

    82104130163

    65656565

    3RV2011-1GA●●3RV2011-1HA●●3RV2011-1JA●●3RV2011-1KA●●

    3RV2021-1GA●●3RV2021-1HA●●3RV2021-1JA●●3RV2021-1KA●●

    10-1613-2016-2218-25

    11 ½1 ½2

    2333

    57 ½7 ½7 ½

    57 ½7 ½7 ½

    10151520

    ————

    208260286325

    65656565

    3RV2011-4AA●●———

    3RV2021-4AA●●3RV2021-4BA●●3RV2021-4CA●●3RV2021-4DA●●

    23-2827-3230-36 3)

    34-40 3)

    2233

    5557 ½

    7 ½101010

    10101010

    20202530

    ————

    364400432480

    50501212

    ————

    3RV2021-4NA●● 5) 3RV2021-4EA●● 5) 3RV2021-4PA●● 6) 3RV2021-4FA●● 6)

    9-12.511-1614-2017-2220-25

    ½11 ½1 ½2

    1 ½2333

    33557 ½

    3557 ½7 ½

    7 ½10101515

    1010152020

    163208260286325

    3030303030

    —————

    3RV2023-1KA●● 7) 3RV2023-4AA●● 7) 3RV2023-4BA●● 7) 3RV2023-4CA●● 7) 3RV2023-4DA●● 7)

    Screw terminals, no auxiliary: ●● = 10 Screw Terminals, with 1NO/1NC Aux:●● = 15

    Spring terminals, no auxiliary: ●● = 20 Spring Terminals, with 1NO/1NC Aux: ●● = 25

    Ring Lug Terminals, no Auxiliary: ●● = 40

    Description Ordering Information

    The 3RV20x MSPs are UL approved as Self Protected Combination Motor Controllers which are also called Type E. In this application, all the required functions for a motor branch are provided in one device: disconnect, short circuit protection, motor control and overload protection. A type E terminal adaptor is required. The 3RV20x MSPs are also approved for use as follows:– Manual Motor Controller: Motor starter, motor disconnect, control and overload—

    protection. – Group Installation: Motor starter only, motor disconnect, control and overload

    protection.– Tap conductor Protection in Group Installation acc. NEC: Motor starter only;

    motor disconnect, control and overload protection.

    When the 3RV20x is used with one of the 3 above mentioned approvals, the 3RV20x can be installed downstream of one circuit breaker or fuse set.

    For more detailed application information and rules how to apply, size and rate the 3RV20x in control panels in general, in group installations or in accordance to interna-tional IEC standards visit our website: www.usa.siemens.com/controlpaneldesign

    E ON/OFF rotary handle with lockout and visible trip indication.

    E Adjustment dial for setting to motor FLA.E Class 10 overload trip characteristics.E Short circuit trip at 13 times the maximum setting of

    the FLA adjustment dial.E Short circuit current rating:E Ambient compensated up to 140° F (applies to side

    by side mounting).E Phase loss sensitivity.E Test trip function.E Terminal versions: screw, spring, ring lug.E Auxiliaries and Accessories see pages 1/7–1/17.E General Information see pages 1/29–1/32.E Technical Data see pages 1/18–1/28.E Dimensions see page 1/33.

    3RV Motor Starter Protectors

    For Motor Protection3RV20 Class 10 — up to 40A

    Product Category IEC

  • SIRIUS

    Siemens Canada Limited Industrial Control Product Catalog 2019 1/5

    1M

    OTO

    R STARTER

    PROTECTO

    RS

    Note: Select MSP by motor Full Load Amperes. Horsepower ratings are for reference only.

    1) Select motor starter protector by motor full load amps. Horsepower ratings for reference only.

    2) Size S2 and S3 are listed as type E combination motor controllers. For required Type E terminals see page 1/10. 3RV2031 MSPs with a current setting limit of 45A or less do not require a type E terminal and fulfill the spacing requirements of UL508.

    3) Shaded ratings apply for group installation only. These ratings do not apply as UL listed manual combination starters.

    4) Pre-assembled motor starter protector and transverse auxiliary switch with 1NO + 1NC is available. Replace the last digit of the order no. with a “5”.

    5) 3RV1 MSPs can only be used with 3RT1 contactors and accessories. 3RV2 MSPs can only be used with 3RT2 contactors and accessories.

    6) For 100kA SCCR rated MSPs, change the part number from 3RV2031 to 3RV2032. (applies to S2 frame only through 65A).

    Refer to pages 1/18 to 1/20 when using an MSP in a Manual Motor Starter or a Manual Self-Protected Combination Motor Controller.

    Illustration

    FLA Adjustment Range [A]

    Single Phase HP rating 1)

    3 Phase HP Rating 1)

    Inst. Short-Circuit Release [A]

    UL AIC (480V) [kA] 6)

    Trip Class 10 Order Number4)

    Trip Class 20 Order Number4)115V 240V 200V 230V 460V 575V

    3RV203 Frame Size S2

    9.5 - 14 1.5 3 5 5 10 15 208 65 3RV2031-4SA10 3RV2031-4SB10

    12 - 17 1.5 3 5 7.5 15 15 260 65 3RV2031-4TA10 3RV2031-4TB10

    14 - 20 1.5 3 7.5 7.5 15 20 260 65 3RV2031-4BA10 3RV2031-4BB10

    18 - 25 2 5 7.5 10 20 25 325 65 3RV2031-4DA10 3RV2031-4DB10

    22 - 32 3 5 10 10 25 30 416 65 3RV2031-4EA10 3RV2031-4EB10

    28 - 36 3 7.5 15 15 30 40 520 65 3RV2031-4PA10 3RV2031-4PB10

    32 - 40 3 7.5 15 15 30 40 585 65 3RV2031-4UA10 3RV2031-4UB10

    35 - 45 3 10 15 15 40 50 650 65 3RV2031-4VA10 3RV2031-4VB10

    42 - 52 5 10 15 20 40 50 741 65 3RV2031-4WA10 3RV2031-4WB10

    49 - 59 5 15 20 25 50 60 845 30 3RV2031-4XA10 3RV2031-4XB10

    54 - 65 5 15 20 25 50 60 845 30 3RV2031-4JA10 3RV2031-4JB10

    62 - 73 7.5 15 25 30 60 75 949 20 3RV2031-4KA10 3RV2031-4KB10

    70 - 80 7.5 15 25 30 60 75 1040 20 3RV2031-4RA10 3RV2031-4RB10

    3RV204 Frame Size S328 - 40 3 7.5 15 15 30 40 520A 65 3RV2041-4FA10 3RV2042-4FB10

    36 - 50 5 10 15 20 40 50 650A 65 3RV2041-4HA10 3RV2042-4HB10

    45 - 63 5 15 20 25 50 60 819A 65 3RV2041-4JA10 3RV2042-4JB10

    57 - 75 7.5 15 25 25 60 75 975A 65 3RV2041-4KA10 3RV2042-4KB10

    65 - 84 7.5 15 25 30 60 75 1170A 65 3RV2041-4RA10 3RV2042-4RB10

    75 - 93 7.5 20 30 40 75 100 3) 1300A 65 3RV2041-4YA10 3RV2042-4YB10

    80 - 100 10 25 40 40 75 100 3) 1300A 65 3RV2041-4MA10 3RV2042-4MB10

    Description Ordering Information

    The 3RV203 / 204 MSPs are UL approved as Self Protected Combination Motor Controllers which are also called Type E. In this application, all the required functions for a motor branch are provided in one device: disconnect, short circuit protection, motor control and overload protection. A type E terminal adaptor is required for all S2 frame 3RV2031 above 45A and all S2 frame 3RV2032 as well as for all S3 frame motor starter protectors.

    The 3RV203 / 204 MSPs are also approved for use as follows:– Manual Motor Controller: Motor starter, motor disconnect, control and overload

    protection. – Group Installation: Motor starter only, motor disconnect, control and overload protection.– Tap conductor Protection in Group Installation acc. NEC: Motor starter only; motor

    disconnect, control and overload protection.

    When the 3RV203 / 204 is used with one of the 3 above mentioned approvals, they can be installed downstream of one circuit breaker or fuse set.

    For more detailed application information and rules how to apply, size and rate these MSPs in control panels in general, in group installations or in accordance to international IEC standards visit our website: www.usa.siemens.com/controlpaneldesign

    E ON/OFF rotary handle with lockout and visible trip indication.

    E Adjustment dial for setting to motor FLA.E Class 10 overload trip characteristics.E Short circuit trip at 13 times the maximum set-

    ting of the FLA adjustment dial.E Short circuit current rating:E Ambient compensated up to 140° F (applies to

    side by side mounting).E Phase loss sensitivity.E Test trip function.E Auxiliaries and Accessories see pages

    1/7–1/17.E General Information see pages 1/29–1/32.E Technical Data see pages 1/18–1/28.E Dimensions see page 1/33.

    3RV Motor Starter Protectors

    For Motor Protection3RV10 Class 10 & 20 — up to 100A

    Product Category IEC

  • SIRIUS

    Siemens Canada Limited Industrial Control Product Catalog 20191/6

    1M

    OTO

    R ST

    ART

    ER

    PRO

    TECT

    ORS

    Siemens / Industrial Controls Previous folio: IC10 1/7

    1) 100 % rated value acc. to UL 489 and IEC 60947-2 (100 % rated breaker).

    2) Circuit breakers for system protection of motor and non-motor loads. Requires use of separate overload protection for motor applications.

    3) Circuit breakers for system and transformer protection according to UL/CSA. Specially designed for trans-formers with high inrush current.

    4) Transverse and lateral auxiliary switches can be ordered separately (see “Mountable accessories”).

    5) Transverse auxiliary switches must not be mounted. Lateral auxiliary switches can be ordered separately (see “Mountable accessories”).

    Selection and ordering dataFor Motor Protection 2)

    For Transformer Protection 3)

    Rated Cur-rent1)

    [A]

    Thermal overload release (non-ad-justable) [A]

    Short Circuit breaking capacity

    [kA]

    Instant-aneous Over Current Release [A]

    Order Number (Screw Terminals)

    Weight [kg]

    Instant-aneous Over Current Release [A]

    Order Number (Screw Terminals)

    Weight [kg]

    480 VAC

    480Y/ 277VAC

    600Y/ 347VAC

    Innovations Frame Size S00 4)

    0.16 0.16 — 65 10 2.1 3RV2711-0AD10 0.390 3.3 3RV2811-0AD10 0.3900.2 0.2 — 65 10 2.6 3RV2711-0BD10 0.390 4.2 3RV2811-0BD10 0.390

    0.25 0.25 — 65 10 3.3 3RV2711-0CD10 0.390 5.2 3RV2811-0CD10 0.3900.32 0.32 — 65 10 4.2 3RV2711-0DD10 0.390 6.5 3RV2811-0DD10 0.3900.4 0.4 — 65 10 5.2 3RV2711-0ED10 0.390 8.2 3RV2811-0ED10 0.3900.5 0.5 — 65 10 6.5 3RV2711-0FD10 0.390 10 3RV2811-0FD10 0.390

    0.63 0.63 — 65 10 8.2 3RV2711-0GD10 0.390 13 3RV2811-0GD10 0.4000.8 0.8 — 65 10 10 3RV2711-0HD10 0.390 16 3RV2811-0HD10 0.4501 1 — 65 10 13 3RV2711-0JD10 0.450 21 3RV2811-0JD10 0.450

    1.25 1.25 — 65 10 16 3RV2711-0KD10 0.450 26 3RV2811-0KD10 0.4601.6 1.6 — 65 10 21 3RV2711-1AD10 0.460 33 3RV2811-1AD10 0.4602 2 — 65 10 26 3RV2711-1BD10 0.460 42 3RV2811-1BD10 0.4602.5 2.5 — 65 10 33 3RV2711-1CD10 0.460 52 3RV2811-1CD10 0.4603.2 3.2 — 65 10 42 3RV2711-1DD10 0.460 65 3RV2811-1DD10 0.4604 4 — 65 10 52 3RV2711-1ED10 0.450 82 3RV2811-1ED10 0.4605 5 — 65 10 65 3RV2711-1FD10 0.460 104 3RV2811-1FD10 0.4606.3 6.3 — 65 10 82 3RV2711-1GD10 0.460 130 3RV2811-1GD10 0.4608 8 — 65 10 104 3RV2711-1HD10 0.460 163 3RV2811-1HD10 0.460

    10 10 — 65 10 130 3RV2711-1JD10 0.460 208 3RV2811-1JD10 0.46012.5 12.5 — 65 10 163 3RV2711-1KD10 0.460 260 3RV2811-1KD10 0.46015 15 — 65 — 208 3RV2711-4AD10 0.470 286 3RV2811-4AD10 0.470

    Innovations Frame Size S0 4)

    20 20 — 50 — 260 3RV2721-4BD10 0.514 325 3RV2821-4BD10 0.51622 22 — 50 — 286 3RV2721-4CD10 0.516 364 3RV2821-4CD10 0.528

    Innovations Frame Size S3 5)

    10 10 65 — 20 150 3RV2742-5AD10 0.460 — — —15 15 65 — 20 225 3RV2742-5BD10 0.460 — — —

    20 20 65 — 20 260 3RV2742-5CD10 0.460 — — —25 25 65 — 20 325 3RV2742-5DD10 0.460 — — —

    30 30 65 — 20 390 3RV2742-5ED10 0.460 — — —

    35 35 — 65 20 455 3RV2742-5FD10 0.460 — — —

    40 40 — 65 20 520 3RV2742-5GD10 0.460 — — —45 45 — 65 20 585 3RV2742-5HD10 0.460 — — —50 50 — 65 20 650 3RV2742-5JD10 0.460 — — —60 60 — 65 20 780 3RV2742-5LD10 0.460 — — —70 70 — 65 10 910 3RV2742-5QD10 0.460 — — —

    Refer to page 1/21 when using as upstream protection of a Manual Motor Controller or a Manual Motor Controller Suitable for Tap Conductor Protection in Group Installations.

    Product Category IEC

    3RV Circuit Breakers

    UL 4893RV — up to 70 A

  • SIRIUS

    Siemens Canada Limited Industrial Control Product Catalog 2019 1/7

    1M

    OTO

    R STARTER

    PROTECTO

    RS

    Selection and ordering data

    Width

    Innovations

    Type Version

    Fits 3RV2 Frame Size

    Screw Connection Order No.

    Auxiliary switches3) mm Innovations

    Transverse auxiliaryswitches

    1 CO1 NO + 1 NC2 NO

    S00, S0, S2,S3 1), 2)

    1)

    3RV2901-1D3RV2901-1E 3RV2901-1F

    Solid-state compatible,transverse auxiliary

    1 CO S00, S0, S2,S3

    3RV2901-1G

    switches for use in dusty atmosphere and in electronic circuits with low operating currents

    Covering caps for transverseauxiliary switch slots (pack of 10)

    S00, S0, S2,S3

    3RV2901-0H

    Lateral auxiliaryswitches(side mount)

    1 NO + 1 NC2 NO2 NC2 NO + 2 NC

    999

    18

    S00, S0, S2,S3

    1), 2)

    1)

    1)

    3RV2901-1A3RV2901-1B3RV2901-1C3RV2901-1JWidth = 9 mm

    Signaling switch4) Innovations

    Signaling switch(side mount)Individual tripped andshort-circuit signaling

    1 NO + 1 NCeach

    18 S00, S0, S2,S3

    1), 2) 3RV2921-1M

    Width = 18 mm

    Auxiliary releases 5) Innovations

    Undervoltagereleases(side mount)

    DC24 V

    S00, S0, S2,S3

    3RV2902-1AB4

    Width = 18 mm AC 50 Hz24 V110 V—230 V400 V415 V500 V

    AC 60 Hz—120 V208 V240 V440 V480 V600 V

    S00, S0, S2,S3 1), 2)

    1), 2)

    3RV2902-1AB03RV2902-1AF03RV2902-1AM13RV2902-1AP03RV2902-1AV03RV2902-1AV13RV2902-1AS0

    Undervoltagereleases withleading

    230 V400 V415 V

    240 V440 V480 V

    S00, S0, S2,S3

    1)

    1)

    1), 2)

    3RV2922-1CP03RV2922-1CV03RV2922-1CV1

    auxiliarycontacts 2 NO(side mount)

    230 V400 V415 V

    240 V440 V480 V

    S00, S0, S2,S3

    1)

    1)

    1), 2)

    3RV2922-1CP03RV2922-1CV03RV2922-1CV1

    Width = 18 mmShunt releases(side mount)

    AC 50/60 Hz100% ON6)

    AC 50/60 Hz5 sec ON7)

    Width = 18 mm 20-24 V90-110 V210-240 V350-415 V500 V

    20-70 V70-190 V190-330 V330-500 V500 V

    S00, S0, S2,S3

    1), 2)

    1), 2)

    1)

    3RV2902-1DB03RV2902-1DF03RV2902-1DP03RV2902-1DV03RV2902-1DS0

    Siemens / Industrial Controls Previous folio: IC10 1/9

    3RV2902-1AB4

    1) This product is also available with spring terminals. The order no. must be changed in the 8th position to a “2”:e.g. 3RV1901-2E or 3RV2901-2E

    2) This product is also available with ring lug terminals. The order no. must be changed in the 8th position to a “4”: e.g. 3RV2901-4E

    3) Each motor starter protector can be fitted with one transverse and one lateral auxiliary switch. The lateral auxiliary switch 2 NO + 2 NC is used without trans-verse auxiliary switch.

    4) One signaling switch can be mounted at the left of the motor starter protector. This accessory cannot be used on the 3RV27 and 3RV28 circuit breakers.

    5) One auxiliary release can be mounted at the right of each MSP. motor starter protector.

    6) The response voltage at the lower limit of the voltage range at 0.85 (Tu=60°C) is valid for 100% (infinite)

    7) The response voltage at the lower limit of the voltage range at 0.9 (Tu=60°C) applies for a duty cycle of 5 seconds at AC 50/60 Hz and DC.

    3RV2901-1E

    3RV2901-1G

    3RV2901-1A

    3RV2921-1M

    Product Category IEC

    3RV Motor Starter Protectors

    AccessoriesAuxiliaries and Accessories

  • SIRIUS

    Siemens Canada Limited Industrial Control Product Catalog 20191/8

    1M

    OTO

    R ST

    ART

    ER

    PRO

    TECT

    ORS

    Siemens / Industrial Controls Previous folio: IC 1/10

    Selection and ordering data

    1) Not suitable for 3RV21 motor starter protectors with overload relay function.2) Approved for motor starter protectors size S0 with In ≤ 32 A.3) For 3RV2 motor starter protectors without accessories mounted on the side.

    4) For 3RV2 motor starter protectors with auxiliary switches with 1 NO + 1 NC, 2 NO and 2 NC mounted on the left (9 mm wide).5) For 3RV2 motor starter protectors with mounted accessories (18 mm wide). Auxiliary switches with 2 NO + 2 NC or signaling switch (mounted on the left) or with auxiliary release (mounted on the right).

    Modu-larspac-ing

    Number of motor starter protectors that can be connected

    Ratedcurrent In at 690 V

    For motor starter protectors Size

    Order No. Orderquantity

    Weight approx.

    Withoutlateralacces-sories

    Incl.lateralauxil-iary switch

    Withauxil-iary trip unit

    Amm kg

    Three-phase busbar systems for Classic and Innovations1)

    3RV19 15-1AB

    3RV19 15-1BB

    3RV19 15-1CB

    3RV19 15-1DB

    For feeding several motor starter protectors with screw terminals, mounted side-by-side on standard mounting rails, insulated, with touch protection.45 2 -- -- 63 S00, S02) 3RV19 15-1AB 1 unit 0.044

    0S ,00S3 2) 3RV19 15-1BB 1 unit 0.0710S ,00S4 2) 3RV19 15-1CB 1 unit 0.0990S ,00S5 2) 3RV19 15-1DB 1 unit 0.124

    55 -- 2 -- 63 S00, S02) 3RV19 15-2AB 1 unit 0.0480S ,00S3 2) 3RV19 15-2BB 1 unit 0.0790S ,00S4 2) 3RV19 15-2CB 1 unit 0.1110S ,00S5 2) 3RV19 15-2DB 1 unit 0.140

    63 -- -- 2 63 S00, S02)5)

    5)

    3RV19 15-3AB 1 unit 0.0524 S00, S02) 3RV19 15-3CB 1 unit 0.120

    55 2 -- -- 108 S2 3RV19 35-1A 1 unit 0.1502S3 3RV19 35-1B 1 unit 0.2142S4 3RV19 35-1C 1 unit 0.295

    75 -- 2 2 108 S2 3RV19 35-3A 1 unit 0.1613 3 S2 3RV19 35-3B 1 unit 0.2624 4 S2 3RV19 35-3C 1 unit 0.369

    Version Modularspacing

    For motor starter protectors Size

    Order No. Orderquantity

    Weightapprox.

    mm kg

    Connecting pieces for three-phase busbars

    3RV19 15-5DB

    For connecting three-phase busbars for motor starter protectors of size S0 (left) to size S00 (right)

    45 S00, S0 3RV19 15-5DBFor Innovations

    1 unit 0.042

    ------

    3)

    4)

    Conductor cross-section,AWG cables, solid or stranded Tighten-

    ingtorque

    For motorstarterprotectorsize

    3RV2 Innovations 2)

    Order No.

    For 3RV1MSP

    For 3RV2MSP

    AWG AWG Nm

    Three-phase feeder terminals3RV29 25-5AB Connection from top

    — 10…4 3…4 S00 3RV2925-5AB— 10…4 3…4 S0 3RV2925-5AB

    3RV2915-5B Connection from below3)

    — 10…4 Input: 4, S00, S0 3RV2915-5BOutput:2 ... 2.5

    3RV2935-5A Connection from top14...0 -- 4-6 S2 3RV2935-5A

    Three-phase feeder terminals for constructing “Type E Starters” Innovations3RV2935-5E Connection from top

    — 10…4 3-4 S00 3RV2925-5EB

    — 10…4 3-4 S0 3RV2925-5EB

    8...0 10...2/0 4.5-6 S2 3RV2935-5E

    3RV29 25-5AB

    1) Do not mix 3RV1 Classic Accessories with 3RV2 Innovations MSPs

    2) Do not mix 3RV2 Innovations Accessories with 3RV1 Classic MSPs

    3) This terminal is connected in place of a switch, please take the space requirement into account.

    3RV2915-5B

    3RV Motor Starter Protectors

    AccessoriesMounting accessories

    Product Category IEC

  • SIRIUS

    Siemens Canada Limited Industrial Control Product Catalog 2019 1/9

    1M

    OTO

    R STARTER

    PROTECTO

    RS

    7/38 Siemens IC 10 · 2015

    Motor Starter Protectors/Circuit BreakersSIRIUS 3RV2 Motor Starter Protectors/Circuit Breakers up to 80 AAccessories

    Mounting accessories

    7

    Overview

    Accessories for "Self-Protected Combination Motor Controllers (Type E)" according to UL 508/UL 60947-4-1 The 3RV20 motor starter protectors with screw terminals are approved according to UL 508/UL 60947-4-1 as "Self-Protected Combination Motor Controllers (Type E)".

    This requires increased clearance and creepage distances (1 inch and 2 inches respectively) at the input side of the device, which are achieved by mounting a terminal block or a phase barrier.

    SIRIUS 3RV2928-1H terminal block

    SIRIUS 3RV2938-1K phase barrier

    -- No accessories needed

    Note:

    According to CSA, these terminal blocks and the phase barriers can be omitted when the device is used as a "Self-Protected Combination Motor Controller (Type E)".

    Link modules Feeders can be easily assembled from single devices with the help of the link modules. The following table shows the different combination options for devices with screw or spring-type terminals.

    -- Version not possible1) The link modules cannot be used for the 3RV2.21-4PA1., 3RV2.21-4FA1.,

    3RV2.31-4K.1., 3RV2.31-4R.1., 3RV2.32-4K.1., 3RV2.32-4R.1., 3RV27 and 3RV28 motor starter protectors/circuit breakers.

    2) To assemble the feeder between a motor starter protector and a soft starter in size S2, the 3RA2932-1AC00 standard mounting rail adapter must be used.

    3) The motor starter protector to contactor hybrid link modules cannot be used for the 3RV2.21-4PA1., 3RV2.21-4FA1., 3RV27 and 3RV28 motor starter protectors/circuit breakers. They are only suitable for constructing direct-on-line starters.

    Note:• Link modules can be used in

    - Sizes S00 and S0: up to max. 32 A- Size S2: up to max. 65 A

    • Hybrid link modules can be used in- Sizes S00 and S0: up to max. 32 A

    Motor starter protectors/circuit breakers

    Size Essential accessories for "Self-Protected Combination Motor Controllers (Type E)" according to UL 508/UL 60947-4-1

    3RV201., 3RV202. S00/S0 3RV2928-1H terminal block or 3RV2928-1K phase barrier

    3RV2031-4B1.,3RV2031-4D.1.,3RV2031-4E1.,3RV2031-4P.1.,3RV2031-4S.1.,3RV2031-4T.1.,3RV2031-4U.1.,3RV2031-4V.1.

    S2 --

    3RV2031-4J.1., 3RV2031-4K.1., 3RV2031-4R.1., 3RV2031-4W.1., 3RV2031-4X.1., 3RV2032

    S2 3RV2938-1K phase barrier

    3RV204 S3 3RT2946-4GA07 terminal block

    NSB0_0

    1379c

    IC01_0

    0408

    Combination devices

    3RV2 motor starter protec-tors/circuit breakersSize

    3RT2 contactors; 3RW30, 3RW40 soft starters; 3RF34 solid-state contactors

    Size

    Link modulesScrew terminals

    Spring-type terminals

    Link modules for connecting switching devices to 3RV2 motor starter protectors/circuit breakers1)

    3RT2 contac-tors with AC or DC coil

    S00 S00 3RA1921-1DA00

    3RA2911-2AA00

    S0 S00 --

    S2 S2 3RA2931-1AA00

    --

    3RT2 contac-tors with AC coil

    S0 S0 3RA2921-1AA00

    3RA2921-2AA00

    S00 S0 --

    3RT2 contac-tors with DC coil

    S0 S0 3RA2921-1BA00

    3RA2921-2AA00

    S00 S0 --

    3RW30 soft starters

    S00 S00 3RA2921-1BA00

    3RA2911-2GA00

    S0 S00 --

    3RW30/3RW40soft starters

    S0 S0 3RA2921-1BA00

    3RA2921-2GA00

    S00 S0 --

    S22) S22) 3RA2931-1AA00

    --

    3RF34 solid-state contac-tors

    S00/S0 S00 3RA2921-1BA00

    --

    Hybrid link modules for connecting contactors with spring-type terminals to 3RV2 motor starter protectors/circuit breakers with screw terminals3)

    3RT2 contac-tors with AC or DC coil

    S00 S00 3RA2911-2FA00

    --

    S0 S0 3RA2921-2FA00

    --

    �S�I�R�I�U�S�_�I�C�1�0�_�c�h�a�p�0�7�_�E�n�g�l�i�s�h�_�2�0�1�5�.�b�o�o�k� � �S�e�i�t�e� �3�8� � �F�r�e�i�t�a�g�,� �1�6�.� �J�a�n�u�a�r� �2�0�1�5� � �1�1�:�5�6� �1�1

    Siemens / Industrial Controls Previous folio: Mod from SIRIUS Innovations

    Special threephase infeed terminals are required for constructing “Type E Starters” with an insulated threephase busbar system (see page 1/8).

    The 3RV29 infeed system also enables the assembly of “Type E Starters”, see page 1/14 onwards.

    3RV Motor Starter Protectors

    AccessoriesMounting accessories

    Product Category IEC

  • SIRIUS

    Siemens Canada Limited Industrial Control Product Catalog 20191/10

    1M

    OTO

    R ST

    ART

    ER

    PRO

    TECT

    ORS

    Siemens / Industrial Controls Previous folio: 1/12 new from Excel

    Selection and ordering data

    VersionFor motor starterprotector size

    Innovations3RV2/3RT2Order No.

    OrderQuantity

    Terminal blocks and phase barriers for “Self-Protected CombinationMotor Controllers (Type E)” according to UL 508 / UL 60947-4-1

    Note:UL 508 / UL 60947-4-1 demands 1-inch clearance and 2-inch creepage distance at line side for “Combination Motor Controller Type E”.The following terminal blocks or phase barriers must be used on 3RV motor starter protectors.The terminal blocks or phase barriers cannot be used in combination with the 3RV19 .5 three-phase busbars. For construction with three-phase busbars, see “Accessories for busbar”Terminal blocks type E For extended clearance andcreepage distances(1 and 2 inch)

    S00, S0 3RV29 28-1H 1 unitS0 — 1 unitS2 3RV29 35-5E 1 unitS3 3RT2946-4GA07 1 unit

    Phase barriersFor extended clearance andcreepage distances(1 and 2 inch)

    S00, S0 3RV29 28-1K 1 unitS2 3RV29 38-1K 1 unit

    Actuating voltage ofcontactor

    Size3RTcontactor

    3RV motorstarterprotector

    Innovations3RV2/3RT2Order No.

    OrderQuantity

    Link modules for motor starter protector to contactor 1)

    For mechanical and electrical connection betweenmotor starter protector and contactor with screwterminals.

    Screw Terminals

    Single-unit packagingAC/DC S00 S00/S0 3RA19 21-1DA00 1 unitAC S0 S00/S0 3RA29 21-1AA00 1 unitAC S2 S2 3RA29 31-1AA00 1 unitAC S3 S3 3RA19 41-1AA00 1 unitDC S0 S00/S0 3RA29 21-1BA00 1 unitDC S2 S2 3RA29 31-1AA00 1 unitDC S3 S3 3RA19 41-1AA00 1 unitMulti-unit packagingAC/DC S00 S00/S0 3RA19 21-1D 10 units

    AC S0 S00/S0 3RA29 21-1A 10 unitsDC S0 S00/S0 3RA29 21-1B 10 unitsAC/DC S2 S2 3RA29 31-1A 5 unitsAC/DC S3 S3 3RA19 41-1A 5 units

    For mechanical and electrical connection between motor starter protector and contactor with spring-type terminals.

    Spring-type Terminals

    Single-unit packaging

    AC/DC S00 S00 3RA29 11-2AA00 1 unitAC 2) S0 S0 3RA29 21-2AA00 1 unitDC S0 S0 3RA29 21-2AA00 1 unitMulti-unit packagingAC/DC S00 S00 3RA29 11-2A 10 unitsAC 2) S0 S0 3RA29 21-2A 10 unitsDC S0 S0 3RA29 21-2A 10 unitsSpacersFor compensating height on AC contactorsSingle-unit packaging S0 S0 3RA29 11-1CA00 1 unit

    Multi-unit packaging S0 S0 3RA29 11-1C 5 units

    3RV29 28-1H

    3RV29 28-1K

    3RT1946-4GA07

    3RA29 21-1AA00

    3RA29 11-2AA00

    1) The link modules for motor starter protector to contactor cannot be used for the 3RV2. 21-4PA1., 3RV2. 21-4FA1., 3RV27 and 3RV28 motor starter protectors

    2) A spacer for height compensation on AC contactors size S0 is optionally available

    NoteSize S0 link modules can be used up to max. 32 A. Size S2 link modules can be used up to 65A max.

    3RV Motor Starter Protectors

    AccessoriesMounting accessories

    Product Category IEC

  • SIRIUS

    Siemens Canada Limited Industrial Control Product Catalog 2019 1/11

    1M

    OTO

    R STARTER

    PROTECTO

    RS

    Siemens / Industrial Controls Previous folio: p/u from SIRIUS Innovations

    SIRIUS 3RV2 Motor Starter Protectors/Circuit Breakers up to 40 AAccessories

    Mounting accessories

    5/30 SIRIUS Innovations Supplement 2012 Illustrations are approximate

    5

    1) The link modules for motor starter protector to soft starter and for motor starter protector to solid-state contactor cannot be used for the 3RV2. 21-4PA1., 3RV2. 21-4FA1., 3RV27 and 3RV28 motor starter protectors.

    Note:S0 link modules can be used up to max. 32 A.S2 link modules can be used up to max. 65 A.

    1) The hybrid link modules for motor starter protector to contactor cannot be used for the 3RV2. 21-4PA1., 3RV2. 21-4FA1., 3RV27 and 3RV28 motor starter protectors or reversing starters.

    2) A spacer for height compensation on AC contactors size S0 is optionally

    3) To assemble the starter between a motor starter protector and a soft starter in size S2, the 3RA2932-1AC00 standard mounting rail adapter must be used.

    available. See 3RA2911-1CA00

    Note:Hybrid link modules can be used up to max. 32 A.

    Size Order No. PU(UNIT,

    SET, M)

    PS* Weightapprox.3RW30, 3RW40

    soft starters; 3RF34 solid-state contactors

    3RV2 motor starter protectors

    kg

    Link modules for motor starter protector to soft starter1) 3) andmotor starter protector to solid-state contactor

    3RA29 21-1BA00

    Connection between motor starter protector and soft starter / solid-state contactor with screw terminals

    Screw terminals

    Single-unit packaging0S/00S00S 3RA29 21-1BA00 1 1 unit 0.0680S/00S0S 3RA29 21-1BA00 1 1 unit 0.068

    Multi-unit packaging0S/00S00S 3RA29 21-1B 1 10 units 0.0680S/00S0S 3RA29 21-1B 1 10 units 0.068

    S2S3 3RA19 41-1A 1 5 units 0.104

    3RA29 21-2GA00

    Connection between motor starter protector and soft starter with spring-type terminals

    Spring-typeterminals

    Single-unit packaging00S00S 3RA29 11-2GA00 1 1 unit 0.038

    0S0S 3RA29 21-2GA00 1 1 unit 0.072Multi-unit packaging

    00S00S 3RA29 11-2G 1 10 units 0.3800S0S 3RA29 21-2G 1 10 units 0.720

    Actuating voltage of contactor

    Size Order No. PU(UNIT,

    SET, M)

    PS* Weightapprox.3RT2

    contactors3RV2 motor starter protectors

    kg

    Hybrid link modules for motor starter protector to contactor1)

    3RA29 11-2FA00

    For mechanical and electrical connection between motor starter protector with screw terminals and contactor with spring-type terminals

    Single-unit packagingAC/DC S00 S00 3RA29 11-2FA00 1 1 unit 0.029AC2)

    4)

    4)S2S2 3RA29 31-1A 1 5 units 0.1043)

    /DC S0 S0 3RA29 21-2FA00 1 1 unit 0.056

    3RA29 21-2FA00

    Multi-unit packagingAC/DC S00 S00 3RA29 11-2F 1 10 units 0.290AC2)/DC S0 S0 3RA29 21-2F 1 10 units 0.560Spacers2)for compensating the height on AC contactors

    Single-unit packaging S0 S0 3RA29 11-1CA00 1 1 unit 0.001Multi-unit packaging S0 S0 3RA29 11-1C 1 5 units 0.001

    * You can order this quantity or a multiple thereof.

    �L�V�1�N�_�0�5�_�0�4�.�f�m� � �P�a�g�e� �3�0� � �F�r�i�d�a�y�,� �S�e�p�t�e�m�b�e�r� �2�7�,� �2�0�1�3� � �2�:�2�8� �P�M

    4) It is only permissible to assemble the feeder between the motor starter protector and the soft starter in Size S3 on a mounting plate.

    S3S3 3RA19 41-1A 1 1 unit 0.1043) S2S2 3RA29 31-1AA00 1 1 unit 0.104

    Selection and ordering data

    3RV Motor Starter Protectors

    AccessoriesMounting accessories

    Product Category IEC

  • SIRIUS

    Siemens Canada Limited Industrial Control Product Catalog 20191/12

    1M

    OTO

    R ST

    ART

    ER

    PRO

    TECT

    ORS

    Siemens / Industrial Controls Previous folio: IC 1/13 New table from Excel

    Selection and ordering data

    Type DesignFor SIRIUSMSP size Order No.

    OrderQuantity

    Weightapprox.(kg)

    Isolator module 1)

    3RV2938-1Awithout padlock

    Visible isolating distance forisolating individual motor starterprotectors from the network,lockable in isolating position.

    S00, S0 3RV29 28-1A 1 unit 0.132

    S2 1) 3RV29 38-1A 1 unit 0.368

    Auxiliary terminal, 3 pole3RT19 46-4F For connection of auxiliary

    and control cables to the mainconductor connections

    S3 3RT29 46-4F 1 unit 0.10

    Covers3RV1 (size S3) with3RT19 46-4EA1 Terminal cover Additional touch guard

    for box terminals to be fitted at the box terminals(2 units can be mounted per MSP)

    S2 3RT29 36-4EA2 1 unit 0.014

    S3 3RT29 46-4EA2 1 unit 0.019

    3RV29 28-4AA00 Terminal cover For maintaining the requiredfor cable lug andbar connection

    voltage clearance and as protectionagainst the equipment being touchedif distant box terminals are used(2 units can be mounted per MSP)

    S3 3RT19 46-4EA1 1 unit 0.03

    3RV29 08-4AA10 Terminal coverfor devices with ring lug terminal connection

    • Main current level S00, S0 2) 3RV29 28-4AA00 1 unit 0.01

    • For transverse auxiliary switches S00, S0 2) 3RV29 08-4AA10 1 unit 0.01

    3RV29 08-0P Scale cover For covering the current settingscale. Packing unit: Bag with 10scale covers.

    S00, S0, S2 3) 3RV29 08-0P 10 unitsS3 3RV19 08-0P 10 units

    Fixing Material3RB1900-0B Push-in lugs Two units are required for

    For screwing themotor starter protectoronto mounting plates.

    each motor starter protector. S00 3RB19 00-0B 10 units 0.10

    Tools for opening spring-type terminals by hand3RA29 08-1A Screwdriver Length approx. 200 mm,

    For all SIRIUSdevices with springterminals

    3.0 mm x 0.5 mm,titanium gray/blackpartially insulated

    S00, S0,S2

    3RA29 08-1A 1 unit 0.045

    1) The isolator module for size S2 can be used only with 3RV2 motor starter protectors/circuit breakers up to max. 65 A. Similarly, it cannot be used with the transverse auxiliary switch or three-phase busbars.

    3RV29 28-1A without padlock

    2) Compatible with 3RV20 motor starter protectors.

    3) Compatible with 3RV20, 3RV21, and 3RV24 motor starter protectors.

    3RV Motor Starter Protectors

    AccessoriesMounting accessories

    Product Category IEC

  • SIRIUS

    Siemens Canada Limited Industrial Control Product Catalog 2019 1/13

    1M

    OTO

    R STARTER

    PROTECTO

    RS

    Siemens / Industrial Controls Previous folio: IC 1/14 New table from Excel

    Selection and ordering data

    Type DetailsFor SIRIUSMSP size Order No.

    Approx.Wt. (kg)

    Door-coupling rotary operating mechanisms for Classic and Innovations3RV29 26-0B The door-coupling rotary operating mechanisms consist of a knob, a coupling driver and a 130/330 mm long

    extension shaft (6 mm x 6 mm). The door-coupling rotary operating mechanisms are designed to degree of protection IP64. The door locking device prevents accidental opening of the control cabinet door in the ON postion of the motor starter protector. The OFF position can be locked with up to 3 padlocks.Door-coupling rotaryoperating mechanisms(black)

    Extension shaft 130 mm S00, S0 3RV29 26-0B 0.111

    S2, S3 3RV29 26-0B 0.1

    Extension shaft 330 mm S00, S0 3RV29 26-0K 0.324

    S2, S3 3RV29 26-0K 0.3

    EMERGENCY STOPdoor-coupling rotaryoperating mechanisms(red/yellow)

    Extension shaft 130 mm S00, S0 3RV29 26-0C 0.110

    S2, S3 3RV29 26-0C 0.1

    Extension shaft 330 mm S00, S0 3RV29 26-0L 0.316

    S2, S3 3RV29 26-0L 0.3

    Door-coupling rotary operating mechanisms for arduous conditions3RV29 26-2C The door-coupling rotary operating mechanisms consist of a knob, a coupling driver, an extension shaft of 300 mm

    length (8 mm x 8 mm), a spacer and two metal brackets, into which the MSP is inserted. The door-coupling rotary operating mechanisms are designed for degree of protection IP65. The door locking device reliably prevents accidental opening of the control cabinet door in the ON position of the MSP. The OFF postion can be locked with up to 3 padlocks. Laterally mountable auxiliary releases and two-pole auxiliary switches can be used. The door-coupling rotary operating mechanisms thus meet the requirements for isolating functions according to IEC 60 947-2.Door-coupling rotaryoperating mechanisms(gray)

    S00, S0 3RV29 26-2B 1.2

    S2 3RV29 36-2B 1.6

    S3 3RV29 46-2B 1.7

    EMERGNCY STOP door-coupling rotary operating mechanisms(red/yellow)

    S00, S0 3RV29 26-2C 1.2

    S2 3RV29 36-2C 1.5

    S3 3RV29 46-2C 1.7

    Enclosures and front plates No UL/CSA certification

    Type DetailsFor SIRIUSMSP size Order No.

    Approx.Wt. (kg)

    Front Plates3RV19 23-4B+ 3RV19 23-4G

    Molded-plastic front platewith rotary operating mechanism, lockable. For actuation of 3RV motor starter protectors in any enclosure

    For actuation of 3RV MSPs in any enclosure, degree of protection IP55 (front plate)

    S00, S0S2, S3

    3RV19 23-4B 0.08

    Molded-plastic front plate withEMERGENCY STOPdoor-coupling rotary operating mechanisms (red/yellow)

    EMERGENCY-STOP operation of 3RV MSPs in any enclosure, degree of protection IP55

    S00, S0S2, S3

    3RV19 23-4E 0.08

    Holders for front plates Holder is mounted on front plate, MSP size S00 or S0 with or without accessories is snapped in

    S00, S0 3RV19 23-4G 0.19

    Enclosures for wall mounting 2)3RV19 23-1CA00 Molded-plastic enclosure for

    wall mountingwith rotary operating mechanism,lockable, with metric cable gland

    Degree of protection IP55, with N and PE terminals, lockable in 0 position overall width:

    54 mm (for switch + lateral auxiliary switch) S00, S0 3RV19 23-1CA00 0.26

    72 mm (for switch + lateral auxiliary switch + auxiliary release)

    S00, S0 3RV19 23-1DA00 0.30

    3RV19 23-1DA01

    Cast aluminum surface-mountenclosurewith rotary operating mechanism,lockable, with metric cable gland

    Degree of protection IP65, with PE terminals,1) lockable in 0 position overall width: 72 mm (for MSP + lateral auxiliary switch + auxiliary release)

    S00, S0 3RV19 23-1DA01 1.02

    Cast aluminum surface-mountenclosurewith EMERGENCY-OFF rotaryoperating mechanism, red/yellow,lockable, with metric cable gland

    Degree of protection IP65, with PE terminals,1) lockable in 0 position overall width: 72 mm (for MSP + lateral auxiliary switch + auxiliary release)

    S00, S0 3RV19 23-1GA01 1.01

    1) If required, an additional N terminal can be mounted (e.g. 8WA10 11-1BG11). 2) For S2 versions, see 3RV1933-1DA00 (black) or 3RV1933-1GA00 (red/yellow)

    3RV Motor Starter Protectors

    AccessoriesRotary operating mechanisms

    Product Category IEC

  • SIRIUS

    Siemens Canada Limited Industrial Control Product Catalog 20191/14

    1M

    OTO

    R ST

    ART

    ER

    PRO

    TECT

    ORS

    Siemens / Industrial Controls Previous folio: LV1 6/53

    SIRIUS 3RV2 Motor Starter Protectors/Circuit Breakers up to 40 AAccessories

    3RV29 infeed system

    5/23SIRIUS Innovations Supplement 2012

    5

    Overview

    3RV29 infeed system

    LV1N_05_04.fm Page 23 Friday, September 27, 2013 2:28 PM

    123a

    456

    3b

    7

    3-phase busbar with infeed3-phase busbar for system expansionExpansion plugExtra-wide expansion plugEnd coverTerminal block for device infeedPlug-in connectorContactor base

    8 Terminal block

    The 3RV29 infeed system is a convenient means of energy supply and distribution for a group of several motor starter protectors or complete motor starters with a screw or springtype connection in sizes S00 and S0 (exception: this system cannot be used for the 3RV21).

    Siemens now has UL/CSA approvals for using the 3RV27 and3RV28 UL489 Circuit Breakers with the 3RV2917 Infeed System and with the 3RV1915 comb-busbars. Up until now it was limited to standard 3RV20 MSPs. These new approvals will greatly enhance application fl exibility for customers. Not only can they use the bus systems to feed motor loads, they can now feed non-motor loads which should allow the bus systems to feed complete control panel applications. Customers will need to remove the line side terminals on any 3RV27 or 28s that will be fed by the bus system.

    The 3RV29 infeed system is approved in accordance with IEC to 500V. It is also UL approved and authorized for “Self-Protected Combination Motor Controller” (Type E starter) as well as for Type F starter (Type E starter + contactor). The system is based on a basic module complete with a lateral incoming unit (three-phase busbar with infeed). This infeed with spring-type terminals is mounted on the right or left depending on the version and can be supplied with a maximum conductor cross section of 4 AWG (with end sleeve).

    A basic module has two sockets onto each of which a motor starter protector can be snapped.

    Expansion modules are available for extending the system (three-phase busbars for system expansion). The individual modules are connected through an expansion plug.

    The electrical connection between the three-phase busbars and the motor starter protectors is implemented through plug-in connectors. The complete system can be mounted on a TH 35 standard mounting rail to EN 60715 and can be expanded as required up to a maximum current carrying capacity of 63 A. The system is mounted extremely quickly and easily thanks to the simple plug-in technique. Thanks to the lateral infeed, the system also saves space in the control cabinet. The additional overall height required for the infeed unit is only 30 mm. The alternative infeed possibilities on each side offer a high degree of fl exibility for confi guring the control cabinet: Infeed on left-hand or right-hand side as well as infeed on one side and outfeed on the other side to supply further loads are all possible.

    A terminal block with spring-type connections in combination with a standard mounting rail enables the integration of not only SIRIUS motor starter protectors but also single-phase, 2-phase and 3-phase components such as 5SY miniature circuit breakers or SIRIUS relay components.

    3RV Motor Starter Protectors

    Accessories3RV29 infeed system

    Product Category IEC

  • SIRIUS

    Siemens Canada Limited Industrial Control Product Catalog 2019 1/15

    1M

    OTO

    R STARTER

    PROTECTO

    RS

    Siemens / Industrial Controls Previous folio: LV1 6/54

    SIRIUS 3RV2 Motor Starter Protectors/Circuit Breakers up to 40 AAccessories

    3RV29 infeed system

    5/24 SIRIUS Innovations Supplement 2012

    5

    � Three-phase busbars with infeedA three-phase busbar with infeed unit is required for connecting the energy supply. This module comprises one infeed module and 2 sockets which each accept one motor starter protector. A choice of two versions with infeed on the left or right is available. The infeed is connected using spring-type terminals. The spring-type terminals permit conductor cross-sections of up to 25 mm2 with end sleeves. An end cover is supplied with each module.

    � Three-phase busbars for system expansionThe three-phase busbars for system expansion allow the system to be expanded. There is a choice of modules with 2 or 3 sock-ets. The system can be expanded as required up to a maximum current carrying capacity of 63 A. An expansion plug is supplied with each module.

    �a Expansion plugThe expansion plug is used for electrical connection of adjacent three-phase busbars. The current carrying capacity of this plug equals 63 A. One expansion plug is supplied with each three-phase busbar for system expansion. Additional expansion plugs are therefore only required as spare parts.

    �b Extra-wide expansion plugThe wide expansion plug makes the electrical connection be-tween two three-phase busbars, thus performing the same func-tion as the 3RV29 17-5BA00 expansion plug; the electrical char-acteristics (e.g. a current carrying capacity of 63 A) are identical.

    The 3RV29 17-5E expansion plug is 10 mm wider than the 3RV29 17-5BA00 expansion plug, hence in the plugged state there is a distance of 10 mm between the connected three-phase busbars. This distance can be used to lay the auxiliary current and control current wiring ("wiring duct"). The motor starter protector and contactor can be wired from underneath, which means that the complete cable duct above the system can be omitted.

    � End coverThe end cover is used to cover the three-phase busbar at the open end of the system. This cover is therefore only required once for each system. An end cover is supplied with each three-phase busbar system with infeed. Further end covers are there-fore only required as spare parts.

    � Plug-in connectorThe plug-in connector is used for the electrical connection be-tween the three-phase busbar and the 3RV2 motor starter pro-tector. These plug-in connectors are available in versions for screw or spring-type terminals.

    � Contactor baseMotor starters can be assembled in the system using the contac-tor base. The contactor bases are suitable for contactors sizes S00 and S0 with spring-type and screw terminals and are simply snapped onto the three-phase busbars. Direct-on-line starters and reversing starters are possible. One contactor base is re-quired for direct-on-line starters and two are required for revers-ing starters.

    To assemble motor starters for reversing starters, the contactor bases can be arranged alongside each other (90 mm overall width). In this case the mechanical interlocking of the contactors is possible. The contactor bases are also suitable for soft start-ers size S00 and S0 with screw connection.

    The infeed system is designed for mounting on a 35 mm stan-dard mounting rail with 7.5 mm overall depth. This standard mounting rail gives the contactor base a stable mounting sur-face to sit on. If standard mounting rails with a depth of 15 mm are used, the spacer connected to the bottom of the contactor base must be knocked out and plugged into the mating piece that is also on the underside. Then the contactor base also has a stable mounting surface. When standard mounting rails with a depth of 7.5 mm are used, the spacer has no function and can be removed.

    The link modules are used for direct start motor starters, in which case the use of a contactor base is not absolutely necessary. Motor starter protector and contactor assemblies can then be di-rectly snapped onto the sockets of the three-phase busbars. For starters of size S00 and S0, the corresponding 3RA19 21-1...., 3RA29 11-2...., 3RA29 21-1.... or 3RA29 21-2.... link modules should generally be used.

    � Terminal blockThe 3RV29 17-5D terminal block enables the integration of not only SIRIUS motor starter protectors but also single-phase, 2-phase and 3-phase components. Using the terminal block the 3 phases can be fed out of the system; which means that single-phase loads can also be integrated in the system. The terminal block is plugged into the slot of the expansion plug and thus en-ables outfeeding from the middle or end of the infeed system. The terminal block can be rotated through 180° and be locked to the support modules of the infeed system. The 3RV19 17-7B 45 mm standard mounting rail for screwing onto the support plate is available in addition in order to be able to plug the sin-gle-phase, 2-phase and 3-phase components onto the infeed system.

    LV1N_05_04.fm Page 24 Friday, September 27, 2013 2:28 PM

    � Terminal block for device infeedA new addition to the system is a connector for outfeeding to a device slot within a module. This offers the option not only of connecting three-phase loads to the system, but also of integrating single-phase loads into the infeed system.

    3RV Motor Starter Protectors

    Accessories3RV29 infeed system

    Product Category IEC

  • SIRIUS

    Siemens Canada Limited Industrial Control Product Catalog 20191/16

    1M

    OTO

    R ST

    ART

    ER

    PRO

    TECT

    ORS

    Siemens / Industrial Controls Previous folio: LV1 6/55

    SIRIUS 3RV2 Motor Starter Protectors/Circuit Breakers up to 40 AAccessories

    3RV29 infeed system

    5/25SIRIUS Innovations Supplement 2012Illustrations are approximate

    5

    Selection and ordering data

    1) I > 14 A, note derating; see the system manual "SIRIUS Innovations", Chapter "Motor Starter Protectors".

    2) I > 16 A, note derating; see the system manual "SIRIUS Innovations", Chapter "Motor Starter Protectors".

    Type Version For 3RV20, 3RV23, 3RV24, 3RV27, 3RV28, motor starter protectors

    Order No.

    StandardPack

    Quantity

    StandardPack

    Quantity

    Weightapprox.

    eziS kgThree-phase busbars with infeed

    3RV29 17-1A

    3-phasebusbars withinfeedincl. end cover 3RV29 17-6A

    For 2 motor starter protectors with screw connection or spring-type terminals• With infeed on the

    leftS00, S0 3RV29 17-1A

    • With infeed on the right

    S00, S0 3RV29 17-1E

    Three-phase busbars for system expansion

    3RV29 17-4A

    Three-phasebusbarsincl. 3RV29 17-5BA00 expansion plug

    For motor starter protectors with screw connection or spring-type terminals• For 2 motor starter

    protectorsS00, S0 3RV29 17-4A

    • For 3 motor starter protectors

    S00, S0 3RV29 17-4B

    Plug-in connectors

    3RV29 17-5AA00

    Plug-inconnectorsto make contact with the 3RV2 motor starter protectors

    • For spring-type terminals

    Spring-typeterminals

    - Single-unit packaging

    S001) 3RV29 17-5AA00S02) 3RV29 27-5AA00

    - Multi-unit packaging

    S001) 3RV29 17-5AS02) 3RV29 27-5A

    3RV29 17-5CA00

    • For screw terminals

    Screw terminals

    - Single-unit packaging

    S001) 3RV29 17-5CA00S02) 3RV19 27-5AA00

    - Multi-unit packaging

    S001) 3RV29 17-5CS02) 3RV19 27-5A

    Type Version For contactors

    Order No. Weightapprox.

    eziS kgContactor bases

    3RV29 27-7AA00

    Contactor basesfor mounting direct-on-line or reversing starters

    Single-unit packaging

    S00 3RV29 17-7AA00

    S00, S0 3RV29 27-7AA00

    * You can order this quantity or a multiple thereof.

    LV1N_05_04.fm Page 25 Friday, September 27, 2013 2:28 PM

    1 unit 0.369

    1 unit 0.369

    1 unit 0.229

    1 unit 0.328

    1 unit 0.0591 unit 0.046

    10 units 0.05910 units 0.046

    1 unit 0.0401 unit 0.029

    1 unit 0.042

    1 unit 0.050

    10 units 0.03610 units 0.029

    3RV Motor Starter Protectors

    Accessories3RV29 infeed system

    Product Category IEC

  • SIRIUS

    Siemens Canada Limited Industrial Control Product Catalog 2019 1/17

    1M

    OTO

    R STARTER

    PROTECTO

    RS

    Siemens / Industrial Controls Previous folio: LV1 6/56

    StandardPack

    Quantity

    SIRIUS 3RV2 Motor Starter Protectors/Circuit Breakers up to 40 AAccessories

    3RV29 infeed system

    5/26 SIRIUS Innovations Supplement 2012 Illustrations are approximate

    5

    1) The expansion plug is included in the scope of supply of the 3RV29 17-4 three-phase busbars for system expansion.

    2) The end cover is included in the scope of supply of the 3RV29 17-1 three-phase busbars with infeed system.

    Type Version Order No. Weightapprox.

    kgTerminal blocks

    3RV29 17-5D

    Terminal blocksFor integration of single-phase, two-phase and three-phase components

    Single-unit packaging 3RV29 17-5D

    45 mm standard mounting rails

    3RV19 17-7B

    45 mm standardmounting railsfor mounting onto bus bar adapters

    Single-unit packaging 3RV19 17-7B

    Extra-wide expansion plugs

    3RV29 17-5E

    Extra-wide expansionplugs as accessory

    Single-unit packaging 3RV29 17-5E

    Expansion plugs

    3RV29 17-5BA00

    Expansion plugs1)as spare part

    Single-unit packaging 3RV29 17-5BA00

    End covers

    3RV29 17-6A

    End covers2)as spare part

    Multi-unit packaging 3RV29 17-6A

    * You can order this quantity or a multiple thereof.

    LV1N_05_04.fm Page 26 Friday, September 27, 2013 2:28 PM

    1 unit 0.049

    1 unit 0.261

    1 unit 0.037

    1 unit 0.026

    10 units 0.005

    Terminal blocks for device infeed

    3RV2917-5FA00

    Terminal blocks for 2)device infeed

    Single-unit packaging 3RV2917-5FA00 1 units 0.010

    3RV Motor Starter Protectors

    Accessories3RV29 infeed system

    Product Category IEC

  • SIRIUS

    Siemens Canada Limited Industrial Control Product Catalog 20191/18

    1M

    OTO

    R ST

    ART

    ER

    PRO

    TECT

    ORS

    Siemens / Industrial Controls Previous folio: LV1T 5/16

    3RV2011, 3RV2111, 3RV2311, 3RV2411

    FLA2) max. 115 1 2200 2 316 A,480 V

    12.5 A, 600 V 230 2 5460 -- 10575/600 -- 10

    Size S00

    81012.5

    65 6565 6565 65

    2.5

    4 65 655 65 656.3 65 65

    0.16 ... 2

    3.2

    656565

    656565

    6565

    303030303030

    303030—16

    Permissible rated data of devices approved for North America (UL/CSA) Motor starter protectors of the 3RV2 series are approved for UL/CSA, and according to UL508/UL 60947-4-1 and CSA C22.2 No. 14/CSA C22.2 No. 60947-4-1 they can be used on their own or as load feeders in combination with a contactor.

    These motor starter protectors can be used as "Manual Motor Controllers" for "Group Installations", as "Manual Motor Control-lers Suitable for Tap Conductor Protection in Group Installations" and as "Self-Protected Combination Motor Controllers" (Type E).

    3RV motor starter protectors as "Manual Motor Controllers"

    If used as a "Manual Motor Controller", the motor starter protector is always operated in combination with an upstream short-circuit protection device. Approved fuses or a circuit breaker accord-ing to UL 489/CSA C22.2 No. 5 can be used. These devices must be dimensioned according to the National Electrical Code (UL) or Canadian Electrical Code (CSA).

    Approval of the 3RV as a Manual Motor Controller can be found under the following file numbers: • UL File No. 47705, CCN: NLRV, • CSA Master Contract 165071, Product Class: 3211 05.

    1) HP rating = Power rating in horse power (maximum motor rating).2) FLA = Full Load Amps/Motor full load current.3) Corresponds to "short-circuit breaking capacity" according to UL/CSA.4) The values in brackets only apply to 3RV2.23 motor starter protectors.

    Motor starter protectors

    hp rating1) for FLA2)max.

    Rated current In

    Type V 1-phase 3-phase A

    240 V ACUL/CSA

    Ibc3)

    kA

    480 V ACUL/CSA

    Ibc3)

    kA

    600 V ACUL/CSA

    Ibc3)

    kA

    Size S33RV20 41/3RV20 42, 3RV21 42, 3RV23 41/3RV23 42 16 65 65 30

    20 65 65 30FLA2) max. 99 A, 115 7 1/2 -- 25 65 65 30600 V 200 20 30 32 65 65 30NEMA size 3 230 20 40 40 65 65 30

    460 -- 75 50 65 65 30575/600 -- 100 63 65 65 30

    75 65 65 3090 65 65 10100 65 65 10

    Size S03RV2021, 3RV2121, 3RV2321, 3RV2421 0.16 ... 12.5 65 65 30

    16 ... 25 65 65 --/(30)4)

    FLA2) max.

    40 A, 480 V

    115 3 5 28, 32 65 50 --200 5 10 36, 40 65 12 --230 7 1/2 10460 -- 30575/600 -- --

    3RV2011, 3RV2111, 3RV2311, 3RV2411

    FLA2) max. 115 1 2200 2 316 A,480 V

    12.5 A, 600 V 230 2 5460 -- 10575/600 -- 10

    Size S00

    81012.5

    65 6565 6565 65

    2.5

    4 65 655 65 656.3 65 65

    0.16 ... 2

    3.2

    656565

    656565

    6565

    303030303030

    303030—16

    Permissible rated data of devices approved for North America (UL/CSA) Motor starter protectors of the 3RV2 series are approved for UL/CSA, and according to UL508/UL 60947-4-1 and CSA C22.2 No. 14/CSA C22.2 No. 60947-4-1 they can be used on their own or as load feeders in combination with a contactor.

    These motor starter protectors can be used as "Manual Motor Controllers" for "Group Installations", as "Manual Motor Control-lers Suitable for Tap Conductor Protection in Group Installations" and as "Self-Protected Combination Motor Controllers" (Type E).

    3RV motor starter protectors as "Manual Motor Controllers"

    If used as a "Manual Motor Controller", the motor starter protector is always operated in combination with an upstream short-circuit protection device. Approved fuses or a circuit breaker accord-ing to UL 489/CSA C22.2 No. 5 can be used. These devices must be dimensioned according to the National Electrical Code (UL) or Canadian Electrical Code (CSA).

    Approval of the 3RV as a Manual Motor Controller can be found under the following file numbers: • UL File No. 47705, CCN: NLRV, • CSA Master Contract 165071, Product Class: 3211 05.

    1) HP rating = Power rating in horse power (maximum motor rating).2) FLA = Full Load Amps/Motor full load current.3) Corresponds to "short-circuit breaking capacity" according to UL/CSA.4) The values in brackets only apply to 3RV2.23 motor starter protectors.

    Motor starter protectors

    hp rating1) for FLA2)max.

    Rated current In

    Type V 1-phase 3-phase A

    240 V ACUL/CSA

    Ibc3)

    kA

    480 V ACUL/CSA

    Ibc3)

    kA

    600 V ACUL/CSA

    Ibc3)

    kA

    Size S33RV20 41/3RV20 42, 3RV21 42, 3RV23 41/3RV23 42 16 65 65 30

    20 65 65 30FLA2) max. 99 A, 115 7 1/2 -- 25 65 65 30600 V 200 20 30 32 65 65 30NEMA size 3 230 20 40 40 65 65 30

    460 -- 75 50 65 65 30575/600 -- 100 63 65 65 30

    75 65 65 3090 65 65 10100 65 65 10

    Size S03RV2021, 3RV2121, 3RV2321, 3RV2421 0.16 ... 12.5 65 65 30

    16 ... 25 65 65 --/(30)4)

    FLA2) max.

    40 A, 480 V

    115 3 5 28, 32 65 50 --200 5 10 36, 40 65 12 --230 7 1/2 10460 -- 30575/600 -- --

    Size S2 3RV2031 3RV2032 3RV2031 3RV2032 3RV2031 3RV203214 65 100 65 100 25 25

    3RV2031, 3RV2131, 3RV2331, 3RV2032, 3RV2332 17 65 100 65 100 25 25 20 65 100 65 100 25 25FLA 2) MAX. 65A 115/120 5 10 25 65 100 65 100 25 25600V 200/208 10 20 32 65 100 65 100 25 25NEMA size 2 230/240 15 25 36 65 100 65 100 25 25

    460/480 — 50 40 65 100 65 100 22 22575/600 — 60 45 65 100 65 100 22 22

    52 65 100 65 100 22 22a) with max 225A Class J fuse 59 65 a) 100 a) 65 a) 100 a) 20 a) 25 a)

    b) with max 250A Class J fuse 65 65 b) 100 b) 65 b) 100 b) 20 b) 25 b)

    3RV Motor Starter Protectors

    General Data3RV — up to 100 A (Domestic applications)

    Product Category IEC

  • SIRIUS

    Siemens Canada Limited Industrial Control Product Catalog 2019 1/19

    1M

    OTO

    R STARTER

    PROTECTO

    RS

    Siemens / Industrial Controls Previous folio: LV1T 5/17

    3RV motor starter protectors as "Manual Motor Controllers Suitable for Tap Conductor Protection in Group Installations"

    The application as "Manual Motor Controllers Suitable for Tap Conductor Protection in Group Installations" is only available from UL. CSA does not recognize this approval! When the motor starter protector is used as a "Manual Motor Controller Suitable for Tap Conductor Protection in Group Installations", it must always be combined with upstream short-circuit protection. As short-cir-cuit-protection device, approved fuses or a motor starter

    protector according to UL 489 can be used.These devices must be dimensioned according to the National Electrical Code.

    The 3RV motor starter protectors are approved as "Manual Motor Controllers Suitable for Tap Conductor Protection in Group Installations" under the following file number:• UL File No. 47705, CCN: NLRV.

    1) HP rating = Power rating in horse power (maximum motor rating).2) FLA = Full Load Amps/Motor full load current.3) Complies with "short-circuit breaking capacity" according to UL.

    Motor starter protectors

    hp rating1) for FLA2)max.

    Rated current In

    240 V AC Up to 480Y/277V AC Up to 600Y/347V ACUL UL UL

    Ibc3) Ibc3) Ibc3)

    Type V 1-phase 3-phase A kA kA kA

    Size S003RV20 11 0.16 ... 0.8 65 65 30

    1 65 65 30FLA2) max.16 A, 115/120 1 2 1.25 65 65 30480 Y / 277 V 200/208 2 3 2 65 65 30NEMA size 0 230/240 2 5 2.5 65 65 30

    460/480 -- 10 3.2 65 65 30575/600 -- 10 4 65 65 30

    5 65 65 306.3 65 65 30

    16 65 65 —

    Size S03RV20 21 0.63 ... 1.6 65 65 30

    2 65 65 30FLA2) max. 115/120 2 5 2.5 65 65 30

    25 A, 480 Y / 277 V 200/208 3 7.5 3.2 65 65 3012.5 A, 600 V 230/240 3 10 4 65 65 30

    460/480 3 20 5 65 65 30NEMA size 1 575/600 — — 6.3 65 65 30

    8 65 65 3010 65 65 30

    25 65 65 —32 50 50 —

    Size S23RV10 31 16 65 65 25

    20 65 65 25FLA2) max. 115 3 -- 25 65 65 2550 A, 600 V 200 7 1/2 15 32 65 65 25NEMA size 2 230 10 20 40 65 65 25

    460 -- 40 45 65 65 25575/600 -- 50 50 65 65 25

    Size S33RV20 4. 16 65 65 30

    20 65 65 30FLA2) max. 115/120 7 1/2 -- 25 65 65 30

    100 A, 480 V 200/208 20 30 32 65 65 3075 A, 600 V 230/240 20 40 40 65 65 30

    460/480 -- 75 50 65 65 30NEMA size 3 575/600 -- 75 63 65 65 30

    75 65 65 3090 65 65 --100 65 65 --

    8 65 65 30

    12.5 65 65 30

    Size S2 3RV2031 3RV2032 3RV2031 3RV2032 3RV2031 3RV203214 65 100 65 100 25 25

    3RV2031, 3RV2032, 3RV2431 17 65 100 65 100 25 25 20 65 100 65 100 25 25FLA 2) MAX. 65A 115/120 5 10 25 65 100 65 100 25 25600V 200/208 10 20 32 65 100 65 100 25 25NEMA size 2 230/240 15 25 36 65 100 65 100 25 25

    460/480 — 50 40 65 100 65 100 22 22575/600 — 60 45 65 100 65 100 22 22

    52 65 100 65 100 22 2259 65 100 30 42 -- --65 65 100 30 42 -- --

    3RV motor starter protectors as "Manual Motor Controllers Suitable for Tap Conductor Protection in Group Installations"

    The application as "Manual Motor Controllers Suitable for Tap Conductor Protection in Group Installations" is only available from UL. CSA does not recognize this approval! When the motor starter protector is used as a "Manual Motor Controller Suitable for Tap Conductor Protection in Group Installations", it must always be combined with upstream short-circuit protection. As short-cir-cuit-protection device, approved fuses or a motor starter

    protector according to UL 489 can be used.These devices must be dimensioned according to the National Electrical Code.

    The 3RV motor starter protectors are approved as "Manual Motor Controllers Suitable for Tap Conductor Protection in Group Installations" under the following file number:• UL File No. 47705, CCN: NLRV.

    1) HP rating = Power rating in horse power (maximum motor rating).2) FLA = Full Load Amps/Motor full load current.3) Complies with "short-circuit breaking capacity" according to UL.

    Motor starter protectors

    hp rating1) for FLA2)max.

    Rated current In

    240 V AC Up to 480Y/277V AC Up to 600Y/347V ACUL UL UL

    Ibc3) Ibc3) Ibc3)

    Type V 1-phase 3-phase A kA kA kA

    Size S003RV20 11 0.16 ... 0.8 65 65 30

    1 65 65 30FLA2) max.16 A, 115/120 1 2 1.25 65 65 30480 Y / 277 V 200/208 2 3 2 65 65 30NEMA size 0 230/240 2 5 2.5 65 65 30

    460/480 -- 10 3.2 65 65 30575/600 -- 10 4 65 65 30

    5 65 65 306.3 65 65 30

    16 65 65 —

    Size S03RV20 21 0.63 ... 1.6 65 65 30

    2 65 65 30FLA2) max. 115/120 2 5 2.5 65 65 30

    25 A, 480 Y / 277 V 200/208 3 7.5 3.2 65 65 3012.5 A, 600 V 230/240 3 10 4 65 65 30

    460/480 3 20 5 65 65 30NEMA size 1 575/600 — — 6.3 65 65 30

    8 65 65 3010 65 65 30

    25 65 65 —32 50 50 —

    Size S23RV10 31 16 65 65 25

    20 65 65 25FLA2) max. 115 3 -- 25 65 65 2550 A, 600 V 200 7 1/2 15 32 65 65 25NEMA size 2 230 10 20 40 65 65 25

    460 -- 40 45 65 65 25575/600 -- 50 50 65 65 25

    Size S33RV20 4. 16 65 65 30

    20 65 65 30FLA2) max. 115/120 7 1/2 -- 25 65 65 30

    100 A, 480 V 200/208 20 30 32 65 65 3075 A, 600 V 230/240 20 40 40 65 65 30

    460/480 -- 75 50 65 65 30NEMA size 3 575/600 -- 75 63 65 65 30

    75 65 65 3090 65 65 --100 65 65 --

    8 65 65 30

    12.5 65 65 30

    3RV Motor Starter Protectors

    General Data3RV — up to 100 A (Domestic applications)

    Product Category IEC

  • SIRIUS

    Siemens Canada Limited Industrial Control Product Catalog 20191/20

    1M

    OTO

    R ST

    ART

    ER

    PRO

    TECT

    ORS

    160.16 ... 12.5 65

    656565

    30—

    Size S003RV2011 + 3RV29 28-1H4) 5)

    FLA2) max. 16 A 115 1 2480 V 200 2 3

    230 2 5NEMA size 0

    575/600——

    10

    3RV motor starter protectors as "Self-Protected Combination Motor Controllers (Type E)"

    Motor starter protectors

    hp rating1) for FLA2)max.

    Rated current In

    Up to 240 V AC Up to 480 Y/277 V AC Up to 600 Y/347 V ACUL/CSA UL/CSA UL/CSAIbc3) Ibc3) Ibc3)

    Type V 1-phase 3-phase A kA kA kA

    Size S03RV2021 + 3RV29 28-1H 4) 5) 0.63 ... 1.6 65 65 30

    2 65 65 30FLA2) max. 115 2 5 2.5 65 65 30

    25 A, 480 V 200 3 7.5 3.2 65 65 3012.5 A, 600 V 230 3 10 4 65 65 30

    460 — 20 5 65 65 30NEMA size 1 575/600 — — 6.3 65 65 30

    8 65 65 3010 65 65 30

    12.5 65 65 3016 65 65 —20 65 65 —22 65 65 —

    Size S23RV2031/3RV2032 + 3RV2938 16 65 65 25

    20 65 65 25FLA2) max. 115 3 -- 25 65 65 25

    50 A, 600 V 200 7 1/2 15 32 65 65 25NEMA size 2 230 10 20 40 65 65 25

    460 -- 40 45 65 65 25575/600 -- 50 50 65 65 25

    Size S33RV2041 + 3RT2946-4GA07 4) 16 65 65 30

    20 65 65 30FLA2) max. 115 10 -- 25 65 65 30

    100 A, 480 V 200 20 30 32 65 65 3075 A, 600 V 230 20 40 40 65 65 30

    460 -- 75 50 65 65 30NEMA size 3 575/600 -- 75 63 65 65 30

    75 65 65 3090 65 65 —100 65 65 —

    25 65 65 —32 50 50 —

    23010

    1) HP rating = Power rating in horse power (maximum motor rating).2) FLA = Full Load Amps/Motor full load current.

    3) Corresponds to "short-circuit breaking capacity" according to UL/CSA.4) Not required for CSA.5) Alternatively, the 3RV2928-1K phase barrier can also be used.

    Ratings of the auxiliary switches and alarm switches

    Lateral auxiliary switch with 1 NO + 1 NC, 2 NO, 2 NC, 2 NO + 2 NC and signalling switch

    Transverse auxiliary switch with 1 changeover contact

    Transverse auxiliary switch with1 NO + 1 NC, 2 NO

    Max. rated voltage AC V 600 250• to NEMA u• to NEMA s AC V 600 250

    Atnerruc detpurretninU 10 5 2.5Breaking capacity A600 B600 C300

    Q300 R300 R300

    UL 508/UL 60947-4-1 approval demands 1-inch clearance and 2-inch creepage distance at line side for “Self-Protected Combination Motor Controller Type E”.

    Therefore, 3RV20 motor starter protectors of sizes S00 to S2 are approved according to UL 508/UL 60947-4-1 in combination with the terminal blocks listed below.

    CSA does not require these extended clearances and creepage distances. According to CSA, these terminal blocks can be omitted

    when the device is used as a “Self-Protected Combination Motor Controller”.

    The 3RV20 motor starter protectors are approved as “Self-Protected Combination Motor Controllers” under the following file numbers:

    • UL File No. E156943, CCN: NKJH

    • CSA Master Contract 165071, Product Class: 3211 08

    160.16 ... 12.5 65

    656565

    30—

    Size S003RV2011 + 3RV29 28-1H4) 5)

    FLA2) max. 16 A 115 1 2480 V 200 2 3

    230 2 5NEMA size 0

    575/600——

    10

    3RV motor starter protectors as "Self-Protected Combination Motor Controllers (Type E)"

    Motor starter protectors

    hp rating1) for FLA2)max.

    Rated current In

    Up to 240 V AC Up to 480 Y/277 V AC Up to 600 Y/347 V ACUL/CSA UL/CSA UL/CSAIbc3) Ibc3) Ibc3)

    Type V 1-phase 3-phase A kA kA kA

    Size S03RV2021 + 3RV29 28-1H 4) 5) 0.63 ... 1.6 65 65 30

    2 65 65 30FLA2) max. 115 2 5 2.5 65 65 30

    25 A, 480 V 200 3 7.5 3.2 65 65 3012.5 A, 600 V 230 3 10 4 65 65 30

    460 — 20 5 65 65 30NEMA size 1 575/600 — — 6.3 65 65 30

    8 65 65 3010 65 65 30

    12.5 65 65 3016 65 65 —20 65 65 —22 65 65 —

    Size S23RV2031/3RV2032 + 3RV2938 16 65 65 25

    20 65 65 25FLA2) max. 115 3 -- 25 65 65 25

    50 A, 600 V 200 7 1/2 15 32 65 65 25NEMA size 2 230 10 20 40 65 65 25

    460 -- 40 45 65 65 25575/600 -- 50 50 65 65 25

    Size S33RV2041 + 3RT2946-4GA07 4) 16 65 65 30

    20 65 65 30FLA2) max. 115 10 -- 25 65 65 30

    100 A, 480 V 200 20 30 32 65 65 3075 A, 600 V 230 20 40 40 65 65 30

    460 -- 75 50 65 65 30NEMA size 3 575/600 -- 75 63 65 65 30

    75 65 65 3090 65 65 —100 65 65 —

    25 65 65 —32 50 50 —

    23010

    1) HP rating = Power rating in horse power (maximum motor rating).2) FLA = Full Load Amps/Motor full load current.

    3) Corresponds to "short-circuit breaking capacity" according to UL/CSA.4) Not required for CSA.5) Alternatively, the 3RV2928-1K phase barrier can also be used.

    Ratings of the auxiliary switches and alarm switches

    Lateral auxiliary switch with 1 NO + 1 NC, 2 NO, 2 NC, 2 NO + 2 NC and signalling switch

    Transverse auxiliary switch with 1 changeover contact

    Transverse auxiliary switch with1 NO + 1 NC, 2 NO

    Max. rated voltage AC V 600 250• to NEMA u• to NEMA s AC V 600 250

    Atnerruc detpurretninU 10 5 2.5Breaking capacity A600 B600 C300

    Q300 R300 R300

    Size S2 3RV2031 3RV2032 3RV2031 3RV2032 3RV2031 3RV203214 65 100 65 100 25 25

    3RV2031/3RV2032 + 3RV2938-1K 4) 17 65 100 65 100 25 25 20 65 100 65 100 25 25FLA 2) MAX. 65A 115/120 5 10 25 65 100 65 100 25 25600V 200/208 10 20 32 65 100 65 100 25 25NEMA size 2 230/240 15 25 36 65 100 65 100 25 25

    460/480 — 50 40 65 100 65 100 22 22575/600 — 60 45 65 100 65 100 22 22

    52 65 100 65 100 22 2259 65 100 20 30 — —65 65 100 20 30 — —

    3RV Motor Starter Protectors

    General Data3RV — up to 100 A (Domestic applications)

    Product Category IEC

  • SIRIUS

    Siemens Canada Limited Industrial Control Product Catalog 2019 1/21

    1M

    OTO

    R STARTER

    PROTECTO

    RS

    Siemens / Industrial Controls Previous folio: LV1T 5/19

    3RV27/28 circuit breakers

    These circuit breakers are approved according to UL 489 and CSA C22.2 No. 5-02 for 100 % rated current (100 % rated breaker). They can be used therefore as upstream short-circuit protective devices for "Manual Motor Controllers" and "Manual Motor Controllers Suitable for Tap Conductor Protection in Group Installations".

    The 3RV27/28 circuit breakers are approved under the following file numbers:• UL File No. E235044, CCN: DIVQ,• CSA Master Contract 165071, Product Class: 1432 01.

    1) Complies with "short-circuit breaking capacity" according to UL.

    Circuit breakers Ratedcurrent In

    240 V AC 480 Y/277 V AC 480 V AC 600 Y/347 V ACUL/CSA UL/CSA UL/CSA UL/CSAIbc1) Ibc1) Ibc1) Ibc1)Type A kA kA kA kA

    Size S33RV27 42 10 65 65 65 20

    15 65 65 65 2020 65 65 65 2025 65 65 65 2030 65 65 65 2035 65 65 -- 2040 65 65 -- 2045 65 65 -- 2050 65 65 -- 2060 65 65 -- 2070 65 65 -- 10

    Size S00/S03RV27 11 / 3RV28 113RV27 21 / 3RV28 21

    0.16 … 1.25 65 65 101.6 65 65 102 65 65 102.5 65 65 103.2 65 65 104 65 65 105 65 65 106.3 65 65 108 65 65 1010 65 65 1012.5 65 65 1015 65 65 --20 50 50 --22 50 50

    6565656565656565656565655050 --

    3RV Motor Starter Protectors

    General Data3RV27/28 circuit breakers

    Product Category IEC

  • SIRIUS

    Siemens Canada Limited Industrial Control Product Catalog 20191/22

    1M

    OTO

    R ST

    ART

    ER

    PRO

    TECT

    ORS

    Siemens / Industrial Controls Previous folio: LV1T 5/11

    14; 17 100 100 ° 100 50 ° 65 30 100 18 10 63 8 5 6320; 25 100 100 ° 100 50 ° 65 30 100 18 10 80 8 5 8032 ... 45 100 100 ° 100 50 ° 65 30 125 15 8 100 6 4 10052 100 100 ° 100 50 ° 65 30 125 15 8 125 6 4 125

    59 ... 80

    Technical specificationsShort-circuit breaking capacity Icu, Ics acc. to IEC 60947-2

    The maximum rated current for the back-up fuse is specified in the tables. The rated ultimate short-circuit breaking capacity then applies as specified on the fuse.

    Fuseless constructionMotor starter protector contactor combinations for short-circuit currents up to 150 kA can be ordered in the form of fuseless load feeders according to Chapter 6.

    Motor starter protectors/circuit breakers

    Rated current In

    Up to 240 V AC1) Up to 400 V1)/415 V AC2)

    Up to 440 V1)/460 V AC2)

    Up to 500 V1)/525 V AC2)

    Up to 690 V AC1)

    (these values do not apply to 3RV17 42 circuit breakers)

    Icu Ics Max. fuse (gL/gG)

    Icu Ics Max. fuse (gL/gG)3)

    Icu Ics Max. fuse (gL/gG)3)

    Icu Ics Max. fuse (gL/gG)3)

    Icu Ics Max.fuse(gL/gG)3)4)

    Type A kA kA A kA kA A kA kA A kA kA A kA kA A

    Size S003RV2.11 0.16 ... 1 100 100 ° 100 100 ° 100 100 ° 100 100 ° 100

    100100 °

    °1.25; 1.6 100 100 ° 100 100 ° 100 100 ° 100 1002; 2.5 100 100 ° 100 100 ° 100 100

    3.2; 4 100 100 ° 100 100 ° 50 105; 6.3 100 100 ° 100 100 ° 50 108 100 100 ° 50 12.5 ° 50 50

    10 100 100 ° 50 12.512 100 100 °

    °50 12.5

    Size S03RV2.21 16 100 100 ° 55 25 100 50 10 80 10 5 80 4 2 63

    4 2 63

    20 100 100 ° 55 25 125 50 10 80 10 5

    22 100 100 ° 55 25 125 50 10 100 10 525 100 100 ° 55 25 125 50 10 100 10 528 100 100 ° 55 25 125 30 10 125 10 5

    32 100 100 ° 55 25 125 30 1036 100 100 ° 20 10 125 12 840 100 100 ° 20 10 125 12 8

    Size S23RV2.31 14; 17 100 100 ° 65 30 100 50 25 100 12 6 63 5 3 63

    20 100 100 ° 65 30 100 50 25 100 12 6 80 5 3 8025 100 100 ° 65 30 100 50 15 100 12 6 80 5 3 8032; 36 100 100 ° 65 30 125 50 15 125 10 5 100 4 2 100

    40; 45 100 100 ° 65 30 160 50 15 125 10 5 100 4 2 10052 100 100 ° 65 30 160 50 15 125 10 5 125 4 2 125

    Size S33RV2. 41 40 100 100 ° 50 25 125 50 20 125 12 6 100 6 3 63

    50 100 100 ° 50 25 125 50 20 125 12 6 100 6 3 8063 100 100 ° 50 25 160 50 20 160 12 6 100 6 3 80

    75 100 100 ° 50 25 160 50 20 160 8 4 125 5 3 10090; 100 100 100 ° 50 25 160 50 20 160 8 4 125 5 3 125

    ° 10010 25° 100 100 ° 1010; 6 32° 100 100 ° 10; 4

    6 5063 42 42 63 4

    ° 50 50 6 5080 42 42 63 4° 50 50 4 6380 42 42 80 4

    16 100 100 55 30 100 50 10 4 6380 10 5 80 4

    6 32° 100 100 ° 4

    804 2 63804 2 100100

    125 10 5 4 2 100100125 6 3 3 2 100100125 6 3 3 2 100100

    4 2 6380

    This table shows the rated ultimate short-circuit breaking capacity Icu and the rated service short-circuit breakingcapacity Ics of the 3RV2 motor starter protectors/circuit breakers with different inception voltages dependent of the rated current In of the motor starter protectors/circuit breakers.Power can be supplied to the motor starter protectors/circuitbreakers via the terminals at the top or at the bottom withoutrestricting the rated data. If the short-circuit current at the placeof installation exceeds the rated short-circuit breaking capacityof the motor starter protector/circuit breaker as specified in the

    table, a back-up fuse is required. It is also possible to install anupstream motor starter protector/circuit breaker with a limiterfunction.

    Size S2, with increased switching capacity3RV2.32

    Values on request

    59 ... 80 Values on request

    1) 10 % overvoltage.2) 5 % overvoltage.3) Back-up fuse only required if the short-circuit current at the place of

    installation > Icu.

    4) Alternatively, fuseless limiter combinations for 690 V AC can also be used.

    Short-circuit resistant up to at least 50 kA

    ° No back-up fuse required, since short-circuit resistant up to 100 kA

    3RV Motor Starter Protectors

    General Data3RV — up to 100 A (Export applications)

    Product Category IEC

  • SIRIUS

    Siemens Canada Limited Industrial Control Product Catalog 2019 1/23

    1M

    OTO

    R STARTER

    PROTECTO

    RS

    Siemens / Industrial Controls Previous folio: LV1T 5/12

    Short-circuit breaking capacity IcuIT in the IT system (IT network) according to IEC 60947-2 3RV motor starter protectors are suitable for operation in IT systems. Values valid for triple-pole short-circuit are Icu up to Ics. In case of double ground fault on different phases at the in-put and output side of a motor starter protector, the special short-circuit breaking capacity IcuIT applies. The specifications in the table below apply to 3RV motor starter protectors.

    In the colored areas, IcuIT is 100 kA, or in some ranges it is 50 kA. Therefore the motor starter protectors are short-circuit re-sistant in these ranges.

    If the short-circuit current at the place of installation exceeds the rated short-circuit breaking capacity of the motor starter protec-tor as specified in the table, a back-up fuse is required. The max-imum rated current for the back-up fuse is specified in the ta-bles. The rated short-circuit breaking capacity then applies as specified on the fuse.

    Motor starter protectors

    Rated current In

    Up to 240 V AC1) Up to 400 V1)/415 V AC2) Up to 500 V1)/525 V AC2) Up to 690 V AC1) 5)

    IcuIT Max. fuse (gL/gG)3)

    IcuIT Max. fuse (gL/gG)3)

    IcuIT Max. fuse (gL/gG)3)4)

    IcuIT Max. fuse (gL/gG)3)

    Type A kA A kA A kA A kA A

    Size S003RV20, 0.16 ... 0.63 100 ° 100 ° On request On request On request On request3RV26 11-0BD10 0.8; 1 100 ° 100 °

    ° 100

    8

    °1.25; 1.6 100

    2; 2.5 1003.2; 4 1005; 6.3 100

    8; 10 100 4412.5 100

    Size S03RV2.21 16 55 80 4

    20 55 80 4 6322 55 80 4

    422

    22

    63

    63

    6363

    6363

    632

    2

    2

    22

    22

    250

    50

    50

    6363

    6363

    5050

    50

    40

    6363

    6363

    501.5

    1.5

    1.5

    1.51.5

    1.51.5

    1.5

    25 5528 5532 55

    36 2040 20

    Size S23RV2.31 14...25 100 ° 8 100 6 80 4 63

    32...45 100 ° 6 125 4 100 3 8052 100 ° 4 160 3 125 2 10059 ... 80

    Size S33RV2. 41 40 50 125 10 63 5 50 5 50

    50 50 125 8 80 3 63 3 6363 50 160 6 80 3 63 3 63

    75 50 160 5 100 2 80 2 8090; 100 50 160 5 125 2 100 2 100

    °8;4°

    °

    °°

    4

    25

    5063

    416 55 80 63

    3232:50

    808080

    8080

    Values on requestSize S2, with increased switching capacity3RV2.32 14 ... 25 100 ° 8 100 6 80 4 63

    32 ... 45 100 ° 6 125 6 100 4 8052 100 ° 6 160 6 125 4 100

    59 ... 80 Values on request

    1) 10 % overvoltage.2) 5 % overvoltage.3) Back-up fuse only required, if short-circuit current at the place of

    installation > IcuIT.4) Alternatively, fuseless lim5) Over-voltage category II applies for applications on IT systems > 600V

    iter combinations for 690 V AC can also be used.

    Short-circuit resistant up to at least 50 kA

    ° No back-up fuse required, since short-circuit resistant up to 100 kA

    3RV Motor Starter Protectors

    General Data3RV — up to 100 A (Export applications)

    Product Category IEC

  • SIRIUS

    Siemens Canada Limited Industrial Control Product Catalog 20191/24

    1M

    OTO

    R ST

    ART

    ER

    PRO

    TECT

    ORS

    Siemens / Industrial Controls Previous folio: 1/24

    Technical data

    Rules for mounting motor starter protectors/circuit breakersWhen mounting MSPs, the following clearance must be maintained to grounded or live parts.

    ot ecnaraelCPSM SUIRIS grounded or live parts

    Y X at the side ZmmmmmmezisepyT

    3RV2.1 S00 up to 690 V 30 70 9

    3RV2. 2 S0 up to 500 V 30 90 9up to 690 V 50 90 30

    3RV2. 3 S2 up to 690 V 50 — 10

    3RV2. 4 S3 up to 240 V 50 167 10up to 440 V 70 167 10up to 500 V 110 167 10up to 690 V 150 167 30

    3RV27 42 S3 up to 240 V 90 167 10up to 400 V 90 167 10

    Standard mounting for S0, S2 and S3

    1) Up to and including the setting range of 32 A. For the 36/40 A setting range the clearance is 70 mm. 2) In conjunction with the type E terminal block 3RV2928-1H the applicable lateral clearance is 30 mm for all voltages.

    Minimum clearance between MSPs and grounded or live parts

    Wiring module

    Size S0: 3RV19 15-1AB

    Size S2: 3RV19 35-1A

    Size S3: 3RA19 43-3D(Caution: The wiring module demands 10 mm spacing between the MSPs)

    Lineside

    Load side

    1)2)

    3RV Motor Starter Protectors

    General Data3RV — up to 100 A

    Product Category IEC

  • SIRIUS

    Siemens Canada Limited Industrial Control Product Catalog 2019 1/25

    1M

    OTO

    R STARTER

    PROTECTO

    RS

    Siemens / Industrial Controls Previous folio: LV1T 5/14

    7/16 Siemens IC 10 · 2015

    Motor Starter Protectors/Circuit BreakersSIRIUS 3RV2 Motor Starter Protectors/Circuit Breakers up to 80 A

    General data

    7

    General data

    Type 3RV2.1. 3RV2.2. 3RV2.3. 3RV27, 3RV28

    Size S00 S0 S2 S00, S0Dimensions (W x H x D) • Screw terminals• Spring-type terminals

    mmmm

    45 x 97 x 9145 x 106 x 91

    45 x 97 x 9145 x 119 x 91

    55 x 140 x 149--

    45 x 144 x 92--

    Standards • IEC 60947-1, EN 60947-1 (VDE 0660 Part 100) Yes• IEC 60947-2, EN 60947-2 (VDE 0660 Part 101) Yes• IEC 60947-4-1, EN 60947-4-1 (VDE 0660 Part 102) Yes Yes Yes --• UL 508/UL 60947-4-1, CSA C22.2 No. 14/CSA C22.2 No. 60947-4-1 Yes Yes Yes --• UL 489, CSA C22.2 No. 5 -- -- -- YesNumber of poles 3Max. rated current In max (= max. rated operational current Ie)

    A 16 40 80 22

    Permissible ambient temperature • Storage/transport °C –50 ... +80• Operation In: 0.16 ... 32 A °C –20 ... +70

    (current reduction above +60 °C)--

    In: 36 ... 40 A °C -- –20 ... +40 (the devices must not be mounted side-by-side and they must not be assembled with link modules with contactors. A lateral clear-ance of 9 mm is required.)

    --

    In: 14 ... 80 A °C -- –20 ... +70 (current reduction above +60 °C)

    --

    Permissible rated current at inside temperature of control cabinet • +60 °C % 100• +70 °C % 87Permissible rated current at ambient temperature of enclosure(applies for motor starter protector/circuit breaker inside enclosure ≤ 32 A)

    • +35 °C % 100 On request

    100• +60 °C % 87 87Rated operational voltage Ue • Acc. to IEC V AC 690 (when a molded-plastic enclosure is used only 500 V)• Acc. to UL/CSA V AC 600Rated frequency Hz 50/60Rated insulation voltage Ui V 690Rated impulse withstand voltage Uimp kV 6Utilization category • IEC 60947-2 (motor starter protector/circuit breaker) A• IEC 60947-4-1 (motor starter) AC-3Trip class CLASS Acc. to IEC 60947-4-1 10 10/20 --DC short-circuit breaking capacity (time constant t = 5 ms) • 1 conducting path 150 V DC kA 10 On

    request10

    • 2 conducting paths in series 300 V DC kA 10 10• 3 conducting paths in series 450 V DC kA 10 10Power loss Pv for each motor starter protector/circuit breaker Dependent on the rated current In (upper setting range)

    In: 0.16 ... 0.63 A W 5 -- 5In: 0.8 ... 6.3 A W 6 -- 6In: 8 ... 16 A W 7 -- 7In: 16 A W -- 7 10 7

    In: 17 ... 25 A W -- 8 12 8In: 28 ... 32 A W -- 11 14 --In: 36 ... 40 A W -- 14